Only qualified personnel should install and service the equipment.The installation, starting up, and servicing
of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and
training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or
serious injury.When working on the equipment, observe all precautions in the literature and on the tags,
stickers, and labels that are attached to the equipment.
Read this manual thoroughlybeforeoperating or servicing
this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as
required.Your personal safety and the proper operation of
this machine depend upon the strict observance of these
precautions.
The three types of advisories are defined as follows:
WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious
injury. All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards.To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes.
WARNING
CAUTIONs
NOTICE
Indicates a potentially hazardous
situation which, if not avoided, could
result in death or serious injury.
Indicates a potentially hazardous
situation which, if not avoided, could
result in minor or moderate injury. It
could also be used to alert against
unsafe practices.
Indicates a situationthat could resultin
equipment or property-damage only
accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made
chemicals can affect the earth’s naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified
chemicals that may affect the ozone layer are refrigerants
that contain Chlorine, Fluorine and Carbon (CFCs) and
those containing Hydrogen, Chlorine, Fluorine and
Carbon (HCFCs). Not all refrigerants containing these
compounds have the same potential impact to the
environment.Trane advocates the responsible handling of
all refrigerants-including industry replacements for CFCs
such as HCFCs and HFCs.
Important Responsible Refrigerant
Practices
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air
conditioning industry. All technicians who handle
refrigerants must be certified.The Federal Clean Air Act
(Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain
refrigerants and the equipment that is used in these
service procedures. In addition, some states or
municipalities may have additional requirements that
must also be adhered to for responsible management of
refrigerants. Know the applicable laws and follow them.
WARNING
Personal Protective Equipment (PPE)
Required!
Installing/servicing this unit could result in exposure to
electrical, mechanical and chemical hazards.
•Before installing/servicing this unit, technicians
MUST put on all PPE required for the work being
undertaken (Examples; cut resistant gloves/sleeves,
butyl gloves, safety glasses, hard hat/bump cap, fall
protection, electrical PPE and arc flash clothing).
ALWAYS refer to appropriate Material Safety Data
Sheets (MSDS)/Safety Data Sheets (SDS) and OSHA
guidelines for proper PPE.
•When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS/SDS and
OSHA/GHS (Global Harmonized System of
Classification and Labelling of Chemicals) guidelines
for information on allowable personal exposure
levels, proper respiratory protection and handling
instructions.
•If there is a risk of energized electrical contact, arc, or
flash, technicians MUST put on all PPE in accordance
with OSHA, NFPA 70E, or other country-specific
requirements for arc flash protection, PRIOR to
servicing the unit. NEVER PERFORM ANY
SWITCHING, DISCONNECTING, OR VOLTAGE
TESTING WITHOUT PROPER ELECTRICAL PPE AND
ARC FLASH CLOTHING. ENSURE ELECTRICAL
METERS AND EQUIPMENT ARE PROPERLY RATED
FOR INTENDED VOLTAGE.
Failure to follow instructions could result in death or
serious injury.
This document andthe information in it arethe property of
Trane, and may not be used or reproduced in whole or in
part without written permission.Trane reserves the right
to revise this publication at any time, and to make changes
to its content without obligation to notify any person of
such revision or change.
Trademarks
All trademarks referenced in this document are the
trademarks of their respective owners.
Axiom, ReliaTel,TOPSS,Tracer,Trane, and theTrane logo
are trademarks or registered trademarks ofTrane in the
United States and other countries.Trane is a business of
Ingersoll Rand. All trademarks referenced in this
document are the trademarks of their respective owners.
LonTalk is a registered trademark of Echelon Corporation.
BACnet is a registered trademark of ASHRAE.
Revision History
Introduction
WSHP-SVX01N-EN (12 Sep 2014)
•Edited Model Number, Electrical Data, Fan
Performance - 2 speed motor change
000 00000000 Digits 26-36 are not
applicable to the EXH or EXV products
WSHP-SVX01N-EN7
Overview of Manual
Note: One copy of this document ships with each unit and
is customer property. It must be retained by the
unit’s maintenance personnel.
This booklet describes proper installation, operation, and
maintenance procedures for HVAC systems. By carefully
reviewing the information within this manual and
following the instructions, the risk of improper operation
and/or component damage will be minimized.
Service and maintenance work should be performed by a
qualified technician and all electrical service and
maintenance work should be performed by a qualified
licensed electrician.
Unit Nameplate
The unit nameplate is located on the outside of the control
box access panel at thefront of the unit. Itincludes the unit
model number, serial number, electrical characteristics,
refrigerant charge, and other pertinent unit data.
Compressor Nameplate
The nameplate for the compressors are located on the
compressor shell.
Model Number Description
All products are identified by a multiple-character model
number that preciselyidentifies a particular type of unit. Its
use will enable the owner/operator, installing contractors,
and service engineers to define the operation, specific
components, and other options for any specific unit.
When ordering replacement parts or requesting service,
be sure to refer to the specific model number and serial
number printed on the unit nameplate.
8WSHP-SVX01N-EN
General Information
Unit Description
Before shipment, each unit is leak tested, dehydrated,
charged with refrigerant and run tested for proper control
operation.
Air-to-Refrigerant Coil
The air-to-refrigerant coil is aluminum fin, mechanically
bonded to the copper tubing.
Water-to-Refrigerant Coil
The water-to-refrigerant coil is a copper or cupro-nickel
(option) and steel tube (tube-within-a-tube) design, leak
tested to assure there is no cross leakage between the
water tube (copper/cupro-nickel) and refrigerant gas (steel
tube).
Table 1.High/Low pressure switch
TripRecoverUnit
LP40 +/-456 +/-4psig
HP650 +/-10550 +/-10psig
Controls
Basic 24V control is available for the GEH/V ½ -5 ton
models and the Deluxe 24V control option is available for
all unit sizes.Tracer™ ZN524, LonTalk® certified control
option is available for allunit sizes. UC400 and UC400 with
wireless comm BACnet is available in all unit sizes.
All power wiring to the equipment is made at the unit
contactor for ½- 5 ton, 1-phase units. For 3-phase units all
power wiring to the equipmentis made tothe contactor or
power block. For EXH/V070 units all power wiring to the
equipment is made to the power block. For the GEH/V 6-25
tons units all power wiring is made to the high voltage
terminal block. All low-voltage wiring is made at the unit’s
low voltage terminal board. EXH and EXV 460V units
require a neutral wire.
System Input Devices and Functions
A thermostat, zone sensor, or building automation system
is required to operate the water-source heat pump.The
flexibility of having several mode capabilities depends
upon the type of sensor and/or remote panel selected.
Troubleshooting and connection diagrams for the 24V
control systems may be locatedin the back of this manual.
All digital control troubleshooting tips and connection
diagrams are located in WSHP-PRB002-EN (ZN524).
Basic 24V Controls
Safety devices for equipment containing the basic 24V
control option include a low-pressure switch to prevent
compressor operation during low temperature or low
suction activity.The switch is set to activate at refrigerant
pressure of 40 psig to fit most applications.
A high pressure switch prevents compressor operation
during high or excessive discharge pressures exceeding
650 psig.
The lockout relay will disable the compressor on a high or
low pressure condition. For units that contain a
condensate overflow switch option, a condensate
overflow condition will also disable the compressor
through the lockout relay.The relay may be reset at the
thermostat, or by cycling power to the unit.
General alarm is accomplished through the lockout relay.
This feature will drive dry contacts only, and cannot be
used to drive field installed control inputs.Trane provides
a 3½-minute time delay for compressor control.
Deluxe 24V Controls (option)
Units containing the Deluxe 24V control design will
incorporate a microprocessor-based control board.The
Trane® microprocessor board is factory wired to a
terminal strip to provide all necessary terminals for field
connection.The deluxe board is equipped with a random
start relay, anti-short cycle timer, brown out protection,
compressor disable, condensate overflow, unit safety
control, diagnostics, and a generic relay (which may be
available for field use). See Table 65, p. 119 for diagnostic
information and Figure 59, p. 62 and Figure 60, p. 63 for
thermostat connections.
Tracer™ UC400
TheTracer™ UC400 is a BTL Listed BACnet® controller
that can operate stand- alone or within a Building
Automations system such asTracer™ SC.
Tracer ZN524 Controls (option)
The digital ZN524 controller is designed to support the ½
to 25 ton water-source heat pumps in either a standalone,
peer-to-peer with aTracer Loop Controller, or as a full
building automation (open protocol) system.
For installation, operation and diagnostics see WSHPPRB002-EN (ZN524).
Pump Module (field installed accessory)
The pump module shall consist of either a single or dual 1/
6 HP bronze pump and a brass three-way shut-off valve.
Cast iron pumps are also acceptable.The pump module
kits shall contain the necessary components for the
installation, operation and maintenance of the water
circuit of a closed-loop distributed pumping application.
WSHP-SVX01N-EN9
General Information
Waterside Economizer (Option)
Instructions for mechanical connection of the waterside
economizer to the water-source heat pump may be found
in the dimensional section of this manual.
The waterside economizer is designed to begin
economizing mode when water temperatures fall below
the field adjustable temperature of 25, 35, 45, 55 or 60°F
(for the Deluxe control option), or below the programmed
set-point (for the ZN524 control option).
When the temperature is less than the setpoint, fluid will
flow into the economizing coil, while simultaneously
halting mechanical operation of the compressor.
Mechanical cooling will continue on a call for a second
stage from the thermostat or system control. Entering
water temperature sensor is factory provided for field
installation on the entering water side of the coil.
Boilerless Control/Electric Heat (Option)
Systems that do not contain a boiler may contain a
boilerless control with electric heat.Trane® offers both a
factory mounted electric heat option, and a field mounted
duct heater option.
If the ½-5 ton GEH, GEV and EXH/V070 unit incorporates
the factory mounted option, the unit will ship from the
factory with an internally mounted nichrome open wire
heating element, designed to start-up electric heat as the
systems primary heat in the event entering water
temperature falls below 55°F. Once the entering water
temperature rises above 60°F, the boilerless controller
returns the unit to normal compressor heating operation,
and locks out the electric heater.
For units comprised of the field installed duct heater
option, the unit will ship from the factory with controls
available to interface with the field provided electric heat
selection.
Note: For geothermal applications, the boilerless
controller has an adjustable setting of 25, 35, 45, 55,
and 60 degrees.
Supplemental or Boilerless Electric Heat
(option)
The GEH/V 6-25 ton models which contain boilerless
control electric heat or supplemental electric heat will
contain the controls interface ONLY for field provided
electric heat selection.The heater for this model shall be
external to the equipment by the contractor for ease of
installation. All power connections for the electric heater
will be completely separate from theunit for field supplied
electric heat.
Note: When the unit has boilerless control, the electric
heat is not used as supplemental electric heat, but
as a primary heat.
Hot Gas Reheat (option)
With the reheat option, the return-air from the space is
conditioned by the air-to-refrigerant coil, then reheated by
the reheat coil to control not only the space temperature,
but to also reduce the relative humidityof the space. When
operating in the reheat mode (meaning the sensible
temperature has been met in the space), the humidistat
signals the reheat relay coil to energize, allowing the high
pressure refrigerant gas to flow from the compressor
through the reheat valve, into the reversing valve, or
reheat coil.
A switching relay has been provided for the reheat
application to adjust the blower motor from normal
operation to low speed when the hot gas reheat is
energized (for ½ -5 ton and EXH/V070 equipment only).
Note: A high static blower motor is required to support
the hot gas reheat option for the GEH/V ½ -5 ton.
Note: Units containing the hot gas reheat option should
not be used as a make-up air unit.
2 Speed Blower Motor (option)
The 6-25 ton GEH/V models have indoor blowers that are
available with 2 speed motors, selectable in the model
number (Digit 12, drive packages one to nine). High speed
airflow matches the single speed motor airflow,
referenced in the Fan Performance tables. Low fan speed
airflow is approximately 50% of high fan speed airflow.
The 6-25 ton GEH/V two-speed blower motors are
available with the following options: Deluxe24V or UC400
controls, Heat Pump (HP) or HP w/Hot Gas Reheat or HP w/
Waterside Economizer. Not available with Boilerless or
Product contains fiberglass wool. Disturbing the
insulation in this product during installation,
maintenance or repair will expose you to airborne
particles of glass wool fibers and ceramic fibers known
to the state of California to cause cancer through
inhalation. Glass wool fibers may also cause
respiratory, skin or eye irritation.
Unit Inspection Checklist
•Unpack all components of the kit.
•Check carefully for any shipping damage. If any
damage is found it must be reported immediately and
a claim made against the transportation company.
Important: Equipment is shipped FOB (Free on Board)
at the manufacturer.Therefore, freight
claims for damages against the carrier must
be initiated by the receiver.
•Visually inspect the components for shipping damage
as soon as possible after delivery, before it is stored.
Concealed damage must be reported within 15 days.
•If concealed damage is discovered, stop unpacking the
shipment.
•Do not remove damaged material from the receiving
location.Take photos of the damage, if possible.The
owner must provide reasonable evidence that the
damage did not occur after delivery.
•Notify the carrier’s terminal of damage immediately by
phone and by mail. Request an immediate joint
inspection of the damage by the carrier and the
consignee.
•Do not attempt to repair any damaged parts until the
parts are inspected by the carrier’s representative.
Jobsite Storage
WARNING
Microbial Growth!
Wet interior unit insulation can become an amplification
site for microbialgrowth (mold), which may cause odors
and serious health related indoor air quality problems. If
there is evidence of microbial growth (mold) on the
interiorinsulation, removeor replace the insulation prior
to operating the system. Failure to remove microbial
growth could result in serious health problems.
This unit is intended for indoor use only.To protect the unit
from damage due to the elements, and to prevent possible
IAQ contaminant sources fromgrowing, the unit should be
stored indoors. If indoor storage is not possible, the
following provisions for outdoor storage must be met:
•Place the unit(s) on a dry surface or raise above the
ground to assure adequate air circulation beneath the
unit.
•Cover the unit(s) with a water proof tarp to protect
them from the elements.
•Make provisions for continuous venting of the covered
units to prevent moisture from standing on the unit(s)
surfaces. Wet interior unit insulation can become an
amplification site for microbial growth (mold) which
has been determined to be a cause of odors and
serious health related indoor air quality problems.
•Store units in the normal UP orientationto maintain oil
in the compressor.
•Horizontal units may be stacked no more than three
units high. Do not stack the vertical unit configurations.
Jobsite Inspection Checklist
Always perform the following checks before
accepting a unit:
•Verify that the nameplate data matches the data on the
sales order and bill of lading (including electrical data).
•Verify that the power supply complies with the unit
nameplate specifications.
•Visually inspect the exterior of the unit, for signs of
shipping damage. Do not sign the bill of lading
accepting the unit(s) until inspection has been
completed. Check for damage promptly after the
unit(s) are unloaded. Once thebill of lading is signed at
the jobsite, the unit(s) are now the property of the
SOLDTO party and future freight claims MAY NOT be
accepted by the freight company.
WSHP-SVX01N-EN13
Unit Dimensions and Weights
GEH and EXH Clearance Dimensions
Access to the unit for service purposes should be provided
at installation. All ½-5 tons and EXH070 configurations
(see Figure 1, p. 14) require an 18 in. (457 mm) surround
clearance from other mechanical and electricalequipment
(where shown) to enable panel removal from the unit for
service/maintenance ability. NEC requires 36 in. clearance
on the control panel side of the unit. Some local codes
Figure 1. GEH ½ to 5 tons and EXH ½ to 6 tons clearance
18" (457)
(3-SIDES)
LEFT RETURN
BACK SUPPLY
UNIT FRONT
36"
(914)
18" (457)
(3-SIDES)
LEFT RETURN
RIGHT SUPPLY
UNIT FRONT
36"
(914)
require a greater service clearance than listed below.
Check all code requirements prior to unit installations.
Equipment containing a same-side supply/return
combination requires a 3 in. (229 mm) limitation on one
side. Access to theTXV may not be possible with this 3 in.
(229 mm) clearance.This configuration is typically applied
in a corridor installation, where space limitations force the
left or right side of the unit against a wall.
18" (457)
(3-SIDES)
LEFT RETURN
LEFT SUPPLY
3"
(76)
UNIT FRONT
36"
(914)
18" (457)
(3-SIDES)
RIGHT RETURN
BACK SUPPLY
UNIT FRONT
36"
(914)
Figure 2.GEH 6-15 tons clearance
36"
(914)
SERVICE
CLEARANCE
TOP VIEW
CONTROL BOX
18" (457)
(3-SIDES)
RIGHT RETURN
LEFT SUPPLY
UNIT FRONT
36"
(914)
18" (457)
(3-SIDES)
RIGHT RETURN
RIGHT SUPPLY
3"
(76)
UNIT FRONT
36"
(914)
Service clearance dimensions for the GEH 6-15 tons
horizontal (see Figure 2, p. 14) includes a two side access
appropriate for control and blower motor/wheel access.
Some local codes require a greater service clearance than
listed below. Check all code requirements prior to unit
installations.
20"
(508)
SERVICE
CLEARANCE
BLOWER ACCESS
PAN EL
14WSHP-SVX01N-EN
Unit Dimensions and Weights
E
GEV ½ to 5 tons and EXV ½ to 6 tons
clearance dimensions
Access to the unit for service purposes should be provided
at installation. A 24 in. surround clearance (see Figure 3,
p. 15) from other mechanical and electrical equipment
(where shown) is recommended for all configurations.
This will enable panel removal from the unit for service/
maintenance. Some local codes require a greater service
clearance than listed below. Check all code requirements
prior to unit installations. Units in a free return application
will require more than a 12 in. minimum clearance to
provide proper air flow to the units air-to-refrigerant coil.
Pictured in Figure 3,p. 15 minimum 1” clearance on return
side with properly attached duct work.
Figure 3.GEV ½-5 tons and EXV ½-6 tons clearance
dimensions
1"
(25.4)
24"
(610)
RIGHT RETURN
TOP/BACK SUPPLY
1"
(25.4)
UNIT FRONT
36"
(914)
1"
(25.4)
GEV 6–10 Tons Clearance Dimensions
A 36 in. service clearance is required for all configurations
at the unit front. It is recommended that 20 in of service
clearance for the sides (see Figure 4, p. 15) from other
mechanical and electrical equipment (where shown).The
unit may be serviced through the front access panel or
remaining open sides. Some local codes require a greater
service clearance than listed below. Check all code
requirements prior to unit installations.
Figure 4. GEV 6–10 tons clearance
FRONT RETURN
TOP SUPPLY
ACCESS PANEL FOR
SHEAVES AND BELTS
20"
(508)
SERVICE
CLEARANCE
(914)
SERVICE
CLEARANC
GEV 12½–25 Tons Clearance Dimensions
Figure 5, p. 15 outlines service clearances. A 36 in. service
clearance is requiredfor all configurationsat the unitfront.
A 24 in. service clearance (see Figure 3, p. 15) from other
mechanical and electrical equipment (where shown) is
recommended for all configurations.The unit may be
serviced through the front accesspanel. Some local codes
require a greater service clearance than listed below.
Check all code requirements prior to unit installations.
Figure 5. GEV 12½–25 tons clearance
18" (457)
CONTROL BOX
NEC REQ.
MIN. 36" (914)
C.B. TO WALL
CLEARANCE
FRONT RETURN-AIR
BACK SUPPLY-AIR
UNIT FRONT
16" (406) TO
FILTER FRAME
FOR RETURN-AIR
MIN. SERVICE
CLEARANCE FOR
EITHER LEFT
OR RIGHT SIDE
IS 22" (559). FOR
FAN SHAFT REMOVAL,
A 22" (559) CLEARANCE
MUST BE PROVIDED
ON EITHER THE
LEFT OR RIGHT SIDE.
36"
UNIT FRONT
24"
(610)
1"
(25.4)
36"
(914)
LEFT RETURN
TOP/BACK SUPPLY
WSHP-SVX01N-EN15
Unit Dimensions and Weights
Figure 6. Left return/left supply (GEH/EXH)
BP
TOP
F X G
OPENING
C
BLOWER
ACCESS
PANEL
1" (25.4)
DRAIN
3/4" (19) NPTI
BACKLEFT SIDEFRONT
RIGHT SIDE
H
Q
K
(13)
1/2"
14"
(356")
H
J
RS
N
A
HI VOLT
WCI mounting location
LO VOLT
ED
6 3/4"
1" (25.4)
REFRIG
AND
CONTROL
(171)
ACCESS
L (W.O.)
M (W.I.)
7"
(178)
1 3/8" (35)
Table 4.Left return/left supply (GEH/EXH)
GEH
UnitABCD
006, 009
012, 015
018
024, 030
036, 042
Std-048
Hi-048,
06058(1473)33(838)21(533)
40
(1016)20(508)15(381)20(508)15(381)
40
(1016)20(508)15(381)20(508)15(381)
46
(1168)23(584)18(457)23(584)18(457)
46
(1168)23(584)18(457)23(584)18(457)
50
(1270)25(635)19(483)25(635)20(508)
58
(1473)33(838)21(533)
EXH
UnitABCD
006-009
012-015
018-024
030-036
042-070
070
Not
1. All dimensions are in inches followed by millimeters in parenthesis.
2. Access to the unit for service purposes should be provided at installation. Horizontal units require an 18 in. (457 mm) surround clear
3. Equipment containing a same-side supply/return combination requires a 3 in. (229 mm) clearance on one side. Access to the TXV may not be possible
4. If hot gas reheat is specified for a size 018, 024, the actual cabinet size increases to an 036 cabinet.
5. When a horizontal model is ordered with the same side return and supply in a ducted application, bottom filter removal is required due to limited
(a) Return air opening dimension
(b) Filter rack dimension
40
(1016)20(508)15(381)20(508)15(381)
40
(1016)20(508)15(381)20(508)15(381)
46
(1168)23(584)18(457)23(584)18(457)
50
(1270)25(635)19(483)25(635)20(508)
58
(1473)33(838)21(533)
58
(1473)39(991)21(533)
es:
mechanical and electrical equipment to enable panel removal from the unit for service/maintenance ability. NEC requires 36 in. clearance on the
control panel side of the unit. Some local codes require a greater service clearance. Check all code requirements prior to unit installations. Installer is
responsible for following all local and NEC code requirements.
with this 3 in. (229 mm) clearance.
access on either side of the filter.
(a)
29-1/2
(597)
29-1/2
(597)
(a)
29-1/2
(597)
29-1/2
(597)
EF x GHJKLNPTIMNPTINPQR
23-1/2
(749)
23-1/2
(749)
6-7/8 x 8
(175) x (203)
6-7/8 x 9-7/8
(175) x (251)
8-1/4 x 9-3/4
(210) x (248)
8-1/4 x 11-3/8
(210) x (289)
10-1/2 x 13-1/2
(267) x (343)17(432)4(102)1 (25)
13-1/8 x 11-3/8
(333) x (289)18(457)
13-7/8 x 13-7/8
(352) x (352)18(457)
11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
13-1/2
(343)
4-1/2
1-3/4
(114)
4-1/4
(108)
4-3/4
1-3/8
(121)
4-3/4
1-3/8
(121)
5-1/4
1-1/2
(133)
(38)1 (25)1 (25)
5-1/4
1-1/2
(133)
(38)1 (25)1 (25)
(45)
3/4
(19)
(35)
(35)
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
3/4
(19)
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
3/4
(19)
38-3/4
(984)
38-3/4
(984)
44-3/4
(1137)
44-3/4
(1137)
48-3/4
(1238)
56-3/4
(1441)
56-3/4
(1441)
18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
31-3/4
(806)
13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)
EF x GHJKLNPTIMNPTINPQR
23-1/2
(749)
23-1/2
(749)
6-7/8 x 8
(175) x (203)
8-1/4 x 9-3/4
(210) x (248)
8-1/4 x 11-3/8
(210) x (289)
10-1/2 x 13-1/2
(267) x (343)17(432)4(102)1(25)
13-1/8 x 11-3/8
(333) x (289)18(457)
13-7/8 x 13-7/8
(352) x (352)18(457)
11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
4-1/4
1-3/4
(108)
(45)
4-1/4
(108)
(19)
4-3/4
1-3/8
(121)
(35)
5-1/4
1-1/2
(133)
(38)1(25)1(25)
5-1/4
1-1/2
(133)
(38)1(25)1(25)
3/4
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
38-3/4
(984)
38-3/4
(984)
44-3/4
(1137)
48-3/4
(1238)
56-3/4
(1441)
56-3/4
(1441)
18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
37-3/4
(959)
13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)
(b)
(b)
S
3-1/4
(83)
3-1/4
(83)
4-1/4
(108)
4-1/4
(108)
3-1/4
(83)
5-1/2
(140)
5-1/2
(140)
S
3-1/4
(83)
3-1/4
(83)
4-1/4
(108)
3-1/4
(83)
5-1/2
(140)
5-1/2
(140)
18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
18-1/2
(597)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)
18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)
ance from other
16WSHP-SVX01N-EN
Figure 7. Left return/back supply (GEH/EXH)
Unit Dimensions and Weights
BP
TOP
F X G
OPENING
C
1"(25.4)
H
DRAIN
3/4" (19) NPTI
BLOWER
H
J
BACKLEFT SIDEFRONT
14"
RIGHT SIDE
(356)
ACCESS
PANEL
K
N
A
Table 5.Left return/back supply (GEH/EXH)
GEH
UnitABCD
006, 009
012, 015
018
024, 030
036, 042
Std-048
Hi-048, 060
40
(1016)20(508)15(381)20(508)15(381)
40
(1016)20(508)15(381)20(508)15(381)
46
(1168)23(584)18(457)23(584)18(457)
46
(1168)23(584)18(457)23(584)18(457)
50
(1270)25(635)19(483)25(635)20(508)
58
(1473)33(838)21(533)
58
(1473)33(838)21(533)
(a)
29-1/2
(597)
29-1/2
(597)
EF x GHJKLNPTIMNPTINPQR
(175) x (203)
6-7/8 x 9-7/8
(175) x (251)
8-1/4 x 9-3/4
(210) x (248)
8-1/4 x 11-3/8
(210) x (289)
10-1/2 x 13-1/2
23-1/2
(749)
23-1/2
(749)
(267) x (343)17(432)4(102)1 (25)
13-1/8 x 11-3/8
(333) x (289)18(457)
13-7/8 x 13-7/8
(352) x (352)18(457)
R
HI VOLT
WCI mounting location
LO VOLT
ED
6-7/8 x 8
1" (25.4)
11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
13-1/2
(343)
S
6 3/4"
(171)
Q
1/2"
(13)
4-1/2
1-3/4
(114)
(45)
4-1/4
(108)
(19)
4-3/4
1-3/8
(121)
(35)
4-3/4
1-3/8
(121)
(35)
5-1/4
1-1/2
(133)
(38)1 (25)1 (25)
5-1/4
1-1/2
(133)
(38)1 (25)1 (25)
3/4
REFRIG
AND
CONTROL
ACCESS
L (W.O.)
M (W.I.)
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
3/4
(19)
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
3/4
(19)
7"
(178)
1 3/8" (35)
38-3/4
(984)
38-3/4
(984)
44-3/4
(1137)
44-3/4
(1137)
48-3/4
(1238)
56-3/4
(1441)
56-3/4
(1441)
18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
31-3/4
(806)
13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)
(b)
18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
18-1/2
(597)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)
S
3-1/4
(83)
3-1/4
(83)
4-1/4
(108)
4-1/4
(108)
3-1/4
(83)
5-1/2
(140)
5-1/2
(140)
EXH UnitABCD
006-009
012-015
018-024
030-036
042-070
070
es:
Not
40
(1016)20(508)15(381)20(508)15(381)
40
(1016)20(508)15(381)20(508)15(381)
46
(1168)23(584)18(457)23(584)18(457)
50
(1270)25(635)19(483)25(635)20(508)
58
(1473)33(838)21(533)
58
(1473)39(991)21(533)
29-1/2
29-1/2
(a)
(597)
(597)
EF x GHJKLNPTIMNPTINPQR
23-1/2
(749)
231/2
(749)
6 -7/8 x 8
(175) x (203)
8-1/4 x 9-3/4
(210) x (248)
8-1/4 x 11-3/8
(210) x (289)
10-1/2 x 13-1/2
(267) x (343)17(432)4(102)1(25)
13-1/8 x 11-3/8
(333) x (289)18(457)
13-7/8 x 13-7/8
(352) x (352)18(457)
11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
4-1/2
(114)
4-1/4
(108)
4-3/4
(121)
9-3/4
(248)
9-3/4
(248)
1-3/4
2-3/4
3-1/4
1-1/2
1-1/2
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
(45)
(70)
(83)
(38)1(25)1(25)
(38)1(25)1(25)
38-3/4
(984)
38-3/4
(984)
44-3/4
(1137)
48-3/4
(1238)
56-3/4
(1441)
56-3/4
(1441)
18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
37-3/4
(959)
13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)
(b)
18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)
S
3-1/4
(83)
3-1/4
(83)
4-1/4
(108)
3-1/4
(83)
5-1/2
(140)
5-1/2
(140)
1. All dimensions are in inches followed by millimeters in parenthesis.
2. Access to the unit for service purposes should be provided at installation. Horizontal units require an 18 in. (457 mm) surround clear
mechanical and electrical equipment to enable panel removal from the unit for service/maintenance ability. NEC requires 36 in. clearance on the
control panel side of the unit. Some local codes require a greater service clearance. Check all code requirements prior to unit installations. Installer is
responsible for following all local and NEC code requirements.
3. Equipment containing a same-side supply/return combination requires a 3 in. (229 mm) clearance on one side. Access to the TXV may not be possible
with this 3 in. (229 mm) clearance.
ance from other
4. If hot gas reheat is specified for a size 018, 024, the actual cabinet size increases to an 036 cabinet.
(a) Return air opening dimension
(b) Filter rack dimension
WSHP-SVX01N-EN17
Unit Dimensions and Weights
Figure 8. Left return/right supply (GEH/EXH)
TOP
N
A
ED
BLOWER
1" (25.4)
ACCESS
PANEL
Q
R
HI VOLT
WCI mounting location
LO VOLT
S
6 3/4"
BP
REFRIG
AND
(171)
CONTROL
ACCESS
L (W.O.)
M (W.I.)
7"
(178)
DRAIN
3/4" (19) NPTI
BACKLEFT SIDEFRONT
RIGHT SIDE
1/2"
(13)
C
F X G
OPENING
H
K
H
1" (25.4)
14"
J
1 3/8" (35)
Table 6.Left return/right supply (GEH/EXH)
GEH UnitABCD
40
40
46
46
50
58
58
20
(508)
20
(508)
23
(584)
23
(584)
25
(635)
33
(838)
33
(838)
(381)
(381)
(457)
(457)
(483)
(533)
(533)
006, 009
012, 015
018
024, 030
036, 042
Std-048
Hi-048, 060
(1016)
(1016)
(1168)
(1168)
(1270)
(1473)
(1473)
EXH UnitABCD
006-009
012-015
018-024
030-036
042-070
070
es:
Not
1. All dimensions are in inches followed by millimeters in parenthesis.
2. Access to the unit for service purposes should be provided at installation. Horizontal units require an 18 in. (457 mm) surround clear
mechanical and electrical equipment to enable panel removal from the unit for service/maintenance ability. NEC requires 36 in. clearance on the
control panel side of the unit. Some local codes require a greater service clearance. Check all code requirements prior to unit installations. Installer is
responsible for following all local and NEC code requirements.
3. Equipment containing a same-side supply/return combination requires a 3 in. (229 mm) clearance on one side. Access to the TXV may not be
possible with this 3 in. (229 mm) clearance.
4. If hot gas reheat is specified for a size 018, 024, the actual cabinet size increases to an 036 cabinet.
(a) Return air opening dimension
(b) Filter rack dimension
40
(1016)20(508)15(381)20(508)15(381)
40
(1016)20(508)15(381)20(508)15(381)
46
(1168)23(584)18(457)23(584)18(457)
50
(1270)25(635)19(483)25(635)20(508)
58
(1473)33(838)21(533)
58
(1473)39(991)21(533)
15
15
18
18
19
21
21
(a)
20
(508)
20
(508)
23
(584)
23
(584)
25
(635)
29-1/2
(597)
29-1/2
(597)
(a)
29-1/2
(597)
29-1/2
(597)
EF x GHJKLNPTIMNPTINPQR
15
6-7/8 x 8 (175) x
(381)
15
(381)
18
(457)
18
(457)
20
(508)
23-1/2
(749)
23-1/2
(749)
(203)
6-7/8 x 9-7/8
(175) x (251)
8-1/4 x 9-3/4
(210) x (248)
8-1/4 x 11-3/8
(210) x (289)
10-1/2 x 13-1/2
(267) x (343)
13-1/8 x 11-3/8
(333) x (289)
13-7/8 x 13-7/8
(352) x (352)
11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
13-1/2
(343)
17
(432)
18
(457)
18
(457)
4-1/2
(114)
4-1/4
(108)
4-3/4
(121)
4-3/4
(121)
4 (102)
5-1/4
(133)
5-1/4
(133)
1-3/4
1/2
(45)
(13)
1/2
(13)
3/4
(19)
3/4
(19)
3/4
(19)
(13)
(13)
(19)
(19)
(19)
2-3/4
(70)
3-1/4
(83)
3-1/4
(83)
1
(25)
1-1/2
(38)1 (25)1 (25)
1-1/2
(38)1 (25)1 (25)
1/2
1/2
3/4
3/4
3/4
38-3/4
(984)
38-3/4
(984)
44-3/4
(1137)
44-3/4
(1137)
48-3/4
(1238)
56-3/4
(1441)
56-3/4
(1441)
18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
31-3/4
(806)
13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)
EF x GHJKL NPTIM NPTINPQR
23-1/2
(749)
23-1/2
(749)
6-7/8 x 8
(175) x (203)
8-1/4 x 9-3/4
(210) x (248)
8-1/4 x 11-3/8
(210) x (289)
10-1/2 x 13-1/2
(267) x (343)17(432)4(102)1(25)
13-1/8 x 11-3/8
(333) x (289)18(457)
13-7/8 x 13-7/8
(352) x (352)18(457)
11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
4-1/2
(114)
4-1/4
(108)
4-3/4
(121)
5-1/4
(133)
5-1/4
(133)
1-3/4
1/2
(45)
(13)
1/2
(13)
3/4
(19)
3/4
(19)
(13)
(13)
(19)
(19)
2-3/4
(70)
3-1/4
(83)
1-1/2
(38)1(25)1(25)
1-1/2
(38)1(25)1(25)
1/2
1/2
3/4
3/4
38-3/4
(984)
38-3/4
(984)
44-3/4
(1137)
48-3/4
(1238)
56-3/4
(1441)
56-3/4
(1441)
18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
37-3/4
(959)
13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)
(b)
18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
18-1/2
(597)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)
(b)
18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)
ance from other
S
3-1/4
(83)
3-1/4
(83)
4-1/4
(108)
4-1/4
(108)
3-1/4
(83)
5-1/2
(140)
5-1/2
(140)
S
3-1/4
(83)
3-1/4
(83)
4-1/4
(108)
3-1/4
(83)
5-1/2
(140)
5-1/2
(140)
18WSHP-SVX01N-EN
Figure 9. Right return/left supply (GEH/EXH)
R
TOP
N
A
ED
1" (25.4)
BLOWER
ACCESS
PANEL
DRAIN
3/4" (19) NPTI
RIGHT SIDE
H
K
H
BACKLEFT SIDEFRONT
J
7" (178)
C
F X G
OPENING
WCI mounting location
HI VOLT
LO VOLT
1"(25.4)
14"
(356)
S
6 3/4"
Unit Dimensions and Weights
BP
REFRIG
AND
CONTROL
(171)
ACCESS
L (W.O.)
M (W.I.)
Q
(13)
1/2"
1 3/8"(35)
Table 7.Right return/left supply (GEH/EXH)
GEH UnitABCD
006, 009
012, 015
018
024, 030
036, 042
Std-048
Hi-048, 060
40
(1016)20(508)15(381)20(508)15(381)
40
(1016)20(508)15(381)20(508)15(381)
46
(1168)23(584)18(457)23(584)18(457)
46
(1168)23(584)18(457)23(584)18(457)
50
(1270)25(635)19(483)25(635)20(508)
58
(1473)33(838)21(533)
58
(1473)33(838)21(533)
EXH UnitABCD
006-009
012-015
018-024
030-036
042-070
es:
Not
070
40
(1016)20(508)15(381)20(508)15(381)
40
(1016)20(508)15(381)20(508)15(381)
46
(1168)23(584)18(457)23(584)18(457)
50
(1270)25(635)19(483)25(635)20(508)
58
(1473)33(838)21(533)
58
(1473)39(991)21(533)
(a)
29-1/2
(597)
29-1/2
(597)
(a)
29-1/2
(597)
29-1/2
(597)
EF x GHJKLNPTIMNPTINPQR
23-1/2
(749)
23-1/2
(749)
6-7/8 x 8
(175) x (203)
6-7/8 x 9-7/8
(175) x (251)
8-1/4 x 9-3/4
(210) x (248)
8-1/4 x 11-3/8
(210) x (289)
10-1/2 x 13-1/2
(267) x (343)17(432)4(102)1 (25)
13-1/8 x 11-3/8
(333) x (289)18(457)
13-7/8 x 13-7/8
(352) x (352)18(457)
11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
13-1/2
(343)
4-1/2
(114)
4-1/4
(108)
4-3/4
(121)
4-3/4
(121)
5-1/4
(133)
5-1/4
(133)
1-3/4
1/2
(45)
(13)
3/4 (19)
1-3/8
1-3/8
1-1/2
1-1/2
1/2
(13)
3/4
(35)
(19)
3/4
(35)
(19)
3/4
(19)
(38)1 (25)1 (25)
(38)1 (25)1 (25)
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
3/4
(19)
38-3/4
(984)
38-3/4
(984)
44-3/4
(1137)
44-3/4
(1137)
48-3/4
(1238)
56-3/4
(1441)
56-3/4
(1441)
18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
31-3/4
(806)
13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)
EF x GHJKLNPTIMNPTINPQR
23-1/2
(749)
23-1/2
(749)
6-7/8 x 8
(175) x (203)
8-1/4 x 9-3/4
(210) x (248)
8-1/4 x 11-3/8
(210) x (289)
10-1/2 x 13-1/2
(267) x (343)17(432)4(102)1(25)
13-1/8 x 11-3/8
(333) x (289)18(457)
13-7/8 x 13-7/8
(352) x (352)18(457)
11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
4-1/2
(114)
4-1/4
(108)
4-3/4
(121)
5-1/4
(133)
5-1/4
(133)
1-3/4
1/2
(45)
(13)
1/2
(13)
3/4
(19)
3/4
(19)
(13)
(13)
(19)
(19)
3/4
(19)
1-3/8
(35)
1-1/2
(38)1(25)1(25)
1-1/2
(38)1(25)1(25)
1/2
1/2
3/4
3/4
38-3/4
(984)
38-3/4
(984)
44-3/4
(1137)
48-3/4
(1238)
56-3/4
(1441)
56-3/4
(1441)
18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
37-3/4
(959)
13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)
1. All dimensions are in inches followed by millimeters in parenthesis.
2. Access to the unit for service purposes should be provided at installation. Horizontal units require an 18 in. (457 mm) surround clear
mechanical and electrical equipment to enable panel removal from the unit for service/maintenance ability. NEC requires 36 in. clearance on the
control panel side of the unit. Some local codes require a greater service clearance. Check all code requirements prior to unit installations. Installer is
responsible for following all local and NEC code requirements.
3. Equipment containing a same-side supply/return combination requires a 3 in. (229 mm) clearance on one side. Access to the TXV may not be possible
with this 3 in. (229 mm) clearance.
4. If hot gas reheat is specified for a size 018, 024, the actual cabinet size increases to an 036 cabinet.
(a) Return air opening dimension
(b) Filter rack dimension
(b)
(b)
S
3-1/4
(83)
3-1/4
(83)
4-1/4
(108)
4-1/4
(108)
3-1/4
(83)
5-1/2
(140)
5-1/2
(140)
S
3-1/4
(83)
3-1/4
(83)
4-1/4
(108)
3-1/4
(83)
5-1/2
(140)
5-1/2
(140)
18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
18-1/2
(597)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)
18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)
ance from other
WSHP-SVX01N-EN19
Unit Dimensions and Weights
Figure 10. Right return/back supply (GEH/EXH)
R
TOP
N
F X G
OPENING
A
ED
S
BP
REFRIG
AND
CONTROL
ACCESS
L (W.O.)
M (W.I.)
H
Q
1" (25.4)
6 3/4" (171)
1/2" (13)
7"
(178)
1 3/8" (35)
BLOWER
ACCESS
PANEL
HI VOLT
WCI mounting location
LO VOLT
(356)
14"
K
C
1" (25.4)
H
DRAIN
3/4" (19) NPTI
J
BACKLEFT SIDEFRONT
RIGHT SIDE
Table 8.Right return/back supply (GEH/EXH)
GEH
UnitABCD
006,009
012,015
018
024,030
036,042
Std-048
Hi-048,
060
40
(1016)20(508)15(381)20(508)15(381)
40
(1016)20(508)15(381)20(508)15(381)
46
(1168)23(584)18(457)23(584)18(457)
46
(1168)23(584)18(457)23(584)18(457)
25
50
(1270)
(635)19(483)25(635)20(508)
58
(1473)33(838)21(533)
58
(1473)33(838)21(533)
EXH
UnitABCD
006-009
012-015
018-024
030-036
042-070
070
Not
es:
1. All dimensions are in inches followed by millimeters in parenthesis.
2. Access to the unit for service purposes should be provided at installation. Horizontal units require an 18 in. (457 mm) surround clear
mechanical and electrical equipment to enable panel removal from the unit for service/maintenance ability. NEC requires 36 in. clearance on the
control panel side of the unit. Some local codes require a greater service clearance. Check all code requirements prior to unit installations. Installer is
responsible for following all local and NEC code requirements.
3. Equipment containing a same-side supply/return combination requires a 3 in. (229 mm) clearance on one side. Access to the TXV may not be possible
with this 3 in. (229 mm) clearance.
4. If hot gas reheat is specified for a size 018, 024, the actual cabinet size increases to an 036 cabinet.
(a) Return air opening dimension
(b) Filter rack dimension
1. All dimensions are in inches followed by millimeters in parenthesis.
2. 2. Access to the unit for service purposes should be provided at installation. Horizontal units require an 18 in. (457 mm) surround clear
other mechanical and electrical equipment to enable panel removal from the unit for service/maintenance ability. NEC requires 36 in. clearance on the
control panel side of the unit Some local codes require a greater service clearance. Check all code requirements prior to unit installations. Installer is
responsible for following all local and NEC code requirements.
3. Equipment containing a same-side supply/return combination requires a 3 in. (229 mm) clearance on one side. Access to the TXV may not be possible
with this 3 in. (229 mm) clearance.
4. If hot gas reheat is specified for a size 018, 024, the actual cabinet size increases to an 036 cabinet.
5. When a horizontal model is ordered with the same side return and supply in a ducted application, bottom filter removal is required due to limited
access on either side of the filter.
(a) Return air opening dimension
(b) Filter rack dimension
(b)
18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
18-1/2
(597)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)
(b)
18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)
ance from
S
3-1/4
(83)
3-1/4
(83)
4-1/4
(108)
4-1/4
(108)
3-1/4
(83)
5-1/2
(140)
5-1/2
(140)
S
3-1/4
(83)
3-1/4
(83)
4-1/4
(108)
3-1/4
(83)
5-1/2
(140)
5-1/2
(140)
Note: It is recommended to order a bottom access filter rack with right return/right supply combination due to potential
problem with return air filter removal.
WSHP-SVX01N-EN21
Unit Dimensions and Weights
D
L
K
D
E
JM
F
B
H
3 5/8"
(92)
8 3/4"
(222)
A
HI VOLT
LO VOLT
12"
(305)
9 1/2"
(241)
W.O.
DRAIN
W.I.
C
3 5/8"
(92)
BLOWER
ACCESS
COMP/CONTROL
ACCESS
TOP
LEFT SIDE
FRONT
RIGHT SIDE
G
Figure 12. Left return/top supply: GEVE—“A” and later design sequence; EXV—“A” and later design sequence
TOP
BLOWER
ACCESS
COMP/CONTROL
WCI mounting location
8 3/4"
(222)
3 5/8"
(92)
ACCESS
HI VOLT
LO VOLT
12"
(305)
9 1/2"
(241)
3 5/8"
(92)
W.O.
DRAIN
W.I.
LEFT SIDE
FRONT
RIGHT SIDE
Table 10. Left return/top supply: GEVE—“A” and later design sequence; EXV—“A” and later design sequence
W.I.
W.O.
Drain
GEV UnitABCDEFGHJKLM
19-1/2
31-1/4
21-1/2
006-015
018, 024, 030
036, 042
Std-048
Hi-048, 060
EXV UnitABCDEFGHJKLM
006-009
012-015
018-024
030-036
042-060
070
Not
es:
1. All dimensions are in inches followed by millimeters in parenthesis.
2. Access to the unit for service purposes should be provided at installation. Vertical units require an 24 in. (610 mm) surround clearance from other
mechanical and electrical equipment to enable panel removal from the unit for service/maintenance ability. NEC requires 36 in. clearance on the
control panel side of the unit. Some local codes require a greater service clearance. Check all code requirements prior to unit installations. Installer is
responsible for following all local and NEC code requirements.
3. Units in a free return application will require more than a 1 in. (25.4 mm) clearance to provide proper air flow to the unit’s air-to-refrigerant coil.
22WSHP-SVX01N-EN
(495)
21-1/2
(546)
24-1/2
(622)
26-1/2
(673)
26-1/2
(673)
19-1/2
(495)
19-1/2
(495)
21-1/2
(546)
24-1/2
(622)
26-1/2
(673)
26-1/2
(673)
(794)
39-1/4
(997)
41-7/8
(1064)
46-7/8
(1191)
46-7/8
(1191)
31-1/4
(794)
31-1/4
(794)
39-1/4
(997)
41-7/8
(1064)
46-7/8
(1191)
50-7/8
(1292)
11-1/2
(546)
(292)4(102)
21-1/2
13-1/2
(546)
(343)4(102)4(1021)
26-1/2
(673)18(457)
30-1/2
(775)18(457)
30-1/2
(775)18(457)
21-1/2
11-1/2
(546)
(292)4(102)
21-1/2
11-1/2
(546)
(292)
21-1/2
13-1/2
(546)
(343)4(102)4(1021)
26-1/2
(673)18(457)
30-1/2
(775)18(457)
30-1/2
(775)18(457)
5-3/4
(146)
3-1/4
5-3/4
(83)
(146)
4-1/4
(108)2 (51)
4-1/4
(108)2 (51)
5-3/4
(146)
5-1/2
5-5/8
(140)
(142)
3-1/4
5-3/4
(83)
(146)
4-1/4
(108)2(51)
4-1/4
(108)2(51)
9-1/2
(241)15(381)17(432)
9-1/2
(241)
9-1/2
(241)19(483)23(584)
9-1/2
(241)29(737)
9-1/2
(241)29(737)
9-1/2
(241)15(381)17(432)
9-1/2
(241)15(381)17(432)
9-1/2
(241)
9-1/2
(241)19(483)23(584)
9-1/2
(241)29(737)
9-1/2
(241)29(737)
23-3/4
(603)17(432)
27-7/8
(708)
27-7/8
(708)
23-3/4
(603)17(432)
27-7/8
(708)
27-7/8
(708)
6-7/8
(175)8 (203)
9-3/4
8-1/4
(368)
10-1/2
(267)
13-7/8
(352)
13-1/8
(333)
6-7/8
(175)8(203)
8-1/4
(210)
8-1/4
(368)
10-1/2
(267)
13-7/8
(352)
13-1/8
(333)
(248)
11-3/8
(289)
13-1/2
(343)
13-7/8
(352)
11-3/8
(289)
9-3/4
(248)
11-3/8
(289)
13-1/2
(343)
11-3/8
(289)
11-3/8
(289)
NPTI
NPTI
3/4
1/2
3/4
(19)
3/4
(19)
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
1/2
(12.7)
3/4
(19)
3/4
(19)
W.O.
NPTI
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
(19)
(12.7)
3/4
(19)
1/4
(6)
1/2
(13)1(25.4)1(25.4)
1/2
(13)1(25.4)1(25.4)
W.I.
NPTI
3/4
(19)
3/4
(19)
3/4
(19)
1/4
(6)
1/2
(13)1(25.4)1(25.4)
1/2
(13)1(25.4)1(25.4)
FPT
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
Drain
FPT
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
Unit Dimensions and Weights
D
E
jM
D
F
H
8 3/4"
(222)
3 5/8"
(92)
LO VOLT
HI VOLT
W.I.
DRAIN
W.O.
A
12"
(305)
3 5/8"
(92)
C
BLOWER
ACCESS
COMP/CONTROL
ACCESS
9 1/2"
(241)
G
LEFT SIDE
FRONT
RIGHT SIDE
TOP
Figure 13. Left return/back supply: GEVE—“A” and later design sequence; EXV—“A” and later design sequence
TOP
BLOWER
ACCESS
B
COMP/CONTROL
WCI mounting location
8 3/4"
(222)
3 5/8"
(92)
ACCESS
HI VOLT
LO VOLT
12"
(305)
9 1/2"
(241)
3 5/8"
(92)
W.O.
DRAIN
W.I.
LEFT SIDE
FRONT
RIGHT SIDE
Table 11. Left return/back supply: GEVE—“A” and later design sequence; EXV—“A” and later design sequence
W.I.
GEV UnitABCDEFGHJKLM
4
(83)
(83)
006-009
012-015
1-3/4
(44)
3-3/4
(95)
3-7/8
(98)
1-7/8
(48)
1-3/4
(44)
3-3/4
(95)
3-7/8
(98)
1-7/8
(48)
9-1/2
15 (381)
(241)
9-1/2
23-3/4
(241)
9-1/2
(241)
9-1/2
(241)
9-1/2
(241)
9-1/2
(241)15(381)17(432)
9-1/2
(241)15(381)17(432)
9-1/2
(241)
9-1/2
(241)19(483)23(584)
9-1/2
(241)29(737)
9-1/2
(241)29(737)
(603)
19 (483) 23 (584)
29 (737)
29 (737)
23-3/4
(603)17(432)
17
(432)
17 (432)
27-7/8
(708)
27-7/8
(708)
27-7/8
(708)
27-7/8
(708)
6-7/8
(175)8 (203)
9-3/4
8-1/4
(368)
10-1/2
(267)
13-7/8
(352)
13-1/8
(333)
6-7/8
(175)8(203)
8-1/4
(210)
8-1/4
(368)
10-1/2
(267)
13-7/8
(352)
13-1/8
(333)
(248)
11-3/8
(289)
13-1/2
(343)
13-7/8
(352)
11-3/8
(289)
9-3/4
(248)
11-3/8
(289)
13-1/2
(343)
11-3/8
(289)
11-3/8
(289)
(102)
006-015
018, 024,
030
036, 042
Std-048
Hi-048, 060
EXV UnitABCDEFGHJKLM
006-009
012-015
018-024
030-036
042-060
070
e:
Not
1. All dimensions are in inches followed by millimeters in parenthesis.
2. Access to the unit for service purposes should be provided at installation. Vertical units require an 24 in. (610 mm) surround clearance from other
mechanical and electrical equipment to enable panel removal from the unit for service/maintenance ability. NEC requires 36 in. clearance on the
control panel side of the unit. Some local codes require a greater service clearance. Check all code requirements prior to unit installations. Installer is
responsible for following all local and NEC code requirements.
3. Units in a free return application will require more than a 1 in. (25.4 mm) clearance to provide proper air flow to the unit’s air-to-refrigerant coil.
19-1/2
21-1/2
24-1/2
26-1/2
26-1/2
19-1/2
19-1/2
21-1/2
24-1/2
26-1/2
26-1/2
WSHP-SVX01N-EN23
(495)
(546)
(622)
(673)
(673)
(495)
(495)
(546)
(622)
(673)
(673)
31-1/4
(794)
39-1/4
(997)
41-7/8
(1064)
46-7/8
(1191)
46-7/8
(1191)
31-1/4
(794)
31-1/4
(794)
39-1/4
(997)
41-7/8
(1064)
46-7/8
(1191)
50-7/8
(1292)
21-1/2
(546)
21-1/2
(546)
26-1/2
(673)
30-1/2
(775)
30-1/2
(775)
21-1/2
(546)
21-1/2
(546)
21-1/2
(546)
26-1/2
(673)18(457)
30-1/2
(775)18(457)
30-1/2
(775)18(457)
18 (457)
18 (457)
18 (457)
006-009
11-1/2
(292)
13-1/2
(343)4 (102)
4-3/4
(121)
012-015
3-1/4
4-1/4
(108)2 (51)
4-1/4
(108)2 (51)
11-1/2
(292)4(102)
11-1/2
(292)
13-1/2
(343)4(102)
5-1/4
(133)
3-1/4
4-1/4
(108)2(51)
4-1/4
(108)2(51)
NPTI
3/4
1/2 (13) 1/2 (13)
(19)
3/4
(19)
1/4
(6)
1/2
1 (25.4)
(13)
1/2
1 (25.4) 1 (25.4)
(13)
W.I.
NPTI
3/4
(19)
3/4
(19)
3/4
(19)
1/4
(6)
1/2
(13)1(25.4)1(25.4)
1/2
(13)1(25.4)1(25.4)
3/4
(19)
3/4
(19)
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
W.O.
NPTI
3/4
(19)
3/4
(19)
1 (25.4)
W.O.
NPTI
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
Drain
FPT
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
Drain
FPT
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
Unit Dimensions and Weights
C
A
3 5/8"
(92)
8 3/4"
(222)
LO VOLT
HI VOLT
W.I.
DRAIN
W.O.
3 5/8"
(92)
12"
(305)
H
B
D
L
F
JM
E
D
K
9 1/2"
(241)
G
FRONT
RIGHT SIDE
TOP
LEFT SIDE
BLOWER
ACCESS
COMP/CONTROL
ACCESS
Figure 14. Right return/top supply: GEVE—“A” and later design sequence; EXV—”A” and later design sequence)
TOP
BLOWER
ACCESS
COMP/CONTROL
ACCESS
WCI mounting location
HI VOLT
LO VOLT
3 5/8"
(92)
8 3/4"
(222)
W.O.
DRAIN
12"
9 1/2"
(305)
3 5/8"
(92)
(241)
W.I.
LEFT SIDE
FRONT
RIGHT SIDE
Table 12. Right return/top supply: GEVE—“A” and later design sequence; EXV—“A” and later design sequence
W.I.
W.O.
Drain
GEV UnitABCDEFGHJKLM
006-015
018, 024, 030
036, 042
Std-048
Hi-048, 060
19-1/2
21-1/2
24-1/2
26-1/2
26-1/2
EXV UnitABCDEFGHJKLM
006-009
012-015
018-024
030-036
042-060
070
Not
e:
1. All dimensions are in inches followed by millimeters in parenthesis.
2. Access to the unit for service purposes should be provided at installation. Vertical units require an 24 in. (610 mm) surround clearance from other
mechanical and electrical equipment to enable panel removal from the unit for service/maintenance ability. NEC requires 36 in. clearance on the
control panel side of the unit. Some local codes require a greater service clearance. Check all code requirements prior to unit installations. Installer is
responsible for following all local and NEC code requirements.
3. Units in a free return application will require more than a 1 in. (25.4 mm) clearance to provide proper air flow to the unit’s air-to-refrigerant coil.
24WSHP-SVX01N-EN
19-1/2
19-1/2
21-1/2
24-1/2
26-1/2
26-1/2
(495)
(546)
(622)
(673)
(673)
(495)
(495)
(546)
(622)
(673)
(673)
31-1/4
39-1/4
41-7/8
(1064)
46-7/8
(1191)
46-7/8
(1191)
31-1/4
31-1/4
39-1/4
41-7/8
(1064)
46-7/8
(1191)
50-7/8
(1292)
(794)
(997)
(794)
(794)
(997)
21-1/2
21-1/2
26-1/2
30-1/2
30-1/2
21-1/2
21-1/2
21-1/2
26-1/2
30-1/2
30-1/2
11-1/2
(546)
(546)
(673)
(775)
(775)
(546)
(546)
(546)
(292)4 (102)
13-1/2
(343)4 (102)4(1021)
18 (457)
18 (457)
18 (457)
11-1/2
(292)4(102)
11-1/2
(292)
13-1/2
(343)4(102)4(102)
(673)18(457)
(775)18(457)
(775)18(457)
5-3/4
(146)
3-1/4
4-1/4
(108)2 (51)
4-1/4
(108)2 (51)
2-1/2
3-1/4
4-1/4
(108)2(51)
4-1/4
(108)2(51)
(83)
(64)
(83)
5-3/4
(146)
5-3/4
(146)
5-3/4
(146)
5-5/8
(143)
9-1/2
(241)15(381)17(432)
9-1/2
23-3/4
(241)
9-1/2
(241)19(483)
9-1/2
(241)29(737)
9-1/2
(241)29(737)
9-1/2
(241)15(381)17(432)
9-1/2
(241)15(381)17(432)
9-1/2
(241)
9-1/2
(241)19(483)23(584)
9-1/2
(241)29(737)
9-1/2
(241)29(737)
(603)
23-3/4
(603)17(432)
17 (432)
23 (584)
27-7/8
(708)
27-7/8
(708)
27-7/8
(708)
27-7/8
(708)
6-7/8
(175)8 (203)
9-3/4
8-1/4
(368)
10-1/2
(267)
13-7/8
(352)
13-1/8
(333)
6-7/8
(175)8(203)
8-1/4
(210)
8-1/4
(368)
10-1/2
(267)
13-7/8
(352)
13-1/8
(333)
(248)
11-3/8
(289)
13-1/2
(343)
13-7/8
(352)
11-3/8
(289)
9-3/4
(248)
11-3/8
(289)
13-1/2
(343)
11-3/8
(289)
11-3/8
(289)
NPTI
3/4
(19)
3/4
(19)
1-3/4
(19)
1/2
(13)1 (25)1 (25)
1/2
(13)1 (25)1 (25)
NPTI
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
1/2
(13)1(25.4)1(25.4)
1/2
(13)1(25.4)1(25.4)
1/2
(13)
3/4
(19)
3/4
(19)
W.I.
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
NPTI
1/2
(13)
3/4
(19)
3/4
(19)
W.O.
NPTI
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
FPT
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
Drain
FPT
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
Unit Dimensions and Weights
C
A
3 5/8"
(92)
8 3/4"
(222)
LO VOLT
HI VOLT
W.I.
DRAIN
W.O.
3 5/8"
(92)
12"
(305)
H
B
D
L
F
JM
E
D
K
9 1/2"
(241)
G
FRONT
RIGHT SIDE
TOP
LEFT SIDE
BLOWER
ACCESS
COMP/CONTROL
ACCESS
Figure 15. Right return/back supply: GEVE—“A” and later design sequence; EXV—“A” and later design sequence
TOP
BLOWER
ACCESS
COMP/CONTROL
ACCESS
WCI mounting location
HI VOLT
LO VOLT
3 5/8"
(92)
8 3/4"
(222)
W.O.
DRAIN
W.I.
3 5/8"
(92)
9 1/2"
(241)
12"
(305)
LEFT SIDE
FRONT
RIGHT SIDE
Table 13. Right return/back supply: GEVE—“A” and later design sequence; EXV—“A” and later design sequence
W.I.
GEV UnitABCDEFGHJKLM
4
006-015
018, 024,
030
036, 042
Std-048
Hi-048, 060
19-1/2
(495)
21-1/2
(546)
24-1/2
(622)
26-1/2
(673)
26-1/2
(673)
31-1/4
(794)
39-1/4
(997)
41-7/8
(1064)
46-7/8
(1191)
46-7/8
(1191)
21-1/2
(546)
21-1/2
(546)
26-1/2
(673)
30-1/2
(775)
30-1/2
(775)
006-009
11-1/2
(292)
012-015
13-1/2
(343)4 (102)
18 (457)
18 (457)
18 (457)
(102)
(152)
3-1/4
4-1/4
(108)2 (51)
4-1/4
(108)2 (51)
6
(83)
1-3/4
(44)
006-009
1-1/4
(32)
012-015
3-7/8
(98)
1-7/8
(48)
9-1/2
15 (381) 17 (432)
(241)
9-1/2
23-3/4
(241)
9-1/2
(241)19(483)
9-1/2
(241)29(737)
9-1/2
(241)29(737)
(603)
17 (432)
23 (584)
27-7/8
(708)
27-7/8
(708)
6-7/8
(175)8 (203)
9-3/4
8-1/4
(368)
10-1/2
(267)
13-7/8
(352)
13-1/8
(333)
(248)
11-3/8
(289)
13-1/2
(343)
13-7/8
(352)
11-3/8
(289)
NPTI
3/4
1/2 (13) 1/2 (13)
(19)
3/4
(19)
1-3/4
(19)
1/2
(13)1 (25)1 (25)
1/2
(13)1 (25)1 (25)
W.I.
EXV UnitABCDEFGHJKLM
006-009
012-015
018-024
030-036
042-060
070
e: All dimensions are in inches followed by millimeters in parenthesis.