Trane Starters, Electrical Components, Drives, CVHE, CVHF Engineering Bulletin

...
Engineering Bulletin
Starters, Drives, and Electrical Components for CenTraVac™ Chillers
Models: CVHE, CVHF, CVHG, CDHF, CDHG
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
SAFETY WARNING
Warnings, Cautions and Notices
Warnings, Cautions and Notices. Note that warnings, cautions and notices appear at
appropriate intervals throughout this manual.Warnings are provided to alert installing contractors to potential hazards that could result in death or personal injury. Cautions are designed to alert personnel to hazardous situations that could result in personal injury, while notices indicate a situation that could result in equipment or property-damage-only accidents.
Your personal safety and the proper operation of this machine depend upon the strict observance
of these precautions.
Read this manual thoroughly before operating or servicing this unit.
ATTENTION: Warnings, Cautions and Notices appear at appropriate sections throughout this
literature. Read these carefully:
WARNING
CAUTIONs
NOTICE:
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only accidents.
Important Environmental Concerns!
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment.
Trane advocates the responsible handling of all refrigerants-including industry replacements for
CFCs such as HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are important to the environment, our
customers, and the air conditioning industry. All technicians who handle refrigerants must be certified.The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded
field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
© 2011Trane All rights reserved CTV-PRB004-EN
WARNING
Warnings, Cautions and Notices
WARNING
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.
Before installing/servicing this unit, technicians MUST put on all Personal Protective Equipment (PPE) recommended for the work being undertaken. ALWAYS refer to appropriate MSDS sheets and OSHA guidelines for proper PPE.
When working with or around hazardous chemicals, ALWAYS refer to the appropriate MSDS sheets and OSHA guidelines for information on allowable personal exposure levels, proper respiratory protection and handling recommendations.
If there is a risk of arc or flash, technicians MUST put on all Personal Protective Equipment (PPE) in accordance with NFPA 70E or other country-specific requirements for arc flash protection, PRIOR to servicing the unit.
Failure to follow recommendations could result in death or serious injury.
Trademarks
Adaptive Frequency, CenTraVac, Duplex,TOPSS,Tracer AdaptiView,Tracer Summit,Trane, and the
Trane logo are trademarks or registered trademarks ofTrane in the United States and other
countries.Trane is a business of Ingersoll Rand. All trademarks referenced in this document are the trademarks of their respective owners.
Cutler-Hammer is a registered trademark of Eaton Corporation.
CTV-PRB004-EN 3
Table of Contents
Introduction ............................................................ 6
About Starters .......................................................... 7
What a Starter Does ................................................ 7
Motor Types and Voltage Classes ........................................ 8
Voltage Classes .................................................... 8
Motors ........................................................... 8
Chiller Selection and Electrical Specification ............................. 10
Standard Components of Trane Starters ............................. 10
Chiller Selection Report ............................................ 10
Motor Protection ...................................................... 13
Low-Voltage Starter Types ............................................. 17
Low Voltage—Wye-Delta ........................................... 18
Low Voltage—Solid-State .......................................... 22
Low Voltage—Unit-Mounted Adaptive Frequency Drive ................ 25
Low Voltage—Remote-Mounted Adaptive Frequency Drive ............. 28
Wye-Delta Starters ........................................... 18
Solid-State Starters ........................................... 22
Medium-Voltage Starter Types (2,300–6,600 Volts) ....................... 31
Medium Voltage—Across-the-Line (2.3–6.6 kV) .......................32
Across-the-Line Starter (2,300–6,600 volts) ........................ 32
Medium Voltage—Primary Reactor (2.3–6.6 kV) ....................... 35
Primary Reactor Starter (2,300–6,600 volts) ....................... 35
Medium Voltage—Autotransformer (2.3–6.6 kV) ...................... 38
Autotransformer Starter (2,300–6,600 volts) .......................38
Unit-Mounted Starter Top Hat—NEC 2005 Code Requirement ........ 40
Medium Voltage—Remote-Mounted Adaptive Frequency Drive ......... 42
Chiller Unit Control Features for the AFD ......................... 43
Medium-Voltage Starter Types (10,000–13,800 Volts) .....................45
Medium Voltage—Across-the-Line (10–13.8 kV) ....................... 45
Across-the-Line Starter (10,000–13,800 volts) ...................... 45
Medium Voltage—Primary Reactor (10–13.8 kV) ...................... 47
Primary Reactor Starter (10,000–13,800 volts) ..................... 47
Medium Voltage—Autotransformer (10–13.8 kV) ...................... 48
Autotransformer Starter (10,000–13,800 volts) .....................48
Electrical System—Ratings ............................................. 49
Electrical System—Design Guidelines ................................... 52
4 CTV-PRB004-EN
Disconnect Means ............................................ 52
Short-Circuit Interruption ...................................... 53
Power Circuit Requirements ....................................54
Electrical System–Power Wire Sizing .................................... 56
Starter Options ........................................................ 61
Multiple Starter Lineups (2,300–6,600 volts) ....................... 61
Industrial-Grade Starters ...................................... 63
Glossary .............................................................. 73
CTV-PRB004-EN 5
Introduction
This document explains key electrical concepts and starter product information relating toTrane
water chillers.Topics include voltage classes, motors, motor protection, starter types, variable­frequency drives, wire sizing, power factor correction, and electrical term definitions.
Information in this document changes frequently.To make sure you are viewing the most recent version, be sure to download the latest copy available on e-Library.
Dimensional data
Job specific submittals are always the best source of dimensional data. General starter dimensions are shown with the descriptions of each starter type in this document.
Wiring information
The best source for additional information is the Installation, Operation, and Maintenance manual
shipped with the chiller. Field connection diagrams are also available on the website.
All unit-mounted starters are designed for top-entry line power only. Remote starters are typically designed for top-entry line power and a bottom exit for load wires.The medium-voltage starter submittals show conduit space for alternate wiring options. Additional wiring options may be available.
For your convenience, power wire sizing charts for various voltages and conduit combinations are provided.
Fuse and circuit breaker sizing
Proper sizing of fuses and circuit breakers upstream of the starter is the responsibility of the customer or the electrical engineer. Disconnects and circuit breakers are options that can be installed within theTrane or local code requirements for installation of overcurrent devices.
Important: Trane, in presenting electrical information and system design and application
concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC and related electrical system is the prerogative and responsibility of the engineering professional.Trane has a policy of continuous product and product information improvement and reserves the right to changedesign and specifications without notice. Consult the chiller submittal for the most up-to-date information as applied to the specific chiller under consideration.
®
starters. WhatTrane would install may not necessarily satisfy UL, NEC,
®
6 CTV-PRB004-EN
About Starters
What a Starter Does
Electric, centrifugal, water-cooled chillers use relatively large induction motors to drive the compressors.These motors use a control device to connect to and disconnect from the electrical power source.These control devices are referred to as combination controllers or, most commonly, as motor starters. Variable-frequency drives or Adaptive Frequency™ Drives (AFDs) also serve as motor starters, but their capabilities extend beyond starting and stopping the motor.
There are three main functions of the motor starter.The first function is to serve as the link between
the chiller’s motor and the electrical distribution system. It is used during the starting and stopping sequence.
Starting an induction motor from standstill causes a large electrical current draw for a few seconds.
The extra current is used to develop the required torque to get the compressor motor running at
full speed.The initial rush of current decreases as the compressor motor ramps up to full speed, and is commonly referred to as inrush current.
The second function of the starter is to keep the initial current inrush below a specified level.Third,
the starter communicates with the unit controller to coordinate motor protection.
Starters can be as simple or as complex as necessary to meet various engineering specifications and/or customer needs. A variable-speed drive can provide starter functions, among other things (see “Low Voltage—Unit-Mounted Adaptive Frequency Drive,” p. 25 and “Medium Voltage—
Remote-Mounted Adaptive Frequency Drive,” p. 42). It will be classified as a starter type for the
purposes of this document.
Several voltage classes and starter types are available as indicated on the chart below. Each one is described in greater detail in this document.
Table 1. Trane CenTraVac chiller starter choices
Low Voltage (208–600 V) Medium Voltage (2,300–6,600 V)
Remote-Mounted Unit-Mounted Remote-Mounted Unit-Mounted Remote-Mounted
Wye-Delta
Up to 1,700 amps
Solid-State
(Up to 1,120 amps with disconnect or circuit breaker required)
Adaptive Frequency Drive
460/480/575/600 V Up to 1,360 amps (460/480 V) 1,120 amps (575/600 V)
Wye-Delta
Up to 1,316 amps (Up to 1,120 amps with disconnect/circuit breaker option)
Solid-State
(Up to 1,120 amps with disconnect or circuit breaker required)
Adaptive Frequency Drive
Up to 1,210 amps Circuit breaker standard 460–480 V
Across-the-Line
Up to 360 amps Isolation switch, power fuses standard
Primary Reactor
Up to 360 amps Isolation switch, power fuses standard
Autotransformer
Up to 360 amps Isolation switch, power fuses standard
Adaptive Frequency Drive
Up to 250 amps Isolation switch, power fuses standard
Across-the-Line
Up to 288 amps Isolation switch, power fuses standard
Primary Reactor
Up to 205 amps Isolation switch, power fuses standard
Autotransformer
Up to 205 amps Isolation switch, power fuses standard
Medium Voltage
(10–13.8 kV)
Across-the-Line
Up to 94 amps Isolation switch, power fuses standard
Primary Reactor
Up to 94 amps Isolation switch, power fuses standard
Autotransformer
Up to 94 amps Isolation switch, power fuses standard
CTV-PRB004-EN 7
MotorTypes and Voltage Classes
Voltage Classes
There are two primary voltage classes typically used in the water-cooled chiller industry: low and
medium. For centrifugal chillers this is generally restricted to three-phase power only.
Low voltage ranges from 208 to 600 volts. Starters and frequency drives in this voltage range include sizes up to 1,700 amps.
Medium voltage has two main voltage groups. One ranging from 2,300 to 6,600 volts and the other ranging from 10,000 to 13,800 volts. Starters in this class have sizes up to 360 amps and 94 amps respectively.
For a given power (kW), the higher the voltage the lower the amperage.The voltage is typically established prior to creating the job plans and specifications.
Motors
A centrifugal motor is a relatively simple motor. Specifically, it is referred to as a three-phase, squirrel-cage, 3,600-rpm, alternating-current induction motor with two-pole construction.
The squirrel-cage motor consists of a fixed frame, or stator, carrying the stator windings and a
rotating member called the rotor. Figure 1 shows a cutaway of a typical low-voltage motor.The rotor is built by rigidly mounting steel laminations to the motor shaft.The motor winding consists of aluminum bars that are die-cast into slots in the rotor.The aluminum bars are connected at each end by a continuous ring.This skeleton of rotor bars with end rings looks like a squirrel cage and gives the motor its name.
Figure 1. Low-voltage motor Figure 2. Medium-voltage motor
Stator
Stator
Squirrel-cage
Squirrel-cage
Rotor shaft
Rotor shaft
Stator
Stator
In a three-phase motor, three windings on the stator connect to a motor terminal board, and ultimately to the power grid via the starter.When the polyphase alternating current flows through the stator winding it produces a rotating magnetic field.The resulting magnetic forces exerted on the rotor bars cause the rotor to spin in the direction of the stator field.The motor accelerates until a speed is reached corresponding to the slip necessary to overcome windage and friction losses.
This speed is referred to as the no-load speed.
Low-voltage motors typically have six motor terminals to electrically connect the motor in a wye (star) or delta configuration. Most low-voltage motors are random-wound motors, but larger amperage higher horsepower motors are form wound for better heat dissipation. Connecting links can be used to convert the six motor electrical connections to three connections.
Medium-voltage motors (2,300–6,600 V) have three motor terminals. Figure 2 shows a typical medium-voltage motor minus the rotor shaft.You can visually compare most low- and medium-
8 CTV-PRB004-EN
MotorTypes and Voltage Classes
voltage motors. Medium-voltage motors are always form wound and you can see that the insulation is thicker and the windings are more evenly spaced.
Figure 3. Ceramic insulators on medium-voltage motor (10-13.8 kV)
Medium-voltage motors (10–13.8 kV) have the same design and construction attributes as other medium-voltage motors with some externally visible differences. Ceramic insulators and larger spacing of the motor terminals are commonly found on typical 10–13. kV medium-voltage motors. Internally, these motors are form wound and structurally similar to other medium-voltage motors.
The ceramic insulators combined with the larger spacing between the motor terminals help
prevent electrical arcing.
Higher voltage motors and starters are being used in large chiller plants where incoming line power makes 10–13.8 kV accessible. In some cases, higher voltage chillers allow for the elimination of electrical components with their associated space requirements and energy losses. In particular, chiller installations with on-site or dedicated power generation, such as district cooling, higher education, hospitals, industrials, and airports have opportunities for electrical distribution system simplification and energy savings.
Benefits of 10,000–13,800 volts include:
No need for step-down transformer
No transformer losses
Higher uncorrected power factor
Reduced electrical design and labor
Reduced mechanical room space
Note: Motors and starters at 10,000–13,800 volts typically cost more, and the motor efficiency is
lower than 2,300–6,600-volt motors.
Motors are available in specific power sizes, which are rated in kilowatts or horsepower.The
TOPSS™ computer software selection program selects the proper motor to meet the specific
cooling duty of the application.
CTV-PRB004-EN 9
Chiller Selection and Electrical Specification
Standard Components of Trane Starters
A 4 kVA control-power transformer (CPT) supports all of the chiller auxiliary power needs— 3 kVA control-power transformer supplied with AFDs.
Primary and secondary current transformers (CTs) support the overload and momentary power loss protection functions of the unit controller.This allows amps per phase and percent amps to be displayed at the unit controller.
Potential transformers (PTs) support motor protection functions such as under/overvoltage within the unit controller.This allows voltage per phase, kilowatts, and power factor to be displayed at the unit controller.
Grounding provisions are standard.
A terminal block for line power connection is standard. Load-side lugs are standard for remote starters.The lug sizes and configuration are shown on the submittal drawing.TheTrane has a circuit breaker as standard. Medium-voltage starters have provisions for a bolted connection.
Chiller Selection Report
The following terms are found on a typicalTOPSS product report. Review the example selection
output report shown in Figure 4, p. 12.
Electrical information
Usually the primary RLA (incoming line), compressor motor RLA, and kW of the chiller are used as nameplate values. In this section, we will review the typical electrical data presented on the selection report.
®
AFD
A. Motor size (kW). The motor size is listed on the program report based on its output kW.The
output kW is the motor’s full, rated power capacity.There is an amperage draw associated with the motor size called full-load amps (FLA). FLA is the amperage the motor would draw if it were loaded to its full rated capacity, i.e. the motor size. The FLA is not available from the chiller selection program, but it can be obtained from motor data sheets upon request.
B. Primary power (kW). The primary power is the power the chiller uses at its design cooling
capacity.The primary power will always be less than or equal to the motor size.
C. Motor locked-rotor amps (LRA). There is a specific locked-rotor amperage value associated
with each specific motor.This is the current draw that would occur if the rotor shaft were instantaneously held stationary within a running motor. LRA is typically six to eight times the motor full-load amps (FLA). LRA is also used commonly in discussing different starter types and the inrush amperages associated with the motor start. For example, a wye-delta starter will typically draw approximately 33 percent of the motor LRA to start. A solid-state starter will draw approximately 45 percent of the motor LRA to start.
D. Primary rated-load amps (RLA [incoming line]). The RLA is also commonly referred to as
the selection RLA or unit RLA.This is the amperage that is drawn on the line side when the chiller is at full cooling capacity. Nameplate RLA (usually the same as primary RLA [incoming line]) is the key number used to size the starter, disconnects, and circuit breaker. Primary RLA (incoming line) is also the value used to determine the minimum circuit ampacity (MCA) for sizing conductors. Primary RLA (incoming line) is always less than or equal to the motor full-load amps (FLA).
E. Compressor motor RLA. This is the amperage between the motor and starter or AFD. If the
unit is a starter, the compressor motor RLA will be almost identical to the primary RLA (incoming line). If the unit is an AFD, typically, the compressor motor RLA will be larger.This value is used to size the AFD.The primary RLA (incoming line) is lower due to the improved power factor of the AFD.
10 CTV-PRB004-EN
Chiller Selection and Electrical Specification
F. Minimum circuit ampacity (MCA). This term appears on the chiller nameplate and is used
by the electrical engineer to determine the size and number of conductors needed to bring power to the starter.
MCA = 1.25 x (Primary RLA [incoming line])+
… with this number rounded up to the next whole number. Said another way, the MCA is 125 percent of the motor design primary RLA (incoming line) plus 100 percent of the amperage of other loads (sump heater, oil pump, purge, etc.).The MCA is listed on the chiller selection report. Power cable sizes and conduits are discussed in “Electrical System–PowerWire Sizing,” p. 56. If the AFD is a remote, free-standing AFD, the MCA will be based on the compressor motor RLA.
(
4000
volts
motor
)
G. Maximum overcurrent protection (MOP or MOCP). The MOP appears on the chiller
nameplate.The electrical engineer often wants to know the MOP when the chiller is selected for sizing fuses and upstream circuit breakers. Understand that the MOP is a maximum, NOT a recommended fuse size. Improperly sized circuit breakers or fuses can result in nuisance trips during the starting of the chiller or insufficient electrical protection. MOP is also NOT used to size incoming power wiring—the MCA is used for this purpose.
CTV-PRB004-EN 11
Chiller Selection and Electrical Specification
8QLW,QIRUPDWLRQ
&9+(



+]

+]
\

6
6


7(&8
7(&8


7ZRSDVVHYDSZDWHUER[
7ZRSDVVFRQGZDWHUER[
'HVLJQ,QIRUPDWLRQ
WRQV
\
OE
N:
OE
N:WRQ
\
OE
N:WRQ
1R
1R
8QLWPRXQWHGORZYROWDJH$)' $
6WDQGDUGFRROLQJ
0%K
0%K
$
(YDSRUDWRU,QIRUPDWLRQ
)
S
S
IW+2
JSP
ZDWHU
)
1$
JSPWRQ
\
QRQPDULQH
SVLJ
KUVTIWGHJ)%WX
&RQGHQVHU,QIRUPDWLRQ
)
IW+2
JSP
ZDWHU
)
S
1$
JSPWRQ
QRQPDULQH
KUVTIWGHJ)%WX
SVLJ
(OHFWULFDO,QIRUPDWLRQ
$
$
$
\
$
$

Figure 4. Excerpt from chiller selection report
0RGHO
,PSHOOHUVL]H 0RWRUVL]H 0RWRUIUHTXHQF\ ,QFRPLQJOLQHIUHTXHQF (YDSVKHOOVL]H (YDSEXQGOHVL]H (YDSWXEHW\SH (YDSWXEHWKLFNQHVV (YDSSDVVHV
  
A
 
&RROLQJFDSDFLW 3ULPDU\SRZHU 3ULPDU\HIILFLHQF 13/9
/RZYROWDJH$)'W\SH
B
 
&RPSUHVVRUVL]H 2ULILFHVL]H
0RWRUYROWDJH ,QFRPLQJOLQHYROWDJH &RQGVKHOOVL]H &RQGEXQGOHVL]H &RQGWXEHW\SH &RQGWXEHWKLFNQHVV &RQGSDVVHV
+&)&UHIULJHUDQWFKDUJH 6KLSSLQJZHLJKW 2SHUDWLQJZHLJKW )UHHFRROLQJRSWLRQ *UHHQ6HDOFHUWLILFDWLRQ
 
  
8QLWKHDWUHMHFWHGWRDPELHQW
)'KHDWUHMHFWHGWRDPELHQW
(YDSOHDYLQJWHP (YDSIORZUDWH (YDSHQWHULQJWHPS (YDSIORZFDSDFLW (YDSIRXOLQJIDFWRU
&RQGHQWHULQJWHPS &RQGIORZUDWH &RQGOHDYLQJWHP &RQGIORZFDSDFLW\ &RQGIRXOLQJIDFWRU
  
  
0RWRU/5$ 3ULPDU\5/$,QFRPLQJOLQH 8QFRUUHFWHGSRZHUIDFWRU
 
SSOLFDWLRQW\SH
(YDSSUHVVXUHGUR (YDSIOXLGW\SH (YDSIOXLGFRQFHQWUDWLRQ (YDSZDWHUER[W\SH (YDSZDWHUER[SUHVVXUH
C
D
&RQGSUHVVXUHGURS &RQGIOXLGW\SH &RQGIOXLGFRQFHQWUDWLRQ &RQGZDWHUER[W\SH &RQGZDWHUER[SUHVVXUH
&RPSUHVVRUPRWRU5/$ 0LQFLUFXLWDPSDFLW 0D[RYHUFXUUHQWSURWHFWLRQ
  
E
F
G
12 CTV-PRB004-EN
Motor Protection
Historically, motor protection was provided in the starter by some type of monitoring system. Starter manufacturers usually provide a full range of optional equipment mounted on the starter. Eaton Cutler-Hammer
Today,Trane provides most of the key motor protection and metering functions (see Table 2, first
column) within the chiller microprocessor control panel as standard. Having the motor control and chiller control in one panel provides better integration and optimization of the two control systems. For example, the chiller controller can unload the chiller when approaching an overload “trip” point, so that the chiller stays online.
Table 2 and Table 3, p. 14 can be used to compare the standard electrical features of the chiller
controller with those of other common Eaton Cutler-Hammer Additional starter-mounted metering and motor protection may not be required and could be considered redundant.These devices are not available for AFDs.
Table 2. Protection and functions by motor packages
®
offers IQ metering and motor protection products for their starters.
®
starter-only-mounted devices.
Protection Functions
Communications Optional Optional Optional Optional Ground fault Optional Long acceleration Standard Standard N/A N/A Maximum number of starts Standard Standard N/A N/A Momentary power loss (distribution fault) Standard N/A N/A N/A Motor overload Standard Standard N/A N/A Motor winding temperature Standard Over temperature Standard N/A N/A N/A Overvoltage Standard Phase imbalance Standard Standard N/A Standard Phase loss Standard Standard N/A Standard Phase reversal Standard N/A N/A Standard Run timer Standard Standard N/A N/A Separate alarm levels Surge capacitor/lightning arrestor Optional N/A N/A N/A Undervoltage Standard
(a)The MP 3000 features Intel-I-Trip overload protection, enhanced custom trip curve development, UL 1053 ground fault, and advanced data logging and
diagnostics. (b)For low voltage, a Trane-supplied circuit breaker or non-fused disconnect is also required when ground fault is specified. (c) The chiller controller monitors the motor temperatures of all three phases with one resistance temperature detector (RTD) per phase (d)For this option, add one or two sets (three RTDs per set) of 100-ohm platinum RTDs to the motor. Contact La Crosse Field Sales Support. (e) Under/over phase-voltage sensors include volts per phase, kW, power factor, kWh, and under/overvoltage. A required pick on medium-voltage starters. (f) Three alarm levels are used: warning only, nonlatching (auto-reset), and latching (manual reset required).
(f)
Tracer AdaptiView MP 3000
(b)
(c)
(e)
Standard Standard N/A N/A
(e)
Standard N/A N/A
Optional
N/A N/A Standard
N/A N/A Standard
(d)
(a)
IQ 150 IQ DP 4130
N/A N/A
CTV-PRB004-EN 13
Motor Protection
Table 3. Starter ONLY: metering functions and accuracies
Metering Functions Tracer AdaptiView MP 3000
Ampere demand N/A N/A Standard (±0.25%) Standard (±0.3%) Current (%RLA) Standard (±3% to ±7%) Standard N/A N/A Current (3-phase) Standard (±3%) Standard Standard (±0.25%) Standard (±0.3%) Voltage (3-phase) Standard Frequency N/A N/A Standard Standard Harmonic distortion current N/A N/A N/A Standard (31 Harmonic distortion voltage N/A N/A N/A Standard (31 Kilowatt Standard Power factor Standard VA (volt-amperes) N/A N/A Standard (±0.5%) Standard (±0.6%) VA demand N/A N/A Standard (±0.5%) Standard (±0.6%) VA hours N/A N/A Standard (±0.5%) Standard VARs (volt-amperes reactive) N/A N/A Standard (±0.5%) Standard (±0.6%) VAR demand N/A N/A Standard (±0.5%) Standard (±0.6%) VAR-hours N/A N/A Standard (±0.5%) Standard Watt, see Kilowatt Standard Watt demand Standard N/A Standard (±0.5%) Standard (±0.6%) Watt-hours Standard N/A Standard (±0.5%) Standard
(a)The MP 3000 features Intel-I-Trip overload protection, enhanced custom trip curve development, UL 1053 ground fault, and advanced data logging and
diagnostics. (b)Under/over phase-voltage sensors include volts per phase, kW, power factor, kWh, and under/overvoltage. A required pick on medium-voltage starters.
(b)
(±2%) N/A Standard (±0.25%) Standard (±0.3%)
(b)
(±5%) N/A N/A N/A
(b)
(±5%) N/A Standard Standard
(b)
N/A Standard (±0.5%) Standard (±0.6%)
(a)
IQ 150 IQ DP 4130
st
)
st
)
Overload protection
Overload or overcurrent protection shields the motor from small levels of overcurrent ranging from 107 to 140 percent of the primary RLA of the chiller. In contrast, fuses and circuit breakers are used to protect against short-circuit currents which may range to well over 100,000 amps.
Inductive loads, such as a chiller motor, behave differently than resistive loads such as electric heaters.Their current draw is greatest at startup and corresponds to the existing load when running. In other words, a motor operating normally draws rated amps (RLA) at rated load, fewer amps at less-than-rated load and more amps at greater-than-rated load. It is the latter condition that requires overload protection.
Adding an overload protection device prevents the motor from drawing more than its rated amperage for an extended period. Basic overload devices simply open the circuit when current draw reaches the “trip” point. More sophisticated devices attempt to restore normal motor operating conditions by reducing the load, but will disconnect the motor if overloading persists.
As with most overload devices, the chiller controller determines the “trip time” by measuring the magnitude of the overload. It then compares the overload to the programmed RLA “time-to-trip” curve. At startup, the standard overload protection is bypassed for the starter’s acceleration time, or until the motor is up to speed. Refer to Figure 5, p. 15 for the chiller controller’s overload time­to-trip curve.
14 CTV-PRB004-EN
Figure 5. Tracer AdaptiView chiller controller overload time-to-trip curves
25
20
Overload Trip
Time (sec)
15
10
5
0
Motor Protection
Nominal
Minimum
Maximum
108
102
Overload situations, left unchecked by protection, can cause excessive motor heat, that can permanently damage the windings and lead to motor failure.The time until motor damage depends mainly on the magnitude of the overcurrent and has an inverse time versus current relationship.The greater the overcurrent, the less time it takes to cause motor damage.
Overcurrent can be the result of motor overload, low line voltage, unbalanced line voltage, blocked load (rotor cannot freely rotate), single phasing, bad connections, broken leads, or other causes. It can occur in any one winding, a set of windings, or in all the motor windings.
The threshold of overcurrent is generally the primary RLA, which may be raised for service factor
or lowered due to any derating factor, such as ambient temperature or line-voltage imbalance.
Overload protection is bypassed during a start due to the high currents associated with locked rotor and motor acceleration. Maximum allowed acceleration times per the AdaptiView unit controller are listed in Table 4.
Table 4. Long acceleration protection
Starting Method (starter type)
Wye-Delta 27 Solid-State 27 Variable-Frequency Drive 12 Across-the-Line 6 Primary Reactor 16 Autotransformer 16
Maximum Setting for the Acceleration Timer (sec)
114
120
126
132
% Run-Load Amps
138
144
150
Motor overheat protection
The unit controller monitors the motor winding temperatures in each phase and terminates chiller
operation when the temperature is excessive.This feature also prevents the chiller from starting if the motor temperature is too high.
Momentary power loss protection (distribution fault)
Momentary power losses longer than two or three line cycles will be detected and cause the chiller to shut down, typically within six cycles. The chiller can also shut down due to excessive or rapid voltage sags. Shutting down the chiller prevents power from being reapplied with different motor phasing.
CTV-PRB004-EN 15
Motor Protection
Phase failure/loss protection
The chiller will shut down if any of the three-phases of current feeding the motor drop below
10 percent RLA for 2.5 seconds.
Phase imbalance protection
Based on an average of the three phases of current, the ultimate phase-imbalance trip point is 30 percent.The RLA of the motor can be derated depending on the percent of this imbalance.The phase-imbalance trip point varies based on the motor load.
Phase reversal protection
Detects reverse-phase rotation and shuts the chiller down (backwards rotation).
Under/overvoltage protection
The chiller is shut down with an automatic reset due to excessive line voltage ±10 percent of the
design voltage.
Short cycling protection
Prevents excessive wear on the motor and starter due to heating from successive starts.The unit controller uses an algorithm based on a motor heating constant and a background timer (measuring the running time since the last start).
Supplemental motor protection
This is a set of optional motor protection features, offered as a option in addition to the Enhanced
Electrical Protection Package (see “SMP, Supplemental Motor Protection—Medium voltage only
(Enhanced Electrical Protection Package option),” p. 66).
16 CTV-PRB004-EN
Low-Voltage StarterTypes
Table 5 shows the most common low-voltage starter types available and lists their advantages and
disadvantages.Typical inrush acceleration profiles for these starters are shown in Figure 6, p. 18. It is very uncommon to see a full-voltage starter in a low-voltage application due to the high inrush current; however, it is represented on the chart to provide a frame of reference.
Which starter type is best?
The wye-delta starter has been around a long time and, except for an AFD, it draws the lowest
inrush current.Wye-delta starters are electromechanical and service technicians are typically more comfortable with them.The solid-state starter is a relatively newer design compared to the wye­delta, and has a slightly higher inrush current in chiller applications.The solid-state starter inrush can be set lower (the starter takes longer to get the motor up to speed), but it must be above the minimum inrush required to develop the proper starting torque.The solid-state starter is comparable in price to the wye-delta starter and has a smoother inrush curve without any current spikes.The wye-delta’s transition spike is not long enough to set utility demand ratchets or reduce the life of the motor.The starter type chosen ultimately depends on the application.
Table 5. Comparison of low-voltage starter types
Starter Type (closed-transition
Wye-Delta (Star-Delta)
Solid-State ~45 33 15%
Adaptive Frequency Drive (AFD)
Inrush Current % LRA
33 33 60%
<13 (<RLA)
Percent Rated Torque
varies 25%
How Often Used Advantages Disadvantages
Trane Adaptive Frequency Drives provide motor control, but they are much more than just starters. They also control the operating speed of the compressor-motor by regulating output voltage in
proportion to output frequency. Varying the speed of the compressor-motor can translate into significant energy savings.
Applications that favor the use of an AFD exhibit increased operating hours at reduced condenser water temperatures and high energy costs. However, it is important to recognize that all variable­speed drives, including theTraneAFD, require more energy near full-load design conditions, often coinciding with the peak electrical demand of the building.This may result in higher demand chargesand diminish the overall energy savings.An analysis of the full-year operation of the chiller plant using an hour-by-hour simulation program that does not use blended kW and kWh energy rates will help determine whether an AFD is appropriate for a specific application and location.
• Equal reduction of torque and inrush current
• Low cost
• Can be unit mounted
• Gradual inrush/ramp up
• No “spike” at transition
• Price comparable to the wye­delta
• Lowest inrush current
• Better chiller efficiency at reduced lift
• Only applicable up to 600 volts
• “Spike” at transition
• Higher level of service expertise than wye-delta
• Higher inrush current than wye-delta
• Starting harmonics may be an issue
• Most expensive
• Efficiency loss at full load
• Harmonics may be an issue
Typical Acceleration Time (seconds)
5–12
5–12
8–30
Unit or remote mounted?
Unit-mounted starters can save on installed cost and space, and they can be tested in the factory and shipped on the chiller in a NEMA 1 enclosure. Remote-mounted starters provide more options for multiple starter lineups, and may be chosen in order to implement some of the industrial starter options such as high-fault and NEMA 12/3R.
CTV-PRB004-EN 17
Low-Voltage StarterTypes
Figure 6. Comparison of low-voltage starting current
120
100
80
60
% LRA
40
20
0
0
Low Voltage—Wye-Delta
Wye-Delta Starters
One of the most common starters in the industry is the wye/star-delta. It is an electromechanical starter initially set up in a “wye” or “star” configuration, then it transitions to a “delta” configuration during the starting sequence.To illustrate a typical starting sequence using a generic (non-Trane) schematic, refer to Figure 7, p. 19 and its “Starting sequence,” p. 19.
X-Line
Solid-State
Wye-Delta
AFD
123456789
Time (seconds)
10
18 CTV-PRB004-EN
Figure 7. Simplified wye-delta wiring schematic
LINE
VOLTAGE
WYE-DELTA
STARTER WIRING
Low-Voltage StarterTypes
1A
1M
S
2M
S
1M
2M
1M
2M
1M
2M
TRANSITION
1A
R
R
R
S
1A
S
1A
S
PR
S
1M
2M
1A
MOTOR
OL
OL
OL
F
CPT
F
START-
STOP
PR
Starting sequence
1. The “start” signal from the CenTraVac controller energizes the pilot relay (PR).
2. The PR contacts close to energize the star contactor (S).
3. The S contacts close to connect the motor in the star configuration.
4. An S interlock closes to energize the start contactor (1M).
5. The 1M contacts close to connect the motor to the line.
6. A time delay relay or current monitoring device initiates transition by energizing the resistor contactor
. 1A contacts close to connect the resistors to the line in the star configuration and in parallel with
7
the compressor
8. A 1A interlock now opens to de-energize the S contactor.
9. The S contacts open to connect the resistors and motor windings in series in the delta configuration.
10. An S interlock closes to energize the run contactor (2M).
11. The 2M contacts close to bypass the resistors and connect the compressor motor directly to the line
(1A).
motor.
in
the delta configuration.
Dimensions
The typical unit-mounted wye-delta starter size is shown in Figure 9, p. 20. Typical remote-
mounted one-, two- and three-door starter sizes are shown in Figure 10, p. 20, Figure 11, p. 20, and
Figure 12, p. 21. Always consult the submittal drawings for as-built dimensions.
CTV-PRB004-EN 19
Low-Voltage StarterTypes
The one-door remote-mounted starter size is generally used for 155- to 606-amp starters with no
disconnect.The two-door size is used for 640- to 1,700-amp starters with no disconnect.The three­door size is used for 1,385- to 1,700-amps when disconnects are included.
Figure 8. Unit-mounted WD Figure 9. Remote 1-door WD
Stator
Squirrel-cage
60”
84”
Rotor shaft
13.5”
38.5”
32”
Figure 10. Remote 2-door WD Figure 11. Remote 3-door WD
Stator
19.3”
Stator
Squirrel-cage
84”
Rotor shaft
Stator
84”
56”
20 CTV-PRB004-EN
19.3”
19.3”
84”
Figure 12. Unit-mounted, wye-delta starter
2
Low-Voltage StarterTypes
1. Top-entry power only
1
2
3
2. 4 kVA control-power transformer
3. Circuit breaker (optional)
4. Transition resistors
4
Standard features
Unit or floor mounted
Control-power transformer
Padlock tab for additional locking of the starter door
Line-side connection terminal block/main lug only
UL and CUL certified
Environmental specification
Designed, developed, and tested in accordance with UL 508
NEMA 1 enclosure as standard
Operation from sea level to 6,000 ft (1,829 m)
Operating ambient temperature range 32°F to 104°F (0°C to 40°C)
Relative humidity, non-condensing 5 percent to 95 percent
Non-operating ambient temperature range -40°F to 158°F (-40°C to 70°C)
Voltage utilization range ±10 percent
CTV-PRB004-EN 21
Low-Voltage StarterTypes
Low Voltage—Solid-State
Solid-State Starters
TheTrane®solid-state starter produces a soft start with a gradual inrush current and no transition
spikes. It controls the starting characteristics of a motor by controlling the voltage to the motor. It does so through the use of silicon controlled rectifiers (SCRs), which are solid-state switching devices, and an integral bypass contactor for power control. An SCR will conduct current in one direction only when a control signal (gate signal) is applied. Because solid-state starters use alternating current (AC), two SCRs per phase are connected in parallel, opposing each other so that current may flow in both directions. For three-phase loads, a full six-SCR configuration is used, as shown in Figure 13.
Figure 13. Six-SCR arrangement
L1
L2
L3
T1
T2
T3
Starting sequence
During starting, control of current or acceleration time is achieved by gating the SCRs “on” at different times within the half-cycle.The gate pulses are originally applied late in the half-cycle and then gradually applied sooner in the half-cycle. If the gate pulse is applied late in the cycle, only a small increment of the wave form is passed through, and the output is low. If the gate pulse is applied sooner in the cycle, a greater increment of the wave form is passed through, and the output is increased. By controlling the SCRs ’ output voltage, the motor’s acceleration characteristic and current inrush are controlled as illustrated in Figure 14.
Figure 14. Starting sequence wave forms
25% voltage 50% voltage full voltage
When the SCRs are fully “phased on,” the integral bypass contactors are energized.The current
flow is transferred from the power pole to the contactors.This reduces the energy loss associated with the power pole, and extends contactor life.When the starter is given the stop command, the SCRs are gated “full voltage” and the bypass contactor is de-energized.The current flow is transferred from the contactors back to the power poles. Less than one second later, the SCRs are turned off and the current flow stops.
22 CTV-PRB004-EN
Low-Voltage StarterTypes
Features
Unit- and floor-mounted models are available
Control-power transformer
Starting current is factory set and field adjustable
Starting torque is factory set and adjustable via a voltage “notch” setting
Six-SCR power section
Air-cooled design with bypass contactor eliminates need for a water-cooling circuit, pump, and heat exchanger
Bypass contactor rated to carry 100 percent of the full-load motor phase current
Protection from shorted SCRs and high starter heatsink temperature
Protection from transient voltage through resistor-capacitor (RC) snubbers across SCRs and metal oxide varistors (MOVs)
Padlock tab for additional locking of starter door
Line-side connection terminal block/main lug only
UL and CUL certified
Dimensions
Typical dimensions for unit- or remote-mounted solid-state starters are shown in Figure 15. Always
consult the submittal drawings for as-built dimensions.
Figure 15. Solid-state dimensions
38.5"
60"
13.5"
CTV-PRB004-EN 23
Low-Voltage StarterTypes
Figure 16. Unit-mounted, solid-state starter
1. Top-entry line power
1
2. Intelligent technology (IT) controller
3. Starter control board
4. Potential transformers
5. 4 kVA control-power transformer
2
3
4
5
Environmental specification
Designed, developed, and tested in accordance with UL 508
NEMA 1 enclosure as standard
Operation from sea level to 6,000 ft (1,829 m)
Operating ambient temperature range 32°F to 104°F (0°C to 40°C)
Relative humidity, non-condensing 5% to 95%
Non-operating ambient temperature range -40°F to 158°F (-40°C to 70°C)
Voltage utilization range ±10%
24 CTV-PRB004-EN
Low-Voltage StarterTypes
Low Voltage—Unit-Mounted Adaptive Frequency Drive
TheTrane Adaptive Frequency Drive is a refrigerant-cooled, microprocessor controlled design.The
AFD is used in lieu of a constant-speed starter and is currently available for use with 460 or 480 volts only. Adaptive Frequency is a trademarked term for theTrane proprietary control logic and made toTrane specifications.
About the Trane AFD
The AFD is unit-mounted and ships completely assembled, wired, and tested from the factory.The
AFD controller is designed to interface with the chiller controller. It adapts to the operating ranges and specific characteristics of the chiller.The optimum chiller efficiency is created by coordinating the compressor-motor speed with the compressor inlet guide vanes.The chiller controller and the AFD controller work together to maintain the chilled-water setpoint and avoid surge. If surge is detected, the chiller controller’s surge-avoidance logic in the chiller controller makes the proper adjustments to move the operating point away from surge.
How it works
The frequency drive regulates output voltage in proportion to output frequency to maintain ideal
motor flux and constant torque-producing capability.Or put simply, a variable-speed drive controls load-side frequency and voltage to adjust the compressor motor speed.The AFD is a voltage­source, pulse-width modulated (PWM) design. It consists of three primary power sections as shown in Figure 17: the active rectifier, the DC bus, and the inverter.
®
variable-speed drive, using
Figure 17. AFD power sections
M
M
Rectifier DC Bus Inverter
Rectifier DC Bus Inverter
Determines line-side harmonics Determines load-side harmonics
Determines line-side harmonics Determines load-side harmonics
Rectifier (active). Takes incoming AC power, filters it with an LCL filter (not shown), and then
converts it to a fixed DC voltage. The insulated-gate bipolar transistor (IGBT) active rectifier significantly reduces the amount of line-side harmonic levels and the amount of ripple on the DC bus.The active rectifier also has some traditional post-generation filtering capabilities to further smooth out remaining line-side harmonics.
DC bus. Capacitors store the DC power provided by the rectifier until it is needed by the inverter.
Inverter. Converts the DC voltage into a synthesized AC output voltage.This synthesized output
controls both the voltage and the frequency.The synthesized output waveform consists of a series of pulses, hence the “pulse” in PWM.
Starting sequence
Trane AFDs are programmed to start the compressor motor using low frequency and low voltage,
thereby minimizing the inrush current.The motor is then brought up to speed by gradually increasing both frequency and voltage at the same time.Thus, current and torque are much lower during startup and motor acceleration than the high current, high torque associated with across­the-line or even reduced-voltage starters; refer to the inrush current vs. time graph (Figure 6, p. 18).
CTV-PRB004-EN 25
Loading...
+ 57 hidden pages