Trane UX2B060A9362A, UX2D120A9602A, DX2B060A9362A, DX2B080A9422A, DX2C100A9482A Installer's Manual

...
Page 1
IIIIII IIIIIIIIIIIIII IIIIIIII
1 8- CD1 9 D8- 1 5
Upflow / Horizontal & Downflow / Horizontal,
Gas-Fired, Direct Vent, 2-Stage Condensing
Furnaces with Variable Speed Inducer
*UX2B060A9362A *UX2B080A9422A *UX2C100A9482A *UX2D120A9602A *DX2B060A9362A *DX2B080A9422A *DX2C100A9482A *DX2D120A9602A
*__Firstlettermay be"A" or "T"
IMPORTANT -- This Document is customer property and is to remain with this unit.
Please return to service information pack upon completion of work.
*UX2 *DX2
DOWNFLOW
A!R
A/R
FLOW
UPFLOW
AIR
FLOW
UPFLOW/HORIZONTAL LEFT
DOWNFLOW/HORIZONTAL RIGHT
/
\
/ _
FLOW
FLOW
\
i °
A341624P03
Page 2
Installer's Guide
SAFETY SECTION
The following safety practices and precautions must be followed during the installation, servicing, and operation of
this furnace.
1. Use only with the type of gas approved for this furnace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position as specified in "Location and Clearances" (page 3), of these
instructions.
3. Provide adequate combustion and ventilation air to the furnace space as specified in "Air for Combustion and
Ventilation" (pages 7-8), of these instructions.
4. Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as
specified in the "Venting" section (pages 13-23), of these instructions.
5. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections, as
specified in "Gas Piping" (page 31), of these instructions.
6. Always install the furnace to operate within the furnace's intended temperature-rise range with a duct system
which has an external static pressure within the allow- able range, as specified on the unit rating plate. Airflow
with temperature rise for cfm versus static is shown in the Service Facts accompanying this furnace.
7. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space
containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace casing and
terminating outside the space containing the furnace.
8. A gas-fired furnace for installation in a residential garage must be installed as specified in "Location and
Clearances" section (page 3), of these instructions.
9. The furnace may be used for temporary heating of buildings or structures under construction only when the
following conditions have been met: a. The furnace venting system must be complete and
installed per manufacturer's instructions.
b. The furnace is controlled only by a room thermostat
(no field jumpers).
c. The furnace return air duct must be complete and
sealed to the furnace and clean air filters are in place.
d. The furnace input rate and temperature rise must be
verified to be within nameplate marking.
e. 100% of the furnace combustion air requirement must
come from outside the structure.
f. The furnace return air temperature range is between
55 and 80 degrees Fahrenheit.
g. Clean the furnace, duct work, and components upon
substantial completion of the construction process, and verify furnace operating conditions including
ignition, input rate, temperature rise and venting, according to the manufacturer's instructions.
10. This product must be gas piped by a Licensed Plumber or Gas Fitter in the Commonwealth of Massachusetts.
CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each
appliance connected to the venting system being placed into operation could result in carbon monoxide
poisoning or death.
The following steps shall be followed for each appliance
connected to the venting system being placed into operation, while all other appliances connected to the
venting system are not in operation:
1. Seal any unused openings in the venting system.
2.
Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 or the CAN/CGA B149 Installation Codes and these instructions. Determine
that there is no blockage or restriction, leakage,
corrosion and other deficiencies which could cause an unsafe condition.
3.
As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are
located and other deficiencies which could cause an unsafe condition.
4. Close fireplace dampers.
5.
Turn on clothes dryers and any appliance not
connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate
a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7.
If improper venting is observed during any of the above
tests, the venting system must be corrected in
accordance with the National Fuel Gas Code, ANSI Z221.1/NFPA 54 and/or CAN/CGA B149
Installation Codes.
8.
After it has been determined that each appliance connected to the venting system properly vents where
tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other gas-fired burning appliance to their previous conditions of use.
Safety signal words are used to designate a degree or level of seriousness associated with a particular hazard. The
signal words for safety markings are DANGER, WARNING, and CAUTION.
a. DANGER indicates an imminently hazardous situation
which, if not avoided, will result in death or serious injury. This signal word is limited to the most extreme situations.
b. WARNING indicates a potentially hazardous situation
which, if not avoided, could result in death or serious injury.
c. CAUTION indicates a potentially hazardous situation
which, if not avoided, may result in minor or moderate
To prevent shortening its service life, the furnace should not be used as a "Construction Heater" during the finishing
phases of construction until the requirements listed in item 9, a-g of the safety section of this publication have been
met. Condensate in the presence of chlorides and fluo- rides from paint, varnish, stains, adhesives, cleaning
compounds, and cement create a corrosive condition which may cause rapid deterioration of the heat exchanger.
© 2008 Trane All Rights Reserved 18-CD1 9D8-1 5
FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could result in
serious injury, death or property damage.
Improper servicing could result in dangerous operation,
serious injury, death, or property damage.
Page 3
Installer's Guide
GENERAL
The manufacturer assumes no responsibility for equipment installed in violation of any code or regulation.
It is recommended that Manual J of the Air Conditioning Contractors Association (ACCA) or A.R.I. 230 be followed in estimating heating requirements. When estimating heating requirements for installation at Altitudes above 2000 ft., remember the gas input must be reduced (See GAS INPUT
ADJUSTMENT).
Material in this shipment has been inspected at the factory and released to the transportation agency without known damage. Inspect exterior of carton for evidence of rough handling in shipment. Unpack carefully after moving equipment to approximate location. If damage to contents is found, report the damage immediately to the delivering agency.
Codes and local utility requirements governing the installa- tion of gas fired equipment, wiring, plumbing, and flue connections must be adhered to. In the absence of local codes,
the installation must conform with latest edition of the National Fuel Gas Code ANSI Z223.1 National Installation
Code, CAN/CGA B149.1. The latest code may be obtained from the American Gas Association Laboratories, 400 N. Capitol St. NW, Washington D.C. 20001. 1-800-699-9277 or
www.aga.org These furnaces have been classified as CATEGORY IV
furnaces in accordance with latest edition of ANSI Z21.47 standards ° CAN/CGA 2.3. Category IV furnaces operate
with positive vent static pressure and with a flue loss less than 17 percent. These conditions require special venting systems, which must be gas tight and water tight. These Category IV Direct Vent furnaces are approved for installa- tion in Manufactured/Mobile housing when used with
BAYMFGH001A.
LOCATION AND CLEARANCES
The location of the furnace is normally selected by the architect, the builder, or the installer. However, before the furnace is moved into place, be sure to consider the following requirements:
1. Is the location selected as near the chimney or vent and as centralized for heat distribution as practical?
2. Do all clearances between the furnace and enclosure equal or exceed the minimums stated in Clearance Table on the Outline Drawings.
3. Is there sufficient space for servicing the furnace and other equipment? A minimum of 24 inches front accessi-
bility to the furnace must be provided. Any access door
or panel must permit removal of the largest component.
4. Are there at least 3 inches of clearance between the furnace combustion air openings in the front panel and any closed panel or door provided?
5. Are the ventilation and combustion air openings large enough and will they remain unobstructed? If outside air is used, are the openings set above the highest snow
accumulation level? (See the Air for Combustion and
Ventilation section.)
6. Allow sufficient height in supply plenum above the furnace to provide for cooling coil installation, if the cooling coil is not installed at the time of this furnace
installation.
7. A furnace shall be installed so electrical components are protected from water.
8. If the furnace is installed in a residential garage, it must be installed so that the burners, and the ignition
18-CD19D8-15 3
Contents
Installation Instructions
General Location and Clearances
Outline Drawings Upflow Installation
Downflow Installations Air For Combustion and Ventilation
Duct Connections Return Air Filters General Venting Venting Materials
Vent Tables Horizontal Venting Through Wall
Venting Through the Roof Venting Routed Through a Masonry Chimney
Downward Venting Condensate Drain Instructions
Field Wiring Diagrams Electrical Connections
Gas Piping Combustion and Input Check High Altitude Derate
Start-up and Adjustment
Preliminary Inspections Lighting Instructions
Sequence of Operation Control and Safety Switch Adjustments
Abnormal Conditions
IFC Error Flash Codes
Fault Code Recovery
source are located not less than 18 inches above the floor and the furnace must be located or protected to avoid
physical damage from vehicles.
IMPORTANT:
The furnace must be installed level The only allowable variation
would be slightly to the left and/or forward in upflow installations or slightly toward the front in horizontal installations. This is necessary for proper condensate drainage.
Do not install the furnace in a corrosive or contaminated atmosphere. Failure to follow this warning could result in
early equipment failure.
Do not install the furnace directly on carpeting, tile or other combustible material other than wood flooring. For vertical downflow application, subbase (BAYBASE205) must be used between the furnace and combustible flooring. When
the downflow furnace is installed vertically with a cased
coil, a subbase is not required.
Page 4
4_
Oo
6
ED
ED oo
i
ol
ii
l
DIM"C"
5/8" J
-,-- 5/8" 4- I/ilJ
OUTLET t°_
AIR /._
OUTSIDEAIR
7/8" HOLE_
ELECTRICALLY.... _ ,
SUPPLY ,_._ .... _1
1/78" x 7/8"_
SLOT KNOCKOUT
CONDENSATE DRAIN
(HORIZONTAL)
I-I/8" KNOCKOUT-
CONDENSATE DRAIN
I-5/16"--=-
,l-m..
01_0
23-3/4"
-i
DIM "D"
_1
3/4,,_-
3/4" --_
--,_ 28- I /2" -_,.
INLET I I
AIR "
I_ 24- I/32" _-J L 3-7/32"
DIM "B"
_---r_2"FLUE CONNECT
SEE NOTES I & 2
"E"
"'--4-1/16"
*UX2 UPFLOW / HORIZONTAL OUTLINE DRAWING
(ALL DIMENSIONS ARE IN INCHES)
',1-3-15/16"
"--2-1/16"
-¢1-1/2" GAS
SUPPLY
"-2-1/8"
__T
I -7/8 22-
--__20-1/4"
5 "
18-
2 ii
[
;0-5/8"
/4" I
IZONTAL APPLICATION
IS SIDE ONLY)
I/2"_
40"
o
DIM "A" ---,'-
-,- I/2"
Model
DIM "A" DIM "B" DIM "C" DIM "D" DIM "E" DIM "F"
(See Note 1 & 2)
*UX2B060A9362A
17-1/2" 2-1/4" 16-1/4" 16" 7-1/2" 2"
*UX2B080A9422A
*UX2C100A9482A 21" 2-1/2" 19-3/4" 19-1/2" 9" 3" *UX2D120A9602A 24-1/2" 2-15/16" 23-1/4" 23" 10" 3"
* Prefix May Be "A" or "T" Notes:
1. *UX2D120A9602A Requires 3" Diameter Vent Pipe. *UX2C100A9482A Requires 2-1/2" or 3" Diameter Vent Pipe.
2. Diameter of Vent Pipe may be limited to 2-1/2" or 3" on some models at different altitudes. Refer to the Vent Length Table for proper application.
7/8" KNOCKOUT ELECTRICAL SUPPLY
(ALTERNATE)
-_1-1/2" KNOCKOUT GAS SUPPLY
(ALTERNATE)
I/8" KNOCKOUT
DRAIN
(ALTERNATE)
MINIMUMCLEARANCETO
COMBUSTIBLE MATERIALS
SIDES O IN. REAR 0 IN. FRONT 3 IN, TOP I IN. FLUE 0 IN.
HORIZONTAL(FLUE BSCHARGEON THE LEFTI
ALCOVE
SIDES
RIGHT O IN
LEFT O IN REAR 6 IN FRONT 18 IN TOP I IN, FLUE 0 IN,
CLOSET
SIDES
RIGHT I IN
LEFT I IN REAR 3 IN FRONT 3 IN TOP I IN
FLUE 0 IN,
From Dwg. 21C341884 Rev. 1
|
3
ltl
Ill
I I
II
II
Ill
n_ iI
Page 5
oo
i
© 0
qo 0 oo
i
t_n
....... 19 5'8 .......
......._2" F u
, CON'\ECT
SEE IOTE J
DIM "D"
!
A
3/4
o_ a,,6,_.... j i 7 _,,4"
*DX2 DOWNFLOW / HORIZONTAL OUTLINE DRAWING
(ALL DIMENSIONS ARE IN INCHES)
From Dwg. 21C341885 Rev. 1
,; llOlR z.N '. t,,_l C,\I ON
',, IS _i i . I
,,
2-i ,'8 ........."-
' 0 "
!
DIM "A" ,.-.-
23/i6"
Model
DIM "A" DIM "B" DIM "C" DIM "D"
(See Note 1)
*DX2BO60A9362A
17-1/2" 2-1/4" 16-1/4" 16"
*DX2BO80A9422A
*DX2C100A9482A 21" 2-1/2" 19-3/4" 19-1/2" *DX2D120A9602A 24-1/2" 2-15/16" 23-1/4" 23"
Prefix May Be "A" or "T" Notes:
1. Diameter of Vent Pipe may be limited to 2-1/2" or 3" on some models at different altitudes. Refer to the Vent Length Table for proper application.
/ _,S,'8' L C R CAL
/ (ONNIC ON AI Ei!'NA I
/
/
/ / ,_'S'/6' i( IRICA
/ CONN ?liON ,*,L ERNAIE)
/ NOC Oi
kc,,,INE_T k.
i ?5"
0 /z"
i
"--- ¢ ......s
,,,Jr ,E DA
--w u T
If ,,,,J v ,
MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS
DOWNFLOW
SIDES 0 REAR 0 I ROi' I 3 ', O[ N i I b E 0 N
HORIZONTAL (FLUE DISCHARGE ON THE LEFT)
ALCOVE
SIDES
RI iT 0 \
REAR 6 _N iRON[ 18 N
-OR N FlU 0 \
CLOSET
SIDES
[EFT ;N REAR _N FRONT _N lOP iN FI U_ i N
|
Itl
Iit
m m
I1
II
ml
I1
Page 6
Installer's Guide
UPFLOW INSTALLATION
Standoffs and screws (See Figure 1) are included with the cased coils for attachment to the furnace. There are clear-
ance alignment holes near the bottom of the coil wrapper. Drill screws are used to engage the furnace top flanges. The standoff is inserted into the cabinet alignment hole. The drill screws are inserted through the standoffs then screwed into the furnace flange. The coil is always placed downstream of
the furnace airflow.
STANDOFFS (4) DRILL SCREWS (4)
J
FOR VERTICAL
- SCREWS (BOTH BIDES)
STANDOFFS
(BOTH SIDES)
DOWNFLOW INSTALLATIONS
(_ CABINET SIDE CABINET SIDE
SUB-BASE SUB-BASE
FLANGE FLANGE
(BENT UP) (BENT UP)
DUCT
Do not install the furnace directly on carpeting, tile or other combustible material other than wood flooring. For vertical downflow application, subbase (BAYBASE205)
must be used between the furnace and combustible flooring. When the downflow furnace is installed vertically
with a cased coil, a subbase is not required.
Required floor opening: (DOWNFLOW)
See Figure 3 and Table I
TABLE 1
CABINET RETURN FLOOROPENING PLENUM OPENING
WIDTH DUCT WIDTH "A.... B.... C.... D"
14-1/2" 13-1/4" 13-5/8" 20-1/8" 12-5/8" 19-3/8" 17-1/2" 16-1/4" 16-5/8" 20-1/8" 15-5/8" 19-3/8"
21" 19-3/4" 20-1/8" 20-1/8" 19-1/8" 19-3/8"
24-1/2" 23-1/4" 23-5/8" 20-1/8" 22-5/8" 19-3/8"
HORIZONTAL INSTALLATION
The coil and furnace must be fully supported when used in the horizontal position. It is always recommended that an auxiliary drain pan be installed under a horizontally in- stalled evaporator coil or 90% gas furnace. Connect the auxiliary drain line to a separate drain line (no trap is
needed in this line). Three brackets (with screws) are included with downflow
furnaces for installation to stabilize and secure the furnace and TXC cased coil in the horizontal position. See Fig-
ure 4.
©
CASED COIL CONNECTION
BRACKET FOR DOWNFLOW
FURNACE IN HORIZONTAL
DOWNFLOW ONLY
IMPORTANT: The 2/4TXC cased coil must be placed downstream of the
furnace. In horizontal installations, the apex of the coil may point either toward or away from the furnace. See
the 2/4TXC coil Installer's Guide for more details.
The cased coil is secured to the furnace and both the furnace and the cased coil must be properly supported. The brackets
mount using the rear screws on the coil case and use the screws provided to secure the bracket to the furnace. The remaining bracket is placed as close to center as possible (horizontally) between the coil case front and the furnace
bottom channel (for downflow/horizontal furnace). Use four of the screws provided to secure the bracket. The upflow furnace,
converted to horizontal, aligns and attaches the TXC coil as in Figure 1. However, the coil requires additional support.
The furnace may be installed in an attic or crawl space in the horizontal position by placing the furnace on the left side (as viewed from the front in the vertical position). The horizontal furnace installation in an attic should be on a service plat- form large enough to allow for proper clearances on all sides and service access to the front of the furnace (See Figure 5 & Clearance Tables, pages 4-5). Line contact is only permis- sible between lines formed by intersections of the top and two sides of the furnace casing and building joists, studs, or framing.
The furnace may be placed horizontally in a crawl space on a pad or other noncombustible material which will raise the unit for sufficient protection from moisture.
@
UPFLOW/ I
HORIZONTAL I
SHOWN WITH DIRECT VENT
18-CD19D8-15
Page 7
Installer's Guide
®
[--
50 CU. FT. OR MORE
UNCONFINED
The furnace must be supported at both ends and the middle when installed horizontally. The furnace must
also be elevated approximately 4-6 inches to allow
clearance for the condensate drain to exit the cabinet in
the horizontal position.
The horizontal furnace may also be suspended from the joists using 3/8" all-thread rods with pieces of angle iron under-
neath the furnace to form a hanging rack at both ends and the midpoint. The rods need to be of sufficient length to
allow for proper clearances from combustible materials. The angle iron needs to be at least 32" in length to allow for
access to service panels.
AIR FOR COMBUSTION AND VENTILATION
If these furnaces are installed in a nondirect vent capacity then the adequate flow of combustion and ventilating air must not be obstructed from reaching the furnace. Air openings provided for combustion air must be kept free of
obstructions which restrict the flow of air. Airflow restric- tions affect the efficiency and safe operation of the furnace.
Keep this in mind should you choose to remodel or change the area which contains your furnace. Furnaces must have a free flow of air for proper performance.
Provisions for combustion and ventilation air shall be made in accordance with latest edition of Section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code,
ANSI Z223.1 -- CAN/CGA B 149.1 or applicable provisions of
the local building codes. Special conditions created by mechanical exhausting of air and fireplaces must be con- sidered to avoid unsatisfactory furnace operation.
OUTSIDE AIR IS RECOMMENDED
The use of indoor air for most applications is acceptable, unless there is the presence of corrosive chemicals or contamination. Certain types of installation will require
the use of outside air for combustion. The following types of installations will require use of
OUTDOOR AIR for combustion, due to chemical exposures:
* Commercial buildings * Buildings with indoor pools * Furnaces installed in "confined" laundry rooms * Furnaces installed in "confined" hobby or craft rooms * Furnaces installed near chemical storage areas.
Exposure to the following substances in the combustion air supply will also require OUTDOOR AIR for combustion:
* Permanent wave solutions * Chlorinated waxes and cleaners
* Chlorine based swimming pool chemicals * Water softening chemicals * Deicing salts or chemicals
* Carbon Tetrachloride * Halogen type refrigerants
* Cleaning solvents (such as perchloroethylene) * Printing inks, paint removers, varnish, etc. * Hydrochloric acid * Cements and glues * Antistatic fabric softeners for clothes dryers * Masonry acid washing materials
18-CD19D8-15 7
.....\ /
Furnace locations may be in a "confined space" or an "unconfined space".
Unconfined space is defined in Figure 6. These spaces may have adequate air by infiltration to provide air for combustion and ventilation. Buildings with tight construction (for example, weather stripping, heavily insulated, caulked, vapor
barrier, etc.), may need additional air to be provided as
described for confined space. Confined spaces are installations with less than 50 cu. ft. of
space per 1000 BTU/hr input from all equipment installed.
Air for combustion and ventilation requirements can be
supplied from inside the building as in Figure 9 or from the outdoors, as in Figure 10.
Q MINIMUM AREA IN SQUARE FEET
FOR UNCONFINED SPACE INSTALLATIONS
FURNACE WITH 8 FT. CEILING
MAXIMUM BTUH MINIMUM AREA IN SQUARE FEET
INPUT RATING OF UNCONFINED SPACE
60,000 375
80,000 500 100,000 625 120,000 875
® -I
m
m FURNAOF
CONFINED
SPACE
1.
All air from inside the building as in Figure 9: The
confined space shall be provided with two permanent openings communicating directly with an additional
room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space.
The total input of all gas utilization equipment installed in the combined space shall be considered in making this determination. Refer to Table 2 for minimum open areas requirements.
2.
All air from outdoors as in Figure 10: The confined space
shall be provided with two permanent openings, one commencing within 12 inches of the top and one com- mencing within 12 inches of the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. Refer to Table 2, for minimum open areas requirements.
MINIMUM FREE AREA IN SQUARE INCHES
EACH OPENING FURNACE ONLY)
Furnace
Maximum
BTUH/INPUT
Rating
60,000 80,000
100,000 120,000
From
Inside
LESS THAN 50 CU. FT. PER 1000 BTU/HR. INPUT
ALL EQUIP. INSTALLED
TABLE 2
Air
lOO lOO
lOO 12o
Air From Outside
Vertical
Duct
15 20
25 30
Horizontal
Duct
30 40
50 60
Page 8
iiiiiiiiiiii
Installer's Guide
®
CONFINED SPACE AIR FROM INSIDE BUILDING
CONFINED SPACE
_J
®
CONFINED SPACE AIR FROM OUTDOORS
L
CONFINED- SPACE
CONFINED SPACE k AIR FROM VENTILATED ATTIC/CRAWL SPACE
_ ATTIC LOUVERS
CONFINED - AIR SPACE
ALTERNATE INLET
INLET A_R _ AIR DUCT
PERMANENT OPENINGS
,UTLET
DOORS
DUCT CONNECTIONS
Air duct systems should be installed in accordance with standards for air conditioning systems, National Fire Protec- tion Association Pamphlet No. 90. They should be sized in accordance with ACCA Manual D or whichever is applicable.
Central furnaces, when used in connection with cooling units, shall be installed in parallel or on the upstream side of the cooling coil to avoid condensation in the heat exchanger. With a parallel flow arrangement, the dampers or other means used to control flow of air shall be adequate to prevent chilled air from entering the furnace, and if manually operated, must be equipped with means to prevent operation of either unit unless the damper is in full heat or cool position.
On any job, flexible connections of nonflammable material may be used for return air and discharge connections to prevent transmission of vibration. Though these units have been specifically designed for quiet, vibration free operation, air ducts can act as sounding boards and could, if poorly instMled, amplify the slightest vibration to the annoyance level.
When the furnace is located in a utility room adjacent to the living area, the system should be carefully designed with returns to minimize noise transmission through the return air grille. Although these furnaces are designed with large blowers operating at moderate speeds, any blower moving a high volume of air will produce audible noise which could be objectionable when the unit is located very close to a living
area. It is often advisable to route the return air ducts under the floor or through the attic. Such design permits the
installation of air return remote from the living area (i.e. central hall).
When the furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace and terminating outside the space containing the furnace.
RETURN AIR DUCT SYSTEMS
Where there is no complete return duct system, the return connection must be run full size from the
furnace to a location outside the utility room, base- ment, attic, or crawl space.
Do Not install return air through the back of the furnace
cabinet. Do Not install return air through the side of the furnace
cabinet on horizontal applications.
NOTE: Minimum return air temperature is 55 ° F.
CONFINED SPACE AIR FROM VENTILATED ATTIC
CONFINED- SPACE
INLET AIR DUCT
8 18-CD19D8-15
:LOUVERS
TO OUTDOORS
All return air duct systems should provide for installation of return air filters.
1. Set the furnace in place.
2. For upflow side return installations, remove the insula- tion around the opening in the blower compartment.
3. The side panels of the upflow furnace include locating notches that are used as guides for cutting an opening for return air, refer to Figure 11 and the outline drawing on page 4 for duct connection dimensions for
various furnaces.
NOTE: On upflow 5 ton airflow models, if the airflow requirement
exceeds 1800 CFM, these models will require return air openings and filters on both sides; OR 1side and the bottom; OR just the bottom.
Page 9
Installer's Guide
4. Ifa 3/4" flange is to be used for attaching the air inlet duct, add to cut where indicated by dotted lines in Figure 11.
Cut corners diagonally and bend outward to form flange.
5. If flanges are not required, and a filter frame is installed, cut between locating notches (Figure 11).
6. The bottom panel of the upflow furnace must be re- moved for bottom return air. Remove the filter and lay
the furnace on its back. Remove the two 1/4" hex screws securing the bottom front channel to the cabinet. Lower
the front edge of the bottom front channel and pull forward to remove the channel. The bottom return air
panel will now easily slide out of the cabinet. Reinstall the bottom front channel and filter for upflow bottom
return installations.
7. The filter retainer is factory supplied for upflow bottom return. Use the filter retainer on side or bottom if filter
is to be used within the furnace cabinet on upflow only installations.
8. The horizontal installation of the upflow furnace
requires an external filter section. Do NOT use the bottom return filter within the furnace. Filter kits are available for horizontal applications.
9. Connect duct work to furnace. See Outline Drawing for supply and return duct size and location. Flexible duct connectors are recommended to connect both supply and return air ducts to the furnace. If only the front of the furnace is accessible, it is recommended that both supply and return air plenums are removable.
NOTE: On upflow 5 ton airflow models, if the airflow requirement
exceeds 1800 CFM, these models will require return air openings and filters on both sides; OR 1 side and the bottom; OR just the bottom.
The upflow furnace blower door has a hinge at the bottom which allows the door to tilt forward for filter replacement without the door being removed (See Figure 12). The furnace filter in the bottom or side configuration can be removed by simply turning the two latches on the blower door and tilting
the door forward.
The filter rails are spring loaded for automatic adjustment to allow standard size, locally obtainable replacement filters.
The filter rack itself slides to adjust to the required width needed for bottom or side return (See Figure 13).
BOTTOM FILTER RACK INSTALLATION
With the filter removed, the filter rack is compressed and
then inserted into the bottom of the furnace. The retaining screw/pin on each side inserts into engagement holes at the
bottom of the furnace cabinet side.
RETURN AIR FILTERS (NOT SUPPLIED)
TYPICAL UPFLOW RETURN AIR FILTER INSTALLATIONS
Filters are not factory supplied for these furnaces. These furnaces require high velocity type air filters. The filters may
be located within the furnace blower compartment for UPFLOW furnaces in either a BOTTOM or SIDE (left side or
right side) return air inlet. Some filters may need to be trimmed for side or bottom filter use.
TABLE 3
MODELS CABINET FILTER
NUMBERS WIDTH QTY & SIZE
*UX2B060A9362A *UX2B080A9422A
*UX2C100A9482A 21" 1 - 20" X 25" X 1" *UX2D120A9602A 24-1/2" 1 - 24" X 25" X 1"
* Firstletter may be "A" or "T"
** NOTE - On 5 ton airflow models, if the airflow requirementexceeds
1800CFM, these models will require return air openings andfilters
on bothsides; OR 1sideand the bottom;OR just the bottom.
®
LOCATING *_ VIDED FOR SIDE
NOTCHES PRO-
RETURN CUTOUT
UPFLOW FURNACE ONLY
17-1/2" 1- 17"X25"X 1"
I
-,. I/-
I
q
4..
J
j CUT OUT FOR
SIDE FILTER
I
*- I
Blower Door Hinge and Bottom Filter Rack Installation
®
FILTER
RACK RAILS
'_ SPRINGS
AUTOMATIC
ADJUSTMENT
RETAINING
PIN
(Both Sides)
*SEE OUTLINE DRAWING _ of Furnace
"_ ,_ RONT
18-CD19D8-15 9
Optional Filter Rack Accessory Kit - BAYRACK960A
Page 10
Installer's Guide
",.: ..... ..
_ _ BOTTOM ENGAGEMENT
BlowerDeck _ II Furnace "
Engagement II " II Cabinet
Filter Rack
Retaining
Screw/Pin Filter
Rack
iiiiiiiiiiii
iiii II _ II Side
ENGAGEMENT
HOLE DETAIL
(Typical both sides
and blower deck) BLOWER EngagementHole
OPTIONAL FILTER RACK INSTALLATION FOR SIDE RE- TURN AIR ON UPFLOW FURNACES (Left or Right)
If side air return is desired, it is necessary to move the filter rack from the bottom of the furnace and reinstall it on the
side. The following instructions should be used:
a. Open or remove the blower door.
b. Remove the filter.
c. Compress the filter rack to disengage the retaining
d. Leave the bottom panel in place. e. After the side cutout is made following the directions
f. Reinstall the furnace filter on the side inserting the
!'" '_" I1..... 11 _lnstallation With_)_Bottom Return
pins/screws from the furnace sides and slide the filter rack out.
in the "Return Air Duct Connections" section on pages 8 and 9, compress the filter rack and reinstall
in the side of the furnace. Confirm that the upper retaining pin/screw locks into the engagement hole in the blower deck and the lower pin/screw rests against the side of the bottom panel. See Figures 15-19.
chamfer end first.
Engagement Hole
For Filter Rack
For Filter Rack
Installation With
Side Return
Furnace
Cabi net .,.,,)_
Side
Retaining Rack
Screw/Pin Assembly
SIDE
CUTOUT
\
®
Furnace
Cabinet
Side
Filter
Rack
RETAINING
PIN -_
Bottom Panel
Furnace Blower Deck
F
EngagementHole ForFilter Rack
InstallationWith BottomReturn
10 18-CD19D8-15
Filter Rack Retaining
Screw/Pin
(Bo_[__,
III J/ FILTER BOTTOM I I.] JJ RACK PANEL
[[I // RAILS INSTALLED I[ V/zJ Typical Upflow Left Side Return Filter
L_z/Rack Installation
Optional Filter Rack Accessory Kit - BAYRACK960A
Page 11
Typical Upflow Right Side Return Filter Rack Installation
O
Installer's Guide
BLOWER DOOR/HINGE REMOVAL
If clearance or other problems create a problem in using the tilting door, the blower door hinge may be removed without creating any problems with the seal of the furnace. To remove the blower door, tilt the door forward 2 to 3 inches and pull up. To remove the tilt feature, simply remove the lower hinge as shown in Figure 22. The bottom of the blower door will catch in the bottom of the furnace front channel for door replacement.
CHAMFER
END OF
FILTER GOES
INTO FILTER RACK FIRST
RETURN AIR FILTERS FOR UPFLOW FURNACE IN HORIZONTAL CONFIGURATION
When the Upflow Furnace is installed in the horizontal
configuration, the return air filters must be installed exterior to the cabinet. Remote filter grilles may be used for home- owner convenience or the filters may be installed in the duct work upstream of the furnace. See Figure 21.
f_
Door Hinge Removed
ALTERNATE UPFLOW FILTER CLIP / BRACKET INSTALLATION (KIT09224)
1. Determine the location to be used. The furnace cabinet has dimples for location of the alternate furnace clips
(Side return only). Pre-drill clearance holes with a 3/16" drill. Bottom return holes are pre-drilled.
2. Install the clips in front and rear of the desired location using the screws provided. The filter clip with the leaf spring mounts in the rear of the cabinet.
ALTERNATE FILTER CLIPS LOCATION
TYPICAL RETURN AIR FILTER INSTALLATION IN
UPFLOW MODEL IN HORIZONTAL POSITION
18-CD19D8-15 11
FILTER CLIP - KIT09224
Page 12
Installer's Guide
iiiiiiiiiiii
INSTALLING THE FILTER
The filter may need to be cut to fit the unit depending on the location of the return air filter.
A score line and the words "CUT HERE" are located on the end of the filter. If your application requires cutting the
filter, do so as indicted by the score mark.
UNIT
SIZE
17-1/2"
21"
24-1/2"
TYPICAL DOWNFLOW FURNACE RETURN AIR FILTER INSTALLATIONS
Two filters are factory supplied for each downflow furnace. These furnaces require high velocity type air filters. Down-
flow furnace filters must be located outside the furnace cabinet. Typical installations are shown in Figure 24.
Tables 5 and 6 provide information for installation of the filter retaining brackets shipped with downflow furnaces.
@
Optional
BAYFLTR206
Door Kit
BOTTOM
DO NOT CUT DO NOT CUT
DO NOT CUT
RETURN AIR
SIDE
DO NOT CUT
CUT ON LINE CUT ON LINE
TABLE 4
MODELS CABINET FILTER
NUMBERS WIDTH QTY & SIZE
*DX060R936
*DX080R942
*DX100R948 21" 2 - 16" X 20" X 1" *DX120R960 24-1/2" 2 - 16" X 20" X 1"
*First letter may be "A" or "T"
LOCATING FILTER RETAINER BRACKETS IN
CABINET RETURNDUCT DIMENSION DIMENSION BRACKET
WIDTH WIDTH "A .... B" LOCATION*
17-1/2" 16-1/4" 15" 14" 14-3/8"
21" 19-3/4" 19-1/2" 14" 13-1/8"
24-1/2" 23-1/4" 22" 14" 13-5/8"
* LOCATION DIMENSION IS FROM END OF DUCT AGAINST THE FURNACE TO THE
SCREW HOLES FOR THE BRACKET.
BOptiyFLnTRI06
17-1/2" 2 - 14" X 20" X 1"
TABLE 5
DUCTWORK
FILTER
p.
Airflow
DOWNFLOW
/ ow% ow;
TABLE 6
MINIMUM CLEARANCE FROM COMBUSTIBLE MATERIALS FOR
UPFLOW/HORIZONTAL AND DOWNFLOW/HORIZONTAL FURNACES
UNIT LOCATION
FURNACE SURFACE
SIDES 0" 1" 0"
BACK 0" 3" 6"
TOP 1" 1" 1"
FRONT 3" 3" 18"
VENT 0" 0" 0"
NOTE: CLEARANCE REQUIRED AT TOP OF PLENUM IS 1"
12 18-CD19D8-15
VERTICAL HORIZONTAL HORIZONTAL
CLOSET CLOSET ALCOVE / ATTIC
Page 13
Installer's Guide
I The following warning complies with State of California law, Proposition 65.
Hazardous Gases! Exposure to fuel substances or by-products of incomplete
fuel combustion is believed by the state of California to cause cancer, birth defects, or other reproductive harm.
Carbon monoxide, fire or smoke can cause serious bodily injury, death, and!or property damage.
A variety of potential sources of carbon monoxide can be
found in a building or dwelling such as gas-fired clothes dryers, gas cooking stoves, water heaters, furnaces and fireplaces. The U.S. Consumer Product Safety Commission recommends that users of gas-burning appliances install
carbon monoxide detectors as well as fire and smoke detec- tors per the manufacturer's installation instructions to help
alert dwelling occupants of the presence of fire, smoke or unsafe levels of carbon monoxide. These devices should be
listed by Underwriters Laboratories, Inc. Standards fbr
Single and Multiple Station Carbon Monoxide Alarms,
UL 2034 or CSA International Standard, Residential Carbon Monoxide Alarming Devices, CSA 6.19
NOTE:
The manufacturer of your furnace does not test any detec-
tors and makes no representations regarding any brand or type of detector.
GENERAL VENTING
THIS FURNACE MUST BE VENTED TO THE OUTDOORS. THESE FURNACES ARE INDUCED DRAFT VENTED
AND MUST NOT BE CONNECTED TO ANY VENT SERV-
ING ANOTHER APPLIANCE. PLEASE NOTE THAT THESE FURNACES USE POSITIVE-PRESSURE VENT SYSTEMS.
Proper venting is essential to obtain maximum efficiency from a condensing furnace. Proper installation of the vent system is necessary to assure drainage of the condensate and prevent deterioration of the vent system.
American Gas Association has certified the design of con-
densing furnaces for a minimum of 0" clearance from com-
bustible materials with a single wall plastic vent pipe.
The recommended system is assembled from 2", 2-1/2", or 3" plastic pipe and fittings (See Table 7, page 15). Where the system is routed to the outdoors through an existing masonry chimney containing flue products from another gas appliance, or where required by local codes, then 3" venting of Type 29-4C stainless steel must be used in place of PVC material.
These furnaces have been classified as CATEGORY IV furnaces in accordance with ANSI Z21.47 "latest edition"
standards. Category IV furnaces operate with positive vent pressure and with a vent gas temperature less than 140 ° F. above the dewpoint. These conditions require special venting systems, which must be gas tight and water tight.
NOTE:
When an existing furnace is removed from a venting
system serving other gas appliances, the venting system is likely to be too large to properly vent the remaining attached appliances.
The following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion or other deficiencies which
could cause an unsafe condition.
3. Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliances not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan, close fireplace dampers.
4. Follow the lighting instructions. Place the appliance
being inspected in operation. Adjust thermostat so
appliance will operate continuously.
5. After it has been determined that each appliance remain- ing connected to the common venting system properly vents when tested as outlined above, return door, win- dows, exhaust fans, fireplace dampers and any other gas-
burning appliance to their previous conditions of use.
If improper venting is observed during any of the above tests, the remaining common venting system must be corrected. Correction could require rerouting or resizing the remaining vent system.
IMPORTANT:
These furnaces may be installed as Direct Vent (sealed com- bustion) or as Nondirect vent (single pipe). The furnaces are shipped DIRECT VENT with sealed combustion.
For DIRECT VENT APPLICATION: The furnaces must be
vented to the exterior of the house and combustion air MUST come through the inlet air pipe FROM OUTSIDE AIR. The pipes
DO NOT have to exit the exterior of the house together or on the same side of the house.
For NONDIRECT VENT APPLICATION: The furnace shall be
vented to the exterior of the house, but combustion air may enter from the surrounding area as long as combustion air requirements are met. (See AIR FOR COMBUSTION AND
VENTILATION)
FURNACE VENT/INLET PIPE INSTALLATION
There are many different variations of the vent/inlet air pipe combination. The vent/inlet air combination used for instal-
lation of these furnaces depends on the needs of the location. However, these guidelines must be followed:
1. The furnace must vent outside the structure.
2. Furnace combustion air requirements must be met for nondirect, single pipe applications (See example on next page).
3. For direct vent application of these furnaces, the vent pipe and air inlet pipe do not have to exit in the same air
space or even on the same surface of the structure.
However, the longest individual pipe will decide the value fbr the longest allowable equivalent vent/inlet air length
as shown in the vent length table.
18-CD19D8-15 13
Page 14
Installer's Guide
NOTE: BAYVENT200* accessories can be used for inlet and outlet
terminals when the pipes do not exit the structure together.
The following are EXAMPLES ONLY:
EX. 1 --
Example 1 shows that the vent may go vertical while the inlet air may be on any side of the structure. The vent pipe would decide the maximum equivalent length for the pipe depending on the furnace and pipe size.
Vent
Air
Inlet =_ Furnace
EX. 2 --
Example 2 shows the vent pipe exhausting through the roof and the inlet air coming from the interior of the house (See Note). The inlet air coming from the interior of the house must meet combustion requirements for area, etc., as shown
in the section AIR FOR COMBUSTION AND VENTILA- TION in this Installer's Guide.
Air_ _ Vent
Inlet_
(See Note)
EX. 4--
The inlet air does not have to come from outside the structure. Example 4 shows the inlet air (See Note), may come from the
attic if the requirements for combustion air are met as shown in the section AIR FOR COMBUSTION AND VENTILATION.
Attic
Vent
_(Soe Note)
FurnaceL
NOTE: ff only the flue gas pipe is to the outside of the structure, a
straight section of pipe (long enough to exit the furnace cabinet) must be attached to the inlet air side with an elbow (which is 5 to 10 equiv, ft.) installed on the end to prevent dust and debris from falling directly into the furnace.
VENT FITTING MATERIAL - PLASTIC
Gas and liquid tight single wall vent fittings, designed for resistance to corrosive flue condensate, MUST be used throughout.
Listed in Table 7 are 2", 2-1/2", and 3" size fittings that meet these requirements. The materials listed are various grades of PVC and ABS plastic.
PIPE JOINTS: All joints must be fastened and sealed to prevent escape of combustion products into the building.
NOTE: It is recommended that the first joints from the furnace be
connected and sealed with high temperature RTV. This will enable the pipes to be removed later without cutting.
EX. 3 --
Example 3 shows the vent exiting one side of the house while the inlet air is on the opposite side of the structure. Here the vent pipe length must be within the allowable length for the size of furnace and size of the vent pipe. This example demonstrates that the pipes do not have to exit on the same
side of the structure.
Air
Inlet
=_ Furnace
14 18-CD19D8-15
Vent
Be sure to properly support these joints.
BONDING OF PVC
Commercially available solvent cement for PVC must be used to join PVC pipe fittings. Follow instructions on con- tainer carefully.
Pipe and Fitting -ASTM D1785, D2466, D2661, & D2665 PVC Primer and Solvent Cement - ASTM D2564
Procedure for Cementing Joints - RefASTM D2855
1. Cut pipe square, remove ragged edges and burrs. Chamfer end of pipe, then clean fitting socket and pipe
joint area of all dirt, grease, moisture or chips.
2. After checking pipe and socket for proper fit, wipe socket and pipe with cleaner-primer. Apply a liberal coat of primer to inside surface of socket and outside of pipe.
DO NOT ALLOW PRIMER TO DRY BEFORE APPLY- ING CEMENT.
3. Apply a thin coat of cement evenly in the socket. Quickly apply a heavy coat of cement to the pipe end and insert pipe into fitting with a slight twisting movement until it
bottoms out.
Page 15
Installer's Guide
4. Hold the pipe in the fitting for 30 seconds to prevent tapered socket from pushing the pipe out of the fitting.
5. Wipe all excess cement from the joint with a rag. Allow
NOTE: Follow venting instructions carefully when using PVC
cemenL
15 minutes before handling. Cure time varies according
to fit, temperature and humidity.
IMPORTANT:
All joints must be water tight. Flue condensate is somewhat acidic, and leaks can cause equipment damage.
TABLE 7
PVC VENT FITTING MATERIAL These fittings are available from your Gas Furnace Distributors.
q
1-518"
[
i_ 4-1/2"
WALL MOUNT FLANGE
BAY69X 148
PLASTIC PIPE DESIGNATIONS
PVC
ASTM STANDARD PIPE TYPE ALLOWABLE TEMPERATURE MARKING
F891 CELLULAR CORE "158 ASTM F891
D2665 DWV PIPE *'158 ASTM D2665
D1785 SCH 40, 80, 120 *'158 ASTM D1785
D2241 SDR SERIES *'158 ASTM D2241
CPVC
ASTM STANDARD PIPE TYPE ALLOWABLE TEMPERATURE MARKING
D2846 CPVC 41 *'212 ASTM D2846
F441 SCH 40, 80 *'212 ASTM F441 F442 SDR SERIES *'212 ASTM F442
ABS
ASTM STANDARD PIPE TYPE ALLOWABLE TEMPERATURE MARKING
D2661 SCH 40 DWV **'180 ASTM D2661
F628 SCH 40 DWV CELLULAR CORE **'180 ASTM F628
* - Allowable temperatures based on classifications covered in ASTM D4396 [Deflection Temps Under Load (264 PSI)] ** - Allowable temperatures based on classifications covered in ASTM D1784 [Deflection Temps Under Load (264 PSI)]
*** - Allowable temperatures based on classifications covered in ASTM D3965 [Deflection Temps Under Load (264 PSI)]
2-3/16"
_----- 5-5/8"
WALL MOUNT FLANGE
BAY69X 147
Connection of the pipe and collar of the combustion air inlet should just be a friction fit. It is recommended that the inlet air joint be sealed with RTV type sealant to allow the joint to
be separated for possible future service. The inlet and vent
pipes must be properly supported throughout the entire length.
Connection of the vent pipe to the vent collar should also be accomplished using RTV type sealant. This type sealant provides a connection which remains flexible and can be separated in the future if service needs require the removal of the vent pipe for service or clearance.
NOTE:
Vent termination kit BAYAIR3OAVENTA or BAYVENT2OOB
may be used in addition to the horizontal and vertical termination options shown in the following figures.
18-CD19D8-15 15
(_ VENT AND INLET AIR CONNECTIONS
Seal VENT PIPE
withRTV sealant
Front of Furnace
Seal INLET AIR PIPE
with RTV sealant
Page 16
Installer's Guide
VENT LENGTH TABLE
iiiiiiiiiiii
ALTITUDE MAXIMUM TOTAL EQUIVALENT LENGTH IN FEET
0-7,000 Feet 2 INCH PIPE 2.5 INCH PIPE 3 or 4 INCH PIPE
UX2/DX2B060A9362A 200 200 200 UX2/DX2B080A9422A 50 120 200 UX2/DX2C100A9482A Not Allowed 60 200 UX2/DX2D120A9602A Not Allowed Not Allowed 200
7,000-9,500 Feet 2 INCH PIPE 2.5 INCH PIPE 3 or 4 INCH PIPE
UX2/DX2B060A9362A 100 100 100 UX2/DX2B080A9422A 25 60 100 UX2/DX2C100A9482A Not Allowed 30 100 UX2/DX2D120A9602A Not Allowed Not Allowed 100
9,500-12,000 Feet 2 INCH PIPE 2.5 INCH PIPE 3 or 4 INCH PIPE
UX2/DX2B060A9362A 50 50 50 UX2/DX2B080A9422A Not Allowed 30 50 UX2/DX2C100A9482A Not Allowed Not Allowed 50
UX2/DX2D120A9602A Not Allowed Not Allowed 50
NOTES: * - First letter may be "A" or "T"
1. Minimum vent length for all models: 3' horizontal or 3' vertical.
2. DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET (Except adapters at the top of the furnace). If different inlet and vent pipe sizes are used, the vent pipe must adhere to the
maximum length limit shown in the table above (See note 6 below for exception). The inlet pipe can be of a larger diameter, but never smaller than the vent pipe.
3. MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED! THE LENGTH SHOWN IS NOT A COMBINED TOTAL, IT IS THE MAXIMUM LENGTH OF EACH (Vent or Inlet air pipes).
4. One SHORT radius 90° elbow is equivalent to 10' of 3" pipe and one LONG radius elbow is equivalent to 6' of 3" pipe. One 90° elbow is equivalent to 71/2' of 21/2'' pipe or 5' of 2" pipe. Two 45° elbows equal one 90°elbow.
5. The termination tee or bend must be included in the total number of elbows. If the BAYAIR30AVENTA termination kit is used, the equivalent length of pipe is 5 feet. BAYVENT200B equivalent length is 0 feet.
6. Pipe adapters are field supplied (except 120).
FOR VENT AND INLET AIR (SEE NOTES)
HORIZONTAL INSTALLATION (Upflow/Horizontal or Downflow/Horizontal)
NOTE: In horizontal venting when the factory supplied "off-set" (2)(3
reducing coupling) is used for 3" vent pipe installation, make sure the marking "Top" is located on the top side of the pipe.
The straight side must be on bottom for proper condensate
drainage. This coupling is factory supplied only with the
followinomodels: UC120 & DC120. UX120 & UY120
UXIO0 _ UYIO0, UX808C960, and all DX & DY models.
LABEL
SAYS
\\\\\
"TOP"
2" _' COUPLING
FACTORY SUPPLIED ONLY WITH
THE FOLLOWING MODELS:
UC120 & DC120 UX120 & UY120
UX100 & UY100 UX080C960
ALL DX & DY MODLES
16 18-CD19D8-15
VENT OUTLET
Page 17
G
Installer's Guide
ELBOW AND TEE MUST BE AS CLOSE TOGETHER AS POSSIBLE
iiiiliiiiii;iiiiiiliiliiliiliiliiliiliiliiliiliilli!ii¸
@
40" UPFLOW OR DOWNFLOW MODELS
COMBUSTION AIR INLET
n
POSSIBLE CONFIGURATIONS FOR TWO PIPE VENTING SYSTEMS
NOTE: VENT AND INL ET MUS T BE SUPPOR TED
SEE VENTING TABLE
STRAPS OR OTHER SUITABLE SUPPORTS AT MAXIMUM OF 3'-0" INTERVALS
UPWARD PITCH -- 1/4" PER FOOT FIRST SUPPORT SHOULD BE AS
CLOSE TO FURNACE CONNECTION AS POSSIBLE.
NOTE:ANY FITTINGS PASSING
THROUGH AN UNHEATED SPACE
MUST BEINSULATED.
45° ELBOW
USE ONLY
APPROVED STRAP
TERMINATION (FIELDSUPPLIED)
--) / VENT X
OUTSIDE I 1"_+1/2"
WALL
A T A MAXIMUM OF 3' INTER VALS
COMBUSTION AIR
BAYAIR3OAVENTA
ELBOW (FIELD
SUPPLIED)
COMBUSTION AIR
L
RAIN CAI
OUTSIDE
WALL
STUB CUT AT
45 °ANGLE
18-CD19D8-15 17
Page 18
Installer's Guide
®
//
VENT CAP
MAINTAIN 12" (18" FOR CANADA) MINIMUM
CLEARANCE ABOVE HIGHEST ANTICIPATED
SNOW LEVEL OR GRADE WHICHEVER IS GREATER
BAYVENT200B
12"MINIMUM
TO OVERHANG
COUPLING
®
( 1" ACCEPTABLE FOR TYPE 29-4C STAINLESS STEEL VENT PIPE )
( PLASTIC
1" CLEARANCE SNOW ACCUMULATION (AIR SPACE )
VENTINGTHROUGH COMBUSTIBLEWALLS
CLEARANCE (0" ACCEPTABLE FOR PVC VENT PIPE )
COUPLING
( PLASTIC
VENTING ) /
14 61N. MIN. I_--
j lj(TOJOINT)_
_'_ PVC WALL
STU r I MOUNT FLANGE
II / APPROVED
NORMALLY EXPECTED
Pitch-- 1/4Inch PerFL
PVC WALL
MOUNT FLANGE
IOPTIONAL)
APPROVED
/
TERMINATION
TERMINATION
/
M_
12" MIN. ABOVE
BAYAIR30AVENTA
NORMALLY EXPECTED SNOW ACCUMULATION
(Sidewall)
When the vent pipe is exposed to temperatures below freezing, i.e., when it passes through unheated spaces, etc., the pipe must be insulated with 112 inch (22.7 mm) thick Armaflex-type insulation or equal.
If the space is heated sufficiently to prevent freezing, then the insulation would not be required. If domestic water pipes are not protected from freezing then it is assumed the space meets the condition of a heated space.
HORIZONTAL VENTING THROUGH WALL
These furnaces may be installed as direct vent (as shipped) or as nondirect vent. Installation must
conform to national, state, and local codes. The vent & inlet terminals must be located at least 12"
minimum above normally expected snow accumulation level. Avoid areas where staining or condensate drippage may be
a problem. Location of the vent/wind terminal should be chosen to meet the requirements of Figure 39 for either direct or nondirect
vent applications. PITCH -- Venting through the wall must maintain 1/4" per
foot pitched upward to insure that condensate drains back to the furnace.
FLUE GAS DEGRADATION -- The moisture content of the flue gas may have a detrimental effect on some building
18 18-CD19D8-15
VENTING THROUGH NON-COMBUSTIBLE WALLS
Pitch- 1/4 Inch PerFt.
materials. This can be avoided by using the roof or chimney venting option. When wall venting is used on any surface that
can be affected by this moisture, it is recommended that a corrosion resistant shield (24 inches square) be used behind
the vent terminal. This shield can be wood, plastic, sheet metal, etc. Also, silicone caulk all cracks, seams and joints
within 3 feet of the vent terminal.
COMBUSTIBLE MATERIAL WALL
A minimum clearance of 1" to combustible materials must be maintained when using single wall stainless steel venting. See Figure 31.
Shield material to be a minimum of 24 gauge stainless or aluminized sheet metal. Minimum dimensions are 12"x12".
Shield must be fastened to both inside and outside of wall. Use screws or anchor type fasteners suited to the outside or
inside wall surfaces.
NONCOMBUSTIBLE MATERIAL WALL
The hole through the wall must be large enough to maintain pitch of vent and properly seal.
Use cement mortar seal on inside and outside of wall. See Figure 32.
Page 19
Installer's Guide
@
®
SUPPORT HORIZONTAL PIPE EVERY 3' 0" WITH THE FIRST SUPPORTAS CLOSE TO THE FURNACE AS POSSIBLE. INDUCED
DRAFT BLOWER, HOUSING, AND
WEIGHT OF THE FLUE PIPE.
FURNACE MUST NOT SUPPORT THE {_ {_ I_ I_
__ | _-I PITCH - t $4" PER FOOT
40" UPFLOVV OR.DO".rv_FLOW FURNACE
HORIZONTAL AND VERTICAL
REMOVE RIBS FROM
VERTICAL
VENT
DISTANCE FROM TOP OF VENT TO BO1TOM OF AIR INLET MUST I
REMOVE RIBS ,_ FROM CAP
COMBUSTION
ROOF BOOT
(FIELD SUPPLIED)
AIR
VENT"_
12' :t I"_
9" MIN.
_ 12-INCH CLEAr4ANCE MUST BEMAINTAINED ABOVE HIGHEST / I I _ MAXIMUM NOT TO EXCEED
COMBUSTION AIR INLET
VENT
AN_C!PATED SNOW LEVEL 24 INCHES ABOVE ROOF,
MAINTAIN 12 IN. (18 IN. FOR CANADA)
MINIMUM CLEARANCE
ANTICIPATED SNOW LEVEL. MAXIMUM OF
_ ABOVE HIGHEST
24 IN. ABOVE ROOF
suP
(FIELD SUPPLIED)
MAINTAIN 12 IN. (18 IN. FOR CANADA)
ABOVE HIGHEST ANTICIPATED SNOW
LEVEL. MAXIMUM OF
24 IN. ABOVE ROOF.
_ SEAL BETWEEN FLANGE, PIPE,
COUPLING AND METAL PANEL WITH HI TEMP RTV SILICONE SEALANT
SUPPORT
FLANGE
PIPE
COUPLING
BAYAIR30AVENTA (VERTICAL)
18-CD19D8-15 19
ELBOW
(FIELD SUPPLIED)
COMBUSTION
AIR
GALVANIZED FIRESTOP SHOULD BE FABRICATED WITH 3-7/8" DIA.
HOLE FOR SUPPORT FLANGE (12" x 12" PANEL OR 12" DIA MIN.)
CLEARANCE (0" ACCEPTABLE FOR PVC VENT PIPE)
( 1 " ACCEPTABLE FOR TYPE 29-4C STAINLESS STEEL VENT PIPE )
CEILING
VENTING THROUGH CEILING
Page 20
Installer's Guide
VENTING THROUGH THE ROOF When penetrating roof with a 2" PVC vent pipe, a 2" electrical
conduit flashing may be used for a weather tight seal. Lubricate flexible seal on flashing before PVC pipe is pushed through the seal. (Field Supplied)
NOTE: No vent cap as shown in Figure 34 is the preferred method
for vertical vent termination in extremely cold climates.
In extreme climate conditions, insulate the exposed pipe above the roof line with Armaflex type insulation.
VENT FITTING MATERIAL - STAINLESS STEEL
Gas and liquid tight single wall metal vent fitting, designed for resistance to corrosive flue condensate such as Type 29-4C MUST be used throughout.
These fittings and fitting accessories are to be supplied locally.
DIRECTION OF STAINLESS STEEL FITTING
Allstainlesssteelfittingmustbeinstalledwithmaleend
towards the furnace.
................................................................................All horizontal stainless steel sections must be positioned
with the seam on top. All long horizontal sections must be supported to prevent
sagging. All pipe joints must be fastened and sealed to prevent escape
of combustion products into the building.
®
FLUE PIPE
COUPLING TO SUPPORT PIPE FROM ANGLES OR OTHER SUITABLE SUPPORT METHOD
PVC PLASTIC VENTING - ONLY
THROUGH UNUSED CHIMNEY
STAINLESS STEEL
VENT CAP
6 IN. MIN.
FLUE PIPE
SUPPORT THE SINGLE WALL FLUE PIPE AND CENTER IT IN THE CHIMNEY OPENING WITH ANGLES AS SHOWN OR ANOTHER EQUIVALENT MANNER.
COUPLING
AS REQUIRED
®
(1"ACCEPTABLE FOR TYPE29-4C STAINLESS STEELVENT PIPE)
SEAL BETWEEN FLANGE, PIPE,
COUPLING AND METAL PANEL
WITH HI TEMP RTV SILICONE SEALANT
SUPPORT _
FLANGE
FLOOR
(0"ACCEPTABLE FOR PVC VENT PIPE)
CLEARANCE
COUPLING
GALVANIZED PANEL (FIRESTOP)
/
FLUE PIPE
TYPE 29-4C STAINLESS STEEL VENTING -
USED THROUGH CHIMNEY THAT VENTS
ANOTHER GAS APPLIANCE
STAINLESS STEEL
VENT CAP
(OPTIONAL)
SEE CAUTION 6 IN. MIN.
SUPPORT THE SINGLE WALL STAINLESS STEEL GAS
VENTING AND CENTER IT IN
THE CHIMNEY OPENING WITH ANGLES AS SHOWN OR
ANOTHER EQUIVALENT MANNER.
NOTE: HORIZONTALVENTING
TO VERTICAL VENTING
NOTE: HORIZONTALVENTING
TO VERTICALVENTING
Do not run vent through chimney for wood burning or
oil furnaces or incinerators or any other gas appliance.
IMPORTANT-
The single wall flue pipe joints must be sealed. The 90° elbow connection to vertical pipe must be sealed to
prevent condensate leakage to base of masonry chimney.
VENTING ROUTED THROUGH A MASONRY CHIMNEY
20 18-CD19D8-15
Do not run vent through chimney for wood burning or oil
furnaces or incinerators.
If remaining free area between single wall flue pipe and masonry chimney is to be used for another gas appliance
venting area must be sufficient to vent that appliance and that appliance must be connected to chimney with separate entry openings.
IMPORTANT-
The single wall flue pipe joints must be sealed. The 90 ° elbow connection to vertical pipe must be sealed to
prevent condensate leakage to base of masonry chimney.
Page 21
Installer's Guide
®
HORIZONTAL VENT CLEARANCES
INSIDE
CORNER DETAIL
FV'] VENTTERMINAL (_) AIR SUPPLY INLET [] AREAWHERE TERMINAL IS NOT PERMITTED
Non-Direct Vent Terminal Clearances
Canadian Installations US Installations
Clearance above grade, veranda, porch, deck, or
A= balcony 12 inches (30 cm) 12 inches (30 cm)
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw),
B= Clearance to window or door that may be opened 12 inches (30 cm) for appliances > 10,000 Btuh (3 kw) 4 feet (1.2m) below or to the side of opening;
C= Clearance to permanently closed window
Vertical clearance to ventilated soffit located above
D= the terminal within a horizontal distance of 2 feet
(61 cm) from the center line of the terminal
E= Clearance to unventilated soffit
F= Clearance to outside corner
G= Clearance to inside corner
Clearance to each side of center line extended 3 feet (91 cm) with a height 15 feet (4.5 m) above the
H=
above meter/regulator assembly meter/regulator assembly
I= Clearance to service regulator vent outlet 3 feet (91 cm)
Clearance to nonmechanical air supply inlet to 6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw),
J= building or the combustion air inlet to any other 12 inches (30 cm) for appliances > 10,000 Btuh (3 kw) 4 feet (1.2 m) below or to side of opening;
appliance 36 inches (91 cm) for appliances > 100,000 Btuh (30 kw)
K= Clearance to a mechanical air supply inlet 6 feet (1.83m) 3 feet (91 cm) above if within
Clearance above a paved sidewalk or paved 7 feet (2.13 m) 1 7 feet (2.13 m)
L= driveway located on public property
M= Clearance under veranda, porch, deck, or balcony 12 inches (30 cm) Notes:
1. In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code.
2. In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code.
1. A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwelling and serves both dwellings. :l:. Pemitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's Installation Instructions.
and =/< 100,000 Btuh (30 kw), 1 foot (0.3m) above opening. 36 inches (91 cm) for appliances > 100,000 Btuh (30 kw)
and =/< 100,000 Btuh (30 kw), 1 foot (300 m) above opening
10 feet (3m) horizontally
18-CD19D8-15 21
Page 22
iiiiiiiiiiiii
iiiiiiiiiiii
Installer's Guide
Direct Vent Terminal Clearances
Canadian Installations US Installations
Clearance above grade, veranda, porch,
A= deck, or balcony 12 inches (30 cm) 12 inches (30 cm)
B= Clearance to window or door that may be 12 inches (30 cm) for appliances > 10,000 Btuh (3 kw) 9 inches (23 cm) for appliances > 10,000 Btuh (3 kw)
opened and =/< 100,000 Btuh (30 kw), and =/< 50,000 Btuh (15 kw),
C= Clearance to permanently closed window
Vertical clearance to ventilated soffit located above the terminal within a
D=
horizontal distance of 2 feet (61 cm) from the center line of the terminal
E= Clearance to unventilated soffit
F= Clearance to outside corner
G= Clearance to inside corner
Clearance to each side of center line 3 feet (91 cm) with a height 15 feet (4.5 m) above the
H=
extended above meter/regulator assembly meter/regulator assembly
I= Clearance to service regulator vent outlet 3 feet (91 cm)
Clearance to nonmechanical air supply 6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw),
J= inlet to building or the combustion air and =/< 100,000 Btuh (30 kw), and =/< 50,000 Btuh (15 kw),
inlet to any other appliance 36 inches (91 cm) for appliances > 100,000 Btuh (30 kw) 12 inches (30 cm) for appliances > 50,000 Btuh (15 kw)
K= Clearance to a mechanical air supply inlet 6 feet (1.83m) 3 feet (91 cm) above if within 10 feet (3m) horizontally
Clearance above a paved sidewalk or
L= paved driveway located on public property 7 feet (2.13 m) l-
M= Clearance under veranda, porch, deck, 12 inches (30 cm) :l:
or balcony
Notes:
1. In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code.
2. In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code.
1-. A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwelling and serves both dwellings. :l:. Pemitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
* Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's Installation Instructions.
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw),
36 inches (91 cm) for appliances > 100,000 Btuh (30 kw) 12 inches (30 cm) for appliances > 50,000 Btuh (15 kw)
12 inches (30 cm) for appliances > 10,000 Btuh (3 kw) 9 inches (23 cm) for appliances > 10,000 Btuh (3 kw)
@
DOWNWARD VENTING
f
Furnace may be in vertical or horizontal configurat_
All horizontal pipes must be
supported at maximum of 3
foot intervals
Slope 1/4" per ft. \ II
Slope 1/4" per ft.
NOTES:
A) Condensate trap for vent pipe must be a minimum of 6 inches in height.
B) Condensate trap for vent and inlet pipe must be connected into a condensate drain pump; an open or
vented drain; or it can be connected to the outlet hose of the furnace's condensate trap. Outdoor drain- ing of the furnace and coil condensate is permissible if allowed by local codes. Caution should be taken
to prevent drains from freezing or causing slippery conditions that could lead to personal injury. Exces- sive draining of condensate may cause saturated ground conditions that may result in damage to plants.
c) The condensate trap should be primed at initial start up prior to heating season operation.
r
I I
DOWNWARD VENT LENGTH IS
LIMITED TO A MAXIMUM OF 15
S EQUIVALENT FEET.
SEE __ Upflow or NOTES Downflow
J
6" Min.
.._!._
40 Inch
Furnace
22 18-CD19D8-15
Page 23
Installer's Guide
IMPORTANT:
The Commonwealth of Massachusetts requires compliance with regulation 248 CMR 4.00 and 5.00 for installation of through - the - wall vented gas appliances as follows:
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall
horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back- up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard
wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or
structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon
monoxide detectors a. In the event that the side wall horizontally vented
gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent
floor level.
b. In the event that the requirements of this
subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be
installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required
in accordance with the above provisions shall comply with NFPA 720 and be ANSI!UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the
building at a minimum height of eight (8) feet above grade
directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY
BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4. This appliance requires a special venting system. If BAYAIR30AVENTA or BAYVENT200B are used, a copy of
the installation instructions for the kit shall remain with the appliance or equipment at the completion of
installation. The venting system installation instructions can be obtained from the manufacturer by writing to the following address:
American Standard, Inc.
6200 Troup Highway Tyler, TX 75707
Attention: Manager of Field Operations Excellence
IMPORTANT: Products installed in Canada must use vent systems that
are certified to the Standard for Type BH Gas Venting Sys- tems (ULC $636) for Class II-A venting systems (up to
65°C). Components of the vent system must not be inter- changed with other vent systems or unlisted pipe or fittings.
Plastic components, specified primers, and glues must be from a single system manufacturer and not intermixed with other system manufacturer's vent system parts. In addi- tion, the first three feet of the vent pipe must be visible for inspection.
18-CD19D8-15 23
Page 24
Installer's Guide
CONDENSATE DRAIN INSTRUCTIONS
IV!_ [q:la//[e] _I
It is recommended that a drain pan be installed under the furnace to prevent property damage, personal injury or death from leaking condensate.
VERTICAL APPLICATIONS Upflow furnace - The connection tubing for left and right
side drainage is shipped in the blower compartment. Install the connection tubing from the trap to the side of the unit and trim all excess tubing to avoid ldnks.
Downflow furnace - The furnace is shipped with the left side drainage setup. To change the right side drain, remove the drain lines from the trap, rotate the trap 180 ° so it exits to the right, reconnect the lines, and run a 1/2" CPVC pipe from the trap out through the right side knock-out. Use RTV silicone sealant to connect the CPVC pipe to the trap for ease of removing to clean the trap.
UPFLOW (VERTICAL)
Left side
Right side
UPFLOW (VERTICAL)
Use
extension hose here
Use Inducer Drain
hose without
extension
UPFLOW HORIZONTAL 17" UNITS
(Left side only)
24 18-CD19D8-15
UPFLOW HORIZONTAL 21" & 24" UNITS
(Left side only)
Page 25
HORIZONTAL APPLICATIONS
Upflow and Downflow furnaces - All horizontal applica- tions are left side only. It is always recommended that the auxiliary drain pan be installed under a horizontally in- stalled evaporator and/or 90% gas furnace. Connect the auxiliary drain pan to a separate drain line (no trap is needed
in this line).
The trap must be repositioned to the exterior of the cabinet. Remove the trap from its present location and reposition the trap outside of the unit, through the long circular hole, next to the secondary recuperative cell. Remove the larger &'ain line (from the secondary cell) and trim to fit between the second- ary cell and the new trap location. On upflow units, plug the hole in the blower deck where the tube went through.
DOWNFLOW (VERTICAL)
i
Installer's Guide
Cut off curved end of
Inducer drain hose
DOWNFLOW (HORIZONTAL)
Remove the hose from the induced blower and reposition into the other &'ain tap of the inducer, which is located 90 ° clockwise around the inducer. Move the cap from that &'ain tap to the unused drain tap. On upflow units, plug the hole in the blower deck where the tube went through. This tube on
downflow units will need to be cut to fit between the inducer and the trap. On upflow units, this tube may need to be
extended, using the tubing shipped with the furnace. Connections must be made to an OPEN/VENTED DRAIN. Outdoor draining of the furnace and coil condensate is
permissible if allowed by local codes. Caution should be taken to prevent drains from freezing or causing slippery conditions that could lead to personal injury. Excessive draining of condensate may cause saturated ground conditions that may result in damage to plants.
NOTE:
Use 1/2" or larger PVC or CPVC pipe and fittings as required
for drain connections (fittings, pipe and solvent cement not
provided).
NOTE: A corrosion resistant condensate pump must be used ifa
pump is required for a specific drain system.
Use CPVC tubing from Trap outlet,
over burner box to cabinet exit
DOWNFLOW (VERTICAL)
18-CD19D8-15 25
Right
side
IMPORTANT:
The condensate drain should be installed with provisions to prevent winter freeze-up of the condensate drain line. Frozen condensate will block drains, resulting in furnace shutdown, ff the drain line cannot be installed in a conditioned space, then
UL listed heat tape should be applied as required to prevent freezing (per manufacturer's instructions). The heat tape should be rated at 5 or 6 watts per foot at 120 volts. Self-regulating (preferred) or thermostatically controlled heat tape is required.
Evaporator and furnace condensate drain piping may be manifolded together. A primary drain vent stack must be installed and terminated below the outlet of the secondary heat exchanger drain connection to prevent water from damaging furnace controls if the primary drain outlet plugs up. Where the furnace is installed above a finished ceiling, the primary drain vent stack must be installed such that overflow from the vent stack opening will flow into an axillary drain pan in order to prevent water damage to the finished ceiling below.
Page 26
Installer's Guide
If upflow furnace is installed over a finished ceiling, overflow
from the primary drain vent stack must flow into an auxiliary drain pan to prevent damage to the finished ceiling below,
Primary drain vent stack must terminate below
secondary heat exchanger condensate drain outlet,
To drain opening
",,,
FIELD WIRING DIAGRAM FOR 2 STAGE FURNACE
SEE
NOTE 7
2STAGE
FURNACE
L
[]
T"STAT
[]
[]
SEE
NOTE 8
[] []
[]
1 TER COMPO[ENT ,,MIRI G
24 V. "L FIELD
---- L ]NE v. _* M_'I_ [NG 24 V. _ FA;T{ _Y
-- L ]NE /.#>" 'A,'IR [MG
SEE
NOTE 6
[]
_]-_
[]
USING A 1 STAGE HEATING THERMOSTAT
,4
1 STAGE HEATING
NO COOLING
NOTES:
I BE SURE POWER AGREES WITH EOglPMENT NAMPLATE(S)
2 LOW VOLTAGE (24V AIRING) TO BE NO 18 AW G MIN 3 GROUNDING OF EQUIPMENT MUST COMPLY WITH LOCAL CODES
SET THERMOSTAT HE_T ¢_TI_IPATOR PER UNIT AIRING DIAGR&M
: THESE LEADS PNOVIDE ,,yS ' ROWER FOR CO_'iMECTION OF ELECTRONIC AIR
CLEANER AND HUMIDIFIER MAX LOAD I0 AMPS EACH
6 THIS CONNECTION IS ONLY USED FOR THERMOSTATS REOUIRIMG
CONNECTION TO THE 24 V POWER SUPPLY (COMMAN)
7 SEE TWINNING CONNEDTION DIAGRAMS FOR PROPER CONNECTIONS
WHEX USING THIS FEATURE
8 WHEN A HEATING THERMOSTAT (WITHOUT FAN SWITCH) IS USED,
NO WIRING ON "G" TERMINAL OF IFD IS USED
9 AI _NI} A2 MilST BE JUM_ERED TOGETHER FOR _ROPER OPERATION
SECOND STAGE HEATING AILL BEGIN I0 MINUTES AFTER FIRST STAGE
_FIELD ADDED JUMPER GROU N D
WlTOW2. \SCREW
{
T'STAT
SEE
NOTE 7
2 STAGE
FURNACE
-D
E]
Fq
Pq
D D
FS
SEE
NOTE 6
D
INTER CII,!f:C ENT ',A"IF_]N("
24 V'. -L_ FIELD
----LINE ,/.j,/WIRI[ G
2 'M'. _, FACT Ow, Y
-- LINE ',,'. _,
Fq @
Fq
'_'11_I O
FIELD WIRING DIAGRAM FOR 2 STAGE FURNACE
2 STAGE HEATING
USING A 2 STAGE HEATING THERMOSTAT
NO COOLING
NOTES'
I
BE SURE POWER AGREES WITH EQUIPMENT NAMPLATE(S).
2
LOW VOLTAGE (24V, WIRING) TO BE NO, 18 A.W,G. MIN.,
3
GROUNDING OF EQUIPMENT MUST COMPLY WITH LOCAL CODES.
4
SET THERMOSTAT HEAT ANTICIPATOR PER UNIT WIRING DIAGRAM.
5
THESE LEADS PROVIDE 115 V. POWER FOR CONNECTION OF ELECTRONIC AIR CLEANER AND HUMIDIFIER MAX, LOAD 1.0 AMPS EACH.
THIS CONNECTION IS ONLY USED FOR THERMOSTATS REQUIRING CONNECTION TO THE 24 V. POWER SUPPLY (COMMON) SEE TWINNING CONNECTION DIAGRAMS FOR PROPER CONNECTIONS WHEN USING THIS FEATURE,
From Dwg. 21B342024 Rev. 0
26 18-CD19D8-15
Page 27
OUTDOOR UNIT
(NO TRANSFORMER)
Installer's Guide
FIELD WIRING DIAGRAM FOR 2 STAGE FURNACE
2 STAGE HEATING, 1 STAGE COOLING
USING A 2 STAGE HEATING, 1 STAGE COOLING THERMOSTAT
(OUTDOOR SECTION WITHOUT TRANSFORMER)
T'STAT
NOTE 7
D Fq
D
2 STAGE
FURNACE
SEE
SEE
NOTE 8 D
t-q
t--q
NOTES:
I. BE SURE POWERAGREES WITH EQUIPMENT NAMPLATE(S)
2. LOWVOLTAGE (24V. WIRING) TO BE NO. 18 A.W.G. MIN..
3. GRO DIG OF EQ IPMENT MUST COMPLYWITH LOCAL CODES
4. SET THERMOSTATHEAT ANTICIPATOR PER U IT WIRING DIAGRAM
5. THESE LEADS PROVIDE 115 V. POWERFOR CON ECTION OF ELECTRONIC AIR CLEA ER AND HUMIDIFIER MAX. LOAD 1.0 AMPS EACH.
6. THIS CONNECTION IS ONLY USED FOR THENMOSTATSREQUIRING CONNECTION TO THE 24 V. POWERSUPPLY. (COMMO)
7. SEE TWINNING CO NECTION DIAGRAMS FOR PROPERCONNECTIONS WHE USING THIS FEATURE
8. THE "Y" TERMINI AL FROM THE THERMOSTATM ST BE WIRED TO THE "Y" TERMINAL OF THE FURNACECO TROL FOR PROPERBLOWER
OPERATION DUAl G COOLING.
OUTDOOR UNIT
(NO TRANSFORMER)
D
D
SEE
NOTE 6 @
INTE:_ COM:_ONENT WIRING
24 V. \ FIELD
----LINE Y._ WIR ING 24 V. _ FACTORY
--LINE Y._ WIRIN(
FIELD WIRING DIAGRAM FOR 2 STAGE FURNACE
2 STAGE HEATING, 1 STAGE COOLING
USING A 1 STAGE HEATING, 1 STAGE COOLING THERMOSTAT
(OUTDOOR SECTION WITHOUT TRANSFORMER)
T'STAT
NOTE 7
__
.N_O_T_E_S_
......
E_---
E_---
__
INTER COMPONENT WIRING
...... 24 V. \ FIELD
----LINE V.TW]RING 24 V. "'_ FACTORY
--LINE V._y WIRING
SEE
SEE
SEE
L
2 STAGE
FURNACE
-B
---D
--D
--D
--[_.
- - [_1
D
D
i
TO 115Vl PH.,
i i
60 HZ.,POWER SUPPLY PER LOCALCODES
HUM SEE NOTE5
EAC SEE
NOTE5
WH
BK
L
NOTES:
I. BE SURE POWERAGREES WITH EQUIPMENT NAMPLATE(S).
2. LOW VOLTAGE (24V. WIRING) TO BE NO. 18 A.W.G. MIN..
3. GROUNDINGOF EQUIPMENT MUST COMPLY WITH LOCAL CODES.
4. SET THERMOSTAT HEAT ANTICIPATOR PER UNIT WIRING DIAGRAM.
5. THESE LEADS PROVIDE 115 V. POWERFOR CONNECTION OF ELECTRONIC AIR CLEANER AND HUMIDIFIER MAX. LOAD I.O AMPS EACH.
6. THIS CONNECTION IS ONLY USED FOR THERMOSTATS REQUIRING CONNECTION TO THE 24 V. POWERSUPPLY. (COMMON)
7. SEE TWINNING CONNECTION DIAGRAMS FOR PROPER CONNECTIONS WHEN USING THIS FEATURE,
8. THE "Y" TERMININAL FROM THE THERMOSTAT MUST BE WIRED TO THE "Y" TERMINAL OF THE FURNACE CONTROL FOR PROPER BLOWER
OPERATION DURING COOLING.
9. Wl AND W2 MUST BE JUMPERED TOGETHER FOR PROPER OPERATION. SECOND STAGE HEATING WILL BEGIN I0 MINUTES AFTER FIRST STAGE.
i
FIELD ADDED _--_f,- ..................F U R N A C E
JUMPER (NOTE 9) ,I I ! _b iK! JUNCTION
['-LH B,<L_]_]_ I BOX
TO115V1 PH,, I .... "_'_' WH/II
60 HZ., POWER J I _ 11
SUPPLYPER 1 I I'm I
'T GROUND
\ SCREW
LOCALCOOES| ,N ._______£_
rwH/I -- ,
HUM SEE J -- ,,_11 I
NOTE__ I
EAC SEE NOTE 5 , B_< From Dwg. B342019 Rev. 0
I ,,
From Dwg. B342021 Rev. 0
18-CD19D8-15 27
Page 28
Installer's Guide
TWINNING CONNECTION DIAGRAM
FOR TWINNING UX/DX-R FURNACES
1 STAGE HEAT / 1 STAGE COOLING THERMOSTAT
OUTDOOR UNIT NO. 1 1 STAGE
(WITH TRANSFORMER) HEATING / COOLING
SEE NOTE 3 THERMOSTAT FURNACE NO. 1
I :Ul
[ @@-(_ OI
(F_ELO SUPPUEO>
A_ERNaTE CONNECTION
OUTDOOR UNIT NO. 1
(NO TRANSFORMER)
ON BOTH UNITS.
2ND STAGE WILL FIRE
10 MINUTES AFTER 1ST i
BJ
SEE NOTE 5
%
i
i
NOTES
FURNACE NO. 2
SLOWEn OPERATION OF
UNIT NO 2 IS SYNCRONIZED
WITH UNIT NO I VIA SIGNALS
FROM TWIN CONNECTION
@
SEE NOTE 4
..... i
l l
,.J
I
i
J
I _OTN FURNACESMUST3_ ROWERE_FRON
THE SANE _lGV LEGOF D_RCNIT PANEL¸
2 _NSURE 24V FURNACE TRANSFORMERS ARE
IN PHASE PRIOR TO COMPLETING CONNECTIONS,
CHECK VOITAGE BET_EN "R" TERMINAIS OF EACH FURNACE 1{ VOLTAGE fS GREATER THAN
/OV, REVERSE THE BL AN RD SECONDARY LEADS
ON ONE OF THE FURNACE TRANSFORNERS
IF OUTDOOR UNIT HAS A RAY TRANSFORNER,
AN iSOIATION R{!AY MUST B_ /NSTA!L[D
(FIELD SUPPLIED USE PILOT DUT_ RELAY {'NC'), SUCH AS RLFORZ5) SEE ALT CONNECTION
IF CURRENT EXCEEDS THERMOSTAT CURRENT RATING, US_ ISOLATION RELAYS _'Ri') AS SRO_N _DO NOT CONNECT _ TO #)
_SOLATION RELAY NOT NEEDED IF THE THERNOSTAT CONTACTS AR_ RATED AT I OA OR A_OV_
S
CONNECTION MAY _ R_OUIRED FOR ELECTRONIC
THERMOSTATS
I[ TER CO_,IPONENT "¢VIRING
F-_-I
I
I
......... SE# #OT_ 4
AI TERNAT# NIR_ND EONF 16URATION
24 V'. '_ FIELD
----LINE /uiv'v'IS<INO
J I
i
I
i
I
i
I
r 1
i,
:1
ISOLATION RELAY
{HELD SUPPLIED}
SEE NOTE 4
%
ISOLATION RELAy
SEE NOTE 4
From Dwg. 21B341336 Rev. 2
24 V. / _> Y'i]R'ING
-- L INE .;,
h FACTO:{'{
,{]fffffffffffffff
TWINNING CONNECTION DIAGRAM
FOR TWINNING UX/DX-R FURNACES
2 STAGE HEAT/1 STAGE COOLING THERMOSTAT
OUTDOOR UNIT NO. 1 2 STAGE HEATING
(WITH TRANSFORMER) 1STAGE COOLING
SEE NOTE 3 THERMOSTAT
OUTDOOR UNIT NO. 1
(NO TRANSFORMER)
E]
Bi
Fq Fq
Fq Fq
i
"I
I _OTN EURNAC[S RUST B[ POWERED #RON
THE SAME HSV I£D O# CIRCUIT PANEl
R INSUR_ 24V FURNAC_ TRANSFORMERS AN_
IN PHASE PRIOR TO COMPLETING CONNECTIONS, CHECK VOLTAGE BETNEEN "R" TERMINALS OF EACH _URNACE /_ VOLTAGE IS GREATER THAN
JOY, REVERSE THE _L AN RD SECONDARY LEADS ON ON# 0# THE #URNAC[ TRANSfORMeRS
S iF OUTDOOR UNIT HAS A RAY TRANSFORM[R,
AN ISOLATION RELAF MUST BE _NSTALLED (FIELR SUPPLIEO USE PILOT DUTY REIAY ('RE'), SUCH AS RLYORYR ) SEE ALT CONNECTION
4
IF CURRENT EXCEEDS TNERNOGTAT CURRENT RATING, USE ISOLATION RELAYS {'RI') AS SNO_N (DO NOT CONNECT _ TO _)
ISOIATION REIAY NOT NEEDED _F THE THERMOSTAT
s?sj;? R
CONTACTS ARE RATED AT IRA OR ABOVE
CONNECTION MAY DE REQUIRED FOR ELECTRONIC
THE RNOS TATS
ISaAT_ON RELAY (F_ELDSUPPUEO)
SEE NOTE 4
r ,
FURNACE NO. 2
BLOWER OPERATION OF
UNIT NO 2 iSSYNCRONIZED
WITH UMT NO 1ViA SIGNA£5
FROM _IN CONNECTION
Fq
...... ' i
RI; L ;
F
R2; _1 :
--L-- ; I I I
I
i
%
I
i:
i
INTER CO,,PC ENT ",/V]RINO
......... SEE NOTE 4
I I
-- LI[ E ._,/VIZ{IN("
From Dwg 21B341337 Rev, 2
ATERRATE _INlflG CORF_G_RATION
24 ,/. h> F ]Ek D
LINE ,/.J ',/'filING 24 '/. _ FACTO_{Y
28 18-CD19D8-15
Page 29
OUTDOOR UNiT NO. 2
(NO TRANSFORMER}
SEE NOTE 3
2STAGEHEATING
1STAGECOOLING
THERMOSTAT
TWINNING CONNECTION DIAGRAM
FOR TWINNING UX/DX-R FURNACES
2 STAGE HEAT / 2 STAGE COOLING THERMOSTAT
FURNACE NO. 1
FURNACE NO.2
BLOWEROPEraTIONOr
wl_ UNIT.Olvl_sle._Ls
°:ff_,22222°
Installer's Guide
_OTE;
OUTDOOR UNiT NO 1
(NO TRANSFORMER)
f
%
SEE NOTE 5
%
CARBON MONOXIDE POISONING HAZARD
Failure to follow the installation instructions for the venting system being placed into operation could result in carbon
monoxide poisoning or death.
ISO_TIONRElY (FIELDSUPPLIED)
RI; _ 'J
tO ::
a2l_; :
I
I
I
I
!
From Dwg. 21 B341338 Rev. 2
%
ISO_TI_ nE_¥
sY"°W
4 ¸ ;
m; ;
SOATO_ i #[iAr '¢0T _,_ F TU[ Trfl2_OSTRT
HITHTRANSFORMER
i_i I
i
R2;_; ;
i i i
I "
ACT_NAT_CO.NECTION
INTER CObIPONENT 'FT[R]NG
ALT!PNAT_ #HUt¢O (O_[ _PAT I_
24 /, I, FIE L D
IIL]NE /. _'¢V[RINQ
24 '/. ;% FA::T }RY--LINE " "A'[ _ IN G
OUTDOORUNIT
SEE NOTE 3
, z0,
ISO_TION RElY
o'
ELECTRICAL CONNECTIONS
Make wiring connections to the unit as indicated on enclosed wiring diagram. As with all gas appliances using electrical
power, this furnace shall be connected into a permanently live electric circuit. It is recommended that furnace be
provided with a separate "circuit protection device" electric circuit. The furnace must be electrically grounded in accor-
dance with local codes or in the absence of local codes with the National Electrical Code, ANSI/NFPA 70 or CSA C22.1
Electrical Code, if an external electrical source is utilized.
The integrated furnace control is polarity sensitive.
The hot leg of the 120V power supply must be connected to the black power lead as indicated on the wiring diagram.
Provision for hooldng up an electronic air cleaner and or humidifier is provided on the integrated control.
Refer to the SERVICE FACTS literature and unit wiring diagram attached to furnace.
18-CD19D8-15 29
Page 30
Installer's Guide
@
AUTOMATIC GAS VALVE
WITH MANUAL SHUT-OFF
MAIN MANUAL m
SHUT-O FF VALVE
GROUND
UNION
JOINT ._
@
MAIN MANUAL
SHUT-OFF VALVE
GROUND
UNION JOINT
DRIP
LEG
AUTOMATIC GAS VALVE
WITH MANUAL SHUT-OFF
iii!iiiiii'i_iiiiliiliiliiliiliiliiliiliiliiliiliiliiliiliil/
DRIP _
LEG
UPFLOW MAY BE LEFT OR
RIGHT HAND GAS PIPING
AUTOMATIC GAS VALVE
WITH MANUAL SHUT-OFF
MAIN MANUAL
SHUT-OFF VALVE
GRO_
UNION JOINT !
HORIZONTAL FURNACE GAS PIPING MAY BE FROM EITHER SIDE
(Typical UPFLOW Furnace in horizontal configuration shown)
THE DOWNFLOW (VERTICAL) MAY BE INSTALLED
LEFT OR RIGHT SIDE GAS PIPING
MAIN MANUAL / GROUND UNION JOINT
VALVE DRIP
SHUT-OFF _
AIR
FLOW
AUTOMATIC GAS VALVE WITH
MANUAL SHUT-OFF
LEG
30 18-CD19D8-15
Page 31
Installer's Guide
GAS PIPING
The upflow/horizontal furnace is shipped standard for left side installation of gas piping. A knockout is provided on the right side for an alternate gas piping arrangement. See Figure
45. The installation of piping shall be in accordance with piping
codes and the regulations of the local gas company. Pipe joint compound must be resistant to the chemical reaction with liquefied petroleum gases.
Refer to piping Table 8, for delivery sizes. Connect gas supply to the unit, using a ground joint union and a manual shut-off valve as shown in Figures 44 & 45. National codes require a condensation drip leg to be installed ahead of the controls as shown in Figures 45 & 46.
Use a backup wrench on the gas valve when installing gas piping to prevent damage to the gas valve and manifold assembly.
The furnace and its individual shut-offvalve must be discon- nected from the gas supply piping system during any pressure
testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).
The furnace must be isolated from the gas supply piping by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig (3.5 kPa).
NOTE: Maximum pressure to the gas valve for natural gas is 13.8"
W.C. Minimum pressure is 5.0" W.C. Maximum pressure to
the gas valve for propane is 13.8" W.C. Minimum pressure is 11.0" W.C.
All gas fittings must be checked for leaks using a soapy
solution before lighting the furnace. DO NOT CHECK
WITH AN OPEN FLAME!
TABLE 8 NATURAL GAS ONLY
TABLE OF CUBIC FEET PER HOUR OF GAS
FOR VARIOUS PIPE SIZES AND LENGTHS
PIPE LENGTH OF PIPE
SIZE 10 20 30 40 50 60 70
1/2 132 92 73 63 56 50 46
3/4 278 190 152 130 115 105 96
1 520 350 285 245 215 195 180
1-1/4 1050 730 590 520 440 400 370
This table is based on pressure drop of 0.3 inch W.C. and 0.6 SRGR. gas
TABLE 9 ORIFICE SIZES
INPUT
RATING
BTUH
60,000 80,000
100,000 120,000
NUMBER
OF
BURNERS
3 4 5
6
MAIN BURNER ORIFICE
DRILL SIZE
NAT. GAS LP GAS
45 56 45 56
45 56 45 56
COMBUSTION AND INPUT CHECK (See also High Altitude Derate)
1. Make sure all gas appliances are off except the furnace.
2. Clock the gas meter with the furnace operating (deter- mine the dial rating of the meter) for one revolution.
3. Match the "See" column in the gas flow (in cfh) Table 10 with the time clocked.
4. Read the "Flow" column opposite the number of seconds clocked.
5. Use the following factors if necessary: For 1 Cu. Ft. Dial Gas Flow CFH =
Chart Flow Reading + 2
For 1/2 Cu Ft. Dial Gas Flow CFH =
Chart Flow Reading + 4
For 5 Cu. Ft. Dial Gas Flow CFH =
10X Chart Flow Reading + 4
©
PRESSURE WITH BURNER BOX REFERENCED
A CAUTION: Beturna,tubing,caps,an, orplugstooriginalpositionswhenpressurechecksare completed.
18-CD19D8-15 31
CORRECT METHOD OF CHECKING DIRECT VENT MANIFOLD
Separate the tube I
I
at the unit Tee and _'
reconnectwith a ,.-. II "_t
shortpiece of field _ II I I
supplied tube and T 11 I I
anotherTeewith /7 _ I ] the "U" Manometer /¢_/ /1
attached. /__ II
Besuretoreconneot I{ JJ
unit tubing to original -- _ \'\ _/ position after testing -- _k_
the manifold pressu re! ___.
Field supplied barb fitting | with manom eter tube is _IL
attached to the"OUTLET _ j PRESSURE TAP" on the
outlet side of the gas valve,
Page 32
Installer's Guide
6. Multiply the final figure by the heating value of the gas obtained from the utility company and compare to the nameplate rating. This must not exceed the name- plate rating.
7. Changes can be made by adjusting the manifold pressure (See Table 11), or changing orifices (orifice change may not always be required). To adjust the manifold pressure:
a. Turn off all electrical power to the system.
b. Attach a manifold pressure gauge to the outlet
pressure tap marked "OUT PRESS TAP" on White-Rodgers gas valve model 36E or boss marked "OUT P" on White-Rodgers gas valve model 36G. (See Figure 48 for White-Rodgers gas valve model 36E and Figure 49 for White-Rodgers gas valve model 36G). For the gas valve model 36E, measurements require removal of the plug and installation of a barbed fitting. Attach flexible tubing and a manometer to the barbed fitting. For the gas valve model 36G, do not remove the pressure tap test screw. Loosen the pressure tap test screw one turn and install flexible tubing and a manometer directly onto the outlet pressure boss.
c. The other side of the manifold pressure gauge must be
referenced to the burner box as shown in Figure 46.
d. Turn on system power and energize valve. e. For the White-Rodgers gas valve model 36E:
1. Adjust low fire by removing the low adjustment
seal screw (See Figure 48).
TABLE 10
GAS FLOW IN CUBIC FEET PER HOUR
2 CUBIC FOOT DIAL
SEC. FLOW SEC.
8 900 29 9 800 30
10 720 31
11 655 32
12 600 33 13 555 34 14 514 35 15 480 36 16 450 37 17 424 38 18 400 39 19 379 40
20 360 41
21 343 42
22 327 43 23 313 44 24 300 45 25 288 46 26 277 47 27 267 48 28 257 49
FLOW SEC. FLOW SEC. FLOW
248 50 144 82 88 240 51 141 84 86 232 52 138 86 84 225 53 136 88 82
218 54 133 90 80 212 55 131 92 78 206 56 129 94 76 200 57 126 96 75
195 58 124 98 73 189 59 122 100 72 185 60 120 104 69 180 62 116 108 67 176 64 112 112 64 172 66 109 116 62
167 68 106 120 60 164 70 103 124 58 160 72 100 128 56 157 74 97 132 54 153 76 95 136 53 150 78 92 140 51 147 80 90 144 50
TABLE 11
FINAL MANIFOLD
FUEL
NATURAL GAS
LP GAS
PRESSURE SETTINGS (inches w.c.)
2nd Stage Max. 1st Stage Max.
3.5" W.C. 1.7" W.C.
10.5" W.C. 6.0" W.C.
2. To increase outlet pressure, turn the 3/32" socket
set screw clockwise. To decrease outlet pressure, turn the set screw counterclockwise. Adjust regula- tor until pressure shown on manometer matches the pressure specified in Table 11.
3. Replace low adjustment seal screw and tighten securely.
4. Cycle the valve several times to verify regulator setting.
5. Adjust high fire by removing the high adjustment seal screw (See Figure 48).
6. To increase outlet pressure, turn the 3/32" socket set screw clockwise. To decrease outlet pressure, turn the set screw counterclockwise. The final
manifold pressure setting shall be as specified in Table 11 with an input of no more than nameplate
rating and no less than 93% of the nameplate rating, unless the unit is derated for high altitude.
7. Replace high adjustment seal screw and tighten securely.
8. Cycle the valve several times to verify regulator setting.
f. For the White-Rodgers gas valve model 36G:
HIGHALTITUDE DERATE
Input ratings (BTUH) of these furnaces are based on sea level operation and should not be changed at elevations up to
2,000 ft. If the installation is 2,000 ft. or above, the furnace input rate
(BTUH) shall be reduced 4% for each 1,000 ft. above sea level. The furnace input rate shall be checked by clocldng the gas
flow rate (CFH) and multiplying by the heating value obtained from the local utility supplier for the gas being
delivered at the installed altitude. Input rate changes can be made by adjusting the manifold pressure (min 3.0 - max
3.7 in. W.C. - Natural Gas) or changing orifices (orifice change may not always be required).
If the desired input rate cannot be achieved with a change in manifold pressure, then the orifices must be changed. LP
installations will require an orifice change.
IMPORTANT: Reinstall the propane orifices to the same depth as the orifices
supplied with the equipment.
Installation of this furnace at altitudes above 2,000 ft. (610m) shall be in accordance with the local codes, or in the absence of local codes, the National Fuel Gas Code, ANSI
Z223.1 / NFPA 54 or National Standard of' Canada, Natural Gas and Propane Installation Code, CSA 149.1. Installation of
this furnace at altitudes above 2,000 ft. (610m) shall be made in accordance with the listed high Altitude Conversion Kit
available with this furnace.
TABLE 12
PART NUMBERS FOR REPLACEMENT ORIFICES
DRILL
SIZE
44 45
46 47
48 49
50
PART
NUMBER
ORF00501
ORF00644 ORF00909
ORF00910 ORF01099 ORF00503
ORF00493
DRILL
SIZE
54 55
56 57
58 59
PART
NUMBER
ORF00555 ORF00693
ORF00907 ORF00908
ORF01338 ORF01339
32 18-CD19D8-15
Page 33
See Table 13 forhelp in selectingorificesiforificechange is required. Fu_'nace input rateand temperature riseshould be checked again afterchanging orificesto confirm the proper rate
forthe altitude.
The vent length table on page 16 shows the required vent lengths for installationsat various altitudes.An optional high altitudeidt isavailable for installationsabove 5000 feet Installationsabove 12,000 feet are not allowed).
TABLE 13
Orifice
Twist Drill
ALTITUDE ABOVE SEA LEVEL
Size If
Installed
and Orifice Required At Other Elevations
At Sea
Level
42 43 44 45 46 47
2000 3000 400G 5000 6000 700G 8000 9000 10000
42 43 43 43 44 44 45 46 47 44 44 44 45 45 46 47 47 48 45 45 45 46 47 47 48 48 50 46 47 47 47 48 48 49 49 50 47 47 47 48 48 49 49 50 51 48 48 49 49 49 50 50 51 52
54 54 55 55 55 55 55 56 56 56 55 55 55 55 56 56 56 56 56 57 56 56 56 57 57 57 58 59 59 60 57 58 59 59 60 60 61 62 63 63 58 59 60 60 61 62 62 63 63 64
From N_ional Fuel Gas Code-Table F-4
White-Rodgers 36E
@
2nd Stage (HI) Manifold Pressure
Adjustment
1st Stage (LO)
Gas Valve On / Off Toggle Switch
White-Rodgers36G 2nd Stage (HI) Manifold
Pressure Adjustment
Gas Valve On / Off Toggle Switch
1. Adjust low fire by removing the low adjustment regulator cover screw (See Figure 49).
2. To increase outlet pressure, turn the regulator adjust screw clockwise. To decrease outlet pressure, turn the regulator adjust screw counterclockwise. Adjust regulator until pressure shown on mano- meter matches the pressure specified in Table 11.
3. Replace and tighten the regulator cover screw
securely.
Manifold Pressure
Adjustment
1st Stage (LO) Manifold Pressure
Adjustment
Installer's Guide
ROTATE THE FRONT COVER AS SHOWN
INSERT THE TOP FLANGE OF THE FRONT COVER
UNDER THE LIP INSIDE
THE BOX
ALL SIDE FLANGES MUST
BE OUTSIDE OF THE BOX
ROTATE THE FRONT COVER INWARD MAKING
SURE THAT ALL SIDE
FLANGES ARE OUTSIDE OF THE BOX.
4. Cycle the valve several times to verify regulator setting.
5. Adjust high fire by removing the high adjustment
regulator cover screw (See Figure 49).
6. To increase outlet pressure, turn the regulator
adjust screw clockwise. To decrease outlet pressure, turn the regulator adjust screw counterclockwise. The final manifold pressure setting shall be as
specified in Table 11 with an input of no more than
nameplate rating and no less than 93% of the nameplate rating, unless the unit is derated for high altitude.
7. Replace high adjustment regulator cover screw and
tighten securely.
8. Cycle the valve several times to verify regulator setting.
g. Turn off all electrical power to the system.
h. Remove the manometer and flexible tubing. Remove
the barbed fitting and replace the plug or tighten the pressure test screw.
i. Turn on electrical power to the system and energize
valve.
j.Using a leakdetectionsolutionorsoap suds,checkfor
leaksatplugor pressurebossscrew.
NOTE:
The manifold pressure must be referenced to the burner
box. The burner box pressure tap equalizes the gas valve pressure regulator. Manifold pressure is checked by installing a tee (field supplied) in the tubing, between the tee coming from the burner box tube and the gas valve, in addition to the regular gas valve pressure tap on the outlet side of the gas valve. See Figure 47.
18-CD19D8-15 33
Page 34
Installer's Guide
EXPLOSION HAZARD! PROPANE GAS IS HEAVIER THAN AIR AND MAY COL- LECT IN ANY LOW AREAS OR CONFINED SPACES. IN
ADDITION, ODORANT FADE MAY MAKE THE GAS UNDETECTABLE EXCEPT WITH A WARNING DEVICE. IF
THE GAS FURNACE IS INSTALLED IN A BASEMENT, AN EXCAVATED AREA OR A CONFINED SPACE, IT IS STRONGLY RECOMMENDED TO CONTACT A GAS
SUPPLIER TO INSTALL A GAS DETECTING WARNING DEVICE IN CASE OF A GAS LEAK.
NOTE: The manufacturer of your furnace does NOT test any detectors and makes no representations regarding any brand or type of detector.
Replace and/or tighten all plugs removed or loosened when adjusting gas pressure. Leak check the fittings before placing the furnace into regular service. Failure to follow this warning could result in fire, explosion, or property damage.
Table 12 lists the main burner orifices used with the furnace. If a change of orifices is required to correct the furnace input
rating refer to Table 13.
REINSTALLATION OF THE BURNER BOX COVER
Figure 49 shows the correct way to reinstall the burner box cover if adjustment or replacement of the flame sensor, hot surface igniter, or main burner orifices have required re-
moval of the cover.
START-UP AND ADJUSTMENT
PRELIMINARY INSPECTIONS
Disconnect power to the unit before removing the blower door. Allow a minimum of 10 seconds for IFC power supply to drain to 0 volts. Failure to follow this warning could result in property damage, personal injury or death.
With gas and electrical power "OFF"
1. Duct connections are properly sealed
2. Filters are in place
3. Venting is properly assembled
4. Blower door is in place
Turn the main gas valve toggle switch (See Figures 48 & 49) within the unit to the "OFF" position. Turn the external gas valve to "ON". Purge the air from the gas lines. After purging, check all gas connections for leaks with a soapy solution --
DO NOT CHECK W1TH AN OPEN FLAME. Allow 5 min- utes for any gas that might have escaped to dissipate.
LP Gas being heavier than air may require forced ventilation. Turn the toggle switch on the gas valve in the unit to the "ON" position.
LIGHTING INSTRUCTIONS
DO NOT attempt to manually light the burner. Failure to follow this warning could result in property damage, personal injury or death.
Lighting instructions appear on each unit. Each installation must be checked out at the time of initial start up to insure proper operation of all components. Check out should include putting the unit through one complete cycle as outlined below.
Turn on the main electrical supply and set the thermostat above the indicated temperature. The ignitor will automati- cally heat, then the gas valve is energized to permit the flow of gas to the burners. After ignition and flame is established, the flame control module monitors the flame and supplies power to the gas valve until the thermostat is satisfied.
To shut off
For complete shutdown: Turn the gas cock knob on the main gas valve to the "OFF" position (See Figure 44). Disconnect the electrical supply to the unit.
Ifthis is done during the cold weather months, provisions must be taken to prevent freeze-up of all water pipes and
water receptacles.
Whenever your house is to be vacant, arrange to have someone inspect your house for proper temperature. This is very important during freezing weather. If for any reason your furnace should fail to operate dam- age could result, such as frozen water pipes.
SEQUENCE OF OPERATION Thermostat call for heat (2-stage thermostat)
Call for 1st stage only:
Wl thermostat contacts close signaling the control module to run its self-check routine. After the control module has
verified that the 1st stage pressure switch contacts are open and the limit switch(es) contacts are closed, the draft blower
will be energized. As the induced draft blower comes up to speed, the pressure
switch contacts will close and the ignitor warm up period will begin. The ignitor will heat for approx. 20 seconds, then the gas valve is energized in 1st stage to permit gas flow to the
burners. The flame sensor confirms that ignition has been achieved
within the 4 second ignition trial period. As the flame sensor confirms that ignition has been achieved,
the delay to fan ON period begins timing and after approx. 45 seconds the indoor blower motor will be energized at low speed and will continue to run during the heating cycle.
Call for 2nd stage after 1st stage:
W2 thermostat contacts close signaling a call for 2nd stage heat. After a 30 second delay, the induced draft blower will be energized on high speed and the 2nd stage pressure switch contacts will close. The gas valve is energized in 2nd stage and the indoor blower motor in high speed.
2nd stage satisfied, 1st stage still called: W2 thermostat contacts open signaling that 2nd stage heating requirements are satisfied.
The induced draft blower is reduced to low speed allowing the 2nd stage pressure switch contacts to open and the gas valve is reduced to 1st stage. The indoor blower motor is reduced to low speed.
1st stage satisfied: W1 thermostat contacts open signaling that 1st stage heating requirements are satisfied. The gas valve will close and the induced draft blower will be de-energized. The indoor blower motor will continue to run for the fan off period (Field selectable at 60, 100, 140 or 180 seconds), then will be de-energized by the control module.
34 18-CD19D8-15
Page 35
Installer's Guide
Thermostat call for heat (1-stage Thermostat)
W1/W2 (jumpered) thermostat contacts close signaling a call
for heat. 1st stage sequence of operation remains the same as above. 2nd stage heat will energize after the stage delay timer (field selectable at .5, 5, 10 or 15 minutes) has expired.
Thermostat satisfied:
W1/W2 (jumpered) contacts open signaling the control
module to close the gas valve. The induced draft blower is switched to low speed and de-energized after the post purge timer has expired. The indoor blower motor will continue to operate after the flames are extinguished and then is switched to low heat speed for the FAN-OFF period.
CONTROL AND SAFETY SWITCH ADJUSTMENTS LIMIT SWITCH CHECK OUT
The limit switch is a safety device designed to close the gas valve should the furnace become overheated. Since proper
operation of this switch is important to the safety of the unit, it must be checked out on initial start up by the installer.
To check for proper operation of the limit switches, set the thermostat to a temperature higher than the indicated temperature to bring on the gas valve. Restrict the airflow
by blocking the return air (disconnecting the indoor blower
may trip the inducer limit). When the furnace reaches the maximum outlet temperature as shown on the rating plate, the burners must shut off. If they do not shut off after a reasonable time and overheating is evident, a faulty limit switch is probable and the limit switch must be replaced.
After checking the operation of the limit control, be sure to
remove the paper or cardboard from the return air inlet. Refer to Service Facts for additional instructions.
NOTE TO INSTALLER
Review the following warnings with the owner. Review con- tents of USER'S INFORMATION MANUAL with the owner.
AIRFLOW ADJUSTMENT
Check inlet and outlet air temperatures to make sure they
iiiiiiiii;iiiiiiiiiiiiIi iiiiiiliiiiiiiiHii
iiii!
are within the ranges specified on the furnace rating name- plate. If the airflow needs to be increased or decreased, see the wiring diagram for information on changing the speed of
the blower motor.
ROOM AIR THERMOSTAT HEAT ANTICIPATOR ADJUSTMENT
Set the thermostat heat anticipator according to the current flow measured, or the settings found in the notes on the furnace wiring diagram (found in the SERVICE FACTS or inside the furnace casing).
INSTRUCTIONS TO THE OWNERS
In the event that electrical, fuel, or mechanical failures occur, the owner should immediately turn the gas supply off at the manual gas valve, located in the
burner compartment. Also turn off electrical power to
the furnace and contact the service agency designated
by your dealer.
BURNER BOX TEMPERATURE LIMIT DEVICE
All models are equipped with a manual reset temperature
limit located on the burner box. In case of excessive tempera- ture, the limit will open and cause the circuit to open which shuts off all flow of gas.
Disconnect power to the unit before removing the blower door. Allow a minimum of 10 seconds for IFC power supply
to drain to 0 volts. Failure to follow this warning could
result in property damage, personal injury or death.
This unit is equipped with a blower door switch which cuts power to the blower and gas valve causing shutdown when the door is removed. Operation with the door removed or ajar can permit the escape of dangerous fumes. All panels must be securely closed at all times for safe operation of the furnace.
INDOOR BLOWER TIMING
Heating: The integrated furnace control module controls the indoor blower. The blower start is fixed at 45 seconds after
ignition. The FAN-OFF period is field selectable by dip switches SW-2, #1 and #2 at 60, 100, 140, or 180 seconds. The factory setting is 100 seconds.
Wl-W2 stage delay (jumpered together) is field selectable by
dip switch SW-1, #1 and #2 at .5, 5, 10 or 15 minutes. The factory setting is 10 minutes. (See wiring diagram).
Cooling: The fan delay off period is factory set at 0 seconds. The option for 80 second delay off is field selectable by dip switch SW-2, #3 (See wiring diagram).
18-CD19D8-15 35
Page 36
Installer's Guide
ABNORMAL CONDITIONS
1. EXCESSIVE COMBUSTION PRESSURE (WIND IN EXCESS OF 40 MP.H.) VENT OR FLUE BLOCKAGE
On a call for heat, the variable speed draft inducer must first ramp up to speed and close the pressure switch before the ignition sequence is allowed to begin. If the pressure switch does not close, the motor will ramp up to maximum speed and continue to operate there for about
i minute.
After one minute the integrated furnace control will turn the motor off for about 30 seconds then back on in an
attempt to reestablish proper operation. This condition is indicative of a highly restricted or blocked inlet or outlet vent pipe or a failed pressure switch.
If pressure against induced draft blower outlet becomes excessive, the pressure switch will open. If the pressure switch is open for more than 3.5 seconds, the variable speed draft inducer will speed up and attempt to close the pressure switch. If the pressure switch is not closed within 12 seconds or if the maximum speed of the motor is reached, the draft inducer sends a fault signal to the integrated furnace control. If the unit is operating in second stage, an inducer fault will cause the furnace control to transition the system to first stage and it will operate there for 10 minutes before attempting to run again in second stage. If the unit is operating in first stage, an inducer fault will cause the furnace control to shut the system down and wait 30 seconds before attempting to reestablish operation in first stage.
2. LOSS OF FLAME If loss of flame occurs during a heating cycle, or flame is
not present at the sensor, the flame control module will close the gas valve. The flame control module will then recycle the ignition sequence, then if ignition is not achieved, it will shut offthe gas valve and lock out the system.
3. POWER FAILURE If there is a power failure during a heating cycle, the
system will restart the ignition sequence automatically when power is restored, if the thermostat still calls for
heat.
4. GAS SUPPLY FAILURE If loss of flame occurs during a heating cycle, the system
integrated control module will recycle the ignition sequence, then if ignition is not achieved, the integrated control module will shut offthe gas vNve and lock out the system.
5. INDUCED DRAFT BLOWER FAILURE Please refer to the variable speed draft inducer
troubleshooting manual for diagnostic assistance.
6. CONDENSATE DRAIN BLOCKAGE If the condensate drain is blocked, either by debris,
improper draining, or by freezing condensate, the pressure switch will sense the accumulation ofconden- sate in the furnace drain pan. The unit will not operate properly until the condensate drain has been cleared, and the condensate flows freely.
7. RESET AFTER LOCKOUT When the integrated control module has shut the system
down and gone into lockout, the system must be manu- ally reset before the unit will restart. The system can be reset by turning the system power off for more than
1 second, or by removing 24VAC from the control for more
than 1 second, or by removing the thermostat call for heat for more than 1 second but less than 20 seconds.
8. RESET AFTER BURNER BOX LIMIT SHUTDOWN If the furnace shuts down, one thing that can be checked
is the burner box temperature limit switch. It is located on the bottom of the burner box. The vent and combus-
tion air inlet terminations should be checked for block- age. If blockage exists, clear the problem and then the
reset button may be depressed. If there is no block- age of the terminations, the limit switch must be reset by a qualified servicer.
36 18-CD19D8-15
Page 37
FAULT CODE RECOVERY
On power up, last 4 faults, if any, will be flashed on the red LED. The newest fault detected will flash first and the oldest
last. There will be a 2 second delay between fault code flashes. Solid red LED error codes will not be displayed.
The Green LED will be on solid during last fault recovery.
At any other time the control is powered, the Green LED
indicator light will operate as shown in Table 14 and the red LED will flash LitePort data (one flash) every 20 seconds.
Fault Code Reset
The last 4 fault codes can be erased from memory by power- ing up the control with "G" energized and then applying "R" to the "WI" terminal 3 times within 6 seconds. The control
will acknowledge the reset by turning on the red LED for 2 seconds.
TABLE 14
INTEGRATED FURNACE CONTROL
GREEN "STATUS" LED FLASH CODES
Flashing Slow --- Normal - No call for Heat
Flashing Fast --- Normal - Call for Heat
Installer's Guide
Green Status LED
*UX / DX Integrated Furnace Control
INTEGRATED FURNACE CONTROL RED LED "ERROR" FLASH CODES
2 Flashes --- System Lockout (Retries or Recycles exceeded)
Draft Pressure Error- Possible problems:
3 Flashes ---
a) Venting problem b) Pressure switch problem c) Inducer problem
4 Flashes --- 5 Flashes ---
6 Flashes---
Open Temperature Limit Switch
Flame sensed when no flame should be present
115 volt AC power reversed, ignitor (Triac) fault, poor grounding or system voltage too low
7 Flashes ---
Gas valve circuit error
8 Flashes --- Low flame sense 9 Flashes --- Open Inducer Limit switch
10 Flashes --- Inducer communication error Solid --- Internal GV error or Low TH voltage
Solid Red w/Solid Green "STATUS" LED
Continuous Reset caused by a blown fuse or internal error.
18-CD19D8-15 37
Page 38
Trane
6200 Troup Highway
Tyler, TX 75707
For more information contact Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to your local dealer (distributor) change design and specifications without notice.
03/08
Loading...