Trane Duplex Water-Cooled Hermetic CenTraVac Installation Manual

Installation
Duplex Water-Cooled
Hermetic CenTraVac CH530 Controller
With
X39640669020
CDHF-SVN01B-EN
Warnings and Cautions
Warnings and Cautions
Notice that warnings and cautions appear at appropriate intervals throughout this manual. Warnings are provided to alert installing contractors to potential hazards that could result in personal injury or
death, while cautions are designed to alert personnel to conditions that could result in equipment damage.
Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
NOTICE:
Warnings and Cautions appear at appropriate sections throughout this manual.
Read these carefully.
WARNING – Indicates a potentially hazardous situation which, if not avoided, could result in
death or serious injury.
CAUTION – Indicates a potentially hazardous situation which, if not avoided, may result in
minor or moderate injury. It may also be used to alert against unsafe practices.
CAUTION – Indicates a situation that may result in equipment or property-damage-only accidents.
© 2005 American Standard Inc. All rights reserved. CDHF-SVN01B-EN
Contents
Warnings and Cautions
General Information
Water Piping
Vent Line Piping
Insulation
Electrical Information
Trane Supplied Starter
Customer Supplied Starter
Line Power Supply
PFCC
PFCC and Unit Mounted Starters
Remote Starter
2
4
25
35
41
43
44
45
47
48
50
51
CDHF-SVN01B-EN
Starter to UCP Control Wiring
Control Circuit Wiring
System Control Wiring
Wiring Diagrams
53
54
56
59
3
General Information
About this Manual
Original date of manual:
This manual contains information regarding installation of Models CDHF 60 Hz and CDHG 50 Hz chillers equipped with Tracer CH530 controller. Reference is made to the CDHF. All installation procedures described for the CDHF apply also to the CDHG. By carefully reviewing the information in this manual and following the instructions given along with the submittal package provided for the unit will assure that the chiller is installed correctly.
Product Description Block
Trane 60 Hz. Model CDHF hermetic CenTraVac product definition and selection system (PDS). Each unit is defined by the product description block which appears on the unit nameplate. An explanation of the PDS product code is provided in the unit operation and maintenance literature.
units are defined by the
4
CDHF-SVN01B-EN
General Information
Commonly Used Acronyms
ASME = American Society of Mechanical Engineers ASHRAE = American Society of Heating, Refrigerant and Air Conditioning Engineers
BAS = Building Automation System LBU = La Crosse Business Unit CABS = Auxiliary Condenser Tube­Bundle Size CDBS = Condenser Bundle Size CDSZ = Condenser Shell Size CWR = Chilled Water Reset
DTFL = Delta-T at Full Load (i.e., the difference between entering and leaving chilled water temperatures at design load) EVBS = Evaporator Bundle Size EVSZ = Evaporator Shell Size
GPM = Gallons-per-Minute
HVAC = Heating, Ventilating, and Air Conditioning IE = Internally Enhanced Tubes IPC = Interprocessor Communication
PFCC = Power Factor Correction Capacitor PSID = Pounds-per-Square-Inch (differential pressure) PSIG = Pounds-per-Square-Inch (gauge pressure)
UCP = Chiller Control Panel
CH530 = Tracer CH530 Chiller Controller
Warnings and Cautions
Notice that WARNINGS and CAUTIONS appear at appropriate intervals throughout this manual. WARNINGS are provided to alert installing contractors to potential hazards that could result in personal injury or death, while CAUTIONS are designed to alert personnel to conditions that could result in equipment damage.
Your personal safety and the proper installation of this machine depend upon the strict observance of these precautions.
Unit Nameplate
The CDHF unit nameplate is located on the left side of the left hand unit control panel (UCP). A typical unit nameplate is illustrated in Figure 1. The following information is provided on the CDHF unit nameplate.
- Unit model and size descriptor
- Unit serial number
- Unit electrical requirements
- Correct operating charge and type of refrigerant.
- Unit test pressures and maximum operating pressures
- Unit Installation and Operation and Maintenance manuals
- Product description block (identifies all unit components and unit “design sequence” used to order literature and make other inquiries about the unit).
CDHF-SVN01B-EN
Metric Conversion
The following conversions apply for tables and charts in this manual,
In. x 2.54 = cm
Ft. x 30.48 = cm.
Lb. x .453 = kg.
5
General Information
Figure 1 – Information from a Typical CDHF Unit Nameplate
MODEL: CDHF2000 DATE OF MFG (DD/MM/YY): @TODAY05 MODEL NO: CDHF2000KR0TA2802745B0A106B0A1CFFRR10W4C0010330001S SERIAL NO: S.O. NO: SAMPLE
RATED VOLTAGE: 4160 VOLTS 60 HZ 3 PH VOLTAGE UTILIZATION RANGE: 3744-4576 VAC
LH CIRCUIT RH CIRCUIT MINIMUM CIRCUIT AMPACITY: 96 AMPS 103 AMPS MAXIMUM OVERCURRENT PROTECTIVE DEVICE: 150 AMPS 175 AMPS
COMPRESSOR MOTOR MAX VOLTS-AC HZ PH RLA KW LRAY LH CIRCUIT 4160 60 3 75 480 400 RH CIRCUIT 4160 60 3 82 523 473 VOLT HZ PH OIL TANK HEATER (LH&RH): 115 60 1 750 WATTS CONTROL CIRCUIT (LH&RH): 115 60 1 4000 VA MAX CARBON TANK HEATER (LH&RH):115 60 1 1.7 RLA PUMPOUT COMPRESSOR(LH&RH): 115 60/50 1 1.55 RLA PURGE COMP MTR(LH&RH): 115/110 60/50 1 8RLA 34.6LRA
WHEN MOTOR CONTROLLER PROVIDED BY OTHERS TRANE ENGINEERING SPEC. S6516-0513 APPLIES
REFRIGERANT SYSTEM LH RH FIELD CHARGED WITH: 1850 1850 LBS. OF R-123 ACTUALLY CHARGED WITH: LBS. OF R-123 MAXIMUM WORKING PRESSURE: 15 15 PSIG HIGH SIDE MAXIMUM WORKING PRESSURE: 15 15 PSIG LOW SIDE
FACTORY TEST PRESSURE: HIGH SIDE 45 PSIG LOW SIDE 45 PSIG FIELD LEAK TEST PRESSURE 8 PSIG MAX. TESTED AT PSIG
MANUFACTURED UNDER ONE OR MORE OF THE FOLLOWING U.S. PATENTS: 4232533 4686834 4689967 4715190 4751653 4800732 5031410 5056032 5058031 5355691 5434738 5537830 5553997 5563489 5600960 5675978 5836382 5848538 6065297 6098422 6250101
SERVICE LITERATURE INSTALLATION MANUAL: CDHF-SVN01A-EN OPERATION/MAINTENANCE MANUAL: CDHF-SVU01A-EN
PRODUCT DESCRIPTION: TVSQ 1 PTON 1975 VTR1 165 VTR2 165 CTM1 75 CTM2 100 MAC1 6 MAC2 6 MODL CDHF DSEQ R0 NTON 2000 VOLT 4160 HRTZ 60 CPM1 512 CPD1 280 CPM2 588 CPD2 274 EVSZ 210D EVBS 1850 EVTM TECU EVTH 35 EFLD WATE EVWT MAR EVWP 1 EVWC STD EVPR 150 EVCO VICT EVWA RRLR CDSZ 210D CDBS 1900 CDTM TECU CDTH 35 CFLD WATE CDWT MAR CDWP 1 CDWC STD CDPR 150 CDCO VICT CDWA LFRF ORC1 1265 ORC2 1265 AGLT UL TEST CWSP TTOL SPCL WCNM BNMP CNIF CH53 OPST YES WPSR WFC TRMM TRM4 EPRO YES CDRP YES SPKG DOM ASCL OUTS APTY STD SRT1 CXL SRT2 CXL SOPT 3RTD GENR NO
6
CDHF-SVN01B-EN
General Information
Responsibilities of Installing Contractors
For your convenience, a summary of the contractor responsibilities typically associated with the chiller installation process is provided below. Table 1 further categorizes these responsibilities by differentiating between Trane­supplied and field-supplied and field installed components.
Refer to the Installation section of this manual for more detailed instructions.
• Locate and maintain the loose parts, i.e. isolators, bulb wells, temperature sensors, flow sensors or other factory-ordered field installed options, for installation as required. Loose parts are located in the starter panel on units with factory-installed unit-mounted starters or in the motor terminal box for units with remote-mounted starters.
• Install unit on a foundation with flat support surfaces level within 1/16”, and of sufficient strength to support concentrated loading. Place manufacturer-supplied isolation pad assemblies under unit. (Use spring isolators for upper floor installations).
• Install unit per applicable Trane installation manual.
• Complete all water piping and electrical connections.
Note: Field-piping must be arranged and supported to avoid stress on the equipment. It is strongly recommended that the piping contractor refrain from piping closer than 3’-0” minimum to the equipment. This will allow for proper fit-up upon arrival of the unit at the jobsite. Any adjustment that is necessary can be made to the piping at that time.
• Where specified, supply and install valves in water piping upstream and downstream of evaporator and condenser water boxes to isolate shells for maintenance, and to balance/trim system.
• Supply and install flow switches (or equivalent devices) in both chilled water and condenser water piping. Interlock each switch with proper pump starter to ensure unit can only operate when water flow is established.
• Supply and install taps for thermometers and pressure gauges in water piping adjacent to inlet and outlet connections of both evaporator and condenser.
• Supply and install drain valves on each water box.
• Supply and install vent cocks on each water box.
• Where specified, supply and install strainers ahead of all pumps and automatic modulating valves.
• Supply and install pressure relief piping from pressure-relief rupture disc to atmosphere.
• If necessary, supply sufficient Refrigerant-HCFC-22 (maximum of 1 lb. per machine) and dry nitrogen (8 psig per machine) for pressure testing under manufacturer’s supervision.
• Start unit under supervision of a qualified service technician.
• Where specified, supply and insulate evaporator and any other portions of machine as required to prevent sweating under normal operating conditions.
• Unit-Mounted Starters Only, remove top of starter panel and cut access area for line-side wiring; front left quadrant of top provides recommended access to starter lugs.
• Supply and install wire terminal lugs to starter.
• Unit-Mounted Starters Only, Supply and install field wiring to line-side lugs of starter.
• Supply and install a Refrigerant Monitor per ASHRAE 15 specifications. Reference the compliance to ASHRAE Standard 15 as shown on the “Model CenTraVac Request for Serviceman”.
To obtain a copy of “Model CenTraVac for Serviceman” (Form 1-27.08-6) order from your local Trane office.
Checksheet and
Checksheet and Request
CDHF-SVN01B-EN
7
General Information
Table 1 – Installation Requirements
Type of Trane-Supplied Trane-Supplied Field-Supplied Requirement Trane-Installed Field-Installed Field-Installed
Rigging A. Safety chains
B. Clevis connectors C. Lifting beam
Isolation A. Isolation pads or A. Isolation pads or spring isolators
spring isolators
Electrical A. Circuit breakers or A. Jumper bars A. Circuit breakers or fusible
fusible disconnects B. Temperature sensor disconnects (optional) (optional) (optional outdoor air) B. Remote-mounted starter
B. Unit-mounted C. Flow switches (may C. PFCCs (Remote-mounted
starter (optional) be field supplied) starter option only)
C. PFCCs (optional) D. Terminal lugs
E. Ground connection(s) F. Jumper bars G. BAS wiring (optional) H. IPC wiring (remote-
mounted starters only
I. Control voltage wiring
(remote-mounted starters only)
J. Oil pump interlock wiring
(remote-mounted starters only)
K. High condenser pressure
interlock wiring (remote-mounted starters only).
L. Chilled water pump contactor
and wiring
M.Condenser water pump
contactor and wiring
N. Option relays and wiring
(See Table 14 & 16)
Water Piping A. Flow switches (May A. Thermometers
be field supplied) B. Water flow pressure gauges
C. Isolation and balancing valves
water piping
D. Vents and drain valves
(1 each per class)
E. Pressure-relief valves
(for water boxes as required) Rupture Disc A. Rupture disc assy A. Vent line and flexible connector Insulation A. Insulation (Optional) A. Insulation
8
CDHF-SVN01B-EN
General Information
Unit Shipment
Each chiller ships from the factory as a hermetically assembled package; it is factory piped, wired and tested. All openings are covered or plugged to prevent contamination during shipment and handling.
See Figure 2 for an illustration of a typical unit and its components. As soon as the unit arrives at the job site, inspect it thoroughly for damage and material shortages. In addition:
1. Verify the chiller’s hermetic integrity by checking the evaporator pressure for an indication of holding charge pressure.
Note: Since there are two refrigerant circuits both must be checked.
To prevent damaging moisture from entering the unit and causing corrosion, each chiller is pressurized with dry nitrogen before shipment.
Note: The holding charge should register approximately 5 psig (at sea level) on the gauge. If the charge has escaped, contact your local Trane sales office for instructions.
2. Check the oil sump sight glasses to verify that the sump was factory-charged with 9 gallons of oil. If no oil level is visible, contact your local Trane sales office.
3. Compare the unit nameplate data (including electrical characteristics) with the corresponding ordering and shipping information to verify that the correct unit was shipped to the job site.
If a thorough inspection of the chiller reveals damage or material shortages, be sure to file these claims with the carrier immediately. Specify the extent and type of damage found, and notify the appropriate Trane sales representative. Do not install a damaged unit without the sales representative’s approval!
Storage
If the chiller will be stored at the job site for an extended period of time before it is installed, exercise these precautionary measures to protect the unit from damage:
1. Do not remove the protective coverings factory-installed on the control panel and compressor inlet vane actuator for shipment.
2. Store the chiller in a dry vibration free and secure area. If factory insulated, protect chiller from prolonged exposure to sunlight.
CAUTION Insulation Damage!
To prevent damage to the factory­installed insulation, do not allow excessive exposure to sunlight.
3. Periodically check the condenser and evaporator pressure to verify that the 5 psig dry nitrogen at 72°F ambient holding charge is still in the chiller. If this charge escapes, contact a qualified service organization and the Trane sales engineer that handled the order.
Note: The storage range for the microcomputer-based devices in the unit control panel is -40°F to 158°F (-40°C to 70°C).
CDHF-SVN01B-EN
9
Figure 2 – Typical CDHF Chiller
General Information
10
CDHF-SVN01B-EN
General Information
Recommended Unit Clearances
Adequate clearance around and above the chiller is required to allow sufficient access for service and maintenance operations.
Figure 3 illustrates the recommended clearances for units with and without options. Figure 4 shows tube bundle locations. Notice that, in each instance, the minimum vertical clearance above the chiller is 3-feet.
In addition, be sure to provide at least 3-feet of working space in front of the unit control panel to satisfy the National Electrical Code, and/or local codes.
Important! Do not install piping or conduit above the compressor motor assembly or behind the suction elbow!
Note: Specific unit clearance requirements are also indicated in the submittal package provided for your unit.
Operating Environment
Besides assuring that the site selected for chiller installation provides the necessary clearances, consider the equipment’s operating environment.
To assure that electrical components operate properly, do not locate the chiller in an area exposed to dust, dirt, corrosive fumes, or excessive heat and humidity. Note that the maximum ambient temperature for chiller operation is 95 to 100°F (35° ­38° C).
CAUTION Equipment Failure!
CDHF operation at ambient temperatures exceeding 100°F (38°C) can fatigue the unit’s rupture disc, causing it to break at a reduced refrigerant pressure (i.e., <15 psig). Starter component damage can also occur because of the panel’s inability to dissipate heat adequately.
If any of these adverse operating conditions are present, take whatever action is necessary to improve the equipment room environment.
Foundation Requirements
Provide rigid, non-warping mounting pads or a concrete foundation as a mounting surface for the chiller. Ensure that the base is of sufficient strength and mass to properly support the chiller at its full operating weight (i.e., including completed piping, and full operating charges of refrigerant, oil and water).
For your convenience, a summary of standard unit shipping and operating weights is provided in Table 2.
Notice that the floor loading for all sizes of chillers is 60 pounds per square inch.
To assure proper unit operation, the chiller must be level within 1/16” over its length and width when set into place on the mounting surface.
Trane will not assume responsibility for equipment problems resulting from an improperly designed or constructed foundation.
CDHF-SVN01B-EN
11
General Information
Figure 3 – Clearance Requirements for Standard CDHF
Notes:
1. Per NEC Article 110 - Unit mounted starters from 0-600V require 42" clearance; 601-2500V require 48" clearance; 2501-9000V require 60" clearance.
2. Clearance 1 can be at either end of machine and is required for tube pull clearance Clearance 2 is always at the opposite end of machine from Clearance1 and is required for service clearance
3. Clearance requirement for evaporator tube removal does not include water box. Add water box dimension to this figure.
UCP Clearance Requirements for Standard CDHF
CL1 CL2
Shell Width Entire Width Height Length Entire Length Clearance 1 Clearance 2
210 D 130.875 184.875 132.750 258.000 606.000 264.000 84.000 250 D 142.625 196.625 136.875 258.000 606.000 264.000 84.000
250 M 142.625 196.625 141.375 312.000 714.000 318.000 84.000
250 X 142.625 196.625 141.375 360.000 810.000 366.000 84.000
12
CDHF-SVN01B-EN
General Information
Figure 4 – Tube Bundle Locations for Model CDHF Units
Cooling Only and Free Cooling Units
EVSZ CDSZ A B C D E F G H 210 D 210 D 4’-5-7/16" 5"-3/8" 7’-9/16" 1’-4-1/4" 5’-0-1/8" 3’-5-1/4" 2’-5" 3’-10-3/16" 250 D 250 D 5’-0-3/4" 5"-1/4 6"-1/2 1’-7-1/4" 5’-8-3/4" 3’-10-5/8" 2’-4-1/8" 3’-11-5/8"
250 M 250 M 5’-0-3/4" 5"-1/4 6"-1/2 1’-7-1/4" 5’-8-3/4" 3’-10-5/8" 2’-4-1/8" 3’-11-5/8"
250 X 250 X 5’-0-3/4" 5"-1/4 6"-1/2 1’-7-1/4" 5’-8-3/4" 3’-10-5/8" 2’-4-1/8" 3’-11-5/8"
CDHF-SVN01B-EN
13
General Information
Table 2 – Typical Shipping and Operating Weights
Operating Weight Shipping Weight TYPE NTON CPKW EVSZ CDSZ (lbs) (kg) (lbs) (kg) CDHF 1500-2000 957 210D 210D 80171 36366 68629 31130 CDHF 2100-2500 1228 250D 250D 93186 42269 79213 35931 CDHG 1250-1750 716 210D 210D 82349 37354 70807 32118 CDHG 2150 892 210D 210D 89680 197710 78288 172595 CDHG 2150 892 250D 250D 96964 43983 82991 37645 CDHF 3000 1340 250M 250M 106659 48381 89425 40563 CDHF 3500 1340 250X 250X 114445 51912 95077 43127
Notes: Weights shown above are accurate within +/- 3% and are based on the following Operating weights include refrigerant, oil charge and water Shells are with largest bundles and TECU .028 wall tubes Compressor weight with medium voltage motor and above CPKW Starter weights not included Waterboxes are 1 pass, 150 psig Non-Marine For other configurations refer to submittal package
14
CDHF-SVN01B-EN
General Information
Note: Immediately report any unit damage incurred during handling or installation at the job site to the Trane sales office.
Rigging
Lifting is the recommended method for moving chillers. Suggested lifting arrangements for standard units are illustrated in Figure 5.
Note that each of the cables used to lift the unit must be capable of supporting the entire weight of the chiller. (See Table 2 for unit shipping and operating weights.) Notice that the lifting beam used to lift the unit must be at least 23 feet long.
See Figure 5 and Table 2 for guidance in selecting cable or sling lengths.
WARNING
Test Lift!
Verify chiller remains horizontal.
To avoid serious injury and possible equipment damage, lift the chiller horizontally; use the lifting arrangement and rigging shown in Figure 5. Failure to lift unit as recommended could result in death or serious injury or lead to equipment damage.
To lift the chiller properly, insert clevis connections at the points indicated in Figure 5; a 2-1/2” diameter lifting hole is provided at each of these points. Next, attach the lifting cables or slings.
Once the lifting cables are in place, attach a safety cable or sling between the first-stage casting of the compressor and the lifting beam. To do this, remove a retaining bolt from the compressor first-stage casting and replace it with an eyebolt, or swivel clevis.
Note: There should not be tension on this safety cable; it is used only to prevent the unit from rolling during the lift.
When the lift is completed, detach the clevis connections and safety chain, then remove the eyebolt that was used to secure the safety chain to the compressor, and reinstall the retaining bolt in its place. If the chiller cannot be moved using the conventional rigging method just described, consider these points.
1. If job site conditions require rigging of the chiller at an angle greater than 45° from horizontal (end-to-end), dowel-pin the com­pressor and remove it from the unit. Be sure to contact a qualified service organization for specific rigging instructions.
2. When lifting the chiller is either impractical or undesirable, attach cables or chains to the jacking slots shown in Figure 5; then push or pull the unit across a smooth surface. Should the chiller be on a shipping skid, it is not necessary to remove the shipping skid from the chiller before moving it into place.
CAUTION Equipment Damage!
To prevent possible equipment damage, do not use a fork lift to move the chiller!
CAUTION Compressor Alignment!
Lifting the compressor/motor assembly from the shells without factory-installed doweling in the compressor casting flanges may result in misalignment of the compressor castings.
3. Position isolator pads (or spring isolators) beneath the chiller feet; see “Unit Isolation” section for instructions.
4. Once the isolators are in place, lower the chiller; again, work from end to end in small increments to maintain stability.
CDHF-SVN01B-EN
CAUTION Oil Loss!
To prevent oil migration out of the oil tank during lifting procedures, remove the oil from the oil tank if the unit will be lifted at any angle greater than 15° from horizontal end-to-end. If oil is allowed to run out of the oil tank into other areas of the chiller, it will be extremely difficult to return the oil to the oil tank even during operation.
15
General Information
Figure 5 – Recommended Lifting Arrangements for CDHF
Y
B
Jacking
A
Points
Safety
C
Chain
X
Safety
Chain
H
LIFTING
BEAM
TYPE NTON EVSZ CDSZ X Y H CDHF 1500-2000 210D 210D 143 in. 23 ft 24.75 in CDHF 2100-2500 250D 250D 143 in. 23 ft 24.75 in CDHG 1250-1750 210D 210D 143 in. 23 ft 24.75 in CDHG 2150 210D 210D 143 in. 23 ft 24.75 in CDHG 2150 250D 250D 143 in. 23 ft 24.75 in CDHF 3000 250M 250M 172 in. 27.5 ft 24.75 in CDHF 3500 250X 250X 199 in. 31.5 ft 24.75 in
Notes:
1. Lifting chains (or cables) are not the same length between point A and B, or between points A and C. Adjust as necessary for an even lift.
2. Lifting holes provided on chillers to attach chains are 2 1/2 inch in diameter.
3. Attach safety chain (or cable) as shown, and without tension. The safety chain is not used for lifting, but is there to prevent the unit from rolling.
4. Do not fork-lift the unit.
16
CDHF-SVN01B-EN
General Information
Unit Isolation
To minimize sound and vibration transmission through the building structure - and to assure proper weight distribution over the mounting surface, always install isolation pads or spring isolators under the chiller feet.
Note: Isolation pads (Figure 6) are provided with each chiller unless spring isolators are specified on the sales order.
Note: The center support is approximately 1/2" shorter (higher) than the end supports. After unit leveling, shim the center isolator pads. If spring isolators are used, shim the isolators for the center support. See Figure 7.
Specific isolator loading data is provided in the unit submittal package. If necessary, contact your local Trane sales office for further information.
Important! When determining placement of isolation pads or spring isolators, remember that the control panel side of the unit is always designated as the unit front.
Isolation Pads
When the unit is ready for final placement, position isolation pads under the chiller feet as shown in Figure 7.
Remember that the chiller must be level within 1/16” over its length and width after it is lowered onto the isolation pads. In addition, all piping connected to the chiller must be properly isolated and supported so that it does not place any stress on the unit.
Spring Isolators
Spring isolators should be considered whenever chiller installation is planned for an upper story location. Base isolator selection and placement on the information presented in Figures 8-10a. (Notice that 3 types of spring isolators - each with its own maximum loading characteristics are used with CDHF chillers).
Spring isolators typically ship assembled and ready for installation. To install and adjust the isolators properly, follow the instructions given.
Note: Do not adjust the isolators until the chiller is piped and charged with refrigerant and water.
1. Position the spring isolators under the chiller as shown in Figures 8 and 9. Make sure that each isolator is centered in relation to the tube sheet.
Note: Spring isolators shipped with the chiller are not identical! Be sure to compare the data provided in the unit submittal package and Figures 8 through 10a to determine proper isolator placement.
2. Set the isolators on the sub-base; shim as necessary to provide a flat, level surface at the same elevation for the end supports, and approximately 1/2" higher for the center support. Be sure to support the full underside of the isolator base plate; do not straddle gaps or small shims.
[8-10 mm]
CDHF-SVN01B-EN
Figure 6 – Isolation Pad
18"
[457 mm]
5/16-3/8"
6"
[152.4 mm]
17
General Information
Figure 7 – Isolation Pad Placement - CDHF, CDHG
Important: Center support is 1/2" (13mm) shorter than end supports. Requires 1/2" steel shim under pad for Center Support at installation after leveling.
Isolation Pad Loading (lb) TYPE NTON CPKW EVSZ CDSZ Left Pad Center Pad Right Pad CDHF 1500-2000 957 210D 210D 25150 26718 28304 CDHF 2100-2500 1228 250D 250D 29292 31056 32838 CDHG 1250-1750 716 210D 210D 25997 27446 28907 CDHG 2150 892 210D 210D 26507 29850 33322 CDHG 2150 892 250D 250D 20680 32316 33967 CDHF 3000 1340 250M 250M 33527 35546 37586 CDHF 3500 1340 250X 250X 35975 38140 40330
TYPE NTON CPKW EVSZ CDSZ Left Pad Center Pad Right Pad CDHF 1500-2000 957 210D 210D 11408 12119 12839 CDHF 2100-2500 1228 250D 250D 13287 14087 14895 CDHG 1250-1750 716 210D 210D 11792 12449 13112 CDHG 2150 892 210D 210D 58438 65808 73462 CDHG 2150 892 250D 250D 13916 14659 15407 CDHF 3000 1340 250M 250M 15208 16123 17049 CDHF 3500 1340 250X 250X 16318 17300 18294
Notes: Isolator pad loading is based on the following Operating weights include refrigerant, oil charge and water Shells are with largest bundles and TECU .028 wall tubes Compressor weight with medium voltage motor and above CPKW Starter weights not included Waterboxes are 1 pass, 150 psig Non-Marine For other configurations refer to submittal package
18
Isolation Pad Loading (kg)
CDHF-SVN01B-EN
General Information
Figure 8 – Spring Isolator Placement - CDHF, CDHG
Estimated Spring Isolator Loading (lb) TYPE NTON CPKW EVSZ CDSZ LF MF RF LR MR RR CDHF 1500-2000 957 210D 210D 14120 14948 15785 11029 11770 12519 CDHF 2100-2500 1228 250D 250D 13861 14721 15591 15431 16334 17247 CDHG 1250-1750 716 210D 210D 14432 15193 15960 11564 12253 12947 CDHG 2150 892 210D 210D 15623 17428 19299 10884 12422 14023 CDHG 2150 892 250D 250D 14413 15209 16012 16267 17108 17955 CDHF 3000 1340 250M 250M 15865 16850 17845 17663 18696 19741 CDHF 3500 1340 250X 250X 17023 18080 19148 18952 20060 21182
Estimated Spring Isolator Loading (kg) TYPE NTON CPKW EVSZ CDSZ LF MF RF LR MR RR CDHF 1500-2000 957 210D 210D 6405 6780 7160 5003 5339 5679 CDHF 2100-2500 1228 250D 250D 6287 6678 7072 7000 7409 7823 CDHG 1250-1750 716 210D 210D 6546 6892 7239 5246 5558 5873 CDHG 2150 892 210D 210D 34443 38422 42547 23995 27386 30915 CDHG 2150 892 250D 250D 6538 6899 7263 7379 7760 8145 CDHF 3000 1340 250M 250M 7196 7643 8095 8012 8480 8954 CDHF 3500 1340 250X 250X 7722 8201 8686 8597 9099 9608
Notes: Vibration isolator loading is based on the following Operating weights include refrigerant, oil charge and water Shells are with largest bundles and TECU .028 wall tubes Compressor weight with medium voltage motor and above CPKW Starter weights not included Waterboxes are 1 pass, 150 psig Non-Marine For other configurations refer to submittal package
CDHF-SVN01B-EN
19
General Information
Figure 9 – Chiller Foot/Isolator Orientation
Side View of Unit
Center tube sheet support leg
Center of Isolator Spring
Note: The spring isolator must be centered in relation to the tube sheet. Do not align the isolator with the flat part of the chiller foot, because the tube sheet is often off-center.
3. If required, bolt the isolators to the floor through the slots provided, or cement the pads.
Note: Fastening the isolators to the
floor is not necessary unless specified.
4. If the chiller must be fastened to the isolators, insert capscrews through the chiller base and into the holes tapped in the upper housing of each isolator. However, do not allow the screws to protrude below the underside of the isolator upper housing. An alternative method of fastening the chiller to the isolators is to cement the neoprene pads.
5. Set the chiller on the isolators; refer to “Rigging” for lifting instructions.
The weight of the chiller will force
the upper housing of each isolator down, perhaps causing it to rest on the isolator’s lower housing. (Figure 10, 10a illustrates spring isolator construction.)
6. Check the clearance (labeled X in Figure 10, 10a ) on each isolator. If this dimension is less than 1/4” on any isolator, use a wrench to turn the adjusting bolt one complete revolution upward.
Note: When the load is applied to
the isolators (Step 5), the top plate of each isolator moves down to compress the springs until either:
a. The springs support the load; or
b. The top plate rests on the
bottom housing of the isolator.
1. If the springs are supporting
End View of Unit
Outside edge of tube sheet
Note: Place isolator near outside edge of tube sheet as shown.
the load, screwing down on the adjusting bolt (Step 7) will immediately begin to raise the chiller.
End of tube sheet
7. Turn the adjusting bolt on each of the remaining isolators to obtain the required minimum clearance at X (Figure 10, 10a ) of 1/4”.
8. Once the minimum required clearance is obtained on each of the isolators, level the chiller by turning the adjusting bolt on each of the isolators on the low side of the unit. Be sure to work from one isolator to the next. Remember that the chiller must be level to within 1/16”: over its length and width, and that clearance X of each isolator must be at least 1/4 inch.
20
CDHF-SVN01B-EN
General Information
Figure 10 – Typical Spring Isolator Types and Construction
Type CT-4 Spring Isolators
5/8" [16 mm]
9-1/4" [235 mm] C-C foundation bolts
6-1/2" [165 mm]
Free Height
7-1/2" [191 mm]
10-1/4"
[260 mm]
Adjusting Bolt
Adjust the isolator so that the upper housing clears the lower housing by at least 1/4” [6 mm]
Acoustical nonskid neoprene pad (top and bottom)
Isolator Maximum Spring
Type Load Deflection Color
and Size (lbs.) (Inches) Coding
CT-4-25 1,800 1.22 Red CT-4-26 2,400 1.17 Purple CT-4-27 3,000 1.06 Orange CT-4-28 3,600 1.02 Green CT-4-31 4,400 0.83 Gray CT-4-32 5,200 0.74 White
Isolator Maximum Spring
Type Load Deflection Color
and Size (Kg) (mm) Coding
CT-4-25 816 31 Red CT-4-26 1,089 30 Purple CT-4-27 1,361 27 Orange CT-4-28 1,633 26 Green CT-4-31 1,996 21 Gray CT-4-32 2,359 19 White
Type CT-7 Spring Isolators
5/8" [16 mm]
8-3/4" [222 mm] C-C foundation bolts
6-5/8" [168
mm] Free
Height
5/8" [16 mm]
7-1/4"
[184 mm]
9-3/4"
[248 mm]
Adjust the isolator so that the upper housing clears the lower housing by at least 1/4” [6 mm]
Adjusting Bolt
Acoustical nonskid neoprene pad (top and bottom)
Isolator Maximum Spring
Type Load Deflection Color
and Size (lbs.) (Inches) Coding
CT-7-25 3,150 1.22 Red CT-7-26 4,200 1.17 Purple CT-7-27 5,250 1.06 Orange CT-7-28 6,300 1.02 Green CT-7-31 7,700 0.83 Gray CT-7-32 9,100 0.74 White
Isolator Maximum Spring
Type Load Deflection Color
and Size (Kg) (mm) Coding
CT-7-25 1,429 31 Red CT-7-26 1,905 30 Purple
CT7-27 2,381 27 Orange CT-7-28 2,858 26 Green CT-7-31 3,493 21 Gray CT-7-32 4,128 19 White
CDHF-SVN01B-EN
21
General Information
Figure 10A – Typical Spring Isolator Types and Construction
CT-12 Spring Isolators
14-3/4" [375 mm]
7-3/8" [187 mm]
6-1/2"
[165 mm]
6-5/8"
[168 mm]
7"
[178
mm]
3-1/2"
[89 mm]
5/8"
[16 mm]
12-1/2"
[318 mm]
13-1/4" [337 mm]
Isolator Max Deflection Spring Type/Size Load lb (kg) inches (mm) Color Code CT-12-25 5,400 1.22 Red
CT-12-26 7,200 1.17 Purple CT-12-27 9,000 1.06 Orange CT-12-28 10,800 1.02 Green CT-12-31 13,200 0.83 Gray CT-12-32 15,600 0.74 White
8-1/8" [206
mm] Free
Height
5/8"
[16 mm]
(2) Adjusting Bolts
Adjust the isolator so that the upper housing clears the lower housing by at least 1/4” [6.4 mm]
Acoustical nonskid neoprene pad (top and bottom)
22
CDHF-SVN01B-EN
CT-16 and CT20 Spring Isolators
General Information
Isolator Max Deflection Spring Type/Size Load lb (kg) inches (mm) Color Code CT 16-26 9600 (4355) 1.17 (29.7) Purple
CT 16-27 12000 (5443) 1.06 (26.9) Orange CT 16-28 14400 (6532) 1.02 (25.9) Green CT 16-31 17600 (7983) 0.83 (21.1) Gray CT 16-32 20800 (9435) 0.74 (18.8) White
Isolator Max Deflection Spring Type/Size Load lb (kg) inches (mm) Color Code
CT 20-26 12000 (5443) 1.17 (29.7) Purple CT 20-27 15000 (6804) 1.06 (26.9) Orange CT 20-28 18000 (8165) 1.02 (25.9) Green CT 20-31 22000 (9979) 0.83 (21.1) Gray CT 20-32 26000 (11794) 0.74 (18.8) White
CDHF-SVN01B-EN
23
General Information
Unit Leveling
Follow the instructions outlined below and illustrated in Figure 11 to determined whether or not the chiller is set level.
1. Measure an equal distance up from each foot of the chiller (identified as X in Figure 11) and make a punch mark at each measured distance.
2. Suspend a clear plastic tube along the length of the chiller as shown in Figure 11.
Figure 11 – Checking Unit Levelness
Raise chiller at one end to align match marks with water level.
3. Fill the tube with water until the level aligns with the punch mark at one end of the chiller; then check the water level at the opposite mark.
If the water level does not align with the punch mark, use full­length shims to raise one end of the chiller until the water level at each end of the tube aligns with the punch marks at both ends of the chiller
4. Once the unit is level across its length, repeat Steps 1 through 3 to see if unit is level across the width.
5. If isolation pads have been used, shim the center support.
Measure and mark an equal distance up from each chiller foot.
Clear Plastic Tube (Fill tube with water to punch mark.)
24
CDHF-SVN01B-EN
Loading...
+ 56 hidden pages