Digital Display
Zone Sensor
Figure 1: Digital Display Zone Sensor
The digital display zone sensor has the
functionality of the full-featured Trane
DDC zone sensor with a liquid crystal
display (LCD). The zone sensor is
compatible with Trane VAV and VariTrac
controllers. The display can be toggled in
the field from zone temperature to zone
setpoint and can be viewed in either
Fahrenheit or Celsius. A communications
jack is provided for Trane portable edit
terminal devices. Additionally, the On/
Cancel buttons allow the system to run in
the occupied mode during nighttime
operation. The ability to override to
maximum and minimum airflow or
position for field balancing is included in
the sensor. Please visit
contact a local Trane representative for
more information.
Table 1: Sensor Specifications
Thermistor Resistance Rating 10k OHM at 77°F (25°C)
Accuracy at 77°F (25°C) 0.4°F (0.2°C)
Setpoint Resistance Rating 500 Ohms at 70°F (21.2°C)
Display Zone Temperature Range 40 to 99°F (10 to 35°C)
Display Setpoint Range 50 to 90°F (10 to 32°C)
Operating Temperature 0 to 120°F (-18 to 49°C)
Storage Temperature -20 to 130°F (-29 to 54°C)
Humidity Range 5 to 95% non-condensing
Power Supply 24 VAC
Maximum VA load 4 VA
Housing Material Rigid Vinyl
Dimensions 4.5” x 2.8” x 1.1”
trane.com
®
or
Features
LCD Readout of Zone Temperature
or Setpoint
Selectable °F or °C Display
Communication Jack
Occupied Mode Override
Maximum and Minimum Override
(114 mm x 71 mm x 28 mm)
©2002 American Standard, Inc. All rights reserved
VAV-SLB007-EN
Placement of the Sensor
Choose a mounting location on an
interior wall near the return air grille,
about five feet above the floor level,
where air circulates freely and is of
average temperature for the zone.
Figure 2: Dimensional Data
AVOID areas such as:
Behind doors
On outside walls or walls facing
uncontrolled areas
In direct sunlight, or sources of radiant
heat that could effect temperature
measurement
In line with discharge air from unit being
controlled
2.8”
(71 mm)
˚F
˚C
MAX
SETPOINT
OVERRIDE
UNNOC
4.5”
ON
CANCEL
(114 mm)
Table 2: Wiring Terminations at Sensor
TB1-1 24 VAC Power Supply
TB1-2 24 V Ground
TB2-1 Zone Temperature
TB2-2 Zone Sensor Ground
TB2-3 Zone Setpoint
TB3-1 Communication +
TB3-2 Communication -
3.3”
(84 mm)
2.1”
(53 mm)
Trane
An American Standard Company
www.trane.com
For more information contact
your local district office or
e-mail us at comfort @trane.com
1.1”
(28 mm)
Literature Order Number VAV-SLB007-EN
File Number SB-TD-VAV-000-SLB007-EN-0602
Supersedes New
Stocking Location La Crosse
Trane has a policy of continuous product and product data improvement and reserves the right to change design
and specifications without notice.