Trane Tracer CH530, CG-SVU02E-GB User Manual

Page 1
Tracer CH530™ Control System for Scroll Chillers CGAN/CXAN 209-214 CGCL 200-600 CGWH/CCUH 115-250 CGWN/CCUN 205-215 RAUL 190-800
CG-SVU02E-GB
Page 2
General information
CG-SVU02E-GB2
Foreword
These instructions are given as a guide to good practice in the installation, start-up, operation, and maintenance by the user, of Trane CH530 chiller control system on scroll chillers. They do not contain full service procedures necessary for the continued successful operation of this equipment. The services of a qualified technician should be employed through the medium of a maintenance contract with a reputable service company. Read this manual thoroughly before unit start-up.
Warnings and cautions
Warnings and Cautions appear at appropriate sections throughout this manual. Your personal safety and the proper operation of this machine require that you follow them carefully. The constructor assumes no liability for installations or servicing performed by unqualified personnel.
WARNING! : Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION! : Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices or for equipment or property-damage-only accidents.
Safety recommendations
To avoid death, injury, equipment or property damage, the following recommendations should be observed during maintenance and service visits:
1. Disconnect the main power supply before any servicing on the unit.
2. Service work should be carried out only by qualified and experienced personnel.
Reception
On arrival, inspect the unit before signing the delivery note.
Reception in France only:
In case of visible damage: The consignee (or the site representative) must specify any damage on the delivery note, legibly sign and date the delivery note, and the truck driver must countersign it. The consignee (or the site representative) must notify Trane Epinal Operations - Claims team and send a copy of the delivery note. The customer (or the site representative) should send a registered letter to the last carrier within 3 days of delivery.
Reception in all countries except France:
In case of concealed damage: The consignee (or the site representative) must send a registered letter to the last carrier within 7 days of delivery, claiming for the described damage. A copy of this letter must be sent to Trane Epinal Operations - Claims team.
Note: for deliveries in France, even concealed damage must be looked for at delivery
and immediately
treated as visible damage.
Page 3
General information
3CG-SVU02E-GB
Warranty
Warranty is based on the general terms and conditions of the manufacturer. The warranty is void if the equipment is repaired or modified without the written approval of the manufacturer, if the operating limits are exceeded or if the control system or the electrical wiring is modified. Damage due to misuse, lack of maintenance or failure to comply with the manufacturer's instructions or recommendations is not covered by the warranty obligation. If the user does not conform to the rules of this manual, it may entail cancellation of warranty and liabilities by the manufacturer.
Maintenance contract
It is strongly recommended that you sign a maintenance contract with your local Service Agency. This contract provides regular maintenance of your installation by a specialist in our equipment. Regular maintenance ensures that any malfunction is detected and corrected in good time and minimizes the possibility that serious damage will occur. Finally, regular maintenance ensures the maximum operating life of your equipment. We would remind you that failure to respect these installation and maintenance instructions may result in immediate cancellation of the warranty.
Training
To assist you in obtaining the best use of it and maintaining it in perfect operating condition over a long period of time, the manufacturer has at your disposal a refrigeration and air conditioning service school. The principal aim of this is to give operators and technicians a better knowledge of the equipment they are using, or that is under their charge. Emphasis is particularly given to the importance of periodic checks on the unit operating parameters as well as on preventive maintenance, which reduces the cost of owning the unit by avoiding serious and costly breakdown.
Page 4
Contents
CG-SVU02E-GB4
General Information 2
Overview 5
DynaView Interface 6
Display Screens 8
Diagnostics 29
TechView Interface 40
Software Download 41
Page 5
Overview
5CG-SVU02E-GB
The Trane CH530 control system that runs the chiller consists of several elements:
• The main processor collects data, status, and diagnostic information and communicates commands to the
LLID (for Low
Level Intelligent Device)
bus. The main processor has an integral display (DynaView).
LLID bus
. The main processor communicates to each input and output device (e.g. temperature and pressure sensors, low voltage binary inputs, analog input/output) all connected to a four-wire bus, rather than the conventional control architecture of signal wires for each device.
• The
communication interface
to a building automation system (BAS).
•A
service tool
to provide all service/maintenance capabilities. Main processor and service tool (TechView) software is downloadable from
www.Trane.com
. The process is discussed later in this section under TechView Interface. DynaView provides bus management. It has the task of restarting the link, or filling in for what it sees as "missing" devices when normal communications has been degraded. Use of TechView may be required.
The CH530 uses the IPC3 protocol based on RS485 signal technology and communicating at 19.2 Kbaud to allow 3 rounds of data per second on a 64-device network. Most diagnostics are handled by the DynaView. If a temperature or pressure is reported out of range by a LLID, the DynaView processes this information and calls out the diagnostic. The individual LLIDs are not responsible for any diagnostic functions.
Note:
It is imperative that the CH530 Service Tool (TechView) be used to facilitate the replacement of any LLID or reconfigure any chiller component
.
Controls Interface
DynaView (picture on cover)
Each chiller is equipped with the DynaView interface. DynaView has the capability to display additional information to the advanced operator including the ability to adjust settings. Multiple screens are available and text is presented in multiple languages as factory­ordered or can be easily downloaded online.
Te c h V i e w
TechView can be connected to the DynaView module and provides further data, adjustment capabilities, diagnostics information, downloadable software, and downloadable languages.
Page 6
DynaView Interface
CG-SVU02E-GB6
Power Up
On power-up, Dynaview will progress through 3 screens.
The first screen (Figure 1) will display for 3-10 seconds. This screen will give the status of the Application software, the Boot Software P/N, selftest results and the application part number. The contrast is adjustable from this screen. The message "Selftest passed" may be replaced with "Err2: RAM Error" or 3Err3: CRC Failure"
Figure 1
Figure 2
Note that the Application and Boot software numbers will vary according to the unit type.
If no application is found, the screen (Figure 2) will display instead of Figure 1.
Page 7
DynaView Interface
7CG-SVU02E-GB
The second screen (Figure 3) will display for 15-25 seconds. If a valid configuration is present, "Tracer CH530" will also be displayed. If the MP configuration is found to be invalid, "MP: Invalid Configuration" is displayed indefinitely. Contact your local Trane service technician.
Figure 3
Figure 4
7
7
The third screen is the first screen of the application.
Page 8
DynaView Interface
CG-SVU02E-GB8
The display on DynaView is a 1/4 VGA display with a resistive touch screen and an LED backlight. The display area is approximately 4 inches wide by 3 inches high (102mm x 60mm).
CAUTION!
Equipment Damage! Putting excessive pressure on the touch screen could cause damage. It takes less than 7 kg of force to break the screen.
In this touch screen application, key functions are determined completely by software and change depending upon the subject matter currently being displayed. The basic touch screen functions are outlined below.
Radio Buttons
Radio buttons show 1 menu choice among 2 or more alternatives, all visible. The possible selections are each associated with a button. The selected button is darkened, presented in reverse video to indicate it is the selected choice. The full range of possible choices as well as the current choice is always in view.
Spin Value Buttons
Spin values are used to allow a variable setpoint to be changed, such as leaving water setpoint. The value increases or decreases by touching the (+) or (-) arrows.
Action Buttons
Action buttons appear temporarily and provide the user with a choice such as Enter or Cancel.
File Folder Tabs
File folder tabs are used to select a screen of data. The tabs are in 1 row across the top of the display. The user selects a screen of information by touching the appropriate tab.
Display Screens
The main body of the screen is used for description text, data, setpoints, or keys (touch sensitive areas). The Chiller Mode is displayed here. A double arrow pointing to the right indicates more information is available about the specific item on that same line. Pressing it will bring you to a sub-screen that will present the information or allow changes to settings.
Figure 5 - Basic Screen Format
Main Reports Settings
Auto Stop Alarms
1 2 3
4
5
6
7
8
9
Page 9
DynaView Interface
9CG-SVU02E-GB
The bottom of the screen (7) is present in all screens and contains the following functions. The contrast (8,9) may require re-adjustment at ambient temperatures significantly different from those present at last adjustment. The other functions are critical to machine operation. The AUTO and STOP keys are used to enable or disable the chiller. The key selected is in black (reverse video). The chiller will stop when the STOP key is touched and after completing the Run Unload mode.
Touching the AUTO key will enable the chiller if no diagnostic is present. (A separate action must be taken to clear active diagnostics.) The AUTO and STOP keys take precedence over the Enter and Cancel keys. (While a setting is being changed, AUTO and STOP keys are recognized even if Enter or Cancel has not been pressed.) The ALARMS button appears only when an alarm is present, and blinks (by alternating between normal and reverse video) to draw attention to a diagnostic condition. Pressing the ALARMS button takes you to the corresponding tab for additional information.
Keypad/Display Lockout Feature
Note:
The DynaView display and Touch Screen Lock screen is shown above. This screen is used if the Display and touch screen and lock feature is enabled. Thirty minutes after the last keystroke, this screen is displayed and the Display and Touch Screen is locked out until the sequence "159 <ENTER>" is pressed.
Until the proper password is entered, there will be no access to the DynaView screens including all reports, setpoints, and Auto/Stop/Alarms/Interlocks. The password "159" can not be changed from either DynaView or TechView.
For setting changes, use the password "314 <ENTER>".
Figure 6 - Keypad
1
Page 10
DynaView Interface
CG-SVU02E-GB10
Main Screens
The Main screen shall be the default screen. After an idle time of 30 minutes the CH530 shall display the Main screen with the first data fields. The remaining items (listed in the following table) will be viewed by selecting the up/down arrow icons.
Figure 7 - Main screen
Main
Main
Reports
Reports
Settings
Settings
Auto
Auto
Stop
Stop
Chiller Mode: Circuit 1 Mode: Circuit 2 Mode: Evap Ent / Lvg Water Temp: Cond Ent / Lvg Water Temp: Active Chilled Water Setpoint:
Running
Running - Limit
Auto
12 / 7 C
30 / 35 C
7 C
Page 11
DynaView Interface
11CG-SVU02E-GB
Table 1 - Main Screen Data Fields Table
Description Units Resolution Dependencies
1. Chiller Mode (>> submodes) enumeration
2. Circuit Mode (>> submodes) enumeration If one circuit chiller
3. Circuit 1 Mode (>> submodes) enumeration If two circuit chiller
4. Circuit 2 Mode (>> submodes) enumeration If two circuit chiller
5. Evap Ent/Lvg Air Temp F / C 0.1
6. Evap Ent/Lvg Water Temp F / C 0.1
7. Cond Ent/Lvg Water Temp F / C 0.1 If option installed
8. Active Chilled Water Setpoint (>>source) F / C 0.1
9. Active Air Temp Setpoint (>>source) F / C 0.1
10. Active Hot Water Setpoint (>>source) F / C 0.1 If option installed
11. External Capacity Control % 1
12. Average Line Current % RLA 1 If option installed
13. Active Demand Limit Setpoint (>>source) % 1
14. Active Ice Termination Setpoint (>>source) F / C 0.1 If option installed
15. Outdoor Air Temperature F / C 0.1 If option installed
16. Software Type enumeration Scroll
17. Software Version X.XX
Figure 8 - Active Chilled Water Subscreen
:
Active Chilled Water Subscreen
The active chilled water setpoint is the setpoint which the unit is currently controlling. It is the result of arbitration between the front panel, BAS, external, and auxiliary setpoints (auxiliary not shown in the following figure), which in cases may be subjected to a form of chilled water reset.
Page 12
DynaView Interface
CG-SVU02E-GB12
The chilled water reset status area in the most right column will display one of the following messages
• Return
• Constant Return
• Outdoor
• Disabled
The left column text "Front Panel", "BAS", "External", "Auxiliary", "Chilled Water Reset", and "Active Chilled Water Setpoint" will always be present regardless of installation or enabling those optional items. In the second column, "-----" will be shown if that option is Not Installed. Otherwise the current setpoint from that source will be shown.
Setpoints that are adjustable from the DynaView (Front Panel chilled water setpoint, Auxiliary chilled water setpoint) will provide navigation to their respective setpoint change screen via a double-arrow to the right of the setpoint source text. The setpoint change screen will look identical to the one provided in the Chiller Setpoints screen. The "Back" button on the setpoint change screen provides navigation back to the setpoint arbitration screen.
The "Back" button on the setpoint arbitration screen provides navigation back to the chiller screen.
Other Active Setpoints
The Active Hot Water Setpoint will behave the same way as the Active Chilled Water Setpoint, with the exception that Hot Water does not have an Auxiliary source. Front Panel Hot Water Setpoint will provide navigation to its setpoint change screen.
The Active Demand Limit Setpoint will behave the same way as the Active Chilled Water Setpoint, except that its units are % and there is an Ice Building source in place of the Auxiliary source. Front Panel Demand Limit Setpoint will provide navigation to its setpoint change screen.
The Active Ice Termination Setpoint will behave the same way as the Active Chilled Water Setpoint, with the exception that Ice Termination does not have an external or auxiliary source.
Page 13
DynaView Interface
13CG-SVU02E-GB
Table 2 - Main screen menu, Chiller Operating Modes - Top Level
Chiller Level Mode
Top Level Mode Description
MP Resetting The main processor is going through reset.
MP Resetting Sub Modes Description
No Chiller Sub-Modes
Chiller Level Mode
Top Level Mode Description
Stopped The chiller is not running either circuit, and cannot run without
intervention.
Stopped Sub Modes Description
Local Stop The chiller is stopped by the DynaView Stop button
command- cannot be remotely overridden.
Immediate Stop The chiller is stopped by the DynaView Immediate Stop
(by pressing the Stop then Immediate Stop buttons in succession) - previous shutdown was manually commanded to shutdown immediately.
No Circuits Available The entire chiller is stopped by circuit diagnostics or lockouts
that may automatically clear.
Diagnostic Shutdown - Manual Reset The chiller is stopped by a diagnostic that requires manual
intervention to reset.
Page 14
DynaView Interface
CG-SVU02E-GB14
Chiller Level Mode
Top Level Mode Description
Run Inhibit The chiller is currently being inhibited from starting (and
running), but may be allowed to start if the inhibiting or diagnostic condition is cleared.
Run Inhibit Sub Modes Description
Ice Building Is Complete The chiller is inhibited from running as the Ice Building
process has been normally terminated on the evaporator entering temperature. The chiller will not start unless the ice building command (hardwired input or Building Automation System command) is removed or cycled.
Start Inhibited by BAS Chiller is stopped by Tracer or other BAS system.
Start Inhibited by External Source The chiller is inhibited from starting or running by the "external
stop" hardwired input.
Start Inhibited by Local Schedule The chiller is inhibited from starting or running by the Local
Schedule.
Diagnostic Shutdown - Auto Reset The entire chiller is stopped by a diagnostic that may
automatically clear.
Waiting for BAS Communications The chiller is inhibited because of lack of communication with
the BAS. This is only valid 15 minutes after power up.
Start Inhibited by Low Ambient Temp The chiller is inhibited based on the outdoor air temperature.
Chiller Level Mode
Top Level Mode Description
Auto The chiller is not currently running but can be expected to
start at any moment given that the proper conditions and interlocks are satisfied.
Auto Sub Modes Description
Waiting For Evaporator Water Flow The chiller will wait a user adjustable time in this mode for
evaporator water flow to be established per the flow switch hardwired input.
Waiting For A Need To Cool The chiller will wait indefinitely in this mode, for an evaporator
leaving water temperature higher than the Chilled Water Setpoint plus some control dead-band.
Waiting For A Need To Heat For water cooled (CGWN), the chiller will wait indefinitely in
this mode, for a condenser leaving water temperature lower than the Hot Water Setpoint plus some control dead-band. For a reversible (CXAN) the chiller will wait indefinitely in this mode, for an evaporator leaving water temperature lower than the Hot Water Setpoint plus some control dead-band.
Power Up Delay Inhibit: MIN:SEC On Power up, the chiller will wait for the Power Up Delay
Timer to expire.
Page 15
DynaView Interface
15CG-SVU02E-GB
Chiller Level Mode
Top Level Mode Description
Waiting to Start The chiller is going through the necessary steps to allow the
lead circuit to start.
Waiting to Start Sub Modes Description
Waiting For Condenser Water Flow The chiller will wait a user adjustable time in this mode for
condenser water flow to be established per the flow switch hardwired input.
Chiller Level Mode
Top Level Mode Description
Running At least one circuit on the chiller is currently running.
Running Sub Modes Description
Maximum Capacity The chiller is operating at its maximum capacity.
Capacity Control Softloading The control is limiting the chiller loading due to capacity based
softloading setpoints.
Unit is Building Ice The chiller is Building Ice, and will terminate on the Ice
Termination Setpoint based on the Entering Evap Water Temperature sensor.
Chiller Level Mode
Top Level Mode Description
Running - Limit At least one circuit on the chiller is currently running, but the
operation of the chiller as a whole is being actively limited by the controls. The sub modes that apply to the Running top modes may also be displayed along with the following limit specific modes.
Running - Limit Sub Modes Description
Demand Limit The number of compressors allowed to operate is being
limited to less than the available number of compressors by either the BAS system, the front panel demand limit setpoint or the external demand limit input.
Page 16
DynaView Interface
CG-SVU02E-GB16
Chiller Level Mode
Top Level Mode Description
Shutting Down The chiller is still running but shutdown is imminent. The
chiller is going through a compressor run-unload.
Shutting Down Sub Modes Description
The Evaporator pump is executing the pump off delay timer.
The Condenser pump is executing the pump off delay timer.
Chiller Level Mode
Top Level Mode Description
Misc. These sub modes may be displayed in most of the top level
chiller modes
Misc. Sub Modes Description
Cond Fans Inhibited By Low Pressure The condenser fans are being inhibited from running because
the ambient temperature was below 10°C and the suction pressure status is not good at startup for each circuit.
Hot Water Control For water cooled (CGWN) the chiller is controlling to the
leaving condenser water temperature. For a reversible (CXAN) the reversing valve is in the heating position. This sub-mode is mutually exclusive with the Chilled Water Control mode.
Chilled Water Control For water cooled (CGWN) the chiller is controlling to the
leaving evaporator water temperature. For a reversible (CXAN) the reversing valve is in the cooling position. This sub-mode is mutually exclusive with the Hot Water Control mode
Air Temperature Control For units that cool air instead of water, the unit is controlling
to the leaving evaporator air temperature.
External Capacity Control The unit capacity is controlled by external inputs (an external
system is responsible for generating staging commands)
Manual Evaporator Pump Override The evaporator water pump relay is on due to a manual
command.
Diagnostic Evap Pump Override The evaporator water pump relay is on due to a diagnostic.
Diagnostic Condenser Fan Override The condenser fan relays are on due to a diagnostic.
Manual Condenser Pump Override The condenser water pump relay is on due to a manual
command.
Manual Compressor Control Signal Chiller capacity control is being controlled by DynaView or
TechView.
Supplemental Heater On The supplemental electric heater is on.
Anti-Freeze Heater On The anti-freeze heater is on.
Local Schedule Active - Event X The Local Schedule is active, and has selected Event X's
values to control the chiller.
Evaporator Water Pump Off Delay: MIN:SEC
Condenser Water Pump Off Delay: MIN:SEC
Page 17
DynaView Interface
17CG-SVU02E-GB
Table 2 - Circuit Level Operating Modes:
Circuit Level Mode
Top Level Mode Description
Stopped The circuit is not running, and cannot run without
intervention.
Stopped Sub Modes Description
Diagnostic Shutdown - Manual Reset The circuit has been shutdown on a latching diagnostic.
Front Panel Circuit Lockout The circuit is manually locked out by the circuit lockout setting
- the nonvolatile lockout setting is accessible through either the DynaView or TechView.
Circuit Level Mode
Top Level Mode Description
Run Inhibit The given circuit is currently being inhibited from starting (and
running), but may be allowed to start if the inhibiting or diagnostic condition is cleared.
Run Inhibit Sub Modes Description
Diagnostic Shutdown - Auto Reset The circuit has been shutdown on a diagnostic that may clear
automatically.
Condenser Pressure Limit The circuit is being inhibited from starting due to high
condenser pressure.
No Compressors Available Based on the configured compressor staging sequence, the
circuit cannot run because necessary compressors are being prevented from running.
Circuit Level Mode
Top Level Mode Description
Auto The circuit is not currently running but can be expected to
start at any moment given that the proper conditions are satisfied.
Auto Sub Modes Description
Calibrating EXV This submode is displayed when the EXV is performing a
calibration. A calibration is only performed when the chiller is not running and never more frequently than once every 24 hours or when the chiller is powered on.
Circuit Level Mode
Top Level Mode Description
Waiting to Start The chiller is going through the necessary steps to allow the
lead circuit to start.
Waiting to Start Sub Modes Description
Waiting For EXV Preposition The circuit will wait for the time it takes the EXV to get to its
commanded pre-position prior to starting the compressor. This is typically a relatively short delay and no countdown timer is necessary (less than 15 seconds).
Circuit Level Mode
Top Level Mode Description
Running The compressor on the given circuit is currently running.
Running Sub Modes Description
No Circuit Sub-Modes
Page 18
DynaView Interface
CG-SVU02E-GB18
Circuit Level Mode
Top Level Mode Description
Running - Limit The compressor on the given circuit is currently running in a
limit mode.
Running - Limit Sub Modes Description
Hot Start Limit Additional stages on a given circuit are being held off based
on leaving evaporator temperature.
Condenser Pressure Limit The circuit is being inhibited from loading due to high
condenser pressure.
Low Evaporator Pressure Limit The circuit is being inhibited from loading due to low
evaporator pressure.
Circuit Level Mode
Top Level Mode Description
Preparing Shutdown The circuit is preparing to de-energize the compressor.
Preparing Shutdown Sub Modes Description
Operational Pumpdown The operational pumpdown is enabled and the circuit is
shutting down.
Circuit Level Mode
Top Level Mode Description
Shutting Down The chiller is going through the necessary steps after de-
energizing the compressor.
Shutting Down Sub Modes Description
No Circuit Sub-Modes
Circuit Level Mode
Top Level Mode Description
Misc. These sub modes may be displayed in most of the top level
circuit modes
Misc. Sub Modes Description
Defrosting The circuit is in a defrost operational mode.
Next Defrost Allowed In: MIN:SEC The circuit recently defrosted, but is not being allowed to
defrost again until the timer elapses, even if other criteria for defrost have been met.
Service Pumpdown The circuit is currently performing a service pumpdown.
Compressor X Running A specific compressor is running where X is A or B.
Restart Time Inhibit Cprsr X: MIN:SEC If there is accumulated Restart Inhibit Time, it must expire
before the compressor is allowed to start. X is denoted as compressor A or B.
Circuit is currently performing Hot Gas Bypass, and the circuit will shut down if the timer expires before Hot Gas Bypass is stopped.
Hot Gas Bypass Time Remaining: MIN:SEC
Page 19
DynaView Interface
19CG-SVU02E-GB
Reports Screen
The Reports tab will allow a user to select from a list of possible reports headings.
Each report will generate a list of status items as defined in the following tables.
Figure 9 - Reports screen
Table 3- Reports Screen
Report Menu
Description
1. Evaporator
2. Condenser
3. Compressor
4. ASHRAE Chiller Log
5. Historic Diagnostics
Report name: System Evaporator
Description Resolution Units
1. Evap Entering Water Temp + or - XXX.X Temperature
2. Evap Leaving Water Temp + or - XXX.X Temperature
3. Evap Entering Air Temp + or - XXX.X Temperature
4. Evap Leaving Air Temp + or - XXX.X Temperature
5. Evap Pump 1 Command On, Off Enumeration
6. Evap Pump 2 Command On, Off Enumeration
7. Evap Water Flow Switch Status Flow, No Flow
Main Reports Settings
Auto Stop Alarms
Evaporator Condenser Compressor ASHRAE Chiller Log Historic Diagnostics
Page 20
DynaView Interface
CG-SVU02E-GB20
Report name: Circuit Evaporator
Description Resolution Units
1. Evap Sat Rfgt Temp + or - XXX.X Temperature
2. Suction Pressure XXX.X Pressure
3. Suction Temperature + or - XXX.X Temperature
4. Suction Superheat + or – XXX.X Delta Temperature
5. Active Superheat Setpoint + or – XXX.X Delta Temperature
6. Evap Approach Temp + or – XXX.X Delta Temperature
7. EXV Position St atus Percent
Report name: System Condenser
Description Resolution Units
1. Cond Entering Water Temp + or - XXX.X Temperature
2. Cond Leaving Water Temp + or - XXX.X Temperature
3. Cond Pump 1 Command On, Off Enumeration
4. Cond Pump 2 Command On, Off Enumeration
5. Cond Water Flow Switch Status (Flow, No Flow) Enumeration
6. Outdoor Air Temperature + or - XXX.X Temperature
Report name: Circuit Condenser
Description Resolution Units
1. Cond Sat Rfgt Temp + or - XXX.X Temperature
2. Discharge Pressure XXX.X Pressure
3. Cond Approach Temp + or - XXX.X Temperature
Report name: System Compressor
Description Resolution Units
1. Chiller Running Time: XXXX:XX hr:min
Report name: Circuit Compressor
Description Resolution Units
1. Compressor A Starts: XXXX Integer
2. Compressor A Running Time: XXXX:XX hr:min
3. Compressor B Starts: XXXX Integer
4. Compressor B Running Time: XXXX:XX hr:min
5. Compressor C Starts: XXXX Integer
6. Compressor C Running Time: XXXX:XX hr:min
7. Hot Gas Bypass Total Time XXXX:XX hr:min
Page 21
DynaView Interface
21CG-SVU02E-GB
Report name: System ASHRAE Chiller Log
Description Resolution Units
1. Current Time/Date XX:XX mmm dd, yyyy Date / Time
2. Chiller Mode: Enum
3. Active Chilled Water Setpoint: XXX.X Temperature
4. Active Air Temperature Setpoint: XXX.X Temperature
5. External Capacity Control XXX Percent
6. Evap Entering Water Temp: XXX.X Temperature
7. Evap Leaving Water Temp: XXX.X Temperature
8. Evap Entering Air Temp: XXX.X Temperature
9. Evap Leaving Air Temp: XXX.X Temperature
10. Evap Water Flow Switch Status: Enum
11. Active Hot Water Setpoint: XXX.X Temperature
12. Cond Entering Water Temp: XXX.X Temperature
13. Cond Leaving Water Temp: XXX.X Temperature
14. Cond Water Flow Switch Status: Enum
15. Outdoor Air Temperature XXX.X Temperature
16. Active Demand Limit Setpoint XXX Percent
17. Average Line Current % RLA 1
Report name: Circuit ASHRAE Chiller Log
Description Resolution Units
1. Circuit Mode Enum
2. Evap Sat Rfgt Temp XXX.X Temperature
3. Suction Pressure XXX.X Pressure
4. Evap Approach Temp: XXX.X Temperature
5. Cond Sat Rfgt Temp XXX.X Temperature
6. Discharge Pressure XXX.X Pressure
7. Cond Approach Temp: XXX.X Temperature
8. Compressor A Starts: XXXX Integer
9. Compressor A Running Time: XX:XX Hours: Minute
10. Compressor B Starts: XXXX Integer
11. Compressor B Running Time: XX:XX Hours: Minute
12. Compressor C Starts XXXX Integer
13. Compressor C Running Time: XX:XX Hours:Minute
Page 22
DynaView Interface
CG-SVU02E-GB22
Settings Screen
The Settings screen provides a user the ability to adjust settings justified to support daily tasks. The layout provides a list of sub-menus, organized by typical subsystem. This organization allows each subscreen to be shorter in length which should improve the users navigation.
Figure 10 - Settings screen
Settings Menu
Description
1. Unit
2. Feature Settings
3. Control Settings
4. Manual Control Settings
5. Display Settings
Main Reports Settings
Auto Stop Alarms
Unit Feature Settings Control Settings Manual Control Settings Display Settings
Page 23
DynaView Interface
23CG-SVU02E-GB
Unit
Description Units
1. Cool/Heat Command (Cool, Heat), Cool Enum
2. Front Panel Chilled Water Setpt (2) + or - XXX.X Temperature
3. Front Panel Air Temp Setpt + or - XXX.X Temperature
4. Auxiliary Chilled Water Setpt + or - XXX.X Temperature
5. Auxiliary Air Temp Setpt + or - XXX.X Temperature
6. Front Panel Hot Water Setpt + or - XXX.X Temperature
7. Auxiliary Hot Water Setpt + or - XXX.X Temperature
8. Front Panel Demand Limit Setpt XX Percent
9. Front Panel Ice Build Cmd On/Auto Enum
10. Front Panel Ice Termn Setpt + or - XXX.X Temperature
11. Setpoint Source Enum
Feature Settings
Description Units
1. Power-Up Start Delay 10 seconds Seconds (MM:SS)
2. Cooling Low Ambient Lockout (Enable, Disable), Enable Enum
3. Cool Low Ambient Lockout Stpt XXX.X Temperature
4. Heat Low Ambient Lockout Stpt XXX.X Temperature
5. Water Pump Off Delay 1 minute Minutes (HH:MM)
6. Ice Building (Enable, Disable), Disable Enum
7. Superheat Optimize Enable (Enable, Disable), Enable Enum
8. Hot Gas Bypass (Enable,Disable) Enum
9. Hot Gas Bypass Max Time 30 seconds Seconds (MM:SS)
10. Operational Pumpdown (Enable, Disable), Disable Enum
11. Supplemental Heat Enum
12. Local Time of Day Schedule Subscreen (see below)
13. External/BAS Subscreen (see below)
14. Chilled Water Reset Subscreen (see below)
15. Air Temperature Reset Subscreen (see below)
16. Evap Freeze Protection - Pumps Subscreen (see below)
17. Cond Freeze Protection - Pumps Subscreen (see below)
Resolution or (Enumerations), Default
(BAS/Ext/FP, Ext/ Front Panel, Front Panel), BAS/Ext/FP
Resolution or (Enumerations), Default
(Heat Only, Freeze Avoid, Heat & Freeze, Disable), Disable
Page 24
DynaView Interface
CG-SVU02E-GB24
External/BAS Feature Settings (subscreen of Feature Settings)
Description Units
1. Ext Chilled/Hot Water Setpoint (Enable, Disable), Disable Enum
2. Ext Demand Limit Setpoint (Enable, Disable), Disable Enum
3. Maximum Capacity Debounce Time 30 seconds Seconds (MM:SS)
4. Limit Annunc Debounce Time 30 seconds Seconds (MM:SS)
5. LCI-C Diag Encoding (Text, Code) Text Enum
6. LCI-C Diag Language Enum
Chilled Water Reset Feature Settings (subscreen of Feature Settings)
Description Units
1. Chilled Water Reset Enum
2. Return Reset Ratio XXX Percent
3. Return Start Reset XXX.X Temperature
4. Return Maximum Reset XXX.X Temperature
5. Outdoor Reset Ratio XXX Percent
6. Outdoor Start Reset XXX.X Temperature
7. Outdoor Maximum Reset XXX.X Temperature
Air Temperature Reset Feature Settings (subscreen of Feature Settings)
Description Units
8. Air Temperature Reset Enum
9. Return Reset Ratio XXX Percent
10. Return Start Reset XXX.X Temperature
11. Return Maximum Reset XXX.X Temperature
12. Outdoor Reset Ratio XXX Percent
13. Outdoor Start Reset XXX.X Temperature
14. Outdoor Maximum Reset XXX.X Temperature
Evap Freeze Protection - Pumps Feature Settings (subscreen of Feature Settings)
Description Units
1. Evaporator Freeze Avoidance: (Enable, Disable), Enable Enum
2. Evap Freeze Avoid Time Const: (Fixed, Adaptive), Adaptive Enum
3. Evap Freeze Avoid Time Const: XX.X Minutes
4. Evap Freeze Avoidance Margin: XXX.X Temperature
Resolution or (Enumerations), Default
(English, Selection 2, Selection 3) English (0)
Resolution or (Enumerations), Default
Resolution or (Enumerations), Default
Resolution or (Enumerations), Default
(Const Return, Outdoor, Return, Disable), Disable
(Const Return, Outdoor, Return, Disable), Disable
Page 25
Cond Freeze Protection - Pumps Feature Settings (subscreen of Feature Settings)
Description Units
1. Condenser Freeze Avoidance: (Enable, Disable), Enable Enum
2. Cond Freeze Avoid Time Const: (Fixed, Adaptive), Adaptive Enum
3. Cond Freeze Avoid Time Const: XX.X Minutes
4. Cond Freeze Avoidance Margin: XXX.X Temperature
Control Settings
Description Units
1. Cooling Design Delta Temp XXX.X Delta Temperature
2. Heating Design Delta Temp XXX.X Delta Temperature
3. Differential to Start XXX.X Delta Temperature
4. Differential to Stop XXX.X Delta Temperature
5. Staging Deadband Adjustment XXX.X Delta Temperature
6. Capacity Control Softload Time 10 seconds Seconds (MM:SS)
7. Circuit Staging Option Enum
8. Compressor Staging Option (Fixed, Bal Starts/Hrs) Enum
9. Compressor Start Delay Time 5 seconds Seconds (MM:SS)
10. Leaving Water Temp Cutout XX.X Temperature
11. Low Refrigerant Temp Cutout XX.X Temperature
12. Evap Flow Overdue Wait Time 30 seconds Seconds (MM:SS)
13. Cond Flow Overdue Wait Time 30 seconds Seconds (MM:SS)
14. Condenser Limit Setpoint 85% Percent
15. Cond Head Temp Setpoint XXX.X Temperature
16. Cond Head Temp Control Deadband XXX.X Delta Temperature
17. Cond Head Temp Inv Prop Range XXX.X Delt a Temperature
18. Cond Low Water Temp Setpoint XXX.X Temperature
19. Defrost Subscreen (see below)
Defrost Control Settings (subscreen of Control Settings)
Description Units
1. Defrost High Ambient Setpoint XXX.X Temperature
2. Defrost Demand Setpt Minimum XXX.X Delta Temperature
3. Defrost Demand Setpt Maximum XXX.X Delta Temperature
4. Defrost Termination Setpt XXXX Pressure
5. Defrost Termination Setpt XXX.X Percent
6. Defrost Drying Time 1 second Seconds
7. Min Time Between Defrosts 30 seconds Seconds (MM:SS)
8. Maximum Defrost Time 10 seconds Seconds (MM:SS)
DynaView Interface
25CG-SVU02E-GB
Resolution or (Enumerations), Default
Resolution or (Enumerations), Default
(Bal Starts/Hrs, Circuit 1 Lead, Circuit 2 Lead), Bal Starts/Hrs -
Not shown if Hot Gas Bypass is installed
Resolution or (Enumerations), Default
Page 26
System Manual Control Settings
Description Resolution or (Enumerations), Default Units Monitor Value
1. Evap Water Pump (Auto, On), Auto
6
Enum 1) Evap Flow status
2) Override Time Remaining
2. Cond Water Pump (Auto, On), Auto
6
Enum 1) Cond Flow status
2) Override Time Remaining
3. Clear Restart Inhibit Timer (Clear Timer) 1) Restart Inhibit Time (composite value)
4. Capacity Control (Auto, Manual) Auto Enum
5. Binding Special Special None
Circuit Manual Control Settings
Description Resolution or (Enumerations), Default Units Monitor Value
1. Cprsr A Pumpdown Enum Suction pressure
2. Cprsr B Pumpdown Enum Suction pressure
3. Cprsr C Pumpdown Enum Suction pressure
4. Cprsr A Lockout (Not Locked Out, Locked Out), Not Locked Out Enum
5. Cprsr B Lockout (Not Locked Out, Locked Out), Not Locked Out Enum
6. Cprsr C Lockout (Not Locked Out, Locked Out), Not Locked Out Enum
7. Defrost Request (Auto, Manual), Auto Enum
8. Front Panel Ckt Lockout (Not Locked Out, Locked Out), Not Locked Out Enum
DynaView Interface
CG-SVU02E-GB26
Status: (Avail, Not Avail, Pumpdown) Override Subscreen command buttons: (Abort, Pumpdown) -
button is either grayed
out or not shown if not available
Status: (Avail, Not Avail, Pumpdown) Override Subscreen command buttons: (Abort, Pumpdown) -
button is either grayed
out or not shown if not available
Status: (Avail, Not Avail, Pumpdown) Override Subscreen command buttons: (Abort, Pumpdown) -
button is either grayed
out or not shown if not available
Page 27
DynaView Interface
27CG-SVU02E-GB
Auto, Stop/Panic Stop
The AUTO and STOP keys are radio buttons within the persistent key display area. The selected key will be black.
The chiller will stop when the STOP key is touched, entering the Run Unload mode. An informational screen will be displayed for 5 seconds indicating that a second depression of an "Immediate Stop" key during this time period will result in an immediate/panic stop. Pressing the "Immediate Stop" key while the panic stop screen is displayed, will cause the unit to stop immediately, skipping the run unload period.
Touching the Auto key will arm the chiller for active cooling if no diagnostic is present. As in UPC2, a separate action must be taken to clear active diagnostics.
The AUTO and STOP keys take precedence over the ENTER and CANCEL keys. While a setting is being changed, AUTO and STOP keys are recognized even if ENTER or CANCEL has not been pressed.
When an active diagnostic is present, an ALARMS key will be added to the persistent display area. This key is used to alert the operator that a diagnostic exists, or to provide navigation to a diagnostic display screen.
Figure 11
Auto Stop Alarms
Page 28
Diagnostics Screen
The diagnostic screen is accessible by depressing the Alarms enunciator A scrollable list of the last (up to 10) active diagnostics will be presented.
Performing a Reset All Active Diagnostics will reset all active diagnostics regardless of type, machine or refrigerant circuit. Compressor diagnostics, which hold off only one compressor, will be treated as circuit diagnostics, consistent with the circuit to which they belong.
The scrollable list will be sorted by time of occurrence. If a diagnostic of severity = warning is present, the "Alarms" key will be present but not flashing. If a diagnostic of severity = shutdown (normal or immediate) is present, the "Alarm" key will display that is flashing. If no diagnostics exist, the "Alarm" key will not be present.
The "Operating Mode At Last Diagnostic" text above the most recent diagnostic will display a sub­screen listing the operating mode and submodes at the time of the last diagnostic.
DynaView Interface
CG-SVU02E-GB28
Figure 12 - Diagnostics screen
Rfgt Setpoint Diagnostic
Auto Stop Alarms
Reset Diags
Operating Mode At Last Diagnostic: [01] 10:56 PM Nov 26, 2001 Low Chilled Water Temp: Unit Off [02] 10:55 PM Nov 26, 2001 Low Evaporator Temp: Unit Off
Page 29
Diagnostics
29CG-SVU02E-GB
The following diagnostic table contains all the diagnostics possible. Not all data is available unless tech view is connected.
Code: Three digit hexadecimal code used on all past products to uniquely identify diagnostics.
Diagnostic Name: Name of Diagnostic and its source. Note that this is the exact text used in the User Interface and/or Service Tool displays.
Severity: Defines the severity of the above effect. Immediate means immediate shutdown of the effected portion, Normal means normal or friendly shutdown of the effected portion, Special Mode means a special mode of operation (limp along) is invoked, but without shutdown, and Info means an Informational Note or Warning is generated.
Persistence: Defines whether or not the diagnostic and its effects are to be manually reset (Latched), or can be either manually or automatically reset (Nonlatched).
Criteria: Quantitatively defines the criteria used in generating the diagnostic and, if nonlatching, the criteria for auto reset. If more explanation is necessary a hot link to the Functional Specification is used.
Reset Level: Defines the lowest level of manual diagnostic reset command which can clear the diagnostic. The manual diagnostic reset levels in order of priority are: Local and Remote. A diagnostic that has a reset level of Local, can only be reset by a local diagnostic reset command, but not by the lower priority remote Reset command whereas a diagnostic listed as Remote reset can be reset by either.
Page 30
Diagnostics
CG-SVU02E-GB30
Diagnostic Name Effects Severity Persistence
Active Modes
[Inactive Modes]
Criteria
Reset Level
MP: Reset Has Occurred
Chiller Warning NonLatch All The main processor has successfully come out of a reset and
built its application. A reset may have been due to a power up, installing new software or configuration. This diagnostic is immediately and automatically cleared and thus can only be seen in the historic diagnostic list.
NA
Low Pressure Cutout Circuit Immediate Latch Starting and
Running [Stop,
See criteria]
The suction refrigerant pressure (gauge) fell below the given threshold for the refrigerant installed:
• 0.7 bar for R22 and R407c
• 0.3 bar for R134a
• 1.0 bar for R410a
Local
High Motor Temp/Overload
Cprsr Immediate Latch All • The High Motor Temperature or the Compressor Overload
switch remained open for more than 35 minutes.
• Five compressor fault diagnostics have occurred within the last 210 minutes.
Local
Compressor Fault Cprsr Immediate NonLatch All The High Motor Temperature or the Compressor Overload
switch input is open.
Local
BAS Failed to Establish Communication
Chiller Special NonLatch At power-up The BAS was setup as "installed" and the BAS did not
communicate with the MP within 15 minutes after power-up.
Remote
BAS Communication Lost
Chiller Special NonLatch All The BAS was setup as "installed" at the MP and the Comm
3 LLID lost communications with the BAS for 15 continuous minutes after it had been established. The chiller follows the value of the Tracer Default Run Command which can be previously written by Tracer and stored nonvolatilely by the MP (either use local or shutdown).
Remote
External Chilled/Hot Water Setpoint
Chiller Warning NonLatch All a. Function Not "Enabled": no diagnostics.
b. "Enabled ": Out-Of-Range Low or Hi or bad LLID, set
diagnostic, default CWS/HWS to next level of priority (e.g. Front Panel SetPoint). This Warning diagnostic will automatically reset if the input returns to the normal range.
Remote
External Demand Limit Setpoint
Chiller Warning NonLatch All a. Function Not "Enabled": no diagnostics.
b. "Enabled ": Out-Of-Range Low or Hi or bad LLID, set
diagnostic, default DLS to next level of priority (e.g. Front Panel SetPoint). This Warning diagnostic will automatically reset if the input returns to the normal range.
Remote
Circuit Pumpdown Terminated
Circuit Warning Latch Operational/Service
Pumpdown [All
Except Operational
and Service Pumpdown]
Going below the low pressure setting + 0.2 bar shall terminate Service Pumpdown. This indicates that the suction pressure of circuit 1 or 2 did not go below the low pressure setting + 0.2 bar within 1 minute from the start of Service Pumpdown.
Remote
Chilled Water Flow (Entering Water Temp)
Chiller Immediate Latch Any Ckt(s)
Energized [No Ckt(s)
Energized]
The entering evaporator water temperature fell below the leaving evaporator water temperature by more than 1.7°C for 37°C sec while at least 1 compressor was running.
Remote
Table 4 - Main Processor Diagnostics
Page 31
Diagnostics
31CG-SVU02E-GB
Evaporator Entering Water Temp Sensor
Chiller Normal Latch All Bad Sensor or LLID Remote
Evaporator Leaving Water Temp Sensor
Chiller Normal Latch All Bad Sensor or LLID Remote
Evaporator Entering Air Temp Sensor
Chiller Normal Latch All Bad Sensor or LLID. Remote
Evaporator Leaving Air Temp Sensor
Chiller Normal Latch All Bad Sensor or LLID Remote
Condenser Entering Water Temp Sensor
Chiller Warning Latch All Bad Sensor or LLID Remote
Condenser Leaving Water Temp Sensor
Chiller Warning Latch All Bad Sensor or LLID Remote
Discharge Pressure Transducer
Circuit Normal Latch All Bad Sensor or LLID Remote
Suction Pressure Transducer
Circuit Immediate Latch All Bad Sensor or LLID Remote
Suction Temperature Sensor
Circuit Immediate Latch All Bad Sensor or LLID Remote
Low Evap Leaving Water Temp: Unit Off
Chiller or
Circuit
Warning
and Special
Action
NonLatch Unit in Stop Mode,
or in Auto Mode
and No Ckt(s)
Energized [Any Ckt
Energized]
a) The leaving chilled water temperature fell below the leaving
water temp cutout setting for 16.6°C- seconds while the Chiller is in the Stop mode, or in Auto mode with no compressors running. Energize Evap Water pump Relay until diagnostic auto resets, then return to normal evap pump control. Automatic reset occurs when the temp rises
1.1°C above the cutout setting for 30 minutes. When this diagnostic is active AND Leaving Water Temperature sensor diagnostic (loss of comm or out of range) the Evap Water pump relay shall be de-energized.
b) If evaporator protection temperature sensors are installed,
the effect is on the appropriate circuit. Else, the effect is on the chiller.
Remote
Low Evap Leaving Water Temp: Unit On
Chiller or
Circuit
Immediate
and Special
Action
NonLatch Any Ckt[s]
Energized [No Ckt(s)
Energizd]
a) The chilled water temperature fell below the cutout
setpoint for 16.6°C-seconds while a compressor was running. Automatic reset occurs when the temperature rises 1.1°C above the cutout setting for 2 minutes. This diagnostic shall not de-energize the Evaporator Water Pump Output. If this diagnostic is active the Low Evap Leaving Water Temp: Unit Off diagnostic shall be suppressed.
b) If evaporator protection temperature sensors are installed,
the effect is on the appropriate circuit. Else, the effect is on the chiller.
Remote
Low Refrigerant Temperature
Circuit Immediate Latch All except [Service
Pumpdown]
The Evaporator Saturated Refrigerant Temperature dropped below the Low Refrigerant Temperature Cutout Setpoint for
16.6°C-seconds.
Local
Page 32
Diagnostics
CG-SVU02E-GB32
High Evaporator Water Temperature
Chiller Immediate NonLatch All The evaporator leaving water temperature is above 46°C. This
diagnostic shall clear once the evaporator leaving water temperature falls below 43.3°C. This diagnostic protects the rupture disk. The evaporator water pump shall not run when this diagnostic is active.
Local
High Pressure Cutout
Circuit Immediate Latch All The high pressure cutout switch was open for more than one
second.
Local
Emergency Stop Chiller Immediate Latch All Emergency Stop input is open. Local
Outdoor Air Temp Sensor
Chiller Warning and
Special Action
Latch All Bad Sensor or LLID. If configured as an air-cooled this diagnostic
shall use a minimum low refrigerant temperature ignore time of 30 seconds.
Remote
MP: Non-Volatile Memory Reformatted
None Warning Latch All MP has determined there was an error in a sector of the Non-Volatile
memory and it was reformatted. Check settings.
Remote
Check Clock Platform Warning Latch All The real time clock had detected loss of its oscillator at some time in
the past. Check / replace battery? This diagnostic can be effectively cleared only by writing a new value to the chillers time clock using the TechView or DynaViews set chiller time functions.
Remote
MP: Could not Store Starts and Hours
Platform Warning Latch All MP has determined there was an error with the previous power
down store. Starts and Hours may have been lost for the last 24 hours.
Remote
MP: Non-Volatile Block Test Error
Platform Warning Latch All MP has determined there was an error with a block in the Non-
Volatile memory. Check settings.
Starts/Hours Modified
Cprsr Warning NonLatch All A counter for compressor starts or hours has been modified by
TechView. This diagnostic is immediately and automatically cleared and thus can only be seen in the historic diagnostic list.
NA
Page 33
Diagnostics
33CG-SVU02E-GB
Evaporator Water Flow Lost Pump 1 (or Pump 2)
Chiller Warning and
Special Action
NonLatch Evap pump
commanded on
After flow had been proven the chilled water flow input was open for more than 4 continuous seconds. The evaporator pump control will switch control to the redundant pump. If redundant pump is not available, diagnostic will clear when flow is established.
Remote
Evaporator Water Flow Overdue Pump 1 (or Pump 2)
Chiller Warning and
Special Action
NonLatch Estab. Evap. Water
Flow on going from
STOP to AUTO.
Evaporator water flow was not proven within a user adjustable time of the evaporator water pump relay being energized. Diagnostic is reset with return of evaporator water flow.
Remote
Fault Detected: Evaporator Water Pump 1 (or Pump 2)
Chiller Warning and
Special Action
NonLatch All Detection of a pump fault will cause pump control to
switch to the redundant pump.
Remote
Condenser Water Flow Lost Pump 1 (or Pump 2)
Chiller Warning and
Special Action
NonLatch Start and All
Run Modes
After flow had been proven the condenser water flow input was open for more than 4 continuous seconds. This diagnostic is automatically cleared once all circuits are de-energized.
Remote
Condenser Water Flow Overdue Pump 1 (or Pump 2)
Chiller Warning and
Special Action
NonLatch Estab Cond
Water Flow
Condenser water flow was not proven within a user adjustable time of the condenser water pump relay being energized.
Remote
Fault Detected: Condenser Water Pump 1 (or Pump 2)
Chiller Warning and
Special Action
NonLatch All Detection of a pump fault will cause pump control to
switch to the redundant pump.
Remote
Fan Fault Circuit Warning NonLatch All The fan fault input was open for more than
5 seconds.
Local
Fan Inverter Fault Circuit Warning NonLatch All The fan fault input is ignored for the first 5 seconds
of start up to allow AFD's to power up.
Local
High Condensing Pressure Pump Add
Chiller Warning Latch Running When running in parallel pump control, with one
pump on, a high condensing pressure will force add the second pump. It will latch on to prevent pump cycling.
Remote
Low Suction Superheat
Circuit Immediate Latch
Ckt Energized
[Ckt Not Energized]
Measured suction superheat stays below 2.22 °C for one continuous minute, with a 1 minute ignore time from the start of the circuit. Suction Superheat = suction temp – sat. suction temp.
Suction Temperature Too High
Circuit Immediate Latch
Ckt Energized
[Ckt Not Energized]
The suction temperature measurement is larger than the entering temperature by more than a threshold value for 5 continuous minutes. The threshold value is 4°C (7.2°F) for cooling-only units. There is an ignore time of 2 minutes following circuit startup. The trip criteria is not evaluated (and time above the threshold is not counted) until the ignore time passes.
Page 34
Diagnostics
CG-SVU02E-GB34
Diagnostic Name Effects Severity Persistence Active Modes
[Inactive
Modes]
Criteria Reset
Level
Excessive Loss of Comm
Chiller Immediate Latch All Loss of comm with 20% or more of the llids configured for the
system has been detected. This diagnostic will suppress the callout of all subsequent comm loss diagnostics. Check power supply(s) and power disconnects - troubleshoot LLIDS buss using TechView
Remote
Comm Loss: External Auto/Stop
Chiller Normal Latch All Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.
Remote
Comm Loss: Emergency Stop
Chiller Normal Latch All Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.
Remote
Comm Loss: Ext Ice Building Ctrl Input
Chiller Warning Latch All Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period. Chiller shall revert to normal (non-ice building) mode regardless of last state.
Remote
Comm Loss: Outdoor Air Temperature
Chiller Warning Latch All Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period. If configured as an air-cooled this diagnostic shall turn on all fans and use a minimum LPC ignore time of 30 seconds.
Remote
Comm Loss: Evap Leaving Water Temp
Chiller Normal Latch All Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.
Remote
Comm Loss: Evap Entering Water Temp
Chiller Normal Latch All Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.
Remote
Comm Loss: Evap Leaving Air Temp
Chiller Normal Latch All Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.
Remote
Comm Loss: Evap Entering Air Temp
Chiller Normal Latch All Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.
Remote
Table 5 - Communication Diagnostics
Notes:
1. The following communication loss diagnostics will not occur unless that input or output is required to be present by the particular configuration and installed options for the chiller.
2. Communication diagnostics (with the exception of "Excessive Loss of Comm" are named by the Functional Name of the input or output that is no longer being heard from by the Main Processor.
Many LLIDs, such as the Quad Relay LLID, have more than one functional output associated with it. A comm loss with such a multiple function board will generate multiple diagnostics. Refer to the Chiller's wiring diagrams to relate the occurrence of multiple communication diagnostics back to the physical llid boards that they have been assigned to (bound).
Page 35
Diagnostics
35CG-SVU02E-GB
Comm Loss: Condenser Leaving Water Temp
Chiller Warning Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period.
Remote
Comm Loss: Condenser Entering Water Temp
Chiller Warning Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period.
Remote
Comm Loss: Discharge Pressure Transducer
Circuit Normal Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period.
Remote
Comm Loss: Suction Pressure Transducer
Circuit Immediate Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period.
Remote
Comm Loss: Ext Chilled/Hot Wtr Setpoint
Chiller Warning and
Special
Action
Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period. Chiller shall discontinue use of the External Chilled/Hot Water Setpoint source and revert to the next higher priority for setpoint arbitration
Remote
Comm Loss: External Demand Limit Setpoint
Chiller Warning and
Special
Action
Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period. Chiller shall discontinue use of the External Demand Limit Setpoint source and revert to the next higher priority for setpoint arbitration
Remote
Comm Loss: Auxiliary Setpoint Command
Chiller Warning and
Special
Action
Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period. Chiller shall discontinue use of the Auxiliary Setpoint and revert to the Chilled Water Setpoint based on setpoint arbitration
Remote
Comm Loss: High Pressure Cutout Switch
Chiller Immediate Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period.
Remote
Comm Loss: Evaporator Water Flow Switch
Chiller Immediate Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period.
Remote
Comm Loss: Condenser Water Flow Switch
Chiller Immediate Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period.
Remote
Comm Loss: Local BAS Interface
Chiller Warning and
Special
Action
NonLatch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period. Use the last values sent from BAS
Remote
Comm Loss: Solenoid Valve
Circuit Normal Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period.
Remote
Comm Loss: Motor Temp/Overload
Cprsr Immediate Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period.
Remote
Comm Loss: Compressor Run Command
Cprsr Immediate Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period.
Remote
Page 36
Diagnostics
CG-SVU02E-GB36
Comm Loss: Condenser Fan Control Relays
Circuit Immediate Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period.
Remote
Comm Loss: Fan Fault
Chiller Warning Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period.
Remote
Comm Loss: Fan Inverter Speed Command
Circuit Warning NonLatch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period.
Remote
Comm Loss: Fan Inverter Fault
Circuit Warning Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period.
Remote
Comm Loss: Op Status Programmable Relays
Chiller Warning Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period.
Remote
Comm Loss: Anti-Freeze Heater Relay
Chiller Warning and
Special
Action
Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period.
Remote
Comm Loss: Supplemental Electric Heat Relay
Chiller Warning Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period.
Remote
Comm Loss: Evaporator Water Pump 1 (or Pump 2) Relay
Chiller Warning and
Special
Action
Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period. For multi-pump systems, control switches to redundant pump. Failure of both pump systems results in a normal shutdown.
Remote
Comm Loss: Condenser Water Pump 1 (or Pump 2) Relay
Chiller Warning and
Special
Action
Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period. For multi-pump systems, control switches to redundant pump. Failure of both pump systems results in a normal shutdown.
Remote
Comm Loss: Evaporator Pump 1 (or Pump 2) Fault Input
Chiller Warning and
Special
Action
Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period. For multi-pump systems, control switches to redundant pump. Failure of both pump systems results in a normal shutdown.
Remote
Comm Loss: Condenser Pump 1 (or Pump 2) Fault Input
Chiller Warning and
Special
Action
Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period. For multi-pump systems, control switches to redundant pump. Failure of both pump systems results in a normal shutdown.
Remote
Comm Loss: Heat/Cool Switch
Chiller Normal Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period.
Remote
Comm Loss: Condenser Speed Signal
Chiller Normal Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period.
Remote
Comm Loss: Suction Temperature
Circuit Immediate Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period.
Page 37
Diagnostics
37CG-SVU02E-GB
Comm Loss: Ext Capacity Control Input 1
Chiller Normal Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period.
Remote
Comm Loss: Ext Capacity Control Input 2
Chiller Normal Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period.
Remote
Comm Loss: Ext Capacity Control Input 3
Chiller Normal Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period.
Remote
Comm Loss: Ext Capacity Control Input 4
Chiller Normal Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period.
Remote
Comm Loss: Hot Gas Bypass Relay
Chiller Normal Latch All Continual loss of communication between the MP and the Functional
ID has occurred for a 35-40 second period.
Remote
Table 6 - Main Processor - Boot Messages and Diagnostics
DynaView Display Message Description
Troubleshooting
Boot Software Part Numbers: LS Flash
--> 6200-0318-XX MS Flash
--> 6200-0319-XX
The "boot code" is the portion of the code that is resident in all MPs regardless of what application code (if any) is loaded. Its main function is to run power up tests and provide a means for downloading application code via the MP's serial connection. The Part numbers for the code are displayed in the lower left-hand corner of the DynaView during the early portion of the power up sequence and during special programming and converter modes. See below.
Err2: RAM Pattern 1 Failure There were RAM errors detected in RAM Test Pattern #1. Recycle power, if the error persists, replace MP.
Err2: RAM Pattern 2 Failure There were RAM errors detected in RAM Test Pattern #2. Recycle power, if the error persists, replace MP.
Err2: RAM Addr Test #1 Failure
There were RAM errors detected in RAM Address Test #1. Recycle power, if error persists, replace MP.
Err2: RAM Addr Test #2 Failure
There were RAM errors detected in RAM Address Test #2. Recycle power, if the error persists, replace MP.
No Application Present Please Load Application...
No Main Processor Application is present - There are no RAM Test Errors. Connect a TechView Service Tool to the MP's serial port, provide chiller model number (configuration information) and download the configuration if prompted by TechView. Then proceed to download the most recent application or specific version as recommended by Technical Service.
MP: Invalid Configuration MP has an invalid configuration based on the current software installed
MP Application Memory CRC Error
App software inside the MP failed its own checksum test. Possible causes: application software in the MP is not complete ­software download to the MP was not completed successfully - or MP hardware problem. Note: User should attempt to reprogram the MP if this diagnostic occurs.
App Present. Running Selftest.Selftest Passed
An application has been detected in the Main Processor's nonvolatile memory and the boot code is proceeding to run a check on its entirety. 8 seconds later, the boot code had completed and passed the (CRC) test. Temporary display of this screen is part of the normal power up sequence.
App Present. Running SelftestErr3: CRC Failure
An application has been detected in Main Processor's nonvolatile memory and the boot code is proceeding to run a check on its entirety. A few seconds later, the boot code had completed but failed the (CRC) test. Connect a TechView Service Tool to the MP's serial port, provide chiller model number (configuration information) and download the configuration if prompted by TechView. Then proceed to download the most recent application or specific version as recommended by Technical Service. Note that this error display may also occur during the programming process, if the MP never had a valid application any time prior to the download. If the problem persists, replace the MP.
Page 38
Diagnostics
CG-SVU02E-GB38
A Valid Configuration is Present
A valid configuration is present in the MP's nonvolatile memory. The configuration is a set of variables and settings that define the physical makeup of this particular chiller. These include: number/airflow and type of fans, number/and size of compressors, special features, characteristics, and control options. Temporary display of this screen is part of the normal power up sequence.
Err4: UnHandled InterruptRestart Timer: [3 sec countdown timer]
An unhandled interrupt has occurred while running the application code. This event will normally cause a safe shutdown of the entire chiller. Once the countdown timer reaches 0, the processor will reset, clear diagnostics, and attempt to restart the application and allow a normal restart of chiller as appropriate. This condition might occur due to a severe electro-magnetic transient such as a near lightening strike. Such events should be rare or isolated and if no damage results to the CH530 control system, the Chiller will experience a shutdown and restart. If this occurs more persistently it may be due to an MP hardware problem. Try replacing the MP. If replacement of the MP proves ineffective, the problem may be a result of extremely high radiated or conducted EMI. Contact Technical Service.If this screen occurs immediately after a software download, attempt to reload both the configuration and the application. Failing this, contact Technical Service.
Err5: Operating System ErrorRestart Timer: [3 sec countdown timer]
An Operating System error has occurred while running the application code. This event will normally cause a safe shutdown of the entire chiller. Once the countdown timer reaches 0, the processor will reset, clear diagnostics, and attempt to restart the application and allow a normal restart of chiller as appropriate.See Err 4.
Err6: Watch Dog Timer ErrorRestart Timer: [3 sec countdown timer]
A Watch Dog Timer Error has occurred while running the application code. This event will normally cause a safe shutdown of the entire chiller. Once the countdown timer reaches 0, the processor will reset, clear diagnostics, and attempt to restart the application allowing a normal restart of chiller as appropriate.
Err7: Unknown ErrorRestart Timer: [3 sec countdown timer]
An unknown Error has occurred while running the application code. This event will normally cause a safe shutdown of the entire chiller. Once the countdown timer reaches 0, the processor will reset, clear diagnostics, and attempt to restart the application allowing a normal restart of chiller as appropriate
Err8: Held in Boot by User Key Press [3 sec countdown timer]
A touch was detected during boot indicating the user wanted to stay in boot mode. This mode can be used to recover from a fatal software error in the application code. Cycle power on the MP to clear this error if it was unintentional.
Converter Mode A command was received from the Service Tool (Tech View) to stop the running application and run in the "converter mode".
In this mode the MP acts as a simple gateway and allows the TechView service computer to talk to all the LLIDS on the IPC3 bus.
Programming Mode A command was received by the MP from the Tech View Service Tool and the MP is in the process of first erasing and then
writing the program code to its internal Flash (nonvolatile) Memory. Note that if the MP never had a prior application already in memory, the error code "Err3"will be displayed instead of this, during the programming download process.
Design Note: In general, all failures/comm loss due to CH530 components should have a latching diagnostic and effect. All customer inputs failures (out of range, etc) are generally nonlatching.
Page 39
Diagnostics
39CG-SVU02E-GB
Programmable Relays (Alarms and Status)
CH530 provides a flexible alarm or chiller status indication to a remote location through a hard wired interface to a dry contact closure.
Four relays are available for this function, and they are provided (generally with a Quad Relay Output LLID) as part of the Alarm Relay Output Option.
The events/states that can be assigned to the programmable relays are listed in the following table and through a TechView configuration.
Event/state Description
Alarm - Latching This output is true whenever there is any active diagnostic that requires a manual reset to clear, that affects the chiller, the
circuit, or any of the compressors on a circuit. This classification does not include informational diagnostics.
Alarm - Auto reset This output is true whenever there is any active diagnostic that could automatically clear that affects the chiller, the circuit or any
of the compressors on a circuit. This classification does not include informational diagnostics. If all of the auto resetting diagnostics were to clear, this output would return to a false condition.
Alarm This output is true whenever there is any diagnostic affecting any component, whether latching or automatically clearing. This
classification does not include informational diagnostics.
Warning This output is true whenever there is any informational diagnostic affecting any component, whether latching or automatically
clearing.
Chiller Limit Mode This output is true whenever the chiller has been running in one of the Unloading types of limit modes (Condenser, Evaporator,
Current Limit or Phase Imbalance Limit) continuously for the last 20 minutes. A given limit or overlapping of different limits must be in effect continuously for 20 minutes prior to the output becoming true. It will become false, if no Unload limits are present for 1 minute. The filter prevents short duration or transient repetitive limits from indicating. The chiller is considered to be in a limit mode for the purposes of front panel display and annunciation, on if it is fully inhibiting loading by virtue of being in either the "hold" or "forced unload" regions of the limit control, excluding the "limited loading region". In previous designs, the "limit load" region of the limit control was included in the criteria for the limit mode call out on the front panel and annunciation outputs.
Compressor Running The output is true whenever any compressors are started or running on the chiller and false when no compressors are either
starting or running on the chiller. This status may or may not reflect the true status of the compressor in Service Pumpdown if such a mode exists for a particular chiller.
Maximum Capacity The output is true whenever the chiller has reached maximum capacity continuously for the Max Capacity Relay debounce time.
The output is false when the chiller does not have all its available compressors running continuously for the debounce time.
Default setting Event/Status
Output relay 1 Compressor running
Output relay 2 Latching alarm
Output relay 3 Chiller limit mode
Output relay 4 Warnings
Table 7 - Chiller events/status descriptions
Table 8 - Default settings
Page 40
TechView Interface
CG-SVU02E-GB40
TechView is the PC (laptop) based tool used for servicing Tracer CH530. Technicians that make any chiller control modification or service any diagnostic with Tracer CH530 must use a laptop running the software application "TechView." TechView is a Trane application developed to minimize chiller downtime and aid the technicians' understanding of chiller operation and service requirements.
CAUTION:
Performing any Tracer CH530 service functions should be done only by a properly trained service technician. Please contact your local Trane service agency for assistance with any service requirements.
TechView software is available via Trane.com. (http://www.trane.com/commercial/s oftware/tracerch530/) This download site provides a user the TechView installation software and CH530 main processor software that must be loaded onto your PC in order to service a CH530 main processor. The TechView service tool is used to load software into the Tracer CH530 main processor.
Minimum PC requirements to install and operate TechView are:
• Pentium II or higher processor
• 128Mb RAM
• 1024 x 768 resolution of display
• CD-ROM
• 56K modem
• 9-pin RS-232 serial connection
• Operating system ­Windows 2000
• Microsoft Office (MS Word, MS Access, MS Excel)
• Parallel Port (25-pin) or USB Port
Note:
TechView was designed for the proceeding listed laptop configuration. Any variation will have unknown results. Therefore, support for TechView is limited to only those operating systems that meet the specific configuration listed here. Only computers with a Pentium II class processor or better are supported; Intel Celeron, AMD, or Cyrix processors are not supported.
TechView is also used to perform any CH530 service or maintenance function.
Servicing a CH530 main processor includes:
• Updating main processor
software
• Monitoring chiller operation
• Viewing and resetting chiller
diagnostics
• Low Level Intelligent Device
(LLID) replacement and binding
• Main processor replacement and
configuration modifications
• Setpoint modifications
• Service overrides
Page 41
TechView Interface
41CG-SVU02E-GB
Software Download
Instructions for First Time TechView Users
This information can also be found at http://www.trane.com/commercial/s oftware/tracerch530/.
1. Create a folder called "CH530" on your C:\ drive. You will select and use this folder in subsequent steps so that downloaded files are easy to locate.
2. Download the Java Runtime installation utility file onto your PC in the CH530 folder (please note that this does not install Java Runtime, it only downloads the installation utility).
• Click on the latest version of Java Runtime shown in the TechView Download table.
• Select "Save this program to disk" while downloading the files (do not select "Run this program from its current location").
3. Download the TechView installation utility file onto your PC in the CH530 folder (please note that this does not install TechView, it only downloads the installation utility).
• Click on the latest version of TechView shown in the TechView Download table.
• Select "Save this program to disk" while downloading the files (do not select "Run this program from its current location").
4. Remember where you downloaded the files (the "CH530" folder). You will need to locate them to finish the installation process.
5. Proceed to "Main Processor Software Download" page and read the instructions to download the latest version of main processor installation files.
Note: you will first select the chiller type to obtain the available file versions.
Page 42
TechView Interface
CG-SVU02E-GB42
6. Select the product family. A table with the download link will appear for that product family.
7. Download the main processor software onto your PC in the CH530 folder (please note that this does not install the main processor, it only downloads the installation utility).
• To do this, click on the latest version of the main processor.
• Select "Save this program to disk" while downloading the files (do not select "Run this program from its current location").
8. Remember where you downloaded the files (the "CH530" folder). You will need to locate them to finish the installation process.
9. To complete the installation process, locate the installation utilities you downloaded into the CH530 folder. If necessary, use your PC's file manager to locate the downloaded files.
10.Install the applications in the following order by double­clicking on the install program and following the installation prompts:
• Java Runtime Environment (JRE_VXXX.exe)
Note: During the Java Runtime Environment installation, you may be prompted to "select the default Java Runtime for the system browsers...". Do not select any system browsers at this step. There should be no default browsers selected for proper operation.
• TechView (6200-0347-VXXX.exe)
• The main processor (6200-XXXX-XX-XX.exe).
- The main processor program will self extract to the proper folder within the TechView program directory, provided the TechView program is properly installed on the C:\ drive.
11. Connect your PC to the CH530 main processor using a standard 9-pin male/9-pin female RS-232 cable.
12.Run the TechView software by selecting the TechView icon placed on your desktop during the installation process. The "Help...About" menu can be viewed to confirm proper installation of latest versions.
Page 43
43CG-SVU02E-GB
Notes
Page 44
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services and parts. For more information visit www.Trane.com
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
© 2016 Trane All rights reserved CG-SVU02E-GB January 2016 Supersedes CG-SVU02D-E4_0107