Trane is a leader in the air-cooled chillers marketplace,
thanks to excellence in design and manufacturing.
This tradition of excellence is present in the Conquest
air-cooled scroll compressor chillers range, a new
generation of chillers and heat pumps, providing
capacities from 42-160 kW.
Trane Quality
Trane is the designer and manufacturer of the core
components applying modern market standards
of quality in the fi nishing, a rigourous testing and
manufacturing plan, a powerful service portfolio
supporting the life cycle of the equipment.
Useful Effi ciency
The cooling only chillers, model CGAX, are rated Class B
(EER at full load at Eurovent conditions) and optimized
for operation at seasonal part load effi ciency (ESEER)
to maximize energy savings during real life building
demand, across all seasons.
The heat pump version, model CXAX, has been
optimized in the same way. Full Load COP is class B
as per Eurovent standard as well, while the part load
effi ciency ratio SCOP is compliant with Ecodesign
directive.
Acoustic Package
Two acoustical package options are available:
• Standard Noise (SN), with an average sound power of
Lw 86 dB(A)
• Low Noise (LN), for sensitive environments with a
sound reduction of an additional -6 dB(A)
The acoustical package does not bring any degradation
on the performances: cooling capacity, operating map,
or effi ciency.
Smart Chillers
• The operating map of the chiller, allows in cooling
mode, operation between -18°C up to 46°C ambient air
temperature.
• In heating mode, CXAX units can deliver 40°C hot
water, down to -15°C ambient air temperature.
• For industrial applications, with evaporator leaving
water temperature down to -12°C is Ecodesign
compliant (SEPR medium temperature > 2,8).
• The low profi le of the Conquest units allows easy
integration in buildings, thanks to the 1,5 m of height
on most of the units.
• A plug & play integration is supported by the option of
Hydraulic Module (with or without buffer tank).
• Chillers are provided with a Smart Controller and
a new generation interface, the Deluxe Touch Display.
• Full integrability capability thanks to available
communication protocols: Modbus, BACnet, LonTalk
and Trane BMS.
A robust design of the compressor and refrigerant
circuit has been validated by an extensive program
of operational tests, in extreme conditions, to ensure
maximum reliability. Quality is verifi ed during each
and every step.
Figure 1 - Scroll compressor
Oil sight Glass
Oil Equalization
Compressors
Direct drive, low speed, new generation of scroll
compressor, with few moving parts, providing high
effi ciency, reliable operation and simplifi ed maintenance.
Suction gas cooled motor winding, maintaining uniform
low temperature for extended motor life.
Fixed Scroll
Discharge
Valve plate
Oldham
Coupling
Orbiting
Rotor
Stator
Scroll
Counter weight
Oil Pick Up
Chiller controller
The Conquest chiller is equipped with the new
generation of chiller control systems, providing
improved control capabilities, and integrated safety
protocols to protect both compressors and motors from
electrical faults like thermal overload and phase reversal.
The LCD display with 6 navigation buttons shows
clear messages in 15 available languages. It features a
customer communication package consisting in: external
chilled water setpoint, external demand limit, analog
capacity output, programmable relays.
Figure 2 - Standard LCD user interface
A deluxe display is available as an option.,It features an
intuitive and user friendly color 7 inch touchscreen, able
to display: Data trending, clear alarms logging, and TIS
enable for remote monitoring.
Figure 3 - Optional deluxe user interface
4
CG-PRC026C-GB
Features and Benefi ts
Microchannel condensing coils on coolingonly units
Conquest chillers are equipped with microchannel
condensing coils allowing excellent heat transfer and a
dramatic improvement of corrosion resistance versus
conventional tubes in fi ns coils. Microchannel coils are
100% aluminum, therefore avoiding galvanic corrosion
which can occur on conventional condensers made with
copper tubes and aluminum fi ns. Microchannel coils are
also well adapted for dirty environment thanks to their
small thickness and fi ns profi le.
Figure 4 - Microchannel condensing coils
Slit fi ns and brazed contact
Air condenser inlet
Microchannels
for R410A
for improved heat transfer
and strength
Air
condenser
outlet
Electronic Expansion Valve
Electronic expansion valve enables tight chilled water
temperature control and low superheat, resulting in
more effi cient full-load and part-load operation.
Application versatility
Extended operating map, allowing chiller operation in
multiple applications:
• Industrial/low temperature process cooling with
precise temperature control capability
• Optimal and reliable operation at high ambient
temperatures.
Figure 5 - Operating map- Cooling-only Model CGAX
50
50
45
45
40
40
35
35
30
30
25
25
20
20
15
15
10
10
Amb Air T°C
5
5
0
0
AmbAir T °C
-5
-5
-10
-10
-15
-15
-20
-20
-15-10-50510152025
-15-10-50510152025
A
B
LWT (°C)
LWT (°C)
Heat pump units coils
The condenser coil is made of aluminum fi ns
mechanically bonded to seamless copper tubing and
includes integral subcooling circuit. The coils are factory
leak tested at 5 Mpa. If the unit is to be installed in a
corrosive environment, aluminum fi ns can be pre-coated
with epoxy (optional), with minimum thickness of 8µm,
in order to withstand 1000 hours of salt spray test
according to ISO 9227.
CG-PRC026C-GB
LWT = Leaving water temperature
Amb Air T = Ambient air temperature
A = Standard operating map
B = Low ambient operating map (Variable air fl ow control)
Minimum start-up/operation ambient based on a
2.22 m/s (5mph) wind across the condenser
5
Features and Benefi ts
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
-15-10-50510152025
Cooling Mode
-25
-20
-15
-10
-5
0
5
10
15
20
25
15 2025 3035 4045 5055 6065
Heating Mode
Figure 6 - Heat Pump Model CXAX operating map
Cooling Mode
A
Amb Air T°C
AmbAir T °C
B
LWT (°C)
LWT (°C)LWT (°C)
LWT = Leaving water temperature
Amb Air T = Ambient air temperature
A = Standard operating map
B = Low ambient operating map (Variable air fl ow control)
Minimum start-up/operation ambient based on a
2.22 m/s (5mph) wind across the condenser
Improved Serviceability
• All main components like compressors, valves and
refrigerant components are easy to access to simplify
servicing. When the unit is supplied with an hydraulic
module, the service valves and strainer can be
accessed with ease for service.
• Water connections are extended up to the edge of the
unit, for easy connection with system water piping.
• Optional pump package is designed for easy
maintenance and service on site.
• Pressure transducers and temperature sensors
are supplied for easy identifi cation of potential
troubleshooting and eventually, replacement, without
the need of refrigerant handling.
• Dead front panel and IP20 protection allow for safe
servicing.
AmbAir T °C
Heating Mode
A
Amb Air T°C
LWT (°C)
6
CG-PRC026C-GB
Application Considerations
Certain applications contraints should be considered
when sizing, selecting and installing Conquest aircooled Scroll chillers. Unit and system reliability often
depend on proper and complete compliance with those
considerations.
Unit Size
Unit oversizing is often not recommended since erratic
unit operation and excessive compressor cycling are
often a direct result of an oversized chiller. If oversizing
is desired, consider the alternative of multiple units,
splitting the total capacity.
Water Treatment
The use of untreated or improperly treated water in
chillers may result in scaling, erosion, corrosion, and
algae or slime buildup. This will adversely affect heat
transfer between the water and system components.
Proper water treatment must be determined locally
and depends on the type of system and local water
characteristics.
Neither salty nor brackish water is recommend for use
in Trane air-cooled Conquest chiller. Usage of either
will lead to a shortened life. Trane encourages the
employment of a qualifi ed water treatment specialist,
familiar with local water conditions, to assist in the
establishment of a proper water treatment program.
Foreign matter in the chilled water system can also
increase pressure drop and, consequently, reduce water
fl ow. For this reason it is important to thoroughly fl ush
all water piping to the unit before making the fi nal piping
connections to the unit.
Effect of the altitude on the cooling capacity
At elevations substantially above sea level, the
decreased air density will decrease condenser capacity
and, therefore, unit capacity and effi ciency.
Water fl ow limits
The minimum water fl ow rates are given in the General
Data section of this catalog. Evaporator fl ow rates below
the tabulated values will result in laminar fl ow causing
freeze-up problems,scaling, stratifi cation and poor
control. The maximum evaporator water fl ow rate is also
given. Flow rates exceeding those listed may result in
very high pressure drop across the evaporator.
Flow Rates Out of Range
Many process cooling jobs require fl ow rates that cannot
be met with the minimum and maximum published
values within the Conquest chiller evaporator. A simple
piping change can alleviate this problem. For example:
a plastic injection molding process requires 5.0 l/s of
10°C water and returns that water at 15.6°C. The selected
chiller can operate at these temperatures, but has a
minimum fl ow rate of 6.6 l/s. The system layout in
Figure 7 can satisfy the process.
Figure 7 - Flow rate out of range systems solution
10°C
10°C
7 l/s
14°C
7 l/s
5 l/s
10°C
2 l/s
15.6°C
5 l/s
L = Load
P = Pump
Flow Proving
Trane provides a factory-installed water fl ow switch
monitored by chilller controller CH535 which protects the
chiller from operating in loss of fl ow conditions.
Leaving Water Temperature Limits
Trane air-cooled Conquest chillers have two distinct
leaving water categories:
• standard, with a leaving solution range of 5.5 to 18°C
• low temperature process cooling, with leaving solution
range of -12 to 18°C
Since the leaving solution temperature below 5.5°C
results in suction temperature at or below the freezing
point of water, a glycol solution is required for all low
temperature.
Consult your local Trane sales engineer for applications
or selections involving low temperature. The maximum
water temperature that can be circulated through the
CGAX evaporator when the unit is not operating is
51.7°C. For the model CXAX the water temperature
limit is 60°C. Evaporator damage may result above this
temperature.
Figure 8 - Temperature out of range system solution
30°C
15 l/s
P
15°C
15 l/s
20°C
15 l/s
15°C
11.2 l/s
15°C
3.8 l/s
35°C
11.2 l/s
L
P
35°C
3.8 l/s
35°C
15 l/s
CG-PRC026C-GB
L = Load
P = Pump
7
Application Considerations
Supply Water Temperature Drop
Full load chilled water temperature drops from 3.3 °C to
10°C may be used as long as minimum and maximum
water temperature and minimum and maximum fl ow
rates are not violated.
Temperature drops outside this range at full load
conditions are beyond the optimum range for control
and may adversely affect the microcomputer’s ability to
maintain an acceptable supply water temperature range.
Furthermore, full load temperature drops of less than
3.3°C may result in inadequate refrigerant superheat
which is critical to long term effi cient and reliable
operation.
Suffi cient superheat is always a primary concern in
any refrigerant system and is especially important in a
packaged chiller where the evaporator is closely coupled
to the compressor.
Parameters which infl uence the water temperature
stability:
• Ambient temperature and water temperature (modify
cooling capacity)
• Number of capacity steps
• Minimum time between starts of a compressor
• Control dead band
• Water loop volume
• Load fl uctuations
• Fluid type or percentage of glycol
Typical Water Piping
All building water piping must be fl ushed prior to
making fi nal connections to the chiller. To reduce
heat loss and prevent condensation, insulation
should be applied. Expansion tanks are also usually
required so that chilled water volume changes can be
accommodated.
Avoidance of Short Water Loops
Adequate chilled water system water volume is an
important system design parameter because it provides
for stable chilled water temperature control and helps
limit unacceptable short cycling of chiller compressors.
The Conquest Air Cooled chiller’s temperature control
sensor is located in the supply (outlet) water connection
or pipe. This location allows the building to act as a
buffer to slow the rate of change of the system water
temperature. If there is not a suffi cient volume of water
in the system to provide an adequate buffer, temperature
control can suffer, resulting in erratic system operation
and excessive compressor cycling.
Typically, a two-minute water loop circulation time is
suffi cient to prevent short water loop issues. Therefore,
as a guideline, ensure the volume of water in the chilled
water loop equals or exceeds two times the evaporator
fl ow rate. For systems with a rapidly changing load
profi le the amount of volume should be increased.
If the installed system volume does not meet the above
recommendations, the following items should be given
careful consideration to increase the volume of water in
the system and, therefore, reduce the rate of change of
the return water temperature.
• A volume buffer tank located in the return water piping.
• Larger system supply and return header piping (which
also reduces system pressure drop and pump energy
use).
An optional factory-installed buffer tank is designed
to meet the minimum two minute loop time without
additional job site piping. The buffer tank can also be
used on jobs that already meet or exceed the minimum
loop time to further reduce the potential for compressor
cycling, increasing the compressor life span, and
reducing system temperature fl uctuations.
8
CG-PRC026C-GB
Minimum water volume for a process application
If a chiller is attached to an on/off load such as a
process load, it may be diffi cult for the controller to
respond quickly enough to the very rapid change in
return solution temperature if the system has only the
minimum water volume recommended. Such systems
may cause chiller low temperature safety trips or in the
extreme case evaporator freezing. In this case, it may
be necessary to add or increase the size of the mixing
tank in the return line or consider the optional factoryinstalled buffer tank with the chiller. Some guidance on
calculating the minimum volume necessary for proper
Scroll Compressors Chillers operation are given here,
through a simplifi ed formula, which does not take in
account variations on chiller effi ciency, compressor
sequencing, evaporator inlet/outlet temperature.
Minimum recommendable volume on the hydraulic loop
V= Cc * T / (Sh * Db) where:
Cc * T = V * Db * Sh
V = Volume of the loop (l)
Cc = Cooling Capacity of the chiller biggest Stage (kW)
T = Compressor Time (min running time (s))
Db = Dead Band (K)
Sh = Brine Specifi c heat (kJ.K-1.kg-1)
Multiple Unit Operation
Whenever two or more units are used on one chilled
water loop, Trane recommends that their operation be
coordinated with a higher level system controller for
best system effi ciency and reliability. The Trane Tracer
system has advanced chilled plant control capabilities
designed to provide such operation.
Application Considerations
CG-PRC026C-GB
9
Unit Placement
Setting The Unit
A base or foundation is not required if the selected unit
location is level and strong enough to support the unit’s
operating weight (see “Weights” section of this catalog).
For a detailed discussion of base and foundation
construction, refer to the sound engineering bulletin or
the unit IOM. Manuals are available through the local
Trane offi ce.
HVAC equipment must be located to minimize sound
and vibration transmission to the occupied spaces of
the building structure it serves. If the equipment must
be located in close proximity to a building, it should be
placed next to an unoccupied space such as a storage
room, mechanical room, etc. It is not recommended to
locate the equipment near occupied, sound sensitive
areas of the building or near windows. Locating the
equipment away from structures will also prevent sound
refl ection, which can increase sound levels at property
lines or other sensitive points.
Isolation and Sound Emission
Structurally transmitted sound can be reduced
by elastomeric vibration eliminators. Elastomeric
isolators are generally effective in reducing vibratory
noise generated by compressors, and therefore, are
recommended for sound sensitive installations. An
acoustical engineer should always be consulted in
critical situations.
Figure 9 - Installation example
Piping isolation
Chiled water piping
should be supported.
Isolators
Flexible electrical
conduit
Concrete base
For maximum isolation effect, water lines and electrical
conduit should also be isolated. Wall sleeves and rubber
isolated piping hangers can be used to reduce the sound
transmitted through water piping. To reduce the sound
transmitted through electrical conduit, use fl exible
electrical conduit.
Local codes on sound emissions should always be
considered. Since the environment in which a sound
source is located affects sound pressure, unit placement
must be carefully evaluated. Sound power levels for
chillers are available on request.
Isolators
Servicing
Adequate clearance for evaporator and compressor
servicing should be provided. Recommended minimum
space envelopes for servicing are located in the
dimensional data section and can serve as a guideline
for providing adequate clearance. The minimum space
envelopes also allow for control panel door swing
and routine maintenance requirements. Local code
requirements may take precedence.
Unit Location
General
Unobstructed fl ow of condenser air is essential to
maintain chiller capacity and operating effi ciency. When
determining unit placement, careful consideration
must be given to assure a suffi cient fl ow of air across
the condenser heat transfer surface. Two detrimental
conditions are possible and must be avoided: warm air
recirculation and coil starvation. Air recirculation occurs
when discharge air from the condenser fans is recycled
back to the condenser coil inlet. Coil starvation occurs
when free airfl ow to the condenser is restricted.
Condenser coils and fan discharge must be kept free of
snow or other obstructions to permit adequate airfl ow
for satisfactory unit operation. Debris, trash, supplies,
etc., should not be allowed to accumulate in the vicinity
of the air-cooled chiller. Supply air movement may draw
debris into the condenser coil, blocking spaces between
coil fi ns and causing coil starvation.
Both warm air recirculation and coil starvation cause
reductions in unit effi ciency and capacity because of
the higher head pressures associated with them. The
air-cooled Conquest chiller offers an advantage over
competitive equipment in these situations. Operation is
minimally affected in many restricted air fl ow situations
due to its advanced chiller controller.
Microprocessor which has the ability to understand the
operating environment of the chiller and adapt to it by
fi rst optimizing its performance and then staying on
line through abnormal conditions. For example, high
ambient temperatures combined with a restricted air
fl ow situation will generally not cause the air-cooled
model CGAX chiller to shut down. Other chillers would
typically shut down on a high pressure nuisance cut-out
in these conditions.
Cross winds, those perpendicular to the condenser, tend
to aid effi cient operation in warmer ambient conditions.
However, they tend to be detrimental to operation
in lower ambients due to the accompanying loss of
adequate head pressure. Special consideration should
be given to low ambient units. As a result, it is advisable
to protect air-cooled chillers from continuous direct
winds exceeding 4.5 m/s in low ambient conditions.
10
CG-PRC026C-GB
Provide Suffi cient Unit-to-Unit Clearance
Units should be separated from each other by suffi cient
distance to prevent warm air recirculation or coil
starvation. Doubling the recommended single unit
air-cooled chiller clearances will generally prove to be
adequate.
Walled Enclosure Installations
When the unit is placed in an enclosure or small
depression, the top of the surrounding walls should be
no higher than the top of the fans. The chiller should be
completely open above the fandeck. There should be no
roof or structure covering the top of the chiller. Ducting
individual fans is not recommended.
Table 1 - CGAX Standard effi ciency and Standard Noise
CGAX
015
Eurovent Performances (1)
Net Cooling Capacity(kW)43495965748299
Total Power input in cooling(kW)15171922262933
Total Power input in cooling - HESP Option (100Pa)(kW)15182124273134
EER2.982.883.082.952.872.842.96
EER - HESP (915 RPM - 100Pa)2.822.742.892.812.782.762.81
ESEER3.893.933.813.823.843.803.93
Eurovent Effi ciency class CoolingBCBBCCB
Sound power level(dBA)83838585858684
Sound power level - HESP Option (100Pa)(dBA)85858989898989
Unit amps (4) (5)
Unit rated amps(A)34384550566474
Unit rated amps - HESP Option (100Pa)(A)35394752576675
Unit start up amps(A)116160167183188189198
Unit start up amps - HESP Option (100Pa)(A)117161169185190191199
Short Circuit Unit Capacity (9)(kA)12121212121215
Compressor
Compressor Number per Circuit#2222223
TypeScrollScrollScrollScrollScrollScrollScroll
Model Circuit1 / Circuit 27.5+7.57.5+1010+1010+1313+1315+1512+12+12
Motor RPM(rpm)2900
Without HYM
Nominal water connection size (Grooved coupling) -
With HYM
Hydraulic Module Components
Expansion Tank Volume(l)25252525252535
Max User water loop Volume for factory mounted
expansion tank (1)
Optional water Buffer tank volume(l)324324324324324324444
Max. Water-side Operating Pressure without pump
package
Max. Water-side Operating Pressure with pump
package
Condenser
TypeFull aluminum Micro channel heat exchanger
Quantity of coil#1111112
Face area per circuit(m²)2.232.232.962.962.962.964.46
Condenser Fan
Quantity#1122222
Diameter(mm)800
Fan / motor TypePropeller fan : Fixed speed AC motor / Variable speed - EC motor
Airfl ow per Fan(m3/h)13788138281236212362123701237513827
Airfl ow per Fan - HESP Option (100Pa)(m3/h)13753137181224812231122111219313727
Motor RPM(rpm)686686686686686686686
Motor RPM - HESP Option (100Pa)(rpm)915915915915915915915
Single pump - Standard head pressure(kg)46464649494945
Single pump - High head pressure(kg)51515151515149
Twin pump - Standard head pressure(kg)70707075757571
Twin pump - High head pressure(kg)82828282828286
Partial heat recovery option(kg)1.481.481.481.483.823.823.82
Water Buffer tank option(kg)319319319319319319425
System data
Nb of refrigerant circuit#1111111
Minimum cooling load % (6)%50435043505033
(1) At Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C according to EN14511:2013
(2) At Evaporator water temperature : 6.6°C (44°F) / 12.2°C (54°F) - condenser air temperature 46°C (114.8°F)
(4) under 400V/3/50Hz
(5) Rated Condition without Pump Package
(6) Percent minimum load can be lowered on demand to local sales offi ce.
(7) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(8) Maximum ambient operation is for unit at 12°C / 7°C
(9) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch.
Electrical & system data are subject to change without notice. Please refer to unit nameplate data.
Table 1 - CGAX Standard effi ciency and Standard Noise (continued)
CGAX
039
Eurovent Performances (1)
Net Cooling Capacity(kW)111127971161 29147164
Total Power input in cooling(kW)38413539475158
Total Power input in cooling - HESP Option (100Pa)(kW)39453643505761
EER2.923.082.792.942.782.862.83
EER - HESP (915 RPM - 100Pa)2.822.812.722.732.612.552.68
ESEER4.133.983.833.643.593.753.81
Eurovent Effi ciency class CoolingBCCBBCC
Sound power level(dBA)85878688888889
Sound power level - HESP Option (100Pa)(dBA)90929092929292
Unit amps (4) (5)
Unit rated amps(A)81967790101111128
Unit rated amps - HESP Option (100Pa)(A)83987893104114131
Unit start up amps(A)214221198212233243253
Unit start up amps - HESP Option (100Pa)(A)215224200215236247256
Short Circuit Unit Capacity (9)(kA)15151515151515
Compressor
Compressor Number per Circuit#3322222
TypeScrollScrollScrollScrollScrollScrollScroll
Model Circuit1 / Circuit 213+13+1315+15+15 7.5+10 / 7.5+10 10+10 / 10+10 10+13 /10+13 13+13 / 13+13 15+15 / 15+15
Motor RPM(rpm)2900
Without HYM
Nominal water connection size (Grooved coupling) -
With HYM
Hydraulic Module Components
Expansion Tank Volume(l)35353535353535
Max User water loop Volume for factory mounted
expansion tank (1)
Optional water Buffer tank volume(l)444444444444444444444
Max. Water-side Operating Pressure without pump
package
Max. Water-side Operating Pressure with pump
package
Condenser
TypeFull aluminum Micro channel heat exchanger
Quantity of coil#2222222
Face area per circuit(m²)5.935.932.232.962.962.962.96
Condenser Fan
Quantity#2324444
Diameter(mm)800
Fan / motor TypePropeller fan : Fixed speed AC motor / Variable speed - EC motor
Airfl ow per Fan(m3/h)14690136761468712358123631259212374
Airfl ow per Fan - HESP Option (100Pa)(m3/h)14660135951468612249122331244712205
Motor RPM(rpm)686686686686686686686
Motor RPM - HESP Option (100Pa)(rpm)915915915915915915915
Single pump - Standard head pressure(kg)47474547474747
Single pump - High head pressure(kg)49494949494949
Twin pump - Standard head pressure(kg)75757575757575
Twin pump - High head pressure(kg)86868484848484
Partial heat recovery option(kg)4.64.62x1.482x1.482x1.482x3.822x3.82
Water Buffer tank option(kg)425425425425425425425
System data
Nb of refrigerant circuit#1122222
Minimum cooling load % (6)%33332225222525
(1) At Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C according to EN14511:2013
(2) At Evaporator water temperature : 6.6°C (44°F) / 12.2°C (54°F) - condenser air temperature 46°C(114.8°F)
(4) under 400V/3/50Hz
(5) Rated Condition without Pump Package
(6) Percent minimum load can be lowered on demand to local sales offi ce.
(7) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(8) Maximum ambient operation is for unit at 12°C / 7°C
(9) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch.
Electrical & system data are subject to change without notice. Please refer to unit nameplate data.
(in) - (mm) 2" - 60.32" - 60.3 3" OD - 76.1 3" OD - 76.1 3" OD - 76.1 3" OD - 76.1 3" OD - 76.1
(in) - (mm) 3" O D - 76.1 3" OD - 76.1 3" OD - 76.1 3" OD - 76.1 3" OD - 76.1 3" OD - 76.1 3" OD - 76.1
(kPa)1000
(kPa)400
SE-SN
(l)2000200020002000200020002000
G 1”1/4
(31.75 mm)
CGAX
045
SE-SN
G 1”1/4
(31.75 mm)
CGAX
035
SE-SN
G 1”1/4
(31.75 mm)
CGAX
040
SE-SN
G 1”1/4
(31.75 mm)
CGAX
046
SE-SN
G 1”1/4
(31.75 mm)
CG-PRC026C-GB
CGAX
052
SE-SN
G 1”1/4
(31.75 mm)
CGAX
060
SE-SN
G 1”1/4
(31.75 mm)
15
General Data
Table 2 - CGAX Standard effi ciency and Low Noise
CGAX
015
Eurovent Performances (1)
Net Cooling Capacity(kW)43495965748299
Total Power input in cooling(kW)15171922262933
Total Power input in cooling - HESP Option (100Pa)(kW)15182124273134
EER2.982.883.082.952.872.842.96
EER - HESP Option (100Pa)2.822.742.892.812.782.762.81
ESEER3.893.933.813.823.843.803.93
Eurovent Effi ciency class CoolingBCBBCCB
Sound power level(dBA)77777979798079
Sound power level - HESP Option (100Pa)(dBA)85858989898989
Unit amps (4) (5)
Unit rated amps(A)34384550566474
Unit rated amps - HESP Option (100Pa)(A)35394752576675
Unit start up amps(A)116160167183188189198
Unit start up amps - HESP Option (100Pa)(A)117161169185190191199
Short Circuit Unit Capacity (9)(kA)12121212121215
Compressor
Compressor Number per Circuit#2222223
TypeScrollScrollScrollScrollScrollScrollScroll
Model Circuit1 / Circuit 27.5+7.57.5+1010+1010+1313+1315+1512+12+12
Motor RPM(rpm)2900
Without HYM
Nominal water connection size (Grooved coupling) -
With HYM
Hydraulic Module Components
Expansion Tank Volume(l)25252525252535
Max User water loop Volume for factory mounted
expansion tank (1)
Optional water Buffer tank volume(l)324324324324324324444
Max. Water-side Operating Pressure without pump
package
Max. Water-side Operating Pressure with pump
package
Condenser
TypeFull aluminum Micro channel heat exchanger
Quantity of coil#111111 2
Face area per circuit(m²)2.232.232.962.962.962.964.46
Condenser Fan
Quantity#1122222
Diameter(mm)800
Fan / motor TypePropeller fan : Fixed speed AC motor / Variable speed - EC motor
Airfl ow per Fan(m3/h)13788138281236212362123701237513827
Airfl ow per Fan - HESP Option (100Pa)(m3/h)13753137181224812231122111219313727
Motor RPM(rpm)686686686686686686686
Motor RPM - HESP Option (100Pa)(rpm)915915915915915915915
Single pump - Standard head pressure(kg)46464649494945
Single pump - High head pressure(kg)51515151515149
Twin pump - Standard head pressure(kg)70707075757571
Twin pump - High head pressure(kg)82828282828286
Partial heat recovery option(kg)1.481.481.481.483.823.823.82
Water Buffer tank option(kg)319319319319319319425
System data
Nb of refrigerant circuit#1111111
Minimum cooling load % (6)%50435043505033
(1) At Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C according to EN14511:2013
(4) under 400V/3/50Hz
(5) Rated Condition without Pump Package
(6) Percent minimum load can be lowered on demand to local sales offi ce.
(7) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(8) Maximum ambient operation is for unit at 12°C / 7°C
(9) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch.
Electrical & system data are subject to change without notice. Please refer to unit nameplate data.
Table 2 - CGAX Standard effi ciency and Low Noise (continued)
CGAX
039
Eurovent Performances (1)
Net Cooling Capacity(kW)111127971161 29147164
Total Power input in cooling(kW)38413539475158
Total Power input in cooling - HESP Option (100Pa)(kW)39453643505761
EER2.923.082.792.942.782.862.83
EER - HESP Option (100Pa)2.822.812.722.732.612.552.68
ESEER4.133.983.833.643.593.753.81
Eurovent Effi ciency class CoolingBCCBBCC
Sound power level(dBA)80828182828283
Sound power level - HESP Option (100Pa)(dBA)90929092929292
Unit amps (4) (5)
Unit rated amps(A)81967790101111128
Unit rated amps - HESP Option (100Pa)(A)83987893104114131
Unit start up amps(A)214221198212233243253
Unit start up amps - HESP Option (100Pa)(A)215224200215236247256
Short Circuit Unit Capacity (9)(kA)15151515151515
Compressor
Compressor Number per Circuit#3322222
TypeScrollScrollScrollScrollScrollScrollScroll
Model Circuit1 / Circuit 213+13+1315+15+15 7.5+10 / 7.5+10 10+10 / 10+10 10+13 /10+13 13+13 / 13+13 15+15 / 15+15
Motor RPM(rpm)2900
Without HYM
Nominal water connection size (Grooved coupling) -
With HYM
Hydraulic Module Components
Expansion Tank Volume(l)35353535353535
Max User water loop Volume for factory mounted
expansion tank (1)
Optional water Buffer tank volume(l)444444444444444444444
Max. Water-side Operating Pressure without pump
package
Max. Water-side Operating Pressure with pump
package
Condenser
TypeFull aluminum Micro channel heat exchanger
Quantity of coil#222222 2
Face area per circuit(m²)5.935.932.232.962.962.962.96
Condenser Fan
Quantity#2324444
Diameter(mm)800
Fan / motor TypePropeller fan : Fixed speed AC motor / Variable speed - EC motor
Airfl ow per Fan(m3/h)14690136761468712358123631259212374
Airfl ow per Fan - HESP Option (100Pa)(m3/h)14660135951468612249122331244712205
Motor RPM(rpm)686686686686686686686
Motor RPM - HESP Option (100Pa)(rpm)915915915915915915915
Single pump - Standard head pressure(kg)47474547474747
Single pump - High head pressure(kg)49494949494949
Twin pump - Standard head pressure(kg)75757575757575
Twin pump - High head pressure(kg)86868484848484
Partial heat recovery option(kg)4.64.62x1.482x1.482x1.482x3.822x3.82
Water Buffer tank option(kg)425425425425425425425
System data
Nb of refrigerant circuit#1122222
Minimum cooling load % (6)%33332225222525
(1) At Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C according to EN14511:2013
(4) under 400V/3/50Hz
(5) Rated Condition without Pump Package
(6) Percent minimum load can be lowered on demand to local sales offi ce.
(7) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(8) Maximum ambient operation is for unit at 12°C / 7°C
(9) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch.
Electrical & system data are subject to change without notice. Please refer to unit nameplate data.
(in) - (mm) 2” - 60.32” - 60.3 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1
(in) - (mm) 3” O D - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1
(kPa)1000
(kPa)400
SE-LN
(l)2000200020002000200020002000
G 1”1/4
(31.75 mm)
CGAX
045
SE-LN
G 1”1/4
(31.75 mm)
CGAX
035
SE-LN
G 1”1/4
(31.75 mm)
CGAX
040
SE-LN
G 1”1/4
(31.75 mm)
CGAX
046
SE-LN
G 1”1/4
(31.75 mm)
CGAX
052
SE-LN
G 1”1/4
(31.75 mm)
CGAX
SE-LN
G 1”1/4
(31.75 mm)
060
CG-PRC026C-GB
17
General Data
Table 3 - CGAX High Effi ciency and Standard Noise
CGAX
015
Eurovent Performances (1)
Net Cooling Capacity(kW)43495965748299
Total Power input in cooling(kW)15171922262933
EER2.982.883.082.952.872.842.96
ESEER3.973.983.964.033.933.864.04
Eurovent Effi ciency class CoolingBCBBCCB
Sound power level(dBA)83838585858684
Unit amps (4) (5)
Unit rated amps(A)35394752576675
Unit rated amps - HESP Option (100Pa)(A)35394752576675
Unit start up amps(A)117161169185190191199
Unit start up amps - HESP Option (100Pa)(A)117161169185190191199
Short Circuit Unit Capacity (9)(kA)12121212121215
Compressor
Compressor Number per Circuit#2222223
TypeScrollScrollScrollScrollScrollScrollScroll
Model Circuit1 / Circuit 27.5+7.57.5+1010+1010+1313+1315+1512+12+12
Motor RPM(rpm)2900
Without HYM
Nominal water connection size (Grooved coupling) -
With HYM
Hydraulic Module Components
Expansion Tank Volume(l)25252525252535
Max User water loop Volume for factory mounted
expansion tank (1)
Optional water Buffer tank volume(l)324324324324324324444
Max. Water-side Operating Pressure without pump
package
Max. Water-side Operating Pressure with pump
package
Condenser
TypeFull aluminum Micro channel heat exchanger
Quantity of coil#111111 2
Face area per circuit(m²)2.232.232.962.962.962.964.46
Condenser Fan
Quantity#1122222
Diameter(mm)800
Fan / motor TypePropeller fan : Variable speed - EC motor / HESP MAX SPEED
Airfl ow per Fan(m3/h)13788138281236212362123701237513827
Motor RPM(rpm)150 - 686 RPM
Single pump - Standard head pressure(kg)46464649494945
Single pump - High head pressure(kg)51515151515149
Twin pump - Standard head pressure(kg)70707075757571
Twin pump - High head pressure(kg)82828282828286
Partial heat recovery option(kg)1.481.481.481.483.823.823.82
Water Buffer tank option(kg)319319319319319319425
System data
Nb of refrigerant circuit#1111111
Minimum cooling load % (6)%50435043505033
(1) At Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C according to EN14511:2013
(2) At Evaporator water temperature : 6.6°C (44°F) / 12.2°C (54°F) - condenser air temperature 46°C (114.8°F)
(4) under 400V/3/50Hz
(5) Rated Condition without Pump Package
(6) Percent minimum load can be lowered on demand to local sales offi ce.
(7) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(8) Maximum ambient operation is for unit at 12°C / 7°C
(9) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch.
Electrical & system data are subject to change without notice. Please refer to unit nameplate data.
Table 3 - CGAX High Effi ciency and Standard Noise (continued)
CGAX
039
Eurovent Performances (1)
Net Cooling Capacity(kW)111127971161 29147164
Total Power input in cooling(kW)38413539475158
EER2.923.082.792.942.782.862.83
ESEER4.224.143.873.823.763.843.88
Eurovent Effi ciency class CoolingBCCBBCC
Sound power level(dBA)85878688888889
Unit amps (4) (5)
Unit rated amps(A)83987893104114131
Unit rated amps - HESP Option (100Pa)(A)83987893104114131
Unit start up amps(A)215224200215236247256
Unit start up amps - HESP Option (100Pa)(A)215224200215236247256
Short Circuit Unit Capacity (9)(kA)15151515151515
Compressor
Compressor Number per Circuit#3322222
TypeScrollScrollScrollScrollScrollScrollScroll
Model Circuit1 / Circuit 213+13+13 15+15+15 7.5+10 / 7.5+10 10+10 / 10+10 10+13 /10+13 13+13 / 13+13 15+15 / 15+15
Motor RPM(rpm)2900
Without HYM
Nominal water connection size (Grooved coupling) -
With HYM
Hydraulic Module Components
Expansion Tank Volume(l)35353535353535
Max User water loop Volume for factory mounted
expansion tank (1)
Optional water Buffer tank volume(l)444444444444444444444
Max. Water-side Operating Pressure without pump
package
Max. Water-side Operating Pressure with pump
package
Condenser
TypeFull aluminum Micro channel heat exchanger
Quantity of coil#222222 2
Face area per circuit(m²)5.935.932.232.962.962.962.96
Condenser Fan
Quantity#2324444
Diameter(mm)800
Fan / motor TypePropeller fan : Variable speed - EC motor / HESP MAX SPEED
Airfl ow per Fan(m
Motor RPM(rpm)150 - 686 RPM
Single pump - Standard head pressure(kg)47474547474747
Single pump - High head pressure(kg)49494949494949
Twin pump - Standard head pressure(kg)75757575757575
Twin pump - High head pressure(kg)86868484848484
Partial heat recovery option(kg)4.64.62x1.482x1.482x1.482x3.822x3.82
Water Buffer tank option(kg)425425425425425425425
System data
Nb of refrigerant circuit#1122222
Minimum cooling load % (6)%33332225222525
(1) At Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C according to EN14511:2013
(2) At Evaporator water temperature : 6.6°C (44°F) / 12.2°C (54°F) - condenser air temperature 46°C (114.8°F)
(4) under 400V/3/50Hz
(5) Rated Condition without Pump Package
(6) Percent minimum load can be lowered on demand to local sales offi ce.
(7) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(8) Maximum ambient operation is for unit at 12°C / 7°C
(9) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch.
Electrical & system data are subject to change without notice. Please refer to unit nameplate data.
(in) - (mm) 2” - 60.32” - 60.3 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1
(in) - (mm) 3” O D - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1
(kPa)1000
(kPa)400
HE-SN
(l)2000200020002000200020002000
3
/h)14690136761468712358123631259212374
G 1”1/4
(31.75 mm)
CGAX
045
HE-SN
G 1”1/4
(31.75 mm)
CGAX
035
HE-SN
G 1”1/4
(31.75 mm)
CGAX
040
HE-SN
G 1”1/4
(31.75 mm)
CGAX
046
HE-SN
G 1”1/4
(31.75 mm)
CGAX
052
HE-SN
G 1”1/4
(31.75 mm)
CGAX
HE-SN
G 1”1/4
(31.75 mm)
060
CG-PRC026C-GB
19
General Data
Table 4 - CGAX High Effi ciency and Low Noise
CGAX
015
Eurovent Performances (1)
Net Cooling Capacity(kW)43495965748299
Total Power input in cooling(kW)15171922262933
EER2.982.883.082.952.872.842.96
ESEER3.973.983.964.033.933.864.04
Eurovent Effi ciency class CoolingBCBBCCB
Sound power level(dBA)77777979798079
Unit amps (4) (5)
Unit rated amps(A)35394752576675
Unit rated amps - HESP Option (100Pa)(A)35394752576675
Unit start up amps(A)117161169185190191199
Unit start up amps - HESP Option (100Pa)(A)117161169185190191199
Short Circuit Unit Capacity (9)(kA)12121212121215
Compressor
Compressor Number per Circuit#2222223
TypeScrollScrollScrollScrollScrollScrollScroll
Model Circuit1 / Circuit 27.5+7.57.5+1010+1010+1313+1315+1512+12+12
Motor RPM(rpm)2900
Without HYM
Nominal water connection size (Grooved coupling) -
With HYM
Hydraulic Module Components
Expansion Tank Volume(l)25252525252535
Max User water loop Volume for factory mounted
expansion tank (1)
Optional water Buffer tank volume(l)324324324324324324444
Max. Water-side Operating Pressure without pump
package
Max. Water-side Operating Pressure with pump
package
Condenser
TypeFull aluminum Micro channel heat exchanger
Quantity of coil#111111 2
Face area per circuit(m²)2.232.232.962.962.962.964.46
Condenser Fan
Quantity#1122222
Diameter(mm)800
Fan / motor TypePropeller fan : Variable speed - EC motor
Airfl ow per Fan(m3/h)13788138281236212362123701237513827
Motor RPM(rpm)150 - 686 RPM
Single pump - Standard head pressure(kg)46464649494945
Single pump - High head pressure(kg)51515151515149
Twin pump - Standard head pressure(kg)70707075757571
Twin pump - High head pressure(kg)82828282828286
Partial heat recovery option(kg)1.481.481.481.483.823.823.82
Water Buffer tank option(kg)319319319319319319425
System data
Nb of refrigerant circuit#1111111
Minimum cooling load % (6)%50435043505033
(1) At Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C according to EN14511:2013
(4) under 400V/3/50Hz
(5) Rated Condition without Pump Package
(6) Percent minimum load can be lowered on demand to local sales offi ce.
(7) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(8) Maximum ambient operation is for unit at 12°C / 7°C
(9) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch.
Electrical & system data are subject to change without notice. Please refer to unit nameplate data.
Table 4 - CGAX High Effi ciency and Low Noise (continued)
CGAX
039
Eurovent Performances (1)
Net Cooling Capacity(kW)111127971161 29147164
Total Power input in cooling(kW)38413539475158
EER2.923.082.792.942.782.862.83
ESEER4.224.143.873.823.763.843.88
Eurovent Effi ciency class CoolingBCCBBCC
Sound power level(dBA)80828182828283
Unit amps (4) (5)
Unit rated amps(A)83987893104114131
Unit rated amps - HESP Option (100Pa)(A)83987893104114131
Unit start up amps(A)215224200215236247256
Unit start up amps - HESP Option (100Pa)(A)215224200215236247256
Short Circuit Unit Capacity (9)(kA)15151515151515
Compressor
Compressor Number per Circuit#3322222
TypeScrollScrollScrollScrollScrollScrollScroll
Model Circuit1 / Circuit 213+13+13 15+15+15 7.5+10 / 7.5+10 10+10 / 10+10 10+13 /10+13 13+13 / 13+13 15+15 / 15+15
Motor RPM(rpm)2900
Single pump - Standard head pressure(kg)47474547474747
Single pump - High head pressure(kg)49494949494949
Twin pump - Standard head pressure(kg)75757575757575
Twin pump - High head pressure(kg)86868484848484
Partial heat recovery option(kg)4.64.62x1.482x1.482x1.482x3.822x3.82
Water Buffer tank option(kg)425425425425425425425
System data
Nb of refrigerant circuit#1122222
Minimum cooling load % (6)%33332225222525
(1) At Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C according to EN14511:2013
(4) under 400V/3/50Hz
(5) Rated Condition without Pump Package
(6) Percent minimum load can be lowered on demand to local sales offi ce.
(7) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(8) Maximum ambient operation is for unit at 12°C / 7°C
(9) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch.
Electrical & system data are subject to change without notice. Please refer to unit nameplate data.
(in) - (mm) 2” - 60.32” - 60.3 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1
(in) - (mm) 3” O D - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1
(kPa)1000
(kPa)400
HE-LN
(l)2000200020002000200020002000
3
/h)14690136761468712358123631259212374
G 1”1/4
(31.75 mm)
CGAX
045
HE-LN
G 1”1/4
(31.75 mm)
CGAX
035
HE-LN
G 1”1/4
(31.75 mm)
CGAX
040
HE-LN
G 1”1/4
(31.75 mm)
CGAX
046
HE-LN
G 1”1/4
(31.75 mm)
CGAX
052
HE-LN
G 1”1/4
(31.75 mm)
CGAX
HE-LN
G 1”1/4
(31.75 mm)
060
CG-PRC026C-GB
21
General Data
Table 5 - CXAX Standard effi ciency and Standard Noise
CXAX
015
Eurovent Performances (1)
Net Cooling Capacity(kW)42485665727994
Total Power input in cooling(kW)1417192 2252832
Total Power input in cooling - HESP Option (100Pa)(kW)15172024273034
EER2.902.832.912.972.842.842.90
EER - HESP Option (100Pa)2.802.762.732.712.632.622.78
ESEER3.713.753.633.803.843.823.96
Eurovent Effi ciency class CoolingBCBBCCB
Sound power level(dBA)8484858 58 58 68 6
Sound power level - HESP Option (100Pa)(dBA)86868 99 29 48 99 5
Heating application data (2)
Net Heating Capacity(A)43515763697896
Total Power input in heating(A)14161921232530
Total Power input in heating - HESP Option (100Pa)(A)15172123262732
COP(A)3.093.152.983.083.013.093.19
COP - HESP Option (100Pa)2.872.972.712.752.672.893.01
Eurovent Effi ciency class HeatingBBCBBBBηs126125115124125124128
SCOP(kA)3.213.212.953.173.193.183.29
Unit amps (4) (5)
Unit rated amps(A)34384550566474
Unit rated amps - HESP Option (100Pa)(A)35394752576675
Unit start up amps(A)116160167183188189198
Unit start up amps - HESP Option (100Pa)(A)117161169185190191199
Short Circuit Unit Capacity (9)(kA)12121212121215
Compressor
Compressor Number per Circuit#2222223
TypeScrollScrollScrollScrollScrollScrollScroll
Model Circuit1 / Circuit 27.5+7.57.5+1010+1010+1313+1315+1512+12+12
Motor RPM(rpm)2900
Expansion Tank Volume(l)25252525252535
Max User water loop Volume for factory mounted expansion tank (1)(l)1450145014501450145014502000
Optional water Buffer tank volume(l)324324324324324324444
Max. Water-side Operating Pressure without pump package(kPa)1000
Max. Water-side Operating Pressure with pump package(kPa)400
Condenser
TypeAluminum fi ns & copper tubes heat exchanger
Quantity of coil#1111112
Face area per circuit(m²)2.962.962.962.962.963.465.93
Condenser Fan
Quantity#1122222
Diameter(mm)800
Fan / motor TypePropeller fan : Fixed speed AC motor / Variable speed - EC motor / HESP MAX SPEED
Airfl ow per Fan(m3/h)14949149601496612721127261335214959
Airfl ow per Fan - HESP Option (100Pa)(m3/h)15048150181497212622126081325815019
Motor RPM(rpm)6866866866 866866 86686
Motor RPM - HESP Option (100Pa)(rpm)91 591591 5915915915915
Single pump - Standard head pressure(kg)46464649494 94 5
Single pump - High head pressure(kg)515151515 15 14 9
Twin pump - Standard head pressure(kg)70707075757571
Twin pump - High head pressure(kg)82828282828286
Partial heat recovery option(kg)1.481.481.481.483.823.823.82
Water Buffer tank option(kg)31931931931931 9319425
System data
Nb of refrigerant circuit#1111111
Minimum cooling load % (6)%50435043505033
POE Oil typeOIL058E / OIL057E
(1) At Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C according to EN14511:2013
(2) At Evaporator water temperature : 40°C / 45°C - Condenser air. DB/WB 7°C / 6°C according to EN14511:2013
(4) under 400V/3/50Hz
(5) Rated Condition without Pump Package
(6) Minimum ambient in heating operation is for unit at 40°C / 45°C
(7) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(8) Maximum ambient operation is for unit at 12°C / 7°C
(9) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch.
Electrical & system data are subject to change without notice. Please refer to unit nameplate data.
SE-SN
G 1”1/4
(31.75 mm)
CXAX
017
SE-SN
G 1”1/4
(31.75 mm)
CXAX
020
SE-SN
G 1”1/4
(31.75 mm)
CXAX
023
SE-SN
G 1”1/4
(31.75 mm)
CXAX
026
SE-SN
G 1”1/4
(31.75 mm)
22
CXAX
030
SE-SN
G 1”1/4
(31.75 mm)
CG-PRC026C-GB
(31.75 mm)
CXAX
036
SE-SN
G 1”1/4
General Data
Table 5 - CXAX Standard effi ciency and Standard Noise (continued)
CXAX
039
Eurovent Performances (1)
Net Cooling Capacity(kW)10 811894114127146162
Total Power input in cooling(kW)3641343 7434955
Total Power input in cooling - HESP Option (100Pa)(kW)38453540465361
EER3.002.882.813.062.962.952.93
EER - HESP Option (100Pa)2.832.652.712.812.752.732.66
ESEER3.953.843.913.883.813.913.88
Eurovent Effi ciency class CoolingBCCBBBB
Sound power level(dBA)8788878 98 88 88 9
Sound power level - HESP Option (100Pa)(dBA)95919 09 29 59 79 2
Heating application data (2)
Net Heating Capacity(A)110120101114127139162
Total Power input in heating(A)35393237424652
Total Power input in heating - HESP Option (100Pa)(A)38433441475157
COP(A)3.143.123.163.083.023.003.11
COP - HESP Option (100Pa)2.902.792.972.792.712.722.84
Eurovent Effi ciency class HeatingBBBBBBBηs125126126120120126128
SCOP(kA)3.203.213.233.063.083.223.26
Unit amps (4) (5)
Unit rated amps(A)83967790101111128
Unit rated amps - HESP Option (100Pa)(A)86987893104114131
Unit start up amps(A)216221198212233243253
Unit start up amps - HESP Option (100Pa)(A)218224200215236247256
Short Circuit Unit Capacity (9)(kA)15151515151515
Compressor
Compressor Number per Circuit#3322222
TypeScrollScrollScrollScrollScrollScrollScroll
Model Circuit1 / Circuit 213+13+1315+15+15 7.5+10 / 7.5+10 10+10 / 10+10 10+13 /10+13 13+13 / 13+13 15+15 / 15+15
Motor RPM(rpm)2900
Evaporator
Quantity#1111111
TypeStainless steel Copper Brazed plate Heat exchanger
Evaporator modelP120Tx110P120Tx110DP300x82DP300x82DP300x82DP300x114DP300x114
Evaporator Water Content volume(l)13.313.38.58.58.511.811.8
Nominal water connection size (Grooved coupling) - Without HYM (in) - (mm)2” - 60.32” - 60.33” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1
Nominal water connection size (Grooved coupling) - With HYM(in) - (mm) 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1
Hydraulic Module Components
Expansion Tank Volume(l)35353535353535
Max User water loop Volume for factory mounted expansion tank (1)(l)2000200020002000200020002000
Optional water Buffer tank volume(l)444444444444444444444
Max. Water-side Operating Pressure without pump package(kPa)1000
Max. Water-side Operating Pressure with pump package(kPa)400
Condenser
TypeAluminum fi ns & copper tubes heat exchanger
Quantity of coil#2222222
Face area per circuit(m²)5.935.932.962.962.962.963.46
Condenser Fan
Quantity#3324444
Diameter(mm)800
Fan / motor TypePropeller fan : Fixed speed AC motor / Variable speed - EC motor / HESP MAX SPEED
Airfl ow per Fan(m3/h)13823138281496014964127251272513351
Airfl ow per Fan - HESP Option (100Pa)(m3/h)13806137861501514980126261261113261
Motor RPM(rpm)6866866866 866866 86686
Motor RPM - HESP Option (100Pa)(rpm)91 591591 5915915915915
Single pump - Standard head pressure(kg)47474547474 74 7
Single pump - High head pressure(kg)494949494 94 94 9
Twin pump - Standard head pressure(kg)75757575757575
Twin pump - High head pressure(kg)86868484848484
Partial heat recovery option(kg)4.64.62x1.482x1.482x1.482x3.822x3.82
Water Buffer tank option(kg)42542542542542 5425425
System data
Nb of refrigerant circuit#1122222
Minimum cooling load % (6)%33332225222525
POE Oil typeOIL058E / OIL057E
(1) At Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C according to EN14511:2013
(2) At Evaporator water temperature : 40°C / 45°C - Condenser air. DB/WB 7°C/6°C according to EN14511:2013
(4) under 400V/3/50Hz
(5) Rated Condition without Pump Package
(6) Minimum ambient in heating operation is for unit at 40°C / 45°C
(7) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(8) Maximum ambient operation is for unit at 12°C / 7°C
(9) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch.
Electrical & system data are subject to change without notice. Please refer to unit nameplate data.
SE-SN
G 1”1/4
(31.75 mm)
CXAX
045
SE-SN
G 1”1/4
(31.75 mm)
CXAX
035
SE-SN
G 1”1/4
(31.75 mm)
CXAX
040
SE-SN
G 1”1/4
(31.75 mm)
CXAX
046
SE-SN
G 1”1/4
(31.75 mm)
CG-PRC026C-GB
CXAX
052
SE-SN
G 1”1/4
(31.75 mm)
CXAX
060
SE-SN
G 1”1/4
(31.75 mm)
23
General Data
Table 6 - CXAX Standard effi ciency and Low Noise
CXAX
015
Eurovent Performances (1)
Net Cooling Capacity(kW)434958677 48 29 6
Total Power input in cooling(kW)1417202 2252932
Total Power input in cooling - HESP Option (100Pa)(kW)15172024273034
EER3.012.932.933.032.902.892.99
EER - HESP Option (100Pa)2.882.812.822.802.702.722.85
ESEER3.713.753.633.803.843.823.96
Eurovent Effi ciency class CoolingBBBBBCB
Sound power level(dBA)7878818 08 08 18 0
Sound power level - HESP Option (100Pa)(dBA)86868 99 29 48 99 5
Heating application data (2)
Net Heating Capacity(kW)43515763697896
Total Power input in heating(kW)1416192123253 0
Total Power input in heating - HESP Option (100Pa)(kW)1 51 72123262732
COP3.093.152.983.083.013.093.19
COP - HESP Option (100Pa)2.872.972.712.752.672.893.01
Eurovent Effi ciency class HeatingBBCBBBBηs126125115124125124128
SCOP3.213.212.953.173.193.183.29
Unit amps (4) (5)
Unit rated amps(A)34384550566474
Unit rated amps - HESP Option (100Pa)(A)35394752576675
Unit start up amps(A)116160167183188189198
Unit start up amps - HESP Option (100Pa)(A)117161169185190191199
Short Circuit Unit Capacity (9)(kA)12121212121215
Compressor
Compressor Number per Circuit#2222223
TypeScrollScrollScrollScrollScrollScrollScroll
Model Circuit1 / Circuit 27.5+7.57.5+1010+1010+1313+1315+1512+12+12
Motor RPM(rpm)2900
Expansion Tank Volume(l)25252525252535
Max User water loop Volume for factory mounted expansion tank (1)(l)1450145014501450145014502000
Optional water Buffer tank volume(l)324324324324324324444
Max. Water-side Operating Pressure without pump package(kPa)1000
Max. Water-side Operating Pressure with pump package(kPa)400
Condenser
TypeAluminum fi ns & copper tubes heat exchanger
Quantity of coil#1111112
Face area per circuit(m²)2.962.962.962.962.963.465.93
Condenser Fan
Quantity#1122222
Diameter(mm)800
Fan / motor TypePropeller fan : Fixed speed AC motor / Variable speed - EC motor
Airfl ow per Fan(m3/h)14949149601496612721127261335214959
Airfl ow per Fan - HESP Option (100Pa)(m3/h)15048150181497212622126081325815019
Power per Motor(kW)0.89 / 1.95
Rated Amps per Motor(A)2.22 / 3
Motor RPM(rpm)686686686686686686686
Motor RPM - HESP Option (100Pa)(rpm)91 591591 5915915915915
Single pump - Standard head pressure(kg)46464649494 94 5
Single pump - High head pressure(kg)515151515 15 14 9
Twin pump - Standard head pressure(kg)70707075757571
Twin pump - High head pressure(kg)82828282828286
Partial heat recovery option(kg)1.481.481.481.483.823.823.82
Water Buffer tank option(kg)319319319319319319425
Operating limits
Minimum Starting/Operating Ambient (7)
Standard ambient unit in cooling mode(°C)5
Low Ambient (Option) in cooling mode(°C)-18
In Heating mode(°C)-15
Maximum ambient operation Standard ambient (8)(°C)46
System data
Nb of refrigerant circuit#1111111
Minimum cooling load % (6)%50435043505033
POE Oil typeOIL058E / OIL057E
(1) At Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C according to EN14511:2013
(2) At Evaporator water temperature : 40°C / 45°C - Condenser air. DB/WB 7°C/6°C according to EN14511:2013
(4) under 400V/3/50Hz
(5) Rated Condition without Pump Package
(6) Minimum ambient in heating operation is for unit at 40°C / 45°C
(7) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(8) Maximum ambient operation is for unit at 12°C / 7°C
(9) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch.
Electrical & system data are subject to change without notice. Please refer to unit nameplate data.
SE-LN
G 1”1/4
(31.75 mm)
CXAX
017
SE-LN
G 1”1/4
(31.75 mm)
CXAX
020
SE-LN
G 1”1/4
(31.75 mm)
CXAX
023
SE-LN
G 1”1/4
(31.75 mm)
CXAX
026
SE-LN
G 1”1/4
(31.75 mm)
24
CXAX
030
SE-LN
G 1”1/4
(31.75 mm)
CG-PRC026C-GB
(31.75 mm)
CXAX
036
SE-LN
G 1”1/4
General Data
Table 6 - CXAX Standard effi ciency and Low Noise (continued)
CXAX
039
Eurovent Performances (1)
Net Cooling Capacity(kW)10 912198111131145161
Total Power input in cooling(kW)3642333 9435057
Total Power input in cooling - HESP Option (100Pa)(kW)38453540465361
EER3.062.872.962.863.032.912.85
EER - HESP Option (100Pa)2.862.712.832.752.822.712.65
ESEER3.953.843.913.883.813.913.88
Eurovent Effi ciency class CoolingBCBCBBC
Sound power level(dBA)8182818 48 38 38 4
Sound power level - HESP Option (100Pa)(dBA)95919 09 29 59 79 2
Heating application data (2)
Net Heating Capacity(kW)11 01201011141271391 62
Total Power input in heating(kW)3539323742465 2
Total Power input in heating - HESP Option (100Pa)(kW)3 84 33441475157
COP3.143.123.163.083.023.003.11
COP - HESP Option (100Pa)2.902.792.972.792.712.722.84
Eurovent Effi ciency class HeatingBBBBBBBηs125126126120120126128
SCOP3.203.213.233.063.083.223.26
Unit amps (4) (5)
Unit rated amps(A)83967790101111128
Unit rated amps - HESP Option (100Pa)(A)86987893104114131
Unit start up amps(A)216221198212233243253
Unit start up amps - HESP Option (100Pa)(A)218224200215236247256
Short Circuit Unit Capacity (9)(kA)15151515151515
Compressor
Compressor Number per Circuit#3322222
TypeScrollScrollScrollScrollScrollScrollScroll
Model Circuit1 / Circuit 213+13+1315+15+15 7.5+10 / 7.5+10 10+10 / 10+10 10+13 /10+13 13+13 / 13+13 15+15 / 15+15
Motor RPM(rpm)2900
Evaporator
Quantity#1111111
TypeStainless steel Copper Brazed plate Heat exchanger
Evaporator modelP120Tx110P120Tx110DP300x82DP300x82DP300x82DP300x114DP300x114
Evaporator Water Content volume(l)13.313.38.58.58.511.811.8
Nominal water connection size (Grooved coupling) - Without HYM (in) - (mm)2” - 60.32” - 60.33” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1
Nominal water connection size (Grooved coupling) - With HYM(in) - (mm) 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1
Hydraulic Module Components
Expansion Tank Volume(l)35353535353535
Max User water loop Volume for factory mounted expansion tank (1)(l)2000200020002000200020002000
Optional water Buffer tank volume(l)444444444444444444444
Max. Water-side Operating Pressure without pump package(kPa)1000
Max. Water-side Operating Pressure with pump package(kPa)400
Condenser
TypeAluminum fi ns & copper tubes heat exchanger
Quantity of coil#2222222
Face area per circuit(m²)5.935.932.962.962.962.963.46
Condenser Fan
Quantity#3324444
Diameter(mm)800
Fan / motor TypePropeller fan : Fixed speed AC motor / Variable speed - EC motor
Airfl ow per Fan(m3/h)13823138281496014964127251272513351
Airfl ow per Fan - HESP Option (100Pa)(m3/h)13806137861501514980126261261113261
Power per Motor(kW)0.89 / 1.95
Rated Amps per Motor(A)2.22 / 3
Motor RPM(rpm)686686686686686686686
Motor RPM - HESP Option (100Pa)(rpm)91 591591 5915915915915
Single pump - Standard head pressure(kg)47474547474 74 7
Single pump - High head pressure(kg)494949494 94 94 9
Twin pump - Standard head pressure(kg)75757575757575
Twin pump - High head pressure(kg)86868484848484
Partial heat recovery option(kg)4.64.62x1.482x1.482x1.482x3.822x3.82
Water Buffer tank option(kg)425425425425425425425
Operating limits
Minimum Starting/Operating Ambient (7)
Standard ambient unit in cooling mode(°C)-10
Low Ambient (Option) in cooling mode(°C)-20
In Heating mode(°C)-20
Maximum ambient operation Standard ambient (8)(°C)46
System data
Nb of refrigerant circuit#1122222
Minimum cooling load % (6)%33332225222525
POE Oil typeOIL058E / OIL057E
(1) At Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C according to EN14511:2013
(2) At Evaporator water temperature : 40°C / 45°C - Condenser air. DB/WB 7°C/6°C according to EN14511:2013
(4) under 400V/3/50Hz
(5) Rated Condition without Pump Package
(6) Minimum ambient in heating operation is for unit at 40°C / 45°C
(7) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(8) Maximum ambient operation is for unit at 12°C / 7°C
(9) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch.
Electrical & system data are subject to change without notice. Please refer to unit nameplate data.
SE-LN
G 1”1/4
(31.75 mm)
CXAX
045
SE-LN
G 1”1/4
(31.75 mm)
CXAX
035
SE-LN
G 1”1/4
(31.75 mm)
CXAX
040
SE-LN
G 1”1/4
(31.75 mm)
CXAX
046
SE-LN
G 1”1/4
(31.75 mm)
CG-PRC026C-GB
CXAX
052
SE-LN
G 1”1/4
(31.75 mm)
CXAX
060
SE-LN
G 1”1/4
(31.75 mm)
25
General Data
Table 7 - CXAX High Effi ciency and Standard Noise
CXAX
015
Eurovent Performances (1)
Net Cooling Capacity(kW)424856657 27 99 4
Total Power input in cooling(kW)1417192 2252832
EER2.902.832.912.972.842.842.90
ESEER3.773.803.844.033.963.984.09
Eurovent Effi ciency class CoolingBCBBCCB
Sound power level(dBA)8484858 58 58 68 6
Heating application data (2)
Net Heating Capacity(kW)43515763697896
Total Power input in heating(kW)1416192123253 0
COP3.093.152.983.083.013.093.19
Eurovent Effi ciency class HeatingBBCBBBBηs(%)127129118127128128134
SCOP3.263.293.033.253.273.283.42
Unit amps (4) (5)
Unit rated amps(A)35394752576675
Unit rated amps - HESP Option (100Pa)(A)35394752576675
Unit start up amps(A)117161169185190191199
Unit start up amps - HESP Option (100Pa)(A)117161169185190191199
Short Circuit Unit Capacity (9)(kA)12121212121215
Compressor
Compressor Number per Circuit#2222223
TypeScrollScrollScrollScrollScrollScrollScroll
Model Circuit1 / Circuit 27.5+7.57.5+1010+1010+1313+1315+1512+12+12
Motor RPM(rpm)2900
Expansion Tank Volume(l)25252525252535
Max User water loop Volume for factory mounted expansion tank (1)(l)1450145014501450145014502000
Optionnal water Buffer tank volume(l)324324324324324324444
Max. Water-side Operating Pressure without pump package(kPa)1000
Max. Water-side Operating Pressure with pump package(kPa)400
Condenser
TypeAluminum fi ns & copper tubes heat exchanger
Quantity of coil#1111112
Face area per circuit(m²)2.962.962.962.962.963.465.93
Condenser Fan
Quantity#1122222
Diameter(mm)800
Fan / motor TypePropeller fan : Variable speed - EC motor / HESP MAX SPEED
Airfl ow per Fan(m3/h)14949149601496612721127261335214959
Power per Motor(kW)1.95 / 1.95
Rated Amps per Motor(A)3 / 3
Motor RPM(rpm)150 - 686 RPM
Single pump - Standard head pressure(kg)46464649494 94 5
Single pump - High head pressure(kg)515151515 15 14 9
Twin pump - Standard head pressure(kg)70707075757571
Twin pump - High head pressure(kg)82828282828286
Partial heat recovery option(kg)1.481.481.481.483.823.823.82
Water Buffer tank option(kg)319319319319319319425
System data
Nb of refrigerant circuit#1111111
Minimum cooling load % (6)%50435043505033
POE Oil typeOIL058E / OIL057E
(1) At Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C according to EN14511:2013
(2) At Evaporator water temperature : 40°C / 45°C - Condenser air. DB/WB 7°C/6°C according to EN14511:2013
(4) under 400V/3/50Hz
(5) Rated Condition without Pump Package
(6) Minimum ambient in heating operation is for unit at 40°C / 45°C
(7) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(8) Maximum ambient operation is for unit at 12°C / 7°C
(9) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch.
Electrical & system data are subject to change without notice. Please refer to unit nameplate data.
HE-SN
G 1”1/4
(31.75 mm)
CXAX
017
HE-SN
G 1”1/4
(31.75 mm)
CXAX
020
HE-SN
G 1”1/4
(31.75 mm)
CXAX
023
HE-SN
G 1”1/4
(31.75 mm)
CXAX
026
HE-SN
G 1”1/4
(31.75 mm)
CXAX
030
HE-SN
G 1”1/4
(31.75 mm)
(31.75 mm)
CXAX
036
HE-SN
G 1”1/4
26
CG-PRC026C-GB
General Data
Table 7 - CXAX High Effi ciency and Standard Noise (continued)
CXAX
039
Eurovent Performances (1)
Net Cooling Capacity(kW)10 811894114127146162
Total Power input in cooling(kW)3641343 7434955
EER3.002.882.813.062.962.952.93
ESEER4.204.023.984.104.004.033.95
Eurovent Effi ciency class CoolingBCCBBBB
Sound power level(dBA)8788878 98 88 88 9
Heating application data (2)
Net Heating Capacity(kW)11 01201011141271391 62
Total Power input in heating(kW)3539323742465 2
COP3.143.123.163.083.023.003.11
Eurovent Effi ciency class HeatingBBBBBBBηs(%)133132131124124128129
SCOP3.393.373.353.163.163.283.30
Unit amps (4) (5)
Unit rated amps(A)86987893104114131
Unit rated amps - HESP Option (100Pa)(A)86987893104114131
Unit start up amps(A)218224200215236247256
Unit start up amps - HESP Option (100Pa)(A)218224200215236247256
Short Circuit Unit Capacity (9)(kA)15151515151515
Compressor
Compressor Number per Circuit#3322222
TypeScrollScrollScrollScrollScrollScrollScroll
Model Circuit1 / Circuit 213+13+1315+15+15 7.5+10 / 7.5+10 10+10 / 10+10 10+13 /10+13 13+13 / 13+13 15+15 / 15+15
Motor RPM(rpm)2900
Evaporator
Quantity#1111111
TypeStainless steel Copper Brazed plate Heat exchanger
Evaporator modelP120Tx110P120Tx110DP300x82DP300x82DP300x82DP300x114DP300x114
Evaporator Water Content volume(l)13.313.38.58.58.511.811.8
Nominal water connection size (Grooved coupling) - Without HYM (in) - (mm)2” - 60.32” - 60.33” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1
Nominal water connection size (Grooved coupling) - With HYM(in) - (mm) 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1
Hydraulic Module Components
Expansion Tank Volume(l)35353535353535
Max User water loop Volume for factory mounted expansion tank (1)(l)2000200020002000200020002000
Optionnal water Buffer tank volume(l)444444444444444444444
Max. Water-side Operating Pressure without pump package(kPa)1000
Max. Water-side Operating Pressure with pump package(kPa)400
Condenser
TypeAluminum fi ns & copper tubes heat exchanger
Quantity of coil#2222222
Face area per circuit(m²)5.935.932.962.962.962.963.46
Condenser Fan
Quantity#3324444
Diameter(mm)800
Fan / motor TypePropeller fan : Variable speed - EC motor / HESP MAX SPEED
Airfl ow per Fan(m3/h)13823138281496014964127251272513351
Power per Motor(kW)1.95 / 1.95
Rated Amps per Motor(A)3 / 3
Motor RPM(rpm)150 - 686 RPM
Single pump - Standard head pressure(kg)47474547474 74 7
Single pump - High head pressure(kg)494949494 94 94 9
Twin pump - Standard head pressure(kg)75757575757575
Twin pump - High head pressure(kg)86868484848484
Partial heat recovery option(kg)4.64.62x1.482x1.482x1.482x3.822x3.82
Water Buffer tank option(kg)425425425425425425425
System data
Nb of refrigerant circuit#1122222
Minimum cooling load % (6)%33332225222525
POE Oil typeOIL058E / OIL057E
(1) At Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C according to EN14511:2013
(2) At Evaporator water temperature : 40°C / 45°C - Condenser air. DB/WB 7°C / 6°C according to EN14511:2013
(4) under 400V/3/50Hz
(5) Rated Condition without Pump Package
(6) Minimum ambient in heating operation is for unit at 40°C / 45°C
(7) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(8) Maximum ambient operation is for unit at 12°C / 7°C
(9) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch.
Electrical & system data are subject to change without notice. Please refer to unit nameplate data.
HE-SN
G 1”1/4
(31.75 mm)
CXAX
045
HE-SN
G 1”1/4
(31.75 mm)
CXAX
035
HE-SN
G 1”1/4
(31.75 mm)
CXAX
040
HE-SN
G 1”1/4
(31.75 mm)
CXAX
046
HE-SN
G 1”1/4
(31.75 mm)
CXAX
052
HE-SN
G 1”1/4
(31.75 mm)
HE-SN
G 1”1/4
(31.75 mm)
CXAX
060
CG-PRC026C-GB
27
General Data
Table 8 - CXAX High Effi ciency and Low Noise
CXAX
015
Eurovent Performances (1)
Net Cooling Capacity(kW)424856657 27 99 4
Total Power input in cooling(kW)1417192 2252832
EER2.902.832.912.972.842.842.90
ESEER3.773.803.844.033.963.984.09
Eurovent Effi ciency class CoolingBCBBCCB
Sound power level(dBA)7878818 08 08 18 0
Heating application data (2)
Net Heating Capacity(kW)43515763697896
Total Power input in heating(kW)1416192123253 0
COP3.093.152.983.083.013.093.19
Eurovent Effi ciency class HeatingBBCBBBBηs(%)127129118127128128134
SCOP3.263.293.033.253.273.283.42
Unit amps (4) (5)
Unit rated amps(A)35394752576675
Unit rated amps - HESP(A)35394752576675
Unit start up amps(A)117161169185190191199
Unit start up amps - HESP(A)117161169185190191199
Short Circuit Unit Capacity (9)(kA)12121212121215
Expansion Tank Volume(l)25252525252535
Max User water loop Volume for factory mounted expansion tank (1)(l)1450145014501450145014502000
Optional water Buffer tank volume(l)324324324324324324444
Max. Water-side Operating Pressure without pump package(kPa)1000
Max. Water-side Operating Pressure with pump package(kPa)400
Condenser
TypeAluminum fi ns & copper tubes heat exchanger
Quantity of coil#1111112
Face area per circuit(m²)2.962.962.962.962.963.465.93
Condenser Fan
Quantity#1122222
Diameter(mm)800
Fan / motor TypePropeller fan : Variable speed - EC motor
Airfl ow per Fan(m3/h)14949149601496612721127261335214959
Motor RPM(rpm)150 - 686 RPM
Single pump - Standard head pressure(kg)46464649494 94 5
Single pump - High head pressure(kg)515151515 15 14 9
Twin pump - Standard head pressure(kg)70707075757571
Twin pump - High head pressure(kg)82828282828286
Partial heat recovery option(kg)1.481.481.481.483.823.823.82
Water Buffer tank option(kg)319319319319319319425
System data
Nb of refrigerant circuit#1111111
Minimum cooling load % (6)%50435043505033
POE Oil typeOIL058E / OIL057E
(1) At Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C according to EN14511:2013
(2) At Evaporator water temperature : 40°C / 45°C - Condenser air. DB/WB 7°C/6°C according to EN14511:2013
(4) under 400V/3/50Hz
(5) Rated Condition without Pump Package
(6) Minimum ambient in heating operation is for unit at 40°C / 45°C
(7) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(8) Maximum ambient operation is for unit at 12°C / 7°C
(9) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch.
Electrical & system data are subject to change without notice. Please refer to unit nameplate data.
HE-LN
G 1”1/4
(31.75 mm)
CXAX
017
HE-LN
G 1”1/4
(31.75 mm)
CXAX
020
HE-LN
G 1”1/4
(31.75 mm)
CXAX
023
HE-LN
G 1”1/4
(31.75 mm)
CXAX
026
HE-LN
G 1”1/4
(31.75 mm)
CXAX
030
HE-LN
G 1”1/4
(31.75 mm)
(31.75 mm)
CXAX
036
HE-LN
G 1”1/4
28
CG-PRC026C-GB
General Data
Table 8 - CXAX High Effi ciency and Low Noise (continued)
CXAX
015
Eurovent Performances (1)
Net Cooling Capacity(kW)10 811894114127146162
Total Power input in cooling(kW)3641343 7434955
EER3.002.882.813.062.962.952.93
ESEER4.204.023.984.104.004.033.95
Eurovent Effi ciency class CoolingBCCBBBB
Sound power level(dBA)8182818 48 38 38 4
Heating application data (2)
Net Heating Capacity(kW)11 01201011141271391 62
Total Power input in heating(kW)3539323742465 2
COP3.143.123.163.083.023.003.11
Eurovent Effi ciency class HeatingBBBBBBBηs(%)133132131124124128129
SCOP3.393.373.353.163.163.283.30
Unit amps (4) (5)
Unit rated amps(A)86987893104114131
Unit rated amps - HESP(A)86987893104114131
Unit start up amps(A)218224200215236247256
Unit start up amps - HESP(A)218224200215236247256
Short Circuit Unit Capacity (9)(kA)15151515151515
Compressor
Compressor Number per Circuit#3322222
TypeScrollScrollScrollScrollScrollScrollScroll
Quantity#1111111
TypeStainless steel Copper Brazed plate Heat exchanger
Evaporator modelP120Tx110P120Tx110DP300x82DP300x82DP300x82DP300x114DP300x114
Evaporator Water Content volume(l)13.313.38.58.58.511.811.8
Nominal water connection size (Grooved coupling) - Without HYM (in) - (mm)2” - 60.32” - 60.33” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1
Nominal water connection size (Grooved coupling) - With HYM(in) - (mm) 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1 3” OD - 76.1
Hydraulic Module Components
Expansion Tank Volume(l)35353535353535
Max User water loop Volume for factory mounted expansion tank (1)(l)2000200020002000200020002000
Optional water Buffer tank volume(l)444444444444444444444
Max. Water-side Operating Pressure without pump package(kPa)1000
Max. Water-side Operating Pressure with pump package(kPa)400
Condenser
TypeAluminum fi ns & copper tubes heat exchanger
Quantity of coil#2222222
Face area per circuit(m²)5.935.932.962.962.962.963.46
Condenser Fan
Quantity#3324444
Diameter(mm)800
Fan / motor TypePropeller fan : Variable speed - EC motor
Airfl ow per Fan(m3/h)13823138281496014964127251272513351
Motor RPM(rpm)150 - 686 RPM
Single pump - Standard head pressure(kg)47474547474 74 7
Single pump - High head pressure(kg)494949494 94 94 9
Twin pump - Standard head pressure(kg)75757575757575
Twin pump - High head pressure(kg)86868484848484
Partial heat recovery option(kg)4.64.62x1.482x1.482x1.482x3.822x3.82
Water Buffer tank option(kg)425425425425425425425
System data
Nb of refrigerant circuit#1122222
Minimum cooling load % (6)%33332225222525
POE Oil typeOIL058E / OIL057E
(1) At Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C according to EN14511:2013
(2) At Evaporator water temperature : 40°C / 45°C - Condenser air. DB/WB 7°C/6°C according to EN14511:2013
(4) under 400V/3/50Hz
(5) Rated Condition without Pump Package
(6) Minimum ambient in heating operation is for unit at 40°C / 45°C
(7) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(8) Maximum ambient operation is for unit at 12°C / 7°C
(9) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch.
Electrical & system data are subject to change without notice. Please refer to unit nameplate data.
Chiller is designed for outdoor application strictly in
accordance with specifi cations and it will be shipped
with a full operating charge of R410A refrigerant
and lubrication oil scroll compressors and electronic
expansion valve.
Quality assurance
Chiller is designed and manufactured under a quality
assurance system and enviromental management
system certifi ed in accordance with standard ISO
9001:2008 and ISO14001.
All chillers follow a production quality plan to ensure
proper construction and operation including electrical
sequence running test.
Unit construction is in accordance with the following
European directives:
Chiller casing and electrical panels are made of
galvanized steel of 1.5 mm thickness mounted on a
riveted structural steel entirely painted base. Unit panels
frames and exposed steel surfaces are painted and have
a corrosion resistance of 1500 hours to salt spray test
according ISO 9227. Electrical panel israted as minimum.
IP54 fully factory mounted and wired with access door
clearly visible from outside with power on/off indication.
Compressors and Motors
Chiller are provided with hermetic Scroll compressors:
• Direct drive 2900 rpm
• Suction gas cooled hermetic motor
• Built-in centrifugal oil pump
• Built-in oil level sight glass and oil charging valve
Compressor motors have a voltage utilization range
of ± 10% on nameplate voltage internal temperature
and current-sensitive motor overload is included for
maximum protection.
Evaporator
The evaporator is a single brazed plate heat exchanger
made of stainless steel 316 L and copper brazing
designed to operate properly and effi ciently with a
refrigerant charge.
Maximum operating pressure on water side does not
exceed 1MPa. The evaporator is fully insulated with
appropriate thickness and close cell type insulation
protected against freezing either with a control activated
heater either with a pump activation sequence whenever
the ambient temperature will be below 3°C. It has only
one entering and only one leaving water connection.
Chiller is able to supply water temperature leaving the
evaporator:
• For comfort application: between 5°C / 20°C
• For process application:
o Between -12°C and 5°C on cooling only units
(CGAX)
o Between -10°C and 5°C on heat pump units (CXAX)
Condenser coil and fans
Ambient temperature operating map is as minimum:
• Cooling only: 5°C (-18°C with Low Ambient Option) up
to 46°C
• Heating mode: -15°C up to 20°C
Cooling-only units coils
Condenser coil is Microchannel type made in aluminum
brazed fi n construction; coils will consist of three main
components: fl at microchannel tube fi ns in between
the microchannel tubes and two refrigerant manifolds.
Coil are cleanable using a high pressure water stream.
Condenser coil includes an integral subcooling circuit.
An option for E-coating or complete coil coating shall be
available.
Heat pump units coils
Condenser coil is made of aluminum fi ns mechanically
bonded to seamless copper tubing and includes integral
subcooling circuit. Coils are factory leak tested at
3.2Mpa under water. If unit will be installed on corrosive
environment aluminum fi ns are pre-coated with epoxy
with minimum thickness of 8µm in order to withstand
1000 hours of salt spray test according ISO 9227.
Chillers are equipped with axial condenser fan and
motors with permanently lubricated ball bearings and
external overload protection shall be provided. Fans
motors are class F. powered through an IP55 electrical
box.
Refrigerant Circuit
Each refrigerant circuit includes compressor(s) high
and low pressure transducer permanent liquid fi lter
drier electronic expansion valve pressure port on each
refrigerant line full operating charge of R410A and POE
oil as long as high pressure side pressostat.
Oil Management
The chiller is equipped with an oil management system
consisting of an oil pump integrated on the compressor
to ensure proper oil circulation throughout the unit and
a crankase heater integrated in the compressor to avoid
startup with low oil temperature. Unit is delivered with
operating oil charge factory supplied and checked (Trane
recommended oil OIL 0057E or OIL 0058E).
48
CG-PRC026C-GB
Mechanical Specifications
Electrical panel
Unit is provided with a weatherproof control and
IP54 power panel with a single point connection with
disconnect switch. The disconnect switch is mechanically
interlocked to disconnect line power from power panel
accessible from the outside the chiller. All components
and control cables are numbered in accordance with
CEI 60750. The unit is equipped with a control power
transformer with two secondary control circuits:
• 230 V single phase connection for evaporator freeze
protection heaters and control board
• 24 V single phase connection for the human interface
control.
Each compressor is provided with a direct on line
starter factory mounted wired and tested. Soft Starter is
available as an option.
Hydraulic module (option)
Hydraulic module is integrated within the chiller frame
fi eld pipe connection is Victaulic and is outside of the
unit casing. Hydraulic kit has the following factory
mounted components:
• Single or double pump (in this case manifolded in
parallel one pump working as redundancy of the other)
factory mounted wired and tested with check valve in
the discharge. Options for standard and high pressure
shall be available.
• Pump crankcase shall be in polyamid impeller in
propylene dynamically balanced. Pump rated for 1MPa
working pressure.
• Pre-charged expansion tank.
• Flow switch.
• Water strainer able to retain particles above 1mm of
diameter.
• Water pressure relief valve.
• Electrical heater for freezing protection up to -10°C.
• Cold critical parts such the brazed plate evaporator
will be insulated with a closed cell foam insulation
againstcondensation of minimum 13 mm.
• Freeze protection shall be made by pump activation as
standard.
• As an option unit shall include a water buffer tank
insulated with closed cell foam of 13mm with
antifreezing protection. Buffer tank will fi t into the
chiller to minimize the system footprint.
Chiller Control System CH535
Chilled water temperature control is fulfi lled through a
microprocessor based controller monitoring water and
refrigerant temperature as long as refrigerant pressure.
Controller is able to generate adequate operational
diagnostics.
The Micropocessor based controller is supplied factory
mounted fully wired confi gured and tested in factory and
it ensures compressor and fan sequence (load control)
fault detection diagnostic and supervision.
The following features are present on the chiller
operational control
• High and low refrigerant pressure protection
• Load limit control to limit compressor loading on high
return water temperature
• Condenser fan sequencing with automatically cycling
in response to ambient condensing pressure.
• Automatic compressor lead-lag to even out run hours
and compressors starts
• Phase reversal/single phasing protection
• Low ambient lockout control with adjustable set point
• Integrated RS485 serial port to allow BMS connectivity
• Options for communication protocols: ModBus.
LonTalk and BACnet should be available
User display interface are provided on the external wall
of the chiller allowing complete graphic management
through icons and touchscreen display:
• Leaving chilled water setpoint adjustment
• Entering and leaving water temperatures display
• Condenser pressure per circuit
• Suction pressure per circuit
• Air ambient temperature
• Condensing temperature per circuit
• Suction temperature per circuit
Safety control readouts on the user display:
• Low chilled water temperature detection
• High refrigerant pressure
• Loss of chilled water fl ow
• Contact to external shut-down per circuit
• Motor current overload
• Phase reversal/unbalance/single phasing
• Failure of leaving water temperature sensor used to
drive the set point
• Compressor status (on/off)
CG-PRC026C-GB
49
Options
Application options
Low ambient option
The low ambient option permits unit controls to allow
start and operation down to ambient temperatures of
-18°C (-0.4°F) for CGAX units; -10°C (26.4°F) for CGAX
heat pump in cooling mode if there is suffi cient glycol in
the evaporator to prevent freezing.
Low noise sound level option
Low noise units are equipped with a jacket encapsulating
each compressor for sound reduction.
SmartFlow Control
Constant speed pump – Variable frequency drive
adjustment
The unit is equipped with a pump package driven
by a speed inverter, without providing continuous
modulation of the speed. The water fl ow is fi xed during
commissioning. The goal of this alternative is to provide
the appropriate fl ow rate and hydraulic balance, without
the need for a mechanical balancing valve, and by taking
advantage of the energy consumption optimization of
the pump.
Water fl ow is adjusted through parameter 204 of the
speed inverter (TR200), when having the dual pump
option, the active pump arbitration is based on pump
equalization time and pump failure status.
The unit is equipped with a pump package driven by a
speed inverter. The modulation of the pump speed is
made in order to ensure that the Differential Pressure
(DP) remains constant within the system. The minimum
pump speed is factory set at 60% of the nominal speed.
The minimum pump frequency can be adjusted through
inverter. The constant DP option is intended to be used
with 2-way water regulation valves in the customer
hydraulic system. At minimum system partial load, when
most of the 2-way valves are closed, a minimum fl ow
rate must be ensured through the chiller evaporator. DP
is measured by a differential pressure sensor supplied by
Trane, that the customer must install on the water loop,
in a freeze protected area. A regulation valve should be
installed on the by-pass line.
Variable speed pump – Constant differential temperature
(DT)
The unit will be equipped with a pump package driven
by a speed inverter. The modulation of the pump speed
is managed to ensure that chiller DT stays constant.
Entering and leaving temperatures at the evaporator will
be measured directly by the chiller controller, through
the factory-supplied sensor. A DT setpoint will be present
on the unit controller. The option for constant DT is
intended to be used with 3-way valves on water systems,
or 2-way valves on water system but constant fl ow at the
by-pass. The minimum pump frequency can be adjusted
on the inverter.
Partial Heat Recovery
Heat recovery appears more and more as a sensible
response to offset energy costs continually on the rise.
The Trane Conquest chillers with Partial Heat Recovery
option combines the energy savings of heat recovery
operation with the installation and maintenance cost
savings of completely factory packaged air cooled liquid
chillers. The CGAX or CXAX in cooling mode with Heat
Recovery option operate as a standard unit as long as
heat is not required or it can simultaneously produce
chilled and hot water which can be used for applications
like: Heating or preheating of boiler systems or domestic
cater, Air conditioning/ventilation air pre-heat, and
Industrial processes.
The Heat Recovery Exchanger is a brazed plate
exchanger , connected to the compressor discharge line,
and sized to recover up to 20% of the nominal cooling
capacity.
The Heat Recovery Exchanger is not approved for Food
and Beverage applications. The use of a primary loop is
mandatory.
Communication options
BACnet™ communication interface
Allows the user to easily interface with BACnet via a
single twisted pair wiring to a factory installed and
tested communication board.
LonTalk™ communication interface
Allows the user to easily interface with LonTalk via a
single twisted pair wiring to a factory installed and
tested communication board.
ModBus™ communication interface
Allows the user to easily interface with ModBus via
a single twisted pair wiring to a factory installed and
tested communication board.
Other options
Coated condensing coils
For cooling only units (CGAX) a complete coating on
microchannel condenser coils shall be available.
For Heat Pump units (CXAX) pre-coated aluminium
epoxy fi ns shall be available.
Compressors soft starters
Electronic solid state soft starter shall be available.
Deluxe display
For a remote display type Deluxe is available.
50
CG-PRC026C-GB
Notes
CG-PRC026C-GB
51
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader
in creating and sustaining safe, comfortable and energy effi cient environments, Trane offers a broad portfolio
of advanced controls and HVAC systems, comprehensive building services and parts. For more information visit
www.Trane.com
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifi cations without notice.