Trane CGAX/CXAX User guide

CG-PRC026C-GB
Conquest air-cooled chillers and heat pumps
Scroll compressor Model CGAX/CXAX 42-160 kW
Features and Benefits
Reliability
A robust design of the compressor and refrigerant circuit has been validated by an extensive program of operational tests, in extreme conditions, to ensure maximum reliability. Quality is verifi ed during each and every step.
Figure 1 - Scroll compressor
Oil sight Glass
Oil Equalization
Compressors
Direct drive, low speed, new generation of scroll compressor, with few moving parts, providing high effi ciency, reliable operation and simplifi ed maintenance. Suction gas cooled motor winding, maintaining uniform low temperature for extended motor life.
Fixed Scroll
Discharge Valve plate
Oldham Coupling
Orbiting
Rotor
Stator
Scroll
Counter weight
Oil Pick Up
Chiller controller
The Conquest chiller is equipped with the new generation of chiller control systems, providing improved control capabilities, and integrated safety protocols to protect both compressors and motors from electrical faults like thermal overload and phase reversal.
The LCD display with 6 navigation buttons shows clear messages in 15 available languages. It features a customer communication package consisting in: external chilled water setpoint, external demand limit, analog capacity output, programmable relays.
Figure 2 - Standard LCD user interface
A deluxe display is available as an option.,It features an intuitive and user friendly color 7 inch touchscreen, able to display: Data trending, clear alarms logging, and TIS enable for remote monitoring.
Figure 3 - Optional deluxe user interface
4
CG-PRC026C-GB
Features and Benefi ts
Microchannel condensing coils on cooling­only units
Conquest chillers are equipped with microchannel condensing coils allowing excellent heat transfer and a dramatic improvement of corrosion resistance versus conventional tubes in fi ns coils. Microchannel coils are 100% aluminum, therefore avoiding galvanic corrosion which can occur on conventional condensers made with copper tubes and aluminum fi ns. Microchannel coils are also well adapted for dirty environment thanks to their small thickness and fi ns profi le.
Figure 4 - Microchannel condensing coils
Slit fi ns and brazed contact
Air condenser inlet
Microchannels
for R410A
for improved heat transfer and strength
Air
condenser
outlet
Electronic Expansion Valve
Electronic expansion valve enables tight chilled water temperature control and low superheat, resulting in more effi cient full-load and part-load operation.
Application versatility
Extended operating map, allowing chiller operation in multiple applications:
• Industrial/low temperature process cooling with precise temperature control capability
• Optimal and reliable operation at high ambient temperatures.
Figure 5 - Operating map- Cooling-only Model CGAX
50
50
45
45
40
40
35
35
30
30
25
25
20
20
15
15
10
10
Amb Air T °C
5
5
0
0
AmbAir T °C
-5
-5
-10
-10
-15
-15
-20
-20
-15 -10 -5 0 5 10 15 20 25
-15 -10 -5 0 5 10 15 20 25
A
B
LWT (°C)
LWT (°C )
Heat pump units coils
The condenser coil is made of aluminum fi ns mechanically bonded to seamless copper tubing and includes integral subcooling circuit. The coils are factory leak tested at 5 Mpa. If the unit is to be installed in a corrosive environment, aluminum fi ns can be pre-coated with epoxy (optional), with minimum thickness of 8µm, in order to withstand 1000 hours of salt spray test according to ISO 9227.
CG-PRC026C-GB
LWT = Leaving water temperature
Amb Air T = Ambient air temperature
A = Standard operating map
B = Low ambient operating map (Variable air fl ow control)
Minimum start-up/operation ambient based on a
2.22 m/s (5mph) wind across the condenser
5
Features and Benefi ts
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
-15 -10 -5 0 5 10 15 20 25
Cooling Mode
-25
-20
-15
-10
-5
0
5
10
15
20
25
15 20 25 30 35 40 45 50 55 60 65
Heating Mode
Figure 6 - Heat Pump Model CXAX operating map
Cooling Mode
A
Amb Air T °C
AmbAir T °C
B
LWT (°C)
LWT (°C ) LWT (°C )
LWT = Leaving water temperature
Amb Air T = Ambient air temperature
A = Standard operating map
B = Low ambient operating map (Variable air fl ow control)
Minimum start-up/operation ambient based on a
2.22 m/s (5mph) wind across the condenser
Improved Serviceability
• All main components like compressors, valves and refrigerant components are easy to access to simplify servicing. When the unit is supplied with an hydraulic module, the service valves and strainer can be accessed with ease for service.
• Water connections are extended up to the edge of the unit, for easy connection with system water piping.
• Optional pump package is designed for easy maintenance and service on site.
• Pressure transducers and temperature sensors are supplied for easy identifi cation of potential troubleshooting and eventually, replacement, without the need of refrigerant handling.
• Dead front panel and IP20 protection allow for safe servicing.
AmbAir T °C
Heating Mode
A
Amb Air T °C
LWT (°C)
6
CG-PRC026C-GB
Application Considerations
Certain applications contraints should be considered when sizing, selecting and installing Conquest air­cooled Scroll chillers. Unit and system reliability often depend on proper and complete compliance with those considerations.
Unit Size
Unit oversizing is often not recommended since erratic unit operation and excessive compressor cycling are often a direct result of an oversized chiller. If oversizing is desired, consider the alternative of multiple units, splitting the total capacity.
Water Treatment
The use of untreated or improperly treated water in chillers may result in scaling, erosion, corrosion, and algae or slime buildup. This will adversely affect heat transfer between the water and system components. Proper water treatment must be determined locally and depends on the type of system and local water characteristics.
Neither salty nor brackish water is recommend for use in Trane air-cooled Conquest chiller. Usage of either will lead to a shortened life. Trane encourages the employment of a qualifi ed water treatment specialist, familiar with local water conditions, to assist in the establishment of a proper water treatment program.
Foreign matter in the chilled water system can also increase pressure drop and, consequently, reduce water fl ow. For this reason it is important to thoroughly fl ush all water piping to the unit before making the fi nal piping connections to the unit.
Effect of the altitude on the cooling capacity
At elevations substantially above sea level, the decreased air density will decrease condenser capacity and, therefore, unit capacity and effi ciency.
Water fl ow limits
The minimum water fl ow rates are given in the General Data section of this catalog. Evaporator fl ow rates below the tabulated values will result in laminar fl ow causing freeze-up problems,scaling, stratifi cation and poor control. The maximum evaporator water fl ow rate is also given. Flow rates exceeding those listed may result in very high pressure drop across the evaporator.
Flow Rates Out of Range
Many process cooling jobs require fl ow rates that cannot be met with the minimum and maximum published values within the Conquest chiller evaporator. A simple piping change can alleviate this problem. For example: a plastic injection molding process requires 5.0 l/s of 10°C water and returns that water at 15.6°C. The selected chiller can operate at these temperatures, but has a minimum fl ow rate of 6.6 l/s. The system layout in Figure 7 can satisfy the process.
Figure 7 - Flow rate out of range systems solution
10°C
10°C 7 l/s
14°C 7 l/s
5 l/s
10°C 2 l/s
15.6°C 5 l/s
L = Load P = Pump
Flow Proving
Trane provides a factory-installed water fl ow switch monitored by chilller controller CH535 which protects the chiller from operating in loss of fl ow conditions.
Leaving Water Temperature Limits
Trane air-cooled Conquest chillers have two distinct leaving water categories:
• standard, with a leaving solution range of 5.5 to 18°C
• low temperature process cooling, with leaving solution range of -12 to 18°C
Since the leaving solution temperature below 5.5°C results in suction temperature at or below the freezing point of water, a glycol solution is required for all low temperature.
Consult your local Trane sales engineer for applications or selections involving low temperature. The maximum water temperature that can be circulated through the CGAX evaporator when the unit is not operating is
51.7°C. For the model CXAX the water temperature
limit is 60°C. Evaporator damage may result above this temperature.
Figure 8 - Temperature out of range system solution
30°C 15 l/s
P
15°C 15 l/s
20°C 15 l/s
15°C
11.2 l/s
15°C
3.8 l/s
35°C
11.2 l/s
L
P
35°C
3.8 l/s
35°C 15 l/s
CG-PRC026C-GB
L = Load P = Pump
7
General Data
Table 1 - CGAX Standard effi ciency and Standard Noise
CGAX
015
Eurovent Performances (1)
Net Cooling Capacity (kW) 43 49 59 65 74 82 99 Total Power input in cooling (kW) 15 17 19 22 26 29 33 Total Power input in cooling - HESP Option (100Pa) (kW) 15 18 21 24 27 31 34 EER 2.98 2.88 3.08 2.95 2.87 2.84 2.96 EER - HESP (915 RPM - 100Pa) 2.82 2.74 2.89 2.81 2.78 2.76 2.81 ESEER 3.89 3.93 3.81 3.82 3.84 3.80 3.93 Eurovent Effi ciency class Cooling BCBBCCB Sound power level (dBA) 83 83 85 85 85 86 84 Sound power level - HESP Option (100Pa) (dBA) 85 85 89 89 89 89 89
Unit amps (4) (5)
Unit rated amps (A) 34 38 45 50 56 64 74 Unit rated amps - HESP Option (100Pa) (A) 35 39 47 52 57 66 75 Unit start up amps (A) 116 160 167 183 188 189 198 Unit start up amps - HESP Option (100Pa) (A) 117 161 169 185 190 191 199 Short Circuit Unit Capacity (9) (kA) 12 12 12 12 12 12 15
Compressor
Compressor Number per Circuit # 2222223 Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Model Circuit1 / Circuit 2 7.5+7.5 7.5+10 10+10 10+13 13+13 15+15 12+12+12 Motor RPM (rpm) 2900
Evaporator
Quantity # 1111111 Type Stainless steel Copper Brazed plate Heat exchanger Evaporator model P80x66 P80x92 P80x92 P80x92 P120Tx76 P120Tx76 P120Tx104 Evaporator Water Content volume (l) 3.8 5.3 5.3 5.3 9.2 9.2 12.5 Nominal water connection size (Grooved coupling) -
Without HYM Nominal water connection size (Grooved coupling) -
With HYM
Hydraulic Module Components
Expansion Tank Volume (l) 25 25 25 25 25 25 35 Max User water loop Volume for factory mounted
expansion tank (1) Optional water Buffer tank volume (l) 324 324 324 324 324 324 444 Max. Water-side Operating Pressure without pump
package Max. Water-side Operating Pressure with pump
package
Condenser
Type Full aluminum Micro channel heat exchanger Quantity of coil # 1111112 Face area per circuit (m²) 2.23 2.23 2.96 2.96 2.96 2.96 4.46
Condenser Fan
Quantity # 1122222 Diameter (mm) 800 Fan / motor Type Propeller fan : Fixed speed AC motor / Variable speed - EC motor Airfl ow per Fan (m3/h) 13788 13828 12362 12362 12370 12375 13827 Airfl ow per Fan - HESP Option (100Pa) (m3/h) 13753 13718 12248 12231 12211 12193 13727 Motor RPM (rpm) 686 686 686 686 686 686 686 Motor RPM - HESP Option (100Pa) (rpm) 915 915 915 915 915 915 915
Partial Heat recovery (PHR) option
Heat-Exchanger Type Stainless steel Copper Brazed plate Heat exchanger Heat-Exchanger Model B3-014-14-4.5M B3-014-14-4.5M B3-014-14-4.5M B3-014-14-4.5M B3-027-14-4.5L B3-027-14-4.5L B3-027-14-4.5L
Water connection size (Thread connection) (in) - (mm)
Water content volume (l) 0.14 0.14 0.14 0.14 0.35 0.35 0.35
Dimensions
Unit Length (mm) 2346 2346 2346 2346 2346 2346 2327 Unit Width (mm) 1285 1285 1285 1285 1285 1285 2250 Unit Height (mm) 1524 1524 1524 1524 1524 1524 1524
Option Additional height
Water Buffer tank option (mm) +330 +330 +330 +330 +330 +330 +330
Weights
Shipping Weight (5) (kg) 519 531 574 579 608 621 853 Operating Weight (5) (kg) 497 509 552 557 587 599 819
Option Additional shipping weight
Single pump - Standard head pressure (kg) 46 46 46 49 49 49 45 Single pump - High head pressure (kg) 51 51 51 51 51 51 49 Twin pump - Standard head pressure (kg) 70 70 70 75 75 75 71 Twin pump - High head pressure (kg) 82 82 82 82 82 82 86 Partial heat recovery option (kg) 1.48 1.48 1.48 1.48 3.82 3.82 3.82 Water Buffer tank option (kg) 319 319 319 319 319 319 425
System data
Nb of refrigerant circuit # 1111111 Minimum cooling load % (6) % 50 43 50 43 50 50 33
Standard unit
R410A refrigerant charge Circuit1 / Circuit 2 (kg) 7.5 9.0 9 .0 9.0 10.5 10.5 14.0 Oil charge Circuit1 / Circuit 2 (l) 6.0 6.3 6.6 6.6 6.6 7.2 10.5
Unit with partial heat recovery option
R410a refrigerant charge Circuit1 / Circuit 2 (kg) 7.5 9.0 9.0 9.0 10.5 10.5 14.0 Oil charge Circuit1 / Circuit 2 (l) 6.0 6.3 6.6 6.6 6.6 7.2 10.5
POE Oil type OIL058E / OIL057E
(1) At Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C according to EN14511:2013 (2) At Evaporator water temperature : 6.6°C (44°F) / 12.2°C (54°F) - condenser air temperature 46°C (114.8°F) (4) under 400V/3/50Hz (5) Rated Condition without Pump Package (6) Percent minimum load can be lowered on demand to local sales offi ce. (7) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser. (8) Maximum ambient operation is for unit at 12°C / 7°C (9) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch. Electrical & system data are subject to change without notice. Please refer to unit nameplate data.
(in) - (mm) 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3
(in) - (mm) 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 3” OD - 76.1
(kPa) 1000
(kPa) 400
SE-SN
(l) 1450 1450 1450 1450 1450 1450 2000
G 1”1/4
(31.75 mm)
CGAX
017
SE-SN
G 1”1/4
(31.75 mm)
CGAX
020
SE-SN
G 1”1/4
(31.75 mm)
CGAX
023
SE-SN
G 1”1/4
(31.75 mm)
CGAX
026
SE-SN
G 1”1/4
(31.75 mm)
CGAX
030
SE-SN
G 1”1/4
(31.75 mm)
14
CGAX
SE-SN
G 1”1/4
(31.75 mm)
CG-PRC026C-GB
036
General Data
Table 2 - CGAX Standard effi ciency and Low Noise
CGAX
015
Eurovent Performances (1)
Net Cooling Capacity (kW) 43 49 59 65 74 82 99 Total Power input in cooling (kW) 15 17 19 22 26 29 33 Total Power input in cooling - HESP Option (100Pa) (kW) 15 18 21 24 27 31 34 EER 2.98 2.88 3.08 2.95 2.87 2.84 2.96 EER - HESP Option (100Pa) 2.82 2.74 2.89 2.81 2.78 2.76 2.81 ESEER 3.89 3.93 3.81 3.82 3.84 3.80 3.93 Eurovent Effi ciency class Cooling BCBBCCB Sound power level (dBA) 77 77 79 79 79 80 79 Sound power level - HESP Option (100Pa) (dBA) 85 85 89 89 89 89 89
Unit amps (4) (5)
Unit rated amps (A) 34 38 45 50 56 64 74 Unit rated amps - HESP Option (100Pa) (A) 35 39 47 52 57 66 75 Unit start up amps (A) 116 160 167 183 188 189 198 Unit start up amps - HESP Option (100Pa) (A) 117 161 169 185 190 191 199 Short Circuit Unit Capacity (9) (kA) 12 12 12 12 12 12 15
Compressor
Compressor Number per Circuit # 2222223 Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Model Circuit1 / Circuit 2 7.5+7.5 7.5+10 10+10 10+13 13+13 15+15 12+12+12 Motor RPM (rpm) 2900
Evaporator
Quantity # 1111111 Type Stainless steel Copper Brazed plate Heat exchanger Evaporator model P80x66 P80x92 P80x92 P80x92 P120Tx76 P120Tx76 P120Tx104 Evaporator Water Content volume (l) 3.8 5.3 5.3 5.3 9.2 9.2 12.5 Nominal water connection size (Grooved coupling) -
Without HYM Nominal water connection size (Grooved coupling) -
With HYM
Hydraulic Module Components
Expansion Tank Volume (l) 25 25 25 25 25 25 35 Max User water loop Volume for factory mounted
expansion tank (1) Optional water Buffer tank volume (l) 324 324 324 324 324 324 444 Max. Water-side Operating Pressure without pump
package Max. Water-side Operating Pressure with pump
package
Condenser
Type Full aluminum Micro channel heat exchanger Quantity of coil # 111111 2 Face area per circuit (m²) 2.23 2.23 2.96 2.96 2.96 2.96 4.46
Condenser Fan
Quantity # 1122222 Diameter (mm) 800 Fan / motor Type Propeller fan : Fixed speed AC motor / Variable speed - EC motor Airfl ow per Fan (m3/h) 13788 13828 12362 12362 12370 12375 13827 Airfl ow per Fan - HESP Option (100Pa) (m3/h) 13753 13718 12248 12231 12211 12193 13727 Motor RPM (rpm) 686 686 686 686 686 686 686 Motor RPM - HESP Option (100Pa) (rpm) 915 915 915 915 915 915 915
Partial Heat recovery (PHR) option
Heat-Exchanger Type Stainless steel Copper Brazed plate Heat exchanger Heat-Exchanger Model B3-014-14-4.5M B3-014-14-4.5M B3-014-14-4.5M B3-014-14-4.5M B3-027-14-4.5L B3-027-14-4.5L B3-027-14-4.5L
Water connection size (Thread connection) (in) - (mm)
Water content volume (l) 0.14 0.14 0.14 0.14 0.35 0.35 0.35
Dimensions
Unit Length (mm) 2346 2346 2346 2346 2346 2346 2327 Unit Width (mm) 1285 1285 1285 1285 1285 1285 2250 Unit Height (mm) 1747 1747 1747 1747 1747 1747 1747
Option Additional height
Water Buffer tank option (mm) +330 +330 +330 +330 +330 +330 +330
Weights
Shipping Weight (5) (kg) 519 531 574 579 608 621 853 Operating Weight (5) (kg) 497 509 552 557 587 599 819
Option Additional shipping weight
Single pump - Standard head pressure (kg) 46 46 46 49 49 49 45 Single pump - High head pressure (kg) 51 51 51 51 51 51 49 Twin pump - Standard head pressure (kg) 70 70 70 75 75 75 71 Twin pump - High head pressure (kg) 82 82 82 82 82 82 86 Partial heat recovery option (kg) 1.48 1.48 1.48 1.48 3.82 3.82 3.82 Water Buffer tank option (kg) 319 319 319 319 319 319 425
System data
Nb of refrigerant circuit # 1111111 Minimum cooling load % (6) % 50 43 50 43 50 50 33
Standard unit
R410A refrigerant charge Circuit1 / Circuit 2 (kg) 7.5 9.0 9 .0 9.0 10.5 10.5 14.0 Oil charge Circuit1 / Circuit 2 (l) 6.0 6.3 6.6 6.6 6.6 7.2 10.5
Unit with partial heat recovery option
R410a refrigerant charge Circuit1 / Circuit 2 (kg) 7.5 9.0 9.0 9.0 10.5 10.5 14.0 Oil charge Circuit1 / Circuit 2 (l) 6.0 6.3 6.6 6.6 6.6 7.2 10.5
POE Oil type OIL058E / OIL057E
(1) At Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C according to EN14511:2013 (4) under 400V/3/50Hz (5) Rated Condition without Pump Package (6) Percent minimum load can be lowered on demand to local sales offi ce. (7) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser. (8) Maximum ambient operation is for unit at 12°C / 7°C (9) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch. Electrical & system data are subject to change without notice. Please refer to unit nameplate data.
(in) - (mm) 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3
(in) - (mm) 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 3” OD - 76.1
(kPa) 1000
(kPa) 400
SE-LN
(l) 1450 1450 1450 1450 1450 1450 2000
G 1”1/4
(31.75 mm)
CGAX
017
SE-LN
G 1”1/4
(31.75 mm)
CGAX
020
SE-LN
G 1”1/4
(31.75 mm)
CGAX
023
SE-LN
G 1”1/4
(31.75 mm)
CGAX
026
SE-LN
G 1”1/4
(31.75 mm)
CGAX
030
SE-LN
G 1”1/4
(31.75 mm)
CGAX
SE-LN
G 1”1/4
(31.75 mm)
036
16
CG-PRC026C-GB
General Data
Table 3 - CGAX High Effi ciency and Standard Noise
CGAX
015
Eurovent Performances (1)
Net Cooling Capacity (kW) 43 49 59 65 74 82 99 Total Power input in cooling (kW) 15 17 19 22 26 29 33 EER 2.98 2.88 3.08 2.95 2.87 2.84 2.96 ESEER 3.97 3.98 3.96 4.03 3.93 3.86 4.04 Eurovent Effi ciency class Cooling BCBBCCB Sound power level (dBA) 83 83 85 85 85 86 84
Unit amps (4) (5)
Unit rated amps (A) 35 39 47 52 57 66 75 Unit rated amps - HESP Option (100Pa) (A) 35 39 47 52 57 66 75 Unit start up amps (A) 117 161 169 185 190 191 199 Unit start up amps - HESP Option (100Pa) (A) 117 161 169 185 190 191 199 Short Circuit Unit Capacity (9) (kA) 12 12 12 12 12 12 15
Compressor
Compressor Number per Circuit # 2222223 Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Model Circuit1 / Circuit 2 7.5+7.5 7.5+10 10+10 10+13 13+13 15+15 12+12+12 Motor RPM (rpm) 2900
Evaporator
Quantity # 1111111 Type Stainless steel Copper Brazed plate Heat exchanger Evaporator model P80x66 P80x92 P80x92 P80x92 P120Tx76 P120Tx76 P120Tx104 Evaporator Water Content volume (l) 3.8 5.3 5.3 5.3 9.2 9.2 12.5 Nominal water connection size (Grooved coupling) -
Without HYM Nominal water connection size (Grooved coupling) -
With HYM
Hydraulic Module Components
Expansion Tank Volume (l) 25 25 25 25 25 25 35 Max User water loop Volume for factory mounted
expansion tank (1) Optional water Buffer tank volume (l) 324 324 324 324 324 324 444 Max. Water-side Operating Pressure without pump
package Max. Water-side Operating Pressure with pump
package
Condenser
Type Full aluminum Micro channel heat exchanger Quantity of coil # 111111 2 Face area per circuit (m²) 2.23 2.23 2.96 2.96 2.96 2.96 4.46
Condenser Fan
Quantity # 1122222 Diameter (mm) 800 Fan / motor Type Propeller fan : Variable speed - EC motor / HESP MAX SPEED Airfl ow per Fan (m3/h) 13788 13828 12362 12362 12370 12375 13827 Motor RPM (rpm) 150 - 686 RPM
Partial Heat recovery (PHR) option
Heat-Exchanger Type Stainless steel Copper Brazed plate Heat exchanger Heat-Exchanger Model B3-014-14-4.5M B3-014-14-4.5M B3-014-14-4.5M B3-014-14-4.5M B3-027-14-4.5L B3-027-14-4.5L B3-027-14-4.5L
Water connection size (Thread connection) (in) - (mm)
Water content volume (l) 0.14 0.14 0.14 0.14 0.35 0.35 0.35
Dimensions
Unit Length (mm) 2346 2346 2346 2346 2346 2346 2327 Unit Width (mm) 1285 1285 1285 1285 1285 1285 2250 Unit Height (mm) 1524 1524 1524 1524 1524 1524 1524
Option Additional height
Water Buffer tank option (mm) +330 +330 +330 +330 +330 +330 +330
Weights
Shipping Weight (5) (kg) 519 531 574 579 608 621 853 Operating Weight (5) (kg) 497 509 552 557 587 599 819
Option Additional shipping weight
Single pump - Standard head pressure (kg) 46 46 46 49 49 49 45 Single pump - High head pressure (kg) 51 51 51 51 51 51 49 Twin pump - Standard head pressure (kg) 70 70 70 75 75 75 71 Twin pump - High head pressure (kg) 82 82 82 82 82 82 86 Partial heat recovery option (kg) 1.48 1.48 1.48 1.48 3.82 3.82 3.82 Water Buffer tank option (kg) 319 319 319 319 319 319 425
System data
Nb of refrigerant circuit # 1111111 Minimum cooling load % (6) % 50 43 50 43 50 50 33
Standard unit
R410A refrigerant charge Circuit1 / Circuit 2 (kg) 7.5 9.0 9 .0 9.0 10.5 10.5 14.0 Oil charge Circuit1 / Circuit 2 (l) 6.0 6.3 6.6 6.6 6.6 7.2 10.5
Unit with partial heat recovery option
R410a refrigerant charge Circuit1 / Circuit 2 (kg) 7.5 9.0 9.0 9.0 10.5 10.5 14.0 Oil charge Circuit1 / Circuit 2 (l) 6.0 6.3 6.6 6.6 6.6 7.2 10.5
POE Oil type OIL058E / OIL057E
(1) At Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C according to EN14511:2013 (2) At Evaporator water temperature : 6.6°C (44°F) / 12.2°C (54°F) - condenser air temperature 46°C (114.8°F) (4) under 400V/3/50Hz (5) Rated Condition without Pump Package (6) Percent minimum load can be lowered on demand to local sales offi ce. (7) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser. (8) Maximum ambient operation is for unit at 12°C / 7°C (9) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch. Electrical & system data are subject to change without notice. Please refer to unit nameplate data.
(in) - (mm) 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3
(in) - (mm) 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 3” OD - 76.1
(kPa) 1000
(kPa) 400
HE-SN
(l) 1450 1450 1450 1450 1450 1450 2000
G 1”1/4
(31.75 mm)
CGAX
017
HE-SN
G 1”1/4
(31.75 mm)
CGAX
020
HE-SN
G 1”1/4
(31.75 mm)
CGAX
023
HE-SN
G 1”1/4
(31.75 mm)
CGAX
026
HE-SN
G 1”1/4
(31.75 mm)
CGAX
030
HE-SN
G 1”1/4
(31.75 mm)
CGAX
HE-SN
G 1”1/4
(31.75 mm)
036
18
CG-PRC026C-GB
General Data
Table 4 - CGAX High Effi ciency and Low Noise
CGAX
015
Eurovent Performances (1)
Net Cooling Capacity (kW) 43 49 59 65 74 82 99 Total Power input in cooling (kW) 15 17 19 22 26 29 33 EER 2.98 2.88 3.08 2.95 2.87 2.84 2.96 ESEER 3.97 3.98 3.96 4.03 3.93 3.86 4.04 Eurovent Effi ciency class Cooling BCBBCCB Sound power level (dBA) 77 77 79 79 79 80 79
Unit amps (4) (5)
Unit rated amps (A) 35 39 47 52 57 66 75 Unit rated amps - HESP Option (100Pa) (A) 35 39 47 52 57 66 75 Unit start up amps (A) 117 161 169 185 190 191 199 Unit start up amps - HESP Option (100Pa) (A) 117 161 169 185 190 191 199 Short Circuit Unit Capacity (9) (kA) 12 12 12 12 12 12 15
Compressor
Compressor Number per Circuit # 2222223 Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Model Circuit1 / Circuit 2 7.5+7.5 7.5+10 10+10 10+13 13+13 15+15 12+12+12 Motor RPM (rpm) 2900
Evaporator
Quantity # 1111111 Type Stainless steel Copper Brazed plate Heat exchanger Evaporator model P80x66 P80x92 P80x92 P80x92 P120Tx76 P120Tx76 P120Tx104 Evaporator Water Content volume (l) 3.8 5.3 5.3 5.3 9.2 9.2 12.5 Nominal water connection size (Grooved coupling) -
Without HYM Nominal water connection size (Grooved coupling) -
With HYM
Hydraulic Module Components
Expansion Tank Volume (l) 25 25 25 25 25 25 35 Max User water loop Volume for factory mounted
expansion tank (1) Optional water Buffer tank volume (l) 324 324 324 324 324 324 444 Max. Water-side Operating Pressure without pump
package Max. Water-side Operating Pressure with pump
package
Condenser
Type Full aluminum Micro channel heat exchanger Quantity of coil # 111111 2 Face area per circuit (m²) 2.23 2.23 2.96 2.96 2.96 2.96 4.46
Condenser Fan
Quantity # 1122222 Diameter (mm) 800 Fan / motor Type Propeller fan : Variable speed - EC motor Airfl ow per Fan (m3/h) 13788 13828 12362 12362 12370 12375 13827 Motor RPM (rpm) 150 - 686 RPM
Partial Heat recovery (PHR) option
Heat-Exchanger Type Stainless steel Copper Brazed plate Heat exchanger Heat-Exchanger Model B3-014-14-4.5M B3-014-14-4.5M B3-014-14-4.5M B3-014-14-4.5M B3-027-14-4.5L B3-027-14-4.5L B3-027-14-4.5L
Water connection size (Thread connection) (in) - (mm)
Water content volume (l) 0.14 0.14 0.14 0.14 0.35 0.35 0.35
Dimensions
Unit Length (mm) 2346 2346 2346 2346 2346 2346 2327 Unit Width (mm) 1285 1285 1285 1285 1285 1285 2250 Unit Height (mm) 1747 1747 1747 1747 1747 1747 1747
Option Additional height
Water Buffer tank option (mm) +330 +330 +330 +330 +330 +330 +330
Weights
Shipping Weight (5) (kg) 519 531 574 579 608 621 853 Operating Weight (5) (kg) 497 509 552 557 587 599 819
Option Additional shipping weight
Single pump - Standard head pressure (kg) 46 46 46 49 49 49 45 Single pump - High head pressure (kg) 51 51 51 51 51 51 49 Twin pump - Standard head pressure (kg) 70 70 70 75 75 75 71 Twin pump - High head pressure (kg) 82 82 82 82 82 82 86 Partial heat recovery option (kg) 1.48 1.48 1.48 1.48 3.82 3.82 3.82 Water Buffer tank option (kg) 319 319 319 319 319 319 425
System data
Nb of refrigerant circuit # 1111111 Minimum cooling load % (6) % 50 43 50 43 50 50 33
Standard unit
R410A refrigerant charge Circuit1 / Circuit 2 (kg) 7.5 9.0 9 .0 9.0 10.5 10.5 14.0 Oil charge Circuit1 / Circuit 2 (l) 6.0 6.3 6.6 6.6 6.6 7.2 10.5
Unit with partial heat recovery option
R410a refrigerant charge Circuit1 / Circuit 2 (kg) 7.5 9.0 9.0 9.0 10.5 10.5 14.0 Oil charge Circuit1 / Circuit 2 (l) 6.0 6.3 6.6 6.6 6.6 7.2 10.5
POE Oil type OIL058E / OIL057E
(1) At Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C according to EN14511:2013 (4) under 400V/3/50Hz (5) Rated Condition without Pump Package (6) Percent minimum load can be lowered on demand to local sales offi ce. (7) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser. (8) Maximum ambient operation is for unit at 12°C / 7°C (9) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch. Electrical & system data are subject to change without notice. Please refer to unit nameplate data.
(in) - (mm) 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3
(in) - (mm) 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 3” OD - 76.1
(kPa) 1000
(kPa) 400
HE-LN
(l) 1450 1450 1450 1450 1450 1450 2000
G 1”1/4
(31.75 mm)
CGAX
017
HE-LN
G 1”1/4
(31.75 mm)
CGAX
020
HE-LN
G 1”1/4
(31.75 mm)
CGAX
023
HE-LN
G 1”1/4
(31.75 mm)
CGAX
026
HE-LN
G 1”1/4
(31.75 mm)
CGAX
030
HE-LN
G 1”1/4
(31.75 mm)
CGAX
HE-LN
G 1”1/4
(31.75 mm)
036
20
CG-PRC026C-GB
General Data
Table 5 - CXAX Standard effi ciency and Standard Noise
CXAX
015
Eurovent Performances (1)
Net Cooling Capacity (kW) 42 48 56 65 72 79 94 Total Power input in cooling (kW) 14 17 19 2 2 25 28 32 Total Power input in cooling - HESP Option (100Pa) (kW) 15 17 20 24 27 30 34 EER 2.90 2.83 2.91 2.97 2.84 2.84 2.90 EER - HESP Option (100Pa) 2.80 2.76 2.73 2.71 2.63 2.62 2.78 ESEER 3.71 3.75 3.63 3.80 3.84 3.82 3.96 Eurovent Effi ciency class Cooling BCBBCCB Sound power level (dBA) 84 84 85 8 5 8 5 8 6 8 6 Sound power level - HESP Option (100Pa) (dBA) 86 86 8 9 9 2 9 4 8 9 9 5
Heating application data (2)
Net Heating Capacity (A) 43 51 57 63 69 78 96 Total Power input in heating (A) 14 16 19 21 23 25 30 Total Power input in heating - HESP Option (100Pa) (A) 15 17 21 23 26 27 32 COP (A) 3.09 3.15 2.98 3.08 3.01 3.09 3.19 COP - HESP Option (100Pa) 2.87 2.97 2.71 2.75 2.67 2.89 3.01 Eurovent Effi ciency class Heating B B C B B B B ηs 126 125 115 124 125 124 128 SCOP (kA) 3.21 3.21 2.95 3.17 3.19 3.18 3.29
Unit amps (4) (5)
Unit rated amps (A) 34 38 45 50 56 64 74 Unit rated amps - HESP Option (100Pa) (A) 35 39 47 52 57 66 75 Unit start up amps (A) 116 160 167 183 188 189 198 Unit start up amps - HESP Option (100Pa) (A) 117 161 169 185 190 191 199 Short Circuit Unit Capacity (9) (kA) 12 12 12 12 12 12 15
Compressor
Compressor Number per Circuit # 2 2 2 2 2 2 3 Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Model Circuit1 / Circuit 2 7.5+7.5 7.5+10 10+10 10+13 13+13 15+15 12+12+12 Motor RPM (rpm) 2900
Evaporator
Quantity #1111111 Type Stainless steel Copper Brazed plate Heat exchanger Evaporator model P80x78 P80x78 P80x78 P120Tx86 P120Tx86 P120Tx86 P120Tx110 Evaporator Water Content volume (l) 4.5 4.5 4.5 10.4 10.4 10.4 13.3 Nominal water connection size (Grooved coupling) - Without HYM (in) - (mm) 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 Nominal water connection size (Grooved coupling) - With HYM (in) - (mm) 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 3” OD - 76.1
Hydraulic Module Components
Expansion Tank Volume (l) 25 25 25 25 25 25 35 Max User water loop Volume for factory mounted expansion tank (1) (l) 1450 1450 1450 1450 1450 1450 2000 Optional water Buffer tank volume (l) 324 324 324 324 324 324 444 Max. Water-side Operating Pressure without pump package (kPa) 1000 Max. Water-side Operating Pressure with pump package (kPa) 400
Condenser
Type Aluminum fi ns & copper tubes heat exchanger Quantity of coil # 1 1 1 1 1 1 2 Face area per circuit (m²) 2.96 2.96 2.96 2.96 2.96 3.46 5.93
Condenser Fan
Quantity #1122222 Diameter (mm) 800 Fan / motor Type Propeller fan : Fixed speed AC motor / Variable speed - EC motor / HESP MAX SPEED Airfl ow per Fan (m3/h) 14949 14960 14966 12721 12726 13352 14959 Airfl ow per Fan - HESP Option (100Pa) (m3/h) 15048 15018 14972 12622 12608 13258 15019 Motor RPM (rpm) 686 686 686 6 86 686 6 86 686 Motor RPM - HESP Option (100Pa) (rpm) 91 5 915 91 5 915 915 915 915
Partial Heat recovery (PHR) option
Heat-Exchanger Type Stainless steel Copper Brazed plate Heat exchanger Heat-Exchanger Model B3-014-14-4.5M B3-014-14-4.5M B3-014-14-4.5M B3-014-14-4.5M B3-027-14-4.5L B3-027-14-4.5L B3-027-14-4.5L
Water connection size (Thread connection) (in) - (mm)
Water content volume (l) 0.14 0.14 0.14 0.14 0.35 0.35 0.35
Dimensions
Unit Length (mm) 2346 2346 2346 2346 2346 2346 2327 Unit Width (mm) 1285 1285 1285 1285 1285 1285 2250 Unit Height (mm) 1524 1524 1524 1524 1524 1724 1524
Option Additional height
Water Buffer tank option (mm) +330 +330 +330 +330 +330 +330 +330
Weights
Shipping Weight (5) (kg) 558 564 616 644 6 49 684 9 11 Operating Weight (5) (kg) 539 5 45 596 6 24 630 66 5 881
Option Additional shipping weight
Single pump - Standard head pressure (kg) 46 46 46 49 49 4 9 4 5 Single pump - High head pressure (kg) 51 51 51 51 5 1 5 1 4 9 Twin pump - Standard head pressure (kg) 70 70 70 75 75 75 71 Twin pump - High head pressure (kg) 82 82 82 82 82 82 86 Partial heat recovery option (kg) 1.48 1.48 1.48 1.48 3.82 3.82 3.82 Water Buffer tank option (kg) 319 319 319 319 31 9 319 425
System data
Nb of refrigerant circuit # 1 1 1 1 1 1 1 Minimum cooling load % (6) % 50 43 50 43 50 50 33
Standard unit
R410A refrigerant charge Circuit1 / Circuit 2 (kg) 12.5 13.0 15.0 15.0 15.0 15.5 26.0 Oil charge Circuit1 / Circuit 2 (l) 6.0 6.3 6.6 6.6 6.6 7.2 10.5
Unit with partial heat recovery option
R410a refrigerant charge Circuit1 / Circuit 2 (kg) 12.5 13.0 15.0 15.0 15.0 15.5 26.0 Oil charge Circuit1 / Circuit 2 (l) 6.0 6.3 6.6 6.6 6.6 7.2 10.5
POE Oil type OIL058E / OIL057E (1) At Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C according to EN14511:2013 (2) At Evaporator water temperature : 40°C / 45°C - Condenser air. DB/WB 7°C / 6°C according to EN14511:2013 (4) under 400V/3/50Hz (5) Rated Condition without Pump Package (6) Minimum ambient in heating operation is for unit at 40°C / 45°C (7) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser. (8) Maximum ambient operation is for unit at 12°C / 7°C (9) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch. Electrical & system data are subject to change without notice. Please refer to unit nameplate data.
SE-SN
G 1”1/4
(31.75 mm)
CXAX
017
SE-SN
G 1”1/4
(31.75 mm)
CXAX
020
SE-SN
G 1”1/4
(31.75 mm)
CXAX
023
SE-SN
G 1”1/4
(31.75 mm)
CXAX
026
SE-SN
G 1”1/4
(31.75 mm)
22
CXAX
030
SE-SN
G 1”1/4
(31.75 mm)
CG-PRC026C-GB
(31.75 mm)
CXAX
036
SE-SN
G 1”1/4
General Data
Table 6 - CXAX Standard effi ciency and Low Noise
CXAX
015
Eurovent Performances (1)
Net Cooling Capacity (kW) 43 49 58 67 7 4 8 2 9 6 Total Power input in cooling (kW) 14 17 20 2 2 25 29 32 Total Power input in cooling - HESP Option (100Pa) (kW) 15 17 20 24 27 30 34 EER 3.01 2.93 2.93 3.03 2.90 2.89 2.99 EER - HESP Option (100Pa) 2.88 2.81 2.82 2.80 2.70 2.72 2.85 ESEER 3.71 3.75 3.63 3.80 3.84 3.82 3.96 Eurovent Effi ciency class Cooling BBBBBCB Sound power level (dBA) 78 78 81 8 0 8 0 8 1 8 0 Sound power level - HESP Option (100Pa) (dBA) 86 86 8 9 9 2 9 4 8 9 9 5
Heating application data (2)
Net Heating Capacity (kW) 43 51 57 63 69 78 96 Total Power input in heating (kW) 14 16 19 21 23 25 3 0 Total Power input in heating - HESP Option (100Pa) (kW) 1 5 1 7 21 23 26 27 32 COP 3.09 3.15 2.98 3.08 3.01 3.09 3.19 COP - HESP Option (100Pa) 2.87 2.97 2.71 2.75 2.67 2.89 3.01 Eurovent Effi ciency class Heating B B C B B B B ηs 126 125 115 124 125 124 128 SCOP 3.21 3.21 2.95 3.17 3.19 3.18 3.29
Unit amps (4) (5)
Unit rated amps (A) 34 38 45 50 56 64 74 Unit rated amps - HESP Option (100Pa) (A) 35 39 47 52 57 66 75 Unit start up amps (A) 116 160 167 183 188 189 198 Unit start up amps - HESP Option (100Pa) (A) 117 161 169 185 190 191 199 Short Circuit Unit Capacity (9) (kA) 12 12 12 12 12 12 15
Compressor
Compressor Number per Circuit # 2 2 2 2 2 2 3 Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Model Circuit1 / Circuit 2 7.5+7.5 7.5+10 10+10 10+13 13+13 15+15 12+12+12 Motor RPM (rpm) 2900
Evaporator
Quantity #1111111 Type Stainless steel Copper Brazed plate Heat exchanger Evaporator model P80x78 P80x78 P80x78 P120Tx86 P120Tx86 P120Tx86 P120Tx110 Evaporator Water Content volume (l) 4.5 4.5 4.5 10.4 10.4 10.4 13.3 Nominal water connection size (Grooved coupling) - Without HYM (in) - (mm) 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 Nominal water connection size (Grooved coupling) - With HYM (in) - (mm) 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 3” OD - 76.1
Hydraulic Module Components
Expansion Tank Volume (l) 25 25 25 25 25 25 35 Max User water loop Volume for factory mounted expansion tank (1) (l) 1450 1450 1450 1450 1450 1450 2000 Optional water Buffer tank volume (l) 324 324 324 324 324 324 444 Max. Water-side Operating Pressure without pump package (kPa) 1000 Max. Water-side Operating Pressure with pump package (kPa) 400
Condenser
Type Aluminum fi ns & copper tubes heat exchanger Quantity of coil # 1 1 1 1 1 1 2 Face area per circuit (m²) 2.96 2.96 2.96 2.96 2.96 3.46 5.93
Condenser Fan
Quantity #1122222 Diameter (mm) 800 Fan / motor Type Propeller fan : Fixed speed AC motor / Variable speed - EC motor Airfl ow per Fan (m3/h) 14949 14960 14966 12721 12726 13352 14959 Airfl ow per Fan - HESP Option (100Pa) (m3/h) 15048 15018 14972 12622 12608 13258 15019 Power per Motor (kW) 0.89 / 1.95 Rated Amps per Motor (A) 2.22 / 3 Motor RPM (rpm) 686 686 686 686 686 686 686 Motor RPM - HESP Option (100Pa) (rpm) 91 5 915 91 5 915 915 915 915
Partial Heat recovery (PHR) option
Heat-Exchanger Type Stainless steel Copper Brazed plate Heat exchanger Heat-Exchanger Model B3-014-14-4.5M B3-014-14-4.5M B3-014-14-4.5M B3-014-14-4.5M B3-027-14-4.5L B3-027-14-4.5L B3-027-14-4.5L
Water connection size (Thread connection) (in) - (mm)
Water content volume (l) 0.14 0.14 0.14 0.14 0.35 0.35 0.35
Dimensions
Unit Length (mm) 2346 2346 2346 2346 2346 2346 2327 Unit Width (mm) 1285 1285 1285 1285 1285 1285 2250 Unit Height (mm) 1747 1747 1747 1747 1747 1947 1747
Option Additional height
Water Buffer tank option (mm) +330 +330 +330 +330 +330 +330 +330
Weights
Shipping Weight (5) (kg) 558 564 616 644 6 49 684 9 11 Operating Weight (5) (kg) 539 5 45 596 6 24 630 66 5 881
Option Additional shipping weight
Single pump - Standard head pressure (kg) 46 46 46 49 49 4 9 4 5 Single pump - High head pressure (kg) 51 51 51 51 5 1 5 1 4 9 Twin pump - Standard head pressure (kg) 70 70 70 75 75 75 71 Twin pump - High head pressure (kg) 82 82 82 82 82 82 86 Partial heat recovery option (kg) 1.48 1.48 1.48 1.48 3.82 3.82 3.82 Water Buffer tank option (kg) 319 319 319 319 319 319 425
Operating limits
Minimum Starting/Operating Ambient (7)
Standard ambient unit in cooling mode (°C) 5 Low Ambient (Option) in cooling mode (°C) -18 In Heating mode (°C) -15
Maximum ambient operation Standard ambient (8) (°C) 46
System data
Nb of refrigerant circuit # 1 1 1 1 1 1 1 Minimum cooling load % (6) % 50 43 50 43 50 50 33
Standard unit
R410A refrigerant charge Circuit1 / Circuit 2 (kg) 12.5 13.0 15.0 15.0 15.0 15.5 26.0 Oil charge Circuit1 / Circuit 2 (l) 6.0 6.3 6.6 6.6 6.6 7.2 10.5
Unit with partial heat recovery option
R410a refrigerant charge Circuit1 / Circuit 2 (kg) 12.5 13.0 15.0 15.0 15.0 15.5 26.0 Oil charge Circuit1 / Circuit 2 (l) 6.0 6.3 6.6 6.6 6.6 7.2 10.5
POE Oil type OIL058E / OIL057E (1) At Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C according to EN14511:2013 (2) At Evaporator water temperature : 40°C / 45°C - Condenser air. DB/WB 7°C/6°C according to EN14511:2013 (4) under 400V/3/50Hz (5) Rated Condition without Pump Package (6) Minimum ambient in heating operation is for unit at 40°C / 45°C (7) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser. (8) Maximum ambient operation is for unit at 12°C / 7°C (9) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch. Electrical & system data are subject to change without notice. Please refer to unit nameplate data.
SE-LN
G 1”1/4
(31.75 mm)
CXAX
017
SE-LN
G 1”1/4
(31.75 mm)
CXAX
020
SE-LN
G 1”1/4
(31.75 mm)
CXAX
023
SE-LN
G 1”1/4
(31.75 mm)
CXAX
026
SE-LN
G 1”1/4
(31.75 mm)
24
CXAX
030
SE-LN
G 1”1/4
(31.75 mm)
CG-PRC026C-GB
(31.75 mm)
CXAX
036
SE-LN
G 1”1/4
General Data
Table 7 - CXAX High Effi ciency and Standard Noise
CXAX
015
Eurovent Performances (1)
Net Cooling Capacity (kW) 42 48 56 65 7 2 7 9 9 4 Total Power input in cooling (kW) 14 17 19 2 2 25 28 32 EER 2.90 2.83 2.91 2.97 2.84 2.84 2.90 ESEER 3.77 3.80 3.84 4.03 3.96 3.98 4.09 Eurovent Effi ciency class Cooling BCBBCCB Sound power level (dBA) 84 84 85 8 5 8 5 8 6 8 6
Heating application data (2)
Net Heating Capacity (kW) 43 51 57 63 69 78 96 Total Power input in heating (kW) 14 16 19 21 23 25 3 0 COP 3.09 3.15 2.98 3.08 3.01 3.09 3.19 Eurovent Effi ciency class Heating B B C B B B B ηs (%) 127 129 118 127 128 128 134 SCOP 3.26 3.29 3.03 3.25 3.27 3.28 3.42
Unit amps (4) (5)
Unit rated amps (A) 35 39 47 52 57 66 75 Unit rated amps - HESP Option (100Pa) (A) 35 39 47 52 57 66 75 Unit start up amps (A) 117 161 169 185 190 191 199 Unit start up amps - HESP Option (100Pa) (A) 117 161 169 185 190 191 199 Short Circuit Unit Capacity (9) (kA) 12 12 12 12 12 12 15
Compressor
Compressor Number per Circuit # 2 2 2 2 2 2 3 Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Model Circuit1 / Circuit 2 7.5+7.5 7.5+10 10+10 10+13 13+13 15+15 12+12+12 Motor RPM (rpm) 2900
Evaporator
Quantity #1111111 Type Stainless steel Copper Brazed plate Heat exchanger Evaporator model P80x78 P80x78 P80x78 P120Tx86 P120Tx86 P120Tx86 P120Tx110 Evaporator Water Content volume (l) 4.5 4.5 4.5 10.4 10.4 10.4 13.3 Nominal water connection size (Grooved coupling) - Without HYM (in) - (mm) 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 Nominal water connection size (Grooved coupling) - With HYM (in) - (mm) 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 3” OD - 76.1
Hydraulic Module Components
Expansion Tank Volume (l) 25 25 25 25 25 25 35 Max User water loop Volume for factory mounted expansion tank (1) (l) 1450 1450 1450 1450 1450 1450 2000 Optionnal water Buffer tank volume (l) 324 324 324 324 324 324 444 Max. Water-side Operating Pressure without pump package (kPa) 1000 Max. Water-side Operating Pressure with pump package (kPa) 400
Condenser
Type Aluminum fi ns & copper tubes heat exchanger Quantity of coil # 1 1 1 1 1 1 2 Face area per circuit (m²) 2.96 2.96 2.96 2.96 2.96 3.46 5.93
Condenser Fan
Quantity #1122222 Diameter (mm) 800 Fan / motor Type Propeller fan : Variable speed - EC motor / HESP MAX SPEED Airfl ow per Fan (m3/h) 14949 14960 14966 12721 12726 13352 14959 Power per Motor (kW) 1.95 / 1.95 Rated Amps per Motor (A) 3 / 3 Motor RPM (rpm) 150 - 686 RPM
Partial Heat recovery (PHR) option
Heat-Exchanger Type Stainless steel Copper Brazed plate Heat exchanger Heat-Exchanger Model B3-014-14-4.5M B3-014-14-4.5M B3-014-14-4.5M B3-014-14-4.5M B3-027-14-4.5L B3-027-14-4.5L B3-027-14-4.5L
Water connection size (Thread connection) (in) - (mm)
Water content volume (l) 0.14 0.14 0.14 0.14 0.35 0.35 0.35
Dimensions
Unit Length (mm) 2346 2346 2346 2346 2346 2346 2327 Unit Width (mm) 1285 1285 1285 1285 1285 1285 2250 Unit Height (mm) 1524 1524 1524 1524 1524 1724 1524
Option Additional height
Water Buffer tank option (mm) +330 +330 +330 +330 +330 +330 +330
Weights
Shipping Weight (5) (kg) 558 564 616 644 6 49 684 9 11 Operating Weight (5) (kg) 539 5 45 596 6 24 630 66 5 881
Option Additional shipping weight
Single pump - Standard head pressure (kg) 46 46 46 49 49 4 9 4 5 Single pump - High head pressure (kg) 51 51 51 51 5 1 5 1 4 9 Twin pump - Standard head pressure (kg) 70 70 70 75 75 75 71 Twin pump - High head pressure (kg) 82 82 82 82 82 82 86 Partial heat recovery option (kg) 1.48 1.48 1.48 1.48 3.82 3.82 3.82 Water Buffer tank option (kg) 319 319 319 319 319 319 425
System data
Nb of refrigerant circuit # 1 1 1 1 1 1 1 Minimum cooling load % (6) % 50 43 50 43 50 50 33
Standard unit
R410A refrigerant charge Circuit1 / Circuit 2 (kg) 12.5 13.0 15.0 15.0 15.0 15.5 26.0 Oil charge Circuit1 / Circuit 2 (l) 6.0 6.3 6.6 6.6 6.6 7.2 10.5
Unit with partial heat receovery option
R410a refrigerant charge Circuit1 / Circuit 2 (kg) 12.5 13.0 15.0 15.0 15.0 15.5 26.0 Oil charge Circuit1 / Circuit 2 (l) 6.0 6.3 6.6 6.6 6.6 7.2 10.5
POE Oil type OIL058E / OIL057E (1) At Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C according to EN14511:2013 (2) At Evaporator water temperature : 40°C / 45°C - Condenser air. DB/WB 7°C/6°C according to EN14511:2013 (4) under 400V/3/50Hz (5) Rated Condition without Pump Package (6) Minimum ambient in heating operation is for unit at 40°C / 45°C (7) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser. (8) Maximum ambient operation is for unit at 12°C / 7°C (9) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch. Electrical & system data are subject to change without notice. Please refer to unit nameplate data.
HE-SN
G 1”1/4
(31.75 mm)
CXAX
017
HE-SN
G 1”1/4
(31.75 mm)
CXAX
020
HE-SN
G 1”1/4
(31.75 mm)
CXAX
023
HE-SN
G 1”1/4
(31.75 mm)
CXAX
026
HE-SN
G 1”1/4
(31.75 mm)
CXAX
030
HE-SN
G 1”1/4
(31.75 mm)
(31.75 mm)
CXAX
036
HE-SN
G 1”1/4
26
CG-PRC026C-GB
General Data
Table 8 - CXAX High Effi ciency and Low Noise
CXAX
015
Eurovent Performances (1)
Net Cooling Capacity (kW) 42 48 56 65 7 2 7 9 9 4 Total Power input in cooling (kW) 14 17 19 2 2 25 28 32 EER 2.90 2.83 2.91 2.97 2.84 2.84 2.90 ESEER 3.77 3.80 3.84 4.03 3.96 3.98 4.09 Eurovent Effi ciency class Cooling BCBBCCB Sound power level (dBA) 78 78 81 8 0 8 0 8 1 8 0
Heating application data (2)
Net Heating Capacity (kW) 43 51 57 63 69 78 96 Total Power input in heating (kW) 14 16 19 21 23 25 3 0 COP 3.09 3.15 2.98 3.08 3.01 3.09 3.19 Eurovent Effi ciency class Heating B B C B B B B ηs (%) 127 129 118 127 128 128 134 SCOP 3.26 3.29 3.03 3.25 3.27 3.28 3.42
Unit amps (4) (5)
Unit rated amps (A) 35 39 47 52 57 66 75 Unit rated amps - HESP (A) 35 39 47 52 57 66 75 Unit start up amps (A) 117 161 169 185 190 191 199 Unit start up amps - HESP (A) 117 161 169 185 190 191 199 Short Circuit Unit Capacity (9) (kA) 12 12 12 12 12 12 15
Compressor
Compressor Number per Circuit # 2 2 2 2 2 2 3 Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Model Circuit1 / Circuit 2 7.5+7.5 7.5+10 10+10 10+13 13+13 15+15 12+12+12 Rated Amps Circuit1 / Circuit 2 (4) (A) 15.5+15.5 15.5+20.2 20.2+20.2 20.2+25.3 25.3+25.3 29.5+29.5 22.9+22.9+22.9 Locked Rotor Amps Circuit1 / Circuit 2 (4) (A) 98+98 98+142 142+142 142+158 158+158 155+155 147+147+147 Motor RPM (rpm) 2900 Oil sump heater Circuit1 / Circuit 2 (W) 0.17 / 0 0.17 / 0 0.17 / 0 0.17 / 0 0.17 / 0 0.17 / 0 0.25 / 0
Evaporator
Quantity #1111111 Type Stainless steel Copper Brazed plate Heat exchanger Evaporator model P80x78 P80x78 P80x78 P120Tx86 P120Tx86 P120Tx86 P120Tx110 Evaporator Water Content volume (l) 4.5 4.5 4.5 10.4 10.4 10.4 13.3 Nominal water connection size (Grooved coupling) - Without HYM (in) - (mm) 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 Nominal water connection size (Grooved coupling) - With HYM (in) - (mm) 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 3” OD - 76.1
Hydraulic Module Components
Expansion Tank Volume (l) 25 25 25 25 25 25 35 Max User water loop Volume for factory mounted expansion tank (1) (l) 1450 1450 1450 1450 1450 1450 2000 Optional water Buffer tank volume (l) 324 324 324 324 324 324 444 Max. Water-side Operating Pressure without pump package (kPa) 1000 Max. Water-side Operating Pressure with pump package (kPa) 400
Condenser
Type Aluminum fi ns & copper tubes heat exchanger Quantity of coil # 1 1 1 1 1 1 2 Face area per circuit (m²) 2.96 2.96 2.96 2.96 2.96 3.46 5.93
Condenser Fan
Quantity #1122222 Diameter (mm) 800 Fan / motor Type Propeller fan : Variable speed - EC motor Airfl ow per Fan (m3/h) 14949 14960 14966 12721 12726 13352 14959 Motor RPM (rpm) 150 - 686 RPM
Partial Heat recovery (PHR) option
Heat-Exchanger Type Stainless steel Copper Brazed plate Heat exchanger Heat-Exchanger Model B3-014-14-4.5M B3-014-14-4.5M B3-014-14-4.5M B3-014-14-4.5M B3-027-14-4.5L B3-027-14-4.5L B3-027-14-4.5L
Water connection size (Thread connection) (in) - (mm)
Water content volume (l) 0.14 0.14 0.14 0.14 0.35 0.35 0.35
Dimensions
Unit Length (mm) 2346 2346 2346 2346 2346 2346 2327 Unit Width (mm) 1285 1285 1285 1285 1285 1285 2250 Unit Height (mm) 1747 1747 1747 1747 1747 1947 1747
Option Additional height
Water Buffer tank option (mm) +330 +330 +330 +330 +330 +330 +330
Weights
Shipping Weight (5) (kg) 558 564 616 644 6 49 684 9 11 Operating Weight (5) (kg) 539 5 45 596 6 24 630 66 5 881
Option Additional shipping weight
Single pump - Standard head pressure (kg) 46 46 46 49 49 4 9 4 5 Single pump - High head pressure (kg) 51 51 51 51 5 1 5 1 4 9 Twin pump - Standard head pressure (kg) 70 70 70 75 75 75 71 Twin pump - High head pressure (kg) 82 82 82 82 82 82 86 Partial heat recovery option (kg) 1.48 1.48 1.48 1.48 3.82 3.82 3.82 Water Buffer tank option (kg) 319 319 319 319 319 319 425
System data
Nb of refrigerant circuit # 1 1 1 1 1 1 1 Minimum cooling load % (6) % 50 43 50 43 50 50 33
Standard unit
R410A refrigerant charge Circuit1 / Circuit 2 (kg) 12.5 13.0 15.0 15.0 15.0 15.5 26.0 Oil charge Circuit1 / Circuit 2 (l) 6.0 6.3 6.6 6.6 6.6 7.2 10.5
Unit with partial heat receovery option
R410a refrigerant charge Circuit1 / Circuit 2 (kg) 12.5 13.0 15.0 15.0 15.0 15.5 26.0 Oil charge Circuit1 / Circuit 2 (l) 6.0 6.3 6.6 6.6 6.6 7.2 10.5
POE Oil type OIL058E / OIL057E (1) At Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C according to EN14511:2013 (2) At Evaporator water temperature : 40°C / 45°C - Condenser air. DB/WB 7°C/6°C according to EN14511:2013 (4) under 400V/3/50Hz (5) Rated Condition without Pump Package (6) Minimum ambient in heating operation is for unit at 40°C / 45°C (7) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser. (8) Maximum ambient operation is for unit at 12°C / 7°C (9) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch. Electrical & system data are subject to change without notice. Please refer to unit nameplate data.
HE-LN
G 1”1/4
(31.75 mm)
CXAX
017
HE-LN
G 1”1/4
(31.75 mm)
CXAX
020
HE-LN
G 1”1/4
(31.75 mm)
CXAX
023
HE-LN
G 1”1/4
(31.75 mm)
CXAX
026
HE-LN
G 1”1/4
(31.75 mm)
CXAX
030
HE-LN
G 1”1/4
(31.75 mm)
(31.75 mm)
CXAX
036
HE-LN
G 1”1/4
28
CG-PRC026C-GB
Electrical Data
Table 13 - CGAX-CXAX SE-SA Condenser fans Electrical Data
Condenser fan
Unit Type
CGAX-CXAX 015 SE-SA 0.89 /0 /0 2.2 /0 /0 0 /0 0 /0
CGAX-CXAX 017 SE-SA 0.89 /0 /0 2.2 /0 /0 0 /0 0 /0
CXAX 020 SE-SA 0.89 /0 /0 2.2 /0 /0 0 /0 0 /0
CGAX 020 SE-SA 0.89 /0.89 /0 2.2 /2.2 /0 0 /0 0 /0
CGAX-CXAX 023 SE-SA 0.89 /0.89 /0 2.2 /2.2 /0 0 /0 0 /0
CGAX-CXAX 026 SE-SA 0.89 /0.89 /0 2.2 /2.2 /0 0 /0 0 /0
CGAX-CXAX 030 SE-SA 0.89 /0.89 /0 2.2 /2.2 /0 0 /0 0 /0
CGAX-CXAX 036 SE-SA 0.89 /0.89 /0 2.2 /2.2 /0 0 /0 0 /0
CGAX 039 SE-SA 0.89 /0.89 /0 2.2 /2.2 /0 0 /0 0 /0
CXAX 039 SE-SA 0.89 /0.89 /0.89 2.2 /2.2 /2.2 0 /0 0 /0
CGAX-CXAX 045 SE-SA 0.89 /0.89 /0.89 2.2 /2.2 /2.2 0 /0 0 /0
CGAX-CXAX 035 SE-SA 0.89 /0 2.2 /0 0.89 /0 2.2 /0
CXAX 040 SE-SA 0.89 /0 2.2 /0 0.89 /0 2.2 /0
CGAX 040 SE-SA 0.89 /0.89 2.2 /2.2 0.89 /0.89 2.2 /2.2
CGAX-CXAX 046 SE-SA 0.89 /0.89 2.2 /2.2 0.89 /0.89 2.2 /2.2
CGAX-CXAX 052 SE-SA 0.89 /0.89 2.2 /2.2 0.89 /0.89 2.2 /2.2
CGAX-CXAX 060 SE-SA 0.89 /0.89 2.2 /2.2 0.89 /0.89 2.2 /2.2
Circuit 1 (Fan 1 / 2 / 3) Circuit 2 (Fan 1 / 2)
Max
Power input (kW)
Max
Amps
(A)
Max
Power input (kW)
Max
Amps
(A)
Table 14 - CGAX-CXAX SE-LA Condenser fans Electrical Data
Condenser fan
Unit Type
CGAX-CXAX 015 SE- LA 1.95/0/0 3/0/0 0/0 0/0
CGAX-CXAX 017 SE- LA 1.95/0/0 3/0/0 0/0 0/0
CXAX 020 SE- LA 1.95/0/0 3/0/0 0/0 0/0
CGAX 020 SE- LA 1.95/0.89/0 3/2.2/0 0/0 0/0
CGAX-CXAX 023 SE- LA 1.95/0.89/0 3/2.2/0 0/0 0/0
CGAX-CXAX 026 SE- LA 1.95/0.89/0 3/2.2/0 0/0 0/0
CGAX-CXAX 030 SE- LA 1.95/0.89/0 3/2.2/0 0/0 0/0
CGAX-CXAX 036 SE- LA 1.95/0.89/0 3/2.2/0 0/0 0/0
CGAX 039 SE- LA 1.95/0.89/0 3/2.2/0 0/0 0/0
CXAX 039 SE- LA 1.95/0.89/0.89 3/2.2/2.2 0/0 0/0
CGAX-CXAX 045 SE- LA 1.95/0.89/0.89 3/2.2/2.2 0/0 0/0
CGAX-CXAX 035 SE- LA 1.95/0 3/0 1.95/0 3/0
CXAX 040 SE- LA 1.95/0 3/0 1.95/0 3/0
CGAX 040 SE- LA 1.95/0.89 3/2.2 1.95/0.89 3/2.2
CGAX-CXAX 046 SE- LA 1.95/0.89 3/2.2 1.95/0.89 3/2.2
CGAX-CXAX 052 SE- LA 1.95/0.89 3/2.2 1.95/0.89 3/2.2
CGAX-CXAX 060 SE- LA 1.95/0.89 3/2.2 1.95/0.89 3/2.2
Circuit 1 (Fan 1 / 2 / 3) Circuit 2 (Fan 1 / 2)
Max
Power input (kW)
Max
Amps
(A)
Max
Power input (kW)
SE = Standard Effi ciency SA = Standard Ambient LA = Low Ambient
Max
Amps
(A)
CG-PRC026C-GB
35
Hydraulic Data
015
017 - 020 - 023
026 - 030
036 - 039 - 045
035 - 040 - 046
052 - 060
0
10
20
30
40
50
60
70
80
90
100
0 5 10 15 20 25 30 35 40 45
015
017 - 020
023
026 - 030
036
039
035
040 - 046
052 - 060
-50
0
50
100
150
200
250
0 5 10 15 20 25 30 35 40 45
015
017 - 020 - 023
026 - 030
036
039 - 045
035 - 040 - 046
052 - 060
-50
0
50
100
150
200
250
0 5 10 15 20 25 30 35 40 45
CGAX Unit without pump package
(Pressure drop)
Water pressure drop (kPa)
Water fl ow (m3/h)
CGAX Single/Dual pump - Standard head pressure
(Avail. pressure)
Water pressure drop (kPa)
Water fl ow (m3/h)
CGAX Single/Dual pump - High head pressure
(Avail. pressure)
Water pressure drop (kPa)
Water fl ow (m3/h)
CG-PRC026C-GB
37
Sound Data
Table 20 - Overall Sound Power Level at full load and 35°C ambient temperature - HESP version
Unit Type 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz Global dBA
CGAX 015 HESP 75 dB 84 dB 82 dB 80 dB 82 dB 77 dB 71 dB 62 dB 85 dBA
CGAX 017 HESP 75 dB 84 dB 82 dB 80 dB 82 dB 77 dB 71 dB 62 dB 85 dBA
CGAX 020 HESP 75 dB 89 dB 89 dB 85 dB 84 dB 80 dB 74 dB 68 dB 89 dBA
CGAX 023 HESP 72 dB 89 dB 89 dB 85 dB 84 dB 80 dB 73 dB 68 dB 89 dBA
CGAX 026 HESP 66 dB 89 dB 89 dB 85 dB 84 dB 79 dB 73 dB 69 dB 89 dBA
CGAX 030 HESP 66 dB 89 dB 89 dB 86 dB 84 dB 80 dB 74 dB 68 dB 89 dBA
CGAX 036 HESP 70 dB 87 dB 85 dB 83 dB 85 dB 80 dB 72 dB 66 dB 89 dBA
CGAX 039 HESP 70 dB 84 dB 85 dB 86 dB 86 dB 81 dB 74 dB 67 dB 90 dBA
CGAX 045 HESP 71 dB 89 dB 90 dB 88 dB 87 dB 84 dB 77 dB 69 dB 92 dBA
CGAX 035 HESP 78 dB 84 dB 85 dB 86 dB 86 dB 81 dB 75 dB 66 dB 90 dBA
CGAX 040 HESP 78 dB 92 dB 92 dB 88 dB 87 dB 83 dB 77 dB 71 dB 92 dBA
CGAX 046 HESP 75 dB 92 dB 92 dB 88 dB 87 dB 83 dB 76 dB 71 dB 92 dBA
CGAX 052 HESP 69 dB 92 dB 92 dB 88 dB 87 dB 82 dB 76 dB 72 dB 92 dBA
CGAX 060 HESP 69 dB 92 dB 92 dB 89 dB 87 dB 83 dB 77 dB 71 dB 92 dBA
CXAX 015 HESP 78 dB 88 dB 90 dB 80 dB 81 dB 75 dB 69 dB 64 dB 86 dBA
CXAX 017 HESP 78 dB 88 dB 90 dB 80 dB 81 dB 75 dB 69 dB 64 dB 86 dBA
CXAX 020 HESP 78 dB 90 dB 88 dB 84 dB 85 dB 79 dB 74 dB 69 dB 89 dBA
CXAX 023 HESP 76 dB 90 dB 88 dB 84 dB 85 dB 79 dB 74 dB 90 dB 92 dBA
CXAX 026 HESP 69 dB 90 dB 88 dB 84 dB 85 dB 79 dB 74 dB 93 dB 94 dBA
CXAX 030 HESP 67 dB 90 dB 88 dB 84 dB 85 dB 80 dB 74 dB 69 dB 89 dBA
CXAX 036 HESP 71 dB 91 dB 93 dB 83 dB 84 dB 78 dB 72 dB 95 dB 95 dBA
CXAX 039 HESP 71 dB 90 dB 92 dB 84 dB 84 dB 80 dB 73 dB 95 dB 95 dBA
CXAX 045 HESP 69 dB 91 dB 92 dB 86 dB 86 dB 82 dB 76 dB 71 dB 91 dBA
CXAX 035 HESP 81 dB 90 dB 92 dB 84 dB 84 dB 80 dB 74 dB 68 dB 90 dBA
CXAX 040 HESP 81 dB 93 dB 91 dB 87 dB 88 dB 82 dB 77 dB 72 dB 92 dBA
CXAX 046 HESP 79 dB 93 dB 91 dB 87 dB 88 dB 82 dB 77 dB 93 dB 95 dBA
CXAX 052 HESP 72 dB 93 dB 91 dB 87 dB 88 dB 82 dB 77 dB 96 dB 97 dBA
CXAX 060 HESP 70 dB 93 dB 91 dB 87 dB 88 dB 83 dB 77 dB 72 dB 92 dBA
CG-PRC026C-GB
43
Typical Unit Schematics
Figure 11 - Refrigerant Chart Cooling-only Units
46
CG-PRC026C-GB
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy effi cient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services and parts. For more information visit www.Trane.com
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifi cations without notice.
© 2016 Trane All rights reserved
CG-PRC026C-GB November 2016 Supersedes CG-PRC026B-GB_1215
We are committed to using environmentally conscious print practices that reduce waste.