Trane CGAX/CXAX User Manual

CG-PRC026C-GB
Conquest air-cooled chillers and heat pumps
Scroll compressor Model CGAX/CXAX 42-160 kW
2
© 2016 Trane
Introduction
Trane is a leader in the air-cooled chillers marketplace, thanks to excellence in design and manufacturing. This tradition of excellence is present in the Conquest air-cooled scroll compressor chillers range, a new generation of chillers and heat pumps, providing capacities from 42-160 kW.
Trane Quality
Trane is the designer and manufacturer of the core components applying modern market standards of quality in the fi nishing, a rigourous testing and manufacturing plan, a powerful service portfolio supporting the life cycle of the equipment.
Useful Effi ciency
The cooling only chillers, model CGAX, are rated Class B (EER at full load at Eurovent conditions) and optimized for operation at seasonal part load effi ciency (ESEER) to maximize energy savings during real life building demand, across all seasons.
The heat pump version, model CXAX, has been optimized in the same way. Full Load COP is class B as per Eurovent standard as well, while the part load effi ciency ratio SCOP is compliant with Ecodesign directive.
Acoustic Package
Two acoustical package options are available:
• Standard Noise (SN), with an average sound power of Lw 86 dB(A)
• Low Noise (LN), for sensitive environments with a sound reduction of an additional -6 dB(A)
The acoustical package does not bring any degradation on the performances: cooling capacity, operating map, or effi ciency.
Smart Chillers
• The operating map of the chiller, allows in cooling mode, operation between -18°C up to 46°C ambient air temperature.
• In heating mode, CXAX units can deliver 40°C hot water, down to -15°C ambient air temperature.
• For industrial applications, with evaporator leaving water temperature down to -12°C is Ecodesign compliant (SEPR medium temperature > 2,8).
• The low profi le of the Conquest units allows easy integration in buildings, thanks to the 1,5 m of height on most of the units.
• A plug & play integration is supported by the option of Hydraulic Module (with or without buffer tank).
• Chillers are provided with a Smart Controller and a new generation interface, the Deluxe Touch Display.
• Full integrability capability thanks to available communication protocols: Modbus, BACnet, LonTalk and Trane BMS.
Table of Contents
3
Introduction .......................................................................................................2
Features and Benefi ts ........................................................................................ 4
Application Considerations .............................................................................. 7
Unit Placement ................................................................................................ 10
Model Number Description ............................................................................ 12
General Data .................................................................................................... 14
Dimensional Data ............................................................................................ 30
Electrical Data .................................................................................................. 33
Hydraulic Data .................................................................................................. 37
Sound Data ...................................................................................................... 40
Typical Unit Schematics .................................................................................. 45
Mechanical Specifi cations ..............................................................................48
Options ............................................................................................................. 50
4
Features and Benefits
Reliability
A robust design of the compressor and refrigerant circuit has been validated by an extensive program of operational tests, in extreme conditions, to ensure maximum reliability. Quality is verifi ed during each and every step.
Compressors
Direct drive, low speed, new generation of scroll compressor, with few moving parts, providing high effi ciency, reliable operation and simplifi ed maintenance. Suction gas cooled motor winding, maintaining uniform low temperature for extended motor life.
Oil Equalization
Oil Pick Up
Oil sight Glass
Rotor
Stator
Fixed Scroll
Discharge Valve plate
Oldham Coupling
Counter weight
Orbiting
Scroll
Figure 1 - Scroll compressor
Chiller controller
The Conquest chiller is equipped with the new generation of chiller control systems, providing improved control capabilities, and integrated safety protocols to protect both compressors and motors from electrical faults like thermal overload and phase reversal.
The LCD display with 6 navigation buttons shows clear messages in 15 available languages. It features a customer communication package consisting in: external chilled water setpoint, external demand limit, analog capacity output, programmable relays.
A deluxe display is available as an option.,It features an intuitive and user friendly color 7 inch touchscreen, able to display: Data trending, clear alarms logging, and TIS enable for remote monitoring.
Figure 2 - Standard LCD user interface
Figure 3 - Optional deluxe user interface
5
Microchannel condensing coils on cooling­only units
Conquest chillers are equipped with microchannel condensing coils allowing excellent heat transfer and a dramatic improvement of corrosion resistance versus conventional tubes in fi ns coils. Microchannel coils are 100% aluminum, therefore avoiding galvanic corrosion which can occur on conventional condensers made with copper tubes and aluminum fi ns. Microchannel coils are also well adapted for dirty environment thanks to their small thickness and fi ns profi le.
Heat pump units coils
The condenser coil is made of aluminum fi ns mechanically bonded to seamless copper tubing and includes integral subcooling circuit. The coils are factory leak tested at 5 Mpa. If the unit is to be installed in a corrosive environment, aluminum fi ns can be pre-coated with epoxy (optional), with minimum thickness of 8µm, in order to withstand 1000 hours of salt spray test according to ISO 9227.
Electronic Expansion Valve
Electronic expansion valve enables tight chilled water temperature control and low superheat, resulting in more effi cient full-load and part-load operation.
Application versatility
Extended operating map, allowing chiller operation in multiple applications:
• Industrial/low temperature process cooling with precise temperature control capability
• Optimal and reliable operation at high ambient temperatures.
LWT = Leaving water temperature
Amb Air T = Ambient air temperature
A = Standard operating map
B = Low ambient operating map (Variable air fl ow control)
Minimum start-up/operation ambient based on a
2.22 m/s (5mph) wind across the condenser
Features and Benefi ts
Figure 4 - Microchannel condensing coils
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
-15 -10 -5 0 5 10 15 20 25
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
-15 -10 -5 0 5 10 15 20 25
A
LWT (°C )
Amb Air T °C
B
AmbAir T °C
LWT (°C)
Figure 5 - Operating map- Cooling-only Model CGAX
Air condenser inlet
Slit fi ns and brazed contact for improved heat transfer and strength
Microchannels
for R410A
Air
condenser
outlet
6
Features and Benefi ts
LWT = Leaving water temperature
Amb Air T = Ambient air temperature
A = Standard operating map
B = Low ambient operating map (Variable air fl ow control)
Minimum start-up/operation ambient based on a
2.22 m/s (5mph) wind across the condenser
Improved Serviceability
• All main components like compressors, valves and refrigerant components are easy to access to simplify servicing. When the unit is supplied with an hydraulic module, the service valves and strainer can be accessed with ease for service.
• Water connections are extended up to the edge of the unit, for easy connection with system water piping.
• Optional pump package is designed for easy maintenance and service on site.
• Pressure transducers and temperature sensors are supplied for easy identifi cation of potential troubleshooting and eventually, replacement, without the need of refrigerant handling.
• Dead front panel and IP20 protection allow for safe servicing.
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
-15 -10 -5 0 5 10 15 20 25
Cooling Mode
-25
-20
-15
-10
-5
0
5
10
15
20
25
15 20 25 30 35 40 45 50 55 60 65
Heating Mode
A
B
A
LWT (°C ) LWT (°C )
Amb Air T °C
Amb Air T °C
AmbAir T °C
Cooling Mode
Heating Mode
LWT (°C)
LWT (°C)
AmbAir T °C
Figure 6 - Heat Pump Model CXAX operating map
7
Application Considerations
Certain applications contraints should be considered when sizing, selecting and installing Conquest air­cooled Scroll chillers. Unit and system reliability often depend on proper and complete compliance with those considerations.
Unit Size
Unit oversizing is often not recommended since erratic unit operation and excessive compressor cycling are often a direct result of an oversized chiller. If oversizing is desired, consider the alternative of multiple units, splitting the total capacity.
Water Treatment
The use of untreated or improperly treated water in chillers may result in scaling, erosion, corrosion, and algae or slime buildup. This will adversely affect heat transfer between the water and system components. Proper water treatment must be determined locally and depends on the type of system and local water characteristics.
Neither salty nor brackish water is recommend for use in Trane air-cooled Conquest chiller. Usage of either will lead to a shortened life. Trane encourages the employment of a qualifi ed water treatment specialist, familiar with local water conditions, to assist in the establishment of a proper water treatment program.
Foreign matter in the chilled water system can also increase pressure drop and, consequently, reduce water fl ow. For this reason it is important to thoroughly fl ush all water piping to the unit before making the fi nal piping connections to the unit.
Effect of the altitude on the cooling capacity
At elevations substantially above sea level, the decreased air density will decrease condenser capacity and, therefore, unit capacity and effi ciency.
Water fl ow limits
The minimum water fl ow rates are given in the General Data section of this catalog. Evaporator fl ow rates below the tabulated values will result in laminar fl ow causing freeze-up problems,scaling, stratifi cation and poor control. The maximum evaporator water fl ow rate is also given. Flow rates exceeding those listed may result in very high pressure drop across the evaporator.
Flow Rates Out of Range
Many process cooling jobs require fl ow rates that cannot be met with the minimum and maximum published values within the Conquest chiller evaporator. A simple piping change can alleviate this problem. For example: a plastic injection molding process requires 5.0 l/s of 10°C water and returns that water at 15.6°C. The selected chiller can operate at these temperatures, but has a minimum fl ow rate of 6.6 l/s. The system layout in Figure 7 can satisfy the process.
L = Load P = Pump
Flow Proving
Trane provides a factory-installed water fl ow switch monitored by chilller controller CH535 which protects the chiller from operating in loss of fl ow conditions.
Leaving Water Temperature Limits
Trane air-cooled Conquest chillers have two distinct leaving water categories:
• standard, with a leaving solution range of 5.5 to 18°C
• low temperature process cooling, with leaving solution range of -12 to 18°C
Since the leaving solution temperature below 5.5°C results in suction temperature at or below the freezing point of water, a glycol solution is required for all low temperature.
Consult your local Trane sales engineer for applications or selections involving low temperature. The maximum water temperature that can be circulated through the CGAX evaporator when the unit is not operating is
51.7°C. For the model CXAX the water temperature
limit is 60°C. Evaporator damage may result above this temperature.
L = Load P = Pump
10°C 5 l/s
10°C 2 l/s
15.6°C 5 l/s
14°C 7 l/s
10°C 7 l/s
Figure 7 - Flow rate out of range systems solution
L
P
P
15°C 15 l/s
15°C
3.8 l/s
35°C
3.8 l/s
35°C 15 l/s
15°C
35°C
11.2 l/s
11.2 l/s
20°C 15 l/s
30°C 15 l/s
Figure 8 - Temperature out of range system solution
8
Application Considerations
Supply Water Temperature Drop
Full load chilled water temperature drops from 3.3 °C to 10°C may be used as long as minimum and maximum water temperature and minimum and maximum fl ow rates are not violated.
Temperature drops outside this range at full load conditions are beyond the optimum range for control and may adversely affect the microcomputer’s ability to maintain an acceptable supply water temperature range. Furthermore, full load temperature drops of less than
3.3°C may result in inadequate refrigerant superheat which is critical to long term effi cient and reliable operation.
Suffi cient superheat is always a primary concern in any refrigerant system and is especially important in a packaged chiller where the evaporator is closely coupled to the compressor.
Parameters which infl uence the water temperature stability:
• Ambient temperature and water temperature (modify cooling capacity)
• Number of capacity steps
• Minimum time between starts of a compressor
• Control dead band
• Water loop volume
• Load fl uctuations
• Fluid type or percentage of glycol
Typical Water Piping
All building water piping must be fl ushed prior to making fi nal connections to the chiller. To reduce heat loss and prevent condensation, insulation should be applied. Expansion tanks are also usually required so that chilled water volume changes can be accommodated.
Avoidance of Short Water Loops
Adequate chilled water system water volume is an important system design parameter because it provides for stable chilled water temperature control and helps limit unacceptable short cycling of chiller compressors.
The Conquest Air Cooled chiller’s temperature control sensor is located in the supply (outlet) water connection or pipe. This location allows the building to act as a buffer to slow the rate of change of the system water temperature. If there is not a suffi cient volume of water in the system to provide an adequate buffer, temperature control can suffer, resulting in erratic system operation and excessive compressor cycling.
Typically, a two-minute water loop circulation time is suffi cient to prevent short water loop issues. Therefore, as a guideline, ensure the volume of water in the chilled water loop equals or exceeds two times the evaporator fl ow rate. For systems with a rapidly changing load profi le the amount of volume should be increased.
If the installed system volume does not meet the above recommendations, the following items should be given careful consideration to increase the volume of water in the system and, therefore, reduce the rate of change of the return water temperature.
• A volume buffer tank located in the return water piping.
• Larger system supply and return header piping (which also reduces system pressure drop and pump energy use).
An optional factory-installed buffer tank is designed to meet the minimum two minute loop time without additional job site piping. The buffer tank can also be used on jobs that already meet or exceed the minimum loop time to further reduce the potential for compressor cycling, increasing the compressor life span, and reducing system temperature fl uctuations.
9
Application Considerations
Minimum water volume for a process application
If a chiller is attached to an on/off load such as a process load, it may be diffi cult for the controller to respond quickly enough to the very rapid change in return solution temperature if the system has only the minimum water volume recommended. Such systems may cause chiller low temperature safety trips or in the extreme case evaporator freezing. In this case, it may be necessary to add or increase the size of the mixing tank in the return line or consider the optional factory­installed buffer tank with the chiller. Some guidance on calculating the minimum volume necessary for proper Scroll Compressors Chillers operation are given here, through a simplifi ed formula, which does not take in account variations on chiller effi ciency, compressor sequencing, evaporator inlet/outlet temperature.
Minimum recommendable volume on the hydraulic loop
V= Cc * T / (Sh * Db) where:
Cc * T = V * Db * Sh
V = Volume of the loop (l)
Cc = Cooling Capacity of the chiller biggest Stage (kW)
T = Compressor Time (min running time (s))
Db = Dead Band (K)
Sh = Brine Specifi c heat (kJ.K
-1
.kg-1)
Multiple Unit Operation
Whenever two or more units are used on one chilled water loop, Trane recommends that their operation be coordinated with a higher level system controller for best system effi ciency and reliability. The Trane Tracer system has advanced chilled plant control capabilities designed to provide such operation.
10
Unit Placement
Setting The Unit
A base or foundation is not required if the selected unit location is level and strong enough to support the unit’s operating weight (see “Weights” section of this catalog).
For a detailed discussion of base and foundation construction, refer to the sound engineering bulletin or the unit IOM. Manuals are available through the local Trane offi ce.
HVAC equipment must be located to minimize sound and vibration transmission to the occupied spaces of the building structure it serves. If the equipment must be located in close proximity to a building, it should be placed next to an unoccupied space such as a storage room, mechanical room, etc. It is not recommended to locate the equipment near occupied, sound sensitive areas of the building or near windows. Locating the equipment away from structures will also prevent sound refl ection, which can increase sound levels at property lines or other sensitive points.
Isolation and Sound Emission
Structurally transmitted sound can be reduced by elastomeric vibration eliminators. Elastomeric isolators are generally effective in reducing vibratory noise generated by compressors, and therefore, are recommended for sound sensitive installations. An acoustical engineer should always be consulted in critical situations.
Figure 9 - Installation example
For maximum isolation effect, water lines and electrical conduit should also be isolated. Wall sleeves and rubber isolated piping hangers can be used to reduce the sound transmitted through water piping. To reduce the sound transmitted through electrical conduit, use fl exible electrical conduit.
Local codes on sound emissions should always be considered. Since the environment in which a sound source is located affects sound pressure, unit placement must be carefully evaluated. Sound power levels for chillers are available on request.
Servicing
Adequate clearance for evaporator and compressor servicing should be provided. Recommended minimum space envelopes for servicing are located in the dimensional data section and can serve as a guideline for providing adequate clearance. The minimum space envelopes also allow for control panel door swing and routine maintenance requirements. Local code requirements may take precedence.
Unit Location
General
Unobstructed fl ow of condenser air is essential to maintain chiller capacity and operating effi ciency. When determining unit placement, careful consideration must be given to assure a suffi cient fl ow of air across the condenser heat transfer surface. Two detrimental conditions are possible and must be avoided: warm air recirculation and coil starvation. Air recirculation occurs when discharge air from the condenser fans is recycled back to the condenser coil inlet. Coil starvation occurs when free airfl ow to the condenser is restricted.
Condenser coils and fan discharge must be kept free of snow or other obstructions to permit adequate airfl ow for satisfactory unit operation. Debris, trash, supplies, etc., should not be allowed to accumulate in the vicinity of the air-cooled chiller. Supply air movement may draw debris into the condenser coil, blocking spaces between coil fi ns and causing coil starvation.
Both warm air recirculation and coil starvation cause reductions in unit effi ciency and capacity because of the higher head pressures associated with them. The air-cooled Conquest chiller offers an advantage over competitive equipment in these situations. Operation is minimally affected in many restricted air fl ow situations due to its advanced chiller controller.
Microprocessor which has the ability to understand the operating environment of the chiller and adapt to it by fi rst optimizing its performance and then staying on line through abnormal conditions. For example, high ambient temperatures combined with a restricted air fl ow situation will generally not cause the air-cooled model CGAX chiller to shut down. Other chillers would typically shut down on a high pressure nuisance cut-out in these conditions.
Cross winds, those perpendicular to the condenser, tend to aid effi cient operation in warmer ambient conditions. However, they tend to be detrimental to operation in lower ambients due to the accompanying loss of adequate head pressure. Special consideration should be given to low ambient units. As a result, it is advisable to protect air-cooled chillers from continuous direct winds exceeding 4.5 m/s in low ambient conditions.
Chiled water piping should be supported.
Isolators
Flexible electrical conduit
Concrete base
Isolators
Piping isolation
11
Unit Placement
Provide Suffi cient Unit-to-Unit Clearance
Units should be separated from each other by suffi cient distance to prevent warm air recirculation or coil starvation. Doubling the recommended single unit air-cooled chiller clearances will generally prove to be adequate.
Walled Enclosure Installations
When the unit is placed in an enclosure or small depression, the top of the surrounding walls should be no higher than the top of the fans. The chiller should be completely open above the fandeck. There should be no roof or structure covering the top of the chiller. Ducting individual fans is not recommended.
12
Model Number Description
Digit 1-4 — Chiller Model
CGAX: Cooling-only unit
CXAX: Heat pump unit
Digit 5-7 — Unit Nominal Size
015: 15 ton
017: 17 ton
020: 20 ton
023: 23 ton
026: 26 ton
030: 30 ton
036: 36 ton
039: 39 ton
045: 45 ton
035: 35 ton
040: 40 ton
046: 46 ton
052: 52 ton
060: 60 ton
Digit 8 — Unit Voltage
E: 400V/3ph/50Hz
Digit 9 — Manufacturing Plant
1 = Europe
Digit 10-11 — Design Sequence
A: Factory asigned
0: Factory asigned
Digit 12 — Effi ciency Level
1: Standard Effi ciency Class (B)
2: High Effi ciency
Digit 13 — Agency Listing
E: CE Certifi cation
Digit 14 — Pressure Vessel Code
4: Pressure Equipment Directive (PED)
Digit 15 — Condenser Temperature Range
A: Standard operating map (5°C/46°C)
C: Low Ambient Cooling (CGAX -18°C/46°C;
CXAX -10°C/46°C)
Digit 16, 17 — Open for future options
Digit 18 — Freeze Protection (Factory-Installed Only)
X: Without freeze protection
2: With freeze protection by heaters
3: With freeze protection by pump activation
Digit 19, 20 — Open for future options
Digit 21 — Evaporator Application
A: Comfort application (5°C/20°C)
B: Process application (CGAX: -12°C/5°C;
CXAX: -10°C/5°C)
Digit 22 — Water Connection (Evaporator)
1: Grooved pipe
2: Grooved pipe, couplings and pipestub
Digit 23 — Condenser Fin Material
B: Standard aluminum fi ns on Heat Pumps
E: Epoxy aluminum fi ns on Heat Pumps
H: Microchannel (MCHE) on Cooling-only Units
J: E-coating on MCHE on Cooling-only units
Digit 24 — Condenser Heat Recovery
X: Without Heat Recovery
2: Partial Heat Recovery
Digit 25 — Open for future options
Digit 26 — Starter Type
A: Across-the-line starter
B: Solid State Soft Starter
Digit 27, 28, 29 — Open for future options
Digit 30 — Human Interface
A: Standard display
B: Deluxe touch display
X: Without display
Digit 31 — Communication Options
X: Without remote communication
1: ModBus Interface
2: LonTalk Interface
3: Smart Web Interface
4: BACnet Interface
Digit 32 — Customer Input/Ouput Options
X: None
A: With
13
Model Number Description
Digit 33 — Smart Sequencer
X: None
Digit 34 — Open for future options
Digit 35 — Hydraulic Module/Pump package type
X: Without contactors
2: Only contactors single pump
4: Only contactors twin pump
5: Single pump package low pressure
6: Single pump package high pressure
7: Dual pump package low pressure
8: Dual pump package high pressure
Digit 36 — Pump fl ow control
X: Constant fl ow
B: Manual fl ow control
C: Variable primary fl ow (constant Delta T)
D: Variable primary fl ow (constant Delta P)
Digit 37 — Buffer Tank
X: No Tank
1: With Tank
Digit 38 — Open digit for future options
Digit 39 — Installation Accessories
1: None
4: Neoprene pads
Digit 40 — Open digit for future options
Digit 41 — Acoustical options
2: High External Static Pressure
3: Standard
4: Low Noise
Digit 42 — Condenser Protection
A: Condenser guard grills
X: Without
Digit 43 — Open digit for future options
Digit 44 — Literature Language
B: Spanish
C: English
D: German
E: French
H: Dutch
J: Italian
M: Swedish
N: Turkish
P: Polish
T: Czech
U: Greek
V: Portuguese
Y: Romanian
3: Hungarian
Digit 45 — Under/Over Voltage Protection
X: None
1: With
Digit 46 — Open for future options
Digit 47 — Customer witness performance test
X: None
Digit 48 — Open for future options
Digit 49 — Supplementary Heat Control
1: With
X: Without
Digit 50 — Special design
X: Standard
S: Special design
14
General Data
Table 1 - CGAX Standard effi ciency and Standard Noise
Eurovent Performances (1)
CGAX
015
SE-SN
CGAX
017
SE-SN
CGAX
020
SE-SN
CGAX
023
SE-SN
CGAX
026
SE-SN
CGAX
030
SE-SN
CGAX
036
SE-SN
Net Cooling Capacity (kW) 43 49 59 65 74 82 99 Total Power input in cooling (kW) 15 17 19 22 26 29 33 Total Power input in cooling - HESP Option (100Pa) (kW) 15 18 21 24 27 31 34 EER 2.98 2.88 3.08 2.95 2.87 2.84 2.96 EER - HESP (915 RPM - 100Pa) 2.82 2.74 2.89 2.81 2.78 2.76 2.81 ESEER 3.89 3.93 3.81 3.82 3.84 3.80 3.93 Eurovent Effi ciency class Cooling BCBBCCB Sound power level (dBA) 83 83 85 85 85 86 84 Sound power level - HESP Option (100Pa) (dBA) 85 85 89 89 89 89 89
Unit amps (4) (5)
Unit rated amps (A) 34 38 45 50 56 64 74 Unit rated amps - HESP Option (100Pa) (A) 35 39 47 52 57 66 75 Unit start up amps (A) 116 160 167 183 188 189 198 Unit start up amps - HESP Option (100Pa) (A) 117 161 169 185 190 191 199 Short Circuit Unit Capacity (9) (kA) 12 12 12 12 12 12 15
Compressor
Compressor Number per Circuit # 2222223 Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Model Circuit1 / Circuit 2 7.5+7.5 7.5+10 10+10 10+13 13+13 15+15 12+12+12 Motor RPM (rpm) 2900
Evaporator
Quantity # 1111111 Type Stainless steel Copper Brazed plate Heat exchanger Evaporator model P80x66 P80x92 P80x92 P80x92 P120Tx76 P120Tx76 P120Tx104 Evaporator Water Content volume (l) 3.8 5.3 5.3 5.3 9.2 9.2 12.5 Nominal water connection size (Grooved coupling) -
Without HYM
(in) - (mm) 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3
Nominal water connection size (Grooved coupling) ­With HYM
(in) - (mm) 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 3” OD - 76.1
Hydraulic Module Components
Expansion Tank Volume (l) 25 25 25 25 25 25 35 Max User water loop Volume for factory mounted
expansion tank (1)
(l) 1450 1450 1450 1450 1450 1450 2000
Optional water Buffer tank volume (l) 324 324 324 324 324 324 444 Max. Water-side Operating Pressure without pump
package
(kPa) 1000
Max. Water-side Operating Pressure with pump package
(kPa) 400
Condenser
Type Full aluminum Micro channel heat exchanger Quantity of coil # 1111112 Face area per circuit (m²) 2.23 2.23 2.96 2.96 2.96 2.96 4.46
Condenser Fan
Quantity # 1122222 Diameter (mm) 800 Fan / motor Type Propeller fan : Fixed speed AC motor / Variable speed - EC motor Airfl ow per Fan (m
3
/h) 13788 13828 12362 12362 12370 12375 13827
Airfl ow per Fan - HESP Option (100Pa) (m
3
/h) 13753 13718 12248 12231 12211 12193 13727 Motor RPM (rpm) 686 686 686 686 686 686 686 Motor RPM - HESP Option (100Pa) (rpm) 915 915 915 915 915 915 915
Partial Heat recovery (PHR) option
Heat-Exchanger Type Stainless steel Copper Brazed plate Heat exchanger Heat-Exchanger Model B3-014-14-4.5M B3-014-14-4.5M B3-014-14-4.5M B3-014-14-4.5M B3-027-14-4.5L B3-027-14-4.5L B3-027-14-4.5L
Water connection size (Thread connection) (in) - (mm)
G 1”1/4
(31.75 mm)
G 1”1/4
(31.75 mm)
G 1”1/4
(31.75 mm)
G 1”1/4
(31.75 mm)
G 1”1/4
(31.75 mm)
G 1”1/4
(31.75 mm)
G 1”1/4
(31.75 mm)
Water content volume (l) 0.14 0.14 0.14 0.14 0.35 0.35 0.35
Dimensions
Unit Length (mm) 2346 2346 2346 2346 2346 2346 2327 Unit Width (mm) 1285 1285 1285 1285 1285 1285 2250 Unit Height (mm) 1524 1524 1524 1524 1524 1524 1524
Option Additional height
Water Buffer tank option (mm) +330 +330 +330 +330 +330 +330 +330
Weights
Shipping Weight (5) (kg) 519 531 574 579 608 621 853 Operating Weight (5) (kg) 497 509 552 557 587 599 819
Option Additional shipping weight
Single pump - Standard head pressure (kg) 46 46 46 49 49 49 45 Single pump - High head pressure (kg) 51 51 51 51 51 51 49 Twin pump - Standard head pressure (kg) 70 70 70 75 75 75 71 Twin pump - High head pressure (kg) 82 82 82 82 82 82 86 Partial heat recovery option (kg) 1.48 1.48 1.48 1.48 3.82 3.82 3.82 Water Buffer tank option (kg) 319 319 319 319 319 319 425
System data
Nb of refrigerant circuit # 1111111 Minimum cooling load % (6) % 50 43 50 43 50 50 33
Standard unit
R410A refrigerant charge Circuit1 / Circuit 2 (kg) 7.5 9. 0 9.0 9.0 10.5 10.5 14.0 Oil charge Circuit1 / Circuit 2 (l) 6.0 6.3 6.6 6.6 6.6 7.2 10.5
Unit with partial heat recovery option
R410a refrigerant charge Circuit1 / Circuit 2 (kg) 7.5 9.0 9.0 9.0 10.5 10.5 14.0 Oil charge Circuit1 / Circuit 2 (l) 6.0 6.3 6.6 6.6 6.6 7.2 10.5
POE Oil type OIL058E / OIL057E
(1) At Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C according to EN14511:2013 (2) At Evaporator water temperature : 6.6°C (44°F) / 12.2°C (54°F) - condenser air temperature 46°C (114.8°F) (4) under 400V/3/50Hz (5) Rated Condition without Pump Package (6) Percent minimum load can be lowered on demand to local sales offi ce. (7) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser. (8) Maximum ambient operation is for unit at 12°C / 7°C (9) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch. Electrical & system data are subject to change without notice. Please refer to unit nameplate data.
15
General Data
Eurovent Performances (1)
CGAX
039
SE-SN
CGAX
045
SE-SN
CGAX
035
SE-SN
CGAX
040
SE-SN
CGAX
046
SE-SN
CGAX
052
SE-SN
CGAX
060
SE-SN
Net Cooling Capacity (kW) 111 127 9 7 116 129 147 16 4 Total Power input in cooling (kW) 38 41 35 39 47 51 58 Total Power input in cooling - HESP Option (100Pa) (kW) 39 45 36 43 50 57 61 EER 2.92 3.08 2.79 2.94 2.78 2.86 2.83 EER - HESP (915 RPM - 100Pa) 2.82 2.81 2.72 2.73 2.61 2.55 2.68 ESEER 4.13 3.98 3.83 3.64 3.59 3.75 3.81 Eurovent Effi ciency class Cooling BCCBBCC Sound power level (dBA) 85 87 86 88 88 88 89 Sound power level - HESP Option (100Pa) (dBA) 90 92 90 92 92 92 92
Unit amps (4) (5)
Unit rated amps (A) 81 96 77 90 101 111 128 Unit rated amps - HESP Option (100Pa) (A) 83 98 78 93 104 114 131 Unit start up amps (A) 214 221 198 212 233 243 253 Unit start up amps - HESP Option (100Pa) (A) 215 224 200 215 236 247 256 Short Circuit Unit Capacity (9) (kA) 15 15 15 15 15 15 15
Compressor
Compressor Number per Circuit # 3322222 Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Model Circuit1 / Circuit 2 13+13+13 15+15+15 7.5+10 / 7.5+10 10+10 / 10+10 10+13 /10+13 13+13 / 13+13 15+15 / 15+15 Motor RPM (rpm) 2900
Evaporator
Quantity # 1111111 Type Stainless steel Copper Brazed plate Heat exchanger Evaporator model P120Tx104 P120Tx104 DP300x82 DP300x82 DP300x82 DP300x114 DP300x114 Evaporator Water Content volume (l) 12.5 12.5 8.5 8.5 8.5 11.8 11.8 Nominal water connection size (Grooved coupling) -
Without HYM
(in) - (mm) 2" - 60.3 2" - 60.3 3" OD - 76.1 3" OD - 76.1 3" OD - 76.1 3" OD - 76.1 3" OD - 76.1
Nominal water connection size (Grooved coupling) ­With HYM
(in) - (mm) 3" O D - 76.1 3" OD - 76.1 3" OD - 76.1 3" OD - 76.1 3" OD - 76.1 3" OD - 76.1 3" OD - 76.1
Hydraulic Module Components
Expansion Tank Volume (l) 35 35 35 35 35 35 35 Max User water loop Volume for factory mounted
expansion tank (1)
(l) 2000 2000 2000 2000 2000 2000 2000
Optional water Buffer tank volume (l) 444 444 444 444 444 444 444 Max. Water-side Operating Pressure without pump
package
(kPa) 1000
Max. Water-side Operating Pressure with pump package
(kPa) 400
Condenser
Type Full aluminum Micro channel heat exchanger Quantity of coil # 2222222 Face area per circuit (m²) 5.93 5.93 2.23 2.96 2.96 2.96 2.96
Condenser Fan
Quantity # 2324444 Diameter (mm) 800 Fan / motor Type Propeller fan : Fixed speed AC motor / Variable speed - EC motor Airfl ow per Fan (m
3
/h) 14690 13676 14687 12358 12363 12592 12374
Airfl ow per Fan - HESP Option (100Pa) (m
3
/h) 14660 13595 14686 12249 12233 12447 12205 Motor RPM (rpm) 686 686 686 686 686 686 686 Motor RPM - HESP Option (100Pa) (rpm) 915 915 915 915 915 915 915
Partial Heat recovery (PHR) option
Heat-Exchanger Type Stainless steel Copper Brazed plate Heat exchanger Heat-Exchanger Model B3-027-20-4.5L B3-027-20-4.5L 2xB3-014-14-4.5M 2xB3-014-14-4.5M 2xB3-014-14-4.5M 2xB3-027-14-4.5L 2xB3-027-14-4.5L
Water connection size (Thread connection) (in) - (mm)
G 1”1/4
(31.75 mm)
G 1”1/4
(31.75 mm)
G 1”1/4
(31.75 mm)
G 1”1/4
(31.75 mm)
G 1”1/4
(31.75 mm)
G 1”1/4
(31.75 mm)
G 1”1/4
(31.75 mm)
Water content volume (l) 0.5 0.5 2x0.14 2x0.14 2x0.14 2x0.35 2x0.35
Dimensions
Unit Length (mm) 2327 2327 2327 2327 2327 2327 2327 Unit Width (mm) 2250 2250 2250 2250 2250 2250 2250 Unit Height (mm) 1524 1524 1524 1524 1524 1524 1524
Option Additional height
Water Buffer tank option (mm) +330 +330 +330 +330 +330 +330 +330
Weights
Shipping Weight (5) (kg) 858 912 917 1004 1014 1034 1060 Operating Weight (5) (kg) 824 879 887 973 983 1004 1029
Option Additional shipping weight
Single pump - Standard head pressure (kg) 47 47 45 47 47 47 47 Single pump - High head pressure (kg) 49 49 49 49 49 49 49 Twin pump - Standard head pressure (kg) 75 75 75 75 75 75 75 Twin pump - High head pressure (kg) 86 86 84 84 84 84 84 Partial heat recovery option (kg) 4.6 4.6 2x1.48 2x1.48 2x1.48 2x3.82 2x3.82 Water Buffer tank option (kg) 425 425 425 425 425 425 425
System data
Nb of refrigerant circuit # 1122222 Minimum cooling load % (6) % 33 33 22 25 22 25 25
Standard unit
R410A refrigerant charge Circuit1 / Circuit 2 (kg) 14.5 15.0 8.0 / 8.0 8.0 / 8.0 8.0 / 8.0 9.0 / 9.0 9.5 / 9.5 Oil charge Circuit1 / Circuit 2 (l) 10.5 11.5 6.3 / 6.3 6.6 / 6.6 6.6 / 6.6 6.6 / 6.6 7.2 / 7.2
Unit with partial heat recovery option
R410a refrigerant charge Circuit1 / Circuit 2 (kg) 14.5 15.0 8.0 / 8.0 8.0 / 8.0 8.0 / 8.0 9.0 / 9.0 9.5 / 9.5 Oil charge Circuit1 / Circuit 2 (l) 10.5 11.5 6.3 / 6.3 6.6 / 6.6 6.6 / 6.6 6.6 / 6.6 7.2 / 7.2
POE Oil type OIL058E / OIL057E
(1) At Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C according to EN14511:2013 (2) At Evaporator water temperature : 6.6°C (44°F) / 12.2°C (54°F) - condenser air temperature 46°C(114.8°F) (4) under 400V/3/50Hz (5) Rated Condition without Pump Package (6) Percent minimum load can be lowered on demand to local sales offi ce. (7) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser. (8) Maximum ambient operation is for unit at 12°C / 7°C (9) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch. Electrical & system data are subject to change without notice. Please refer to unit nameplate data.
Table 1 - CGAX Standard effi ciency and Standard Noise (continued)
16
General Data
Table 2 - CGAX Standard effi ciency and Low Noise
Eurovent Performances (1)
CGAX
015
SE-LN
CGAX
017
SE-LN
CGAX
020
SE-LN
CGAX
023
SE-LN
CGAX
026
SE-LN
CGAX
030
SE-LN
CGAX
036
SE-LN
Net Cooling Capacity (kW) 43 49 59 65 74 82 99 Total Power input in cooling (kW) 15 17 19 22 26 29 33 Total Power input in cooling - HESP Option (100Pa) (kW) 15 18 21 24 27 31 34 EER 2.98 2.88 3.08 2.95 2.87 2.84 2.96 EER - HESP Option (100Pa) 2.82 2.74 2.89 2.81 2.78 2.76 2.81 ESEER 3.89 3.93 3.81 3.82 3.84 3.80 3.93 Eurovent Effi ciency class Cooling BCBBCCB Sound power level (dBA) 77 77 79 79 79 80 79 Sound power level - HESP Option (100Pa) (dBA) 85 85 89 89 89 89 89
Unit amps (4) (5)
Unit rated amps (A) 34 38 45 50 56 64 74 Unit rated amps - HESP Option (100Pa) (A) 35 39 47 52 57 66 75 Unit start up amps (A) 116 160 167 183 188 189 198 Unit start up amps - HESP Option (100Pa) (A) 117 161 169 185 190 191 199 Short Circuit Unit Capacity (9) (kA) 12 12 12 12 12 12 1 5
Compressor
Compressor Number per Circuit # 2222223 Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Model Circuit1 / Circuit 2 7.5+7.5 7.5+10 10+10 10+13 13+13 15+15 12+12+12 Motor RPM (rpm) 2900
Evaporator
Quantity # 1111111 Type Stainless steel Copper Brazed plate Heat exchanger Evaporator model P80x66 P80x92 P80x92 P80x92 P120Tx76 P120Tx76 P120Tx104 Evaporator Water Content volume (l) 3.8 5.3 5.3 5.3 9.2 9.2 12.5 Nominal water connection size (Grooved coupling) -
Without HYM
(in) - (mm) 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3
Nominal water connection size (Grooved coupling) ­With HYM
(in) - (mm) 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 2” - 60.3 3” OD - 76.1
Hydraulic Module Components
Expansion Tank Volume (l) 25 25 25 25 25 25 35 Max User water loop Volume for factory mounted
expansion tank (1)
(l) 1450 1450 1450 1450 1450 1450 2000
Optional water Buffer tank volume (l) 324 324 324 324 324 324 444 Max. Water-side Operating Pressure without pump
package
(kPa) 1000
Max. Water-side Operating Pressure with pump package
(kPa) 400
Condenser
Type Full aluminum Micro channel heat exchanger Quantity of coil # 1111112 Face area per circuit (m²) 2.23 2.23 2.96 2.96 2.96 2.96 4.46
Condenser Fan
Quantity # 1122222 Diameter (mm) 800 Fan / motor Type Propeller fan : Fixed speed AC motor / Variable speed - EC motor Airfl ow per Fan (m
3
/h) 13788 13828 12362 12362 12370 12375 13827
Airfl ow per Fan - HESP Option (100Pa) (m
3
/h) 13753 13718 12248 12231 12211 12193 13727 Motor RPM (rpm) 686 686 686 686 686 686 686 Motor RPM - HESP Option (100Pa) (rpm) 915 915 915 915 915 915 915
Partial Heat recovery (PHR) option
Heat-Exchanger Type Stainless steel Copper Brazed plate Heat exchanger Heat-Exchanger Model B3-014-14-4.5M B3-014-14-4.5M B3-014-14-4.5M B3-014-14-4.5M B3-027-14-4.5L B3-027-14-4.5L B3-027-14-4.5L
Water connection size (Thread connection) (in) - (mm)
G 1”1/4
(31.75 mm)
G 1”1/4
(31.75 mm)
G 1”1/4
(31.75 mm)
G 1”1/4
(31.75 mm)
G 1”1/4
(31.75 mm)
G 1”1/4
(31.75 mm)
G 1”1/4
(31.75 mm)
Water content volume (l) 0.14 0.14 0.14 0.14 0.35 0.35 0.35
Dimensions
Unit Length (mm) 2346 2346 2346 2346 2346 2346 2327 Unit Width (mm) 1285 1285 1285 1285 1285 1285 2250 Unit Height (mm) 1747 1747 1747 1747 1747 1747 1747
Option Additional height
Water Buffer tank option (mm) +330 +330 +330 +330 +330 +330 +330
Weights
Shipping Weight (5) (kg) 519 531 574 579 608 621 853 Operating Weight (5) (kg) 497 509 552 557 587 599 819
Option Additional shipping weight
Single pump - Standard head pressure (kg) 46 46 46 49 49 49 45 Single pump - High head pressure (kg) 51 51 51 51 51 51 49 Twin pump - Standard head pressure (kg) 70 70 70 75 75 75 71 Twin pump - High head pressure (kg) 82 82 82 82 82 82 86 Partial heat recovery option (kg) 1.48 1.48 1.48 1.48 3.82 3.82 3.82 Water Buffer tank option (kg) 319 319 319 319 319 319 425
System data
Nb of refrigerant circuit # 1111111 Minimum cooling load % (6) % 50 43 50 43 50 50 33
Standard unit
R410A refrigerant charge Circuit1 / Circuit 2 (kg) 7.5 9. 0 9.0 9.0 10.5 10.5 14.0 Oil charge Circuit1 / Circuit 2 (l) 6.0 6.3 6.6 6.6 6.6 7.2 10.5
Unit with partial heat recovery option
R410a refrigerant charge Circuit1 / Circuit 2 (kg) 7.5 9.0 9.0 9.0 10.5 10.5 14.0 Oil charge Circuit1 / Circuit 2 (l) 6.0 6.3 6.6 6.6 6.6 7.2 10.5
POE Oil type OIL058E / OIL057E
(1) At Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C according to EN14511:2013 (4) under 400V/3/50Hz (5) Rated Condition without Pump Package (6) Percent minimum load can be lowered on demand to local sales offi ce. (7) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser. (8) Maximum ambient operation is for unit at 12°C / 7°C (9) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch. Electrical & system data are subject to change without notice. Please refer to unit nameplate data.
Loading...
+ 36 hidden pages