Trane CGA-SVX01A-EN Installation, Operation And Maintenance Manual

CGA-SVX01A-EN
Installation Operation Maintenance
Air-Cooled Cold Generator Air-Cooled Cold Generator
With Heat Pump Option
®
®
2
MODEL NOMENCLATURE INSTALLATION
RIGGING MOUNTING WATER PIPING
FIGURE 1: RECOMMENDED HOISTING ARRANGEMENT FIGURE 2: DIMENSION FOR MOUNTING
FIGURE 3: SERVICE & MAINTENANCE CLEARANCE ELECTRICAL WIRING UNIT POWER SUPPLY
FIGURE 4: TYPICAL PIPING ARRANGEMENT
FIGURE 5: TYPICAL SYSTEM APPLICATION
ELECTRICAL DATA FLOW SWITCH INTERLOCK
CIRCUIT DIAGRAM FOR CGAK 030 - 075
CIRCUIT DIAGRAM FOR CGAR 030 - 075
CIRCUIT DIAGRAM FOR CGAK 100 - 200
CIRCUIT DIAGRAM FOR CGAR 100 - 150 INSTALLATION CHECKLIST
PRE-START PROCEDURE
VOLTAGE UTILIZATION RANGE VOLTAGE IMBALANCE WATER FLOW RATE UNIT WATER PRESSURE DROP
FIGURE 6: HYDRAULIC CHARACTERISTIC PRE-START CHECKLIST
OPERATION
START-UP PROCEDURE EXTENDED UNIT SHUT-DOWN/WINTERIZATION STANDARD AMBIENT OPERATION OPTIONAL LOW AMBIENT OPERATION (CGAK) OPTIONAL HEAT PUMP OPERATION (CGAR) ELECTRICAL CONTROL & PROTECTION SYSTEM
MAINTENANCE TROUBLE ANALYSIS
TABLE OF CONTENTS
3 4
11 12
17
22
26 27
3
CGA 1,2,3
K4050
5,6,7
58D9F10R11M12R13N14A
15
CGA-SVX01A-EN
MODEL NOMENCLATURE
DIGIT 1,2,3
CGA=Air-Cooled Cold Generator
®
DIGIT 4 - Model
K=Cooling Only (030~200) R=Cooling With Heat Pump Option (030~150)
DIGIT 5,6,7 - Number
030 040 050 075 100 125 150 175 200
DIGIT 8 - Voltage
1=220V/60Hz/1Ph (For model 030,040,050) 2=220V/60Hz/3Ph (For model 050,075,100,125,150, 175, 200) 3=380V/60Hz/3Ph (For model 050,075,100,125,150, 175, 200) 4=460V/60Hz/3Ph (For model 050,075,100,125,150, 175, 200) 5=380V/50Hz/3Ph (For model 050,075,100,125,150, 175, 200) 6=400V/50Hz/3Ph (For model 050,075,100,125,150, 175, 200) 7=415V/50Hz/3Ph (For model 050,075,100,125,150, 175, 200)
DIGIT 9 - Development Sequence
D=Fourth Design
DIGIT 10 - Controls
F=Fixed Entering Water Temperature Control (Standard Option) A=Adjustable Entering Water Temperature Control (Microprocessor Controller) (For CGAK Models as Optional) (For CGAR Models as Standard Option)
DIGIT 11- Water Pump
N = No Pump R = Standard Pump (Standard Option)
DIGIT 12 - Refrigerant Pressure Gauges
M = No (Standard Option) G = With High/Low Pressure Gauges
DIGIT 13 - Temperature Kit
R = Standard Ambient Temperature Kit (Standard Option) L = Low Ambient Temperature Kit (For CGAK Models Only)
DIGIT 14 - Other Options
M = Standard Fin + Standard Grille Cover N = Standard Fin + Luxury Grille Cover C = Blue Fin + Standard Grille Cover B = Blue Fin + Luxury Grille Cover
DIGIT 15 - Service Sequence
A = First
© American Standard Inc. 2001
4
INSTALLATION
Table 1 - Unit Shipping Weights
Maximum Shipping Weight (Kg)
230 250 260 370 450 500 530 550 570
Model
030 040 050 075 100 125 150 175 200
CGA-SVX01A-EN
Complete the “Installation Checklist” during installation to verify completion of all recommended procedures before unit start-up.
RIGGING
Each unit is bolted to a shipping skid for shipment to the job site. Move the unit using a forklift of suitable capacity. See Table 1 for unit shipping weights.
Locate the unit near a large-capacity drain to allow system drainage during unit shutdown and repair. Rig the unit using canvas belt. Fasten the belt to the unit over the unit’s base as show in Figure 1.
MOUNTING
Mounting methods that will minimize sound and vibration problems are:
1. Mount the unit directly on an isolated concrete pad or on isolated concrete footings at each unit mounting point.
2. Install the optional neoprene or spring isolators at each mounting location.
Refer to Figure 2 for unit and base dimensions and Figure 3 for recommended service clearance.
WATER PIPING
Thoroughly flush all water system piping before making the final piping connections to the unit.
5
Figure - 1: Recommended Hoisting Arrangement (CGAK-075 As Shown)
CGA-SVX01A-EN
© American Standard Inc. 2001
6
Figure - 2: Dimension for Mounting (CGAK-075 As Shown) Note: All Dimensions in Millimeter
CGA-SVX01A-EN
7
Figure - 3: Service and Maintenance Clearance (CGAK-075 As Shown)
CGA-SVX01A-EN
© American Standard Inc. 2001
8
CGA-SVX01A-EN
CAUTION: If using an acidic commercial flushing solution, construct a temporary bypass around the unit to prevent damage to the evaporator.
CAUTION: To avoid possible equipment damage, do not use untreated or improperly treated water.
For unit’s water connection sizes and locations, please refer to Figure 2.
CAUTION: To prevent unit damage, do not reverse system piping connections to the unit; water entering the unit must enter at the designated “Water In” and leaving water must exit the unit through the designated “Water Out” connection.
Figure 4 illustrates typical unit piping components. Components and layout will vary slightly depending upon the locations of the connections and water source.
Figure 5 gives a schematic of a typical system application for this unit.
Provide vents at high points in the piping to bleed air from the chilled water system. Install pressures gage(s) to monitor entering and leaving chilled water pressure.
CAUTION: To prevent damage to the waterside components of unit, do not allow evaporator pressure to exceed 100 psig (i.e. maximum working pressure). Use an expansion tank to isolate this pressure if water pressure exceeds this value.
ELECTRICAL WIRING
WARNING: To prevent injury or death, disconnect electrical power source before completing wiring connections to the unit.
CAUTION: Use only copper conductors for terminal connections to avoid corrosion or over heating.
Figure 2 shows the location of the unit electrical access openings. Table 2 provides minimum circuit ampacities, recommended fuse sizes, and motor electrical data.
UNIT POWER SUPPLY
Refer to the unit wiring schematic fixed to the control panel cover. The installer must provide a power supply of proper voltage and a fused disconnect switch to the unit.
Run properly sized power wirings through the electrical access opening on the side of the unit, and connect it to the Voltage Terminal Block (1TB1) in the unit control panel. Install a fused disconnect switch as required by local codes. Provide proper equipment grounds for the ground connections in the unit control panel and at the fused disconnect switch.
Refer to wiring diagrams from Page 13 to Page 16 for reference of a typical unit installa­tion. For actual wiring diagram, refer to the one fixed to the control panel cover.
FLOW SWITCH INTERLOCK
To avoid possible evaporator freeze-up resulting from reduced water flow, install a flow switch ( or other flow sensing device) in the evaporator outlet water line. This sensing device must be adjusted to stop compressor operation if water flow to the evaporator drops below 70% of the system design full­flow rate.
The installer must provide interconnecting wiring between the unit control panel and the water flow sensing switch in the evaporator water line.
9
Figure - 4: Typical Piping Arrangement (CGAK-075 As Shown)
CGA-SVX01A-EN
© American Standard Inc. 2001
10
Figure - 5: Typical System Application (CGAK-075 And Fans As Shown)
CGA-SVX01A-EN
Loading...
+ 22 hidden pages