Trane CGAM Installation & Operation Manual

Page 1
Installation, Operation, and Maintenance
Air-Cooled Scroll Chillers
Model CGAM 20 – 130Tons — Made in USA
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
June 2012 CG-SVX17E-EN
SAFETY WARNING
Page 2
Warnings, Cautions and Notices
Warnings, Cautions and Notices. Note that warnings,
cautions and notices appear at appropriate intervals throughout this manual. Warnings are provide to alert installing contractors to potential hazards that could result in death or personal injury. Cautions are designed to alert personnel to hazardous situations that could result in personal injury, while notices indicate a situation that could result in equipment or property-damage-only accidents.
Your personal safety and the proper operation of this
machine depend upon the strict observance of these precautions.
Read this manual thoroughly before operating or servicing this unit.
ATTENTION: Warnings, Cautions and Notices appear at
appropriate sections throughout this literature. Read these carefully:
WARNING
CAUTIONs
NOTICE:
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situationthat could result in equipment or property-damage only
must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards.To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
WARNING
R-410A Refrigerant under Higher Pressure than R-22!
The units described in this manual use R-410A
refrigerant which operates at higher pressures than R­22 refrigerant. Use ONLY R-410A rated service equipment or components with these units. For specific handling concerns with R-410A, please contact your localTrane representative. Failure to use R-410A rated service equipment or components could result in equipment exploding under R-410A high pressures which could result in death, serious injury, or equipment damage.
Important Environmental Concerns!
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment.Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified.The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that
WARNING
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.
Before installing/servicing this unit, technicians MUST put onall PersonalProtective Equipment (PPE) recommended for the work being undertaken.
ALWAYSrefer to appropriateMSDS sheetsand OSHA
guidelines for proper PPE.
When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS sheets and
OSHA guidelines for information on allowable personal exposure levels, proper respiratory protection and handling recommendations.
If there is a risk of arc or flash, technicians MUST put on all Personal Protective Equipment (PPE) in accordance with NFPA 70E or other country-specific requirements for arc flash protection, PRIOR to servicing the unit.
Failure to follow recommendations could result in death or serious injury.
© 2012Trane All rights reserved CG-SVX17E-EN
Page 3
WARNING
Hazardous Service Procedures!
The maintenance and troubleshooting procedures
recommended in this manual could result in exposure to electrical, mechanical or other potential safety hazards. Always refer to the safety warnings provided throughout this manual concerning these procedures. Unless specified otherwise, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized.
When necessary to work with live electrical
components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks. Failure to follow all of the recommended safety warnings provided, could result in death or serious injury.
Introduction
Overview
This manual covers the installation, operation and
maintenance of the CGAM units.
Warnings, Cautions and Notices
Revision Summary
CG-SVX17E-EN
The following points describe the changes to this revision
of the manual:
High ambient option added
Copper fin option added
Seismically rated isolator option added
No Freeze Protection option added
Pump package option pressure drop information revised
Maximum loop volume for pump package expansion tank added
Diagnostics tables updated
Trademarks
Trane, CompleteCoat,Tracer and theTrane logo are
trademarks ofTrane in the United States and other countries. All trademarks referenced in this document are the trademarks of their respective owners.
CG-SVX17E-EN 3
Page 4
Table of Contents
Model Number Descriptions .............................................................. 6
Nameplates ........................................................................... 6
Unit Nameplate ........................................................................ 6
Compressor Nameplate ................................................................. 6
Model Number Coding System .......................................................... 6
Unit Model Number Description ......................................................... 7
Compressor Model Number Description .................................................. 8
General Information ..................................................................... 9
Unit Description ....................................................................... 9
Accessory/Options Information ......................................................... 10
General Data ........................................................................... 12
Pre-Installation ......................................................................... 16
Inspection Checklist ................................................................... 16
Unit Storage ......................................................................... 16
Installation Requirements .............................................................. 16
Unit Dimensions/Weights ............................................................... 17
Installation - Mechanical ................................................................ 32
Location Requirements ................................................................ 32
Rigging .............................................................................. 32
Unit Isolation and Leveling ............................................................. 36
Evaporator Piping ..................................................................... 46
Partial Heat Recovery .................................................................. 54
Dual High Head Pump Package ......................................................... 57
Installation - Electrical ................................................................... 64
General Recommendations ............................................................ 64
Electrical Data Tables .................................................................. 65
Installer-Supplied Components ......................................................... 70
Interconnecting Wiring ................................................................ 72
Communications Interface options ...................................................... 77
BACnet Communications Interface for Chillers (BCI-C) ..................................... 78
Object Data Points and Diagnostic Data Points with Corresponding Chiller Models ............ 83
BCI-C Alarming ....................................................................... 89
CGAM Operating Principles .............................................................. 90
General .............................................................................. 90
Refrigerant Cycle ..................................................................... 98
Oil System Operation (CGAM) .......................................................... 99
4 CG-SVX17E-EN
Page 5
Controls Interface ...................................................................... 101
CH530 Communications Overview ..................................................... 101
DynaView Interface .................................................................. 101
Display Screens ..................................................................... 102
Basic Screen Format ................................................................. 102
Main Screen ........................................................................ 103
Settings Screen ...................................................................... 104
Local Time of Day Schedule Screen .................................................... 106
Lockout Screen ...................................................................... 109
Reports ............................................................................. 109
Power Up and Self Tests .............................................................. 110
TechView ........................................................................... 110
Pre-Start Checkout ..................................................................... 121
Unit Voltage Power Supply ............................................................ 122
Water System ....................................................................... 123
Start Up Checklist .................................................................. 124
Unit Start-Up Procedures ............................................................... 126
Sequence of Operation ............................................................... 126
Start-Up ............................................................................ 127
Seasonal Unit Start-Up Procedure ..................................................... 128
Limit Conditions ..................................................................... 128
Unit Shutdown ........................................................................ 129
Normal Shutdown to Stopped ......................................................... 129
Seasonal Unit Shutdown ............................................................. 129
Maintenance .......................................................................... 131
Periodic Maintenance ................................................................ 131
Compressor Service Information ....................................................... 132
Condenser Maintenance .............................................................. 136
Evaporator Maintenance .............................................................. 136
Pump Package Maintenance ........................................................... 137
Diagnostics ........................................................................... 139
Main Processor Diagnostic ............................................................ 140
Sensor Failure Diagnostics ............................................................ 146
Communication Diagnostics ........................................................... 147
Main Processor- Boot Messages and Diagnostics ........................................ 150
Unit Wiring ........................................................................... 151
CG-SVX17E-EN 5
Page 6
Model Number Descriptions
Nameplates
The CGAM unit nameplates are applied to the exterior
surface of the control panel door for 20-70Ton sizes.The 80-120Ton sizes have a nameplate on a support beam to the right side of the starter panel.
A compressor nameplate is located on each compressor.
See Figure 1.
Unit Nameplate
The unit nameplate provides the following information:
Unit model and size descriptor.
Unit serial number.
Identifies unit electrical requirements.
Lists correct operating charges of R-410A and refrigerant oil.
Lists unit design pressures.
Identifies installation, operation and maintenance and service data literature.
Lists drawing numbers for unit wiring diagrams.
Figure 1. Unit and compressor nameplates
Compressor Nameplate
The compressor nameplate provides the following
information:
Compressor model number.
Compressor serial number.
Compressor electrical characteristics.
Utilization Range.
Recommended refrigerant.
Model Number Coding System
The model numbers for the unit and the compressors are
comprised of numbers and letter which represent features of the equipment.
See “Unit Model Number Description,” p. 7 and
“Compressor Model Number Description,” p. 8 for details.
Each position, or group of positions, in a number or letter is used to represent a feature.For example, from the chart, we can determine that the letter “F” in digit 8 of the unit model number indicates unit voltage is 460/60/3.
CGAM Unit Nameplate
6 CG-SVX17E-EN
CGAM Compressor Nameplate
Page 7
Unit Model Number Description
Digits 1-4— Chiller Model
CGAM= Air-Cooled Scroll Packaged Chiller
Digits 5-7— Unit Nominal Ton
020 = 20Tons 026 = 26Tons 030 = 30Tons 035 = 35Tons 040 = 40Tons 052 = 52Tons 060 = 60Tons 070 = 70Tons 080 = 80Tons 090 = 90Tons 100 = 10 0Tons 110 = 110 T o n s 120 = 120Tons 130 = 130Tons
Digit 8— Unit Voltage
A = 208 Volt 60 Hz 3 Phase B = 230 Volt 60 Hz 3 Phase D = 380 Volt 60 Hz 3 Phase E = 400 Volt 50 Hz 3 Phase F = 460 Volt 60 Hz 3 Phase G = 575 Volt 60 Hz 3 Phase
Digit 9— Manufacturing Plant
2 = Pueblo, USA
Digits 10-11— Design Sequence
A-Z = Factory/ABU Assigned
Digit 12— Unit Type
2 = High Efficiency
Digit 13— Agency Listing
X = No Agency Listing A = UL Listed to U.S. and Canadian Safety Standard
Digit 14— Pressure Vessel Code
X = No Pressure Code
Digit 15— Unit Application
B = High Ambient (32-125°F/0-52°C) D = Wide Ambient (0-125°F/18-52°C)
Digit 16— Refrigerant Isolation
Valves
2 = Refrigerant Isolation Valves (Discharge Valve)
Digit 17— Seismically Rated
A = Not Seismically Rated Unit B = IBC Seismically Rated Unit C = OSHPD Seismically Rated Unit
Digit 18— Freeze Protection (Factor-Installed Only)
X = Without Freeze Protection 1 = With Freeze Protection (External
T-Stat Control)
Digit 19— Insulation
A = Factory Insulation - All Cold Parts B = Insulation for High Humidity/Low EvapTemp
Digit 20— Factory Charge
1 = Full Factory Refrigerant Charge (HFC-R10A) 2 = Nitrogen Charge
Digit 21— Evaporator
Application
A = Standard Cooling (42 to 65°F/5.5
to 18°C) B = Low Temperature Processing (lower than 42°F/5.5°C) C = Ice-Making - Hardwired Interface (20 to 65°F/-7 to 18°C)
Digit 22— Water Connections
1 = Grooved Pipe Connection
Digit 23— Condenser Fin Material
A = Lanced Aluminum Fins
C = Non-Lanced Copper Fins D = Lanced Aluminum Fins w/ CompleteCoat™
Digit 24— Condenser Heat Recovery
X = No Heat Recovery 1 = Partial Heat Recovery with Fan Control
Digit 25— Not Used
X
Digit 26— Starter Type
A = Across the Line Starter/Direct on
Line
Digit 27— Incoming Power Line Connection
1 = Single Point Power Connection
Digit 28— Power Line Connection Type
A = Terminal Block
C = Circuit Breaker D = Circuit Breaker with High Fault Rated Control Panel
Digit 29— Enclosure Type
1 = WaterTight (per UL 1995 Standard)
Digit 30— Unit Operator Interface
A = Dyna-View/English
B = Dyna-View/Spanish-Spain C = Dyna-View/Spanish-Mexico D = Dyna-View/French E = Dyna-View/German F = Dyna-View/Dutch G = Dyna-View/Italian H = Dyna-View/Japanese J = Dyna-View/Portuguese-Portugal K = Dyna-View/Portuguese-Brazil L = Dyna-View/Korean M = Dyna-View/Thai N = Dyna-View/Simplified Chinese P = Dyna-View/Traditional Chinese R = Dyna-View/Russian
T = Dyna-View/Polish
U = Dyna-View/Czech V = Dyna-View/Hungarian W = Dyna-View/Greek Y = Dyna-View/Romanian
Z = Dyna-View/Swedish
Digit 31— Remote Interface (Digital Comm)
X = No Remote Digital Communication 2 = LonTalk/Tracer Summit Interface 3 = Time of Day Scheduling 4 = BACNet Interface
Digit 32— External Chilled/Hot
Water and Current Demand
Limit Setpoint
X = No External Chilled Water Setpoint
A = External Chilled Water and
Demand Limit Setpoint 4-20mA B = External Chilled Water and Demand Limit Setpoint 2-10Vdc
Digit 33— Percent Capacity
X = Without Percent Capacity 1 = With Percent Capacity
Digit 34— Programmable Relays
X = No Programmable Relays
A = Programmable Relays
Digit 35— PumpType
X = No Pumps and No Contactors 8 = Dual High Head Pump
Digit 36— Pump Flow Control
X = No Pump Control B = Pump Flow Controlled by
Variable Speed Drive
Digit 37— BufferTank
X = No BufferTank 1 = With BufferTank
Digit 38— Short Circuit Rating
A = Default A Short Circuit Rating
B = High A Short Circuit Rating
Digit 39— Installation
Accessories
X = No Installation Accessories 1 = Elastomeric Isolators 3 = Seismically Rated Isolators
Digit 40— Water Strainer
A = With Water Strainer Factory-
Installed
Digit 41— sound Attenuator Package
3 = Super Quiet 5 = Comprehensive Acoustic Package
Digit 42— Appearance Options
X = No Appearance Options
A = Architectural Louvered Panels
B = Half Louvers
Digit 43— Exterior Finish
1 = Standard Paint
Digit 44— Label, Literature Language
B = Spanish D = English E = French and English
CG-SVX17E-EN 7
Page 8
Digit 45— Phase Reversal Protection
1 = Phase Reversal Protection
Digit 46— Shipping Package
X = No Skid (Standard) A = Unit Containerization Package
Digit 47— PerformanceTest Options
X = No PerformanceTest 2 = 1 PointTest with Report 3 = Witness 1 PointTest with Report
Digit 48— Flow Switch Set Point
C=15 F=35 H= 45 L=60
Digit 49— Not Used
X
Digit 50— Specials
X = None S = Special
Note: If a digit is not defined it may be
held for future use.
Compressor Model
Number Description
Digits 1-4— Compressor Model
CSHD= Light Commercial
CSHN= Commercial
Digits 5-7— Capacity
125 = CSHD
161 = CSHD
184 = CSHN
250 = CSHN
315 = CSHN
374 = CSHN
Digit 8— Voltage
J = 200-230/60/3
K = 460/60/3 - 400/50/3
F = 230/50/3
D = 575/60/3
X = 380/60/3
Digit 9— Unloading
0 = No Unloading
Digit 10 — Design Sequence
Factory Assigned
Digit 11— Protection Module
Voltage
0= iInt Line Break - CDHD
A= 115 VAC
B= 230 VAC
H= 24 VAC
K= 115/230 VAC - CSHN
Digit 12— Basic Compressor
Variation
M= Suction & DischargeTube, Oil
Equalizer with Seal Nut, Grade 32 POE oil
8 CG-SVX17E-EN
Page 9
General Information
Unit Description
The CGAM units are scroll type, air-cooled, liquid chillers,
designed for installation outdoors.The 20-35 ton units have a single independent refrigerant circuit, with two compressors per circuit.The 40 ton and larger units have 2 independent refrigerant circuits, with two compressors per circuit.The CGAM units are packaged with an evaporator and condenser.
Note: Each CGAM unit is a completely assembled,
hermetic -compressors packaged unit that is factory-piped, wired, leak-tested, dehydrated, charged and tested for proper control operations prior to shipment.The chilled water inlet and outlet openings are covered for shipment.
The CGAM series featuresTrane's exclusive Adaptive Control logic with CH530 controls. It monitors the control variables that govern the operation of the chiller unit. Adaptive Control logic can correct these variables, when necessary, to optimize operational efficiencies, avoid chiller shutdown, and keep producing chilled water.
Each refrigerant circuit is provided with filter, sight glass, electronic expansion valve, and charging valves on the CGAM.
The evaporator is a brazed plate heat exchanger which is
equipped with a water drain and vent connections in the water piping.The condenser is an air-cooled slit fin coil.
The condensers are available in three configurations
depending on the tonnage of the unit. Units may be referred to the size by the condenser configuration.The three configurations are slant, V and W.
Figure 3. CGAM “V” 40-70Ton Configuration
Figure 4. CGAM “W” 80-130Ton Configuration
Figure 2. CGAM Slant 20-35 Ton Configuration
CG-SVX17E-EN 9
Page 10
General Information
Accessory/Options Information
Check all the accessories and loose parts which are shipped with the unit against the original order. Included in these items will be water vessel drain plugs, rigging diagrams, electrical diagrams, and service literature, which are placed inside the control panel and/or starter panel for shipment. Also check for optional components, such as isolators.
The unit isolators and fan prop rod ship on brackets
attached to the frame of the unit. The location varies by unit tonnage.The following figures show the location of these ship with items for the different sizes.
Figure 5. Slant 20-35 ton - ship with location -
isolators and prop rod
Figure 6. V 40-70 ton - ship with location - isolator and
prop rod
Elastomeric Isolators
Prop Rod
Elastomeric solators
Prop Rod
Seismic Isolators
Seismic Isolators
10 CG-SVX17E-EN
Page 11
General Information
Figure 7. W 80-130 ton - ship with location - isolator
and prop rod
Prop Rod
Elastomeric Isolators
Seismic Isolators
CG-SVX17E-EN 11
Page 12
General Data
General Data
Table 1. General Data - 60 Hz - IP
Size 20 26 30 35 40 52 60 70 80 90 100 110 120 130 Compressor
Number#22224444444446
25-50­75-100
20+20
+25
15-31­46-62-
81-100
Tonnage/circuit¹ 10+10 13+13 15+15 15+20 10+10 13+13 15+15 15+20 20+20 20+25 25+25 25+30 30+30
Evaporator
Water storage (gal) 1.4 2.2 2.2 3.2 2.4 4.1 5.0 7.5 7.0 9.0 10.3 11.5 11.5 12.3
Min. flow (gpm) 30 38 42 50 57 74 84 100 115 129 145 157 170 184
Max. flow (gpm) 69 89 100 117 136 176 201 238 275 307 346 375 407 440
Water connection (in) 2 2.5 2.5 2.5 3 3 3 3 4 4 4 4 4 4
Condenser
Quantity of coils#11112222444444
Coil length (in) 91 91 127 127 91 91 127 127 121 121 144 144 144 180 Coil height (in) 68 68 68 68 68 68 68 68 42 42 42 42 42 42
Number of rows#22222222333333
Fins per foot (fpf) 192 192 192 192 192 192 192 192 192 192 192 192 192 192
Fan
Quantity#223344666688810
Diameter (in) 28.8 28.8 28.8 28.8 28.8 28.8 28.8 28.8 28.8 28.8 28.8 28.8 28.8 28.8
Airflow per fan (cfm) 9413 9420 9168 9173 9413 9420 9168 9173 9470 9472 9094 9096 9098 9094
Power per motor (kW) 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2
Motor RPM (rpm) 840 840 840 840 840 840 840 840 840 840 840 840 840 840
Tip speed (ft/min) 6333 6333 6333 6333 6333 6333 6333 6333 6333 6333 6333 6333 6333 6333
General Unit
Refrig circuits#11112222222222
25-50-
25-50-
25-50-
21-43-
25-50-
22-44-
25-50-
Capacity steps % 50-100 50-100 50-100 43-100
Refrig charge/circuit¹ (lbs) 32 34 48 48 32 32 50.5 48 74 78 81 91.5 86 112
Oil charge/circuit¹ (gal) 1.7 1.7 3.5 3.5 1.7 1.7 3.5 3.5 3.5 3.5 3.5 3.7 3.8 5.8
Min ambient - wide(°F)00000000000000
Min ambient - high (°F) n/a 32 32 32 32
75-100
75-100
75-100
71-100
75-100
72-100
75-100
23-45­73-100
Pump Package
Avail head pressure² (ft H2O) 78.2 77.7 71.1 67.6 67.1 58.6 76.7 63.5 82.0 78.1 69.0 61.9 71.3 62.2
Power (HP) 5.0 5.0 5.0 5.0 5.0 5.0 7.6 7.6 10.2 10.2 10.2 10.2 15.2 15.2
Expansion tank
volume
(gal)55555555666666
4
Partial Heat Recovery
Water storage/circuit¹ (gal) 0.02 0.02 0.02 0.03 0.02 0.02 0.02 0.03 0.03 0.04 0.04 0.04 0.06 0.06
Max flow (gpm) 39 39 39 39 78 78 78 78 127 127 127 127 127 127
Water connection (in) 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5 2.5 2.5
Buffer Tank
Buffer tank volume (gal) 140 140 140 140 140 140 140 140 152 152 195 195 195 195
Notes:
1. Data shown for circuit one only. The second circuits always matches.
2. When facing the control panel, circuit 1 is on the right side of unit.
3. Pump available head pressure is based on: 44/54°F evaporator with water, .0001 hr-ft²-°F/Btu, 95°F ambient and 0 ft elevation.
4. See Table 29, p. 62 for maximum loop volumes with pump package expansion tank.
12 CG-SVX17E-EN
Page 13
General Data
Table 2. General Data - 60 Hz - SI
Size 20 26 30 35 40 52 60 70 80 90 100 110 120 130 Compressor
Number#22224444444446
25-50­75-100
20+20
+25
15-31­46-62-
81-100
Tonnage/circuit¹ 10+10 13+13 15+15 15+20 10+10 13+13 15+15 15+20 20+20 20+25 25+25 25+30 30+30
Evaporator
Water storage (l) 5.3 8.3 8.3 12.1 9.1 15.5 18.9 28.4 26.5 34.1 39.0 43.5 43.5 46.6
Min. flow (l/s) 1.8 2.3 2.6 3.1 3.6 4.6 5.3 6.3 7.2 8.1 9.1 9.9 10.7 11.6
Max. flow (l/s) 4.4 5.6 6.3 7.4 8.6 11.1 12.7 15.1 17.4 19.4 21.9 23.7 25.7 27.8
Water connection (mm) 50.8 63.5 63.5 63.5 76.2 76.2 76.2 76.2 101.6 101.6 101.6 101.6 101.6 101.6
Condenser
Qty of coils#11112222444444
Coil length (mm) 2311 2311 3226 3226 2311 2311 3226 3226 3073 3073 3658 3658 3658 4572 Coil height (mm) 1727 1727 1727 1727 1727 1727 1727 1727 1067 1067 1067 1067 1067 1067
Number of rows#22222222333333
Fins per foot (fpf) 192 192 192 192 192 192 192 192 192 192 192 192 192 192
Fan
Quantity/circuit¹#2233223323444
Diameter (mm) 732 732 732 732 732 732 732 732 732 732 732 732 732 732
Airflow per fan
Power per motor (kW) 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2
Motor RPM (rpm) 840 840 840 840 840 840 840 840 840 840 840 840 840 840
Tip speed(m/s)3232323232323232323232323232
(m³/
15993 16005 15577 15585 15993 16005 15577 15585 16090 16093 15451 15454 15458 15451
h)
General Unit
Refrig circuits#11112222222222
25-50-
25-50-
25-50-
21-43-
25-50-
22-44-
25-50-
Capacity steps % 50-100 50-100 50-100 43-100
Refrig charge/circuit¹ (kg) 14.5 15.4 21.8 21.8 14.5 14.5 22.9 21.8 33.6 35.4 36.7 41.5 39.0 50.8
Oil charge /circuit¹ (l) 6.6 6.6 13.4 13.4 6.6 6.6 13.4 13.4 13.4 13.4 13.4 13.9 14.4 22.0
Min ambient - wide (°C) -18 -18 -18 -18 -18 -18 -18 -18 -18 -18 -18 -18 -18 -18
Min ambient - high (°C) n/a 0 0 0 0
75-100
75-100
75-100
71-100
75-100
72-100
75-100
23-45-
73-100
Pump Package
Avail head pressure² (kPa) 233.7 232.3 212.6 202.1 200.6 175.0 229.2 189.7 245.1 233.3 206.3 185.0 213.1 185.8
Power (HP) 5.0 5.0 5.0 5.0 5.0 5.0 7.6 7.6 10.2 10.2 10.2 10.2 15.2 15.2
Expansion tank
volume
(l) 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 22.7 22.7 22.7 22.7 22.7 22.7
4
Partial Heat Recovery
Water storage/circuit¹ (l) 0.07 0.09 0.09 0.11 0.07 0.09 0.09 0.11 0.12 0.16 0.16 0.16 0.21 0.21
Max flow (l/s) 2.5 2.5 2.5 2.5 5.0 5.0 5.0 5.0 8.0 8.0 8.0 8.0 8.0 8.0
Water connection (mm) 38.1 38.1 38.1 38.1 38.1 38.1 38.1 38.1 63.5 63.5 63.5 63.5 63.5 63.5
Buffer Tank
Buffer tank volume (l) 116 116 116 116 116 116 116 116 127 127 162 162 162 162
Notes:
1. Data shown for circuit one only. The second circuit always matches.
2. When facing the control panel, circuit 1 is on the right side of unit.
3. Pump available head pressure is based on: 6.7/12.2°C evaporator with water, .01761 m²°C/kW, 35°C ambient and 0 m elevation.
4. See Table 30, p. 63 for maximum loop volumes with pump package expansion tank.
CG-SVX17E-EN 13
Page 14
General Data
Table 3. General Data - 50 Hz - IP
Size 20 26 30 35 40 52 60 70 80 90 100 110 120 Compressor
Number#2222444444444
Tonnage/circuit¹ 10+10 13+13 15+15 15+20 10+10 13+13 15+15 15+20 20+20 20+25 25+25 25+30 30+30
Evaporator
Water storage (gal) 1.4 2.2 2.2 3.2 2.4 4.1 5.0 7.5 7.0 9.0 10.3 11.5 11.5
Min. flow(gpm)253236414862718397109123133142
Max. flow (gpm) 59 75 85 98 115 149 170 199 234 262 296 319 341
Water connection (in) 2 2.5 2.5 2.5 3 3 3 3 4 4 4 4 4
Condenser
Quantity of coils#1111222244444
Coil length (in) 91 91 127 127 91 91 127 127 121 121 144 144 144 Coil height (in) 68 68 68 68 68 68 68 68 42 42 42 42 42
Number of rows#2222222233333
Fins per foot (fpf) 192 192 192 192 192 192 192 192 192 192 192 192 192
Fan
Quantity#2233446666888
Diameter (in) 28.8 28.8 28.8 28.8 28.8 28.8 28.8 28.8 28.8 28.8 28.8 28.8 28.8
Airflow/fan (cfm) 7796 7783 7587 7590 7795 7801 7587 7590 7827 7829 7503 7505 7506
Power/motor (kW) 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8
Motor RPM (rpm) 700 700 700 700 700 700 700 700 700 700 700 700 700
Tip speed
General Unit
Refrig circuits#1111222222222
Capacity steps % 50-100 50-100 50-100 43-100
Refrig charge/circuit¹ (lbs) 34 34 48 48 32 32 48 48 74 74 82 86 84
Oil charge/circuit¹ (gal) 1.7 1.7 3.5 3.5 1.7 1.7 3.5 3.5 3.5 3.5 3.5 3.7 3.8
Min ambient - wide(°F)0000000000000
Min ambient - high (°F) n/a 32 32 32
Partial Heat Recovery
Water storage/circuit¹ (gal) 0.02 0.02 0.02 .02 0.02 0.02 0.02 0.02 0.03 0.03 0.03 0.04 0.04
Max flow (gpm) 39 39 39 39 78 78 78 78 127 127 127 127 127
Water connection (in) 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5 2.5
Notes:
1. Data shown for circuit one only. The second circuits always matches.
2. When facing the control panel, circuit 1 is on the right side of unit.
(ft/
5278 5278 5278 5278 5278 5278 5278 5278 5278 5278 5278 5278 5278
min)
25-50­75-100
25-50­75-100
25-50­75-100
21-43­71-100
25-50­75-100
22-44­72-100
25-50­75-100
23-45­73-100
25-50­75-100
14 CG-SVX17E-EN
Page 15
General Data
Table 4. General Data - 50 Hz - SI
Size 20 26 30 35 40 52 60 70 80 90 100 110 120 Compressor
Number#2222444444444
Tonnage/circuit¹ 10+10 13+13 15+15 15+20 10+10 13+13 15+15 15+20 20+20 20+25 25+25 25+30 30+30
Evaporator
Water storage (l) 5.3 8.3 8.3 12.1 9.1 15.5 18.9 28.4 26.5 34.1 39.0 43.5 43.5
Min. flow (l/s) 1.6 2.0 2.2 2.6 3.0 3.9 4.4 5.2 6.1 6.8 7.7 8.3 8.9
Max. flow (l/s) 3.7 4.8 5.4 6.2 7.3 9.4 10.8 12.6 14.8 16.5 18.7 20.2 21.6
Water connection (mm) 50.8 63.5 63.5 63.5 76.2 76.2 76.2 76.2 101.6 101.6 101.6 101.6 101.6
Condenser
Quantity of coils#1111222244444
Coil length (mm) 2311 2311 3226 3226 2311 2311 3226 3226 3073 3073 3658 3658 3658 Coil height (mm) 1727 1727 1727 1727 1727 1727 1727 1727 1067 1067 1067 1067 1067
Number of rows#2222222233333
Fins per foot (fpf) 192 192 192 192 192 192 192 192 192 192 192 192 192
Fan
Quantity#2233446666888
Diameter (mm) 732 732 732 732 732 732 732 732 732 732 732 732 732
Airflow/fan
Power/motor (kW) 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8
Motor RPM (rpm) 700 700 700 700 700 700 700 700 700 700 700 700 700
Tip speed (m/s) 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8
General Unit
Refrig circuits#1111222222222
Capacity steps % 50-100 50-100 50-100 43-100
Refrig charge/circuit¹ (kg) 15.4 15.4 21.8 21.8 14.5 14.5 21.8 21.8 33.6 33.6 37.2 39.0 38.1
Oil charge/circuit ¹ (l) 6.6 6.6 13.4 13.4 6.6 6.6 13.4 13.4 13.4 13.4 13.4 13.9 14.4 Min ambient - wide (°C) -18 -18 -18 -18 -18 -18 -18 -18 -18 -18 -18 -18 -18 Min ambient - high (°C) n/a 0 0 0
Partial Heat Recovery
Water storage/circuit¹ (l) 0.07 0.07 0.09 0.09 0.07 0.07 0.09 0.09 0.12 0.12 0.12 0.16 0.16
Max flow (l/s) 2.5 2.5 2.5 2.5 5.0 5.0 5.0 5.0 8.0 8.0 8.0 8.0 8.0
Water connection (mm) 38.1 38.1 38.1 38.1 38.1 38.1 38.1 38.1 63.5 63.5 63.5 63.5 63.5
Notes:
1. Data shown for circuit one only. The second circuit always matches.
2. When facing the control panel, circuit 1 is on the right side of unit.
(m³/
13245 13223 12890 12895 13244 13254 12890 12895 13298 13302 12748 12751 12753
h)
25-50­75-100
25-50­75-100
25-50­75-100
21-43­71-100
25-50­75-100
22-44­72-100
25-50­75-100
23-45­73-100
25-50­75-100
CG-SVX17E-EN 15
Page 16
Pre-Installation
Inspection Checklist
When the unit is delivered, verify that it is the correct unit
and that it is properly equipped. Compare the information which appears on the unit nameplate with the ordering and submittal information.
Inspect all exteriorcomponents for visibledamage. Report any apparent damage or material shortage to the carrier and make a “unit damage” notation on the carrier's delivery receipt. Specify the extent and type of damage found and notify the appropriateTrane Sales Office.
Do not proceedwith installation ofa damaged unitwithout sales office approval.
To protect against loss due to damage incurred in transit,
complete the following checklist upon receipt of the unit.
Inspect the individual pieces of the shipment before accepting the unit. Check for obvious damage to the unit or packing material.
Inspect the unit for concealed damage as soon as possible after delivery and before it is stored. Concealed damage must be reported within 15 days.
If concealed damage is discovered, stop unpacking the shipment. Do not remove damaged material from the receiving location.Take photos of the damage, if possible.The owner must provide reasonable evidence that the damage did not occur after delivery.
Notify the carrier's terminal of the damage immediately, by phone and by mail. Request an immediate, joint inspection of the damage with the carrier and the consignee.
Notify theTrane sales representative and arrange for repair. Do not repair the unit, however, until damage is inspected by the carrier's representative.
Unit Storage
If the chiller is to be stored in ambients of 32°F or less, evaporator should be blown out to remove any liquid and refrigerant isolation valves should be closed.
If the chiller is to be stored for more than one month prior to installation, observe the following precautions:
Do not remove the protective coverings from the electrical panel.
Store the chiller in a dry, vibration-free, secure area.
Units charged with refrigerant should not be stored where temperatures exceed 155°F.
At least every three months, attach a gauge and manually check the pressure in the refrigerant circuit. If the refrigerant pressure is below 200 psig at 70 F (or 145 psig at 50 F), call a qualified service organization and the appropriateTrane sales office.
Note: Pressure will be approximately 20 psig if shipped
with the optional nitrogen charge.
Installation Requirements
A list of the contractor responsibilities typically associated with the unit installation process is provided.
Type
Foundation
Rigging
Isolation
Electrical
Water piping
Insulation
Water Piping Connection Componen ts
Other Materials
Trane
Supplied
Trane
Installed
• Circuit breakers (optional)
•Unit mounted starter
• Flow switch
•Water strainer
• Insulation
•High humidity insulation (optional)
•Grooved pipe
• R-410A refrigerant (1 lb. maximum per machine as needed)
• Dry nitrogen (20 psig maximum per machine as needed)
Trane
Supplied
Field
Installed
• Elastomeric isolators (optional)
Field Supplied Field Installed
• Meet foundation requirements
• Safety chains
• Clevis connectors
• Lifting beam
• Elastomeric isolators (optional)
• Circuit breakers (optional)
• Electrical connections to unit mounted starter
• Wiring sizes per submittal and NEC
• Terminal lugs
• Ground connection(s)
• BAS wiring (optional)
• Control voltage wiring
• Chilled water pump contactor and wiring including interlock
• Option relays and wiring
• Taps for thermometers and gauges
• Thermometers
• Water flow pressure gauges
• Isolation and balancing valves in water piping
• Vents and drain
• Pressure relief valves
• Insulation
16 CG-SVX17E-EN
Page 17
Unit Dimensions/Weights
Dimensions
Figure 8. CGAM 20 and 26 ton - no options
Fan
Control
panel
Wire
connection
50.4 in
(1279 mm)
84.7 in
(2151 mm)
Compressor
21.2 in
(535 mm)
92.7 in
113.8 in
(2354 mm)
(2890 mm)
Figure 9. CGAM 20 and 26 ton - service clearances and mounting locations
Door
swing
Service and Airflow1Clearance
47.2 in (1200 mm)
31.5 in
(800 mm)
23.6 in
(600 mm)
39.4 in
(1000 mm)
Distance from edge to
middle of mounting hole
1.5 in (38 mm)
47.2 in
(1199 mm)
Control
panel side
Mounting Locations
21in
Water connections are 1.7 in (44 mm) from the end.
Hole dia
(533 mm)
101.2 in (2570 mm)
Chilled
water outlet
0.56 in (15 mm)
16.9 in
(429 mm)
Chilled water
inlet
20.3 in
(515 mm)
(246 mm)
9.7 in
Chilled water
connection side
1
More clearance may be needed for airflow
depending on the installation.
CG-SVX17E-EN 17
Total of four mounting locations.
Page 18
Unit Dimensions/Weights
Figure 10. CGAM 30 and 35 ton - no options
Control
panel
84.7 in
(2151 mm)
Fan
Chilled water
inlet
Wire
connection
50.4 in
(1279 mm)
The number of fans shown does not represent
the number of fans installed.
Compressor
(541 mm)21.3 in
128.4 in (3263 mm)
149.8 in
(3804 mm)
Figure 11. CGAM 30 and 35 ton - service clearances and mounting locations
Service and Airflow1Clearance
Distance from edge to middle of mounting hole
1.5 in (38 mm)
47.2 in
(1199 mm)
Control
panel side
21.9 in
Door
swing
The number of fans shown does not represent
the number of fans installed.
47.2 in (1200 mm)
31.5 in
(800 mm)
23.6 in
(600 mm)
39.4 in
(1000 mm)
Chilled water
outlet
Water connections are 1.6 in (40 mm) from unit end.
16.9 in
(429 mm)
Mounting Locations
Hole dia
(556 mm)
132.2 in (3358 mm)
0.56 in (15 mm)
(516 mm)
20.3 in
9.7 in
(246 mm)
Chilled water
connection side
1
More clearance may be needed for airflow
depending on the installation.
18 CG-SVX17E-EN
Total of four mounting locations.
Page 19
Unit Dimensions/Weights
Figure 12. CGAM 40 and 52 ton- no options
Control panel
88.4 in
(2245 mm)
Wire
connection
84.8 in
(2155 mm)
23.8 in
Fan Compressor
(603 mm)
89.9 in(2282 mm)
113.8 in (2890 mm)
Note: When facing the control panel, circuit 1 is on the right side of unit.
Figure 13. CGAM 40 and 52 ton- service clearances and mounting locations
Service and Airflow1Clearance
Distance from edge to middle of mounting hole
1.5 in (38 mm)
14.4 in
(367 mm)
Water connections are even with unit end.
Mounting Locations
0.56 in (15 mm)
Hole dia
Chilled water
inlet
Chilled water
outlet
25.8 in (656 mm)
7. 9 i n (200 mm)
Door
swing
47.2 in
(1200 mm)
1
More clearance may be needed for airflow
depending on the installation.
31.5 in
(800 mm)
39.4 in
39.4 in
(1000 mm)
(1000 mm)
85.4 in
(2164 mm)
Control
panel side
(493 mm)
19.4 in
94 in (2388 mm)
Total of four mounting locations.
Chilled water
connection side
CG-SVX17E-EN 19
Page 20
Unit Dimensions/Weights
Figure 14. CGAM 60 and 70 ton - no options
Control panel
88.4 in
(2245 mm)
Wire connection
84.8 in
(2155 mm)
23.8 in
The number of fans shown does not represent
the number of fans installed.
Fan
Compressor
(603 mm)
125.8 in (3196 mm)
149.8 in (3804 mm)
Note: When facing the control panel, circuit 1 is on the right side of unit.
Figure 15. CGAM 60 and 70 ton - service clearances and mounting locations
Service and Airflow1Clearance
The number of fans shown does not represent
the number of fans installed.
Distance from edge to middle of mounting hole
1.5 in (38 mm)
14.4 in
(367 mm)
Water connections are even with unit end.
Mounting Locations
0.56 in (15 mm)
Hole dia
Chilled water
inlet
Chilled water
outlet
31.1 in (790 mm)
7. 9 i n
(199 mm)
Door
swing
(1200 mm)
47.2 in
1
More clearance may be needed for airflow
depending on the installation.
39.4 in
39.4 in(1000 mm)
31.5 in
(800 mm)
(1000 mm)
85.4 in
(2169 mm)
Control
panel side
(493 mm)
19.4 in
79.7 in (2024 mm)
129.8 in (3297 mm)
Total of six mounting locations.
Chilled water connection side
20 CG-SVX17E-EN
Page 21
Unit Dimensions/Weights
Figure 16. CGAM 80 and 90 ton - no options
CompressorFan
Control
panel
Wire onnection
88.9 in
(2257 mm)
Note: When facing the control panel, circuit 1 is on the right side of unit.
92.6 in
(2352 mm)
29.6 in
(751 mm)
89.2 in (2265 mm)
143.1 in (3634 mm)
Chilled water inlet
Chilled water outlet
(790 mm)
31.1 in
(200 mm)
7. 9 i n
11.5 in
(292 mm)
Water connections are 5.5 in (139 mm) from unit end.
Figure 17. CGAM 80 and 90 ton - service clearances and mounting locations
Service and Airflow1Clearance
Distance from edge to
middle of mounting hole
Door
swing
47.2 in
(1200 mm)
1
More clearance may be need for airflow
depending on the installation.
(1000 mm)
39.4 in
(1000 mm)
39.4 in
39.4 in (1000 mm)
85.9 in
(2182 mm)
Control
panel side
1.5 in (38 mm)
Mounting Locations
0.56 in (15 mm)
Hole dia
30.2 in
(767 mm)
83.7 in (2126 mm)
123.9 in (3147 mm)
Total of six mounting location.
Chilled water
connection side
CG-SVX17E-EN 21
Page 22
Unit Dimensions/Weights
Figure 18. CGAM 100, 110 and 120 ton- no options
CompressorFan
Control
panel
Wire
connection
88.9 in
(2257 mm)
The number of fans shown does not represent the
number of fans installed.
Note: When facing the control panel, circuit 1 is on the right side of unit.
92.5 in
(2349 mm)
29.6 in
(751 mm)
111.7 in (2837 mm)
165.9 in (4214 mm)
Chilled water inlet
Chilled water outlet
31.1 in
(790 mm)
11.5 in
(292 mm)
Water connections are 5.4 in (139 mm)
from unit end.
7. 9 i n
(199 mm)
Figure 19. CGAM 100, 110 and 120 ton- service clearances and mounting locations
Mounting Locations
Distance from edge to
middle of mounting hole
1.5 in (38 mm)
30.2 in
89.2 in (2266 mm)
Total of six mounting locations.
Door
swing
Service and Airflow1Clearance
The number of fans shown does not represent the
number of fans installed.
47.2 in
(1200 mm)
1
More clearance may be needed for airflow
depending on the installation.
(1000 mm)
39.4 in
(1000 mm)
39.4 in
39.4 in (1000 mm)
85.9 in
(2181 mm)
Control
panel side
0.56 in (15 mm)
Hole dia
(767 mm)
146.9 in (3731 mm)
Chilled water
connection side
22 CG-SVX17E-EN
Page 23
Unit Dimensions/Weights
Figure 20. CGAM 130 ton
Control Panel
Wire Connection
88.9 in
(2257 mm)
92.5 in
(2349 mm)
29.6 in
Compressor
(751 mm)
149.8 in (3804 mm)
201.9 in (5128 mm)
Fan
Note: When facing the control panel, circuit 1 is on the right side of unit.
Figure 21. CGAM 130 ton- service clearances and mounting locations
Service and Airflow1Clearance
The number of fans shown does not represent the
number of fans installed.
(1000 mm)
39.4 in
Water connections are 25 in (635 mm) from unit end.
Mounting Locations
Distance from edge to
middle of mounting hole
1.5 in (38 mm)
Hole dia
11.5 in (292 mm)
0.56 in (15 mm)
Chilled water
inlet
Chilled water
outlet
31.1 in
(790 mm)
7. 9 i n
(199 mm)
Door
Swing
47.2 in
(1200 mm)
1
More clearance may be needed for airflow
depending on the installation.
CG-SVX17E-EN 23
(1000 mm)
39.4 in
39.4 in (1000 mm)
85.2in
(2174 mm)
Control
panel side
30.2 in
(767 mm)
69.5 in (1765 mm)
130.6 in (3317 mm)
163 in (4140 mm)
Total of eight mounting locations.
Chilled water
connection side
Page 24
Unit Dimensions/Weights
Unit Dimensions - Optional Pump Package, BufferTank, Partial Heat Recovery
Figure 22. Sizes 20 and 26 ton — pump package, buffer tank, partial heat recovery
Fan
Control Panel
Wire
Connection
Pump Package
VFD
50.6 in
(1285 mm)
84.7 in
(2151 mm)
Compressor
Lifting Locations
20.8 in (529 mm)
92.4 in (2348 mm)
114.0 in (2895 mm)
134 in (3404 mm)
Figure 23. Sizes 30 and 35 ton — pump package, buffer tank, partial heat recovery
Fan
Control Panel
84.7 in (2151 mm)
Wire
Connection
Pump Package
VFD
50.6 in
(1285 mm)
Compressor
Lifting Locations
21.0 in (534 mm)
128.2 in (3256 mm)
150.0 in (3809 mm)
170.0 in (4318 mm)
Pump Package
BufferTank
Length w/ PP or PHR
Length w/ buffer tank
Pump Package
BufferTank
24 CG-SVX17E-EN
Page 25
Unit Dimensions/Weights
Figure 24. Sizes 40 and 52 ton — pump package, buffer tank, partial heat recovery
Fan
23.7 in (602 mm)
89.9 in (2282 mm)
114.4 in (2906 mm)
Compressor
134.7 in (3421 mm)
Pump Package
VFD
Control Panel
88.6 in (2250 mm)
Wire Connection
84.8 in (2155 mm)
Lifting
Locations
Figure 25. Sizes 60 and 70 ton — pump package, buffer tank, partial heat recovery
Control Panel
Wire Connection
Fan
Compressor
Pump Package
Pump Package
BufferTank
Length w/ PP or PHR
Length w/ buffer tank
BufferTank
Pump Package
VFD
88.6 in (2250 mm)
84.8 in (2155 mm)
Lifting Locations
23.7 in (602 mm)
125.8 in (3196 mm)
150.4 in (3820 mm)
170.7 in (4336 mm)
CG-SVX17E-EN 25
Page 26
Unit Dimensions/Weights
Figure 26. Sizes 80 and 90 ton — pump package, buffer tank, partial heat recovery
Control
Panel
Wire
Connection
89 in (2261 mm)
92 in (2337 mm)
Locations
Lifting
Fan
29.6 in (752 mm)
89.2 in (2265 mm)
Compressors
144 in (3658 mm)
BufferTank
Figure 27. Sizes 100, 110 and 120 ton — pump package, buffer tank, partial heat recovery
Fan
Compressors
BufferTank
Pump Package VFD
Pump Package
Length w/ buffer tank
Length w/ PP or PHR156 in (3962 mm)
Pump Package VFD
Control
Panel
Wire
Connection
89 in (2261 mm)
92 in (2337 mm)
Locations
Lifting
29.6 in (752 mm)
111.7 in (2837 mm)
167.0 in (4242 mm)
Pump Package
Length w/ buffer tank
Length w/ PP or PHR179.0 in (4547 mm)
26 CG-SVX17E-EN
Page 27
Unit Dimensions/Weights
Figure 28. Size 130 ton — pump package, buffer tank, partial heat recovery
Fan
Compressors
Control Panel
92 in (2337 mm)
Wire
Connection
BufferTank Pump Package
Pump Package VFD
89 in (2261 mm)
Lifting
Locations
29.6 in (752 mm)
149.8 in (3804 mm)
203.0 in (5156 mm)
215.0 in (5461 mm)
Length w/ buffer tank
Length w/ PP or PHR
CG-SVX17E-EN 27
Page 28
Unit Dimensions/Weights
Pump Package, Partial Heat Recover and BufferTank - Water Connections
Figure 29. CGAM 20 and 26 ton - pump package, buffer tank, partial heat recovery unit water connections
Pump Package
Chilled water inlet
Water connections are recessed
1.3 in (33 mm) from unit end.
12.5 in (317 mm)
39.8 in
(1011 mm)
Chilled water outlet
12.8 in (325 mm)
9.7 in
(246 mm)
Chilled
water
inlet
22.4 in
(569 mm)
BufferTank
Chilled water outlet
22 in
(559 mm)
20.9 in
(531mm)
29.8 in
(757 mm)
Water connections are recessed
from unit end. Outlet is 14.8 in (377 mm) and inlet is 0.3 in (7.8 mm)
Partial Heat Recovery
Heating outlet
Partial heat recovery connections are even with unit edge.
The chilled water inlet and outlet connections are the same
as the standard unit unless pump package or buffer tank are ordered.
Heating inlet
67.4 in (1712 mm)
Figure 30. CGAM 30 and 35 ton - pump package, buffer tank, partial heat recovery unit water connections
Pump Package
BufferTank
Partial Heat Recovery
15.2 in
(385 mm)
6.9 in
(176mm)
Chilled water inlet
Water connections are recessed
1.3 in (33 mm) from unit end.
12.3 in (313 mm)
39.9 in
(1012 mm)
Chilled water outlet
12.9 in (327 mm)
9.7 in
(246 mm)
Chilled water
inlet
22.2 in
(564 mm)
(531mm)
29.8 in
(757 mm)
Water connections are recessed
from unit end. Outlet is 14.8 in (377 mm) and inlet is 0.3 in (7.8 mm)
20.9 in
Chilled water outlet
22 in
(559 mm)
15.2 in
(385 mm)
(182mm)
Heating outlet
Partial heat recovery connections are even with unit edge.
The chilled water inlet and outlet connections are the same
as the standard unit unless pump package or buffer tank are ordered.
Heating inlet
67.4 in (1712 mm)
7. 2 i n
28 CG-SVX17E-EN
Page 29
Unit Dimensions/Weights
Figure 31. CGAM 40 and 52 ton- pump package, buffer tank, partial heat recovery unit water connections
Pump Package
9.2 in
(234mm)
66.8 in (1696 mm)
Water outlet connection is even with unit end,
inlet is 6.1 in (154 mm) from unit end.
(499mm)
18.7in (474 mm)
Chilled water inlet
Chilled water
outlet
19.7in
19.7in (500mm)
Water inlet connect is even with unit end, outlet is recessed 14.8 in (376 mm) from unit end.
BufferTank
(474mm) 18.7in
70.4 in (1788 mm)
Partial Heat Recovery
Heating outlet
Chilled
water
inlet
Chilled water outlet
19.7in (500mm)
44.2in (1122mm)
Partial heat recovery connections are even with unit end.
The chilled water connections are the same as the standard
unit unless pump package or buffer tank are ordered.
Figure 32. CGAM 60 and 70 ton- pump package, buffer tank, partial heat recovery unit water connections
Pump Package
BufferTank
Partial Heat Recovery
Heating outlet
Heating inlet
(1392mm)
45.4in
(1153mm)
Heating inlet
54.8in
9.2 in
(234mm)
66.8 in (1696 mm)
Water outlet connection is even with unit end,
inlet is 6.1 in (154 mm) from unit end.
(499mm)
18.7in (474 mm)
Chilled water inlet
Chilled water
outlet
19.7in
19.7in (500mm)
(474mm) 18.7in
70.4 in (1788 mm)
Water inlet connect is even with unit end, outlet is recessed 14.8 in (376 mm) from unit end.
Chilled
water
inlet
Chilled water outlet
19.7in (500mm)
44.2in (1122mm)
Partial heat recovery connections are even with unit end.
The chilled water connections are the same as the standard
unit unless pump package or buffer tank are ordered.
55.2in
(1402mm)
45.6in
(1158mm)
CG-SVX17E-EN 29
Page 30
Unit Dimensions/Weights
Figure 33. CGAM 80 and 120 ton- pump package, buffer tank, partial heat recovery unit water connections
Pump Package
(with or without buffer tanks)
Chilled water inlet
Partial Heat Recovery
1.8 in (46 mm) Heating outlet
Heating inlet
28.9 in (733 mm)
7.9in(199mm)
Chilled water outlet
Water connections are 5.9 in (151 mm) from unit end.
11.5 in (292 mm)
22.6 in (575 mm)
Water connections are .7 in (18 mm) from unit end.
Figure 34. CGAM 130 ton- pump package unit water connections
Pump Package
(with or without buffer tanks)
Chilled water inlet
28.9 in (734 mm)
7.9in (200 mm)
Partial Heat Recovery
49.6 in (1259mm)
40.4 in (1025mm)
1.8 in (46 mm) Heating outlet
Heating inlet
49.6 in (1259mm)
40.4 in (1025mm)
Chilled water outlet
Water outlet connect is 25 in (635 mm) and
inlet is 6.3 in (159 mm) from unit end.
11.5 in (292 mm)
22.6 in (575 mm)
30 CG-SVX17E-EN
Water connections are .7 in (18 mm) from unit end.
Page 31
Unit Dimensions/Weights
Weights
Table 5. Weights - 60 Hz
Base Unit
Without Pump
Tons
lb kg lb kg lb kg lb kg lb kg lb kg lb kg lb kg lb kg
2185 991 2207 1002 2726 1236 2814 1277 3253 1475 3964 1799 39 18 24 11 258 117
20
2249 1020 2278 1034 2790 1265 2891 1311 3317 1504 4035 1830 39 8 31 14 258 117
26
2846 1291 2879 1306 3388 1537 3496 1586 3915 1776 4636 2103 47 21 36 16 360 163
30
2878 1305 2919 1325 3420 1551 3545 1608 3947 1790 4676 2121 47 21 44 20 360 163
35
3666 1663 3696 1677 4285 1944 4382 1988 4876 2212 5524 2506 94 43 34 15 515 234
40
3761 1706 3805 1726 4379 1986 4505 2044 4970 2254 5633 2555 94 43 49 22 515 234
52
4978 2258 5032 2283 5814 2637 5984 2715 6405 2905 7102 3222 111 50 59 27 719 326
60
5045 2289 5119 2323 5881 2668 6092 2764 6472 2936 7190 3262 111 50 80 36 719 326
70
5607 2543 5691 2582 6486 2942 6788 3080 7077 3210 7969 3615 170 77 90 41 1270 576
80
5859 2658 5959 2704 6738 3056 7073 3209 7329 3324 8237 3737 170 77 109 49 1270 576
90
6646 3015 6757 3066 7549 3424 7907 3587 8265 3749 9419 4273 178 81 120 54 1511 686
100
6724 3050 6844 3105 7627 3460 8003 3631 8343 3785 9506 4313 178 81 129 59 1511 686
110
6762 3067 6882 3122 8018 3637 8393 3808 8734 3962 9896 4490 178 81 131 60 1511 686
120
7753 3517 7898 3583 9006 4085 9427 4277 9722 4410 10905 4947 178 81 156 71 1889 857
130
Notes:
1. Weights based on aluminum fins, refrigerant charge, isolators, circuit breakers and louvers.
2. Base unit weights are shown above on the left side for units without a pump package, units with a pump package and units with both pump package
buffer tank options. The partial heat recovery and copper weights are in addition to the base unit weights.
3. All weights ±3%.
Base Unit
With Pump
With Pump and Buffer Tank
Base Unit
Partial Heat
Recovery - add
Copper -
addShipping Operating Shipping Operating Shipping Operating Shipping Operating
Table 6. Weights - 50 Hz
Base Unit Partial Heat Recovery - add
Tons
lb kg lb kg lb kg lb kg lb kg 20 26 30 35 40 52 60 70 80 90
100 110 120
Notes:
1. Weights based on aluminum fins, refrigerant charge, isolators, circuit breakers and louvers.
2. The partial heat recovery and copper weights are in addition to the base unit weights.
3. All weights ±3%.
2187 992 2209 1002 39 18 24 11 258 117 2249 1020 2278 1034 39 18 31 14 258 117 2845 1291 2879 1306 47 21 36 16 360 163 2877 1305 2919 1325 47 21 44 20 360 163 3665 1663 3696 1677 94 43 34 15 515 234 3760 1706 3805 1726 94 43 48 22 515 234 4977 2258 5032 2283 111 50 59 27 719 326 5044 2289 5119 2323 111 50 79 36 719 326 5606 2543 5691 2582 170 77 90 41 1270 576 5857 2657 5958 2703 170 77 107 49 1270 576 6628 3007 6741 3059 178 81 118 54 1511 686 6711 3045 6833 3100 178 81 129 59 1511 686 6756 3065 6878 3121 178 81 129 59 1511 686
Copper - addShipping Operating Shipping Operating
CG-SVX17E-EN 31
Page 32
Installation - Mechanical
Location Requirements
Sound Considerations
Refer toTrane Engineering Bulletin Chiller Sound Ratings and Installation Guide CG-PRB010-EN for
sound consideration applications.
Locate the unit away from sound-sensitive areas.
Install the optional elastomeric isolators under the unit. Refer to “Unit Isolation.”
Chilled water piping should not besupported by chiller frame.
Install rubber vibration isolators in all water piping.
Seal all wall penetrations.
Note: Consult an acoustical engineer for critical
applications.
Foundation
Provide rigid, non-warping mounting pads or a concrete foundation of sufficient strength and mass to support the applicable operating weight (i.e., including completed piping, and full operating charges of refrigerant, oil and water). Refer to the chapter on “Unit Dimensions/Weights” for unit operating weights. Once in place, the unit must be level within 1/4” (6.4 mm) over its length and width.The
Trane Company is not responsible for equipment
problems resulting from an improperly designed or constructed foundation.
Clearances
Provide enough space around the unit to allow the installation and maintenance personnel unrestricted access to all servicepoints. Refer to submittal drawings for the unit dimensions, to provide sufficient clearance for the opening of control panel doors and unit service. Refer to the chapter on “Unit Dimensions/Weights” for minimum clearances. In all cases, local codes which require additional clearances will take precedence over these recommendations.
Rigging
Refer to Unit Dimensions/Weights section for typical unit lifting weights. Refer to the rigging label attached to the unit for further details.
Lifting Procedure
WARNING
Heavy Objects!
Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted. Each of the cables (chains or slings), hooks, and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift. Other lifting arrangements could cause equipment or property damage. Failure to follow instructions above or properly lift unit could result in unit dropping and possibly crushing operator/ technician which could result in death or serious injury.
WARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper
center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level. Failure to properly lift unit could result in unit dropping and possibly crushing operator/technician which could result in death or serious injury and possible equipment or property-only damage.
Lifting using either a single spreader bar or an H-type spreader is acceptable. Attach chains or cables to lifting beam. Lifting beam crossbars MUST be positioned so lifting cables do not contact the sides of the unit.
Important: The center of gravity (CG) is never at the
midpoint of the base rail lifting strap holes.
A level unit lift is required for a safe lift and
to prevent unit damage.
Lifting a unit with equal length straps will NOT produce a level unit during the lift because the CG will not be at the midpoint between the base lifting holes.The following adjustments must be made to produce a level lift:
Single spreader bar lifting method
If the unit CG is closer to the control panel, the
straps on the control panel side of the spreader bar must be adjusted to be shorter than those on the opposite side of the spreader bar, allowing the spreader bar to move toward the control panel and over the unit CG. Several adjustments of the strap length may be required to produce a level unit during lift.
H-type spreader bar lifting method
If the straps from the H bar to the unit base are the
same length, the crane lifting point on the center web of theH bar must beadjusted to producea level unit lift. See Figure 35, p. 33 for illustration.
32 CG-SVX17E-EN
Page 33
Installation - Mechanical
Figure 35. H-type spreader bar adjustment for level unit
lift
Crane lift point must move to the unit CG to produce a level unit lift
Crane lift point
“H” type spreader bar
Lifting Straps to unit base
Figure 36. CGAM slant 20-35 ton rigging
Figure 37. CGAM V 40-70 Ton Rigging
X
Figure 38. CGAM W 80-130 Ton Rigging
Z
Y
Z
Y
X
CG-SVX17E-EN 33
Page 34
Installation - Mechanical
Table 7. CGAM center of gravity (in) - 60 Hz
Aluminum fins Copper fins
Unit
(tons)
20 50 24 38 56 23 34 67 23 35 51 24 39 57 23 35 67 23 35 26 49 24 38 56 23 33 67 23 34 51 24 39 57 23 34 67 23 35 30 63 23 38 71 23 34 83 23 35 65 23 39 72 23 35 83 23 36 35 63 23 38 72 22 34 84 23 35 65 23 39 73 23 35 83 23 36 40 48 45 37 53 42 34 62 43 35 50 45 38 53 42 35 61 43 36 52 49 45 37 53 43 34 61 43 34 50 45 38 53 43 35 61 43 35 60 61 45 38 67 43 34 76 43 35 63 45 38 68 43 35 76 43 36 70 62 46 37 68 43 34 76 43 35 63 45 38 68 43 35 76 43 35 80 59 47 38 68 46 37 68 46 35 62 46 42 69 46 41 68 46 39
90 59 47 37 68 46 36 67 46 34 61 46 41 68 46 40 68 46 38 100 72 47 38 82 46 37 81 46 35 75 46 42 82 46 41 81 46 39 110 72 47 38 81 46 37 80 46 35 74 46 42 81 46 41 81 46 39 120 72 47 38 83 46 36 82 46 35 74 46 42 83 46 40 83 46 38 130 86 47 39 100 46 38 100 46 36 89 46 44 100 46 42 101 46 40
20 50 24 38 57 23 33 67 23 34 52 24 39 57 23 35 67 24 35
26 50 24 37 56 23 33 67 23 34 51 24 38 57 23 34 67 23 35
30 63 23 37 71 23 34 83 23 34 65 23 38 72 23 35 83 23 35
35 63 23 37 71 23 34 83 23 34 65 23 38 73 23 35 83 23 35
40 50 45 37 54 42 34 62 43 35 51 45 38 54 43 35 62 43 36
52 50 45 37 54 43 34 62 43 35 51 45 38 54 43 35 62 43 35
60 63 45 38 69 43 35 77 43 35 64 45 38 69 43 36 77 43 36
70 63 46 38 69 43 34 77 43 35 65 45 38 70 43 35 77 43 36
80 58 47 38 67 46 37 67 46 35 61 46 42 68 46 41 67 46 39
90 58 47 37 67 46 36 66 46 35 60 46 41 67 46 40 67 46 39 100 71 47 38 80 46 37 79 46 35 73 46 42 81 46 41 80 46 39 110 71 47 38 80 46 37 79 46 35 73 46 42 80 46 41 80 46 39 120 70 47 38 82 46 36 81 46 35 73 46 42 82 46 40 82 46 39 130 84 46 39 98 46 38 99 46 36 88 46 44 99 46 42 100 46 40
Base Unit
XYZX YZ X YZXYZXY ZXY Z
Package
With Pump
With Pump Pkg,
Buffer Tank Base Unit
Units without partial heat recovery
Units with partial heat recovery
With Pump
Package
With Pump Pkg,
Buffer Tank
34 CG-SVX17E-EN
Page 35
Installation - Mechanical
Table 8. CGAM center of gravity (in) - 50 Hz
Aluminum fins Copper fins
Unit
(tons)
20 49 24 38 54 23 35 66 23 36 51 24 39 55 23 36 66 24 36 26 49 24 38 54 23 34 66 23 35 51 24 39 55 23 36 65 23 36 30 63 23 38 69 23 35 82 23 36 65 23 39 70 23 36 82 23 37 35 63 23 38 69 23 35 82 23 35 65 23 39 71 23 36 82 23 36 40 48 45 37 52 43 35 61 43 35 50 45 38 52 43 36 60 43 36 52 49 45 37 52 43 34 61 43 35 50 45 38 53 43 35 60 43 36 60 61 45 38 67 43 34 76 43 35 63 45 38 68 43 35 75 43 36 70 62 46 37 67 43 34 76 43 35 63 45 38 68 43 35 76 43 36 80 59 47 38 68 46 37 67 46 35 62 46 42 69 46 41 68 46 39
90 59 47 37 67 46 36 67 46 35 61 46 41 68 46 40 67 46 38 100 72 47 38 81 46 37 80 46 35 74 46 42 81 46 41 80 46 39 110 72 47 38 81 46 37 80 46 35 74 46 42 81 46 41 80 46 39 120 72 47 38 82 46 36 81 46 35 74 46 42 82 46 40 81 46 39
20 49 24 38 54 23 34 66 24 35 51 24 39 55 24 36 66 24 36
26 50 24 37 54 23 34 66 24 35 51 24 38 55 23 35 65 24 36
30 63 23 37 68 23 35 81 23 35 65 23 38 70 23 36 81 23 36
35 63 23 37 69 23 34 82 23 35 65 23 38 71 23 35 82 23 36
40 50 45 37 53 43 35 62 43 35 51 45 38 53 43 36 61 43 36
52 50 45 37 53 43 35 62 43 35 51 45 38 54 43 35 61 43 36
60 63 45 38 68 43 35 77 43 35 64 45 38 69 43 36 76 43 36
70 63 46 38 69 43 35 77 43 35 65 45 38 69 43 35 77 43 36
80 58 47 38 67 46 37 66 46 35 61 46 42 68 46 41 67 46 39
90 58 47 37 66 46 36 66 46 35 60 46 41 67 46 40 67 46 39 100 70 47 38 79 46 37 79 46 36 73 46 42 80 46 41 79 46 39 110 70 47 38 79 46 37 79 46 35 73 46 42 80 46 41 79 46 39 120 70 47 38 80 46 37 80 46 35 73 46 42 81 46 40 80 46 39
Base Unit
XYZXYZXYZXYZXYZXYZ
Package
With Pump
With Pump Pkg,
Buffer Tank Base Unit
Units without partial heat recovery
Units with partial heat recovery
With Pump
Package
With Pump Pkg,
Buffer Tank
CG-SVX17E-EN 35
Page 36
Installation - Mechanical
Unit Isolation and Leveling
Mounting
Construct an isolated concrete pad for the unit or provide concrete footings at each of the four unit mounting points. Mount the unit directly to the concrete pads or footings.
Level the unit using the base rail as a reference.The unit must be level within 1/4” over the entire length. Use shims as necessary to level the unit.
Elastomeric Isolator Installation (optional)
Install the optional neoprene isolators at each mounting location. Isolators are identified by part number and color.
1. Secure the isolators to themounting surface, using the mounting slots in the isolator base plate, as shown in
Figure 39. Do not fully tighten the isolator mounting
bolts at this time.
2. Align the mounting holes in the base of the unit, with the threaded positioning pins on the top of isolators.
3. Lower the unit on to the isolators and secure the isolator to the unit with a nut. Maximum isolator deflection should be approximately 1/4”.
4. Level the unit carefully. Refer to “Leveling”. Fully tighten the isolator mounting bolts.
Figure 39. CGAM Elastomeric isolator
W
C
L
Mounting molded in Neoprene
H
H
A
B NC TAP
DDia2Holes
Mounting molded in Neoprene
E
«B»Dia
RP/RDP
«M»
L C
A
1/2-13NC-2B
D
H
E
1/2-13
W
H
Table 9. CGAM elastomeric rated isolator
Max Load
Ext
(lbs) Color Deflection (in) Type
57 250 Black 58 525 Red 59 750 Green 60 1100 Gray 61 1500 Brown 62 2250 Red 63 3000 Green 64 4000 Gray
0.50 RDP3-WR
0.50 RDP4-WR
Ext A B C D E H L M W
57 58
2.5 .5 4.12 .56 .25 2.88 5.5 1.13 3.38
59 60 61 62
3.0 .5 5.0 .56 .38 2.75 6.25
63 64
1.60
±.25
4.63
Seismically Rated Isolator Installation
Seismically rated isolators are required for OSHPD seismically rated units, and optional for IBC seismically rated units.
Isolators are identified by part number and color. See
Table 10, p. 36. For dimensions, see Figure 40 and Figure 41, p. 37. Install the optional seismically rated
isolators at each mounting location .
Table 10. CGAM seismically rated isolator
Rated Load
Model
MSSH-1E-530N 530 1.17 453 Black/Dk Blue MSSH-1E-825N 825 1.07 769 Red/ Dk Blue MSSH-1E-1000 1000 1.00 1000 Tan M2SS-1E-800 800 1.32 606 Black M2SS-1E-1060N 1060 1.17 906 Black/Dk Blue M2SS-1E-1300 1300 1.05 1240 Red M2SS-1E-1650N 1650 1.07 1538 Red/Dk Blue M2SS-1E-2000 2000 1.00 2000 Tan M2SS-1E-2400N 2400 1.04 2300 Tan/Dk Blue
(lbs)
Rated Deflection (in)
Spring Rate (lbs/in) Color Code
36 CG-SVX17E-EN
Page 37
Installation - Mechanical
R
Figure 40. MSSH seismically rated isolator
2 1/4
6 1/4
27/8
7/8
8
FREE &
OPERATING
HEIGHT
11/2
STEEL SHIM (REMOVE AFTER SPRING ADJUSTMENT)
53/4
8
5/8 EQUIPMENT CLAMP DOWN NUT
71/4
10 1/4
CUSTOMER EQUIPMENT
(1/2)
11/8
CUSTOMER EQUIPMENT
5/8 ADJUS TING NUT
PPING SPACER
SHI REMOVAL STRAP (NOT SHOWN IN OTHER VIEW FOR CLARIT
Y)
1/2 LIMIT STOP (NOT SHOWN IN TOP VIEW FOR CLARITY)
13/16 DIA HOLEFOR ATTACHMENT TO CONCRETE (4 TYP)
(BASE PLATE) 3/4 DIA HOLEFOR ATTACHMENT TO STEEL (4 TYP) (VIEW CUT AWAY FOR CLA
ELASTOMERIC SNUBBER
3/8 GAP
1/4 - 3/8
PVC BUSHING
TOP COMPRESSION CUP
ELASTOMERIC CUP
Figure 41. M2SS seismically rated isolator
11/2 11 1/4
21/4
61/4
27/8
7/8
3/8 GAP
71/4
FREE &
OPERATING
HEIGHT
71/8
5/8 ADJUSTING NUT (2 TYP)
43/4
14 1/4
8
5/8 EQUIPMENT CLAMP DOWN NUT
CUSTOMER
EQUIPMENT
C
USTOMER
EQUIPMENT
(1/2)
1/2 LIMIT STO P
(NOTSHOWN IN TOP VIEW
FOR CLARITY)
STEEL SHIM (REMOVE AFTER SPRING ADJUSTMENT)
8)
(3/
13/16 DIA HOLE FO R ATTACHMENT TO CONCRETE (4 TYP)
2
(BASE PLATE) 3/4 DIAHOLE FOR ATTACHMENT TO
EL (4 TYP)
STE (VIEW CUT AWAY FOR CLARITY
ELASTOMERIC SNUBBER
1/4 -3/8
PVC BUSHING TOP COMPRESSION CUP (2 TYP)
ELASTOMERIC CUP
8
CG-SVX17E-EN 37
(3/8)
Page 38
Installation - Mechanical
Installation of Seismically Rated Isolators
See Figure 42 and Figure 43, p. 38 for reference.
Figure 42. MSSH Seismic isolator installation reference
("H")
("H")
CUSTOMER EQUIPMENT
("G")
("B")
CUSTOMER EQUIPMENT
("E")
("E")
GROMMET
1/4 - 3/8
WASHER
("F")
("F")
("E")
("I")
("A")
("I")
("A")
1. Set isolators on mounting surface, ensuring that all isolator centerlines match the submittal drawing. All isolator base plates (B) must be installed on a level surface. Shim orgrout as required, levelingall isolat(or base plates at the same elevation.
2. Anchor all isolators to the surface using thru holes (C) for concrete or (D) for steel as require. Welding to steel is permitted providing the weld achieves the required strength.
3. Remove clamp down nut (H) and washer (I). Isolators are shipped with (2) removable spacer shims (E) between the top plate and the housing.
Important: These shims MUST be in place when the
equipment is positioned over the isolators.
4. With all shims (E) in place, place the equipment onto the top plate (A) of the isolators.
5. Bolt equipment securely to the isolators using doubler plate (included in isolator kit), washer (I) and nut (H) as shown in Figure 44, p. 38.
Figure 44. Seismic isolator installation detail
Screw
Nut
Washer
("C")
("D") ("C")
Figure 43. M2SS Seismic isolator installation reference
("G")
("G")
("H")
("H")
CUSTOMER EQUIPMENT
CUSTOMER EQUIPMENT
("A")
("E")
("E")
1/4 - 3/8
WASHER
("F")
("B")
GROMMET
("A")
("I")
("E")
("I")
("F")
G rail
Doubler Plate
Isolator
(top
panel)
Important: The following adjustment process can only
begin after the equipment or machine is at its full operating weight.
6. Back off each of the (2) or (4) limit stop locknuts (F) per isolator 1/4-3/8”.
7. Adjust each isolator in sequence by turning adjusting nut(s) (G) one full clockwise turn at a time. Repeat this procedure on all isolators, one at a time. check the limit stop locknuts (F) periodically to ensure that clearance between the washer and rubber grommet is maintained. Stop adjustment of an isolator only when the top plate (A) has risen just above the shim (E).
8. Remove all spacer shims (E).
9. Fine adjust isolators to level equipment.
10. Adjust all limit stop locknuts(F) per isolator to obtain 3/ 8” gap. the limit stop nuts must be kept at this 3/8” gap to ensure uniform bolt loading during uplift.
("C")
("D")
("C")
38 CG-SVX17E-EN
Page 39
Installation - Mechanical
Mounting Point Locations andWeights
Figure 45. Mounting Point Locations
4
3
8
7
Control Panel
1
2
Control Panel
4
3
2
1
Control Panel
4
3
2
1
6
5
Table 11. Elastomeric isolator locations - base unit - with or without partial heat recovery
Location
Size (ton)
20-26
30-35
40-52
60-70
80-120
130
12345678
RDP-3 Grey 60
RDP-4 Brown 61
RDP-4 Red 62
RDP-4 Red 62
RDP-4 Red 62
RDP-4 Red 62
RDP-3 Grey 60
RDP-4 Brown 61
RDP-4 Red 62
RDP-4 Red 62
RDP-4 Green 63
RDP-4 Red 62
RDP-3 Grey 60
RDP-3 Grey 60
RDP-4 Red 62
RDP-3 Gray 60
RDP-4 Red 62
RDP-4 Red 62
RDP-3 Grey 60
RDP-3 Grey 60
RDP-4 Red 62
RDP-4 Brown 61
RDP-4 Red 62
RDP-4 Red 62
----
----
---­RDP-3
Gray 60 RDP-3
Gray 60 RDP-4
Red 62
RDP-3 Gray 60
RDP-3 Gray 60
RDP-4 Red 62
6
5
--
-­RDP-3
Grey 60
RDP-3 Grey 60
Table 12. Elastomeric isolator locations - with pump package- with or without partial heat recovery
Location
Size (ton)
20-26
30-35
40-52
60-90
100-120
130
CG-SVX17E-EN 39
12345678
RDP-3 Brown 61
RDP-4 Brown 61
RDP-4 Red 62
RDP-4 Red 62
RDP-4 Green 63
RDP-4 Red 62
RDP-3 Grey 60
RDP-4 Brown 61
RDP-4 Red 62
RDP-4 Red 62
RDP-4 Green 63
RDP-4 Red 62
RDP-3 Grey 60
RDP-4 Brown 61
RDP-4 Red 62
RDP-4 Red 62
RDP-4 Green 63
RDP-4 Red 62
RDP-3 Grey 60
RDP-4 Brown 61
RDP-4 Red 62
RDP-4 Red 62
RDP-4 Green 63
RDP-4 Red 62
----
----
---­RDP-4
Red 62 RDP-4
Green 63 RDP-4
Red 62
RDP-4 Red 62
RDP-4 Green 63
RDP-4 Red 62
--
-­RDP-4
Red 62
RDP-4 Red 62
Page 40
Installation - Mechanical
Table 13. Elastomeric isolator locations - with pump package and buffer tank option - with or without partial heat
recovery
Location
Size (ton)
20-35
40-52
60-70
80-90
100-120
130
12345678
RDP-3 Grey 60
RDP-4 Brown 61
RDP-4 Brown 61
RDP-4 Green 63
RDP-4 Grey 64
RDP-4 Green 63
RDP-3 Grey 60
RDP-4 Brown 61
RDP-4 Brown 61
RDP-4 Green 63
RDP-4 Grey 64
RDP-4 Green 63
RDP-4 Green 63
RDP-4 Grey 64
RDP-4 Green 63
RDP-4 Red 62
RDP-4 Green 63
RDP-4 Green 63
RDP-4 Green 63
RDP-4 Grey 64
RDP-4 Green 63
RDP-4 Red 62
RDP-4 Green 63
RDP-4 Green 63
----
---­RDP-4
Green 63 RDP-4
Red 62 RDP-4
Green 63 RDP-4
Green 63
RDP-4 Green 63
RDP-4 Red 62
RDP-4 Green 63
RDP-4 Green 63
--
--
RDP-4 Green 63
RDP-4 Green 63
Table 14. Seismically rated isolator locations
Size
(ton)
20
26
30
35
40
52
60
70
80
90
100
110
120
130
12345678
MSSH-1E-825N
Red/Dk Blue
MSSH-1E-1000
Tan
M2SS-1E-1300
Red
M2SS-1E-1300
Red
M2SS-1E-1300
Red
M2SS-1E-1300
Red
M2SS-1E-
1650N Red/Dk
Blue
M2SS-1E-
1650N Red/Dk
Blue
M2SS-1E-2000
Tan
M2SS-1E-2000
Tan
M2SS-1E-2000
Tan
M2SS-1E-2000
Tan
M2SS-1E-2000
Tan
M2SS-1E-
1650N Red/Dk
Blue
MSSH-1E-825N
Red/Dk Blue
MSSH-1E-825N
Red/Dk Blue
M2SS-1E-1060N
Black/Dk Blue
M2SS-1E-1060N
Black/Dk Blue
M2SS-1E-1300
Red
M2SS-1E-1650N
Red/Dk Blue
M2SS-1E-1650N
Red/Dk Blue
M2SS-1E-1650N
Red/Dk Blue
M2SS-1E-2000
Tan
M2SS-1E-2000
Tan
M2SS-1E-2000
Tan
M2SS-1E-2000
Tan
M2SS-1E-2000
Tan
M2SS-1E-1650N
Red/Dk Blue
MSSH-1E-530N
Black/Dk Blue
MSSH-1E-530N
Black/Dk Blue M2SS-1E-800
Black
M2SS-1E-800
Black
M2SS-1E-800
Black
M2SS-1E-1060N
Black/Dk Blue
M2SS-1E-1060N
Black/Dk Blue
M2SS-1E-1060N
Black/Dk Blue
M2SS-1E-1060N
Black/Dk Blue
M2SS-1E-1060N
Black/Dk Blue
M2SS-1E-1300
Red
M2SS-1E-1300
Red
M2SS-1E-1300
Red
M2SS-1E-1300
Red
MSSH-1E-530N
Black/Dk Blue
MSSH-1E-530N
Black/Dk Blue
M2SS-1E-800
M2SS-1E-800
M2SS-1E-1060N
Black/Dk Blue
M2SS-1E-1060N
Black/Dk Blue
M2SS-1E-1060N
Black/Dk Blue
M2SS-1E-1060N
Black/Dk Blue
M2SS-1E-1300
M2SS-1E-1650N
M2SS-1E-1650N
M2SS-1E-1650N
M2SS-1E-2000
M2SS-1E-1650N
Locations
Black
Black
Red
Red/Dk Blue
Red/Dk Blue
Red/Dk Blue
Tan
Red/Dk Blue
M2SS-1E-800
Black
M2SS-1E-800
Black
M2SS-1E-800
Black
M2SS-1E-800
Black
M2SS-1E-800
Black
M2SS-1E-800
Black
M2SS-1E-800
Black
M2SS-1E-1060N
Black/Dk Blue
M2SS-1E-800
Black
M2SS-1E-800
Black
M2SS-1E-800
Black
M2SS-1E-800
Black
M2SS-1E-800
Black
M2SS-1E-800
Black
M2SS-1E-800
Black
M2SS-1E-1300
Red
M2SS-1E-800
Black
M2SS-1E-1060N
Black/Dk Blue
40 CG-SVX17E-EN
Page 41
Installation - Mechanical
Table 15. Point weights (lbs) - 60 Hz - base unit
Isolator location
Size
(tons)
20 706 645 408 365 - - - - 822 648 425 487 - - - ­26 792 614 369 420 - - - - 808 716 486 443 - - - ­30 887 858 627 425 - - - - 1027 882 673 574 - - - ­35 894 862 645 436 - - - - 1035 884 690 587 - - - ­40 1152 1036 611 811 - - - - 1198 1246 823 858 - - - ­52 1081 1156 714 769 - - - - 1210 1283 844 898 - - - ­60 1130 1198 771 821 493 527 - - 1252 1319 900 949 603 637 - ­70 1118 1210 781 849 511 558 - - 1239 1330 911 978 622 668 - ­80 1435 1662 774 886 396 449 - - 1796 1835 863 1203 581 594 - -
90 1508 1763 802 927 406 466 - - 1872 1931 888 1249 591 611 - ­100 1640 1587 847 1120 608 866 - - 1771 1993 1195 1342 886 995 - ­110 1673 1634 851 1134 602 863 - - 1803 2038 1200 1356 878 993 - ­120 1691 1651 854 1138 600 861 - - 1821 2055 1204 1360 876 990 - ­130 1284 1273 910 1229 861 852 569 826 1270 1749 1301 1197 990 1246 1009 933
20 708 661 414 382 - - - - 773 713 482 453 - - - -
26 793 630 375 437 - - - - 752 789 550 402 - - - -
30 891 882 633 439 - - - - 1032 905 677 590 - - - -
35 955 829 593 507 - - - - 1041 908 694 603 - - - -
40 1062 1111 749 785 - - - - 1191 1239 879 914 - - - -
52 1073 1148 770 825 - - - - 1202 1276 900 954 - - - -
60 1111 1179 802 851 539 573 - - 1232 1299 931 980 650 683 - -
70 1098 1190 812 880 558 604 - - 1311 1280 917 895 600 858 - -
80 1529 1756 780 891 384 437 - - 1889 1926 872 1213 568 580 - -
90 1602 1858 808 933 394 454 - - 1966 2023 896 1260 577 596 - ­100 1732 1680 860 1138 596 848 - - 1862 2083 1213 1361 870 978 - ­110 1765 1726 864 1152 589 846 - - 1935 1895 1210 1775 830 810 - ­120 1784 1745 867 1156 588 843 - - 1953 1913 1214 1780 827 807 - ­130 1129 1587 1144 1072 855 803 589 812 1589 1476 1146 1605 938 1204 990 935
1234567812345678
Aluminum Fins Copper Fins
Without partial heat recovery
With partial heat recovery
CG-SVX17E-EN 41
Page 42
Installation - Mechanical
Table 16. Point weights (lbs) - 60 Hz - with pump package
Isolator location
Size
(tons)
20875612603619----802803809552---­26910630614624----834825823555---­30 939 892 940 609 - - - - 1173 822 892 853 ---­35 946 897 958 620 - - - - 1182 824 908 866 ---­40 1214 1109 1009 932 - - - - 1336 1244 1146 1054 ---­52 1225 1146 1030 972 - - - - 1349 1279 1165 1096 ---­60 1275 1196 890 832 852 794 - - 1287 1340 1227 938 863 901 - ­70 1265 1209 897 855 870 829 - - 1292 1239 1233 1181 869 830 - ­80 1296 1663 922 1070 901 763 - - 1637 1812 1190 1307 927 1012 - -
90 1556 1616 816 1152 857 887 - - 1712 1910 1217 1349 934 1031 - ­100 1278 1684 1330 1175 1013 1226 - - 1562 1736 1653 1828 1162 1278 - ­110 1306 1733 1339 1189 1006 1221 - - 1594 1778 1661 1846 1152 1275 - ­120 1276 1623 1280 1630 1285 1091 - - 1742 1721 1721 1700 1133 1679 - ­130 835 1195 1150 1206 1168 1224 1177 1233 1341 1335 1253 1247 1116 1665 1565 1556
20877626609636----802819817568----
26852706681581----835841831571----
30 944 916 944 624 - - - - 1181 843 894 871 ----
35 1025 846 889 710 - - - - 1190 846 910 884 ----
40 1118 1190 1154 899 - - - - 1329 1236 1202 1110 ----
52 1128 1229 1177 938 - - - - 1342 1272 1222 1152 ----
60 1259 1180 912 854 903 845 - - 1284 1211 1252 1180 899 846 - -
70 1249 1192 919 878 922 880 - - 1273 1221 1261 1209 917 879 - -
80 1570 1609 804 1123 832 852 - - 1728 1903 1203 1320 911 996 - -
90 1649 1707 827 1166 842 871 - - 1804 2001 1231 1362 918 1015 - ­100 1584 1635 1178 1212 951 1331 - - 1648 1823 1680 1855 1141 1257 - ­110 1616 1681 1183 1226 943 1329 - - 1680 1865 1688 1873 1131 1254 - ­120 1586 1562 1136 1679 1212 1196 - - 1828 1809 1748 1730 1114 1653 - ­130 1067 1199 1089 1221 1124 1256 1143 1275 1381 1115 1359 1638 1324 1586 1305 1558
1234567812345678
Aluminum Fins Copper Fins
Without partial heat recovery
With partial heat recovery
42 CG-SVX17E-EN
Page 43
Installation - Mechanical
Table 17. Point weights (lbs) - 60 Hz - with pump package and buffer tank options
Isolator location
Size
(tons)
20 617 413 1728 1650 ----6105381867 1650 - - - ­26 650 434 1741 1653 ----6405621884 1650 - - - ­30 860 552 1885 1782 ----8587182074 1789 - - - ­35 868 556 1903 1794 ----8657222092 1801 - - - ­40 838 790 2266 2136 ----9679182396 2264 - - - ­52 856 820 2279 2182 ----9859482410 2311 - - - ­60 882 838 1205 1146 1810 1721 - - 1007 963 1325 1265 1926 1836 - ­70 878 848 1208 1166 1826 1763 - - 1004 972 1328 1285 1942 1878 - ­80 1868 2086 1234 1379 899 1005 - - 1892 2452 1703 1650 1040 1005 - -
90 1873 2145 1281 1657 957 828 - - 2169 2400 1565 1738 1012 1128 - ­100 1681 2251 1789 1796 1263 1267 - - 2292 2524 1638 1812 1559 1734 - ­110 1710 2298 1797 1810 1255 1263 - - 2324 2568 1645 1828 1549 1732 - ­120 1862 2235 1856 1671 1234 1666 - - 2314 2562 1710 1896 1685 1871 - ­130 1210 1223 1148 1742 1580 1599 1504 1523 1110 1688 1706 1728 1768 1791 1801 1824
20 624 423 1729 1672 ----6165491870 1671 - - - -
26 585 516 1813 1604 ----6465741886 1671 - - - -
30 872 569 1883 1805 ----8677382074 1810 - - - -
35 880 572 1900 1817 ----8747422092 1821 - - - -
40 831 783 2322 2191 ----9599112452 2320 - - - -
52 849 813 2336 2238 ----9779412466 2367 - - - -
60 870 827 1218 1159 1866 1777 - - 841 928 1732 1273 1742 1920 - -
70 866 836 1222 1179 1883 1819 - - 837 937 1737 1294 1758 1962 - -
80 1823 2358 1285 1248 980 953 - - 2217 2293 1679 1736 827 1165 - -
90 1959 2243 1296 1667 945 809 - - 2293 2389 1710 1782 832 1183 - ­100 1762 2347 1817 1815 1247 1245 - - 2380 2613 1661 1836 1540 1715 - ­110 1791 2394 1825 1829 1239 1241 - - 2413 2657 1668 1851 1530 1713 - ­120 1941 2333 1885 1694 1220 1639 - - 2403 2651 1733 1919 1666 1852 - ­130 1158 1611 1132 1573 1639 1514 1607 1482 1476 1637 1559 1720 1688 1849 1757 1918
1234567812345678
Aluminum Fins Copper Fins
Without partial heat recovery
Without partial heat recovery
CG-SVX17E-EN 43
Page 44
Installation - Mechanical
Table 18. Point Weights (lbs) - 50 Hz - base unit
Isolator location
Aluminum Fins Copper Fins
Size (tons)123456123456
Without partial heat recovery 20 767 606 348 406 - - 833 658 415 478 - ­26 792 614 369 420 - - 808 716 486 443 - ­30 887 858 627 425 - - 1027 882 673 574 - ­35 894 862 645 436 - - 1035 884 690 587 - ­40 1152 1036 611 811 - - 1198 1246 823 858 - ­52 1081 1156 714 769 - - 1210 1283 844 898 - ­60 1130 1198 771 821 493 527 1252 1319 900 949 603 637 70 1118 1210 781 849 511 558 1239 1330 911 978 622 668 80 1435 1662 774 886 396 449 1796 1835 863 1203 581 594 90 1507 1763 802 927 406 465 1872 1931 887 1249 591 610
100 1654 1606 840 1113 593 847 1787 2008 1188 1336 869 977 110 1671 1632 849 1132 600 862 1801 2036 1198 1354 876 991 120 1690 1651 853 1137 600 860 1820 2055 1203 1360 875 990
With partial heat recovery 20 769 621 354 422 - - 784 724 472 444 - ­26 793 629 375 437 - - 752 789 550 402 - ­30 891 882 633 439 - - 1032 905 677 590 - ­35 955 829 593 507 - - 1041 908 694 603 - ­40 1062 1111 749 785 - - 1191 1239 879 914 - ­52 1073 1148 770 824 - - 1202 1276 900 953 - ­60 1111 1179 802 851 539 573 1232 1299 931 980 650 683 70 1098 1190 812 880 558 604 1311 1281 917 895 600 858 80 1529 1756 780 891 384 437 1889 1926 872 1213 568 580 90 1601 1857 807 932 394 454 1965 2022 896 1259 577 596
100 1745 1697 853 1131 581 829 1877 2098 1206 1354 853 961 110 1763 1724 862 1150 588 844 1933 1893 1208 1772 828 809 120 1782 1743 866 1155 587 842 1951 1911 1213 1779 826 807
Table 19. Point Weights (lbs) - 50 Hz - with pump package
Aluminum Fins Copper Fins
Size (tons)123456123456
20 811 679 575 491 - - 871 738 648 557 - ­26 834 690 598 504 - - 894 748 671 571 - ­30 936 890 851 550 - - 1162 828 811 786 - ­35 943 895 887 572 - - 1173 829 843 812 - ­40 1193 1119 943 888 - - 1232 1336 1162 928 - ­52 1204 1156 963 928 - - 1330 1287 1097 1054 - ­60 1273 1202 879 826 833 781 1287 1346 1214 933 845 888 70 1264 1215 886 850 852 816 1291 1246 1220 1175 851 818 80 1298 1667 914 1059 885 748 1641 1816 1180 1296 912 998 90 1558 1619 807 1142 842 871 1716 1913 1207 1338 920 1016
100 1292 1707 1317 1162 983 1186 1582 1755 1638 1812 1129 1244 110 1306 1735 1328 1179 990 1201 1596 1780 1650 1834 1134 1257 120 1271 1847 1245 1205 1219 1179 1755 1743 1673 1662 1062 1582
44 CG-SVX17E-EN
Isolator location
Without partial heat recovery
Page 45
Installation - Mechanical
Table 19. Point Weights (lbs) - 50 Hz - with pump package (continued)
Isolator location
Aluminum Fins Copper Fins
Size (tons)123456123456
With partial heat recovery 20 871 636 523 566 - - 873 753 655 574 - ­26 895 645 545 580 - - 896 763 677 587 - ­30 941 914 856 565 - - 1170 849 813 804 - ­35 948 919 892 588 - - 1181 850 846 830 - ­40 1186 1111 998 944 - - 1309 1244 1133 1068 - ­52 1197 1148 1019 984 - - 1322 1279 1152 1109 - ­60 1257 1186 901 849 884 832 1283 1218 1239 1174 882 834 70 1248 1199 908 872 903 867 1273 1228 1248 1202 900 866 80 1572 1613 796 1113 817 837 1731 1906 1193 1309 896 982 90 1650 1709 818 1155 827 856 1806 2003 1220 1352 904 1000
100 1600 1655 1163 1199 921 1293 1667 1841 1665 1838 1108 1224 110 1617 1683 1173 1216 927 1309 1683 1867 1677 1861 1114 1236 120 1600 1581 1098 1627 1128 1115 1682 1868 1724 1910 1177 1301
Table 20. Point Weights (lbs) - 50 Hz - with pump package and buffer tank options
Isolator location
Aluminum Fins Copper Fins
Size (tons)123456123456
Without partial heat recovery 20 616 419 1637 1585 - - 609 544 1778 1584 - ­26 637 430 1662 1596 - - 628 558 1804 1593 - ­30 853 554 1801 1719 - - 850 721 1990 1726 - ­35 862 557 1835 1743 - - 859 724 2025 1750 - ­40 735 882 2280 2010 - - 954 920 2321 2229 - ­52 843 822 2204 2146 - - 972 950 2335 2275 - ­60 881 842 1196 1143 1788 1709 1006 966 1316 1262 1905 1824 70 877 851 1200 1164 1804 1750 1003 975 1320 1283 1921 1865 80 1872 2089 1224 1369 884 991 2131 2206 1654 1710 829 1168 90 1876 2150 1271 1643 943 814 2206 2301 1684 1756 834 1185
100 1700 2273 1774 1778 1230 1233 2309 2542 1627 1801 1524 1698 110 1713 2300 1786 1798 1238 1246 2325 2569 1636 1818 1531 1713 120 1872 2259 1809 1631 1165 1569 2330 2575 1673 1857 1600 1784
With partial heat recovery 20 623 429 1639 1607 - - 614 555 1780 1604 - ­26 573 511 1733 1548 - - 633 569 1806 1614 - ­30 865 571 1798 1742 - - 859 740 1990 1746 - ­35 874 574 1833 1766 - - 868 744 2025 1770 - ­40 818 784 2247 2155 - - 946 912 2377 2284 - ­52 836 814 2260 2202 - - 964 942 2391 2331 - ­60 869 830 1209 1156 1845 1765 994 954 1329 1275 1961 1880 70 866 839 1213 1177 1861 1806 991 964 1333 1296 1977 1921 80 1827 2361 1274 1237 966 938 2221 2298 1667 1724 815 1150 90 1961 2247 1285 1652 931 796 2295 2393 1697 1770 820 1167
100 1780 2368 1801 1797 1215 1212 2467 2452 1851 1840 1234 1840 110 1794 2396 1813 1817 1222 1224 2484 2479 1861 1858 1240 1856 120 1951 2356 1837 1653 1151 1543 2418 2664 1696 1880 1581 1765
CG-SVX17E-EN 45
Page 46
Installation - Mechanical
Evaporator Piping
Evaporator water connections are grooved.
Thoroughly flush all water piping to the CGAM unit before
making the final piping connections to the unit.
Components and layout will vary slightly, depending on the location of connections and the water source.
NOTICE:
Equipment Damage!
If using an acidic commercial flushing solution, construct a temporary bypass around the unit to prevent damage to internal components of the evaporator and the pump.
NOTICE:
Proper Water Treatment!
The use of untreated or improperly treated water could
result in scaling, erosion, corrosion, algae or slime. It is recommended that the services of a qualified water treatment specialist be engaged to determine what water treatment, if any, is required.Trane assumes no responsibility for equipment failures which result from untreated or improperly treated water, or saline or brackish water.
Figure 46. Water piping components
Drainage
Locate the unit near a large capacity drain for water vessel drain-down during shutdown or repair. Evaporators are provided with drain connections. Refer to “Water Piping.” All local and national codes apply.
A vent is provided on the top of the evaporator at the chilled water inlet. Be sure to provide additional vents at high points in the pipingto bleedair fromthe chilled water system. Install necessary pressure gauges to monitor the entering and leaving chilled water pressures.
Provide shutoff valves in lines to the gauges to isolate them from the system when they are not in use. Use rubber vibration eliminators to prevent vibration transmission through the water lines.
If desired, install thermometers in the lines to monitor entering and leaving water temperatures. Install a balancing valve in the leaving water line to control water flow balance. Install shutoff valves on both the entering and leaving water lines so that the evaporator can be isolated for service.
Evaporator Piping Components
Piping components include all devices and controls used to provide proper water system operation and unit operating safety. See Figure 46, p. 46.These components are listed below.
4
6
8
B
6
5
UNIT
7
5
5
3
3
Table 21. Water piping components
Item Description Item Description
1 Bypass Valve Pi Gauge 2 Isolation Valves FT Water Flow Switch 3 Vibration Eliminators T1 Evap Water Inlet Temp Sensor 4 Evaporator Heat Exchanger T2 Evap Water Outlet Temp Sensor 5 Water Heater A Isolate unit for initial water loop cleaning 6 Valve for Pressure Point 7 Strainer
B
Brazed plate differential pressure gauge and piping not supplied. Must account for water head height difference when calculating brazed plate pressure differential.
2
1
A
2
CUSTOMER PIPING
46 CG-SVX17E-EN
Page 47
Installation - Mechanical
Entering Chilled Water Piping
Air vents (to bleed air from system)
Water pressure gauges with shutoff valves
Vibration eliminators
Shutoff (isolation) valves
• Thermometers (if desired)
Relief valve
Leaving Chilled Water Piping
Air vents (to bleed air from system)
Water pressure gauges with shutoff valves
Vibration eliminators
Shutoff (isolation) valves
• Thermometers (if desired)
Balancing valve
NOTICE:
Water Damage!
Standard pressure is 72.5 Psig for all factory installed components on the suction side of water pump. Standard pressure of components on the discharge side of water pump is 145 Psig.You MUST drain the system FIRST before releasing the pressure. Failure to do so could result in water spray which could cause equipment and/or property damage.
Water Strainer
The water strainer is factory-installed with taps for the
pressure gauges on the inlet and outlet. Install pressure gauges in order to measure differential pressure across the filter.This will help to determine when it is necessary to clean the water strainer.
Flow Switch
NOTICE:
Equipment Damage!
Flow switch is on a 24V circuit. Do NOT apply 120V to the flow switch. Incorrect voltage application could cause damage to the flow switch.
The flow switch is factory-installed and programmed
based on the operating conditions submitted with the order.The leaving evaporator temperature, fluid type and fluid concentration affect the selected flow switch. If the operating conditions on the job site change, the flow switch may need to be replaced.
The sensor head includes 3 LEDs, two yellow and one
green.Wait 15 seconds after poweris applied to the sensor before evaluating LEDs for flow status. When wired correctly and flow is established, only the green LED should be lit. Following are the LED indicators:
Green ON, both yellow OFF — Flow
Green and outside yellow ON — No Flow
Center yellow ON continuously — Miswire
Factory installed jumper wire W11 must be removed if using auxiliary contacts and/or additional proof of flow. See schematics in CGAM-SVE01*-EN for more details.
Note: Use caution when connecting the auxiliary
contacts.Terminals 1X5-3 and 1X5-9 are to be used for field connections of auxiliary contacts. Inadvertant use of 1X5-4 and 1X5-9 will result in a FALSE FLOW indication.
NOTICE:
Equipment Damage!
Incorrect wiring of auxiliary contacts could cause equipment damage.
CG-SVX17E-EN 47
If using auxiliary flow sensing, both yellow LEDs come on initially when flow is stopped.The center yellow LED will turn off after approximately 7 seconds.The LED indicators are otherwise the same as indicated above.
Evaporator Label
The BPHE evaporator label, including barcode, is located
under the insulation, in the locations shown in Figure 47,
p. 48. Insulation backing over this area has not been
removed, so that it can be rolled back to access BPHE label.
Page 48
Installation - Mechanical
Figure 47. BPHE label locations
20T BPHE - P80
26/30/36T BPHE - P120
BPHE LABEL LOCATION
BARCODE
ADDITIONAL INSULATION TAP
40T BPHE - DP200
BPHE LABEL LOCATION
BARCODE
ADDITIONAL INSULATION TAP
ROLL BACK THE INSULATION
52-130T BPHE - DP400
BPHE LABEL LOCATION
BARCODE
ADDITIONAL INSULATION TAP
BPHE LABEL LOCATION
BARCODE
ADDITIONAL INSULATION TAP
ROLL BACK THE INSULATION
48 CG-SVX17E-EN
Page 49
Installation - Mechanical
P R E S S U R E DR OP ( F t.of H2 O)
FLOW (GPM)
020
026
030
040
052
060
070
080 090
100
120
110
035
130
PRESSURE DROP (Ft.of H2O)
FLOW (GPM)
020
026
030
040 052
060
070
080
090 100
120
110
035
130
Pressure Drop Curves
For overlapping pressure drop curves, see General DataTables in section “General Information,” p. 9 for limit values
.
Figure 48. Total unit pressure drop curves (60 Hz)
+]
40
20
10
5
1
10 100
50
200
400
Figure 49. Total Unit Pressure Drop Curves (50 Hz)
40
20
10
5
1
10 100
50
50Hz
200
400
CG-SVX17E-EN 49
Page 50
Installation - Mechanical
Freeze Protection
Depending on the ambient temperature the unit may be exposed to, there are up to four different options for freeze protection.They are listed in order of highest ambient (least freeze protection) to lowest ambient (most freeze protection).
1. Water pump (for protection with ambient temperatures down to 0°F)
a. CH530 controller can start the pump when the
ambient temperatures drops to prevent freezing. For this option the pump must to be controlled by the CGAM unit and this function must be validated.
b. Water circuit valves need to stay open at all times.
Note: If dual high head pump package option is
selected, the chiller MUST control the pumps.
OR
2. Heaters (for protection with ambient temperatures down to -20°F)
Note: This option is not applicable for units ordered
with “No Freeze Protection” (model number digit 18 is “X”). Factory mounted heaters are NOT installed on these units, and one of the other forms of freeze protection must be used.
a. For units with freeze protection selected (model
number digit 18is“1”), heaters are factory-installed on the evaporator and water pipingand will protect them from freezing in ambient temperatures down to -20°F (-29°C).
b. Install heat tape on all water piping, pumps, and
other components that maybe damaged if exposed to freezing temperatures. Heat tape must be designed for low ambient temperature applications. Heat tape selection should be based on the lowest expected ambient temperature.
NOTICE:
Equipment Damage!
All heaters have separate power from the unit. All
heaters must be energized or the CH530 must control the pumps when the unit is off (unless the water circuit is drained). In the event of power loss, neither heaters nor CH530 control of the pumps will protect the evaporator from catastrophic damage. In order to provide freeze protection in the event of a power loss you MUST drain the evaporator or use sufficient freeze inhibitor in the evaporator.
OR
3. Freeze inhibitor
Freeze protection can be accomplished by adding
sufficient glycol to protect against freezing below the lowest ambient expected.
See “Low Evap Refrigerant Cutout/Percent Glycol
Recommendations,” p. 50.
OR
4. Drain water circuit (for protection with ambients below
-20°F)
a. Shut off the power supply to the unit and to all
heaters.
b. Purge the water circuit.
c. Blow outthe evaporatorto ensureno liquid isleft in
the evaporator.
Note: By default the CH530 freeze protection control is
enabled and will request the start of the chilled water pump with ambient temperatures less than the evaporator low leaving water temperature setpoint.The pump remains ON until the minimum evaporator water temperature is greater than low leaving water temperature setpoint plus 7°C. The minimum on time for the pump is 5 minutes. If you do NOT want the CH530 to start the pump when the ambient temperature drops to freezing, disable this freeze protection control.
Low Evap Refrigerant Cutout/Percent Glycol Recommendations
The table below shows the low evaporator temperature
cutout for different glycol levels.
Additional glycol beyond the recommendations will adversely effect unit performance.The unit efficiency will be reduced and the saturated evaporator temperature will be reduced. For some operating conditions this effect can be significant.
If additional glycol is used, then use the actual percent glycol to establish the low refrigerant cutout setpoint.
50 CG-SVX17E-EN
Page 51
Installation - Mechanical
Table 22. Low Evap RefrigerantTemp Cutout and LowWater Temp Cutout
ETHYLENE GLYCOL PROPYLENE GLYCOL
Low
Refrig
Solution
%
Glycol
Freeze
Point [F]
0 32 22 35 42 42 42 0 32 22 35 42 42 42 1 31.6 21.6 34.6 41.6 39.1 38.2 1 31.6 21.6 34.6 41.6 39.1 38.2 2 31.0 21.0 34.0 41.0 38.5 37.6 2 31.0 21.0 34.0 41.0 38.5 37.6 3 30.3 20.3 33.3 40.3 37.8 37.0 3 30.4 20.4 33.4 40.3 37.8 37.0 4 29.7 19.7 32.7 39.7 37.2 36.3 4 29.9 19.9 32.9 39.7 37.2 36.3 5 29.0 19.0 32.0 39.0 36.5 35.7 5 29.3 19.3 32.3 39.0 36.5 35.7 6 28.3 18.3 31.3 38.3 35.8 35.0 6 28.7 18.7 31.7 38.3 35.8 35.0 7 27.6 17.6 30.6 37.6 35.1 34.3 7 28.1 18.1 31.1 37.6 35.1 34.3 8 26.9 16.9 29.9 36.9 34.4 33.6 8 27.6 17.6 30.6 36.9 34.4 33.6
9 26.2 16.2 29.2 36.2 33.7 32.9 9 27.0 17.0 30.0 36.2 33.7 32.9 10 25.5 15.5 28.5 35.5 33.0 32.1 10 26.4 16.4 29.4 35.5 33.0 32.1 11 24.7 14.7 27.7 34.7 32.2 31.4 11 25.7 15.7 28.7 34.7 32.2 31.4 12 23.9 13.9 26.9 33.9 31.4 30.6 12 25.1 15.1 28.1 33.9 31.4 30.6 13 23.1 13.1 26.1 33.1 30.6 29.8 13 24.4 14.4 27.4 33.1 30.6 29.8 14 22.3 12.3 25.3 32.3 29.8 29.0 14 23.8 13.8 26.8 32.3 29.8 29.0 15 21.5 11.5 24.5 31.5 29.0 28.1 15 23.1 13.1 26.1 31.5 29.0 28.1 16 20.6 10.6 23.6 30.6 28.1 27.2 16 22.4 12.4 25.4 30.6 28.1 27.2 17 19.7 9.7 22.7 29.7 27.2 26.3 17 21.6 11.6 24.6 29.7 27.2 26.3 18 18.7 8.7 21.7 28.7 26.2 25.4 18 20.9 10.9 23.9 28.7 26.2 25.4 19 17.8 7.8 20.8 27.8 25.3 24.5 19 20.1 10.1 23.1 27.8 25.3 24.5 20 16.8 6.8 19.8 26.8 24.3 23.5 20 19.3 9.3 22.3 26.8 24.3 23.5 21 15.8 5.8 18.8 25.8 23.3 22.5 21 18.4 8.4 21.4 25.8 23.3 22.5 22 14.7 4.7 17.7 24.7 22.2 21.4 22 17.6 7.6 20.6 24.7 22.2 21.4 23 13.7 3.7 16.7 23.7 21.2 20.3 23 16.7 6.7 19.7 23.7 21.2 20.3 24 12.5 2.5 15.5 22.5 20.0 19.2 24 15.7 5.7 18.7 22.5 20.0 19.2 25 11.4 1.4 14.4 21.4 18.9 18.1 25 14.8 4.8 17.8 21.4 18.9 18.1 26 10.2 0.2 13.2 20.2 17.7 16.9 26 13.8 3.8 16.8 20.2 17.7 16.9 27 9.0 -1.0 12.0 19.0 16.5 15.7 27 12.7 2.7 15.7 19.0 16.5 15.7 28 7.7 -2.3 10.7 17.7 15.2 14.4 28 11.6 1.6 14.6 17.7 15.2 14.4 29 6.4 -3.6 9.4 16.4 13.9 13.1 29 10.5 0.5 13.5 16.4 13.9 13.1 30 5.1 -4.9 8.1 15.1 12.6 11.8 30 9.3 -0.7 12.3 15.1 12.6 11.8 31 3.7 -6.3 6.7 13.7 11.2 10.4 31 8.1 -1.9 11.1 13.7 11.2 10.4 32 2.3 -7.7 5.3 12.3 10.4 10.4 32 6.8 -3.2 9.8 12.3 10.4 10.4 33 0.8 -9.2 3.8 10.8 10.4 10.4 33 5.5 -4.5 8.5 10.8 10.4 10.4 34 -0.7 -10.7 2.3 10.4 10.4 10.4 34 4.1 -5.9 7.1 10.4 10.4 10.4 35 -2.3 -12.3 0.7 10.4 10.4 10.4 35 2.7 -7.3 5.7 10.4 10.4 10.4 36 -3.9 -13.9 -0.9 10.4 10.4 10.4 36 1.3 -8.7 4.3 10.4 10.4 10.4 37 -5.6 -15.6 -2.6 10.4 10.4 10.4 37 -0.3 -10.3 2.7 10.4 10.4 10.4 38 -7.3 -17.3 -4.3 10.4 10.4 10.4 38 -1.8 -11.8 1.2 10.4 10.4 10.4 39 -9.0 -19.0 -5.0 10.4 10.4 10.4 39 -3.5 -13.5 -0.5 10.4 10.4 10.4 40 -10.8 -19.0 -5.0 10.4 10.4 10.4 40 -5.2 -15.2 -2.2 10.4 10.4 10.4
Temp
Cutout
[F]
Low
Water
Temp
Cutout
[F]
Min Chilled Water Set
Point [F]
Number of
compressors
%
Glycol
Solution
Freeze
Point [F]
Low Refrig Temp
Cutout
[F]
Low
Water
Temp
Cutout
[F]
Min Chilled Water Set
Point [F]
Number of
compressors
246 246
CG-SVX17E-EN 51
Page 52
Installation - Mechanical
Table 22. Low Evap RefrigerantTemp Cutout and LowWater Temp Cutout (continued)
ETHYLENE GLYCOL PROPYLENE GLYCOL
Low
Refrig
Solution
%
Glycol
Freeze
Point [F]
41 -12.7 -19.0 -5.0 10.4 10.4 10.4 41 -6.9 -16.9 -3.9 10.4 10.4 10.4 42 -14.6 -19.0 -5.0 10.4 10.4 10.4 42 -8.8 -18.8 -5.0 10.4 10.4 10.4 43 -16.6 -19.0 -5.0 10.4 10.4 10.4 43 -10.7 -19.0 -5.0 10.4 10.4 10.4 44 -18.6 -19.0 -5.0 10.4 10.4 10.4 44 -12.6 -19.0 -5.0 10.4 10.4 10.4 45 -20.7 -19.0 -5.0 10.4 10.4 10.4 45 -14.6 -19.0 -5.0 10.4 10.4 10.4 46 -22.9 -19.0 -5.0 10.4 10.4 10.4 46 -16.7 -19.0 -5.0 10.4 10.4 10.4 47 -25.1 -19.0 -5.0 10.4 10.4 10.4 47 -18.9 -19.0 -5.0 10.4 10.4 10.4 48 -27.3 -19.0 -5.0 10.4 10.4 10.4 48 -21.1 -19.0 -5.0 10.4 10.4 10.4 49 -29.7 -19.0 -5.0 10.4 10.4 10.4 49 -23.4 -19.0 -5.0 10.4 10.4 10.4 50 -32.1 -19.0 -5.0 10.4 10.4 10.4 50 -25.8 -19.0 -5.0 10.4 10.4 10.4 51 -34.5 -19.0 -5.0 10.4 10.4 10.4 51 -28.3 -19.0 -5.0 10.4 10.4 10.4 52 -37.1 -19.0 -5.0 10.4 10.4 10.4 52 -30.8 -19.0 -5.0 10.4 10.4 10.4 53 -39.7 -19.0 -5.0 10.4 10.4 10.4 53 -33.4 -19.0 -5.0 10.4 10.4 10.4 54 -42.3 -19.0 -5.0 10.4 10.4 10.4 54 -36.1 -19.0 -5.0 10.4 10.4 10.4 55 -45.0 -19.0 -5.0 10.4 10.4 10.4 55 -38.9 -19.0 -5.0 10.4 10.4 10.4
Temp
Cutout
[F]
Low
Water
Temp
Cutout
[F]
Min Chilled Water Set
Point [F]
Number of
compressors
%
Glycol
Solution
Freeze
Point [F]
Low Refrig Temp
Cutout
[F]
Low
Water
Temp
Cutout
[F]
Min Chilled Water Set
Point [F]
Number of
compressors
246 246
52 CG-SVX17E-EN
Page 53
Installation - Mechanical
Performance Adjustment Factors
Concentration and type of glycol used will affect unit performance. If operating conditions, including concentration of freeze inhibitor, have changed since the unit was ordered, contact sales representative to rerun selection. See Figure 50,
p. 53 through Figure 55, p. 53 for approximate adjustment factors.
Figure 50. Ethylene - compressor power adjustment
0.999
0.9985
0.998
0.9975
0.997
0.9965
0.996
Adjustment Factor
0.9955
0.995
0.9945
0.994 0 5 10 15 20 25 30 35 40 45
50 Hz
60 Hz
% Ethylene Glycol by Weight
Figure 51. Propylene - compressor power adjustment
0.999
0.998
0.997
0.996
0.995
0.994
0.993
0.992
Adjustment Factor
0.991
0.99
0.989
0.998 0 5 10 15 20 25 30 35 40 45 50
50 Hz
60 Hz
% Ethylene Glycol by Weight
Figure 52. Ethylene - GPM adjustment
1. 14
1. 12
1. 10
1.08
1.06
Adjustment Factor
1.04
1.02
1. 0 0 0 5 10 15 20 25 30 35 40 45
% Ethylene Glycol by Weight
50 Hz
60 Hz
Figure 53. Propylene - GPM adjustment
1.06
1.05
1.04
1.03
1.02
50 Hz
Adjustment Factor
1. 01
1. 0 0
0.99 0 5 10 15 20 25 30 35 40 45 50
% Ethylene Glycol by Weight
Figure 54. Ethylene - capacity adjustment
0.996
0.994
0.992
0.990
0.988
0.986
0.984
Adjustment Factor
0.982
0.980
0.978
0.976
0 5 10 15 20 25 30 35 40 45
60 Hz
% Ethylene Glycol by Weight
Figure 55. Propylene - capacity adjustment
0.995
0.990
0.985
0.980
0.975
0.970
Adjustment Factor
0.965
0.960
0.955 0 5 10 15 20 25 30 35 40 45 50
% Ethylene Glycol by Weight
50 Hz
60 Hz
60 Hz
50 Hz
CG-SVX17E-EN 53
Page 54
Installation - Mechanical
Partial Heat Recovery
The partial heat recovery is comprised of an auxiliary heat
exchanger installed in the discharge line between the compressor and the air -cooled condenser.The heat exchangercools compressor dischargegas and rejects the energy to a separate water loop for hot water applications.
The chiller can simultaneously produce chilled and hot
water.
The heating capacity is driven by the cooling demand on
the chiller, the condensing temperature and the flow rate through the heat exchanger.
The partial heat recovery includes:
Brazed plate heat exchanger
Units 20-35Tons have a single braze plate heat
exchanger. Units 40-130Tons have two braze plate heat exchangers in parallel arrangement.
Piping between the heat exchanger(s)
Insulation of the heat exchanger(s) and water pipe
• Two temperature sensors to read the inlet/outlet hot water temperature information on the unit control display
Heater on partial heat recovery heat exchanger(s) and water pipe
Manual air vent
Drain pipe
Water circulating inside the heat recovery heat exchanger
should never be used for drinking water, it must be used through an indirect loop to heat or preheat hot water.
Important: The installation must comply with the rules
and legislation applicable at the jobsite location regarding the use of drinkable water.The use of the water circulating in the heat recovery exchanger as drinkable water is not recommended. An intermediate heat exchanger should be used.
The partial heat recovery pump must run at least three
minutes after the partial heat recovery fan control is disabled. During thethree minutes, water flow through the brazed plate heat exchanger will gradually be reduced and the unit can be switched to conventional cooling mode without partial heat recovery fan control.
Partial Heat Recovery Piping
A field installed safety or relief valve on the water side is required with the partial heat recovery to prevent risks resulting from a failure of the thermostat.
A 16 mesh strainer must be installed close to the partial heat recovery heat exchanger entering water line to protect the heat exchanger.
The partial heat recovery water temperature should be
controlled via an external devise such as a 3-way valve or variable speed pump. In addition, a water tank and additional heater is suggested in the partial heat recovery loop.
Insulate water lines and other portions of the heatrecovery water loop to prevent heat loss and potential injury due exposure to a hot surface.
For recommended partial heat recovery piping see
Figure 56, p. 55.
NOTICE:
Proper Water Treatment!
The use of untreated or improperly treated water could
result in scaling, erosion, corrosion, algae or slime. It is recommended that the services of a qualified water treatment specialist be engaged to determine what water treatment, if any, is required.Trane assumes no responsibility for equipment failures which result from untreated or improperly treated water, or saline or brackish water.
NOTICE:
Equipment Damage!
Do not use untreated or improperly treated water in the heat recovery water loop since it will cause inefficient operation and potential damage to the unit such as: reduced heat transfer between water and refrigerant, increased water pressure drop and reduced water flow.
NOTICE:
Equipment Damage!
If the partial heat recovery heat exchanger is drained the heater must be turned off to avoid damaging the partial heater recovery heat exchanger. The heater should only be on when the heat recovery heat exchanger has water in it.
54 CG-SVX17E-EN
Page 55
Installation - Mechanical
Figure 56. Partial Heat Recovery Piping Recommendations
CGAM Unit
Note: In addition to those recommended for field piping, the CGAM unit includes factory installed manual air vent and
water drain valve with partial heat recovery option. See Figure 81, p. 96 through Figure 83, p. 97 for partial heat recovery component locations.
Partial Heat Recovery Freeze Protection
The heat recovery condenser is insulated and a factory-
installed heater is installed and will protect the heat exchangerfrom freezing in ambienttemperatures down to
-20°F (-29°C).
When the ambient temperature drops to approximately
39°F (3.9°C) the thermostat energizes the heaters.
Note: The inlet and outlet piping should be protected
against freezing by one of the following methods:
Install heat tape on all field-installed water piping.
OR
Add freeze inhibit fluid to the partial heat recovery water loop.
CG-SVX17E-EN 55
Page 56
Installation - Mechanical
Partial Heat Recovery Pressure Drop Curves
Figure 57. Partial heat recovery pressure drop curve —
60 Hz
8
7
6
26/30
20
35
40
5
4
3
2
52/60
70
90/100/110
80
PHR Water Pressure Drop (psid)
1
0
0 20406080100
PHR Water Flow Rate (gpm)
120/130
Figure 58. Partial heat recovery pressure drop curve —
50 Hz
12
10
60/70
8
40/52
30/35
6
20/26
4
2
PHR Water Pressure Drop (psid)
0
0 20406080100120
PHR Water Flow Rate (gpm)
80/90/100
110/120
Table 23. Partial heat recovery flow rates — 60 Hz
Size 20 26 30 35 40 52 60 70 80 90 100 110 120 130
Nominal Flow
(a)
Rate Maximum Flow Rate (gpm) 39 39 39 39 79 79 79 79 127 127 127 127 127 127
(a)Water temperature inlet 122°F, outlet 131°F
(gpm)1319182426393750465961708379
Table 24. Partial heat recovery flow rates — 50 Hz
Size 20 26 30 35 40 52 60 70 80 90 100 110 120 130
Nominal Flow
(a)
Rate Maximum Flow Rate (gpm) 39 39 39 39 79 79 79 79 127 127 127 127 127 39
(a)Water temperature inlet 122°F, outlet 131°F
(gpm)1115162021303240394748586511
Note: Partial heat recovery may function at flow rates near zero. However, heat transfer performance is severely reduced
and water flow distribution is poor.
56 CG-SVX17E-EN
Page 57
Installation - Mechanical
Dual High Head Pump Package
Pump package includes: two high head pumps, VFD, expansion vessels, drainage valves, shut-off valves at entering and leaving connections. See Figure 60.
The pump package is single point power integrated into
the chiller unit power with aseparate factorywired control panel.The control of the pump is integrated into the chiller controller.
Important: When pump package is selected, the chiller
MUST control the pumps.
The CH530 displays evaporator pump starts and run-
times. Freeze protection down to an ambient of
-20°F (-29°C) is included as standard.The cold parts of the
pump package will also be insulated. Designed with one redundant pump, the chiller controls both pumps through a lead/lag and failure/recovery functionality.
A variable speed drive is installed in an additional panel to control the pump.The inverter should be adjusted by the customer upon start up to balance the system flow and head requirements.The purpose is to save on wasted pump energy caused by a traditional balancing valve.
Note: Speed command is also available for customer-
provided variable flow input.
Figure 59. Field water piping pump package unit
3
CGAM Unit with Pump Package Option
1 - Bypass Valve 2 - Isolation Valve 3 - Vibration Eliminators A - Isolate unit for initial water loop cleaning
B
3
2
1
2
CUSTOMER PIPING
Building/ Process Load
A
Table 25. Field water piping components - unit with
pump package option
Item Description
1 Bypass Valve 2 Isolator Valve 3 Vibration Eliminator A Isolate unit for initial water loop cleaning B See Figure 60 for CGAM pump package unit schematic.
Figure 60. Pump package unit schematic
4
INLET
C
OUTLET
Insulated Water Line
Water Line
Table 26. Pump package components
Item Description Item Description Item Description
1 Centrifugal Pump (Dual pumps std) 9 Automatic Air Vent Pi Gauge 2 Water Strainer 10 Manual Air Bleed FT Water Flow Switch 3 Butterfly Valve 11 Drain Valve T1 Evap Water Inlet Temp Sensor 4 Inverter 12 Water Heater T2 Evap Water Outlet Temp Sensor 5 Valve for Pressure Point 13 Buffer Tank (Optional) A Optional Buffer Tank 6 Expansion Tank B Insulated Pump Box 7N/A C Brazed plate differential pressure gauge and piping not supplied.
8 Evaporator heat exchanger
Must account for water head height difference when calculating brazed plate pressure differential.
CONNECTIONS TO UNIT
CG-SVX17E-EN 57
Page 58
Installation - Mechanical
Pressure Drop Information - Units with Optional Pump Package
Water only
Factory Installed Pump Package - Pump Curves. Figure 61 through Figure 64, p. 59 show manufacturer pump
curves for factory-installed pump package.
Figure 61. Pump curve - 20-52T - water only
Figure 62. Pump curve - 60-70T - water only
58 CG-SVX17E-EN
Page 59
Installation - Mechanical
Figure 63. Pump curve - 80-110T - water only
Figure 64. Pump curve - 120-130T - water only
CG-SVX17E-EN 59
Page 60
Installation - Mechanical
Unit Component Pressure Drop. Figure 65 shows the pressure drop values for unit components.
Figure 65. Unit component pressure drop - water only
100
10
040
026/030
035
052
020
PRESSURE HEAD (Ft. of H2O)
1
10 100 1000
070
080
090
100
110/120
060
FLOW RATE (GPM)
130
System Head Pressure. See Figure 66 for the system head pressure available.
Note: System Head Pressure = Pump Pressure - Component Pressure)
Figure 66. CGAM pump package available head pressure - water only
140
120
100
80
60
PRESSURE HEAD (Ft. of H2O)
40
20
0
0 50 100 150 200 250 300 350 400 450 500
020
026/030
035
040
052
060
FLOW RATE (GPM)
080
090
100
070
110
130
120
60 CG-SVX17E-EN
Page 61
Installation - Mechanical
Unit with Optional Pump Package Systems ­Glycol
If using glycol in system, apply adjustment factors to pressure drops per the following formulas:
Glycol Pump Head =
Water Pump Head x Pump Adjustment Factor
Glycol Component Pressure Drop = Components Pressure Drop x Component Adjustment F
actor
Note:
F
or Water Pump Head, see Figure 61, p. 58 through
Figure 64, p. 59
For Component Pressure Drop, see Figure 65, p. 60
For Pump and Component Adjustment Factors, see
Table 27
Table 27. Brine adjustment factors
Ethylene Glycol Propylene Glycol
Percentage
Glycol
5% 1.004 1.085 1.004 1.165 10% 1.009 1.120 1.009 1.200 15% 1.015 1.155 1.015 1.235 20% 1.021 1.190 1.021 1.270 25% 1.028 1.235 1.028 1.300 30% 1.034 1.280 1.034 1.330 35% 1.040 1.345 1.040 1.365 40% 1.046 1.410 1.046 1.400 45% - - 1.051 1.460
Adjustment for Adjustment for
Pump Components Pump Components
Pump Package Requirements
The following requirements must be met for proper
operation of pump package:
Maximum working pressure 150 psig
Fluid type shown in Table 28
Table 28. Working fluid
Fluid Type Fluid Percent (of weight)
Water 100% Ethylene Glycol 0-40% Propylene Glycol 0-45%
Customer pressure drop must not exceed pump kage head pressures found in section “General
pac
Information,” p. 9.
If buffer tank option is selected, customer water
v
olume must not exceed the values in Table 29, p. 62 and Table 30, p. 63. User volume expansion capacity is defined as theadditional expansion volume usable for the
customer if the chiller is installed with pump
package and buffer tank options.
CG-SVX17E-EN 61
Page 62
Installation - Mechanical
Expansion Tank - Maximum Loop Volume
Expansion tanks supplied as part of the pump package option will allow loop expansion due to ambient fluctuations for maximum loop volumes shown in
Table 29 and Table 30, p. 63.
Note: Negative values indicate that a field-installed tank
Important: Chilled waterside pressure relief valve is
designed to open at 226 ft. If relief valve is opening at lower pressures, verify system has sufficient expansion tank volume for the water and/or glycol solution used.
is required to cover the expansion due to ambient fluctuations of the fluid in the chiller.
Table 29. Maximum loop volume - gallons (external to the chiller)
Maximum Ambient = 100°F Maximum Ambient = 115°F
% Ethylene Glycol % Propylene Glycol % Ethylene Glycol % Propylene Glycol
Size Water 10 20 30 40 10 20 30 40 45 Water 10 20 30 40 10 20 30 40 45
WITHOUT BUFFER TANK 020 479 433 296 199 148 292 198 139 108 98 317 293 216 155 120 222 155 112 87 80 026 479 433 296 199 148 292 198 139 108 98 317 293 216 155 120 222 155 112 87 80 030 479 433 296 199 148 292 198 139 108 98 317 293 216 155 120 222 155 112 87 80 035 479 433 296 199 148 292 198 139 108 98 317 293 216 155 120 222 155 112 87 80 040 474 428 291 194 143 286 193 134 102 93 312 287 211 150 114 216 149 106 82 75 052 474 428 291 194 143 286 193 134 102 93 312 287 211 150 114 216 149 106 82 75 060 474 428 291 194 143 286 193 134 102 93 312 287 211 150 114 216 149 106 82 75 070 474 428 291 194 143 286 193 134 102 93 312 287 211 150 114 216 149 106 82 75 080 626 565 383 253 185 377 252 174 131 119 411 378 276 194 147 283 194 136 104 95 090 626 565 383 253 185 377 252 174 131 119 411 378 276 194 147 283 194 136 104 95 100 626 565 383 253 185 377 252 174 131 119 411 378 276 194 147 283 194 136 104 95 110 626 565 383 253 185 377 252 174 131 119 411 378 276 194 147 283 194 136 104 95 120 626 565 383 253 185 377 252 174 131 119 411 378 276 194 147 283 194 136 104 95 130 626 565 383 253 185 377 252 174 131 119 411 378 276 194 147 283 194 136 104 95
WITH BUFFER TANK 020 335 289 152 55 4 148 54 -5 -36 -46 173 149 72 11 -24 78 11 -32 -57 -64 026 335 289 152 55 4 148 54 -5 -36 -46 173 149 72 11 -24 78 11 -32 -57 -64 030 335 289 152 55 4 148 54 -5 -36 -46 173 149 72 11 -24 78 11 -32 -57 -64 035 335 289 152 55 4 148 54 -5 -36 -46 173 149 72 11 -24 78 11 -32 -57 -64 040 338 292 155 58 7 150 57 -2 -34 -43 176 151 75 14 -22 80 13 -30 -54 -61 052 338 292 155 58 7 150 57 -2 -34 -43 176 151 75 14 -22 80 13 -30 -54 -61 060 338 292 155 58 7 150 57 -2 -34 -43 176 151 75 14 -22 80 13 -30 -54 -61 070 338 292 155 58 7 150 57 -2 -34 -43 176 151 75 14 -22 80 13 -30 -54 -61 080 470 409 226 97 29 220 96 17 -25 -38 254 221 119 38 -9 127 38 -20 -52 -62 090 470 409 226 97 29 220 96 17 -25 -38 254 221 119 38 -9 127 38 -20 -52 -62 100 425 364 181 52 -16 175 51 -28 -70 -83 210 177 74 -7 -54 82 -7 -65 -97 -107 110 425 364 181 52 -16 175 51 -28 -70 -83 210 177 74 -7 -54 82 -7 -65 -97 -107 120 425 364 181 52 -16 175 51 -28 -70 -83 210 177 74 -7 -54 82 -7 -65 -97 -107 130 425 364 181 52 -16 175 51 -28 -70 -83 210 177 74 -7 -54 82 -7 -65 -97 -107
62 CG-SVX17E-EN
Page 63
Installation - Mechanical
Table 30. Maximum loop volume - liters (external to the chiller)
Maximum Ambient = 100°F Maximum Ambient = 115°F
% Ethylene Glycol % Propylene Glycol % Ethylene Glycol % Propylene Glycol
Size Water 10 20 30 40 10 20 30 40 45 Water 10 20 30 40 10 20 30 40 45
WITHOUT BUFFER TANK 020 1813 1639 1121 754 561 1104 751 528 407 372 1201 1108 818 587 453 839 586 422 331 303 026 1813 1639 1121 754 561 1104 751 528 407 372 1201 1108 818 587 453 839 586 422 331 303 030 1813 1639 1121 754 561 1104 751 528 407 372 1201 1108 818 587 453 839 586 422 331 303 035 1813 1639 1121 754 561 1104 751 528 407 372 1201 1108 818 587 453 839 586 422 331 303 040 1793 1619 1101 734 541 1084 731 508 387 352 1181 1088 798 567 433 819 566 402 311 283 052 1793 1619 1101 734 541 1084 731 508 387 352 1181 1088 798 567 433 819 566 402 311 283 060 1793 1619 1101 734 541 1084 731 508 387 352 1181 1088 798 567 433 819 566 402 311 283 070 1793 1619 1101 734 541 1084 731 508 387 352 1181 1088 798 567 433 819 566 402 311 283 080 2370 2139 1448 958 701 1426 955 657 496 449 1555 1430 1044 736 558 1072 735 516 394 358 090 2370 2139 1448 958 701 1426 955 657 496 449 1555 1430 1044 736 558 1072 735 516 394 358 100 2370 2139 1448 958 701 1426 955 657 496 449 1555 1430 1044 736 558 1072 735 516 394 358 110 2370 2139 1448 958 701 1426 955 657 496 449 1555 1430 1044 736 558 1072 735 516 394 358 120 2370 2139 1448 958 701 1426 955 657 496 449 1555 1430 1044 736 558 1072 735 516 394 358 130 2370 2139 1448 958 701 1426 955 657 496 449 1555 1430 1044 736 558 1072 735 516 394 358
WITH BUFFER TANK 020 1268 1094 576 209 16 559 206 -17 -138 -173 656 563 273 42 -92 294 41 -123 -214 -242 026 1268 1094 576 209 16 559 206 -17 -138 -173 656 563 273 42 -92 294 41 -123 -214 -242 030 1268 1094 576 209 16 559 206 -17 -138 -173 656 563 273 42 -92 294 41 -123 -214 -242 035 1268 1094 576 209 16 559 206 -17 -138 -173 656 563 273 42 -92 294 41 -123 -214 -242 040 1278 1104 586 219 26 569 216 -7 -128 -163 666 573 283 52 -82 304 51 -113 -204 -232 052 1278 1104 586 219 26 569 216 -7 -128 -163 666 573 283 52 -82 304 51 -113 -204 -232 060 1278 1104 586 219 26 569 216 -7 -128 -163 666 573 283 52 -82 304 51 -113 -204 -232 070 1278 1104 586 219 26 569 216 -7 -128 -163 666 573 283 52 -82 304 51 -113 -204 -232 080 1778 1547 856 366 109 834 363 65 -96 -143 963 838 452 144 -34 480 143 -76 -198 -234 090 1778 1547 856 366 109 834 363 65 -96 -143 963 838 452 144 -34 480 143 -76 -198 -234 100 1608 1377 686 196 -61 664 193 -105 -266 -313 793 668 282 -26 -204 310 -27 -246 -368 -404 110 1608 1377 686 196 -61 664 193 -105 -266 -313 793 668 282 -26 -204 310 -27 -246 -368 -404 120 1608 1377 686 196 -61 664 193 -105 -266 -313 793 668 282 -26 -204 310 -27 -246 -368 -404 130 1608 1377 686 196 -61 664 193 -105 -266 -313 793 668 282 -26 -204 310 -27 -246 -368 -404
CG-SVX17E-EN 63
Page 64
Installation - Electrical
General Recommendations
All wiring must comply with local codes and the National Electric Code.Typical field wiring diagrams are included at the end of the manual. Minimum circuit ampacities and other unit electricaldata are on theunit nameplate. See the unit order specifications for actual electrical data. Specific electrical schematics and connection diagrams are shipped with the unit.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
NOTICE:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors could result in equipment damage.
NOTICE:
Equipment Damage!
Do not allow conduit to interfere with other components, structural members or equipment. Control voltage (115V) wiring in conduit must be separate from conduit carrying low voltage (<30V) wiring.To prevent control malfunctions, do not run low voltage wiring (<30V) in conduit with conductors carrying more than 30 volts.
64 CG-SVX17E-EN
Page 65
Installation - Electrical
Electrical Data Tables
Table 31. Electrical Data - 60 Hz
Unit Size Rated
Power
208/60/3 1 2 2 1 6.2 39-39 267-267 106 125 122 150 230/60/3 1 2 2 1 6.7 39-39 267-267 106 125 122 150 380/60/3 1 2 2 1 3.7 22-22 160-160 60 80 n/a
20
460/60/3 1 2 2 1 3.2 19-19 142-142 51 60 64 80 575/60/3 1 2 2 1 2.6 15-15 103-103 42 50 52 60 208/60/3 1 2 2 1 6.2 51-51 315-315 131 175 148 175 230/60/3 1 2 2 1 6.7 44-44 315-315 117 150 134 175 380/60/3 1 2 2 1 3.7 26-26 177-177 69 90 n/a
26
460/60/3 1 2 2 1 3.2 21-21 158-158 56 70 69 80 575/60/3 1 2 2 1 2.6 19-19 126-126 50 60 59 70 208/60/3 1 2 3 1 6.2 53-53 320-320 143 175 160 200 230/60/3 1 2 3 1 6.7 54-54 320-320 146 175 153 200 380/60/3 1 2 3 1 3.7 31-31 210-210 83 110 n/a
30
460/60/3 1 2 3 1 3.2 26-26 160-160 70 90 83 100 575/60/3 1 2 3 1 2.6 21-21 135-135 57 70 66 80 208/60/3 1 2 3 1 6.2 53-74 320-485 169 225 186 250 230/60/3 1 2 3 1 6.7 54-67 320-485 162 225 175 225 380/60/3 1 2 3 1 3.7 31-40 210-260 94 125 n/a
35
460/60/3 1 2 3 1 3.2 26-33 160-215 79 110 92 110 575/60/3 1 2 3 1 2.6 21-26 135-175 64 90 73 90 208/60/3 2 4 4 1 6.2 39-39/39-39 267-267/267-267 197 225 214 250 230/60/3 2 4 4 1 6.7 39-39/39-39 267-267/267-267 198 225 214 250 380/60/3 2 4 4 1 3.7 22-22/22-22 160-160/160-160 112 125 n/a
40
460/60/3 2 4 4 1 3.2 19-19/19-19 142-142/142-142 95 110 108 125 575/60/3 2 4 4 1 2.6 15-15/15-15 103-103/103-103 79 90 89 100 208/60/3 2 4 4 1 6.2 51-51/51-51 315-315/315-315 246 250 263 300 230/60/3 2 4 4 1 6.7 44-44/44-44 315-315/315-315 220 250 237 250 380/60/3 2 4 4 1 3.7 26-26/26-26 177-177/177-177 129 150 n/a
52
460/60/3 2 4 4 1 3.2 21-21/21-21 158-158/158-158 106 125 119 125 575/60/3 2 4 4 1 2.6 19-19/19-19 126-126/126-126 93 110 103 110 208/60/3 2 4 6 1 6.2 53-53/53-53 320-320/320-320 269 300
380/60/3 2 4 6 1 3.7 31-31/31-31 210-210/210-210 157 175
60
460/60/3 2 4 6 1 3.2 26-26/26-26 160-160/160-160 132 150 148 150 575/60/3 2 4 6 1 2.6 21-21/21-21 135-135/135-135 107 125 118 125 208/60/3 2 4 6 1 6.2 53-74/74-54 320-485/485-320 316 350
380/60/3 2 4 6 1 3.7 31-40/40-31 210-260/260-210 177 200
70
460/60/3 2 4 6 1 3.2 26-33/33-26 160-215/215-160 148 175 164 175 575/60/3 2 4 6 1 2.6 21-26/26-21 135-175/175-135 120 125 131 150
Number
Circuits
Qty
Comp
Qty
Fans
Motor
Power
(kw)
Cond
Fan FLA
Compressor
RLA¹
Compressor
LRA²
Fan
No pump Pump
MCA MOPD MCA MOP
n/a230/60/3 2 4 6 1 6.7 50-50/50-50 320-320/320-320 259 300
n/a230/60/3 2 4 6 1 6.7 50-67/67-50 350-485/485-350 297 350
CG-SVX17E-EN 65
Page 66
Installation - Electrical
Table 31. Electrical Data - 60 Hz
Unit Size Rated
Power
208/60/3 2 4 6 1 6.2 74-74/74-74 485-485/485-485 358 400 388 450 230/60/3 2 4 6 1 6.7 67-67/67-67 485-485/485-485 331 350 362 400 380/60/3 2 4 6 1 3.7 40-40/40-40 260-260/260-260 194 225 n/a
80
460/60/3 2 4 6 1 3.2 33-33/33-33 215-215/215-215 162 175 186 200 575/60/3 2 4 6 1 2.6 26-26/26-26 175-175/175-175 131 150 150 175 208/60/3 2 4 6 1 6.2 74-91/91-74 485-560/560-485 397 450 428 500 230/60/3 2 4 6 1 6.7 67-85/85-67 485-560/560-485 370 450 401 450 380/60/3 2 4 6 1 3.7 40-55/55-40 260-310/310-260 227 275 n/a
90
460/60/3 2 4 6 1 3.2 33-42/42-33 215-260/260-215 182 200 206 225 575/60/3 2 4 6 1 2.6 26-34/34-26 175-210/210-175 149 175 168 200 208/60/3 2 4 8 1 6.2 91-91/91-91 560-560/560-560 444 500 475 500 230/60/3 2 4 8 1 6.7 85-85/85-85 560-560/560-560 418 500 449 500 380/60/3 2 4 8 1 3.7 55-55/55-55 310-310/310-310 263 300 n/a
100
460/60/3 2 4 8 1 3.2 42-42/42-42 260-260/260-260 206 225 230 250 575/60/3 2 4 8 1 2.6 34-34/34-34 210-210/210-210 169 200 188 200 208/60/3 2 4 8 1 6.2 91-110/110-91 560-680/680-560 485 500 516 600 230/60/3 2 4 8 1 6.7 85-109/109-85 560-680/680-560 473 500 504 600 380/60/3 2 4 8 1 3.7 55-60/60-55 310-360/360-310 275 300 n/a
110
460/60/3 2 4 8 1 3.2 42-51/51-42 260-320/320-260 226 250 250 250 575/60/3 2 4 8 1 2.6 34-39/39-34 210-235/235-210 179 200 198 225 208/60/3 2 4 8 1 6.2 110-110/110-110 680-680/680-680 521 600 n/a 230/60/3 2 4 8 1 6.7 109-109/109-109 680-680/680-680 522 600 568 600 380/60/3 2 4 8 1 3.7 60-60/60-60 360-360/360-360 285 300 n/a
120
460/60/3 2 4 8 1 3.2 51-51/51-51 320-320/320-320 244 250 268 300 575/60/3 2 4 8 1 2.6 39-39/39-39 235-235/235-235 188 225 207 225
208/60/3 2 6 10 1 6.2 74-74-91/91-74-74
230/60/3 2 6 10 1 6.7 67-67-85/85-67-67
380/60/3 2 6 10 1 3.7 40-40-55/55-40-40
130
460/60/3 2 6 10 1 3.2 33-33-42/42-33-33
575/60/3 2 6 10 1 2.6 26-26-34/34-26-26
1. RLA - Rated Load Amps - Rated in accordance with UL Standard 1995.
2. LRA - Locked Rotor Amps - Based on full winding starts.
3. MCA - Minimum Circuit Ampacity - 125 percent of largest compressor RLA plus 100 percent of all other loads.
4. MOPD or Max fuse size - 225 percent of the largest compressor RLA plus all other loads.
5. Local codes may take precedence.
6. Voltage Utilization Range: +/- 10% of rated voltage Rated voltage (use range): 208/60/3 (187.2-228.8), 230/60/3(208-254), 380/60/3 (342-418), 460/60/3 (414-506), 575/60/3 (516-633)
7. One separate 120/60/1, 15 amp customer provided power connection is required to power the heaters.
8. n/a - not available
Number
Circuits
Qty
Comp
Qty
Fans
Motor
Power
(kw)
Cond
Fan FLA
Compressor
RLA¹
Compressor
LRA²
485-485-560/
560-485-485
485-485-560/
560-485-485
260-260-310/
310-260-260
215-215-260/
260-215-215
175-175-210/
210-175-175
Fan
No pump Pump
MCA MOPD MCA MOP
569 600 n/a
531 600 578 600
321 350 n/a
261 300 285 300
212 225 231 250
66 CG-SVX17E-EN
Page 67
Installation - Electrical
Table 32. Lug Range Size - 60 Hz
No Pump Pump
Unit Size Rated Power
208/60/3 #6 - 350 MCM #14 - 1/0 #14 - 1/0 #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM 230/60/3 #6 - 350 MCM #14 - 1/0 #14 - 1/0 #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM
20
26
30
35
40
52
60
70
1. Optional circuit breaker and high fault circuit breaker.
2. Will accept two conduits per phase in this size.
3. Copper wire only, based on nameplate Minimum Circuit Ampacity (MCA).
4. Data shown for circuit one. The second circuit is always the same.
5. n/a - not available
380/60/3 #6 - 350 MCM #14 - 1/0 #14 - 1/0 460/60/3 #6 - 350 MCM #14 - 1/0 #14 - 1/0 #6 - 350 MCM #14 - 1/0 #14 - 1/0 575/60/3 #6 - 350 MCM #14 - 1/0 n/a #6 - 350 MCM #14 - 1/0 n/a 208/60/3 #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM 230/60/3 #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM 380/60/3 #6 - 350 MCM #14 - 1/0 #14 - 1/0 n/a n/a n/a 460/60/3 #6 - 350 MCM #14 - 1/0 #14 - 1/0 #6 - 350 MCM #14 - 1/0 #14 - 1/0 575/60/3 #6 - 350 MCM #14 - 1/0 n/a #6 - 350 MCM #14 - 1/0 n/a 208/60/3 #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM 230/60/3 #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM 380/60/3 #6 - 350 MCM #14 - 1/0 #14 - 1/0 n/a n/a n/a 460/60/3 #6 - 350 MCM #14 - 1/0 #14 - 1/0 #6 - 350 MCM #14 - 1/0 #14 - 1/0 575/60/3 #6 - 350 MCM #14 - 1/0 n/a #6 - 350 MCM #14 - 1/0 n/a 208/60/3 #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM 230/60/3 #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM 380/60/3 #6 - 350 MCM #14 - 1/0 #14 - 1/0 n/a n/a n/a 460/60/3 #6 - 350 MCM #14 - 1/0 #14 - 1/0 #6 - 350 MCM #14 - 1/0 #14 - 1/0 575/60/3 #6 - 350 MCM #14 - 1/0 n/a #6 - 350 MCM #14 - 1/0 n/a 208/60/3 #4 - 500 MCM 3/0 - 500 MCM² 3/0 - 500 MCM² #4 - 500 MCM 3/0 - 500 MCM² 3/0 - 500 MCM² 230/60/3 #4 - 500 MCM 3/0 - 500 MCM² 3/0 - 500 MCM² #4 - 500 MCM 3/0 - 500 MCM² 3/0 - 500 MCM² 380/60/3 #4 - 500 MCM #6 - 350 MCM #6 - 350 MCM n/a n/a n/a 460/60/3 #4 - 500 MCM #6 - 350 MCM #6 - 350 MCM #4 - 500 MCM #6 - 350 MCM #6 - 350 MCM 575/60/3 #4 - 500 MCM #6 - 350 MCM n/a #4 - 500 MCM #6 - 350 MCM n/a 208/60/3 #4 - 500 MCM 3/0 - 500 MCM² 3/0 - 500 MCM² #4 - 500 MCM 3/0 - 500 MCM² 3/0 - 500 MCM² 230/60/3 #4 - 500 MCM 3/0 - 500 MCM² 3/0 - 500 MCM² #4 - 500 MCM 3/0 - 500 MCM² 3/0 - 500 MCM² 380/60/3 #4 - 500 MCM #6 - 350 MCM #6 - 350 MCM n/a 460/60/3 #4 - 500 MCM #6 - 350 MCM #6 - 350 MCM #4 - 500 MCM #6 - 350 MCM #6 - 350 MCM 575/60/3 #4 - 500 MCM #6 - 350 MCM n/a #4 - 500 MCM #6 - 350 MCM n/a 208/60/3 #4 - 500 MCM 3/0 - 500 MCM² 3/0 - 500 MCM²
380/60/3 #4 - 500 MCM #6 - 350 MCM #6 - 350 MCM 460/60/3 #4 - 500 MCM #6 - 350 MCM #6 - 350 MCM #4 - 500 MCM #6 - 350 MCM #6 - 350 MCM 575/60/3 #4 - 500 MCM #6 - 350 MCM n/a #4 - 500 MCM #6 - 350 MCM n/a 208/60/3 #4 - 500 MCM 3/0 - 500 MCM² 3/0 - 500 MCM²
380/60/3 #4 - 500 MCM 3/0 - 500 MCM² 3/0 - 500 MCM² 460/60/3 #4 - 500 MCM #6 - 350 MCM #6 - 350 MCM #4 - 500 MCM #6 - 350 MCM #6 - 350 MCM 575/60/3 #4 - 500 MCM #6 - 350 MCM n/a #4 - 500 MCM #6 - 350 MCM n/a
Blocks
Terminal
Std Fault
Ckt Breaker¹
High Fault
Ckt Breaker¹
Terminal
Blocks
Std Fault
Ckt Breaker¹
n/a230/60/3 #4 - 500 MCM 3/0 - 500 MCM² 3/0 - 500 MCM²
n/a230/60/3 #4 - 500 MCM 3/0 - 500 MCM² 3/0 - 500 MCM²
High Fault
Ckt Breaker¹
CG-SVX17E-EN 67
Page 68
Installation - Electrical
Table 32. Lug Range Size - 60 Hz
No Pump Pump
Unit Size Rated Power
208/60/3 #4 - 500 MCM 3/0 - 500 MCM² 3/0 - 500 MCM² #4 - 500 MCM² 3/0-500 MCM² 3/0-500 MCM² 230/60/3 #4 - 500 MCM 3/0 - 500 MCM² 3/0 - 500 MCM² #4 - 500 MCM² 3/0-500 MCM² 3/0-500 MCM²
80
90
100
110
120
130
1. Optional circuit breaker and high fault circuit breaker.
2. Will accept two conduits per phase in this size.
3. Copper wire only, based on nameplate Minimum Circuit Ampacity (MCA).
4. Data shown for circuit one. The second circuit is always the same.
5. n/a - not available
380/60/3 #4 - 500 MCM 3/0 - 500 MCM² 3/0 - 500 MCM² n/a 460/60/3 #4 - 500 MCM #6 - 350 MCM #6 - 350 MCM #4 - 500 MCM 3/0-500 MCM² 3/0-500 MCM² 575/60/3 #4 - 500 MCM #6 - 350 MCM n/a #4 - 500 MCM #6 - 350 MCM n/a 208/60/3 #4 - 500 MCM² 3/0 - 500 MCM² 3/0 - 500 MCM² #4 - 500 MCM² 3/0-500 MCM² 3/0-500 MCM² 230/60/3 #4 - 500 MCM² 3/0 - 500 MCM² 3/0 - 500 MCM² #4 - 500 MCM² 3/0-500 MCM² 3/0-500 MCM² 380/60/3 #4 - 500 MCM 3/0 - 500 MCM² 3/0 - 500 MCM² n/a 460/60/3 #4 - 500 MCM 3/0 - 500 MCM² 3/0 - 500 MCM² #6 - 350 MCM 3/0 - 500 MCM² 3/0 - 500 MCM² 575/60/3 #4 - 500 MCM #6 - 350 MCM n/a #6 - 350 MCM #6 - 350 MCM n/a 208/60/3 #4 - 500 MCM² 3/0 - 500 MCM² 3/0 - 500 MCM² #6 - 350 MCM 3/0-500 MCM² 3/0-500 MCM² 230/60/3 #4 - 500 MCM² 3/0 - 500 MCM² 3/0 - 500 MCM² #6 - 350 MCM 3/0-500 MCM² 3/0-500 MCM² 380/60/3 #4 - 500 MCM 3/0 - 500 MCM² 3/0 - 500 MCM² n/a 460/60/3 #4 - 500 MCM 3/0 - 500 MCM² 3/0 - 500 MCM² #6 - 350 MCM 3/0 - 500 MCM² 3/0 - 500 MCM² 575/60/3 #4 - 500 MCM 3/0 - 500 MCM² n/a #6 - 350 MCM 3/0 - 500 MCM² n/a 208/60/3 #4 - 500 MCM² 3/0 - 500 MCM² 3/0 - 500 MCM² #6 - 350 MCM 3/0-500 MCM² 3/0-500 MCM² 230/60/3 #4 - 500 MCM² 3/0 - 500 MCM² 3/0 - 500 MCM² #6 - 350 MCM 3/0-500 MCM² 3/0-500 MCM² 380/60/3 #4 - 500 MCM 3/0 - 500 MCM² 3/0 - 500 MCM² n/a 460/60/3 #4 - 500 MCM 3/0 - 500 MCM² 3/0 - 500 MCM² #6 - 350 MCM 3/0 - 500 MCM² 3/0 - 500 MCM² 575/60/3 #4 - 500 MCM 3/0 - 500 MCM² n/a #6 - 350 MCM 3/0 - 500 MCM² n/a 208/60/3 #4 - 500 MCM² 3/0 - 500 MCM² 3/0 - 500 MCM² n/a 230/60/3 #4 - 500 MCM² 3/0 - 500 MCM² 3/0 - 500 MCM² #6 - 350 MCM 3/0-500 MCM² 3/0-500 MCM² 380/60/3 #4 - 500 MCM 3/0 - 500 MCM² 3/0 - 500 MCM² n/a 460/60/3 #4 - 500 MCM 3/0 - 500 MCM² 3/0 - 500 MCM² #6 - 350 MCM 3/0 - 500 MCM² 3/0 - 500 MCM² 575/60/3 #4 - 500 MCM 3/0 - 500 MCM² n/a #6 - 350 MCM 3/0 - 500 MCM² n/a 208/60/3 #4 - 500 MCM² 3/0 - 500 MCM² 3/0 - 500 MCM² n/a 230/60/3 #4 - 500 MCM² 3/0 - 500 MCM² 3/0 - 500 MCM² #4 - 500 MCM² 3/0 - 500 MCM² 3/0 - 500 MCM² 380/60/3 #4 - 500 MCM 3/0 - 500 MCM² 3/0 - 500 MCM² n/a 460/60/3 #4 - 500 MCM 3/0 - 500 MCM² 3/0 - 500 MCM² #4 - 500 MCM 3/0 - 500 MCM² 3/0 - 500 MCM² 575/60/3 #4 - 500 MCM 3/0 - 500 MCM² n/a #4 - 500 MCM 3/0 - 500 MCM² n/a
Blocks
Terminal
Std Fault
Ckt Breaker¹
High Fault
Ckt Breaker¹
Terminal
Blocks
Std Fault
Ckt Breaker¹
High Fault
Ckt Breaker¹
68 CG-SVX17E-EN
Page 69
Installation - Electrical
Table 33. Electrical Data - 50Hz
Unit Size
20 26 30 35 40 52 60 70 80
90 100 110 120
1. RLA - Rated Load Amps - Rated in accordance with UL Standard 1995.
2. LRA - Locked Rotor Amps - Based on full winding starts.
3. MCA - Minimum Circuit Ampacity - 125 percent of largest compressor RLA plus 100 percent of all other loads.
4. MOPD or Max fuse size - 225 percent of the largest compressor RLA plus all other loads.
5. Local codes may take precedence.
6. Voltage Utilization Range: +/- 10% of rated voltage Rated voltage (use range):
7. One separate 120/50/1, 15 amp customer provided power connection is required to power the heaters.
8. n/a - not available
9. Pump package not available with 50 Hz units.
Rated
Power
400/50/3 1 2 2 1 2.4 17-17 142-142 46 60 400/50/3 1 2 2 1 2.4 21-21 158-158 55 70 400/50/3 1 2 3 1 2.4 27-27 160-160 71 90 400/50/3 1 2 3 1 2.4 27-33 160-215 79 110 400/50/3 2 4 4 1 2.4 17-17/17-17 142-142/142-142 85 100 400/50/3 2 4 4 1 2.4 21-21/21-21 158-158/158-158 102 110 400/50/3 2 4 6 1 2.4 27-27/27-27 160-160/160-160 133 150 400/50/3 2 4 6 1 2.4 27-33/33-27 160-215/215-160 147 175 400/50/3 2 4 6 1 2.4 33-33/33-33 215-215/215-215 160 175 400/50/3 2 4 6 1 2.4 33-43/43-33 215-260/260-215 181 200 400/50/3 2 4 8 1 2.4 43-43/43-43 260-260/260-260 204 225 400/50/3 2 4 8 1 2.4 43-47/47-43 260-320/260-320 214 250 400/50/3 2 4 8 1 2.4 47-47/47-47 320-320/320-320 223 250
Number
Circuits
400/50/3 (360-440)
Qty
Comp
Qty
Fans
Fan Motor
Power (kW)
Cond Fan
FLA
Compressor
RLA¹ ²
Compressor
LRA¹ ³ MCA MOPD
Table 34. Lug Size Range - 50 Hz
Unit Size Rated Power Terminal Blocks
20 26 30 35 40 52 60 70 80
90 100 110 120
1. Optional circuit breaker and high fault circuit breaker.
2. Will accept two conduits per phase in this size.
3. Copper wire only, based on nameplate Minimum Circuit Ampacity (MCA).
4. Data shown for circuit one. The second circuit is always the same.
5. n/a - not available
400/50/3 #6 - 350 MCM #14 - 1/0 #14 - 1/0 400/50/3 #6 - 350 MCM #14 - 1/0 #14 - 1/0 400/50/3 #6 - 350 MCM #14 - 1/0 #14 - 1/0 400/50/3 #6 - 350 MCM #14 - 1/0 #14 - 1/0 400/50/3 #4 - 500 MCM #6 - 350 MCM #6 - 350 MCM 400/50/3 #4 - 500 MCM #6 - 350 MCM #6 - 350 MCM 400/50/3 #4 - 500 MCM #6 - 350 MCM #6 - 350 MCM 400/50/3 #4 - 500 MCM #6 - 350 MCM #6 - 350 MCM 400/50/3 #4 - 500 MCM #6 - 350 MCM #6 - 350 MCM 400/50/3 #4 - 500 MCM #6 - 350 MCM #6 - 350 MCM 400/50/3 #4 - 500 MCM 3/0 - 500 MCM² 3/0 - 500 MCM² 400/50/3 #4 - 500 MCM 3/0 - 500 MCM² 3/0 - 500 MCM² 400/50/3 #4 - 500 MCM 3/0 - 500 MCM² 3/0 - 500 MCM²
Std Fault
Ckt Breaker¹
High Fault
Ckt Breaker¹
CG-SVX17E-EN 69
Page 70
Installation - Electrical
Installer-Supplied Components
Customer wiring interface connections are shown in the electrical schematics and connection diagrams that are shipped with the unit.The installer must provide the following components if not ordered with the unit:
Power supply wiring (in conduit) for all field-wired connections.
All control (interconnecting) wiring (in conduit) for field supplied devices.
Circuit breakers.
Power Supply Wiring
WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards.To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
All power supply wiring must be sized and selected accordingly by the project engineer in accordance with NECTable 310-16.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
All wiring must comply with local codes and the National Electrical Code.The installing (or electrical) contractor must provide and install the system interconnecting wiring, as well as the power supply wiring. It must be properly sized and equipped with the appropriate fused disconnect switches.
The type and installation location(s) of the fused
disconnects must comply with all applicable codes.
NOTICE:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors could result in equipment damage.
conduits and connected to the terminal blocks or HACR type breakers. Refer to Table 35.
To provide proper phasing of 3-phase input, make
connections as shown in field wiring diagrams and as stated on the WARNING label in the starter panel. For additional information on proper phasing, refer to “Unit
Voltage Phasing,” p. 122. Proper equipment ground must
be provided to each ground connection in the panel (one for each customer-supplied conductor per phase).
The high voltage field-provided connections are made
through knockouts on the right side of the panel.The low voltage connections are made through the left side of the panel (Figure 35). Additional grounds may be required for each 115 volt power supply to the unit. Green lugs are provided for 115V customer wiring.
Control Power Supply
The unit is equipped with a control power transformer; it
is not necessary to provide additional control power voltage to the unit. No other loads should be connected to the control power transformer.
All units are factory-connected for appropriate labeled
voltages.
NOTICE:
Equipment Damage!
Control panel main processor does not check for loss of power to the heat tape nor does it verify thermostat operation. A qualified technician must verify power to the heat tape and confirm operation of the heat tape thermostat to avoid catastrophic damage to the evaporator or partial heat recovery heat exchanger.
Heater Power Supply
For units with freeze protection selected (model number digit 18 is “1”), the evaporator shell is insulated from ambient air and protected from freezing temperatures by a thermostatically-controlled immersion heaters. When the ambient temperature drops to approximately 37°F (2.8°C) the thermostat energizes the heaters.The heaters will provide protection from ambient temperatures down to -20°F (-29°C).
It is required to provide an independent power source (115V 60-Hz-20 amp, 50Hz-15 amp), with a fused­disconnect to the heaters.The heaters are factory-wired back to the unit control panel.
Note: If evaporator is drained, the heater must be turned
off in order to avoid damaging the evaporator.The heater should only be on when the evaporator has water in it.
Knock-outs for wiring are located on the bottom right side of the control panel.The wiring is passed through these
70 CG-SVX17E-EN
Page 71
Installation - Electrical
Table 35. Power Entrance
“V” Configuration 40-70Ton
“Slant” Configuration 20-35Ton
Low
Voltage
Power
Low Voltage Power
Low Voltage Power
Incoming Power
“W” Configuration 80-130Ton
Incoming Power
Incoming Power
Partial Heat Recovery Power Supply
The partial heat recover heat exchanger is insulated from
ambient air and protected from freezing temperatures by an immersion heater. When the ambient air temperature drops to approximately 37°F (2.8°C) the thermostat energizes the heaters.The heaters will provide protection from ambient temperatures down to -20°F (-29°C).
It is required to provide an independent power source (115V 60-Hz-20 amp, 50Hz-15 amp), with a fused­disconnect to the heater.The heaters are factory-wired back to the unit control panel.
CG-SVX17E-EN 71
Note: If partial heat recovery heat exchanger is drained,
the heater must be turned off in order to avoid damaging the partial heat recovery heat exchanger.
The heater should only be on when the heat
recovery heat exchanger has water in it.
Water Pump Power Supply
Provide power supply wiring with disconnect for the chilled water pump(s).
Page 72
Installation - Electrical
InterconnectingWiring
Chilled Water Flow (Pump) Interlock
All CGAM model chillers have a factory-installed flow switch. In addition, it isrecommended to usean additional field-supplied control voltage contact input through an auxiliary contact to prove flow. Connect the auxiliary contact to 1X5-3 and 1X5-9. Refer to the field wiring for details.The auxiliary contact can be a BAS signal, starter contactor auxiliary or any signal which indicates the pump is running.
Chilled Water Pump Control
An evaporator water pump output relay closes when the chiller is given a signal to go into the Auto mode of operation from any source.The contact is opened to turn off the pump in the event of most machine level diagnostics to prevent the build up of pump heat.
The relay output from 1A9 is required to operate the
EvaporatorWater Pump (EWP) contactor. Contacts should be compatible with 115/240 VAC control circuit. Normally, the EWP relay follows the AUTO mode of the chiller.
Whenever the chiller has nodiagnostics and is inthe AUTO
mode, regardless of where the auto command is coming from, the normally open relay is energized. When the chiller exits the AUTO mode, the relay is timed to open in an adjustable (usingTechView) 0 to 30 minutes.The non­AUTOmodes in which the pumpis stopped, include Reset, Stop, External Stop, Remote Display Stop, Stopped by
Tracer, Start Inhibited by Low AmbientTemp, and Ice
Building complete.
t
NOTICE:
Equipment Damage!
If the microprocessor calls for a pump to start and water does not flow, the evaporator may be damaged catastrophically. It is the responsibility of the installing contractor and/or the customer to ensure that a pump will always be running when called upon by the chiller controls.
Table 36. Pump Relay Operation
Chiller Mode Relay Operation
Auto Instant close
Ice Building Instant close
Tracer Override Close
Stop Timed to Open
Ice Complete Instant Open
Diagnostics Instant Open
When going from Stopto Auto, the EWP relay is energized
immediately. If evaporator water flow is not established in 4 minutes and 15 seconds, the CH530 de-energizes the
EWP relay and generates a non-latching diagnostic. If flow returns (e.g. someone else is controlling the pump), the diagnostic is cleared, the EWP relay is re-energized, and normal control resumed.
If evaporator water flow is lost once it has been established, the EWP relay remains energized and a non­latching diagnostic is generated. If flow returns, the diagnostic is cleared and the chiller returns to normal operation.
NOTICE:
Equipment Damage!
Do NOT enable/disable the chiller by removing water flow or equipment damage can occur.
In general, when there is either a non-latching or latching diagnostic, the EWP relayis turned off as thoughthere was a zero time delay.The relay continues to be energized with:
A Low Chilled WaterTemperature diagnostic (non-
latching) unless also accompanied by an Evap Leaving
WaterTemperature Sensor Diagnostic.
or
A Loss of EvaporatorWater Flow diagnostic (non-latching)
and the unit is in the AUTO mode, after initially having proven evaporator water flow.
Note: If pump control is used for freeze protection then
the pump MUST be controlled by the CGAM CH530 control. If another method of freeze protection is used (i.e. glycol, heaters, purge, etc) then the pump may be controlled by another system.
Chilled Water Pump Control - Field Supplied Dual Pumps
CH530 can provide pump control for two customer­supplied pumps, as long as the pump contactor coils 1A9 and connect the pump fault feedback signals 1A12 are properly connected.
In this situation, the unit will leave the factory with Evaporator Pump Control (EVPC) = No Pump Control (Pump Request Relay) (NPMP) and Evaporator Pump Fault Input (EVFI) = Installed (INST).When the contactors and pumps are set up in the field, the CH530 ServiceTool (TechView) must be used to reconfigure to Evaporator Pump Control = Dual Pump Fixed Speed and Evaporator Pump Fault Input = Not Installed or Installed depending on how the fault feedback wire is connected. It is strongly recommended to install the Fault Input if possible as the controls will “hot-swap” the pumps upon detection of a fault, and may avoid the inevitable Flow Loss diagnostic (and unit shutdown) that will result if there is no fault feedback.
72 CG-SVX17E-EN
Page 73
Installation - Electrical
When configured for Dual Pump Fixed Speed, the CH530
will swap pumps on detection of a fault (if installed), or when a flow loss or overdue event occurs. It will also switch pumps each time the overall pump request is removed and re-engaged,unless a fault is detected on one of the pumps.If faults are detectedon both pumps,the unit will be shut down.
In addition to the factory installed flow switch, a field­supplied auxiliary contact is required, so that the chiller will only detect flow if a pump is running and the flow switch says flow is present.
Chilled Water Pump Control - Optional Pump Package
When factory installed pump package option is selected,
the chiller MUST control the pumps. See “Chilled Water
Pump Control,” p. 72.
Table 37. Alarm and Status Relay Output Configuration Table
Description
Alarm - Latching
Alarm - Auto Reset
Alarm
Alarm Ckt 1
Alarm Ckt 2 Chiller Limit Mode (with
a 20 minute filter) Circuit 1 Running
Circuit 2 Running
Chiller Running
Maximum Capacity This output is true whenever the chiller has all compressors on. The output is false once one compressor is shut off.
This output is true whenever there is any active diagnostic that requires a manual reset to clear, that affects either the
, the Circuit, or any of the Compressors on a circuit. This classification does not include informational diagnostics.
Chiller This output is true whenever there is any active diagnostic that could automatically clear, that affects either the Chiller,
the Circuit, or an This output is true whenever there is any diagnostic affecting any component, whether latching or automatically clearing.
This classification does not include informational diagnostics This output is true whenever there is any diagnostic effecting Refrigerant Circuit 1, whether latching or automatically
clearing, including diagnostics affecting the entire chiller This output is true whenever there is any diagnostic affecting Refrigerant Circuit 2 whether latching or automatically
clearing, including diagnostics effecting the entire chiller This output is true whenever the chiller has been running in one of the Unloading types of limit modes (Condenser,
Ev
aporator, Current Limit or Phase Imbalance Limit) continuously for the last 20 minutes.
This output is true whenever any compressor is running (or commanded to be running) on Refrigerant Circuit 1, and false when no compressors are commanded to be running on that circuit.
This output is true whenever any compressor is running (or commanded to be running) on Refrigerant Circuit 2, and false when no compressors are commanded to be running on that circuit.
This output is true whenever any compressor is running (or commanded to be running) on the chiller and false when no compressors are commanded to be running on the chiller
y of the Compressors on a circuit. This classification does not include informational diagnostics.
Alarm and Status Relay Outputs
(Programmable Relays)
A programmable relay concept provides for enunciation of
certain events or states of the chiller, selected from a list of likely needs, while only using four physical output relays, as shown in the field wiring diagram.The four relays are provided (generally witha Quad Relay Output LLID) as part of theAlarm Relay Output Option.The relay’s contacts are isolated Form C (SPDT), suitable for use with 120 VAC circuits drawing up to 2.8 amps inductive, 7.2 amps resistive, or 1/3 HP and for 240VAC circuits drawing up to
0.5 amp resistive.
The list of events/states that can be assigned to the
programmable relays can be found in Table 37.The relay will be energized when the event/state occurs.
. This classification does not include informational diagnostics.
. This classification does not include informational diagnostics.
.
Relay Assignments Using TechView
CH530 ServiceTool (TechView) is used to install the Alarm and Status Relay Option package and assign any of the above list of events or status to each of the four relays provided with the option.The relays to be programmed are referred to by the relay’s terminal numbers on the LLID board 1A18.
The default assignmentsfor the four availablerelays of the
CGAM Alarm and Status Package Option are:
Table 38. Default Relay Assignments
Relay
Relay 1 Terminals J2 -12,11,10: Compressor Running Relay 2 Terminals J2 - 9,8,7: Latching Alarm
CG-SVX17E-EN 73
Table 38. Default Relay Assignments
Relay
Relay 3 Terminals J2-6,5,4: Chiller Limit Mode Relay 4 Terminals J2-3,2,1: Warning
If any of the Alarm/Status relays are used, provide electrical power, 115 VAC with fused-disconnect to the panel and wire through the appropriate relays (terminals on 1A13. Provide wiring (switched hot, neutral, and ground connections) to the remote annunciation devices. Do not use power from the chiller’s control panel transformer to power these remote devices. Refer to the field diagrams which are shipped with the unit.
Page 74
Installation - Electrical
Low VoltageWiring
NOTICE:
WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards.To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
The remote devices described below require low voltage
wiring. All wiring to and from these remote input devices to the Control Panel must be made with shielded, twisted pair conductors. Be sure to ground the shielding only at the panel.
Note: To prevent control malfunctions, do not run low
voltage wiring (<30 V) in conduit with conductors carrying more than 30 volts.
Emergency Stop
CH530 provides auxiliary control for a customer specified/ installed latching trip out. When this customer-furnished remote contact 6K5 is provided, the chiller will run normally when the contact is closed. When the contact opens, the unit will trip on a manually resettable diagnostic.This condition requires manual reset at the chiller switch on the front of the control panel.
Connect low voltage leads to terminal strip locations on 1A13, J2-3 and 4. Refer to the field diagrams that are shipped with the unit.
Silver or gold-plated contacts are recommended.These customer-furnished contacts must be compatible with 24
VDC, 12 mA resistive load.
External Auto/Stop
If the unit requires the external Auto/Stop function, the installer must provide leads from the remote contact 6K4 to the proper terminals on 1A13, J2-1 and 2.
The chiller will run normally when the contact is closed. When the contact opens, the compressor(s), if operating,
will go to the RUN:UNLOAD operating mode and cycle off. Unit operation willbe inhibited. Closure of the contact will permit the unit to return to normal operation.
Field-supplied contacts for all low voltage connections must be compatible with dry circuit 24 VDC for a 12 mA resistive load. Refer to the field diagrams that are shipped with the unit.
Equipment Damage!
Do NOT enable/disable the chiller by removing water flow or equipment damage can occur.
Ice Building Option
CH530 provides auxiliary control for a customer specified/ installed contact closure for ice building if so configured and enabled.This output is known as the Ice Building Status Relay. The normally open contact will be closed when ice building is in progress and open when ice building has been normally terminated either through Ice
Termination setpoint being reached or removal of the Ice
Building command. When contact 6K6 is provided, the chiller will run normally when the contact is open.
CH530 will accept either an isolated contact closure (External Ice Building command) or a Remote Communicated input (Tracer) to initiate andcommand the Ice Building mode.
CH530 also provides a “Front Panel IceTermination Setpoint”, settable throughTechView, and adjustable from 20 to 31°F (-6.7 to -0.5°C) in at least 1°F (1°C) increments.
When in the Ice Building mode, and the evaporator
entering water temperature drops below the ice termination setpoint, the chiller terminates the Ice Building mode and changes to the Ice Building Complete Mode.
NOTICE:
Evaporator Damage!
Freeze inhibitor must be adequate for the leaving water temperature. Failure to do so may result in damage to system components.
TechView may also be used to enable or disable Ice
Machine Control.This setting does not prevent theTracer from commanding Ice Building mode.
Upon contact closure, the CH530 will initiate an ice building mode, in which the unit runs fully loaded at all times. Ice building shall be terminated either by opening the contact or based on the entering evaporator water temperature. CH530 will not permit the ice building mode to be reentered until the unit has been switched out of ice building mode (open 5K20 contacts) and then switched back into ice building mode (close 5K20 contacts.)
In ice building, all limits (freeze avoidance, evaporator, condenser, current) will be ignored. All safeties will be enforced.
If, while in ice building mode, the unit gets down to the freeze stat setting (water or refrigerant), the unit will shut down on a manually resettable diagnostic, just as in normal operation.
74 CG-SVX17E-EN
Page 75
Installation - Electrical
Connect leads from 6K6 to the proper terminals of 1A16. Refer to the field diagrams which are shipped with the unit.
Silver or gold-plated contacts are recommended.These customer furnished contacts must be compatible with 24
VDC, 12 mA resistive load.
External Chilled Water Setpoint (ECWS) Option
The CH530 provides inputs that accept either 4-20 mA or 2-
10 VDC signals to set the external chilled water setpoint (ECWS).This is not a reset function.The input defines the set point.This input is primarily used with generic BAS (building automation systems).The chilled water setpoint set via the DynaView or through digital communication withTracer.
The chilled water setpoint may be changed from a remote
location by sending either a 2-10VDC or 4-20 mA signal to the 1A14, J2-1 and 2.The 2-10 VDC and 4-20 mA each correspond to a 10 to 65°F (-12 to 18°C) external chilled water setpoint.
The following equations apply:
Voltage Signal
VDC = (8*ECWS
Current Signal
mA = (16*ECWS
Note: To convert ECWS values to °F, use the following
If the ECWS input develops an open or short, the LLID will report either a very high or very low valueback to the main processor.This will generate an informational diagnostic and the unit will default to using the Front Panel (DynaView) Chilled Water Setpoint.
TechView ServiceTool is used to set the input signal type
from the factory default of 2-10 VDC to that of 4-20 mA.
TechView is also used to install or remove the External
ChilledWater Setpoint option aswell asa meansto enable and disable ECWS.
+ 2*ECWS
°F
+ 4*ECWS
°F
- 10*ECWS
max
- 20*ECWS
max
formula: °F = 1.8*(°C) + 32
)/(ECWS
min
min
)/ (ECWS
max
max
- ECWS
- ECWS
min
)
min
2-10 VDC and 4-20 mA shall each correspond to an EDLS range with a minimum of 0% and amaximum of 100%.The following equations exist.
Global Scroll Voltage Signal Current Signal As generated from
external source As processed by
CH530
Vdc = 8*(EDLS) + 2 mA = 16*(EDLS) + 4
EDLS = (Vdc - 2)/8 EDLS = (mA - 4)/16
The minimum EDLS will be clamped at the front panel
based on 100% /Total number of Compressors. For input signals beyond the 2-10VDC or 4-20mA range, the end of range value shall be used. For example, if the customer inputs 21 mA, the EDLS shall limit it self to the corresponding 20 mA EDLS.
ECWS and EDLS Analog Input Signal
Wiring Details:
Both the ESWS and EDLS can be connected and setup as either a 2-10 VDC (factory default), 4-20 mA, or resistance input (also a form of 4-20 mA) as indicated below. Depending on the type to be used, theTechView Service
Tool must be used to configure the LLIDand the MPfor the
proper input type that is being used.This is accomplished by a setting change on the Custom Tab of the Configuration View withinTechView.
The J2-3 and J2-6 terminal is chassis grounded and
terminal J2-1 and J2-4 can be used to source 12VDC.The ECLS uses terminals J2-2 and J2-3. EDLS uses terminals
)
J2-5 and J2-6. Both inputs are only compatible with high-side current sources.
Figure 67. Wiring Examples for ECLS and EDLS
External Demand Limit Setpoint (EDLS) Option
CH530 provide a means to limit the capacity of the chiller by limiting the number of compressors or stages that are allowed to run.The maximum number of compressor or stages allowed to run can vary from one to the number of stages on the unit.The staging algorithm is free to decide which compressor or stage shall be turned off or prevented from running to meet this requirement.
CH530 shall accept either a 2-10 VDC or 4-20 mA analog input suitable for customer connection to set the unit external demand limit setpoint (EDLS).
CG-SVX17E-EN 75
Page 76
Installation - Electrical
Chilled Water Reset (CWR)
CH530 resets the chilled water temperature set point based on either return water temperature, or outdoor air temperature.
The following shall be selectable:
One of three ResetTypes: None, Return Water
Temperature Reset, Outdoor AirTemperature Reset, or
Constant Return WaterTemperature Reset.
Reset Ratio Set Points.
For outdoor air temperature reset there shall be both positive and negative reset ratio's.
Start Reset Set Points.
Maximum Reset Set Points.
The equations for each type of reset are as follows:
Return
CWS' = CWS + RATIO (START RESET - (TWE -TWL))
and CWS' > or = CWS
and CWS' - CWS < or = Maximum Reset
Outdoor
CWS' = CWS + RATIO * (START RESET -TOD)
and CWS' > or = CWS
and CWS' - CWS < or = Maximum Reset
where
CWS' is the new chilled water set point or the "reset CWS"
CWS is the active chilled water set point before any reset has occurred, e.g. normally Front Panel, Tracer, or ECWS
RESET RATIO is a user adjustable gain
START RESET is a user adjustable reference
TOD is the outdoor temperature
TWE is entering evap. water temperature
TWL is leaving evap. water temperature
MAXIMUM RESET is a user adjustable limit providing the maximum amount of reset. For all types of reset, CWS' ­CWS < or = Maximum Reset.
the same as the Return Reset equation except on selection of Constant Return Reset, the MP will automatically set Ratio, Start Reset, and Maximum Reset to the following.
RATIO = 100%
START RESET = Design DeltaTemp.
MAXIMUM RESET = Design DeltaTemp.
The equation for Constant Return is then as follows:
CWS' = CWS + 100% (Design DeltaTemp. - (TWE -TWL))
and CWS' > or = CWS
and CWS' - CWS < or = Maximum Reset
When any type of CWR is enabled, the MP will step the Active CWS toward the desired CWS' (based on the above
equations and setup parameters) at a rate of 1 degree F every 5 minutes until the Active CWS equals the desired CWS'.This applies when the chiller is running.
When the chiller is not running the CWS is reset
immediately (within one minute) for Return Reset and at a rate of 1 degree F every 5 minutes for Outdoor Reset.The chiller will start at the Differential to Start value above a fully reset CWS or CWS' for both Return and Outdoor Reset.
Percent Capacity Output Option
CH530 provides an optional percent capacity output for those customers without a communicating BAS interface.
The active unit capacity (AUC) is provided through a 2-10
VDC analog output at 1A25 terminals J2-4 andJ2-6 (GND).
The active unit capacity value (in %) can be derived from
the 2-10 VDC output voltage (OV) using the following calculation:
AUC = 100*(OV - 2.0V)/(10.0V - 2.0V)
Note: The percent capacity output is based on the
number and size of compressors energized, and is not adjusted for operating conditions. This value cannot be used as an accurate measure of total unit current, power or cooling capacity.
Reset
Type
Return
Outdoor
Reset Ratio
Range
10-
120%
80-
-80%
Start Reset
Range
4-30°F 0-20°F
(2.2-16.7°C) (0.0-11.1°C)
50 - 130°F 0 - 20°F
(10-54.4°C) (0.0-11.1°C)
Maximum
Reset
Range
In addition to Return and Outdoor Reset, the MP provides a menu item for the operator to select a Constant Return Reset. Constant Return Reset will reset the leaving water temperature set point so as to provide a constant entering water temperature.The Constant Return Reset equation is
76 CG-SVX17E-EN
Increment Factory
Default
ValueIP SI
1% 1% 50%
1% 1% 10%
Page 77
Installation - Electrical
Communications Interface options
Tracer Communications Interface
This option allows theTracer CH530controller to exchange
information (e.g. operating setpoints and Auto/Standby commands) with a higher-level control device, such as a
Tracer Summit or a multiple-machine controller. A
shielded, twisted pair connection establishes the bi­directional communications link between theTracer CH530 and the building automation system.
Note: To prevent control malfunctions, do not run low
voltage wiring (<30 V) in conduit with conductors carrying more than 30 volts.
WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards.To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
Field wiring for the communication link must meet the following requirements:
All wiring must be in accordance with the NEC and local codes.
Communication link wiring must be shielded, twisted pair wiring (Belden 8760 or equivalent). See the table below for wire size selection:
Table 39. Wire Size
Wire Size
14 AWG (2.5 mm2) 5,000 FT (1525 m) 16 AWG (1.5 mm 18 AWG (1.0 mm
2
) 2,000 FT (610 m)
2
) 1,000 FT (305 m)
Maximum Length of
Communication Wire
• The communication link cannot pass between buildings.
All units on the communication link can be connected in a “daisy chain” configuration.
LonTalk Communications Interface for Chillers (LCI-C)
CH530 provides an optional LonTalk Communication Interface (LCI-C) between the chiller and a Building Automation System (BAS). An LCI-C LLID shall be used to provide “gateway” functionality between a LonTalk compatible device and the Chiller.The inputs/outputs
include both mandatory andoptional network variables as established by the LonTalk Functional Chiller Profile 8040.
Installation Recommendations
22 AWG Level 4 unshielded communication wire recommended for most LCI-C installations
LCI-C link limits: 4500 feet, 60 devices
• Termination resistors are required
105 ohms at each end for Level 4 wire
82 ohms at each end forTrane "purple" wire
LCI-C topology should be daisy chain
Zone sensor communication stubslimited to 8 per link, 50 feet each (maximum)
One repeater can be used for an additional 4500 feet, 60 devices, 8 communication stubs
Table 40. LonTalk Points List
Length
Inputs/Outputs
Chiller Enable/Disable Request 2 bytes SNVT_switch Chilled Water Setpoint 2 bytes SNVT_temp_p Capacity Limit Setpoint
(used by Demand Limit Setpoint) Operating Mode Request 1 byte SNVT_hvac_mode Chiller Running State 2 bytes SNVT_switch Active Chilled Water or Hot Water
Setpoint Actual Running Capacity 2 bytes SNVT_lev_percent Active Capacity Limit Setpoint (from
Active Demand Limit Setpoint) Evaporator Leaving Water Temp 2 bytes SNVT_temp_p Evaporator Entering Water Temp 2 bytes SNVT_temp_p Alarm Description 31 bytes SNVT_str_asc Chiller Status
00 = Chiller off 01 = Chiller in start mode 02 = Chiller in run mode 03 = Chiller in pre-shutdown mode 04 = Chiller in service mode 03 = Cooling only 0A = Cooling with compressor not
running 0B = Ice-making mode bit 0 (MSB) = in alarm mode bit 1 = run enabled bit 2 = local bit 3 = limited bit 4 = evaporator water flow
and
Contents SNVT / UNVT
2 bytes SNVT_lev_percent
2 bytes SNVT_temp_p
2 bytes SNVT_lev_percent
3 bytes SNVT_chlr_status
CG-SVX17E-EN 77
Page 78
Installation - Electrical
BACnet Communications Interface for Chillers (BCI-C)
The optional BACnetCommunication Interface for Chillers
(BCI-C) is comprised of aTracer UC400 controller with interface software. It is a non-programmable communications module that allows the RTWD or RTUD unit to communicate on a BACnet communications network.
BACnet Data Points and Configuration Property Definitions
The BCI-C device allows certain models ofTrane chillers
with CH530 controls to communicate with BACnet systems and devices using BACnet MS/TP.This section includes information about:
BACnet protocol implementation conformance statement (PICS)
Object types: descriptions and configuration (refer to
Table 41, p. 79)
BACnet protocol: data link layers, device address binding, networking options, and character sets
Object data points and configurations
BACnet Protocol Implementation Conformance Statement (PICS)
Standardized Device Profile (Annex L)
Profile Description
BACnet Advanced Application Controller (B-AAC) BACnet Application Specific Controller (B-ASC) ü BACnet Building Controller (B-BC) BACnet Operator Workstation (B-OWS) BACnet Smart Actuator (B-SA) BACnet Smart Sensor (B-SS)
Supported
Profile
Interoperability Building Blocks (Annex K)
Data Sharing Description
Data Sharing-COV-B (DS-COV-B) Data Sharing-ReadProperty-A (DS-RP-A) ü Data Sharing-ReadProperty-B (DS-RP-B) ü Data Sharing-ReadPropertyMultiple-B (DS-RPM-B) ü Data Sharing-WriteProperty-A (DS-WP-A) ü Data Sharing-WriteProperty-B (DS-WP-B) ü Data Sharing-WritePropertyMultiple-B (DS-WPM-B) ü
Alarm and Event Management Description
Alarm and Event-ACKI-B (AE-ACK-B) ü Alarm and Event-Alarm Summary-B (AE-ASUM-B) ü Alarm and Event-Enrollment Summary-B (AE-ESUM-
B) Alarm and Event-Information-B (AE-INFO-B) ü
Alarm and Event-Notification Internal-B (AE-N-I-B)
Trending Description
Trending-Automated Trend Retrieval-B (T-ATR-B) ü T rending-viewing and Modifying Trends Internal-B (T-
VMT-I-B)
Device Management Description
Device Management-Backup and Restore-B (DM-BR­B)
Device Management-Device Communication Control­B (DM-DCC-B)
Device Management-Dynamic Device Binding-A (DM­DDB-A)
Device Management-Dynamic Device Binding-B (DM­DDB-B)
Device Management-Dynamic Object Binding-B (DM­DOB-B)
Device Management-List Manipulation-B (DM-LM-B) ü Device Management-Object Creation and Deletion-B
(DM-OCD-B) Device Management-Private Transfer-A (DM-PT-A) ü Device Management-Private Transfer-B (DM-PT-B) ü Device Management-Reinitialize Device-B (DM-RD-B) ü Device Management-TimeS ynchronization-B (DM-TS-
B)
Supported
BIBB
Supported BIBB
Supported BIBB
Supported BIBB
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
78 CG-SVX17E-EN
Segmentation Capability
Segmentation Description
Segmented Requests/ Window Size: 1 ü Segmented Responses/ Window Size: 1 ü
Supported
Segment
Page 79
Installation - Electrical
Object Types
Table 41. Descriptions and configurations
Object
Type Required Properties Read Properties Written
Analog Input
Analog Output
Analog Value
• Object_Identifier
• Object_Name
• Object_Type
• Present_Value
• Status_Flags
• Event_State
• Out_Of_Service
•Units
• Object_Identifier
• Object_Name
• Object_Type
• Present_Value
• Status_Flags
• Event_State
• Out_Of_Service
•Units
• Priority_Array
• Relinquish_Default
• Object_Identifier
• Object_Name
• Object_Type
• Present_Value
• Status_Flags
• Event_State
• Out_Of_Service
•Units
• Object_Name
• Description
• Out_Of_Service
• Present_Value
• Reliability
• Min_Pres_Value
• Max_Pres_Value
• COV_Increment
• Time_Delay
• Notification_Class
• High_Limit
• Low_Limit
• Deadband
• Limit_Enable
• Event_Enable
•Notify_Type
• Object_Name
• Description
• Out_Of_Service
• Present_Value
• Reliability
• Min_Pres_Value
• Max_Pres_Value
• Relinquish_Default
• COV_Increment
• Time_Delay
• Notification_Class
•High_Limit
• Low_Limit
• Deadband
• Limit_Enable
• Event_Enable
•Notify_Type
• Object_Name
• Description
• Out_Of_Service
• Present_Value
• Reliability
• Relinquish_Default
• COV_Increment
• Time_Delay
• Notification_Class
•High_Limit
• Low_Limit
• Deadband
• Limit_Enable
• Event_Enable
•Notify_Type
(a)
Optional Properties Read
• Description
• Reliability
• Min_Pres_Value
• Max_Pres_Value
• COV_Increment
• Time_Delay
• Notification _Class
• High_Limit
• Low_Limit
• Deadband
• Limit_Enable
• Event_Enable
• Acked_Transitions
•Notify_Type
• Event_Time_Stamps
• Description
• Reliability
• Min_Pres-Value
• Max_Pres_Value
• COV_Increment
• Time_Delay
• Notification _Class
• High_Limit
• Low_Limit
• Deadband
• Limit_Enable
• Event_Enable
• Acked_Transitions
•Notify_Type
• Event_Time_Stamps
• Description
• Reliability
• Priority_Array
• Relinquish_Default
• COV_Increment
• Time_Delay
• Notification_Class
• High_Limit
• Low_Limit
• Deadband
• Limit_Enable
• Event_Enable
• Acked_Transitions
•Notify_Type
• Event_Time_Stamps
Ability to
Create
Yes
Yes
Yes
Ability to
Delete
Yes, only user created objects
Yes, only user created objects
Yes, only user created objects
CG-SVX17E-EN 79
Page 80
Installation - Electrical
Table 41. Descriptions and configurations (continued)
Object
Type Required Properties Read Properties Written
• Object_Name
• Description
• Out_Of_Service
• Inactive_Text
• Active_Text
• Present_Value
• Reliability
• Change_Of_State_Count
• Elapsed_Active_Time
• Time_Delay
• Notification_Class
• Alarm_Value
• Event_Enable
• Acked_Transitions
•Notify_Type
• Object_Name
• Description
• Out_Of_Service
• Inactive_Text
• Active_Text
• Present_Value
• Reliability
• Change_Of_State_Count
• Elapsed_Active_Time
• Minimum_On_Time
• Minimum_Off_Time
• Relinquish_Default
• Time_Delay
• Notification_Class
• Event_Enable
• Acked_Transitions
•Notify_Type
• Object_Name
• Description
• Out_Of_Service
• Inactive_Text
• Active_Text
• Present_Value
• Reliability
• Change_Of_State_Count
• Elapsed_Active_Time
• Minimum_On_Time
• Minimum_Off_Time
• Relinquish_Default
• Time_Delay
• Notification_Class
• Alarm_Value
• Event_Enable
• Acked_Transitions
•Notify_Type
Binary Input
Binary Output
Binary Value
• Object_Identifier
• Object_Name
• Object_Type
• Present_Value
• Status_Flags
• Event_State
• Out_Of_Service
•Polarity
• Object_Identifier
• Object_Name
• Object_Type
• Present_Value
• Status_Flags
• Event_State
• Out_Of_Service
•Polarity
• Priority_Array
• Relinquish_Default
• Object_Identifier
• Object_Name
• Object_Type
• Present_Value
• Status_Flags
• Event_State
• Out_Of_Service
•Polarity
(a)
Optional Properties Read
• Description
• Inactive_Text
• Active_Text
• Change_Of_State_Time
• Change_Of_State_Count
• Time_Of_State_Count_Reset
• Elapsed_Active_Time
• Time_Of_Active_Time_Reset
• Time_Delay
• Notification_Class
• Alarm_Value
• Event_Enable
• Acked_Transitions
•Notify_Type
• Event_Time_Stamps
• Reliability
• Description
• Inactive_Text
• Active_Text
• Change_Of_State_Time
• Change_Of_State_Count
• Time_Of_State_Count_Reset
• Elapsed_Active_Time
• Time_Of_Active_Time_Reset
• Minimum_On_Time
• Minimum_Off_Time
• Time_Delay
• Notification_Class
• Feedback_Value
• Event_Enable
• Acked_Transitions
•Notify_Type
• Event_Time_Stamps
• Reliability
• Description
• Inactive_Text
• Active_Text
• Change_Of_State_Time
• Change_Of_State_Count
• Time_Of_State_Count_Reset
• Elapsed_Active_Time
• Time_Of_Active_Time_Reset
• Priority_Array
• Relinquish_Default
• Minimum_On_Time
• Minimum_Off_Time
• Time_Delay
• Notification_Class
• Alarm_Value
• Event_Enable
• Acked_Transitions
•Notify_Type
• Event_Time_Stamps
• Reliability
Ability to
Create
Yes
Yes
Yes
Ability to
Delete
Yes, only user created objects
Yes, only user created objects
Yes, only user created objects
80 CG-SVX17E-EN
Page 81
Installation - Electrical
Table 41. Descriptions and configurations (continued)
Object
Type Required Properties Read Properties Written
• Object_Name
•Location
• Description
• APDU_Segment_Timeout
• APDU_Timeout
• Number_Of_APDU_Retries
• Backup_Failure_Timeout
• Object_Name
•Notify_Type
• Event_Parameters
• Object_Property_Reference
• Event_Enable
• Notification_Class
• Object_Name
• Description
• State_Text
• Out_Of_Service
• Present_Value
• Reliability
• Time_Delay
• Notification_Class
• Alarm_Values
• Fault_Values
• Event_Enable
•Notify_Type
• Object_Name
• Description
• State_Text
• Out_Of_Service
• Present_Value
• Reliability
• Time_Delay
• Notification_Class
• Event_Enable
•Notify_Type
Device
Event Enrollment Object
Multistate Input
Multistate Output
• Object_Identifier
• Object_Name
• Object_Type
• System_Status
• Vendor_Name
• Vendor_Identifier
• Model_Name
• Firmware_Revision
• Application_Software_Version
• Protocol_Version
• Protocol_Revision
• Protocol_Services_Supported
• Protocol_Object_Types_Supported
• Object_List
• Max_APDU_Length_Accepted
• Segmentation_Supported
• APDU_Timeout
• Number_Of_APDU_Retries
• Device_Address_Binding
• Database_Revision
• Object_Identifier
• Object_Name
• Object_Type
• Event_Type
•Notify_Type
• Event_Parameters
• Object_Property_Reference
• Event_State
• Event_Enable
• Acked_Transitions
• Notification_Class
• Event_Time_Stamps
• Object_Identifier
• Object_Name
• Object_Type
• Present_Value
• Status_Flags
• Event_State
• Out_Of_Service
• Number_Of_States
• Object_Identifier
• Object_Name
• Object_Type
• Present_Value
• Status_Flags
• Event_State
• Out_Of_Service
• Number_Of_States
• Priority_Array
• Relinquish Default
(a)
Optional Properties Read
•Location
• Description
• Max_Segments_Accepted
• APDU_Segment_Timeout
• Max_Master
• Max_Info_Frames
•Local_Time
• Local_Date
• Configuration_Files
• Last_Restore_Time
• Backup_Failure_Timeout
• Active_COV_Subscriptions
•None
• State_Text
• Reliability
• Time_Delay
• Notification_Class
• Alarm_Values
• Fault_Values
• Event_Enable
• Acked_Transitions
•Notify_Type
• Event_Time_Stamps
• State_Text
• Reliability
• Relinquish_Default
• Time_Delay
• Notification_Class
• Feedback_Values
• Event_Enable
• Acked_Transitions
•Notify_Type
• Event_Time_Stamps
Ability to
Ability to
Create
None None
Yes, only user
Yes
Yes
Yes
created objects
Yes, only user created objects
Yes, only user created objects
Delete
CG-SVX17E-EN 81
Page 82
Installation - Electrical
Table 41. Descriptions and configurations (continued)
Object
Type Required Properties Read Properties Written
• Object_Identifier
• Object_Name
• Object_Type
• Present_Value
• Status_Flags
• Event_State
Multistate Value
Notification Class
Trend
(a)Properties written for Present_Value and Reliability only if Out_of_Service is TRUE.
• Out_Of_Service
• Number_Of_States
• Object_Identifier
• Object_Name
• Object_Type
• Notification_Class
•Priority
• Ack_Required
• Recipient_List
• Object_Identifier
• Object_Name
• Object_Type
• Log_Enable
• Stop_When_Full
• Buffer_Size
• Log_Buffer
• Record_Count
• Total_Record_Count
• Event_State
• Object_Name
• Description
• State_Text
• Out_Of_Service
• Present_Value
• Reliability
• Priority_Array
• Relinquish_Default
• Time_Delay
• Notification_Class
• Alarm_Values
• Fault_Values
• Event_Enable
•Notify_Type
• Object_Name
•Priority
• Ack_Required
• Recipient_List None Yes
• Object_Name
•Log_Enable
• Start_Time
• Stop_Time
• Log_DeviceObjectProperty
• Log_Interval
• Stop_When_Full
• Buffer_Size
• Log_Buffer
• Record_Count
• Notification_Threshold
• Notification_Class
• Event_Enable
•Notify_Type
(a)
Optional Properties Read
• State_Text
• Reliability
• Relinquish_Default
• Time_Delay
• Notification_Class
• Alarm_Values
• Fault_Values
• Event_Enable
• Acked_Transitions
•Notify_Type
• Event_Time_Stamps
• Start_Time
• Stop_Time
• Log_DeviceObjectProperty
• Log_Interval
• Stop_When_Full
• Buffer_Size
• Notification_Threshold
• Records_Since_Notification
• Last_Notify_Record
• Notification_Class
• Event_Enable
• Acked_Transitions
• Event_Time_Stamps
Ability to
Create
Yes
Yes
Ability to
Delete
Yes, only user created objects
Yes, only user created objects
Yes, only user created objects
BACnet Protocol
Data Link Layer Options
Data Link Layer Description Option
ANSI/ATA 878.1, 2.5 Mb ARCNET (Clause 8) ANSI/AT A 878.1, RS-485 ARCNET (Clause 8), Baud Rate(s) BACnet IP, (Annex J) BACnet IP, (Annex J), Foreign Device ISO 8802-3, Ethernet (Clause 7)(10Base2, 10Base5,
10BaseT, Fiber) LonTalk, (Clause 11), Medium MS/TP Master (Clause 9), Baud Rate(s): 9600, 19200,
38400, 76800, and 115200 @1.5% Nominal Baud Rate MS/TP Slave (Clause 9), Baud Rate(s) Other Point-to-Point, EIA 232 (Clause 10), Baud R ate(s): 9600,
19200, 38400 Point-to-Point, Modem (Clause 10), Baud Rate(s): 9600,
19200, 38400
82 CG-SVX17E-EN
Device Address Binding
Device Address Binding Supported?
Static Device Binding Supported ü
Networking Options
Networking Descriptions
Annex H, BACnet Tunneling
ü
BACnet/IP Broadcast Management Device (BBMD) Does the BBMD Support Registrations by Foreign
Devices? Router
Supported Option
Page 83
Installation - Electrical
Character Sets
Indicates support for multiple characterssets, but does not imply that all character sets are supportedsimultaneously. Maximum supported string length is 64 bytes (any character set).
Character Set Descriptions Supported
ANSI X3.4 ü IBM/Microsoft DBCS ISO 10646 (UCS-4) ISO 10646 (UCS2) ü ISO 8859-1 ü JIS C 6226
Object Data Points and Diagnostic Data Points with Corresponding Chiller Models
For quick reference, the following tables are listed two different ways. Table 42 through Table 47 are listed by input/output type and sorted by object identifier.These tables provide the user with the units type for each object type. Table 48 is sorted by object name and provides a complete list of object names, types, values/ranges, and descriptions. Not all points are available to the user.The available data points are defined during self-configuration and are dependent on the type of equipment
.
Table 42. Analog Output
Object
Identifier
Analog
Output 1
Analog
Output 2
Analog
Output 4
Object
Name
Chilled
Water
Setpoint
Current
Limit
Setpoint
Hot Water
Setpoint
Description Units
Desired leaving
water
temperature if
chiller is in
cooling mode.
Sets the
maximum
capacity that the
chiller can use. Desired leaving
water
temperature if
chiller is in
heating mode.
Perce
°F
(64)
nt
(98)
°F
(64)
Valid
Range
0°F to
75°F
0% to
120%
80°F to
140°F
Relinq
Default
44°F
100%
120°F
Table 43. Analog Input
Object Identifier
Analog Input, 1
Analog Input, 2
Analog Input, 5
Analog Input, 7
Analog Input, 10
Analog Input, 12
Analog Input, 14
Analog Input, 16
Analog Input, 18
Analog Input, 20
Analog Input, 22
Analog Input, 24
Analog Input, 25
Analog Input, 26
Analog Input, 27
Object Name Description Units
Active Cool/Heat Setpoint Temperature
Active Current Limit Setpoint
Actual Running Capacity
Suction Pressure- Ckt 1
Suction Pressure- Ckt 2
Evaporator Saturated Refrigerant Temperature­Ckt 1
Evaporator Saturated Refrigerant Temperature­Ckt 2
Condenser Refrigerant Pressure- Ckt 1
Condenser Refrigerant Pressure- Ckt 2
Condenser Saturated Refrigerant Temperature­Ckt 1
Condenser Saturated Refrigerant Temperature­Ckt 2
Unit Power Consumption
Local Atmospheric Pressure
Starts­Compressor 1A
Starts­Compressor 1B
Active chiller water or hot water setpoint.
Active capacity current limit setpoint.
Level of capacity that the chiller is currently running at.
Circuit 1 suction pressure.
Circuit 2 suction pressure.
Circuit 2 evaporator refrigerant temperature.
Circuit 2 evaporator refrigerant temperature.
Circuit 1 condenser refrigerant pressure.
Circuit 2 condenser refrigerant pressure.
Circuit 1 condenser refrigerant temperature.
Circuit 2 condenser refrigerant temperature.
The power being consumed by the chiller.
Local atmospheric pressure.
Number of starts for compressor 1A.
Number of starts for compressor 1B.
Degrees­Fahrenheit (64)
Percent (98)
Percent (98)
PSI
PSI
Degrees­Fahrenheit (64)
Degrees­Fahrenheit (64)
PSI
PSI
Degrees­Fahrenheit (64)
Degrees­Fahrenheit (64)
Kilowatts
PSI
None
None
CG-SVX17E-EN 83
Page 84
Installation - Electrical
Table 43. Analog Input (continued)
Object Identifier
Analog Input, 28
Analog Input, 29
Analog Input, 34
Analog Input, 35
Analog Input, 36
Analog Input, 37
Analog Input, 42
Analog Input, 43
Analog Input, 44
Analog Input, 45
Analog Input, 46
Analog Input, 47
Analog Input, 48
Analog Input, 49
Analog Input, 50
Object Name Description Units
Starts­Compressor 2A
Starts­Compressor 2B
Run Time­Compressor 1A
Run Time­Compressor 1B
Run Time­Compressor 2A
Run Time­Compressor 2B
Airflow Percentage­Circuit 1
Airflow Percentage­Circuit 2
Evaporator Entering Water Temp
Evaporator Leaving Water Temp
Condenser Entering Water Temp
Condenser Leaving Water Temp
High Side Oil Pressure­Compressor 1A
High Side Oil Pressure­Compressor 1B
High Side Oil Pressure­Compressor 2A
Number of starts for compressor 2A.
Number of starts for compressor 2B.
Total run time of compressor 1A.
Total run time of compressor 1B.
Total run time of compressor 2A.
Total run time of compressor 2B.
Approximate airflow percentage of circuit 1.
Approximate airflow percentage of circuit 2.
T emperature of the water entering the evaporator.
T emperature of the water leaving the evaporator.
T emperature of the water entering the condenser.
T emperature of the water leaving the condenser.
Pressure of the oil at the high side of compressor 1A.
Pressure of the oil at the high side of compressor 1B.
Pressure of the oil at the high side of compressor 2A.
None
None
Hours
Hours
Hours
Hours
Percent (98)
Percent (98)
Degrees­Fahrenheit (64)
Degrees­Fahrenheit (64)
Degrees­Fahrenheit (64)
Degrees­Fahrenheit (64)
PSI
PSI
PSI
Table 43. Analog Input (continued)
Object Identifier
Analog Input, 51
Analog Input, 56
Analog Input, 57
Analog Input, 58
Analog Input, 59
Analog Input, 60
Analog Input, 61
Analo5 Input, 62
Analog Input, 63
Analog Input, 64
Analog Input, 65
Analog Input, 66
Analog Input, 67
Analog Input, 68
Analog Input, 69
Object Name Description Units
High Side Oil Pressure­Compressor 2B
Refrigerant Disch T emp- Ckt 1
Outdoor Air Temperature
Condenser Control Output
Phase AB Voltage­Compressor 1A
Phase BC Voltage­Compressor 1A
Phase CA Voltage­Compressor 1A
Phase AB Voltage­Compressor 1B
Phase BC Voltage­Compressor 1B
Phase CA Voltage­Compressor 1B
Phase AB Voltage­Compressor 2A
Phase BC Voltage­Compressor 2A
Phase CA Voltage­Compressor 2A
Phase AB Voltage­Compressor 2B
Phase BC Voltage­Compressor 2B
Pressure of the oil at the high side of compressor 2B.
T emperature of the refrigerant being discharged from Ckt 1.
Outdoor air temperature.
Percentage of condenser water flow being requested by the chiller.
Phase AB voltage, compressor 1A.
Phase BC voltage, compressor 1A.
Phase CA voltage, compressor 1A.
Phase AB voltage, compressor 1B.
Phase BC voltage, compressor 1B.
Phase CA voltage, compressor 1B.
Phase AB voltage, compressor 2A.
Phase BC voltage, compressor 2A.
Phase CA voltage, compressor 2A.
Phase AB voltage, compressor 2B.
Phase BC voltage, compressor 2B.
PSI
Degrees­Fahrenheit (64)
Degrees­Fahrenheit (64)
Percent (98)
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
84 CG-SVX17E-EN
Page 85
Installation - Electrical
Table 43. Analog Input (continued)
Object Identifier
Analog Input, 70
Analog Input, 71
Analog Input, 72
Analog Input, 73
Analog Input, 74
Analog Input, 75
Analog Input, 76
Analog Input, 77
Analog Input, 78
Analog Input, 79
Analog Input, 80
Analog Input, 81
Analog Input, 82
Analog Input, 83
Analog Input, 84
Analog Input, 85
Analog Input, 86
Analog Input, 87
Analog Input, 88
Analog Input, 89
Object Name Description Units
Phase CA Voltage­Compressor 2B
Line 1 Current (in Amps)­Compressor 1A
Line 2 Current (in Amps)­Compressor 1A
Line 3 Current (in Amps)­Compressor 1A
Line 1 Current (in Amps)­Compressor 1B
Line 2 Current (in Amps)­Compressor 1B
Line 3 Current (in Amps)­Compressor 1B
Line 1 Current (in Amps)­Compressor 2A
Line 2 Current (in Amps)­Compressor 2A
Line 3 Current (in Amps)­Compressor 2A
Line 1 Current (in Amps)­Compressor 2B
Line 2 Current (in Amps)­Compressor 2B
Line 3 Current (in Amps)­Compressor 2B
Line 1 Current (%RLA)­Compressor 1A
Line 2 Current (%RLA)­Compressor 1A
Line 3 Current (%RLA)­Compressor 1A
Line 1 Current (%RLA)­Compressor 1B
Line 2 Current (%RLA)­Compressor 1B
Line 3 Current (%RLA)­Compressor 1B
Line 1 Current (%RLA)­Compressor 2A
Phase CA voltage, compressor 2B
Line 1 Current (in Amps)­Compressor 1A
Line 2 Current (in Amps)­Compressor 1A
Line 3 Current (in Amps)­Compressor 1A
Line 1 Current (in Amps)­Compressor 1B
Line 2 Current (in Amps)­Compressor 1B
Line 3 Current (in Amps)­Compressor 1B
Line 1 Current (in Amps)­Compressor 2A
Line 2 Current (in Amps)­Compressor 2A
Line 3 Current (in Amps)­Compressor 2A
Line 1 Current (in Amps)­Compressor 2B
Line 2 Current (in Amps)­Compressor 2B
Line 3 Current (in Amps)­Compressor 2B
Line 1 Current (%RLA)­Compressor 1A
Line 2 Current (%RLA)­Compressor 1A
Line 3 Current (%RLA)­Compressor 1A
Line 1 Current (%RLA)­Compressor 1B
Line 2 Current (%RLA)­Compressor 1B
Line 3 Current (%RLA)­Compressor 1B
Line 1 Current (%RLA)­Compressor 2A
Volts
Amps
Amps
Amps
Amps
Amps
Amps
Amps
Amps
Amps
Amps
Amps
Amps
Percent (98)
Percent (98
Percent (98)
Percent (98)
Percent (98)
Percent (98)
Percent (98)
Table 43. Analog Input (continued)
Object Identifier
Analog Input, 90
Analog Input, 91
Analog Input, 92
Analog Input, 93
Analog Input, 94
Analog Input, 95
Analog Input, 96
Analog Input, 97
Object Name Description Units
Line 2 Current (%RLA)­Compressor 2A
Line 3 Current (%RLA)­Compressor 2A
Line 1 Current (%RLA)­Compressor 2B
Line 2 Current (%RLA)­Compressor 2B
Line 3 Current (%RLA)­Compressor 2B
Number of Circuits
Number of Compressors, Ckt 1
Number of Compressors, Ckt 2
Line 2 Current (%RLA)­Compressor 2A
Line 3 Current (%RLA)­Compressor 2A
Line 1 Current (%RLA)­Compressor 2B
Line 2 Current (%RLA)­Compressor 2B
Line 3 Current (%RLA)­Compressor 2B
Number of Circuits
Number of Compressors, Ckt 1
Number of Compressors, Ckt 2
Table 44. Multistate Output
Object Identifier
Multi-State Output, 1
Object Name
Chiller Mode Command
Description
Mode of operation of the chiller.
Table 45. Multistate Input
BCI-C Object Identifier
Multi-State Input, 1
Multi-State Input, 2
Multi-State Input, 3
Multi-State Input, 4
Object Name
Running Mode
Operating Mode
MP Comm. Status
Refrigeran t Type
Description Object States
Indicates the primary running mode of the chiller.
Indicates the primary operating mode of the chiller.
Communication status.
Refrigerant type.
Percent (98)
Percent (98)
Percent (98
Percent (98)
Percent (98)
None
None
None
Relinq Default
1 = Cool
1 = Chiller Off 2 = Chiller in Start Mode 3 = Chiller in Run Mode 4 = Chiller in Pre-shutdown Mode 5 = Chiller in Service Mode
1 = HVAC_Heat 2 = HVAC_Cool 3 = HVAC_Ice 4 = Not Used
1 = R-22 2 = Communication 3 = Communication Lost 4 = Failed to Established 5 = Waiting to Establish
1 = R-11 2 = R-12 3 = R-22 4 = R-123
5 = R-134A 6 = R407C 7 = R-410A
Object States
1 = HVAC _Heat 2 = HVAC_Cool 3 = HVAC_Ice 4 = Not Used
CG-SVX17E-EN 85
Page 86
Installation - Electrical
Table 45. Multistate Input (continued)
BCI-C Object Identifier
Multi-State Input, 5
Multi-State Input, 6
Multi-State Input, 7
Object Name
Model
Cooling Type
Manuf. Location
Description Object States
1 = RTA 2 = CVH 3 = CVG 4 = CVR 5 = CDH
6 = RTH
Indicates the model type of the chiller.
Cooling type of the condenser.
Location where chiller was manufactured.
7 = CGW 8 = CGA 9 = CCA 10 = RTW 11 = RTX 12 = RTU 13 = CCU 14 = CXA 15 = CGC 16 = RAU
1 = Water Cooled 2 = Air Cooled
1 = Field Applied 2 = La Crosse 3 = Pueblo
4 = Charmes 5 = Rushville 6 = Macon 7 = Waco 8 = Lexington 9 = Forsyth 10 = Clarksville 11 = Ft. Smith 12 = Penang 13 = Colchester 14 = Curitiba 15 = Taicang 16 = Taiwan 17 = Epinal 18 = Golbey
Table 46. Binary Output
Object Identifier
Binary Output, 1
Binary Output, 2
Binary Output, 4
Object Name
Chiller Auto Stop Command
Remote Diagnosti c Reset Command
Noise Reduction Request
Description
Allows the chiller to run if conditions for running are met.
Resets remotely diagnostics that can be reset.
Requests chiller to enter mode to reduce noise.
Relinq Default
True
False
False
Object States
Inactive = Stop Active = Auto
Inactive = No Reset Request Active = Reset Request
Inactive = Normal Active = Reduced Noise
Table 47. Binary Input
Object Identifie r
Binary Input, 1
Binary Input, 2
Binary Input, 3
Binary Input, 4
Binary Input, 5
Binary Input, 6
Binary Input, 7
Binary Input, 9
Binary Input, 10
Binary Input, 11
Binary Input, 12
Binary Input, 17
Binary Input, 19
Binary Input, 20
Binary Input, 22
Binary Input, 23
Binary Input, 24
Binary Input, 25
Object Name
Run Enabled
Local Setpoint Control
Capacity Limited
Chiller Running State
Condenser Water Flow Status
Maximum Capacity
Head Relief Request
Compresso r 1A Running
Compresso r 1B Running
Compresso r 2A Running
Compresso r 2B Running
Evaporator Water Pump Request
Condenser Water Pump Request
Noise Reduction Active
Evaporator Water Flow Status
Alarm Present
Shutdown Alarm Present
Last Diagnostic
Description Object States
Indicates if the chiller is available to run or is currently running.
Indicates if the chiller is being controlled by local setpoints instead of BAS setpoints.
Indicates if conditions may exist that prevent the chiller from reaching setpoint.
Indicates if the chiller is running or stopped.
Condenser water flow status.
Indicates if all available chiller capacity is being used.
Indicates if the chiller is asking an outside system to provide more heat rejection from the condenser water loop.
Indicates if compressor 1A is running.
Indicates if compressor 1B is running.
Indicates if compressor 2A is running.
Indicates if compressor 2B is running.
Indicates a request from the chiller to turn on the evaporator water pump.
Indicates a request from the chiller to turn on the condenser water pump.
Indicates if the chiller is in a state where noise is being reduced.
Indicates if water is flowing through the evaporator.
Indicates if an alarm is active.
Indicates if a shutdown alarm is active.
Indicates last diagnostic for the chiller.
Inactive = Stop Active = Auto
Inactive =Remote Control Active = Local Control
Inactive = Not Limited Active = Limited
Inactive = Off Active = On
Inactive = No Flow Active = Flow
Inactive = Off Active = On
Inactive = Off Active = On
Inactive = Off Active = Running
Inactive = Off Active = Running
Inactive = Off Active = Running
Inactive = Off Active = Running
Inactive = Off Active = On
Inactive = Off Active = On
Inactive = Off Active = On
Inactive = No Flow Active = Flow
Inactive = No Alarm Active = Alarm
Inactive = No Alarm Active = None
Inactive = Off Active = On
86 CG-SVX17E-EN
Page 87
Installation - Electrical
Table 48. All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)
Object Identifier
Analog Output 1 Chilled Water Setpoint Desired leaving water temperature if chiller is in cooling mode. Analog Output 2 Current Limit Setpoint Sets the maximum capacity that the chiller can use. Analog Output 4 Hot Water Setpoint Desired leaving water temperature if chiller is in heating mode.
Analog Input, 1 Active Cool/Heat Setpoint Temperature Active chiller water or hot water setpoint. Analog Input, 2 Active Current Limit Setpoint Active capacity current limit setpoint. Analog Input, 5 Actual Running Capacity Level of capacity that the chiller is currently running at. Analog Input, 7 Suction Pressure- Ckt 1 Circuit 1 suction pressure. Analog Input, 10 Suction Pressure- Ckt 2 Circuit 2 suction pressure.
Analog Input, 12
Analog Input, 14 Analog Input, 16 Condenser Refrigerant Pressure- Ckt 1 Circuit 1 condenser refrigerant pressure.
Analog Input, 18 Condenser Refrigerant Pressure- Ckt 2 Circuit 2 condenser refrigerant pressure. Analog Input, 20
Analog Input, 22 Analog Input, 24 Unit Power Consumption The power being consumed by the chiller.
Analog Input, 25 Local Atmospheric Pressure Local atmospheric pressure. Analog Input, 26 Starts- Compressor 1A Number of starts for compressor 1A. Analog Input, 27 Starts- Compressor 1B Number of starts for compressor 1B. Analog Input, 28 Starts- Compressor 2A Number of starts for compressor 2A. Analog Input, 29 Starts- Compressor 2B Number of starts for compressor 2B. Analog Input, 34 Run Time- Compressor 1A Total run time of compressor 1A. Analog Input, 35 Run Time- Compressor 1B Total run time of compressor 1B. Analog Input, 36 Run Time- Compressor 2A Total run time of compressor 2A. Analog Input, 37 Run Time- Compressor 2B Total run time of compressor 2B. Analog Input, 42 Airflow Percentage- Circuit 1 Approximate airflow percentage of circuit 1. Analog Input, 43 Airflow Percentage- Circuit 2 Approximate airflow percentage of circuit 2. Analog Input, 44 Evaporator Entering Water Temp Temperature of the water entering the evaporator. Analog Input, 45 Evaporator Leaving Water Temp Temperature of the water leaving the evaporator. Analog Input, 46 Condenser Entering Water Temp Temperature of the water entering the condenser. Analog Input, 47 Condenser Leaving Water Temp Temperature of the water leaving the condenser. Analog Input, 48 High Side Oil Pressure- Compressor 1A Pressure of the oil at the high side of compressor 1A. Analog Input, 49 High Side Oil Pressure- Compressor 1B Pressure of the oil at the high side of compressor 1B. Analog Input, 50 High Side Oil Pressure- Compressor 2A Pressure of the oil at the high side of compressor 2A. Analog Input, 51 High Side Oil Pressure- Compressor 2B Pressure of the oil at the high side of compressor 2B. Analog Input, 56 Refrigerant Disch Temp- Ckt 1 Temperature of the refrigerant being discharged from Ckt 1. Analog Input, 57 Outdoor Air Temperature Outdoor air temperature. Analog Input, 58 Condenser Control Output Percentage of condenser water flow being requested by the chiller. Analog Input, 59 Phase AB Voltage- Compressor 1A Phase AB voltage, compressor 1A. Analog Input, 60 Phase BC Voltage- Compressor 1A Phase BC voltage, compressor 1A. Analog Input, 61 Phase CA Voltage- Compressor 1A Phase CA voltage, compressor 1A. Analo5 Input, 62 Phase AB Voltage- Compressor 1B Phase AB voltage, compressor 1B. Analog Input, 63 Phase BC Voltage- Compressor 1B Phase BC voltage, compressor 1B.
(a)
Object Name Description
Evaporator Saturated Refriger ant Temperature­Ckt 1
Evaporator Saturated Refriger ant Temperature­Ckt 2
Condenser Saturated Refrigerant T emperature­Ckt 1
Condenser Saturated Refrigerant T emperature­Ckt 2
Circuit 2 evaporator refrigerant temperature.
Circuit 2 evaporator refrigerant temperature.
Circuit 1 condenser refrigerant temperature.
Circuit 2 condenser refrigerant temperature.
CG-SVX17E-EN 87
Page 88
Installation - Electrical
Table 48. All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)
Object Identifier
Analog Input, 64 Phase CA Voltage- Compressor 1B Phase CA voltage, compressor 1B. Analog Input, 65 Phase AB Voltage- Compressor 2A Phase AB voltage, compressor 2A. Analog Input, 66 Phase BC Voltage- Compressor 2A Phase BC voltage, compressor 2A. Analog Input, 67 Phase CA Voltage- Compressor 2A Phase CA voltage, compressor 2A. Analog Input, 68 Phase AB Voltage- Compressor 2B Phase AB voltage, compressor 2B. Analog Input, 69 Phase BC Voltage- Compressor 2B Phase BC voltage, compressor 2B. Analog Input, 70 Phase CA Voltage- Compressor 2B Phase CA voltage, compressor 2B Analog Input, 71 Line 1 Current (in Amps)- Compressor 1A Line 1 Current (in Amps)- Compressor 1A Analog Input, 72 Line 2 Current (in Amps)- Compressor 1A Line 2 Current (in Amps)- Compressor 1A Analog Input, 73 Line 3 Current (in Amps)- Compressor 1A Line 3 Current (in Amps)- Compressor 1A Analog Input, 74 Line 1 Current (in Amps)- Compressor 1B Line 1 Current (in Amps)- Compressor 1B Analog Input, 75 Line 2 Current (in Amps)- Compressor 1B Line 2 Current (in Amps)- Compressor 1B Analog Input, 76 Line 3 Current (in Amps)- Compressor 1B Line 3 Current (in Amps)- Compressor 1B Analog Input, 77 Line 1 Current (in Amps)- Compressor 2A Line 1 Current (in Amps)- Compressor 2A Analog Input, 78 Line 2 Current (in Amps)- Compressor 2A Line 2 Current (in Amps)- Compressor 2A Analog Input, 79 Line 3 Current (in Amps)- Compressor 2A Line 3 Current (in Amps)- Compressor 2A Analog Input, 80 Line 1 Current (in Amps)- Compressor 2B Line 1 Current (in Amps)- Compressor 2B Analog Input, 81 Line 2 Current (in Amps)- Compressor 2B Line 2 Current (in Amps)- Compressor 2B Analog Input, 82 Line 3 Current (in Amps)- Compressor 2B Line 3 Current (in Amps)- Compressor 2B Analog Input, 83 Line 1 Current (%RLA)- Compressor 1A Line 1 Current (%RLA)- Compressor 1A Analog Input, 84 Line 2 Current (%RLA)- Compressor 1A Line 2 Current (%RLA)- Compressor 1A Analog Input, 85 Line 3 Current (%RLA)- Compressor 1A Line 3 Current (%RLA)- Compressor 1A Analog Input, 86 Line 1 Current (%RLA)- Compressor 1B Line 1 Current (%RLA)- Compressor 1B Analog Input, 87 Line 2 Current (%RLA)- Compressor 1B Line 2 Current (%RLA)- Compressor 1B Analog Input, 88 Line 3 Current (%RLA)- Compressor 1B Line 3 Current (%RLA)- Compressor 1B Analog Input, 89 Line 1 Current (%RLA)- Compressor 2A Line 1 Current (%RLA)- Compressor 2A Analog Input, 90 Line 2 Current (%RLA)- Compressor 2A Line 2 Current (%RLA)- Compressor 2A Analog Input, 91 Line 3 Current (%RLA)- Compressor 2A Line 3 Current (%RLA)- Compressor 2A Analog Input, 92 Line 1 Current (%RLA)- Compressor 2B Line 1 Current (%RLA)- Compressor 2B Analog Input, 93 Line 2 Current (%RLA)- Compressor 2B Line 2 Current (%RLA)- Compressor 2B Analog Input, 94 Line 3 Current (%RLA)- Compressor 2B Line 3 Current (%RLA)- Compressor 2B Analog Input, 95 Number of Circuits Number of Circuits Analog Input, 96 Number of Compressors, Ckt 1 Number of Compressors, Ckt 1 Analog Input, 97 Number of Compressors, Ckt 2 Number of Compressors, Ckt 2 Multi-State Input, 1 Running Mode Indicates the primary running mode of the chiller. Multi-State Input, 2 Operating Mode Indicates the primary operating mode of the chiller. Multi-State Input, 3 MP Communication Status Communication status. Multi-State Input, 4 Refrigerant Type Refrigerant type. Multi-State Input, 5 Model Information Indicates the model type of the chiller. Multi-State Input, 6 Cooling Type Cooling type of the condenser. Multi-State Input, 7 Manufacturing Location Location where chiller was manufactured. Binary Output, 1 Chiller Auto Stop Command Allows the chiller to run if conditions for running are met. Binary Output, 2 Remote Diagnostic Reset Command Resets remotely diagnostics that can be reset. Binary Output, 4 Noise Reduction Request Requests chiller to enter mode to reduce noise. Binary Output, 1 Chiller Auto Stop Command Allows the chiller to run if conditions for running are met.
(a)
Object Name Description
88 CG-SVX17E-EN
Page 89
Installation - Electrical
Table 48. All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)
Object Identifier
Binary Input, 1 Run Enabled Indicates if the chiller is available to run or is currently running. Binary Input, 2 Local Setpoint Control
Binary Input, 3 Capacity Limited Binary Input, 4 Chiller Running State Indicates if the chiller is running or stopped.
Binary Input, 5 Condenser Water Flow Status Condenser water flow status. Binary Input, 6 Maximum Capacity Indicates if all available chiller capacity is being used. Binary Input, 7 Head Relief Request Indicates if the chiller is asking an outside system to provide more heat Binary Input, 9 Compressor 1A Running Indicates if compressor 1A is running. Binary Input, 10 Compressor 1B Running Indicates if compressor 1B is running. Binary Input, 11 Compressor 2A Running Indicates if compressor 2A is running. Binary Input, 12 Compressor 2B Running Indicates if compressor 2B is running.
Binary Input, 17 Evaporator Water Pump Request
Binary Input, 19 Condenser Water Pump Request Binary Input, 20 Noise Reduction Active Indicates if the chiller is in a state where noise is being reduced.
Binary Input, 22 Evaporator Water Flow Status Indicates if water is flowing through the evaporator. Binary Input, 23 Alarm Present Indicates if an alarm is active. Binary Input, 24 Shutdown Alarm Present Indicates if a shutdown alarm is present. Binary Input, 25 Last Diagnostic Indicates the last diagnostic for the chiller.
(a)AI=Analog Input, AO=Analog Output, AV=Analog Value, BI=Binary Input, BO=Binary Output, MI=Multistate Input, MO=Multistate Output
(a)
Object Name Description
Indicates if the chiller is being controlled by local setpoints instead of BAS setpoints.
Indicates if conditions may exist that prevent the chiller from reaching setpoint.
Indicates a request from the chiller to turn on the evaporator water pump.
Indicates a request from the chiller to turn on the condenser water pump.
BCI-C Alarming
The BCI-C unit has three binary input points that are used
for communicating alarms and one binary output point that is used to reset alarms remotely.Those inputs and output points are:
BI 23; Alarm Present–This object indicates if any alarms are active regardless of severity. A notification will be sent to any recipients of the Information Notification Class object when the point transitions from No Alarm to Alarm.
BI 24; Shutdown Alarm Present– This object indicates if any alarms that result in the shutdown of the chiller are active. A notification will be sent to any recipients of the Critical Notification Class object when the point transitions from No Alarm to Alarm.
BI 25; Last Diagnostic–The active text of this object will reflect the description of the last diagnostic to occur on the chiller.
BO 2; Remote Diagnostic Reset Command–This object is used to remotely reset diagnostics on the chiller. Immediately aftercommanding this point value to 1, the BCI-C will send the reset command to the chiller and set this point value back to 0 and clear the priority array.
Note: Not all diagnostics are able to be reset remotely.
Some will require local reset at the chiller front panel.
CG-SVX17E-EN 89
Page 90
CGAM Operating Principles
This section contains an overview of the operation of
CGAM air-cooled liquid chiller equipped with microcomputer-based control systems. It describes the overall operating principles of the CGAM water chiller.
Note: To ensure proper diagnosis and repair, contact a
qualified service organization if a problem should occur.
General
The Model CGAM units are scroll compressor air-cooled
liquid chillers.These units are equipped with unit­mounted starter/control panels and operates with R-410A refrigerant.
Figure 68. Slant 20-35 ton component location
The basic components of an CGAM unit are:
Unit-mounted panel containing starter andTracer CH530 controller and Input/Output LLIDS
Scroll compressors
Brazed plate evaporator
Air-cooled condenser with subcooler
Electronic expansion valve
Optional partial heat recovery
Related interconnecting piping.
Components of a typical CGAM unit are identified in the following
diagrams.
Discharge line
Ball valve
High pressure side
Schrader
Service valves
Low pressure side
Schrader
High pressure side
Schrader
Vent
valve
switch
Flow
Drain
valve
Figure 69. V 40-70 ton component location - circuit 1
High pressure side
Schrader
90 CG-SVX17E-EN
Low pressure side Schrader
Discharge line
Ball valve
Page 91
CGAM Operating Principles
Figure 70. V 40-70 ton component location- circuit 2
Flow
switch
Vent valve
Drain
valve
Service valves
Discharge line
ball valve
Low pressure side
Schrader
Figure 71. W 80-130 ton component location - compressor view
High pressure side
Schrader
CG-SVX17E-EN 91
Page 92
CGAM Operating Principles
Figure 72. W 80-130 ton component location - evaporator side
Pump Package Components - Optional
Figure 73. Pump package components, slant 20-35T, view 1
Expansion tank
Pump
Manual air bleed
Victaulic coupling
Flexible hose
Relief valve
Junction box
Gauge Pressure port
Butterfly Valve
Pressure port
Strainer
Thermostat
Blow down valve
Handle
Immersion heater
92 CG-SVX17E-EN
Page 93
CGAM Operating Principles
Figure 74. Pump package components, slant 20-35T, view 2
Temperature sensor
Pressure port
Butterfly valve
Figure 75. Pump package components,V40-70T, view 1
Victaulic coupling
Pump
Relie f valve
Thermostat
Temperature sensor
Flow switch
Drain valve
Manual air bleed
Temperature sensor
Junction box
hermostat
T
Immersion heaters
Junction box
Immersion Heater
Handle
Gauge pressure port
Flexible hose
Expansion tank
Pressure port
Thermostat
Blow down valve
Drain Valve
CG-SVX17E-EN 93
Page 94
CGAM Operating Principles
Figure 76. Pump package components,V40-70T, view 2
Immersion Heaters
Victa ulic coupling
Strainer
Butterfly valve
Pressure port
Butterfly valve/balance valve
Figure 77. Pump package components — V 40-70 ton — view 3
Temp sensor
Drain valve
Flow switch
94 CG-SVX17E-EN
Pressure port
Immersion Heater
Page 95
CGAM Operating Principles
Figure 78. Pump package components —W 80-130 ton — view 1
Buffer tank (optional)
Auto air bleed
Junction box
Thermostat
Immersion heater
Victa ulic coupling
Butterfly valve
Thermostat
Strainer
Blow down valve
Handle
Figure 79. Pump package components —W 80-130 ton — view 2
Expansion tank
Junction box
Pump
Flexible Hose
Immersion
heater Gauge pressure port
Relie f Valve
Immersion heater
Manual air bleed
Victaulic coupling
Butterfly valve
Victaulic coupling
Temperature sensor
Immersion heater
Temperature sensor
Pressure port
Drain valve
Flow switch
Pressure port
CG-SVX17E-EN 95
Page 96
CGAM Operating Principles
Buffer Tank Components - Optional
Figure 80. Buffer tank components — slant 20-35 ton & V 40-70 ton
Auto air bleed
Pressure port
Victaulic coupling
Victaulic coupling
Immersion heater
Partial Heat Recovery Components
Figure 81. Partial heat recovery components, slant 20-35T
Manual Air Bleed
Victaulic Coupling
Auto air bleed
Thermostat
Junction box
HPC
Pressure Transducer
Temperature Sensor
Schrader
Valve
Temperature Sensor
Immersion Heater
Drain Valve
BPHE
96 CG-SVX17E-EN
Page 97
CGAM Operating Principles
p
Figure 82. Partial heat recovery components,V40-70T
Pressure Transducer
Schrader Valve
Manual Air Bleed
Immersion Heater
Temperature Sensor
HPC
Drain Valve
Victaulic Couplings
BPHE
Figure 83. Partial heat recovery components —W 80-130 ton
Victaulic Coupling
Pressure Transducer
HPC
Temperature Sensor
Schrader Valve
Tem
erature Sensor
Manual Air Bleed
Drain ValveBPHE
Immersion H eater
CG-SVX17E-EN 97
Page 98
CGAM Operating Principles
Refrigerant Cycle
Figure 84. CGAM refrigerant circuit
T
COMP 1B
COMP 1A
DISCHARGE LINE
SCHRADER VALVE
P
SUCTION LINE
BALL VALVE
SERVICE VALVE
ANGLE VALVE
FILTER & DRIER
LIQUID LINE
SCHRADER VALVE
T
P
HPC
SERVICE VALVE
BPHE
SCHRADER VALVE
The refrigeration cycle of the Model CGAM chiller is
conceptually similar to otherTrane air-cooled chiller products.The CGAM chiller uses a brazed plate evaporator and an air-cooled condenser.The compressors use suction gas cooled motors and an oil management system to provide almost oil-free refrigerant to the condenser and evaporator for maximum heat transfer while lubricating and sealing compressor bearings.The lubrication system helps to assure long compressor life and contributes to quiet operation.
Refrigerant condensers in the air-cooled heat exchanger which is available in three configurations—slant, V and
W—based on the CGAM nominal tonnage cooling
capacity.Liquid refrigerant ismetered intothe brazed plate evaporator using an electronic expansion valve to maximize chiller efficiency at full and part load operation.
The CGAM chiller is equipped with a unit-mounted starter
and control panel. Microprocessor-based unit control
EXV
Discharge temperature sensor used:
1.) Low leaving temp application without partial heat recovery option.
2.) Partial heat recovery option with fan control function.
modules (TraneTracer™CH530) provide accurate chilled water control and provide monitoring, protection and adaptive limit functions.The adaptive nature of the controls intelligently prevent the chiller from operating outside of its limits, or compensates forunusual operating conditions while keeping the chiller running rather than simply shutting off the chiller. If problems do occur, the CH530 controls provide diagnostic messages to help the operator in troubleshooting.
Refrigerant Cycle Description
The CGAM refrigeration cycle is described using the
pressure-enthalpy chart shown in Figure 84 Key State Points 1 through 5 are indicated on the chart. A schematic showing refrigerant components throughout the system is shown in Figure 85.
Refrigerant evaporation occurs in the brazed plate evaporator. Metered refrigerant vaporizes as it cools the chilled water or liquid flowing through the evaporator
98 CG-SVX17E-EN
Page 99
CGAM Operating Principles
passages.The refrigerant vapor leaves the evaporator as superheated gas. State Point 1.
Refrigerant vapor generated in the evaporator flowsto the compressor suction manifold where it enters and flows across the compressormotor windings toprovide cooling.
The vapor is then compressed in the compressor scroll
chambers and discharged. Oil from the compressor sump lubricates the bearings and seals the small clearances between the compressor scrolls. Refrigerant vapor is discharged to the air-cooled condenser at State Point 2.
After the refrigerant vapor condenses into liquid (State Points 3 and 4) it is returned to the evaporator (State Point
5) where the refrigerant again flashes into vapor and the refrigeration cycle repeats.
Oil System Operation (CGAM)
Overview
The oil isefficiently separated insidethe scroll compressor
and will remain in the scroll compressor during all run
Figure 86. CGAM scroll compressor sizes
Figure 85. Pressure/Enthalpy Curve
Liquid
3
4
Pre ssu re
5
Ent hal py
2
1
Gas
cycles. Between 1-2% of the oil circulates around with the refrigerant.
Figure 87. Compressor Internal Components, 15-30T
CG-SVX17E-EN 99
Page 100
CGAM Operating Principles
Figure 88. Compressor Internal Components, 15-30T
100 CG-SVX17E-EN
Loading...