ProductHermetic Scroll Liquid Chillers, Air Cooled
ModelCG
Literature TypeProgramming, Trouble Shooting Guide
Sequence01B
DateJanuary 2005
File No.SV-RF-CG-SVP01B-EN 1/05
SupersedesCG-SVP01A-EN 4/03
IntelliPak
TM
Air-Cooled Cold Generator
Models
"H" and Later Design Sequence
CGAF-C20 CGAF-C40
CGAF-C25 CGAF-C50
CGAF-C30 CGAF-C60
With 3-DTM Scroll Compressors
Ó
ÿ
2005 American Standard Inc. All rights reserved
http://www.trane.com
Trane has a policy of continuous product and product data
improvement and reserves the right to change design and
specifications without notice. Only qualified technicians should
perform the installation and servicing of equipment referred to
in this publication.
Page 2
About The Manual
Literature Change History
CG-SVP01B-EN (January 2005)
Original issue of this manual; provides specific programming, diagnostic, and troubleshooting information CGAF
units with “K” and later design sequence.
Overview of Manual
Note: One copy of this document ships inside the
control panel of each unit and is customer
property. It must be retained by the unit’s
maintenance personnel.
These units are equipped with electronic control modules
which provides operating functions that are significantly different than conventional units.
The manual is divided into 6 sections. Each section provides the operator with specific information about the system operating parameters and their related screens. By
carefully following the screen layout within this manual
while scrolling through the Human Interface, the operator
can monitor operating status, set specific operating parameters, and diagnose system problems.
Before attempting to operate or service this equipment, refer to the “Start-Up” and “Test Mode” procedures in the applicable Installation, Operation and Maintenance manual,
listed on the unit nameplate.
Note: The procedures discussed in this manual
should only be performed by qualified, experienced
HVAC technicians.
Refer to the Table of Contents and Index for specific topics
contained in this manual and supporting manuals.
2
Page 3
About The Manual
Literature Change History ....................................................... 2
Overview of Manual ................................................................. 2
General Information
Model Number Description ...................................................... 4
Unit Nameplate ........................................................................ 4
Refrigerant Ckt 1, Suction and Liquid Pressures ................. 20
Refrigerant Ckt 2, Suction and Liquid Pressures ................. 20
Compressor 1A Current, Phase A and B .............................. 20
Compressor 1B Current, Phase A and C .............................. 20
Compressor 2A Current, Phase B and C .............................. 21
Compressor 2B Current, Phase A and C .............................. 21
1.8 GBAS 0-5VDC Module Status Submenu ........................ 21
GBAS 0-5VDC Analog Input 1, Voltage and Assignment ..... 21
GBAS 0-5VDC Analog Input 2, Voltage and Assignment ..... 21
GBAS 0-5VDC Analog Input 3, Voltage and Assignment ..... 21
GBAS 0-5VDC Analog Input 4, Voltage and Assignment ..... 21
GBAS 0-5VDC Demand Limit Input Status ........................... 21
GBAS 0-5VDC Binary Output 1, Status and Assignment ..... 21
GBAS 0-5VDC Binary Output 2, Status and Assignment ..... 21
GBAS 0-5VDC Binary Output 3, Status and Assignment ..... 21
GBAS 0-5VDC Binary Output 4, Status and Assignment ..... 21
GBAS 0-5VDC Binary Output 5, Status and Assignment ..... 21
1.9 GBAS 0-10VDC Module Status Submenu ...................... 21
GBAS 0-10VDC Analog Input 1, Voltage and Assignment ... 21
GBAS 0-10VDC Analog Input 2, Voltage and Assignment ... 21
GBAS 0-10VDC Analog Input 3, Voltage and Assignment ... 21
GBAS 0-10VDC Analog Input 4, Voltage and Assignment ... 21
GBAS 0-10VDC Demand Limit Input Status ......................... 22
GBAS 0-10VDC Binary Output 1, Status and Assignment... 22
GBAS 0-10VDC Analog Output 1, Voltage and Assignment 22
GBAS 0-10VDC Analog Output 2, Voltage and Assignment 22
GBAS 0-10VDC Analog Output 3, Voltage and Assignment 22
GBAS 0-10VDC Analog Output 4, Voltage and Assignment 22
GBAS 0-10VDC Analog Output 5, Voltage and Assignment 22
2 Setpoints Menu
HI Leaving Solution Setpoint ................................................. 34
HI Ice Build Terminate Setpoint ............................................. 34
Index .......................................................................................... 65
4
Page 5
General Information
G = Superheat / Subcooling
P
* = Field Installed Options
Model Number Description
All Trane products are identified by a multiple-character
model number that precisely identifies a particular type of
unit. An explanation of the alphanumeric identification code
is provided below. Its use will enable the owner/operator, installing contractors, and service engineers to define the op-
Sample Model Number: CGAF - C30 4 A A B 0 D etc.
Digit Number:1,2,3,4 5,6,7 8 9 10 11 12 13 +
Digit 1,2 - Unit FunctionDigit 9 - Heating Capacity Digit 13, etc. Miscellaneous
Digit 4 - Development Sequence Digit 11 - Leaving Water Setpoint
F = SixthA = 40 - 50 F w/o Ice Machine
B = 30 - 39 F w/o Ice MachineH = Hot Gas Bypass
Digit 5,6,7 - Nominal Capacity
C20 = 20 TonsE = 20 - 29 F w/o Ice MachineK = Stock Unit
C25 = 25 Tons1 = 40 - 50 F w Ice Machine L = LonTalk® Communication Interface Module
C30 = 30 Tons2 = 30 - 39 F w Ice MachineM = *Remote Human Interface
C40 = 40 Tons3 = 51 - 65 F w Ice Machine N = Generic BAS Module 0-10 VDC Analog Output
C50 = 50 Tons4 = 20 - 29 F w Ice MachineP = Remote Setpoint Potentiometer P/S
C60 = 60 TonsS = SpecialQ = *Zone Sensor (Chilled Solution Reset) P/S
Digit 8 - Power Supply
E = 200/60/3 P/S***W = **Electronic Low Ambient Dampers P/S
F = 230/60/3Y = *Inter-Processor Comm Bridge (IPCB)
4 = 460/60/3 P/S***9 = Packed Stock Unit
5 = 575/50/3
9 = 380/50/30 = None ** = Factory or Field Installed Option
D = 415/50/31 = UL/CSA*** Available on Pack Stock Units
S = Special
Unit Nameplate
One Mylar unit nameplate is located on the outside upper
left corner of the control panel door. It includes the unit
model number, serial number, electrical characteristics,
weight, refrigerant charge, as well as other pertinent unit
data. A small metal nameplate with the Model Number, Serial Number, and Unit Weight is located just above the Mylar
nameplate, and a third nameplate is located on the inside of
the control panel door.
D = 51 - 65 F w/o Ice Machine J = Generic BAS Module 0-5 VDC Input, Binary O.
Digit 12 - Agency Approval
Hazard Identification
WARNING – Indicates a potentially hazardous
situation which, if not avoided, could result in death or
serious injury.
CAUTION – Indicates a potentially hazardous
situation which, if not avoided, may result in minor or
moderate injury. It may also be used to alert against
unsafe practices.
CAUTION - Indicates a situation that may result in
equipment or propertydamage only accidents.
Echelon, LON, LONWORKS, LonBuilder, NodeBuilder, LonManager, LonTalk, LonUsers, Neuron, 3120, 3150, the Echelon logo, and the LonUsers logo are
trademarks of Echelon Corporation registered in the United States and other countries. LonLink, LonResponse, LonSupport, LonMaker, and LonPoint are
trademarks of Echelon Corporation.
eration, specific components, and other options for any specific unit.
When ordering replacement parts or requesting service, be
sure to refer to the specific model number, serial number,
and DL number (if applicable) stamped on the unit nameplate.
B = No Unit Heat Tape (50 Hz Units Only)
C = Compressor Current Sensing (CSM)
E = *Unit Isolators - Neoprene P/S
F = *Unit Isolators - Spring P/S
S = Special
V = Copper Fin Condenser Coil
Commonly Used Acronyms
For convenience, a number of acronyms and abbreviations
are used throughout this manual. These acronyms are alphabetically listed and defined below.
A/D = Analog/Digital
BAS = Building Automation System
CAR = Circuit shuwdown - Auto Reset
Cf = Evaporator limit control integrator
CGA = Air cooled - Cold Generator
UCM = Cold generator module. Contains I/O for most
chilled solution functions.
Comp(s) = compressor(s)
Cond = condenser
Ckt = circuit
CLE = Chilled solution flow integrator
CMR = Circuit shutdown - Manual Reset
CRS = Control response setpoint
CSA = Canadian Standards Association
CCW = counterclockwise
CW = clockwise
DBZ = Width of Dead Band Zone
DDT = Design Delta-T setpoint
Delta T = The temperature difference between EST & LST
Diag = diagnostics
EST = Entering solution temperature
Ent = Entering
5
Page 6
General Information
Evap = Evaporator
Ext = External
GBAS = Generic Building Automation System Module
gfm = gallons per minute
HGBP = Hot gas bypass
HI = Human Interface
HO = History Only
HSLLS = Hot Start Load Limit setpoint
HVAC = Heating, Ventilation and Air Conditioning
IAR = Information only Auto Reset
IBTS = Ice Build Terminate Setpoint
ICS = Integrated Comfort System
IFW = Informational Warning
INFO = Information Only [Diagnostic]
I/O = Inputs/outputs
IOM = installation/operation/maintenance manual
IPC = Interprocessor communications
IPCB Module = Interprocessor communications bridge
module
IRDT = Ice Rebuild Delay Timer
LCD = Liquid Crystal Display
LCI = LonTalk® Communication Interface
LCI-I = LonTalk® Communication Interface for Intellipak
LED = Light Emitting Diode
LH = left-hand
LonTalk = An open, device networking communications
protocol for controls. This protocol is defined in ANSI
approved standard EIA/CEA-709.1-A-1999.
LSC = Low Solution Temperature Cutout Setpoint
LPC = Low Pressure Cutout [Switch]
LST = Leaving solution temperature
MAR = Machine shutdown - Auto Reset
Max = maximum
MCM = Multiple circuit compressor module
Min = minimum
Misc = miscellaneous
MMR = Machine shutdown - Manual Reset
Mod = module
Mon = monitor
NCS = Number of capacity steps
num = number
OA = Outdoor air
OAT = Outdoor air Temperature
PAR = Partial System Disable, Auto Reset [Diagnostic]
PMR = Partial System Disable, Manual Reset [Diagnostic]
PRT = Pump Run Timer
PSIG = pounds-per-square-inch gauge pressure
PWM = Pulse width modulated
RAM = Random Access Memory
RTM = rooftop module
ROM = Read Only Memory
S/W = Software
Sat - saturated
SCM = single circuit compressor module
SCT = Saturated Condensing Temperature
Soln = solution
STP = setpoint
TCI Module = Trane communications interface module
Temp = temperature
UCM = Unit Control Modules
UL = Underwriter's Laboratories
VFD = Variable Frequency Drive
w.c. = water column
XL = across-the-line start
Glossary of Terms
Carefully review these definitions since they are used
throughout this document and the I.O.M.. Knowledge of
these terms is essential in gaining an understanding of how
these units operate.
Active Setpoint
The setpoint which is currently being used for control by
the setpoint source selection.
Comm3
Trane proprietary network communication protocol.
Comm5
Trane’s implementation of LonTalk (an open network
communication protocol.)
Chilled Solution Temperature Reset
A function that shifts the Leaving Solution Temp Setpoint
an amount based on the value of another parameter—
typically ZoneTemp, Entering Solution Temp or Outdoor
Air Temp. The purpose of this function is to lower unit capacity to better meet load requirements.
Compressor Protection Switch
A pressure switch installed on the suction line that prevents compressor operation below the switch's setpoint.
Control Band
The range of temperatures or pressures which would
normally be maintained by the various control functions.
Control Point
The value of a setpoint that an algorithm is using at any
given time.
Deadband
As applied to LST control, this refers to a range of temperatures equally spaced above and below the CSS in
which the control algorithm is satisfied. There is not adjustment of machine capacity within the deadband.
Emergency Stop
UCM binary input. Can be used for emergency shutdown
of the unit by field-installed contacts. A diagnostic is produced when this input is open.
External Auto/Stop
A binary input on the UCM that allows the use of a fieldsupplied switch to perform normal unit on/off action.
Leaving Solution Setpoint
Active leaving solution setpoint. This setpoint is the control setpoint for process and comfort cooling.
Leaving Solution Temperature Control Point
The revised temperature setpoint after chilled solution
temp reset has been applied.
An open, device networking communications protocol for
controls. This protocol is defined in ANSI approved standard EIA/CEA-709.1-A-1999.
Low Ambient Compressor Lockout
A function which prevents compressor operation at low
outdoor ambient temperatures.
Remote Human Interface
A human interface module designed to be mounted remotely from the unit. There will be some functional differences between a unit mounted and a remote mounted
human interface module.
Reset Amount Maximum
The maximum amount of reset allowed.
Reset End Temperature
The temperature at which the maximum reset amount
will occur.
Reset Start Temperature
The temperature at which reset will begin.
Unit Control Module
This term is used to describe the set of electronic modules which make up the unit control system.
6
Page 7
General Information
UCM Control System
Trane Large Commercial Cold Generator Units are controlled by a microelectronic control system that consists of a
network of modules and are referred to as Unit Control
Modules (UCM).
The unit size, peripheral devices, options, etc... determine
the number and type of modules that a particular unit may
employ.
The UCM receives analog and binary inputs, then processes this information and supplies outputs in the form of
modulating voltages, contact closures, etc... to control
damper actuators, fan motors, compressors, valves, and
other electrical devices in the system to maintain set temperature levels.
The UCM provides some equipment protection functions
both directly and indirectly, such as chilled water flow and
compressor lockouts.
Listed below are the various modules that may be employed in a UCM control system.
Cold Generator Module (1U48) (CGM - Standard)
The Cold Generator Module (CGM) responds to cooling requests by energizing the proper unit components based on
information received from other unit modules, sensors, remote panels, and customer supplied binary inputs. It initiates unit operation based on that information.
Compressor Module (1U49) (MCM)
The Compressor module, (Single Circuit & Multiple Circuit),
upon receiving a request for mechanical cooling, energizes
the appropriate compressors and condenser fans. It monitors the compressor operation through feedback information
it receives from various protection devices. It also provides
heat tape output control for heat exchanger protection.
Interprocessor Communications Board (1U55) (IPCB used with Optional Remote Human Interface)
The Interprocessor Communication Board expands communications from the unit’s UCM network to a Remote Human
Interface Panel. DIP switch settings on the IPCB module for
this application should be; Switches 1 and 2 “Off”, Switch 3
“On”.
Trane Communications Interface Module (1U54) (TCI Optional - used with Trane ICS
The Trane Communication Interface module expands communications from the unit’s UCM network to a Trane Tracer
™
100
or a Tracer Summit™ system and allows external
setpoint adjustment and monitoring of status and diagnostics.
DIP Switch settings on the TCI module for these applications should be:
Switches 1, 2, and 3 are “Off”
™
)
Generic Building Automation System Module (1U51 =
GBAS 0-5V, 1U98 = GBAS 0-10V) (Optional - used with
Non-Trane Building Control System)
The Generic Building Automation System (GBAS) module
allows a non-Trane building control system to communicate
with the unit and accepts external setpoints in form of analog inputs (0 - 5 DCV or 0 - 10 DCV depending on the module selected) and a binary Input for demand limit. Five (5)
binary outputs are available on 0 - 5 DCV modules. One (1)
binary output and four (4) analog outputs are available on
the 0 - 10 DCV modules. Refer to the “Field Installed Control Wiring” section for the control wiring to the GBAS module and the various desired setpoints with the corresponding DC voltage inputs.
Lontalk Communication Interface Module (1U54)
(LCI Optional - used on units with Trane ICS
Building Automation Systems)
The LonTalk Communication Interface module expands
communications from the unit’s UCM network to a Trane
Tracer Summit™ or a 3rd party building automation system,
that utilizes LonTalk, and allows external setpoint and configuration adjustment and monitoring of status and diagnostics.
Current Sensing Module (1U90) (CSM - Optional)
Current transformers located around two (2) of the main
power leads for each compressor monitors the running current during compressor operation. The information is sent to
the UCM and can be accessed through the “Compressor
Status” submenu displayed at the Human Interface Module.
Monitors the system operating superheat and subcooling
through the use of pressure transducers, liquid line, and
suction line temperature sensors. The information is sent to
the SSM and can be accessed through the “Compressor
Status” submenu displayed at the Human Interface Module.
™
or 3rd party
Power Disconnecting Switches
Manual Disconnect Switch
(Optional 1S14) Manual disconnect switch 1S14, located in
the unit control panel, instead of the power terminal block
1TB1, allows the operator to disconnect power from the
unit's “high” voltage (200V-575V) section, the 115V section,
and the 24V section without having to open the control
panel door. A description of its features and operation are
given in the Installation, Operation, & Maintanence manual.
115V Control Circuit Switch (1S1)
Control circuit switch (1S1) is provided on all units and is located downstream of the 115V transformer 1T1. It allows
the operator to disconnect power from the unit's 115V control components by placing the switch in the "Off" position.
24V Transformer Switch (1S70)
Transformer switch 1S70 is provided on all units and is located downstream of 24V transformers 1T2 and 1T3. It allows the operator to disconnect (24V) power from all of the
unit's control modules by placing the switch in the "Off" position.
For a complete description of the 24V components and operation, refer to the latest edition of the applicable Installation, Operation and Maintenance manual listed on the unit
nameplate.
7
Page 8
General Information
Human Interface Module
(1U65 = Local 6U66 = Remote)
The Human Interface (HI) Module illustrated in Figure 1 is
the device which enables the customer, building owner, or
contractor, to communicate to the unit the necessary parameters for unit operation.
The local (unit mounted) Human Interface and the Remote
Human Interface Panels’ functions are identical, except for
Service mode which is not available on the Remote Human
Interface Panel.
The local HI Module is located in the unit’s main control
panel. A small door located in the unit’s control panel door
allows access to the HI Module’s keypad and display window.
There is a 2 line by 40 character LCD screen which provides status information for the various unit functions as
well as menus used to set or modify the operating parameters. There is a 16 key keypad adjacent to the LCD screen
which allows the operator to scroll through the various
menus and make adjustments to the setpoints, etc...
The information displayed in the LCD window will be top
level unit status information unless the operator initiates
other displays.
Figure 1
Human Interface Module
General Operation
At power-up, the Human Interface LCD will display one of
three initial screens illustrated in the "General Status" section.
1. Unit Status (Unit Off or Stopped) (The unit is configured
and operational, but is not running). This screen shows
state, mode, and function information when the unit is off
or stopped.
2. Unit Status (Unit On) (The unit is configured and operational, and is running). This screen shows state, mode,
and function information when the unit is on.
3. No Configuration (the unit needs to be configured). This
screen shows that required configuration data is missing.
The LCD screen has a backlight that makes the information
easier to read. The light will go out if no keys are pressed
for 30 minutes. If it goes out, simply press the STATUS key.
8
Page 9
General Information
Menu Keys
The six keys illustrated in Figure 2 in the MENU area (STATUS, SETPOINTS, SETUP, CONFIGURATION, DIAGNOSTICS, and SERVICE MODE) are used to bring up the various interactive menus where the user inputs and accesses
unit operating data. Pressing these keys will display the initial screen for the menu designated by the key’s name. The
following information describes the keys and their functions
when viewing the various menus.
If no key is pressed for 30 minutes while the LCD is displaying a menu screen, it will revert back to the unit operating
status screen.
Figure 2
Human Interface Keypad
SETPOINTS Key
Pressing the SETPOINTS key will cause the LCD screen to
display the first of the setpoint screens where the operator
will designate default temperature setpoints and setpoint
source information. While scrolling through the setpoint
screens, pressing this key again will cause the LCD to display the first setpoint screen.
DIAGNOSTICS Key
Pressing the DIAGNOSTICS key at any time will allow the
operator to view any unit function failures. The LCD screen
will display one of the diagnostic screens (depending on
which diagnostic, if any, is present). If no key is pressed for
30 minutes while the screen is displaying diagnostic information, it will revert back to the operating status display.
CONFIGURATION Key
Pressing the CONFIGURATION key will cause the LCD
screen to display the first of the configuration screens
where the operator will designate unit configuration data
such as unit type, capacity, installed options, etc...
This information was programmed at the factory. Pressing
the configuration key at any level in the configuration menu
will display the first configuration screen.
Note: This key should be used if the unit's
configuration data is lost or new options are added
in the field, and to view current configuration.
STATUS Key
Pressing the STATUS key causes the LCD to display the
operating status screen; i.e. "On", "Unit Stop", "External
Stop", "Emergency Stop", "Service Mode". Pressing the
NEXT key allows the operator to scroll through the screens
which provide information such as air and refrigerant temperatures, pump operation, compressor operation, as well
as active cooling and compressor lockout setpoints. Pressing the STATUS key while viewing any of the data screens
will cause the LCD to go back to the operating status
screen.
SETUP Key
Pressing the SETUP key will cause the LCD screen to display screens where the operator will designate various operating parameters such as temperature ranges, limits, percentages, etc. for the control of the unit’s various operating
modes. Pressing the SETUP key at any level in the SETUP
menu will display the first SETUP screen.
SERVICE MODE Key
Pressing the SERVICE MODE key causes the LCD to display the first of the service test mode screens showing various unit components which may be turned on or off for the
particular test being performed. Once the status of these
components is designated, the LCD will display screens
that allow the operator to designate the TEST START time
delay for each test.
Data Manipulation Keys
The six data manipulation keys illustrated inFigure 2, (ENTER, CANCEL, + (Plus), - (Minus), PREVIOUS, and NEXT
are used to modify the data within the screens (change values, move the cursor, confirm choices, etc...)
ENTER Key
This key will confirm the new values that were designated
by pressing the + (Plus) or - (Minus) keys at all edit points.
When viewing status and diagnostics screens, it has no
function.
CANCEL Key
After changing data, at an editable screen, but before confirming it with the ENTER key, pressing the CANCEL key
will return the data to its previous value. This key shall also
function to clear active diagnostics.
9
Page 10
General Information
+ (Plus) Key
When viewing a setpoint screen, this key will increase the
temperature or pressure value of the setpoint. When working with a status menu, it will add the current status display
to the custom menu. When viewing the setup or service test
screens, it will increase setpoints or toggle choices On or
Off at each edit point.
- (Minus) Key
This key when viewing the setpoint screen will decrease the
temperature or pressure value of the setpoint. When viewing the setup or service test screens, it will decrease
setpoints or toggle choices On or Off at each edit point.
When viewing the custom menu, pressing the - (Minus) key
will remove the status screen from the custom menu. When
viewing diagnostics screens it has no function.
PREVIOUS Key
Pressing the PREVIOUS key causes the LCD to scroll
backwards through the various displays for each menu. At
displays with multiple edit points, it moves the cursor from
one edit point to another.
NEXT Key
Pressing the NEXT key causes the LCD to scroll forward
through the various displays for each menu. At displays
with multiple edit points it moves the cursor from one edit
point to another.
Unit Operation Keys
AUTO Key
Pressing the AUTO key at any time will cause the display to
go to the top level status display and, if the unit is shutdown, will cause the unit to begin operation in the appropriate mode no matter what level in the menu structure is currently being displayed. If the current display is an editable
display, the AUTO key will confirm the desired edit.
STOP Key
Pressing the STOP key will cause the unit to transition to
the stop state. If the current display is editable, pressing the
STOP key will cancel the desired edit.
TEST START Key (SERVICE)
Pressing this key while viewing any screen in the SERVICE
Mode menu will start the service test. When viewing status,
setup, setpoint, and diagnostics screens, it has no function.
CUSTOM Key
The Custom menu is simply a status menu that contains
screens that the user monitors most frequently. The Custom
menu can only contain five status screens. To create the
Custom menu, press the STATUS key, followed by the
NEXT key (this brings up the initial status screen). If you
want to add this screen to the Custom menu, press the +
(Plus) key, if not, press the Next key again until a status
screen appears that you would like to add to the Custom
menu. Pressing the + (Plus) key while viewing any of the
various status screens will add that screen to the Custom
menu. Once the Custom menu is programed it can be accessed by pressing the CUSTOM key. To remove a status
screen from the Custom menu, press the CUSTOM key,
then press the NEXT key until the status screen that you
want to remove appears, then press the - (Minus) key.
After adding a screen to the Custom menu, the following
screen is displayed:
“Item Added to Custom Menu”
If the + (PLUS) key is pressed and the Custom menu is full,
the following screen is displayed:
“Custom Menu Is Full”
After deleting a screen from the Custom Menu, the following screen is displayed:
“Item Deleted from Custom Menu”
If the CUSTOM key is pressed and there are no entries, the
following screen is displayed:
No items are selected for Custom Report
See Operators Manual to select entries
10
Page 11
General Information
(Blank)
(Diagnostics)
Trouble Indicator
____________________ ____________________
General Status Display
Anytime the unit is powered up, or the STATUS, AUTO, or STOP keys are pressed, the unit mounted Human Interface will
display one of the following three general status display screens. The operator will then be able to enter keystrokes which
will allow him to navigate through a set of menus and submenus in order to provide/access various monitoring, setup, and
configuration infromation. The Human Interface will not display screens or parts of screens for which the unit is not configured.
Unit "Off" or "Stopped"
If at power up the unit is not running, the following display will appear on the Human Interface LCD screen. When this screen
is being displayed, the only functional keys are the six menu keys (STATUS, SETPOINTS, DIAGNOSTICS, SETUP, CONFIGURATION, AND SERVICE MODE), the AUTO key, the CUSTOM key, and the STOP key.
Mode of Oper ation
(On)
(Off)
_______________
Solution Pump
_____
Top Level State
(External Stop)
(Emergency Stop)
Trouble Indicator
(Unit Shutdown)
(Unit Stop)(Blank)
Unit "On"
If the unit has entered an operating state (running), the following display will appear on the Human Interface LCD screen.
When this screen is being displayed, the only functional keys are the six menu keys (STATUS, SETPOINTS, DIAGNOSTICS, SETUP, CONFIGURATION, AND SERVICE MODE), the AUTO key, the CUSTOM key, and the STOP key.
Mode of Operation
(Cool 0)
(Hot Gas Bypass)
(Cool 1)
(Cool 2)(On)
(Cool 3)(Off)
(Cool 4)
(Flow SW State Fail)*
_______________
Top Level State
(Servi ce Mode On) Ice Bui lding Co mple te
(Comfort Cooling) Ice Rebuild Delay
(Process Cooling) Unit Standby(Diagnostics)
(Ice Building)(Blank)
(Loop Stabilization)
Solution Pump
_____
*Service Test Mode Only - Flow switch failed to open after solution pump turned off.
No Configuration
If at power up the unit has not been programmed with the necessary configuration data for normal unit operation, the following display will appear on the Human Interface LCD screen. When this screen is being displayed, the only functional key is
the CONFIGURATION key.
No Configuration Present
Press Configuration Key
Note: This screen will only appear when the CGM has been field replaced. Refer to the Configuration Menu.
11
Page 12
General Information
g
g
g
g
g
g
g
g
g
g
g
49
g
g
g
g
g
g
g
g
g
g
g
g
g
Factory Presets
If your application requires different settings, turn to the
listed page beside the function, press the designated funcThe CGM controlled unit has many operating functions
whose settings are preset at the factory, but may be modified to meet the unique requirements of each job. The following list identifies each of the unit's adjustable functions
tion menu key, then press and hold the NEXT or PREVI-
OUS key until its screen appears on the LCD. Once the
proper screen appears, simply follow the programming in-
structions given below the applicable screen in this manual.
and the value assigned to it. If these factory presets match
your application's requirements and the"System Start-Up
procedures in the Installation, Operation & Maintyenance
manual has been completed, simply press the AUTO key at
Note: Record any changes made to the factory
preset values in the corresponding space provided.
the Human Interface module to begin unit operation.
Factory PresetChangedSee page... To adjust
Toto adjustPress....
Setpoints
Leavin
Low Ambient Compressor Lockout
Temperature Setpoint40 de
Heat Tape Temperature Setpoint40 de
Hot Start Load Limit Setpoint71 de
Ice Buildin
Low Solution Cutout Temperature35 de
Low Ambient Pump Override Temperature35 de
Use Leavin
Use Ice Buildin
Use Hot Start Load Limit Setpoint From:HI STP Menu35SETPOINTS
Use Capacity Limit Setpoint From:No Source Selected35SETPOINTS
Solution Setpoint44 deg F34SETPOINTS
F34SETPOINTS
F34SETPOINTS
F34SETPOINTS
Terminate Temperature27 deg F34SETPOINTS
F34SETPOINTS
F34SETPOINTS
Solution Setpoint From:HI STP Menu34SETPOINTS
Terminate Setpoint From:HI STP Menu34SETPOINTS
Information format
Display Text inEn
Display Units inEn
Unit ControlLocal23SETUP
Unit Address
General Unit Functions Setup
Delay unit Start0 Seconds23SETUP
Demand Limit DefinitionNone24SETUP
Hot Gas Bypass FunctionDisabled24SETUP
Hot Gas Bypass Max Run Time30 Minutes24SETUP
Hot Start Time In terval60 Minutes24SETUP
Hot Operation Response Option50% Capacity
Pumpdown FunctionDisabled24SETUP
Compressor Lead/La
Default Chiller Solution Pump ModeAuto24SETUP
Evaporator Solution Pump Off Delay Time30 Seconds25SETUP
Loop Stabilization Time120 Seconds25SETUP
Low Ambient Compressor LockoutEnabled25SETUP
Leavin
Chiller ApplicationComfort25SETUP
Evaporator Solution Flow Switch Provin
OA Temp Reset Type: Start Temp70 de
OA Temp Reset Type: End Temp50 de
OA Temp Reset Type: Max Amount of Reset5 de
Zone Temp Reset Type: Start Temp78 de
Zone Temp Reset Type: End Temp75 de
Zone Temp Reset Type: Max Amount of Reset5 de
Enterin
Enterin
Enterin
GBAS (0-10 VDC) Analog Input 1 AssignmentNot Assigned29SETUP
GBAS (0-10 VDC) Analog Input 2 AssignmentNot Assigned29SETUP
GBAS (0-10 VDC) Analog Input 3 AssignmentNot Assigned29SETUP
GBAS (0-10 VDC) Analog Input 4 AssignmentNot Assigned29SETUP
GBAS (0-10 VDC) Binary Output DefinitionIndicate selected
GBAS (0-10 VDC) Output Alarm AssignmentsAny active diagnostic30SETUP
GBAS (0-10 VDC) Analog Output 1 AssignmentLeaving solution temp30SETUP
GBAS (0-10 VDC) Analog Output 2 AssignmentEntering solution temp30SETUP
GBAS (0-10 VDC) Analog Output 3 AssignmentActive cooling capacity30SETUP
GBAS (0-10 VDC) Analog Output 4 AssignmentOutside air temperature30SETUP
CGM alarm output de finitions
diag alarms29SETUP
Any Active Diagnostic30SETUP
13
Page 14
General Information
S
C
Factory Presets (Continued)
Factory PresetChangedSee page... To adjust
Toto adjustPress....
Actuator Setup Definitions
Number 1 Low Ambient Maximum Stroke30 seconds31SETUP
Number 1 Low Ambient Minimum Voltage2.0v31SETUP
Number 1 Low Ambient Maximum Voltage10.0v31SETUP
Number 1 Low Ambient ActingDirect31SETUP
Number 2 Low Ambient Maximum Stroke30 seconds31SETUP
Number 2 Low Ambient Minimum Voltage2.0v31SETUP
Number 2 Low Ambient Maximum Voltage10.0v31SETUP
Number 2 Low Ambient ActingDirect31SETUP
Ckt 1 Suction Line Pressure Transducer - voltage at 0 PSIG0.118 V32SETUP
Ckt 1 Suction Line Pressure Transducer - voltage at 100 PSIG4.847 V32SETUP
Ckt 2 Suction Line Pressure Transducer - voltage at 0 PSIG0.118 V32SETUP
Ckt 2 Suction Line Pressure Transducer - voltage at 100 PSIG4.847 V32SETUP
Ckt 1 Liquid Line Pressure Transducer - voltage at 0 PSIG0.118 V32SETUP
Ckt 1 Liquid Line Pressure Transducer - voltage at 400 PSIG4.847 V32SETUP
Ckt 2 Liquid Line Pressure Transducer - voltage at 0 PSIG0.118 V32SETUP
Ckt 2 Liquid Line Pressure Transducer - voltage at 400 PSIG4.847 V32SETUP
Head Pressure Control Setup
Saturated condenser Temp Control Band
(Lower Limit)85 deg F26SETUP
Saturated condenser Temp Control Band
(Upper Limit)125 deg F26SETUP
Saturated condenser Temp Control Band
(Temporary Low Limit Suppression)10 deg F27SETUP
Saturated condenser Temp
(Efficiency Check Point)110 deg F27SETUP
Saturated condenser Temp (Low Ambient
Control Point)100 deg F27SETUP
Some of the operating displays on the Human Interface LCD screen are intended to be accessed by qualified users only,
and require a password to change. The following screens display the various programming sections that require a password
in order to view or to modify the preset operating parameters. The password for each screen is a different series of + (Plus)
or - (Minus) key strokes in a predefined sequence. Shown below are the password protected screens, and the passwords for
accessing them.
The following screens display the various programming sections that require a
specific PASSWORD to be entered by a qualified operator in order to view or
to modify the operating parameters.
The following screen will appear if the PASSWORD is not entered within approximately
15 seconds.
Password Entry Time Limit Exceeded
1. Press the NEXT key until the following screen is displayed.
Configuration is Password Protected
Please Enter Pasword:
2. Press the + or - keys in this sequence ( + - - - ) to access this restricted screen.
3. Press the ENTER key to confirm the password and enter the menu.
4. Press the NEXT key until the following screen is displayed.
Dia gnostic Re set is Password Pr otected
Please Enter Pasword:
1. Press the + or - keys in this sequence ( - + + ) to access this restricted screen.
2. Press the ENTER key to confirm the password and Lock the definitions.
3. Press the NEXT key until the following screen is displayed.
Diagnostic Log is Password Protected
Please Enter Pasword: __________
1. Press the + or - keys in this sequence ( - + + -) to access thi s restricted screen.
2. Press the ENTER key to confirm the password and Lock the definitions.
3. Press the NEXT key until the following screen is displayed.
15
Page 16
System Operating Status
See "General Status" Display Description
g
g
g
g
Active Ice Build Terminate STP = 0 - 99 F
g
g
g
g
y
STATUS Menu
The STATUS menu is used to view various operating conditions such as temperatures and humidity levels. It’s used to
view unit component status such as fan, compressor,
heater, and economizer operation, as well as setpoint status.
Press the STATUS key to enter into the status menu. The
"STATUS MODE" will automatically return to the power up screen
after 30 minutes, if no keys are pressed.
Cool 0 Solution Pump Off
Standb
1. Press the NEXT key to scroll forward thro ugh the status screens.
2. Press the PREVIOUS key to scroll backwards to view previously
displayed status screens.
3. Press the + (Plus) key while viewin
that screen to the custom menu. Refer to the custom menu for
the creation and maintenance of customized menus.
Active Leaving Solution Setpoint 55.0 F
Temp: Entering 55.0 F Leaving 50.0 F
This screen is displayed when the unit is in Ice Buildin
Active Ice Build Ter mina te STP 5 5.0 F
Temp: Entering 55.0 F Leaving 50.0 F
Diagnostics
any status screen to add
OR
.
The screens shown in this section are for example only.
Pressing the + (Plus) key while viewing any of the status
display screens will add that screen to the Custom menu.
When a status screen is displayed for 30 minutes without a
key being pressed, the LCD screen will revert to the general
operating status display. If this happens, press the STATUS
key again to return to the status menu. The following are
examples of status screens that may be viewed by pressing
the STATUS key.
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Enteri n
Leavin
Used on Units:
Possible Values:
Enteri ng = 0 - 99.9 F
Leavin
All Units
All Units
Active Solution Setpoint = 0 - 99 F
= 0 - 99.9 F
= 0 - 99.9 F
All Units
= 0 - 99.9 F
Compressor Status Submenu
Press ENTER to View Data in This Submenu
1. Press the ENTER key to advance to the followin
2. Press the NEXT key to bypass this menu and advance to
"General Status Submenu"
screen.
Note:
The ran
are 0 to 99.9 F. "ERR" will appear if the
temperature is out of ran
Used on Units:
e for all temperature inputs
e.
All Units
16
Page 17
System Operating Status
K3 - On, Off, Locked,
/
Suction range 0 - 100 PSIG
Comp Off
q
p
The following screens are displayed for 20 through 60 Ton units.
Compressor Relay K11 Off
Enabled
1. Press the NEXT key until the following screen is displayed. K11 - On, Off, Locked, or
Compressor Relay K12 Off
Enabled
1. Press the NEXT key until the following screen is displayed.
The following screens are displayed for 40 through 60 Ton units.
Compressor Relay K3 Off
Enabled
1. Press the NEXT key until the following screen is displayed.
Compressor Relay K4 Off
Enabled
Disabled By:
Bad Cond Temp SensorHot Start Operation
Bad Ent Soln SensorLow Ambient Lockout
Bad Leav Soln SensorLow Leav Soln Cutout
Compressor ProtectionLow Pressure Cutout
Compressor Protect LPCLPC Delay
Contactor FailureMinimum Off Time
Demand/Capacity LimitOver/Under Voltage
Evap Flow ProtectionPhase Loss/Reversal
Evap Limit ControlTracer Lockout
Used on Units:
Possible Values:
K4 - On, Off, L ocked,
K12 - On , Off, Locked
20 thru 60 Ton Units
1. Press the NEXT key until the following screen is displayed.
Compre ssor Module Ckt 1
Satura ted Conde nsor Temperature 8 1.0 F
1. Press the NEXT key until the following screen is displayed.
The following three screens are applicable when Superheat
Subcool Module is installed.
Refrigerant Ckt 1 - Temperature Data
Suction 75 .0 F Sat Liquid 81.0 F
1. Press the NEXT key until the following screen is displayed.
Refrigerant Ckt 1 - Pressure Data
Suction 72 PSIG Li
1. Press the NEXT key until the following screen is displayed. Comp Off
Refrigerant Circuit 1
Su
erhea t 28.0 F Subcooling 18.0 F
1. Press the NEXT key until the following screen is displayed.
The following screens are displayed for 40 through 60 Ton units.
Compressor Module Ckt 2
Saturated Condenser Temperature 97.0 F
uid 265 PSIG
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Liquid range 0 - 400 PSIG
Used on Units:
Possible Values:
Used on Units:
Possible Values:
All Units
-40 to 200 F
With superheat/subcool module
-40 to 200 F
With superheat/subcool module
With superheat/subcool module
0 - 99.9 F
40 Thru 60 Ton Units
-40 to 200 F
17
Page 18
1. Press the NEXT key until the following screen is displayed.
/
Suction range 0 - 100 PSIG
40 Thru 60 Ton Units
The following three screens are applicable when Superheat
Subcool Module is installed.
Refrigerant Ckt 2 - Temperature Data
Suction 72.0 F Sat Liquid 9 7.0 F
1. Press the NEXT key until the following screen is displayed.
1. Press the NEXT key until the following screen is displayed.
Compressor 1A Phase Currents - Amps
Phase A 86 Phase B 84
1. Press the NEXT key until the following screen is displayed.
Compressor 1B Phase Currents - Amps
Phase A 81 Phase C 78
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Liquid = 0.0 to 400.0 PSIG
Comp Off
Used on Units:
Possible Values:
Liquid = 0.0 to 400.0 PSIG
Comp Off
Used on Units: With
Possible Values:
Used on Units: With
Possible Values:
Off, Make Ice
All Units
Flo w, No Flo w
All Units with Superheat/Subcooling
0.0 to 100.0 PSIG
40 - 60 Ton Units with Superheat/Cooling
0.0 to 100.0 PSIG
Current Sensing Module
0 to 255
Current Sensing Module
0 to 255
21
Page 22
System Operating Status
Output = On, Off
With GBAS 0-10 VDC Modul e
g
1. Press the NEXT key until the following screen is displayed.
Compressor 2A Phase Currents - Amps
Phase B 88 Phase C 90
1. Press the NEXT key until the following screen is displayed.
Compressor 2B Phase Currents - Amps
Phase A 93 Phase C 89
1. Press the NEXT key until the following screen is displayed.
End of Submenu ( NEXT) to Re-enter STATUS
2. Pressing the NEXT key will display the beginning of
the Submenu.
3. Press the NEXT key again to advance to the following screen.
This screen is displayed when GBAS 0-5 VDC Module is installed
GBAS 0-5VDC Module Status Submenu
Press ENTER to View Data in This Submenu
1. Press the ENTER key until the following screen is displayed.
2. Press the NEXT key to bypass this menu and advance to
"GBAS 0-10VDC Module Status Submenu"
GBAS 0-5VDC Analog Input 1 0.00 VDC
Assigned: NOT ASSIGNED
3. Press the NEXT key to display Generic BAS Analog Input Leaving Solution Setpoint
screens 2, 3, & 4. Ice Build Terminate Setpoint
4. Press the NEXT key to advance to the following screen. Hot Start Load Li mit Setpoint
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Assignment = Not Assigned
Capacity Limit Setpoint
With Current Sensing Module on 40-60 Ton
0 to 255
With Current Sensing Module on 40-60 Ton
0 to 255
With GBAS 0-5VDC Module
Input = 0.00 to 5.00 VDC
GBAS (0-5VDC) Demand Limit Input Status
OPEN
1. Press the NEXT key until the following screen is displayed.
GBAS (0-5VDC) Binary Output 1 OFF
Assigned: OUTPUT IS NOT ASSIGNED
2. Press the NEXT key to display Generic BAS Binary Output Indicate any comp is running
screens 2, 3, 4 & 5. Indi cate unit at max capacity
3. Press the NEXT key to advance to the following screen. Indicate selected di ag alarms
End of Submenu ( NEXT) to Re-enter STATUS
1. Pressing the NEXT key will display the beginning of
the Submenu.
2. Press the NEXT key again to advance to the following screen.
This screen is displayed when GBAS 0-10 VDC Module is installed
GBAS 0-10VDC Module Status Submenu
Press ENTER to View Data in This Submenu
1. Press the ENTER key until the following screen is displayed.
2. Press the NEXT key to bypass this menu and advance to
"General Status" Display Screen.
GBAS 0-10VDC Analog Input 1 0.00 VDC
Assi
3. Press the NEXT key to display Generic BAS Analog Input Leaving Solution Setpoint
screens 2, 3 & 4. Ice Build Terminate Setpoint
4. Press the NEXT key to advance to the following screen. Hot Start Load Limit Setpoint
ned: NOT ASSIGNED
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Assignment = Output Is Not Assigned
Used on Units:
Possible Values:
Assignment = Output Is Not Assigned
Capacity Limit Setpoint
With GBAS 0-5VDC Module
Open, Closed
With GBAS 0-5VDC Module
Output = 0.00 - 10.00 VDC
22
Page 23
System Operating Status
Used on Units:
With GBAS 0-10 VDC Module
g
Used on Units:
With GBAS 0-10 VDC Module
g
g
g
Used on Units:
With GBAS 0-10 VDC Module
g
g
g
g
g
g
Open
g
GBAS (0-10VDC) Demand Limit Input Status
1. Press the NEXT key until the followin
GBAS (0-10VDC) Binary Output OFF
ned: OUTPUT IS NOT ASSIGNED
Assi
1. Press the NEXT key until the following screen is displayed.
GBAS 0-10VDC Analog Output 1 0.0 VDC
Assigned: NOT ASSIGNED
Assi
nment = Leaving solution temperature Assignment = Ckt1 liquid line pressure
Enterin
Ckt1 saturated condenser temp Ckt1 sat liquid temperature
Ckt2 saturated condenser temp Ckt2 sat liquid temperature
Ckt1 suction temperature ICS Defined temperature
Ckt2 suction temperature Outsi de air temperature
Ckt1 suction pressure Active Cooli n
Ckt2 suction pressure
2. Press the NEXT key to display Generic BAS Analo
screens 2, 3 & 4.
3. Press the NEXT key to advance to the followin
End of Submenu (NEXT) to Re-enter STATUS
screen is displayed.
solution temperature Ckt2 liquid line pressure
Output
screen.
Possible Values:
Possible Values:
Assi
Indicate selected dia
Indicate unit at max capacity
Indicate any comp is runnin
Possible Values:
Open, Closed
Output = On, Off
nment = Output Is Not Assigned
alarms
0.0 to 10.0 VDC
Capacity
4. Pressin
the Submenu.
5. Press the AUTO or STOP key to return to the top level
status information.
the NEXT key will display the beginning of
23
Page 24
System Programming SETUP
After the unit is installed, the CGM must be programmed
with certain setup information (chilled solution setpoints, ON
and OFF times, system defaults, setpoint sources, etc...) in
order to operate and function properly. The data necessary
for unit operation will vary depending on certain factors
such as unit size, type, and installed options.
This section of the manual provides step by step instructions for programming this information. Also provided are instructions for checking unit operating status, accessing and
clearing diagnostics, and performing service tests.
Some of the displays shown in this manual may not appear
on the Human Interface (HI) LCD screen during programing. Only the applicable screens for the specific unit options
and operating parameters will be displayed.
Start with the first setup screen in the SETUP menu and
program the necessary information by completing the steps
located below each illustrated window. Information that pertains to when the screens are applicable, the factory preset
values, and the possible values that may be designated is
located to the right of each programmable screen.
Ignore the steps that do not apply to your unit and application, and move on to the next applicable set of instructions
in the manual. Continue this process until all applicable
screens are programmed with the required information.
SETUP Menu
The setup menu is used to input initial operating information such as control parameters, functions enable/disable, text display (language), temperature display (C or F), and system tuning parameters. When a setup screen is displayed for 30 minutes without a key being pressed, the LCD screen will revert to the appropriate power-up display. If this happens, press the
SETUP key again to return to the setup menu.
1. Press the SETUP key to display the fol lowing screen.
Display Text in ENGLISH LANGUAGE
Display Units in ENGLISH
2. Press the + or - key until the proper "language" is displayed.
3. Press the ENTER key to confirm this choice.
4. Press the NEXT key to advance the cursor to the "Units"
5. Press the + or - key until the proper "language" is displayed.
6. Press the ENTER key to confirm this choice.
Used on Units:
Possible Values:
Units = SI, English
All
Text = English, French, Spanish
7. Press the NEXT key until the following screen is displayed.
Unit contr ol: LOCAL
Unit Address 4 9
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor to the "Address" (TCI only)
4. Press the + or - key until the proper value is displayed. (TCI only)
5. Press the ENTER key to confirm this choice. (TCI only)
6. Press the NEXT key until the following screen is displayed.
Genera l Unit Functions Setup Submenu
Press ENTER to Review or Adjust
1.To view the factory preset or to modified the factory presets
to meet specific application requirements, press the
ENTER key to advance to the following screens. If no
adjustments are required, press the NEXT key to advance to
the "Ice Building Control Functions Submenu".
Reduce Multi-Unit Startup Power Demand.
After Power-Up, Dela y Unit Star t 0 Sec
2. Press the + or - key until the proper value is displayed.
3. Press the ENTER key to confirm this choice.
4. Press the NEXT key until the following screen is displayed.
Used on Units:
Possible Values:
Addres s:
Used on Units:
Possible Values:
All Units when TCI or LCI installed
All Units
Control = Local, BAS/NETWORK
33 to 63 (TCI only)
0 to 255 sec
24
Page 25
System Programming SETUP
,
Dema nd Limit De finition: NON E
Reduce cooling capacity by this amount
1. Press the + or - key until the proper value is displayed. 25% - 2 Ckt Only
2. Press the ENTER key to confirm this choice. 50% - All Units
3. Press the NEXT key until the following screen is displayed. 75% - 2 Ckt Only
Compressor Lead/Lag Function: DISABLED
Stage C omp(s) Up/Down in Fixed Sequence
ORNote:
Compressor Lead/Lag Function: ENABLED
1st On = Least Starts, 1st Off = Most Runtime
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Hot Gas Bypass Function: DISABLED
Provides Cooling Level Less Than Cool 1
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice. Lead\Lag is Enabled.
3. Press the NEXT key until the following screen is displayed.
Hot Gas Bypass Max Run Time 30 Min
Max HGBP Duration Until Shut Off Comp
Used on Units:
GBAS10V or TCI
Possible Values:
100% - All Units
Used on Units:
Possible Values:
Lead\Lag can not be Enabled if Hot Gas
Bypass is Enabled.
Used on Units:
installed
Possible Values:
Note:
Hot Gas Bypass can not be Enabled if
Used on Units:
Possible Values:
All Units with GBAS5V,
None - All Units
All Units
Enabled, Disabled
With Ho t Gas Byp ass Option
Enabled, Disabled
With Ho t Gas Byp ass Option i nstalled
10 to 120 minutes
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Capacity=50% if LST exceeds Hot Strt STP
During Hot Start Time Interval: 60 Min
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Hot Operation Response Option:
50% CAPACITY PER CKT
1. Press the + or - key until the proper value is displayed. Allow normal operation
2. Press the ENTER key to confirm this choice. (Info Reset Diag)
3. Press the NEXT key until the following screen is displayed. Shut off co mpressors
Pumpdown Function: DISABLED
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Default Chiller Solution Pump Mode : ON
Pump Always ON Except for Emergency STOP
Default Chiller Solution Pump Mode : AUTO
Turn Pump ON As Requested By CGM Module
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
AUTO RESET DIAG
OR
Used on Units:
Possible Values:
Used on Units:
Possible Values:
(Auto Reset Dia g)
(Manu al Reset Diag)
Used on Units:
Possible Values:
Used on Units:
Possible Values:
All Units
10 to 120 minutes
All Units
50% Capacity per ckt
All Units
Enable, Disable
All Units
On, Auto
25
Page 26
System Programming SETUP
g
g
All Units with Leaving Solution Reset
g
g
Start Temp OA: 46 - 125 F
Zone: 67 - 81 F
Zone: 66 - 80 F
g
g
g
pp
Evap Soln Pump Off Dela y time 30 Sec
Delay Pum p OFF Request By This Amount
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Loop Stabilization Time: 120 Sec
Run Pump To A llow Soln Te mp To Stabilize
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Leaving Solution Reset Type:
NONE - NO RESET APPLIED
1. Press the + or - key until the proper value is displayed. Zone Temp Reset
2. Press the ENTER key to confirm this choice. Enterin
3. Press the NEXT key until the following screen is displayed.
The followin
ENT Soln Reset is selected.
Rese t Type: Outside Air Temp Reset
Start Tem p 70.0 F End Temp 50.0 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor to the "End Temp" Reset Type: Outside Air Temp Reset
4. Press the + or - key until the proper value is displayed. Zone Temp Reset
5. Press the ENTER key to confirm this choice. Enterin
6. Press the NEXT key until the followin
Rese t Type: Outside Air Temp Reset
Maximum A mount of Reset A
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice. ENT Soln Temp Reset: 5 - 79 F
3. Press the NEXT key until the followin
Select Type of Cooling Control Based On
Chille r Application: PROCESS COOLING
two screens will display when either OA, Zone, or
screen is displayed.
lied 5 .0 F
screen is displayed. Max Amount (Zone, OA, ENT Soln Temp Reset): 3 - 16 F
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Outside Air Temp Reset
Used on Units:
Possible Values:
ENT Soln Temp Reset: 6 - 80 F
End Temp OA: 45 - 124 F
All Units
30 to 600 seconds
All Units
30 to 255 seconds
All Units
Enable, Disable
All Units
None - No Reset Applied
Solutio n Temp Reset
Soln Temp Reset
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
26
Used on Units:
Possible Values:
All Units
Comfort Coolin
, Process Coolin
Page 27
System Programming SETUP
Enabled, Disabled
360 Min
j
g
pp
End of Submenu (NEXT) to Re-ente r SETUP
1. Pressing the NEXT key will display the beginning of
the Submenu.
2. Press the NEXT key again to advance to the following screen.
The following screens are displayed with Ice Buil ding Control Option.
Ice Building Cont rol Functions Submenu
Press ENTER to Review or Ad
1. To view the factory preset or to modify the factory presets
to meet specific appli cation requi rements, press the
ENTER key to advance to the following screens. If no
adjustments are required, press the NEXT key to advance to
the "Ice Building Control Functions Submenu".
Ice Building Function: DISABLED
Ice Buildin
2. Press the + or - key until the proper "Function" is displayed.
3. Press the ENTER key to confirm this choice.
4. Press the NEXT key to advance the cursor to the "Mode" Mode = One Time, Continuous
5. Press the + or - key until the proper value is displayed.
6. Press the ENTER key to confirm this choice.
7. Press the NEXT key until the following screen is displayed.
Interval Between Ice Building Cycles.
Ice Rebuild Delay Time 360 Min
Mode: ONE TIME
ust
Used on Units:
Possible Values:
Units with Ice Building Control Option
Function =
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
End of Submenu (NEXT) to Re-ente r SETUP
1. Pressing the NEXT key will display the beginning of
the Submenu.
2. Press the NEXT key again to advance to the following screen.
Head Pressure Ctrl Setup Submenu
Press ENTER to Review or Adjust
1.To view the factory preset or to modified the factory presets
to meet specifi c application requi rements, press the
ENTER key to advance to the following screens. If no
adjustments are required, press the NEXT key to advance to
the "GBAS 0-5 VDC Module I/O Assignments"
Sat urat ed Condens er Temp Control Ba nd
Lower Limit 85 F U
2. Press the + or - key until the proper "LowerLimit" is displayed.
3. Press the ENTER key to confirm this choice.
4. Press the NEXT key to advance the cursor to the "Upper Limit" Upper Limit - 110 to 130 F
5. Press the + or - key until the proper value is displayed.
6. Press the ENTER key to confirm this choice.
7. Press the NEXT key until the following screen is displayed.
er Limit 125 F
Used on Units:
Factory Preset:
Possible Values:
Used on Units:
Possible Values:
Units with Ice Building Control Option
All Units
30 to 1410 Minutes
Lower Limit - 70 to 90 F
27
Page 28
System Programming SETUP
(
Saturated Condens er Temp Control Band
Temporary Low Limit Suppress ion 10 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Saturated Condenser Temperature
Efficiency Check Point 110 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Saturated Condenser Temperature
Low Ambient Control Point 100 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Saturated Condenser Temperature
Low Ambient Control Deadband 4.0 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Saturated Condenser Temperature
OA Temp Supression Setpoint 40 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
End of Submenu
NEXT) to Re-enter STATUS
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Used on Units:
Possible Values:
All Uni ts
All Uni ts
All Uni ts
All Uni ts
All Uni ts
0 to 20 F
95 to 115 F
80 to 110 F
2.0 to 10.0 F
25 to 66 F, Disabled
1. Pressing the NEXT key will display the beginning of
the Submenu.
2. Press the NEXT key again to advance to the following screen.
This screen is displayed when GBAS 0-5 VDC Module is installed
GBAS 0-5VDC Module I/O Assignment
Press ENTER to Review or Adjust
1.To view the factory preset or to modified the factory presets
to meet specific application requirements, press the
ENTER key to advance to the following screens. If no
adjustments are required, press the NEXT key to advance to
"GBAS 0-10 VDC Module I/O Assignments"
GBAS (0-5VDC) Analog Input 1 Assignment
NOT ASSIGNED
2. Press the + or - key until the proper value is displayed. Hot Start Load Limit Setpoint
3. Press the ENTER key to confirm this choice. Capaci ty Li mit Setpoint
4. Press the NEXT key to display Generic BAS Analog Input
2 screen.
5. Press the + or - key until the proper value is displayed.
6. Press the ENTER key to confirm each choice.
7. Repeat steps 1 - 4 to display Generic BAS Analog Input
screens 2, 3 & 4.
8. Press the NEXT key to advance to the following screen.
Used on Units:
Possible Values:
Ice Build Terminate Setpoint
With GBAS 0-5VDC Module
Leaving Solution Setpoint
28
Page 29
System Programming SETUP
With GBAS 0-5VDC Modul e
Not Assigned
k
j
GBAS (0-5VDC) Binary Output 1 Definition
OUTPUT IS NOT ASSIGNED
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed. Indicate Selected Diag Alarms
The following screens will display if "Indicate selected diagnostics Indicate any comp is running
alarms" is assigned to any of the 5 Binary Output Definitions.
GBAS (0-5VDC) Output 1 Alarm Assignments
Press ENTER to Review or Ad
1.To view the factory preset or to modified the factory presets
to meet specific application requirements, press the
ENTER key. If no adjustments are required, press the NEXT
ey to advance to the following screen.
Assign Diag To GBAS (0-5V) Output #1 ?
Any Active Diagnostic (No)
2. Press the + or - key until the proper value is displayed. If "YES"
is assigned to "Any Active Diagnostic", pressing the NEXT key
will advance to the Binary Output 2 Definition screen. Assigning
"NO" to the "Any Active Diagnostic" will advance to the selectable
diagnostic screens.
3. Press the ENTER key to confirm each choice.
4. Press the NEXT key to scroll through each Active Diagnostic.
ust
Used on Units:
Possible Values:
Indi cate Uni t at Max Capacity
Used on Units:
Possible Values:
With GBAS 0-5VDC Modul e
Yes, No
Active Diagnostics
CGM ICS Temperature Sensor FailLiquid Pressure Sensor Fail Ckt 1
CGM Module Data Storage ErrorLiquid Pressure Sensor Fail Ckt 2
CGM OA Temp Sensor FailureLow Ambient Evap Soln Pump Override
CGM Zone Temp Sensor FailureLow Soln Cutout Temp (Man)
Ckt 1 Pumpdown Terminated by TimeLow Soln Cutout Temp (Auto)
Ckt 2 Pumpdown Terminated by TimeLow Press Control Open - Ckt 1
Comp Contactor Fail - Ckt 1Low Press Control Open - Ckt 2
Comp Contactor Fail - Ckt 2LSS Adjusted To Maintain Min Diff
Compressor Trip - Ckt 1EST/LST Low Temperature Indication
Compressor Trip - Ckt 2MCM Communications Failure
Comp Protection LPC Open - Ckt 1Sat Liquid Temp Sensor Fail Ckt 1
Comp Protection LPC Open - Ckt 2Sat Liquid Temp Sensor Fail Ckt 2
Cond Temp Sensor Failure - Ckt 1SCM Communications Failure
Cond Temp Sensor Failure - Ckt 2Suction Pressure Sensor Fail Ckt 1
Current Sensor Module Comm FailSuction Pressure Sensor Fail Ckt 2
Emergency StopSuction Temp Sensor Failure - Ckt 1
Evap Enteri ng Soln Temp Sensor FailSuction Temp Sensor Failure - Ckt 2
Evap Leaving Soln Temp Sensor FailSuperheat/Subcool Module Comm Fail
Evap Solution Flow Proving SwitchBAS Module Comm Failure
Evap Solution Flow LossBAS/NETWORK Comm Failure
Extern Leaving Soln STP Input FailUnit HI Communications Failure
GBAS 0-5VDC Module Comm Failure
GBAS 0-10VDC Module Comm Fail
Hot Start Load Limit (Auto)
Hot Start Load Limit (Info)
Hot Start Load Limit (Man)
Hot Start Load Limit STP Fail
IBTS Adjusted To Maintain Min Diff
Ice Build Terminate Setpoint Fail
Leaving Solution Setpoint Fail
29
Page 30
1. Press the NEXT key to display Generic BAS Binary Output
With GBAS 0-5VDC Module
g
g
g
g
g
g
g
g
With GBAS 0-10VDC Module
g
g
g
g
g
g
j
2 Definition screen.
GBAS (0-5VDC) Binary Output 2 Definition
System Programming SETUP
2. Press the + or - key until the proper value is displayed.
3. Press the ENTER key to confirm this choice.
4. Press the NEXT key to display Generic BAS Binary Output Indicate Selected Di a
3 screen. Indicate Unit at Max Capacity
5. Press the + or - key until the proper value is displayed. Indicate any comp is runnin
6. Press the ENTER key to confirm each choice.
7. Repeat steps 1 - 4 to display Generic BAS Binary Output
screens 3, 4 & 5.
8. Press the N EXT key to advance to the follow in
End of Submenu (NEXT) to Re-enter SETUP
1. Pressin
the Submenu.
2. Press the NEXT key a
This screen is displayed when GBAS 0-10 VDC Module is installed
GBAS 0-10VDC Module I/O Assignments
1.To view the factory preset or to modified the factory presets
to meet specific application requirements, press the
ENTER key. If no adjustments are required, press the NEXT
key to advance to the "CGM Alarm Output Diagnostic
Assignments"
GBAS (0-10VDC) Analog Input 1 Assignment
NOT A SSIGNED
2. Press the + or - key until the proper value is displayed.
3. Press the ENTER key to confirm this choice.
4. Press the NEXT key to display Generic BAS Analo
2 screen. Ice Build Terminate Setpoint
5. Press the + or - key until the proper value is displayed. Hot Start Load Limit Setpoint
6. Press the ENTER key to confirm each choice. Capacity Limit Setpoint
7. Repeat steps 1 - 4 to display Generic BAS Analo
screens 2, 3 & 4.
8. Press the N EXT key to advance to the following scree n.
GBAS (0-10VDC ) Binary Output Definition
OUTPUT IS NOT A SSIGNED
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the followin
The followin
alarms" is assigned.
GBAS (0-10VDC) Output Alarm Assignments
Press ENTER to Review or Ad
1.To view the factory preset or to modified the factory presets
to meet specific application requirements, press the
ENTER key to advance to the followin
adjustments are required, press the NEXT key to advance to
the GBAS Anal o
the NEXT key will display the beginning of
ain to advance to the following screen.
screen i s displayed . Indicate Sele cted Diag Alarms
screen will display if "Indicate selected dia
ust
screens. If no
Output Assignment screen.
screen.
Input Leaving Solutio n Setpoin t
Inp ut
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Indicate Unit at Max Capa city
Indicate any comp is runnin
Outp ut is Not Assigned
Alarms
With GBAS 0-10VDC Module
Not Assi
Output is Not Assigned
ned
30
Page 31
System Programming SETUP
With GBAS 0-10VDC Module
With GBAS 0-10VDC Module
(
y
)
Assign D iag To GBAS (0-10V) Output ?
Any Ac tive D iagnostic (No)
2. Press the + or - key until the proper value is displayed. If "YES"
is assigned to "Any Active Diagnostic", pressing the NEXT key
will advance to the "End of Submenu" screen.
Assigning "NO" to the "Any Active Diagnostic" will advance to
the selectable diagnostic screens. See 0-5 active diagnostics list.
3. Press the ENTER key to confirm each choice.
4. Press the NEXT key to scroll through each Active Diagnostic.
GBAS (0 -10VDC) Analog Output 1 Assignment
NOT ASSIGN ED
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
Used on Units:
Possible Values:
Used on Units:
Yes, No
GBAS (0-10VDC) Analog Output 2 Assignment
NOT ASSIGN ED
1. Press the + or - key until the proper value is displayed. Ckt 1 Sat Cond Temp
2. Press the ENTER key to confirm this choice. Ckt 2 Sat Cond Temp
3. Press the NEXT key until the following screen is displayed. Ckt 1 Sat Liquid Temp
4. Press the NEXT key to display Generic BAS Analog Output Ckt 2 Sat Liquid Te mp
3 screen. Ckt 1 Suction Pressure
5. Press the + or - key until the proper value is displayed. Ckt 2 Suctio n Pressure
6. Press the ENTER key to confirm each choice. Ckt 1 Su ction Temperature
7. Repeat steps 1 - 4 to display Generic BAS Analog Output Ckt 2 Suction Temperature
screens 3 & 4. Enteri ng So lution Temperature
8. Press the NEXT key to advance to the foll owing screen. ICS Define d Temperature
End of Submenu
1. Pressing the NEXT key will display the beginning of
the Submenu.
2. Press the NEXT key again to advance to the following screen.
CGM Alarm Output D iagnostic Assignments
1.To view the factory preset or to modified the factory presets
to meet specific application requirements, press the
ENTER key to advance to the fo llowing scree ns. If no
adjustments are required, press the NEXT key to advance to
the "Device Characteristic Setup Definitions" screen.
Assign D iagnostic to CGM Alarm Output?
An
Active Diagnostic (No
2. Press the + or - key until the proper value is displayed. If "YES"
is assigned to "Any Active Diagnostic", pressing the NEXT key
will advance to the "End of Submenu" screen.
Assigning "NO" to the "Any Active Diagnostic" will advance to
the selectable diagnostic screens. See the active diagnostics
list in the GBAS 0-5V section.
3. Press the ENTER key to confirm this choice.
4. Press the NEXT key until the following screen is displayed.
1. Pressing the NEXT key will display the beginning of
the Submenu.
2. Press the NEXT key again to advance to the following screen.
NEXT) to Re-enter SETUP
-
Possible Values:
Ckt 1 Liqui d Line Pressure
Ckt 2 Liqui d Line Pressure
Leaving Solution Temperature
Outside Air Te mperature
Used on Units:
Possible Values:
Active Cooling Capacity
All Units
Yes, No
31
Page 32
All Units
All Units
All Units
40 - 60 Ton Units
40 - 60 Ton Units
Device Characteristic Setup Definitions
Press ENTER to Review or Adjust
1.To view the factory preset or to modified the factory presets
to meet specific application requirements, press the
ENTER key to advance to the following screens. If no
adjustments are required, press the NEXT key to advance to
the "Control Al gori thm Tuning Paramete rs".
Actuator Setup Ckt1 Low Ambient Output
Max Stroke Tim e 60 Sec
2. Press the + or - key until the proper value is displayed.
3. Press the ENTER key to confirm this choice.
4. Press the NEXT key until the following screen is displayed.
Actuator Setup Ckt1 Low Ambient Output
Min Voltage 2 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup Ckt1 Low Ambient Output
Max Voltage 10 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to ad vance the cursor to the "4 00 PSIG"
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm this choice.
6. Press the NEXT ke y until the followin
End of Submenu (NEXT) to Re-enter STA TUS
screen is displayed.
screen is displayed.
screen is displayed.
screen is displayed.
Used on Units:
Possible Value s:
100 PSIG - 1.000 to 5.000 VD C
Used on Units:
Possible Value s:
400 PSIG - 1.000 to 5.000 VDC
Used on Units:
Possible Value s:
100 PSIG - 1.000 to 5.000 VD C
Used on Units:
Possible Value s:
400 PSIG - 1.000 to 5.0 00 VD C
With Superheat/Subcoolin
With Superheat/Subcoolin
Option
Option
1. Pressin
the Submenu.
2. Press the NEXT key a
Control Algorithm Tuning Parame ters
Press ENTER to Review or Ad
1.To view the factory preset or to modified the factory presets
to meet specific application requirements, press the
ENTER key to advance to the follow in
adjustments are required, press the NEXT key to advance to
the be
Comfort Cooling
Desi
2. Press the + or - key until the proper value is displayed.
3. Press the ENTER key to confirm this choice.
4. Press the NEXT ke y until the followin
the NEXT key will display the beginning of
ain to ad vance to the fol lowing screen.
ust
screens. If no
inning of the "Setup" menu.
n Delta Temperature Setpoint 10.0 F
screen is displayed.
33
Used on Units:
Possible Value s:
4.0 to 20.0 F
Page 34
System Programming SETUP
g
g
g
g
g
g
Pos sible Va lues:
EN TER key to ad va nce to the foll owi ng screens. If no
adjustments are required, press the NEXT key to advance to
the be
Com fort Cooling
Design Delta Temperature Setpoint 10.0 F
2. Press the + or - key until the proper value is displayed.
3. Press the ENTER key to confirm this choice.
4. Press the NEXT key until the followin
Com fort Cooling
Control Re sponse Setpoint 25
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the followin
Proces s Cooling C ontrol Gains
Proportional 25 % /F Reset Time 90s
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor to the "Reset Time"
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm this choice.
6. Press the NEXT key until the followin
Proces s Cooling C ontrol Gains
Proport Bias 0% Max C y Rate 1 5.0 cph
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor to the "Max Cy
Rate ".
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm this choice.
6. Press the NEXT key until the followin
Low Am bient Fan Control Gain
Proportional 2.0 % /F Reset Time 90 Sec
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor to the "Reset Time"
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm this choice.
6. Press the NEXT key until the followin
Low Am bient Fan Control Gain
Rate Tim e 0 Se c
1. Press the + or - key until the proper value is displayed.
inning of the "Setup" menu.
screen is displayed.
screen is displayed.
screen is displayed.
screen is displayed.
screen is displayed.
Used on Units:
Pos sible Va lues:
Used on Units:
Pos sible Va lues:
Used on Units:
Pos sible Va lues:
Reset Time 30 to 3600 Sec
Used on Units:
Pos sible Va lues:
Ma x C y Ra te - 1.5 to 2 0.0 cph
Used on Units:
Pos sible Va lues:
Reset Time 5 to 60 0 Se c
Used on Units:
All Units
4.0 to 20.0 F
All Units
1 to 128
All Units
Proportional 2.0 to 200.0
All Units
Proport Bias 0 to 400%
All Units
Proportional 0.2 to 20.0
All Units
0 to 50
34
Page 35
System Programming SETPOINTS
g
g
g
g
g
g
g
g
g
g
g
All Brazed Plate Units
g
g
g
g
g
g
g
p
p
p
p(s)
p
SETPOINTS Menu
When a setpoint screen is displayed for 30 minutes without
a key being pressed, the LCD screen will revert to the gen-
The SETPOINTS menu is used to designate default
setpoints, low ambient compressor lockout setpoints and
eral operating status display. If this happens, press the
SETPOINT key again to return to the setpoint menu.
select setpoint sources.
These setpoints will be active (in use) for the "Setpoint
Source Selection" designated as "DEFAULT" for these inputs.
HI Leaving Solution Setpoint: 44 F
1. Press the + or - key until the proper value is displayed. Ran
2. Press the ENTER key to confirm thi s choice. Ran
3. Press the NEXT key until the followin
Stop Ice Making When Ent Soln Temp Below
Hi Ice Build Terminate Set
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the followin
Comp(s) OFF if Solution Temp Below
Low Solution Cutout Tem
1. Press the + or - key until the proper value is displayed. Solution Setpoint’
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the followin
Heat Output ON When EST or LST Less Than
Heat Ta
1. Press the + or - key until the proper value is displayed. Solution Setpoint’
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the followin
e Temperature Setpoint: 40.0 F
oint: 27.0 F
: 35.0 F
screen i s displayed. Range 20.0 - 29.0°F
screen is displayed.
screen is displayed.
screen is displayed.
Used on Units:
Possible Values:
Ran
Ran
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Note: Maximum settin
Used on Units:
Possible Values:
Note: Maximum settin
All Units
Based on Confi
Units with Ice Buildin
20.0 to 31.0 F
All Units
-10.0 to 60.0 F
0 to 45.0 F
ured Leaving Solution STP Range:
e 51.0 - 65.0°F
e 40.0 - 50.0°F
e 30.0 - 39.0°F
e 10.0 - 75.0°F (SPECIAL)
Control Option
may be limited by ’Hi Leavin
may be limited by ’Hi Leavin
HI Hot Start Load Limit Setpoint: 71.0 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the followin
Request Pump ON When OA Temp Less Than
Low Ambient Pum
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the followin
Low Ambient Comp Lockout Temp: 40 F
Com
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the followin
Use Leav ing Solution Se tpoint
From: HUMAN INTERFACE STP MENU
1. Press the + or - key until the proper value is displayed. GBAS 0-10VDC Module
2. Press the ENTER key to confirm thi s choice. Ext Leavin
OFF if OA Temp Below This Value
Overr ide Temp: 35 F
screen is displayed.
screen is displayed.
screen is displayed.
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Used on Units:
Possible Values:
GBAS 0-5VDC Module
All Units
60.0 to 80.0 F
All Units
-20.0 to 50.0 F
All Units
-20.0 to 60.0 F
All Units
Human Interface STP Menu
Soln STP Input
35
Page 36
System Programming SETPOINTS
Used on Units:
Used on Units:
Used on Units:
3. Press the NEXT key until the following screen is displayed.
Use Ic e Building Te rminate Setpoint
From: HUMAN INTERFACE STP MENU
1. Press the + or - key until the proper value is displayed. GBAS 0-10VDC Module
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Use Hot Star t Load Limit Se tpoint
From: HUMAN INTERFACE STP MENU
1. Press the + or - key until the proper value is displayed. GBAS 0-10VDC Module
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Use Capacity Limit Setpoint
From: NO SOURCE SELECTED
1. Press the + or - key until the proper value is displayed. GBAS 0-10VDC Module
2. Press the ENTER key to confirm this choice.
3. Pressing the NEXT key will return to the 1st SETPOINT
screen.
4. Press the AUTO or STOP key to return to the top level
status information screen.
Possible Values:
GBAS 0-5VDC Module
Possible Values:
GBAS 0-5VDC Module
Possible Values:
GBAS 0-5VDC Module
With Ice Building Control Option
Human Interface STP Menu
All Units
Human Interface STP Menu
With GBAS5V or GBAS10V
No Source Selected
36
Page 37
CONFIGURATION Menu
Used on Units:
20, 25, 30, 40, 50, 60
Used on Units:
Used on Units:
Installed, Not Installed
Used on Units:
51-65 F, 40-50 F, 30-39 F,
20-29 F, Special
Used on Units:
Installed, Not Installed
Used on Units:
Installed, Not Installed
Used on Units:
Installed, Not Installed
Used on Units:
Installed, Not Installed
g
System Configuration
The CGM controlled unit has many operating functions
whose settings are preset at the factory. The following configuration programming steps are provided for those cases
where the Human Interface module has been replaced after
the unit has been in operation and must be reconfigured.
Press the CONFIGURATION key to display the following
screens. Check the unit model number and compare it to the
data that is displayed in the following screens
Configuration - Model Num Digit 5,6,7
Unit Capacity 50
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 8
Line Voltage 460 VAC
1. Press the + or - key unti l the proper value is displayed. Special Voltage
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 11
Ice Buildin
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 11
Leaving Solution STP Range 40 - 50 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 13+
Hot Gas Bypass Option INSTALLED
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 13+
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 13+
GBAS 0-10VDC Module INSTALLED
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 13+
Control INSTALLED
-
Refer to the Model number stamped on the unit nameplate
located on the control panel door while scrolling through the
configuraton screes. Certain digits of this alpha/numeric
model number provide information that must be entered at
the Human Interface (HI) in order for the CGM network to
operate properly.
All Units
Possible Values:
All Units
Possible Values:
415 VAC, 460 VAC, 575 VAC,
Possible Values:
Possible Values:
Possible Values:
Possible Values:
Possible Values:
Possible Values:
200 VAC, 230 VAC, 380 VAC,
All Units
All Units
All Units
All Units
All Units
All Units
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
37
Page 38
System Configuration
All Units
Installed, Not Installed
All Units
Installed, Not Installed
All Units
Installed, Not Installed
All Units
20 to 30 Ton Units
40 to 60 Ton Units
With GBAS 10VDC Module
3. Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 13+
Curre nt Sensing Module IN STALLED
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 13+
BAS Communications Module INSTALLED
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 13+
Remote Human Interface INSTALLED
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
The following displays are not editable.
Software Revision Number Report:
Cold Gener ator Module (CGM) 1.00
1. Press the NEXT key until one of the following screens is displayed.
Software Revision Number Report:
Single Compress or Module (SCM) 1.00
OR
Software Revision Number Report:
Multiple Compressor Module (MCM) 1.00
1. Press the NEXT key until the following screen is displayed.
Software Revision Number Report:
GBAS 0-5VDC Module 1.0 0
1. Press the NEXT key until the following screen is displayed.
Software Revision Number Report:
GBAS 0-10VD C Module 1 .00
1. Press the NEXT key until the following screen is displayed.
Software Revision Number Report:
Superheat/Subcool Module (SSM) 1.00
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Used on Units:
Possible Values:
With GBAS 5VDC Module
With SSM Module
1.0 or Greater
1.0 or Greater
1.0 or Greater
1.0 or Greater
1.0 or Greater
1.0 or Greater
38
Page 39
1. Press the NEXT ke y until th e following screen is displayed.
g
g
g
g
Software Revision N umber Report:
Curre nt Sensing Module (CSM) 1.00
1. Press the NEXT ke y until th e followin
Software Revision N umber Report:
Unit Human Interfac e (HI) 1.00
1. Press the NEXT ke y until th e followin
Software Revision N umber Report:
Remote Huma n Interface (RHI) 1.00
1. Press the NEXT ke y until th e followin
Software Revision N umber Report:
BAS Communications: Comm3 1.00
1. Pressin
CONFIGURATION screen.
2. Press the AUTO or STOP ke y to return to the top level
status info rmation screen.
the NEXT key will return to the 1st
screen is displayed.
screen is displayed.
screen is displayed.
System Configuration
Used on Units:
Possible Value s:
Used on Units:
Possible Value s:
Used on Units:
Possible Value s:
Used on Units:
Possible Value s:
Comm5 (with LC I module )
Possible Value s:
With CSM Module
1.0 or Greater
All Units
1.0 or Greater
With Re mote H uman Inte rface Module
1.0 or Greater
With TCI o r LCI Module
Comm3 (with TCI module)
1.0 or Greater
39
Page 40
System Testing & Troubleshooting
All Units
All Units
All Units
With Ho t Gas Byp ass Option
SERVICE MODE Menu
The SERVICE MODE menu is used to input operating parameters for unit operation during a service test. Depending
on the particular test being conducted, the user will cycle
through all unit outputs (compressors, fans, pump, etc...)
and selectively turn them On or Off for the test. After designating the operating status for each unit component, the operator will designate the "TEST START" delay time.
To operate the system in the TEST MODE, press the SERVICE
MODE key to enter into the service mode menu and scroll
through all of the system outputs and selectively turn them
"On" or "Off".
CGM Eva p Solution Pump R elay: OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Liquid Line Solenoid Valve Ctrl Relays:
Ckt 1 ON Ckt 2 OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor to the "Ckt 2"
Circuit 2 is use d for 40 through 60 Ton units only.
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm this choice.
6. Press the NEXT key until the following screen is displayed.
Low Ambient LPC Bypass Relay(s)
Ckt 1 ON Ckt 2 OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor to the "Ckt 2"
Circuit 2 is use d for 40 through 60 Ton units only.
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm this choice.
6. Press the NEXT key until the following screen is displayed.
CGM Hot Gas Bypass Control Relay: OFF
When a service mode screen is displayed for 30 minutes
without a key being pressed, the LCD screen will revert to
the general operating status display. If this happens, press
the SERVICE MODE key again to return to the service
menu.
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Used on Units:
Possible Values:
On, Off
On, Off
On, Off
On, Off
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Compressor Relays
K11 OFF K 12 OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor to the "K11"
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm this choice.
6. Press the NEXT key until the following screen is displayed.
40
Used on Units:
Possible Values:
20 to 3 0 Ton
On, Off
Page 41
System Testing & Troubleshooting
g
40 to 60 To n
g
g
g
40 to 60 To n
g
g
g
OR
The followin
Compress or R elays
K11 OFF K 12 OFF K3 OFF K4 OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm thi s choice.
3. Press the NEXT key to advance the curso r to the "K12"
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm thi s choice.
6. Press the NEXT key to advance the curso r to the "K3"
7. Press the + or - key until the proper value is displayed.
8. Press the ENTER key to confirm thi s choice.
9. Press the NEXT key to advance the curso r to the "K4"
10. Press the + or - key until the proper value is displayed.
11. Press th e ENTER ke y to confirm this choice.
12. Pre ss the NEXT key until the followin
Condenser Fan Outputs
1A OFF 1B OFF 1C OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm thi s choice.
3. Press the NEXT key to advance the curso r to the "1B"
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm thi s choice.
6. Press the NEXT ke y until th e followin
7. Press the + or - key until the proper value is displayed.
8. Press the ENTER key to confirm thi s choice.
9. Press the NEXT key to advance the curso r to the "2B"
screen will display on 40 to 60 Ton units.
screen is displayed.
screen is displayed.
Used on Units:
Possible Values:
Used on Units:
Possible Values:
All Units
On, Off
On, Off, Auto
The followin
Condenser Fan Outputs
2A OFF 2B OFF 2C OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm thi s choice.
3. Press the NEXT key to advance the curso r to the "1B"
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm thi s choice.
6. Press the NEXT key to advance the curso r to the "2A"
7. Press the + or - key until the proper value is displayed.
8. Press the ENTER key to confirm thi s choice.
9. Press the NEXT key to advance the curso r to the "2B"
Condenser Fan Speed
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm thi s choice.
Circuit 2 is used for 40 through 60 Ton units only.
3. Press the NEXT key to advance the curso r to the "Ckt 2"
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm thi s choice.
6. Press the NEXT ke y until th e followin
MCM He ater Tape Relay K13: OFF
Relay ON: Heat Off, Rela y OFF: Heat On
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm thi s choice.
3. Press the NEXT ke y until th e followin
CGM Alarm Output: OFF
screen will display on 40 to 60 Ton units.
screen is displayed.
screen is displayed.
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Note: Th is is the low ambient damper position
Used on Units:
Possible Values:
On, Off, Auto
All Units
Auto, 0 to 100%
All Brazed Plate Units
On, Off
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm thi s choice.
3. Press the NEXT ke y until th e followin
screen is displayed.
41
Page 42
System Testing & Troubleshooting
0.0 to 1 0.0 VDC
0.0 to 1 0.0 VDC
3. Press the NEXT key until the following screen is displayed.
CGM Ice Build Relay Output : OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
GBAS 0-5VDC Module Relay Outputs
#1 OFF #2 OFF #3 OFF #4 OFF #5 OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT ke y to advance the cu rsor to the "#2 Output"
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm this choice.
6. Repeat steps 1 - 4 for Outputs 3, 4 & 5.
7. Press the NEXT key until the following screen is displayed.
GBAS 0-10 VDC Module Relay Output: OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
GBAS 0-10VDC Module Analog Outputs
Out #1 0.2 VD C Out #2 0.4 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT ke y to advance the cu rsor to the "#2 Output"
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm this choice.
6. Press the NEXT key until the following screen is displayed.
GBAS 0-10VDC Module Analog Outputs
Out #3 0.6 VD C Out #4 0.8 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT ke y to advance the cu rsor to the "#4 Output"
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm this choice.
6. Press the NEXT key until the following screen is displayed.
CGM ICS C ontrolled Rela y: OFF
Used on Units:
Possible Value s:
Used on Units:
Possible Value s:
Used on Units:
Possible Value s:
Used on Units:
Possible Value s:
Used on Units:
Possible Value s:
Used on Units:
Possible Value s:
With Ice Bui lding Control Option
With GBAS 5VDC Mod ule Option
With GBAS 10VDC Mo dule Option
With GBAS 10VDC Mo dule Option
With GBAS 10VDC Mo dule Option
With TCI Module Op tion (For Future Use)
On, Off
On, Off
On, Off
On, Off
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
42
Page 43
System Testing & Troubleshooting
All Units
5 to 255 seconds
All Units
All Units
All Units
g
3. Press the NEXT key until the following screen is displayed.
Start Test in 5 Sec
Press TEST START To Begin, STOP To Halt
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
The following screen will be displayed after pressing the "TEST
START" key if a SERVICE MODE screen has been displayed
during the previous 60 minutes.
Test Start In 5
Press STOP To Halt
If a screen has not been displayed during the SERVICE MODE
procedure for 60 minutes and the TEST START key is pressed,
the following screen will be displayed.
Press SERVICE MODE
To Revie w Selections
When the START TEST timer expires, this screen will be displayed
at the unit mounted Human Interface and at the remote mounted
Human Interface, if installed.
Service Test Is Active
Press STOP To Ha lt
Note:
There is no time-out period when the unit is operating in the
SERVICE TEST mode. Press the "STOP" or "AUTO" key to
discontinue the Service Test. Only the STATUS, CUSTOM,
SERVICE MODE, DIAGNOSTICS, and STOP keys are functional
once the TEST START key has been pressed.
Sec
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Used on Units:
Used on Units:
120 to 0 Seconds
After pressing the STOP or AUTO key, the following screen is displayed
Service Mode, STOP SYSTEM Restart
Communicatin
and then the following screen is displayed:
Updating Unit Data. Please Wait
TRANE INTELLIPAK
and then the top level status screen is displayed.
With Unit. Please Wait
43
Page 44
System Testing & Troubleshooting
g
g
g
DIAGNOSTICS Menu
The DIAGNOSTICS menu is used to view diagnostics that
have resulted from system failures within the unit. There are
two lists where diagnostics reside; the Active list, and the
Diagnostic Event Log.
The Active list is used for viewing all active diagnostics and
for clearing manually resetable diagnostics. This list of diagnostics are displayed after pressing the DIAGNOSTICS key
if active diagnostics are present.
Active manual diagnostics can be cleared in batch form at
the unit mounted Human Interface. When an Active diagnostic is manually or automatically cleared, it is removed
from this buffer. Automatically resetting diagnostics can not
be reset by the Human Interface, because the condition
which caused the diagnostic has to be corrected for the diagnostic to clear.
The word “MORE” is displayed on all screens if more than
one diagnostic exists, except for the last diagnostic. Upon
reaching the last diagnostic, the word “MORE” disappears.
Pressing the NEXT key at this point causes the display to
advance to the first diagnostic in the Diagnostic Event Log.
The Diagnostic Event Log screens are displayed after
scrolling through the Active list or after pressing the
DIAGNOSTICS key when no active diagnostics are present.
It’s used to view the past 20 diagnostics. Diagnostics in this
log are stacked in inverse chronological order, with the first
diagnostic screen being the most recently reported diagnostic.
When a new diagnostic is displayed, the words “NOT
VIEWED” are displayed with it. After viewing the last
unviewed diagnostic, the words "NOT VIEWED" change to
"VIEWED" for every diagnostic in the log. The diagnostic
will remain this way as long as it is in the log. This allows
the operator to distinquish between old and new diagnostics
in the Event Log.
Pressing the NEXT key after reaching the last diagnostic in
the Event Log advances the display to the first diagnostic in
the Active list if any exist. If not, the display reverts back to
the first Event Log diagnostic. If the Diagnostic Event Log is
full (20 events), and another diagnostic occurs, the oldest
diagnostic is pushed off the end of the list. If all 20 diagnostics in the list are active when the 21st occurs, then the oldest Active diagnostic is pushed off the end of the list. When
an Active diagnostic is automatically or manually cleared in
the Active buffer, its status in the Diagnostic Log changes
from Active to History. If the operator does not clear an active diagnostic in the Active log, its status will still show as
Active in the Diagnostic Log.
When a diagnostic screen is displayed for more than four
hours without a key being pressed, the screen will return to
the operating status display.
One of the following screens will be the first screen displayed when
the DIAGNOSTIC" key is pressed.
Diagnostic Menu ---- Info
No Active Dia
Press CANCEL to Clear All Active Manual
nostics, or Press NEXT to View
Dia
1. If there are active diagnostics, pressing the "CANCEL" key to clear
the diagnostics will prompt the following screen.
Diagnostic Reset Is Password Protected
Please Enter Password:
1. Press the + (Plus) or - (Minus) keys to enter the password
2. Press the ENTER key to confirm this choice. When the
correct password is entered, the following screen will be displayed.
nostics (NEXT) History Lo
OR
Used on Units:
Possible Values:
All Units
+ (Plus) and - (Minus)
44
Page 45
System Testing & Troubleshooting
p
g
Resetting Active Manual Diagnostics
Sendin
and then the following screen will be displayed
Resetting Active Manual Dia gnostic s
U
and then the following screen will be displayed
Active Diagnostic ---- Info
"Please Wait . . . Unit Is In Reset Mode"
3. Pressing the "NEXT" key to view the diagnostics will prompt the
following screen if a "MANUAL RESET" failure has occurred.
Active Diagnostic ---- Manual Reset
The word MORE will only appear if more than one failure has
occurred.
Pressing the "NEXT" key to view the diagnostics will prompt the
following screen if an "AUTO RESET" failure has occurred.
Active Diagnostic ---- Auto Reset
The word MORE will only appear if more than one failure has occurred.
dating Unit Data, Please Wait
Reset Request
OR
More
OR
More
Used on Units:
Used on Units:
All Units
All Units
Possible Values:
CGM OA Temp Sensor Failure,IBTS Adjusted to Maintain Min Diff
CGM Zone Temp Sensor Failure,Ice Build Terminate Setpoint Fail
Cond Temp Sensor Failure - Ckt 1, Leaving Solution Setpoint Fail
Cond Temp Sensor Failure - Ckt 2, Low Ambient Evap Solution Pump Override
Current Sensing Module Comm FailLow Solution Cutout Temp (Auto)
Evap Solution Flow Proving SwitchLSS Adjusted to Maintain Min Diff
Ext. Leaving Solution STP Input FailMCM Communications Failure
GBAS 0-5V Module Comm FailureSCM Communications Failure
GBAS 0-10V Module Comm FailBAS Module Comm Fai l ure
Hot Start Load Limit (Auto)BAS/NETWORK Comm Failure
Hot Start Load Limit STP FailUnit HI Communications Failure
OR
Pressing the "NEXT" key to view the diagnostics will prompt the following
screen if an "Information Only" failure has occured.
45
Page 46
System Testing & Troubleshooting
Active Diagnostic ---- Info
The word MORE will only appear if more than one failure has
occured.
If additional active diagnostics are present, pressing the NEXT key will display them.
Possible Values:
CGM ICS Temperature Sensor FailSat Liquid Temp Sensor Fail Ckt 1
CGM Module Data Storage ErrorSat Liquid Temp Sensor Fail Ckt 2
EST/LST Low Temperature IndicationSuction Pressure Sensor Fail Ckt 1
Hot Start Load Limit (Info)Suction Pressure Sensor Fail Ckt 2
Liquid Pressure Sensor Fail Ckt 1Suction Temp Sensor Fail Ckt 1
Liquid Pressure Sensor Fail Ckt 2Suction Temp Sensor Fail Ckt 2
Pumpdown Terminated By Time Ckt 1Superheat/Subcool Module Fail
Pumpdown Terminated By Time Ckt 2
After viewing all active diagnostics, pressing the NEXT key will display the following screen
Log 1 __________
Pressing the NEXT key will display each successive log entry.screens associated with the type of diagnostic.
1. Pressing the "CANCEL" key to clear the diagnostics log will
display the following screen.
Diagnostic Log Is Password Protected
Please Enter Password:
1. Press the + (Plus) or - (Minus) keys to enter the password
2. Press the ENTER key to confirm this choice. When the
correct password is entered, the following screen will be
displayed.
More
Used on Units:
Used on Units:
Possible Values:
Not Viewed, Active or History, Manual, Auto,
or Info., Any diagnostic listed under the previous
Used on Units:
Possible Values:
All Units
All Units
Log Number 1-20, Viewed or
All Units
+ (Plus) and - (Minus)
Active Diagnostics ____________________
"Please Wait . . . Updating Diagnostic Log"
If the "DIAGNOSTIC LOG" is empty when the "CANCEL" key is
pressed, the following screen will be displayed.
Active Diagnostics ---- Info
"Diagnostic Buffer Is Already Empty !"
Press the AUTO or STOP key to return to the top level status screen.
Failure Modes
When any condition results in the unit's unability to perform
a normal function, it is said to have entered a failure mode.
There are two types of failure modes.
1. An "Analog input out of range" failure mode.
This failure mode occurs when a sensing device such as a
temperature sensor begins to transmit information that is
outside its allowable range.
2. A "Fault recognition by input logic" failure mode.
This failure mode occurs when the UCM receives information that does not "make sense" or does not conform to its
predefined logic.
Used on Units:
Possible Values:
Used on Units:
Possible Values:
All Units
Manual, Auto, or Info
All Units
Manual, Auto, or Info
46
Page 47
All Units with Local HI
All Units with Local HI
k
System Testing & Troubleshooting
Communications Link Problems
If one of these messages appear on the Human Interface screen,
that Human Interface is not communicating with the unit.
LOCAL HI COMMUNICATIONS LOSS
OR
REMOTE HI COMMUNICATIONS LOSS
CHECK COMM LINK WIRING TO UNIT NUMBER 3
If one of these messages appear on the Human Interface screen,
the link is noisy or there is another Human Interface of the same
type on the link.
Impr oper Human Interface Configuration
OR
Improper Human Interface Configuration
More than one Remote HI on lin
Used With:
Problem:
has lost communications with the CGM. See
"Fail Diagnostic" for additional information.
Check:
Interface and CGM. Verify crimping and polarity
of communications wiring. There should be no
loose connections or crimps on wire insulation.
Used With:
Possible Values:
Problem:
communications with the unit whose number
is specified (#3 in this example).
Check:
or crimps on wire insulation.
Used With:
Problem:
Local HI has been installed on the link.
Check:
Interface and CGM. Verify crimping of
communications wiring. There should be no
loose connections or crimps on wire insulation.
If a Remote HI was installed, verify that a
Local HI was not installed by mistake.
Used With:
Problem:
Remote HI has been installed on the link.
Check:
face and the IPCB and CGM. Verify crimpi ng of
communications wiring. There should be no
loose connections or crimps on wire insulation.
Verify that no other Remote HI’s have been
connected to the same communications link/unit.
The Unit Mounted (Local) Human interface
Wiring between Unit Mounted (Local) Human
All Uni ts with Remote Human Interface
Unit Number 1 through 4
The Remote Human Interface has lost
Field/unit wiring between Remote Human
Interface and the IPCB on the unit number
specified. Also, verify wiring between the IPCB
and CGM of the unit whose number is specified.
Verify crimping and polarity of communications
wiring. There should be no loose connections
Noisy Communications link or a second
Wiring between Unit Mounted (Local) Human
All Uni ts with Remote Human Interface
Noisy Communications link or a second
Field/Unit wiring between Remote Human Inter-
Diagnostics
There are four types of diagnostics:
1. (PMR) Partial System Disable, Manual Reset
2. (PAR) Partial System Disable, Auto Reset
3. (INFO) Information Only
4. (HO) History Only
The following Troubleshooting chart lists possible Failure
Modes and:
1. The Diagnostic Displayed
screen and if it is a PMR, PAR, INFO or HO diagnostic.
2. The condition which caused the failure mode to occur or
the Reason for Diagnostic
3. The UCM’s Reaction
47
on the Human Interface’s LCD
.
to the failure mode.
Page 48
System Testing & Troubleshooting
i
y
p
(INFO) A manual reset may be
made at the Human Interface, at
Tracer, or by cycling power to the
(INFO) An automatic reset occurs
after the CGM ICS Temperature
Sensor returns to its allowable
range. In order to prevent rapid
cycling of the diagnostic, there is a
10 second delay prior to the
CGM.
(PAR) An automatic reset occ urs
after the OA Temp input returns to
its allowable range. In order to
prevent rapid cy cling of the
Diagnostic, there is a 10 second
delay before the automatic reset.
(PAR) An automatic reset occ urs
after the designated Zone
Temperature signal returns to its
allowable range. In order to prevent
rapid cycling of the Diagnostic,
there is a 10 second delay before
the automatic reset.
An information only diagnostic will
be displayed at the Human
No change in unit operation
occurs. This diagnostic is for
information only.
The unit is reading a signal that is out of
range for the CGM ICS Temperature
sensor input on the CGM. (Temp < -40 F
or Temp > 200 F).
Interface.
An error occurred while the CGM was
writing data to its internal non-volatile
memory (EEPROM).
Unit actions that occur when this
diagnostic is active include;
a. Low Ambient Compressor
Lockout function is disabled
b. Low Ambient Pump Override
function is activated (ie: Solution
Pump ON request is issued).
c. LPC Bypass Time is set to
Minimum Bypass Time (time used
for OA Temp >65 degF).
d. If Leaving Solution Reset type
selected is OA Temp Reset, then
the Reset type reverts to NONE
for the duration of the failure.
The Reset type reverts to NONE
for the duration of the failure.
The unit is reading a signal that is out of
range for the Outside Air Temperature
sensor input on the CGM. (Temp < -40 F
or Temp > 200 F).
laced.
need to be re
The Leaving Solution Reset type
selected is Zone Temp Reset, and the
unit is reading a signal that is out of
range for this input (Temp < -40 F or
Temp > 200 F).
DIAGNOSTIC DISPLAYEDREASON FOR DIAGNOSTICUCM’S REACTIONRESET REQUIRED
CGM ICS Temperature Sensor Fail
Problem: CGM is receiv ing a signal
which is out of range from the CGM
ICS Temperature Sensor input.
CGM Module Data Storage Error
Problem: There was a data
transmission error.
Check: This can be caused by an
intermittent power loss . Turn the
unit off for 1-2 minutes, then back on
again. If diagnostic pers ists, then
CGM OA Temp Sensor Failure
the CG M ma
Problem: The Outside Air
Temperature sensor input is out of
range.
Check: Sensor resistance between
830 ohms (200 F) and 345.7Kohms
(-40 F). If so, check field/unit wiring
between Sens or and CGM.
48
CGM Zone Temp Sensor Failure
Problem: The CGM Zone
Temperature sensor input is out of
range.
Check: Sensor resistance between
830 ohms (200 F) and 345.7Kohms
(-40 F). If so, check field/unit wiring
between Sens or and CGM.
Page 49
y
p
p
p
(INFO) This diagnostic is reset when
y
p
p
p
a compres sor on Circ uit 1 is staged
on due to a cooling demand.
(INFO) This diagnostic is reset when
a compres sor on Circ uit 2 is staged
on due to a cooling demand.
System Testing & Troubleshooting
(PMR) A manual reset is required
after the diagnostic is set. It can be
reset by the HI or Trac er, or by
cycling power to the CGM.
PMR) A manual reset is required
after the diagnostic is set. It can be
reset by the HI or Trac er, or by
cycling power to the CGM.
No Change in unit operation
occurs. This diagnostic is for
information only.
Unit remained in pumpdown for 30
seconds without the occurrence of
an LPC event. Pumpdown sequence
was terminated by a 30 second
timer.
DIAGNOSTIC DISPLAYED REASON FOR DIAGNOSTICUCM’S REACTIONRESET REQUIRED
Circuit 1 Pumpdown Terminated
by Time
Problem: Unit went through
Pumpdown on Circuit 1 and LPC
never tripped. Pumpdown was
terminated after 30 s econds.
Check: Check circuit 1 pumpdown
No Change in unit operation
occurs. This diagnostic is for
information only.
Unit remained in pumpdown for 30
seconds without the occurrence of
an LPC event. Pumpdown sequence
was terminated by a 30 second
timer.
eration.
er o
ro
solenoid valve and low pressure
switch to verif
Crcuit 2 Pumpdown Terminated by
Time
(Circuit #2 40-60 Ton units only)
Problem: Unit went through
Pumpdown on Circuit 2 and LPC
never tripped. Pumpdown was
terminated after 30 s econds.
Check: Check circuit 2 pumpdown
A "Lockout Circuit #1" request is
issued to the Compressor Staging
Control function. The Compressor
Relays, LPC Bypass Relay,
Liquid Line Solenoid Relay, and
Hot Gas Bypass Relay for
Circuit 1 are all de-energized
A "Lockout Circuit #2" request is
issued to the Compressor Staging
Control function. The
Compressor Relays, LPC
Bypass Relay, and Liquid Line
Solenoid Relay for Circuit 2 are
all de-energized
The circuit #1 compressor proving
input on the SCM/MCM is detected
closed continuously for more than 3
seconds while neither compressor
output on Circuit #1 is clos ed.
eration.
er o
ro
solenoid valve and low pressure
switch to verif
Compressor Contactor Fail -
Circuit 1
Problem: The Compressor
Contactor for Circuit #1 has
malfunctioned.
The Circ uit #2 compressor proving
Compressor Contactor Fail -
input on the MCM is detected c losed
Circuit 2
continuous ly for more than 3
(Circuit #2 40-60 Ton units only)
seconds while neither compressor
output on Circuit #2 is clos ed.
Problem: The Compressor
Contactor for Circuit #2 has
malfunctioned.
49
Page 50
System Testing & Troubleshooting
g
(PMR) A manual reset is required
after this diagnostic occurs. The
Diagnostic can be reset by the unit
mounted Human Interface Module or
Tracer, or by cycling power to the
(PMR) A manual reset is required
anytime after the Diagnostic is set.
The Diagnostic c an be reset by the
Human Interface or Tracer, or by
cycling power to the CGM.
(PMR) A manual reset is required
anytime after the Diagnostic is set.
The Diagnostic c an be reset by the
Human Interface or Tracer, or by
cycling power to the CGM.
CGM.
(PMR) A manual reset is required
after this diagnostic occurs. The
Diagnostic can be reset by the unit
mounted Human Interface Module or
Tracer, or by cycling power to the
CGM.
(PAR) An automatic reset occurs
after the #1 Condenser Temperature
input returns to its allowable range
within 10 seconds .
A “Lockout Circuit #1” request is
While the Circuit 1 LPC Bypass
issued to the Compressor Staging
Control function. The Compressor
Relay was energized, the 7 PSIG
LPC switch: a) was open at the time
ized.
A “Lockout Circuit #2” request is
issued to the Compressor Staging
Control function. The
Compressor Relays, LPC
Bypass Relay, Liquid Line
Solenoid Relay for Circuit 2 are all
Relays, LPC Bypass Relay,
Liquid Line Solenoid Relay, and
Hot Gas Bypass Relay for
Circuit 1 are all de-energized.
A “Lockout Circuit #2” request is
issued to the Compressor Staging
Control function. The
Compressor Relays, LPC
Bypass Relay, and Liquid Line
Solenoid Relay for Circuit 2 are all
de-energized.
A “Lockout Circuit #1” request is
issued to the Compressor Staging
Control function. The
Compressor Relays, LPC
Bypass Relay, Liquid Line
Solenoid Relay, and Hot Gas
Bypass Relay for Circuit 1 are all
de-ener
The Circ uit #2 Compressor proving
input is detected open continuously
for more than 3 seconds when either
a compres sor was requested to
start, or b) the switch opened 4 times
after a compress or on Circuit 1 was
started but prior to ac cumulating 3
continuous minutes of run time.
While the Circuit 2 LPC Bypass
Relay was energized, the 7 PSIG
LPC switch: a) was open at the time
a compres sor was requested to
start, or b) the switch opened 4 times
after a compress or on Circuit 2 was
started but prior to ac cumulating 3
continuous minutes of run time.
The Circ uit #1 Compressor proving
input is detected open continuously
for more than 3 seconds when either
or both compress or outputs on
Circuit #1 are energiz ed (as
described in the Compressor
Protection function).
or both compress or outputs on
de-energized
A “Lockout Circuit # 1” request is
issued to the Compressor Staging
Control function. The
Compressor Relays, LPC
Bypass Relay, Liquid Line
Solenoid Relay, and Hot Gas
Bypass Relay for Circuit 1 are all
de-energized.
Circuit #2 are energiz ed (as
described in the Compressor
Protection function).
The unit is reading a signal that is out
of range for the circ uit #1 Saturated
Condenser Temperature sensor.
(Temp < -40 F or Temp > 200 F).
DIAGNOSTIC DISPLAYEDREASON FOR DIAGNOSTICUCM’S REACTIONRESET REQUIRED
Compressor Protection - LPC Open -
Circuit 1
Problem: State of refrigerant charge
for circuit #1 is low.
Compressor Protection - LPC Open -
Circuit 2 (Circuit #2 40-60 Ton units
only)
Problem: State of refrigerant charge
Compressor Trip - Circuit 2
(Ckt #2 40-60 Ton units only)
Problem: The Compress or Circuit #2
for circuit #2 is low.
Compressor Trip - Circuit 1
Problem: The Compress or Circuit #1
has tripped.
50
has tripped.
Cond Temp Sensor Failure - Circuit 1
Problem: The Saturated Condenser
Temperature Input is out of range for
Circuit #1.
Check: Sensor resistance between
830 ohms (200 F) and 345.7Kohms
(-40 F). If so, check field/unit wiring
between Sens or and MCM/SCM.
Page 51
System Testing & Troubleshooting
(PAR) An automatic reset occurs after
the #2 Condenser Temp input returns
to its allowable range within 10
seconds.
(PAR) An automatic reset occurs after
communication has been restored.
(PMR) A manual reset is required after
the Emergency Stop input recloses.
The Diagnostic can be reset by the
Human Interface or Tracer or by
cycling power to the CGM.
(INFO) An automatic reset occurs after
the EST and LST have both risen to
greater than 3oF above the heat tape
temperature setpoint.
A “Lockout Circuit #2” request is
The unit is reading a signal that is out
issued to the Compressor Staging
of range for the circuit #2 Saturated
Control function. The Compressor
Relays, LPC Bypass Relay, and
Liquid Line Solenoid Relay for
Circuit 2 are all de-energized.
Condenser Temperature sensor.
(Temp < -40 F or Temp > 200 F).
No Change in unit operation
The CGM has lost communications
occurs. The Current Sensing
Module is used for monitoring
purposes only, and does not affect
unit operation. This diagnostic is
for information only.
with the CSM.
“OFF or “Close” requests are
issued as appropriate to the
An open circuit has occurred on the
Emergency Stop input caused either
following functions;
by a High Duct Temp T-stat trip, or the
a. Compressor Staging control. (All
Compressor Relays, Liquid Line
Solenoid Relays, LPC Bypass
Relay, and HGBP Relay are
deenergized).
b. Evaporator Solution Pump
Control. (S
No change in the unit operation.
This diagnostic is for information
only.
opening of field-provided contacts,
switch, etc...
An abnormal temperature reading of
the chilled solution exists.
DIAGNOSTIC DISPLAYEDREASON FOR DIAGNOSTICUCM’S REACTIONRESET REQUIRED
Cond Temp Sensor Failure - Circuit 2
(Circuit #2 40-60 Ton units only)
Problem: The Saturated Condenser
Temperature Input is out of range for
Circuit #2.
Check: Sensor resistance between
830 ohms (200 F) and 345.7Kohms
(-40 F). If so,
Current Sensing Module Comm Fail
Problem: The CGM has lost
communications with the Current
Sensing Module (CSM)..
Check: Check field/unit wiring between
CGM and CSM.
Emergency Stop
Problem: The Emergency Stop input
on the CGM is open.
51
EST/LST Low Temperature Indication
Problem: Either the entering solution
temperature or the leaving solution
temperature has fallen below the heat
tape temperature setpoint.
Page 52
(PMR) A manual reset is
System Testing & Troubleshooting
(PMR) A manual reset is
required after this diagnostic
occurs. The Diagnostic can
be reset by the unit mounted
Human Interface Module or
Tracer, or by cycling power
required after this diagnostic
occurs. The Diagnostic can
be reset by the unit mounted
Human Interface Module or
Tracer, or by cycling power
to the CGM.
to the CGM.
When this diagnostic is active:
a. A "Lockout Ckts" request is sent
to the compressor staging function.
All Compressor Relays, LPC
Bypass relays, and Liquid Line
Solenoids will be de-energized.
Min On times, H GBP, and
Pumpdown will be bypassed.
b. The following functions will be
disabled:
1) Compressor Staging,
2) Process/Comfort Cooling,
3) Ice Building.
c. Evaporator Solution Pump
Control is not affected.
d. The Heat Tape relay output will
When this diagnostic is active:
a. A "Lockout Ckts" request is sent
to the compressor staging function.
All Compressor Relays, LPC
Bypass relays, and Liquid Line
Solenoids will be de-energized.
Min On times, H GBP, and
Pumpdown will be bypassed.
b. If Leaving Solution Reset type
selected is Entering Soluti on Reset,
then th e Reset type reverts to
NONE for the duration of the failure.
c. Evaporator Solution Pump
Control is not affected.
d. The Heat Tape relay output will
energize.
The unit is reading a signal that is out
of range for this input on the CGM
The unit is reading a signal that is out
of range for this input on the CGM.
(Temp < -40 F or Temp > 200 F).
(Temp < -40 F or Temp > 200 F).
energize.
DIAGNOSTIC DISPLAYEDREASON FOR DIAGNOSTICUCM’S REACTIONRESET REQUIRED
Evaporator Entering Solution
Temperature Sensor Fail
Problem: The Evaporator Entering
Solution Temperature Sensor input is
out of range.
Check: Sensor resistance between
830 ohms (200 F) and 345.7Kohms
(-40 F). If so, check field/unit wiring
between Sensor and CGM.
Evaporator Leaving Solution
Temperature Sensor Fail
Problem: The Evaporator Leaving
Solution Temperature sensor input is
out of range.
Check: Sensor resistance between
830 ohms (200 F) and 345.7Kohms
(-40 F). If so, check field/unit wiring
between Sensor and CGM.
52
Page 53
System Testing & Troubleshooting
For Service Parts Replacement,
please note:
(a) For proper operation of units with
Brazed Plate heat exchangers,
please insure the following board is
installed:
Multiple Compressor Module (MCM)
- Software Version number greater
(PMR) A manual reset is required
after this diagnostic occurs. The
Diagnostic can be reset by the unit
mounted Human Interface Module
or Tracer, or by cycling power to the
CGM.
than or equal to 10.00orSingle Compressor Module
(SCM) - Software Version number
greater than or equal to 10.00
(b) To eliminate this diagnostic
when it is due to an incompatible
Software Version number(s), please
install the appropriate board(s) per
the fol lowing:
Cold Generator Module (CGM) -
Software Version number greater
than or equal to 3.00
CG Unit Human Interface (HI) -
Software Version number greater
than or equal to 27.00
A "Lockout all Circuit" request
is issued to the comp ressor
staging function. Compressor
Relays, LPC Bypass Relays,
Liquid Line Solenoid Relays
and HGBP relay are all de-
energized.
Units with a Brazed Plate heat
exchanger require a flow proving switch
for freeze protection functionality. This
flow proving switch input was detected
close d (shorted) at the time th e sol ution
pump was commanded ON (Only on
units with "Chiller Solution Pump Mode"
set to AU TO).
Also, units with Brazed Plate heat
exchanger require newer versions of
control boards for proper operation.
During power-up, the unit detected at
least one replacement module with a
Software Verison number less than what
is required.
DIAGNOSTIC DISPLAYEDREASON FOR DIAGNOSTICUCM’S REACTIONRESET REQUIRED
Evaporator Solution Flow Loss
The switch connected to the flow
proving switch input on a unit with a
Brazed Plate heat exchanger has
faile d CLOSED;
or
during power-up, a unit with a
Brazed Plate heat exchanger has
detected that older versions of
control modules are installed.
53
Page 54
System Testing & Troubleshooting
(PAR) An automatic reset
occurs after the Evap
Solution Flow Proving
Switch has detected
Solution flow for 6
continuous seconds.
(PAR) An automatic reset occurs
after the External Leaving Solution
Setpoint returns to its allowable
range. In order to prevent rapid
cycling of the Diagnostic, there is a
10 second delay before the
automatic reset.
When the Solution Flow Switch
input is detected OPEN
(no flow) for 6 continuous
seconds, the Unit will de-
energize
the following relays:
Compressor Relays, LPC
Bypass Relays, Liquid Line
Solenoids, and HGBP Relay.
While the diagnostic is active,
the Leaving Solution Setpoint
will revert to using the default
(HI) Leaving Solution Setpoint.
The diagnostic can occur at any time
after the Evaporator Solution Pump
Relay has been requested ON, and the
Solution Flow Switch input is detected
OPEN (no flow) for 5 continuous
minutes.
The External Leaving Solution Setpoint
(LSS) is designated as the Leaving
Solution Setpoint source and it is out of
range. Out of range is defined as one of
the following:
a) External LSS > 65 deg F or < 51 deg
F for unit with LSS Range 51-65 deg F.
b) External LSS > 50 deg F or < 40 deg
F for unit with LSS Range 40-50 deg F.
c) External LSS > 39 deg F or < 30 deg
F for unit with LSS Range 30-39 deg F.
d) External LSS > 29 deg F or < 20 deg
F for unit with LSS Range 20-29 deg F.
e) External LSS > 75 deg F or < 10 deg
F for unit with LSS Range SPECIAL.
DIAGNOSTIC DISPLAYEDREASON FOR DIAGNOSTICUCM’S REACTIONRESET REQUIRED
Evap Solution Flow Proving Switch
Problem: Solution Flow Switch is
open after the Solution Pump is ON.
Check: Verify Solution Pump
operation and that the Evaporator
Solution Flow Switch is working
properly.
External Leaving Solution STP Input
Fail
Problem: CGM is receiving an
External Leaving Solution Setpoint
(LSS) Input signal which is out of
range. Check field/unit wiring
between CGM and External
Leaving Solution Setpoint
potentiometer.
54
Page 55
g
(PAR) An automatic reset occurs
g
after communication has been
restored.
System Testing & Troubleshooting
(PAR) An automatic reset occurs
after communication has been
restored.
The UCM will initiate the following
The CGM has lost communications
actions ;
with the GBAS Module.
ized.
a. If the Demand Limit input was
closed prior to communications
loss, then the Demand Limit
commands issued to the
Compressor Staging function
will be cancelled.
b. If any of the GBAS setpoint
control parameters are the
HI-selected setpoint sources,
then those setpoints will revert
to the default HI setpoints .
c. Any active GBAS output
control parameters will be
ignored.
d. A failsafe function in the GBAS
module will cause all GBAS
outputs to be zeroed and
de-ener
The UCM will initiate the following
actions ;
a. If the Demand Limit input was
closed prior to communications
loss, then the Demand Limit
commands issued to the
Compressor Staging function
will be cancelled.
b. If any of the GBAS setpoint
control parameters are the
HI-selected setpoint sources,
then those setpoints will revert
to the default HI setpoints .
c. Any active GBAS output
control parameters will be
ignored.
d. A failsafe function in the GBAS
The CGM has lost communications
with the GBAS Module.
module will cause all GBAS
ized.
outputs to be zeroed and
de-ener
DIAGNOSTIC DISPLAYEDREASON FOR DIAGNOSTICUCM’S REACTIONRESET REQUIRED
GBAS 0-5VDC Module Comm
Failure
Problem: The CGM has lost
communications with the GBAS
Module.
Check: Check field/unit wiring
between CGM and GBAS.
GBAS 0-5VDC Module Comm
Failure
Problem: The CGM has lost
communications with the GBAS
Module.
Check: Check field/unit wiring
between CGM and GBAS.
55
Page 56
System Testing & Troubleshooting
expired.
expired.
(PAR ) An automatic reset occurs after
the Leaving Solution Temperature
decreas es 5 deg F or more below the
Hot Start Load Limit Setpoint.
(INFO ) An automatic reset occurs after
the Leaving Solution Temperature
decreas es 5 deg F or more below the
Hot Start Load Limit Setpoint.
(PMR) A manual reset is required after
this diagnostic oc curs. The Diagnostic
can be reset by the unit mounted
Human Interface Module or Tracer, or
by cycling power to the CGM.
(PAR ) An automatic reset occurs after
the designated Hot Start Load Limit
Setpoint source sends a signal that is
within range for 10 continuous seconds,
or after a different setpoint source is
user-defined.
While this diagnostic is active, the
second compressor on each
refrigerant circuit is shut off
and/or prevented from s taging
ON.
No change in unit operation
occurs. This diagnostic is for
information only.
Hot Operation Response is set to "50%
CAPACITY PER CKT, AUTO RESET
DIAG ". The Leaving Solution Temp
exceeded the Hot Start Load Limit
Setpoint after the Hot Start Time Interval
Hot Operation Response is set to
"ALLO W N ORMAL OPERATIO N, INFO
RESET DIAG". The Leaving Solution
Temp exceeded the Hot Start Load Limit
A "lockout all Ckts" request is
issued to the compressor staging
function. The Unit will deenergize
the following relays: Compressor
Relays, LPC Bypass Relays,
Liquid Line Solenoids, and HGBP
Relay . Comfort/Process C ooling,
and Ice Building are terminated
and prevented from oc curring
until the diagnostic condition is
cleared.
The default (HI) Hot Start Load
Limit Setpoint will become the
active setpoint while this
diagnostic is active.
Setpoint after the Hot Start Time Interval
Hot Operation Response is set to
"SHUT OFF COMPRESSORS,
MANUAL RESET DIAG ". The Leaving
Solution Temp exc eeded the Hot Start
Load Limit Setpoint after the Hot Start
Time Interval expired.
The unit is reading a signal that is out of
range for the Hot Start Load Limit
Setpoint.
DIAGNOSTIC DISPLAYEDREASON FOR DIAGNOSTICUCM’S REACTIONRESET REQUIRED
Hot Start Load Limit (Auto)
Problem: The Leaving Solution
Temperature is too hot.
Hot Start Load Limit (Info)
Problem: The Leaving Solution
Temperature is too hot.
Hot Start Load Limit (Man)
Problem: The Leaving Solution
Temperature is too hot.
Hot Start Load Limit Setpoint Fail
Problem: The Hot Start Load Limit
Setpoint is out of range.
Check: If Hot Start Load Limit
Setpoint Source is ass igned to
either GBAS module, but this
setpoint has not been assigned to
one of that GBAS module’s
analog inputs, this diagnostic c an
occur.
56
Page 57
System Testing & Troubleshooting
g
(INFO) An automatic reset occurs after
the Circ uit 1 Saturated Liquid Pressure
Sensor input returns to its allowable
range. In order to prevent rapid cy cling
of the Diagnostic, there is a 10 second
(PAR) An automatic reset occurs after
the designated Leaving Solution
Setpoint returns to its allowable range.
In order to prevent rapid c ycling of the
Diagnostic, there is a 10 s econd delay
(PAR) An automatic reset occurs after
the designated Ice Build Terminate
Setpoint source sends a signal that is
within range for 10 continuous seconds,
or after a different setpoint source is
(PAR) An automatic reset occurs after
the difference between the active Ice
Build Terminate Setpoint and the
Leaving Solution Cutout Temp Setpoint
meets the minimum difference
requirement.
user-defined.
before the automatic reset.
delay before the automatic reset.
The Superheat/Subcool
calculation is invalid and the
vaiues are set to zero. No
other change in unit operation
occurs. This diagnos tic is for
(Pres sure < 0 PSIG or Pressure > 400
information only.
PSIG).
While the diagnostic is active,
the Leaving Solution Setpoint
will revert to using the default
The default (HI) Ice Build
Terminate Setpoint will become
the active setpoint while this
The active Ice Build Terminate
Setpoint is set to the Leaving
Solution Cutout Temp Setpoint
plus the larger of 1) calculated
Minimum Differential v alue, or
2) 6.5 deg F.
The active Ice Build Terminate Setpoint
and the Leaving Solution Cutout Temp
Setpoint are too close together for proper
unit operation.
The unit is reading a signal that is out of
diagnostic is active.
range for the Ice Build Terminate
Setpoint.
The designated Leaving Solution Setpoint
(HI) Leaving Solution Setpoint.
e SPECIAL.
The unit is reading a signal that is out of
range for the Circuit 1 Saturated Liquid
source is out of range. Out of range is
defined as one of the following:
a) LSS > 65 deg F or < 51 deg F for unit
with LSS Range 51-65 deg F.
b) LSS > 50 deg F or < 40 deg F for unit
with LSS Range 40-50 deg F.
c) LSS > 39 deg F or < 30 deg F for unit
with LSS Range 30-39 deg F.
d) LSS > 29 deg F or < 20 deg F for unit
with LSS Range 20-29 deg F.
e) LSS > 75 deg F or < 10 deg F for unit
with LSS Ran
Line Pressure Sensor input on the SSM.
DIAGNOSTIC DISPLAYEDREASON FOR DIAGNOSTICUCM’S REACTIONRESET REQUIRED
IBTS Adjusted to Maintain Min Diff
Problem: The active Ice Build
Terminate Setpoint (IBTS) is
closer to the Leaving Solution
Ice Build Terminate Setpoint Fail
Problem: The Ic e Build Terminate
Cutout Temp Setpoint than the
calculated Minimum Differential.
Setpoint is out of range.
Liquid Pressure Sensor Fail
Circuit 1
Problem: Circuit 1 Saturated Liquid
Line Pressure sensor input is out
of range.
Check: Check field/unit wiring
Leaving Solution Setpoint Fail
Problem: The designated Leaving
Solution Setpoint is out of range.
If either GBAS module is
designated as the Leaving Solution
Setpoint source, verify that GBAS
module has this input assigned to
Check: If Ice Build Terminate
Setpoint Source is ass igned to
either GBAS module, but this
setpoint has not been assigned to
one of that GBAS module’s analog
inputs, this diagnostic can occur.
57
one of it’s analog inputs.
between Sens or and SSM.
Page 58
g
(INFO) An automatic reset occurs
g
g
g
after the Circuit 2 Saturated Liquid
System Testing & Troubleshooting
Pressure Sensor input returns to its
allowable range. In order to prevent
rapid cycling of the Diagnostic, there
is a 10 second delay before the
automatic reset.
(PAR) An automatic reset occurs
after the Outsid e Air Tem p
increases 5 deg F or more above
the Low Ambient Evaporator Pump
Override Temp Setpoint.
(PAR) An automatic reset occurs
after the Evaporator Solution
Temperature(s) rises 4 deg F or
more above the Low Solution Cutout
Temperature Setpoint.
(PMR) A manual reset is required
after this diagnostic occurs. The
Diagnostic can be reset by the unit
mounted Human Interface Module
or Tracer, or by cycling power to the
CGM.
(PMR) A manual reset is required
anytime after the Diagnostic is s et.
The Diagnostic can be reset by the
Human Interface or Tracer, or by
cycling power to the CGM.
nos tic is fo r inform ation
The Superheat/Subcool
calculation is invalid and the
vaiues are set to zero. No other
The unit is reading a signal that is out
of range for the Circuit 2 Saturated
Liquid Line Pressure Sensor input on
only.
change in unit operation occurs.
This di a
the SSM. (Pressure < 0 PSIG or
Pressure > 400 PSIG).
The Evaporator Solution Pump
The Outside Air (Am bient)
Relay is energized while this
condition exists.
temperature is below the Low
Ambient Evap Pump Override Temp
A "Lockout all Circuits" request is
issued to the Compressor
Staging Function. Compressors
are prevented from staging on
and the Unit will de-energize the
following relays: Compressor
Relays, LPC Bypas s Relays,
Liquid Line Solenoids, and
HGBP Relay.
A “Lockout Circuit # 1” request is
issued to the Compressor
Staging Control function. The
Compressor Relays, LPC
Bypass Relay, Liquid Line
Solenoid Relay, and Hot Gas
Bypass Relay for Circuit 1 are all
the time the LPC Bypas s Relay de-
energized. On a standard unit this is
de-energized.
the 45 PSIG LPC switch, but can be
20 PSIG or lower on units w ith a lower
Leaving Solution Setpoint range.
While this diagnostic is active,
Compressors are prevented
from staging on. The Unit will
deenergize the following:
Compressor Relays, LPC
Bypass Relays, Liquid Line
Solenoids, and HGBP Relay.
, the
Setpoint.
While no compressors were running,
the Evaporator Solution
Temperature(s) went below the Low
Solution Cutout Te m p Setp oi nt.
Evaporator Solution Temperature(s)
went below the Low Solution Cutout
While compressors were runnin
Temperature Setpoint.
With one or more compressors
running, the higher pressure of the
two LPC switches on Circuit 1 has
opened 6 times with the LPC Bypass
relay de-energized, or it was open at
DIAGNOSTIC DISPLAYEDREASON FOR DIAGNOSTICUCM’S REACTIONRESET REQUIRED
Liquid Pressure Sensor Fail Circuit 2
(Circuit #2 40-60 Ton units only)
Problem: Circuit 2 Saturated Liquid
Line Pressure sensor input is out of
range.
Check: Check field/unit wiring
Low Ambient Evaporator Solution
Pump Override
between Sensor and SSM.
Solution Temperature is too
Problem: Outside Air Temp too low,
reques t So lution Pump to run to
keep Solution moving.
Low Solution Cutout Temperature
(Auto)
Problem: The Evaporator Leaving or
Enterin
low.
Low Solution Cutout Temperature
(Man)
Solution Temperature is too
Low Pressure Control Open -
Circuit 1
Problem: The refrigerant in Circuit 1
is cold and may cause the Solution
in the Chiller barrel to become too
cold. Also, there may be a state of
Problem: The Evaporator Leaving or
Enterin
low.
charge issue with Circuit 1.
58
Page 59
(PMR) A manual reset is required
g
g
System Testing & Troubleshooting
nostic is set.
The Diagnostic can be reset by
the Human Interface or Tracer, or
anytime after the Dia
by cycling power to the CGM.
(PAR) An automatic reset occurs
after the difference between the
active Leaving Solution Setpoint
and the Leaving Solution Cutout
Temperature Setpoint meets the
minimum difference requirement.
(PAR) An automatic reset occurs
after communication has been
restored.
(INFO) An automatic reset occurs
after the Circuit 1 Saturated Liquid
Temperature Sensor input returns
to its allowable range. In order to
prevent rapid cycling of the
Diagnostic, there is a 10 second
delay before the automatic reset.
The active Leaving Solution
Setpoint is set to the Leaving
Solution Cutout Temperature
Setpoint plus the calculated
A “Lockout Circuit # 2” request is
iss ued to the Compress or Staging
Control function. The Compressor
Relays, LPC Bypass Relay, Liquid
Line Solenoid Relay, and Hot Gas
Bypass Relay for Circuit 2 are all
de-energized.
The active Leaving Solution Setpoint
With one or more compressors
running, the higher pressure of the
two LPC switches on Circuit 2 has
opened 6 times with the LPC Bypas s
relay de-energized, or it was open at
the time the LPC Bypass Relay de-
energized. On a standard unit this is
the 45 PSIG LPC s witch, but c an be
20 PSIG or lower on units with a lower
and the Leaving Solution Cutout
Leaving Solution Setpoint range.
Minimum Differential value.
Temperature Setpoint are too close
together for proper unit operation.
Solution
A “Lockout” request is sent to the
Compressor Staging Control
function. The Liquid Line Solenoid
Relays and LPC Byp-energized.
The CGM has lost communications
with the MCM.
The Superheat/Subcool calculation
The Superheat/Subcool Module is
is inv alid and the values are set to
zero. No other c hange in unit
installed and the unit is reading a
signal that is out of range for the
operation occurs. This diagnostic
Circuit 1 Saturated Liquid Line
is for information only.
Temperature Sensor input on the
SCM/MCM. (Temp < -55 F or Temp >
209 F).
DIAGNOSTIC DISPLAYEDREASON FOR DIAGNOSTICUCM’S REACTIONRESET REQUIRED
Low Pressure Control Open -
Circ uit 2 (Circuit #2 40-60 Ton units
only)
Problem: The refrigerant in Circuit 2
is cold and may cause the Solution in
the Chiller barrel to bec ome too cold.
Also, there may be a state of charge
iss ue with Circuit 2.
LSS Adjusted to Maintain Minimum
Differential
Problem: The ac tive Leavin
Setpoint (LSS) is closer to the
Leaving Solution Cutout Temp
Setpoint than the calculated
Minimum Differential.
MCM Communications Failure
(40-60 Ton units only)
Problem: The CGM has lost
communications with the MCM.
Check: Check field/unit wiring
between CGM and MCM.
Sat Liquid Temperature Sensor Fail
Circuit 1
Problem: Circuit 1 Saturated Liquid
Line Temperature sensor input is out
of range.
Check: Sensor resistance between
830 ohms (200 F) and 345.7Kohms
(-40 F). If not, check field/unit wiring
between Sens or and SCM/MCM.
59
Page 60
System Testing & Troubleshooting
g
(PAR) An automatic reset occurs
after communication has been
(INFO) An automatic reset occurs
after the Circuit 2 Saturated Liquid
Temperature Sensor input returns to
its allowable range. In order to
prevent rapid cycling of the
Diagnostic, there is a 10 sec ond
delay before the automatic res et.
restored.
(INFO) An automatic reset occurs
after the Circuit 1 Suction Line Temp
Sensor input returns to its allowable
range. In order to prevent rapid
cycling of the Diagnostic, there is a
10 second delay before the
automatic reset.
(INFO) An automatic reset occurs
after the Circuit 2 Suction Line
Temperature Sensor input returns to
its allowable range. In order to
prevent rapid cycling of the
Diagnostic, there is a 10 sec ond
delay before the automatic res et.
ized.
The Superheat/Subcool
calc ulation is invalid and the
values are set to zero. No other
change in unit operation occurs.
This diagnostic is for information
The Superheat/Subcool
calc ulation is invalid and the
values are set to zero. No other
change in unit operation occurs.
This diagnostic is for information
only.
The Superheat/Subcool Module is
installed and the unit is reading a
signal that is out of range for the
Circuit 2 Saturated Liquid Line
Temperature Sensor input on the
MCM. (Temp < -40 F or Temp > 200
F).
A “Lockout” request is s ent to the
Compressor Staging Control
function. The Liquid Line
The CGM has los t communications
with the SCM.
Solenoid Relays and LPC
Bypass Relays are de-
energized. A failsafe function in
the SCM will cause all SCM
outputs to be z eroed and de-
ener
The Superheat/Subcool Module is
installed and the unit is reading a
signal that is out of range for the
only.
Circuit 1 Suction Line Temp Sensor
input on the SCM/MCM. (Temp < -
40 F or Temp > 200 F).
The Superheat/Subcool
calc ulation is invalid and the
values are set to zero. No other
change in unit operation occurs.
This diagnostic is for information
only.
The Superheat/Subcool Module is
installed and the unit is reading a
signal that is out of range for the
Circuit 2 Suction Line Temperature
Sensor input on the MCM. (Temp < -
40 F or Temp > 200 F).
DIAGNOSTIC DISPLAYED REASON FOR DIAGNOSTICUCM’S REACTIONRESET REQUIRED
Saturated Liquid Temperature
Sensor Fail - Circuit 2
(Circuit #2 40-60 Ton units only)
Problem: Circ uit 2 Saturated Liquid
Line Temperature sensor input is out
of range.
Check: Sens or resistance between
830 ohms (200 F) and 345.7Kohms
(-40 F). If not, check field/unit wiring
between Sensor and MCM.
Suction Temp Sensor Fail - Circuit 1
Problem: Circ uit 1 Suction Line Temp
sensor input is out of range.
Check: Sens or resistance between
830 ohms (200 F) and 345.7Kohms
(-40 F). If not, check field/unit wiring
between Sensor and SCM/MCM.
Suction Temp Sensor Fail - Circuit 2
(Ckt #2 40-60 Ton units only)
Problem: Circ uit 2 Suction Line Temp
sensor input is out of range.
Check: Sens or resistance between
830 ohms (200 F) and 345.7Kohms
(-40 F). If not, check field/unit wiring
SCM Communications Failure
(20-30 Ton units only)
Problem: The CGM has lost
communications with the SCM.
Check: Check field/unit wiring
between CGM and SCM.
between Sensor and MCM.
60
Page 61
(INFO) An automatic reset occurs
after the Circuit 1 Suction Line
System Testing & Troubleshooting
Temperature Sensor input returns to
its allowable range. In order to
prevent rapid cycling of the
Diagnostic, there is a 10 s econd
delay before the automatic reset.
(INFO) An automatic reset occurs
after the Circuit 2 Suction Line
Temperature Sensor input returns to
its allowable range. In order to
prevent rapid cycling of the
Diagnostic, there is a 10 s econd
delay before the automatic reset.
(PAR) An automatic reset occurs
after communication has been
restored.
The Superheat/Subcool
calculation is invalid and the
values are set to zero. No other
change in unit operation occurs.
This diagnostic is for information
only.
The Superheat/Subcool Module is
installed and the unit is reading a
signal that is out of range for the
Circuit 1 Suction Line Temperature
Sensor input on the SCM/MCM.
(Temp < -40 F or Temp > 200 F).
DIAGNOSTIC DISPLAYEDREASON FOR DIAGNOSTICUCM’S REACTIONRESET REQUIRED
Suction Temperature Sens or Fail -
Circuit 1
Problem: Circuit 1 Suction Line
Temperature sensor input is out of
range.
Check: Sensor resistance between
830 ohms (200 F) and 345.7Kohms
(-40 F). If not, check field/unit wiring
The Superheat/Subcool
calculation is invalid and the
values are set to zero. No other
change in unit operation occurs.
This diagnostic is for information
only.
The Superheat/Subcool Module is
installed and the unit is reading a
signal that is out of range for the
Circuit 2 Suction Line Temperature
Sensor input on the MCM. (Temp < -
40 F or Temp > 200 F).
between Sens or and SCM/MCM.
Suction Temperature Sens or Fail -
Circuit 2
(Ckt #2 40-60 Ton units only)
Problem: Circuit 2 Suction Line
Temperature sensor input is out of
range.
Check: Sensor resistance between
830 ohms (200 F) and 345.7Kohms
(-40 F). If not, check field/unit wiring
No Change in unit operation
occurs. The Superheat/Subcool
Module is used for monitoring
purposes only, and does not
affect unit operation. This
diagnostic is for information
only.
The CGM has lost communications
with the SSM.
between Sens or and MCM.
Superheat/Subcool Module Comm
Fail
Problem: The CGM has lost
communications with the
Superheat/Subcool Module (SSM).
Check: Check field/unit wiring
between CGM and SSM Module.
61
Page 62
System Testing & Troubleshooting
g
)
y
y
occurs after communic ation
with the TCI or LCI Module.setpoints provided by the network
the network has been designated
after comunications with the
communications with the
other
ed as an
setpoints provided by the
or ignored. Where the network
a. disallow any interaction after communication has been
communications with the
ineffective, and and H I interaction with the
mounted HI d isplay: LOCAL HI
COMMUNICATIONS
LOSS CHECK COMM LINK
WIRING BETWEEN
option, then on the remote
MODULES
(If the unit has a remote HI
HI module, this diagnostic
displa
will be reported and
automatic reset diagnostic).
DIAGNOSTIC DISPLAYED REASON FOR DIAGNOSTIC UCM’ S REACTION RESET REQUIRED
BAS Modul e Communications FailureCGM has lost communicationsAll active commands and(PAR) An automatic reset
Problem: The RTM has lostthrough the TCI or LCI will behas been restored.
communications with the TCI or LCI.cancelled and/ or ignored. Where
Check: Check field/ unit wiringas setpoint source, local HI default
between RTM and TCI or LCI Module.setpoints will be used.
BAS/NETWORK Comm Fai lureThe TCI or LC I has l ost Al l acti ve commands and(PAR) An automatic reset occurs
Probl em: The TCI o r LCI has lostnetwork for > 15 minu tes.netwo rk throug h the TCI or network and TCI or LCI
communications with Tracer.LCI will be cancelled and/has been restored.
control panel
Check: Network (Tracer or 3rd party has been designated as setpoint
building control panel) is powered up source, local HI default
and running properly. If so, check unit setpoints will be used.
wiring between TCI or LCI and network
(Tracer or 3rd party buildin
Unit HI Communications Failure The CGM has lost A failsafe function in the HI will; (INFO) An automatic reset occurs
62
communications with the U nit Interface. CGM (o r any other and the HI. When the fail ure
mounted (local) Human Interface modules), screen is cleared, the
(HI). b. render all HI keystrokesGeneral display is restored
Check: Field/unit wiring between c. cause the following to be CGM is again permitted.
Problem: The CGM has lost unit-mounted Human between the HI and the
CGM and Local HI. displayed on the unit-
Page 63
be assigned:
capacity
• Evap Leaving Solution Temp• Ice Building• Hot Gas Bypass Relay