Trane CGAF-C20, CGAF-C50, CGAF-C40, CGAF-C25, CGAF-C30 Programming, Troubleshooting Manual

...
Page 1
Programming CG-SVP01B-EN Troubleshooting Guide
Product Section Refrigeration
Product Hermetic Scroll Liquid Chillers, Air Cooled
Model CG
Literature Type Programming, Trouble Shooting Guide
Sequence 01B
Date January 2005
File No. SV-RF-CG-SVP01B-EN 1/05
Supersedes CG-SVP01A-EN 4/03
IntelliPak
TM
Air-Cooled Cold Generator
Models
"H" and Later Design Sequence CGAF-C20 CGAF-C40 CGAF-C25 CGAF-C50 CGAF-C30 CGAF-C60
With 3-DTM Scroll Compressors
Ó
ÿ
2005 American Standard Inc. All rights reserved
http://www.trane.com
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. Only qualified technicians should perform the installation and servicing of equipment referred to in this publication.
Page 2
About The Manual
Literature Change History
CG-SVP01B-EN (January 2005)
Original issue of this manual; provides specific program­ming, diagnostic, and troubleshooting information CGAF units with “K” and later design sequence.
Overview of Manual
Note: One copy of this document ships inside the control panel of each unit and is customer property. It must be retained by the unit’s maintenance personnel.
These units are equipped with electronic control modules which provides operating functions that are significantly dif­ferent than conventional units.
The manual is divided into 6 sections. Each section pro­vides the operator with specific information about the sys­tem operating parameters and their related screens. By carefully following the screen layout within this manual while scrolling through the Human Interface, the operator can monitor operating status, set specific operating param­eters, and diagnose system problems.
Before attempting to operate or service this equipment, re­fer to the “Start-Up” and “Test Mode” procedures in the ap­plicable Installation, Operation and Maintenance manual, listed on the unit nameplate.
Note: The procedures discussed in this manual should only be performed by qualified, experienced HVAC technicians.
Refer to the Table of Contents and Index for specific topics contained in this manual and supporting manuals.
2
Page 3
About The Manual
Literature Change History ....................................................... 2
Overview of Manual ................................................................. 2
General Information
Model Number Description ...................................................... 4
Unit Nameplate ........................................................................ 4
Hazard Identification ................................................................ 4
Commonly Used Acronyms ..................................................... 4
Glossary of Terms .................................................................... 5
UCM Control System ............................................................... 6
UCM Module ............................................................................ 6
Compressor Module ................................................................ 6
Interprocessor Communications Bridge Module ..................... 6
Trane Communications Interface Module ............................... 6
Generic BAS Module ............................................................... 6
Power Disconnecting Switches ............................................... 6
Manual Disconnect Switch ...................................................... 6
115V Control Circuit Switch (1S1) ........................................... 6
24 Transformer Switch (1S70) ................................................ 6
Human Interface Module ......................................................... 7
General Operation ................................................................... 7
Menu Keys ............................................................................... 8
Data Manipulation Keys .......................................................... 8
Unit Operation Keys ................................................................ 9
General Status Display .......................................................... 10
Unit "Off" or "Stopped" .......................................................... 10
Unit "On" ................................................................................ 10
No Configuration .................................................................... 10
Factory Presets ..................................................................... 11
Password Protected Screens ................................................ 14
1 Status Menu
1.1 <top level status screen> ................................................. 15
1.2 Active Leaving Solution Setpoint or
Active Ice Build Terminate STP ........................................ 15
1.3 Compressor Status Submenu ......................................... 15
Compressor Relay K11 ......................................................... 16
Compressor Relay K12 ......................................................... 16
Compressor Relay K3 ........................................................... 16
Compressor Relay K4 ........................................................... 16
Compressor Module Ckt 1, Saturated Condensor Temperature16
Refrigerant Ckt 1, Suction and
Sat Liquid Temperatures ....................................................... 16
Refrigerant Ckt 1, Suction and Liquid Pressures ................. 16
Refrigerant Ckt 1, Superheat and
Subcooling Temperatures ...................................................... 16
Compressor Module Ckt 2, Saturated
Condensor Temperature ........................................................ 16
Refrigerant Ckt 2, Suction and
Sat Liquid Temperatures ....................................................... 17
Refrigerant Ckt 2, Suction and Liquid Pressures ................. 17
Refrigerant Ckt 2, Superheat and
Subcooling Temperatures ...................................................... 17
Ckt 1 and 2 Liquid Line Solenoid Valve ................................ 17
Compressor 1A Currents, Phase A and B............................. 17
Compressor 1B Currents, Phase A and C ............................ 17
Compressor 2A Currents, Phase B and C ............................ 17
Compressor 2B Currents, Phase A and C ............................ 17
1.4 General System Status Submenu ................................... 17
CGM Evap Solution Pump Relay and Evap Soln Flow
Switch Proving ....................................................................... 17
MCM Heat Tape Control Relay ............................................. 18
CGM Hot Gas Bypass Control Relay .................................... 18
CGM Ice Building Control Relay ........................................... 18
Setpoint Value Measured, CGM Ext Leaving Soln STP ....... 18
1.5 Controlling Setpoint Status Submenu ........................... 18
Active Leaving Solution Setpoint, and source ...................... 18
Active Ice Build Termination Setpoint, and source ............... 18
Active Hot Start Load Limit Setpt, and source ...................... 19
Active Capacity Limit Setpoint, and source .......................... 19
1.6 Temperature Input Status Submenu .............................. 19
Temp Measured by Sensor Connected To
CGM Entering Soln Temp Input ............................................ 19
Table of Contents
Temp Measured by Sensor Connected To
CGM Leaving Soln Temp Input ............................................. 19
Temp Measured by Sensor Connected To
CGM Outside Air Temp Input ................................................ 19
Compressor Module Ckt 1 Saturated
Condenser Temperature ........................................................ 19
Refrigerant Ckt 1, Suction and
Liquid Line Temperatures ...................................................... 19
Compressor Module Ckt 2 Saturated
Condenser Temperature ........................................................ 19
Refrigerant Ckt 2, Suction and
Liquid Line Temperatures ...................................................... 20
Temp Measured by Sensor Connected To
CGM Zone Temp Input .......................................................... 20
Temp Measured by Sensor Connected To
CGM ICS Temp Input ............................................................ 20
1.7 Misc Input Status Submenu ............................................ 20
CGM Ice Build Command Input ............................................ 20
CGM Evap Soln Flow Switch Input ....................................... 20
Refrigerant Ckt 1, Suction and Liquid Pressures ................. 20
Refrigerant Ckt 2, Suction and Liquid Pressures ................. 20
Compressor 1A Current, Phase A and B .............................. 20
Compressor 1B Current, Phase A and C .............................. 20
Compressor 2A Current, Phase B and C .............................. 21
Compressor 2B Current, Phase A and C .............................. 21
1.8 GBAS 0-5VDC Module Status Submenu ........................ 21
GBAS 0-5VDC Analog Input 1, Voltage and Assignment ..... 21
GBAS 0-5VDC Analog Input 2, Voltage and Assignment ..... 21
GBAS 0-5VDC Analog Input 3, Voltage and Assignment ..... 21
GBAS 0-5VDC Analog Input 4, Voltage and Assignment ..... 21
GBAS 0-5VDC Demand Limit Input Status ........................... 21
GBAS 0-5VDC Binary Output 1, Status and Assignment ..... 21
GBAS 0-5VDC Binary Output 2, Status and Assignment ..... 21
GBAS 0-5VDC Binary Output 3, Status and Assignment ..... 21
GBAS 0-5VDC Binary Output 4, Status and Assignment ..... 21
GBAS 0-5VDC Binary Output 5, Status and Assignment ..... 21
1.9 GBAS 0-10VDC Module Status Submenu ...................... 21
GBAS 0-10VDC Analog Input 1, Voltage and Assignment ... 21 GBAS 0-10VDC Analog Input 2, Voltage and Assignment ... 21 GBAS 0-10VDC Analog Input 3, Voltage and Assignment ... 21 GBAS 0-10VDC Analog Input 4, Voltage and Assignment ... 21
GBAS 0-10VDC Demand Limit Input Status ......................... 22
GBAS 0-10VDC Binary Output 1, Status and Assignment... 22 GBAS 0-10VDC Analog Output 1, Voltage and Assignment 22 GBAS 0-10VDC Analog Output 2, Voltage and Assignment 22 GBAS 0-10VDC Analog Output 3, Voltage and Assignment 22 GBAS 0-10VDC Analog Output 4, Voltage and Assignment 22 GBAS 0-10VDC Analog Output 5, Voltage and Assignment 22
2 Setpoints Menu
HI Leaving Solution Setpoint ................................................. 34
HI Ice Build Terminate Setpoint ............................................. 34
Low Solution Cutout Temp .................................................... 34
Heat Tape Temperature Setpoint .......................................... 34
Hot Start Load Limit Setpoint ................................................ 34
Low Ambient Pump Override Temp....................................... 34
Low Ambient Comp Lockout Temp........................................ 34
Leaving Solution Setpoint Source ......................................... 34
Ice Building Terminate Setpoint Source ................................ 35
Hot Start Load Limit Setpoint Source ................................... 35
Capacity Limit Setpoint Source ............................................. 35
3 Setup Menu ........................................................ 23
3.1 Language Selection and Unit of Measure ...................... 23
3.2 Local/Remote Control and Unit Address ....................... 23
3.3 General Unit Functions Setup Submenu ....................... 23
Reduce Multi-Unit Startup Power Demand, After
Power-Up, Delay Unit Start ................................................... 23
Demand Limit Definition ........................................................ 24
Compressor Lead/Lag Function Enable/Disable .................. 24
Hot Gas Bypass Function Enable/Disable ............................ 24
Hot Gas Bypass Max Run Time ............................................ 24
Hot Start Time Interval........................................................... 24
3
Page 4
Table of Contents
Hot Operation Response Option ........................................... 24
Pumpdown Function Enable/Disable .................................... 24
Default Chiller Solution Pump Mode ..................................... 24
Evap Soln Pump Off Delay Time........................................... 25
Loop Stabilization Time ......................................................... 25
Low Ambient Compressor Lockout Enable/Disable.............. 25
Leaving Solution Reset Type ................................................ 25
Reset Start and End Temperatures ....................................... 25
Reset Maximum Amount Applied .......................................... 25
Chiller Application (Comfort or Process Cooling) ................. 25
3.4 Ice Building Control Functions Submenu ..................... 26
Ice Building Function Enable/Disable and Ice Building Mode
(Once or Continuous) ............................................................ 26
Ice Build Delay Time (Between Cycles) ................................ 26
3.5 Head Pressure Ctrl Setup Submenu .............................. 26
Saturated Condenser Temp Control Band, Lower
and Upper Limits ................................................................... 26
Saturated Condenser Temp Control Band, Temporary Low
Limit Suppression .................................................................. 27
Saturated Condenser Temperature, Efficiency Check Point 27 Saturated Condenser Temperature,
Low Ambient Control Point .................................................... 27
Saturated Condenser Temperature, Low Ambient Control
Deadband .............................................................................. 27
Saturated Condenser Temperature, OA Temp Supression
Setpoint .................................................................................. 27
3.6 GBAS 0-5VDC Module I/O Assignment .......................... 27
GBAS (0-5VDC) Analog Input 1 Assignment ........................ 27
GBAS (0-5VDC) Analog Input 2 Assignment ........................ 27
GBAS (0-5VDC) Analog Input 3 Assignment ........................ 27
GBAS (0-5VDC) Analog Input 4 Assignment ........................ 27
GBAS (0-5VDC) Binary Output 1 Definition ......................... 28
GBAS (0-5VDC) Output 1 Alarm Assignments ..................... 28
Assign Diag to GBAS (0-5V) Output 1 .................................. 28
GBAS (0-5VDC) Binary Output 2 Definition ......................... 29
GBAS (0-5VDC) Output 2 Alarm Assignments ..................... 29
Assign Diag to GBAS (0-5V) Output 2 .................................. 29
GBAS (0-5VDC) Binary Output 3 Definition ......................... 29
GBAS (0-5VDC) Output 3 Alarm Assignments ..................... 29
Assign Diag to GBAS (0-5V) Output 3 .................................. 29
GBAS (0-5VDC) Binary Output 4 Definition ......................... 29
GBAS (0-5VDC) Output 4 Alarm Assignments ..................... 29
Assign Diag to GBAS (0-5V) Output 4 .................................. 29
GBAS (0-5VDC) Binary Output 5 Definition ......................... 29
GBAS (0-5VDC) Output 5 Alarm Assignments ..................... 29
Assign Diag to GBAS (0-5V) Output 5 .................................. 29
3.7 GBAS 0-10VDC Module I/O Assignment ........................ 29
GBAS (0-10VDC) Analog Input 1 Assignment ...................... 29
GBAS (0-10VDC) Analog Input 2 Assignment ...................... 29
GBAS (0-10VDC) Analog Input 3 Assignment ...................... 29
GBAS (0-10VDC) Analog Input 4 Assignment ...................... 29
GBAS (0-10VDC) Binary Output Definition .......................... 29
GBAS (0-10VDC) Output Alarm Assignments ...................... 29
Assign Diag to GBAS (0-10V) Output ................................... 30
GBAS (0-10VDC) Analog Output 1 Definition....................... 30
GBAS (0-10VDC) Analog Output 2 Definition....................... 30
GBAS (0-10VDC) Analog Output 3 Definition....................... 30
GBAS (0-10VDC) Analog Output 4 Definition....................... 30
GBAS (0-10VDC) Analog Output 5 Definition....................... 30
3.8 CGM Alarm Output Disagnostic Assignments .............. 30
Assign Diagnostic to CGM Alarm Output .............................. 30
3.9 Device Characteristics Setup Definitions ...................... 31
Actuator Setup, Ckt 1 Low Ambient Output, Max Stroke Time 31
Actuator Setup, Ckt 1 Low Ambient Output, Min Voltage ..... 31
Actuator Setup, Ckt 1 Low Ambient Output, Max Voltage .... 31
Actuator Setup, Ckt 1 Low Ambient Output,
Direct/Reverse Acting ............................................................ 31
Actuator Setup, Ckt 2 Low Ambient Output, Max Stroke Time 31
Actuator Setup, Ckt 2 Low Ambient Output, Min Voltage ..... 31
Actuator Setup, Ckt 2 Low Ambient Output, Max Voltage .... 31
Actuator Setup, Ckt 2 Low Ambient Output,
Direct/Reverse Acting ............................................................ 32
Ckt 1 Suction Line Pressure Transducer, 0 PSIG and 100
PSIG Voltages ....................................................................... 32
Ckt 1 Liquid Line Pressure Transducer, 0 PSIG and 400 PSIG
Voltages ................................................................................. 32
Ckt 1 Suction Line Pressure Transducer, 0 PSIG and 400
PSIG Voltages ....................................................................... 32
Ckt 2 Liquid Line Pressure Transducer, 0 PSIG and 400 PSIG
Voltages ................................................................................. 32
Ckt 2 Suction Line Pressure Transducer, 0 PSIG and 400
PSIG Voltages ....................................................................... 32
3.10 Control Algorithm Tuning Parameters ......................... 32
Comfort Cooling, Design Delta Temperature Setpoint ......... 32
Comfort Cooling, Control Response Setpoint ....................... 33
Process Cooling Control Gains, Proportional and Reset Time 33
Process Cooling Control Gains, Proport Bias and Max Cycle
Rate ....................................................................................... 33
Low Ambient Fan Control Gain, Proportional and Reset Time . 33
Low Ambient Fan Control Gain, Rate Time .......................... 33
4 Configuration Menu .......................................... 36
Configuration - Model Num Digit 5,6,7 Capacity (tonnage) .. 36
Configuration - Model Num Digit 8 Line Voltage .................. 36
Configuration - Model Num Digit 11 Ice Building Control ..... 36
Configuration - Model Num Digit 11 Leaving Solution
Setpoint Range ...................................................................... 36
Configuration - Model Num Digit 13+ Hot Gas Bypass Option ... 36
Configuration - Model Num Digit 13+ Voltage/Phase Monitor..... 36
Configuration - Model Num Digit 13+ GBAS 0-5VDC Module .... 36
Configuration - Model Num Digit 13+ GBAS 0-10VDC Module .. 36 Configuration - Model Num Digit 13+
Superheat/Subcool Module ........................................................... 37
Configuration - Model Num Digit 13+ Current Sensing Module .. 37 Configuration - Model Num Digit 13+ TCI
Communications Module ............................................................... 37
Configuration - Model Num Digit 13+ Remote Human Interface 37
Software Revision Number Report, Cold Generator Module
(CGM) .................................................................................... 37
Software Revision Number Report, Single Compressor
Module (SCM) ........................................................................ 37
Software Revision Number Report, Multiple Compressor
Module (MCM) ....................................................................... 37
Software Revision Number Report, GBAS 0-5VDC Module 37 Software Revision Number Report, GBAS 0-10VDC Module37 Software Revision Number Report, Superheat/Subcool
Module (SSM) ........................................................................ 37
Software Revision Number Report, Current Sensing Module
(CSM) ..................................................................................... 38
Software Revision Number Report, Unit Human Interface (HI) 38 Software Revision Number Report, Remote Human Interface
(RHI) ...................................................................................... 38
Software Revision Number Report, TCI4 Communications
Module (TCI) .......................................................................... 38
5 Service Mode Menu ....................................... 39
CGM Evap Solution Pump Relay .......................................... 39
Liquid Line Solenoid Valve Ctrl Relays, Ckt 1 and Ckt 2...... 39
Low Ambient LPC Bypass Relay(s), Ckt 1 and Ckt 2 ........... 39
CGM Hot Gas Bypass Control Relay .................................... 39
Compressor Relays, K11 and K12 or K11,K12, K3 and K4.. 40
Condenser Fan Outputs, 1A, 1B and 1C .............................. 40
Condenser Fan Outputs, 2A, 2B and 2C .............................. 40
Condenser Fan Speed, Ckt 1 and Ckt 2 ............................... 40
CGM Alarm Output ................................................................ 40
MCM Heater Tape Relay K13................................................ 40
CGM Ice Build Relay Output ................................................. 41
GBAS 0-5VDC Module Relay Outputs 1-5 ........................... 41
GBAS 0-10VDC Module Relay Output ................................. 41
GBAS 0-10VDC Module Analog Outputs 1 and 2 Voltages . 41 GBAS 0-10VDC Module Analog Outputs 3 and 4 Voltages . 41
CGM ICS Controlled Relay ................................................... 41
Index .......................................................................................... 65
4
Page 5
General Information
G = Superheat / Subcooling
P
* = Field Installed Options
Model Number Description
All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit. An explanation of the alphanumeric identification code is provided below. Its use will enable the owner/operator, in­stalling contractors, and service engineers to define the op-
Sample Model Number: CGAF - C30 4 A A B 0 D etc. Digit Number: 1,2,3,4 5,6,7 8 9 10 11 12 13 +
Digit 1,2 - Unit Function Digit 9 - Heating Capacity Digit 13, etc. Miscellaneous
CG = Cold Generator A = Standard A = Communications Interface (TCI)
Digit 3 - Unit Type Digit 10 - Design Sequence
A = Air-Cooled Condenser H = Brazed Plate Chiller D = Non-Fused Unit-Mounted Disconnect
Digit 4 - Development Sequence Digit 11 - Leaving Water Setpoint
F = Sixth A = 40 - 50 F w/o Ice Machine
B = 30 - 39 F w/o Ice Machine H = Hot Gas Bypass
Digit 5,6,7 - Nominal Capacity
C20 = 20 Tons E = 20 - 29 F w/o Ice Machine K = Stock Unit C25 = 25 Tons 1 = 40 - 50 F w Ice Machine L = LonTalk® Communication Interface Module C30 = 30 Tons 2 = 30 - 39 F w Ice Machine M = *Remote Human Interface C40 = 40 Tons 3 = 51 - 65 F w Ice Machine N = Generic BAS Module 0-10 VDC Analog Output C50 = 50 Tons 4 = 20 - 29 F w Ice Machine P = Remote Setpoint Potentiometer P/S C60 = 60 Tons S = Special Q = *Zone Sensor (Chilled Solution Reset) P/S
Digit 8 - Power Supply
E = 200/60/3 P/S*** W = **Electronic Low Ambient Dampers P/S F = 230/60/3 Y = *Inter-Processor Comm Bridge (IPCB) 4 = 460/60/3 P/S*** 9 = Packed Stock Unit 5 = 575/50/3 9 = 380/50/3 0 = None ** = Factory or Field Installed Option D = 415/50/3 1 = UL/CSA *** Available on Pack Stock Units S = Special
Unit Nameplate
One Mylar unit nameplate is located on the outside upper left corner of the control panel door. It includes the unit model number, serial number, electrical characteristics, weight, refrigerant charge, as well as other pertinent unit data. A small metal nameplate with the Model Number, Se­rial Number, and Unit Weight is located just above the Mylar nameplate, and a third nameplate is located on the inside of the control panel door.
D = 51 - 65 F w/o Ice Machine J = Generic BAS Module 0-5 VDC Input, Binary O.
Digit 12 - Agency Approval
Hazard Identification
WARNING – Indicates a potentially hazardous
situation which, if not avoided, could result in death or serious injury.
CAUTION – Indicates a potentially hazardous
situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
CAUTION - Indicates a situation that may result in
equipment or propertydamage only accidents.
Echelon, LON, LONWORKS, LonBuilder, NodeBuilder, LonManager, LonTalk, LonUsers, Neuron, 3120, 3150, the Echelon logo, and the LonUsers logo are trademarks of Echelon Corporation registered in the United States and other countries. LonLink, LonResponse, LonSupport, LonMaker, and LonPoint are trademarks of Echelon Corporation.
eration, specific components, and other options for any spe­cific unit.
When ordering replacement parts or requesting service, be sure to refer to the specific model number, serial number, and DL number (if applicable) stamped on the unit name­plate.
B = No Unit Heat Tape (50 Hz Units Only) C = Compressor Current Sensing (CSM)
E = *Unit Isolators - Neoprene P/S F = *Unit Isolators - Spring P/S
S = Special V = Copper Fin Condenser Coil
Commonly Used Acronyms
For convenience, a number of acronyms and abbreviations are used throughout this manual. These acronyms are al­phabetically listed and defined below.
A/D = Analog/Digital BAS = Building Automation System CAR = Circuit shuwdown - Auto Reset Cf = Evaporator limit control integrator CGA = Air cooled - Cold Generator UCM = Cold generator module. Contains I/O for most
chilled solution functions. Comp(s) = compressor(s) Cond = condenser Ckt = circuit CLE = Chilled solution flow integrator CMR = Circuit shutdown - Manual Reset CRS = Control response setpoint CSA = Canadian Standards Association CCW = counterclockwise CW = clockwise DBZ = Width of Dead Band Zone DDT = Design Delta-T setpoint Delta T = The temperature difference between EST & LST Diag = diagnostics EST = Entering solution temperature Ent = Entering
5
Page 6
General Information
Evap = Evaporator Ext = External GBAS = Generic Building Automation System Module gfm = gallons per minute HGBP = Hot gas bypass HI = Human Interface HO = History Only HSLLS = Hot Start Load Limit setpoint HVAC = Heating, Ventilation and Air Conditioning IAR = Information only Auto Reset IBTS = Ice Build Terminate Setpoint ICS = Integrated Comfort System IFW = Informational Warning INFO = Information Only [Diagnostic] I/O = Inputs/outputs IOM = installation/operation/maintenance manual IPC = Interprocessor communications IPCB Module = Interprocessor communications bridge
module IRDT = Ice Rebuild Delay Timer LCD = Liquid Crystal Display LCI = LonTalk® Communication Interface LCI-I = LonTalk® Communication Interface for Intellipak LED = Light Emitting Diode LH = left-hand LonTalk = An open, device networking communications
protocol for controls. This protocol is defined in ANSI
approved standard EIA/CEA-709.1-A-1999. LSC = Low Solution Temperature Cutout Setpoint LPC = Low Pressure Cutout [Switch] LST = Leaving solution temperature MAR = Machine shutdown - Auto Reset Max = maximum MCM = Multiple circuit compressor module Min = minimum Misc = miscellaneous MMR = Machine shutdown - Manual Reset Mod = module Mon = monitor NCS = Number of capacity steps num = number OA = Outdoor air OAT = Outdoor air Temperature PAR = Partial System Disable, Auto Reset [Diagnostic] PMR = Partial System Disable, Manual Reset [Diagnostic] PRT = Pump Run Timer PSIG = pounds-per-square-inch gauge pressure PWM = Pulse width modulated RAM = Random Access Memory RTM = rooftop module ROM = Read Only Memory S/W = Software Sat - saturated SCM = single circuit compressor module SCT = Saturated Condensing Temperature Soln = solution STP = setpoint TCI Module = Trane communications interface module Temp = temperature UCM = Unit Control Modules UL = Underwriter's Laboratories VFD = Variable Frequency Drive w.c. = water column XL = across-the-line start
Glossary of Terms
Carefully review these definitions since they are used throughout this document and the I.O.M.. Knowledge of these terms is essential in gaining an understanding of how these units operate.
Active Setpoint
The setpoint which is currently being used for control by the setpoint source selection.
Comm3
Trane proprietary network communication protocol.
Comm5
Trane’s implementation of LonTalk (an open network communication protocol.)
Chilled Solution Temperature Reset
A function that shifts the Leaving Solution Temp Setpoint an amount based on the value of another parameter— typically ZoneTemp, Entering Solution Temp or Outdoor Air Temp. The purpose of this function is to lower unit ca­pacity to better meet load requirements.
Compressor Protection Switch
A pressure switch installed on the suction line that pre­vents compressor operation below the switch's setpoint.
Control Band
The range of temperatures or pressures which would normally be maintained by the various control functions.
Control Point
The value of a setpoint that an algorithm is using at any given time.
Deadband
As applied to LST control, this refers to a range of tem­peratures equally spaced above and below the CSS in which the control algorithm is satisfied. There is not ad­justment of machine capacity within the deadband.
Emergency Stop
UCM binary input. Can be used for emergency shutdown of the unit by field-installed contacts. A diagnostic is pro­duced when this input is open.
External Auto/Stop
A binary input on the UCM that allows the use of a field­supplied switch to perform normal unit on/off action.
Leaving Solution Setpoint
Active leaving solution setpoint. This setpoint is the con­trol setpoint for process and comfort cooling.
Leaving Solution Temperature Control Point
The revised temperature setpoint after chilled solution temp reset has been applied.
LonTalk©
An open, device networking communications protocol for controls. This protocol is defined in ANSI approved stan­dard EIA/CEA-709.1-A-1999.
Low Ambient Compressor Lockout
A function which prevents compressor operation at low outdoor ambient temperatures.
Remote Human Interface
A human interface module designed to be mounted re­motely from the unit. There will be some functional differ­ences between a unit mounted and a remote mounted human interface module.
Reset Amount Maximum
The maximum amount of reset allowed.
Reset End Temperature
The temperature at which the maximum reset amount will occur.
Reset Start Temperature
The temperature at which reset will begin.
Unit Control Module
This term is used to describe the set of electronic mod­ules which make up the unit control system.
6
Page 7
General Information
UCM Control System
Trane Large Commercial Cold Generator Units are con­trolled by a microelectronic control system that consists of a network of modules and are referred to as Unit Control Modules (UCM).
The unit size, peripheral devices, options, etc... determine the number and type of modules that a particular unit may employ.
The UCM receives analog and binary inputs, then pro­cesses this information and supplies outputs in the form of modulating voltages, contact closures, etc... to control damper actuators, fan motors, compressors, valves, and other electrical devices in the system to maintain set tem­perature levels.
The UCM provides some equipment protection functions both directly and indirectly, such as chilled water flow and compressor lockouts.
Listed below are the various modules that may be em­ployed in a UCM control system.
Cold Generator Module (1U48) (CGM - Standard)
The Cold Generator Module (CGM) responds to cooling re­quests by energizing the proper unit components based on information received from other unit modules, sensors, re­mote panels, and customer supplied binary inputs. It ini­tiates unit operation based on that information.
Compressor Module (1U49) (MCM)
The Compressor module, (Single Circuit & Multiple Circuit), upon receiving a request for mechanical cooling, energizes the appropriate compressors and condenser fans. It moni­tors the compressor operation through feedback information it receives from various protection devices. It also provides heat tape output control for heat exchanger protection.
Interprocessor Communications Board (1U55) (IPCB ­used with Optional Remote Human Interface)
The Interprocessor Communication Board expands commu­nications from the unit’s UCM network to a Remote Human Interface Panel. DIP switch settings on the IPCB module for this application should be; Switches 1 and 2 “Off”, Switch 3 “On”.
Trane Communications Interface Module (1U54) (TCI ­Optional - used with Trane ICS
The Trane Communication Interface module expands com­munications from the unit’s UCM network to a Trane Tracer
100
or a Tracer Summit™ system and allows external setpoint adjustment and monitoring of status and diagnos­tics.
DIP Switch settings on the TCI module for these applica­tions should be: Switches 1, 2, and 3 are “Off”
)
Generic Building Automation System Module (1U51 = GBAS 0-5V, 1U98 = GBAS 0-10V) (Optional - used with Non-Trane Building Control System)
The Generic Building Automation System (GBAS) module allows a non-Trane building control system to communicate with the unit and accepts external setpoints in form of ana­log inputs (0 - 5 DCV or 0 - 10 DCV depending on the mod­ule selected) and a binary Input for demand limit. Five (5) binary outputs are available on 0 - 5 DCV modules. One (1) binary output and four (4) analog outputs are available on the 0 - 10 DCV modules. Refer to the “Field Installed Con­trol Wiring” section for the control wiring to the GBAS mod­ule and the various desired setpoints with the correspond­ing DC voltage inputs.
Lontalk Communication Interface Module (1U54)
(LCI Optional - used on units with Trane ICS Building Automation Systems) The LonTalk Communication Interface module expands communications from the unit’s UCM network to a Trane Tracer Summit™ or a 3rd party building automation system, that utilizes LonTalk, and allows external setpoint and con­figuration adjustment and monitoring of status and diag­nostics.
Current Sensing Module (1U90) (CSM - Optional)
Current transformers located around two (2) of the main power leads for each compressor monitors the running cur­rent during compressor operation. The information is sent to the UCM and can be accessed through the “Compressor Status” submenu displayed at the Human Interface Module.
Superheat & Subcooling Module (1U91) (SSM ­Optional)
Monitors the system operating superheat and subcooling through the use of pressure transducers, liquid line, and suction line temperature sensors. The information is sent to the SSM and can be accessed through the “Compressor Status” submenu displayed at the Human Interface Module.
or 3rd party
Power Disconnecting Switches
Manual Disconnect Switch
(Optional 1S14) Manual disconnect switch 1S14, located in the unit control panel, instead of the power terminal block 1TB1, allows the operator to disconnect power from the unit's “high” voltage (200V-575V) section, the 115V section, and the 24V section without having to open the control panel door. A description of its features and operation are given in the Installation, Operation, & Maintanence manual.
115V Control Circuit Switch (1S1)
Control circuit switch (1S1) is provided on all units and is lo­cated downstream of the 115V transformer 1T1. It allows the operator to disconnect power from the unit's 115V con­trol components by placing the switch in the "Off" position.
24V Transformer Switch (1S70)
Transformer switch 1S70 is provided on all units and is lo­cated downstream of 24V transformers 1T2 and 1T3. It al­lows the operator to disconnect (24V) power from all of the unit's control modules by placing the switch in the "Off" po­sition.
For a complete description of the 24V components and op­eration, refer to the latest edition of the applicable Installa­tion, Operation and Maintenance manual listed on the unit nameplate.
7
Page 8
General Information
Human Interface Module
(1U65 = Local 6U66 = Remote)
The Human Interface (HI) Module illustrated in Figure 1 is the device which enables the customer, building owner, or contractor, to communicate to the unit the necessary pa­rameters for unit operation.
The local (unit mounted) Human Interface and the Remote Human Interface Panels’ functions are identical, except for Service mode which is not available on the Remote Human Interface Panel.
The local HI Module is located in the unit’s main control panel. A small door located in the unit’s control panel door allows access to the HI Module’s keypad and display win­dow.
There is a 2 line by 40 character LCD screen which pro­vides status information for the various unit functions as well as menus used to set or modify the operating param­eters. There is a 16 key keypad adjacent to the LCD screen which allows the operator to scroll through the various menus and make adjustments to the setpoints, etc...
The information displayed in the LCD window will be top level unit status information unless the operator initiates other displays.
Figure 1
Human Interface Module
General Operation
At power-up, the Human Interface LCD will display one of three initial screens illustrated in the "General Status" sec­tion.
1. Unit Status (Unit Off or Stopped) (The unit is configured and operational, but is not running). This screen shows state, mode, and function information when the unit is off or stopped.
2. Unit Status (Unit On) (The unit is configured and opera­tional, and is running). This screen shows state, mode, and function information when the unit is on.
3. No Configuration (the unit needs to be configured). This screen shows that required configuration data is missing.
The LCD screen has a backlight that makes the information easier to read. The light will go out if no keys are pressed for 30 minutes. If it goes out, simply press the STATUS key.
8
Page 9
General Information
Menu Keys
The six keys illustrated in Figure 2 in the MENU area (STA­TUS, SETPOINTS, SETUP, CONFIGURATION, DIAGNOS­TICS, and SERVICE MODE) are used to bring up the vari­ous interactive menus where the user inputs and accesses unit operating data. Pressing these keys will display the ini­tial screen for the menu designated by the key’s name. The following information describes the keys and their functions when viewing the various menus.
If no key is pressed for 30 minutes while the LCD is display­ing a menu screen, it will revert back to the unit operating status screen.
Figure 2
Human Interface Keypad
SETPOINTS Key
Pressing the SETPOINTS key will cause the LCD screen to display the first of the setpoint screens where the operator will designate default temperature setpoints and setpoint source information. While scrolling through the setpoint screens, pressing this key again will cause the LCD to dis­play the first setpoint screen.
DIAGNOSTICS Key
Pressing the DIAGNOSTICS key at any time will allow the operator to view any unit function failures. The LCD screen will display one of the diagnostic screens (depending on which diagnostic, if any, is present). If no key is pressed for 30 minutes while the screen is displaying diagnostic infor­mation, it will revert back to the operating status display.
CONFIGURATION Key
Pressing the CONFIGURATION key will cause the LCD screen to display the first of the configuration screens where the operator will designate unit configuration data such as unit type, capacity, installed options, etc...
This information was programmed at the factory. Pressing the configuration key at any level in the configuration menu will display the first configuration screen.
Note: This key should be used if the unit's configuration data is lost or new options are added in the field, and to view current configuration.
STATUS Key
Pressing the STATUS key causes the LCD to display the operating status screen; i.e. "On", "Unit Stop", "External Stop", "Emergency Stop", "Service Mode". Pressing the NEXT key allows the operator to scroll through the screens which provide information such as air and refrigerant tem­peratures, pump operation, compressor operation, as well as active cooling and compressor lockout setpoints. Press­ing the STATUS key while viewing any of the data screens will cause the LCD to go back to the operating status screen.
SETUP Key
Pressing the SETUP key will cause the LCD screen to dis­play screens where the operator will designate various op­erating parameters such as temperature ranges, limits, per­centages, etc. for the control of the unit’s various operating modes. Pressing the SETUP key at any level in the SETUP menu will display the first SETUP screen.
SERVICE MODE Key
Pressing the SERVICE MODE key causes the LCD to dis­play the first of the service test mode screens showing vari­ous unit components which may be turned on or off for the particular test being performed. Once the status of these components is designated, the LCD will display screens that allow the operator to designate the TEST START time delay for each test.
Data Manipulation Keys
The six data manipulation keys illustrated inFigure 2, (EN­TER, CANCEL, + (Plus), - (Minus), PREVIOUS, and NEXT are used to modify the data within the screens (change val­ues, move the cursor, confirm choices, etc...)
ENTER Key
This key will confirm the new values that were designated by pressing the + (Plus) or - (Minus) keys at all edit points. When viewing status and diagnostics screens, it has no function.
CANCEL Key
After changing data, at an editable screen, but before con­firming it with the ENTER key, pressing the CANCEL key will return the data to its previous value. This key shall also function to clear active diagnostics.
9
Page 10
General Information
+ (Plus) Key
When viewing a setpoint screen, this key will increase the temperature or pressure value of the setpoint. When work­ing with a status menu, it will add the current status display to the custom menu. When viewing the setup or service test screens, it will increase setpoints or toggle choices On or Off at each edit point.
- (Minus) Key
This key when viewing the setpoint screen will decrease the temperature or pressure value of the setpoint. When view­ing the setup or service test screens, it will decrease setpoints or toggle choices On or Off at each edit point. When viewing the custom menu, pressing the - (Minus) key will remove the status screen from the custom menu. When viewing diagnostics screens it has no function.
PREVIOUS Key
Pressing the PREVIOUS key causes the LCD to scroll backwards through the various displays for each menu. At displays with multiple edit points, it moves the cursor from one edit point to another.
NEXT Key
Pressing the NEXT key causes the LCD to scroll forward through the various displays for each menu. At displays with multiple edit points it moves the cursor from one edit point to another.
Unit Operation Keys
AUTO Key
Pressing the AUTO key at any time will cause the display to go to the top level status display and, if the unit is shut­down, will cause the unit to begin operation in the appropri­ate mode no matter what level in the menu structure is cur­rently being displayed. If the current display is an editable display, the AUTO key will confirm the desired edit.
STOP Key
Pressing the STOP key will cause the unit to transition to the stop state. If the current display is editable, pressing the STOP key will cancel the desired edit.
TEST START Key (SERVICE)
Pressing this key while viewing any screen in the SERVICE Mode menu will start the service test. When viewing status, setup, setpoint, and diagnostics screens, it has no function.
CUSTOM Key
The Custom menu is simply a status menu that contains screens that the user monitors most frequently. The Custom menu can only contain five status screens. To create the Custom menu, press the STATUS key, followed by the NEXT key (this brings up the initial status screen). If you want to add this screen to the Custom menu, press the + (Plus) key, if not, press the Next key again until a status screen appears that you would like to add to the Custom menu. Pressing the + (Plus) key while viewing any of the various status screens will add that screen to the Custom menu. Once the Custom menu is programed it can be ac­cessed by pressing the CUSTOM key. To remove a status screen from the Custom menu, press the CUSTOM key, then press the NEXT key until the status screen that you want to remove appears, then press the - (Minus) key.
After adding a screen to the Custom menu, the following screen is displayed:
“Item Added to Custom Menu”
If the + (PLUS) key is pressed and the Custom menu is full, the following screen is displayed:
“Custom Menu Is Full”
After deleting a screen from the Custom Menu, the follow­ing screen is displayed:
“Item Deleted from Custom Menu”
If the CUSTOM key is pressed and there are no entries, the following screen is displayed:
No items are selected for Custom Report See Operators Manual to select entries
10
Page 11
General Information
(Blank)
(Diagnostics)
Trouble Indicator
____________________ ____________________
General Status Display
Anytime the unit is powered up, or the STATUS, AUTO, or STOP keys are pressed, the unit mounted Human Interface will display one of the following three general status display screens. The operator will then be able to enter keystrokes which will allow him to navigate through a set of menus and submenus in order to provide/access various monitoring, setup, and configuration infromation. The Human Interface will not display screens or parts of screens for which the unit is not config­ured.
Unit "Off" or "Stopped"
If at power up the unit is not running, the following display will appear on the Human Interface LCD screen. When this screen is being displayed, the only functional keys are the six menu keys (STATUS, SETPOINTS, DIAGNOSTICS, SETUP, CON­FIGURATION, AND SERVICE MODE), the AUTO key, the CUSTOM key, and the STOP key.
Mode of Oper ation
(On)
(Off)
_______________
Solution Pump
_____
Top Level State
(External Stop) (Emergency Stop)
Trouble Indicator
(Unit Shutdown) (Unit Stop) (Blank)
Unit "On"
If the unit has entered an operating state (running), the following display will appear on the Human Interface LCD screen. When this screen is being displayed, the only functional keys are the six menu keys (STATUS, SETPOINTS, DIAGNOS­TICS, SETUP, CONFIGURATION, AND SERVICE MODE), the AUTO key, the CUSTOM key, and the STOP key.
Mode of Operation
(Cool 0)
(Hot Gas Bypass)
(Cool 1) (Cool 2) (On) (Cool 3) (Off) (Cool 4)
(Flow SW State Fail)*
_______________
Top Level State
(Servi ce Mode On) Ice Bui lding Co mple te (Comfort Cooling) Ice Rebuild Delay (Process Cooling) Unit Standby (Diagnostics) (Ice Building) (Blank) (Loop Stabilization)
Solution Pump
_____
*Service Test Mode Only - Flow switch failed to open after solution pump turned off.
No Configuration
If at power up the unit has not been programmed with the necessary configuration data for normal unit operation, the follow­ing display will appear on the Human Interface LCD screen. When this screen is being displayed, the only functional key is the CONFIGURATION key.
No Configuration Present
Press Configuration Key
Note: This screen will only appear when the CGM has been field replaced. Refer to the Configuration Menu.
11
Page 12
General Information
g
g
g
g
g
g
g
g
g
g
g
49
g
g
g
g
g
g
g
g
g
g
g
g
g
Factory Presets
If your application requires different settings, turn to the
listed page beside the function, press the designated func­The CGM controlled unit has many operating functions whose settings are preset at the factory, but may be modi­fied to meet the unique requirements of each job. The fol­lowing list identifies each of the unit's adjustable functions
tion menu key, then press and hold the NEXT or PREVI-
OUS key until its screen appears on the LCD. Once the
proper screen appears, simply follow the programming in-
structions given below the applicable screen in this manual. and the value assigned to it. If these factory presets match your application's requirements and the"System Start-Up procedures in the Installation, Operation & Maintyenance manual has been completed, simply press the AUTO key at
Note: Record any changes made to the factory preset values in the corresponding space provided.
the Human Interface module to begin unit operation.
Factory Preset Changed See page... To adjust
To to adjust Press....
Setpoints
Leavin Low Ambient Compressor Lockout Temperature Setpoint 40 de Heat Tape Temperature Setpoint 40 de Hot Start Load Limit Setpoint 71 de Ice Buildin Low Solution Cutout Temperature 35 de Low Ambient Pump Override Temperature 35 de Use Leavin Use Ice Buildin Use Hot Start Load Limit Setpoint From: HI STP Menu 35 SETPOINTS Use Capacity Limit Setpoint From: No Source Selected 35 SETPOINTS
Solution Setpoint 44 deg F 34 SETPOINTS
F 34 SETPOINTS F 34 SETPOINTS F 34 SETPOINTS
Terminate Temperature 27 deg F 34 SETPOINTS
F 34 SETPOINTS F 34 SETPOINTS
Solution Setpoint From: HI STP Menu 34 SETPOINTS
Terminate Setpoint From: HI STP Menu 34 SETPOINTS
Information format
Display Text in En Display Units in En Unit Control Local 23 SETUP Unit Address
General Unit Functions Setup
Delay unit Start 0 Seconds 23 SETUP Demand Limit Definition None 24 SETUP Hot Gas Bypass Function Disabled 24 SETUP Hot Gas Bypass Max Run Time 30 Minutes 24 SETUP Hot Start Time In terval 60 Minutes 24 SETUP Hot Operation Response Option 50% Capacity
Pumpdown Function Disabled 24 SETUP Compressor Lead/La Default Chiller Solution Pump Mode Auto 24 SETUP Evaporator Solution Pump Off Delay Time 30 Seconds 25 SETUP Loop Stabilization Time 120 Seconds 25 SETUP Low Ambient Compressor Lockout Enabled 25 SETUP Leavin Chiller Application Comfort 25 SETUP Evaporator Solution Flow Switch Provin OA Temp Reset Type: Start Temp 70 de OA Temp Reset Type: End Temp 50 de OA Temp Reset Type: Max Amount of Reset 5 de Zone Temp Reset Type: Start Temp 78 de Zone Temp Reset Type: End Temp 75 de Zone Temp Reset Type: Max Amount of Reset 5 de Enterin Enterin Enterin
Solution Reset Type None 25 SETUP
Solution Temp Reset Type: Start Temp 45 deg F 25 SETUP Solution Temp Reset Type: End Temp 40 deg F 25 SETUP Solution Temp Reset Type: Max Amount 5 deg F 25 SETUP
Function Disabled 24 SETUP
lish Language 23 SETUP
lish 23 SETUP
23 SETUP
(Auto Reset Dia
Disabled 25 SETUP
.) 24 SETUP
F 25 SETUP F 25 SETUP
F 25 SETUP
F 25 SETUP F 25 SETUP
F 25 SETUP
12
Page 13
General Information
Factory Presets (Continued)
Factory Preset Changed See page... To adjust
To to adjust Press....
Ice Building C ontrol Fuctions
Ice Building Function Disabled 26 SETUP Ice Building Mode One Time 26 SETUP Ice Rebuild Delay Time 360 Minutes 26 SETUP
GBAS 0-5 VDC Module I/O Assignments
GBAS (0-5 VDC) Analog Input 1 Assignment Not Assigned 27 SETUP GBAS (0-5 VDC) Analog Input 2 Assignment Not Assigned 27 SETUP GBAS (0-5 VDC) Analog Input 3 Assignment Not Assigned 27 SETUP GBAS (0-5 VDC) Analog Input 4 Assignment Not Assigned 27 SETUP GBAS (0-5 VDC) Binary Output 1 Definition Indicate any comp
is running 28 SETUP GBAS 0-5 V Output 1 Alarm Assignments Any active diagnostic 28 SETUP GBAS (0-5 VDC) Binary Output 2 Definition Indicate selected
diagnostics 29 SETUP
GBAS 0-5 V Output 2 Alarm Assignments Comp protection LPC
Open C kt 1 29 SETUP
Comp protection LPC
Open Ckt 2 (40-60 Ton) 29 SETUP
Compressor Trip Ckt 1 29 SETUP Compressor Trip Ckt 2
(40 - 60 Ton) 29 SETUP Comp Contactor Fail Ckt 1 29 SETUP Comp Contactor Fail Ckt 2
(40 - 60 Ton) 29 SETUP
Low Press Control
Open - Ckt 1 29 SETUP
Low Press Control
Open - Ckt 2 (40-60 Ton) 29 SETUP
GBAS (0-5 VDC) Binary Output 3 Definition Indicate Unit at
Max capacity 29 SETUP
GBAS (0-5 VDC) Output 3 Alarm Assignments Any active diagnostic 29 SETUP GBAS (0-5 VDC) Binary Output 4 Definition Indicate selected
diag alarms 29 SETUP GBAS (0-5 VDC) Output 4 Alarm Assignments Any active diagnostic 29 SETUP GBAS (0-5 VDC) Binary Output 5 Definition Indicate selected
diag alarms 29 SETUP GBAS (0-5 VDC) Output 5 Alarm Assignments Any active diagnostic 29 SETUP
GBAS 0-10 VDC Module I/O Ass ignments
GBAS (0-10 VDC) Analog Input 1 Assignment Not Assigned 29 SETUP GBAS (0-10 VDC) Analog Input 2 Assignment Not Assigned 29 SETUP GBAS (0-10 VDC) Analog Input 3 Assignment Not Assigned 29 SETUP GBAS (0-10 VDC) Analog Input 4 Assignment Not Assigned 29 SETUP GBAS (0-10 VDC) Binary Output Definition Indicate selected
GBAS (0-10 VDC) Output Alarm Assignments Any active diagnostic 30 SETUP GBAS (0-10 VDC) Analog Output 1 Assignment Leaving solution temp 30 SETUP GBAS (0-10 VDC) Analog Output 2 Assignment Entering solution temp 30 SETUP GBAS (0-10 VDC) Analog Output 3 Assignment Active cooling capacity 30 SETUP GBAS (0-10 VDC) Analog Output 4 Assignment Outside air temperature 30 SETUP
CGM alarm output de finitions
diag alarms 29 SETUP
Any Active Diagnostic 30 SETUP
13
Page 14
General Information
S
C
Factory Presets (Continued)
Factory Preset Changed See page... To adjust
To to adjust Press....
Actuator Setup Definitions
Number 1 Low Ambient Maximum Stroke 30 seconds 31 SETUP Number 1 Low Ambient Minimum Voltage 2.0v 31 SETUP Number 1 Low Ambient Maximum Voltage 10.0v 31 SETUP Number 1 Low Ambient Acting Direct 31 SETUP Number 2 Low Ambient Maximum Stroke 30 seconds 31 SETUP Number 2 Low Ambient Minimum Voltage 2.0v 31 SETUP Number 2 Low Ambient Maximum Voltage 10.0v 31 SETUP Number 2 Low Ambient Acting Direct 31 SETUP Ckt 1 Suction Line Pressure Transducer -­ voltage at 0 PSIG 0.118 V 32 SETUP Ckt 1 Suction Line Pressure Transducer -­ voltage at 100 PSIG 4.847 V 32 SETUP Ckt 2 Suction Line Pressure Transducer -­ voltage at 0 PSIG 0.118 V 32 SETUP Ckt 2 Suction Line Pressure Transducer -­ voltage at 100 PSIG 4.847 V 32 SETUP Ckt 1 Liquid Line Pressure Transducer -­ voltage at 0 PSIG 0.118 V 32 SETUP Ckt 1 Liquid Line Pressure Transducer -­ voltage at 400 PSIG 4.847 V 32 SETUP Ckt 2 Liquid Line Pressure Transducer -­ voltage at 0 PSIG 0.118 V 32 SETUP Ckt 2 Liquid Line Pressure Transducer -­ voltage at 400 PSIG 4.847 V 32 SETUP
Head Pressure Control Setup
Saturated condenser Temp Control Band (Lower Limit) 85 deg F 26 SETUP Saturated condenser Temp Control Band (Upper Limit) 125 deg F 26 SETUP Saturated condenser Temp Control Band (Temporary Low Limit Suppression) 10 deg F 27 SETUP Saturated condenser Temp (Efficiency Check Point) 110 deg F 27 SETUP Saturated condenser Temp (Low Ambient Control Point) 100 deg F 27 SETUP
aturated condenser Temp (Low Ambient
ontrol Deadband) Saturated condenser Temp (OA Temp Suppression Setpoint)
4.0 deg F 27 SETUP
40 deg F 27 SETUP
14
Page 15
General Information
Password Protected Screens
Some of the operating displays on the Human Interface LCD screen are intended to be accessed by qualified users only, and require a password to change. The following screens display the various programming sections that require a password in order to view or to modify the preset operating parameters. The password for each screen is a different series of + (Plus) or - (Minus) key strokes in a predefined sequence. Shown below are the password protected screens, and the passwords for accessing them.
The following screens display the various programming sections that require a specific PASSWORD to be entered by a qualified operator in order to view or to modify the operating parameters.
The following screen will appear if the PASSWORD is not entered within approximately 15 seconds.
Password Entry Time Limit Exceeded
1. Press the NEXT key until the following screen is displayed.
Configuration is Password Protected
Please Enter Pasword:
2. Press the + or - keys in this sequence ( + - - - ) to access this restricted screen.
3. Press the ENTER key to confirm the password and enter the menu.
4. Press the NEXT key until the following screen is displayed.
Dia gnostic Re set is Password Pr otected
Please Enter Pasword:
1. Press the + or - keys in this sequence ( - + + ) to access this restricted screen.
2. Press the ENTER key to confirm the password and Lock the definitions.
3. Press the NEXT key until the following screen is displayed.
Diagnostic Log is Password Protected
Please Enter Pasword: __________
1. Press the + or - keys in this sequence ( - + + -) to access thi s restricted screen.
2. Press the ENTER key to confirm the password and Lock the definitions.
3. Press the NEXT key until the following screen is displayed.
15
Page 16
System Operating Status
See "General Status" Display Description
g
g
g
g
Active Ice Build Terminate STP = 0 - 99 F
g
g
g
g
y
STATUS Menu
The STATUS menu is used to view various operating condi­tions such as temperatures and humidity levels. It’s used to view unit component status such as fan, compressor, heater, and economizer operation, as well as setpoint sta­tus.
Press the STATUS key to enter into the status menu. The "STATUS MODE" will automatically return to the power up screen after 30 minutes, if no keys are pressed.
Cool 0 Solution Pump Off Standb
1. Press the NEXT key to scroll forward thro ugh the status screens.
2. Press the PREVIOUS key to scroll backwards to view previously displayed status screens.
3. Press the + (Plus) key while viewin that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus.
Active Leaving Solution Setpoint 55.0 F Temp: Entering 55.0 F Leaving 50.0 F
This screen is displayed when the unit is in Ice Buildin
Active Ice Build Ter mina te STP 5 5.0 F Temp: Entering 55.0 F Leaving 50.0 F
Diagnostics
any status screen to add
OR
.
The screens shown in this section are for example only. Pressing the + (Plus) key while viewing any of the status display screens will add that screen to the Custom menu. When a status screen is displayed for 30 minutes without a key being pressed, the LCD screen will revert to the general operating status display. If this happens, press the STATUS key again to return to the status menu. The following are examples of status screens that may be viewed by pressing the STATUS key.
Used on Units: Possible Values:
Used on Units: Possible Values:
Enteri n Leavin
Used on Units: Possible Values:
Enteri ng = 0 - 99.9 F Leavin
All Units
All Units
Active Solution Setpoint = 0 - 99 F
= 0 - 99.9 F
= 0 - 99.9 F
All Units
= 0 - 99.9 F
Compressor Status Submenu Press ENTER to View Data in This Submenu
1. Press the ENTER key to advance to the followin
2. Press the NEXT key to bypass this menu and advance to "General Status Submenu"
screen.
Note:
The ran are 0 to 99.9 F. "ERR" will appear if the temperature is out of ran
Used on Units:
e for all temperature inputs
e.
All Units
16
Page 17
System Operating Status
K3 - On, Off, Locked,
/
Suction range 0 - 100 PSIG
Comp Off
q
p
The following screens are displayed for 20 through 60 Ton units.
Compressor Relay K11 Off Enabled
1. Press the NEXT key until the following screen is displayed. K11 - On, Off, Locked, or
Compressor Relay K12 Off Enabled
1. Press the NEXT key until the following screen is displayed.
The following screens are displayed for 40 through 60 Ton units.
Compressor Relay K3 Off Enabled
1. Press the NEXT key until the following screen is displayed.
Compressor Relay K4 Off Enabled
Disabled By:
Bad Cond Temp Sensor Hot Start Operation Bad Ent Soln Sensor Low Ambient Lockout Bad Leav Soln Sensor Low Leav Soln Cutout Compressor Protection Low Pressure Cutout Compressor Protect LPC LPC Delay Contactor Failure Minimum Off Time Demand/Capacity Limit Over/Under Voltage Evap Flow Protection Phase Loss/Reversal Evap Limit Control Tracer Lockout
Used on Units: Possible Values:
K4 - On, Off, L ocked,
K12 - On , Off, Locked
20 thru 60 Ton Units
1. Press the NEXT key until the following screen is displayed.
Compre ssor Module Ckt 1 Satura ted Conde nsor Temperature 8 1.0 F
1. Press the NEXT key until the following screen is displayed. The following three screens are applicable when Superheat Subcool Module is installed.
Refrigerant Ckt 1 - Temperature Data Suction 75 .0 F Sat Liquid 81.0 F
1. Press the NEXT key until the following screen is displayed.
Refrigerant Ckt 1 - Pressure Data Suction 72 PSIG Li
1. Press the NEXT key until the following screen is displayed. Comp Off
Refrigerant Circuit 1 Su
erhea t 28.0 F Subcooling 18.0 F
1. Press the NEXT key until the following screen is displayed.
The following screens are displayed for 40 through 60 Ton units.
Compressor Module Ckt 2 Saturated Condenser Temperature 97.0 F
uid 265 PSIG
Used on Units: Possible Values:
Used on Units: Possible Values:
Used on Units: Possible Values:
Liquid range 0 - 400 PSIG
Used on Units: Possible Values:
Used on Units: Possible Values:
All Units
-40 to 200 F
With superheat/subcool module
-40 to 200 F
With superheat/subcool module
With superheat/subcool module
0 - 99.9 F
40 Thru 60 Ton Units
-40 to 200 F
17
Page 18
1. Press the NEXT key until the following screen is displayed.
/
Suction range 0 - 100 PSIG
40 Thru 60 Ton Units
The following three screens are applicable when Superheat Subcool Module is installed.
Refrigerant Ckt 2 - Temperature Data Suction 72.0 F Sat Liquid 9 7.0 F
1. Press the NEXT key until the following screen is displayed.
Refrigerant Ckt 2 - Pressure Data Suction 65 PSIG Liquid 251 PSIG
1. Press the NEXT key until the following screen is displayed.
Refrigerant C ircuit 2 Superheat 2 8.0 F Subcooling 18 .0 F
1. Press the NEXT key until the following screen is displayed.
Ckt 1 Liquid Line Solenoid Valve: OPEN
System Operating Status
Used on Units: Possible Values:
Used on Units: Possible Values:
Liquid range 0 - 400 PSIG Comp Off
Used on Units: Possible Values:
Comp Off
Used on Units: Possible Values:
40-60 Ton Units with superheat/subcool module
-40 to 200 F
40-60 Ton Units with superheat/subcool module
40-60 Ton Units with superheat/subcool module
0 - 99.9 F
20, 25 & 30 Ton Units
Open, Closed
The following screen is displayed for 40 through 60 Ton units.
OR
Ckt 1 Liquid Line Sole noid Valve: OPEN Ckt 2 Liquid Line Sole noid Valve: CLOSED
1. Press the NEXT key until the following screen is displayed.
Compressor 1A Phase Currents - Amps Phase A 86 Phase B 84
1. Press the NEXT key until the following screen is displayed.
Compressor 1B Phase Currents - Amps Phase A 81 Phase C 78
1. Press the NEXT key until the following screen is displayed. The following screens are displayed for 40 through 60 Ton units.
Compressor 2A Phase Currents - Amps Phase B 88 Phase C 90
1. Press the NEXT key until the following screen is displayed.
Compressor 2B Phase Currents - Amps Phase A 93 Phase C 89
1. Press the NEXT key until the following screen is displayed.
End of Submenu (NEXT) to R e-enter STATU S
2. Pressing the NEXT key will display the beginning of the Submenu.
3. Press the NEXT key again to advance to the following screen.
Used on Units: Possible Values:
Used on Units: Possible Values:
Used on Units: Possible Values:
Used on Units: Possible Values:
Used on Units: Possible Values:
Open, Closed
All Units with Current Sensing Module
0 - 255
All Units with Current Sensing Module
0 - 255
40-60 Ton Units with Current Sensing Module
0 - 255
40-60 Ton Units with Current Sensing Module
0 - 255
General System Status Submenu Press ENTER to View Data in This Submenu
1. Press the ENTER key until the following screen is displayed.
2. Press the NEXT key to bypass this menu and advance to "Controlling Setpoint Status Submenu"
CGM Evap Solution Pump Relay: OFF Evap Soln Flow Switch Proving: FLOW
1. Press the NEXT key until the following screen is displayed.
Used on Units: Possible Values:
Evap Soln Flow Switch Proving = Flow, No Flow
All Units
CGM Evap So lu tion Pump Relay = On, Off
18
Page 19
This screen is displayed on units with Brazed Plate.
Used on Units:
g
g
Used on Units:
With Ice Building Control
g
g
Used on Units:
g
g
g
MCM He at Tape Control Relay: OFF
1. Press the NEXT key until the followin
This screen is displayed when Hot Gas Bypass is installed.
CGM Hot Gas Bypass Control Relay: OFF
screen is displayed.
System Operating Status
Possible Values:
Used on Units: Possible Values:
All Brazed Plate Units
On, Off
With Hot Gas Bypass option
On, Off
1. Press the NEXT key until the followin
CGM Ice Building Control R elay: ON
1. Press the NEXT key until the followin
This screen is displayed when Leavin is selected.
Setpoint Value Measured CGM Ext Leaving Soln STP Input is 4 4.0 F
1. Press the NEXT key until the followin
End Of Sub-Menu (NEXT) To Re-e nter STA TUS
2. Pressin the Submenu.
3. Press the NEXT key a
the NEXT key will display the beginning of
ain to advance to the following screen.
screen is displayed.
screen is displayed.
Solution Setpoint Source
screen is displayed.
Controlling Setpoint Status Submenu Press ENTER to View Data in This Submenu
1. Press the ENTER key until the following screen is displayed.
2. Press the NEXT key to bypass this menu and advance to "Temperature Input Status Submenu"
Active Leaving Solution Setpoint From EXT LEAVING SOLN STP INPUT is 55.0 F
1. Press the NEXT key until the following screen is displayed. This screen is displayed when Ice Building is enabled.
Active Ice Build Terminate Setpoint From HUMAN INTERFACE STP MENU is 33.0 F
Possible Values:
Source se le cted
Possible Values:
Used on Units: Possible Values:
On, Off
With CGM Ext Leaving Soln Setpoint
0 - 99
All Units
Human Interface STP Menu, Ext Leaving Soln STP Input, GBAS 0-10 VDC Module, GBAS 0-5 VDC Module, BAS/NETWORK Setpoi nt Range = 0 - 99.9 F
Used on Units: Possible Values:
With Ice Building Option
Human Interface STP Menu, Ext Leaving Soln STP Input, GBAS 0-10 VDC Module, GBAS 0-5 VDC Module, BAS/NETWORK (Tracer) (TCI only) Setpoi nt Range = 0 - 99.9 F
19
Page 20
1. Press the NEXT key until the following screen is displayed.
Active Hot Start Load Limit Setpt From HUMAN INTERFACE STP MENU is 78.0 F
1. Press the NEXT key until the following screen is displayed.
Activ e Capacity Limit Setpoint Fr om HUMAN INTERFACE STP MENU is 63 %
1. Press the NEXT key until the following screen is displayed.
End of Submenu (NEXT) to Re-e nter STATUS
2. Pressing the NEXT key will display the beginning of the Submenu.
3. Press the NEXT key again to advance to the following screen.
Temperature Input Status Submenu Press ENTER to View Data in This Submenu
System Operating Status
Used on Units: Possible Values:
GBAS 0-10 VDC Module, GBAS 0-5 VDC Module, Setpoint Range = 0 - 99.9 F
Used on Units: Possible Values:
GBAS 0-10 VDC Module, GBAS 0-5 VDC Module, BAS/NETWORK Setpoint Range = 0 - 99.9 F Blank
All Units
Human Interface STP Menu,
With GBAS 5V or GBAS 10V or TCI or LCI
No Source Selected,
1. Press the ENTER key until the following screen is displayed.
2. Press the NEXT key to bypass this menu and advance to "Misc Input Status Submenu"
Temp Measur ed By Sensor Connected To CGM Entering Soln Temp Input 55 F
1. Press the NEXT key until the following screen is displayed.
Temp Measur ed By Sensor Connec te d To CGM Leaving Soln Temp Input 50.0 F
1. Press the NEXT key until the following screen is displayed.
Temp Measured By Sensor Connected To CGM Outside Air Temp Input 86.0 F
1. Press the NEXT key until the following screen is displayed.
Compressor Module Ckt 1 Saturated Condenser Temperature 81.0 F
1. Press the NEXT key until the following screen is displayed.
Refrigerant Ckt 1 - Temperature Data Suction 75.0 F Sat Liquid 81.0 F
Used on Units: Possible Values:
Used on Units: Possible Values:
Used on Units: Possible Values:
Used on Units: Possible Values:
Used on Units: Possible Values:
All Units
All Units
All Units
All Units
With Superheat/Subcooling installed
-40.0 to 200 F
-40.0 to 200 F
-40.0 to 200 F
-40.0 to 200 F
-40.0 to 200 F
1. Press the NEXT key until the following screen is displayed. The following screens are displayed for 40 through 60 Ton units.
Compr essor Module Ckt 2 Saturated Condenser Temperature 97.0 F
20
Used on Units: Possible Values:
40 through 60 Ton
-40.0 to 200 F
Page 21
System Operating Status
With Ice Building Control Option
Suction =
Suction =
Refrigerant Ckt 2 - Temperature Data Suction 72.0 F Sat Liquid 97.0 F
1. Press the NEXT key until the following screen is displayed.
Temp Measured By Sensor Connected To CGM Zone Temp Input 75.0 F
1. Press the NEXT key until the following screen is displayed.
Temp Measured By Sensor Connected To CGM ICS Temp Input 62.0 F
1. Press the NEXT key until the following screen is displayed.
End of Submenu (NEXT) to Re-enter STATUS
2. Pressing the NEXT key will display the beginning of the Submenu.
3. Press the NEXT key again to advance to the following screen.
Misc Input Status Submenu Press ENTER to View Data in This Submenu
1. Press the ENTER key until the following screen is displayed.
2. Press the NEXT key to bypass this menu and advance to "GBAS 0-5VDC Module Status Submenu"
Used on Units:
40-60 Ton with Superheat/Subcooling
Module installed
Possible Values:
Used on Units: Possible Values:
Used on Units: Possible Values:
-40.0 to 200 F
All Units
-40.0 to 200 F
With TCI Module Installed
-40.0 to 200 F
CGM Ice Build Command Input: OFF
1. Press the NEXT key until the following screen is displayed.
CGM Evap Soln Flow Switch Input: FLOW
1. Press the NEXT key until the following screen is displayed.
Refrigerant Ckt 1 - Pressure Data Suction 72 PSIG Liquid 265 PSIG
1. Press the NEXT key until the following screen is displayed.
Refrigerant Ckt 2 - Pressure Data Suction 65 PSIG Liquid 251 PSIG
1. Press the NEXT key until the following screen is displayed.
Compressor 1A Phase Currents - Amps Phase A 86 Phase B 84
1. Press the NEXT key until the following screen is displayed.
Compressor 1B Phase Currents - Amps Phase A 81 Phase C 78
Used on Units: Possible Values:
Used on Units: Possible Values:
Used on Units: Possible Values:
Liquid = 0.0 to 400.0 PSIG Comp Off
Used on Units: Possible Values:
Liquid = 0.0 to 400.0 PSIG Comp Off
Used on Units: With Possible Values:
Used on Units: With Possible Values:
Off, Make Ice
All Units
Flo w, No Flo w
All Units with Superheat/Subcooling
0.0 to 100.0 PSIG
40 - 60 Ton Units with Superheat/Cooling
0.0 to 100.0 PSIG
Current Sensing Module
0 to 255
Current Sensing Module
0 to 255
21
Page 22
System Operating Status
Output = On, Off
With GBAS 0-10 VDC Modul e
g
1. Press the NEXT key until the following screen is displayed.
Compressor 2A Phase Currents - Amps Phase B 88 Phase C 90
1. Press the NEXT key until the following screen is displayed.
Compressor 2B Phase Currents - Amps Phase A 93 Phase C 89
1. Press the NEXT key until the following screen is displayed.
End of Submenu ( NEXT) to Re-enter STATUS
2. Pressing the NEXT key will display the beginning of the Submenu.
3. Press the NEXT key again to advance to the following screen.
This screen is displayed when GBAS 0-5 VDC Module is installed
GBAS 0-5VDC Module Status Submenu Press ENTER to View Data in This Submenu
1. Press the ENTER key until the following screen is displayed.
2. Press the NEXT key to bypass this menu and advance to "GBAS 0-10VDC Module Status Submenu"
GBAS 0-5VDC Analog Input 1 0.00 VDC Assigned: NOT ASSIGNED
3. Press the NEXT key to display Generic BAS Analog Input Leaving Solution Setpoint screens 2, 3, & 4. Ice Build Terminate Setpoint
4. Press the NEXT key to advance to the following screen. Hot Start Load Li mit Setpoint
Used on Units: Possible Values:
Used on Units: Possible Values:
Used on Units: Possible Values:
Assignment = Not Assigned
Capacity Limit Setpoint
With Current Sensing Module on 40-60 Ton
0 to 255
With Current Sensing Module on 40-60 Ton
0 to 255
With GBAS 0-5VDC Module
Input = 0.00 to 5.00 VDC
GBAS (0-5VDC) Demand Limit Input Status OPEN
1. Press the NEXT key until the following screen is displayed.
GBAS (0-5VDC) Binary Output 1 OFF Assigned: OUTPUT IS NOT ASSIGNED
2. Press the NEXT key to display Generic BAS Binary Output Indicate any comp is running screens 2, 3, 4 & 5. Indi cate unit at max capacity
3. Press the NEXT key to advance to the following screen. Indicate selected di ag alarms
End of Submenu ( NEXT) to Re-enter STATUS
1. Pressing the NEXT key will display the beginning of the Submenu.
2. Press the NEXT key again to advance to the following screen.
This screen is displayed when GBAS 0-10 VDC Module is installed
GBAS 0-10VDC Module Status Submenu Press ENTER to View Data in This Submenu
1. Press the ENTER key until the following screen is displayed.
2. Press the NEXT key to bypass this menu and advance to "General Status" Display Screen.
GBAS 0-10VDC Analog Input 1 0.00 VDC Assi
3. Press the NEXT key to display Generic BAS Analog Input Leaving Solution Setpoint screens 2, 3 & 4. Ice Build Terminate Setpoint
4. Press the NEXT key to advance to the following screen. Hot Start Load Limit Setpoint
ned: NOT ASSIGNED
Used on Units: Possible Values:
Used on Units: Possible Values:
Assignment = Output Is Not Assigned
Used on Units: Possible Values:
Assignment = Output Is Not Assigned
Capacity Limit Setpoint
With GBAS 0-5VDC Module
Open, Closed
With GBAS 0-5VDC Module
Output = 0.00 - 10.00 VDC
22
Page 23
System Operating Status
Used on Units:
With GBAS 0-10 VDC Module
g
Used on Units:
With GBAS 0-10 VDC Module
g
g
g
Used on Units:
With GBAS 0-10 VDC Module
g
g
g
g
g
g
Open
g
GBAS (0-10VDC) Demand Limit Input Status
1. Press the NEXT key until the followin
GBAS (0-10VDC) Binary Output OFF
ned: OUTPUT IS NOT ASSIGNED
Assi
1. Press the NEXT key until the following screen is displayed.
GBAS 0-10VDC Analog Output 1 0.0 VDC Assigned: NOT ASSIGNED
Assi
nment = Leaving solution temperature Assignment = Ckt1 liquid line pressure Enterin Ckt1 saturated condenser temp Ckt1 sat liquid temperature Ckt2 saturated condenser temp Ckt2 sat liquid temperature Ckt1 suction temperature ICS Defined temperature Ckt2 suction temperature Outsi de air temperature Ckt1 suction pressure Active Cooli n Ckt2 suction pressure
2. Press the NEXT key to display Generic BAS Analo screens 2, 3 & 4.
3. Press the NEXT key to advance to the followin
End of Submenu (NEXT) to Re-enter STATUS
screen is displayed.
solution temperature Ckt2 liquid line pressure
Output
screen.
Possible Values:
Possible Values:
Assi Indicate selected dia Indicate unit at max capacity Indicate any comp is runnin
Possible Values:
Open, Closed
Output = On, Off
nment = Output Is Not Assigned
alarms
0.0 to 10.0 VDC
Capacity
4. Pressin the Submenu.
5. Press the AUTO or STOP key to return to the top level status information.
the NEXT key will display the beginning of
23
Page 24
System Programming SETUP
After the unit is installed, the CGM must be programmed with certain setup information (chilled solution setpoints, ON and OFF times, system defaults, setpoint sources, etc...) in order to operate and function properly. The data necessary for unit operation will vary depending on certain factors such as unit size, type, and installed options.
This section of the manual provides step by step instruc­tions for programming this information. Also provided are in­structions for checking unit operating status, accessing and clearing diagnostics, and performing service tests.
Some of the displays shown in this manual may not appear on the Human Interface (HI) LCD screen during program­ing. Only the applicable screens for the specific unit options and operating parameters will be displayed.
Start with the first setup screen in the SETUP menu and program the necessary information by completing the steps located below each illustrated window. Information that per­tains to when the screens are applicable, the factory preset values, and the possible values that may be designated is located to the right of each programmable screen.
Ignore the steps that do not apply to your unit and applica­tion, and move on to the next applicable set of instructions in the manual. Continue this process until all applicable screens are programmed with the required information.
SETUP Menu
The setup menu is used to input initial operating information such as control parameters, functions enable/disable, text dis­play (language), temperature display (C or F), and system tuning parameters. When a setup screen is displayed for 30 min­utes without a key being pressed, the LCD screen will revert to the appropriate power-up display. If this happens, press the SETUP key again to return to the setup menu.
1. Press the SETUP key to display the fol lowing screen.
Display Text in ENGLISH LANGUAGE
Display Units in ENGLISH
2. Press the + or - key until the proper "language" is displayed.
3. Press the ENTER key to confirm this choice.
4. Press the NEXT key to advance the cursor to the "Units"
5. Press the + or - key until the proper "language" is displayed.
6. Press the ENTER key to confirm this choice.
Used on Units: Possible Values:
Units = SI, English
All
Text = English, French, Spanish
7. Press the NEXT key until the following screen is displayed.
Unit contr ol: LOCAL Unit Address 4 9
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor to the "Address" (TCI only)
4. Press the + or - key until the proper value is displayed. (TCI only)
5. Press the ENTER key to confirm this choice. (TCI only)
6. Press the NEXT key until the following screen is displayed.
Genera l Unit Functions Setup Submenu Press ENTER to Review or Adjust
1.To view the factory preset or to modified the factory presets to meet specific application requirements, press the ENTER key to advance to the following screens. If no adjustments are required, press the NEXT key to advance to the "Ice Building Control Functions Submenu".
Reduce Multi-Unit Startup Power Demand. After Power-Up, Dela y Unit Star t 0 Sec
2. Press the + or - key until the proper value is displayed.
3. Press the ENTER key to confirm this choice.
4. Press the NEXT key until the following screen is displayed.
Used on Units: Possible Values: Addres s:
Used on Units: Possible Values:
All Units when TCI or LCI installed
All Units
Control = Local, BAS/NETWORK
33 to 63 (TCI only)
0 to 255 sec
24
Page 25
System Programming SETUP
,
Dema nd Limit De finition: NON E Reduce cooling capacity by this amount
1. Press the + or - key until the proper value is displayed. 25% - 2 Ckt Only
2. Press the ENTER key to confirm this choice. 50% - All Units
3. Press the NEXT key until the following screen is displayed. 75% - 2 Ckt Only
Compressor Lead/Lag Function: DISABLED Stage C omp(s) Up/Down in Fixed Sequence
OR Note:
Compressor Lead/Lag Function: ENABLED 1st On = Least Starts, 1st Off = Most Runtime
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Hot Gas Bypass Function: DISABLED Provides Cooling Level Less Than Cool 1
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice. Lead\Lag is Enabled.
3. Press the NEXT key until the following screen is displayed.
Hot Gas Bypass Max Run Time 30 Min Max HGBP Duration Until Shut Off Comp
Used on Units:
GBAS10V or TCI
Possible Values:
100% - All Units
Used on Units: Possible Values:
Lead\Lag can not be Enabled if Hot Gas
Bypass is Enabled.
Used on Units:
installed
Possible Values: Note:
Hot Gas Bypass can not be Enabled if
Used on Units: Possible Values:
All Units with GBAS5V,
None - All Units
All Units
Enabled, Disabled
With Ho t Gas Byp ass Option
Enabled, Disabled
With Ho t Gas Byp ass Option i nstalled
10 to 120 minutes
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Capacity=50% if LST exceeds Hot Strt STP During Hot Start Time Interval: 60 Min
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Hot Operation Response Option: 50% CAPACITY PER CKT
1. Press the + or - key until the proper value is displayed. Allow normal operation
2. Press the ENTER key to confirm this choice. (Info Reset Diag)
3. Press the NEXT key until the following screen is displayed. Shut off co mpressors
Pumpdown Function: DISABLED
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Default Chiller Solution Pump Mode : ON Pump Always ON Except for Emergency STOP
Default Chiller Solution Pump Mode : AUTO Turn Pump ON As Requested By CGM Module
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
AUTO RESET DIAG
OR
Used on Units: Possible Values:
Used on Units: Possible Values:
(Auto Reset Dia g)
(Manu al Reset Diag)
Used on Units: Possible Values:
Used on Units: Possible Values:
All Units
10 to 120 minutes
All Units
50% Capacity per ckt
All Units
Enable, Disable
All Units
On, Auto
25
Page 26
System Programming SETUP
g
g
All Units with Leaving Solution Reset
g
g
Start Temp OA: 46 - 125 F
Zone: 67 - 81 F
Zone: 66 - 80 F
g
g
g
pp
Evap Soln Pump Off Dela y time 30 Sec Delay Pum p OFF Request By This Amount
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Loop Stabilization Time: 120 Sec Run Pump To A llow Soln Te mp To Stabilize
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Low Ambient Compressor Lockout: ENABLED Use Low Ambient Compressor Lockout STP
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Leaving Solution Reset Type: NONE - NO RESET APPLIED
1. Press the + or - key until the proper value is displayed. Zone Temp Reset
2. Press the ENTER key to confirm this choice. Enterin
3. Press the NEXT key until the following screen is displayed.
The followin ENT Soln Reset is selected.
Rese t Type: Outside Air Temp Reset Start Tem p 70.0 F End Temp 50.0 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor to the "End Temp" Reset Type: Outside Air Temp Reset
4. Press the + or - key until the proper value is displayed. Zone Temp Reset
5. Press the ENTER key to confirm this choice. Enterin
6. Press the NEXT key until the followin
Rese t Type: Outside Air Temp Reset Maximum A mount of Reset A
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice. ENT Soln Temp Reset: 5 - 79 F
3. Press the NEXT key until the followin
Select Type of Cooling Control Based On Chille r Application: PROCESS COOLING
two screens will display when either OA, Zone, or
screen is displayed.
lied 5 .0 F
screen is displayed. Max Amount (Zone, OA, ENT Soln Temp Reset): 3 - 16 F
Used on Units: Possible Values:
Used on Units: Possible Values:
Used on Units: Possible Values:
Used on Units: Possible Values:
Outside Air Temp Reset
Used on Units: Possible Values:
ENT Soln Temp Reset: 6 - 80 F End Temp OA: 45 - 124 F
All Units
30 to 600 seconds
All Units
30 to 255 seconds
All Units
Enable, Disable
All Units
None - No Reset Applied
Solutio n Temp Reset
Soln Temp Reset
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
26
Used on Units: Possible Values:
All Units
Comfort Coolin
, Process Coolin
Page 27
System Programming SETUP
Enabled, Disabled
360 Min
j
g
pp
End of Submenu (NEXT) to Re-ente r SETUP
1. Pressing the NEXT key will display the beginning of the Submenu.
2. Press the NEXT key again to advance to the following screen. The following screens are displayed with Ice Buil ding Control Option.
Ice Building Cont rol Functions Submenu Press ENTER to Review or Ad
1. To view the factory preset or to modify the factory presets to meet specific appli cation requi rements, press the ENTER key to advance to the following screens. If no adjustments are required, press the NEXT key to advance to the "Ice Building Control Functions Submenu".
Ice Building Function: DISABLED Ice Buildin
2. Press the + or - key until the proper "Function" is displayed.
3. Press the ENTER key to confirm this choice.
4. Press the NEXT key to advance the cursor to the "Mode" Mode = One Time, Continuous
5. Press the + or - key until the proper value is displayed.
6. Press the ENTER key to confirm this choice.
7. Press the NEXT key until the following screen is displayed.
Interval Between Ice Building Cycles. Ice Rebuild Delay Time 360 Min
Mode: ONE TIME
ust
Used on Units: Possible Values:
Units with Ice Building Control Option
Function =
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
End of Submenu (NEXT) to Re-ente r SETUP
1. Pressing the NEXT key will display the beginning of the Submenu.
2. Press the NEXT key again to advance to the following screen.
Head Pressure Ctrl Setup Submenu Press ENTER to Review or Adjust
1.To view the factory preset or to modified the factory presets to meet specifi c application requi rements, press the ENTER key to advance to the following screens. If no adjustments are required, press the NEXT key to advance to the "GBAS 0-5 VDC Module I/O Assignments"
Sat urat ed Condens er Temp Control Ba nd Lower Limit 85 F U
2. Press the + or - key until the proper "LowerLimit" is displayed.
3. Press the ENTER key to confirm this choice.
4. Press the NEXT key to advance the cursor to the "Upper Limit" Upper Limit - 110 to 130 F
5. Press the + or - key until the proper value is displayed.
6. Press the ENTER key to confirm this choice.
7. Press the NEXT key until the following screen is displayed.
er Limit 125 F
Used on Units: Factory Preset: Possible Values:
Used on Units: Possible Values:
Units with Ice Building Control Option
All Units
30 to 1410 Minutes
Lower Limit - 70 to 90 F
27
Page 28
System Programming SETUP
(
Saturated Condens er Temp Control Band Temporary Low Limit Suppress ion 10 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Saturated Condenser Temperature Efficiency Check Point 110 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Saturated Condenser Temperature Low Ambient Control Point 100 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Saturated Condenser Temperature Low Ambient Control Deadband 4.0 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Saturated Condenser Temperature OA Temp Supression Setpoint 40 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
End of Submenu
NEXT) to Re-enter STATUS
Used on Units:
Possible Values:
Used on Units: Possible Values:
Used on Units: Possible Values:
Used on Units: Possible Values:
Used on Units: Possible Values:
All Uni ts
All Uni ts
All Uni ts
All Uni ts
All Uni ts
0 to 20 F
95 to 115 F
80 to 110 F
2.0 to 10.0 F
25 to 66 F, Disabled
1. Pressing the NEXT key will display the beginning of the Submenu.
2. Press the NEXT key again to advance to the following screen.
This screen is displayed when GBAS 0-5 VDC Module is installed
GBAS 0-5VDC Module I/O Assignment Press ENTER to Review or Adjust
1.To view the factory preset or to modified the factory presets to meet specific application requirements, press the ENTER key to advance to the following screens. If no adjustments are required, press the NEXT key to advance to "GBAS 0-10 VDC Module I/O Assignments"
GBAS (0-5VDC) Analog Input 1 Assignment NOT ASSIGNED
2. Press the + or - key until the proper value is displayed. Hot Start Load Limit Setpoint
3. Press the ENTER key to confirm this choice. Capaci ty Li mit Setpoint
4. Press the NEXT key to display Generic BAS Analog Input 2 screen.
5. Press the + or - key until the proper value is displayed.
6. Press the ENTER key to confirm each choice.
7. Repeat steps 1 - 4 to display Generic BAS Analog Input screens 2, 3 & 4.
8. Press the NEXT key to advance to the following screen.
Used on Units: Possible Values:
Ice Build Terminate Setpoint
With GBAS 0-5VDC Module
Leaving Solution Setpoint
28
Page 29
System Programming SETUP
With GBAS 0-5VDC Modul e
Not Assigned
k
j
GBAS (0-5VDC) Binary Output 1 Definition OUTPUT IS NOT ASSIGNED
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed. Indicate Selected Diag Alarms
The following screens will display if "Indicate selected diagnostics Indicate any comp is running alarms" is assigned to any of the 5 Binary Output Definitions.
GBAS (0-5VDC) Output 1 Alarm Assignments Press ENTER to Review or Ad
1.To view the factory preset or to modified the factory presets to meet specific application requirements, press the ENTER key. If no adjustments are required, press the NEXT
ey to advance to the following screen.
Assign Diag To GBAS (0-5V) Output #1 ? Any Active Diagnostic (No)
2. Press the + or - key until the proper value is displayed. If "YES"
is assigned to "Any Active Diagnostic", pressing the NEXT key will advance to the Binary Output 2 Definition screen. Assigning "NO" to the "Any Active Diagnostic" will advance to the selectable diagnostic screens.
3. Press the ENTER key to confirm each choice.
4. Press the NEXT key to scroll through each Active Diagnostic.
ust
Used on Units: Possible Values:
Indi cate Uni t at Max Capacity
Used on Units: Possible Values:
With GBAS 0-5VDC Modul e
Yes, No
Active Diagnostics
CGM ICS Temperature Sensor Fail Liquid Pressure Sensor Fail Ckt 1 CGM Module Data Storage Error Liquid Pressure Sensor Fail Ckt 2 CGM OA Temp Sensor Failure Low Ambient Evap Soln Pump Override CGM Zone Temp Sensor Failure Low Soln Cutout Temp (Man) Ckt 1 Pumpdown Terminated by Time Low Soln Cutout Temp (Auto) Ckt 2 Pumpdown Terminated by Time Low Press Control Open - Ckt 1 Comp Contactor Fail - Ckt 1 Low Press Control Open - Ckt 2 Comp Contactor Fail - Ckt 2 LSS Adjusted To Maintain Min Diff Compressor Trip - Ckt 1 EST/LST Low Temperature Indication
Compressor Trip - Ckt 2 MCM Communications Failure Comp Protection LPC Open - Ckt 1 Sat Liquid Temp Sensor Fail Ckt 1 Comp Protection LPC Open - Ckt 2 Sat Liquid Temp Sensor Fail Ckt 2 Cond Temp Sensor Failure - Ckt 1 SCM Communications Failure Cond Temp Sensor Failure - Ckt 2 Suction Pressure Sensor Fail Ckt 1 Current Sensor Module Comm Fail Suction Pressure Sensor Fail Ckt 2 Emergency Stop Suction Temp Sensor Failure - Ckt 1 Evap Enteri ng Soln Temp Sensor Fail Suction Temp Sensor Failure - Ckt 2 Evap Leaving Soln Temp Sensor Fail Superheat/Subcool Module Comm Fail Evap Solution Flow Proving Switch BAS Module Comm Failure Evap Solution Flow Loss BAS/NETWORK Comm Failure Extern Leaving Soln STP Input Fail Unit HI Communications Failure GBAS 0-5VDC Module Comm Failure GBAS 0-10VDC Module Comm Fail Hot Start Load Limit (Auto) Hot Start Load Limit (Info) Hot Start Load Limit (Man) Hot Start Load Limit STP Fail IBTS Adjusted To Maintain Min Diff Ice Build Terminate Setpoint Fail Leaving Solution Setpoint Fail
29
Page 30
1. Press the NEXT key to display Generic BAS Binary Output
With GBAS 0-5VDC Module
g
g
g
g
g
g
g
g
With GBAS 0-10VDC Module
g
g
g
g
g
g
j
2 Definition screen.
GBAS (0-5VDC) Binary Output 2 Definition
System Programming SETUP
2. Press the + or - key until the proper value is displayed.
3. Press the ENTER key to confirm this choice.
4. Press the NEXT key to display Generic BAS Binary Output Indicate Selected Di a 3 screen. Indicate Unit at Max Capacity
5. Press the + or - key until the proper value is displayed. Indicate any comp is runnin
6. Press the ENTER key to confirm each choice.
7. Repeat steps 1 - 4 to display Generic BAS Binary Output screens 3, 4 & 5.
8. Press the N EXT key to advance to the follow in
End of Submenu (NEXT) to Re-enter SETUP
1. Pressin the Submenu.
2. Press the NEXT key a
This screen is displayed when GBAS 0-10 VDC Module is installed
GBAS 0-10VDC Module I/O Assignments
1.To view the factory preset or to modified the factory presets to meet specific application requirements, press the ENTER key. If no adjustments are required, press the NEXT key to advance to the "CGM Alarm Output Diagnostic Assignments"
GBAS (0-10VDC) Analog Input 1 Assignment NOT A SSIGNED
2. Press the + or - key until the proper value is displayed.
3. Press the ENTER key to confirm this choice.
4. Press the NEXT key to display Generic BAS Analo 2 screen. Ice Build Terminate Setpoint
5. Press the + or - key until the proper value is displayed. Hot Start Load Limit Setpoint
6. Press the ENTER key to confirm each choice. Capacity Limit Setpoint
7. Repeat steps 1 - 4 to display Generic BAS Analo screens 2, 3 & 4.
8. Press the N EXT key to advance to the following scree n.
GBAS (0-10VDC ) Binary Output Definition OUTPUT IS NOT A SSIGNED
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the followin
The followin alarms" is assigned.
GBAS (0-10VDC) Output Alarm Assignments Press ENTER to Review or Ad
1.To view the factory preset or to modified the factory presets to meet specific application requirements, press the ENTER key to advance to the followin adjustments are required, press the NEXT key to advance to the GBAS Anal o
the NEXT key will display the beginning of
ain to advance to the following screen.
screen i s displayed . Indicate Sele cted Diag Alarms
screen will display if "Indicate selected dia
ust
screens. If no
Output Assignment screen.
screen.
Input Leaving Solutio n Setpoin t
Inp ut
Used on Units: Possible Values:
Used on Units: Possible Values:
Used on Units: Possible Values:
Indicate Unit at Max Capa city Indicate any comp is runnin
Outp ut is Not Assigned
Alarms
With GBAS 0-10VDC Module
Not Assi
Output is Not Assigned
ned
30
Page 31
System Programming SETUP
With GBAS 0-10VDC Module
With GBAS 0-10VDC Module
(
y
)
Assign D iag To GBAS (0-10V) Output ? Any Ac tive D iagnostic (No)
2. Press the + or - key until the proper value is displayed. If "YES" is assigned to "Any Active Diagnostic", pressing the NEXT key will advance to the "End of Submenu" screen. Assigning "NO" to the "Any Active Diagnostic" will advance to the selectable diagnostic screens. See 0-5 active diagnostics list.
3. Press the ENTER key to confirm each choice.
4. Press the NEXT key to scroll through each Active Diagnostic.
GBAS (0 -10VDC) Analog Output 1 Assignment NOT ASSIGN ED
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
Used on Units: Possible Values:
Used on Units:
Yes, No
GBAS (0-10VDC) Analog Output 2 Assignment NOT ASSIGN ED
1. Press the + or - key until the proper value is displayed. Ckt 1 Sat Cond Temp
2. Press the ENTER key to confirm this choice. Ckt 2 Sat Cond Temp
3. Press the NEXT key until the following screen is displayed. Ckt 1 Sat Liquid Temp
4. Press the NEXT key to display Generic BAS Analog Output Ckt 2 Sat Liquid Te mp 3 screen. Ckt 1 Suction Pressure
5. Press the + or - key until the proper value is displayed. Ckt 2 Suctio n Pressure
6. Press the ENTER key to confirm each choice. Ckt 1 Su ction Temperature
7. Repeat steps 1 - 4 to display Generic BAS Analog Output Ckt 2 Suction Temperature screens 3 & 4. Enteri ng So lution Temperature
8. Press the NEXT key to advance to the foll owing screen. ICS Define d Temperature
End of Submenu
1. Pressing the NEXT key will display the beginning of the Submenu.
2. Press the NEXT key again to advance to the following screen.
CGM Alarm Output D iagnostic Assignments
1.To view the factory preset or to modified the factory presets to meet specific application requirements, press the ENTER key to advance to the fo llowing scree ns. If no adjustments are required, press the NEXT key to advance to the "Device Characteristic Setup Definitions" screen.
Assign D iagnostic to CGM Alarm Output? An
Active Diagnostic (No
2. Press the + or - key until the proper value is displayed. If "YES" is assigned to "Any Active Diagnostic", pressing the NEXT key will advance to the "End of Submenu" screen. Assigning "NO" to the "Any Active Diagnostic" will advance to the selectable diagnostic screens. See the active diagnostics list in the GBAS 0-5V section.
3. Press the ENTER key to confirm this choice.
4. Press the NEXT key until the following screen is displayed.
1. Pressing the NEXT key will display the beginning of the Submenu.
2. Press the NEXT key again to advance to the following screen.
NEXT) to Re-enter SETUP
-
Possible Values:
Ckt 1 Liqui d Line Pressure
Ckt 2 Liqui d Line Pressure
Leaving Solution Temperature Outside Air Te mperature
Used on Units: Possible Values:
Active Cooling Capacity
All Units
Yes, No
31
Page 32
All Units
All Units
All Units
40 - 60 Ton Units
40 - 60 Ton Units
Device Characteristic Setup Definitions Press ENTER to Review or Adjust
1.To view the factory preset or to modified the factory presets to meet specific application requirements, press the ENTER key to advance to the following screens. If no adjustments are required, press the NEXT key to advance to the "Control Al gori thm Tuning Paramete rs".
Actuator Setup Ckt1 Low Ambient Output Max Stroke Tim e 60 Sec
2. Press the + or - key until the proper value is displayed.
3. Press the ENTER key to confirm this choice.
4. Press the NEXT key until the following screen is displayed.
Actuator Setup Ckt1 Low Ambient Output Min Voltage 2 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup Ckt1 Low Ambient Output Max Voltage 10 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup Ckt 1 Low Ambient Output Direct/Reverse Act DIRECT ACTING
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup Ckt 2 Low Ambient Output Max Stroke Tim e 60 Sec
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup Ckt 2 Low Ambient Output Min Voltage 2 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup Ckt 2 Low Ambient Output Max Voltage 10 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup Ckt 2 Low Ambient Output Direct/Reverse Act DIRECT ACTING
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
System Programming SETUP
Used on Units:
Possible Values:
Used on Units: Possible Values:
Used on Units:
Possible Values:
Used on Units:
Possible Values:
Used on Units: Possible Values:
Used on Units:
Possible Values:
Used on Units: Possible Values:
Used on Units:
Possible Values:
1 to 255 Seconds
All Units
0 - 10 VDC
0 - 10 VDC
Direct Acting/Reverse Acting
40 - 60 Ton Units
1 to 255 Seconds
0 - 10 VDC
40 - 60 Ton Units
0 - 10 VDC
Direct Acting/Reverse Acting
32
Page 33
System Programming SETUP
g
0 PSIG - 0.000 to 4.000 VDC
g
g
0 PSIG - 0.000 to 4.000 VDC
g
40-60 Ton With Superheat/Subcooling
0 PSIG - 0.000 to 4.000 VDC
g
40-60 Ton With Superheat/Subcooling
0 PSIG - 0.000 to 4.000 VDC
g
g
g
g
g
All Units
g
j
g
Ckt 1 Suction Line Pressure Transducer 0 PSIG= 0.118 VDC 100 PSIG= 4.847 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to ad vance the cursor to the "1 00 PSIG"
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm this choice.
6. Press the NEXT ke y until the followin
Ckt 1 Liquid Line Pressure Transducer 0 PSIG= 0.118 VDC 400 PSIG= 4.847 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to ad vance the cursor to the "4 00 PSIG"
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm this choice.
6. Press the NEXT ke y until the followin
Ckt 2 Suction Line Pressure Transducer 0 PSIG= 0.118 VDC 100 PSIG= 4.847 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to ad vance the cursor to the "1 00 PSIG"
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm this choice.
6. Press the NEXT ke y until the followin
Ckt 2 Liquid Line Pressure Transducer 0 PSIG= 0.118 VDC 400 PSIG= 4.847 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to ad vance the cursor to the "4 00 PSIG"
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm this choice.
6. Press the NEXT ke y until the followin
End of Submenu (NEXT) to Re-enter STA TUS
screen is displayed.
screen is displayed.
screen is displayed.
screen is displayed.
Used on Units: Possible Value s:
100 PSIG - 1.000 to 5.000 VD C
Used on Units: Possible Value s:
400 PSIG - 1.000 to 5.000 VDC
Used on Units: Possible Value s:
100 PSIG - 1.000 to 5.000 VD C
Used on Units: Possible Value s:
400 PSIG - 1.000 to 5.0 00 VD C
With Superheat/Subcoolin
With Superheat/Subcoolin
Option
Option
1. Pressin the Submenu.
2. Press the NEXT key a
Control Algorithm Tuning Parame ters Press ENTER to Review or Ad
1.To view the factory preset or to modified the factory presets to meet specific application requirements, press the ENTER key to advance to the follow in adjustments are required, press the NEXT key to advance to the be
Comfort Cooling Desi
2. Press the + or - key until the proper value is displayed.
3. Press the ENTER key to confirm this choice.
4. Press the NEXT ke y until the followin
the NEXT key will display the beginning of
ain to ad vance to the fol lowing screen.
ust
screens. If no
inning of the "Setup" menu.
n Delta Temperature Setpoint 10.0 F
screen is displayed.
33
Used on Units: Possible Value s:
4.0 to 20.0 F
Page 34
System Programming SETUP
g
g
g
g
g
g
Pos sible Va lues:
EN TER key to ad va nce to the foll owi ng screens. If no adjustments are required, press the NEXT key to advance to the be
Com fort Cooling Design Delta Temperature Setpoint 10.0 F
2. Press the + or - key until the proper value is displayed.
3. Press the ENTER key to confirm this choice.
4. Press the NEXT key until the followin
Com fort Cooling Control Re sponse Setpoint 25
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the followin
Proces s Cooling C ontrol Gains Proportional 25 % /F Reset Time 90s
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor to the "Reset Time"
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm this choice.
6. Press the NEXT key until the followin
Proces s Cooling C ontrol Gains Proport Bias 0% Max C y Rate 1 5.0 cph
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor to the "Max Cy Rate ".
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm this choice.
6. Press the NEXT key until the followin
Low Am bient Fan Control Gain Proportional 2.0 % /F Reset Time 90 Sec
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor to the "Reset Time"
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm this choice.
6. Press the NEXT key until the followin
Low Am bient Fan Control Gain Rate Tim e 0 Se c
1. Press the + or - key until the proper value is displayed.
inning of the "Setup" menu.
screen is displayed.
screen is displayed.
screen is displayed.
screen is displayed.
screen is displayed.
Used on Units:
Pos sible Va lues:
Used on Units:
Pos sible Va lues:
Used on Units:
Pos sible Va lues:
Reset Time 30 to 3600 Sec
Used on Units:
Pos sible Va lues:
Ma x C y Ra te - 1.5 to 2 0.0 cph
Used on Units:
Pos sible Va lues:
Reset Time 5 to 60 0 Se c
Used on Units:
All Units
4.0 to 20.0 F
All Units
1 to 128
All Units
Proportional 2.0 to 200.0
All Units
Proport Bias 0 to 400%
All Units
Proportional 0.2 to 20.0
All Units
0 to 50
34
Page 35
System Programming SETPOINTS
g
g
g
g
g
g
g
g
g
g
g
All Brazed Plate Units
g
g
g
g
g
g
g
p
p
p
p(s)
p
SETPOINTS Menu
When a setpoint screen is displayed for 30 minutes without a key being pressed, the LCD screen will revert to the gen-
The SETPOINTS menu is used to designate default setpoints, low ambient compressor lockout setpoints and
eral operating status display. If this happens, press the SETPOINT key again to return to the setpoint menu.
select setpoint sources.
These setpoints will be active (in use) for the "Setpoint Source Selection" designated as "DEFAULT" for these in­puts.
HI Leaving Solution Setpoint: 44 F
1. Press the + or - key until the proper value is displayed. Ran
2. Press the ENTER key to confirm thi s choice. Ran
3. Press the NEXT key until the followin
Stop Ice Making When Ent Soln Temp Below Hi Ice Build Terminate Set
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the followin
Comp(s) OFF if Solution Temp Below Low Solution Cutout Tem
1. Press the + or - key until the proper value is displayed. Solution Setpoint’
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the followin
Heat Output ON When EST or LST Less Than Heat Ta
1. Press the + or - key until the proper value is displayed. Solution Setpoint’
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the followin
e Temperature Setpoint: 40.0 F
oint: 27.0 F
: 35.0 F
screen i s displayed. Range 20.0 - 29.0°F
screen is displayed.
screen is displayed.
screen is displayed.
Used on Units: Possible Values:
Ran
Ran
Used on Units: Possible Values:
Used on Units: Possible Values:
Note: Maximum settin
Used on Units: Possible Values:
Note: Maximum settin
All Units
Based on Confi
Units with Ice Buildin
20.0 to 31.0 F
All Units
-10.0 to 60.0 F
0 to 45.0 F
ured Leaving Solution STP Range: e 51.0 - 65.0°F e 40.0 - 50.0°F e 30.0 - 39.0°F
e 10.0 - 75.0°F (SPECIAL)
Control Option
may be limited by ’Hi Leavin
may be limited by ’Hi Leavin
HI Hot Start Load Limit Setpoint: 71.0 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the followin
Request Pump ON When OA Temp Less Than Low Ambient Pum
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the followin
Low Ambient Comp Lockout Temp: 40 F Com
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the followin
Use Leav ing Solution Se tpoint From: HUMAN INTERFACE STP MENU
1. Press the + or - key until the proper value is displayed. GBAS 0-10VDC Module
2. Press the ENTER key to confirm thi s choice. Ext Leavin
OFF if OA Temp Below This Value
Overr ide Temp: 35 F
screen is displayed.
screen is displayed.
screen is displayed.
Used on Units: Possible Values:
Used on Units: Possible Values:
Used on Units: Possible Values:
Used on Units: Possible Values:
GBAS 0-5VDC Module
All Units
60.0 to 80.0 F
All Units
-20.0 to 50.0 F
All Units
-20.0 to 60.0 F
All Units
Human Interface STP Menu
Soln STP Input
35
Page 36
System Programming SETPOINTS
Used on Units:
Used on Units:
Used on Units:
3. Press the NEXT key until the following screen is displayed.
Use Ic e Building Te rminate Setpoint From: HUMAN INTERFACE STP MENU
1. Press the + or - key until the proper value is displayed. GBAS 0-10VDC Module
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Use Hot Star t Load Limit Se tpoint From: HUMAN INTERFACE STP MENU
1. Press the + or - key until the proper value is displayed. GBAS 0-10VDC Module
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Use Capacity Limit Setpoint From: NO SOURCE SELECTED
1. Press the + or - key until the proper value is displayed. GBAS 0-10VDC Module
2. Press the ENTER key to confirm this choice.
3. Pressing the NEXT key will return to the 1st SETPOINT screen.
4. Press the AUTO or STOP key to return to the top level status information screen.
Possible Values:
GBAS 0-5VDC Module
Possible Values:
GBAS 0-5VDC Module
Possible Values:
GBAS 0-5VDC Module
With Ice Building Control Option
Human Interface STP Menu
All Units
Human Interface STP Menu
With GBAS5V or GBAS10V
No Source Selected
36
Page 37
CONFIGURATION Menu
Used on Units:
20, 25, 30, 40, 50, 60
Used on Units:
Used on Units:
Installed, Not Installed
Used on Units:
51-65 F, 40-50 F, 30-39 F,
20-29 F, Special
Used on Units:
Installed, Not Installed
Used on Units:
Installed, Not Installed
Used on Units:
Installed, Not Installed
Used on Units:
Installed, Not Installed
g
System Configuration
The CGM controlled unit has many operating functions whose settings are preset at the factory. The following con­figuration programming steps are provided for those cases where the Human Interface module has been replaced after the unit has been in operation and must be reconfigured.
Press the CONFIGURATION key to display the following screens. Check the unit model number and compare it to the data that is displayed in the following screens
Configuration - Model Num Digit 5,6,7 Unit Capacity 50
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 8 Line Voltage 460 VAC
1. Press the + or - key unti l the proper value is displayed. Special Voltage
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 11 Ice Buildin
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 11 Leaving Solution STP Range 40 - 50 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 13+ Hot Gas Bypass Option INSTALLED
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 13+
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 13+ GBAS 0-10VDC Module INSTALLED
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 13+
Control INSTALLED
-
Refer to the Model number stamped on the unit nameplate located on the control panel door while scrolling through the configuraton screes. Certain digits of this alpha/numeric model number provide information that must be entered at the Human Interface (HI) in order for the CGM network to operate properly.
All Units
Possible Values:
All Units
Possible Values:
415 VAC, 460 VAC, 575 VAC,
Possible Values:
Possible Values:
Possible Values:
Possible Values:
Possible Values:
Possible Values:
200 VAC, 230 VAC, 380 VAC,
All Units
All Units
All Units
All Units
All Units
All Units
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
37
Page 38
System Configuration
All Units
Installed, Not Installed
All Units
Installed, Not Installed
All Units
Installed, Not Installed
All Units
20 to 30 Ton Units
40 to 60 Ton Units
With GBAS 10VDC Module
3. Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 13+ Curre nt Sensing Module IN STALLED
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 13+ BAS Communications Module INSTALLED
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 13+ Remote Human Interface INSTALLED
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
The following displays are not editable.
Software Revision Number Report: Cold Gener ator Module (CGM) 1.00
1. Press the NEXT key until one of the following screens is displayed.
Software Revision Number Report: Single Compress or Module (SCM) 1.00
OR
Software Revision Number Report: Multiple Compressor Module (MCM) 1.00
1. Press the NEXT key until the following screen is displayed.
Software Revision Number Report: GBAS 0-5VDC Module 1.0 0
1. Press the NEXT key until the following screen is displayed.
Software Revision Number Report: GBAS 0-10VD C Module 1 .00
1. Press the NEXT key until the following screen is displayed.
Software Revision Number Report: Superheat/Subcool Module (SSM) 1.00
Used on Units: Possible Values:
Used on Units: Possible Values:
Used on Units: Possible Values:
Used on Units: Possible Values:
Used on Units: Possible Values:
Used on Units: Possible Values:
Used on Units: Possible Values:
Used on Units: Possible Values:
Used on Units: Possible Values:
With GBAS 5VDC Module
With SSM Module
1.0 or Greater
1.0 or Greater
1.0 or Greater
1.0 or Greater
1.0 or Greater
1.0 or Greater
38
Page 39
1. Press the NEXT ke y until th e following screen is displayed.
g
g
g
g
Software Revision N umber Report: Curre nt Sensing Module (CSM) 1.00
1. Press the NEXT ke y until th e followin
Software Revision N umber Report: Unit Human Interfac e (HI) 1.00
1. Press the NEXT ke y until th e followin
Software Revision N umber Report: Remote Huma n Interface (RHI) 1.00
1. Press the NEXT ke y until th e followin
Software Revision N umber Report: BAS Communications: Comm3 1.00
1. Pressin CONFIGURATION screen.
2. Press the AUTO or STOP ke y to return to the top level status info rmation screen.
the NEXT key will return to the 1st
screen is displayed.
screen is displayed.
screen is displayed.
System Configuration
Used on Units: Possible Value s:
Used on Units: Possible Value s:
Used on Units: Possible Value s:
Used on Units: Possible Value s:
Comm5 (with LC I module )
Possible Value s:
With CSM Module
1.0 or Greater
All Units
1.0 or Greater
With Re mote H uman Inte rface Module
1.0 or Greater
With TCI o r LCI Module
Comm3 (with TCI module)
1.0 or Greater
39
Page 40
System Testing & Troubleshooting
All Units
All Units
All Units
With Ho t Gas Byp ass Option
SERVICE MODE Menu
The SERVICE MODE menu is used to input operating pa­rameters for unit operation during a service test. Depending on the particular test being conducted, the user will cycle through all unit outputs (compressors, fans, pump, etc...) and selectively turn them On or Off for the test. After desig­nating the operating status for each unit component, the op­erator will designate the "TEST START" delay time.
To operate the system in the TEST MODE, press the SERVICE MODE key to enter into the service mode menu and scroll through all of the system outputs and selectively turn them "On" or "Off".
CGM Eva p Solution Pump R elay: OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Liquid Line Solenoid Valve Ctrl Relays: Ckt 1 ON Ckt 2 OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor to the "Ckt 2"
Circuit 2 is use d for 40 through 60 Ton units only.
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm this choice.
6. Press the NEXT key until the following screen is displayed.
Low Ambient LPC Bypass Relay(s) Ckt 1 ON Ckt 2 OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor to the "Ckt 2"
Circuit 2 is use d for 40 through 60 Ton units only.
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm this choice.
6. Press the NEXT key until the following screen is displayed.
CGM Hot Gas Bypass Control Relay: OFF
When a service mode screen is displayed for 30 minutes without a key being pressed, the LCD screen will revert to the general operating status display. If this happens, press the SERVICE MODE key again to return to the service menu.
Used on Units: Possible Values:
Used on Units: Possible Values:
Used on Units: Possible Values:
Used on Units: Possible Values:
On, Off
On, Off
On, Off
On, Off
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Compressor Relays K11 OFF K 12 OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor to the "K11"
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm this choice.
6. Press the NEXT key until the following screen is displayed.
40
Used on Units: Possible Values:
20 to 3 0 Ton
On, Off
Page 41
System Testing & Troubleshooting
g
40 to 60 To n
g
g
g
40 to 60 To n
g
g
g
OR
The followin
Compress or R elays K11 OFF K 12 OFF K3 OFF K4 OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm thi s choice.
3. Press the NEXT key to advance the curso r to the "K12"
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm thi s choice.
6. Press the NEXT key to advance the curso r to the "K3"
7. Press the + or - key until the proper value is displayed.
8. Press the ENTER key to confirm thi s choice.
9. Press the NEXT key to advance the curso r to the "K4"
10. Press the + or - key until the proper value is displayed.
11. Press th e ENTER ke y to confirm this choice.
12. Pre ss the NEXT key until the followin
Condenser Fan Outputs 1A OFF 1B OFF 1C OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm thi s choice.
3. Press the NEXT key to advance the curso r to the "1B"
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm thi s choice.
6. Press the NEXT ke y until th e followin
7. Press the + or - key until the proper value is displayed.
8. Press the ENTER key to confirm thi s choice.
9. Press the NEXT key to advance the curso r to the "2B"
screen will display on 40 to 60 Ton units.
screen is displayed.
screen is displayed.
Used on Units: Possible Values:
Used on Units: Possible Values:
All Units
On, Off
On, Off, Auto
The followin
Condenser Fan Outputs 2A OFF 2B OFF 2C OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm thi s choice.
3. Press the NEXT key to advance the curso r to the "1B"
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm thi s choice.
6. Press the NEXT key to advance the curso r to the "2A"
7. Press the + or - key until the proper value is displayed.
8. Press the ENTER key to confirm thi s choice.
9. Press the NEXT key to advance the curso r to the "2B"
Condenser Fan Speed
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm thi s choice.
Circuit 2 is used for 40 through 60 Ton units only.
3. Press the NEXT key to advance the curso r to the "Ckt 2"
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm thi s choice.
6. Press the NEXT ke y until th e followin
MCM He ater Tape Relay K13: OFF Relay ON: Heat Off, Rela y OFF: Heat On
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm thi s choice.
3. Press the NEXT ke y until th e followin
CGM Alarm Output: OFF
screen will display on 40 to 60 Ton units.
screen is displayed.
screen is displayed.
Used on Units: Possible Values:
Used on Units: Possible Values:
Note: Th is is the low ambient damper position
Used on Units: Possible Values:
On, Off, Auto
All Units
Auto, 0 to 100%
All Brazed Plate Units
On, Off
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm thi s choice.
3. Press the NEXT ke y until th e followin
screen is displayed.
41
Page 42
System Testing & Troubleshooting
0.0 to 1 0.0 VDC
0.0 to 1 0.0 VDC
3. Press the NEXT key until the following screen is displayed.
CGM Ice Build Relay Output : OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
GBAS 0-5VDC Module Relay Outputs #1 OFF #2 OFF #3 OFF #4 OFF #5 OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT ke y to advance the cu rsor to the "#2 Output"
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm this choice.
6. Repeat steps 1 - 4 for Outputs 3, 4 & 5.
7. Press the NEXT key until the following screen is displayed.
GBAS 0-10 VDC Module Relay Output: OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
GBAS 0-10VDC Module Analog Outputs Out #1 0.2 VD C Out #2 0.4 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT ke y to advance the cu rsor to the "#2 Output"
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm this choice.
6. Press the NEXT key until the following screen is displayed.
GBAS 0-10VDC Module Analog Outputs Out #3 0.6 VD C Out #4 0.8 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT ke y to advance the cu rsor to the "#4 Output"
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm this choice.
6. Press the NEXT key until the following screen is displayed.
CGM ICS C ontrolled Rela y: OFF
Used on Units: Possible Value s:
Used on Units: Possible Value s:
Used on Units: Possible Value s:
Used on Units: Possible Value s:
Used on Units: Possible Value s:
Used on Units: Possible Value s:
With Ice Bui lding Control Option
With GBAS 5VDC Mod ule Option
With GBAS 10VDC Mo dule Option
With GBAS 10VDC Mo dule Option
With GBAS 10VDC Mo dule Option
With TCI Module Op tion (For Future Use)
On, Off
On, Off
On, Off
On, Off
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
42
Page 43
System Testing & Troubleshooting
All Units
5 to 255 seconds
All Units
All Units
All Units
g
3. Press the NEXT key until the following screen is displayed.
Start Test in 5 Sec Press TEST START To Begin, STOP To Halt
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
The following screen will be displayed after pressing the "TEST START" key if a SERVICE MODE screen has been displayed during the previous 60 minutes.
Test Start In 5
Press STOP To Halt
If a screen has not been displayed during the SERVICE MODE procedure for 60 minutes and the TEST START key is pressed, the following screen will be displayed.
Press SERVICE MODE
To Revie w Selections
When the START TEST timer expires, this screen will be displayed at the unit mounted Human Interface and at the remote mounted Human Interface, if installed.
Service Test Is Active
Press STOP To Ha lt
Note:
There is no time-out period when the unit is operating in the SERVICE TEST mode. Press the "STOP" or "AUTO" key to discontinue the Service Test. Only the STATUS, CUSTOM, SERVICE MODE, DIAGNOSTICS, and STOP keys are functional once the TEST START key has been pressed.
Sec
Used on Units: Possible Values:
Used on Units:
Possible Values:
Used on Units:
Used on Units:
120 to 0 Seconds
After pressing the STOP or AUTO key, the following screen is displayed
Service Mode, STOP SYSTEM Restart
Communicatin
and then the following screen is displayed:
Updating Unit Data. Please Wait
TRANE INTELLIPAK
and then the top level status screen is displayed.
With Unit. Please Wait
43
Page 44
System Testing & Troubleshooting
g
g
g
DIAGNOSTICS Menu
The DIAGNOSTICS menu is used to view diagnostics that have resulted from system failures within the unit. There are two lists where diagnostics reside; the Active list, and the Diagnostic Event Log.
The Active list is used for viewing all active diagnostics and for clearing manually resetable diagnostics. This list of diag­nostics are displayed after pressing the DIAGNOSTICS key if active diagnostics are present.
Active manual diagnostics can be cleared in batch form at the unit mounted Human Interface. When an Active diag­nostic is manually or automatically cleared, it is removed from this buffer. Automatically resetting diagnostics can not be reset by the Human Interface, because the condition which caused the diagnostic has to be corrected for the di­agnostic to clear.
The word “MORE” is displayed on all screens if more than one diagnostic exists, except for the last diagnostic. Upon reaching the last diagnostic, the word “MORE” disappears. Pressing the NEXT key at this point causes the display to advance to the first diagnostic in the Diagnostic Event Log.
The Diagnostic Event Log screens are displayed after scrolling through the Active list or after pressing the DIAGNOSTICS key when no active diagnostics are present. It’s used to view the past 20 diagnostics. Diagnostics in this
log are stacked in inverse chronological order, with the first diagnostic screen being the most recently reported diagnos­tic.
When a new diagnostic is displayed, the words “NOT VIEWED” are displayed with it. After viewing the last unviewed diagnostic, the words "NOT VIEWED" change to "VIEWED" for every diagnostic in the log. The diagnostic will remain this way as long as it is in the log. This allows the operator to distinquish between old and new diagnostics in the Event Log.
Pressing the NEXT key after reaching the last diagnostic in the Event Log advances the display to the first diagnostic in the Active list if any exist. If not, the display reverts back to the first Event Log diagnostic. If the Diagnostic Event Log is full (20 events), and another diagnostic occurs, the oldest diagnostic is pushed off the end of the list. If all 20 diagnos­tics in the list are active when the 21st occurs, then the old­est Active diagnostic is pushed off the end of the list. When an Active diagnostic is automatically or manually cleared in the Active buffer, its status in the Diagnostic Log changes from Active to History. If the operator does not clear an ac­tive diagnostic in the Active log, its status will still show as Active in the Diagnostic Log.
When a diagnostic screen is displayed for more than four hours without a key being pressed, the screen will return to the operating status display.
One of the following screens will be the first screen displayed when the DIAGNOSTIC" key is pressed.
Diagnostic Menu ---- Info
No Active Dia
Press CANCEL to Clear All Active Manual
nostics, or Press NEXT to View
Dia
1. If there are active diagnostics, pressing the "CANCEL" key to clear the diagnostics will prompt the following screen.
Diagnostic Reset Is Password Protected
Please Enter Password:
1. Press the + (Plus) or - (Minus) keys to enter the password
2. Press the ENTER key to confirm this choice. When the correct password is entered, the following screen will be displayed.
nostics (NEXT) History Lo
OR
Used on Units: Possible Values:
All Units
+ (Plus) and - (Minus)
44
Page 45
System Testing & Troubleshooting
p
g
Resetting Active Manual Diagnostics
Sendin
and then the following screen will be displayed
Resetting Active Manual Dia gnostic s
U
and then the following screen will be displayed
Active Diagnostic ---- Info "Please Wait . . . Unit Is In Reset Mode"
3. Pressing the "NEXT" key to view the diagnostics will prompt the following screen if a "MANUAL RESET" failure has occurred.
Active Diagnostic ---- Manual Reset
The word MORE will only appear if more than one failure has occurred.
Possible Values:
Comp Contactor Fail - Ckt 1 Evap Leaving Solution Temp Sensor Fail Comp Contactor Fail - Ckt 2 Evap Entering Solution Temp Sensor Fail Comp Prot - LPC Open (Ckt 1) Evap Solution Flow Loss Comp Prot - LPC Open (Ckt 2) Hot Start Load Limit (Man) Compressor Trip - Ckt 1 Low Solution Cutout Temp (Man) Compressor Trip - Ckt 2 Low Pressure Control Open - Ckt 1 Emergency Stop Low Pressure Control Open - Ckt 2
Pressing the "NEXT" key to view the diagnostics will prompt the following screen if an "AUTO RESET" failure has occurred.
Active Diagnostic ---- Auto Reset
The word MORE will only appear if more than one failure has occurred.
dating Unit Data, Please Wait
Reset Request
OR
More
OR
More
Used on Units:
Used on Units:
All Units
All Units
Possible Values:
CGM OA Temp Sensor Failure, IBTS Adjusted to Maintain Min Diff CGM Zone Temp Sensor Failure, Ice Build Terminate Setpoint Fail Cond Temp Sensor Failure - Ckt 1, Leaving Solution Setpoint Fail Cond Temp Sensor Failure - Ckt 2, Low Ambient Evap Solution Pump Override Current Sensing Module Comm Fail Low Solution Cutout Temp (Auto) Evap Solution Flow Proving Switch LSS Adjusted to Maintain Min Diff Ext. Leaving Solution STP Input Fail MCM Communications Failure GBAS 0-5V Module Comm Failure SCM Communications Failure GBAS 0-10V Module Comm Fail BAS Module Comm Fai l ure Hot Start Load Limit (Auto) BAS/NETWORK Comm Failure Hot Start Load Limit STP Fail Unit HI Communications Failure
OR
Pressing the "NEXT" key to view the diagnostics will prompt the following screen if an "Information Only" failure has occured.
45
Page 46
System Testing & Troubleshooting
Active Diagnostic ---- Info
The word MORE will only appear if more than one failure has occured. If additional active diagnostics are present, pressing the NEXT key will display them.
Possible Values:
CGM ICS Temperature Sensor Fail Sat Liquid Temp Sensor Fail Ckt 1 CGM Module Data Storage Error Sat Liquid Temp Sensor Fail Ckt 2 EST/LST Low Temperature Indication Suction Pressure Sensor Fail Ckt 1 Hot Start Load Limit (Info) Suction Pressure Sensor Fail Ckt 2 Liquid Pressure Sensor Fail Ckt 1 Suction Temp Sensor Fail Ckt 1 Liquid Pressure Sensor Fail Ckt 2 Suction Temp Sensor Fail Ckt 2 Pumpdown Terminated By Time Ckt 1 Superheat/Subcool Module Fail Pumpdown Terminated By Time Ckt 2
After viewing all active diagnostics, pressing the NEXT key will display the following screen
Log 1 __________
Pressing the NEXT key will display each successive log entry. screens associated with the type of diagnostic.
1. Pressing the "CANCEL" key to clear the diagnostics log will display the following screen.
Diagnostic Log Is Password Protected
Please Enter Password:
1. Press the + (Plus) or - (Minus) keys to enter the password
2. Press the ENTER key to confirm this choice. When the correct password is entered, the following screen will be displayed.
More
Used on Units:
Used on Units: Possible Values:
Not Viewed, Active or History, Manual, Auto, or Info., Any diagnostic listed under the previous
Used on Units: Possible Values:
All Units
All Units
Log Number 1-20, Viewed or
All Units
+ (Plus) and - (Minus)
Active Diagnostics ____________________
"Please Wait . . . Updating Diagnostic Log"
If the "DIAGNOSTIC LOG" is empty when the "CANCEL" key is pressed, the following screen will be displayed.
Active Diagnostics ---- Info
"Diagnostic Buffer Is Already Empty !"
Press the AUTO or STOP key to return to the top level status screen.
Failure Modes
When any condition results in the unit's unability to perform a normal function, it is said to have entered a failure mode. There are two types of failure modes.
1. An "Analog input out of range" failure mode.
This failure mode occurs when a sensing device such as a temperature sensor begins to transmit information that is outside its allowable range.
2. A "Fault recognition by input logic" failure mode. This failure mode occurs when the UCM receives informa­tion that does not "make sense" or does not conform to its predefined logic.
Used on Units:
Possible Values:
Used on Units:
Possible Values:
All Units
Manual, Auto, or Info
All Units
Manual, Auto, or Info
46
Page 47
All Units with Local HI
All Units with Local HI
k
System Testing & Troubleshooting
Communications Link Problems
If one of these messages appear on the Human Interface screen, that Human Interface is not communicating with the unit.
LOCAL HI COMMUNICATIONS LOSS
OR
REMOTE HI COMMUNICATIONS LOSS CHECK COMM LINK WIRING TO UNIT NUMBER 3
If one of these messages appear on the Human Interface screen, the link is noisy or there is another Human Interface of the same type on the link.
Impr oper Human Interface Configuration
OR
Improper Human Interface Configuration More than one Remote HI on lin
Used With: Problem:
has lost communications with the CGM. See "Fail Diagnostic" for additional information.
Check:
Interface and CGM. Verify crimping and polarity of communications wiring. There should be no loose connections or crimps on wire insulation.
Used With: Possible Values: Problem:
communications with the unit whose number is specified (#3 in this example).
Check:
or crimps on wire insulation.
Used With: Problem:
Local HI has been installed on the link.
Check:
Interface and CGM. Verify crimping of communications wiring. There should be no loose connections or crimps on wire insulation. If a Remote HI was installed, verify that a Local HI was not installed by mistake.
Used With: Problem:
Remote HI has been installed on the link.
Check:
face and the IPCB and CGM. Verify crimpi ng of communications wiring. There should be no loose connections or crimps on wire insulation. Verify that no other Remote HI’s have been connected to the same communications link/unit.
The Unit Mounted (Local) Human interface
Wiring between Unit Mounted (Local) Human
All Uni ts with Remote Human Interface
Unit Number 1 through 4
The Remote Human Interface has lost
Field/unit wiring between Remote Human Interface and the IPCB on the unit number specified. Also, verify wiring between the IPCB and CGM of the unit whose number is specified. Verify crimping and polarity of communications wiring. There should be no loose connections
Noisy Communications link or a second
Wiring between Unit Mounted (Local) Human
All Uni ts with Remote Human Interface
Noisy Communications link or a second
Field/Unit wiring between Remote Human Inter-
Diagnostics
There are four types of diagnostics:
1. (PMR) Partial System Disable, Manual Reset
2. (PAR) Partial System Disable, Auto Reset
3. (INFO) Information Only
4. (HO) History Only
The following Troubleshooting chart lists possible Failure Modes and:
1. The Diagnostic Displayed screen and if it is a PMR, PAR, INFO or HO diagnostic.
2. The condition which caused the failure mode to occur or the Reason for Diagnostic
3. The UCM’s Reaction
47
on the Human Interface’s LCD
.
to the failure mode.
Page 48
System Testing & Troubleshooting
i
y
p
(INFO) A manual reset may be
made at the Human Interface, at
Tracer, or by cycling power to the
(INFO) An automatic reset occurs
after the CGM ICS Temperature
Sensor returns to its allowable
range. In order to prevent rapid
cycling of the diagnostic, there is a
10 second delay prior to the
CGM.
(PAR) An automatic reset occ urs
after the OA Temp input returns to
its allowable range. In order to
prevent rapid cy cling of the
Diagnostic, there is a 10 second
delay before the automatic reset.
(PAR) An automatic reset occ urs
after the designated Zone
Temperature signal returns to its
allowable range. In order to prevent
rapid cycling of the Diagnostic,
there is a 10 second delay before
the automatic reset.
An information only diagnostic will
be displayed at the Human
No change in unit operation
occurs. This diagnostic is for
information only.
The unit is reading a signal that is out of
range for the CGM ICS Temperature
sensor input on the CGM. (Temp < -40 F
or Temp > 200 F).
Interface.
An error occurred while the CGM was
writing data to its internal non-volatile
memory (EEPROM).
Unit actions that occur when this
diagnostic is active include;
a. Low Ambient Compressor
Lockout function is disabled
b. Low Ambient Pump Override
function is activated (ie: Solution
Pump ON request is issued).
c. LPC Bypass Time is set to
Minimum Bypass Time (time used
for OA Temp >65 degF).
d. If Leaving Solution Reset type
selected is OA Temp Reset, then
the Reset type reverts to NONE
for the duration of the failure.
The Reset type reverts to NONE
for the duration of the failure.
The unit is reading a signal that is out of
range for the Outside Air Temperature
sensor input on the CGM. (Temp < -40 F
or Temp > 200 F).
laced.
need to be re
The Leaving Solution Reset type
selected is Zone Temp Reset, and the
unit is reading a signal that is out of
range for this input (Temp < -40 F or
Temp > 200 F).
DIAGNOSTIC DISPLAYED REASON FOR DIAGNOSTIC UCM’S REACTION RESET REQUIRED
CGM ICS Temperature Sensor Fail
Problem: CGM is receiv ing a signal
which is out of range from the CGM
ICS Temperature Sensor input.
CGM Module Data Storage Error
Problem: There was a data
transmission error.
Check: This can be caused by an
intermittent power loss . Turn the
unit off for 1-2 minutes, then back on
again. If diagnostic pers ists, then
CGM OA Temp Sensor Failure
the CG M ma
Problem: The Outside Air
Temperature sensor input is out of
range.
Check: Sensor resistance between
830 ohms (200 F) and 345.7Kohms
(-40 F). If so, check field/unit wiring
between Sens or and CGM.
48
CGM Zone Temp Sensor Failure
Problem: The CGM Zone
Temperature sensor input is out of
range.
Check: Sensor resistance between
830 ohms (200 F) and 345.7Kohms
(-40 F). If so, check field/unit wiring
between Sens or and CGM.
Page 49
y
p
p
p
(INFO) This diagnostic is reset when
y
p
p
p
a compres sor on Circ uit 1 is staged
on due to a cooling demand.
(INFO) This diagnostic is reset when
a compres sor on Circ uit 2 is staged
on due to a cooling demand.
System Testing & Troubleshooting
(PMR) A manual reset is required
after the diagnostic is set. It can be
reset by the HI or Trac er, or by
cycling power to the CGM.
PMR) A manual reset is required
after the diagnostic is set. It can be
reset by the HI or Trac er, or by
cycling power to the CGM.
No Change in unit operation
occurs. This diagnostic is for
information only.
Unit remained in pumpdown for 30
seconds without the occurrence of
an LPC event. Pumpdown sequence
was terminated by a 30 second
timer.
DIAGNOSTIC DISPLAYED REASON FOR DIAGNOSTIC UCM’S REACTION RESET REQUIRED
Circuit 1 Pumpdown Terminated
by Time
Problem: Unit went through
Pumpdown on Circuit 1 and LPC
never tripped. Pumpdown was
terminated after 30 s econds.
Check: Check circuit 1 pumpdown
No Change in unit operation
occurs. This diagnostic is for
information only.
Unit remained in pumpdown for 30
seconds without the occurrence of
an LPC event. Pumpdown sequence
was terminated by a 30 second
timer.
eration.
er o ro
solenoid valve and low pressure
switch to verif
Crcuit 2 Pumpdown Terminated by
Time
(Circuit #2 40-60 Ton units only)
Problem: Unit went through
Pumpdown on Circuit 2 and LPC
never tripped. Pumpdown was
terminated after 30 s econds.
Check: Check circuit 2 pumpdown
A "Lockout Circuit #1" request is
issued to the Compressor Staging
Control function. The Compressor
Relays, LPC Bypass Relay,
Liquid Line Solenoid Relay, and
Hot Gas Bypass Relay for
Circuit 1 are all de-energized
A "Lockout Circuit #2" request is
issued to the Compressor Staging
Control function. The
Compressor Relays, LPC
Bypass Relay, and Liquid Line
Solenoid Relay for Circuit 2 are
all de-energized
The circuit #1 compressor proving
input on the SCM/MCM is detected
closed continuously for more than 3
seconds while neither compressor
output on Circuit #1 is clos ed.
eration.
er o ro
solenoid valve and low pressure
switch to verif
Compressor Contactor Fail -
Circuit 1
Problem: The Compressor
Contactor for Circuit #1 has
malfunctioned.
The Circ uit #2 compressor proving
Compressor Contactor Fail -
input on the MCM is detected c losed
Circuit 2
continuous ly for more than 3
(Circuit #2 40-60 Ton units only)
seconds while neither compressor
output on Circuit #2 is clos ed.
Problem: The Compressor
Contactor for Circuit #2 has
malfunctioned.
49
Page 50
System Testing & Troubleshooting
g
(PMR) A manual reset is required
after this diagnostic occurs. The
Diagnostic can be reset by the unit
mounted Human Interface Module or
Tracer, or by cycling power to the
(PMR) A manual reset is required
anytime after the Diagnostic is set.
The Diagnostic c an be reset by the
Human Interface or Tracer, or by
cycling power to the CGM.
(PMR) A manual reset is required
anytime after the Diagnostic is set.
The Diagnostic c an be reset by the
Human Interface or Tracer, or by
cycling power to the CGM.
CGM.
(PMR) A manual reset is required
after this diagnostic occurs. The
Diagnostic can be reset by the unit
mounted Human Interface Module or
Tracer, or by cycling power to the
CGM.
(PAR) An automatic reset occurs
after the #1 Condenser Temperature
input returns to its allowable range
within 10 seconds .
A “Lockout Circuit #1” request is
While the Circuit 1 LPC Bypass
issued to the Compressor Staging
Control function. The Compressor
Relay was energized, the 7 PSIG
LPC switch: a) was open at the time
ized.
A “Lockout Circuit #2” request is
issued to the Compressor Staging
Control function. The
Compressor Relays, LPC
Bypass Relay, Liquid Line
Solenoid Relay for Circuit 2 are all
Relays, LPC Bypass Relay,
Liquid Line Solenoid Relay, and
Hot Gas Bypass Relay for
Circuit 1 are all de-energized.
A “Lockout Circuit #2” request is
issued to the Compressor Staging
Control function. The
Compressor Relays, LPC
Bypass Relay, and Liquid Line
Solenoid Relay for Circuit 2 are all
de-energized.
A “Lockout Circuit #1” request is
issued to the Compressor Staging
Control function. The
Compressor Relays, LPC
Bypass Relay, Liquid Line
Solenoid Relay, and Hot Gas
Bypass Relay for Circuit 1 are all
de-ener
The Circ uit #2 Compressor proving
input is detected open continuously
for more than 3 seconds when either
a compres sor was requested to
start, or b) the switch opened 4 times
after a compress or on Circuit 1 was
started but prior to ac cumulating 3
continuous minutes of run time.
While the Circuit 2 LPC Bypass
Relay was energized, the 7 PSIG
LPC switch: a) was open at the time
a compres sor was requested to
start, or b) the switch opened 4 times
after a compress or on Circuit 2 was
started but prior to ac cumulating 3
continuous minutes of run time.
The Circ uit #1 Compressor proving
input is detected open continuously
for more than 3 seconds when either
or both compress or outputs on
Circuit #1 are energiz ed (as
described in the Compressor
Protection function).
or both compress or outputs on
de-energized
A “Lockout Circuit # 1” request is
issued to the Compressor Staging
Control function. The
Compressor Relays, LPC
Bypass Relay, Liquid Line
Solenoid Relay, and Hot Gas
Bypass Relay for Circuit 1 are all
de-energized.
Circuit #2 are energiz ed (as
described in the Compressor
Protection function).
The unit is reading a signal that is out
of range for the circ uit #1 Saturated
Condenser Temperature sensor.
(Temp < -40 F or Temp > 200 F).
DIAGNOSTIC DISPLAYED REASON FOR DIAGNOSTIC UCM’S REACTION RESET REQUIRED
Compressor Protection - LPC Open -
Circuit 1
Problem: State of refrigerant charge
for circuit #1 is low.
Compressor Protection - LPC Open -
Circuit 2 (Circuit #2 40-60 Ton units
only)
Problem: State of refrigerant charge
Compressor Trip - Circuit 2
(Ckt #2 40-60 Ton units only)
Problem: The Compress or Circuit #2
for circuit #2 is low.
Compressor Trip - Circuit 1
Problem: The Compress or Circuit #1
has tripped.
50
has tripped.
Cond Temp Sensor Failure - Circuit 1
Problem: The Saturated Condenser
Temperature Input is out of range for
Circuit #1.
Check: Sensor resistance between
830 ohms (200 F) and 345.7Kohms
(-40 F). If so, check field/unit wiring
between Sens or and MCM/SCM.
Page 51
System Testing & Troubleshooting
(PAR) An automatic reset occurs after
the #2 Condenser Temp input returns
to its allowable range within 10
seconds.
(PAR) An automatic reset occurs after
communication has been restored.
(PMR) A manual reset is required after
the Emergency Stop input recloses.
The Diagnostic can be reset by the
Human Interface or Tracer or by
cycling power to the CGM.
(INFO) An automatic reset occurs after
the EST and LST have both risen to
greater than 3oF above the heat tape
temperature setpoint.
A “Lockout Circuit #2” request is
The unit is reading a signal that is out
issued to the Compressor Staging
of range for the circuit #2 Saturated
Control function. The Compressor
Relays, LPC Bypass Relay, and
Liquid Line Solenoid Relay for
Circuit 2 are all de-energized.
Condenser Temperature sensor.
(Temp < -40 F or Temp > 200 F).
No Change in unit operation
The CGM has lost communications
occurs. The Current Sensing
Module is used for monitoring
purposes only, and does not affect
unit operation. This diagnostic is
for information only.
with the CSM.
“OFF or “Close” requests are
issued as appropriate to the
An open circuit has occurred on the
Emergency Stop input caused either
following functions;
by a High Duct Temp T-stat trip, or the
a. Compressor Staging control. (All
Compressor Relays, Liquid Line
Solenoid Relays, LPC Bypass
Relay, and HGBP Relay are
deenergized).
b. Evaporator Solution Pump
Control. (S
No change in the unit operation.
This diagnostic is for information
only.
opening of field-provided contacts,
switch, etc...
An abnormal temperature reading of
the chilled solution exists.
DIAGNOSTIC DISPLAYED REASON FOR DIAGNOSTIC UCM’S REACTION RESET REQUIRED
Cond Temp Sensor Failure - Circuit 2
(Circuit #2 40-60 Ton units only)
Problem: The Saturated Condenser
Temperature Input is out of range for
Circuit #2.
Check: Sensor resistance between
830 ohms (200 F) and 345.7Kohms
(-40 F). If so,
Current Sensing Module Comm Fail
Problem: The CGM has lost
communications with the Current
Sensing Module (CSM)..
Check: Check field/unit wiring between
CGM and CSM.
Emergency Stop
Problem: The Emergency Stop input
on the CGM is open.
51
EST/LST Low Temperature Indication
Problem: Either the entering solution
temperature or the leaving solution
temperature has fallen below the heat
tape temperature setpoint.
Page 52
(PMR) A manual reset is
System Testing & Troubleshooting
(PMR) A manual reset is
required after this diagnostic
occurs. The Diagnostic can
be reset by the unit mounted
Human Interface Module or
Tracer, or by cycling power
required after this diagnostic
occurs. The Diagnostic can
be reset by the unit mounted
Human Interface Module or
Tracer, or by cycling power
to the CGM.
to the CGM.
When this diagnostic is active:
a. A "Lockout Ckts" request is sent
to the compressor staging function.
All Compressor Relays, LPC
Bypass relays, and Liquid Line
Solenoids will be de-energized.
Min On times, H GBP, and
Pumpdown will be bypassed.
b. The following functions will be
disabled:
1) Compressor Staging,
2) Process/Comfort Cooling,
3) Ice Building.
c. Evaporator Solution Pump
Control is not affected.
d. The Heat Tape relay output will
When this diagnostic is active:
a. A "Lockout Ckts" request is sent
to the compressor staging function.
All Compressor Relays, LPC
Bypass relays, and Liquid Line
Solenoids will be de-energized.
Min On times, H GBP, and
Pumpdown will be bypassed.
b. If Leaving Solution Reset type
selected is Entering Soluti on Reset,
then th e Reset type reverts to
NONE for the duration of the failure.
c. Evaporator Solution Pump
Control is not affected.
d. The Heat Tape relay output will
energize.
The unit is reading a signal that is out
of range for this input on the CGM
The unit is reading a signal that is out
of range for this input on the CGM.
(Temp < -40 F or Temp > 200 F).
(Temp < -40 F or Temp > 200 F).
energize.
DIAGNOSTIC DISPLAYED REASON FOR DIAGNOSTIC UCM’S REACTION RESET REQUIRED
Evaporator Entering Solution
Temperature Sensor Fail
Problem: The Evaporator Entering
Solution Temperature Sensor input is
out of range.
Check: Sensor resistance between
830 ohms (200 F) and 345.7Kohms
(-40 F). If so, check field/unit wiring
between Sensor and CGM.
Evaporator Leaving Solution
Temperature Sensor Fail
Problem: The Evaporator Leaving
Solution Temperature sensor input is
out of range.
Check: Sensor resistance between
830 ohms (200 F) and 345.7Kohms
(-40 F). If so, check field/unit wiring
between Sensor and CGM.
52
Page 53
System Testing & Troubleshooting
For Service Parts Replacement,
please note:
(a) For proper operation of units with
Brazed Plate heat exchangers,
please insure the following board is
installed:
Multiple Compressor Module (MCM)
- Software Version number greater
(PMR) A manual reset is required
after this diagnostic occurs. The
Diagnostic can be reset by the unit
mounted Human Interface Module
or Tracer, or by cycling power to the
CGM.
than or equal to 10.00orSingle Compressor Module
(SCM) - Software Version number
greater than or equal to 10.00
(b) To eliminate this diagnostic
when it is due to an incompatible
Software Version number(s), please
install the appropriate board(s) per
the fol lowing:
Cold Generator Module (CGM) -
Software Version number greater
than or equal to 3.00
CG Unit Human Interface (HI) -
Software Version number greater
than or equal to 27.00
A "Lockout all Circuit" request
is issued to the comp ressor
staging function. Compressor
Relays, LPC Bypass Relays,
Liquid Line Solenoid Relays
and HGBP relay are all de-
energized.
Units with a Brazed Plate heat
exchanger require a flow proving switch
for freeze protection functionality. This
flow proving switch input was detected
close d (shorted) at the time th e sol ution
pump was commanded ON (Only on
units with "Chiller Solution Pump Mode"
set to AU TO).
Also, units with Brazed Plate heat
exchanger require newer versions of
control boards for proper operation.
During power-up, the unit detected at
least one replacement module with a
Software Verison number less than what
is required.
DIAGNOSTIC DISPLAYED REASON FOR DIAGNOSTIC UCM’S REACTION RESET REQUIRED
Evaporator Solution Flow Loss
The switch connected to the flow
proving switch input on a unit with a
Brazed Plate heat exchanger has
faile d CLOSED;
or
during power-up, a unit with a
Brazed Plate heat exchanger has
detected that older versions of
control modules are installed.
53
Page 54
System Testing & Troubleshooting
(PAR) An automatic reset
occurs after the Evap
Solution Flow Proving
Switch has detected
Solution flow for 6
continuous seconds.
(PAR) An automatic reset occurs
after the External Leaving Solution
Setpoint returns to its allowable
range. In order to prevent rapid
cycling of the Diagnostic, there is a
10 second delay before the
automatic reset.
When the Solution Flow Switch
input is detected OPEN
(no flow) for 6 continuous
seconds, the Unit will de-
energize
the following relays:
Compressor Relays, LPC
Bypass Relays, Liquid Line
Solenoids, and HGBP Relay.
While the diagnostic is active,
the Leaving Solution Setpoint
will revert to using the default
(HI) Leaving Solution Setpoint.
The diagnostic can occur at any time
after the Evaporator Solution Pump
Relay has been requested ON, and the
Solution Flow Switch input is detected
OPEN (no flow) for 5 continuous
minutes.
The External Leaving Solution Setpoint
(LSS) is designated as the Leaving
Solution Setpoint source and it is out of
range. Out of range is defined as one of
the following:
a) External LSS > 65 deg F or < 51 deg
F for unit with LSS Range 51-65 deg F.
b) External LSS > 50 deg F or < 40 deg
F for unit with LSS Range 40-50 deg F.
c) External LSS > 39 deg F or < 30 deg
F for unit with LSS Range 30-39 deg F.
d) External LSS > 29 deg F or < 20 deg
F for unit with LSS Range 20-29 deg F.
e) External LSS > 75 deg F or < 10 deg
F for unit with LSS Range SPECIAL.
DIAGNOSTIC DISPLAYED REASON FOR DIAGNOSTIC UCM’S REACTION RESET REQUIRED
Evap Solution Flow Proving Switch
Problem: Solution Flow Switch is
open after the Solution Pump is ON.
Check: Verify Solution Pump
operation and that the Evaporator
Solution Flow Switch is working
properly.
External Leaving Solution STP Input
Fail
Problem: CGM is receiving an
External Leaving Solution Setpoint
(LSS) Input signal which is out of
range. Check field/unit wiring
between CGM and External
Leaving Solution Setpoint
potentiometer.
54
Page 55
g
(PAR) An automatic reset occurs
g
after communication has been
restored.
System Testing & Troubleshooting
(PAR) An automatic reset occurs
after communication has been
restored.
The UCM will initiate the following
The CGM has lost communications
actions ;
with the GBAS Module.
ized.
a. If the Demand Limit input was
closed prior to communications
loss, then the Demand Limit
commands issued to the
Compressor Staging function
will be cancelled.
b. If any of the GBAS setpoint
control parameters are the
HI-selected setpoint sources,
then those setpoints will revert
to the default HI setpoints .
c. Any active GBAS output
control parameters will be
ignored.
d. A failsafe function in the GBAS
module will cause all GBAS
outputs to be zeroed and
de-ener
The UCM will initiate the following
actions ;
a. If the Demand Limit input was
closed prior to communications
loss, then the Demand Limit
commands issued to the
Compressor Staging function
will be cancelled.
b. If any of the GBAS setpoint
control parameters are the
HI-selected setpoint sources,
then those setpoints will revert
to the default HI setpoints .
c. Any active GBAS output
control parameters will be
ignored.
d. A failsafe function in the GBAS
The CGM has lost communications
with the GBAS Module.
module will cause all GBAS
ized.
outputs to be zeroed and
de-ener
DIAGNOSTIC DISPLAYED REASON FOR DIAGNOSTIC UCM’S REACTION RESET REQUIRED
GBAS 0-5VDC Module Comm
Failure
Problem: The CGM has lost
communications with the GBAS
Module.
Check: Check field/unit wiring
between CGM and GBAS.
GBAS 0-5VDC Module Comm
Failure
Problem: The CGM has lost
communications with the GBAS
Module.
Check: Check field/unit wiring
between CGM and GBAS.
55
Page 56
System Testing & Troubleshooting
expired.
expired.
(PAR ) An automatic reset occurs after
the Leaving Solution Temperature
decreas es 5 deg F or more below the
Hot Start Load Limit Setpoint.
(INFO ) An automatic reset occurs after
the Leaving Solution Temperature
decreas es 5 deg F or more below the
Hot Start Load Limit Setpoint.
(PMR) A manual reset is required after
this diagnostic oc curs. The Diagnostic
can be reset by the unit mounted
Human Interface Module or Tracer, or
by cycling power to the CGM.
(PAR ) An automatic reset occurs after
the designated Hot Start Load Limit
Setpoint source sends a signal that is
within range for 10 continuous seconds,
or after a different setpoint source is
user-defined.
While this diagnostic is active, the
second compressor on each
refrigerant circuit is shut off
and/or prevented from s taging
ON.
No change in unit operation
occurs. This diagnostic is for
information only.
Hot Operation Response is set to "50%
CAPACITY PER CKT, AUTO RESET
DIAG ". The Leaving Solution Temp
exceeded the Hot Start Load Limit
Setpoint after the Hot Start Time Interval
Hot Operation Response is set to
"ALLO W N ORMAL OPERATIO N, INFO
RESET DIAG". The Leaving Solution
Temp exceeded the Hot Start Load Limit
A "lockout all Ckts" request is
issued to the compressor staging
function. The Unit will deenergize
the following relays: Compressor
Relays, LPC Bypass Relays,
Liquid Line Solenoids, and HGBP
Relay . Comfort/Process C ooling,
and Ice Building are terminated
and prevented from oc curring
until the diagnostic condition is
cleared.
The default (HI) Hot Start Load
Limit Setpoint will become the
active setpoint while this
diagnostic is active.
Setpoint after the Hot Start Time Interval
Hot Operation Response is set to
"SHUT OFF COMPRESSORS,
MANUAL RESET DIAG ". The Leaving
Solution Temp exc eeded the Hot Start
Load Limit Setpoint after the Hot Start
Time Interval expired.
The unit is reading a signal that is out of
range for the Hot Start Load Limit
Setpoint.
DIAGNOSTIC DISPLAYED REASON FOR DIAGNOSTIC UCM’S REACTION RESET REQUIRED
Hot Start Load Limit (Auto)
Problem: The Leaving Solution
Temperature is too hot.
Hot Start Load Limit (Info)
Problem: The Leaving Solution
Temperature is too hot.
Hot Start Load Limit (Man)
Problem: The Leaving Solution
Temperature is too hot.
Hot Start Load Limit Setpoint Fail
Problem: The Hot Start Load Limit
Setpoint is out of range.
Check: If Hot Start Load Limit
Setpoint Source is ass igned to
either GBAS module, but this
setpoint has not been assigned to
one of that GBAS module’s
analog inputs, this diagnostic c an
occur.
56
Page 57
System Testing & Troubleshooting
g
(INFO) An automatic reset occurs after
the Circ uit 1 Saturated Liquid Pressure
Sensor input returns to its allowable
range. In order to prevent rapid cy cling
of the Diagnostic, there is a 10 second
(PAR) An automatic reset occurs after
the designated Leaving Solution
Setpoint returns to its allowable range.
In order to prevent rapid c ycling of the
Diagnostic, there is a 10 s econd delay
(PAR) An automatic reset occurs after
the designated Ice Build Terminate
Setpoint source sends a signal that is
within range for 10 continuous seconds,
or after a different setpoint source is
(PAR) An automatic reset occurs after
the difference between the active Ice
Build Terminate Setpoint and the
Leaving Solution Cutout Temp Setpoint
meets the minimum difference
requirement.
user-defined.
before the automatic reset.
delay before the automatic reset.
The Superheat/Subcool
calculation is invalid and the
vaiues are set to zero. No
other change in unit operation
occurs. This diagnos tic is for
(Pres sure < 0 PSIG or Pressure > 400
information only.
PSIG).
While the diagnostic is active,
the Leaving Solution Setpoint
will revert to using the default
The default (HI) Ice Build
Terminate Setpoint will become
the active setpoint while this
The active Ice Build Terminate
Setpoint is set to the Leaving
Solution Cutout Temp Setpoint
plus the larger of 1) calculated
Minimum Differential v alue, or
2) 6.5 deg F.
The active Ice Build Terminate Setpoint
and the Leaving Solution Cutout Temp
Setpoint are too close together for proper
unit operation.
The unit is reading a signal that is out of
diagnostic is active.
range for the Ice Build Terminate
Setpoint.
The designated Leaving Solution Setpoint
(HI) Leaving Solution Setpoint.
e SPECIAL.
The unit is reading a signal that is out of
range for the Circuit 1 Saturated Liquid
source is out of range. Out of range is
defined as one of the following:
a) LSS > 65 deg F or < 51 deg F for unit
with LSS Range 51-65 deg F.
b) LSS > 50 deg F or < 40 deg F for unit
with LSS Range 40-50 deg F.
c) LSS > 39 deg F or < 30 deg F for unit
with LSS Range 30-39 deg F.
d) LSS > 29 deg F or < 20 deg F for unit
with LSS Range 20-29 deg F.
e) LSS > 75 deg F or < 10 deg F for unit
with LSS Ran
Line Pressure Sensor input on the SSM.
DIAGNOSTIC DISPLAYED REASON FOR DIAGNOSTIC UCM’S REACTION RESET REQUIRED
IBTS Adjusted to Maintain Min Diff
Problem: The active Ice Build
Terminate Setpoint (IBTS) is
closer to the Leaving Solution
Ice Build Terminate Setpoint Fail
Problem: The Ic e Build Terminate
Cutout Temp Setpoint than the
calculated Minimum Differential.
Setpoint is out of range.
Liquid Pressure Sensor Fail
Circuit 1
Problem: Circuit 1 Saturated Liquid
Line Pressure sensor input is out
of range.
Check: Check field/unit wiring
Leaving Solution Setpoint Fail
Problem: The designated Leaving
Solution Setpoint is out of range.
If either GBAS module is
designated as the Leaving Solution
Setpoint source, verify that GBAS
module has this input assigned to
Check: If Ice Build Terminate
Setpoint Source is ass igned to
either GBAS module, but this
setpoint has not been assigned to
one of that GBAS module’s analog
inputs, this diagnostic can occur.
57
one of it’s analog inputs.
between Sens or and SSM.
Page 58
g
(INFO) An automatic reset occurs
g
g
g
after the Circuit 2 Saturated Liquid
System Testing & Troubleshooting
Pressure Sensor input returns to its
allowable range. In order to prevent
rapid cycling of the Diagnostic, there
is a 10 second delay before the
automatic reset.
(PAR) An automatic reset occurs
after the Outsid e Air Tem p
increases 5 deg F or more above
the Low Ambient Evaporator Pump
Override Temp Setpoint.
(PAR) An automatic reset occurs
after the Evaporator Solution
Temperature(s) rises 4 deg F or
more above the Low Solution Cutout
Temperature Setpoint.
(PMR) A manual reset is required
after this diagnostic occurs. The
Diagnostic can be reset by the unit
mounted Human Interface Module
or Tracer, or by cycling power to the
CGM.
(PMR) A manual reset is required
anytime after the Diagnostic is s et.
The Diagnostic can be reset by the
Human Interface or Tracer, or by
cycling power to the CGM.
nos tic is fo r inform ation
The Superheat/Subcool
calculation is invalid and the
vaiues are set to zero. No other
The unit is reading a signal that is out
of range for the Circuit 2 Saturated
Liquid Line Pressure Sensor input on
only.
change in unit operation occurs.
This di a
the SSM. (Pressure < 0 PSIG or
Pressure > 400 PSIG).
The Evaporator Solution Pump
The Outside Air (Am bient)
Relay is energized while this
condition exists.
temperature is below the Low
Ambient Evap Pump Override Temp
A "Lockout all Circuits" request is
issued to the Compressor
Staging Function. Compressors
are prevented from staging on
and the Unit will de-energize the
following relays: Compressor
Relays, LPC Bypas s Relays,
Liquid Line Solenoids, and
HGBP Relay.
A “Lockout Circuit # 1” request is
issued to the Compressor
Staging Control function. The
Compressor Relays, LPC
Bypass Relay, Liquid Line
Solenoid Relay, and Hot Gas
Bypass Relay for Circuit 1 are all
the time the LPC Bypas s Relay de-
energized. On a standard unit this is
de-energized.
the 45 PSIG LPC switch, but can be
20 PSIG or lower on units w ith a lower
Leaving Solution Setpoint range.
While this diagnostic is active,
Compressors are prevented
from staging on. The Unit will
deenergize the following:
Compressor Relays, LPC
Bypass Relays, Liquid Line
Solenoids, and HGBP Relay.
, the
Setpoint.
While no compressors were running,
the Evaporator Solution
Temperature(s) went below the Low
Solution Cutout Te m p Setp oi nt.
Evaporator Solution Temperature(s)
went below the Low Solution Cutout
While compressors were runnin
Temperature Setpoint.
With one or more compressors
running, the higher pressure of the
two LPC switches on Circuit 1 has
opened 6 times with the LPC Bypass
relay de-energized, or it was open at
DIAGNOSTIC DISPLAYED REASON FOR DIAGNOSTIC UCM’S REACTION RESET REQUIRED
Liquid Pressure Sensor Fail Circuit 2
(Circuit #2 40-60 Ton units only)
Problem: Circuit 2 Saturated Liquid
Line Pressure sensor input is out of
range.
Check: Check field/unit wiring
Low Ambient Evaporator Solution
Pump Override
between Sensor and SSM.
Solution Temperature is too
Problem: Outside Air Temp too low,
reques t So lution Pump to run to
keep Solution moving.
Low Solution Cutout Temperature
(Auto)
Problem: The Evaporator Leaving or
Enterin
low.
Low Solution Cutout Temperature
(Man)
Solution Temperature is too
Low Pressure Control Open -
Circuit 1
Problem: The refrigerant in Circuit 1
is cold and may cause the Solution
in the Chiller barrel to become too
cold. Also, there may be a state of
Problem: The Evaporator Leaving or
Enterin
low.
charge issue with Circuit 1.
58
Page 59
(PMR) A manual reset is required
g
g
System Testing & Troubleshooting
nostic is set.
The Diagnostic can be reset by
the Human Interface or Tracer, or
anytime after the Dia
by cycling power to the CGM.
(PAR) An automatic reset occurs
after the difference between the
active Leaving Solution Setpoint
and the Leaving Solution Cutout
Temperature Setpoint meets the
minimum difference requirement.
(PAR) An automatic reset occurs
after communication has been
restored.
(INFO) An automatic reset occurs
after the Circuit 1 Saturated Liquid
Temperature Sensor input returns
to its allowable range. In order to
prevent rapid cycling of the
Diagnostic, there is a 10 second
delay before the automatic reset.
The active Leaving Solution
Setpoint is set to the Leaving
Solution Cutout Temperature
Setpoint plus the calculated
A “Lockout Circuit # 2” request is
iss ued to the Compress or Staging
Control function. The Compressor
Relays, LPC Bypass Relay, Liquid
Line Solenoid Relay, and Hot Gas
Bypass Relay for Circuit 2 are all
de-energized.
The active Leaving Solution Setpoint
With one or more compressors
running, the higher pressure of the
two LPC switches on Circuit 2 has
opened 6 times with the LPC Bypas s
relay de-energized, or it was open at
the time the LPC Bypass Relay de-
energized. On a standard unit this is
the 45 PSIG LPC s witch, but c an be
20 PSIG or lower on units with a lower
and the Leaving Solution Cutout
Leaving Solution Setpoint range.
Minimum Differential value.
Temperature Setpoint are too close
together for proper unit operation.
Solution
A “Lockout” request is sent to the
Compressor Staging Control
function. The Liquid Line Solenoid
Relays and LPC Byp-energized.
The CGM has lost communications
with the MCM.
The Superheat/Subcool calculation
The Superheat/Subcool Module is
is inv alid and the values are set to
zero. No other c hange in unit
installed and the unit is reading a
signal that is out of range for the
operation occurs. This diagnostic
Circuit 1 Saturated Liquid Line
is for information only.
Temperature Sensor input on the
SCM/MCM. (Temp < -55 F or Temp >
209 F).
DIAGNOSTIC DISPLAYED REASON FOR DIAGNOSTIC UCM’S REACTION RESET REQUIRED
Low Pressure Control Open -
Circ uit 2 (Circuit #2 40-60 Ton units
only)
Problem: The refrigerant in Circuit 2
is cold and may cause the Solution in
the Chiller barrel to bec ome too cold.
Also, there may be a state of charge
iss ue with Circuit 2.
LSS Adjusted to Maintain Minimum
Differential
Problem: The ac tive Leavin
Setpoint (LSS) is closer to the
Leaving Solution Cutout Temp
Setpoint than the calculated
Minimum Differential.
MCM Communications Failure
(40-60 Ton units only)
Problem: The CGM has lost
communications with the MCM.
Check: Check field/unit wiring
between CGM and MCM.
Sat Liquid Temperature Sensor Fail
Circuit 1
Problem: Circuit 1 Saturated Liquid
Line Temperature sensor input is out
of range.
Check: Sensor resistance between
830 ohms (200 F) and 345.7Kohms
(-40 F). If not, check field/unit wiring
between Sens or and SCM/MCM.
59
Page 60
System Testing & Troubleshooting
g
(PAR) An automatic reset occurs
after communication has been
(INFO) An automatic reset occurs
after the Circuit 2 Saturated Liquid
Temperature Sensor input returns to
its allowable range. In order to
prevent rapid cycling of the
Diagnostic, there is a 10 sec ond
delay before the automatic res et.
restored.
(INFO) An automatic reset occurs
after the Circuit 1 Suction Line Temp
Sensor input returns to its allowable
range. In order to prevent rapid
cycling of the Diagnostic, there is a
10 second delay before the
automatic reset.
(INFO) An automatic reset occurs
after the Circuit 2 Suction Line
Temperature Sensor input returns to
its allowable range. In order to
prevent rapid cycling of the
Diagnostic, there is a 10 sec ond
delay before the automatic res et.
ized.
The Superheat/Subcool
calc ulation is invalid and the
values are set to zero. No other
change in unit operation occurs.
This diagnostic is for information
The Superheat/Subcool
calc ulation is invalid and the
values are set to zero. No other
change in unit operation occurs.
This diagnostic is for information
only.
The Superheat/Subcool Module is
installed and the unit is reading a
signal that is out of range for the
Circuit 2 Saturated Liquid Line
Temperature Sensor input on the
MCM. (Temp < -40 F or Temp > 200
F).
A “Lockout” request is s ent to the
Compressor Staging Control
function. The Liquid Line
The CGM has los t communications
with the SCM.
Solenoid Relays and LPC
Bypass Relays are de-
energized. A failsafe function in
the SCM will cause all SCM
outputs to be z eroed and de-
ener
The Superheat/Subcool Module is
installed and the unit is reading a
signal that is out of range for the
only.
Circuit 1 Suction Line Temp Sensor
input on the SCM/MCM. (Temp < -
40 F or Temp > 200 F).
The Superheat/Subcool
calc ulation is invalid and the
values are set to zero. No other
change in unit operation occurs.
This diagnostic is for information
only.
The Superheat/Subcool Module is
installed and the unit is reading a
signal that is out of range for the
Circuit 2 Suction Line Temperature
Sensor input on the MCM. (Temp < -
40 F or Temp > 200 F).
DIAGNOSTIC DISPLAYED REASON FOR DIAGNOSTIC UCM’S REACTION RESET REQUIRED
Saturated Liquid Temperature
Sensor Fail - Circuit 2
(Circuit #2 40-60 Ton units only)
Problem: Circ uit 2 Saturated Liquid
Line Temperature sensor input is out
of range.
Check: Sens or resistance between
830 ohms (200 F) and 345.7Kohms
(-40 F). If not, check field/unit wiring
between Sensor and MCM.
Suction Temp Sensor Fail - Circuit 1
Problem: Circ uit 1 Suction Line Temp
sensor input is out of range.
Check: Sens or resistance between
830 ohms (200 F) and 345.7Kohms
(-40 F). If not, check field/unit wiring
between Sensor and SCM/MCM.
Suction Temp Sensor Fail - Circuit 2
(Ckt #2 40-60 Ton units only)
Problem: Circ uit 2 Suction Line Temp
sensor input is out of range.
Check: Sens or resistance between
830 ohms (200 F) and 345.7Kohms
(-40 F). If not, check field/unit wiring
SCM Communications Failure
(20-30 Ton units only)
Problem: The CGM has lost
communications with the SCM.
Check: Check field/unit wiring
between CGM and SCM.
between Sensor and MCM.
60
Page 61
(INFO) An automatic reset occurs
after the Circuit 1 Suction Line
System Testing & Troubleshooting
Temperature Sensor input returns to
its allowable range. In order to
prevent rapid cycling of the
Diagnostic, there is a 10 s econd
delay before the automatic reset.
(INFO) An automatic reset occurs
after the Circuit 2 Suction Line
Temperature Sensor input returns to
its allowable range. In order to
prevent rapid cycling of the
Diagnostic, there is a 10 s econd
delay before the automatic reset.
(PAR) An automatic reset occurs
after communication has been
restored.
The Superheat/Subcool
calculation is invalid and the
values are set to zero. No other
change in unit operation occurs.
This diagnostic is for information
only.
The Superheat/Subcool Module is
installed and the unit is reading a
signal that is out of range for the
Circuit 1 Suction Line Temperature
Sensor input on the SCM/MCM.
(Temp < -40 F or Temp > 200 F).
DIAGNOSTIC DISPLAYED REASON FOR DIAGNOSTIC UCM’S REACTION RESET REQUIRED
Suction Temperature Sens or Fail -
Circuit 1
Problem: Circuit 1 Suction Line
Temperature sensor input is out of
range.
Check: Sensor resistance between
830 ohms (200 F) and 345.7Kohms
(-40 F). If not, check field/unit wiring
The Superheat/Subcool
calculation is invalid and the
values are set to zero. No other
change in unit operation occurs.
This diagnostic is for information
only.
The Superheat/Subcool Module is
installed and the unit is reading a
signal that is out of range for the
Circuit 2 Suction Line Temperature
Sensor input on the MCM. (Temp < -
40 F or Temp > 200 F).
between Sens or and SCM/MCM.
Suction Temperature Sens or Fail -
Circuit 2
(Ckt #2 40-60 Ton units only)
Problem: Circuit 2 Suction Line
Temperature sensor input is out of
range.
Check: Sensor resistance between
830 ohms (200 F) and 345.7Kohms
(-40 F). If not, check field/unit wiring
No Change in unit operation
occurs. The Superheat/Subcool
Module is used for monitoring
purposes only, and does not
affect unit operation. This
diagnostic is for information
only.
The CGM has lost communications
with the SSM.
between Sens or and MCM.
Superheat/Subcool Module Comm
Fail
Problem: The CGM has lost
communications with the
Superheat/Subcool Module (SSM).
Check: Check field/unit wiring
between CGM and SSM Module.
61
Page 62
System Testing & Troubleshooting
g
)
y
y
occurs after communic ation
with the TCI or LCI Module. setpoints provided by the network
the network has been designated
after comunications with the
communications with the
other
ed as an
setpoints provided by the
or ignored. Where the network
a. disallow any interaction after communication has been
communications with the
ineffective, and and H I interaction with the
mounted HI d isplay: LOCAL HI
COMMUNICATIONS
LOSS CHECK COMM LINK
WIRING BETWEEN
option, then on the remote
MODULES
(If the unit has a remote HI
HI module, this diagnostic
displa
will be reported and
automatic reset diagnostic).
DIAGNOSTIC DISPLAYED REASON FOR DIAGNOSTIC UCM’ S REACTION RESET REQUIRED
BAS Modul e Communications Failure CGM has lost communications All active commands and (PAR) An automatic reset
Problem: The RTM has lost through the TCI or LCI will be has been restored.
communications with the TCI or LCI. cancelled and/ or ignored. Where
Check: Check field/ unit wiring as setpoint source, local HI default
between RTM and TCI or LCI Module. setpoints will be used.
BAS/NETWORK Comm Fai lure The TCI or LC I has l ost Al l acti ve commands and (PAR) An automatic reset occurs
Probl em: The TCI o r LCI has lost network for > 15 minu tes. netwo rk throug h the TCI or network and TCI or LCI
communications with Tracer. LCI will be cancelled and/ has been restored.
control panel
Check: Network (Tracer or 3rd party has been designated as setpoint
building control panel) is powered up source, local HI default
and running properly. If so, check unit setpoints will be used.
wiring between TCI or LCI and network
(Tracer or 3rd party buildin
Unit HI Communications Failure The CGM has lost A failsafe function in the HI will; (INFO) An automatic reset occurs
62
communications with the U nit Interface. CGM (o r any other and the HI. When the fail ure
mounted (local) Human Interface modules), screen is cleared, the
(HI). b. render all HI keystrokes General display is restored
Check: Field/unit wiring between c. cause the following to be CGM is again permitted.
Problem: The CGM has lost unit-mounted Human between the HI and the
CGM and Local HI. displayed on the unit-
Page 63
be assigned:
capacity
• Evap Leaving Solution Temp • Ice Building • Hot Gas Bypass Relay
• ICS Defined Temp • Flow Proving • Alarm Relay
• Condenser Entering Solution Temp • Condenser Pump • Low Ambient Bypass 1 Relay
• Outdoor Air Temp Proving • Low Ambient Bypass 2 Relay
• Condenser Leaving Solution Temp • Solution Pump Relay
• Zone Temperature • Ice Making Relay
• ICS Temperature • ICS Relay
Module I/O Summary
UNIT MODULE ANALOG INPUTS ANALOG OUTPUTS BINARY INPUTS BINARY OUTPUTS
Cold Generator • External Leaving Solution Setpoint • None • Emergency Stop • Liquid Line Relay (Ckt #1)
Module (CGM) • Evap Entering Solution Temp • External Auto/Stop • Liquid Line Relay (Ckt #2)
Current Sensing • Compressor A, Phase A • None • None • None
Module (CSM) • Compressor A, Phase B
• Compressor B, Phase A
• Compressor B, Phase C
• Compressor C, Phase B
• Compressor C, Phase C
• Compressor D, Phase A
• Compressor D, Phase C
Generic Building Four inputs, which can be assigned: • None • Demand Limit Five outputs, which can
Automation System 0- • Occ Zone Cool Setpoint
63
5VDC (GBAS 0-5V) • Unocc Zone Cool Setpoint • Compressors running
Module • Occ Zone Heat Setpoint • Running at maximum
• Unocc Zone Heat Setpoint
• Supply Air Cooling Setpoint • Selected diagnostics
• Supply Air Heating Setpoint messages
• Space Static Pressure Setpoint
• SA Static Pressure Setpoint
• Min OA CFM Setpoint
• Leaving Solution Setpoint
• Ice Build Terminate Setpoint
• Hot Start Load Limit Setpoint
• Maximum Capacity Level Setpoint
Page 64
be assigned:
g
g
ned:
y
capacit
ned: can be assi
• Evap Te mp Ckt2
• ICS Defin ed Temp
• Liqu id Pressure Ckt1
• Suction Pressure Ckt1
• Liqu id Pressure Ckt2
• Suction Pressure Ckt2
• Active Cooling Capacity
• Outdoor Air Temp
• Saturated Liquid Temp Ckt1
be assi
• Saturated Liquid Temp Ckt2
(Low Ambient Ckt #1) • Compressor Proving (Ckt #2) • Compressor Relay K12
(Low Ambient Ckt #2) • Low Pressure Cutout (Ckt #2) • Compressor Relay K4
• Heater Tape
• Condenser Fan B
• High Pressure Control • Condenser Fan A
• Hot Start Load Limit Setpoint • Sat. Cond Temp Ckt1
• Maximum Capacity Level • Sat. Cond Temp Ckt2 • Selected diagnostics
Setpoint • Evap Temp Ckt1 messages
Module I/O Summary
UNIT MODULE ANALOG INPUTS ANALOG OUTPUTS BINARY INPUTS BI NARY OUTPUTS
10VDC (GBAS 0-10V) • Leaving Solution Setpoint • Leaving Soln Temp • Compressors running
Generic Building Four inputs, which can Four outputs, which can • Demand Limit One output, which
Module • Ice Build Terminate Setpoint • Entering Soln Temp • Running at maximum
Automation System 0-
Human Interface (HI) • None • None • None • None
Module
64
(Ckt #1)
• Evap/Suction Temperature • Condenser Fan Speed • Low Pressure Cutout(Ckt #1) • Compressor Relay K3
(Ckt #2)
• Saturated Condenser • High Pressure Control (Ckt #1) • Condenser Fan 1A
Temperature Sensor (Ckt #1) • High Pressure Control (Ckt #2) • Condenser Fan 1B
• Saturated Condenser • Condenser Fan 1C
Temperature Sensor (Ckt #2) • Condenser Fan 2A
• Saturated Liquid Temp (Ckt #1) • Condenser Fan 2B
• Saturated Liquid Temp (Ckt #2) • Condenser Fan 2C
Interprocessor • None • None • None • None
Communications
Bridge (IPCB) Module
Multiple Compressor • Evap/Suction Temperature • Condenser Fan Speed • Compressor Proving (Ckt #1) • Compressor Relay K11
Module (MCM)
Temperature
• Saturated Liquid Temperature
Single Compressor • Evap/Suction Temperature • Condenser Fan Speed • Compressor Proving • Compressor Relay K11
Module (SCM) • Saturated Condenser (Low Ambient) • Low Pressure Cutout • Compressor Relay K12
Page 65
• Suction Pressure Ckt #1
• Suction Pressure Ckt #2
Module I/O Summary
UNIT MODULE ANALOG INPUTS ANALOG OUTPUTS BINARY INPUTS BINARY OUTPUTS
Superheat/Subcool • Liquid Pressure Ckt #1 • None • None • None
Module (SSM) • Liquid Pressure Ckt #2
Trane Communication • None • None • None • None
Interface (TCI)
Module
LonTalk Communication • None • None • None • None
Interface (LCI) Module
65
Page 66
Index
Symbols
+ (Plus) Key...9 + (Plus) Key...10;
- (Minus) Key...9
- (Minus) Key...10; 115V Control Circuit Switch (1S1)...7;
Disconnecting Switches
24V Transformer Switch (1S70)...7;
Disconnecting Switches
See
Data Manipulation Keys
See
Data Manipulation Keys
See
See
Power
Power
A
Active Setpoint .........................................................5
AUTO Key ................................................................ 9
C
CANCEL Key ........................................................... 8
Cautions ................................................................... 4
Cold Generator Module ........................................... 6
Communications Link Problems ............................46
Compressor Module ................................................ 6
Compressor Protection Switch ................................ 5
CONFIGURATION Key ............................................ 8
CONFIGURATION Menu....................................... 36
Control Band ............................................................ 5
Control circuit switch (1S1) ...................................... 6
Control Parameters ................................................ 32
Control Point ............................................................ 5
Current Sensing Module .......................................... 6
CUSTOM Key .......................................................... 9
D
Data Manipulation Keys ........................................... 8
Deadband ................................................................ 5
DIAGNOSTICS Key ................................................. 8
Disconnect switch 1S14........................................... 6
E
Emergency Stop ...................................................... 5
ENTER Key.............................................................. 8
External Auto/Stop ................................................... 5
G
Generic Building Automation System ...................... 6
H
Head Pressure Control ..........................................26
HI module;
Human Interface Keypad ......................................... 8
See
Human Interface Module ......................................... 7
See
See
Figure 2
Figure 1
Human Interface Module
I
Ice Building ............................................................ 26
Information Format ................................................ 23
Interprocessor Communications Board ................... 6
Leaving Solution Setpoint ........................................ 5
Leaving Solution Temperature Control Point ........... 5
Literature Change History ........................................ 2
Loop Stabilization .................................................. 25
Low Ambient Compressor Lock-out ......................... 5
L
LonTalk .............................................................. 4,5,6
LonTalk Communication Interface
(LCI) module ........... 4,5,6,19,23,24,28,38,61,63
M
Manual disconnect switch 1S14 .............................. 6
See
Manual Disconnect Switch
Menu Keys ............................................................... 8
microelectronic control system ................................ 6
See
UCM Control System
Model Number Description ...................................... 4
Module I/O Summary ............................................. 62
N
NEXT Key ................................................................ 9
No Configuration ...................................................... 7
See
non-Trane building control systems;
Module
Generic BAS
66
Page 67
P
PREVIOUS Key ....................................................... 9
R
Remote Human Interface ........................................ 5
See
Interprocessor Communication Module
Reset Amount Maximum ......................................... 5
Reset End Temperature ........................................... 5
Reset Start Temperature.......................................... 5
S
SCM or MCM;
SERVICE MODE Key .............................................. 8
SERVICE MODE Menu .........................................39
Setpoint Source Selection ..................................... 34
SETPOINTS Key ..................................................... 8
SETUP Menu ........................................................23
SETUP Key .............................................................. 8
STATUS Key ............................................................ 8
STATUS Menu ....................................................... 15
STOP Key ................................................................ 9
Superheat & Subcooling Module ............................. 6
See
Compressor Module
T
TEST START Key (SERVICE) ............................... 9
Trane Communications Interface Module.............. 6
See
Trane integrated comfort systems;
Communications Interface Module
Transformer switch 1S70 ....................................... 6
Trane
U
Unit Control Module ...............................................5
Unit Nameplate ......................................................4
Unit Operation Keys ............................................... 9
Unit Status (Unit Off or Stopped) ........................... 7
Unit Status (Unit On) .............................................. 7
W
Warnings ................................................................ 4
67
Page 68
68
Loading...