Models: 50 or 60 Hz
CGAD020C CGAD040C CGAD070C CGAD100C
CGAD025C CGAD050C
CGAD030C CGAD060C
Junho 2006
CGAD080C CGAD120C
CGAD090C CGAD150C
CG-PRC002A-EN
Introduction
CGAD
Air-Cooled
Liquid Chillers
Designed for great performance.
Built to last.
For more than 40 years Trane has
been using the best resources available
on development engineering, production
and marketing to produce quality equipments.
All this tradition and know-how were
gathered to develop the new generation of
CGAD liquid chillers 20 to 150 Tons,
equipped with scroll compressors.
3 = 220V/60Hz/3ph - no accessories
K = 380V/60Hz/3ph - no accessories
4 = 440V/60Hz/3ph - no accessories
H = 380V/50Hz/3ph - no accessories
R = 220V/60Hz/3ph - with circuit breaker
S = 380V/60Hz/3ph - with circuit breaker
T = 440V/60Hz/3ph - with circuit breaker
U = 380V/50Hz/3ph - with circuit breaker
V = 220V/60Hz/3ph - with disconnect
switch
X = 380V/60Hz/3ph - with disconnect
switch
Y = 440V/60Hz/3ph - with disconnect
switch
Z = 380V/50Hz/3ph - with disconnect switch
Digit 10 - Refrigerant Type
2 = Refrigerant R-22
4 = Refrigerant R-407C
Digit 11 - Piping Configuration
0
= Standard Piping
A = Piping with Service Valves
in Suction and Discharge Lines.
B
= Piping with Solenoid Valve
C = Piping with Solenoid Valve and
Service Valves in Suction and
Discharge Lines.
Digit 12 - CH-530 Control Modules
0=Standard Control Module
1 = With Alarm Relay
2 = With Remoto Setpoint Adjustment
3 = With Ice Making / Demand Limit
4 = With Communication COMM3
5 = With Alarm + External Setp.
6 = With Alarm + Ice Making / Demand Limit
7 = With Alarm + Communication COMM3
8 = External Setp. + Ice Making / Demand Limit
9 = External Setp. + Communication COMM3
A = Ice Making / Demand Limit + COMM3
B = Alarm + Ext. Setp. + Ice Making /Dem. Lim.
C = Alarm + Ext. Setp. + COMM3
D = Alarm + Ice Making/Dem. Lim + COMM3
E = Ext. Setp. + Ice Making/Dem. Lim. + COMM3
F = All modules
Digit 13 - Coil Type
A = Coil with Aluminum Fins
S = Coil with Special protection
(Yellow Fin)
Digit 14 - Expansion Valve
T = Thermostatic Expansion Valve
E = Electronic Expansion Valve (only R-22)
Digits 15 and 16 - Accessories
4
Contact the Marketing Department.
The product code describes optional configuration, capacity and features. It is very important to
indicate the correct order of the equipment code in order to avoid future problems in the shipment.
Each digit of the product code is described above.
CG-PRC002A-EN
General
Nominal Capacity
Nominal System
Nominal Current
Nominal Capacity
Nominal System
Nominal Current
CSHA100
CSHA100
CSHA100
CSHA100
Nominal Capacity
Storage Volume
Min. water flow
Max. water flow
Total face area
Operating weight
Shipping weight
Refrigerant type
Capacity stages
Data
Tab. 01 - General Data - CGAD 20-90 TR - 50 or 60 Hz
Model
60 Hz
(2)
(2)
kW/Tons
kW/Tons
Standard
Optional
Efficiency
50 Hz
Efficiency
Compressor
Model
Type
Quantity2
Evaporator
Inlet connection
Outlet connection
Condenser
Type
No. of coils222444444444
Fins per inches
No. of rows
Fans
Quantity23346668868
Diameter
Air flow
RPMRPM
Motor power
Transmission typeDirectDirectDirectDirectDirectDirectDirectDirectDirectDirectDirectDirect
(1 ) D a t a b as e d o n o p er a tio n co nd itio n s a c o rd ing to s t a n d a rt ARI 59 0 - 9 2
(2 ) T h e s e cu r re n t v a lues ref e r to
(3 ) T h e s e va lues to th e glo b a l e q u ip m en t c o n s u m p ti o n ( c o m p ress o r s a n d fa n s)
(4 ) T h e s e cu r re n t v a lues ref e r to 3 8 0 V / 50 H z power su p p l y
(5 ) T h e measu r e m e n ts shown take in t o a c c o u n t th e depth of t he e letric a l fra m e coup l e d to the e q u ipment (s e e p a g e 27 o f thi s m an u a l)
(6 ) T h e floor are a measu r e m e n ts d o n o t take in to a c c o nt the b a s e o f the e lectric a l fr a m e co u p led to the e q u ip m en t .
220 V / 6 0 H z
pow e r su p p ly
CG-PRC002A-EN
5
Selection
Procedures
Liquid chiller capacity tables 03 and 04, on
pages 11 and 12 show the most frequent
leaving water temperatures. The table
reflects a temperature drop of 5,5 ºC (10ºF)
through the evaporator. For low temperature selections, refer to figures 04 and 05
for Adjustment Factors of Ethylene and
Propylene Glycol.
To select a CGAD Air-Cooled Liquid Chiller
Trane, the following information is
required:
1
Thermal project load of project in tons of
cooling.
2
Chilled water temperature project drop.
3
Leaving chilled water project temperature.
4
Project ambient temperature and refrigerant type.
The evaporator flow is determined
through the following formulas:
GPM =
L/s =
NOTE 1:
The flow should be within the limits
specified in table 01, General Data
(page 05).
Tons X 24
Temperature drop (°F)
kW (Capacity) X 0,239
Temperature drop (°C)
Selection example:
Data:
System load required= 70 Tons.
Leaving chilled water temp. = 7ºC
Chilled water temperature drop = 5,5ºC
(10°F)
Project ambient temperature = 35ºC
1
Calculate the required chilled water flow
using the formula below:
GPM =
70 Tons x 24
10ºF
2
Using table 03 (Performance Data - R-22), a
CGAD 080 unit at these conditions will
output 76,2 Tons with a compressor
consumption of 81,1 kW.
3
Determine the evaporator pressure drop
using the flow and the evaporator water
pressure drop curves, figure 05.
Introducing the curve at 168 GPM, the
pressure drop for an evaporator with the
nominal value of 80 Tons is 9 ft, or 2,74 m.
4
For selection of low temperature units, or
applications in which the altitude is
significantly above sea level, or the
temperature drop is different from 5,5 ºC,
contact a local Trane engineer for further
information.
= 168 GPM
For example:
Corrected capacity = Capacity (not
adjusted) x Glycol Capacity Adjustment
Factor
Corrected Flow = Flow (not adjusted) x
Glycol Flow Rate Adjustment Factor
5
The final unit selection is: CGAD 080B
Refrigerant Type: R-22
Cooling capacity =76,2 Tons.
Entering temperatures = 12,5 °C
Leaving chilled water temperature = 7ºC
Chilled water flow =168 GPM
Evaporator pressure drop =2,74 m
Compressor consumption = 81,1 kW
NOTE 2:
Minimum leaving chilled water temperature setpoint
The minimum leaving chilled water
temperature setpoint is 4ºC. For applications where a lower setpoint is required, a
glycol solution must be used. Contact the
local Trane engineer for further information.
Note:
The selection above is an example for manual equipment selection. Please note that a more accurate data check is required for a correct selection.
6
CG-PRC002A-EN
Application
Considerations
Unit Sizing
Unit capacities are listed in the Performance Data section. Intentionally oversizing a unit to assure adequate capacity is
not recommended. The excess in the
system and compressor capacity calculation results in an over-sized liquid chiller. In
addition, an oversized unit is usually more
expensive to purchase, install and operate.
If over-sizing is desired, consider using two
units.
Unit Placement
1
Setting the Unit
2
Isolation and Sound Transmissions
The most effective isolation solution is to
locate the unit away from any sound
sensitive area. Structurally transmitted
sound can be reduced by vibration
eliminators. Spring isolators have proved
to be of little efficiency in CGAD Air-Cooled
Liquid Chiller installations and thus are not
recommended. An acoustical engineer
should always be consulted on applications with critical acoustic reduction levels.
For maximum isolation, water lines and
electrical conduits should also be isolated.
Wall sleeves and rubber-isolated piping
hangers can be used to reduce the sound
transmitted through water piping. To
reduce the sound transmitted through
electrical conduits, use flexible electrical
conduits. State and local codes on sound
emissions should always be considered.
As the environment in which a sound
source is located affects the sound
pressure, unit placement must be
carefully evaluated.
Two conditions should be avoided in order
to achieve optimum performance: warm air
recirculation and coil starvation.
Warm air recirculation occurs when the
airflow from the condenser fans discharged
back at the condenser coil inlet, due to
installation site restrictions.
B - Provide Vertical Clearance
C - Provide Side Clearance
D - Provide enough clearance between devices
Coil starvation occurs when the free airflow
to the condenser coil is restricted. Both
warm air recirculation and coil starvation
cause reductions in unit efficiency and
capacity, due to the associated high
discharge pressures. See page 24 (Maintenance and air circulation clearances).
4
Unit Location
A
General
Unobstructed airflow for the condenser is
essential to assure efficient operation and
the liquid chiller capacity. When determining unit placement, careful considerations
must be given to assure enough air flow
across the condenser heat-transfer
surface.
CG-PRC002A-EN
E -Installations in locations surrounded by walls
7
Application
Considerations
Evaporator hydraulic piping
components
The figure below shows how to proceed
with the installation of the water piping.
An air purge is placed on the evaporator
and at the water outlet. Provide additional
air purges at high piping points to release
it from the chilled water system.
Evaporator Drain
The evaporator drain connection must be
piped to an available strainer in order to
drain the evaporator even during operation. Install a gate valve in the drain line.
Thermometers and
Manometers
It is essential to install thermometers (items 5 and 12 in the figure) and
manometers (item 9) at the chilled water
inlet and outlet. These instruments must
be installed close to the unit, with a maximum scale of 1°C for thermometers and
0,1 kgf/cm2 for manometers.
Important: In order to avoid evaporator
damages, do not exceed a 150-psig water pressure.
The manometer with connection should
be installed at water inlet and outlet according to item 9 in the figure below in order
to avoid reading mistakes. Manometers
and thermometers must be installed at the
appropriate height to avoid parallax errors*.
Thermometers must be of glass or mercury-scale type, with colored contrasting
fluid, and provide easy reading.
- Manometers must be equipped with
siphons;
- Install gate valves to isolate the manome-
ters when they are not being used.
Use piping joints to facilitate assembly and
disassembly services.
Inlet and outlet must be equipped with
gate valves to isolate the evaporator during
service, and a globe valve must be installed at the outlet to adjust the water flow.
Flow-Switch
Verify that safety interlockings, particularly
the flow-switch, are installed in straight and
horizontal runs, with vanes adequate to the
pipe diameter, and the distance from curves and valves must be at least 5 times its
diameter, on each side.
Water treatment
The use of untreated or improperly treated
water may result in scaling, erosion, corrosion, algae and slime. The services of a
qualified water treatment specialist should
be engaged to determine what treatment,
if any, is advisable. Trane do Brasil assumes
no responsibility for equipment failures
resulting from the use of untreated or
improperly treated water.
8
9
1
2
3
4
5
Fig. 01 - Components
* Parallax error: Apparent displacement of an object, when the observation point changes. It is especially said of the apparent deviation of a measure instrument needle, when it is
not observed from a vertical point of view (parallax error).