Trane CAUC-C20, CAUC-C60, CAUC-C40, CAUC-C30, CAUC-C80 User Manual

...
Air-Cooled Condensers
20 to 120 Tons
April 200 1
ACDS-PRC00 1 -EN

Introduction

Trane has the r ight condenser...If you are
designing a new system or replacing an existing air -cooled condenser , T rane can satisfy virtually any application need. Whether coupled with an industrial compressor, a single zone commercial self-contained unit, compressor chiller or a Cold Generator the right air -cooled condenser for the job. When teamed with any one of a
®
chiller , T rane has
wide range of compressor -evaporator combinations, Trane air-cooled condensers, available in 20 to 120 tons, are ideal for multistory office buildings, hotels, schools, municipal and industrial facilities.
©American Standard Inc. 2001
ACDS-PRC001-EN
Contents
Introduction Featur es and Benefits
Application Considerations Selection Procedur e
Model Number Description
General Data P erformance Data
Performance Adjustment Factors
Electric P o wer Dimension and Weights Mechanical Specifications
2 4
5 6
8 9
11 10 12
13
23
ACDS-PRC001-EN
3

Features and Benefits

20 to 120 T on Units
T rane 20 to 120 ton air-cooled condensers have an operating range of 40 F to 115 F, with a low ambient option down to 0 F.
The control panel is factory-installed and wired to prevent potential damage and to provide weathertight protection.
The control panel contains:
fan motor contactors.
fan cycling controls.
terminal point connection for
compressor interlock.
115-volt control power transformer .
These standard features reduce installation costs and provide easy interface with control logic.
Application
All Trane air-cooled condenser coils are tube-in-sheet construction with copper tubing mechanically bonded to configurated aluminum fins. 20 to 30 ton condensers are single circuit; 40 to 120 ton units are dual circuited; all feature integral subcooling.
Copper coils are optional.
Durable Construction
T rane 20 to 120 ton condensers are built for long life. The unit frame is constructed of 14 gauge g alvanized steel. Louvered panels provide excellent coil protection while enhancing unit appearance and strength. The unit surface is phosphatized and finished with T rane Slate Grey air -dry paint. This air dry­paint finish exceeds 500 consecutive hour salt spray resistance in accordance with AS TM B117.
Considerations
Certain application constraints should be considered when sizing, selecting, and installing air -cooled condensers. Unit and system reliability depends on properly and completely acknowledging these considerations. Consult your local T rane sales engineer if your application varies from these guidelines.
Setting the Unit
A base or foundation is not required if the selected unit location is level and strong enough to support the operating weight. Refer to the Weights section for the weight of individual units.
Isolation and Sound Emission
The most effective method of noise isolation is proper unit location. Units should be placed away from noise sensitive areas. Structurally transmitted noise can be reduced with the use of spring isolators and they are recommended for acoustically sensitive applications. Flexible electrical conduit, for maximum isolation effectiveness, will
reduce sound transmitted through electrical conduit.
State and local codes on sound emissions should always be considered. Since the environment in which a sound source is located affects sound pressure, unit placement must be carefully evaluated.
Servicing
Recommended minimum space envelopes for servicing are located in the Dimensional Data section and serve as guidelines for providing adequate clearance. The minimum space envelopes also allow for control panel door swing and routine maintenance requirements.
ACDS-PRC001-EN4
Application Considerations
Unit Location
Unobstructed flow of condenser air is essential to maintaining capacity and operating efficiency . When determining unit placement, careful consideration must be given to assure a sufficient flow of air across the condenser heat transfer surface. Two detrimental conditions are possible and must be avoided: Warm air recirculation and coil starvation.
Warm air recirculation occurs when discharge air from the condenser fans is recycled back at the condenser coil inlet. Coil starvation occurs when free airflow to the condenser is restricted.
Both warm air recirculation and coil starvation cause reductions in unit efficiency and capacity because of the higher head pressures associated with them. In more severe cases, nuisance unit shutdowns will result from excessive head pressures.
Cross winds, those perpendicular to the condenser, tend to aid ef ficient operation in warmer ambient conditions. However, they tend to be detrimental to operation in lower ambients or when hot gas bypass is used due to the accompanying loss of adequate head pressure. As a result, it is advisable to protect air -cooled condensers from continuous direct winds exceeding 10 miles per hour.
Debris, trash, supplies, etc., should not be allowed to accumulate in the vicinity of the air -cooled condenser. Supply air movement may draw debris into the condenser coil, blocking spaces between coil fins and causing coil starvation. Special consideration should be given to low ambient units. Condenser coils and fan discharge must be kept free of snow or other obstructions to permit adequate airflow for satisfactory unit operation.
Clearance
V ertical condenser air discharge must be unobstructed. While it is dif ficult to predict the degree of warm air recirculation, a unit installed with a ceiling or other obstruction above it will lose capacity and the maximum ambient operation will be reduced. Nuisance high head pressure tripouts may also occur.
The inlet to the coil must also be unobstructed. A unit installed closer than the minimum recommended distance to a wall or other vertical riser may experience a combination of coil starvation and warm air recirculation, resulting in unit capacity and efficiency reductions, as well as possible excessive head pressures. The recommended lateral distances are listed in the Dimensional Data section.
V oltag e
Nominal voltage is the nameplate rating voltage. The actual range of line voltages at which the equipment can satisfactorily operate is given below:
Nominal Voltage
Voltage Utilization Range 200/220 180-220 or 208-254
460 416-508 575 520-635
200/230-volt units ship from the factory set for operation in the 180 through 220­volt range. By c hanging leads on unit transformers, the unit will operate in the 208 through 254-volt range.
Effects of Altitude
The tables in the Performance Data section are for use at sea level. At elevations substantially above sea level, the decreased air density will decrease condenser capacity. R efer to the Performance Adjustment F actors section to correct performance at other altitudes.
Ambient Limitations
T rane condensers are designed for year­around applications in ambients from 0 F through 115 F. For operation below 0 F or above 115 F, contact the local Trane sales office.
Start-up and operation of Trane condensers at lower ambient temperatures require that sufficient head pressure be maintained for proper operation. Minimum operating ambient temperatures for standard unit selections and units with hot gas bypass are shown in the General Data section. These temperatures are based on still conditions (winds not exceeding five mph.) Greater wind velocities will result in a drop in head pressure, therefore, increasing the minimum starting and operating ambient temperatures.
Units with the low ambient option are capable of starting and operating in ambients down to 0 F, 10 F with hot gas bypass. Optional low ambient units use a condenser fan damper arrangement that controls condenser capacity by modulating in response to head pressure.
Maximum cataloged ambient temperature operation of a standard condenser is 115 F. Operation at design ambients above 115 F can result in excessive head pressures. For operation above 115 F, contact the local Trane sales office.
5ACDS-PRC001-EN
Selection Pr ocedures
When selecting a combination of equipment, it becomes necessary to match the compressor and condenser performance. The following procedure should be used in determining the correct condenser .
First:
Determine the total cooling load and the evaporator sst and compressor required.
Example:
Given – Total cooling load = 96 tons
The compressor was selected from COM-DS-1 catalog according to the sst and maximum acceptable condensing temperature for adequate compressor capacity.
a
Plot at least two gross compressor capacities (less subcooling) at the design suction temperature and different condensing temperatures. (subcooling factor is .047% per deg. F subcooling, 16
F for CU AB-D10E) Example: (From COM-DS-1) CUAB-D1 0E Compressor at 45 F sst.
With: 1 15 F condensing temperature = 113.5
tons divided by 1.075 subcooling factor =
105.6 tons. With: 125 F condensing temperature = 105.1
tons divided by 1.075 subcooling factor =
97.8 tons b
Plot two gross condenser heat rejection points on chart PD-1 divided by the compressor N factor (Table PD-1 to PD-3) at different condensing temperatures.
Example: Anticipating 100 ton condenser to meet design load of 96 tons.
Cond. Temp ITD (MBh) = Tons ÷ N F actor = Tons
11 5 at 20 = 830 = 69.2 ÷ 1.25* = 55.4 125 at 30 = 1285 = 107.1 ÷ 1.30* = 82.3
– Ambient temp = 95 F – Evaporator sst = 45 F – Compressor – CUAB-D1 0E
Gross Heat of Rejection
c
T ransfer the results from the compressor and condenser plots to Chart SP-1 and do the following. Draw a line through the two points representing gross heat compressor capacities less subcooling (1 05.6 and 82.3). Draw a line through the two points representing condenser gross heat of rejection (55.4 and 82.3).
d
At the point of intersection of the compressor and condenser lines draw dashed lines to the left and bottom margins of Chart SP-1. The end points of these lines will show a resultant gross condenser capacity of 93.8 tons at 129.4 F condensing temperature.
e
From c hart PD-2 calculate the percent increase in capacity due to subcooling.
Example:
At 95 F ambient and 129.4 F condensing temperature there is a 10.1% increase in capacity due to subcooling. This yields a system net capacity of 93.8 tons x 110% = 1 03.2 tons.
f
If necessary use the values in Table PD-4 to adjust the system capacity for altitude.
g
Compare this result with the design capacity and condensing temperature.
The required cooling load is 96 tons, therefore, the CAUC-D1 0 is the proper selection.
Repeat the process steps B through G as necessary to achieve the most economic condenser selection.
*N factor corrected from Table PD-2 sst – saturated suction temperature F – degree Fahrenheit N – compressor factor ITD – initial temperature difference
ACDS-PRC001-EN6

Selection Example

Chart SP-1 — Selection Example
7ACDS-PRC001-EN

Model Number Description

20 To 60 Ton Model Nomenclature
Digit 1 — Unit Type
C = Condenser
Digit 2 — Condenser
A = Air-Cooled
Digit 3 — Airflow
U = Upflow
C A U C C20 4 1 * 0 3 H 0
1 2 3 4 5,6,7 8 9 10 11 12 13 14
Digit 4 — Development Sequence
C = Third
Digit s 5,6,7 — Nominal Capacity
C20 = 20 Tons C40 = 40 Tons C25 = 25 Tons C50 = 50 Tons C30 = 30 Tons C60 = 60 Tons
Digit 8 — Power Supply
G = 200/230/60/3 XL 4 = 460/60/3 XL 5 = 575/60/3 XL
Digit 9 — Condenser Circuit
1 = Single (20-30 Ton) 2 = Dual (40-60 Ton)
Digit 10 — Design Sequence
* = Factory Assigned
Digit 1 1 — Ambient Control
0 = Standard 1=0 F
Digit 12 — Agency Approval
0 = None 3 = UL/CSA
Digits 13, 14 — Miscellaneous
H = Copper Fins 1 = Spring Isolators 2 = Rubber Isolators
1
80 T o 120 Ton Model Nomenclature
C A U C C80 4 2 A 0 3 H 0
1 2 3 4 5,6,7 8 9 10 11 12 13 14
Digit 1 — Unit Type
C = Condenser
Digit 2 — Condenser
A = Air-Cooled
Digit 3 — Airflow
U = Upflow
1. The service digit for each model number contains 14 digits; all 14 digits must be referenced.
Digit 4 — Development Sequence
C = Third
Digits 5,6,7 — Nominal Capacity
C80 = 80 Tons D10 = 100 Tons D12 = 120 Tons
Digit 8 — Power Supply
F = 230/60/3 4 = 460/60/3 5 = 575/60/3 E = 200/60/3
Digit 9 — Condenser Circuit
2 = Dual Circuit
Digit 10 — Design Sequence
A = First
1
Digit 1 1 — Ambient Control
0 = Standard 1 = 0 F
Digit 12 — Agency Approval
0 = None 2 = CSA 3 = UL/CSA
Digits 13, 14 — Miscellaneous
H = Copper Fins 1 = Spring Isolators
ACDS-PRC001-EN8
Loading...
+ 16 hidden pages