Trane CAUC-C20, CAUC-C60, CAUC-C40, CAUC-C30, CAUC-C80 User Manual

...
Air-Cooled Condensers
20 to 120 Tons
April 200 1
ACDS-PRC00 1 -EN

Introduction

Trane has the r ight condenser...If you are
designing a new system or replacing an existing air -cooled condenser , T rane can satisfy virtually any application need. Whether coupled with an industrial compressor, a single zone commercial self-contained unit, compressor chiller or a Cold Generator the right air -cooled condenser for the job. When teamed with any one of a
®
chiller , T rane has
wide range of compressor -evaporator combinations, Trane air-cooled condensers, available in 20 to 120 tons, are ideal for multistory office buildings, hotels, schools, municipal and industrial facilities.
©American Standard Inc. 2001
ACDS-PRC001-EN
Contents
Introduction Featur es and Benefits
Application Considerations Selection Procedur e
Model Number Description
General Data P erformance Data
Performance Adjustment Factors
Electric P o wer Dimension and Weights Mechanical Specifications
2 4
5 6
8 9
11 10 12
13
23
ACDS-PRC001-EN
3

Features and Benefits

20 to 120 T on Units
T rane 20 to 120 ton air-cooled condensers have an operating range of 40 F to 115 F, with a low ambient option down to 0 F.
The control panel is factory-installed and wired to prevent potential damage and to provide weathertight protection.
The control panel contains:
fan motor contactors.
fan cycling controls.
terminal point connection for
compressor interlock.
115-volt control power transformer .
These standard features reduce installation costs and provide easy interface with control logic.
Application
All Trane air-cooled condenser coils are tube-in-sheet construction with copper tubing mechanically bonded to configurated aluminum fins. 20 to 30 ton condensers are single circuit; 40 to 120 ton units are dual circuited; all feature integral subcooling.
Copper coils are optional.
Durable Construction
T rane 20 to 120 ton condensers are built for long life. The unit frame is constructed of 14 gauge g alvanized steel. Louvered panels provide excellent coil protection while enhancing unit appearance and strength. The unit surface is phosphatized and finished with T rane Slate Grey air -dry paint. This air dry­paint finish exceeds 500 consecutive hour salt spray resistance in accordance with AS TM B117.
Considerations
Certain application constraints should be considered when sizing, selecting, and installing air -cooled condensers. Unit and system reliability depends on properly and completely acknowledging these considerations. Consult your local T rane sales engineer if your application varies from these guidelines.
Setting the Unit
A base or foundation is not required if the selected unit location is level and strong enough to support the operating weight. Refer to the Weights section for the weight of individual units.
Isolation and Sound Emission
The most effective method of noise isolation is proper unit location. Units should be placed away from noise sensitive areas. Structurally transmitted noise can be reduced with the use of spring isolators and they are recommended for acoustically sensitive applications. Flexible electrical conduit, for maximum isolation effectiveness, will
reduce sound transmitted through electrical conduit.
State and local codes on sound emissions should always be considered. Since the environment in which a sound source is located affects sound pressure, unit placement must be carefully evaluated.
Servicing
Recommended minimum space envelopes for servicing are located in the Dimensional Data section and serve as guidelines for providing adequate clearance. The minimum space envelopes also allow for control panel door swing and routine maintenance requirements.
ACDS-PRC001-EN4
Application Considerations
Unit Location
Unobstructed flow of condenser air is essential to maintaining capacity and operating efficiency . When determining unit placement, careful consideration must be given to assure a sufficient flow of air across the condenser heat transfer surface. Two detrimental conditions are possible and must be avoided: Warm air recirculation and coil starvation.
Warm air recirculation occurs when discharge air from the condenser fans is recycled back at the condenser coil inlet. Coil starvation occurs when free airflow to the condenser is restricted.
Both warm air recirculation and coil starvation cause reductions in unit efficiency and capacity because of the higher head pressures associated with them. In more severe cases, nuisance unit shutdowns will result from excessive head pressures.
Cross winds, those perpendicular to the condenser, tend to aid ef ficient operation in warmer ambient conditions. However, they tend to be detrimental to operation in lower ambients or when hot gas bypass is used due to the accompanying loss of adequate head pressure. As a result, it is advisable to protect air -cooled condensers from continuous direct winds exceeding 10 miles per hour.
Debris, trash, supplies, etc., should not be allowed to accumulate in the vicinity of the air -cooled condenser. Supply air movement may draw debris into the condenser coil, blocking spaces between coil fins and causing coil starvation. Special consideration should be given to low ambient units. Condenser coils and fan discharge must be kept free of snow or other obstructions to permit adequate airflow for satisfactory unit operation.
Clearance
V ertical condenser air discharge must be unobstructed. While it is dif ficult to predict the degree of warm air recirculation, a unit installed with a ceiling or other obstruction above it will lose capacity and the maximum ambient operation will be reduced. Nuisance high head pressure tripouts may also occur.
The inlet to the coil must also be unobstructed. A unit installed closer than the minimum recommended distance to a wall or other vertical riser may experience a combination of coil starvation and warm air recirculation, resulting in unit capacity and efficiency reductions, as well as possible excessive head pressures. The recommended lateral distances are listed in the Dimensional Data section.
V oltag e
Nominal voltage is the nameplate rating voltage. The actual range of line voltages at which the equipment can satisfactorily operate is given below:
Nominal Voltage
Voltage Utilization Range 200/220 180-220 or 208-254
460 416-508 575 520-635
200/230-volt units ship from the factory set for operation in the 180 through 220­volt range. By c hanging leads on unit transformers, the unit will operate in the 208 through 254-volt range.
Effects of Altitude
The tables in the Performance Data section are for use at sea level. At elevations substantially above sea level, the decreased air density will decrease condenser capacity. R efer to the Performance Adjustment F actors section to correct performance at other altitudes.
Ambient Limitations
T rane condensers are designed for year­around applications in ambients from 0 F through 115 F. For operation below 0 F or above 115 F, contact the local Trane sales office.
Start-up and operation of Trane condensers at lower ambient temperatures require that sufficient head pressure be maintained for proper operation. Minimum operating ambient temperatures for standard unit selections and units with hot gas bypass are shown in the General Data section. These temperatures are based on still conditions (winds not exceeding five mph.) Greater wind velocities will result in a drop in head pressure, therefore, increasing the minimum starting and operating ambient temperatures.
Units with the low ambient option are capable of starting and operating in ambients down to 0 F, 10 F with hot gas bypass. Optional low ambient units use a condenser fan damper arrangement that controls condenser capacity by modulating in response to head pressure.
Maximum cataloged ambient temperature operation of a standard condenser is 115 F. Operation at design ambients above 115 F can result in excessive head pressures. For operation above 115 F, contact the local Trane sales office.
5ACDS-PRC001-EN
Selection Pr ocedures
When selecting a combination of equipment, it becomes necessary to match the compressor and condenser performance. The following procedure should be used in determining the correct condenser .
First:
Determine the total cooling load and the evaporator sst and compressor required.
Example:
Given – Total cooling load = 96 tons
The compressor was selected from COM-DS-1 catalog according to the sst and maximum acceptable condensing temperature for adequate compressor capacity.
a
Plot at least two gross compressor capacities (less subcooling) at the design suction temperature and different condensing temperatures. (subcooling factor is .047% per deg. F subcooling, 16
F for CU AB-D10E) Example: (From COM-DS-1) CUAB-D1 0E Compressor at 45 F sst.
With: 1 15 F condensing temperature = 113.5
tons divided by 1.075 subcooling factor =
105.6 tons. With: 125 F condensing temperature = 105.1
tons divided by 1.075 subcooling factor =
97.8 tons b
Plot two gross condenser heat rejection points on chart PD-1 divided by the compressor N factor (Table PD-1 to PD-3) at different condensing temperatures.
Example: Anticipating 100 ton condenser to meet design load of 96 tons.
Cond. Temp ITD (MBh) = Tons ÷ N F actor = Tons
11 5 at 20 = 830 = 69.2 ÷ 1.25* = 55.4 125 at 30 = 1285 = 107.1 ÷ 1.30* = 82.3
– Ambient temp = 95 F – Evaporator sst = 45 F – Compressor – CUAB-D1 0E
Gross Heat of Rejection
c
T ransfer the results from the compressor and condenser plots to Chart SP-1 and do the following. Draw a line through the two points representing gross heat compressor capacities less subcooling (1 05.6 and 82.3). Draw a line through the two points representing condenser gross heat of rejection (55.4 and 82.3).
d
At the point of intersection of the compressor and condenser lines draw dashed lines to the left and bottom margins of Chart SP-1. The end points of these lines will show a resultant gross condenser capacity of 93.8 tons at 129.4 F condensing temperature.
e
From c hart PD-2 calculate the percent increase in capacity due to subcooling.
Example:
At 95 F ambient and 129.4 F condensing temperature there is a 10.1% increase in capacity due to subcooling. This yields a system net capacity of 93.8 tons x 110% = 1 03.2 tons.
f
If necessary use the values in Table PD-4 to adjust the system capacity for altitude.
g
Compare this result with the design capacity and condensing temperature.
The required cooling load is 96 tons, therefore, the CAUC-D1 0 is the proper selection.
Repeat the process steps B through G as necessary to achieve the most economic condenser selection.
*N factor corrected from Table PD-2 sst – saturated suction temperature F – degree Fahrenheit N – compressor factor ITD – initial temperature difference
ACDS-PRC001-EN6

Selection Example

Chart SP-1 — Selection Example
7ACDS-PRC001-EN

Model Number Description

20 To 60 Ton Model Nomenclature
Digit 1 — Unit Type
C = Condenser
Digit 2 — Condenser
A = Air-Cooled
Digit 3 — Airflow
U = Upflow
C A U C C20 4 1 * 0 3 H 0
1 2 3 4 5,6,7 8 9 10 11 12 13 14
Digit 4 — Development Sequence
C = Third
Digit s 5,6,7 — Nominal Capacity
C20 = 20 Tons C40 = 40 Tons C25 = 25 Tons C50 = 50 Tons C30 = 30 Tons C60 = 60 Tons
Digit 8 — Power Supply
G = 200/230/60/3 XL 4 = 460/60/3 XL 5 = 575/60/3 XL
Digit 9 — Condenser Circuit
1 = Single (20-30 Ton) 2 = Dual (40-60 Ton)
Digit 10 — Design Sequence
* = Factory Assigned
Digit 1 1 — Ambient Control
0 = Standard 1=0 F
Digit 12 — Agency Approval
0 = None 3 = UL/CSA
Digits 13, 14 — Miscellaneous
H = Copper Fins 1 = Spring Isolators 2 = Rubber Isolators
1
80 T o 120 Ton Model Nomenclature
C A U C C80 4 2 A 0 3 H 0
1 2 3 4 5,6,7 8 9 10 11 12 13 14
Digit 1 — Unit Type
C = Condenser
Digit 2 — Condenser
A = Air-Cooled
Digit 3 — Airflow
U = Upflow
1. The service digit for each model number contains 14 digits; all 14 digits must be referenced.
Digit 4 — Development Sequence
C = Third
Digits 5,6,7 — Nominal Capacity
C80 = 80 Tons D10 = 100 Tons D12 = 120 Tons
Digit 8 — Power Supply
F = 230/60/3 4 = 460/60/3 5 = 575/60/3 E = 200/60/3
Digit 9 — Condenser Circuit
2 = Dual Circuit
Digit 10 — Design Sequence
A = First
1
Digit 1 1 — Ambient Control
0 = Standard 1 = 0 F
Digit 12 — Agency Approval
0 = None 2 = CSA 3 = UL/CSA
Digits 13, 14 — Miscellaneous
H = Copper Fins 1 = Spring Isolators
ACDS-PRC001-EN8
General Data
Table GD-1 — General Data
20 T on 25 T on 30 T on 40 T on 50 T on 60 T on 80 T on 100 T on 120 T on
Model Number CAUC-C20 CAUC-C25 CAUC-C30 CAUC-C40 CAUC-C50 CAUC-C60 CAUC-C80 CAUC-D10 CAUC-D12
Gross Heat Rejection (MBh) Condenser Fan Data
Number/Size/T ype 2/26”/Prop 3/26”/Prop 3/26”/Prop 4/26”/Prop 6/26”/Prop 6/26”/Prop 8/26”/Prop 12/26”/Prop 12/26”/P rop Fan Drive Direct Direct Direct Direct Direct Direct Direct Direct Direct No. of Motors/Hp (Each) 2/1.0 3/1.0 3/1.0 4/1.0 6/1.0 6/1.0 8/1 .0 12/1.0 12/1 .0 Nominal Cfm 12,400 16,700 19,000 24,800 33,400 38,000 49,600 66,800 76,000
Condenser Coil Data
No./Size (In.) 1/63x71 1/71x71 1/45x71 2/65x70 2/51x96 2/66x90 4/65x70 4/51x96 4/66x90 Face Area (Sq. Ft.) 31.0 35.0 46.1 63.2 67.1 88.0 126.4 136.0 165.0
Rows/Fins Per Ft. 3/168 3/156 3/168 3/168 3/156 3/168 3/168 3/156 3/168 General Data
No. Refrigerant Circuits 1 1 1222 222 Operating Charge Condenser Storage Capacity367 76 96 136 142 184 272 284 368
Ambient Temperature Operating Range
Standard Ambient (F) 40-115 40-115 40-11 5 40-115 40-1 1 5 40-115 40-1 15 40-115 40-1 15 Low Ambient Option (F) 0-115 0-115 0-115 0-115 0-115 0-1 15 0-115 0-11 5 0-1 15
Notes:
1. Gross Heat Rejection is at a 30 F ITD (Intial Temperature Difference) between condensing temperature and ambient air entering condenser (includes the effect of subcooling).
2. Operating charge is for entire unit.
3. At conditions of 95 F ambient, condenser is 95 percent full.
2
(Lbs of R-22) 25 28 37 52 56 74 104 112 148
1
301 373 455 614 712 888 1244 1425 181 9
1/49x71
9ACDS-PRC001-EN

P erformance Adjustment Factors

Chart PD-2— Compressor-Condenser Capacity Incr ease Due T o Subcooling (R-22)
Table PD-1 –- N Factor –- Semihermetic Compr essors
Cond. Temp. 30 35 40 45 50
110 1 .34 1.32 1.29 1.27 1.25
115 1.36 1.34 1.31 1.29 1.27 120 1.40 1 .37 1.34 1.32 1.30 125 1.43 1 .40 1.37 1.34 1.32 130 1.48 1 .44 1.40 1.38 1.35 135 1.52 1 .48 1.44 1.41 1.38 140 1.58 1 .54 1.49 1.45 1.42 145 1.65 1 .59 1.54 1.49 1.46
Note:
1. In order to determine N factor for CUAB units, find proper factor corresponding with the proper suction and condensing temperature from Table 9-1. This factor should be adjusted by adding or subtracting the correction value from Table 9-2.
Saturated Suction Temperature (F)
Table PD-2–- N Factor –- Open Compressors
Cond.
Temp. 30 35 40 45 50
110 1.245 1 .225 1 .21 5 1.195 1.175
115 1 .260 1.240 1.230 1.210 1.190 120 1.275 1.255 1.245 1.225 1.205 125 1.290 1.270 1.260 1.240 1.220 130 1.305 1.285 1.275 1.255 1.235 135 1.320 1.300 1.290 1.270 1.250 140 1 .335 1.315 1.305 1.285 1.265
Saturated Suction Temperature (F)
Table PD-3 –- Altit ude Corr ection Multiplier F or Cooling Capacity –- Air -Cooled Condenser
Altitude (Ft) 2,000 4,000 6,000 8,000 10,000
Correction Multiplier 0.977 0.949 0.917 0.881 0.843
Table PD-4 –- N Factor Corr ection –- Compressor
Compressor Correction Factor CUAB-015M + 0.02
020M ––– 025M – 0.01 030M + 0.01
040R – 0.02 050R – 0.04 060R – 0.04 075E – 0.02 100E – 0.04
ACDS-PRC001-EN10
P erformance Data
Chart PD-1 — Condenser Heat Rejection (R-22), 20-120 Ton
11ACDS-PRC001-EN

Electrical Data

Table ED-1 — Electrical Data
Unit Characteristics Condenser Fan Motor
Nominal Electrical Voltage Ampacity Size No./HP (Ea.) (Ea.) (Ea.)
T ons Model No. Characteristics Range (3),(5) (2),(5) (1) (1) (1) (1),(4)
20 CAUC-C204 460/60/3 416-508 4.1 15 2/1 .0 1 .8 9.0 0.9
25 CAUC-C254 460/60/3 416-508 5.9 15 3/1.0 1.8 9.0 0.9
30 CAUC-C304 460/60/3 416-508 5.9 15 3/1.0 1.8 9.0 0.9
40 CAUC-C404 460/60/3 416-508 7.7 15 4/1.0 1.8 9.0 0.9
50 CAUC-C504 460/60/3 416-508 11.3 15 6/1.0 1.8 9.0 0.9
60 CAUC-C604 460/60/3 416-508 11.3 15 6/1.0 1.8 9.0 0.9
80 CAUC-C80F 230/60/3 208-254 34 40 8/1.0 4.1 20.7 0.9
100 CAUC-D10F 230/60/3 208-254 50 60 12/1.0 4.1 20.7 0.9
120 CAUC-D12F 230/60/3 208-254 50 60 12/1.01 4.1 20.7 0.9
Notes:
1. Electric information is for each individual motor.
2. Maximum fuse size is permitted by NEC 440-22 is 300 percent of one motor RLA plus the RLA of the remaining motors.
3. Minimum circuit ampacity equals 125 percent of the RLA of one motor plus the RLA of the remaining motors.
4. All Kw values taken at conditions of 45 F saturated suction temperature at the compressor and 95 F ambient.
5. Local codes may take precedence.
CAUC-C20G 200-230/60/3 180-220/208-254 9.2 15 2/1 .0 4.1 20.7 0.9
CAUC-C205 575/60/3 520-635 3.2 15 2/1.0 1.4 7.2 0.9
CAUC-C25G 200-230/60/3 180-220/208-254 13.3 20 3/1.0 4.1 20.7 0.9
CAUC-C255 575/60/3 520-635 4.6 15 3/1.0 1.4 7.2 0.9
CAUC-C30G 200-230/60/3 180-220/208-254 13.3 20 3/1 .0 4.1 20.7 0.9
CAUC-C305 575/60/3 520-635 4.6 15 3/1.0 1.4 7.2 0.9
CAUC-C40G 200-230/60/3 180-220/208-254 17.4 20 4/1.0 4.1 20.7 0.9
CAUC-C405 575/60/3 520-635 6.0 15 4/1.0 1.4 7.2 0.9
CAUC-C50G 200-230/60/3 180-220/208-254 25.6 30 6/1.0 4.1 20.7 0.9
CAUC-C505 575/60/3 520-635 8.8 15 6/1.0 1.4 7.2 0.9
CAUC-C60G 200-230/60/3 180-220/208-254 25.6 30 6/1.0 4.1 20.7 0.9
CAUC-C605 575/60/3 520-635 8.8 15 6/1.0 1.4 7.2 0.9
CAUC-C80E 200/60/3 180-220 34 40 8/1.0 4.1 20.7 0.9
CAUC-C804 460/60/3 416-508 15 20 8/1.0 1.8 9.0 0.9 CAUC-C805 575/60/3 520-635 12 15 8/1.0 1.4 7.2 0.9
CAUC-D10E 200/60/3 180-220 50 60 12/1.0 4.1 20.7 0.9
CAUC-D104 460/60/3 416-508 22 25 12/1.0 1.8 9.0 0.9 CAUC-D105 575/60/3 520-635 17 20 12/1.0 1.4 7.2 0.9
CAUC-D12E 200/60/3 180-220 50 60 12/1.0 4.1 20.7 0.9
CAUC-D124 460/60/3 416-508 22 25 12/1.0 1.8 9.0 0.9 CAUC-D125 575/60/3 520-635 17 20 12/1.0 1.4 7.2 0.9
Allowable Circuit Fuse FLA LRA KW
Minimum Maximum
ACDS-PRC001-EN12
Dimensional (20 Ton) Data
Figure DD-1 — CAUC-C20 Unit Dimensions, Recommended Clearances, Mounting Locations, Electr ic and Refr ig erant Connection Siz es and Locations
13ACDS-PRC001-EN
Dimensional (25 Ton) Data
Figure DD-2 — CAUC-C25 Unit Dimensions, Recommended Clearances, Mounting Locations, Electric and Refr ig er ant Connection Sizes and Locations
ACDS-PRC001-EN14
Dimensional (30 Ton) Data
Figure DD-3 — CAUC-C30 Unit Dimensions, Recommended Clearances, Mounting Locations, Electr ic and Refrig er ant Connection Sizes and Locations
15ACDS-PRC001-EN
Dimensional (40 Ton) Data
Figure DD-4 — CAUC-C40 Unit Dimensions, Recommended Clearances, Mounting Locations, Electric and Refrigerant Connection Sizes and Locations
ACDS-PRC001-EN16
Dimensional (50 Ton) Data
Figure DD-5 — CAUC-C50 Unit Dimensions, Recommended Clearances, Mounting Locations, Electr ic and Refrig er ant Connection Sizes and Locations
17ACDS-PRC001-EN
Dimensional (60 Ton) Data
Figure DD-6 — CAUC-C60 Unit Dimensions, Recommended Clearances, Mounting Locations, Electric and Refr ig er ant Connection Sizes and Locations
ACDS-PRC001-EN18
Dimensional (80 Ton) Data
Figure DD-7 — CAUC-C80 Unit Dimensions, Recommended Clearances, Mounting Locations, Electric and Refriger ant Connection Sizes and Locations
NOTES:
1. HOT GAS DISCHARGE AND LIQUID LINE CONNECTION LOCATIONS SHOWN IN THE FRONT VIEW DO NOT REPRESENT HOLES IN THE UNIT PANEL. ACCESS TO THESE CONNECTIONS ARE PROVIDED BY THE CUSTOMERS.
2. DIMENSIONAL TOLERANCE +/- 1/8”.
19ACDS-PRC001-EN
Dimensional (1 00 Ton) Data
Figure DD-9 — CAUC-C100 Unit Dimensions, Recommended Clear ances, Mounting Locations, Electric and Refr ig er ant Connection Sizes and Locations
ACDS-PRC001-EN20
Dimensional (120 Ton) Data
Figure DD-1 0 — CAUC-C120 Unit Dimensions, Recommended Clearances, Mounting Locations, Electr ic and Refr ige rant Connection Sizes and Locations
NOTES:
1. HOT GAS DISCHARGE AND LIQUID LINE CONNECTION LOCATIONS SHOWN IN THE FRONT VIEW DO NOT REPRESENT HOLES IN THE UNIT PANEL. ACCESS TO THESE CONNECTIONS ARE PROVIDED BY THE CUSTOMERS.
2. DIMENSIONAL TOLERANCE +/- 1/8”.
21ACDS-PRC001-EN
Weights
Figure W -1 — 20-30 Tons
Figure W -2 — 40-60 Tons
Top View (Mounting Locations)
T able W-1 — 20 to 60 Ton Weights (Lbs./Kg.)
Nominal Model Weight Loc. 1 Loc. 2 Loc. 3 Loc. 4 Loc. 5 Loc. 6 Tons Number AL CU AL CU AL CU AL CU AL CU AL CU AL CU
20 CAUC-C20 Lb. 1146 1348 320 371 326 365 248 306 252 301 –– –– –– ––
25 CAUC-C25 Lb. 1190 1394 329 378 337 381 259 315 265 319 –– –– –– ––
30 CAUC-C30 Lb. 1302 1585 353 414 371 444 282 355 296 381 –– –– –– ––
40 CAUC-C40 Lb. 2048 2366 363 406 347 392 349 404 334 389 335 401 320 387
50 CAUC-C50 Lb. 2280 2664 407 464 392 449 387 453 373 438 367 441 354 427
60 CAUC-C60 Lb. 2465 3010 433 515 420 505 417 511 405 501 401 507 389 497
Operating Weight On Isolator At Mounting Locations
Kg. 519.8 611.5 145.2 168.3 147.9 165.6 112.5 138.8 114.3 136.5
Kg. 539.8 632.3 149.2 171.5 152.9 172.8 117.5 142.9 120.2 144.7
Kg. 590.6 719.0 160.1 187.8 168.3 201.4 127.9 161.0 134.3 172.8
Kg. 929.0 1073.2 164.7 184.2 157.4 177.8 158.3 183.3 151.5 176.5 152.0 181.9 145.2 175.5
Kg. 1034.2 1208.4 184.6 210.5 177.8 203.7 175.5 205.5 169.2 198.7 166.5 200.0 160.6 193.7
Kg. 1118.1 1365.3 196.4 233.6 190.5 229.1 189.2 231.8 183.7 227.3 181.9 230.0 176.5 225.4
Figure W -3 — 80-120 Tons
Top View (Mounting Locations)
T able W-2 — 80 to 120 Ton Weights (Lbs./Kg.)
Nominal Model Coil Operating Weight On Isolator At Mounting Points
Tons Number Fin Weight Loc. 1 Loc. 2 Loc. 3 Loc. 4 Loc. 5 Loc. 6 Loc.7 Loc.8
80 CAUC-C80 Kg. 1830.7 233.2 216.8 236.8 220.0 237.7 220.9 241.3 224.1
100 CAUC-D10 Kg. 2227.6 286.2 272.2 285.8 271.3 285.3 271.3 284.9 270.8
120 CAUC-D12 Kg. 2482.1 316.6 302.1 317.5 303.0 317.5 303.0 318.4 303.9
AL Lb. 4036 514 478 522 485 524 487 532 494
CU Lb. 4542 603 571 600 569 600 568 597 566
Kg. 2060.3 273.5 259.0 272.2 258.1 272.2 257.6 270.8 256.7
AL Lb. 4911 631 600 630 598 629 598 628 597
CU Lb. 5371 586 549 597 560 600 562 611 572
Kg. 2436.3 265.8 249.0 270.8 254.0 272.2 254.9 277.1 259.5
AL Lb. 5472 698 666 700 668 700 668 702 670
CU Lb. 5971 774 742 779 747 780 748 786 753
Kg. 2708.4 351.1 336.6 353.4 338.8 353.8 339.3 356.5 341.6
ACDS-PRC001-EN22
Mec hanical Specifications
General
Factory-assembled and wired air cooled condensing unit. The unit frame is constructed of 14 gauge welded galvanized steel. P anels and access doors are 14 or 16 gauge galvaniz ed steel. Unit surface is phosphatized and finished with Trane Slate Gray air-dry paint. This paint finish exceeds ASTM­B117 500 hour continuous salt spray test. The unit coils are protected with steel louvered panels. These panels add strength to the cabinet and an aesthetically pleasing appearance to the unit.
Refriger ation Circuits and Contr ol
The 20 to 30 ton units are single circuit. The 40 to 120 ton units are dual circuited. All the necessary controls to run the unit fans are provided. The control panel contains fan motor contactors, terminal point connection for compressor interlock and 115 volt control power transformer. Standard units will operate from 40 to 115 F. All units shipped with factory installed liquid line service valves.
Condenser Coils and Fans
Condenser coils have configurated aluminum fins mechanically bonded to copper tubing with integralsubcooler. The coils are underwater burst/leak tested at 450 psi. Direct drive condenser fan motors have permanently lubricated ball bearings and thermal overload protection.
Low Ambient Operation
Standard ambient control allows operation down to 40 F with cycling of condenser fans. Optional low ambient allows operation down to 0 F with external damper assembly for head pressure control. Refer to Options section for details.

Options

Low Ambient Control
Low ambient allows operation down to 0 F through the use of fan cycling and head pressure control dampers. The control consists of a heavy gauge damper assembly, R-22 operator , tubing and grommet. All components are factory-mounted for both production and Pac ked Stoc k Plus units. Lo w ambient control must be ordered when the air -cooled condenser is matched with a CCKC heat recovery chiller.
Copper Finned Condenser Coil
Copper fins are mechanically bonded to copper tubes for use in corrosive atmospheres. Nominal unit capacity remains the same.
Spring Isolation Pa ck age
Spring isolators reduce transmission of noise and vibration to building structure, equipment, and adjacent spaces. Isolators consist of a cast, spring loaded, telescoping housing as the isolation medium. Mountings include built-in leveling bolts, resilient inserts that act as centering guides, and ribbed neoprene acoustical pads bonded to the bottom of the isolator. The kit includes instructions for field installation.
Neoprene-in-shear Isolation P ack age
Neoprene isolators reduce transmission of noise and vibration to building structure, equipment, and adjacent spaces. Isolators have a steel plate and base completely imbedded in neoprene. Mountings have a 1/4-inch deflection. The kit includes instructions for field installation. A vailable on 20 to 60-ton units only.
23ACDS-PRC001-EN
The T rane Company
Unitary Products Group 2701 Wilma Rudolph Blvd. Clarksville, TN 37040 www.trane.com
An American Standard Company
Literature Order Number ACDS-PRC001-EN File Number PL-RF -A CDS-PRC0001-EN-04-200 1 Supersedes ACDS-DS-1 07/00 Stocking Location Inland-LaCrosse
Since The Trane Company has a policy of continuous product and product data improvement, it reserves the right to change design and specifications without notice.
Loading...