Models BCHC and BCVC
“AO” and later design sequence
April 2008
BCXC-SVX01B-EN
Warnings, Cautions and Notices
Warnings, Cautions and Notices. Note that warnings, cautions and notices appear at
appropriate intervals throughout this manual. Warnings are provide to alert installing contractors
to potential hazards that could result in personal injury or death. Cautions are designed to alert
personnel to hazardous situations that could result in personal injury, while notices indicate a
situation that may result in equipment or property-damage-only accidents.
Your personal safety and the proper operation of this machine depend upon the strict observance
of these precautions.
ATTENTION: Warnings, Cautions and Notices appear at appropriate sections throughout this
literature. Read these carefully.
WARN ING – Indicates a potentially hazardous situation which, if not avoided, could result in
death or serious injury.
CAUTION – Indicates a potentially hazardous situation which, if not avoided, could result in
minor or moderate injury. It could also be used to alert against unsafe practices.
NOTICE – Indicates a situation that could result in equipment or property-damage only accidents.
Important
Environmental Concerns!
Scientific research has shown that certain man-made chemicals can affect the earth's naturally
occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the
identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine
and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all
refrigerants containing these compounds have the same potential impact to the environment.
Trane advocates the responsible handling of all refrigerants-including industry replacements for
CFCs such as HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are important to the environment, our
customers, and the air conditioning industry. All technicians who handle refrigerants must be
certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these
service procedures. In addition, some states or municipalities may have additional requirements
that must also be adhered to for responsible management of refrigerants. Know the applicable
laws and follow them.
WARNING
Refrigerant warning information!
System contains oil and refrigerant under high pressure. Recover refrigerant to relieve pressure
before opening the system. See unit nameplate for refrigerant type. Do not use non-approved
refrigerants, refrigerant substitutes, or refrigerant additives.
Failure to follow proper procedures or the use of non-approved refrigerants, refrigerant
substitutes, or refrigerant additives could result in death or serious injury or equipment damage.
Never solder, braze or weld on refrigerant lines or any unit components that are above
atmospheric pressure or where refrigerant may be present. Always remove refrigerant by
following the guidelines established by the EPA Federal Clean Air Act or other state or local
codes as appropriate. After refrigerant removal, use dry nitrogen to bring system back to
atmospheric pressure before opening system for repairs. Mixtures of refrigerants and air under
pressure may become combustible in the presence of an ignition source leading to an explosion.
Excessive heat from soldering, brazing or welding with refrigerant vapors present can form
highly toxic gases and extremely corrosive acids. Failure to follow all proper safe refrigerant
handling practices could result in death or serious injury.
BCXC-SVX01B-EN3
Introduction
About This Manual
Use this manual for commercial blower coil models BCHC and BCVC. This is the second version
of this manual; this manual supercedes BCXB-SVX01A-EN. It provides specific installation,
operation, and maintenance instructions for “AO” and later design sequences.
For previous design sequence information, contact your local Trane representative.
Trademarks
Trane, the Trane logo, Frostat, Integrated Comfort, Rover, Tracer, and Tracer Summit are trademarks
of Trane in the United States and other countries. All trademarks referenced in this document are
the trademarks of their respective owners.
Following is a complete description of
the blower coil model number. Each
digit in the model number has a
corresponding code that identifies
specific unit options.
A =115/60/1H = 575/60/3
B =208/60/1J =220/50/1
C =230/60/1K =240/50/1
D =277/60/1L = 380/50/3
E= 208/60/3M = 415/50/3
F=230/60/3N =190/50/3
G =460/60/3P = two-speed,
115/60/1
0=no motor, ctrls, elec ht.
Digit 9 —Insulation Type
1=1” matte-faced
2=1” foil-faced
Digits 10, 11 — Design Sequence
A0
Digit 12 — Motor, Drive, and
Control Box Location
A =same side as coil connections,
horizontal or counterswirl only
B =opposite side from coil
connections, horizontal or
counterswirl only
C =same side as coil connections,
pre-swirl only
D =opposite side from coil
connections, pre-swirl only
R =right-hand access
L=left-hand access
Digit 13 — Drain Pan Type, Coil
& Drain Connection Side
0=none
1=polymer drain pan & right-hand
connections
2=polymer drain pan & left-hand
connections
3=stainless steel drain pan & right-
hand connections
4=stainless steel drain pan & left-
hand connections
Digit 14 — Unit Coil #1*
Note: All coils are hydronic unless stated
otherwise.
0=none
A =1-row preheat
L=2-row hydronic high-capacity
preheat
F=4-row hydronic
G =6-row hydronic
J=4-row hydronic, autochangeover
K =6-row hydronic, autochangeover
M =4-row hydronic high-capacity
N =6-row hydronic high-capacity
R =4-row hydronic high-capacity,
autochangeover
T=6-row hydronic high-capacity,
autochangeover
1=3-row DX, 3/16” distributor
(0.032)
2=4-row DX, 3/16” distributor
(0.032)
3=6-row DX, 3/16” distributor
(0.032)
4=3-row DX, 3/16” distributor
(0.049)
5=4-row DX, 3/16” distributor
(0.049)
6=6-row DX, 3/16” distributor
(0.049)
Digit 15 — Unit Coil #2*
Note: All coils are hydronic unless stated
otherwise.
0=none
A =1-row reheat
L=2-row hydronic high-capacity
reheat
F=4-row hydronic
G =6-row hydronic
H =2-row hydronic, autochangeover
J=4-row hydronic, autochangeover
K =6-row hydronic, autochangeover
M =4-row hydronic high-capacity
N =6-row hydronic high-capacity
P=2-row hydronic high-capacity,
autochangeover
R =4-row hydronic high-capacity,
autochangeover
T=6-row hydronic high-capacity,
autochangeover
1=3-row DX, 3/16” distributor
(0.032)
2=4-row DX, 3/16” distributor
(0.032)
3=6-row DX, 3/16” distributor
(0.032)
4=3-row DX, 3/16” distributor
(0.049)
5=4-row DX, 3/16” distributor
(0.049)
6=6-row DX, 3/16” distributor
(0.049)
Digit 16 — Motor Horsepower
0=none4 =1 hp
1=1/3 hp5 =1-1/2 hp
2=1/2 hp6 =2 hp
3=3/4 hp7 =3 hp
Digit 17 — Motor Drives
0=none
A =390–552 rpm / 60 Hz
B =478–678 rpm / 60 Hz
C =540–765 rpm / 60 Hz
D =619–878 rpm / 60 Hz
E= 727–1029 rpm / 60 Hz
F=879–1245 rpm / 60 Hz
G =1000–1417 rpm / 60 Hz
H =1200–1700 rpm / 60 Hz
J=1313–1859 rpm / 60 Hz
K =1615–2288 rpm / 60 Hz
L=678–877 rpm / 60 Hz
M =765–990 rpm / 60 Hz
N =878–1136 rpm / 60 Hz
P = 1029–1332 rpm / 60 Hz
R =1245–1611 rpm / 60 Hz
T= 1174–1519 rpm / 50 Hz
0=none
A=fan status
C=condensate overflow
D=low limit
F=A & CK=C & D
G=A & DN=A, C, & D
Digit 36 — Control Options 2
0=none
A =outside air sensor, field-mounted
B =discharge air sensor
C=A & B
Digit 37 — Control Options 3
0=none
A =dehumidification with
communicated value
B =dehumidification with local
humidity sensor
Digit 38 — Zone Sensors
0=none
1=off/auto, setpoint knob, on/cancel,
COMM
2=off/auto/high/low, setpoint knob,
on/cancel, COMM
3=wall mtd. zone sensor (set point,
occ, COMM)
4=wall mtd. zone sensor (occ,
COMM)
5=wall mtd. zone temp sensor
A =digital zone sensor (O, A, H, L; SP;
OCC; COMM)
B =digital zone sensor (CPS; OCC;
COMM)
C =wireless zone sensor (setpoint
only)
Digit 39 — Extra Belt
0=none
1=ship loose extra belt
Digit 40 — Extra Filter
0=none
1=ship loose extra 1” throwaway
filter
2=ship loose extra 2” pleated
throwaway
8 BCXC-SVX01B-EN
General Information
Blower Coil General Information
Blower coil units are draw-thru air handlers for cooling load conditions of 400–3000 cfm. Units are
available in either horizontal (model BCHC) or vertical (model BCVC) configurations. Horizontal
units are typically ceiling suspended via threaded rods. Knockouts are provided in all four corners
to pass the rods through the unit. Horizontal units can also be floor mounted. Vertical units are
typically floor mounted. They have a side inlet for easy duct connection, and do not require a field
fabricated inlet plenum. Vertical units ship in two pieces and can be set up in either a pre-swirl or
counter-swirl configuration.
Basic unit components consist of a water coil, condensate drain pan, filter, duct collars, one fan
wheel, and motor with drive. See Figure 1. Drive components consist of sheaves, belt, and motor.
The coil, drain pan, and motor/drive assembly can easily be field-converted from right hand to left
hand configurations or vice versa.
Figure 1. Blower coil air handler unit components (model BCHC, horizontal unit)
Main coil with copper
tubes and enhanced
aluminum fins in 2-, 4-,
Unit sizes 12, 18, 24, 36,
54, 72, and 90 MBh
Knockouts in all four
corners for hanger rods
Galvanized steel
cabinet in 14-, 18-, 22-,
and 28-inch heights
or 6-row hydronic or 3-,
4-, or 6-row DX
Internal filter frame
accommodates 1- or
2-inch filters
Angle filter option and/or
Forward curved fan
Control options
include control
interface, Tracer™
ZN010, ZN510, or
ZN520
1/3 to 3 hp motor
with drive
selections from
390 to 1611 rpm
Internal 1- or
2-row auxiliary
coil in preheat
or reheat position
mixing box accommodates
2-inch filters
Main and auxiliary
drain connections on
same side of unit
Two, four, or six-row main coils are available for either hydronic cooling or heating. Three, four, or
six-row direct expansion (DX) coils are also available for cooling. An optional one, two, four, or sixrow heating coil is available factory-installed in either the preheat or reheat position. Also, a onerow preheat steam is available.
All units have an internal flat filter frame for one or two-inch filters. An optional angle filter box (two
inch only), mixing box, bottom/top filter access box, or combination angle filter mixing box is
available.
In addition, all units are available with either a basic or deluxe piping package option that includes
a variety of control valve sizes in two or three-way configurations. The basic package consists of
BCXC-SVX01B-EN9
General Information
a control valve and stop (ball) valves. The deluxe package consists of a control valve, a stop (ball)
valve, a circuit setter, and strainer.
Belt-drive motors range from 1/3 to 3 horsepower in a wide range of voltages. All motors have
internal thermal and current overloads, permanently sealed ball bearings, and a resilient cradle
mount to reduce noise and vibration transmission.
Variable pitch sheave drive kit options help make it possible to more accurately select design static
pressure. For additional flexibility, 115 volt single phase, two speed motors are optional.
Note: Sheaves are factory set in the middle of the range. Field adjustment of sheaves, motor, and
Units may have no controls (4 x 4 junction box) or any of four different control types:
1. control interface
2. Tracer™ ZN010
3. Tracer ZN510
4. Tracer ZN520
All control options are factory-installed and tested.
belt are required to arrive at desired rpm. Refer to the original sales order and Table 35, p. 68
for drive information.
10 BCXC-SVX01B-EN
Pre-Installation
Receiving and Handling
Blower coil units are packaged for easy handling and storage on the job site. Upon delivery, inspect
all components for possible shipping damage. See the “Receiving Checklist” section (below) for
detailed instructions. Trane recommends leaving units and accessories in their shipping packages/
skids for protection and handling ease until installation.
Shipping Package
Blower coil air handlers ship assembled on skids with protective coverings over the coil and
discharge openings.
Ship-Separate Accessories
Field-installed sensors ship separately inside the unit’s main control panel. Piping packages,
mixing boxes, ship separately packaged on the same skid as the unit.
Receiving Checklist
Complete the following checklist immediately after receiving unit shipment to detect possible
shipping damage.
Inspect individual cartons before accepting. Check for rattles, bent carton corners, or other visible
indications of shipping damage.
If a unit appears damaged, inspect it immediately before accepting the shipment. Manually
rotate the fan wheel to ensure it turns freely. Make specific notations concerning the damage on
the freight bill. Do not refuse delivery.
Inspect the unit for concealed damage before it is stored and as soon as possible after delivery.
Report concealed damage to the freight line within the allotted time after delivery. Check with the
carrier for their allotted time to submit a claim.
Do not move damaged material from the receiving location. It is the receiver’s responsibility to
provide reasonable evidence that concealed damage did not occur after delivery.
Do not continue unpacking the shipment if it appears damaged. Retain all internal packing,
cartons, and crate. Take photos of damaged material if possible.
Notify the carrier’s terminal of the damage immediately by phone and mail. Request an
immediate joint inspection of the damage by the carrier and consignee.
Notify your Trane representative of the damage and arrange for repair. Have the carrier inspect
the damage before making any repairs to the unit.
Compare the electrical data on the unit nameplate with the ordering and shipping information
to verify the correct unit is received.
Jobsite Storage Recommendations
This unit is intended for indoor use only. To protect the unit from damage due to the elements and
prevent it from possibly becoming a contaminant source for IAQ problems, store the unit indoors.
If indoor storage is not possible, the Trane Company makes the following provisions for outdoor
storage:
1.Place the unit(s) on a dry surface or raised off the ground to assure adequate air circulation
beneath unit and to assure that no portion of the unit contacts standing water at any time.
2.Cover the entire unit with a canvas tarp only. Do not use clear, black, or plastic tarps as they
may cause excessive moisture condensation and equipment damage.
Note: Wet interior unit insulation can become an amplification site for microbial growth (mold),
which may cause odors and health-related indoor air quality problems. If there is visible
evidence of microbial growth (mold) on the interior insulation, remove and replace the
insulation prior to operating the system.
BCXC-SVX01B-EN11
Pre-Installation
Installation Preparation
Before installing the unit, perform the following procedures to ensure proper unit operation.
1. Verify the floor or foundation is level. Shim or repair as necessary. To ensure proper unit
operation, install the unit level (zero tolerance) in both horizontal axes. Failure to level the unit
properly can result in condensate management problems, such as standing water inside the
unit. Standing water and wet surfaces inside units can result in microbial growth (mold) in the
drain pan that may cause unpleasant odors and serious health-related indoor air quality
problem.
2. Allow adequate service and code clearances as recommended in the “Service Access” section
(below). Position the unit and skid assembly in its final location. Test lift the unit to determine
exact unit balance and stability before hoisting it to the installation location.
Service Access
See Ta b le 1 , below, and Figure 2, p. 13 for recommended service and code clearances.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
Figure 2. Top view of blower coil unit showing recommended service and code clearances
3
3
Rigging and Handling
Before preparing the unit for lifting, estimate the approximate center of gravity for lifting safety.
Because of placement of internal components, the unit weight may be unevenly distributed, with
more weight in the coil area. Approximate unit weights are given in “Dimensions and Weights,”
p. 15. Also, you may reference the unit weight on the unit nameplate.
Before hoisting the unit into position, use a proper rigging method such as straps, slings, or
spreader bars for protection and safety. Always test-lift the unit to determine the exact unit balance
and stability before hoisting it to the installation location.
WARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper center of gravity lift point. To avoid
dropping of unit, reposition lifting point if unit is not level. Failure to properly lift unit could
result in death or serious injury or possible equipment or property-only damage.
Unit Handling Procedure
1. Position rigging sling under wood skid using spreader bars to avoid unit damage.
2. Use a forklift with caution to prevent unit damage. The fork length must be at least 68 inches
long to safely fork the unit from front or back.
3. The unit center of gravity will fall within the center of gravity block at various locations
depending on unit options.
4. See unit nameplate for unit weight.
Unit Location Recommendations
When selecting and preparing the unit installation location, consider the following
recommendations.
BCXC-SVX01B-EN13
Pre-Installation
1. Consider the unit weight. Reference the unit weight on the unit nameplate or in “Dimensions
and Weights,” p. 15.
2. Allow sufficient space for the recommended clearances, access panel removal, and
maintenance access. Refer to Figure 2, p. 13.
3. The installer must provide threaded suspension rods for ceiling mounted units. All units must
be installed level.
4. Coil piping and condensate drain requirements must be considered.
Allow room for proper ductwork and electrical connections. Support all piping and ductwork
independently of unit to prevent excess noise and vibration.
Skid Removal
The unit ships on skids that provide forklift locations from the front or rear. The skid allows easy
maneuverability of the unit during storage and transportation. Remove the skids before placing the
unit in its permanent location.
Remove the skids using a forklift or jack. Lift one end of the unit off of the skids. Vibration isolators
for external isolation are field supplied.
Pre-Installation Checklist
Complete the following checklist before beginning unit installation.
Verify the unit size and tagging with the unit nameplate.
Make certain the floor or foundation is level, solid, and sufficient to support the unit and
accessory weights. Refer to “Dimensions and Weights,” p. 15. Level or repair the floor before
positioning the unit if necessary.
Allow minimum recommended clearances for routine maintenance and service. Refer to unit
submittals for dimensions.
Allow one and one half fan diameters above the unit for the discharge ductwork.
14 BCXC-SVX01B-EN
Dimensions and Weights
Horizontal Blower Coil
top view
M
M
M
*NOTE: ON UNITS WITHOUT A
BOTTOM FILTER ACCESS SECTION
P
P
Q
Q
1.5
front view
J
J
Table 2.Horizontal blower coil dimensions (in.) and weights (lb)
Three-way, 1/2” and 1” valve deluxe piping package
F
A
B
AB
E
C
D
Table 11. Piping package dimensions (in.)
Piping
package
2-way1/25/812.0252.65012.6255.650N/AN/A
3-way 1/2 5/812.0882.09712.6884.4976.3516.351
Nominal
tube size Actual sizeABCDEF
1 1-1/813.2954.26013.2209.2883.020N/A
3/47/815.6231.75015.3136.2906.7016.701
11-1/813.3703.69013.2109.0609.8139.813
1-1/41-3/816.8853.73816.41010.0233.05210.520
24 BCXC-SVX01B-EN
Installation Controls
Installing Wall Mounted Controls
Wall mounted zone sensors ship taped to the control box. Refer to Figure 3 for zone sensor
dimensions.
Position the controller on an inside wall three to five feet above the floor and at least 18 inches from
the nearest outside wall. Installing the controller at a lower height may give the advantage of
monitoring the temperature closer to the zone, but it also exposes the controller to airflow
obstructions. Ensure that air flows freely over the controller.
Before beginning installation, follow the wiring instructions below. Also, refer to the unit wiring
schematic for specific wiring details and point connections.
Wiring Instructions
Avoid mounting the controller in an area subject to the following conditions:
•Dead spots, such as behind doors or in corners that do not allow free air circulation.
•Air drafts from stairwells, outside doors, or unsectioned hollow walls.
•Radiant heat from the sun, fireplaces, appliances, etc.
•Airflow from adjacent zones or other units.
•Unheated or uncooled spaces behind the controller, such as outside walls or unoccupied
spaces.
•Concealed pipes, air ducts, or chimneys in partition spaces behind the controller.
Zone Sensor Installation
Follow the procedure below to install the zone sensor module (see Figure 3).
Figure 3. Wall-mounted zone sensor dimensions
1. Note the position of the setpoint adjustment knob and gently pry the adjustment knob from the
cover using the blade of a small screwdriver.
2. Insert the screwdriver blade behind the cover at the top of the module and carefully pry the
cover away from the base.
3. To install the zone sensor module without a junction box (directly to the wall):
a. Using the module base as a template, mark the rectangular cutout for the control wiring and
module installation holes. Ensure the base is level.
b. Set the base aside and make the cutout. Then, drill two 3/16” diameter holes approximately
one-inch deep. Insert and fully seat the plastic anchors.
c. Pull the control wires through the cutout and attach the module to the wall using the screws
provided.
4. To install the zone sensor module to a standard junction box:
a. Level and install a 2” x 4” junction box (installer supplied) vertically on the wall.
BCXC-SVX01B-EN25
Installation Controls
b. Pull the control wires through the cutout. Attach the module to the wall using the screws
provided.
5. Strip the insulation on the interconnection wires back 0.25 inch and connect to TB1. Screw down
the terminal blocks.
6. Replace the zone sensor cover and adjustment knob.
If installing a Tracer™ ZN510 or ZN520 zone sensor, see “Tracer Summit Communication Wiring,”
p. 27 for more information.
Communication Wiring
Units with Tracer ZN510 or ZN520 only
Note: Communication link wiring is a shielded, twisted pair of wire and must comply with
Follow these general guidelines when installing communication wiring on units with either a
Tracer™ ZN510 or ZN520 controller:
•Maintain a maximum 5000 ft. aggregate run
•Install all communication wiring in accordance with the NEC and all local codes.
•Solder the conductors and insulate (tape) the joint sufficiently when splicing communication
wire. Do not use wire nuts to make the splice.
•Do not pass communication wiring between buildings because the unit will assume different
ground potentials.
•Do not run power in the same conduit or wire bundle with communication link wiring.
applicable electrical codes.
Service Communication Wiring
Establish service communication using Rover™ service software connected to the Tracer™ ZN
controller using a twisted wire pair to one of the following connection points:
•Remote zone sensor module
•Connections on the board
This allows the technician to view and edit the Tracer™ controller configuration and troubleshoot
the unit.
Note: Unit control options and field wiring practices may limit the controller’s communication
ability.
Route interconnecting wiring from the Tracer™ controller to provide service communication at the
wall-mounted zone sensor module. Install wiring by referencing the unit wiring diagram and
Ta b l e 12 , p . 2 9 for appropriate wire sizes. After wiring is complete, connect the communication
cable (provided with the Rover™ service tool) to the telephone style RJ11 connection on the zone
sensor module. Attach the other end of the cable to a computer running Trane Rover software to
communicate.
Zone Sensors Without Interconnecting Wiring
Establish service communication to the Tracer™ ZN controller by wiring directly to the board inside
the control box. Refer to the unit-wiring diagram for appropriate communication terminals on the
board.
Once wiring is complete, Use Trane Rover™ software to communicate to the Tracer™ ZN controller.
Tracer Communications
Tracer™ ZN controllers have Comm5 communication ports. Typically, a communication link is
applied between unit controllers and a building automation system. Communication also is
possible via Rover™, Trane’s service tool.
26 BCXC-SVX01B-EN
Peer-to-peer communication across controllers is possible even when a building automation
system is not present.You do not need to observe polarity for Comm5 communication links.
The controller provides six 0.25-inch quick-connect terminals for the Comm5 communication link
connections, as follows:
•Two terminals for communication to the board
•Two terminals for communication from the board to the next unit (daisy chain)
•Two terminals for a connection from the zone sensor back to the controller
Each controller has its own unique address or I.D. number on a Neuron chip. Setting dip switches
are not required on the Tracer™ controller.
Tracer Summit Communication Wiring
For Tracer™ ZN-controlled units that will interface with the Trane Tracer Summit® building
management system, terminate the communication wiring in the control box at the designated
terminals on the board. Reference the unit wiring diagram or submittals.
Ground shields at each Tracer™ ZN controller, taping the opposite end of each shield to prevent
any connection between the shield and anther ground. Refer to Trane publication CNT-SVX04A-EN,
Tracer ZN.520 Unit Controller - Installation, Operation and Programming Guide, for the
communication wiring diagram.
Communication wire must conform to the following specification:
•Shielded twisted pair 18 AWG
•Capacitance 23 (21-25) picofarads (pF) per foot
•Listing/Rating – 300V 150C NEC 725-2 (b) Class 2 Type CL2P
•Trane Part No. 400-20-28 or equivalent, available through Trane BAS Buying Group Accessories
catalog.
Installation Controls
BCXC-SVX01B-EN27
Installation Electrical
Unit Wiring Diagrams
Specific unit wiring diagrams are provided on the inside of the control panel door. Typical unit
wiring diagrams are in “Wiring Diagrams,” p. 81. Use these diagrams for connections or trouble
analysis.
WARNING
Grounding Required!
Follow proper local and state electrical codes for requirements on grounding. Failure to follow
code could result in death or serious injury.
Supply Power Wiring
Wiring must conform to NEC and all applicable code requirements.
It is the installer’s responsibility to provide adequately-sized power wires and proper unit
grounding.
Bring supply wiring through provided equipment knockouts located at the power connection point
on the unit. Equipment submittals should be referred to for the exact electrical access connection
point. Connect the power wires to the power connection point provided.
Connection to the installer-provided ground path must be made to the green wire or green
grounding screw provided on each unit.
Locate unit wiring diagrams on the inside of the control box cover. Refer to the unit-specific wiring
diagrams for wiring, connection point, and fuse installation information. Refer to the unit
nameplate for unit-specific electrical information, such as voltage, minimum circuit ampacity
(MCA), and maximum fuse size (MFS).
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
NOTICE
Use copper conductors only!
Unit terminals are not designed to accept other conductor types. Failure to use copper
conductors could cause equipment damage.
NOTICE
Correct phase critical!
Correct phase sequence is critical. If phase sequence of the incoming line voltage is not correct,
it could cause motor damage.
Electrical Connections
Units have one of three different connection points, depending on the unit type and options.
1. If the unit has no controls: power and ground are tucked inside of the handy box.
2. If the unit has a control interface or Tracer™ ZN controller: power and ground are inside the
control box. If the unit has a control interface or a Tracer controller, the power wires and ground
wire are inside the control box connected to a non fused disconnect switch.
28 BCXC-SVX01B-EN
Loading...
+ 64 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.