ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information
pack upon completion of work.
NOTE: Units operating in low ambient conditions require compressor crankcase heaters due to changes in head pressure.
Refer to Table 1 for the appropriate crankcase heater accessory
number. Install the heater before operating the low ambient control.
HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING
Refer to Figure 1 on page 2 to identify the kit components.
Inspect Contents
You must report damage and make claims to the
transportation company immediately. Report missing
parts to your supplier immediately and replace with
authorized parts only.
Remove these four (4) access panels (see
Figure 2, page 2):
• Control/Heat box access panel
• Blower access panel
• Compressor access panel
• Coil access panel
3. Mount Control Module
The Control Module is to be mounted to the universal
bracket (included in the kit) or the Compressor Startkit
bracket, depending upon your unit's configuration.
Continue with the following section that applies to your
configuration:
• 3a. 230 Volt 2/4WC** with Compressor Start Kit,
460 Volt 2/4WC*3060A4 & 460 Volt 4WCZ6 units.
Go to page 3.
• 3b. 230 Volt Single Phase 2/4WC** units WITH-
OUT Start Kit, All 4TC** units & 230/460 Volt
Three Phase 2/4WC** units except for 2/
4WC*3060A4 & 460 Volt 4WCZ6 units. Go to page
4.
• 3c. 230 Volt 2/4YC** and 4DC** units with
Compressor Start Kit, 460 Volt 2/4YC*3060A4, &
460 Volt 4YCZ6 units. Go to page 5.
• 3d. 230 Volt 2/4YC** & 4DC** Single Phase units
WITHOUT Start Kit & 230/460 Volt Three Phase
2/4YC** & 4DC** units except 460 Volt 2/
4YC*3060A4, & 460 Volt 4YCZ6 units. Go to page 6.
Page 2
Installer’s Guide
Control Module
Solid State
Relay (SSR)
Universal Bracket
Bushing
Low Voltage
Pigtail Assembly
Liquid Sensor Clamp
Liquid Sensor
Assembly
Sheet Metal
Screw (5)
Wire Nuts (5)
Figure 1. Identify LOAM Kit Components
Outdoor Air Sensor
Thermal
Compound
Outdoor
Air Sensor
Retainer
Dart
Press Tight Insulating Tape
(sensor Insulation)
Information
Label
Cable Ties (5)
Coil/Filter Access
Panel
Compressor
Access Panel
Blower Access
Panel
Figure 2. Identify Exterior Components
2
Control/Heat
Box Access
Panel
Note: Unit vents not
shown
4 Louvered Panels
(1 on each side)
Page 3
3a. 2/4WC** Units
230 Volt 2/4WC** with Compressor Start Kit &
460 Volt 2/4WC*3060A4 & 460 Volt 4WCZ6 units
1.Remove the Control Module from the Universal Bracket
(remove 2 machine screws).
2.Mount the Control Module to the Compressor Start Kit
bracket using the two (2) machine screws. See Figure 3.
3.Continue with step 4. Mounting the Liquid Line Sensor,
page 7.
Installer’s Guide
Control Module
Compressor
Start Kit
SSR
Start Kit
Bracket
Mount Control
Module
to Start Kit Bracket
Using Two Machine
Screws.
460v Transformer is
mounted in place of
Start Kit for 460 volt
2/4WC*3060A4 &
4WCZ6 units
Figure 3. 230 Volt 2/4WC** with Compressor Start Kit & 460 Volt 2/4WC*3060A4 & 460 Volt 4WCZ6 units
3
Page 4
Installer’s Guide
3b. 2/4WC** and 4TC** Units
230 Volt Single Phase 2/4WC** units WITHOUT
Start Kit, All 4TC** units & 230/460 Volt Three
Phase 2/4WC** Units except for 2/4WC*3060A4 &
460 Volt 4WCZ6 units
Note: Use the Universal Bracket shipped in the Low
Ambient kit. Mount the Control Module to the Universal
Bracket as needed so that the assembly matches the
illustration below.
1.Mount the Control Module and Universal Bracket assembly
bracket to the back of the control box with two (2)
sheetmetal screws inserted horizontally. Also, mount the
Universal Bracket to the bottom of the control box with one
(1) sheetmetal screw inserted vertically.See Figure 4.
2.Continue with step 4, Mounting the Liquid Line Sensor,
page 7.
Control Box
Mount Universal
Bracket to back
wall of Control Box
with two (2)
Sheetmetal Screws
(horizontally)
Mount Universal
Bracket to Control
Box with one (1)
Sheetmetal Screw
(vertically)
Figure 4. 230 Volt Single Phase 2/4WC** units WITHOUT Start Kit, All 4TC** units &
230/460 Volt Three Phase 2/4WC** units except for 2/4WC*3060A4 & 460 Volt 4WCZ6 units
4
Universal
Bracket
Control
Module
Page 5
3c. 2/4YC** and 4DC** Units
230 Volt 2/4YC** and 4DC** units with Compressor Start Kit, 460 volt 2/4YC*3060A4, & 460 volt
4YCZ6 units
Installer’s Guide
1.Remove the Control Module from the Universal Bracket (2
machine screws).
2.Then, align the two holes in the ControlModule with the
two clearance holes in the Start Kit bracket.
3.Mount the Control module to the Start Kit bracket with the
two (2) machine metal screws you removed from the
Universal Bracket. See Figure 5.
Continue with step 4, Mounting the Liquid Line Sensor, page 7.
Mount Control Module
to Start Kit Bracket
Using Two Sheetmetal
Screws
Compressor
Start Kit
460v Transformer is
mounted in
place of Start
Kit for 460 Volt
2/4YC*3060A4
& 460 Volt
4YCZ6 units
Figure 5. 230 Volt 2/4YC** and 4DC** units with Compressor Start Kit,
Start Kit
Bracket
Control
Module
460 volt 2/4YC*3060A4, & 460 volt 4YCZ6 units
5
Page 6
Installer’s Guide
3d. 2/4YC** and 4DC** Units
230 Volt 2/4YC** & 4DC** Single Phase units
WITHOUT Start Kit & 230/460 Volt Three Phase 2/
4YC** & 4DC** units except 460 Volt 2/
4YC*3060A4, & 460 Volt 4YCZ6 units
Note: Use the Universal Bracket shipped in the Low
Ambient kit. Mount the Control Module to the Universal
Bracket as needed so that the assembly matches the
illustration below.
1. Mount the Control Module and Universal Bracket
assembly to the bottom of the control box with two
(2) sheetmetal screws. One is inserted horizontally
from inside the control box into the universal
bracket, and one is inserted vertically . See Figure
6.
2. Continue with step 4, Mount the Liquid LineSensor, page 7.
Control Box
Mount Universal
Bracket to back
wall of Control
Box Using one
(1) Sheetmetal
Screw
(Horizonally).
Mount Universal
Bracket to Control
Box using one (1)
Sheetmetal Screw
(vertically)
Universal
Bracket
Control
Module
Figure 6. 230 Volt 2/4YC** & 4DC** Single Phase units WITHOUT Start Kit &
230/460 Volt Three Phase 2/4YC** & 4DC** units except 460 volt 2/4YC*3060A4, & 460 volt 4YCZ6 units
6
Page 7
Installer’s Guide
4. Mount the Liquid Line Temperature Sensor
In this step you mount the liquid line sensor to the
liquid line. See Figure 7.
1.Attach the liquid line temperature sensor to the
liquid line above the TXV as follows.
a.) Apply thermal compound (provided in kit) to an
area on the liquid line where you are mounting
the sensor. See Figure 7.
b.) Use the clamp (provided in kit) and attach the
sensor to the liquid line. See Figure 7.
c.) Wrap the sensor with insulating tape (provided
in kit).
2.Route the sensor wires through the compressor
area, past the blower and into the Control Box. See
Figure 9, page 8.
Continue with step 5. Route the Sensor Leads.
Figure 7. Liquid Line Temperature Sensor Location
5. Mount the Outdoor Temperature Sensor
In this step you attach the outdoor sensor to the
outside of the outdoor coil. See Figure 9, page 8.
1. On the outdoor fan grill, remove eight (8) plastic
screw caps covering the fan screws. Then, remove
the eight (8) screws that secure the outdoor fan grill
to the top of the unit. See Figure 8. Remove the fan
assembly and place it on top of the unit with the fan
blades facing up.
2. Remove the back outdoor coil louvered panel to
access the outer surface of the outdoor coil:
a.) Remove the three (3) screws across the top of the
panel.
b.) Lift or slide the panel up enough to unhook it
from the slots in the unit.
3. Insert the retainer into the outside surface of the
spine-fin coil about half way up the outside surface
of the coil. Attach the outdoor air sensor to the clip
on the outdoor air sensor retainer dart. See Figure
8 below and Figure 9, page 8.
Insert Dart End into
Coil
Attach Air Sensor to
Clip on Retainer Dart
Figure 8. Mount Outdoor Air Sensor
Continue with step 6. Route the Sensor Leads.
6. Route the Sensor Leads
In this step you route the outdoor sensor leads to
the Control Box.
1.Route the outdoor temperature sensor lead wires
down to the intermediate top and then under the
outdoor coil. See Figure 9, page 8. You may need to
lift the coil slightly to slide the sensor lead wires
under the coil.
2.Route the outdoor temperature sensor leads down
into the compressor compartment through the one
(1") hole. See Figure 9. Using a wire tie from the
kit, tie the leads to the existing wiring at the point
where the leads go through the sheet metal
opening. Ensure that the leads DO NOT lie
across the sharp sheet metal edges of the
openings.
3.Continue to route the sensor leads through
the compressor compartment, through the
partition, and into the Blower compartment. From
the Blower compartment, continue to route the
leads into the Control Box. Use wire ties to
secure the leads to the existing wires. This
ensures that any wiring is kept away from
the blower and sharp sheet metal.
4.In the Control Box, route the sensor leads to the
Control Module. You make the connections later.
5.Reinstall the outdoor fan assembly with the eight
(8) screws and screw caps you removed in the
Mount the Liquid Line Temperature Sensor section.
6. To make your connections, continue with step 7Connect Module Wires, page 9.
7
Page 8
Installer’s Guide
REMOVE 8 FAN GRILL SCREWS
TO ROUTE OUTDOOR SENSOR WIRES
BEHIND COIL INTO COMPRESSOR AREA
LIQUID LINE
SENSOR WIRES
OUTDOOR
TEMPERATURE
SENSOR DART
LOUVERED PANEL REMOVE 3 SCREWS
LIFT PANEL UP TO UNHOOK FROM SLOT
OUTDOOR
TEMPERATURE
SENSOR WIRES
Figure 9. Mount Outdoor Temperature Sensor
8
Page 9
Installer’s Guide
7. Connect Control Module Wires
There are five (5) Control Module wiring configurations. Depending on your configuration continue with
the section that applies.
• 7a. 2/4YC** and 4TC** Single Phase 230 Volt
Cooling and Gas/Electric Models. Go to page 9.
• 7b. 2/4WC** & 4DC** Single Phase 230 Volt
Heat Pump Models. Go to page 10.
• 7c. 2/4YC** and 4TC** Three Phase 230 & 460
Volt Cooling and Gas/Electric Models. Go to page
11.
• 7d. 2/4WC** & 4DC** Three Phase 230 Volt
Heat Pump Models. Go to page 12.
• 7e. 2/4WC** Three Phase 460 Volt Heat Pump
Models. Go to page 13.
7a. 2/4YC** and 4TC** Single Phase 230 Volt Cooling
and Gas/Electric Models. See Figure 10.
Disconnect the black fan motor lead from the
contactor (this wire is attached to contactor terminal
“L2”, with a quick connect terminal). Cut the
terminal off of this wire and strip the end about 1/2
inch. Select one of the black wires from the SSR relay
on the Control Module, cut the terminal off and strip
the end about 1/2 inch. Connect these two (the black
fan motor lead to the black SSR lead) with a wire nut
supplied.
Connect the other black wire from the solid state
relay (SSR) to the contactor terminal “L2” (from
where the fan motor lead was disconnected).
Connect Low voltage wires (BYO):
1. Connect the 3-pin BYO low voltage wire harness
(supplied in kit) to J5 on the Control Module (3-pin
male connector). See Figure 11. Note: to ease the
insertion of the connector housing on to the J5
header, place the connector on the tips of the three
header pins. Angle the connector upward toward
the header latch while pushing connector over the
header pins.
2. Connect the yellow lead wire of the harness to a
¼ " male tab on the right hand side of the main
contactor (low voltage contactor coil terminal).
3. Connect the blue lead wire of the harness to the
wire nut junction of the blue wire (use new wire
nuts from kit).
4. Connect the orange wire to the wire nut junction
of the yellow wire (use new wire nuts from kit).
5. Connect the Liquid Line Sensor to J2 on the Control Module. See Figure 11 on page 10.
6. Connect the Outdoor Temperature Sensor (Ambient Sensor) to J3 on the Control Module. See Figure 11 on page 10.
7. Reinstall louvers and panels. Continue with step 8.System Setup, Page 14.
Figure 10. 2/4YC** and 4TC** Single Phase 230 Volt Cooling and Gas/Electric Models
IMPORTANT — Retain this wiring diagram; please return this document to service information pack upon completion of work.
9
Page 10
Installer’s Guide
1 2 3 4
ON
OFF
S2
TEST
S1
AMBIENT
LIQUID
B Y O
ALERT
Lite
Port
RED
LED
GREEN
LED
S2-1,2,3,4
DIP SWITCHES
S1
TEST
SWITCH
AMBIENT
SENSOR
(OUTDOOR
TEMP SENSOR)
LIQUID
LINE
SENSOR
B,Y,O
J5
J2
J3
7b. 2/4WC** & 4DC** Single Phase 230 Volt Heat
Pump Models. See Figure 12.
Disconnect and remove the black lead from the Defrost Board relay to the "L2" terminal of the contactor
(the black wire is attached to the “COM” terminal of
the relay). Firmly hold relay when removing wire.
Connect one of the black leads from the (SSR) on the
Control Module to the position on the unit contactor
"L2" (where the previous wire was removed). Connect
the other black lead on the (SSR) on the Contoller
Module to the "COM" terminal on the Defrost Board.
Connect Low voltage wires (BYO):
1. Connect the 3-pin BYO low voltage wire harness
(supplied in kit) to J5 on the Control Module (3pin male connector). See Figure 11. Note: to ease
the insertion of the connector housing on to the J5
header, place the connector on the tips of the three
header pins. Angle the connector upward toward
the header latch while pushing connector over the
header pins.
2. Connect the yellow lead wire of the harness to a
¼ ” male tab on the right hand side of the main
contactor (low voltage contactor coil terminal). See
Figure 12.
3. Connect the blue lead wire of the harness to the
wire nut junction of the blue wire (use new wire
nuts in kit).
4. Connect the orange wire to the wire nut junction
of the orange wire (use new wire nuts from kit).
5. Connect the Liquid Line Sensor to J2 on the
Control Module. See Figure 11.
6. Connect the Outdoor Temperature Sensor (Ambient Sensor) to J3 on the Control Module.
7. Reinstall louvers and panels. Continue with step 8.System Setup, page 14.
B,Y,O
LIQUID
LINE
SENSOR
AMBIENT
SENSOR
(OUTDOOR
TEMP SENSOR)
Figure 11. Control Module Switches, Connectors, and LEDs
J5
J2
LIQUID
AMBIENT
J3
ALERT
RED
LED
Lite
Por t
1
S1
TEST
S1
TEST
SWITCH
ON
S2
OFF
GREEN
LED
S2-1,2,3,4
DIP SWITCHES
IMPORTANT — Retain this wiring diagram; please return this document to service information pack upon completion of work.
10
Figure 12. 2/4WC** & 4DC** Single Phase 230 Volt Heat Pump Models
Page 11
Installer’s Guide
7c 2/4YC** and 4TC** Three Phase 230 Volt Cooling
and Gas/Electric Models. See Figure 13.
Disconnect the black fan motor lead from the
contactor (this wire is attached to contactor terminal
“T2”, with a quick connect terminal). Cut the
terminal off of this wire and strip the end about 1/2
inch. Select one of the black wires from the SSR relay
on the Control Module, cut the terminal off and strip
the end about 1/2 inch. Connect these two ( the black
fan motor lead to the black SSR lead) with a wire nut
supplied.
Connect the other black wire from the SSR to the
contactor terminal “T2” (from where the fan motor
lead was disconnected).
Connect Low voltage wires (BYO):
1. Connect the 3-pin BYO low voltage wire harness
(supplied in kit) to J5 on the Control Module(3-pin
male connector). See Figure 14 on page 12. Note: to
ease the insertion of the connector housing on to the
J5 header, place the connector on the tips of the
three header pins. Angle the connector upward toward the header latch while pushing connector over
the header pins.
2. Connect the yellow lead wire of the harness to a
¼ " male tab on the right hand side of the main
contactor (low voltage contactor coil terminal). See
Figure 13.
3. Connect the blue lead wire of the harness to the
wire nut junction of the blue wire (use new wire
nuts from kit).
4. Connect the orange wire to the wire nut junction
of the yellow wire (use new wire nuts from kit).
5. Connect the Liquid Line Sensor to J2 on the Control Module.See Figure 14 on page 12.
6. Connect the Outdoor Temperature Sensor (Ambient Sensor) to J3 on the Control Module.
7. Reinstall louvers and panels. Continue with step 8.System Setup, Page 14.
Figure 13. 2/4YC** and 4TC** 230/460 volt Three Phase Cooling and Gas/Electric Models
IMPORTANT — Retain this wiring diagram; please return this document to service information pack upon completion of work.
11
Page 12
Installer’s Guide
1 2 3 4
ON
OFF
S2
TEST
S1
AMBIENT
LIQUID
B Y O
ALERT
Lite
Port
RED
LED
GREEN
LED
S2-1,2,3,4
DIP SWITCHES
S1
TEST
SWITCH
AMBIENT
SENSOR
(OUTDOOR
TEMP SENSOR)
LIQUID
LINE
SENSOR
B,Y,O
J5
J2
J3
7d. 2/4WC** & 4DC** Three Phase 230 Volt Heat
Pump and Dual Fuel Models. See Figure 15.
Disconnect and remove the black lead from the Defrost Board relay to the "T2" terminal of the contactor
(the black wire is attached to the “COM” terminal of
the relay). Firmly hold relay when removing wire.
Connect one of the black leads from the (SSR) on the
Control Module to the position on the unit contactor
"T2" (where the previous wire was removed). Connect
the other black lead on the (SSR) on the Control
Module to the "COM" terminal on the Defrost Board.
Connect Low voltage wires (BYO):
1. Connect the 3-pin BYO low voltage wire harness
(supplied in kit) to J5 on the Control Module (3pin male connector). See Figure 14. Note: to ease
the insertion of the connector housing on to the J5
header, place the connector on the tips of the three
header pins. Angle the connector upward toward
the header latch while pushing connector over the
header pins.
2. Connect the yellow lead wire of the harness to a
¼” male tab on the right hand side of the main
contactor (low voltage contactor coil terminal). See
Figure 15.
3. Connect the blue lead wire of the harness to the
wire nut junction of the blue wire (use new wire
nuts in kit).
4. Connect the orange wire to the wire nut junction
of the orange wire (use new wire nuts from kit).
5. Connect the Liquid Line Sensor to J2 on the
Control Module. See Figure 14.
6. Connect the Outdoor Temperature Sensor (Ambient Sensor) to J3 on the Control Module.
7. Reinstall louvers and panels. Continue with step 8.System Setup, page 14.
B,Y,O
LIQUID
LINE
SENSOR
AMBIENT
SENSOR
(OUTDOOR
TEMP SENSOR)
Figure 14. Control Module Switches, Connectors, and LEDs
J5
J2
LIQUID
AMBIENT
J3
ALERT
RED
LED
Lite
Por t
1
S1
TEST
S1
TEST
SWITCH
ON
S2
OFF
GREEN
LED
S2-1,2,3,4
DIP SWITCHES
IMPORTANT — Retain this wiring diagram; please return this document to service information pack upon completion of work.
12
Figure 15. 2/4WC** & 4DC** Three Phase 230 Volt Heat Pump Models
Page 13
Installer’s Guide
7e. 2/4WC** Three Phase 460 Volt Heat Pump Models
(see Figure 16)
Disconnect and remove the black lead from the fan
relay (terminal #1) to the unit contactor "T2". Connect
one black lead from the SSR on the Control Module to
the #1 terminal of the fan relay. Connect the other
black lead to the unit contactor "T2" terminal.
Connect Low voltage wires (BYO):
1.Connect the 3-pin BYO low voltage wire harness
(supplied in kit) to J5 on the Control Module (3-pin
male connector). See Figure 14. NOTE: to ease the
insertion of the connector housing on to the J5
header, place the connector on the tips of the three
header pins. Angle the connector upward toward
the header latch while pushing connector over the
header pins.
2.Connect the yellow lead wire of the harness to a
¼ " male tab on the right hand side of the main
contactor (low voltage contactor coil terminal). See
Figure 16.
3.Connect the blue lead wire of the harness to the
wire nut junction of the blue wire (use new wire
nuts in kit).
4.Connect the orange wire to the wire nut junction
of the orange wire (use new wire nuts from kit).
See Figure 16.
5.Connect the Liquid Line Sensor to J2 on the
Control Module. See Figure 14.
6.Connect the Outdoor Temperature Sensor (Ambient Sensor) to J3 on the Control Module.
7.Reinstall louvers and panels. Continue with step 8.System Setup, page 14.
Figure 16. 2/4WC** Three Phase 460 Volt Heat Pump Models
IMPORTANT — Retain this wiring diagram; please return this document to service information pack upon completion of work.
13
Page 14
Installer’s Guide
8. System Setup
The Control Module contains a momentary test
switch (S1) and a 4-position installer selectable
dip switch (S2). Both components are located in
the lower right hand corner of the Control
Module. See Figure 11 on page 10.
8a. Test Switch (S1)
The test switch provides a means of verifying that
the fan motor is under the control of the Low
Ambient Control Module. A "Y" signal must be
present in order to test the control. Depressing the
test switch causes the fan to alternately cycle on
(for 3 seconds) and off (for 3 seconds) for a total
time of 12 seconds. The on / off fan operation may
be observed by watching the fan once the test
function has been invoked or by monitoring the
head pressure using a gauge set. The LED on the
solid state relay should light when voltage is being
applied to the fan motor. Once the 12-second test
period is complete the control resumes normal
control operation.
8b. Dip Switches (S2)
The Control Module will control a liquid
temperature set point as determined by the dip
switch settings. The dip switch is used:
1. To select either Automatic mode or Manual
Mode operation (S2 dip switch 4 setting).
2. To select the liquid temperature set point (S2
dip switch 1, 2 and 3 settings).
Automatic Mode (S2 dip switch 4 in “Off”
position) - The Control Module determines the
approach temperature based upon the liquid and
ambient temperature readings. The approachtemperature = liquid temperature – ambient
temperature. The approach temperature is
calculated only when the ambient temperature is
in the range of 65 to 75 deg F and the outdoor fan
is on continuously. If the Control Module has not
yet acquired an approach temperature, S2 dip
switch 1, 2 and 3 settings are used for
determining the liquid temperature set point the
same as in Manual Mode. If the Control Module
has acquired an approach temperature, then the
liquid temperature set point is determined as
follows:
Liquid Temperature Set Point = ApproachTemperature + 70 deg F
Manual Mode (S2 dip switch 4 in “On” position) The S2 dip switch 1,2,3 settings are read by the
Control Module and used to determine the liquid
temperature set point when:
1) Y is first applied,
2) After initial startup mode completion, during
the system control mode and no sooner than six
minutes after Y is applied.
The liquid temperature set point will not change
during system start-up.
The dip switches should be set prior to initial
application of the Y signal to the Control Module.
The dip switches should be set for each specific
HVAC system based upon the following
instructions:
8c. Determine liquid temperature set point
Reference appropriate high side charging chart
for liquid pressure for cooling units and head
pressure for heat pump units.
Locate the high side pressure for 70 deg F
outdoor temperature at the expected indoor wet
bulb temperature in Table 2. Correct the high
side pressure according to the specific unit being
used. For Heat pumps subtract 7 psi, for cooling
only units subtract 0 (zero) psi. Using the
refrigerant properties chart, find the saturation
temperature for the calculated liquid pressure.
Subtract the anticipated sub-cooling temperature
(typically 12 degrees) from the saturation
temperature to obtain an estimate of the liquid
temperature. Set S2 dip switch 1, 2 and 3 settings
to the nearest liquid temperature set point in the
table below.
S2 Dip Switch4: Off - Automatic Mode
(recommended setting)
On - Manual Mode
Table 2. Liquid Temperature Set Point
LIQUID TEMP
SET POINT°F
70 °FOFFOFFOFF
76 °FOFFOFFON
82 °FOFFONOFF
88 °FOFFONON
94 °FONOFFOFF
100 °FONOFFON
106 °FONONOFF
112 °FONONON
8d. LEDs
The Control Module contains two LEDs, one
green and one red surface mount. See Figure 11
on page 10. The green LED is a status indicator
labeled Lite Port on the Control Module and
flashes at a ½ second on (plus fast blink at the
end for lite port data) and ½ second off rate in
the cooling mode. In the heating mode the green
DIP
SWITCH 1
DIP
SWITCH 2
SWITCH 3
DIP
14
Page 15
Installer’s Guide
LED is full on with a blink/flicker OFF (LitePort
data transmission) every second.
The red LED is a small surface mount component
located near the end of the large capacitor. The
red LED is labeled ALERT on the Control Module. The red LED indicator is normally off. If the
red LED is on or flashing then a fault is indicated
according to the following:
If the cause of a fault is cleared or repaired then
the red LED fault indication will clear with the
removal and reapplication of 24 VAC power (Y) to
the control.
Table 3. Control Module Red LED Status
sutatSDELdeRstluseR
NOdnoceS01/1:gnihsalF
ffOdnoceS01/1
NOdnoceS½:gnihsalF
ffOdnoceS½
ylsuounitnocNOdraobtluaFMORPEEC2I
Control Module SSR LED.
The solid state relay (SSR) on the Control Module
also contains a green LED indicator. This LED
indicates when the solid state relay is energized
by the control. If the control is cycling the fan then
this LED will be on/off accordingly.
tluaFrosneSdiuqiL
FrosneStneibmA
tlua
9. Attach the Information label
Attach the Information Label to the Control Box
cover. This label identifies the fan motor cycling
during low ambient operation.
10. System Check-Out
10a. 2/4YC ** and 4TC** Units only
• Verify that the Control Module is installed and
wired per the instructions contained within this
installer’s guide (J5-Blue connected to “B”, J5Yellow connected to “Y”, J5-Orange connected to
“Y”, Liquid sensor installed and connected, ambient sensor installed and connected).
• If uncertain about S2 dip switch 1,2,3,4 settings,
leave in the factory preset position.
• Apply power to the unit. Apply “Y” control signal.
• Verify the green LED is flashing at ½ second
ON ½ second OFF rate.
• Verify no red LED faults are present.
• The fan should run continuously for a minimum
of 10 seconds after “Y” is applied. After 10 seconds
the control may begin to cycle the fan if the
ambient outdoor temperature is 70 degrees or
below. If the fan is cycling and the outdoor temperature is below 70 degrees, the control is
working. If after 10 seconds of “Y” application the
fan is on continuously, the TEST Switch (S1)
may be used to verify the Control Module has
control over the fan. Momentarily depress the
TEST Switch (S1) on the Control Module. The fan
should then cycle 3 seconds on then 3 seconds off
for 12 seconds.
Note: If the green LED on the Control Module is
full on with a blink/flicker OFF every second make
certain the orange wire from the Control Module is
connected to “Y” per these instructions.
10b. 2/4WC** and 4DC** Units Only
• Verify that the kit is installed and wired per the
instructions contained within this installer’s guide.
(J5-Blue connected to “B”, J5-Yellow connected to
“Y”, J5-Orange connected to “O”, Liquid sensor
installed and connected, Ambient sensor installed
and connected).
• If uncertain about dip switch settings (S2-1,2,3,4),
leave in the factory preset position.
.elbariaperdleiftoN.eruliaf
• Apply power to the unit. Apply “Y” and “O” control
signal.
• Verify the green LED is flashing at ½ second ON ½
second OFF rate.
• Verify no red LED faults are present.
• The fan should run continuously for a minimum of
10 seconds after “Y” and “O” have been applied.
After 10 seconds the control may begin to cycle the
fan if the ambient outdoor temperature is 70 deg or
below. If the fan is cycling and the outdoor temperature is below 70 deg, the control is working. If after
10 seconds of “Y” application the fan is on continuously, the TEST Switch (S1) may be used to verify
the Control Module has control over the fan. Momentarily depress the TEST Switch (S1) on the
Control Module. The fan should then cycle 3 seconds on then 3 seconds off for 12 seconds.
NOTE: If the green LED is full on with a blink/
flicker OFF every second make certain the orange
wire from the Control Module is connected to “O” per
these instructions and the “O” signal is present.
The Control Module will leave the fan ON continuously during heating mode, that is No “O” signal
present. The green LED is full on with a blink/
flicker off every second in the heating mode.
15
Page 16
Installer’s Guide
Trane
6200 Troup Highway
Tyler, TX 75707-9010
16
The manufacturer has a policy of continuous product and product data improvement. It
reserves the right to change design and specification without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.