Trane BAYHTR1405A, BAYHTR1405, BAYHTR1408, BAYHTR1408A, BAYHTR1410A Installer's Manual

...
EHTR-IN-39
INSTALLER'S
Library Product Section
GUIDE
ALL phases of this installation must comply with
NATIONAL, STATE AND LOCAL CODES
Model:
BAYHTR1405A BAYHTR1405 BAYHTR1408A BAYHTR1408 BAYHTR1410A
WARNING:
A. GENERAL
These air handlers and heaters are designed so that all wiring between the heater and air handler is accom­plished via mating polarized plugs, power for the air handler is provided from heater circuit 1, so that only one conduit (power source) is needed to provide power to the unit on single circuit applications.
1. Check the applicable tables to insure that the Heater selected is approved for use with the air handler in which it is to be applied, in the cofiguration in which it is to be installed.
2. Check the components received for damage. Report any defects or shortages to the transportation com­pany immediately.
3. Be sure power supply agrees with listing shown on heater nameplate.
B. INSTALLATION With
1. Remove the blower access panel from the front of the air handler unit.
2. Unplug the female polarized plug from the air handler electrical junction box and remove the junction box, male polarized plug, power wiring and discard .
3. Remove the cover from the heater compartment of the air handler and discard.
4. Remove the cover from the heater field wiring and control compartment box. An adapter plate is pro-
vided for heaters which are used with air han­dlers that are 21.5" wide or wider. When re­quired, attach the adapter plate to the back of the heater on the side opposite the knockouts using 2 screws.
Since the manufacturer has a policy of continuous product improvement, it reserves the right to change specifications and design without notice.
© American Standard Inc. 1998
BAYHTR1410 BAYHTR3410 BAYHTR1415A BAYHTR3415 BAYHTR1419B
HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING
5. Remove the appropriate knockouts in the heater field
6. Insert the heater assembly into the heater cavity of the
IMPORTANT: Conduit must attach directly to the heater
7. Make all wiring connections per applicable field wiring
TWG Air Handlers
8. Connect the female polarized plug (disconnected in
9. Refer to the heater airflow chart on the air handler
10. For heaters with self contained circuit breakers, an
11. Replace all panels removed during the heater instal-
Product Model Literature Type Sequence Date File No. Supercedes
Supplementary Electric Heaters
for Air Handler Installations
wiring compartment. See Figure 1 on page 2. Remove the appropriate knockouts in the air handler for making electrical connections to the heater. The holes in the air handler must align with the holes in the heater field wiring compartment.
air handler so that the field wiring holes in the air handler and the heater will align. Secure the heater compartment to the air handler with the four screws removed from the hardware envelope.
control box.
diagrams in these instructions. All instructions must conform to national and local electrical codes.
item 2) from the air handler control box to the male polarized plug on the bottom of the heater control box
rating nameplate for the appropriate minimum blower speed tap selection to be used with an approved heater installed.
opening in the blower access panel is provided so that the breakers may be operated without removal of the blower access panel. Remove the metal cover from the circuit breaker opening in the air handler access panel and discard, cut out the fiberglass insulation only in the areas where the circuit breakers will extend through the opening. Install the plastic "AirTite" circuit breaker cover in the front panel opening with the two screws provided.
lation.
18-HB13D5-1
Service Literature
Unitary Accessories
Electric, Steam, Hot Water Coils
September 1998
SU-UN-ACC-EHTR-IN-39 9/98
Unitary
TVF
39
New
INSTALLER'S GUIDE
C. INSTALLATION with TWE/TVF Air Handlers
1. Position the air handler in the vertical position for ease of installing the heater .
2. Remover the blower access panel from the front of the air handler.
3. Unplug the female polarized plug from the male side. The male side is mounted in a bracket on the upper left hand corner of the air handler. The female side of the polarized plug will be connected to the male polarized plug of the heater.
4. Remove the cover from the heater field wiring and control compartment box. An adapter plate is
provided for heaters which are used with air handlers that are 21.5” wide or wider. When required, attach the adapter plate to the back of the heater on the side opposite the knockouts using 2 screws.
5. Remove the appropriate knockouts in the heater field wiring compartment. See Figure 1 on page 2. Remove the appropriate knockouts in the air handler for making electrical connections to the heater. The holes in the air handler must align with the holes in the heater field wiring compartment.
6. Insert the heater assembly into the heater cavity of the air handler so that the field wiring holes in the air handler and the heater will align. Secure the heater to the air handler compartment with the 4 screws provided in the hardware envelope.
7/8” diameter hole in the side panel of the air handler, adjacent to the air handler control box.
NOTE: Air handlers approved to use the 1426 heater have
a plate covering the lower 1.2” of the heater cavity. This plate must be left in place for a blower barrier seal. The plate is removed only when the 1426 heater is used.
IMPORTANT: Conduit must attach directly to the
heater control box.
8. Make all wiring connections per applicable field wiring diagrams. All instructions must conform to national and local electrical codes.
9. Connect the female polarized plug (disconnected in item 3) from the air handler control box to the male polarized plug on the bottom of the heater control box.
10. Refer to the heater airflow chart on the air handler rating nameplate for the appropriate minimum blower speed tap selection to be used with the approved heater installed.
11. For heaters with self contained circuit breakers, an opening in the blower access panel is provided so that the breakers may be operated without removal of the blower access panel. Remove the metal cover from the circuit breaker opening on the air handler access panel and discard. Cut out the fiberglass insulation only in the areas where the circuit breakers will extend through the opening. Install the plastic “AirTite” circuit breaker cover in the front panel opening with the two screws provided.
7. Install the hole plug from the hardware envelope in the
rebmuN
fo
stiucriC
esahP
Page 2
retaeH
.oNledoM
A5041RTHYABseY11 08.4004610206.3003213.71
5041RTHYABoN11 08.4004610206.3003213.71
A8041RTHYABseY11 86.7002622367.5007917.72
8041RTHYABoN11 86.7002622367.5007917.72
A0141RTHYABseY11 06.9008230402.7006426.43 0141RTHYABoN11 06.9008230402.7006426.43 0143RTHYABoN13 06.9008236.4302.70064203
A5141RTHYABseY21 63.510042542/0435.11003938.02/6.43 5143RTHYABoN13 63.51004252.8335.11003931.33
B9141RTHYABseY21 02.910055604/0424.41002947.43/7.43
tiucriC
rekaerB
12. Replace all panels removed during the heater instal­lation.
ATADRETAEH--RTHYAB
TLOV042TLOV802
yticapaC
HUTBWKHUTBWK
retaeH
repspmA
tiucriC
yticapaC
retaeH
repspmA
tiucriC