Trane BAYHTR1405A, BAYHTR1405, BAYHTR1408, BAYHTR1408A, BAYHTR1410A Installer's Manual

...
Page 1
EHTR-IN-39
INSTALLER'S
Library Product Section
GUIDE
ALL phases of this installation must comply with
NATIONAL, STATE AND LOCAL CODES
Model:
BAYHTR1405A BAYHTR1405 BAYHTR1408A BAYHTR1408 BAYHTR1410A
WARNING:
A. GENERAL
These air handlers and heaters are designed so that all wiring between the heater and air handler is accom­plished via mating polarized plugs, power for the air handler is provided from heater circuit 1, so that only one conduit (power source) is needed to provide power to the unit on single circuit applications.
1. Check the applicable tables to insure that the Heater selected is approved for use with the air handler in which it is to be applied, in the cofiguration in which it is to be installed.
2. Check the components received for damage. Report any defects or shortages to the transportation com­pany immediately.
3. Be sure power supply agrees with listing shown on heater nameplate.
B. INSTALLATION With
1. Remove the blower access panel from the front of the air handler unit.
2. Unplug the female polarized plug from the air handler electrical junction box and remove the junction box, male polarized plug, power wiring and discard .
3. Remove the cover from the heater compartment of the air handler and discard.
4. Remove the cover from the heater field wiring and control compartment box. An adapter plate is pro-
vided for heaters which are used with air han­dlers that are 21.5" wide or wider. When re­quired, attach the adapter plate to the back of the heater on the side opposite the knockouts using 2 screws.
Since the manufacturer has a policy of continuous product improvement, it reserves the right to change specifications and design without notice.
© American Standard Inc. 1998
BAYHTR1410 BAYHTR3410 BAYHTR1415A BAYHTR3415 BAYHTR1419B
HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING
5. Remove the appropriate knockouts in the heater field
6. Insert the heater assembly into the heater cavity of the
IMPORTANT: Conduit must attach directly to the heater
7. Make all wiring connections per applicable field wiring
TWG Air Handlers
8. Connect the female polarized plug (disconnected in
9. Refer to the heater airflow chart on the air handler
10. For heaters with self contained circuit breakers, an
11. Replace all panels removed during the heater instal-
Product Model Literature Type Sequence Date File No. Supercedes
Supplementary Electric Heaters
for Air Handler Installations
wiring compartment. See Figure 1 on page 2. Remove the appropriate knockouts in the air handler for making electrical connections to the heater. The holes in the air handler must align with the holes in the heater field wiring compartment.
air handler so that the field wiring holes in the air handler and the heater will align. Secure the heater compartment to the air handler with the four screws removed from the hardware envelope.
control box.
diagrams in these instructions. All instructions must conform to national and local electrical codes.
item 2) from the air handler control box to the male polarized plug on the bottom of the heater control box
rating nameplate for the appropriate minimum blower speed tap selection to be used with an approved heater installed.
opening in the blower access panel is provided so that the breakers may be operated without removal of the blower access panel. Remove the metal cover from the circuit breaker opening in the air handler access panel and discard, cut out the fiberglass insulation only in the areas where the circuit breakers will extend through the opening. Install the plastic "AirTite" circuit breaker cover in the front panel opening with the two screws provided.
lation.
18-HB13D5-1
Service Literature
Unitary Accessories
Electric, Steam, Hot Water Coils
September 1998
SU-UN-ACC-EHTR-IN-39 9/98
Unitary
TVF
39
New
Page 2
INSTALLER'S GUIDE
C. INSTALLATION with TWE/TVF Air Handlers
1. Position the air handler in the vertical position for ease of installing the heater .
2. Remover the blower access panel from the front of the air handler.
3. Unplug the female polarized plug from the male side. The male side is mounted in a bracket on the upper left hand corner of the air handler. The female side of the polarized plug will be connected to the male polarized plug of the heater.
4. Remove the cover from the heater field wiring and control compartment box. An adapter plate is
provided for heaters which are used with air handlers that are 21.5” wide or wider. When required, attach the adapter plate to the back of the heater on the side opposite the knockouts using 2 screws.
5. Remove the appropriate knockouts in the heater field wiring compartment. See Figure 1 on page 2. Remove the appropriate knockouts in the air handler for making electrical connections to the heater. The holes in the air handler must align with the holes in the heater field wiring compartment.
6. Insert the heater assembly into the heater cavity of the air handler so that the field wiring holes in the air handler and the heater will align. Secure the heater to the air handler compartment with the 4 screws provided in the hardware envelope.
7/8” diameter hole in the side panel of the air handler, adjacent to the air handler control box.
NOTE: Air handlers approved to use the 1426 heater have
a plate covering the lower 1.2” of the heater cavity. This plate must be left in place for a blower barrier seal. The plate is removed only when the 1426 heater is used.
IMPORTANT: Conduit must attach directly to the
heater control box.
8. Make all wiring connections per applicable field wiring diagrams. All instructions must conform to national and local electrical codes.
9. Connect the female polarized plug (disconnected in item 3) from the air handler control box to the male polarized plug on the bottom of the heater control box.
10. Refer to the heater airflow chart on the air handler rating nameplate for the appropriate minimum blower speed tap selection to be used with the approved heater installed.
11. For heaters with self contained circuit breakers, an opening in the blower access panel is provided so that the breakers may be operated without removal of the blower access panel. Remove the metal cover from the circuit breaker opening on the air handler access panel and discard. Cut out the fiberglass insulation only in the areas where the circuit breakers will extend through the opening. Install the plastic “AirTite” circuit breaker cover in the front panel opening with the two screws provided.
7. Install the hole plug from the hardware envelope in the
rebmuN
fo
stiucriC
esahP
Page 2
retaeH
.oNledoM
A5041RTHYABseY11 08.4004610206.3003213.71
5041RTHYABoN11 08.4004610206.3003213.71
A8041RTHYABseY11 86.7002622367.5007917.72
8041RTHYABoN11 86.7002622367.5007917.72
A0141RTHYABseY11 06.9008230402.7006426.43 0141RTHYABoN11 06.9008230402.7006426.43 0143RTHYABoN13 06.9008236.4302.70064203
A5141RTHYABseY21 63.510042542/0435.11003938.02/6.43 5143RTHYABoN13 63.51004252.8335.11003931.33
B9141RTHYABseY21 02.910055604/0424.41002947.43/7.43
tiucriC
rekaerB
12. Replace all panels removed during the heater instal­lation.
ATADRETAEH--RTHYAB
TLOV042TLOV802
yticapaC
HUTBWKHUTBWK
retaeH
repspmA
tiucriC
yticapaC
retaeH
repspmA
tiucriC
Page 3
INSTALLER'S GUIDE
NOTE 2
NOTE 1
SIDE ENTRANCE
FOR HEATER ELECTRICAL CONNECTIONS
RESISTANCE HEATER CONTROL BOX
POLARIZED PLUG
NOTE 1
NOTE 2
TOP ENTRANCE
FOR HEATER ELECTRICAL CONNECTIONS
CABINET
NOTES
1. HEATER LINE VOLTAGE KNOCKOUT LOCATIONS FOR 1" OR 1-1/2" CONDUIT. CONDUIT MUST BE ATTACHED DIRECTLY TO THE HEATER CONTROL BOX. WIRE AND CONDUIT SIZE MUST COMPLIY WITH N.E.C.
2. HEATER LINE VOLTAGE KNOCKOUT LOCATIONS FOR 3/ 4" OR 1-1/4" CONDUIT. CONDUIT MUST BE ATTACHED DIRECTLY TO THE HEATER CONTROL BOX. WIRE AND CONDUIT SIZE MUST COMPLIY WITH N.E.C.
3. BLOWER CIRCUIT POWER SUPPLY LEADS & LOW VOLT­AGE HEATER CONTROL LEADS FROM AIR HANDLER CONTROL BOX ARE CONNECTED TO THE HEATER VIA A POLARIZED PLUG
LEADS FROM AIR HANDLER CONTROL BOX (SEE NOTE 3)
BLOWER ACCESS PANEL
Page 3
Page 4
INSTALLER'S GUIDE
RIA
RELDNAHRELDNAH
RELDNAHRELDNAH
RELDNAH
LEDOM
REBMUNREBMUN
REBMUNREBMUN
REBMUN
FOREBMUN
RETAEHRETAEH
RETAEHRETAEH
RETAEH
SKCARSKCAR
SKCARSKCAR
SKCAR
FOREBMUN
STIUCRICSTIUCRIC
STIUCRICSTIUCRIC
STIUCRIC
A810FVT A420FVT A520FVT A030FVT A630FVT
A810GWT A520GWT A030GWT
A730/630GWT A240GWT A840GWT A060GWT C810EWT C420EWT C030EWT C630EWT C24OEWT C840EWT C060EWT P810EWT -------­P420EWT P030EWT P630EWT P24OEWT P840EWT P060EWT P360EWT E130EWT 0001/007 0001/007 0001/007 0001/007 0001/007 0001/007 5211/007 5211/007 0531/0001 E730EWT E040EWT E260EWT E560EWT
5041
wk08.4wk08.4
wk08.4wk08.4
wk08.4
112222224
111111122
L/L--M/L--M/L-------­L/L--H/L--H/L-------­L/L L/L M/L M/L M/L M/L H/L H/L-­L/L L/L M/L M/L M/L M/L M/M M/M-­L/L L/L M/L M/L M/L M/L M/M M/M H/H L/L L/L M/L M/L H/L H/L-----­L/L L/L M/L M/L M/L M/L H/L H/L-­L/L L/L L/L L/L L/L L/L M/L M/L-­L/L L/L L/L L/L L/L L/L M/L M/L-­L/L L/L L/L L/L L/L L/L M/L H/L-­L/L L/L L/L L/L L/L L/L L/L H/L M/L L/L L/L L/L L/L L/L L/L L/L L/L M/L
A5041
wk08.4wk08.4
wk08.4wk08.4
wk08.4
8041
wk86.7wk86.7
wk86.7wk86.7
wk86.7
A8041
wk86.7wk86.7
wk86.7wk86.7
wk86.7
SEE AIR HANDLER NAMEPLA TE.
MAY NOT BE APPRO VED IN ALL CONFIGURATIONS -
007/006 007/006 009/006 009/006 009/006 009/006 0031/0001 0031/0001 0031/0001
0011/006 0011/006 0011/006 0011/006 0011/006 0011/006 0041/0011 0041/0011 0041/0011 0051/009 0051/009 0051/009 0051/009 0051/009 0051/009 0081/0021 0081/0021 0081/0021 0051/009 0051/009 0051/009 0051/009 0051/009 0051/009 0081/0021 0081/0021 0081/0021
0143 01410141
01410141
0141
wk06.9wk06.9
wk06.9wk06.9
wk06.9
A0141
wk06.9wk06.9
wk06.9wk06.9
wk06.9
--------
----RTHYABREBMUNLEDOMRETAEH
5143
wk63.51wk63.51
wk63.51wk63.51
wk63.51
A5141
wk63.51wk63.51
wk63.51wk63.51
wk63.51
----
----
B9141
wk02.91wk02.91
wk02.91wk02.91
wk02.91
--
--
The Trane Company
Unitary Products Group 6200 Troup Highway Tyler, TX 75707-9010
An American-Standard Company
Page 4
Technical Literature - Printed in U.S.A.