Trane BAYRLAY004A, BAYECON201A, BAYECON200A Installer's Manual

18-HE39D9-6
Installer’s Guide
Horizontal Economizer & Rain Hood
Model: BAYECON200A BAYECON201A BAYRLAY004A
WARNING:
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service
information pack upon completion of work.
General
Important: The Economizer installation requires that you first install an air filter rack ordered separately. Use: BAYFLTR101A for 2/4YC*, WC*, TC*, DC* *018-3036A BAYFLTR201A for 2/4YC*, WC*, TC*, DC* *042-3060A.
When the economizer is installed in WC* models, relay accessory kit BAYRLAY004A is required. Refer to the drawing on page 6 to make your relay wiring connections in the Control Box.
Identify Economizer Kit Contents
Refer to Figure 2 on page 3 to identify the kit contents.
Inspect Contents
You must report damage and make claims to the transporta­tion company immediately. Report missing parts to your supplier immediately and replace with authorized parts only.
!
ELECTRIC SHOCK HAZARD OPEN AND LOCK OUT ALL UNIT DISCONNECTS PRIOR TO ACCESSORY INSTALLATION OR UNIT MAINTENANCE, TO PREVENT INJURY OR DEATH FROM ELECTRICAL SHOCK OR CONTACT WITH MOVING PARTS.
!
SAFETY HAZARD DO NOT REMOVE END COVERS FROM ECONOMIZER AC­TUATOR; THE SPRING-RETURN ASSEMBLY MAY RELEASE AND CAUSE PERSONAL INJURY.
Used with: 2/4TC*,WC*,YC*,DC* *018-036A 2/4TC*,WC*,YC*,DC* *042-060A
(Required with WC* models)
HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING
Install Economizer Kit
1. Remove the unit economizer/filter access panel, the evaporator coil and blower access panel, and the electri cal control box access panel, see Figure 1 on page 2.
2. Filter frame must be installed prior to economizer installa-
tion.
3. Apply two gaskets to horizontal economizer mounting flanges. See Figure 2 on page 3.
4a. Small Cabinet - BAYECON200A
(TC*,WC*,YC*,DC* *018A to 3036A)
Set the horizontal economizer over the horizontal return air opening on the unit. The notches in the bottom flange of the economizer clear the two existing screws below the return air opening of the unit.
4b. Medium Cabinet Only - - BAYECON201A
(TC*,WC*,YC*,DC* *042A to 3060A)
Apply a gasket to the economizer and slide the top flange of the economizer under the lip between the top and bottom sections of the unit. Mate the notches on
WARNING
WARNING
the top flange of the economizer with the existing screws between the top and bottom sections of the unit. The notches on the bottom flange of the economizer clear the two existing screws below the return air opening of the unit.
CAUTION
!
Use care when inserting the economizer in the return air compartment, to prevent damaging the foil faced insula­tion.
INSTALLER’S GUIDE
5. Drill three (3) 9/64” holes through the mating holes in the top flange of economizer and into the unit. Then, drive three (3) #10 sheet metal screws to secure the top.
6. Drill three (3) 9/64” engagement holes on each side of the economizer. Then, drive three (3) #10 sheet metal screws into each side of the economizer to the unit.
7.
Mount the Mixed Air sensor to the left Blower partition using two sheetmetal screw. See Figure 4, page 4. The 2 yellow wires will connect to the Economizer wiring harness in a later step. Install any economizer options (enthalpy sensor or CO2 sensor) at this time per instructions provided with the sensor.
8. Apply a gasket to the Rain Hood flanges. See Figure 2.
9. Place the Rain Hood over the horizontal return air opening of the economizer. See Figure 2. Use the #10 sheet metal screws provided to attach the hood to the economizer.
10.
Route the main wiring harness. From the Economizer assembly, route the main wiring harness to the Mixed Air sensor and to the Control Box. See Figure 3.
11. Connect the two (2) Mixed Air Sensor wires (pulled from harness) to the mating pigtail wires (with Stake-Ons) from the Mixed Air Sensor.
12. In the Control Box, complete the wiring connections per the wiring diagram on page 5. Secure all wires with wire ties so that there is no interference with any moving parts in the unit.
IMPORTANT - When the economizer is installed in heat pump models (WC*), a relay accessory kit (BAYRLAY004A) is required. Mount relay accessory kit in unit control box as illustrated on page 6.
13. Attach the return duct to the economizer.
14. Power the economizer and run the checkout procedure on page
7. Make desired adjustments to the controller: set the minimum occupied damper position, set the outside air (if enthalpy used), and the IAQ sensor (if used).
15. Replace the unit Coil access panel, the Blower access panel, and the Control Box access panel.
Top Sealing Flange
Horizontal Return Air Panel
Down Flow Return Air Panel
TC, WC, or YC Unit
Coil Access Panel
Control Box Access Panel
Blower Access Panel
Page 2
Figure 1. Remove Panels
Horizontal Economizer Assembly
Economizer A B C D E
BAYECON200AA 22" 20" 16-7/8" 15-11/16 11-11/16
BAYECON201AA 26" 22-21/32" 19" 17-11/16 14-11/16
INSTALLER’S GUIDE
NOTE: BAYECON200A economizer only contains two clearance notches in the top flange.
1.) From EconomizerAssembly, Pass Wire Harness Through Coil Grom­met. See View A.
Economizer
A
B
C
Duct
D
E
Figure 2. Apply Two Gaskets to Mounting Flanges
2.) Continue Routing Behind Compressor Compartment and into Blower Compartment.
4.) Continue Routing the Remaining Harness Through the Grommet and into the Control Box.
Gaskets (2)
Rain Hood
Location of Mixed Air Sensor
3.) Pull the 2 Mixed Air Sensor Wires (with Stake-Ons) from the Harness and Route Down Near the Mixed Air Sensor.
Figure 3. Main Wire Harness Routing
Page 3
Loading...
+ 5 hidden pages