Trane BAS-SVP10A-EN User Manual

Integration Manual
Trane Communicating Thermostats (BACnet)
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
August 2011 BAS-SVP10A-EN
Copyright
© 2011 Trane All rights reserved
This document and the information in it are the property of Trane and may not be used or reproduced inwhole or in part, without the written permission of Trane. Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
Trane and its logo are trademarks of Trane in the United States and other countries. All trademarks referenced in this document are the trademarks of their respective owners.
Warnings, Cautions, and Notices
Warnings, cautions, and notices are provided in appropriate places throughout this document:
WARNING
CAUTIONs
NOTICE:
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only accidents.
Table of Contents
Overview .............................................................. 5
Product Description ................................................5
Related Documents ................................................ 6
Planning Your Integration ...........................................6
“How To” Information .............................................. 6
Summary of BACnet Objects ............................................ 7
Supported BACnet Services ......................................... 7
Default Device Name and Default Device ID ........................... 7
Fan Coil Objects ................................................... 8
Rooftop and Heat Pump Objects .................................... 10
Standard Object Types Supported .................................. 12
List of Proprietary Properties ....................................... 13
Configuration Objects for Fan Coils .................................. 13
Configuration Objects for Rooftop and Heat Pump Units ............... 13
BACnet Object Properties .............................................. 14
Fan Coil Object Properties .......................................... 14
Rooftop and Heat Pump Object Properties ........................... 19
Objects You Can Use in Site Graphics ................................... 23
Fan Coils ......................................................... 23
Rooftop and Heat Pump Units ...................................... 24
Wiring Requirements for Communicating Thermostats ...................25
BACnet MS/TP Link Wiring ......................................... 25
BACnet Configuration Requirements ............................ 25
BACnet Wiring Best Practices ................................... 25
BACnet Wiring Procedure ......................................26
Trane BACnet Termination for BACnet Links ...................... 26
Product Specifications ............................................. 27
Network Adapter .................................................. 27
Communicating Thermostat Status LEDs ............................ 28
Troubleshooting .................................................. 28
Additional Information and Considerations .............................. 29
MS/TP Network Integration .........................................29
Site Graphics ................................................ 29
Free Programmed Objects or Loops (Supervisory Controllers Other
Than Tracer SC) ........................................... 29
Retries and Timeouts (Supervisory Controllers Other Than Tracer SC) . 30
BAS-SVP10A-EN 3
Objects and Parameters ........................................... 30
Tracer SC Network Configuration ................................... 32
Data Normalization .................................................... 36
Example: Occupancy Request ...................................... 36
Template: TStat_FanCoil_Trane ..................................... 36
Template: TStat_HeatPump_Trane .................................. 39
Template: TStat_RTU_Trane ........................................ 40
Trane Communicating Thermostat Points List ............................ 42
TStat_Fan_Coil_Trane ............................................. 42
TStat_HeatPump_Trane Template ................................... 43
TStat_RTU_Trane Template ........................................ 44
4 BAS-SVP10A-EN

Overview

This document is written to guide you through integration of the Trane Communicating Thermostats into an MS/TP network using the BACnet protocol and managed by a Tracer SC.

Product Description

The Trane Communicating Thermostats are available for heat pump, rooftop, and fan coil applications.
X13511541010 and -2010 (Heat Pump and Rooftop) These Trane Communicating Thermostats are BACnet MS/TP devices specifically designed for
single stage and multi-stage control of heating/cooling equipment such as rooftop and self­contained units. The products feature an intuitive, menu-driven, back-lit LCD display, which walks users through the programming steps, making the process extremely simple.
X13511543010 (Fan Coil) This Trane Communicating thermostat is specifically designed for fan coil control. The product
features a backlit LCD display with dedicated function menu buttons for simple operation. Three additional inputs are also provided for monitoring and / or various advanced functions. All models feature configurable System and Fan button functions to meet a variety of
applications.
Accurate temperature control is achieved due to the product’s PI proportional control algorithm, which virtually eliminates temperature offset associated with traditional, differential-based thermostats.
The Communicating Thermostats contain an SPST auxiliary switch that can be used to control lighting or auxiliary reheat. Three additional inputs are also provided for monitoring and / or various advanced functions.
The thermostats are also compatible with the occupancy sensor cover accessories. Thermostats equipped with an occupancy sensor cover provide advanced active occupancy logic, which will automatically switch occupancy levels from Occupied to Unoccupied as required by local activity being present or not. This advanced occupancy functionality provides advantageous energy savings during occupied hours without sacrificing occupant comfort.
BAS-SVP10A-EN 5
Overview

Related Documents

See the following documents for Communicating Thermostat installation and configuration information.
Trane Communicating Thermostats for Heat Pump Control User Guide (BAS-SVU10x-EN)
Trane Communicating Thermostats for Rooftop Control User Guide (BAS-SVU11x-EN)
Trane Communicating Thermostats for Fan Coil Control User Guide (BAS-SVU12x-EN)
See the following documents for Tracer SC network integration information.
Tracer™ SC System Controller Installation and Setup (BAS-SVX31x-EN)
Tracer™ BACnet™ Terminator Installation (X39641151-01x)
Unit Controller Wiring Guide For the Tracer SC™ System Controller (BAS-SVN03x-EN
Finally, see the following documents for information about equipment including fan coils, rooftop units, and heat pumps.
Communicating Thermostats for Rooftop and Heat Pump Control Product Data Sheet (BAS-PRC064-EN)
Communicating Thermostats for Fan Coil Control Product Data Sheet (BAS-PRC065-EN)
All these documents are available from your Trane distributor.

Planning Your Integration

Study the following information presented in the chapters of this guide as you plan the work:
Communicating Thermostat BACnet objects (points) and their properties (ranges, values, and enumeration sets for points). (See
Properties,” p. 14.)
Tips and considerations presented in “Additional Information and Considerations,” p. 29.If your network is managed by a Tracer SC, pay special attention to “Tracer SC Network
Configuration,” p. 32.
Wiring instructions in “Wiring Requirements for Communicating Thermostats,” p. 25.
Available Graphical User Interface (GUI) objects that you can use in graphics presented in
“Objects You Can Use in Site Graphics,” p. 23.

“How To” Information

The following “how to” questions are described or clarified either in this manual or in other documents cited in this table.
How do I set up alarming in Tracer SC?
How do I set the MAC address of the Trane Communicating Thermostat?
How do I install a Trane Communicating Thermostat on the Tracer SC link?
“Summary of BACnet Objects,” p. 7. and “BACnet Object
Question Information Location or Answer
See the Tracer™ SC System Controller Installation and Setup Manual (BAS-SVX31x-EN)
See “Default Device Name and Default Device ID,” p. 7. Also, see the appropriate User Guide listed in “Related
Documents” on this page.
See “No automatic installation,” p. 32.
6 BAS-SVP10A-EN

Summary of BACnet Objects

The Building Automation and Control Network (BACnet and ANSI/ASHRAE Standard 135-2004) protocol is a standard that allows building automation systems or components from different manufacturers to share information and control functions. BACnet provides building owners the capability to connect various types of building control systems or subsystems together for many uses. In addition, multiple vendors can use this protocol to share information for monitoring and supervisory control between systems and devices in a multi-vendor interconnected system.
The BACnet protocol identifies standard objects (data points) called BACnet objects. Each object has a defined list of properties that provide information about that object. BACnet also defines a number of standard application services that are used to access data and manipulate these objects and provides a client/server communication between devices.

Supported BACnet Services

The BACnet communicating thermostat meets all requirements for designation as an Application Specific Controller (B-ASC). The BACnet thermostat series supports the following BACnet Interoperability Building Blocks (BIBBs).
Table 1. BACnet Interoperability Building Blocks
Application Service Designation
Data Sharing – Read Property - B DS-RP-B
Data Sharing – Read Property Multiple - B DS-RPM-B
Data Sharing – Write Property - B DS-WP-B
Device Management - Device Communication Control - B DM-DCC-B
Device Management – Dynamic Device Binding - B DM-DDB-B
Device Management – Dynamic Object Binding - B DM-DOB-B
Notes:
The thermostat does not support seqmented requests or responses.
Models X13511541010 and -2010—Time synchronization can be made through a network even if the thermostat does not support the full date. Therefore, the device cannot claim conformance to the DeviceManagement – TimeSynchronization - B (DM-TS-B) service. The device object does not have the Local_Time or Local_Date properties.

Default Device Name and Default Device ID

The Default Device Name is set to: TStat_EquipType_Trane_MAC where: EquipType is FanCoil,
RTU, or HeatPump and MAC is the current MAC address of the device.
The Device Name is changed if you change the device MAC address.
The Device Name and Device ID properties are writable in the Device object. Both properties can be changed from any BACnet network management tool as long as the tool itself can write to these properties.
(X13511543010) Fan Coil Models
Default Device ID is set to: 7300MAC where MAC is the current MAC address of the device that you set from the Installer Configuration Parameter menu on the Trane Communicating Thermostat.
The Device ID changes if the device’s MAC address is changed. For example, when a fan coil communicating thermostat with a MAC address of 41 is connected to a network, its default Device Name will be TStat_FanCoil_Trane_41 and its default Device ID will be 730041.
BAS-SVP10A-EN 7
Summary of BACnet Objects
(X13511541010 and -2010) Rooftop and Heat Pump Models
Default Device ID is set to: 7600MAC where MAC is the current MAC address of the device.
The device ID and the Device Name change if you change the device’s MAC address. For example, when a heat pump communicating thermostat with a MAC address of 63 is connected to a network, its default Device Name will be TStat_HeatPump_Trane_63 and its default Device ID will be 760063.

Fan Coil Objects

Table 2. Objects table for fan coils (X13511543010)
Object Name Type and Instance Object Property
Room Temperature AV 7 Present_Value (R,W)
Room Temp Override BV 8 Present_Value (R,W)
Outdoor Temperature AV 9 Present_Value (R,W)
Supply Temperature AI 12 Present_Value (R)
AUX Command BV 14 Present_Value (R,W)
Sequence of Operation MV 15 Present_Value (R,W)
System Mode MV 16 Present_Value (R,W)
Fan Mode MV 17 Present_Value (R,W)
Occupancy Command MV 18 Present_Value (R,W)
Keypad Lockout MV 19 Present_Value (R,W)
Control Output GRP 20 Present_Value (R)
PI Heating Demand AV 21 Present_Value (R)
PI Cooling Demand AV 22 Present_Value (R)
Controller Status GRP 24 Present_Value (R)
AUX Status BI 25 Present_Value (R)
Heating Valve Status MV 26 Present_Value (R)
Cooling Valve Status MV 27 Present_Value (R)
Fan Status MV 28 Present_Value (R)
BI 1 Status BI 29 Present_Value (R)
BI 2 Status BI 30 Present_Value (R)
UI 3 Status BI 31 Present_Value (R)
Local Motion BI 32 Present_Value (R)
Effective Occupancy MV 33 Present_Value (R)
Controller Alarms GRP 34 Present_Value (R)
Window Alarm BI 35 Present_Value (R)
Filter Alarm BI 36 Present_Value (R)
Service Alarm BI 37 Present_Value (R)
Temperature Setpoints GRP 38 Present_Value (R)
Occupied Heat Setpoint AV 39 Present_Value (R,W)
Occupied Cool Setpoint AV 40 Present_Value (R,W)
Stand-by Heat Setpoint AV 41 Present_Value (R,W)
Stand-by Cool Setpoint AV 42 Present_Value (R,W)
8 BAS-SVP10A-EN
Summary of BACnet Objects
Table 2. Objects table for fan coils (X13511543010) (continued)
Object Name Type and Instance Object Property
Unoccupied Heat Setpoint AV 43 Present_Value (R,W)
Unoccupied Cool Setpoint AV 44 Present_Value (R,W)
General Options 1 GRP 45 Present_Value (R)
BI 1 Configuration MV 46 Present_Value (R,W)
BI 2 Configuration MV 47 Present_Value (R,W)
UI 3 configuration MV 48 Present_Value (R,W)
Menu Scroll BV 49 Present_Value (R,W)
Auto Mode Enable BV 50 Present_Value (R,W)
Temperature Scale BV 51 Present_Value (R,W)
Pipe Number MV 52 Present_Value (R,W)
AUX Configuration MV 54 Present_Value (R,W)
General Options 2 GRP 55 Present_Value (R)
Password Value AV 56 Present_Value (R,W)
Fan Mode Sequence MV 58 Present_Value (R,W)
Heating Setpoint Limit AV 58 Present_Value (R,W)
Cooling Setpoint Limit AV 59 Present_Value (R,W)
Setpoint Type BV 60 Present_Value (R,W)
Setpoint Function BV 61 Present_Value (R,W)
Temporary Occupancy Time MV 62 Present_Value (R,W)
Deadband AV 63 Present_Value (R,W)
Reheat Time Base BV 64 Present_Value (R,W)
Proportional Band MV 65 Present_Value (R,W)
Auto Fan BV 66 Present_Value (R,W)
Stand-by Time AV 67 Present_Value (R,W)
Unoccupied Time AV 68 Present_Value (R,W)
Output Configuration Options GRP 74 Present_Value (R)
Control Type BV 75 Present_Value (R,W)
Floating Motor Timing MV 76 Present_Value (R,W)
On Off Control CPH MV 77 Present_Value (R,W)
BAS-SVP10A-EN 9
Summary of BACnet Objects

Rooftop and Heat Pump Objects

Table 3. Rooftop and heat pump ungrouped objects
Type and
Object Name
Room Temperature AV 7 Present_Value (R,W) √√ √ Room Temp Override BV 8 Present_Value (R,W) √√ √ Outdoor Temperature AV 9 Present_Value (R,W) √√ √ Outdoor Temp Override BV 10 Present_Value (R,W) √√ √ Room Humidity AV 11 Present_Value (R) Occupancy Command MV 12 Present_Value (R,W) √√ √ System Mode HP MV 13 Present_Value (R,W) System Mode RTU MV 14 Present_Value (R,W) √√ Fan Mode MV 15 Present_Value (R,W) √√ √ Supply Temp AI 16 Present_Value (R) √√ Supply RH AV 17 Present_Value (R) Keypad Lockout MV 18 Present_Value (R,W) √√ √
Control Output GR 19 Present_Value (R) √√
PI Heating Demand AV 20 Present_Value (R) √√ √ PI Cooling Demand AV 21 Present_Value (R) √√ √ Economizer Output AV 22 Present_Value (R)
Controller Status GRP 23 Present_Value (R)
AUX BI 24 Present_Value (R) √√ √ G Fan BI 25 Present_Value (R) √√ √ Y1 Cool BI 26 Present_Value (R) √√ √ Y2 Cool BI 27 Present_Value (R) √√ W1 Heat BI 28 Present_Value (R) √√ √ W2 Heat BI 29 Present_Value (R) √√ Reversing Valve BI 30 Present_Value (R) DI 1 Status BI 31 Present_Value (R) √√ √ DI 2 Status BI 32 Present_Value (R) √√ Local Motion BI 33 Present_Value (R) √√ √ Effective Occupancy MV 34 Present_Value (R) √√ √
Controller Alarms GRP 35 Present_Value (R)
Frost Alarm BI 36 Present_Value (R) √√ √ Filter Alarm BI 38 Present_Value (R) √√ √ Service Alarm BI 39 Present_Value (R) √√ √ Fan Lock Alarm BI 40 Present_Value (R) √√ √
Temperature Setpoints GRP 41 Present_Value (R)
Occupied Heat Setpoint AV 42 Present_Value (R,W) √√ √ Occupied Cool Setpoint AV 43 Present_Value (R,W) √√ √ Unoccupied Heat Setpoint AV 44 Present_Value (R,W) √√ √ Unoccupied Cool Setpoint AV 45 Present_Value (R,W) √√ √
General Options 1- GRP 46 Present_Value (R) √√ √
Temperature Scale BV 47 Present_Value (R,W) √√ √ Heating Setpoint Limit AV 48 Present_Value (R,W) √√ √ Cooling Setpoint Limit AV 49 Present_Value (R,W) √√ √
Heating Lockout Temperature
Cooling Lockout Temperature
Deadband AV 52 Present_Value (R,W) √√ √ Heating CPH MV 53 Present_Value (R,W) √√ √
Instance Object Property
AV 50 Present_Value (R,W) √√ √
AV 51 Present_Value (R,W) √√ √
Rooftop
-1010
√√
Heat Pump
-2010
Dehumidifi-
cation
-1050
10 BAS-SVP10A-EN
Summary of BACnet Objects
Table 3. Rooftop and heat pump ungrouped objects
Dehumidifi-
Type and
Object Name
Cooling CPH MV 54 Present_Value (R,W) √√ √ Frost Protection BV 55 Present_Value (R,W) √√ √ Aux Contact BV 56 Present_Value (R,W) √√ √ Menu Scroll BV 57 Present_Value (R,W) √√ √
General Options 2- GRP 58 Present_Value (R) √√ √
Password Value AV 59 Present_Value (R,W) √√ √ Power-up Delay AV 60 Present_Value (R,W) √√ √
Temporary Occupancy Time
Fan Control BV 62 Present_Value (R,W) √√ √ Anticycle MV 63 Present_Value (R,W) √√ √ Fan Purge Delay BV 64 Present_Value (R,W) √√ √ DI 1 Configuration MV 65 Present_Value (R,W) √√ √ DI 2 Configuration MV 66 Present_Value (R,W) √√ Proportional Band MV 67 Present_Value (R,W) √√ √ Unoccupied Time AV 68 Present_Value (R,W) √√ √
Stages Configuration Options
Heating Stages MV 73 Present_Value (R,W) √√ Cooling Stages MV 74 Present_Value (R,W) √√ Heatpump Stages MV 75 Present_Value (R,W)
Economizer Model Configuration Options
Economizer Changeover Setpoint
Economizer Minimum Position
Mechanical Cooling Enabled
Mixed Air Setpoint AV 80 Present_Value (R,W)
Heatpump Model Configuration Options
High Balance Point AV 82 Present_Value (R,W) √√ Low Balance Point AV 83 Present_Value (R,W) √√ Comfort Mode BV 84 Present_Value (R,W) √√
Reversing Valve Configuration
Compressor Interlock BV 86 Present_Value (R,W)
Dehumidification Model Configuration Options
RH Display BV 88 Present_Value (R,W)
Dehumidification RH Setpoint
Dehumidification Hysterisys
Dehumidification Low OA Lockout
Dehumidification Lockout Functions
Dehumidification Output Status
Humidification Model Configuration Options
Humidification RH Setpoint AV 95 Present_Value (R,W)
Instance Object Property
MV 61 Present_Value (R,W) √√ √
GRP 72 Present_Value (R)
GRP 76 Present_Value (R)
AV 77 Present_Value (R,W)
AV 78 Present_Value (R,W)
BV 79 Present_Value (R,W)
GRP 81 Present_Value (R)
BV 85 Present_Value (R,W)
GRP 87 Present_Value (R)
AV 89 Present_Value (R,W)
AV 90 Present_Value (R,W)
AV 91 Present_Value (R,W)
BV 92 Present_Value (R,W)
BI 93 Present_Value (R)
GRP 94 Present_Value (R)
Rooftop
-1010
Heat Pump
-2010
cation
-1050
BAS-SVP10A-EN 11
Summary of BACnet Objects
Table 3. Rooftop and heat pump ungrouped objects
Type and
Object Name
Eff (Effective) Reset Humidification RH Spt (Setpoint)
Humidification High Limit Spt (Setpoint)
Low RH Setpoint AV 98 Present_Value (R,W)
Low Temp Reset RH Setpoint
High Temp Reset RH Setpoint
Humidifier Output AV 101 Present_Value (R)
Instance Object Property
AV 96 Present_Value (R)
AV 97 Present_Value (R,W)
AV 99 Present_Value (R,W)
AV 100 Present_Value (R,W)

Standard Object Types Supported

Table 4. Standard object types supported
Supported
Object Type
Analog Input Reliability Out_of_Service
Objects
Dynamically
Creatable
Dynamically
Deletable
Dehumidifi-
Rooftop
-1010
Heat Pump
-2010
cation
-1050
Optional Properties Supported Writable Properties
Analog Value Reliability Present_Value (a,b,e)
Binary Input Reliability
Binary Value Reliability
Device Max_Master
Group N/A N/A
Multi-state Value Reliability
Schedule (Rooftop and heat
pump only)
Footnotes for fan coils:
a : Present_Value and Out_of_Service properties are writable for every AV objects except PI Heating Demand (AV21) and
PI Cooling Demand (AV22).
b : Present_Value property for Room Temperature (AV7) and Room Humidity (AV10) is writable only if Room Temp Override
(BV8) is enabled and Room Humidity Override (BV11) is enabled respectively.
Active_Text Inactive_Text
Active_Text Inactive_Text
Max_Info_frames
States_Text
Weekly_schedule Present_Value
Out_of_Service (a,e) Object_Name (c ,f)
Out_of_Service
Present_Value Out_of_Service
Object_Identifier Object_name Max_Master
Present_Value (d) Out_of_Service (d)
Weekly_Schedule
12 BAS-SVP10A-EN
c : Object_Name property is writable only for Room Temperature (AV7). d : Present_Value and Out_of_Service properties are writable for every MV objects except Heating Valve Status (MV26), Cooling
Valve Status (MV27), Fan Status (MV28), and Effective Occupancy (MV33)
Footnotes for rooftop units and heat pumps
e: The following AV’s are defined as read only. When Out_of_Service properties is set to true, the Present_Value, if written,
is not derived to the application level of the thermostat.
- Room Humidity (AV11)
- PI Heating Demand (AV20)
- PI Cooling Demand (AV21)
- Economizer Output (AV22)
- Eff Reset Humidification RH Spt (AV96)
- Humidifier Output (AV101)
f: Object_Name property is writable for 1 object only: Room_Temperature (AV7).

List of Proprietary Properties

Table 5. Proprietary Properties
Property Name ID BACnet Data Type Description
Major_Version 1000 CharacterString The version number of the BACnet communications
MS/TP_Address 1001 Unsigned Display the MAC layer address of the module
MS/TP_Baud_Rate 1002 Unsigned Display the communication baud rate of the module
Sensor_Offset 1005 REAL Display the temperature or humidity calibration value. The
Summary of BACnet Objects
module. This the hardware version number
range is –5.0 deg F to 5.0 deg F for a temperature and – 15% to 15% for humidity.

Configuration Objects for Fan Coils

The following objects and group objects listed in Table 2, p. 8 should be typically used for configuration purposes:
General Options 1 Group GRP 45 and its complete list of objects
General Options 2 Group GRP 55 and its complete list of objects
Output Configuration Options Group GRP 74 and its complete list of objects

Configuration Objects for Rooftop and Heat Pump Units

The following objects and group objects listed in Table 2, p. 8 should be typically used for configuration purposes:
General Options 1 Group GRP 46 and its complete list of objects
General Options 2 Group GRP 58 and its complete list of objects
Programmable Model Configuration Options Group GRP 69 and its complete list of objects
Stages Configuration Options Group GRP 72 and its complete list of objects;
Economizer Model Configuration Option Group GRP 76 and its complete list of objects;
Heatpump Model Configuration Option Group GRP 81 and its complete list of objects;
Dehumidification Model Configuration Option Group GRP 87 and its complete list of objects;
Humidification Model Configuration Option Group GRP 94 and its complete list of objects;
BAS-SVP10A-EN 13

BACnet Object Properties

This section lists ranges, enumerations, and values for the set of Communicating Thermostat objects.

Fan Coil Object Properties

Table 6. List of property value range restrictions
Object Type and
Object Name
Room Temperature AV 7 -39.9°F (-40°C) 121.9°F (50°C) N/A
Outdoor Temperature AV 9 -39°F (-40°C) 121.9°F (50°C) N/A
Room Humidity AV 10 5% 90% N/A
Supply Temperature AI 12 -39.9°F (-40°C) 121.9°F (50°C) N/A
PI Heating demand AV 21 0% 100% 0%
PI Cooling demand AV 22 0% 100% 0%
Occupied Heat
Setpoint
Occupied Cool
Setpoint
Stand-by Heat
Setpoint
Stand-by Cool
Setpoint
Unoccupied Heat
Setpoint
Unoccupied Cool
Setpoint
Password Value AV 56 0 1000 0
Heating Setpoint Limit AV 58 40°F (4.5°C) 90°F (32°C) 90°F (32°C)
Cooling Setpoint Limit AV 59 54°F (12°C) 100°F (37.5°C) 54°F (12°C)
Deadband AV 63 2°F (1°C) 5°F (2.5°C) 2°F (1°C)
Stand-by Time AV 67 0.5 Hours 24.0 Hours 0.5 Hours
Unoccupied Time AV 68 0.0 Hours 24.0 Hours 0.0 Hours
RH Setpoint AV 45 30% 100% 50%
Dehumidification
Hysterisys
Dehumidification MAX
cooling
Instance
AV 39 40°F (4.5°C) 90°F (32°C) 72°F (22°C)
AV 40 54°F (12°C) 100°F (37.5°C) 74°F (24°C)
AV 41 40°F (4.5°C) 90°F (32°C) 72°F (22°C)
AV 42 54°F (12°C) 100°F (37.5°C) 74°F (24°C)
AV 43 40°F (4.5°C) 90°F (32°C) 62°F (16.5°C)
AV 44 54°F (12°C) 100°F (37.5°C) 80°F (26.5°C)
AV 46 2% 20% 5%
AV 47 20% 100% 100%
Minimum Range
Value
Maximum Range
Value Default Value
Table 7. List of property enumeration sets for BV objects and BI objects
Object Type and
Object Name
Room Temp Override BV 8 Normal Override Normal
Room Humidity
Override
Dehumidification
Lockout
AUX Command BV 14 Off On Off
Dehumidification
Status
Aux Status BI 25 Off On Off
BI 1 Status BI 29 Deactivated Activated Deactivated
BI 2 Status BI 30 Deactivated Activated Deactivated
UI 3 Status(*) BI 31 Deactivated Activated Deactivated
Local Motion BI 32 No Motion Motion No Motion
Window Alarm BI 35 Off On Off
14 BAS-SVP10A-EN
instance Inactive_Text Active_Text Default value
BV 11 Normal Override Normal
BV 13 Disabled Enabled Enabled
BI 23 Off On Off
BACnet Object Properties
Table 7. List of property enumeration sets for BV objects and BI objects (continued)
Object Type and
Object Name
Filter Alarm BI 36 Off On Off
Service Alarm BI 37 Off On Off
Menu Scroll BV 49 No Scroll Scroll Active Scroll Active
Auto Mode Enable BV 50 Disabled Enabled Enabled
Temperature Scale BV 51 °C °F °F
Setpoint Type BV 60 Permanent Temporary Permanent
Setpoint Function BV 61 Dual Setpoints Attached Setpoints Dual Setpoints
Reheat Time Base BV 64 15 minutes 10 seconds 15 minutes
Auto Fan BV 66 Auto Speed
RH Display BV 70 Disabled Enabled Disabled
Control Type BV 75 On/Off Floating On/Off
Direct/ Reverse Acting BV 78 Direct Acting Reverse Acting Direst Acting
* This object will be linked to the value of the ‘UI 3 Configuration’ object. When the ‘UI 3 Configuration’ object value is 0, 3
or 4, the value will be set to ‘Deactivated.’
Table 8. List of property enumeration sets for MV objects
Object Name Object ID BACnet Index Text Default value
Sequence of
Operation
System Mode
Table Note 1
Fan Mode
Table Note 3
Occupancy Command
Keypad Lockout MV 19
instance Inactive_Text Active_Text Default value
Auto Speed / Auto
Demand
1 Cooling Only
2 Heating Only
MV 15 3 Cooling & Reheat
4 Heating & Reheat
5 Cool/Heat4P
6 Cool/Heat4P&Reht
1 Off
MV 16 2 Auto
3 Cool
4 Heat
MV 17 1, 2, 3 or 4 Table Note 4 Table Note 5
MV 18 1 Local Occupancy
2 Occupied
3 Unoccupied
1 Level 0
2 Level 1
3 Level 2
4 Level 3
5 Level 4
6 Level 5
Auto Speed
Heating Only
Table Note 2
Depends on network
command
Level 0
Table Notes:
1 Enumeration sets for MV16 depends on Sequence of Operation (MV15) value upon device discovery. If required enumeration
is not present, set MV15 to desired value and rediscover MV16 object. Available enumeration will now reflect required configuration.
2 Default value of MV16 depends on MV15 value upon device discovery. (See Table 9.)
BAS-SVP10A-EN 15
Loading...
+ 33 hidden pages