Trane BAS-SVP10A-EN User Manual

Page 1
Integration Manual
Trane Communicating Thermostats (BACnet)
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
August 2011 BAS-SVP10A-EN
Page 2
Copyright
© 2011 Trane All rights reserved
This document and the information in it are the property of Trane and may not be used or reproduced inwhole or in part, without the written permission of Trane. Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
Trane and its logo are trademarks of Trane in the United States and other countries. All trademarks referenced in this document are the trademarks of their respective owners.
Warnings, Cautions, and Notices
Warnings, cautions, and notices are provided in appropriate places throughout this document:
WARNING
CAUTIONs
NOTICE:
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only accidents.
Page 3
Table of Contents
Overview .............................................................. 5
Product Description ................................................5
Related Documents ................................................ 6
Planning Your Integration ...........................................6
“How To” Information .............................................. 6
Summary of BACnet Objects ............................................ 7
Supported BACnet Services ......................................... 7
Default Device Name and Default Device ID ........................... 7
Fan Coil Objects ................................................... 8
Rooftop and Heat Pump Objects .................................... 10
Standard Object Types Supported .................................. 12
List of Proprietary Properties ....................................... 13
Configuration Objects for Fan Coils .................................. 13
Configuration Objects for Rooftop and Heat Pump Units ............... 13
BACnet Object Properties .............................................. 14
Fan Coil Object Properties .......................................... 14
Rooftop and Heat Pump Object Properties ........................... 19
Objects You Can Use in Site Graphics ................................... 23
Fan Coils ......................................................... 23
Rooftop and Heat Pump Units ...................................... 24
Wiring Requirements for Communicating Thermostats ...................25
BACnet MS/TP Link Wiring ......................................... 25
BACnet Configuration Requirements ............................ 25
BACnet Wiring Best Practices ................................... 25
BACnet Wiring Procedure ......................................26
Trane BACnet Termination for BACnet Links ...................... 26
Product Specifications ............................................. 27
Network Adapter .................................................. 27
Communicating Thermostat Status LEDs ............................ 28
Troubleshooting .................................................. 28
Additional Information and Considerations .............................. 29
MS/TP Network Integration .........................................29
Site Graphics ................................................ 29
Free Programmed Objects or Loops (Supervisory Controllers Other
Than Tracer SC) ........................................... 29
Retries and Timeouts (Supervisory Controllers Other Than Tracer SC) . 30
BAS-SVP10A-EN 3
Page 4
Objects and Parameters ........................................... 30
Tracer SC Network Configuration ................................... 32
Data Normalization .................................................... 36
Example: Occupancy Request ...................................... 36
Template: TStat_FanCoil_Trane ..................................... 36
Template: TStat_HeatPump_Trane .................................. 39
Template: TStat_RTU_Trane ........................................ 40
Trane Communicating Thermostat Points List ............................ 42
TStat_Fan_Coil_Trane ............................................. 42
TStat_HeatPump_Trane Template ................................... 43
TStat_RTU_Trane Template ........................................ 44
4 BAS-SVP10A-EN
Page 5

Overview

This document is written to guide you through integration of the Trane Communicating Thermostats into an MS/TP network using the BACnet protocol and managed by a Tracer SC.

Product Description

The Trane Communicating Thermostats are available for heat pump, rooftop, and fan coil applications.
X13511541010 and -2010 (Heat Pump and Rooftop) These Trane Communicating Thermostats are BACnet MS/TP devices specifically designed for
single stage and multi-stage control of heating/cooling equipment such as rooftop and self­contained units. The products feature an intuitive, menu-driven, back-lit LCD display, which walks users through the programming steps, making the process extremely simple.
X13511543010 (Fan Coil) This Trane Communicating thermostat is specifically designed for fan coil control. The product
features a backlit LCD display with dedicated function menu buttons for simple operation. Three additional inputs are also provided for monitoring and / or various advanced functions. All models feature configurable System and Fan button functions to meet a variety of
applications.
Accurate temperature control is achieved due to the product’s PI proportional control algorithm, which virtually eliminates temperature offset associated with traditional, differential-based thermostats.
The Communicating Thermostats contain an SPST auxiliary switch that can be used to control lighting or auxiliary reheat. Three additional inputs are also provided for monitoring and / or various advanced functions.
The thermostats are also compatible with the occupancy sensor cover accessories. Thermostats equipped with an occupancy sensor cover provide advanced active occupancy logic, which will automatically switch occupancy levels from Occupied to Unoccupied as required by local activity being present or not. This advanced occupancy functionality provides advantageous energy savings during occupied hours without sacrificing occupant comfort.
BAS-SVP10A-EN 5
Page 6
Overview

Related Documents

See the following documents for Communicating Thermostat installation and configuration information.
Trane Communicating Thermostats for Heat Pump Control User Guide (BAS-SVU10x-EN)
Trane Communicating Thermostats for Rooftop Control User Guide (BAS-SVU11x-EN)
Trane Communicating Thermostats for Fan Coil Control User Guide (BAS-SVU12x-EN)
See the following documents for Tracer SC network integration information.
Tracer™ SC System Controller Installation and Setup (BAS-SVX31x-EN)
Tracer™ BACnet™ Terminator Installation (X39641151-01x)
Unit Controller Wiring Guide For the Tracer SC™ System Controller (BAS-SVN03x-EN
Finally, see the following documents for information about equipment including fan coils, rooftop units, and heat pumps.
Communicating Thermostats for Rooftop and Heat Pump Control Product Data Sheet (BAS-PRC064-EN)
Communicating Thermostats for Fan Coil Control Product Data Sheet (BAS-PRC065-EN)
All these documents are available from your Trane distributor.

Planning Your Integration

Study the following information presented in the chapters of this guide as you plan the work:
Communicating Thermostat BACnet objects (points) and their properties (ranges, values, and enumeration sets for points). (See
Properties,” p. 14.)
Tips and considerations presented in “Additional Information and Considerations,” p. 29.If your network is managed by a Tracer SC, pay special attention to “Tracer SC Network
Configuration,” p. 32.
Wiring instructions in “Wiring Requirements for Communicating Thermostats,” p. 25.
Available Graphical User Interface (GUI) objects that you can use in graphics presented in
“Objects You Can Use in Site Graphics,” p. 23.

“How To” Information

The following “how to” questions are described or clarified either in this manual or in other documents cited in this table.
How do I set up alarming in Tracer SC?
How do I set the MAC address of the Trane Communicating Thermostat?
How do I install a Trane Communicating Thermostat on the Tracer SC link?
“Summary of BACnet Objects,” p. 7. and “BACnet Object
Question Information Location or Answer
See the Tracer™ SC System Controller Installation and Setup Manual (BAS-SVX31x-EN)
See “Default Device Name and Default Device ID,” p. 7. Also, see the appropriate User Guide listed in “Related
Documents” on this page.
See “No automatic installation,” p. 32.
6 BAS-SVP10A-EN
Page 7

Summary of BACnet Objects

The Building Automation and Control Network (BACnet and ANSI/ASHRAE Standard 135-2004) protocol is a standard that allows building automation systems or components from different manufacturers to share information and control functions. BACnet provides building owners the capability to connect various types of building control systems or subsystems together for many uses. In addition, multiple vendors can use this protocol to share information for monitoring and supervisory control between systems and devices in a multi-vendor interconnected system.
The BACnet protocol identifies standard objects (data points) called BACnet objects. Each object has a defined list of properties that provide information about that object. BACnet also defines a number of standard application services that are used to access data and manipulate these objects and provides a client/server communication between devices.

Supported BACnet Services

The BACnet communicating thermostat meets all requirements for designation as an Application Specific Controller (B-ASC). The BACnet thermostat series supports the following BACnet Interoperability Building Blocks (BIBBs).
Table 1. BACnet Interoperability Building Blocks
Application Service Designation
Data Sharing – Read Property - B DS-RP-B
Data Sharing – Read Property Multiple - B DS-RPM-B
Data Sharing – Write Property - B DS-WP-B
Device Management - Device Communication Control - B DM-DCC-B
Device Management – Dynamic Device Binding - B DM-DDB-B
Device Management – Dynamic Object Binding - B DM-DOB-B
Notes:
The thermostat does not support seqmented requests or responses.
Models X13511541010 and -2010—Time synchronization can be made through a network even if the thermostat does not support the full date. Therefore, the device cannot claim conformance to the DeviceManagement – TimeSynchronization - B (DM-TS-B) service. The device object does not have the Local_Time or Local_Date properties.

Default Device Name and Default Device ID

The Default Device Name is set to: TStat_EquipType_Trane_MAC where: EquipType is FanCoil,
RTU, or HeatPump and MAC is the current MAC address of the device.
The Device Name is changed if you change the device MAC address.
The Device Name and Device ID properties are writable in the Device object. Both properties can be changed from any BACnet network management tool as long as the tool itself can write to these properties.
(X13511543010) Fan Coil Models
Default Device ID is set to: 7300MAC where MAC is the current MAC address of the device that you set from the Installer Configuration Parameter menu on the Trane Communicating Thermostat.
The Device ID changes if the device’s MAC address is changed. For example, when a fan coil communicating thermostat with a MAC address of 41 is connected to a network, its default Device Name will be TStat_FanCoil_Trane_41 and its default Device ID will be 730041.
BAS-SVP10A-EN 7
Page 8
Summary of BACnet Objects
(X13511541010 and -2010) Rooftop and Heat Pump Models
Default Device ID is set to: 7600MAC where MAC is the current MAC address of the device.
The device ID and the Device Name change if you change the device’s MAC address. For example, when a heat pump communicating thermostat with a MAC address of 63 is connected to a network, its default Device Name will be TStat_HeatPump_Trane_63 and its default Device ID will be 760063.

Fan Coil Objects

Table 2. Objects table for fan coils (X13511543010)
Object Name Type and Instance Object Property
Room Temperature AV 7 Present_Value (R,W)
Room Temp Override BV 8 Present_Value (R,W)
Outdoor Temperature AV 9 Present_Value (R,W)
Supply Temperature AI 12 Present_Value (R)
AUX Command BV 14 Present_Value (R,W)
Sequence of Operation MV 15 Present_Value (R,W)
System Mode MV 16 Present_Value (R,W)
Fan Mode MV 17 Present_Value (R,W)
Occupancy Command MV 18 Present_Value (R,W)
Keypad Lockout MV 19 Present_Value (R,W)
Control Output GRP 20 Present_Value (R)
PI Heating Demand AV 21 Present_Value (R)
PI Cooling Demand AV 22 Present_Value (R)
Controller Status GRP 24 Present_Value (R)
AUX Status BI 25 Present_Value (R)
Heating Valve Status MV 26 Present_Value (R)
Cooling Valve Status MV 27 Present_Value (R)
Fan Status MV 28 Present_Value (R)
BI 1 Status BI 29 Present_Value (R)
BI 2 Status BI 30 Present_Value (R)
UI 3 Status BI 31 Present_Value (R)
Local Motion BI 32 Present_Value (R)
Effective Occupancy MV 33 Present_Value (R)
Controller Alarms GRP 34 Present_Value (R)
Window Alarm BI 35 Present_Value (R)
Filter Alarm BI 36 Present_Value (R)
Service Alarm BI 37 Present_Value (R)
Temperature Setpoints GRP 38 Present_Value (R)
Occupied Heat Setpoint AV 39 Present_Value (R,W)
Occupied Cool Setpoint AV 40 Present_Value (R,W)
Stand-by Heat Setpoint AV 41 Present_Value (R,W)
Stand-by Cool Setpoint AV 42 Present_Value (R,W)
8 BAS-SVP10A-EN
Page 9
Summary of BACnet Objects
Table 2. Objects table for fan coils (X13511543010) (continued)
Object Name Type and Instance Object Property
Unoccupied Heat Setpoint AV 43 Present_Value (R,W)
Unoccupied Cool Setpoint AV 44 Present_Value (R,W)
General Options 1 GRP 45 Present_Value (R)
BI 1 Configuration MV 46 Present_Value (R,W)
BI 2 Configuration MV 47 Present_Value (R,W)
UI 3 configuration MV 48 Present_Value (R,W)
Menu Scroll BV 49 Present_Value (R,W)
Auto Mode Enable BV 50 Present_Value (R,W)
Temperature Scale BV 51 Present_Value (R,W)
Pipe Number MV 52 Present_Value (R,W)
AUX Configuration MV 54 Present_Value (R,W)
General Options 2 GRP 55 Present_Value (R)
Password Value AV 56 Present_Value (R,W)
Fan Mode Sequence MV 58 Present_Value (R,W)
Heating Setpoint Limit AV 58 Present_Value (R,W)
Cooling Setpoint Limit AV 59 Present_Value (R,W)
Setpoint Type BV 60 Present_Value (R,W)
Setpoint Function BV 61 Present_Value (R,W)
Temporary Occupancy Time MV 62 Present_Value (R,W)
Deadband AV 63 Present_Value (R,W)
Reheat Time Base BV 64 Present_Value (R,W)
Proportional Band MV 65 Present_Value (R,W)
Auto Fan BV 66 Present_Value (R,W)
Stand-by Time AV 67 Present_Value (R,W)
Unoccupied Time AV 68 Present_Value (R,W)
Output Configuration Options GRP 74 Present_Value (R)
Control Type BV 75 Present_Value (R,W)
Floating Motor Timing MV 76 Present_Value (R,W)
On Off Control CPH MV 77 Present_Value (R,W)
BAS-SVP10A-EN 9
Page 10
Summary of BACnet Objects

Rooftop and Heat Pump Objects

Table 3. Rooftop and heat pump ungrouped objects
Type and
Object Name
Room Temperature AV 7 Present_Value (R,W) √√ √ Room Temp Override BV 8 Present_Value (R,W) √√ √ Outdoor Temperature AV 9 Present_Value (R,W) √√ √ Outdoor Temp Override BV 10 Present_Value (R,W) √√ √ Room Humidity AV 11 Present_Value (R) Occupancy Command MV 12 Present_Value (R,W) √√ √ System Mode HP MV 13 Present_Value (R,W) System Mode RTU MV 14 Present_Value (R,W) √√ Fan Mode MV 15 Present_Value (R,W) √√ √ Supply Temp AI 16 Present_Value (R) √√ Supply RH AV 17 Present_Value (R) Keypad Lockout MV 18 Present_Value (R,W) √√ √
Control Output GR 19 Present_Value (R) √√
PI Heating Demand AV 20 Present_Value (R) √√ √ PI Cooling Demand AV 21 Present_Value (R) √√ √ Economizer Output AV 22 Present_Value (R)
Controller Status GRP 23 Present_Value (R)
AUX BI 24 Present_Value (R) √√ √ G Fan BI 25 Present_Value (R) √√ √ Y1 Cool BI 26 Present_Value (R) √√ √ Y2 Cool BI 27 Present_Value (R) √√ W1 Heat BI 28 Present_Value (R) √√ √ W2 Heat BI 29 Present_Value (R) √√ Reversing Valve BI 30 Present_Value (R) DI 1 Status BI 31 Present_Value (R) √√ √ DI 2 Status BI 32 Present_Value (R) √√ Local Motion BI 33 Present_Value (R) √√ √ Effective Occupancy MV 34 Present_Value (R) √√ √
Controller Alarms GRP 35 Present_Value (R)
Frost Alarm BI 36 Present_Value (R) √√ √ Filter Alarm BI 38 Present_Value (R) √√ √ Service Alarm BI 39 Present_Value (R) √√ √ Fan Lock Alarm BI 40 Present_Value (R) √√ √
Temperature Setpoints GRP 41 Present_Value (R)
Occupied Heat Setpoint AV 42 Present_Value (R,W) √√ √ Occupied Cool Setpoint AV 43 Present_Value (R,W) √√ √ Unoccupied Heat Setpoint AV 44 Present_Value (R,W) √√ √ Unoccupied Cool Setpoint AV 45 Present_Value (R,W) √√ √
General Options 1- GRP 46 Present_Value (R) √√ √
Temperature Scale BV 47 Present_Value (R,W) √√ √ Heating Setpoint Limit AV 48 Present_Value (R,W) √√ √ Cooling Setpoint Limit AV 49 Present_Value (R,W) √√ √
Heating Lockout Temperature
Cooling Lockout Temperature
Deadband AV 52 Present_Value (R,W) √√ √ Heating CPH MV 53 Present_Value (R,W) √√ √
Instance Object Property
AV 50 Present_Value (R,W) √√ √
AV 51 Present_Value (R,W) √√ √
Rooftop
-1010
√√
Heat Pump
-2010
Dehumidifi-
cation
-1050
10 BAS-SVP10A-EN
Page 11
Summary of BACnet Objects
Table 3. Rooftop and heat pump ungrouped objects
Dehumidifi-
Type and
Object Name
Cooling CPH MV 54 Present_Value (R,W) √√ √ Frost Protection BV 55 Present_Value (R,W) √√ √ Aux Contact BV 56 Present_Value (R,W) √√ √ Menu Scroll BV 57 Present_Value (R,W) √√ √
General Options 2- GRP 58 Present_Value (R) √√ √
Password Value AV 59 Present_Value (R,W) √√ √ Power-up Delay AV 60 Present_Value (R,W) √√ √
Temporary Occupancy Time
Fan Control BV 62 Present_Value (R,W) √√ √ Anticycle MV 63 Present_Value (R,W) √√ √ Fan Purge Delay BV 64 Present_Value (R,W) √√ √ DI 1 Configuration MV 65 Present_Value (R,W) √√ √ DI 2 Configuration MV 66 Present_Value (R,W) √√ Proportional Band MV 67 Present_Value (R,W) √√ √ Unoccupied Time AV 68 Present_Value (R,W) √√ √
Stages Configuration Options
Heating Stages MV 73 Present_Value (R,W) √√ Cooling Stages MV 74 Present_Value (R,W) √√ Heatpump Stages MV 75 Present_Value (R,W)
Economizer Model Configuration Options
Economizer Changeover Setpoint
Economizer Minimum Position
Mechanical Cooling Enabled
Mixed Air Setpoint AV 80 Present_Value (R,W)
Heatpump Model Configuration Options
High Balance Point AV 82 Present_Value (R,W) √√ Low Balance Point AV 83 Present_Value (R,W) √√ Comfort Mode BV 84 Present_Value (R,W) √√
Reversing Valve Configuration
Compressor Interlock BV 86 Present_Value (R,W)
Dehumidification Model Configuration Options
RH Display BV 88 Present_Value (R,W)
Dehumidification RH Setpoint
Dehumidification Hysterisys
Dehumidification Low OA Lockout
Dehumidification Lockout Functions
Dehumidification Output Status
Humidification Model Configuration Options
Humidification RH Setpoint AV 95 Present_Value (R,W)
Instance Object Property
MV 61 Present_Value (R,W) √√ √
GRP 72 Present_Value (R)
GRP 76 Present_Value (R)
AV 77 Present_Value (R,W)
AV 78 Present_Value (R,W)
BV 79 Present_Value (R,W)
GRP 81 Present_Value (R)
BV 85 Present_Value (R,W)
GRP 87 Present_Value (R)
AV 89 Present_Value (R,W)
AV 90 Present_Value (R,W)
AV 91 Present_Value (R,W)
BV 92 Present_Value (R,W)
BI 93 Present_Value (R)
GRP 94 Present_Value (R)
Rooftop
-1010
Heat Pump
-2010
cation
-1050
BAS-SVP10A-EN 11
Page 12
Summary of BACnet Objects
Table 3. Rooftop and heat pump ungrouped objects
Type and
Object Name
Eff (Effective) Reset Humidification RH Spt (Setpoint)
Humidification High Limit Spt (Setpoint)
Low RH Setpoint AV 98 Present_Value (R,W)
Low Temp Reset RH Setpoint
High Temp Reset RH Setpoint
Humidifier Output AV 101 Present_Value (R)
Instance Object Property
AV 96 Present_Value (R)
AV 97 Present_Value (R,W)
AV 99 Present_Value (R,W)
AV 100 Present_Value (R,W)

Standard Object Types Supported

Table 4. Standard object types supported
Supported
Object Type
Analog Input Reliability Out_of_Service
Objects
Dynamically
Creatable
Dynamically
Deletable
Dehumidifi-
Rooftop
-1010
Heat Pump
-2010
cation
-1050
Optional Properties Supported Writable Properties
Analog Value Reliability Present_Value (a,b,e)
Binary Input Reliability
Binary Value Reliability
Device Max_Master
Group N/A N/A
Multi-state Value Reliability
Schedule (Rooftop and heat
pump only)
Footnotes for fan coils:
a : Present_Value and Out_of_Service properties are writable for every AV objects except PI Heating Demand (AV21) and
PI Cooling Demand (AV22).
b : Present_Value property for Room Temperature (AV7) and Room Humidity (AV10) is writable only if Room Temp Override
(BV8) is enabled and Room Humidity Override (BV11) is enabled respectively.
Active_Text Inactive_Text
Active_Text Inactive_Text
Max_Info_frames
States_Text
Weekly_schedule Present_Value
Out_of_Service (a,e) Object_Name (c ,f)
Out_of_Service
Present_Value Out_of_Service
Object_Identifier Object_name Max_Master
Present_Value (d) Out_of_Service (d)
Weekly_Schedule
12 BAS-SVP10A-EN
Page 13
c : Object_Name property is writable only for Room Temperature (AV7). d : Present_Value and Out_of_Service properties are writable for every MV objects except Heating Valve Status (MV26), Cooling
Valve Status (MV27), Fan Status (MV28), and Effective Occupancy (MV33)
Footnotes for rooftop units and heat pumps
e: The following AV’s are defined as read only. When Out_of_Service properties is set to true, the Present_Value, if written,
is not derived to the application level of the thermostat.
- Room Humidity (AV11)
- PI Heating Demand (AV20)
- PI Cooling Demand (AV21)
- Economizer Output (AV22)
- Eff Reset Humidification RH Spt (AV96)
- Humidifier Output (AV101)
f: Object_Name property is writable for 1 object only: Room_Temperature (AV7).

List of Proprietary Properties

Table 5. Proprietary Properties
Property Name ID BACnet Data Type Description
Major_Version 1000 CharacterString The version number of the BACnet communications
MS/TP_Address 1001 Unsigned Display the MAC layer address of the module
MS/TP_Baud_Rate 1002 Unsigned Display the communication baud rate of the module
Sensor_Offset 1005 REAL Display the temperature or humidity calibration value. The
Summary of BACnet Objects
module. This the hardware version number
range is –5.0 deg F to 5.0 deg F for a temperature and – 15% to 15% for humidity.

Configuration Objects for Fan Coils

The following objects and group objects listed in Table 2, p. 8 should be typically used for configuration purposes:
General Options 1 Group GRP 45 and its complete list of objects
General Options 2 Group GRP 55 and its complete list of objects
Output Configuration Options Group GRP 74 and its complete list of objects

Configuration Objects for Rooftop and Heat Pump Units

The following objects and group objects listed in Table 2, p. 8 should be typically used for configuration purposes:
General Options 1 Group GRP 46 and its complete list of objects
General Options 2 Group GRP 58 and its complete list of objects
Programmable Model Configuration Options Group GRP 69 and its complete list of objects
Stages Configuration Options Group GRP 72 and its complete list of objects;
Economizer Model Configuration Option Group GRP 76 and its complete list of objects;
Heatpump Model Configuration Option Group GRP 81 and its complete list of objects;
Dehumidification Model Configuration Option Group GRP 87 and its complete list of objects;
Humidification Model Configuration Option Group GRP 94 and its complete list of objects;
BAS-SVP10A-EN 13
Page 14

BACnet Object Properties

This section lists ranges, enumerations, and values for the set of Communicating Thermostat objects.

Fan Coil Object Properties

Table 6. List of property value range restrictions
Object Type and
Object Name
Room Temperature AV 7 -39.9°F (-40°C) 121.9°F (50°C) N/A
Outdoor Temperature AV 9 -39°F (-40°C) 121.9°F (50°C) N/A
Room Humidity AV 10 5% 90% N/A
Supply Temperature AI 12 -39.9°F (-40°C) 121.9°F (50°C) N/A
PI Heating demand AV 21 0% 100% 0%
PI Cooling demand AV 22 0% 100% 0%
Occupied Heat
Setpoint
Occupied Cool
Setpoint
Stand-by Heat
Setpoint
Stand-by Cool
Setpoint
Unoccupied Heat
Setpoint
Unoccupied Cool
Setpoint
Password Value AV 56 0 1000 0
Heating Setpoint Limit AV 58 40°F (4.5°C) 90°F (32°C) 90°F (32°C)
Cooling Setpoint Limit AV 59 54°F (12°C) 100°F (37.5°C) 54°F (12°C)
Deadband AV 63 2°F (1°C) 5°F (2.5°C) 2°F (1°C)
Stand-by Time AV 67 0.5 Hours 24.0 Hours 0.5 Hours
Unoccupied Time AV 68 0.0 Hours 24.0 Hours 0.0 Hours
RH Setpoint AV 45 30% 100% 50%
Dehumidification
Hysterisys
Dehumidification MAX
cooling
Instance
AV 39 40°F (4.5°C) 90°F (32°C) 72°F (22°C)
AV 40 54°F (12°C) 100°F (37.5°C) 74°F (24°C)
AV 41 40°F (4.5°C) 90°F (32°C) 72°F (22°C)
AV 42 54°F (12°C) 100°F (37.5°C) 74°F (24°C)
AV 43 40°F (4.5°C) 90°F (32°C) 62°F (16.5°C)
AV 44 54°F (12°C) 100°F (37.5°C) 80°F (26.5°C)
AV 46 2% 20% 5%
AV 47 20% 100% 100%
Minimum Range
Value
Maximum Range
Value Default Value
Table 7. List of property enumeration sets for BV objects and BI objects
Object Type and
Object Name
Room Temp Override BV 8 Normal Override Normal
Room Humidity
Override
Dehumidification
Lockout
AUX Command BV 14 Off On Off
Dehumidification
Status
Aux Status BI 25 Off On Off
BI 1 Status BI 29 Deactivated Activated Deactivated
BI 2 Status BI 30 Deactivated Activated Deactivated
UI 3 Status(*) BI 31 Deactivated Activated Deactivated
Local Motion BI 32 No Motion Motion No Motion
Window Alarm BI 35 Off On Off
14 BAS-SVP10A-EN
instance Inactive_Text Active_Text Default value
BV 11 Normal Override Normal
BV 13 Disabled Enabled Enabled
BI 23 Off On Off
Page 15
BACnet Object Properties
Table 7. List of property enumeration sets for BV objects and BI objects (continued)
Object Type and
Object Name
Filter Alarm BI 36 Off On Off
Service Alarm BI 37 Off On Off
Menu Scroll BV 49 No Scroll Scroll Active Scroll Active
Auto Mode Enable BV 50 Disabled Enabled Enabled
Temperature Scale BV 51 °C °F °F
Setpoint Type BV 60 Permanent Temporary Permanent
Setpoint Function BV 61 Dual Setpoints Attached Setpoints Dual Setpoints
Reheat Time Base BV 64 15 minutes 10 seconds 15 minutes
Auto Fan BV 66 Auto Speed
RH Display BV 70 Disabled Enabled Disabled
Control Type BV 75 On/Off Floating On/Off
Direct/ Reverse Acting BV 78 Direct Acting Reverse Acting Direst Acting
* This object will be linked to the value of the ‘UI 3 Configuration’ object. When the ‘UI 3 Configuration’ object value is 0, 3
or 4, the value will be set to ‘Deactivated.’
Table 8. List of property enumeration sets for MV objects
Object Name Object ID BACnet Index Text Default value
Sequence of
Operation
System Mode
Table Note 1
Fan Mode
Table Note 3
Occupancy Command
Keypad Lockout MV 19
instance Inactive_Text Active_Text Default value
Auto Speed / Auto
Demand
1 Cooling Only
2 Heating Only
MV 15 3 Cooling & Reheat
4 Heating & Reheat
5 Cool/Heat4P
6 Cool/Heat4P&Reht
1 Off
MV 16 2 Auto
3 Cool
4 Heat
MV 17 1, 2, 3 or 4 Table Note 4 Table Note 5
MV 18 1 Local Occupancy
2 Occupied
3 Unoccupied
1 Level 0
2 Level 1
3 Level 2
4 Level 3
5 Level 4
6 Level 5
Auto Speed
Heating Only
Table Note 2
Depends on network
command
Level 0
Table Notes:
1 Enumeration sets for MV16 depends on Sequence of Operation (MV15) value upon device discovery. If required enumeration
is not present, set MV15 to desired value and rediscover MV16 object. Available enumeration will now reflect required configuration.
2 Default value of MV16 depends on MV15 value upon device discovery. (See Table 9.)
BAS-SVP10A-EN 15
Page 16
BACnet Object Properties
Table 9. MV15 (Sequence of Operation) values for Note 2
MV15 Index Function
1 Cooling Only Cool Cool
2 Cooling with Reheat Auto Heat
3 Heating Only Heat Heat
4 Heating with Reheat Heat Heat
5 Cooling/Heating 4 Pipes Auto Heat
6 Cooling/Heating 4 Pipes with Reheat Auto Heat
Table Notes: (continued)
3 Enumeration sets for MV17 depends on Fan Mode Sequence (MV58) value upon device discovery. If required enumeration
is not present, set MV58 to desired value and rediscover MV17 object. Available enumeration will now reflect required configuration.
4, 5 Available state text and default value depends on Fan Mode Sequence (MV58) value upon device discovery.
Default Value is BV50 Enabled
Default Value is BV50 Disabled
MV17 Index
1 1 Low - 2 Med - 3 High High
2 1 Low - 2 High High
3
4 1 Low - 2 High - 3 Auto High
5 1 Auto -2 On Auto
State Text Index
1 Low - 2 Med - 3 High
- 4 Auto
Default Value
High
Table 10. Additional MV values
Object Name Object ID BACnet Index Text Default value
Function MV58
Heating Valve Status Table Note 6
Cooling Valve Status
Table Note 8
Fan Status MV 28
Effective Occupancy MV 33
Table Notes:
6 Enumeration sets for MV26 depends on Control Type (BV75) value and Pipe Number (MV52) value upon device discovery.
If required enumeration is not present, set BV75 and MV52 to desired value and rediscover MV26 object. Available enu­meration will now reflect required configuration.
7 Available object name, state text and default value depends on Control Type (BV75) value and Pipe Number (MV52) upon
device discovery as shown in Table 11.
MV 26
MV 27
Table Note 7
Table Note 9
1 Off
2 Low
3 Med
4 High
1 Occupied
2 Unoccupied
3 Temporary Occupied
4 Stand-by
Table Note 7
Table Note 9
Table Note 7
Table Note 9
Off
Depends on local occupancy
Table 11. Various object indexes and values for Note 7
BV75 Value MV52 Index
On/Off 1 (2 pipe) Unused Output N/A N/A
2 (4 pipe)
Floating 1 (2 pipe) Unused Output N/A N/A
2 (4 pipe)
8 Enumeration sets for MV27 depends on Control Type (BV75) value and Pipe Number (MV52) value upon device discovery.
If required enumeration is not present, set BV75 and MV52 to desired value and rediscover MV27 object. Available enu-
Name
Heating Valve Status
Heating Valve Status
16 BAS-SVP10A-EN
MV26 Object
Function MV26 State Text Index
1 Closed – 2 Open Closed
1 Stopped - 2 Opening - 3 Closing
Default Value
Stopped
Page 17
BACnet Object Properties
meration will now reflect required configuration.
9 Available object name, state text and default value depends on Control Type (BV75) value and Pipe Number (MV52) upon
device discovery. (See Table 12.)
Table 12. Various object indexes and values for Note 9
Function MV26
BV75 Value MV52 Index MV27 Object Name
On/Off
Floating
1 (2 pipe) Heat/Cool Valve Status 1 Closed – 2 Open Closed
2 (4 pipe) Cooling Valve Status 1 Closed – 2 Open Closed
1 (2 pipe) Heat/Cool Valve Status
2 (4 pipe) Cooling Valve Status
Table 13. Additional MV Values
Object Name Object ID BACnet Index Text Default Value
1 None
2 Rem NSB
BI1 Configuration MV 46
BI2 Configuration MV 47
UI3 Configuration MV 48
Pipe Number MV 52
Out#1 Cfg MV 53
AUX Configuration MV 54
Fan Mode Sequence MV 58
3 Motion NO
4 Motion NC
5 Window
1 None
2 Door Dry
3 Override
4 Filter
5 Service
1 None
2 COC/NH
3 COC/NC
4 COS
5 SS
1 2 Pipe
2 4 Pipe
1 2
2 4
1 Not used
2 NO with Occ
3 NC with Occ
4 NO with Occ & Fan
5 NC with Occ & Fan
6 Network controlled
1 Low-Med-High
2 Low-High
3 Low-Med-High-Auto
4 Low-High-Auto
5 On-Auto
State Text Index Default Value
1 Stopped - 2 Opening ­3 Closing
1 Stopped - 2 Opening ­3 Closing
Stopped
Stopped
None
None
None
4 Pipes
4
Not Used
On-Auto
BAS-SVP10A-EN 17
Page 18
BACnet Object Properties
Table 13. Additional MV Values (continued)
Object Name Object ID BACnet Index Text Default Value
Temporary Occupancy Time
Proportional Band MV 65
Floating Motor Timing
MV 62
MV 76
1 0 hour
2 1 hour
3 2 hours
4 3 hours
5 4 hours
6 5 hours
7 6 hours
8 7 hours
9 8 hours
10 9 hours
11 10 hours
12 11 hours
13 12 hours
14 13 hours
15 14 hours
16 15 hours
17 16 hours
18 17 hours
19 18 hours
20 19 hours
21 20 hours
22 21 hours
23 22 hours
24 23 hours
25 24 hours
1 3 3 F 1.2 C
2 4 4 F 1.7 C
3 5 5 F 2.2 C
4 6 6 F 2.8 C
5 7 7 F 3.3 C
6 8 8 F 3.9 C
7 9 9 F 5.0 C
8 10 10 F 5.6 C
1 0.5 minute
2 1 minute
3 1.5 minutes
4 2 minutes
5 2.5 minutes
6 3 minutes
7 3.5 minutes
8 4 minutes
9 4.5 minutes
10 5 minutes
11 5.5 minutes
12 6 minutes
13 6.5 minutes
14 7 minutes
15 7.5 minutes
16 8 minutes
17 8.5 minutes
18 9 minutes
2 hours
3
1.5 minutes
18 BAS-SVP10A-EN
Page 19
Table 13. Additional MV Values (continued)
Object Name Object ID BACnet Index Text Default Value
1 3 CPH
On-Off Control CPH MV 77
2 4 CPH
3 5 CPH
4 6 CPH
5 7 CPH
6 8 CPH

Rooftop and Heat Pump Object Properties

Table 14. List of property value range restrictions for AI and AV objects
Object Type
Object Name
Room Temperature AV 7 -40°F (-40°C) 122°F (50°C) N/A
Outdoor Temperature AV 9 -40°F (-40°C) 122°F (50°C) N/A
Room Humidity AV 11 0% 100% N/A
Supply Temp AI 16 -40°F (-40°C) 122°F (50°C) N/A
Supply RH AV 17 0% 100% N/A
PI Heating Demand AV 20 0% 100% N/A
PI Cooling Demand AV 21 0% 100% N/A
Economizer Output AV 22 0% 100% N/A
Occupied Heat Setpoint AV 42 40°F (4.5°C) 90°F (32°C) 72°F (22°C)
Occupied Cool Setpoint AV 43 54°F (12°C) 100°F (37.5°C) 75°F (24°C)
Unoccupied Heat Setpoint AV 44 40°F (4.5°C) 90°F (32°C) 62°F (16.5°C)
Unoccupied Cool Setpoint AV 45 54°F (12°C) 100°F (37.5) 80°F (26.5°C)
Heating Setpoint Limit AV 48 40°F (4.5°C) 90°F (32°C) 90°F (32°C)
Cooling Setpoint Limit AV 49 54°F (12°C) 100°F (37.5) 54°F (12°C)
Heating Lockout Temperature
Cooling Lockout Temperature AV 51 -40°F (-40°C) 95°F (35°C) -40°F (-40°C)
Deadband AV 52 2°F (1°C) 4°F (2°C) 2°F (1°C)
Password Value AV 59 0 1000 0
Power-up Delay AV 60 10 sec 120 sec 10 sec
Unoccupied Time AV 68 0.5 hrs 24.0. hrs 0.5 hrs
Economizer Changeover Setpoint
Economizer Minimum Position
Mixed Air Setpoint AV 80 50°F (10°C) 90°F (32°C) 55°F (13°C)
High Balance Point AV 82 34°F (1°C) 90°F (32°C) 90°F (32°C)
Low Balance Point AV 83 -40°F (-40°C) 30°F (-1°C) -12°F (-24°C)
Dehumidification RH Setpoint
Dehumidification Hysterisys AV 90 2% 20% 5%
Dehumidification Low OA Lockout
Humidification RH Setpoint AV 95 10% 90% 50%
Eff (Effective) Reset Humidification RH Spt (Setpoint)
Humidification High Limit Spt (Setpoint)
Low RH Setpoint AV 98 10% 90% 20%
Low Temp Reset RH Setpoint AV 99 -40°F (-40°C) 15°F (-9.5°C) -20°F (-29°C)
High Temp Reset RH Setpoint AV 100 20°F (-6.5°C) 55°F (13°C) 32°F (0.0°C)
and Instance
AV 50 -15°F (-26°C) 120°F (49°C) 120°F (49°C)
AV 77 14°F (-10°C) 70°F (21°C) 55°F (13°C)
AV 78 0% 100% 0%
AV 89 15% 95% 70%
AV 91 -40°F (-40°C) 122°F (50°C) 32°F (0°C)
AV 96 0% 100% N/A
AV 97 50% 90% 85%
Under Range
BACnet Object Properties
4 CPH
Value Over Range Value Default Value
BAS-SVP10A-EN 19
Page 20
BACnet Object Properties
Table 14. List of property value range restrictions for AI and AV objects (continued)
Object Name
Humidifier Output AV 101 0% 100% N/A
Table 15. List of property enumeration sets for BI and BV objects
Object Name
Room Temp Override BV 8 Normal Override Normal
Outdoor Temp Override BV 10 Normal Override Normal
AUX BI 24 Off On Off
G Fan BI 25 Off On Off
Y1 Cool BI 26 Off On Off
Y2 Cool BI 27 Off On Off
W1 Heat BI 28 Off On Off
W2 Heat BI 29 Off On Off
Reversing Valve BI 30 Off On Off
DI 1 Status BI 31 Not Activated Activated Not Activated
DI 2 Status BI 32 Not Activated Activated Not Activated
Local Motion BI 33 No Motion Motion No Motion
Frost Alarm BI 36 Off On Off
Clock Alarm BI 37 Off On Off
Filter Alarm BI 38 Off On Off
Service Alarm BI 39 Off On Off
Fan Lock Alarm BI 40 Off On Off
Temperature Scale BV 47 °C °F °F
Frost Protection BV 55 Off On Off
Aux Contact BV 56 N.O. N.C. N.O.
Menu Scroll BV 57 No Scroll Scroll Active Scroll Active
Fan Control BV 62 Off On On
Fan Purge Delay BV 64 Off On Off
Progressive Recovery BV 70 Off Active Off
Mechanical Cooling Enabled BV 79 Off On Off
Comfort Mode BV 84 Comfort Economy Comfort
Reversing Valve Configuration
Compressor Interlock BV 86 Off On Off
RH Display BV 88 Disabled Enabled Disabled
Dehumidification Lockout Functions
Dehumidification Output Status
Object Type
and Instance
Under Range
Value Over Range Value Default Value
Object Type
and Instance Inactive_Text Active_Text Default Value
BV 85
BV 92 Disabled Enabled Enabled
BI 93 Off On N/A
Normally Cool Energized in Heating
Normally Heat Energized in Cooling
Normally Heat Energized in Cooling
20 BAS-SVP10A-EN
Page 21
Table 16. List of property enumeration sets for MV objects
Object Type and
Object Name
Occupancy Command MV12
System Mode HPU MV13
System Mode RTU MV14
Fan Mode MV15
Keypad Lockout MV18
Effective Occupancy MV 34
Heating CPH MV53
Cooling CPH MV54
Temporary Occupancy Time MV61
Anticycle MV63
instance BACnet Index Text Default Value
1 Local Occupancy
3 Unoccupied
1 Off
2 Auto
3 Cool
4 Heat
5 Emergency
1 Off
2 Auto
3 Cool
4 Heat
1 On
3 Smart
1 Level 0
3 Level 2
1 Occupied
2 3 Unoccupied
3 Temporary Occupied
1 3 CPH
2 4 CPH
3 5 CPH
4 6 CPH
5 7 CPH
6 8 CPH
1 3 CPH
2 4 CPH
1 0 hour
2 1 hour
3 2 hours
4 3 hours
5 4 hours
6 5 hours
7 6 hours
8 7 hours
9 8 hours
10 9 hours
11 10 hours
12 11 hours
13 12 hours
1 0 minute
2 1 minute
3 2 minutes
4 3 minutes
5 4 minutes
6 5 minutes
BACnet Object Properties
Local Occupancy 2 Occupied
Auto
Auto
Smart2 Auto
Level 02 Level 1
Depends on local occupancy
4 CPH
4 CPH
3 hours
2 minutes
BAS-SVP10A-EN 21
Page 22
BACnet Object Properties
Table 16. List of property enumeration sets for MV objects (continued)
Object Name
DI1 Configuration MV65
DI2 Configuration MV66
Proportional Band MV 67
Event Display MV71
Heating Stages MV73
Cooling Stages MV74
Heat Pump Stages MV75
Object Type and
instance BACnet Index Text Default Value
1 None
2 RemNSB
3 RemOVR
4 Filter
5 Service
6 Fan lock
1 None
2 RemNSB
3 RemOVR
4 Filter
5 Service
6 Fan lock
1 2 2 F 0.6 C
2 3 3 F 1.2 C
3 4 4 F 1.7 C
4 5 5 F 2.2 C
5 6 6 F 2.8 C
6 7 7 F 3.3 C
7 8 8 F 3.9 C
1 2 Events
2 4 Events
1 1 Stage
2 2 Stages
1 1 Stage
2 2 Stages
1 1 Stage
2 2 Stages
None
None
2
2 Event
2 Stages
2 Stages
2 Stages
22 BAS-SVP10A-EN
Page 23

Objects You Can Use in Site Graphics

Fan Coils

You can use the following objects in site graphics:
Room Temperature (AV7) Heating Valve Status (MV26)
Occupied and Unoccupied Heat Setpoints (AV39 and AV43) Cooling Valve Status (MV28)
Occupied and Unoccupied Cool Setpoints (AV40 and AV34) PI Heating Demand (AV21)
Outdoor Temperature (AV9) PI Cooling Demand (AV22)
Supply Temperature (AI12) (If available) Window Alarm (BI35)
Occupancy Command (MV18) Filter Alarm (BI36)
System Mode (MV16) Service Alarm (BI37)
Room Humidity (AV10) (If available) Fan Mode (MV17)
Room Humidity Setpoint (AV71) (If available) Fan Status (MV28)
Figure 1. Sample Fan Coil Graphic
Room Temperature
Occupied Heating Setpoint
Occupied Cooling Setpoint
Unoccupied Heating Setpoint
Unoccupied Cooling Setpoint
Room Humidity
Room Humidity Setpoint
Filter Alarm
Normal
71.2 ºF
71.0 ºF
73.0 ºF
62.0 ºF
82.0 ºF
49.7 ºF
50.0 %
Occupancy
System Mode
Fan Mode
Outdoor Temperature
Supply Temperature
65.2ºF
Cooling Valve Status
Closed
Heating Valve Status
Open
Fan Status
On
Occupied
Heat
High
42 ºF
BAS-SVP10A-EN 23
Page 24
Objects You Can Use in Site Graphics

Rooftop and Heat Pump Units

You can use the following objects in site graphics:
Room Temperature (AV7) W1 Heat (BI28)
Occupied and Unoccupied Heat Setpoints (AV 42 and AV44)
Occupied and Unoccupied Cool Setpoints (AV 43 and AV45)
Outdoor Temperature (AV9) Aux (BI24)
Supply Temperature (AI16) (If available) DI 1 Status (BI31)
Occupancy Command (MV12) DI 2 Status (BI 32)
Effective Occupancy (MV34) Frost Alarm (BI36) (if available)
System Mode RTU (MV14) or System Mode HPU (MV13) Filter Alarm (BI38) (if available)
G Fan (BI25) Service Alarm (BI39) (if available)
Y1 Cool (BI26) Fan Lock Alarm (BI40) (if available)
Y2 Cool (BI27)
W2 Heat (BI29) or Reversing Valve (BI30)
Economizer Output (AV22) (if available)
Outdoor Temperature (AV9)
52.4 ºF
Economizer (AV22)
10%
Room Temperature (AV7)
Occupied Heat Setpoint (AV 42)
Occupied Cool Setpoint (AV 43)
Unoccupied Heat Setpoint (AV 44)
Unoccupied Cool Setpoint (AV 45)
Filter Alarm (BI 38)
Off
Supply Temperature (AI16)
65.2 ºF
68.2 ºF
69.0 ºF
72.0 ºF
62.0 ºF
82.0 ºF
G Fan (BI25)
Y1 Cool (BI26)
Y2 Cool (BI27)
W1 Heat (BI28)
W2 Heat (BI29) Occupancy (MV12) System Mode RTU (MV14) Aux (BI24) DI 1 Status (BI31) DI 2 Status (BI 32) Frost Alarm (BI36) Service Alarm (BI39)
On
Off
Off
On
Off
Occupied
Heat
On
Off
Off
Off
24 BAS-SVP10A-EN
Page 25

Wiring Requirements for Communicating Thermostats

BACnet networks use a daisy chain configuration. A daisy chain means that there is only one main cable and every network device is connected directly along its path.
Figure 2 illustrates two improper network configurations and the proper daisy chain configuration.
Figure 2. Incorrect and correct network configurations

BACnet MS/TP Link Wiring

BACnet MS/TP link wiring must be field-supplied and installed in compliance with the National Electric Code (NEC) and local codes.

BACnet Configuration Requirements

Follow these configuration requirements:
BACnet wiring must use daisy-chain configuration. Maximum length is 4,000 ft (1219 m).
BACnet links are polarity sensitive; consistent wiring polarity must be maintained between devices.
Limit each link to 30 controllers or 60 total controllers per Tracer SC.

BACnet Wiring Best Practices

The following wiring practices are recommended:
Use 18 AWG, (24 pF/ft. max.), shielded, twisted pair communication wire (Trane purple wire).
Strip no more than 2 in. (5 cm) of the outer conductor of shielded wire.
Avoid sharing 24 Vac power between unit controllers.
Ensure that 24 Vac power supplies are consistently grounded. If grounds are not maintained, intermittent or failed communication could result.
Connect the shield portion of the communication wire at the first unit controller in the link.
Use a Tracer BACnet terminator at each end of the link.
For additional best practices, see the Unit Controller Wiring Guide For the Tracer SC™ System Controller (BAS-SVN03x-EN).
BAS-SVP10A-EN 25
Page 26
Wiring Requirements for Communicating Thermostats

BACnet Wiring Procedure

Follow these steps to connect communication wiring as shown in Figure 3, p. 26.
1. Attach the communication link wiring to the Tracer SC at Link 1 or Link 2.
Note: It is not necessary to place the Tracer SC at the end of the of the communication link.
2. Attach the wiring from the first unit controller to the first set of communication terminals on the next unit controller.
Note: Some unit controllers have only one set of communication terminals. In that case, attach
the wiring to the same set of terminals.
3. Wire and tape shields together at each unit controller between the Tracer SC and the BACnet terminator.
4. Repeat steps 1 through 3 for each unit controller on the link.
Note: For more information about the specific unit controller you are wiring, see the
Installation Guide for the specific controller.
Figure 3. Daisy chain configuration for BACnet wiring

Trane BACnet Termination for BACnet Links

For correct termination placement, follow these guidelines:
All BACnet links must be properly terminated. Use a Tracer BACnet terminator at each end of the link.
Connect the communication wire shield to the ground terminal of the link termination block at the Tracer SC as shown in Figure 2. The Tracer SC provides the ground for the BACnet/MSTP link.
Tape back the shield at each of the BACnet terminators.
During installation, compile a set of as-built drawings or a map of the communication wire layout. Sketches of the communication layout should feature the BACnet terminators.
26 BAS-SVP10A-EN
Page 27
Figure 4. Terminating BACnet links using BACnet terminators

Product Specifications

Specifications for Communicating Thermostats are as follows.
Table 17. Communicating Thermostat Specifications
Media Twisted pair 22AWG-24 AWG, shielded recommended
Characteristic Impedance 100-130 ohms
Distributed capacitance Less than 100 pF per meter (30 pF per foot)
Maximum length per segment 1200 meters (4000 feet) Note: AWG 18 cable
Polarity Polarity sensitive
Multi-drop Daisy-chain (no T connections)
Terminations Always use Trane BACnet terminators at each end of the link.
Maximum number of nodes per segment 30
Baud rate 9600, 19200, 38400, 76800 (Auto detect)
Item Details

Network Adapter

The polarity of the connection to the cable is important. From one module to the other it is important that the same colored wire be connected to “plus” or “+” and the other colored wire be connected to the “minus” or ”-“.
Important: The Ref terminal should NEVER be used to wire shields. The 2 shields from each feed
of the network connection to a thermostat should be wired together in the back of the thermostat and properly protected to prevent any accidental connection to the ground.
The joined shield connection should then be grounded at a SINGLE point on the whole segment. More than one ground connection to a shielded wire may induce ground loop noises and affect communication.
BAS-SVP10A-EN 27
Page 28
Wiring Requirements for Communicating Thermostats

Communicating Thermostat Status LEDs

Table 18 shows the different possibilities with the Status LED behaviour for a BACnet module.
Table 18. Status LED conditions with causes and possible solutions (fan coil)
Condition of the Status LED Possible Cause Solution
1 short blink
2 short blinks (no wires connected to the module)
2 short blinks (wires connected to the module)
2 short blinks and a longer blink (wires connected to the module)
Right after power is applied: 2 long blinks and then no blinking
BACnet communication NOT active at default MAC address = 254
Normal operation until BACnet link is connected.
Thermostat is not at the same baud rate as the network
The thermostat has detected the presence of a network
Polarity has been reversed at the thermostat.

Troubleshooting

Table 19. Causes and solutions for error condition
Error / Trouble Condition Possible Cause Solution
Two or more controllers have the same MAC address.
The MS/TP network has too many devices.
Thermostat does not come online
Too many devices were installed without any repeaters.
The MS/TP cable runs are broken Locate the break and correct wiring
MS/TP connections at the module are reversed
The thermostat does not have power
Change MAC address to another value from 0 to 127
N/A
Power off and on the thermostat
N/A
Reverse polarity at the thermostat
Modify each duplicate address to a unique number.
Do not exceed the maximum number of devices and maximum length allowed by the EIA-485 specifications.
Repeaters need to be installed as specified in this document.
Respect polarity of the wires on a MS/ TP network.
Apply power to the thermostat
28 BAS-SVP10A-EN
Page 29

Additional Information and Considerations

This chapter explains some special tips and considerations that apply to the Trane Communicating Thermostats. These tips and considerations are grouped in the following categories:
MS/TP network integration
Objects and parameters
Tracer SC network configuration

MS/TP Network Integration

Before doing any BACnet integration, make sure to have Trane PICS (Protocol Implementation Conformance Statement). This PICS document lists all the BACnet Services and Object types supported by a device and can be found on the Trane portal.
The Trane Communicating Thermostats do not support the Change of Value (COV) service. COV reporting allows an object to send out notices when its Present-Value property is incremented by a pre-defined value. Since this is not supported at the thermostat, you should pay special attention to the polling time settings at the Supervisory Controller and Workstation level when using a graphical interface or an application program to read or write to the BACnet objects.

Site Graphics

For example, some site graphics might poll every data item linked to the graphic page on a COV basis. If the third party device does not support COV, the graphic interface then relies on a pre­configured polling interval, which is usually in hundredths of milliseconds. Any device containing a monitored object could be subject to network traffic congestion if such a polling interval is used. Trane strongly recommends a polling interval of 5 seconds or more for any graphic interface. This becomes even more critical in area graphics where a single representation might poll many devices. If proper poll rate is not respected, devices may be reported offline by certain front ends by saturating the traffic handling capacity of BACnet MS/TP without COV subscription.

Free Programmed Objects or Loops (Supervisory Controllers Other Than Tracer SC)

As for the application program, you might want to read and write any MS/TP data on an “If Once” basis or a “Do Every” loop basis instead of reading or writing to a third party device’s object directly in the program. Otherwise, any read or write request will occur at the Supervisory Controller’s program scan rate, which might be in hundredths of milliseconds. This can easily bog down a network as single commands can be sent to all ASC devices down the MS/TP trunks every hundredth of a millisecond.
Fan Coils
Programs writing to the devices should have a structure similar to the following:
If Once Schedule = On then MV13 = Occupied End If If Once Schedule = Off Then MV13 = Unoccupied End If
OR
Do Every 5min If Schedule = On Then MV13= Occupied Else MV13 = Unoccupied End If
End Do
BAS-SVP10A-EN 29
Page 30
Additional Information and Considerations
Rooftop and Heat Pump Units
Programs writing to the devices should have a structure similar to the following:
If Once Schedule = On then MV11 = Occupied End If If Once Schedule = Off Then MV11 = Unoccupied End If
OR
Do Every 5min If Schedule = On Then MV11= Occupied Else MV11 = Unoccupied End If
End Do

Retries and Timeouts (Supervisory Controllers Other Than Tracer SC)

Another thing to look for in a BACnet integration is the Device object of the Supervisory Controller (and the Operator’s Workstation). This object contains the 2 following required properties:
Retry Timeout The Retry Timeout property specifies the time between re-transmissions if the
acknowledgement has not been received. When you are experiencing problems with controllers dropping off-line, increasing this value may help.
Number of APDU Retries; The Number of APDU Retries property specifies the number of times unsuccessful
transmissions will be repeated. If the receiving controller has not received the transmission successfully after this many attempts, no further attempts will be made.
For example, if one of the thermostats does not reply to a Supervisory Controller (Tracer SC) request, and the Retry Timeout is set to 2000 msec and the Number of APDU Retries is set to 1 (still at the Tracer SC level), then the Tracer SC will send one other request, 2 seconds later. If the MS/ TP device does not reply, it will be considered Off-line by the workstation.
So having a Retry Timeout value of 10000 msec and a Number of APDU Retries property set to 3 at the SC level may prevent device from dropping Off-line. These properties should also be changed at the Workstation level since the workstation will likely issue requests to any MS/TP devices when the graphics are used.

Objects and Parameters

The following items apply to all equipment types.
Each thermostat is delivered from the factory with the default MAC address set at 254. At this value, the BACnet communication is NOT active and the device will not participate in the token pass either. The local LED status (located on the backside of the board) is one short flash only. To enable the BACnet communication, set the local MAC address configuration property of the thermostat to any valid value from 0 to 127 using the Installer Configuration Parameter menuon the Thermostat. (Refer to the Trane Communicating Thermostats for Heat Pump Control User Guide (BAS-SVU10A-EN), Trane Communicating Thermostats for Rooftop Control User Guide (BAS-SVU11A-EN), or the Trane Communicating Thermostats for Fan Coil Control User Guide (BAS-SVU12A-EN) for details.)
All configuration objects are available and can be edited locally from the device itself using the local configuration routine. (See the Communicating Thermostat User Guides mentioned previously in this section or in
In its default mode of operation, the device will automatically match its baud rate to the baud rate of the network. Automatic baud rate detection will occur when the MS/TP communication port is initialized (on power up). If the network speed is changed, the device will keep listening at the previously detected speed for 10 minutes before resuming automatic baud rate detection. Re-powering the devices will force immediate auto-detection.
30 BAS-SVP10A-EN
“Related Documents,” p. 6.)
Page 31
Additional Information and Considerations
If the device should go offline, the communicated value from the front-end Tracer SC will be released:
– Room Temperature
– Outdoor Temperature
– Occupancy
Device Name and Device ID properties are writable in BACnet device object. Both properties can be renamed from any BACnet network management tool as long as the tool itself give access to write to these properties.
The BACnet Data Link layer has two key parameters: the device object name and the device object ID. The device object name must be a unique BACnet device object name within the BACnet network (i.e. not just the MS/TP sub-network). The device object ID must also be a unique BACnet device object ID in the entire BACnet network (i.e. not just the MS/TP sub­network).
The following items apply to fan coils only.
Enumeration sets for System Mode MV16 depends on Sequence of Operation (MV15) value upon device discovery. If required enumerations are not present, set MV15 to desired value and rediscover MV16 object. Available enumeration will now reflect required configuration.
Enumeration sets for MV16 depends on Fan Mode Sequence (MV58) value upon device discovery. If required enumerations are not present, set MV58 to desired value and rediscover MV16 object. Available enumeration will now reflect required configuration.
Enumeration sets for MV26 and MV27 depend on Control Type (BV75) value and Pipe Number (MV52) value upon device discovery. If required enumeration is not present, set BV75 and MV52 to desired value and rediscover MV26 and BV27 object. Available enumeration will now reflect required configuration.
To assign manually a Room Temperature (AV7) value, users must first enable the Override mode in the Room Temp Override (BV8) object.
To assign manually a Room Humidity (AV10) value, users must first enable the Override mode in the Room Humidity Override (BV11) object.
BAS-SVP10A-EN 31
Page 32
Additional Information and Considerations

Tracer SC Network Configuration

You should be aware of these important facts about Communicating Thermostat capabilities in the Tracer SC network.
No automatic installation
The Trane Communicating Thermostats do not automatically install on the Tracer SC. Custom templates are available and you can select one of these templates (“Template: TStat_RTU_Trane,”
p. 40,“Template:TStat_FanCoil_Trane,”p. 36,or“Template: TStat_HeatPump_Trane,” p. 39) to get
the unit ready to install. Refer to the Tracer™ SC System Controller Installation and Setup Manual (BAS-SVX31x-EN) for details about using a template to install a Communicating Thermostat on a BACnet link.
No priority array
Binary, Analog, and Multistate Values do not use a priority array. In order to reliably control these points, they must be controlled by only controlled from multiple sources, the most recent source to control the point will be in control.
Night Purge disabled
A Trane Communicating Thermostat as a member of Area should have Night Purge disabled. Using Night Purge could result in the Heat Cool Mode Request being controlled incorrectly on a transition from Night Purge to another state. You can disable Night Purge for the entire area on the functions page of Area in the Economizer Control section (Figure 5).
one source (for example, Area control). If they are being
Figure 5. The Economizer Control section of the Area Functions page
Night purge can also be disabled from the members page by checking the box next to certain members and going to actions > edit configuration (Figure 6).
32 BAS-SVP10A-EN
Page 33
Additional Information and Considerations
Figure 6. Area members page (actions > edit configuration)
Heat only/cool only
If the thermostat is configured as cool only, it will not accept its Heat Cool Mode Request to be controlled to any heating mode. The converse applies if the thermostat is configured for heat only, it will not accept its Heat Cool Mode Request to be controlled to any cooling mode. If the point is controlled to an invalid state, it will quickly revert to the previous state.
Parameters not supported
In the Occupancy frame of the Equipment/Space status page, the following properties will not be displayed:
Last Controlled
Controlled by
Time Remaining
These are parameters that the thermostat points do not support.
Figure 7. Occupancy section of the Equipment/Space status page
BAS-SVP10A-EN 33
Page 34
Additional Information and Considerations
These properties are also shown but not populated on point status pages (Figure 8, p. 34 ).
Figure 8. Status section of the Point Status page
No active setpoint or heat/cool mode data
The Spaces Summary and Equipment Summary pages do not show data for active setpoint or heat/ cool mode as these devices do not have Space Temperature Setpoint Active and Heat Cool Mode Status points ( ).
Figure 9. Air Handlers section of the Equipment Status page
Discharge air temp requirements
The point Discharge Air Temperature on all of these devices only reports data if the respective input is configured as a discharge air sensor and a valid sensor is connected.
Inappropriate text on graphic displays
In some cases, Binary and Multistate points on a Tracer SC custom graphic display state text that does not match the space or equipment pages.
34 BAS-SVP10A-EN
Page 35
Additional Information and Considerations
Outdoor air temperature
On the TStat_FanCoil, the point Outdoor Air Temperature is only controlled from a BAS. It is not used in the control sequence of the device. If this value is to be shown on the LCD display on the thermostat, it’s recommended to use global referencing to send the Facility Outdoor Air Temperature to this point.
BAS-SVP10A-EN 35
Page 36

Data Normalization

Special data normalization has been applied to various points in the factory loaded equipment templates. This data normalization serves to make a consistent interface to equipment across Tracer SC. This chapter lists special data normalizations for each equipment template.

Example: Occupancy Request

The following example of the Occupancy Request point in the TStat_FanCoil_Trane template indicates how to interpret the special data normalization.
The point name in Tracer SC is Occupancy Request.
The point name in the BACnet device is Occupancy Command (Multistate Value instance 18 (MV18)).
Table 20 and Table 21 show the corresponding Tracer SC and fan coil states.
When Tracer SC writes the state in the left hand column to the Occupancy Request point, the BACnet point is controlled to the corresponding state on the right hand column.
Table 20. Tracer SC writing to the fan coil (Occupancy Request)
Tracer SC state and text Fan coil state and text
1 - Occupied 2 - Occupied
2 - Unoccupied 3 - Unoccupied
3 - Occupied Bypass 2 - Occupied
4 - Occupied Standby 2 - Occupied
5 - Auto 1 - Local Occupancy
When Tracer SC reads the state and text in the left hand column from the BACnet device, it reports the state and text in the right hand column in the Occupancy Request point.
Table 21. Reading from Fan Coil to Tracer SC (Occupancy Request)
Fan Coil state and text Tracer SC state and text
1 - Local Occupancy 5 - Auto
2 - Occupied 1 - Occupied
3 - Unoccupied 2 - Unoccupied

Template: TStat_FanCoil_Trane

This section lists special data normalizations for points in this template.
The Tracer SC Point name: Occupancy Status
The BACnet point name, type, and instance: Effective Occupancy (MV 33)
Table 22. Tracer SC writing to the fan coil (Occupancy Status)
Tracer SC state and text Fan coil state and text
1 - Occupied 1 - Occupied
2 - Unoccupied 2 - Unoccupied
3 - Occupied Bypass 1 - Occupied
4 - Occupied Standby 4 - Stand-by
5 - Auto 1 - Occupied
Table 23. Reading from fan coil to Tracer SC (Occupancy Status)
Fan Coil state and text Tracer SC state and text
1 - Occupied 1 - Occupied
2 - Unoccupied 2 - Unoccupied
3 - Temporary Occupied 1 - Occupied
4 - Stand-by 4 - Occupied Standby
36 BAS-SVP10A-EN
Page 37
Tracer SC point name: Occupancy Request
BACnet point name, type, and instance: Occupancy Command (MV 18)
Table 24. Tracer SC writing to the fan coil (Occupancy Request)
Tracer SC state and text Fan coil state and text
1 - Occupied 2 - Occupied
2 - Unoccupied 3 - Unoccupied
3 - Occupied Bypass 2 - Occupied
4 - Occupied Standby 2 - Occupied
5 - Auto 1 - Local Occupancy
Table 25. Reading from fan coil to Tracer SC (Occupancy Request)
Fan coil state and text Tracer SC state and text
1 - Local Occupancy 5 - Auto
2 - Occupied 1 - Occupied
3 - Unoccupied 2 - Unoccupied
Tracer SC Point name: Heat Cool Mode Request
BACnet point name, type and instance: System Mode (MV 16)
Table 26. Tracer SC writing to the fan coil (Heat Cool Mode Request)
Tracer SC state and text Fan coil state and text
1 - Auto 2 - Auto
2 - Heat 4 - Heat
3 - Morning Warm-up 4 - Heat
4 - Cool 3 - Cool
5 - Night Purge 3 - Cool
6 - Pre Cool 3 - Cool
7 - Off 1 - Off
8 - Test 2 - Auto
9 - Emergency Heat 4 - Heat
10 - Fan Only 2 - Auto
11 - Free Cool 3 - Cool
12 - Ice-Making 3 - Cool
13 - Max Heat 4 - Heat
14 - Economizer 3 - Cool
15 - Dehumidify 3 - Cool
16 - Calibrate 2 - Auto
Data Normalization
Table 27. Reading from fan coil to Tracer SC (Heat Cool Mode Request)
Fan coil state and text Tracer SC state and text
1 - Off 7 - Off
2 - Auto 1 - Auto
3 - Cool 4 - Cool
4 - Heat 2 - Heat
BAS-SVP10A-EN 37
Page 38
Data Normalization
Tracer SC Point name: Supply Fan Staged Speed Status
BACnet point name, type, and instance: Fan Status (MV 28)
Table 28. Tracer SC writing to the fan coil (Supply Fan Staged Speed Status)
Tracer SC state and text Fan coil state and text
1 - Auto 4 - High
2 - Off 1 - Off
3 - Low 2 - Low
4 - Medium 3 - Medium
5 - High 4 - High
Table 29. Reading from fan coil to Tracer SC (Supply Fan Staged Speed Status)
Fan coil state and text Tracer SC state and text
1 - Off 2 - Off
2 - Low 3 - Low
3 - Medium 4 - Medium
4 - High 5 - High
Tracer SC Point name: Fan Mode BAS
BACnet point name, type, and instance: Fan Mode (MV 17)
Table 30. Tracer SC writing to the fan coil (Fan Mode BAS)
Tracer SC state and text Fan coil state and text
1 - On 2 - On
2 - Auto 1 - Auto
3 - Smart 1 - Auto
Table 31. Reading from fan coil to tracer SC (Fan Mode BAS)
Fan Coil state and text Tracer SC state and text
1 - Auto 2 - Auto
2 - On 1 - On
38 BAS-SVP10A-EN
Page 39

Template: TStat_HeatPump_Trane

This section lists special data normalizations for points in this template.
Tracer SC Point name: Occupancy Status
BACnet point name, type, and instance: Effective
Table 32. Tracer SC writing to the heat pump (Occupancy Status)
Tracer SC state and text Heat pump state and text
1 - Occupied 1 - Occupied
2 - Unoccupied 2 - Unoccupied
3 - Occupied Bypass 1 - Occupied
4 - Occupied Standby 1 - Occupied
5 - Auto 1 - Occupied
Table 33. Reading from heat pump to Tracer SC (Occupancy Status)
Heat pump state and text Tracer SC state and text
1 - Occupied 1 - Occupied
2 - Unoccupied 2 - Unoccupied
3 - Temporary Occupied 1 - Occupied
Tracer SC Point name: Occupancy Request
BACnet point name, type and instance: Occupancy Command (MV 12)
Data Normalization
Occupancy (MV 34)
Table 34. Tracer SC writing to the heat pump (Occupancy Request)
Tracer SC state and text Heat pump state and text
1 - Occupied 2 - Occupied
2 - Unoccupied 3 - Unoccupied
3 - Occupied Bypass 2 - Occupied
4 - Occupied Standby 2 - Occupied
5 - Auto 1 - Local Occupancy
Table 35. Reading from heat pump to Tracer SC (Occupancy Request)
Heat pump state and text Tracer SC state and text
1 - Local Occupancy 5 - Auto
2 - Occupied 1 - Occupied
3 - Unoccupied 2 - Unoccupied
Tracer SC Point name: Heat Cool Mode Request
BACnet point name, type and instance: System Mode (MV 13)
BAS-SVP10A-EN 39
Page 40
Data Normalization
Table 36. Tracer SC writing to the heat pump (Heat Cool Mode Request)
Tracer SC state and text Heat pump state and text
1 - Auto 2 - Auto
2 - Heat 4 - Heat
3 - Morning Warm-up 4 - Heat
4 - Cool 3 - Cool
5 - Night Purge 3 - Cool
6 - Pre Cool 3 - Cool
7 - Off 1 - Off
8 - Test 2 - Auto
9 - Emergency Heat 5 - Emergency
10 - Fan Only 2 - Auto
11 - Free Cool 3 - Cool
12 - Ice-Making 3 - Cool
13 - Max Heat 4 - Heat
14 - Economizer 3 - Cool
15 - Dehumidify 3 - Cool
16 - Calibrate 2 - Auto
Table 37. Reading from Heat Pump to Tracer SC (Heat Cool Mode Request)
Heat pump state and text Tracer SC state and text
1 - Off 7 - Off
2 - Auto 1 - Auto
3 - Cool 4 - Cool
4 - Heat 2 - Heat
5 - Emergency 9 - Emergency Heat

Template: TStat_RTU_Trane

This section lists special data normalizations for points in this template.
Tracer SC Point name: Occupancy Status
BACnet point name, type, and instance: Effective Occupancy (MV 34)
Table 38. Tracer SC writing to the rooftop unit (Occupancy Status)
Tracer SC state and text Rooftop unit state and text
1 - Occupied 1 - Occupied
2 - Unoccupied 2 - Unoccupied
3 - Occupied Bypass 1 - Occupied
4 - Occupied Standby 1 - Occupied
5 - Auto 1 - Occupied
Table 39. Reading from rooftop unit to Tracer SC (Occupancy Status)
Rooftop unit state and text Tracer SC state and text
1 - Occupied 1 - Occupied
2 - Unoccupied 2 - Unoccupied
3 - Temporary Occupied 1 - Occupied
40 BAS-SVP10A-EN
Page 41
Tracer SC Point name: Occupancy Request
BACnet point name, type, and instance: Occupancy Command (MV 12)
Table 40. Tracer SC writing to the rooftop unit (Occupancy Request)
Tracer SC state and text Rooftop unit state and text
1 - Occupied 2 - Occupied
2 - Unoccupied 3 - Unoccupied
3 - Occupied Bypass 2 - Occupied
4 - Occupied Standby 2 - Occupied
5 - Auto 1 - Local Occupancy
Table 41. Reading from rooftop unit to Tracer SC (Occupancy Request)
Rooftop unit state and text Tracer SC state and text
1 - Local Occupancy 5 - Auto
2 - Occupied 1 - Occupied
3 - Unoccupied 2 - Unoccupied
Tracer SC Point name: Heat Cool Mode Request
BACnet point name, type and instance: System Mode (MV 14)
Table 42. Tracer SC writing to the rooftop unit (Heat Cool Mode Request)
Tracer SC state and text Rooftop unit state and text
1 - Auto 2 - Auto
2 - Heat 4 - Heat
3 - Morning Warm-up 4 - Heat
4 - Cool 3 - Cool
5 - Night Purge 3 - Cool
6 - Pre Cool 3 - Cool
7 - Off 1 - Off
8 - Test 2 - Auto
9 - Emergency Heat 4 - Heat
10 - Fan Only 2 - Auto
11 - Free Cool 3 - Cool
12 - Ice-Making 3 - Cool
13 - Max Heat 4 - Heat
14 - Economizer 3 - Cool
15 - Dehumidify 3 - Cool
16 - Calibrate 2 - Auto
Data Normalization
Table 43. Reading from rooftop unit to Tracer SC (Heat Cool Mode Request)
Rooftop unit state and text Tracer SC state and text
1 - Off 7 - Off
2 - Auto 1 - Auto
3 - Cool 4 - Cool
4 - Heat 2 - Heat
BAS-SVP10A-EN 41
Page 42

Trane Communicating Thermostat Points List

The following tables provide side by side lists of Tracer SC points and Communicating Thermostat device point names and related information.

TStat_Fan_Coil_Trane

Table 44. Points Available in the TStat_Fan_Coil_Trane Template
TStat Device Point
Tracer SC Point Name
Diagnostic Present Service Alarm BI 37
Dirty Filter Alarm Filter Alarm BI 36
Discharge Air Temperature Supply Temperature AI 12
Display Temperature Scale Temperature Scale BV 51
Emergency Heat Status AUX Status BI 25
Fan Mode BAS Fan Mode MV 17 Yes
Heat Cool Mode Request System Mode MV 16 Yes
Keypad Lockout Keypad Lockout MV 19
Minimum Heating Cooling Setpoint Differential
Occupancy Input Local Motion BI 32
Occupancy Request Occupancy Command MV 18 Yes
Occupancy Status Effective Occupancy MV 33 Yes
Occupied Cooling Setpoint Occupied Cool Setpoint AV 40
Occupied Heating Setpoint Occupied Heat Setpoint AV 39
Occupied Standby Cooling Setpoint Stand-by Cool Setpoint AV 42
Occupied Standby Heating Setpoint Stand-by Heat Setpoint AV 41
Outdoor Air Temperature Outdoor Temperature AV 9
Space Temperature Active Room Temperature AV 7
Supply Fan Staged Speed Status Fan Status MV 28 Yes
Timed Override Duration Setpoint Temporary Occupancy Time MV 62
Unoccupied Cooling Setpoint Unoccupied Heat Setpoint AV 43
Unoccupied Cooling Setpoint Unoccupied Cool Setpoint AV 44
Deadband AV 63
PI Heating Demand AV 21
PI Cooling Demand AV 22
Password Value AV 56
Heating Setpoint Limit AV 58
Cooling Setpoint Limit AV 59
Stand-by Time AV 67
Unoccupied Time AV 68
BI 1 Status BI 29
BI 2 Status BI 30
UI 3 Status BI 31
Window Alarm BI 35
Room Temp Override BV 8
AUX Command BV 14
Menu Scroll BV 49
Auto Mode Enable BV 50
Setpoint Type BV 60
Setpoint Function BV 61
Reheat Time Base BV 64
Auto Fan BV 66
Control Type BV 75
Sequence of Operation MV 15
Heating Valve Status MV 26
Name
Point
Type
Point
Instance
Data
Normaliza-
tion
42 BAS-SVP10A-EN
Page 43
Table 44. Points Available in the TStat_Fan_Coil_Trane Template (continued)
Tracer SC Point Name

TStat_HeatPump_Trane Template

Table 45. Points Available in the TStat_HeatPump_Trane Template
Tracer SC Point Name
Cool Output 1 Status Y1 Cool BI 26
Cool Output 2 Status Y2 Cool BI 27
Diagnostic Present Service Alarm BI 39
Dirty Filter Alarm Filter Alarm BI 38
Discharge Air Temperature Supply Temperature AI 16
Display Temperature Scale Temperature Scale BV 47
Fan Mode BAS Fan Mode MV 15
Fan Output Status G Fan BI 25
Heat Cool Mode Request System Mode HP MV 13 Yes
Heat Output 1 Status W1 Heat BI 28
In Defrost Frost Protection BV 55
Keypad Lockout Keypad Lockout MV 18
Low Temperature Alarm Frost Alarm BI 36
Minimum Heating Cooling Setpoint Differential
Occupancy Input Local Motion BI 33
Occupancy Request Occupancy Command MV 12 Yes
Occupancy Status Effective Occupancy MV 34 Yes
Occupied Cooling Setpoint Occupied Cool Setpoint AV 43
Occupied Heating Setpoint Occupied Heat Setpoint AV 42
Outdoor Air Temperature Outdoor Temperature AV 9
Reversing Valve Reversing Valve BI 30
Space Temperature Active Room Temperature AV 7
Supply Fan Configuration Command Fan Control BV 62
Supply Fan Failure Fan Lockout Alarm BI 40
Timed Override Duration Setpoint Temporary Occupancy Time MV 61
Unoccupied Cooling Setpoint Unoccupied Cool Setpoint AV 45
Unoccupied Heating Setpoint Unoccupied Heat Setpoint AV 44
Trane Communicating Thermostat Points List
TStat Device Point
Name
Cooling Valve Status MV 27
BI 1 Configuration MV 46
BI 2 Configuration MV 47
UI 3 Configuration MV 48
Pipe Number MV 52
AUX Configuration MV 54
Fan Mode Sequence MV 57
Proportional Band MV 65
Floating Motor Timing MV 76
On Off Control CPH MV 77
TStat Device Point
Name Point Type
Deadband AV 52
PI Heating Demand AV 20
PI Cooling Demand AV 21
Heating Setpoint Limit AV 48
Cooling Setpoint Limit AV 49
Point
Type
Point
Instance
Point
Instance
Data
Normaliza-
tion
Data
Normaliza-
tion
BAS-SVP10A-EN 43
Page 44
Trane Communicating Thermostat Points List
Table 45. Points Available in the TStat_HeatPump_Trane Template (continued)
Tracer SC Point Name
TStat Device Point
Name Point Type
Heating Lockout Temperature
Cooling Lockout Temperature
Password Value AV 59
Power-up Delay AV 60
Unoccupied Time AV 68
High Balance Point AV 82
Low Balance Point AV 83
AUX BI 24
DI 1 Status BI 31
DI 2 Status BI 32
Room Temp Override BV 8
Outdoor Temp Override BV 10
Aux Contact BV 56
Menu Scroll BV 57
Fan Purge Delay BV 64
Comfort Mode BV 84
Reversing Valve Configuration
Compressor Interlock BV 86
Heating CPH MV 53
Cooling CPH MV 54
Anticycle MV 63
DI 1 Configuration MV 65
DI 2 Configuration MV 66
Proportional Band MV 67
Heat Pump Stages MV 75
AV 50
AV 51
BV 85
Point
Instance
Data
Normaliza-
tion

TStat_RTU_Trane Template

Table 46. Points Available in the TStat_RTU_Trane Template
Data
TStat Device Point
Tracer SC Point Name
Cool Output 1 Status Y1 Cool BI 26
Cool Output 2 Status Y2 Cool BI 27
Diagnostic Present Service Alarm BI 39
Dirty Filter Alarm Filter Alarm BI 38
Discharge Air Temperature Supply Temperature AI 16
Display Temperature Scale Temperature Scale BV 47
Economizer Minimum Position Setpoint BAS
Economizer Mixed Air Enable Setpoint BAS
Economizer Outdoor Air Enable Setpoint BAS
Fan Mode BAS Fan Mode MV 15
Fan Output Status G Fan BI 25
Heat Cool Mode Request System Mode RTU MV 14 Yes
Heat Output 1 Status W1 Heat BI 28
Economizer Minimum Position
Mixed Air Setpoint AV 80
Economizer Changeover Setpoint
Name Point Type
AV 78
AV 77
44 BAS-SVP10A-EN
Point
Instance
Normaliza-
tion
Page 45
Trane Communicating Thermostat Points List
Table 46. Points Available in the TStat_RTU_Trane Template (continued)
TStat Device Point
Tracer SC Point Name
Heat Output 2 Status W2 Heat BI 29
In Defrost Frost Protection BV 55
Keypad Lockout Keypad Lockout MV 18
Low Temperature Alarm Frost Alarm BI 36
Minimum Heating Cooling Setpoint Differential
Occupancy Input Local Motion BI 33
Occupancy Request Occupancy Command MV 12 Yes
Occupancy Status Effective Occupancy MV 34 Yes
Occupied Cooling Setpoint Occupied Cool Setpoint AV 43
Occupied Heating Setpoint Occupied Heat Setpoint AV 42
Outdoor Air Damper Position Economizer Output AV 22
Outdoor Air Temperature Outdoor Temperature AV 9
Space Temperature Active Room Temperature AV 7
Supply Fan Configuration Command Fan Control BV 62
Supply Fan Failure Fan Lockout Alarm BI 40
Timed Override Duration Setpoint Temporary Occupancy Time MV 61
Unoccupied Cooling Setpoint Unoccupied Cool Setpoint AV 45
Unoccupied Heating Setpoint Unoccupied Heat Setpoint AV 44
Deadband AV 52
PI Heating Demand AV 20
PI Cooling Demand AV 21
Heating Setpoint Limit AV 48
Cooling Setpoint Limit AV 49
Heating Lockout Temperature
Cooling Lockout Temperature
Password Value AV 59
Power-up Delay AV 60
Unoccupied Time AV 68
AUX BI 24
DI 1 Status BI 31
DI 2 Status BI 32
Room Temp Override BV 8
Outdoor Temp Override BV 10
Aux Contact BV 56
Menu Scroll BV 57
Fan Purge Delay BV 64
Mechanical Cooling Enabled BV 79
Heating CPH MV 53
Cooling CPH MV 54
Anticycle MV 63
DI 1 Configuration MV 65
DI 2 Configuration MV 66
Proportional Band MV 67
Heating Stages MV 73
Cooling Stages MV 74
Name Point Type
AV 50
AV 51
Point
Instance
Data
Normaliza-
tion
BAS-SVP10A-EN 45
Page 46
Notes
Page 47
Notes
Page 48
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
© 2011 Trane All rights reserved
BAS-SVP10A-EN 26 Aug 2011
New
We are committed to using environmentally
conscious print practices that reduce waste.
Loading...