Only qualified personnel should install and service the equipment.The installation, starting up, and servicing
of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and
training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or
serious injury.When working on the equipment, observe all precautions in the literature and on the tags,
stickers, and labels that are attached to the equipment.
Read this manual thoroughly before operating or servicing
this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as
required.Your personal safety and the proper operation of
this machine depend upon the strict observance of these
precautions.
The three types of advisories are defined as follows:
WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious
injury. All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards.To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes.
WARNING
CAUTIONs
NOTICE
Indicates a potentially hazardous
situation which, if not avoided, could
result in death or serious injury.
Indicates a potentially hazardous
situation which, if not avoided, could
result in minor or moderate injury. It
could also be used to alert against
unsafe practices.
Indicates a situation that could result in
equipment or property-damage only
accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made
chemicals can affect the earth’s naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified
chemicals that may affect the ozone layer are refrigerants
that contain Chlorine, Fluorine and Carbon (CFCs) and
those containing Hydrogen, Chlorine, Fluorine and
Carbon (HCFCs). Not all refrigerants containing these
compounds have the same potential impact to the
environment.Trane advocates the responsible handling of
all refrigerants-including industry replacements for CFCs
such as HCFCs and HFCs.
Important Responsible Refrigerant
Practices
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air
conditioning industry. All technicians who handle
refrigerants must be certified. The Federal Clean Air Act
(Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain
refrigerants and the equipment that is used in these
service procedures. In addition, some states or
municipalities may have additional requirements that
must also be adhered to for responsible management of
refrigerants. Know the applicable laws and follow them.
WARNING
Personal Protective Equipment (PPE)
Required!
Installing/servicing this unit could result in exposure to
electrical, mechanical and chemical hazards.
•Before installing/servicing this unit, technicians
MUST put on all PPE required for the work being
undertaken (Examples; cut resistant gloves/sleeves,
butyl gloves, safety glasses, hard hat/bump cap, fall
protection, electrical PPE and arc flash clothing).
ALWAYS refer to appropriate Material Safety Data
Sheets (MSDS)/Safety Data Sheets (SDS) and OSHA
guidelines for proper PPE.
•When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS/SDS and
OSHA/GHS (Global Harmonized System of
Classification and Labelling of Chemicals) guidelines
for information on allowable personal exposure
levels, proper respiratory protection and handling
instructions.
•If there is a risk of energized electrical contact, arc, or
flash, technicians MUST put on all PPE in accordance
with OSHA, NFPA 70E, or other country-specific
requirements for arc flash protection, PRIOR to
servicing the unit. NEVER PERFORM ANY
SWITCHING, DISCONNECTING, OR VOLTAGE
TESTING WITHOUT PROPER ELECTRICAL PPE AND
ARC FLASH CLOTHING. ENSURE ELECTRICAL
METERS AND EQUIPMENT ARE PROPERLY RATED
FOR INTENDED VOLTAGE.
Failure to follow instructions could result in death or
serious injury.
This document and the information in it are the property of
Trane, and may not be used or reproduced in whole or in
part without written permission.Trane reserves the right
to revise this publication at any time, and to make changes
to its content without obligation to notify any person of
such revision or change.
Trademarks
All trademarks referenced in this document are the
trademarks of their respective owners.
Revision History
WSHP-SVX13C-EN (03 January 2015)
•Added the option of a plenum fan allowing the unit to
work at higher external static pressures (ESP)
•Added selection of new motor
•Added option of insulated water coil and suction line
Product contains fiberglass wool. Disturbing the
insulation in this product during installation,
maintenance or repair will expose you to airborne
particles of glass wool fibers and ceramic fibers known
to the state of California to cause cancer through
inhalation. Glass wool fibers may also cause
respiratory, skin or eye irritation.
Unit Inspection
•Unpack all components of the kit.
•Check carefully for any shipping damage. If any
damage is found it must be reported immediately and
a claim made against the transportation company.
•Visually inspect the components for shipping damage
as soon as possible after delivery, before it is stored.
Concealed damage must be reported within 15 days.
•If concealed damage is discovered, stop unpacking the
shipment.
•Do not remove damaged material from the receiving
location.Take photos of the damage, if possible.The
owner must provide reasonable evidence that the
damage did not occur after delivery.
•Notify the carrier ’s terminal of damage immediately by
phone and by mail. Request an immediate joint
inspection of the damage by the carrier and the
consignee.
•Do not attempt to repair any damaged parts until the
parts are inspected by the carrier’s representative.
Jobsite Inspection
Always perform the following checks before
accepting a unit:
•Verify that the nameplate data matches the data on the
sales order and bill of lading (including electrical data).
•Verify that the power supply complies with the unit
nameplate specifications.
•Visually inspect the exterior of the unit, for signs of
shipping damage. Do not sign the bill of lading
accepting the unit(s) until inspection has been
completed. Check for damage promptly after the
unit(s) are unloaded. Once the bill of lading is signed at
the jobsite, the unit(s) are now the property of the
SOLDTO party and future freight claims MAY NOT be
accepted by the freight company.
Jobsite Storage
WARNING
Microbial Growth!
Wet interior unit insulation can become an amplification
site for microbial growth (mold), which may cause odors
and serious health related indoor air quality problems. If
there is evidence of microbial growth (mold) on the
interior insulation, remove or replace the insulation prior
to operating the system. Failure to remove microbial
growth could result in serious health problems.
This unit is intended for indoor use only.To protect the unit
from damage due to the elements, and to prevent possible
IAQ contaminant sources from growing, the unit should be
stored indoors. If indoor storage is not possible, the
following provisions for outdoor storage must be met:
•Place the unit(s) on a dry surface or raise above the
ground to assure adequate air circulation beneath the
unit.
•Cover the unit(s) with a water proof tarp to protect
them from the elements.
•Make provisions for continuous venting of the covered
units to prevent moisture from standing on the unit(s)
surfaces. Wet interior unit insulation can become an
amplification site for microbial growth (mold) which
has been determined to be a cause of odors and
serious health related indoor air quality problems.
•Store units in the normal UP orientation to maintain oil
in the compressor.
•Do not stack vertical units. Horizontal units may be
stacked two high.
Model Number Description
All products are identified by a multiple-character model
number that precisely identifies a particular type of unit. Its
use will enable the owner/operator, installing contractors,
and service engineers to define the operation, specific
components, and other options for any specific unit.
When ordering replacement parts or requesting service,
be sure to refer to the specific model number and serial
number printed on the unit nameplate.
Unit Description
Before shipment, each unit is leak tested, dehydrated,
charged with refrigerant and run tested for proper control
operation.
Unit Nameplate
The unit nameplate is located on the outside of the control
box access panel at the front of the unit. It includes the unit
model number, serial number, electrical characteristics,
refrigerant charge, and other pertinent unit data.
WSHP-SVX13C-EN7
General Information
Compressor Nameplate
The nameplate for the compressors are located on the
compressor shell.
Air-to- Refrigerant Coil
The air-to-refrigerant coil is aluminum fin, mechanically
bonded to the copper tubing.
Water-to-Refrigerant Coil
The water-to-refrigerant coil is a copper or cupro-nickel
(option) and steel tube (tube-within-a-tube) design, leak
tested to assure there is no cross leakage between the
water tube (copper/cupro-nickel) and refrigerant gas (steel
tube).
.
Table 1.High/Low pressure switch
TripRecoverUnit
LP40 +/-456 +/-4psig
HP650 +/-10550 +/-10psig
Controls
The control system offered to control the unit is the
Tracer™ UC400 programmable BACnet™ unit controller.
The UC400 controller is standard for all unit sizes.
All power wiring to the equipment is made at the unit
power block. VSH/V 460V units require a neutral wire.
System Input Devices and Functions
A zone sensor or building automation system is required
to operate the water-source heat pump.The flexibility of
having several mode capabilities depends upon the type
of sensor and/or remote panel selected.
Troubleshooting and connection diagrams for the UC400
control systems may be located in the back of this manual.
Pump Module (field installed accessory)
The pump module shall consist of either a single or dual
1/6 HP bronze pump and a brass 3-way shut-off valve. Cast
iron pumps are also acceptable. The pump module kits
shall contain the necessary components for the
installation, operation and maintenance of the water
circuit of a closed-loop distributed pumping application.
Access to the unit for service purposes should be provided
at installation. All configurations require clearance (see
Figure 2, p. 9 and Figure 1, p. 9) from other mechanical
and electrical equipment (as shown) to enable panel
removal from the unit for service/maintenance ability.
Some local and/or NEC codes require a greater service
clearance than listed below. Check all code requirements
prior to unit installations. The installer is responsible for
compliance with local and NEC code requirements.
Note: *Units in a free return application will
require more than a 1 inch clearance to
provide proper air flow to the units air-torefrigerant coil.
WSHP-SVX13C-EN9
1"
UNIT FRONT
36"
24"
LEFT RETURN
TOP/BACK SUPPLY
Unit Dimensions
Figure 3. Left return/top supply - VSV with ECM
D
L
F
K
JM
TOP
B
LEFT SIDE
D
E
8 3/4”
H
3 5/8”
BLOWER
ACCESS
COMP/CONTROL
ACCESS
HI VOLT
LO VOLT
A
FRONTRIGHT SIDE
12”
9 1/2”
G
3 5/8”
W.O.
DRAIN
W.I.
C
Table 3.Dimensional data - left return/top supply -VSV with ECM
Note: Access to the unit for service purposes should be provided at installation. Local and/or NEC codes may require greater service clearance. Check all
code requirements prior to the unit installation. Installer is responsible for following all local and NEC code requirements.
10WSHP-SVX13C-EN
W.I.
NPTI
W.O.
NPTI
Drain
FPT
Figure 4. Left return/top supply - VSV 5 tons with ECM
E
L
G
F
Unit Dimensions
K
J
TOP
B
LEFT SIDE
D
BLOWER
ACCESS
H
W.O.
COMP/CONTROL
10-5/8
ACCESS
HI VOLT
LO VOLT
4-5/8
A
FRONT
DRAIN
2 1/2"
W.I.
8 1/4"
19
C
RIGHT SIDE
Table 4.Dimensional data - left return/top supply -VSV060 with ECM
Note: Access to the unit for service purposes should be provided at installation. Local and/or NEC codes may require greater service clearance. Check all
code requirements prior to the unit installation. Installer is responsible for following all local and NEC code requirements.
WSHP-SVX13C-EN11
W.I.
NPTI
W.O.
NPTI
Drain
FPT
Unit Dimensions
Figure 5. Left return/back supply - VSV 5 tons with ECM
D
E
JM
TOP
F
D
H
BLOWER
ACCESS
B
COMP/CONTROL
LEFT SIDE
8 3/4"
3 5/8"
ACCESS
HI VOLT
9 1/2"
LO VOLT
A
FRONTRIGHT SIDE
12"
G
3 5/8"
W.O.
DRAIN
W.I .
C
Table 5.Dimensional data - left return/back supply -VSV060 with ECM
W.I.
UnitsABCDEFGHJKLM
024–033 24-1/2 41-7/8 26-1/2183-1/41-7/89-1/2202310-1/2 13-1/23/163/43/43/4
042–050 26-1/2 46-7/8 30-1/2184-1/429-1/224-1/4 27-7/8 13-7/8 11-3/81/2113/4
Note: Access to the unit for service purposes should be provided at installation. Local and/or NEC codes may require greater service clearance. Check all
code requirements prior to the unit installation. Installer is responsible for following all local and NEC code requirements.
NPTI
NPTI
W.O.
Drain
FPT
12WSHP-SVX13C-EN
Figure 6. Left return/back supply - VSV 5 tons with ECM
F
D
K
J
TOP
G
E
L
H
B
BLOWER
ACCESS
Unit Dimensions
W.O.
COMP/CONTROL
LEFT SIDE
10-5/8
ACCESS
HI VOLT
LO VOLT
4-5/8
A
FRONT
DRAIN
2 1/2"
W.I.
8 1/4"
19
C
RIGHT SIDE
Table 6.Dimensional data - left return/back supply -VSV060 with ECM
Note: Access to the unit for service purposes should be provided at installation. Local and/or NEC codes may require greater service clearance. Check all
code requirements prior to the unit installation. Installer is responsible for following all local and NEC code requirements.
NPTI
NPTI
W.O.
Drain
FPT
WSHP-SVX13C-EN13
Unit Dimensions
B
E
Figure 7. Right return/top supply - VSV with ECM
BLOWER
ACCESS
F
D
H
D
L
K
JM
TOP
COMP/CONTROL
ACCESS
W.O.
HI VOLT
LO VOLT
C
LEFT SIDE
8 3/4"
3 5/8"
Table 7.Dimensional data - right return/top supply -VSV with ECM
UnitsABCDEFGHJKLM
DRAIN
12"
3 5/8"
9 1/2"
G
W.I .
A
FRONTRIGHT SIDE
W.I.
NPTI
W.O.
NPTI
Drain
FPT
024–033 24-1/2 41-7/8 26-1/2183-1/45-3/49-1/2202310-1/2 13-1/23/163/43/43/4
042–050 26-1/2 46-7/8 30-1/2184-1/429-1/224-1/4 27-7/8 13-7/8 11-3/81/2113/4
Note: Access to the unit for service purposes should be provided at installation. Local and/or NEC codes may require greater service clearance. Check all
code requirements prior to the unit installation. Installer is responsible for following all local and NEC code requirements.
14WSHP-SVX13C-EN
Figure 8. Right return/top supply - VSV 5 tons with ECM
Unit Dimensions
G
F
E
L
D
J
TOP
BLOWER
ACCESS
H
B
W.O.
DRAIN
2 1/2"
W.I.
19
8 1/4"
C
RIGHT SIDE
LEFT SIDE
10-5/8
4-5/8
COMP/CONTROL
ACCESS
HI VOLT
LO VOLT
A
FRONT
K
Table 8.Dimensional data - right return/top supply - VSV060 with ECM
Note: Access to the unit for service purposes should be provided at installation. Local and/or NEC codes may require greater service clearance. Check all
code requirements prior to the unit installation. Installer is responsible for following all local and NEC code requirements.
WSHP-SVX13C-EN15
W.I.
NPTI
W.O.
NPTI
Drain
FPT
Unit Dimensions
H
G
Figure 9. Right return/back supply VSV with ECM
F
D
B
BLOWER
ACCESS
D
E
JM
TOP
COMP/CONTROL
ACCESS
W.O.
HI VOLT
LO VOLT
C
LEFT SIDE
8 3/4"
3 5/8"
DRAIN
12"
W.I .
A
FRONTRIGHT SIDE
9 1/2"
3 5/8"
Table 9.Dimensional data - right return/back supply - VSV with ECM
UnitsABCDEFGHJKLM
024–033 24-1/2 41-7/8
042–050 26-1/2 46-7/8 30-1/2184-1/429-1/224-1/4 27-7/8 13-7/8 11-3/81/2113/4
Note: Access to the unit for service purposes should be provided at installation. Local and/or NEC codes may require greater service clearance. Check all
code requirements prior to the unit installation. Installer is responsible for following all local and NEC code requirements.
26-1/2
(673)
183-1/41-7/89-1/2202310-1/2 13-1/23/163/43/43/4
NPTI
W.I.
W.O.
NPTI
Drain
FPT
16WSHP-SVX13C-EN
Figure 10. Right return/back supply - VSV 5 tons with ECM
G
L
E
B
BLOWER
ACCESS
Unit Dimensions
F
K
D
J
TOP
H
W.O.
DRAIN
2 1/2"
W.I.
19
8 1/4"
C
RIGHT SIDE
LEFT SIDE
10-5/8
4-5/8
COMP/CONTROL
ACCESS
HI VOLT
LO VOLT
A
FRONT
Table 10. Dimensional data - right return/back supply - VSV060 with ECM
Note: Access to the unit for service purposes should be provided at installation. Local and/or NEC codes may require greater service clearance. Check all
code requirements prior to the unit installation. Installer is responsible for following all local and NEC code requirements.
NPTI
NPTI
W.O.
Drain
FPT
WSHP-SVX13C-EN17
Unit Dimensions
Figure 11. Left return/top supplyVSV with plenum fan
FD
D
TOP
JM
B
LEFT SIDE
E
9-3/4
BLOWER
ACCESS
H
W.O.
DRAIN
W.I.
RIGHT SIDE
C
3.56
HI VOLT
LO VOLT
FRONT
9-1/2
12
G
A
3-5/8
Table 11. Dimensional data—left return/top supply with plenum fan
Note: Access to the unit for service purposes should be provided at installation. Local and/or NEC codes may require greater service clearance. Check all
code requirements prior to the unit installation. Installer is responsible for following all local and NEC code requirements.
18WSHP-SVX13C-EN
W.I.
NPTI
W.O.
NPTI
Drain
FPT
Figure 12. Left return/top supply — VSV060 with plenum fan
DG
TOP
J
F
D
BLOWER
ACCESS
Unit Dimensions
B
LEFT SIDE
10-5/8
4-5/8
H
W.O.
HI VOLT
LO VOLT
FRONT
AC
26.0780
DRAIN
W.I.
8-1/4
2-1/2
19
RIGHT SIDE
Table 12. Dimensional data—left return/top supply - VSV060 with plenum fan
Note: Access to the unit for service purposes should be provided at installation. Local and/or NEC codes may require greater service clearance. Check all
code requirements prior to the unit installation. Installer is responsible for following all local and NEC code requirements.
NPTI
NPTI
W.O.
Drain
FPT
WSHP-SVX13C-EN19
Unit Dimensions
Figure 13. Right return/top supply with plenum fan
FD
D
E
BLOWER
ACCESS
B
HI VOLT
3.56
9-3/4
LEFT SIDE
LO VOLT
FRONT
A
H
9-1/2
12
G
3-5/8
TOP
W.O.
DRAIN
W.I.
RIGHT SIDE
MJ
C
Table 13. Dimensional data - right return/top supply with plenum fan
UnitsABCDEFGHJKLM
024–033 24-1/2 66-3/32 26-1/2183-1/4 7-23/32 9-1/22023N/AN/A1-3/43/43/43/4
042–050 26-1/2 71-3/32 30-1/2184-1/4 5-23/32 9-1/224-1/4 27-7/8N/AN/A1/2113/4
Note: Access to the unit for service purposes should be provided at installation. Local and/or NEC codes may require greater service clearance. Check all
code requirements prior to the unit installation. Installer is responsible for following all local and NEC code requirements.
20WSHP-SVX13C-EN
W.I.
NPTI
W.O.
NPTI
Drain
FPT
Figure 14. Right return/top supply -VSV060 with plenum fan
BLOWER
ACCESS
Unit Dimensions
G
F
D
TOP
J
D
B
HI VOLT
LO VOLT
FRONT
AC
26.0780
LEFT SIDE
10-5/8
4-5/8
W.O.
DRAIN
H
19
8-1/4
2-1/2
W.I.
RIGHT SIDE
Table 14. Dimensional data - right return/top supply - VSV060 with plenum fan
Note: Access to the unit for service purposes should be provided at installation. Local and/or NEC codes may require greater service clearance. Check all
code requirements prior to the unit installation. Installer is responsible for following all local and NEC code requirements.
NPTI
NPTI
W.O.
Drain
FPT
WSHP-SVX13C-EN21