Trane Axiom Mid-Range and
Large Water Source Heat Pumps
The 6 through 25 ton horizontal and vertical water source
heat pumps are used in a broad range of applications.
Schools, office buildings, health care/rehabilitation facilities, condominiums and retirement facilities are just a few
of the types of buildings utilizing the energy conscious
watersource design.
Model GEV (pictured to the right) is a floor mounted product that provides a serviceability to maintenance components; indoor air quality standards; sound attenuation; and
best of all, higher efficiencies rated in accordance to ARIISO 13256-1 performance and ASHRAE 90.1 standards.
Trane’s design incorporates system advantages such as
n Superior maintenance accessibility
n Dual-sloped, plastic drain pan
n Maximum return-air and supply-air flexibility
n Multiple fan speed motor packages
n Quiet unit design
n Integrated controls
n Dual circuit design
n High and low pressure safeties as standard
n Dehumidification option
n Waterside economizing option
n
2 Speed Blower Motor (option)
n Supplemental electric heat option
1
Trane Axiom Mid-Range and Large Water Source Heat Pumps
AHRI - ISO Ratings
Model GEH
Water Loop (WLHP) Ground Loop (GLHP)Ground Water (GWHP)
Cooling 86F Heating 68F Cooling 59F Heating 50F Full Cool 77F Full Heat 32F
Cooling
capacity
(BTUH) EER
072 18.0 2100 75,500 13.4 83,800 4.8 83,200 21.9 69,100 4.2 74,600 16.0 54,400 3.5
090 22.5 2625 88,100 14.1 99,200 4.7 94,600 20.7 83,000 4.1 88,100 15.8 64,500 3.4
120 30.0 3500 115,900 13.4 147,100 4.6 129,000 19.3 122,600 4.1 120,600 14.9 99,200 3.2
150 37.5 4375 152,800 14.3 175,000 4.4 166,800 20.6 147,800 4.1 158,000 16.4 118,000 3.4
180 45.0 5250 180,800 13.1 222,700 4.4 204,700 18.5 183,100 4.0 188,500 14.7 147,900 3.5
Model GEV
Water Loop (WLHP) Ground Loop (GLHP)Ground Water (GWHP)
Cooling 86F Heating 68F Cooling 59F Heating 50F Full Cool 77F Full Heat 32F
Cooling
capacity
(BTUH) EER
072 18.0 2100 74,900 15.2 82,800 4.6 84,800 22.9 70,200 4.2 78,800 17.5 54,500 3.4
090 22.5 2625 89,700 15.1 103,600 4.5 98,600 22.9 83,600 4.1 92,100 17.4 65,600 3.4
120 30.0 3500 119,300 14.5 134,300 4.5 131,400 21.1 113,900 4.1 123,200 16.6 90,400 3.4
150 37.5 4375 154,300 15.4 185,300 4.8 170,400 22.2 152,900 4.3 158,900 17.3 120,600 3.6
180 45.0 5250 185,700 14.1 221,500 4.4 205,000 20.1 180,400 4.1 192,200 16.1 143,500 3.5
240 60.0 7000 249,800 15.1 270,800 4.6 280,200 22.1 223,800 4.2 258,000 17.0 177,900 3.5
300 75.0 8750 305,700 13.9 350,400 4.3 339,400 19.5 286,400 3.8 315,500 15.7 234,600 3.3
Note: Models with capacities greater than 135,000 BTUH are not included in the ARI water-to-air and brine-to-air heat pump certification program.
(a)Rated in accordance with ISO Standard 13256-1: 1998 (Water Loop Heat Pumps, Ground Water Heat Pumps, Ground Loop Heat Pumps).
Heating
capacity
(BTUH)
Heating
capacity
(BTUH)
COP COP Size Water flow Airflow
COP COP Size Water flow Airflow
Cooling
capacity
(BTUH) EER
Cooling
capacity
(BTUH) EER
Heating
capacity
(BTUH) COP
Heating
capacity
(BTUH) COP
Cooling
capacity
(BTUH) EER
Cooling
capacity
(BTUH) EER
Heating
capacity
(BTUH)
Heating
capacity
(BTUH)
Unit size
Horizontal 072 090 120 150 180
Length (inch) 41 41 41 47 47
Height (inch) 21 21 21 28 28
Width (inch) 79 79 79 85 85
Vertical 072 090 120 150 180 240 300
Length (inch) 42 42 42 82 82 82 82
Height (inch) 63 63 63 68 68 68 68
Width (inch) 36 36 36 36 36 36 36
General Data
072 090 120 150 180 240 300
Compressor type Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Approximate Total weight (lb) 665 676 785 857 955 1599 1620
Filter: Standard Height 20x20x1(4) 20x20x1(4) 20x20x1(4) 20x25x1(6) 20x25x1(6) 20x25x1(6) 20x25x1(6)
Water in/out size (FPT) (In) 1-1/4 1-1/4 1-1/2 1-1/2 1-1/2 2 2
Condensate size (NPTI) (In) 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Blower wheel size (In) 13 x 13 13 x 13 13 x 13 15 x 15 15 x 15 13 x 13 13 x 13
WSHP-SLB043-EN January 29, 2015
2