Trane Axiom GEHB 012, Axiom GEHB 036, Axiom GEHB 024, Axiom GEHB 015, Axiom GEHB 030 Installation, Operation And Maintenance Manual

...
Installation, Operation and Maintenance
Axiom™ Horizontal/Vertical
Water-Source Comfort System Models GEH and GEV
15 - 25 Ton
1/2 - 5 Ton
6 - 10 Ton
6 - 15 Ton
006 - 060 – 50/60 HZ 006 - 060 – 50/60 Hz "R" and later 072 - 180 – 50/60 Hz 072 - 300 – 50/60 Hz "D" and later
March 2007 WSHP-SVX01E-EN
Preface and Warnings and Cautions
Overview of Manual
Note: One copy of this document
ships inside the control panel of each unit and is customer property. It must be retained by the unit’s maintenance personnel.
This booklet describes proper installation, operation, and maintenance procedures for air cooled systems. By carefully reviewing the information within this manual and following the instructions, the risk of improper operation and/or component damage will be minimized.
Service and maintenance work should be performed by a qualified technician” and all electrical service and maintenance work should be performed by a qualified licensed electrician.
Hazard Identification
Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully.
WARNI NG
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
CAUTION
Indicates a situation that may result in equipment or property-damage­only accidents.
Model Number Description
All products are identified by a multiple-character model number that precisely identifies a particular type of unit. Its use will enable the owner/operator, installing contractors, and service engineers to define the operation, specific components, and other options for any specific unit.
When ordering replacement parts or requesting service, be sure to refer to the specific model number and serial number printed on the unit nameplate.
Inspection
Unpack all components of the kit.
Check carefully for any shipping damage. If any damage is found it must be reported immediately and a claim made against the transportation company.
Visually inspect the components for shipping damage as soon as possible after delivery, before it is stored. Concealed damage must be reported within 15 days.
If concealed damage is discovered, stop unpacking the shipment.
Do not remove damaged material from the receiving location. Take photos of the damage, if possible. The owner must provide reasonable evidence that the damage did not occur after delivery.
Notify the carrier’s terminal of damage immediately by phone and by mail. Request an immediate joint inspection of the damage by the carrier and the consignee.
Note: Do not attempt to repair any
damaged parts until the parts are inspected by the carrier’s representative.
Overview
Your unit is designed to comfort condition all year long with safe, efficient, trouble-free operation. It is important that you understand how to operate and maintain your unit to keep it operating safely and efficiently. This manual will acquaint you with these important procedures.
Familiarize yourself with this manual and store it in a convenient location for future reference.
Important!
Equipment is shipped FOB (Free on Board) at the manufacturer. Therefore, freight claims for damages against the carrier must be initiated by the receiver.
Unit contains HCFC (R-22) Refrigerant
Instructions!
Section 608, Paragraph C of the 1990 Clean Air Act states:
Effective July 1, 1992, it shall be unlawful for any person, in course of maintaining, servicing, repairing, or disposing of an air conditioning system, to knowingly vent or release any CFC or HCFC refrigerant. Minimal releases (air purges or refrigerant hoses) associated with good faith attempts to recapture or recycle are exempt from the ban on venting.
© 2007 American Standard All rights reserved WSHP-SVX01E-EN
Table of Contents
Overview of Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Hazard Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Model Number Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Jobsite Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Jobsite Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unit Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Compressor Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Air-to-Refrigerant Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Water-to-Refrigerant Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
System Input Devices and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Basic 24V Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Deluxe 24V Controls (option) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Tracer ZN510 or ZN524 Controls (option) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Waterside Economizer (option) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Boilerless Control/Electric Heat (option) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Supplemental or Boilerless Electric Heat (option) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Hot Gas Reheat (option) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Weight Distribution for Hanging the GEH Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
GEH Clearance Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
GEV 1/2 through 5 Ton Clearance Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
GEV 6 through 10 Ton Clearance Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
GEV 12 1/2 through 25 Ton Clearance Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . 10
General Installation Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Supply-Air Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Return-Air Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Dual Filtration (GEH 1/2 to 5 ton) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Return-Air Duct Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Sound Attenuation Pad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Hanging the Horizontal Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Condensate Drain Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Supply/Return Pipe Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Types of Hose Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Cleaning and Flushing the Water Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Connecting a Water Regulating Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Installation for Single Compressor Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Installation for Multiple Compressor Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Field Installed Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Main Unit Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
WSHP-SVX01E-EN 3
Table of Contents
Control Power Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Thermostat Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Controls Using 24 VAC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Controls Using 24 VAC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Deluxe Board Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Blower Motor Speed-Tap Retrofit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Air Flow Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Waterside Economizer Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Waterside Economizer Installation for GEV and GEH 6 to 25 Ton Models . . . . . . 61
Start-up Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Economizer Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Electrical Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Pre-Start Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Pre-Start. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Initial Unit Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Start-Up Checklist and Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Sequence of Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Operating Pressures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Operation Pressures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Water Pressure Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Condensate Trap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Warranty Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Standard Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Extended Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
4 WSHP-SVX01E-EN
General Information
WARNI NG
Fiberglass Wool!
Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation. Glass wool fibers may also cause respiratory, skin or eye irritation.
Jobsite Inspection
Always perform the following checks before accepting a unit:
Verify that the nameplate data matches the data on the sales order and bill of lading (including electrical data).
Verify that the power supply complies with the unit nameplate specifications.
Visually inspect the exterior of the unit, for signs of shipping damage. Do not sign the bill of lading accepting the unit(s) until inspection has been completed. Check for damage promptly after the unit(s) are unloaded. Once the bill of lading is signed at the jobsite, the unit(s) are now the property of the SOLD TO party and future freight claims MAY NOT be accepted by the freight company.
Verify that the refrigerant charge has been retained during shipment by use of gauges. Schrader taps are located internal to the cabinet.
After assuring that charge has been retained, reinstall the schrader caps to assure that refrigerant leakage does not occur.
WARNI NG
Microbial Growth!
Wet interior unit insulation can become an amplification site for microbial growth (mold), which may cause odors and serious health related indoor air quality problems. If there is evidence of microbial growth (mold) on the interior insulation, remove or replace the insulation prior to operating the system. Failure to remove microbial growth could result in serious health problems.
Jobsite Storage
This unit is intended for indoor use only. To protect the unit from damage due to the elements, and to prevent possible IAQ contaminant sources from growing, the unit should be stored indoors. If indoor storage is not possible, the following provisions for outdoor storage must be met:
Place the unit(s) on a dry surface or raise above the ground to assure adequate air circulation beneath the unit.
Cover the unit(s) with a water proof tarp to protect them from the elements.
Make provisions for continuous venting of the covered units to prevent moisture from standing on the unit(s) surfaces. Wet interior unit insulation can become an amplification site for microbial growth (mold) which has been determined to be a cause of odors and serious health related indoor air quality problems.
Store units in the normal UP orientation to maintain oil in the compressor.
Horizontal units may be stacked no more than three units high. Do not stack the vertical unit configurations.
Unit Nameplate
The unit nameplate is located on the outside of the control box access panel at the front of the unit. It includes the unit model number, serial number, electrical
characteristics, refrigerant charge, and other pertinent unit data.
Compressor Nameplate
The nameplate for the compressors are located on the compressor shell.
Unit Description
Before shipment, each unit is leak tested, dehydrated, charged with refrigerant and run tested for proper control operation.
Air-to-Refrigerant Coil
The air-to-refrigerant coil is aluminum fin, mechanically bonded to the copper tubing.
Water-to-Refrigerant Coil
The water-to-refrigerant coil is a copper or cupro-nickel (option) and steel tube (tube-within-a-tube) design, leak tested to assure there is no cross leakage between the water tube (copper/cupro-nickel) and refrigerant gas (steel tube).
Controls
The control system offered to control the unit is a Basic 24 Volt control for the 1/2 through 5 ton sizes, a Deluxe 24 Volt control option for all unit sizes, a Tracer™ ZN510, LonTalk™ certified control option for the 1/2 through 5 ton unit sizes, or a Tracer ZN524, LonTalk certified control option for all unit sizes.
All power wiring to the equipment is made at the unit contactor for the 1/2 through 5 ton, and at the high voltage terminal block for the 6 through 25 ton. All low voltage wiring is made at the unit’s low voltage terminal board.
System Input Devices and Functions
A thermostat, zone sensor or building automation system is required to operate the water-source heat pump. The flexibility of having several mode capabilities depends upon the type of sensor and/or remote panel selected.
WSHP-SVX01E-EN 5
General Information
Troubleshooting and connection diagrams for the 24 Volt control systems may be located in the back of this manual. All digital control troubleshooting tips and connection diagrams are located in WSHP-IOP-2 (ZN510) or WSHP-PRB002-EN (ZN524).
Basic 24V Controls
Safety devices for equipment containing the basic 24V control option include a low pressure switch or suction line temperature sensor to prevent compressor operation during low temperature activity. The switch or sensor is set to activate at refrigerant pressures of 20 psig (1/2 to 5 ton units) or 7 psig (6 to 25 ton units) to fit most applications.
A high pressure switch prevents compressor operation during high or excessive discharge pressures exceeding 395 psig.
The lockout relay communicates the low or high pressure situation to the compressor to prevent operation. For units that contain a condensate overflow switch option, a condensate overflow situation will also be communicated to the compressor through the lockout relay if an overflow condition exists. The relay may be reset at the thermostat, or by cycling power to the unit.
General alarm is accomplished through the lockout relay and is used in driving light emitting diodes (LEDs). This feature will drive dry contacts only, and cannot be used to drive field installed control inputs. Trane recommends 3 minute or greater minimum off time for compressor control.
Deluxe 24V Controls (option)
Units containing the Deluxe 24V control design will incorporate a microprocessor-based control board. The Trane microprocessor board is factory wired to a terminal strip to provide all necessary terminals for field connection. The deluxe board is equipped with a random start relay, anti-short cycle timer, brown out
protection, compressor disable, condensate overflow, unit safety control, diagnostics and a generic relay (which may be available for field use). SeeTa bl e 3 4 for diagnostic information and Figure 62 and
Figure 63 for thermostat connections.
Trane recommends 3 minute or greater minimum off time for compressor control.
Tracer ZN510 or ZN524 Controls (option)
The digital ZN510 and ZN524 controller is designed to support the 1/2 through 25 ton water-source heat pumps in either a standalone, peer­to-peer with a Tracer Loop Controller, or as a full building automation (open protocol) system. The 1/2 through 5 ton units that incorporate direct digital controls will typically come equipped with the ZN510 control board. The exception to this would be if the equipment contained hot gas reheat, waterside economizer, or boilerless control with electric heat. The ZN524 digital control board is designed to interface and run these mechanical options. All units over 5 tons would ship with the Tracer ZN524 control board.
For installation, operation and diagnostics of the ZN510 and ZN524 WSHP-IOP-2 (ZN510) and/or WSHP­PRB002-EN (ZN524).
Waterside Economizer (option)
Instructions for mechanical connection of the waterside economizer to the water-source heat pump may be found in the dimensional section of this manual.
The waterside economizer is designed to begin economizing mode when water temperatures fall below the field adjustable temperature of 25, 35, 45, 55 or 65 F (for the Deluxe control option), or below the programmed set-point (for the ZN524 control option).
When the temperature is less than the setpoint, fluid will flow into the economizing coil, while simultaneously halting mechanical operation of the compressor. Mechanical cooling will continue on a call for a second stage from the thermostat or system control.
Boilerless Control/Electric Heat (option)
Systems that do not contain a boiler may contain a boilerless control with electric heat. Trane offers both a factory mounted electric heat option, and a field mounted duct heater option.
If the 1/2 through 5 ton GEH and GEV unit incorporates the factory mounted option, the unit will ship from the factory with an internally mounted nichrome open wire heating element, designed to start-up electric heat as the systems primary heat in the event entering water temperature falls below 55 F. Once the entering water temperature rises above 60 F, the boilerless controller returns the unit to normal compressor heating operation, and locks out the electric heater.
If the unit contains a cooling only heat pump design, the electric heat contactor is wired directly to the thermostat for primary heating, and the compressor contactor for cooling.
For units comprised of the field installed duct heater option, the unit will ship from the factory with controls available to interface with the field provided electric heat selection.
Note: For geothermal applications,
the boilerless controller has an adjustable setting of 25, 35, 45, 55 and 60 degrees.
Supplemental or Boilerless Electric Heat (option)
The 6 through 25 ton models which contain boilerless control electric heat or supplemental electric heat will contain the controls interface ONLY for field provided electric heat selection. The heater for this model shall be external to the equipment by the contractor for ease of installation. All power connections for the electric
6 WSHP-SVX01E-EN
heater will be completely separate from the unit for field supplied electric heat.
Note: When the unit has boilerless
control, the electric heat is not used as supplemental electric heat, but as a primary heat.
Hot Gas Reheat (option)
With the reheat option, the return-air from the space is conditioned by the air-to-refrigerant coil, then reheated by the reheat coil to control not only the space temperature, but to also reduce the relative humidity of the space. When operating in the reheat mode (meaning the sensible temperature has been met in the space), the humidistat signals the reheat relay coil to energize, allowing the high pressure refrigerant gas to flow from the compressor through the reheat valve, into the reversing valve, or reheat coil for dehumidification.
A switching relay has been provided for the reheat application to adjust the blower motor from normal operation to low speed when the hot gas reheat is energized (for 1/2 through 5 ton equipment only).
Note: A high static blower motor is
required to support the hot gas reheat option for the 1/2 through 5 ton equipment.
Note: Units containing the hot gas
reheat option should not be used as a make-up air unit.
Note: Water regulating valves
should not be used with the hot gas reheat option. Trane places a thermal expansion valve on all WSHPs as well as GSHPs to regulate refrigerant flow vs. water flow to the unit.
General Information
WSHP-SVX01E-EN 7
Weights
WARNI NG
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level. Failure to properly lift unit could result in death or serious injury or possible equipment or property-only damage.
Weight Distribution for Hanging the GEH Model
Approximate weight distribution for proper hanging of the GEH unit is indicated by the diagram to the right.
Tolerance on the weights determined are ± 15%.
Total weights for each unit size are listed above.
Table 1. Unit weights
GEH 60 HZ
006-015 006-012 188 lb (85 kg) 158 lb (71 kg) 018-030 015-024 278 lb (125 kg) 248 lb (112 kg) 036-042 030-036 318 lb (143 kg) 288 lb (130 kg) 048-060 042-060 428 lb (193 kg) 398 lb (179 kg) 072 - 701 lb (318 kg) 652 lb (296 kg) 090 072 714 lb (325 kg) 666 lb (303 kg) 120 090 831 lb (377 kg) 789 lb (359 kg) 150 120 907 lb (412 kg) 865 lb (393 kg) 180 150 999 lb (454 kg) 957 lb (435 kg)
GEH 50 HZ
GEV 60 HZ
006-015 006-012 178 lb (80 kg) 158 lb (71 kg) 018-030, 040 015-024 268 lb (121 kg) 248 lb (112 kg) 036, 042 030, 036 308 lb (139 kg) 288 lb (130 kg) 048, 060 042-060 396 lb (178 kg) 248 lb (112 kg)
072 - 617 lb (280 kg) 577 (262 kg) 090 072 648 (294 kg) 608 (276 kg) 120 090 861 (391 kg) 821 (373 kg) 150 120 1215 lb (547 kg) 1170 lb (527 kg) 180 150 1225 lb (551 kg) 1180 lb (531 kg) 240 180 1615 lb (727 kg) 1580 lb (711 kg) 300 240 1665 lb (749 kg) 1640 lb (738 kg)
GEV 50 HZ
Shipping Weight with pallet
Shipping Weight w/o pallet
Operating Weight
Figure 1. Weight distribution
1/2 through 5 - ton
Figure 2. Weight distribution
6 through 15 - ton
Table 2. Table 2: Waterside economizer
weight
GEV 60 HZ
072 - 148 lb (67 kg) 006-015 006-012 54 lb (24.5 kg) 072 - 138 lb (63 kg) 090 072 168 lb (76 kg) 018-030 015-024 65 lb (29.5 kg) 090 072 144 lb (65 kg) 120 090 207 lb (94 kg) 036-042 030-036 76 lb (35 kg) 120 090 166 lb (75 kg) 150, 180 120, 150 275 lb (125 kg) 048-060 042-060 97 lb (44 kg) 150 120 213 lb (97 kg) 240 180 310 lb (141 kg) 180 150 213 lb (97 kg) 300 240 395 lb (179 kg)
GEV 50 HZ
Economizer Weight
8 WSHP-SVX01E-EN
GEH 60 HZ
GEH 50 HZ
Economizer Weight
GEH 60 HZ
GEH 50 HZ
Economizer Weight
GEH Clearance
LEFT RETURN BACK SUPPLY
UNIT FRONT
LEFT RETURN
RIGHT SUPPLY
LEFT RETURN
LEFT SUPPLY
UNIT FRONT UNIT FRONT
3"
(76)
18" (457) (4-SIDES)
RIGHT RETURN
BACK SUPPLY
UNIT FRONT
RIGHT RETURN
LEFT SUPPLY
RIGHT RETURN
RIGHT SUPPLY
UNIT FRONT UNIT FRONT
3"
(76)
18" (457)
(4-SIDES)
18" (457)
(4-SIDES)
18" (457) (4-SIDES)
18" (457) (3-SIDES)
18" (457) (3-SIDES)
Dimensions
Access to the unit for service purposes should be provided at installation. All 1/2 through 5 ton configurations require an 18" (457 mm) surround clearance from other mechanical and electrical equipment (where shown) to enable panel removal from the unit for service/ maintenance ability. Some local codes require a greater service clearance than listed below. Check all code requirements prior to unit installations.
Equipment containing a same-side supply/return combination requires a 3" (229 mm) limitation on one side. Access to the TXV may not be possible with this 3" (229 mm) clearance. This configuration is typically applied in a corridor installation, where space limitations force the left or right side of the unit against a wall.
Service clearance dimensions for the 6 through 15 ton horizontal includes a two side access appropriate for control and blower motor/wheel access. Some local codes require a greater service clearance than listed below. Check all code requirements prior to unit installations.
Dimensions
Figure 3. GEH 1/2 through 5 ton clearance
WSHP-SVX01E-EN 9
36"
(914)
SERVICE
CLEARANCE
CONTROL BOX
20"
(508)
SERVICE
CLEARANCE
Figure 4. GEH 6 through 15 ton clearance
TOP VIEW
BLOWER ACCESS PANEL
Dimensions
GEV 1/2 through 5 Ton Clearance Dimensions
Access to the unit for service purposes should be provided at installation. All configurations require an 24" (610 mm) surround clearance from other mechanical and electrical equipment (where shown) to enable panel removal from the unit for service/maintenance ability. Some local codes require a greater service clearance than listed below. Check all code requirements prior to unit installations. Units in a free return application will require more than a 1" (25.4) clearance to provide proper air flow to the units air-to­refrigerant coil.
GEV 6 through 10 Ton Clearance Dimensions
Minimum access for service clearances are provided below. Any one unit side other than the control panel or return-air side may be placed against a wall. The unit may be serviced through the three remaining open sides. Some local codes require a greater service clearance than listed below. Check all code requirements prior to unit installations.
1"
(25.4)
24"
(610)
RIGHT RETURN
TOP/BACK SUPPLY
UNIT FRONT
24"
(610)
(25.4)
1"
Figure 5. GEV 1/2 through 5 ton clearance
ACCESS PANEL FOR SHEAVES AND BELTS
20"
(508)
SERVICE
CLEARANCE
1"
(25.4)
UNIT FRONT
1"
(25.4)
FRONT RETURN
TOP SUPPLY
24"
(610)
LEFT RETURN
TOP/BACK SUPPLY
(914)
SERVICE
CLEARANCE
36"
24"
(610)
GEV 12 1/2 through 25 Ton Clearance
Figure 6. GEH 6 through 15 ton clearance
Dimensions
The diagram below outlines the minimum required unit service clearances. Any one unit side other than the control panel or return-air side may be placed against a wall. The unit may be serviced through the three remaining open sides. Some local codes require a greater service clearance than listed below. Check all code requirements prior to unit installations.
CONTROL BOX
NEC REQ.
MIN. 36" (914)
C.B. TO WALL
CLEARANCE
Figure 7. GEV 12 1/2 through 25 ton clearance
10 WSHP-SVX01E-EN
18" (457)
FRONT RETURN-AIR
BACK SUPPLY-AIR
UNIT FRONT
16" (406) TO
FILTER FRAME
FOR RETURN-AIR
MIN. SERVICE CLEARANCE FOR EITHER LEFT OR RIGHT SIDE IS 18" (457). FOR FAN SHAFT REMOVAL, A 22" (559) CLEARANCE MUST BE PROVIDED ON EITHER THE LEFT OR RIGHT SIDE.
Dimensions
Figure 8. Left return, left supply
Table 3. Measurements
Unit A B C D E F G H J K
006,
40"
20"
15"
20"
009
(1016)
(508)
(381)
012,
40"
20"
015
(1016)
018 46"
(1168)
024,
46"
030
(1168)
036,
50"
042
(1270)
048,
58"
060
(1473)
(508) 23"
(584) 23"
(584) 25"
(635) 33"
(838)
15" (381)
17" (432)
17" (432)
19" (483)
21" (533)
WSHP-SVX01E-EN 11
(508) 20"
(508) 23"
(584) 23"
(584) 25"
(635) 25"
(635)
15" (381)
15" (381)
18" (457)
18" (457)
20" (508)
28" (711)
6 7/8" (175)8"(203)
6 7/8" (175)
8 1/4" (210)
8 1/4" (210)
10 1/2" (267)
13 7/8" (352)
9 7/8" (251)
9 3/4" (248)
11 3/8" (289)
13 1/2" (343)
13 7/8" (352)
11 1/2" (292)
11 1/2" (292)
13 1/2" (343)
13 1/2" (343)
16 3/8" (416)4"(102)
18" (457)
4 1/4" (108)
4 1/4" (108)
4 3/4" (121)
4 3/4" (121)
6 5/8" (168)2"(51)1"(25.4)
L NPTIMNPTI N P Q R S
2 1/8"
1/2"
1/2"
(54) 2 5/8"
(67) 2 7/8"
(73) 2 7/8"
(73) 1 3/4"
(45)
(12.7) 1/2"
(12.7) 3/4"
(19) 3/4"
(19) 3/4"
(19)
(12.7) 1/2"
(12.7) 3/4"
(19) 3/4"
(19) 3/4"
(19) 1"
(25.4)
38 3/4" (984)
38 3/4" (984)
44 3/4" (1137)
44 3/4" (1137)
48 3/4" (1238)
56 3/4" (1441)
18 3/4" (476)
18 3/4" (476)
21 3/4" (552)
21 3/4" (552)
23 3/4" (603)
31 3/4" (806)
13 5/8" (346)
13 5/8" (346)
15 5/8" (397)
15 5/8" (397)
17 5/8" (448)
19 5/8" (498)
18 1/2" (470)
18 1/2" (470)
18 1/2" (470)
18 1/2" (470)
23 1/2" (597)
23 1/2" (597)
3 3/8" (86)
3 3/8" (86)
4 1/4" (108)
4 1/4" (108)
3 1/4" (83)
5 1/2" (140)
Dimensions
Figure 9. Left return/back supply
Table 4. Measurements
Unit A B C D E F G H J K
006,
40"
20"
15"
20"
15"
009
(1016)
012,
40"
015
(1016)
018 46"
(1168)
024,
46"
030
(1168)
036,
50"
042
(1270)
048,
58"
060
(1473)
(508) 20"
(508) 23"
(584) 23"
(584) 25"
(635) 33"
(838)
(381) 15"
(381) 17"
(432) 17"
(432) 19"
(483) 21"
(533)
(508) 20"
(508) 23"
(584) 23"
(584) 25"
(635) 25"
(635)
(381) 15"
(381) 18"
(457) 18"
(457) 20"
(508) 28"
(711)
6 7/8" (175)8"(203)
6 7/8" (175)
8 1/4" (210)
8 1/4" (210)
10 1/2" (267)
13 7/8" (352)
9 7/8" (251)
9 3/4" (248)
11 3/8" (289)
13 1/2" (343)
13 7/8" (352)
11 1/2"
4 1/4"
(292)
(108)
11 1/2"
4 1/4"
(292)
(108)
13 1/2"
4 3/4"
(343)
(121)
13 1/2"
4 3/4"
(343)
(121)
16 3/8" (416)4"(102)
18"
6 5/8"
(457)
(168)2"(51)1"(25.4)1"(25.4)
12 WSHP-SVX01E-EN
L NPTIMNPTI N P Q R S
2 1/8"
1/2"
1/2"
38 3/4"
(54) 2 5/8"
(67) 2 7/8"
(73) 2 7/8"
(73) 1 3/4"
(45)
(12.7) 1/2"
(12.7) 3/4"
(19) 3/4"
(19) 3/4"
(19)
(12.7) 1/2"
(12.7) 3/4"
(19) 3/4"
(19) 3/4"
(19)
(984) 38 3/4"
(984) 44 3/4"
(1137) 44 3/4"
(1137) 48 3/4"
(1238) 56 3/4"
(1441)
18 3/4" (476)
18 3/4" (476)
21 3/4" (552)
21 3/4" (552)
23 3/4" (603)
31 3/4" (806)
13 5/8" (346)
13 5/8" (346)
15 5/8" (397)
15 5/8" (397)
17 5/8" (448)
19 5/8" (498)
18 1/2" (470)
18 1/2" (470)
18 1/2" (470)
18 1/2" (470)
23 1/2" (597)
23 1/2" (597)
3 3/8" (86)
3 3/8" (86)
4 1/4" (108)
4 1/4" (108)
3 1/4" (83)
5 1/2" (140)
Dimensions
Figure 10. Left return/right supply
Table 5. Measurements
Unit
Unit
60
50
HZ
HZ A B C D E F G H J K
006-
006 40"
009 012-
009-
015
012
018 015 46"
024-
018-
030
024
036-
030-
042
036
048-
042-
060
060
(1016) 40"
(1016)
(1168) 46"
(1168) 50"
(1270) 58"
(1473)
20" (508)
20" (508)
23" (584)
23" (584)
25" (635)
33" (838)
15" (381)
15" (381)
17" (432)
17" (432)
19" (483)
21" (533)
20" (508)
20" (508)
23" (584)
23" (584)
25" (635)
29 1/2" (749)
15" (381)
15" (381)
18" (457)
18" (457)
20" (508)
21 1/2" (546)
6 7/8" (175)8"(203)
6 7/8"
9 7/8"
(175)
(251)
8 1/4"
9 3/4"
(210)
(248)
8 1/4"
11 3/8"
(210)
(289)
10 1/2"
13 1/2"
(267)
(343)
13 7/8"
13 7/8"
(352)
(352)
11 1/2"
4 1/4"
(292)
(108)
11 1/2"
4 1/4"
(292)
(108)
13 1/2"
4 3/4"
(343)
(121)
13 1/2"
4 3/4"
(343)
(121)
16 3/8" (416)4"(102)
18"
6 5/8"
(457)
(168)2"(51)1"(25.4)1"(25.4)
WSHP-SVX01E-EN 13
L NPTIMNPTI N P Q R
2 1/8"
1/2"
1/2"
(54) 2 5/8"
(67) 2 7/8"
(73) 2 7/8"
(73) 1 3/4"
(45)
(12.7) 1/2"
(12.7) 3/4"
(19) 3/4"
(19) 3/4"
(19)
(12.7) 1/2"
(12.7) 3/4"
(19) 3/4"
(19) 3/4"
(19)
38 3/4" (984)
38 3/4" (984)
44 3/4" (1137)
44 3/4" (1137)
48 3/4" (1238)
56 3/4" (1441)
18 3/4" (476)
18 3/4" (476)
21 3/4" (552)
21 3/4" (552)
23 3/4" (603)
31 3/4" (806)
13 5/8" (346)
13 5/8" (346)
15 5/8" (397)
15 5/8" (397)
17 5/8" (448)
19 5/8" (498)
18 1/2" (470)
18 1/2" (470)
18 1/2" (470)
18 1/2" (470)
23 1/2" (597)
23 1/2" (597)
Dimensions
Figure 11. Right return/left supply
Table 6. Measurements
Unit A B C D E F G H J K
006,
40"
20"
15"
20"
009
(1016)
(508)
(381)
012,
40"
20"
015
(1016)
018 46"
(1168)
024,
46"
030
(1168)
036,
50"
042
(1270)
048,
58"
060
(1473)
(508) 23"
(584) 23"
(584) 25"
(635) 33"
(838)
15" (381)
17" (432)
17" (432)
19" (483)
21" (533)
14 WSHP-SVX01E-EN
(508) 20"
(508) 23"
(584) 23"
(584) 25"
(635) 25"
(635)
15" (381)
15" (381)
18" (457)
18" (457)
20" (508)
28" (711)
6 7/8" (175)8"(203)
6 7/8"
9 7/8"
(175)
(251)
8 1/4"
9 3/4"
(210)
(248)
8 1/4"
11 3/8"
(210)
(289)
10 1/2"
13 1/2"
(267)
(343)
13 7/8"
13 7/8"
(352)
(352)
11 1/2"
4 1/4"
(292)
(108)
11 1/2"
4 1/4"
(292)
(108)
13 1/2"
4 3/4"
(343)
(121)
13 1/2"
4 3/4"
(343)
(121)
16 3/8" (416)4"(102)
18"
6 5/8"
(457)
(168)2"(51)1"(25.4)
L NPTIMNPTI N P Q R S
2 1/8"
1/2"
1/2"
38 3/4"
(54) 2 5/8"
(67) 2 7/8"
(73) 2 7/8"
(73) 1 3/4"
(45)
(12.7) 1/2"
(12.7) 3/4"
(19) 3/4"
(19) 3/4"
(19)
(12.7) 1/2"
(12.7) 3/4"
(19) 3/4"
(19) 3/4"
(19) 1"
(25.4)
(984) 38 3/4"
(984) 44 3/4"
(1137) 44 3/4"
(1137) 48 3/4"
(1238) 56 3/4"
(1441)
18 3/4" (476)
18 3/4" (476)
21 3/4" (552)
21 3/4" (552)
23 3/4" (603)
31 3/4" (806)
13 5/8" (346)
13 5/8" (346)
15 5/8" (397)
15 5/8" (397)
17 5/8" (448)
19 5/8" (498)
18 1/2" (470)
18 1/2" (470)
18 1/2" (470)
18 1/2" (470)
23 1/2" (597)
23 1/2" (597)
3 3/8" (86)
3 3/8" (86)
4 1/4" (108)
4 1/4" (108)
3 1/4" (83)
5 1/2" (140)
Dimensions
Figure 12. Right return/back supply
Table 7. Measurements
Unit A B C D E F G H J K
006,
40"
20"
15"
20"
009
(1016)
(508)
(381)
012,
40"
20"
015
(1016)
018 46"
(1168)
024,
46"
030
(1168)
036,
50"
042
(1270)
048,
58"
060
(1473)
(508) 23"
(584) 23"
(584) 25"
(635) 33"
(838)
15" (381)
17" (432)
17" (432)
19" (483)
21" (533)
WSHP-SVX01E-EN 15
(508) 20"
(508) 23"
(584) 23"
(584) 25"
(635) 25"
(635)
15" (381)
15" (381)
18" (457)
18" (457)
20" (508)
28" (711)
6 7/8" (175)8"(203)
6 7/8"
9 7/8"
(175)
(251)
8 1/4"
9 3/4"
(210)
(248)
8 1/4"
11 3/8"
(210)
(289)
10 1/2"
13 1/2"
(267)
(343)
13 7/8"
13 7/8"
(352)
(352)
11 1/2"
4 1/4"
(292)
(108)
11 1/2"
4 1/4"
(292)
(108)
13 1/2"
4 3/4"
(343)
(121)
13 1/2"
4 3/4"
(343)
(121)
16 3/8" (416)4"(102)
18"
6 5/8"
(457)
(168)2"(51)1"(25.4)
L NPTIMNPTI N P Q R S
2 1/8"
1/2"
1/2"
38 3/4"
(54) 2 5/8"
(67) 2 7/8"
(73) 2 7/8"
(73) 1 3/4"
(45)
(12.7) 1/2"
(12.7) 3/4"
(19) 3/4"
(19) 3/4"
(19)
(12.7) 1/2"
(12.7) 3/4"
(19) 3/4"
(19) 3/4"
(19) 1"
(25.4)
(984) 38 3/4"
(984) 44 3/4"
(1137) 44 3/4"
(1137) 48 3/4"
(1238) 56 3/4"
(1441)
18 3/4" (476)
18 3/4" (476)
21 3/4" (552)
21 3/4" (552)
23 3/4" (603)
31 3/4" (806)
13 5/8" (346)
13 5/8" (346)
15 5/8" (397)
15 5/8" (397)
17 5/8" (448)
19 5/8" (498)
18 1/2" (470)
18 1/2" (470)
18 1/2" (470)
18 1/2" (470)
23 1/2" (597)
23 1/2" (597)
3 3/8" (86)
3 3/8" (86)
4 1/4" (108)
4 1/4" (108)
3 1/4" (83)
5 1/2" (140)
Dimensions
Figure 13. Right return/right supply
Table 8. Measurements
Unit A B C D E F G H J K
006,
40"
20"
15"
20"
009
(1016)
(508)
(381)
012,
40"
20"
015
(1016)
018 46"
(1168)
024,
46"
030
(1168)
036,
50"
042
(1270)
048,
58"
060
(1473)
(508) 23"
(584) 23"
(584) 25"
(635) 33"
(838)
15" (381)
17" (432)
17" (432)
19" (483)
21" (533)
16 WSHP-SVX01E-EN
(508) 20"
(508) 23"
(584) 23"
(584) 25"
(635) 25"
(635)
15" (381)
15" (381)
18" (457)
18" (457)
20" (508)
28" (711)
6 7/8" (175)8"(203)
6 7/8"
9 7/8"
(175)
(251)
8 1/4"
9 3/4"
(210)
(248)
8 1/4"
11 3/8"
(210)
(289)
10 1/2"
13 1/2"
(267)
(343)
13 7/8"
13 7/8"
(352)
(352)
11 1/2"
4 1/4"
(292)
(108)
11 1/2"
4 1/4"
(292)
(108)
13 1/2"
4 3/4"
(343)
(121)
13 1/2"
4 3/4"
(343)
(121)
16 3/8" (416)4"(102)
18"
6 5/8"
(457)
(168)2"(51)1"(25.4)
L NPTIMNPTI N P Q R S
2 1/8"
1/2"
1/2"
38 3/4"
(54) 2 5/8"
(67) 2 7/8"
(73) 2 7/8"
(73) 1 3/4"
(45)
(12.7) 1/2"
(12.7) 3/4"
(19) 3/4"
(19) 3/4"
(19)
(12.7) 1/2"
(12.7) 3/4"
(19) 3/4"
(19) 3/4"
(19) 1"
(25.4)
(984) 38 3/4"
(984) 44 3/4"
(1137) 44 3/4"
(1137) 48 3/4"
(1238) 56 3/4"
(1441)
18 3/4" (476)
18 3/4" (476)
21 3/4" (552)
21 3/4" (552)
23 3/4" (603)
31 3/4" (806)
13 5/8" (346)
13 5/8" (346)
15 5/8" (397)
15 5/8" (397)
17 5/8" (448)
19 5/8" (498)
18 1/2" (470)
18 1/2" (470)
18 1/2" (470)
18 1/2" (470)
23 1/2" (597)
23 1/2" (597)
3 3/8" (86)
3 3/8" (86)
4 1/4" (108)
4 1/4" (108)
3 1/4" (83)
5 1/2" (140)
Dimensions
Figure 14. Left return/top supply
Table 9. Measurements
Unit GEV A B C D E F G H J K L M N
006-
19 1/2"
31 1/4"
015
(495)
018, 024, 21 1/2"
(546)
030, 040
036,
24 1/2"
042
(622)
Std-
26 1/2"
048
(673)
Hi-
26 1/2"
048,
(673)
060
(794)
39 1/4" (997)
41 7/8" (1064)
46 7/8" (1191)
46 7/8" (1191)
21 1/2" (546)
21 1/2" (546)
26 1/2" (673)
30 1/2" (775)
30 1/2" (775)
WSHP-SVX01E-EN 17
11 1/2" (292)4"(102)
13 1/2" (343)4"(102)4"(1021)
18" (457)
18" (457)
18" (457)
3 1/4" (83)
4 1/4" (108)2"(51)
4 1/4" (108)2"(51)
3 3/4" (95)
1 7/8" (48)
16 1/2" (419)
17 1/2" (445)
19 1/2" (495)
21 1/2" (546)
21 1/2" (546)
15" (381)
23 3/4" (603)
19" (483)
29" (737)
29" (737)
18" (457)
17" (432)
23" (584)
27" (686)
27" (686)
6 7/8" (175)8"(203)
8 1/4" (368)
10 1/2" (267)
13 7/8" (352)
13 1/8" (333)
9 3/4" (248) 3/4"
11 3/8" (289)
13 1/2" (343)
13 7/8" (352)
11 3/8" (289)
3/4" (19)2"(51)
(19)2"(51)
1 3/4" (19)
2 1/4" (57)
2 1/4" (57)
03/4"
3 1/2" (89)1"(25.4)1"(25.4
3 1/2" (89)1"(25.4)1"(25.4
W.I. NPTI
1/2" (12.7)
3/4" (19)
(19)
W.O. NPTI
1/2" (12.7 )
3/4" (19)
3/4" (19)
)
)
Drain FPT
3/4" (19)
3/4" (19)
3/4" (19)
3/4" (19)
3/4" (19)
Dimensions
Figure 15. Left return/back supply
Table 10. Measurements
Unit GEV A B C D E F G H J K L M N
006-
19 1/2" (495)
21 1/2" (546)
24 1/2" (622)
26 1/2" (673)
26 1/2" (673)
31 1/4" (794)
39 1/4" (997)
41 7/8" (1064)
46 7/8" (1191)
46 7/8" (1191)
015
018, 024, 030, 040
036, 042
Std­048
Hi­048, 060
18 WSHP-SVX01E-EN
21 1/2" (546)
21 1/2" (546)
26 1/2" (673)
30 1/2" (775)
30 1/2" (775)
11 1/2" (292)4"(102)
13 1/2" (343)4"(102)4"(1021)
18" (457)
18" (457)
18" (457)
3 1/4" (83)
4 1/4" (108)2"(51)
4 1/4" (108)2"(51)
3 3/4" (95)
1 7/8" (48)
16 1/2" (419)
17 1/2" (445)
19 1/2" (495)
21 1/2" (546)
21 1/2" (546)
15" (381)
23 3/4" (603)
19" (483)
29" (737)
29" (737)
18" (457)
17" (432)
23" (584)
27" (686)
27" (686)
6 7/8" (175)8"(203)
8 1/4" (368)
10 1/2" (267)
13 7/8" (352)
13 1/8" (333)
9 3/4" (248) 3/4"
11 3/8" (289)
13 1/2" (343)
13 7/8" (352)
11 3/8" (289)
3/4" (19)2"(51)
(19)2"(51)
1 3/4" (19)
2 1/4" (57)
2 1/4" (57)
03/4"
3 1/2" (89)1"(25.4)1"(25.4
3 1/2" (89)1"(25.4)1"(25.4
W.I. NPTI
1/2" (12.7)
3/4" (19)
(19)
W.O. NPTI
1/2" (12.7 )
3/4" (19)
3/4" (19)
)
)
Drain FPT
3/4" (19)
3/4" (19)
3/4" (19)
3/4" (19)
3/4" (19)
Dimensions
Figure 16. Right return/top supply
Table 11. Measurements
Unit GEV A B C D E F G H J K L M N
006-
19 1/2"
31 1/4"
015 018,
024, 030, 040
036, 042
Std­048
Hi­048, 060
(495)
21 1/2" (546)
24 1/2" (622)
26 1/2" (673)
26 1/2" (673)
(794)
39 1/4" (997)
41 7/8" (1064)
46 7/8" (1191)
46 7/8" (1191)
21 1/2" (546)
21 1/2" (546)
26 1/2" (673)
30 1/2" (775)
30 1/2" (775)
WSHP-SVX01E-EN 19
11 1/2" (292)4"(102)
13 1/2" (343)4"(102)4"(1021)
18" (457)
18" (457)
18" (457)
3 1/4" (83)
4 1/4" (108)2"(51)
4 1/4" (108)2"(51)
3 3/4" (95)
1 7/8" (48)
16 1/2" (419)
17 1/2" (445)
19 1/2" (495)
21 1/2" (546)
21 1/2" (546)
15" (381)
23 3/4" (603)
19" (483)
29" (737)
29" (737)
18" (457)
17" (432)
23" (584)
27" (686)
27" (686)
6 7/8" (175)8"(203)
8 1/4" (368)
10 1/2" (267)
13 7/8" (352)
13 1/8" (333)
9 3/4" (248) 3/4"
11 3/8" (289)
13 1/2" (343)
13 7/8" (352)
11 3/8" (289)
3/4" (19)2"(51)
(19)2"(51)
1 3/4" (19)
2 1/4" (57)
2 1/4" (57)
03/4"
3 1/2" (89)1"(25.4)1"(25.4)
3 1/2" (89)1"(25.4)1"(25.4)
W.I. NPTI
1/2" (12.7)
3/4" (19)
(19)
W.O. NPTI
1/2" (12.7)
3/4" (19)
3/4" (19)
Drain FPT
3/4" (19)
3/4" (19)
3/4" (19)
3/4" (19)
3/4" (19)
Dimensions
Figure 17. Right return/back supply
Table 12. Measurements
Unit GEV A B C D E F G H J K L M N
006-
19 1/2" (495)
21 1/2" (546)
24 1/2" (622)
26 1/2" (673)
26 1/2" (673)
31 1/4" (794)
39 1/4" (997)
41 7/8" (1064)
46 7/8" (1191)
46 7/8" (1191)
015 018,
024, 030, 040
036, 042
Std­048
Hi­048, 060
20 WSHP-SVX01E-EN
21 1/2" (546)
21 1/2" (546)
26 1/2" (673)
30 1/2" (775)
30 1/2" (775)
11 1/2" (292)4"(102)
13 1/2" (343)4"(102)4"(1021)
18" (457)
18" (457)
18" (457)
3 1/4" (83)
4 1/4" (108)2"(51)
4 1/4" (108)2"(51)
3 3/4" (95)
1 7/8" (48)
16 1/2" (419)
17 1/2" (445)
19 1/2" (495)
21 1/2" (546)
21 1/2" (546)
15" (381)
23 3/4" (603)
19" (483)
29" (737)
29" (737)
18" (457)
17" (432)
23" (584)
27" (686)
27" (686)
6 7/8" (175)8"(203)
8 1/4" (368)
10 1/2" (267)
13 7/8" (352)
13 1/8" (333)
9 3/4" (248) 3/4"
11 3/8" (289)
13 1/2" (343)
13 7/8" (352)
11 3/8" (289)
3/4" (19)2"(51)
(19)2"(51)
1 3/4" (19)
2 1/4" (57)
2 1/4" (57)
03/4"
3 1/2" (89)1"(25.4)1"(25.4)
3 1/2" (89)1"(25.4)1"(25.4)
W.I. NPTI
1/2" (12.7)
3/4" (19)
(19)
W.O. NPTI
1/2" (12.7)
3/4" (19)
3/4" (19)
Drain FPT
3/4" (19)
3/4" (19)
3/4" (19)
3/4" (19)
3/4" (19)
Dimensions
Figure 18. GEH 072-120 (60Hz) GEH 072-090 (50 Hz) GEH-right return/left supply
Table 13. Measurements
GEH 60 Hz
072 - 36 1/4"
090 072 36 1/8"
120 090 36 1/8"
WSHP-SVX01E-EN 21
GEH 50 Hz A B C D
(921)
(917)
(917)
15 5/8" (397)
12 3/4" (324)
13" (330)
6 5/8" (168)
6 3/4" (171)
7 1/4" (184)
1 1/4" (32)
1 1/4" (32)
1 1/2" (38)
Dimensions
Figure 19. GEH 072-120 (60Hz) GEH 072-090 (50Hz) GEH-right return/back supply
Table 14. Measurements
GEH 60 Hz
072 - 36 1/4"
090 072 36 1/8"
120 090 36 1/8"
22 WSHP-SVX01E-EN
GEH 50 Hz A B C D
(921)
(917)
(917)
15 5/8" (397)
12 3/4" (324)
13" (330)
6 5/8" (168)
6 3/4" (171)
7 1/4" (184)
1 1/4" (32)
1 1/4" (32)
1 1/2" (38)
Dimensions
Figure 20. GEH 072-120 (60Hz) GEH 072-090 (50Hz) GEH- left return/right supply
Table 15. Measurements
GEH 60 Hz
072 - 36 1/8"
090 072 36 1/8"
120 090 36 1/8"
WSHP-SVX01E-EN 23
GEH 50 Hz A B C D
(917)
(917)
(917)
17" (432)8"(203)
13 3/4" (349)
13" (330)
7 3/4" (197)
7 1/4" (184)
1 1/4" (32)
1 1/4" (32)
1 1/2" (38)
Dimensions
Figure 21. GEH 072-120 (60Hz) GEH 072-090 (50Hz) GEH- left return/back supply
Table 16.
GEH 60 Hz
072 - 36 1/8"
090 072 36 1/8"
120 090 36 1/8"
24 WSHP-SVX01E-EN
GEH 50 Hz A B C D
(917)
(917)
(917)
17" (432)8"(203)
13 3/4" (349)
13" (330)
7 3/4" (197)
7 1/4" (184)
1 1/4" (32)
1 1/4" (32)
1 1/2" (38)
Dimensions
Figure 22. GEH 150-180 (60Hz) GEH 120-150 (50Hz) GEH- right return/left supply
WSHP-SVX01E-EN 25
Dimensions
Figure 23. GEH 150-180 (60Hz) GEH 120-150 (50Hz) GEH- right return/back supply
26 WSHP-SVX01E-EN
Dimensions
Figure 24. GEH 150-180 (60Hz) GEH 120-150 (50Hz) GEH- left return/right supply
WSHP-SVX01E-EN 27
Dimensions
Figure 25. GEH 150-180 (60Hz) GEH 120-150 (50Hz) GEH- left return/back supply
28 WSHP-SVX01E-EN
Dimensions
Figure 26. 6 - 10 ton (60Hz) 6 and 7 1/2 ton (50Hz) - front return/back supply
Table 17. Measurements
Unit Size A B C
6 Ton 6 5/8"
7.5 Ton 6 5/8"
10 Ton 6 1/2"
(168)
(168)
(165)
WSHP-SVX01E-EN 29
18 3/8" (467)
18 3/8" (403)
18 1/2" (470)
1 1/4"
1 1/4"
1 1/2"
Loading...
+ 67 hidden pages