Trane TUC1B040A9241A, TUC1B060A9361A, TUC1B080A9421A, TUC1C100A9481A, TUC1D100A9601A Installer's Manual

...
11118888----C
CDDDD11119999DDDD5555----22225555
CC
Installer’s Guide
Upflow/ Horizontal and Downflow/ Horizontal Gas-Fired Condensing Furnaces
*UC1B040A9241A *UC1B060A9361A *UC1B080A9421A *UC1C100A9481A
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit.
Please return to service information pack upon completion of work.
*UC1
*UC1D100A9601A *UC1D120A9601A *DC1B040A9241A *DC1B060A9361A
*DC1B080A9421A *DC1C100A9481A *DC1D120A9601A
*DC1
DOWNFLOW
UPFLOW/ HORIZONTAL
UPFLOW
DOWNFLOW/ HORIZONTAL
A341624P01
Installer’s Guide
SAFETY SECTION
The following safety practices and precautions must be followed during the installation, servicing, and opera­tion of this furnace.
1. Use only with the type of gas approved for this fur­nace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position as specified in “Location and Clearances” (page 4), of these instructions.
3. Provide adequate combustion and ventilation air to the furnace space as specified in “Air for Combus­tion and Ventilation” (pages 8-9), of these instruc­tions.
4. Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in the “Venting” section (pages 16-
26), of these instructions.
5. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifi­cally for the detection of leaks to check all connec­tions, as specified in “Gas Piping” (page 32), of these instructions.
6. Always install the furnace to operate within the furnace’s intended temperature-rise range with a duct system which has an external static pressure within the allowable range, as specified on the unit rating plate. Airflow with temperature rise for cfm versus static is shown in the Service Facts accom­panying this furnace.
7. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the fur­nace casing and terminating outside the space con­taining the furnace.
8. A gas-fired furnace for installation in a residential garage must be installed as specified in “Location and Clearances” section (page 4), of these instruc­tions.
9. The furnace may be used for temporary heating of buildings or structures under construction only when the following conditions have been met: a. The furnace venting system must be complete
and installed per manufacturers instructions.
b. The furnace is controlled only by a room ther-
mostat (no field jumpers).
c. The furnace return air duct must be complete
and sealed to the furnace and clean air filters are in place.
d. The furnace input rate and temperature rise
must be verified to be within nameplate mark­ing.
e. 100% of the furnace combustion air require-
ment must come from outside the structure.
f. The furnace return air temperature range is
between 55 and 80 degrees Fahrenheit.
g. Clean the furnace, duct work, and components
upon substantial completion of the construction process, and verify furnace operating conditions including ignition, input rate, temperature rise and venting, according to the manufacturer's instructions.
10. This product must be gas piped by a Licensed Plumber or Gas Fitter in the Commonwealth of Mas­sachusetts.
Safety signal words are used to designate a degree or level of seriousness associated with a particular hazard. The signal words for safety markings are DANGER, WARNING, and CAUTION.
a. DANGER indicates an imminently hazardous situa-
tion which, if not avoided, will result in death or seri­ous injury. This signal word is limited to the most ex­treme situations.
b. WARNING indicates a potentially hazardous situation
which, if not avoided, could result in death or serious injury.
c. CAUTION indicates a potentially hazardous situation
which, if not avoided, may result in minor or moder­ate injury. It is also used to alert against unsafe prac­tices and hazards involving only property damage.
!
WARNING
CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each appli­ance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death. The following steps shall be followed for each appliance connected to the venting system being placed into op­eration, while all other appliances connected to the vent­ing system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and hori­zontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/ NFPA 54 or the CAN/ CGA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, cor­rosion and other deficiencies which could cause an unsafe condition.
3. As far as practical, close all building doors and win­dows and all doors between the space in which the appliance(s) connected to the venting system are lo­cated and other deficiencies which could cause an unsafe condition.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not con­nected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not op­erate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermo­stat so appliance is operating continuously.
© 2009 Trane All Rights Reserved 18-CD19D5-25
Installer’s Guide
7. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z221.1/ NFPA 54 and/ or CAN/ CGA B149 In­stallation Codes.
8. After it has been determined that each appliance connected to the venting system properly vents where tested as outlined above, return doors, win­dows, exhaust fans, fireplace dampers and any other gas-fired burning appliance to their previous conditions of use.
!
WARNING
FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could re­sult in serious injury, death or property damage. Improper servicing could result in dangerous opera­tion, serious injury, death, or property damage.
GENERAL INSTALLATION INSTRUCTIONS
The manufacturer assumes no responsibility for equip­ment installed in violation of any code or regulation. It is recommended that Manual J of the Air Condition­ing Contractors Association (ACCA) or A.R.I. 230 be fol­lowed in estimating heating requirements. When esti­mating heating requirements for installation at alti­tudes above 2000 ft., remember the gas input may need to be reduced (See High Altitude Installation).
Material in this shipment has been inspected at the factory and released to the transportation agency without known damage. Inspect exterior of carton for evidence of rough handling in ship­ment. Unpack carefully after moving equipment to approximate location. If damage to contents is found, report the damage immediately to the de­livering agency.
Codes and local utility requirements governing the installation of gas fired equipment, wiring, plumbing, and flue connections must be adhered to. In the ab­sence of local codes, the installation must conform with latest edition of the National Fuel Gas Code ANSI Z223.1 • National Installation Code, CAN/CGA B149.1. The latest code may be obtained from the American Gas Association Laboratories, 400 N. Capitol St. NW, Washington D.C. 20001. 1-800-699-9277 or www.aga.org These furnaces have been classified as CATEGORY IV furnaces in accordance with latest edition of ANSI Z21.47 • CAN/ CGA 2.3 standards. Category IV furnaces operate with positive vent static pressure and with a flue loss less than 17 percent. These conditions require special venting systems, which must be gas tight and water tight. These Category IV Direct Vent furnaces are approved for installation in Manufactured/ Mobile housing when used with BAYMFGH100A.
Contents
INSTALLATION INSTRUCTIONS
General Installation Instructions 3 Location and Clearances 4 Outline Drawings 5 Upflow Installation 7 Downflow Installation 7 Horizontal Installation 7 Air For Combustion and Ventilation 8 Duct Connections 10 Return Air Filters 11 General Venting Instructions 16 Venting Material 16 Venting Tables 18 Horizontal Venting 21 Venting Through The Wall 21 Venting Through The Roof 25 Downward Venting 25 Venting Through a Masonry Chimney 26 Condensate Drain Instructions 27 Electrical Connections 29 Field Wiring Diagrams 29 Gas Piping 32 Combustion Input Checks 33
Start Up and Adjustment 35
Preliminary Inspections 35 Lighting Instructions 36 Sequence Of Operation 36 Control And Safety Switch Adjustments 36 Airflow Adjustment 37
Abnormal Conditions 37
IFC Error Flash Code 39
!
CAUTION
To prevent shortening its service life, the furnace
should not be used as a “Construction Heater” during the finishing phases of construction until the require­ments listed in item 9, a-g of the safety section of this publication have been met. Condensate in the pres­ence of chlorides and fluorides from paint, varnish, stains, adhesives, cleaning compounds, and cement create a corrosive condition which may cause rapid de­terioration of the heat exchanger.
!
CAUTION
Do NOT install the furnace in a corrosive or contami­nated atmosphere.
18-CD19D5-25 3
Installer’s Guide
LOCATION AND CLEARANCES
The location of the furnace is normally selected by the architect, the builder, or the installer. However, before the furnace is moved into place, be sure to consider the following requirements:
1. Is the location selected as near the vent and as cen­tralized for heat distribution as practical?
2. Do all clearances between the furnace and enclo­sure equal or exceed the minimums shown in the Table 1.
3. Is there sufficient space for servicing the furnace and other equipment? A minimum of 24 inches front accessibility to the furnace must be provided. Any access door or panel must permit removal of the largest component.
4. Are there at least 3 inches of clearance between the furnace front panel and any closed panel or door provided?
5. Are the vent pipe and combustion air inlet pipe within vent table lengths? Will the pipes remain un­obstructed?
6. Allow sufficient height in supply plenum above or below the furnace to provide for cooling coil installa­tion if the cooling coil is not installed at the time of this furnace installation.
7. A furnace shall be installed so electrical components are protected from water.
8. If the furnace is installed in a residential garage, it must be installed so that the burners and the ig­nition source are located not less than 18 inches (46 cm) above the floor and the furnace must be located or protected to avoid physical damage from ve­hicles.
IMPORTANT:
The furnace must be installed level. The only allowable variation would be slightly to the left and/or forward in up­flow installations or slightly toward the front in horizontal in­stallations. This is necessary for proper condensate drain­age.
4 18-CD19D5-25
18-CD19D5-25 5
Installer’s Guide
*UC1 OUTLINE DRAWING
(ALL DIMENSIONS ARE IN INCHES)
6 18-CD19D5-25
Installer’s Guide
*DC1 DOWNFLOW/ HORIZONTAL OUTLINE DRAWING
(ALL DIMENSIONS ARE IN INCHES)
Installer’s Guide
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
UPFLOW INSTALLATION
Standoffs and screws (See Figure 1) are included with the cased coils for attachment to the furnace. There are clearance alignment holes near the bottom of the coil wrapper. Drill screws are used to engage the furnace top flanges. The standoff is inserted into the cabinet alignment hole. The drill screws are inserted through the standoffs then screwed into the furnace flange. The coil is always placed downstream of the furnace air­flow.
1
CASED
UPFLOW
FURNACE
STANDOFFS (4)
COIL
STANDOFFS
(BOTH SIDES)
DRILL SCREWS (4)
FOR VERTICAL
INSTALLATIONS:
SCREWS
(BOTH SIDES)
TABLE 1
CABINET
WIDTH
RETURN
DUCT WIDTH
17-1/2" 16-1/4" 16-5/8" 20-1/8" 15-5/8" 19-3/8"
21" 19-3/4" 20-1/8" 20-1/8" 19-1/8" 19-3/8"
24-1/2" 23-1/4" 23-5/8" 20-1/8" 22-5/8" 19-3/8"
FLOOR OPENING PLENUM OPENING
"A" "B" "C" "D"
HORIZONTAL INSTALLATION
The coil and furnace must be fully supported when used in the horizontal position. It is always recommended that an auxiliary drain pan be installed under a horizon­tally installed evaporator coil or 90% gas furnace. Con­nect the auxiliary drain line to a separate drain line (no trap is needed in this line). Three brackets (with screws) are included with down­flow furnaces for installation to stabilize and secure the furnace and 2/4TXC cased coil in the horizontal posi- tion. See Figure 3.
IMPORTANT: The 2/4TXC cased coil must be placed downstream of the furnace. In horizontal installations, the apex of the coil may point either toward or away from the furnace. See
the 2/4TXC coil Installer's Guide for more details.
4
CASED COIL CONNECTION
BRACKET FOR DOWNFLOW
FURNACE IN HORIZONTAL
DOWNFLOW ONLY
DOWNFLOW INSTALLATIONS
!
WARNING
Do NOT install the furnace directly on carpeting, tile or other combustible material other than wood flooring. For vertical downflow application, subbase (BAYBASE-
205) must be used between the furnace and combus­tible flooring. When the downflow furnace is installed vertically with a cased coil, a subbase is not required.
Required floor opening:
2
SUBBASE CROSS SECTION
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
3
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
FURNACE
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
FRONT
18-CD19D5-25 7
A (width)
B (depth)
The cased coil is secured to the furnace and both the furnace and the cased coil must be properly supported. The brackets mount using the rear screws on the coil case and use the screws provided to secure the bracket to the furnace. The remaining bracket is placed as close to center as possible (horizontally) between the coil case front and the furnace bottom channel (for downflow/ horizontal furnace). Use four of the screws provided to secure the bracket. The upflow furnace, converted to horizontal, aligns and attaches the TXC coil as in Fig­ure 1. However, the coil requires additional support. The furnace may be installed in an attic or crawl space in the horizontal position by placing the furnace on the left side (as viewed from the front in the vertical posi­tion). The horizontal furnace installation in an attic should be on a service platform large enough to allow for proper clearances on all sides and service access to the front of the furnace (See Figure 5 & Clearance Table). Line contact is only permissible between lines formed by intersections of the top and two sides of the furnace casing and building joists, studs, or framing.
D
C
The furnace may be placed horizontally in a crawl space on a pad or other noncombustible material which will raise the unit for sufficient protection from moisture.
Installer’s Guide
5
UPFLOW/ HORIZONTAL SHOWN
The furnace must be supported at both ends and the middle when installed horizontally. The furnace must also be elevated a minimum of 6 inches to allow clearance for the condensate drain to exit the cabinet in the horizontal position.
The horizontal furnace may also be suspended from the joists using 3/8" all-thread rods with pieces of angle iron underneath the furnace to form a hanging rack at both ends and the midpoint. The rods need to be of sufficient length to allow for proper clearances from combustible materials. The angle iron needs to be at least 32" in length to allow for access to service panels.
AIR FOR COMBUSTION AND VENTILATION
If these furnaces are installed in a nondirect vent capacity
then the adequate flow of combustion and ventilating air must not be obstructed from reaching the furnace. Air openings provided for combustion air must be kept free of obstructions which restrict the flow of air. Air­flow restrictions affect the efficiency and safe operation of the furnace. Keep this in mind should you choose to remodel or change the area which contains your fur­nace. Furnaces must have a free flow of air for proper performance.
6
50 CU. FT. OR MORE PER 1000 BTU/ HR. INPUT ALL EQUIP. INSTALLED
UNCONFINED
Provisions for combustion and ventilation air shall be made in accordance with latest edition of Section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1 — CAN/ CGA B149.1 or ap­plicable provisions of the local building codes. Special conditions created by mechanical exhausting of air and fireplaces must be considered to avoid unsatisfactory furnace operation.
OUTSIDE AIR IS RECOMMENDED
The use of indoor air for most applications is acceptable, unless there is the presence of corrosive chemicals
or contamination. Certain types of installation will require the use of outside air for combustion.
The following types of installations will require use of OUTDOOR AIR for combustion, due to chemical expo­sures: * Commercial buildings * Buildings with indoor pools * Furnaces installed in “confined” laundry rooms * Furnaces installed in “confined” hobby or craft rooms * Furnaces installed near chemical storage areas. Exposure to the following substances in the combustion air supply will also require OUTDOOR AIR for combus­tion: * Permanent wave solutions * Chlorinated waxes and cleaners * Chlorine based swimming pool chemicals * Water softening chemicals * Deicing salts or chemicals * Carbon Tetrachloride * Halogen type refrigerants * Cleaning solvents (such as perchloroethylene) * Printing inks, paint removers, varnish, etc. * Hydrochloric acid * Cements and glues * Antistatic fabric softeners for clothes dryers * Masonry acid washing materials Furnace locations may be in a “confined space” or anunconfined space”. Unconfined space is defined in Figure 6. These spaces may have adequate air by infiltration to provide air for combustion and ventilation. Buildings with tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.), may need addi­tional air to be provided as described for confined space. Confined spaces are installations with less than 50 cu. ft. of space per 1000 BTU/hr input from all equipment installed. Air for combustion and ventilation require­ments can be supplied from inside the building as in Figure 8 or from the outdoors, as in Figure 9.
8 18-CD19D5-25
Installer’s Guide
TABLE 2
MINIMUM AREA IN SQUARE FEET
FOR UNCONFINED SPACE INSTALLATIONS
FURNACE
MAXIMUM BTUH
INPUT RATING
60,000
80,000 100,000 120,000
MINIMUM AREA IN SQUARE FEET
WITH 8 FT. CEILING
OF UNCONFINED SPACE
375 500 625 875
7
CONFINED
SPACE
1. All air from inside the building as in Figure 8: The confined space shall be provided with two perma­nent openings communicating directly with an addi­tional room(s) of sufficient volume so that the com­bined volume of all spaces meets the criteria for an unconfined space. The total input of all gas utiliza­tion equipment installed in the combined space shall be considered in making this determination. Refer to Table 2 for minimum open areas require­ments.
2.
All air from outdoors as in Figure 9: The confined space shall be provided with two permanent open­ings, one commencing within 12 inches of the top and one commencing within 12 inches of the bot­tom of the enclosure. The openings shall communi­cate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. Refer to Table 3, for minimum open areas requirements.
TABLE 3
MINIMUM FREE AREA IN SQUARE INCHES
EACH OPENING (FURNACE ONLY)
8
9
Furnace
Maximum
BTUH/INPUT
Rating
60,000
80,000 100,000 120,000
18-CD19D5-25 9
Air
From
Inside
100 100 100 120
Vertical
Duct
Air From Outside
Horizontal
15 20 25 30
Duct
30 40 50 60
Installer’s Guide
DUCT CONNECTIONS
Air duct systems should be installed in accordance with standards for air conditioning systems, National Fire Protection Association Pamphlet No.90. They should be sized in accordance with ACCA Manual D or whichever is applicable. Central furnaces, when used in connection with cooling units, shall be installed in parallel or on the upstream side of the cooling coil to avoid condensation in the heat exchanger. With a parallel flow arrangement, the damp­ers or other means used to control flow of air shall be adequate to prevent chilled air from entering the fur­nace, and if manually operated, must be equipped with means to prevent operation of either unit unless the damper is in full heat or cool position. On any job, flexible connections of nonflammable mate­rial may be used for return air and discharge connections to prevent transmission of vibration. Though these units have been specifically designed for quiet, vibration free operation, air ducts can act as sounding boards and could, if poorly installed, amplify the slightest vibration to the annoyance level. When the furnace is located in a utility room adjacent to the living area, the system should be carefully de­signed with returns to minimize noise transmission through the return air grille. Although these furnaces are designed with large blowers operating at moderate speeds, any blower moving a high volume of air will produce audible noise which could be objectionable when the unit is located very close to a living area. It is often advisable to route the return air ducts under the floor or through the attic. Such design permits the in­stallation of air return remote from the living area (i.e. central hall). When the furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace and termi­nating outside the space containing the furnace.
RETURN AIR DUCT CONNECTION
NOTE: On upflow 5 or 6 ton airflow models where the airflow requirement exceeds 1800 CFM - Models will require return air openings and filters on: (1) both sides; or (2) one side and the bottom; or (3) just the bottom.
All return air duct systems should provide for installa­tion of return air filters.
1. Determine the appropriate position to set the furnace in order to connect to the existing supply and return ductwork.
2. For side return installations on upflow models, remove the insulation around the opening in the blower compartment.
10 18-CD19D5-25
3. The side panels on upflow furnaces include locating notches which may be used as guides for cutting an opening for return air. Refer to Figure 11 and the outline drawing on page 5 for duct connection dimensions for various furnaces.
4. If a 3/4" flange is to be used for attaching the air inlet duct, add to cut where indicated by dashed lines in Figure 11. Cut corners diagonally and bend outward to form flange.
5. If flanges are not required, and a filter frame is installed, cut along knockout guidelines.
6. Upflow Furnaces: Use the optional filter rack on either side or on the bottom if the filter is to be used within the furnace cabinet.
When the upflow furnace is installed in the horizon­tal right or left application and a return duct is attached to the top side as shown in Figure 10, install the filter in a remote location.
!
WARNING
Do not install the filter in the return duct directly above the furnace in horizontal applications. Install the filter remotely. Installing the filter directly above the furnace in horizontal applications may cause property damage, serious injury or death.
!
WARNING
TO PREVENT INJURY OR DEATH DUE TO CONTACT WITH MOVING PARTS, TURN THE POWER TO THE FURNACE OFF BEFORE SERVICING FILTERS.
Do not install the filter in the return duct directly above the furnace in horizontal applications.
When the upflow furnace is installed in the horizon­tal right or left application and a close coupled (less than 36") return duct is attached to the bottom side of the furnace as shown in Figure 10, securely attach a 1/2" mesh metal hardware cloth protective e screen to the inside bottom of the filter grill to
prevent personal injury from contacting moving parts when reaching into the return opening to replace the filter.
Close coupled (less than 36") return (filter directly beneath bottom side return) is not recommended due to noise considerations.
Downflow Furnaces: Brackets are factory supplied to mount filters in the return air duct work.
7. Connect the duct work to the furnace. See Outline Drawing (pages 5&6) for supply and return duct size and location. Flexible duct connectors are recom­mended to connect both supply and return air ducts to the furnace.
Installer’s Guide
REMOVE FILTER FROM UPFLOW FURNACE WHEN RETURN DUCT IS ATTACHED TO FURNACE TOP SIDE (HORIZONTAL LEFT OR RIGHT APPLICATIONS) AS SHOWN.
Close coupled (less than 36") return (filter directly beneath bottom side return) not recommended due to noise considerations. If used, securely attach 1/2" mesh metal hardware cloth protective screen to the inside bottom of filter grill.
If only the front of the furnace is accessible, it is recommended that both supply and return air plenums are removable.
8. When replacing a furnace, old duct work should be cleaned out. Thin cloths should be placed over the registers and the furnace fan should be run for 10 minutes. Don’t forget to remove the cloths before you start the furnace.
FILTER
0
RETURN AIR FILTERS
(Filter and filter rack are not supplied with unit)
TYPICAL UPFLOW RETURN AIR FILTER INSTALLA­TIONS
These furnaces require high velocity type air filters. The optional filters may be located within the furnace blower compartment for UPFLOW furnaces in either a BOTTOM or SIDE (left side or right side) return air inlet. Some optional filters may need to be trimmed for side or bottom filter use.
The furnace and the blower filter rack installation can be seen in Figure 12 & 13.
The optional furnace filter in the bottom or side con­figuration can be removed by simply turning the two latches on the blower door and tilting the door forward.
The filter rails are spring loaded for automatic adjust­ment to allow standard size, locally obtainable replace­ment filters. The filter rack itself slides to adjust to the required width needed for bottom or side return.
TABLE 4
MODELS
NUMBERS
*UC1B040A9241A *UC1B060A9361A *UC1B080A9421A
*UC1C100A9481A 21" 1 - 20" X 25" X 1"
*UC1D100A9601A## *UC1D120A9601A##
*DC1B040A9241A *DC1B060A9361A *DC1B080A9421A
*DC1C100A9481A 21" 2 - 16" X 20" X 1"
*DC1D120A9601A 24-1/2" 2 - 16" X 20" X 1"
## - Requires filters on 2 sides OR 1 side and bottom filter or just the bottom
CABINET
WIDTH
17-1/2" 1 - 17" X 25" X 1"
24-1/2" 1 - 24" X 25" X 1"
17-1/2" 2 - 14" X 20" X 1"
FILTER
QTY & SIZE
NOTE:
On upflow 5 or 6 ton airflow models where the airflow requirement exceeds 1800 CFM - Models will require return air openings and filters on: (1) both sides; or (2) one side and the bottom; or (3) just the bottom.
q
LOCATING NOTCHES PROVIDED FOR SIDE RETURN CUTOUT
*
*
*
*
SEE OUTLINE DRAWING
*
18-CD19D5-25 11
CUT OUT
FOR
SIDE
FILTER
FRONT
of Furnace
Installer’s Guide
w
Airflow
NOTE: The narrow 14.5" width furnace cabinet prevents use of the filter rack for right side return. Pre-drill clearance holes and then attach filter clips with the screws provided. The filter clip with the leaf spring mounts in the rear of the cabinet
OPTIONAL FILTER RACK INSTALLATION FOR BOTTOM RETURN
With the filter removed, the filter rack is compressed and then inserted into the bottom of the furnace. The retaining screw/pin on each side inserts into engagement holes at the bottom of the furnace cabinet side. See Figures 13, 14 & 16.
NOTE: Remove the bottom front channel to install the filter rack in the 14-1/2" width cabinet furnaces.
t
e
r
Airflow
BOTTOM FILTER RACK INSTALLATION
Blower Deck Engagement
Hole
ENGAGEMENT
HOLE DETAIL
(Typical both sides and blower deck)
y
Furnace
Cabinet
Side
VIEW
Filter Rack
Optional Filter Rack Accessory Kit
BAYRACK960A
12 18-CD19D5-25
Engagement Hole For
Filter Rack Installation With Bottom Return
Filter Rack Retaining Screw/Pin
Loading...
+ 28 hidden pages