Trane Ascend ACR Series Installation, Operation And Maintenance Manual

SSAAFFEETTYY WWAARRNNIINNGG
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
March 2019
AACC--SSVVXX000011AA--EENN
With AdaptiSpeed™ Technology Quiet operation enabled by InvisiSound™ Technology 150 to 300 Nominal Tons
Installation, Operation, and Maintenance
©2019 Ingersoll Rand
AC-SVX001A-EN
Introduction
Read this manual thoroughly before operating or servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAU
TION
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
NOTICE
Indicates a situation that could result in equipment or property-damage only accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs and HCFCs such as saturated or unsaturated HFCs and HCFCs.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section
608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WWAARRNNIINNGG
PPrrooppeerr FFiieelldd WWiirriinngg aanndd GGrroouunnddiinngg RReeqquuiirreedd!!
FFaaiilluurree ttoo ffoollllooww ccooddee ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy.. AAllll ffiieelldd wwiirriinngg MMUUSSTT bbee ppeerrffoorrmmeedd bbyy qquuaalliiffiieedd ppeerrssoonnnneell.. IImmpprrooppeerrllyy iinnssttaalllleedd aanndd ggrroouunnddeedd ffiieelldd wwiirriinngg ppoosseess FFIIRREE aanndd EELLEECCTTRROOCCUUTTIIOONN hhaazzaarrddss.. TToo aavvooiidd tthheessee hhaazzaarrddss,, yyoouu MMUUSSTT ffoollllooww rreeqquuiirreemmeennttss ffoorr ffiieelldd wwiirriinngg iinnssttaallllaattiioonn aanndd ggrroouunnddiinngg aass ddeessccrriibbeedd iinn NNEECC aanndd yyoouurr llooccaall// ssttaattee//nnaattiioonnaall eelleeccttrriiccaall ccooddeess..
WWAARRNNIINNGG
PPeerrssoonnaall PPrrootteeccttiivvee EEqquuiippmmeenntt ((PPPPEE)) RReeqquuiirreedd!!
FFaaiilluurree ttoo wweeaarr pprrooppeerr PPPPEE ffoorr tthhee jjoobb bbeeiinngg uunnddeerrttaakkeenn ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy.. TTeecchhnniicciiaannss,, iinn oorrddeerr ttoo pprrootteecctt tthheemmsseellvveess ffrroomm ppootteennttiiaall eelleeccttrriiccaall,, mmeecchhaanniiccaall,, aanndd cchheemmiiccaall hhaazzaarrddss,, MMUUSSTT ffoollllooww pprreeccaauuttiioonnss iinn tthhiiss mmaannuuaall aanndd oonn tthhee ttaaggss,, ssttiicckkeerrss,, aanndd llaabbeellss,, aass wweellll aass tthhee iinnssttrruuccttiioonnss bbeellooww::
•• BBeeffoorree iinnssttaalllliinngg//sseerrvviicciinngg tthhiiss uunniitt,, tteecchhnniicciiaannss MMUUSSTT ppuutt oonn aallll PPPPEE rreeqquuiirreedd ffoorr tthhee wwoorrkk bbeeiinngg uunnddeerrttaakkeenn ((EExxaammpplleess;; ccuutt rreessiissttaanntt gglloovveess//sslleeeevveess,, bbuuttyyll gglloovveess,, ssaaffeettyy ggllaasssseess,, hhaarrdd hhaatt//bbuummpp ccaapp,, ffaallll pprrootteeccttiioonn,, eelleeccttrriiccaall PPPPEE aanndd aarrcc ffllaasshh ccllootthhiinngg)).. AALLWWAAYYSS rreeffeerr ttoo aapppprroopprriiaattee MMaatteerriiaall SSaaffeettyy DDaattaa SShheeeettss ((MMSSDDSS))//SSaaffeettyy DDaattaa SShheeeettss ((SSDDSS)) aanndd OOSSHHAA gguuiiddeelliinneess ffoorr pprrooppeerr PPPPEE..
•• WWhheenn wwoorrkkiinngg wwiitthh oorr aarroouunndd hhaazzaarrddoouuss cchheemmiiccaallss,, AALLWWAAYYSS rreeffeerr ttoo tthhee aapppprroopprriiaattee MMSSDDSS//SSDDSS aanndd OOSSHHAA//GGHHSS ((GGlloobbaall HHaarrmmoonniizzeedd SSyysstteemm ooff CCllaassssiiffiiccaattiioonn aanndd LLaabbeelllliinngg ooff CChheemmiiccaallss)) gguuiiddeelliinneess ffoorr iinnffoorrmmaattiioonn oonn aalllloowwaabbllee ppeerrssoonnaall eexxppoossuurree lleevveellss,, pprrooppeerr rreessppiirraattoorryy pprrootteeccttiioonn aanndd hhaannddlliinngg iinnssttrruuccttiioonnss..
•• IIff tthheerree iiss aa rriisskk ooff eenneerrggiizzeedd eelleeccttrriiccaall ccoonnttaacctt,, aarrcc,, oorr ffllaasshh,, tteecchhnniicciiaannss MMUUSSTT ppuutt oonn aallll PPPPEE iinn aaccccoorrddaannccee wwiitthh OOSSHHAA,, NNFFPPAA 7700EE,, oorr ootthheerr ccoouunnttrryy--ssppeecciiffiicc rreeqquuiirreemmeennttss ffoorr aarrcc ffllaasshh pprrootteeccttiioonn,, PPRRIIOORR ttoo sseerrvviicciinngg tthhee uunniitt.. NNEEVVEERR PPEERRFFOORRMM AANNYY SSWWIITTCCHHIINNGG,, DDIISSCCOONNNNEECCTTIINNGG,, OORR VVOOLLTTAAGGEE TTEESSTTIINNGG WWIITTHHOOUUTT PPRROOPPEERR EELLEECCTTRRIICCAALL PPPPEE AANNDD AARRCC FFLLAASSHH CCLLOOTTHHIINNGG.. EENNSSUURREE EELLEECCTTRRIICCAALL MMEETTEERRSS AANNDD EEQQUUIIPPMMEENNTT AARREE PPRROOPPEERRLLYY RRAATTEEDD FFOORR IINNTTEENNDDEEDD VVOOLLTTAAGGEE..
AC-SVX001A-EN
3
WWAARRNNIINNGG
FFoollllooww EEHHSS PPoolliicciieess!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy..
•• AAllll IInnggeerrssoollll RRaanndd ppeerrssoonnnneell mmuusstt ffoollllooww IInnggeerrssoollll RRaanndd EEnnvviirroonnmmeennttaall,, HHeeaalltthh aanndd SSaaffeettyy ((EEHHSS)) ppoolliicciieess wwhheenn ppeerrffoorrmmiinngg wwoorrkk ssuucchh aass hhoott wwoorrkk,, eelleeccttrriiccaall,, ffaallll pprrootteeccttiioonn,, lloocckkoouutt//ttaaggoouutt,, rreeffrriiggeerraanntt hhaannddlliinngg,, eettcc.. AAllll ppoolliicciieess ccaann bbee ffoouunndd oonn tthhee BBOOSS ssiittee.. WWhheerree llooccaall rreegguullaattiioonnss aarree mmoorree ssttrriinnggeenntt tthhaann tthheessee ppoolliicciieess,, tthhoossee rreegguullaattiioonnss ssuuppeerrsseeddee tthheessee ppoolliicciieess..
•• NNoonn--IInnggeerrssoollll RRaanndd ppeerrssoonnnneell sshhoouulldd aallwwaayyss ffoollllooww llooccaall rreegguullaattiioonnss..
WWAARRNNIINNGG
RReeffrriiggeerraanntt uunnddeerr HHiigghh PPrreessssuurree!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd rreessuulltt iinn aann eexxpplloossiioonn wwhhiicchh ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy oorr eeqquuiippmmeenntt ddaammaaggee.. SSyysstteemm ccoonnttaaiinnss rreeffrriiggeerraanntt uunnddeerr hhiigghh pprreessssuurree.. RReeccoovveerr rreeffrriiggeerraanntt ttoo rreelliieevvee pprreessssuurree bbeeffoorree ooppeenniinngg tthhee ssyysstteemm.. SSeeee uunniitt nnaammeeppllaattee ffoorr rreeffrriiggeerraanntt ttyyppee.. DDoo nnoott uussee nnoonn--aapppprroovveedd rreeffrriiggeerraannttss,, rreeffrriiggeerraanntt ssuubbssttiittuutteess,, oorr rreeffrriiggeerraanntt aaddddiittiivveess..
Factory Warranty Information
Compliance with the following is required to preserve the factory warranty:
AAllll UUnniitt IInnssttaallllaattiioonnss
Startup MUST be performed by Trane, or an authorized agent of Trane, to VALIDATE this WARRANTY. Contractor must provide a two-week startup notification to Trane (or an agent
Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Factory Training
Factory training is available through Trane University to help you learn more about the operation and maintenance of your equipment. To learn about available training opportunities contact Trane University.
Online: www.trane.com/traneuniversity
Phone: 855-803-3563
Email: traneuniversity@trane.com
IInnttrroodduuccttiioonn
4
AC-SVX001A-EN
Model Number Information . . . . . . . . . . . .. . . . 7
Nameplates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Unit Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Model Number Coding System. . . . . . . . . 7
Compressor Nameplate . . . . . . . . . . . . . . . . . . . 7
Model Number Descriptions. . . . . . . . . .. . . . . . 8
Unit Model Number. . . . . . . . . . . . . . . . . . . . . . . 8
Compressor Information . . . . . . . . . . . . . . . . . 10
Model Number . . . . . . . . . . . . . . . . . . . . . . 10
Serial Number . . . . . . . . . . . . . . . . . . . . . . . 10
General Information . .. . . . . . . . . .. . . . . . . . . . . 11
Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . 11
Unit Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Accessory/Option Information . . . . . . . . . . . . 11
General Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Drive Cooling Fluid . . . . . . . . . . . . . . . . . . . . . . 14
Pre-Installation . . . . . . . . . . .. . . . . . . . . .. . . . . . . 15
Unit Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Exterior Inspection . . . . . . . . . . . . . . . . . . . 15
Inspection for Concealed
Damage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Repair. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Storage Requirements . . . . . . . . . . . . . . . . . . . 15
Installation Requirements . . . . . . . . . . . . . . . . 16
Dimensions and Weights . . . . . . . . . . . . .. . . . . 17
Weights. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Service Clearance . . . . . . . . . . . . . . . . . . . . . . . 18
Unit Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . 19
Installation Mechanical . . . . . . . . . .. . . . . . . . . . 23
Location Requirements . . . . . . . . . . . . . . . . . . 23
Sound Considerations. . . . . . . . . . . . . . . . 23
Foundation . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Lifting and Moving Instructions . . . . . . . . . . . 23
Center of Gravity . . . . . . . . . . . . . . . . . . . . . . . . 26
Isolation and Sound Emission . . . . . . . . . . . . 26
Unit Isolation and Leveling. . . . . . . . . . . . 26
Elastomeric Isolators . . . . . . . . . . . . . . . . . 26
Mounting Locations, Weights,
Isolators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Compressor Mounting Bolt
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Drainage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Refrigerant Pressure Relief Valves . . . . . . . . 31
Evaporator Piping . . . . . . . . . . . . . . . . . . . . . . . 31
Evaporator Piping Components . . . . . . . 32
Evaporator Waterside Pressure Drop
Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Freeze Protection . . . . . . . . . . . . . . . . . . . . . . . . 35
Low Evaporator Refrigerant Cutout,
Glycol Requirements . . . . . . . . . . . . . . . . . . . . 37
Installation Electrical . .. . . . . . . . . .. . . . . . . . . . 38
General Recommendations. . . . . . . . . . . . . . . 38
Adaptive FrequencyDrive
Capacitor Discharge. . . . . . . . . . . . . . . . . . 39
Units with Nitrogen Charge
Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Installer-Supplied Components . . . . . . . . . . . 39
Power Supply Wiring. . . . . . . . . . . . . . . . . 40
Control Power Supply . . . . . . . . . . . . . . . . 41
Service Power Connection . . . . . . . . . . . . 41
Heater Power Supply. . . . . . . . . . . . . . . . . 42
Chilled Water Pump Control . . . . . . . . . . . . . . 42
Programmable Relays . . . . . . . . . . . . . . . . . . . 43
Relay Assignments Using Tracer TU . . . . . . 43
Low Voltage Wiring. . . . . . . . . . . . . . . . . . . . . . 44
Emergency Stop . . . . . . . . . . . . . . . . . . . . . 44
External Auto/Stop . . . . . . . . . . . . . . . . . . . 44
External Circuit Lockout – Circuit #1
and #2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Ice Building Option . . . . . . . . . . . . . . . . . . 44
External Chilled Water Setpoint
(ECWS) Option . . . . . . . . . . . . . . . . . . . . . . 45
External Demand Limit Setpoint
(EDLS) Option . . . . . . . . . . . . . . . . . . . . . . . 45
EDLS and ECWS Analog Input Signal
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Chilled Water Reset (CWR) . . . . . . . . . . . 46
Transformer Power Rating . . . . . . . . . . . . . . . 47
Communications Interface . . . . . . . . . . . . . . . 47
Table of Contents
AC-SVX001A-EN
5
LonTalk Interface (LCI-C) . . . . . . . . . . . . . 47
BACnet Interface (BCI-C). . . . . . . . . . . . . . 47
Modbus Remote Terminal Unit
Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Operating Principles. . . . . . . . .. . . . . . . . . . . . . . 48
Refrigeration Circuits . . . . . . . . . . . . . . . . . . . . 48
Refrigeration Cycle . . . . . . . . . . . . . . . . . . . . . . 48
Refrigerant R-134a . . . . . . . . . . . . . . . . . . . . . . . 48
Compressor and Oil System . . . . . . . . . . . . . . 48
Condenser and Fans . . . . . . . . . . . . . . . . . . . . . 48
Evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Drive Cooling System . . . . . . . . . . . . . . . . . . . . 49
Controls . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . 50
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
UC800 Specifications . . . . . . . . . . . . . . . . . . . . 50
Wiring and Port Descriptions. . . . . . . . . . 50
Communication Interfaces . . . . . . . . . . . . 51
Rotary Switches . . . . . . . . . . . . . . . . . . . . . 51
LED Description and Operation. . . . . . . . 51
Tracer AdaptiView TD7 Display . . . . . . . . . . . 53
Operator Interface. . . . . . . . . . . . . . . . . . . . 53
Home Screen . . . . . . . . . . . . . . . . . . . . . . . 53
Viewing Chiller Operating
Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Reports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Equipment Settings . . . . . . . . . . . . . . . . . . 59
Display Settings . . . . . . . . . . . . . . . . . . . . . 61
Security Settings. . . . . . . . . . . . . . . . . . . . . 62
InvisiSound Ultimate — Noise
Reduction Mode . . . . . . . . . . . . . . . . . . . . . 63
Tracer TU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Pre-Start. . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . 65
Start-up and Shutdown. . . . . . . . . . . . . . . . . .. . 66
Unit Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Temporary Shutdown And Restart . . . . . . . . 66
Extended Shutdown Procedure . . . . . . . . . . 66
Seasonal Unit Start-up Procedure . . . . . . . . 67
System Restart After Extended
Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Sequence of Operation. . . . . . . . . . . . . . . . . . . 67
Software Operation Overview. . . . . . . . . 67
Power Up Diagram . . . . . . . . . . . . . . . . . . 69
Power Up to Starting . . . . . . . . . . . . . . . . . 70
Stopped to Starting . . . . . . . . . . . . . . . . . . 71
Running (Lead Compressor/Circuit
Start and Run) . . . . . . . . . . . . . . . . . . . . . . . 72
Running (Lag Compressor/Circuit
Start and Run) . . . . . . . . . . . . . . . . . . . . . . . 73
Satisfied Setpoint . . . . . . . . . . . . . . . . . . . . 74
Normal Shutdown to Stopped or
Run Inhibit . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Immediate Shutdown to Stopped or
Run Inhibit . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Ice Making (Running to Ice Making to
Running) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Ice Making (Auto to Ice Making to Ice
Making Complete) . . . . . . . . . . . . . . . . . . . 78
Maintenance . . . . . . . . . .. . . . . . . . . .. . . . . . . . . . 79
Recommended Maintenance . . . . . . . . . . . . . 79
Weekly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Monthly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Annual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Refrigerant and Oil Charge
Management . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Lubrication System . . . . . . . . . . . . . . . . . . . . . . 80
Oil Sump Level Check . . . . . . . . . . . . . . . . 80
Drive Cooling System . . . . . . . . . . . . . . . . . . . . 81
Service Intervals . . . . . . . . . . . . . . . . . . . . . 81
Unit Diagnostics . . . . . . . . . . . . . . . . . . . . . 81
pH Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Pressure Relief Cap . . . . . . . . . . . . . . . . . . 82
Drive Cooling Expansion Tank . . . . . . . . 82
Condenser Coil Corrosion Protection
Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Condenser Coil Cleaning . . . . . . . . . . . . . . . . . 82
Coil Cleaning Interval . . . . . . . . . . . . . . . . 82
Cleaning Air Side of Coils . . . . . . . . . . . . 83
Cleaning Coated Coils . . . . . . . . . . . . . . . . 83
Reinstallation of Compressor Mounting
Bolts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Servicing Chiller Roof . . . . . . . . . . . . . . . . . . . 83
Diagnostics. . . . . . . . . . . . . . . . . . .. . . . . . . . . .. . . 84
TTaabbllee ooff CCoonntteennttss
6
AC-SVX001A-EN
General Diagnostics Information. . . . . . . . . . 84
AFD Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . 84
Main Processor Diagnostics . . . . . . . . . . . . . . 87
Communication Diagnostics. . . . . . . . . . . . . . 99
Unit Wiring . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . 104
Log and Check Sheets . . . . . . . . . . . . . . . . . . . . 105
AscendModel ACR Installation Completion Check Sheet and Request for
Trane Service . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Operator Log . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
TTaabbllee ooff CCoonntteennttss
AC-SVX001A-EN
7

Model Number Information

Nameplates

Unit nameplates are applied to the exterior of the control panel. A compressor nameplate is located on each compressor. When the unit arrives, compare all nameplate data with ordering, submittal, and shipping information.

Unit Nameplate

See figure below for a typical unit nameplate. The outdoor unit nameplate provides the following information:
Unit model and size description.
Unit serial number.
Unit electrical requirements.
Operating charges of R-134a and refrigerant oil (Trane OIL00311).
Unit test pressures.
Installation, operation and maintenance and service data literature.
Drawing numbers for unit wiring diagrams

Model Number Coding System

Model numbers are composed of numbers and letters that represent features of the equipment. Shown below is a sample of typical unit model number.
ACRA 200F UA01 AA1F N1X1 A2D0 0CB1 X03X AA01 000
Each position, or group of positions, in the model number is used to represent a feature. Unit model number digits are selected and assigned in accordance with the definitions as listed in Model Number Descriptions chapter. For example, position 08 of the unit model number above contains the letter “F” which indicates the unit voltage is 460/60/3.

Compressor Nameplate

The compressor nameplate provides the following information:
Compressor model number.
Compressor serial number.
Compressor electrical characteristics
Utilization range.
Recommended refrigerant
See Model Number Descriptions chapter for compressor model and serial number descriptions.
8
AC-SVX001A-EN

Model Number Descriptions

Unit Model Number

Digit 1, 2, 3, 4 — Unit Model
ACRA = Air-Cooled Screw Chiller
Digit 5, 6, 7 — Nominal Tonnage
150 = 150 Tons 165 = 165 Tons 180 = 180 Tons 200 = 200 Tons 225 = 225 Tons 250 = 250 Tons 275 = 275 Tons 300 = 300 Tons
Digit 8 — Unit Voltage
A = 200/60/3 B = 230/50/3 C = 380/50/3 D = 380/60/3 E = 400/50/3 F = 460/60/3 G = 575/60/3 H = 400/60/3
Digit 9 — Manufacturing Location
U = Trane Commercial Systems, Pueblo, CO
USA
Digits 10, 11 — Design Sequence
** = Factory assigned
Digit 12 — Unit Sound Package
1 = InvisiSoundStandard Unit 2 = InvisiSoundSuperior (Line Wraps,
Reduced Fan Speed) 3 = InvisiSoundUltimate (Compressor
Sound Attenuation, Line Wraps, Reduced Fan Speed)
Digit 13 — Agency Listing
0 = No Agency Listing A = UL/cUL Listing
Digit 14 — Pressure Vessel Code
A = ASME Pressure Vessel Code C = CRN or Canadian Equivalent Pressure
Vessel Code
D = Australia Pressure Vessel Code
Digit 15 — Factory Charge
1 = Refrigerant Charge R-134a 2 = Nitrogen Charge
Digit 16 — Evaporator Application
F = Standard Cooling (40 to 65°F/5.5 to 18°
C) G = Low Temp Process Cooling (below 40°F/
5.5°C) C = Ice Making (20 to 6°F/7 to 18°C) with
Hardwired Interface
Digit 17 — Evaporator Configuration
N = 2-pass Evaporator P = 3-pass Evaporator
Digit 18 — Evaporator Fluid Type
1 = Water 2 = Calcium Chloride 3 = Ethylene Glycol 4 = Propylene Glycol 5 = Methanol
Digit 19 — Water Connection
X = Grooved Pipe F = Grooved Pipe + Flange
Digit 20 — Flow Switch
1 = Factory Installed - Other Fluid (15 cm/s) 2 = Factory Installed - Water 2 (35 cm/s) 3 = Factory Installed - Water 3 (45 cm/s)
Digit 21 — Insulation
A = Factory Insulation — All Cold Parts 0.75” B = Evaporator-only Insulation for High
Humidity/Low Evap Temp 1.25”
Digit 22 — Unit Application
1 = Standard Ambient (32 to 105°F/0 to
40.6°C) 2 = Low Ambient (0 to 105°F/-17.7 to 40.6°
C) 3 = Extreme Low Ambient (–20 to 105°F/
-28.9 to 40.6°C)
4 = High Ambient (32 to 125°F/0 to 52°C) 5 = Wide Ambient (0 to 125°F/-17.7 to 52°C)
Digit 23 — Condenser Fin Options
A = Aluminum Fins with Slits D = CompleteCoatEpoxy Coated Fins
Digit 24, 25 — Not Used
00 = Reserved for future use
Digit 26 — Power Line Connection Type
A = Terminal Block C = Circuit Breaker D = Circuit Breaker with High Fault Rated
Control Panel
Digit 27 — Short Circuit Current Rating
A = Default A Short Circuit Rating B = High A Short Circuit Rating
Digit 28 — Transformer
0 = No Transformer 1 = Factory Installed Transformer
Digit 29 — Line Voltage Harmonic Mitigation
X = DC Reactors (~30% TDD) 1 = Filter circuit (IEEE519 Compliant)
Digit 30 — Electrical Accessories
0 = No Convenience Outlet C = 15A 115V Convenience Outlet (Type B)
Digit 31 — Remote Communication Option
0 = None 1 = LonTalk® Interface (LCI-C) 2 = BACnet® MS/TP Interface 3 = ModbusInterface
Digit 32 — Hard Wire Communication
X = None A = Hard Wired Bundle - All B = Remote Leaving Water Temp Setpoint C = Remote Leaving Temp and Demand Limit
Setpoints
D = Programmable Relay E = Programmable Relay and Leaving Water
and Demand Limit Setpoint
F = Percent Capacity G = Percent Capacity and Leaving Water and
Demand Limit Setpoint H = Percent Capacity and Programmable
Relay
AC-SVX001A-EN
9
Digit 33 — Not Used
A = Reserved for future use
Digit 34 — Structural Options
A = Standard Unit Structure
Digit 35 — Appearance Accessories
0 = No Appearance Options A = Architectural Louvered Panels
Digit 36 — Unit Isolation
0 = None 1 = Elastomeric Isolators
Digit 37, 38 — Not Used
00 = Reserved for future use
Digit 39 — Special
0 = None S = Special F = Ship to Final Finisher
MMooddeell NNuummbbeerr DDeessccrriippttiioonnss
10
AC-SVX001A-EN

Compressor Information

Model Number

Digit 1, 2, 3, 4 — Compressor Type
CHHS = Positive displacment, helical rotary (twin screw) hermetic
compressor
Digit 5 — Frame Size
R = R Frame: 70 - 100 tons S = S Frame: 112 - 165 tons
Digit 6 — Motor Length
B = 145 mm C = 170 mm E = 165 mm F = 190 mm
Digit 7— Motor Winding Characteristics
* = Factory assigned
Digit 8 — Volume Ratio
E = Variable Volume Ratio
Digit 9— Refrigerant
1 = R-134a
Digits 10, 11 — Design Sequence
** = Factory assigned

Serial Number

Digit 1, 2 — Year
YY = Last two digits of year of manufacture
Digit 3, 4 — Week
WW = Week of build, from 00 to 52
Digit 5 — Day
1 = Monday 2 = Tuesday 3 = Wednesday 4 = Thursday 5 = Friday 6 = Saturday 7 = Sunday
Digit 6, 7, 8 — Coded Time Stamp
TTT = Used to ensure uniqueness of serial number
Digit 9 — Assembly Line
Assembly line compressor was built on. Varies with facility.
Digit 10 — Build Location
A = Monterrey
MMooddeell NNuummbbeerr DDeessccrriippttiioonnss
AC-SVX001A-EN
11

General Information

Unit Description

The AscendACR units are helical-rotary type, air­cooled chillers designed for outdoor installation. The refrigerant circuits are factory-piped, leak tested and dehydrated. Every unit is electrically tested for proper control operation before shipment.
Chilled water inlet and outlet openings are covered for shipment. The chiller features Trane’s exclusive Adaptive Controllogic, which monitors the control variables that govern the operation of the chiller unit. Adaptive Control logic can adjust capacity variables to avoid chiller shutdown when necessary, and keep producing chilled water. The units feature two independent refrigerant circuits. Each circuit utilizes at least one compressor driven by an Adaptive Frequency Drive. Each refrigerant circuit is provided with filter, sight glass, electronic expansion valve, and charging valves. The shell-and-tube evaporator is manufactured in accordance with the ASME standards or other international codes. Each evaporator is fully insulated and equipped with water drain and vent connections.
Units are shipped with full oil charge and can be ordered with either a factory refrigerant charge, or optional nitrogen charge.

Unit Length

Units are EXTENDED length if either of the following are selected:
Transformer: Model number digit 28 = 1
Harmonic Filtration Option: Model number digit 29 = 1
Units without Harmonic Filtration Option or Transformer (digits 28, 29 = 0X) are STANDARD length.

Accessory/Option Information

Check all the accessories and loose parts which are shipped with the unit against the shipping list. Included in these items will be water vessel drain plugs, electrical diagrams, and service literature, which are placed inside the control panel for shipment.
If optional elastomeric isolators are ordered with unit (model number digit 36 = 1), they are shipped mounted
on diagonal supports on the end of the unit opposite control panel. See figures below.
Figure 1. Elastomeric isolator shipping location
Elastomeric Isolator
Shipping Locations
(not all isolators shown ­quantity varies with unit configuration)
Figure 2. Elastomeric isolators attached for shipping
12
AC-SVX001A-EN

General Data

Table 1. General data table
Unit Size (tons)
150 165 180 200 225 250 275 300
Compressor Model
CHHSR CHHSR CHHSR CHHSR CHHSS CHHSS CHHSS CHHSS
Quantity
# 2 2 2 2 2 2 2 2
Evaporator
Water Storage
(gal)
17.5 18.7 21.9 23.9 26.6 28.7 33.0 36.0
(L)
66.1 70.9 82.8 90.5 100.6 108.8 125.0 136.1
2 Pass arrangement
Water Connection Size
(in)
5 5 6 6 6 6 8 8
(mm)
125 125 150 150 150 150 200 200
Minimum Flow
(gpm)
171 187 202 228 261 288 318 354
(l/s)
10.8 11.8 12.7 14.4 16.5 18.2 20.1 22.3
Maximum Flow
(gpm)
626 684 742 835 957 1055 1165 1299
(l/s)
39.5 43.1 46.8 52.7 60.4 66.5 73.5 81.9
3 Pass arrangement
Water Connection Size
(in)
4 4 5 5 5 5 6 6
(mm)
100 100 125 125 125 125 150 150
Minimum Flow
(gpm)
114 124 135 152 174 192 212 236
(l/s)
7.2 7.8 8.5 9.6 11.0 12.1 13.4 14.9
Maximum Flow
(gpm)
417 456 495 557 638 703 777 866
(l/s)
26.3 28.8 31.2 35.1 40.2 44.3 49.0 54.6
Condenser
Qty of Coils
8 10 10 12 12 12 14 16
Coil Length
(in)
78.74 78.74 78.74 78.74 78.74 78.74 78.74 78.74
(mm)
2000 2000 2000 2000 2000 2000 2000 2000
Coil Height
(in)
50 50 50 50 50 50 50 50
(mm)
1270 1270 1270 1270 1270 1270 1270 1270
Fins/Ft
192 192 192 192 192 192 192 192
Rows 3 3 3 3 3 3 3 3
Condenser Fans
Quantity
# 8 10 10 12 12 12 14 16
Diameter
(in)
37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5
(mm)
953 953 953 953 953 953 953 953
Total Airflow
(cfm) 107,392 134,240 134,240 161,088 161,088 161,088 187,936 214,784
(m3/
hr)
182,460 228,075 228,075 273,690 273,690 273,690 319,305 364,920
Tip Speed
(ft/
min)
8700 8700 8700 8700 8700 8700 8700 8700
(M/S)
44.2 44.2 44.2 44.2 44.2 44.2 44.2 44.2
GGeenneerraall IInnffoorrmmaattiioonn
AC-SVX001A-EN
13
Table 1. General data table (continued)
Unit Size (tons)
150 165 180 200 225 250 275 300
Ambient Temperature Range
Standard Ambient
°F (°C) 32 to 105 (0 to 40.6)
Low Ambient
°F (°C) 0 to 105 (-17.7 to 40.6)
Extreme Low Ambient
°F (°C) -20 to 105 (-28.9 to 40.6)
High Ambient °F (°C) 32 to 125 (0 to 52)
Wide Ambient
°F (°C) 0 to 125 (-17.7 to 52)
General Unit
Refrigerant
HFC-134a
Refrigerant Ckts
# 2
Minimum Load % 20 18 17 15 20 18 16 15
Refrigerant Charge/ckt
(lbs)
172 181 210 218 265 261 318 325
(kg)
78 82 95 99 120 118 144 148
Oil Trane OIL00311
Oil Charge/ckt
(gal)
3.0 3.0 3.0 3.0 4.0 4.0 4.0 4.0
(L)
11.4 11.4 11.4 11.4 15.1 15.1 15.1 15.1
GGeenneerraall IInnffoorrmmaattiioonn
14
AC-SVX001A-EN

Drive Cooling Fluid

NNOOTTIICCEE
EEqquuiippmmeenntt DDaammaaggee!!
UUssee ooff uunnaapppprroovveedd fflluuiiddss,, oorr ddiilluuttiioonn ooff aapppprroovveedd fflluuiidd,, ccoouulldd rreessuulltt iinn ccaattaassttrroopphhiicc eeqquuiippmmeenntt ddaammaaggee.. UUssee oonnllyy TTrraannee HHeeaatt TTrraannssffeerr FFlluuiidd PP//NN CCHHMM0011002233.. TThhiiss fflluuiidd iiss aa ddiirreecctt uussee ccoonncceennttrraattiioonn aanndd iiss nnoott ttoo bbee ddiilluutteedd.. DDoo nnoott ttoopp ooffff wwiitthh wwaatteerr oorr aannyy ootthheerr fflluuiidd..
NNoottee:: The use of incorrect compounds in the drive
cooling system may result in scaling, erosion, corrosion or freezing. The Trane Company warranty specifically excludes liability for corrosion, erosion, freezing or deterioration of Trane equipment.
Proper fluid level is important to the operation of the unit. See Drive Cooling Expansion Tank section in Maintenance chapter for fluid level check instructions. The circuit capacities are shown in table below.
If the level is below the recommended minimum levels, contact your local Trane office.
NNoottee:: Drive cooling fluid service life is 5 years. See
maintenance chapter for more drive cooling system information.
Table 2. Drive Cooling
Unit Size
(tons)
Fluid Volume (gal) Fluid Volume (l)
Voltage
Ambient
(a)
Ckt1 Ckt2 Ckt 1 Ckt2
Standard Length
150 to 200 All All 1.4 2.0 5.5 7.7
225 to 250
200/60, 230/50,
460/60, 575/60
Std, Low, Extra Low
1.4 2.0 5.5 7.7
High, Wide
1.5 2.1 5.8 8.1
380/60, 380/50, 400/50
All 1.5 2.1 5.8 8.1
275 to 300 All All 1.5 2.1 5.8 8.1
Extended Length
150 to 200 All All 1.7 2.2 6.2 8.5
225 to 250
200/60, 230/50,
460/60, 575/60
Std, Low, Extra Low
1.7 2.2 6.2 8.5
High, Wide
1.7 2.3 6.6 8.8
380/60, 380/50, 400/50
All 1.7 2.3 6.6 8.8
275 to 300 All All 1.7 2.3 6.6 8.8
(a)
See model number description section, digit 22, for ambient information.
(a)
See model number description section, digit 22, for ambient information.
GGeenneerraall IInnffoorrmmaattiioonn
AC-SVX001A-EN
15

Pre-Installation

Unit Inspection

To protect against loss due to damage incurred in transit, perform inspection immediately upon receipt of the unit.

Exterior Inspection

If the job site inspection reveals damage or material shortages, file a claim with the carrier immediately. Specify the type and extent of the damage on the bill of lading before signing. Notify the appropriate sales representative.
IImmppoorrttaanntt:: Do not proceed with installation of a
damaged unit without sales representative’s approval.
Visually inspect the complete exterior for signs of shipping damages to unit or packing material.
Verify that the nameplate data matches the sales order and bill of lading.
Verify that the unit is properly equipped and there are no material shortages.
NNoottee:: Corrosion due to dirt, road grim, road salt, and
other contaminates picked up during shipping is not the responsibility of the carrier.

Inspection for Concealed Damage

Visually inspect the components for concealed damage as soon as possible after delivery and before it is stored.
If concealed damage is discovered:
Notify the carrier’s terminal of the damage immediately by phone and by mail.
Concealed damage must be reported within 15 days.
Request an immediate, joint inspection of the damage with the carrier and consignee.
Stop unpacking the unit.
Do not remove damaged material from receiving location.
Take photos of the damage, if possible.
The owner must provide reasonable evidence that the damage did not occur after delivery.

Repair

Notify the appropriate sales representative before arranging unit installation or repair.
IImmppoorrttaanntt:: Do not repair unit until the damage has
been inspected by the carrier’s representative.

Storage Requirements

Extended storage of outdoor unit prior to installation requires these precautionary measures:
Store the outdoor unit in a secure area.
For units that have been charged with refrigerant, verify the following valves are closed on each circuit:
Suction service valve (butterfly valve)
Liquid line angle valve or EXV (EXV is driven
closed whenever circuit is powered)
– Oil line shutoff valves to brazed plate heat
exchangers
NNoottee:: Units with factory refrigerant charge (model
number digit 15 = 1) are shipped with suction, liquid and oil line shutoff valves closed, isolating most of refrigerant charge in the evaporator. If unit goes directly into long term storage, it is recommended that these valve positions be confirmed.
For units with nitrogen charge option (model number digit 15 = 2), units are shipped with valves open. If unit goes directly into storage prior to refrigerant charge, confirm all service valves are open.
At least every three months (quarterly), check the pressure in the refrigerant circuits to verify that the refrigerant charge is intact. If it is not, contact a qualified service organization and the appropriate Trane sales office.
16
AC-SVX001A-EN

Installation Requirements

Type
Trane Supplied Trane Installed
Trane Supplied Field Installed
Field Supplied Field Installed
Foundation
• Meet foundation requirements
Rigging
• Safety chains
• Clevis connectors
• Lifting beam
• Spreader bar
Disassembly/Reassembly (as required)
Trane, or an agent of Trane specifically authorized to perform start-up of Trane® products (contact your local Trane office for pricing)
Isolation
Elastomeric isolators (optional)
• Elastomeric isolators (optional)
Electrical
• Circuit breakers (optional)
• Unit Mounted Starter
• Circuit breakers (optional)
• Electrical connections to unit mounted starter
• Wiring sizes per submittal and NEC
• Terminal lugs
• Ground connection(s)
• BAS wiring (optional)
• Control voltage wiring
• Chilled water pump contactor and wiring
• Option relays and wiring
Water piping
Flow switch
• Taps for thermometers and gauges
• Thermometers
• Water flow pressure gauges
• Isolation and balancing valves in water piping
• Vents and drain
• Waterside pressure relief valves
• Water strainer
Insulation Insulation Insulation
Water Piping Connection Components
Grooved pipe Flange kit (optional)
Other Materials
• R-134a refrigerant
• Dry nitrogen (optional)
Ascend™ Model ACR Installation Completion Check Sheet and Request for Trane Service (AC-ADF001*-EN) See Log and Check Sheet chapter
Chiller Start-up Commissioning
Trane, or an agent of Trane specifically authorized to perform start-up of Trane® products
Trane specifically authorized to perform start-up of Trane® products
PPrree--IInnssttaallllaattiioonn
AC-SVX001A-EN
17

Dimensions and Weights

Weights

Table 3. Unit weights
Standard Length Extended Length
Shipping Operating Shipping Operating
Unit Size
(tons)
lb
kg
lb
kg
lb
kg
lb
kg
InvisiSound™ Standard or Superior
150 11333 5141 11479 5207 13492 6120 13638 6186
165 12377 5614 12533 5685 14532 6592 14688 6662
180 12698 5760 12881 5843 14853 6737 15036 6820
200 13808 6263 14008 6354 15991 7254 16191 7344
225 15244 6915 15466 7015 17427 7905 17649 8006
250 15622 7086 15862 7195 17805 8076 18045 8185
275 16820 7630 17095 7754 18975 8607 19250 8732
300 17965 8149 18265 8285 20121 9127 20421 9263
InvisiSound™ Ultimate
150 12133 5504 12279 5570 14292 6483 14438 6549
165 13177 5977 13333 6048 15332 6955 15488 7025
180 13498 6123 13681 6206 15653 7100 15836 7183
200 14608 6626 14808 6717 16791 7616 16991 7707
225 16044 7278 16266 7378 18227 8268 18449 8368
250 16422 7449 16662 7558 18605 8439 18845 8548
275 17620 7992 17895 8117 19775 8970 20050 9095
300 18765 8512 19040 8636 20921 9490 21196 9614
Notes:
1. Weights include factory charge of refrigerant and oil, as well as architectural louvered panels. See Unit Length section of General Data chapter to determine unit length.
2. Model number digit 12 = 1 or 2
3. Model number digit 12 = 3
18
AC-SVX001A-EN

Service Clearance

Figure 3. Unit service clearance requirements
36” (914.4mm)
40”
(1016
mm)
24” (600.1mm)
Control
Panel
NO OBSTRUCTIONS ABOVE UNIT
TOP VIEW
See
note 1
85” (2160mm)
See note 2
NNootteess::
1. A full 40” clearance is required in front of the control panel. Must be measured from front of panel, not end of unit base.
2. Clearance of 85” on the side of the unit is required for coil replacement. Preferred side for coil replacement is shown (left side of the unit, as facing control panel), however either side is acceptable.
DDiimmeennssiioonnss aanndd WWeeiigghhttss
AC-SVX001A-EN
19

Unit Dimensions

Figure 4. Unit dimensions, standard length
DDiimmeennssiioonnss aanndd WWeeiigghhttss
20
AC-SVX001A-EN
Table 4. Unit dimensions, standard length
Unit Size
150 165 180 200
225, 250
275 300
Dim in
mm
in
mm
in
mm
in
mm
in
mm
in
mm
in
mm
A 158.6 4027.0 211.4 5368.8 212.5 5397.4 265.3 6739.5 265.3 6739.5 318.1 8080.5 370.9 9422.5
B 52.4 1330.0 105.2 2671.9 103.5 2629.4 156.4 3971.5 156.4 3971.5 209.0 5308.5 261.8 6650.5
C 11.8 300.0 11.8 300.0 11.8 300.0 11.8 300.0 11.8 300.0 11.8 300.0 11.8 300.0
D 51.2 1300.0 51.2 1300.0 51.2 1300.0 51.2 1300.0 51.2 1300.0 51.2 1300.0 51.2 1300.0
E 78.8 2000.0 74.8 1900.0 74.8 1900.0 74.8 1900.0 74.8 1900.0 61.4 1560.0 74.8 1900.0
F 63.0 1600.0 118.1 3000.0 118.1 3000.0 100.8 2560.0 100.8 2560.0 72.4 1840.0 100.8 2560.0
G 76.4 1940.0 76.4 1940.0 137.8 3500.0 174.8 4440.0
H 25.0 635.0 25.0 635.0 25.0 635.0 25.0 635.0 25.0 635.0 25.0 635.0 25.0 635.0
I 128.1 3255.0 145.6 3699.0 145.6 3699.0 65.9 1674.0 65.9 1674.0 65.9 1674.0 65.9 1674.0
J 120.5 3061.0 120.5 3061.0 158.5 4026.0 79.7 2024.0
K 184.5 4686.0
L 223.0 5663.5 275.8 7005.5 275.8 7005.5 328.6 8347.5 328.6 8347.5 381.5 9689.5 434.3 11031.5
M 228.9 5813.0 281.7 7155.0 281.7 7155.0 334.5 8497.0 334.5 8497.0 387.4 9839.0 440.2 11181.0
N 20.4 519.5 20.4 519.5 19.6 497.5 19.6 497.5 21.8 553.6 20.6 522.5 20.6 522.5
O 17.7 449.5 17.7 449.5 15.4 390.5 15.4 390.5 17.6 446.6 16.1 407.7 16.1 407.7
P 49.3 1252.5 49.3 1252.5 49.9 1268.0 49.9 1268.0 49.9 1268.0 51.3 1303.3 51.3 1303.3
Q
38.5 977.5 38.5 977.5 37.9 962.0 37.9 962.0 37.9 962.0 36.5 927.3 36.5 927.3
R 19.3 489.5 19.3 489.5 17.6 447.5 17.6 447.5 19.8 503.6 18.2 462.5 18.2 462.5
S 19.7 499.5 19.7 499.5 18.2 462.5 18.2 462.5 20.4 518.6 18.9 480.5 18.9 480.5
T 15.8 400.0 15.8 400.0 15.8 400.0 15.8 400.0 15.8 400.0 15.8 400.0 15.8 400.0
U 66.9 1700.0 66.9 1700.0 66.9 1700.0 66.9 1700.0 66.9 1700.0 66.9 1700.0 66.9 1700.0
V 59.1 1500.0 55.1 1400.0 55.1 1400.0 55.1 1400.0 55.1 1400.0 41.8 1060.0 55.1 1400.0
W 63.0 1600.0 118.1 3000.0 118.1 3000.0 100.8 2560.0 100.8 2560.0 72.4 1840.0 100.8 2560.0
X 76.4 1940.0 76.4 1940.0 137.8 3500.0 155.1 3940.0
Y 53.6 1362.5 106.5 2704.4 105.5 2679.4 158.3 4021.5 158.3 4021.5 210.3 5340.0 263.1 6682.0
DDiimmeennssiioonnss aanndd WWeeiigghhttss
AC-SVX001A-EN
21
Figure 5. Unit dimensions, extended length
DDiimmeennssiioonnss aanndd WWeeiigghhttss
22
AC-SVX001A-EN
Table 5. Unit dimensions, extended length
Unit Size
150 165 180 200
225, 250
275 300
Dim in
mm
in
mm
in
mm
in
mm
in
mm
in
mm
in
mm
A 158.6 4027.0 211.4 5368.8 212.5 5397.4 265.3 6739.5 265.3 6739.5 318.1 8080.5 370.9 9422.5
B 52.4 1330.0 105.2 2671.9 103.5 2629.4 156.4 3971.5 156.4 3971.5 209.0 5308.5 261.8 6650.5
C 27.6 700.0 27.6 700.0 27.6 700.0 51.2 1300.0 51.2 1300.0 51.2 1300.0 51.2 1300.0
D 86.6 2200.0 86.6 2200.0 86.6 2200.0 63.0 1600.0 63.0 1600.0 63.0 1600.0 63.0 1600.0
E 80.4 2042.0 76.4 1942.0 76.4 1942.0 76.4 1942.0 76.4 1942.0 63.1 1602.0 76.4 1942.0
F 63.0 1600.0 118.1 3000.0 118.1 3000.0 59.1 1500.0 59.1 1500.0 72.4 1840.0 100.8 2560.0
G 118.1 3000.0 118.1 3000.0 137.8 3500.0 174.8 4440.0
H 55.1 1400.0 55.1 1400.0 55.1 1400.0 58.3 1482.0 58.3 1482.0 58.3 1482.0 58.3 1482.0
I 150.9 3832.0 168.4 4276.0 168.4 4276.0 85.4 2169.0 85.4 2169.0 85.4 2169.0 85.4 2169.0
J 120.5 3061.0 120.5 3061.0 158.5 4026.0 79.7 2024.0
K 184.5 4686.0
L 275.8 7005.5 328.6 8347.5 328.6 8347.5 381.5 9689.5 381.5 9689.5 434.3 11031.5 487.1 12373.5
M 281.7 7155.0 334.5 8497.0 334.5 8497.0 387.4 9839.0 387.4 9839.0 440.2 11181.0 493.0 12523.0
N 20.4 519.5 20.4 519.5 19.6 497.5 19.6 497.5 21.8 553.6 20.6 522.5 20.6 522.5
O 17.7 449.5 17.7 449.5 15.4 390.5 15.4 390.5 17.6 446.6 16.1 407.7 16.1 407.7
P 49.3 1252.5 49.3 1252.5 49.9 1268.0 49.9 1268.0 49.9 1268.0 51.3 1303.3 51.3 1303.3
Q
38.5 977.5 38.5 977.5 37.9 962.0 37.9 962.0 37.9 962.0 36.5 927.3 36.5 927.3
R 19.3 489.5 19.3 489.5 17.6 447.5 17.6 447.5 19.8 503.6 18.2 462.5 18.2 462.5
S 19.7 499.5 19.7 499.5 18.2 462.5 18.2 462.5 20.4 518.6 18.9 480.5 18.9 480.5
T 27.6 700.0 27.6 700.0 27.6 700.0 51.2 1300.0 51.2 1300.0 51.2 1300.0 51.2 1300.0
U 86.6 2200.0 86.6 2200.0 86.6 2200.0 63.0 1600.0 63.0 1600.0 63.0 1600.0 63.0 1600.0
V 80.4 2042.0 76.4 1942.0 76.4 1942.0 76.4 1942.0 76.4 1942.0 63.1 1602.0 76.4 1942.0
W 63.0 1600.0 118.1 3000.0 118.1 3000.0 59.1 1500.0 59.1 1500.0 72.4 1840.0 63.0 1600.0
X 118.1 3000.0 118.1 3000.0 137.8 3500.0 155.1 3940.0
Y 53.6 1362.5 106.5 2704.4 105.5 2679.4 158.3 4021.5 158.3 4021.5 210.3 5340.0 263.1 6682.0
DDiimmeennssiioonnss aanndd WWeeiigghhttss
AC-SVX001A-EN
23

Installation Mechanical

Location Requirements

Sound Considerations

Locate the unit away from sound-sensitive areas.
Install the optional elastomeric isolators under the unit. See Isolation and Sound Emission section.
Chilled water piping should not be supported by chiller frame.
Install rubber vibration isolators in all water piping.
Use flexible electrical conduit.
Seal all wall penetrations.
NNoottee:: Consult an acoustical engineer for critical
applications.

Foundation

Provide rigid, non-warping mounting pads or a concrete foundation of sufficient strength and mass to support the applicable operating weight (i.e., including completed piping, and full operating charges of refrigerant, oil and water). See Dimensions and Weights chapter for unit operating weights. Once in place, the unit must be level within 1/4” (6.4 mm) across the length and width of the unit. The Trane Company is not responsible for equipment problems resulting from an improperly designed or constructed foundation.

Clearances

Provide enough space around the unit to allow the installation and maintenance personnel unrestricted access to all service points. See submittal drawings for the unit dimensions, to provide sufficient clearance for the opening of control panel doors and unit service. See Dimensions and Weights chapter for minimum clearances. In all cases, local codes which require additional clearances will take precedence over these recommendations.
For close spacing information, see RLC-PRB037*-EN.

Lifting and Moving Instructions

WWAARRNNIINNGG
HHeeaavvyy OObbjjeecctt!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd rreessuulltt iinn uunniitt ddrrooppppiinngg wwhhiicchh ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy,, aanndd eeqquuiippmmeenntt oorr pprrooppeerrttyy--oonnllyy ddaammaaggee.. EEnnssuurree tthhaatt aallll tthhee lliiffttiinngg eeqquuiippmmeenntt uusseedd iiss pprrooppeerrllyy rraatteedd ffoorr tthhee wweeiigghhtt ooff tthhee uunniitt bbeeiinngg lliifftteedd.. EEaacchh ooff tthhee ccaabblleess ((cchhaaiinnss oorr sslliinnggss)),, hhooookkss,, aanndd sshhaacckklleess uusseedd ttoo lliifftt tthhee uunniitt mmuusstt bbee ccaappaabbllee ooff ssuuppppoorrttiinngg tthhee eennttiirree wweeiigghhtt ooff tthhee uunniitt.. LLiiffttiinngg ccaabblleess ((cchhaaiinnss oorr sslliinnggss)) mmaayy nnoott bbee ooff tthhee ssaammee lleennggtthh.. AAddjjuusstt aass nneecceessssaarryy ffoorr eevveenn uunniitt lliifftt..
WWAARRNNIINNGG
IImmpprrooppeerr UUnniitt LLiifftt!!
FFaaiilluurree ttoo pprrooppeerrllyy lliifftt uunniitt iinn aa LLEEVVEELL ppoossiittiioonn ccoouulldd rreessuulltt iinn uunniitt ddrrooppppiinngg aanndd ppoossssiibbllyy ccrruusshhiinngg ooppeerraattoorr//tteecchhnniicciiaann wwhhiicchh ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy,, aanndd eeqquuiippmmeenntt oorr pprrooppeerrttyy--oonnllyy ddaammaaggee.. TTeesstt lliifftt uunniitt aapppprrooxxiimmaatteellyy 2244 iinncchheess ((6611 ccmm)) ttoo vveerriiffyy pprrooppeerr cceenntteerr ooff ggrraavviittyy lliifftt ppooiinntt.. TToo aavvooiidd ddrrooppppiinngg ooff uunniitt,, rreeppoossiittiioonn lliiffttiinngg ppooiinntt iiff uunniitt iiss nnoott lleevveell..
WWAARRNNIINNGG
PPrrooppeerr LLiiffttiinngg CCoonnffiigguurraattiioonn RReeqquuiirreedd!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd ccaauussee tthhee uunniitt ttoo ddrroopp wwhhiicchh ccoouulldd rreessuulltt iinn ddeeaatthh,, sseerriioouuss iinnjjuurryy oorr eeqquuiippmmeenntt ddaammaaggee.. UUssee OONNLLYY lliiffttiinngg llooccaattiioonnss ddeessiiggnnaatteedd wwiitthh llaabbeell sshhoowwnn bbeellooww.. DDOO NNOOTT uussee llooccaattiioonnss mmaarrkkeedd wwiitthh ddoo--nnoott--lliifftt llaabbeell.. SSeeee ffoolllloowwiinngg ffiigguurreess ffoorr aacccceeppttaabbllee lliiffttiinngg ccoonnffiigguurraattiioonn,, aanndd rreeffeerr ttoo llaabbeellss oonn tthhee uunniitt..
Figure 6. Lift/Do Not Lift labels
Lift Do Not Lift
24
AC-SVX001A-EN
NNOOTTIICCEE
EEqquuiippmmeenntt DDaammaaggee!!
MMoovviinngg tthhee cchhiilllleerr uussiinngg aa ffoorrkk lliifftt ccoouulldd rreessuulltt iinn eeqquuiippmmeenntt oorr pprrooppeerrttyy--oonnllyy ddaammaaggee.. DDoo nnoott uussee aa ffoorrkk lliifftt ttoo mmoovvee tthhee cchhiilllleerr!!
IImmppoorrttaanntt::
See unit nameplate and/or unit submittal for total shipping weight.
See following figures for unit lifting configuration.
See Dimensions and Weights chapter, or unit submittal, for lifting point locations.
See Center of Gravity section for more information.
Figure 7. 4–point lift configuration — 150, 160, 180 ton units
96” (2438mm) Spreader Bar
Lifting Location 3 (Lifting location 4 located on other side of unit)
Lifting Location 1 (Lifting location 2 located on other side of unit)
Control Panel
IInnssttaallllaattiioonn MMeecchhaanniiccaall
AC-SVX001A-EN
25
Figure 8. 6–point lift configuration — 200, 225, 250, 275 ton units
96” (2438mm) Spreader Bar
96”
(2438mm)
Spreader Bar
Lifting Location 1 (Lifting location 2 located on other side of unit)
Lifting Location 3 (Lifting location 4 located on other side of unit)
Lifting Location 5 (Lifting location 6 located on other side of unit)
Control Panel
Figure 9. 8–point lift configuration — 300 ton units
96” (2438mm) Spreader Bar
Qty 2
Lifting Location 1 (Lifting location 2 located on other side of unit)
Lifting Location 3 (Lifting location 4 located on other side of unit)
Lifting Location 5 (Lifting location 6 located on other side of unit)
Lifting Location 7 (Lifting location 8 located on other side of unit)
Control Panel
IInnssttaallllaattiioonn MMeecchhaanniiccaall
26
AC-SVX001A-EN

Center of Gravity

Figure 10. Center of gravity
END VIEW
(Non-Control Panel End)
Z
Y
CG
SIDE VIEW
X
CG
Control Panel
Table 6. Center of gravity dimensions
Unit Size
CGx
CGy
CGz CGx
CGy
CGz
in
mm
in
mm
in
mm
in
mm
in
mm
in
mm
Standard Length Unit Extended Length Unit
150 93.9 2384 44.2 1122 44.2 1124 128.2 3255 44.0 1118 43.3 1100
165 105.8 2686 44.2 1122 45.9 1166 139.1 3532 44.2 1124 44.9 1142
180 106.0 2691 44.5 1131 45.6 1159 139.6 3545 44.5 1129 44.7 1135
200 114.1 2898 44.1 1121 47.2 1199 147.2 3738 44.2 1124 46.3 1175
225 115.8 2941 44.1 1120 45.2 1148 148.8 3780 44.2 1122 44.4 1129
250 115.1 2924 44.1 1120 45.6 1158 149.0 3785 44.1 1121 44.8 1139
275 127.7 3242 44.0 1117 46.1 1172 162.3 4122 44.2 1122 45.4 1153
300 139.5 3544 44.0 1116 47.1 1197 174.3 4427 43.8 1113 46.4 1178

Isolation and Sound Emission

The most effective form of isolation is to locate the unit away from any sound sensitive area. Structurally transmitted sound can be reduced by elastomeric vibration eliminators. Spring isolators are not recommended. Consult an acoustical engineer in critical sound applications.
For maximum isolation effect, isolate water lines and electrical conduit. Wall sleeves and rubber isolated piping hangers can be used to reduce the sound transmitted through water piping. To reduce the sound transmitted through electrical conduit, use flexible electrical conduit.
State and local codes on sound emissions should always be considered. Since the environment in which a sound source is located affects sound pressure, unit placement must be carefully evaluated. Sound power levels for Stealth chillers are available on request.

Unit Isolation and Leveling

For additional reduction of sound and vibration, install the optional elastomeric isolators.
Construct an isolated concrete pad for the unit or provide concrete footings at the unit mounting points.
Mount the unit directly to the concrete pads or footings.
Level the unit using the base rail as a reference. The unit must be level within 1/4” (6.4 mm) over the entire length and width. Use shims as necessary to level the unit.

Elastomeric Isolators

NNoottee:: See unit submittal, or tables in this section, for
point weights, isolator locations and isolator selections.
1. Secure the isolators to the mounting surface using the mounting slots in the isolator base plate. Do not fully tighten the isolator mounting bolts at this time.
2. Align the mounting holes in the base of the unit with the threaded positioning pins on the top of the isolators.
3. Lower the unit onto the isolators and secure the isolator to the unit with a nut.
4. Level the unit carefully. Fully tighten the isolator mounting bolts.
IInnssttaallllaattiioonn MMeecchhaanniiccaall
AC-SVX001A-EN
27
Figure 11. Elastomeric isolator
0.50 in
1.60±0.25
Mounting molded in neoprene
3.0
2.75
0.38
1/2 - 13NC - 2B
0.56 in
F
E
G
D
A
B
C
Isolator
Max Load
(lb)
Max Deflection
(in)
A B C D E F G
Type
Black-60 1100 0.5 2.5 2.88 0.25 1.13 5.50 4.12 3.38 RDP-3
Brown-61 1500 0.5 3.0 2.75 0.38 1.60 6.25 5.00 4.63 RDP-4
Red-62 2250 0.5 3.0 2.75 0.38 1.60 6.25 5.00 4.63 RDP-4
Green-63 3000 0.5 3.0 2.75 0.38 1.60 6.25 5.00 4.63 RDP-4
Black-64 4000 0.5 3.0 2.75 0.38 1.60 6.25 5.00 4.63 RDP-4

Mounting Locations, Weights, Isolators

See figure below for mounting point location designations.
Figure 12. Mounting point locations (top view)
1 3 5 7
Control panel
9
2 4 6 8 10
NNoottee:: Quantity of isolators varies with unit. See
submittal for actual number required for specific unit.
Point Weights
Table 7. Point weights, units with InvisiSound standard or superior option - I-P (lb)
Unit Size
Point Weights (lb)
1 2 3 4 5 6 7 8 9 10
Standard Length Units
150 1818 1609 1661 1478 1516 1586 731 932
165 1752 1710 1709 1652 1744 1768 941 1099
180 1774 1757 1741 1723 1781 1844 952 1124
200 1777 1823 1744 1651 1714 1698 1501 1636 126 136
IInnssttaallllaattiioonn MMeecchhaanniiccaall
28
AC-SVX001A-EN
Table 7. Point weights, units with InvisiSound standard or superior option - I-P (lb) (continued)
Unit Size
Point Weights (lb)
1 2 3 4 5 6 7 8 9 10
225 1966 1882 2000 1896 1911 1928 1595 1816 113 135
250 2014 1939 2069 1964 1972 1981 1609 1827 111 133
275 1942 1845 1913 1790 1839 1812 1832 2023 870 954
300 1991 1934 2137 2038 2151 2104 1951 2053 741 862
Extended Length Units
150 2268 2021 2036 1850 1687 1881 739 1008
165 2181 1966 2115 2006 2139 2390 768 965
180 2147 1936 2181 2041 2224 2574 771 977
200 2583 2375 2157 2083 1843 2047 736 861 610 693
225 2806 2479 2418 2266 2040 2311 785 969 610 741
250 2844 2519 2497 2342 2112 2384 801 982 597 723
275 2699 2394 2417 2282 2297 2538 994 1204 1013 1133
300 2888 2488 2575 2374 2093 2281 1820 2090 708 802
Table 8. Point weights, units with InvisiSound standard or superior option - SI (kg)
Unit Size
Point Weight (kg)
1 2 3 4 5 6 7 8 9 10
Standard Length Units
150 824 730 753 670 688 719 332 423
165 794 775 775 749 791 802 427 499
180 804 797 790 781 808 836 432 510
200 806 827 791 749 777 770 681 742 57 62
225 892 854 907 860 867 874 723 824 51 61
250 913 879 938 891 894 898 730 828 51 60
275 881 837 868 812 834 822 831 917 395 433
300 903 877 969 924 976 954 885 931 336 391
Extended Length Units
150 1029 916 923 839 765 853 335 457
165 989 892 959 910 970 1084 348 437
180 974 878 989 926 1009 1167 350 443
200 1172 1077 978 945 836 928 334 390 277 314
225 1272 1124 1097 1028 925 1048 356 439 277 336
250 1290 1142 1132 1062 958 1081 363 445 271 328
275 1224 1086 1096 1035 1042 1151 451 546 459 514
300 1310 1128 1168 1077 949 1034 825 948 321 364
Table 9. Point weights, units with InvisiSound ultimate option - I-P (lb)
Unit Size
Point Weights (lb)
1 2 3 4 5 6 7 8 9 10
Standard Length Units
150 1818 1609 1861 1678 1716 1786 731 932
165 1752 1710 1909 1852 1944 1968 941 1099
IInnssttaallllaattiioonn MMeecchhaanniiccaall
AC-SVX001A-EN
29
Table 9. Point weights, units with InvisiSound ultimate option - I-P (lb) (continued)
Unit Size
Point Weights (lb)
1 2 3 4 5 6 7 8 9 10
180 1774 1757 1941 1923 1981 2044 952 1124
200 1777 1823 1944 1851 1914 1898 1501 1636 126 136
225 1966 1882 2200 2096 2111 2128 1595 1816 113 135
250 2014 1939 2269 2164 2172 2181 1609 1827 111 133
275 1942 1845 2113 1990 2039 2012 1832 2023 870 954
300 1991 1934 2337 2238 2351 2304 1951 2053 741 862
Extended Length Units
150 2268 2021 2236 2050 1887 2081 739 1008
165 2181 1966 2315 2206 2339 2590 768 965
180 2147 1936 2381 2241 2424 2774 771 977
200 2583 2375 2357 2283 2043 2247 736 861 610 693
225 2806 2479 2618 2466 2240 2511 785 969 610 741
250 2844 2519 2697 2542 2312 2584 801 982 597 723
275 2699 2394 2617 2482 2497 2738 994 1204 1013 1133
300 2888 2488 2775 2574 2293 2481 1820 2090 708 802
Table 10. Point weights, units with InvisiSound ultimate option - SI (kg)
Unit Size
Point Weight (kg)
1 2 3 4 5 6 7 8 9 10
Standard Length Units
150 824 730 844 761 778 810 332 423
165 794 775 866 840 882 892 427 499
180 804 797 880 872 899 927 432 510
200 806 827 881 839 868 861 681 742 57 62
225 892 854 998 950 957 965 723 824 51 61
250 913 879 1029 981 985 989 730 828 51 60
275 881 837 958 903 925 912 831 917 395 433
300 903 877 1060 1015 1066 1045 885 931 336 391
Extended Length Units
150 1029 916 1014 930 856 944 335 457
165 989 892 1050 1000 1061 1175 348 437
180 974 878 1080 1016 1099 1258 350 443
200 1172 1077 1069 1035 926 1019 334 390 277 314
225 1272 1124 1187 1118 1016 1139 356 439 277 336
250 1290 1142 1223 1153 1049 1172 363 445 271 328
275 1224 1086 1187 1126 1133 1242 451 546 459 514
300 1310 1128 1259 1167 1040 1125 825 948 321 364
Isolator Selections
See Dimensions and Weights chapter for isolator mounting position dimensions.
IInnssttaallllaattiioonn MMeecchhaanniiccaall
30
AC-SVX001A-EN
Table 11. Elastomeric isolator selections
Unit Size
Isolator Position
1 2 3 4 5 6 7 8 9 10
Standard Length Units
150 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Brown 61 Brown 61 - -
165 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Red 62 Red 62 - -
180 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Red 62 Red 62 - -
200 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Black 60 Black 60
225 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Black 60 Black 60
250 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Black 60 Black 60
275 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Brown 61 Brown 61
300 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Brown 61 Brown 61
Extended Length Units
150 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Brown 61 Brown 61 - -
165 Black 64 Black 64 Black 64 Black 64 Black 64 Black 64 Brown 61 Brown 61 - -
180 Black 64 Black 64 Black 64 Black 64 Black 64 Black 64 Brown 61 Brown 61 - -
200 Black 64 Black 64 Black 64 Black 64 Black 64 Black 64 Brown 61 Brown 61 Brown 61 Brown 61
225 Black 64 Black 64 Black 64 Black 64 Black 64 Black 64 Brown 61 Brown 61 Brown 61 Brown 61
250 Black 64 Black 64 Black 64 Black 64 Black 64 Black 64 Brown 61 Brown 61 Brown 61 Brown 61
275 Black 64 Black 64 Black 64 Black 64 Black 64 Black 64 Brown 61 Brown 61 Brown 61 Brown 61
300 Black 64 Black 64 Black 64 Black 64 Black 64 Black 64 Black 64 Black 64 Brown 61 Brown 61

Compressor Mounting Bolt Removal

UUnniittss wwiitthh IInnvviissiiSSoouunndd™™ UUllttiimmaattee OOppttiioonn ((MMooddeell NNuummbbeerr DDiiggiitt 1122 == 33))
For chillers built with InvisiSound Ultimate option, compressor mounting bolts must be removed to assure minimum noise during operation. Use a 24mm socket to remove the (3) M15 x 75mm mounting bolts for each compressor. They are located under compressor mounting feet. See figure below.
IImmppoorrttaanntt::
DO NOT DISCARD MOUNTING BOLTS. Store bolts in the control panel for future use.
All mounting bolts MUST be reinstalled prior to compressor removal or unit move.
NNOOTTIICCEE
EEqquuiippmmeenntt DDaammaaggee!!
FFaaiilluurree ttoo rreeiinnssttaallll bboollttss ccoouulldd ccaauussee sshhiiffttiinngg ooff ppaarrttss aanndd rreessuulltt iinn eeqquuiippmmeenntt ddaammaaggee.. DDoo nnoott rreemmoovvee ccoommpprreessssoorr oorr mmoovvee uunniitt wwiitthhoouutt rreeaattttaacchhiinngg ccoommpprreessssoorr mmoouunnttiinngg bboollttss..
Figure 13. Compressor mounting bolt removal
Compressor
Mounting Bolt
Compressor
Mounting
Foot
Isolator

Drainage

Locate the unit near a large capacity drain for water vessel drain-down during shutdown or repair. Evaporators are provided with drain connections. A vent on top of evaporator waterbox prevents vacuum by allowing air into evaporator for complete drainage. All local and national codes apply.
IInnssttaallllaattiioonn MMeecchhaanniiccaall
Loading...
+ 82 hidden pages