Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and
air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered
equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the
literature and on the tags, stickers, and labels that are attached to the equipment.
May 2017
MMUUAA--SSVVXX000033BB--EENN
Page 2
Introduction
Read this manual thoroughly before operating or servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal safety and the
proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
Indicates a potentially hazardous situation which, if not avoided, could result in
death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in
minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only
accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally
occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the
identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine,
Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon
(HCFCs). Not all refrigerants containing these compounds have the same potential impact to the
environment. Trane advocates the responsible handling of all refrigerants-including industry
replacements for CFCs and HCFCs such as saturated or unsaturated HFCs and HCFCs.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our
customers, and the air conditioning industry. All technicians who handle refrigerants must be
certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in
these service procedures. In addition, some states or municipalities may have additional
requirements that must also be adhered to for responsible management of refrigerants. Know
the applicable laws and follow them.
This document and the information in it are the property of Trane, and may not be used or
reproduced in whole or in part without written permission. Trane reserves the right to revise this
publication at any time, and to make changes to its content without obligation to notify any
person of such revision or change.
All trademarks referenced in this document are the trademarks of their respective owners.
Inspect shipment immediately when received to determine if any damage has occurred to the
crate during shipment.
After the unit has been uncrated, check for any visible damage to the unit. Check motor position
and turn blower wheel to determine if damage has occurred to these critical parts.
If any damage is found, the cosignee should sign the bill of lading indicating such damage and
immediately file claim for damage with transportation company.
Pre-Installation Instructions
Installer Please Note: This equipment has been test fired and inspected. It has been shipped free
from defects from our factory. However, during shipment and installation, problems such as
loose wires, leaks or loose fasteners may occur. It is the installer's responsibility to inspect and
correct any problems that may be found.
When the unit is received and uncrated, check the external data plate and all labels on the unit for
type of gas, electrical, and operational specifications to confirm that these agree with those at
point of installation. If the unit is equipped with an Outdoor Duct Furnace, also check the data
plate and all labels located inside each furnace.
Every rooftop unit will include an informational packet which will include the following: The
blower manual, outdoor duct furnace and evaporative cooler/cooling coil manuals (if applicable
to the unit order), wiring diagram(s), factory installed service convenience options manual (if
applicable to unit order) and special controls/data sheets.
NNoottee:: It is the owner's responsibility to provide any scaffolding or other apparatus required to
perform emergency service or annual/periodic maintenance to this equipment.
1. Open all disconnect switches before installing the unit. Failure to do so may result
in personal injury or death from electrical shock.
2. Failure to comply with the general requirements may result in extensive property
damage, severe personal injury or death.
3. This product must be installed by a licensed plumber or gas fitter when installed
within the Commonwealth of Massachusetts.
4. Do not alter the duct furnace in any way or damage to the unit, severe personal
injury or death will occur.
5. Never service any component without first disconnecting all electrical and gas
supplies to the unit or severe personal injury or death may occur.
6. Insure that all power sources conform to the unit requirements or damage to the
unit may result.
WWAARRNNIINNGG
•The use or storage of gasoline or other flammable vapors or liquids in open containers in the
vicinity of this appliance is hazardous.
•If you smell gas:
– Do not touch electrical switches.
– Extinguish any open flames.
– Immediately call your gas supplier.
•For all units that are equipped with gas fired outdoor duct furnaces (certified by ETL)
installation must be made in accordance with local codes, or in the absence of local codes,
with the latest edition of ANSI Standard Z223.1 (N.F.P.A. No. 54) National Fuel Gas Code. All
of the ANSI and NFPA Standards referred to in these installation instructions are those that
were applicable at the time the design was certified. The ANSI Standards are available from
the American National Standards Institute, Inc., 11 West 42nd Street, New York, NY, 10036 or
www.ansi.org. The NFPA Standards are available from the National Fire Protection
Association, Batterymarch Park, Quincy, MA 02269.
•If installed in Canada, the installation must conform with local building codes, or in the
absence of local building codes, with CSA B149.1 “Installation Codes for Natural Gas Burning
Appliances and Equipment” or CSA B149.2 “Installation Codes for Propane Gas Burning
Appliances and Equipment”. These outdoor duct furnaces have been designed for and
certified to comply with CSA 2.8.
•These units have been designed certified for outdoor use only, and may be located on the
roof of the building or at any convenient location external to the building to be heated.
•Make certain that the power sources conform to the requirements of the heater.
•Follow installation instructions CAREFULLY to avoid creating unsafe conditions. All wiring
should be done and checked by a qualified electrician, using copper wire only. All gas
connections should be made and leak-tested by a suitably qualified individual, per
instructions in this manual.
•Use only the fuel for which the heater is designed (see nameplate). Using LP gas in a heater
that requires natural gas, or vice versa, will create the risk of gas leaks, carbon monoxide
poisoning and explosion.
•Make certain that power source conforms to electrical requirements of heater. Disconnect
power before installing or servicing heater. If power disconnect is out of sight, lock it in open
position and tag it to prevent unexpected application of power. Failure to do so could result in
fatal electric shock.
•Special attention must be given to any grounding information pertaining to this heater. To
prevent the risk of electrocution the heater must be securely and adequately grounded. This
should be accomplished by connecting a grounded conductor from the service panel to the
conduit box of the heater. To ensure proper ground, the grounding means must be tested by
qualifi edfield technician.
•Do not insert fingers or foreign objects into the heater or its air moving device. Do not block
or tamper with the heater in any manner while in operation or just after it has been turned off,
as some parts may be hot enough to cause injury.
•This heater is intended for general heating applications ONLY. It must NOT be used in
potentially dangerous locations such as flammable explosive, chemical-laden or wet
atmospheres.
•In cases in which property damage may result from malfunction of the heater, a backup
system or a temperature sensitive alarm should be used.
•The venting is an integral part of the unit and must not be altered in the field. The Natural
Vented units are equipped with a vent cap which is designed for natural draft venting. Air for
combustion enters the base of the vent cap through a protective grill and products of
combustion are discharged at the upper section of the vent cap. This vent cap is shipped in a
separate carton and should be installed per the Venting section of the Outdoor Rooftop GasFired Duct Furnace Installation and Service Manual. The Power Vented unit has a induced
draft venting system. The combustion air inlet and products of combustion discharge grills
are located in the upper section of the Duct Furnace side access panel.
•A pilot burner plate is provided in the Duct Furnace for access to the pilot burner and ignition
system without removing the burner drawer. Clearance between the external unit and any
obstruction must be sufficient for proper servicing of pull out burner drawer. See Figure 2, p.
11 and Figure 3, p. 11 for this clearance.
•These units are certified for operation on either natural or propane gases. If a unit is to be
installed at an altitude exceeding 2000 feet (610 m) above sea level, derate the unit input of
each duct furnace by 4% for each 1000 feet (305 m) above sea level. Special main burner gas
orifices are required for installations above 2000 feet (610 m).
•In Canada, if unit is to be installed at altitudes of 2000 feet (610 m) to 4500 feet (1372 m), each
duct furnace must have the main burners re-orificed to give 90% of the normal altitude input
rating.
•If the unit was ordered from the factory for high altitude operation, confirm input rating. See
Gas Input Adjustment.
Unless otherwise specified, the following conversions may be used for calculating SI unit
measurements:
Rig unit using either belt or cable slings. Use spreader bars to protect the top of the unit when it
is lifted. See Figure 1, p. 10
On units with a total length of less than 104 inch (2642 mm), excluding evaporative cooler, two
holes are provided in the base rail on each side of the unit. Slide pipes beneath the unit through
these holes and attach rigging to pipes for lifting the unit.
On units with a total length of a 104 inch (2642 mm) or greater, excluding evaporative cooler,
lifting lugs attached to the base rail are provided. Attach rigging to lugs for lifting the unit. For
distance between lifting lugs and total unit lengths, refer to original Submittal Sheets supplied
specified for the unit. Also see Center of Gravity and Weights Sections in this manual.
The presence of chlorine vapors or other corrosive vapors in the combustion air supply for gas-fi
red heating equipment presents a potential corrosive hazard. Chlorine will, when exposed to
flame, precipitate from the compound (usually freon or degreaser vapors) and go into solution
with any condensation that is present in the heat exchanger or associated parts. The result is
hydrochloric acid which will readily attack all metals, including 300 grade stainless steel. Care
should be taken to separate these vapors from the combustion process. This may be done by
wise location of the unit with regard to exhausters or prevailing wind direction.
Before placing rooftop unit in its permanent location, make certain that the roof is capable of
carrying the additional load of this equipment. Check the unit weight given at the end of this
manual.
These units are suitable for installation on combustible flooring.
Single, double and triple duct furnace only models have base rails which can be mounted either
on solid planking or steel channels. All other units installed on field furnished supports must use
the recommended method shown in Mounting on Field Furnished Supports or equivalent.
Roof curb kits for rooftop units are shipped unassembled. Included with the roof curb kit are
insulated or uninsulated curb rails, bolts and screws needed for assembly, sealant, a roll of selfadhering rubber gasketing, and installation instructions. Roof insulation, cant stripping, flashing,
roof felts, caulking, and nails must be furnished by the installer. See , separate roof curb
specifications.
If a variable frequency drive (VFD) has been ordered with the unit, consideration should be made
for the VFD operating temperature range: 14°F to 130°F. For temperatures below 14°F, VFD must
be factory-installed within the VFD Enclosure accessory (Model Digit 22, option 9), or fieldmounted indoors.
Installation must conform with local building codes or in the absence of local codes with the
latest edition of the National Fuel Gas Code ANSI Z223.1 (N.F.P.A. No. 54) National Fuel Gas
Code.
A heat loss study and a complete layout of the system should be made first.
When locating the unit in its permanent location, make certain that the roof is capable of carrying
the additional load of the equipment. CChheecckk tthhee uunniitt nneett wweeiigghhttss sseeccttiioonn ooff tthhiiss mmaannuuaall.
Make certain that clearances are provided for service, minimum clearance to combustible
material and to venting cap. See Figure 2, p. 11 for this information.
Ducts connected to units which do not have either a blower section or a supply plenum must
have a removable access panel in the duct, which is connected to a duct furnace. The duct
openings shall be accessible when the unit is installed in service and shall be of such size that
smoke or reflected light may be observed inside the casing to indicate the presence of leaks in
the heating element. The covers for the panels shall be attached in such manner as to prevent
leaks. Ducts exposed to the outdoors must be insulated and sealed to prevent water from
entering either the unit or building through the duct.
If a single, double or triple duct furnace only unit is connected to a return air duct or any other
inlet air restriction, the appliance shall be installed on the positive pressure side of the air
circulating blower.
Minimum clearances to combustible material are shown on the unit data plate. It is important
that clearances be maintained for servicing the unit (refer to Submittal Insert for service
clearances), and that minimum clearances are provided from the unit (including vent cap, if
Natural Vent model) to combustible material. Clearances around the outside air hood (if unit is so
equipped) must be unobstructed. See Figure 2, p. 11.
Mounting on Field Furnished Supports
Single, double, triple duct furnace only models have base rails which are suitable for mounting
either directly on solid planking or steel channels. Never install the unit on a soft roof where the
rails could sink, reducing clearance between the bottom panel and the roof, or cause damage to
the roofing surface.
NNOOTTIICCEE
WWAARRNNIINNGG
MUA-SVX003B-EN
13
Page 14
IInnssttaallllaattiioonn
All other models must use the following method or an equivalent when unit supports are field
furnished: Each section of the Rooftop unit must be supported, which includes supports located
at both ends. If the unit consists of a High CFM Blower section, a DX Coil, a Duct Furnace and a
Supply Plenum, five supports are required. See Figure 4, p. 14.
Figure 4. Mounting On Field-Furnished Supports
Mounting on Roof Curb
Assemble and install roof curb per Roof Curb Installation Instructions. See Figures Figure 5, p.
15, Figure 6, p. 21, Figure 7, p. 21, and Figure 8, p. 22 for roof opening sizes, distance between
Note: Dimensions listed apply to both insulated and uninsulated roof curb types. Roof curb kit part numbers listed are the insulated roof curb type; contact customer service for
All venting installations shall be in accordance with the latest edition of Part 7, “Venting of
Equipment”, of the National Fuel Gas Code, ANSI Z223.1 or applicable provisions of local
building codes.
The Natural Vented units are equipped with a vent cap which is designed for natural draft
venting. Air for combustion enters the base of the vent cap through a protective grill and
products of combustion are discharged at the upper section of the vent cap. TThhiiss vveenntt ccaapp iiss
sshhiippppeedd iinn aa sseeppaarraattee ccaarrttoonn aanndd sshhoouulldd bbee iinnssttaalllleedd ppeerr tthhee VVeennttiinngg sseeccttiioonn ooff tthhee
OOuuttddoooorr RRooooffttoopp GGaass--FFiirreedd DDuucctt FFuurrnnaaccee IInnssttaallllaattiioonn aanndd SSeerrvviiccee MMaannuuaall..
The Power Vented unit has a induced draft venting system. The combustion air inlet and
products of combustion discharge louvers are located in the upper section of the Duct Furnace
side access panel. NNeevveerr llooccaattee tthheessee uunniittss iinn aann aarreeaa wwhheerree tthhee flfluuee pprroodduuccttss ddiisscchhaarrggee
oouuttlleett mmaayy bbee ddiirreecctteedd aatt aannyy ffrreesshh aaiirr vveennttss.. SSeeee tthhee OOuuttddoooorr RRooooffttoopp GGaass--FFiirreedd DDuucctt
FFuurrnnaaccee IInnssttaallllaattiioonn aanndd SSeerrvviiccee MMaannuuaall ffoorr iinnssttaallllaattiioonn aanndd sseerrvviicciinngg rreeqquuiirreemmeennttss..
Duct Connections
All ductwork must be properly supported so that no strain is put on the unit. Do not alter or bend
the discharge duct flanges supplied on your furnace/air handler.
Ducts connected to units which do not have either a blower section or a supply plenum must
have a removable access panel in the duct which is connected to a duct furnace. The duct
openings shall be accessible when the unit is installed in service, and shall be of such size that
smoke or reflected light may be observed inside the casing to indicate the presence of leaks in
the heating element. The covers for the panels shall be attached in such a manner as to prevent
leaks. Ducts exposed to the outdoors must be insulated and sealed to prevent water from
entering either the unit or building through the duct.
If a single, double or triple duct furnace only unit is connected to a return air duct, or any other
inlet air restriction, the appliance shall be installed on the positive pressure side of the air
circulating blower.
When connecting return air duct to Standard or High CFM cabinets, attach duct to return air
opening flange when no dampers are used. Otherwise, if dampers are used, attach return air duct
around collar at bottom of damper assembly. Also refer to the Submittal Data Sheets specified
for your unit.
When connecting supply air duct to Supply Plenum, attach duct to supply air opening flange
when no dampers are used. Otherwise, if dampers are used, attach supply air duct around collar
at bottom of damper assembly.
IInnssttaallllaattiioonn
WWAARRNNIINNGG
Gas Piping†
MUA-SVX003B-EN
All gas piping must be installed in accordance with local codes. It is required that a ground union
be installed adjacent to the gas valve of each duct furnace, and a ground union be installed just
external of each duct furnace for unit servicing. On vertical runs, a drip leg should be provided
upstream of any control manifold. A gas shutoff valve should be, or may be required by local
codes, installed upstream of the external ground union for each duct furnace. A 1/8 inch N.P.T.
plugged tapping, accessible for test gauge connection, must be installed immediately upstream
of the unit gas supply connection.
It is recommended that the gas piping not be installed through the bottom of the duct furnace
bottom panel. If piping must penetrate the duct furnace bottom panel, it must be sealed to
prevent water leakage.
Gas piping must be installed to allow for removal of burner drawer for unit maintenance.
The gas line should be supported so that no strain is placed on the unit. Pipe compounds which
are not soluble to liquid petroleum gases must be used on threaded joints.
The appliance and its individual shutoff valve must be disconnected from the gas supply piping
system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa).
The appliance must be isolated from the gas supply piping system by closing the individual
manual shutoff valve during any pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 psi (3.5 kPa).
For additional gas piping information, including pipe sizing and drip leg installation, refer to
Outdoor Rooftop Gas-Fired Duct Furnace Installation and Service Manual.
For additional piping information, refer to the National Fuel Gas Code Z233.1 (latest edition).
Before any connection is made to an existing line supplying other gas appliances, contact the
local gas company to make certain that the existing line is of adequate size to handle the
combined load.
Check all connections for leaks with soap solution.
NNoottee:: *Also refer to Outdoor Duct Furnace Installation Manual supplied with your unit.
EElleeccttrroonniicc:: On units equipped with electronic modulating control, follow control manufacturer’s
installation instructions for sensing of outlet air temperature.
All electrical connections must conform to the latest edition of ANSI/NFPA No. 70 National
Electrical Code and applicable local codes. In Canada, to the Canadian Electrical Code, Part I CSA
Standard C22.1.
The rooftop packaged unit is wired at the factory and ready to be connected. Actual unit wiring
will differ according to the options chosen. Each unit is shipped with its own wiring diagram;
refer to this wiring diagram for all electrical connections to the unit.
All electrical connections, line voltage and thermostat, are made in the Electrical Cabinet (See
Figure 10, p. 26). Line voltage connections are made at the High Voltage Terminal Block.
Thermostat connections are made at the Main Connection Board (See Figure 10, p. 26).
Figure 9. Standard Blower Cabinet, Single Duct Furnace with Supply Plenum & Various
Options Shown
MUA-SVX003B-EN
25
Page 26
IInnssttaallllaattiioonn
Figure 10. Electrical Cabinet
Outdoor line voltage conduits leading into the unit should be installed to prevent rain from
wetting any high voltage wire. Locate the thermostat in accordance with the instructions
supplied with the thermostat. All field wiring must have a minimum temperature rating of 185°F
(85°C). Control wiring must be a minimum of 18 gauge wire size. Control wiring must be sized for
the length of run.
Locate line voltage disconnect box per local codes. If mounting the disconnect box to the unit,
never mount it to an unit access panel. Possible locations include the front of the blower or filter
section, the outdoor air hood or the rear of the supply plenum (See Figure 11, p. 27). Electrical
conduit must be routed so as not to interfere with removal of any access panel.
See Coil Installation/Maintenance Manual for Refrigerant Piping, Liquid and Suction Line
Components, Refrigerant Charging and Thermal Expansion Valve Adjustment. Remove coil
cabinet access door located next to blower section. Cut holes in fixed door to allow suction and
liquid line passage. Provide weatherproof seal around suction and liquid lines at piping plate
when installed.
The DX Coil has a 300 ft/min. (1.524 m/s) minimum and a 600 ft/min. (3.048 m/s) maximum
velocity through the coil requirement. This is due to prevention of coil icing or condensate blowoff. To calculate the velocity through the coil, apply the following formula:
Condensate Drain piping must have a P-trap in line immediately downstream of drain pan
connection, external to the unit, to prevent possible outside air leakage into unit. The P-trap shall
be of sufficient differential to overcome negative pressure of the indoor air blower. A minimum
height difference of 2 inch is required (See Figure 12, p. 28). Before unit operation begins, the Ptrap must be primed with either water (summer) or glycol (winter).
MUA-SVX003B-EN
27
Page 28
H
Total
Height
of Trap
Total Height Of Trap = X+ H + (1-1/2 X Pipe Diameter)
(without Insulation)
Unit
Housekeeping
Pad
X
IInnssttaallllaattiioonn
Chilled Water Coil Equipped Units (Optional)
See Coil Installation/Maintenance Manual for General Coil Piping Recommendations. Remove
the coil cabinet door and cut holes in door to allow chilled water piping passage. Provide
weatherproof seal around chilled water pipes at piping plate when installed.
The Chilled Water Coil has a 600 ft/min (3.048 m/s) maximum velocity through the coil
requirement. This is due to prevention of condensate blow-off. To calculate the velocity through
the coil apply the following formula:
Condensate Drain piping must have a P-trap in line immediately downstream of drain pan
connection, external to the unit, to prevent possible outside air leakage into unit. The P-trap shall
be of sufficient differential to overcome negative pressure of the indoor air blower. A minimum
height difference of 2 inch is required (See Figure 12, p. 28). Before unit operation begins, prime
P-trap with either water (summer) or glycol (winter).
Figure 12. Drain Pan Connection
Evaporative Cooler Equipped Units (Optional)
Refer to Evaporative Cooler Installation and Service Manual for water and electrical connections.
28
MUA-SVX003B-EN
Page 29
Operation
General Information
Refer to Outdoor Rooftop Gas-Fired Duct Furnace Installation and Service Manual for specific
information regarding the heating operation of this unit.
All units are equipped with a intermittent pilot ignition system. The pilot is lit and extinguished
each cycle of unit heating operation.
On natural gas units, the ignitor will continue to spark and pilot gas will continue to flow until the
pilot flame is proven.
LP (propane) units are equipped with 100% lockout. The lockout function shuts off the main and
pilot gas valves if the pilot gas fails to ignite within 90 seconds of the onset of trial for ignition.
The gas control system operates at 24 VAC and is supplied by a step-down transformer found in
the electrical cabinet that will match the unit line voltage specified. See Figure 10, p. 26 for unit
controls location.
Do not use a thermostatic fan control switch when either two-stage fi ring or modulated gas
controls are used.
Gas Control System
The standard unit comes equipped for single stage operation. Unit heating operation is
accomplished at full input. Each duct furnace is equipped with an individual ignition control
system which consists of the following components: ignition control module, gas valve and pilot
burner.
The iiggnniittiioonn ccoonnttrrooll mmoodduullee is the heart of the ignition control system. This control initiates all
gas flow, provides means to light the pilot burner, proves and monitors the pilot burner
operation.
The ggaass vvaallvvee consists of two operators which provide gas to the pilot and main burners. Both
operators are energized and de-energized by the ignition control module each heating cycle.
The ppiilloott bbuurrnneerr includes an ignitor and flame sense probe. The ignitor provides the spark,
originating at the ignition control module, to light the pilot. The ignition control module proves
and monitors the pilot flame through the flame sensing probe.
All units follow the same basic sequence of operation and is as follows:
1. Thermostat calls for heat. PPoowweerr vveenntteedd uunniittss oonnllyy: Drafter relay energizes drafter with call
for heat.
2. Ignition control module energizes pilot operator of gas valve and initiates spark at ignitor of
the pilot burner.
3. Pilot burner ignition is proven to the ignition control by the flame sense probe and sparking
of the ignitor is discontinued.
4. Once pilot burner operation is proven, the ignition control module energizes the main burner
operator of the gas valve, allowing gas flow to the main burners. PPoowweerr vveenntteedd uunniittss oonnllyy:
In addition, drafter operation must be proven by drafter end switch before ignition control
module energizes main burner operator of gas valve.
5. Approximately 60 seconds after the main burners light the fan time delay initiates fan
operation.
6. Thermostat is satisfied and call for heat is removed. PPoowweerr vveenntteedd uunniittss oonnllyy: Drafter relay
de-energizes drafter with removal of call for heat.
7. Ignition control module de-energizes pilot and main burner operators of the gas valve,
ceasing all gas flow.
8. Approximately two minutes after satisfying the thermostat, fan operation ceases.
MUA-SVX003B-EN
29
Page 30
OOppeerraattiioonn
Optional Gas Controls
These units are available with optional gas controls which will give either multi-stage or
modulating operation. The sequence of operation of those units equipped with these optional
gas controls differs only at what rate each duct furnace’s main burners ignite and operate at or
the order of duct furnace firing for those units equipped with two or three duct furnaces.
TTwwoo SSttaaggee UUnniittss: Two stages of heating; first stage is 40% of full rate, second stage is 100% of
full rate. Main burner ignition is at first stage only.
TThhrreeee SSttaaggee UUnniittss: Dual duct furnace models: First furnace is equipped with two stage heating;
second furnace is equipped with a single stage heating but fired independently giving three
stages of heating. Triple duct furnace models: Each duct furnace is equipped with single stage
heating but fired independently, giving three stages. Each stage is 33% of the unit’s full input
rate. Duct furnace one will always light first and disengage last.
FFoouurr SSttaaggee UUnniittss: Dual duct furnace models only. Each duct furnace is equipped with two stage
heating but fired independently, giving four stages. Each stage is 25% of the units full input rate.
Duct furnace one will always light first and disengage last.
SSiixx SSttaaggee UUnniittss: Triple duct furnace models only. Each duct furnace is equipped with two stage
heating but fired independently giving six stages. Each stage is 16.5% of the units full input rate.
Duct furnace one will always light first and disengage last.
EElleeccttrroonniicc MMoodduullaattiioonn UUnniittss: These units are equipped with a electronic modulating control
which provides unit fi ring capabilities of 40 to 100% of the units full input rate. This control is
found in the gas train downstream of the gas valve and allows main burner ignition only at the
maximum rate. A thermostat with remote setpoint adjustment modulates the gas input.
Muullttii--SSttaaggee ww// EElleeccttrroonniicc MMoodduullaattiioonn UUnniittss: These dual and triple duct furnace models are
equipped with an electronic modulating control on duct furnace one and single or two stage
heating on each successive duct furnace. Furnace one (modulated) will fire first and disengage
last. Additional stages of heat will engage after furnace one has fired at maximum modulation
capability for the duration of the delay setting. The amount of modulation and each stage size
depends upon unit size and the number of stages. See following chart:
Static Pressure through the unit should never exceed 2.0 inch W.C. (0.50 kPa). The standard unit
is operated at a temperature rise range of 20 to 60°F (11 to 33°C). The high temperature rise
model is operated at a temperature rise range of 60 to 90°F (33 to 50°C).
IImmppoorrttaanntt:: It is important that the final temperature leaving the unit does not exceed 160°F (71°
C). When final air throughput adjustments are being made, a check of the discharge
air temperature should be made after unit has operated for 15 to 20 minutes.
IImmppoorrttaanntt:: At initial unit installation, unit should be started momentarily to confirm proper
blower wheel rotation as the unit will deliver some air with the blower wheel running
backwards.
Two basic air control systems can be used to deliver conditioned air to the occupied space:
intermittent or constant fan operation.
IInntteerrmmiitttteenntt FFaann OOppeerraattiioonn: The unit employs an air control system which utilizes a fan time
delay relay to operate the fan while heating and the thermostat while cooling. Refer to unit wiring
diagram.
CCoonnssttaanntt FFaann OOppeerraattiioonn: The unit can be wired to give an air control system which constantly
circulates air through the unit and occupied space with constant fan operation. Refer to unit
wiring diagram.
IImmppoorrttaanntt:: Check blower belt tension. Proper belt tension is important to the long life of the belt
and motor. Proper belt tension will allow the belt to be depressed 1⁄2 inch to 3⁄4 inch.
It is important that the blower motor and the blower wheel pulleys be in good alignment, with
the motor and blower shafts parallel.
Belt tension must be adjusted to give approximately 3/4 inch deflection of the belt when finger
pressure is applied to the middle of the belt (See Figure 13). Small changes in this tension may
be necessary for optimum operation. Belts will stretch over a period of time, requiring an
adjustment to this tension. See MAINTENANCE section for belt and pulley adjustments.
Figure 13. Belt Tension Guide
MUA-SVX003B-EN
These units are set at the factory for the RPM required to meet the air volume (CFM) and external
static pressure ordered. If the estimated external static is incorrect, or changes were made to the
duct system, the blower RPM may need to be changed.
Both the Standard and High CFM Blowers use motors which are equipped with adjustable pitch
pulleys. After removing belt(s), loosen the pulley set screw and remove the key, turn adjustable
half of a pulley clockwise to increase RPM, or counter-clockwise to decrease RPM. Insert key,
31
Page 32
OOppeerraattiioonn
Lighting
tighten set screw and replace belt(s). Adjust belt tension to give 1⁄2 inch to 3⁄4 inch belt play when
depressed.
After changing blower RPM, confirm blower motor full load amps have not been exceeded. See
motor data plate for maximum full load amps.
(Refer to Outdoor Duct Furnace Manual for all heating functions - general comments are as
follows.) Purge the gas line to the unit of air before attempting to light the pilot. Check for gas
leaks.
This unit is equipped with an intermittent ignition system. A lighting instruction is attached to the
unit. To set the intermittent ignition system into operation proceed as follows:
1. Turn on the gas valve(s) main manual valve.
2. Turn on electrical power. The unit is now under thermostat control.
3. Set thermostat to highest level. This will initiate the sequence of operation detailed in the Gas
Control System section. Check main burners for operation.
4. Set thermostat to lowest level. This will interrupt power to the ignition control and shut off
gas. Confirm pilot and main burners have been extinguished.
5. Set the thermostat to the desired setting.
For complete unit shutdown, proceed as follows:
1. Turn off the gas valve(s) main manual valve.
2. Set thermostat to lowest setting.
3. Shut off all electric power.
Gas Input Adjustment
When shipped from the factory, all units are equipped for the average heat content of the gas
which is stamped on the unit rating plate.
For an accurate input rate measurement the following meter method should be used to
determine unit input rate. If the meter method is not possible, a manifold pressure check should
be made.
1. Obtain the heating value of the gas from the local utility or gas dealer. This should be in units
of Btu/ft
3
(MJ/m3).
2. Determine the gas flow rate as shown in the following example. EXAMPLE: Assume this unit
has a input rate of 250,000 Btu/hr (73.2 kW) and the heating value of the gas is 1000 Btu/ft
3
(37.3 MJ/m3).
Gas Flow Rate=
250,000 Btu/hr
1000 Btu/ft
=
4.17 ft
3
/min
3
x 60 min/hr
3. Before determining the gas flow rate to the unit, all other gas appliances connected to the
same meter must be turned off.
4. Fire unit according to instructions.
5. After approximately 15 minutes of unit operation, determine volume of gas used in five
minutes of unit operation. For the Example above the unit should use 4.17 ft
3
20.8 ft
(1.97 L/s x 5 min x 60 s/min = 591L) of gas. Minor input adjustments can be made by
3
/min x 5 min or
removing pressure regulator cap and turning regulator clockwise to increase input or counter
clockwise to decrease input. Any appreciable adjustment in input rate should be made by
reorificing.
2. Install a 1⁄8 inch pipe connection in the tapped hole provided in the gas valve body near outlet
of the valve.
3. Attach manometer to 1⁄8 inch pipe connection by means of a rubber hose.
4. Fire unit according to instructions and observe the pressure and confirm it matches the unit
manifold pressure from the unit rating plate.
5. Small variations in the manifold pressure can be made by means of the gas valve pressure
regulator. Remove pressure regulator cap and turn regulator clockwise to increase pressure
or counter-clockwise to decrease pressure.
Pilot Adjustment
1. Disconnect wire from terminal marked MV at gas valve.
2. Provide call for heat.
3. Pilot adjustment is found on the gas valve. Remove pilot adjustment cap.
4. Adjust the pilot screw to provide properly sized flame.
5. A proper pilot burner flame is a soft steady flame that envelopes 3⁄8 to 1⁄2 inch (9.5 to
12.7mm) of the flame sense probe tip.
6. Replace the pilot adjustment cap.
7. Reconnect wire to terminal MV.
Primary Air Shutter Adjustment
After the unit has been in operation for at least 15 minutes, adjust the primary air flow to the
burners. Turn the friction-locked manually rotated air shutters clockwise to close, counter
clockwise to open. For correct air adjustment, close the air shutter until yellow tips in the flame
appear. Then open the air shutter to the point just beyond the position where yellow tipping
disappears.
Controls
PPrriimmaarryy LLiimmiitt CCoonnttrrooll:: The primary limit control is a factory installed component surface
mounted in the inlet airstream at the end of the heat exchanger. When the temperature reaches
MUA-SVX003B-EN
33
Page 34
OOppeerraattiioonn
the limit set point, normally caused by insufficient air throughput, all gas is shutoff. The limit
control has an automatic reset and once the unit has cooled, it will reset itself. This is a safety
control and if cycling on the primary limit is noted, corrective action must be taken. See unit
wiring diagram for electrical location. This control must never be bypassed. Upon completion of
unit installation, the primary limit must be checked for proper operation. This can be
accomplished by removing power to the indoor air blower and a call for heat.
DDrraaffttoorr EEnndd SSwwiittcchh ((PPoowweerr vveenntteedd uunniittss oonnllyy)):: This switch is located at the end of the draftor
motor and is integral to the motor. The switch, which is normally open, will close when draftor
motor attains the minimum speed for proper combustion allowing main burner operation. The
pilot burner will light without a proven draftor end switch. See unit wiring diagram for electrical
location.
CCllooggggeedd FFiilltteerr SSwwiittcchh::(Optional) The clogged filter switch monitors the pressure differential
across the air filters. If this pressure differential becomes too great, the switch will alert of this
condition. At this point the air filters must either be cleaned or replaced. The switch will reset
itself.
FFiirreessttaatt:: (Optional) Located in either the return airstream, the supply airstream, or both, this
control monitors temperatures with set points which are field adjustable. If the temperature
exceeds the set point, the control will cease unit operation. To resume unit operation, a manual
reset of this control is required.
FFrreeeezzeessttaatt:: (Optional) Located in either the return airstream, the supply airstream, or both, this
control monitors temperatures with set points which are field adjustable. If the temperature does
not exceed the set point, the control will cease unit operation.
34
MUA-SVX003B-EN
Page 35
Start-Up
Before starting the unit, use the “Gas Equipment Start Up Sheet” (located at the end of this
manual) and read the Outdoor Duct Furnace Manual entirely in conjunction with the procedures
outlined below to ensure that the unit is completely and properly installed and ready for start up.
1. Inspect all wiring connections; connections should be clean and tight. TTrraaccee cciirrccuuiittss ttoo
iinnssuurree tthhaatt aaccttuuaall wwiirriinngg aaggrreeeess wwiitthh tthhee ““aass wwiirreedd”” ddiiaaggrraammss pprroovviiddeedd wwiitthh tthhee uunniitt.
Information in the wiring diagram title block should match the data appearing on the unit
nameplate.
2. Lubricate all electrical motors according to the manufacturer’s recommendations.
3. Verify that the system switch is in the OFF position.
4. Check unit supply voltage to ensure that it is within the utilization range.
5. Inspect the interior of the unit; remove any debris or tools which may be present.
1. Close the unit disconnect switch which provides power to the unit.
IImmppoorrttaanntt:: High voltage is present in some areas of the unit (primarily the main electrical
cabinet) with the unit disconnect switch closed. Failure to exercise caution when
working in the presence of energized electrical components may result in injury or
death from electrical shock.
1. Close the unit disconnect switch which provides power to the unit.
IImmppoorrttaanntt:: High voltage is present in some areas of the unit (primarily the main electrical
cabinet) with the unit disconnect switch closed. Failure to exercise caution when
working in the presence of energized electrical components may result in injury or
death from electrical shock.
2. Set the thermostat/switching subbase as indicated below:
a. Position the cooling system switch at either COOL or AUTO;
b. Set the fan switch to AUTO.
MUA-SVX003B-EN
35
Page 36
SSttaarrtt--UUpp
3. Place the system switch in the ON position.
NNoottee:: With the thermostat calling for cooling, unit operation is automatic.
FFiinnaall CChheecckkoouutt
Run the unit sequentially through its stages of heating and cooling. Once proper unit operation is
verified, perform these final steps:
1. Inspect unit for debris and/or misplaced tools and hardware.
2. Be sure all gas valves and controls are in the operating position if the unit will be operating
immediately.
3. Cycle unit on all safety controls to verify proper unit operation.
4. Confirm proper operating control (thermostat or ductstat) operation by cycling unit.
To check gas tightness of the safety shut-off valves, turn off the manual valve upstream of the
appliance combination control. Remove the 1/8 inch pipe plug on the inlet side of the
combination control and connect a manometer to that tapping. Turn the manual valve on to
apply pressure to the combination control. Note the pressure reading on the manometer, then
turn the valve off. A loss of pressure indicates a leak. If a leak is detected, use a soap solution to
check all threaded connections. If no leak is found, combination control is faulty and must be
replaced before putting appliance back in service.
NNoottee:: Gas tightness of the safety shutoff valves must be checked on at least an annual basis.
These units have been developed for outdoor installation. Maintenance is required and it is
suggested that the following unit servicing and inspections be performed routinely. Also read in
entirety and refer to the Outdoor Duct Furnace Manual for maintenance requirements.
Inspect area near unit to be sure that there is no combustible material located within the
minimum clearance requirements (See Figure 2, p. 11). Service panels provide easy access to the
gas controls (located in duct furnace section), the blower compartment, the electrical cabinet and
the supply plenum. To remove the service door from any of these compartments, refer to access
panel removal section in beginning of this manual.
The pilot burner can be serviced by removing the pilot plate from the main burner drawer
assembly.
1. Shut off the gas supply at the gas shutoff valve and electrical power to the unit.
2. Break the union upstream of duct furnace gas valve and loosen the union external to the
furnace; swing downward the piping to clear drawer.
3. Disconnect duct furnace gas valve wiring taking note of all wire locations. Disconnect ignitor
and flame sensing probe wires at ignition control module and any other wires.
4. Remove the locking screws holding the burner drawer assembly in position.
5. Slide the burner drawer out of the duct furnace.
6. Removal of burners is accomplished by sliding burner towards manifold, compressing
locating spring, until the rear of the burner clears slot in back of burner drawer.
7. With burner drawer removed from duct furnace, inspect the inside surfaces of the heat
exchanger. Wire brush if necessary.
WWAARRNNIINNGG
WWAARRNNIINNGG
MUA-SVX003B-EN
37
Page 38
MMaaiinntteennaannccee
8. Remove any dirt, dust or other foreign matter from the burners using a wire brush and/or
compressed air. Insure all parts of the burner are unobstructed. Inspect and clean pilot burner
if necessary.
9. Reassemble the duct furnace by replacing all parts in order.
10. Light unit per the unit lighting instructions.
11. Check the burner adjustment. See the Primary Air Adjustment section of this manual.
12. Check all gas control valves and pipe connections for leaks.
13. Check the operation of the duct furnace gas valve by lowering the setting of the thermostat,
stopping the operation of the duct furnace. The duct furnace gas valve should close,
extinguishing the pilot and main burner flames.
14. Inspect and service the blower section of the system.
RRoouuttiinnee MMaaiinntteennaannccee
The unit should be thoroughly checked before the start and at the end of each heating and
cooling season.
1. Motors and belts should be inspected.
2. Tighten belts if loose.
3. Check and clean DX or Chilled Water coil twice yearly, if unit is so equipped per
manufacturer’s service manual. Chilled Water coil must be winterized at beginning of heating
season (i.e. drain water from coil per manufacturer’s instructions).
4. Check air throughput at beginning of heating season to confirm unit operation is within the
specified temperature rise range.
5. At beginning of heating season clear Condensate Drain Pan and P-trap of water if unit is
equipped with DX or Chilled water coil. Clean out drain pan and fill P-trap with a non-toxic
glycol solution.
6. Evaporative cooler must be cleaned and maintained per manufacturer’s instruction
frequently during the operating season.
7. Inspect Control Dampers during periodic maintenance. Damper pivot points should be
cleaned to ensure free damper operation.
8. Blower wheels should be checked periodically for dirt build-up on blades. Clean as required.
Filters
38
It is recommended that air filters be changed or cleaned at least four times a year. More frequent
attention to filters is required if the air being handled by the unit is unusually dirty. Air flow
reduction, caused by the dirty air filters, will increase the discharge air temperature and may
cause unit cycling on the primary limit.
Filters (by others) should be serviced regularly and changed or washed when necessary to
maintain the required air throughput. In a dusty environment, filters may clog up in less than one
month.
Table 3. High CFM Blower Air Filter Size Requirements
Number of Filters Required
Unit Input
16 x 20 (in)20 x 20 (in)
200 MBtuh (58.6 kW)
8
MUA-SVX003B-EN
Page 39
Table 3. High CFM Blower Air Filter Size Requirements (continued)
MMaaiinntteennaannccee
Unit Input
Number of Filters Required
16 x 20 (in)20 x 20 (in)
250 MBtuh (73.2 kW)
300 MBtuh (87.9 kW)
350 MBtuh (102.6 kW)
400 MBtuh (117.2 kW)
500 MBtuh (146.5 kW)
600 MBtuh (175.8 kW)
700 MBtuh (205.1 kW)
800 MBtuh (234.4 kW)
1,200 MBtuh (351.6kW)
84
84
84
84
Table 4. Standard CFM Blower Air Filter Size Requirements
Number of Filters Required
Unit Input
16 x 20 (in)20 x 20 (in)
100 MBtuh (29.3 kW)
150 MBtuh (44.0 kW)
200 MBtuh (58.6 kW)
250 MBtuh (73.2 kW)
300 MBtuh (87.9 kW)
350 MBtuh (102.6 kW)
400 MBtuh (117.2 kW)
500 MBtuh (146.5 kW)
600 MBtuh (175.8 kW)
700 MBtuh (205.1 kW)
800 MBtuh (234.4 kW)
4
4
42
42
42
42
8
12
8
12
12
4
4
6
4
6
Air Blower
Belt Tension Adjustment Standard CFM Blower belt tension can be adjusted by loosening motor
mounting bolts marked A (See Figure 14). To tighten belt, slide motor down motor mounting
bracket and re-fasten motor to mounting bracket.
High CFM Blower belt(s) tension can be adjusted by first loosening motor mounting plate bolts
marked A (See Figure 14). To tighten belt tension, turn belt tension adjustment screws marked B
(See Figure 14) counter-clockwise. To loosen belt tension, turn clockwise. Once belt tension has
been adjusted, re-fasten motor mounting plate bolts.
Blower RPM Adjustment
1. Loosen and remove belt(s).
2. Match driver pulley to one found in Figure 15.
3. Loosen setscrew(s) marked A.
4. If driver pulley is equipped with external key, marked B, remove.
MUA-SVX003B-EN
39
Page 40
MMaaiinntteennaannccee
5. Adjust driver pulley pitch diameter for desired speed by opening (slower) or closing (faster)
moving parts by half or full turns. Do not open sheave past point where flange projects past
the hub end.
6. If driver pulley is equipped with external key, marked B, replace.
7. Tighten setscrew(s) marked A.
8. Replace and retension belt(s).
9. Realign drive if necessary.
Figure 14. Blower Belt Tension
40
MUA-SVX003B-EN
Page 41
Figure 15. Blower RPM Adjustment
MMaaiinntteennaannccee
MUA-SVX003B-EN
41
Page 42
Troubleshooting
For troubleshooting of the duct furnace, refer to Indoor Rooftop Gas-Fired Duct Furnace
Installation and Service Manual. For Evaporative Cooler/Cooling Coil equipped units, refer to
these specific manuals for additional troubleshooting guides.
For additional troubleshooting, see following Troubleshooting Guide.
Troubleshooting Guide — Air Blower
ProblemProbable
Cause
Noise
Blower Wheel
Hitting Scroll Side
Blower Wheel
Hitting Cutoff
Drive
Solution
1. Blower Wheel not centered in blower
housing.
2. Damaged blower housing.
3. Damaged blower wheel.
4. Shaft loose in blower bearing.
5. Blower Wheel loose on shaft.
6. Blower bearing loose in bearing support.
1. Cutoff not secure in blower housing.
2. Cutoff damaged.
3. Cutoff improperly positioned.
1. Pulley not tight on shaft (motor and/or
blower wheel).
2. Belts too loose. Adjust for belt stretching
after 48 hours of operation.
3. Belts too tight.
4. Belts wrong cross section.
5. Belts not matched in length on multi-belt
drive.
6. Variable pitch pulleys not adjusted so each
pulley has same pitch diameter (multi-belt
drives).
7. Misaligned pulleys.
8. Belts worn.
9. Motor or motor base loose.
10.Belts oily or dirty
11.Improper drive selection
Bearing
Shaft Seal Squeal
42
1. Defective bearing.
2. Needs lubrication.
3. Loose on bearing support.
4. Loose on shaft.
5. Seals misaligned.
6. Foreign material in bearing.
7. Worn bearing.
8. Fretting corrosion between inner race and
shaft.
1. Needs lubrication.
2. Misaligned.
MUA-SVX003B-EN
Page 43
TTrroouubblleesshhoooottiinngg
ProblemProbable
Cause
Blower Wheel
Housing
Electrical
Shaft
Solution
1. Loose on shaft
2. Defective blower wheel. Do not run blower.
Contact manufacturer.
3. Unbalanced.
4. Worn as a result of contact with abrasive or
corrosive material.
1. Foreign material in housing.
2. Cutoff of other part loose (rattling during
operation).
1. Lead-in cable not secure.
2. AC hum in motor or relay
3. Starting relay chatter.
4. Noisy motor bearings.
5. Single phasing a 3–phase motor.
1. Bent.
2. Undersized. May cause noise at blower
wheel, bearings or pulley.
3. If more than two bearings are on a shaft,
they must be properly aligned.
CFM Low Insufcient Air
Flow
High Air Velocity
Obstruction in High
Velocity Air Stream
may cause Rattle
or Pure Tone
Whistle
Pulsation or Surge
Rattles and/or
Rumbles
Blower
1. Duct work too small for application.
2. Blower selection too small for application.
3. Registers or grilles too small for application.
4. Cooling coil with insufcient face area for
application.
1. Dampers.
2. Registers.
3. Grilles.
4. Sharp elbows.
5. Sudden expansion in duct work.
6. Sudden contraction in duct work.
7. Turning vanes.
1. Blower too large for application.
2. Ducts vibrate at same frequency as blower
pulsations.
1. Actual system is more restrictive than
expected.
2. Dampers closed.
3. Registers closed.
4. Leaks in supply duct.
Dirty or clogged.
1. Obstruction near unit outlet.
2. Sharp elbows near unit outlet.
3. Improperly designed turning vanes.
4. Projections, dampers or other obstructions
in part of duct system where air velocity is
high.
1. Oversized duct work.
2. Access door open.
3. Registers or grilles not installed.
4. Filters not in place.
5. System resistance lower than anticipated.
BlowerBlower RPM is too great.
Blower Does Not
Operate
Installation
Unit
Troubleshooting Guide — Electric Motors
ProblemProbable
Motor
Cause
Blown fuse or open
circuit breaker
Overload tripCheck and reset, if manual.
Improper line
connections
Improper current
supply
1. Incorrect electrical connection.
2. Wrong voltage.
3. Blown fuse.
1. Broken belt(s).
2. Loose pulleys.
3. Power to unit is disconnected.
4. Motor overload protector has broken circuit.
5. Optional thermostats, restats, freezestats
may lockout blower operation if set
incorrect.
Solution
Replace fuse or reset circuit breaker.
Check connections to unit wiring diagram.
Check to determine that power supply agrees
with motor nameplate specications.
Mechanical failure.Determine that motor and drive turn freely.
44
Check bearings
MUA-SVX003B-EN
Page 45
TTrroouubblleesshhoooottiinngg
ProblemProbable
Solution
Cause
Motor overloadedReduce load or replace motor.
With a 3 phase
power source, one
phase may be
open
Defective capacitor Replace capacitor.
Motor StallsWrong applicationConsult manufacturer.
Overloaded motorReduce load or replace motor.
Low line voltage.Check across AC line and correct if possible.
Motor runs and
then dies down
Motor does not
come up to speed
Motor takes too
long to accelerate
Partial loss of line
voltage
Motor undersized
for application
Voltage too low at
motor terminals
Line wiring to
motor is too small
Excessive load.
Loose connection
Loose connection
Check line for open phase.
Check for loose connections. Determine
adequacy of main power supply.
Replace with larger motor.
Check across AC line and correct if possible.
Install larger line wiring.
Replace with larger motor.
Check connections and tighten where
necessary.
Wrong Rotation (3
Phase)
Motor OverheatsMotor overloadedReplace with larger motor.
Motor Vibrates
Improperly wired
to AC line (wrong
sequence of
phases)
Motor ventilation
clogged
Motor (3 phase)
may have open
phase
Line voltage too
high or too low
Worn blower
bearings.
Motor mounting
bolts loose
Driven equipment
unbalanced
Worn motor
bearings.
3 phase Motor
running on single
phase
Check unit wiring diagram. Reverse any two
line voltage connections.
Clean motor.
Check to insure that all connections are tight.
Check across AC line and correct if possible.
Replace blower bearings.
Tighten mounting bolts.
Balance driven equipment.
Replace motor.
Check for open circuit and correct.
MUA-SVX003B-EN
45
Page 46
TTrroouubblleesshhoooottiinngg
ProblemProbable
Cause
Bent motor shaftReplace motor.
Rapid Motor
Bearing Wear
Excessive
overhung load due
to over-tensioned
belt
Troubleshooting Guide — Fan Assembly
ProblemProbable
Short Belt LifeSpin burns from
Belts turn over in
grooves
Cause
belt slippage
High ambient
temperature
Grease or oil on
belts
Worn pulleysReplace pulleys.
Belt MisalignmentRealign drive.
Damaged beltReplace belt.
Solution
Reduce belt tension.
Solution
Tension belt.
Use Gripnotch belts.
Clean belts and pulleys.
Excessive vibration Tension belts. Replace belts if damaged.
Worn pulleysReplace pulleys.
Pulley
Misalignment
Belt SquealExcessive loadHigh starting load. Retension drive.
Belt BreakageForeign material in
Excessive
Vibration
Belts mismatched
after service
drive
Belts damaged
during installation
Extreme OverloadEliminate overload.
Damaged belt cord
section
Loose beltsTension drive.
Belts improperly
tensioned
Belts improperly
tensioned, causing
more stretch of
some belts than
others
Old belts and new
belts used on same
drive
Different brand
name belts used
on same drive
Realign drive.
Provide drive guard.
Replace belts.
Replace belts.
Tension drive with slack of each belt on the
same side of drive.
Replace belts and tension drive with slack of
each belt on the same side of the drive.
Replace with new belts.
Replace with a set of machine-matched belts.
46
MUA-SVX003B-EN
Page 47
TTrroouubblleesshhoooottiinngg
ProblemProbable
Solution
Cause
Realign drive.
Replace belts and install properly.
Driver pulley must be disassembled, cleaned
and lubricated, then reassembled.
Drive fails to
adjust
Driver and driven
shafts shifted from
parallel
Belt cord section
damaged during
installation
Fretting corrosion
(drive allowed to
operate at one
speed over a
period of time)
Troubleshooting Guide — DX Cooling Coil
ProblemProbable
Cause
No or Insufcient
Cooling
Coil icing
Air bindingPurge and charge system.
Thermal expansion
valve**
Solution
1. Low liquid line pressure.*
2. Thermal expansion valve.**
3. Low air ow across coil.
1. Bulb mounted at incorrect location.
2. Bulb not secured properly.
Insufcient air ow
Air bypassing coilCaulk safe off.
Undersized
system, demand
exceeding cooling
system capacity
Too much outside
air
Refrigerant leakDetermine leak location and correct.
Low liquid pressure Determine cause and correct.*
Water in
Conditioned Air
NNoottee:: *Refer to condensing unit installation and service manual.
**Refer to thermal expansion valve installation instruction.
Exceeding coil face
velocity - 600 fpm.
Drain pan p-trap
clogged.
1. See air blower troubleshooting.
2. Clogged coil
Replace system.*
Check outside air dampers.
Reduce unit air ow.
Clean pan and p-trap.
MUA-SVX003B-EN
47
Page 48
TTrroouubblleesshhoooottiinngg
Troubleshooting Guide — Chilled Water Cooling Coil
ProblemProbable
Cause
No or Insufcient
Cooling
Water in
Conditioned Air
Circulating pump
failure.
Chilled water
temperature not
cool enough.
Air binding (air in
coil).
Insufcient chilled
water ow.
Insufcient air
ow.
Air bypassing coil.Caulk safe off.
Undersized
system, demand
exceeding cooling
system capacity.
Too much outside
air.
Exceeding coil face
velocity - 600 fpm.
Solution
Repair or replace pump.*
Check chiller.*
Bleed coil.
1. Circulating pump capacity is inadequate.*
2. System piping losses too great.
1. See air blower troubleshooting.
2. Clogged coil
Replace system.*
Check outside air dampers.
Reduce unit air ow.
Drain pan p-trap
clogged.
NNoottee:: *Refer to Manufacturer’s Installation and Service Manual.
Clean pan and p-trap.
48
MUA-SVX003B-EN
Page 49
Unit Net & Ship Weights
NNoottee:: All unit weights are less motor, outside air hood and cooling coils with drain pan. For units
ordered with double wall construction (Optional) add an additional 10% of the base unit
weight. GR-G = Vent Type G, Natural Vent; GR-P = Vent Type P, Power Vent (Refer to
model number description)
MUA-SVX003B-EN
49
Page 50
UUnniitt NNeett && SShhiipp WWeeiigghhttss
Double Wall Construction Adder
For units ordered with double wall construction: add an additional 10% to the base unit weight.
Cooling Coil Weight Adder
Table 5. Cooling Coil Weight Adder
Capacity
10, 15
20, 25, 50
30, 35, 60, 70
40, 80
DX CoilChilled Water Coil
4 Row6 Row4 Row6 Row
97 lbs.132 lbs.75 lbs.102 lbs.
126 lbs.177 lbs.98 lbs.135 lbs.
165 lbs.229 lbs.125 lbs.176 lbs.
177 lbs
.249 lbs.135 lbs.196 lbs.
50
MUA-SVX003B-EN
Page 51
Approximate Motor Shipping Weights
Table 6. Approximate Motor Shipping Weights (lbs)
UUnniitt NNeett && SShhiipp WWeeiigghhttss
MUA-SVX003B-EN
51
Page 52
Center of Gravity
NNoottee:: Values based on Average Motor Weight (Actual Center of Gravity and Corner Weights for
Specific Motor Size are Available Upon Request)
Figure 16. Center of Gravity
Center of Gravity Data
52
MUA-SVX003B-EN
Page 53
CCeenntteerr ooff GGrraavviittyy
MUA-SVX003B-EN
53
Page 54
CCeenntteerr ooff GGrraavviittyy
54
MUA-SVX003B-EN
Page 55
CCeenntteerr ooff GGrraavviittyy
MUA-SVX003B-EN
55
Page 56
Model Number Description
AH Model Number Description
AHA20OA0F000CF105H0P
124
5, 6
789
10,
12131415161718192021
11
Digits 1, 2 — Unit Type
AH — Air Handling Unit
Digit 3 — Connection Side
A – Left-hand access
B – Right-hand access
Digit 4 — Development Sequence
A — First Generation
Digits 5, 6 — Unit Size
20 — 1500 - 8000 Cfm
40 — 4000 - 14000 Cfm
Digit 7 — Venting Type
O — None
Digit 8 — Main Power Supply
A — 115/60/1
B — 208/60/1
C — 230/60/1
D — 208/60/3
E — 230/60/3
F — 460/60/3
G — 575/60/3
Digit 9 — Gas Control Option
0 — No gas control option
Digits 10, 11 — Design Sequence
F0 — Design Sequence
Digit 12 — Fuel Type
0 — No selection
Digit 13 — Heat Exchanger Material
0 — No selection
Digit 14 — Air Handler Arrangements
B — Blower (Standard)
C — Blower (Standard) Plenum
D — Blower (Standard) Evaporative Cooler
E — Blower (Standard) Evaporative Cooler/
Plenum
G — Blower (High CFM)
J — Blower (High CFM)/Plenum
K — Blower (High CFM)/Coil Cabinet
L — Blower (High CFM)/Coil Cabinet/ Plenum
Digit 15 — Motor Selection
A — 1/2 HP. w/Contactor
B — 3/4 HP. w/Contactor
C — 1 HP. w/Contactor
D — 1-1/2 HP. w/Contactor
E — 2 HP. w/Contactor
F — 3 HP. w/Contactor
G — 5 HP. w/Contactor
H — 1/2 HP. w/Magnetic Starter
J — 3/4 HP. w/Magnetic Starter
K — 1 HP. w/Magnetic Starter
L — 1-1/2 HP. w/Magnetic Starter
N — 2 HP. w/Magnetic Starter
P — 3 HP. w/Magnetic Starter
Q — 5 HP. w/Magnetic Starter
R — 7-1/2 HP. w/Magnetic Starter
T — 10 HP. w/Magnetic Starter
U — 15 HP. w/Magnetic Starter
V — 1 HP. w/VFD
W — 1–1/2 HP. w/VFD
X — 2 HP. w/VFD
Y — 3 HP. w/VFD
Z — 5 HP. w/VFD
1 — 7–1/2 HP. w/VFD
2 — 10 HP. w/VFD
3 — 15 HP. w/VFD
Digit 16 — Motor Speed
1 — Single Speed ODP 1800 RPM
2 — Single Speed TEFC 1800 RPM
3 — Single Speed High Efficiency ODP 1800
RPM
4 — Single Speed High Efficiency TEFC 1800
RPM
Digit 17 — Coil Options
O — No cooling coil selection
A — DX coil, 4 Row, Single Circuit
B — DX coil, 4 Row, Dual Circuit
C — DX coil, 6 Row, Single Circuit
D — DX coil, 6 Row, Dual Circuit
E — Chilled Water Coil, 4 Row, Single Circuit
G — Chilled Water Coil, 6 Row, Dual Circuit
Digit 18 — Air Inlet Configuration
1 — Outside Air (OA) Horizontal Inlet
2 — Outside Air W/Air Hood, Horizontal Inlet
3 — Bottom Return Air (RA)
4 — Outside and Return Air (OA/RA)
5 — Outside and Return Air W/Air Hood
Digit 19— Air Control and Damper
Arrangements
0 — No selection
A — Outside Air 2 Pos. Motor / SR
B — Return Air 2 Pos. Motor / SR
C — OA/RA 2 Pos. / SR
Q — OA/RA Mod. Mtr. w/CO
E — OA/RA Mod. Mtr. w/Mixed Air Control /
Min. Pot. / SR
H — OA/RA Mod. Mtr. w/Mixed Air Control /
SR
K — OA/RA Mod. Mtr. w/Min. Pot. / SR
M — OA/RA Mod. Mtr. w/Dry Bulb / Mixed Air
Control / Min. Pot. /SR
N — OA/RA Mod. Mtr. w/Enthalpy Controlled
Economizer / SR
P — OA/RA Mod. Mtr. w/Pressure Control
(Space Pressure)
R — OA/RA Mod. Mtr. w/S-350-P Proportional
Mixed Air Control/SR
U — OA/RA MTR. W/External 0-10 VDC and
4-20 mA Analog Input/SR (External Input)
W — ASHRAE Cycle I (OA/RA 2 pos. w/warm-
up stat/SR
X — ASHRAE Cycle II (OA/RA Mod W/Warm-
up Stat/Mixed Air/min pot/SR)
Y — ASHRAE Cycle III (OA/RA Mod. W/Warmup Stat/Mixed Air/SR)
Z — Manual Dampers
Sensor
2
Digit 20 — California Shipment
0 — Non-California Shipment
1 — California Shipment
56
MUA-SVX003B-EN
Page 57
MMooddeell NNuummbbeerr DDeessccrriippttiioonn
Digit 21 — Miscellaneous Options
B — 12” Evaporative Media (Celdek)
C — Moisture Eliminators
D — Horizontal Return
E — Air Flow Proving Switch
F — Freezestat
H — Return Air Firestat
J — Supply Air Firestat
K — Manual Blower Switch
N — Double Wall Construction
P — Low Leak Dampers
Q — Clogged Filter Switch
T — Status Indicator Lights (Elec Cabinet)
W — 8" Evaporative Media (Glasdek)
X — 12" Evaporative Media (Glasdek)
Y — Ambient Lockout
Z — Freezestat for Evap. Cooler
0 — No Filters Selected
1 — 1" Washable (Standard) Filters
2 — 2" Washable Filters
3 — 2" Throwaway Filters
4 — 1" Pleated Media Filters
5 — 2" Pleated Media Filters
Digit 22 — VFD Accessories
1 — Field Installed VFD
2 — Factory Installed VFD
3 — VFD Remote Keypad (Field Installed)
4 — CO
5 — CO
6 — Pressure Sensor
7 — 2-Speed VFD Relays
8 — 3-Speed VFD Relays
9 — VFD Enclosure
Sensor, 100% Outside Air
2
Sensor, Mixed Air
2
MUA-SVX003B-EN
57
Page 58
MMooddeell NNuummbbeerr DDeessccrriippttiioonn
GR Model Number Description
GRAA40GDCC0N2B
1234
Digit 1 — Gas Heating Equipment
G — Gas
Digit 2 — Unit Type
F – Rooftop Duct Furnace
R – Rooftop Heating Unit
S – Special Unit Type
Digit 3 — Furnace Type
A – Standard Temp Rise (20-60 F) LH
B – Standard Temp Rise (20-60 F) RH
C – High Temp Rise (60-90 F) LH
D – High Temp Rise (60-90 F) RH
S – Special Furnace Type
A – 115/60/1
B – 208/60/1
C – 230/60/1
D – 208/60/3
E – 230/60/3
F – 460/60/3
G – 575/60/3
S – Special Main Power Supply
Digit 9 — Main Power Supply Gas
Control Option (Intermittent Pilot
Ignition)
A – Single-Stage
B – Two-Stage
G – Electronic Modulating With Room T-Stat
H – Electronic Modulating With Duct T-Stat
J – Electronic Modulating With Duct T-Stat
and Override Room Thermostat
K – Electronic Modulating W/External 4-20
mA Input (Furnace 1)
L – Electronic Modulating W/External 4-20
mA Input (All furnaces)
M – Electronic Modulating W/External 0-10
VDC Input (Furnace 1)
N – Electronic Modulating W/External 0-10
VDC Input (All furnaces)
P – Two-Stage Remote Temperature Control
R – Three-Stage Remote Temperature Control
T – Four-Stage Remote Temperature Control
U – S-350 2 Stage Modular Electronic Control
System
W – S-350 3 Stage Modular Electronic Control
System
X – S-350 4 Stage Modular Electronic Control
System
Y – S-350 6 Stage Modular Electronic Control
System
S – Special Gas Control
Digits 10,11 — Design Sequence
F0 – Design Sequence
Digit 7 — Venting Type
Digit 12 — Fuel Type
G – Gravity Venting
P – Power Venting
S – Special Venting
N – Natural Gas
P – LP (Propane) Gas
L – Natural Gas with 100% Lockout
S – Special Fuel Type
A – Duct Furnace
B — Blower (Standard)
C — Blower (Standard) Plenum
D — Blower (Standard) Evaporative Cooler
E — Blower (Standard) Evaporative Cooler/
Plenum
G — Blower (High CFM)
J — Blower (High CFM)/Plenum
K — Blower (High CFM)/Coil Cabinet
L — Blower (High CFM)/Coil Cabinet/ Plenum
S – Special Rooftop Arrangement
Digit 15 — Rooftop Heating Unit Motor
Selection
0 – None (Rooftop duct furnace)
A — 1/2 HP. w/Contactor
B — 3/4 HP. w/Contactor
C — 1 HP. w/Contactor
D — 1-1/2 HP. w/Contactor
E — 2 HP. w/Contactor
F — 3 HP. w/Contactor
G — 5 HP. w/Contactor
H — 1/2 HP. w/Magnetic Starter
J — 3/4 HP. w/Magnetic Starter
K — 1 HP. w/Magnetic Starter
L — 1-1/2 HP. w/Magnetic Starter
N — 2 HP. w/Magnetic Starter
P — 3 HP. w/Magnetic Starter
Q — 5 HP. w/Magnetic Starter
R — 7-1/2 HP. w/Magnetic Starter
T — 10 HP. w/Magnetic Starter
U — 15 HP. w/Magnetic Starter
V — 1 HP. w/VFD
W — 1–1/2 HP. w/VFD
58
MUA-SVX003B-EN
Page 59
MMooddeell NNuummbbeerr DDeessccrriippttiioonn
Digit 15 — Rooftop Heating Unit Motor
Selection (cont.)
X — 2 HP. w/VFD
Y — 3 HP. w/VFD
Z — 5 HP. w/VFD
1 — 7–1/2 HP. w/VFD
2 — 10 HP. w/VFD
3 — 15 HP. w/VFD
S – Special Motor
Digit 16 — Motor Speed
1 — Single Speed ODP 1800 RPM
2 — Single Speed TEFC 1800 RPM
3 — Single Speed High Efficiency ODP 1800
RPM
4 — Single Speed High Efficiency TEFC 1800
RPM
S — Special Motor Speed
Digit 17 — Coil Options
O — No cooling coil selection
A — DX coil, 4 Row, Single Circuit
B — DX coil, 4 Row, Dual Circuit
C — DX coil, 6 Row, Single Circuit
D — DX coil, 6 Row, Dual Circuit
E — Chilled Water Coil, 4 Row, Single Circuit
G — Chilled Water Coil, 6 Row, Dual Circuit
S — Special Coil
Digit 18 — Air Inlet Configuration
O — None (Rooftop Duct Furnace)
1 — Outside Air (OA) Horizontal Inlet
2 — Outside Air W/Air Hood, Horizontal Inlet
3 — Bottom Return Air (RA)
4 — Outside and Return Air (OA/RA)
5 — Outside and Return Air W/Air Hood
S — Special Air inlet configuration
Digit 19— Air Control and Damper
Arrangements
0 — No selection
A — Outside Air 2 Pos. Motor / SR
B — Return Air 2 Pos. Motor / SR
C — OA/RA 2 Pos. / SR
D — OA/RA Mod. Mtr. w/CO
E — OA/RA Mod. Mtr. w/Mixed Air Control /
Min. Pot. / SR
H — OA/RA Mod. Mtr. w/Mixed Air Control /
SR
K — OA/RA Mod. Mtr. w/Min. Pot. / SR
M — OA/RA Mod. Mtr. w/Dry Bulb / Mixed Air
Control / Min. Pot. /SR
Sensor
2
Digit 19— Air Control and Damper
Arrangements (cont.)
N — OA/RA Mod. Mtr. w/Enthalpy Controlled
Economizer / SR
P — OA/RA Mod. Mtr. w/Pressure Control
Mixed Air Control/SR
U — OA/RA MTR. W/External 0-10 VDC and
4-20 mA Analog Input/SR (External Input)
W — ASHRAE Cycle I (OA/RA 2 pos. w/warm-
up stat/SR
X — ASHRAE Cycle II (OA/RA Mod W/Warm-
up Stat/Mixed Air/min pot/SR)
Y — ASHRAE Cycle III (OA/RA Mod. W/Warmup Stat/Mixed Air/SR)
Z — Manual Dampers
S — Special Air Control and Damper
Arrangement
Sensor
2
Digit 20 — California Shipment
0 — Non-California Shipment
1 — California Shipment
Digit 21 — Miscellaneous Options
A — Orifices For Elevation Above 2000 Feet
(Specify Elevation)
B — 12” Evaporative Media (Celdek)
C — Moisture Eliminators
D — Horizontal Return
E — Air Flow Proving Switch
F — Freezestat
G — Fan Time Delay Control (Duct Furnace
Only)
H — Return Air Firestat
J — Supply Air Firestat
K — Manual Blower Switch
L — 409 Stainless Steel Furnace Drip Pan
M — Input De-rate
N — Double Wall Construction
P — Low Leak Dampers
Q — Clogged Filter Switch
R — High/Low Gas Pressure Limit Switches
T — Status Indicator Lights (Elec Cabinet)
V — Manual Reset High Limit Switch
W — 8" Evaporative Media (Glasdek)
X — 12" Evaporative Media (Glasdek)
Y — Ambient Lockout
Z — Freezestat for Evap. Cooler
0 — No Filters Selected
1 — 1" Washable (Standard) Filters
2 — 2" Washable Filters
3 — 2" Throwaway Filters
4 — 1" Pleated Media Filters
5 — 2" Pleated Media Filters
6 — Service Convenience Package
7 — Through the Base Utilities
Ingersoll Rand (NYSE: IR) advances the quality of life by creating comfortable, sustainable and efficient
®
environments. Our people and our family of brands — including Club Car
®
— work together to enhance the quality and comfort of air in homes and buildings; transport and protect
Trane
, Ingersoll Rand®, Thermo King®and
food and perishables; and increase industrial productivity and efficiency. We are a global business committed to a
world of sustainable progress and enduring results.
ingersollrand.com
Ingersoll Rand has a policy of continuous product and product data improvements and reserves the right to change design and specifications
without notice.
We are committed to using environmentally conscious print practices.