Trane AUH1D100A9601A, AUH1C080A9601A, AUH1D120A9601A, AUH1C100A9481A, ADH1B065A9421A Installer's Manual

...
18-CD29D1-11
Installer’s Guide
Upflow/ Horizontal, Downflow/ Horizontal, Gas-Fired, Direct Vent Condensing Furnaces
*UH1B040A9241A *UH1B060A9361A *UH1B080A9421B *UH1C080A9601A
*__First letter may be “A” or “T”
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit.
Please return to service information pack upon completion of work.
*UH1
*UH1C100A9481A *UH1D100A9601A *UH1D120A9601A
*DH1B040A9241A *DH1B065A9421A *DH1C085A9481A *DH1D110A9601A
*DH1
DOWNFLOW
*UH1
UPFLOW/HORIZONTAL
*DH1
DOWNFLOW/HORIZONTAL
A341624P13
Installer’s Guide
WARNING
!
SAFETY SECTION
Safety signal words are used to designate a degree or level of seriousness associated with a particular haz­ard. The signal words for safety markings are WARN- ING and CAUTION. a. WARNING indicates a potentially hazardous situa-
tion which, if not avoided, could result in death or serious injury.
b. CAUTION indicates a potentially hazardous situa-
tion which, if not avoided, may result in minor or moderate injury. It is also used to alert against un­safe practices and hazards involving only property damage.
The following safety practices and precautions must be followed during the installation, servicing, and opera­tion of this furnace.
1. Use only with the type of gas approved for this furnace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position as specified in “Location and Clearances” (page 4), of these instructions.
3. Provide adequate combustion and ventilation air to the furnace space as specified in “Air for Combustion and Ventilation” (pages 8-9), of these instructions.
4. Combustion products must be discharged outdoors. Con­nect this furnace to an approved vent system only, as specified in the “Venting” section (starting on page 15), of these instructions.
5. Never test for gas leaks with an open flame. Use a com­mercially available soap solution made specifically for the detection of leaks to check all connections, as speci­fied in “Gas Piping” (pages 31-32), of these instructions.
6. Always install the furnace to operate within the furnace’s intended temperature-rise range with a duct system which has an external static pressure within the al­lowable range, as specified on the unit rating plate. Airflow with temperature rise for cfm versus static is shown in the Service Facts accompanying this furnace.
7. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
8. A gas-fired furnace for installation in a residential garage must be installed as specified in “Location and Clear­ances” section (page 4), of these instructions.
9. The furnace may be used for temporary heating of build­ings or structures under construction only when the following conditions have been met:
a. The furnace venting system must be complete
and installed per manufacturers instructions.
b. The furnace is controlled only by a room ther-
mostat (no field jumpers).
c. The furnace return air duct must be complete
and sealed to the furnace and clean air filters are in place.
d. The furnace input rate and temperature rise
must be verified to be within nameplate mark­ing.
e. 100% of the furnace combustion air require-
ment must come from outside the structure.
CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each ap­pliance connected to the venting system being placed into operation could result in carbon monoxide poi­soning or death. The following steps shall be followed for each appli­ance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and hor­izontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the CAN/CGA B149 Installation Codes and these instructions. Deter­mine that there is no blockage or restriction, leak­age, corrosion and other deficiencies which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other deficiencies which could cause an unsafe condition.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not con­nected to the venting system. Turn on any ex­haust fans, such as range hoods and bathroom ex­hausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appli­ance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z221.1/NFPA 54 and/or CAN/CGA B149.1 In­stallation Codes.
8. After it has been determined that each appliance connected to the venting system properly vents where tested as outlined above, return doors, win­dows, exhaust fans, fireplace dampers and any other gas-fired burning appliance to their previous conditions of use.
© 2014 Trane All Rights Reserved 18-CD29D1-11
Installer’s Guide
WARNING
!
CAUTION
!
f. The furnace return air temperature range is
between 55 and 80 degrees Fahrenheit.
g. Clean the furnace, duct work, and components
upon substantial completion of the construc­tion process, and verify furnace operating con­ditions including ignition, input rate, tempera­ture rise and venting, according to the manu­facturer's instructions.
10. This product must be gas piped by a Licensed Plumber or Gas Fitter in the Commonwealth of Massachusetts.
FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could result in serious injury, death or property damage. Improper servicing could result in dangerous opera­tion, serious injury, death, or property damage.
GENERAL INSTALLATION INSTRUCTIONS
The manufacturer assumes no responsibility for equip­ment installed in violation of any code or regulation. It is recommended that Manual J of the Air Condition­ing Contractors Association (ACCA) or A.R.I. 230 be followed in estimating heating requirements. When estimating heating requirements for installation at altitudes above 2000 ft., remember the gas input may need to be reduced (See High Altitude Installation).
Material in this shipment has been inspected at the factory and released to the transportation agency without known damage. Inspect exterior of carton for evidence of rough handling in ship­ment. Unpack carefully after moving equipment to approximate location. If damage to contents is found, report the damage immediately to the de­livering agency.
Codes and local utility requirements governing the installation of gas fired equipment, wiring, plumb­ing, and flue connections must be adhered to. In the absence of local codes, the installation must conform with latest edition of the National Fuel Gas Code ANSI
Z223.1 • National Installation Code, CAN/CGA B149.1.  
The latest code may be obtained from the American Gas Association Laboratories, 400 N. Capitol St. NW, Washington D.C. 20001. 1-800-699-9277 or www.aga.org These furnaces have been classified as CATEGORY IV furnaces in accordance with latest edition of ANSI
Z21.47 • CAN/ CGA 2.3 standards.
Category IV furnaces operate with positive vent stat­ic pressure and with a flue loss less than 17 percent. These conditions require special venting systems, which must be gas tight and water tight. These Cate­gory IV Direct Vent furnaces are approved for installa-
tion in  Manufactured/ Mobile housing when used with  BAYMFGH100A.
Contents
INSTALLATION INSTRUCTIONS
General Installation Instructions 3 Location and Clearances 4 Outline Drawings 5 Upflow Installation 7 Downflow Installation 7 Horizontal Installation 7 Air For Combustion and Ventilation 8 Duct Connections 10 Return Air Filters 11 General Venting Instructions 15 Venting Material 17 Venting Tables 18 Horizontal Venting 21 Venting Through The Wall 21 Venting Through The Roof 22 Downward Venting 24 Venting Through a Masonry Chimney 24 Condensate Drain Instructions 27 Electrical Connections 30 Field Wiring Diagrams 29 Gas Piping 32 Combustion Input Checks 33
Start Up and Adjustment 36
Preliminary Inspections 36 Lighting Instructions 36 Sequence Of Operation 37 Control And Safety Switch Adjustments 37 Airflow Adjustment 37
Abnormal Conditions 38
IFC Error Flash Code 40
To prevent shortening its service life, the furnace should not be used as a “Construction Heater” during the finish­ing phases of construction until the requirements listed in item 9, a-g of the safety section of this publication have been met. Condensate in the presence of chlorides and fluorides from paint, varnish, stains, adhesives, clean­ing compounds, and cement create a corrosive condition which may cause rapid deterioration of the heat exchang­er.
18-CD29D1-11 3
Installer’s Guide
CAUTION
!
WARNING
!
UPFLOW
FURNACE
CASED
COIL
SCREWS
(BOTH SIDES)
STANDOFFS
(BOTH SIDES)
STANDOFFS (4)
DRILL SCREWS (4)
WARNING
!
EXPLOSION HAZARD! PROPANE GAS IS HEAVIER THAN AIR AND MAY COLLECT IN ANY LOW AREAS OR CONFINED SPAC­ES. IN ADDITION, ODORANT FADE MAY MAKE THE GAS UNDETECTABLE EXCEPT WITH A WARNING DEVICE. IF THE GAS FURNACE IS INSTALLED IN A BASEMENT, AN EXCAVATED AREA OR A CONFINED SPACE, IT IS STRONGLY RECOMMENDED TO CON­TACT A GAS SUPPLIER TO INSTALL A GAS DETECT­ING WARNING DEVICE IN CASE OF A GAS LEAK.
NOTE: The manufacturer of your furnace does NOT test any detectors and makes no representations regarding any brand or type of detector.
Do NOT install the furnace in a corrosive or contaminated atmosphere.
LOCATION AND CLEARANCES
The location of the furnace is normally selected by the ar­chitect, the builder, or the installer. However, before the furnace is moved into place, be sure to consider the follow­ing requirements:
1. Is the location selected as near the vent and as central­ized for heat distribution as practical?
2. Do all clearances between the furnace and enclosure equal or exceed the minimums shown in the Table 1.
3. Is there sufficient space for servicing the furnace and other equipment? A minimum of 24 inches front ac­cessibility to the furnace must be provided. Any access door or panel must permit removal of the largest com­ponent.
4. Are there at least 3 inches of clearance between the fur­nace front panel and any closed panel or door provided?
5. Are the ventilation and combustion air openings large enough and will they remain unobstructed? If outside air is used, are the openings set 12" minimum above the highest snow accumulation level?
6. Allow sufficient height in supply plenum above or below the furnace to provide for cooling coil installation if the cooling coil is not installed at the time of this furnace installation.
7. A furnace shall be installed so electrical components are protected from water.
8. If the furnace is installed in a residential garage, it must be installed so that the burners and the ignition source are located not less than 18 inches (46 cm) above the floor and the furnace must be located or protected to avoid physical damage from vehicles.
UPFLOW INSTALLATION
Standoffs and screws (See Figure 1) are included with the cased coils for attachment to the furnace. There are clearance alignment holes near the bottom of the coil wrapper. Drill screws are used to engage the fur­nace top flanges. The standoff is inserted into the cabinet alignment hole. The drill screws are inserted through the standoffs then screwed into the furnace flange.
The coil is always placed downstream of the furnace airflow.
1
FOR VERTICAL
INSTALLATIONS:
DOWNFLOW INSTALLATIONS
FIRE HAZARD Do NOT install the furnace directly on carpeting, tile or other combustible material other than wood floor­ing. For vertical downflow application, subbase (BAY­BASE-205) must be used between the furnace and combustible flooring. When the downflow furnace is installed vertically with a cased coil, a subbase is not required.
Required floor opening:
IMPORTANT:
The furnace must be installed level. The only allowable varia­tion would be slightly to the left and/or forward in upflow instal­lations or slightly toward the front in horizontal installations. This is necessary for proper condensate drainage.
NOTE: On upflow 5 or 6 ton airflow models where the airflow re­quirement exceeds 1800 CFM - Models will require return air openings and filters on: (1) both sides; or (2) one side and the bottom; or (3) just the bottom.
4 18-CD29D1-11
2
CABINET
WIDTH
17-1/2" 16-1/4" 16-5/8" 20-1/8" 15-5/8" 19-3/8"
21" 19-3/4" 20-1/8" 20-1/8" 19-1/8" 19-3/8"
24-1/2" 23-1/4" 23-5/8" 20-1/8" 22-5/8" 19-3/8"
SUBBASE CROSS SECTION
TABLE 1
RETURN
DUCT WIDTH
FLOOR OPENING PLENUM OPENING
"A" "B" "C" "D"
1. *UH1D120A9601, *UH1C080A9601, *UH1C100A9481, AND
UH1D100A9601 REQUIRE 3” DIAMETER VENT PIPE.
2. DIAMETER OF VENT PIPE MAY BE LIMITED TO 2-1/2” OR 3”
ON SOME MODELS AT DIFFERENT ALTITUDES. REFER TO THE
VENT LENGTH TABLE FOR PROPER APPLICATION.
Installer’s Guide
From Dwg. C341884 Rev. 9
(ALL DIMENSIONS ARE IN INCHES)
*UH1 OUTLINE DRAWING, UPFLOW / HORIZONTAL
18-CD29D1-11 5
Installer’s Guide
From Dwg. C341885 Rev. 7
(ALL DIMENSIONS ARE IN INCHES)
*DH1 OUTLINE DRAWING, DOWNFLOW / HORIZONTAL
17-1/2" 2-1/4" 16-1/4" 16"
MODEL DIM "A" DIM"B" DIM "C" DIM "D"
*DH1B040A9241
*DH1B065A9421
*DH1C085A9481 21" 2-1/2" 19-3/4" 19-1/2"
*DH1D110A9601 24-1/2" 2-15/16" 23-1/4" 23"
* May be "A" or "T"
Part numbers can end in A-Z
6 18-CD29D1-11
Installer’s Guide
3
A (width)
FURNACE
FRONT
HORIZONTAL INSTALLATION
The coil and furnace must be fully supported when used in the horizontal position. It is always recommended that an auxiliary drain pan be installed under a horizontally in­stalled evaporator coil or 95% gas furnace. Connect the aux­iliary drain line to a separate drain line (no trap is needed in this line). Three brackets (with screws) are included with downflow furnaces for installation to stabilize and secure the fur­nace and TXC cased coil in the horizontal position. See Figure 4.
IMPORTANT: The 2/4TXC cased coil must be placed downstream of the furnace. In horizontal installations, the apex of the coil may point either toward or away from the furnace. See the 2/4TXC coil Installer's Guide for more details.
The cased coil is secured to the furnace and both the fur­nace and the cased coil must be properly supported. The brackets mount using the rear screws on the coil case and use the screws provided to secure the bracket to the fur­nace. The remaining bracket is placed as close to center as possible (horizontally) between the coil case front and the
furnace  bottom  channel  (for  downow/horizontal  furnace). 
Use four of the screws provided to secure the bracket. The upflow furnace, converted to horizontal, aligns and attaches the TXC coil as in Figure 1. However, the coil requires ad­ditional support.
B (depth)
D
C
5
UPFLOW/ HORIZONTAL SHOWN
The furnace may be placed horizontally in a crawl space on a pad or other noncombustible material which will raise the unit for sufficient protection from moisture. The furnace
must be supported at both ends and the middle when installed horizontally. The furnace must also be elevated a minimum of 6 inches to allow clearance for the condensate drain to exit the cabinet in the horizontal position.
The horizontal furnace may also be suspended from the
joists  using  3/8"  all-thread  rods  with  pieces  of  angle  iron 
underneath the furnace to form a hanging rack at both ends and the midpoint. The rods need to be of sufficient length to allow for proper clearances from combustible materials. The angle iron needs to be at least 32" in length to allow for access to service panels.
6
50 CU. FT. OR MORE PER 1000 BTU/HR. INPUT ALL EQUIP. INSTALLED
4
CASED COIL CONNECTION
BRACKET FOR DOWNFLOW 
FURNACE IN HORIZONTAL
DOWNFLOW ONLY
The furnace may be installed in an attic or crawl space in the horizontal position by placing the furnace on the left side (as viewed from the front in the vertical position). The horizontal furnace installation in an attic should be on a service platform large enough to allow for proper clearances on all sides and service access to the front of the furnace (See Figure 3 & Clearance Table 1). Line contact is only permissible between lines formed by intersections of the top and two sides of the furnace casing and building joists, studs, or framing.
UNCONFINED
AIR FOR COMBUSTION AND VENTILATION
If these furnaces are installed in a nondirect vent capac­ity then the adequate flow of combustion and ventilating air must not be obstructed from reaching the furnace. Air openings provided for combustion air must be kept free of obstructions which restrict the flow of air. Airflow restric­tions affect the efficiency and safe operation of the furnace.
Keep this in  mind  should  you choose to  remodel  or  change 
the area which contains your furnace. Furnaces must have a free flow of air for proper performance. Provisions for combustion and ventilation air shall be made in accordance with latest edition of Section 5.3, Air for Com­bustion and Ventilation, of the National Fuel Gas Code,
ANSI Z223.1  —  CAN/CGA B149.1  or  applicable provisions 
of the local building codes. Special conditions created by mechanical exhausting of air and fireplaces must be con­sidered to avoid unsatisfactory furnace operation.
18-CD29D1-11 7
Installer’s Guide
OUTSIDE AIR IS RECOMMENDED
The use of indoor air for most applications is acceptable, unless there is the presence of corrosive chemicals or contamination. Certain types of installation will require the use of outside air for combustion. The following types of installations will require use of OUTDOOR AIR for combustion, due to chemical exposures: * Commercial buildings
* Buildings with indoor pools
* Furnaces installed in “confined” laundry rooms * Furnaces installed in “confined” hobby or craft rooms * Furnaces installed near chemical storage areas. Exposure to the following substances in the combustion air supply will also require OUTDOOR AIR for combustion: * Permanent wave solutions * Chlorinated waxes and cleaners * Chlorine based swimming pool chemicals * Water softening chemicals * Deicing salts or chemicals * Carbon Tetrachloride * Halogen type refrigerants * Cleaning solvents (such as perchloroethylene) * Printing inks, paint removers, varnish, etc. * Hydrochloric acid * Cements and glues * Antistatic fabric softeners for clothes dryers * Masonry acid washing materials
Furnace locations may be in a “confined space” or an “un- confined space”.
Unconfined space is defined in Figure 6. These spaces may have adequate air by infiltration to provide air for combus-
tion and  ventilation.  Buildings  with  tight   construction  (for 
example, weather stripping, heavily insulated, caulked, va­por barrier, etc.), may need additional air to be provided as described for confined space.
1. All air from inside the building as in Figure 8: The con­fined space shall be provided with two permanent open­ings communicating directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space. The total input of all gas utilization equipment installed in the combined space shall be considered in making this determination. Refer to Table 2 for minimum open ar­eas requirements.
2. All air from outdoors as in Figure 9: The confined space shall be provided with two permanent openings, one commencing within 12 inches of the top and one com­mencing within 12 inches of the bottom of the enclo­sure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. Refer to Table 2, for minimum open areas requirements.
TABLE 3
MINIMUM FREE AREA IN SQUARE INCHES
EACH OPENING (FURNACE ONLY)
Furnace
Maximum
BTUH/INPUT
Rating
40,000 60,000 80,000 97,000
110,000
Air
From
Inside
100 100 100 100 110
Air From Outside
Vertical
Duct
10 15 20 25 28
Horizontal
Duct
20 30 40 50 55
8
Confined spaces are installations with less than 50 cu. ft. of
space per 1000  BTU/hr  input  from  all  equipment  installed, 
as in Figure 7. Air for combustion and ventilation require­ments can be supplied from inside the building as in Figure 8 or from the outdoors, as in Figure 9.
Table 2
MINIMUM AREA IN SQUARE FEET
FOR UNCONFINED SPACE INSTALLATIONS
FURNACE MAXI-
MUM BTUH INPUT
RATING
40,000 60,000 80,000 97,000
110,000
WITH 8 FT. CEILING
MINIMUM AREA IN SQUARE FEET
OF UNCONFINED SPACE
250 375 500 625 688
7
CONFINED
SPACE
8 18-CD29D1-11
9
Installer’s Guide
On any job, flexible connections of nonflammable materi­al may be used for return air and discharge connections to pre vent transmission of vibration. Though these units have been specifically designed for quiet, vibration free operation, air ducts can act as sounding boards and could, if poorly in­stalled, amplify the slightest vibration to the annoyance lev­el. When the furnace is located in a utility room adjacent to the living area, the system should be carefully designed with returns to minimize noise transmission through the return air grille. Although these furnaces are designed with large blowers operating at moderate speeds, any blow­er moving a high volume of air will produce audible noise which could be objectionable when the unit is located very close to a living area. It is often advisable to route the re­turn air ducts under the floor or through the attic. Such de­sign permits the installation of air return remote from the living area (i.e. central hall). When the furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space con­taining the furnace, the return air shall also be handled by a duct(s) sealed to the furnace and terminating outside the space containing the furnace.
RETURN AIR DUCT CONNECTION
NOTE: On upflow 5 or 6 ton airflow models where the airflow re­quirement exceeds 1800 CFM - Models will require return air openings and filters on: (1) both sides; or (2) one side and the bottom; or (3) just the bottom.
All return air duct systems should provide for installation of return air filters.
1. Determine the appropriate position to set the furnace in order to connect to the existing supply and return ductwork.
2. For side return installations on upflow models, remove the insulation around the opening in the blower com­partment.
DUCT CONNECTIONS
Air duct systems should be installed in accordance with standards for air conditioning systems, National Fire Pro­tection Association Pamphlet No. 90. They should be sized in accordance with ACCA Manual D or whichever is appli­cable. Central furnaces, when used in connection with cooling units, shall be installed in parallel or on the upstream side of the cooling coil to avoid condensation in the heat ex­changer. With a parallel flow arrangement, the dampers or other means used to control flow of air shall be adequate to prevent chilled air from entering the furnace, and if manu­ally operated, must be equipped with means to prevent op­eration of either unit unless the damper is in full heat or cool position.
NOTE: Minimum return air temperature is 55° F.
3. The side panels on upflow furnaces include locating notches which may be used as guides for cutting an opening for return air. Refer to Figure 11 and the out­line drawing on pages 5-6 for duct connection dimen­sions for various furnaces.
  4.  If a 3/4" ange is to be used for attaching the air inlet 
duct, add to cut where indicated by dashed lines in Figure 11. Cut corners diagonally and bend outward to form flange.
5. If flanges are not required, and a filter frame is in­stalled, cut along knockout guidelines.
6. Upflow Furnaces: Use the optional filter rack on either side or on the bottom if the filter is to be used within the furnace cabinet.
When the upflow furnace is installed in the horizontal
application and a return duct is attached to the top side as shown in Figure 10, install the filter in a remote location.
Do not install the filter in the return duct directly
above the furnace in horizontal applications.
18-CD29D1-11 9
Installer’s Guide
WARNING
!
WARNING
!
When the upflow furnace is installed in the horizontal
application and a close coupled (less than 36") return duct is attached to the bottom side of the furnace as
shown in Figure 10, securely attach a 1/2" mesh metal 
hardware cloth protective screen to the inside bottom of the filter grill to prevent personal injury from
contacting moving parts when reaching into the return opening to replace the filter.
Close coupled (less than 36") return (filter directly
beneath bottom side return) is not recommended due to noise considerations.
Downflow Furnaces:  Brackets are factory supplied 
to mount filters in the return air duct work.
FIRE OR EXPLOSION HAZARD
Do not install the filter in the return duct directly above the furnace in horizontal applications. Install the filter re­motely. Failure to follow the safety warnings exactly could result in serious injury, death or property damage.
SAFETY HAZARD
To prevent injury or death due to contact with moving parts, turn the power to the furnace off before servicing filters
Failure to follow the safety warnings exactly could result in serious injury, death or property damage.
REMOVE FILTER FROM UPFLOW FURNACE WHEN RETURN DUCT IS ATTACHED TO FURNACE TOP SIDE (HORIZONTAL APPLICATIONS) AS SHOWN.
Close coupled (less than 36") return (filter directly beneath bottom side return) not recommended due to noise considerations. If used, securely
attach 1/2" mesh metal hardware cloth 
protective screen to the inside bottom of filter grill.
FILTER
0
7. Connect the duct work to the furnace. See Outline Drawing (pages 5-6) for supply and return duct size and location. Flexible duct connectors are recommend­ed to connect both supply and return air ducts to the furnace. If only the front of the furnace is accessible, it is recom­mended that both supply and return air plenums are removable.
8. When replacing a furnace, old duct work should be cleaned out. Thin cloths should be placed over the registers and the furnace fan should be run for 10 min­utes. Don’t forget to remove the cloths before you start the furnace.
q
LOCATING NOTCHES PROVIDED FOR SIDE RETURN CUTOUT
*
*
*
*
CUT OUT
FOR
SIDE
FILTER
FRONT
of Furnace
*SEE OUTLINE DRAWING
RETURN AIR FILTERS (Filter and filter rack are not supplied with unit)
TYPICAL UPFLOW RETURN AIR FILTER INSTALLATIONS
These furnaces require high velocity type air filters. The optional filters may be located within the furnace blower
compartment for UPFLOW furnaces in either a BOTTOM 
or SIDE (left side or right side) return air inlet. Some optional filters may need to be trimmed for side or bottom filter use.
The furnace and the blower filter rack installation can be seen in Figure 12.
The optional furnace filter in the bottom or side configura­tion can be removed by simply turning the two latches on the blower door and tilting the door forward.
The filter rails are spring loaded for automatic adjustment to allow standard size, locally obtainable replacement filters. The filter rack itself slides to adjust to the required width needed for bottom or side return.
TABLE 4 - MINIMUM CLEARANCE FROM COMBUSTIBLE MATERIALS FOR
UPFLOW/HORIZONTAL LEFT AND DOWNFLOW/HORIZONTAL RIGHT FURNACES
UNIT LOCATION
FURNACE SURFACE
SIDES 0" 1" 0"
BACK 0" 3" 6"
TOP 1" 1" 1"
FRONT 3" 3" 18"
VENT 0" 0" 0"
NOTE: CLEARANCE REQUIRED AT TOP OF PLENUM IS 1"
10 18-CD29D1-11
VERTICAL
CLOSET
HORIZONTAL
CLOSET
HORIZONTAL
ALCOVE / ATTIC
Installer’s Guide
Filter
TABLE 5
UPFLOW FURNACE RETURN AIR FILTERS
CABINET
WIDTH
14-1/2" 1 14" X 25" X 1" 17-1/2" X 25" X 1"
17-1/2" 1 17" X 25" X 1" 17-1/2" X 25" X 1"
21" 1 20" X 25" X 1" 17-1/2" X 25" X 1"
24-1/2" 1 24" X 25" X 1" 17-1/2" X 25" X 1"
**NOTE: For upflow 5 ton airflow models where the airflow requirement exceeds 1800 CFM - Models will require return air openings and filters on: (1) both sides, or (2) one side and the bottom, or (3) just on the bottom
QTY*
CABINET
BOTTOM FILTER
CABINET
SIDE FILTER
Airflow
NOTE: The narrow 14.5" width furnace cabinet prevents use of the filter rack for right side return. Pre-drill clear­ance holes and then attach filter clips with the screws provided. The filter clip with the leaf spring mounts in the rear of the cabinet
OPTIONAL FILTER RACK INSTALLATION FOR BOTTOM RETURN - BAYRACK960
The following checklist should be used when installing as a bottom return filter on an upflow furnace:
a. Remove the filter.
b. Remove the bottom panel.
c. Pre-drill two engagement holes with 3/16" drill at
dimple locations. See Figure 14.
d. With the filter removed, the filter rack is compressed
and then inserted into the bottom of the furnace. The retaining screw/pin on each side inserts into engage­ment holes at the bottom of the furnace cabinet side. See Figure 15.
e. Reinstall the furnace filter in the bottom position by
inserting the chamfer end first into the filter rack.
NOTE: Remove the bottom front channel to install the filter rack in the 14-1/2" width cabinet furnaces.
e
w
Airflow
BOTTOM FILTER RACK INSTALLATION
r
Blower Deck Engagement
PRE-DRILL
Two clearance holes with a 3/16” drill at dimple locations (one per side)
t
Furnace
Cabinet
Side
Hole
VIEW
Rack
Filter Rack Retaining
Optional Filter Rack Accessory Kit
Engagement Hole For
Filter Rack Installation With Bottom Return (Pre-drill 3/16” diameter clearance holes)
Screw/Pin
BAYRACK960A
18-CD29D1-11 11
Installer’s Guide
Filter Rack Assembly
Furnace Blower Deck
Filter Rack Retaining Screw/Pin
Engagement Hole For
Return
Filter Rack Installation With Side
Furnace
Cabinet
Side
Filter Rack
RETAINING
PIN
(Both Sides)
SPRINGS
SIDE
CUTOUT
FILTER
RACK
RAILS
BOTTOM
PANEL
INSTALLED
Airflow
RETAINING
PIN
(Both Sides)
SPRINGS
SIDE
CUTOUT
FILTER
RACK
RAILS
BOTTOM
PANEL
INSTALLED
Airflow
TABLE 6
Cabinet Width Left Side Bottom Right Side
14.5 X
17.5 X X X
21 X X X
24.5 X X X
1. UC1B060C has 10x7 blower which requires use of alternate filter clips for left side filter. "K1" and later use the filter rack.
2. Remove bottom front channel to install or reposition filter rack.
X - All Models
OPTIONAL FILTER RACK INSTALLATION FOR SIDE RETURN AIR ON UPFLOW FURNACES (Left or Right) ­BAYRACK960
The following checklist should be used when installing a right or left side return filter on an upflow furnace:
a. Remove the filter.
b. Leave the bottom panel in place.
c. Make side cutout by following the directions in the
“Return Air Duct Connections” section on page 9.
d. Compress the filter rack and reinstall in the side
position on the furnace. Confirm that the upper retaining pin/screw locks into the engagement hole in the blower deck and the lower pin/screw rests against the side of the bottom panel. See Figures 14, 18-20.
e. Reinstall the furnace filter in the side position by
inserting the chamfer end first into the filter rack.
1
X2Use Alternate Filter Clips Only
i
Typical Upflow Left Side Return Filter Rack Installation
o
y
u
BLOWER DECK
12 18-CD29D1-11
BOTTOM ENGAGEMENT
Furnace
Cabinet
Side
Retaining Screw/Pin
Filter Rack
Bottom Panel
Typical Upflow Right Side Return Filter Rack Installation
p
Airflow
Accessory filter kit
BAYFLTR203, 204, or 
205 used for Upflow Horizontal furnaces
Typical Horizontal Filter Installation
Loading...
+ 28 hidden pages