Trane 4TTX3, 4TTX4 User Manual

4 (1)
18-AC50D1-3
Condensing n
4TTX3; 4TTX4
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT -- This Document is customer property and is to remain with this unit. Please return to service information
pack upon completion of work.
These instructions do not cover all variations in systems nor provide for every possible contingency to
this installation must comply with NATIONAL, STATE
AND LOCAL CODES. Should further information be
desired or should particular problems arise which are not covered sufficiently for the purchaser's purposes, the matter should be referred to your installing dealer or local distributor.
A. GENERAL
The following instructions cover 4TTX3; 4TTX4 Condensing Units.
NOTICE:
These outdoor units may be used with indoor units
equipped with Thermostatic Expansion Valve or
Accutron TM Flow Control Check Valve (F.C.C.V.) assembly
for refrigerant flow control only.
UNiT CONTAINS R-410A REFRIGERANT!
R-410A OPERATING PRESSURE EXCEEDS THE
LiMiT OF R-22. PROPER SERVICE EQUIPMENT IS
REQUIRED. FAILURE TO USE PROPER SERVICE
TOOLS MAY RESULT IN EQUIPMENT DAMAGE OR
PERSONAL INJURY.
SERVICE
USE ONLY R-410A REFRIGERANT AND
APPROVED POE COMPRESSOR OiL.
5 FT. ABOVE UNIT=UNRESTRICTED
These units use R-410A refrigerant which operates at 50
to 70% higher pressures than R-22. Use only R-410A
approved service equipment. Refrigerant cylinders are painted a "Rose" color to indicate the type of refrigerant and may contain a "dip" tube to allow for charging of liquid refrigerant into the system. All R-410A systems use a POE oil that readily absorbs moisture from the atmosphere. To limit this "hygroscopic" action, the system should remain sealed whenever possible. Never break a vacuum with air and always change the driers when opening the system for component replacement.
Check for transportation damage after unit is uncrated. Report promptly, to the carrier, any damage found to the unit.
To determine the electrical power requirements of the unit, refer to the nameplate of the unit. The electrical power available must agree with that listed on the nameplate.
B. LOCATION & PREPARATION
OF THE UNiT
1. When removing unit from the pallet, notice the tabs on the basepan. Remove tabs by cutting with a sharp tool as
shown in Figure 2 (see page 2).
2. The unit should be set on a level support pad at least as large as the unit base pan, such as a concrete slab. If this is not the application used please refer to application
bulletin "XLi-APG**-EN" (* latest revision number).
|nsta||er's Guide
@
3. The support pad must NOT be in direct contact with any structure. Unit must be positioned a minimum of 12" from any wall or surrounding shrubbery to insure adequate airflow. Clearance must be provided in front of control box (access panels) & any other side requiring
service access to meet National Electrical Code. Also, the unit location must be far enough away from any
structure to prevent excess roof run-offwater from pouring directly on the unit. Do not locate unit(s) close
to bedroom(s).
4. The top discharge area must be unrestricted for at least five (5) feet above the unit.
5. When the outdoor unit is mounted on a roof', be sure the roof will support the unit's weight. Properly selected isolation is recommended to prevent sound or vibration transmission to the building structure.
6. The maximum length of refrigerant lines from outdoor to indoor unit should NOT exceed sixty (60) feet.
7. If outdoor unit is mounted above the air handler, maximum lift should not exceed sixty (60) feet (suction line). If air handler is mounted above condensing unit, maximum lift should not exceed sixty (60) feet (liquid
line).
NOTE: Refer to "Refrigerant Piping Software" Pub. No. 32-3312-0",
and "Refrigerant Piping Manual Pub. No. 32-3009=0* (the position of the * denotes the latest revision no.)
8. Locate and install indoor coil or air handler in accor- dance with instruction included with that unit.
C. ACCUTRON TM FLOW CONTROL VALVE
If the indoor unit System Refrigerant Flow control is an Accutron TM orifice and check valve assembly, an orifice size change may be necessary.
®
BRAZE TYPE INDOOR END
SEALING CAP
ACCUTRON TM
oo> -" ADAP'E""xi'2)
\ FLQWCQN,.QL
SSH
_ LIQUID LINE
FIELD SUPPLIED
The outdoor model determines the required orifice size. Check the listed orifice size on nameplate of the selected outdoor model. If the indoor unit is factory shipped with a diffhrent orifice size, the orifice must be changed to obtain system rated performance.
NOTE:
Attach R-410A CAUTION Label (located in documentation
package) to access panel of indoor section.
IMPORTANT:
The outdoor unit is shipped withthe proper size orifice and a stick-on orifice size label in an envelope attached to the outdoor unit. Outdoor unit nameplate will have correct orifice size specified as BA YFCCV---A for rated performance.
D. iNSTALLiNG REFRIGERANT LINES
If using existing refrigerant lines make certain that all joints
are brazed, not soldered.
Condensing units have provisions for braze connections. Pressure taps are provided on the service valves of outdoor
unit for compressor suction and liquid pressures. The indoor end of the recommended refrigerant line sets may
be straight or with a 90 degree bend, depending upon situa- tion requirements. This should be thoroughly checked out before ordering refrigerant line sets.
The gas line must always be insulated.
In scroll compressor applications, dome temperatures may be hot. Do not touch top of compressor, may cause minor to severe burning.
The units are factory charged with the system charge required when using fifteen (15) feet of connecting line. Unit
nameplate charge is the same. Final refrigerant charge adjustment is necessary. Use
the Charging Charts in the outdoor unit Service Facts.
1. Determine the most practical way to run the lines.
2. Consider types of bends to be made and space limitations.
NOTE:
Large diameter tubing will be very difficult to rebend once it
has been shaped.
3. Determine the best starting point for routing the refrigerant tubing -- INSIDE OR OUTSIDE THE
STRUCTURE.
4.
Provide a pull-thru hole of sufficient size to allow both liquid and gas lines.
5.
Be sure the tubing is of sufficient length.
6.
Uncoil the tubing -- do not ldnk or dent.
7.
Route the tubing making all required bends and properly secure the tubing before maMng connections.
8.
To prevent a noise within the building structure due to vibration transmission from the refrigerant lines, the following precautions should be taken:
a. When the refrigerant lines have to be fastened to floor
joists or other framing in a structure, use isolation
type hangers.
© 2006 American Standard inc. All Rights Reserved 18-AC50D1-3
|nsta||er's Guide
©
LIQUID LINE SERVICE VALVE
CAP'_ (_
UNIT SIDE OF f
SERVICE VALVE "_._.._ _
PORT
LIQUID LINE CONNECTION
ROLLED EDGE TO
CAPTIVATE STEM
b. Isolation hangers should also be used when refrigerant
lines are run in stud spaces or enclosed ceilings.
c. Where the refrigerant lines run through a wall or sill,
they should be insulated and isolated.
d. Isolate the lines from all ductwork.
E. SERVICE VALVE OPERATION
BRASS LIQUID LiNE SERVICE VALVE
The Brass Liquid Line Service Valve is factory shipped in the seated position to hold factory charge. The pressure tap
service port (when depressed) opens only to the field brazing side of the valve when the valve is in the seated position.
The liquid line valve is not a back seating valve (see WARNING below).
Extreme caution should be exercised when opening the Liquid Line Service Valve. Turn valve stem counterclock- wise only until the stem contacts the rolled edge. (See Figure 4) No torque is required.
BRASS GAS LINE SERVICE VALVE
The Brass Gas Line Service Valve is shipped in the closed position to hold the fhctory refrigerant charge. The pressure tap service port (when depressed) opens only to the field
brazing side when the valve is in the closed position. The Gas
Line Service Valve is full open with a 1/4 turn. See Figure 5. BRAZING REFRIGERANT LINES
1. Remove lower access cover to access service valves.
2. Before brazing, remove plugs from external eopper stub tubes. Clean internal and external surfaces of stub
tubes prior to brazing.
3. Cut and fit tubing, minimizing the use of sharp 90 ° bends.
4. Insulate the entire gas line and its fittings.
5. Do NOT allow uninsulated liquid line to come in direct contact with bare gas line.
6. Precautions should be taken to avoid heat damage to the pressure tap valve core during brazing. It is
recommended that the pressure tap port valve core be removed and a wet rag wrapped around
the valve body.
NOTICE: Use care to make sure that no moisture enters pressure tap
port, while wet rag is being used.
7. Use a Dry Nitrogen Purge and Brazing Alloy without flux when brazing the field line to the copper factory connec-
tion. Flow dry nitrogen into either valve pressure tap port, thru the tubing and out the other port while brazing.
8. Braze using accepted good brazing techniques.
LEAK CHECK
IMPORTANT:
Replace pressure tap port valve core before attaching hoses for evacuation.
After the brazing operation of refrigerant lines to both the
outdoor and indoor unit is completed, the field brazed connections must be checked for leaks. Pressurize through the service valve ports, the indoor unit and field refrigerant lines with dry nitrogen to 350-400 psi. Use soap bubbles or other leak-checking methods to see that all field joints are leak-free! If not, release pressure; then repair!
SYSTEM EVACUATION
NOTE: Since the outdoor unit has a refrigerant charge, the gas and
liquid line valves must remain closed.
1. Upon completion of leak check, evacuate the refrigerant lines and indoor coil before opening the gas and liquid
line valves.
2. Attach appropriate hoses from manifold gauge to gas and liquid line pressure taps.
NOTE:
Unnecessary switching of hoses can be avoided and complete evacuation of all lines leading to sealed system can be accomplished with manifold center hose and connecting branch hose to a cylinder of R-410A and
vacuum pump.
3.
Attach center hose of manifold gauges to vacuum pump.
4.
Evacuate until the micron gauge reads no higher than 350 microns.
5. Close offvalve to vacuum pump and observe the micron gauge. If gauge pressure rises above 500 microns in one (1) minute., then evacuation is incomplete, or system has a leak.
6. If vacuum gauge does not rise above 500 microns in one (1) minute, the evacuation should be complete.
7. With vacuum pump and micron gauge blanked off; open
valve on R-410A cylinder and charge refrigerant lines and
indoor coil with vapor to tank pressure of R-410A supply.
@
GAS LINE SERVICE VALVE
FORFULLOPEN
OFVALVE
UNIT SIDE / _STEM
PRESSURETAPPORT
/
GAS LINE CONNECTION
NOTICE: Precautions should be taken to avoid heat damage to
basepan during brazing. It is recommended to keep the flame directly off of the baeepan.
18-AC50D1-3
Loading...
+ 5 hidden pages