ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information pack upon completion of work.
These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with
the installation. Should further information be desired or should particular problems arise which are not covered sufficiently for the
purchaser’s purposes, the matter should be referred to your installing dealer or local distributor.
Note: The manufacturer recommends installing only approved matched indoor and outdoor systems. All of the manufacture’s split
systems are A.H.R.I. rated only with TXV/EEV indoor systems. Some of the benefits of installing approved matched indoor and
outdoor split systems are maximum efficiency, optimum performance and the best overall system reliability.
Section 10. Service Valves ................................................................... 11
Section 11. Electrical - Low Voltage .................................................... 13
Section 12. Electrical - High Voltage ................................................... 16
Section 13. Start Up .............................................................................. 17
Section 14. System Charge Adjustment ............................................. 18
Section 15. Checkout Procedures and Troubleshooting ................... 22
Section 1. Safety
▲
WARNING
!
▲
WARNING
!
▲
WARNING
!
▲
WARNING
!
▲
CAUTION
!
▲
CAUTION
!
▲
WARNING
!
This information is intended for use by individuals
possessing adequate backgrounds of electrical and
mechanical experience. Any attempt to repair a central
air conditioning product may result in personal injury
and/or property damage. The manufacture or seller
cannot be responsible for the interpretation of this
information, nor can it assume any liability in connection with its use.
These units use R-410A refrigerant which operates
at 50 to 70% higher pressures than R-22. Use only
R-410A approved service equipment. Refrigerant cylinders are painted a “Rose” color to indicate the type
of refrigerant and may contain a “dip” tube to allow
for charging of liquid refrigerant into the system. All
R-410A systems use a POE oil that readily absorbs
moisture from the atmosphere. To limit this “hygroscopic” action, the system should remain sealed
whenever possible. If a system has been open to the
atmosphere for more than 4 hours, the compressor oil
must be replaced. Never break a vacuum with air and
always change the driers when opening the system
for component replacement. For specific handling
concerns with R-410A and POE oil reference Retrofit
Bulletins SS-APG006-EN and APP-APG011-EN.
LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing, and troubleshooting of this product, it may be necessary to work
with live electrical components. Failure to follow all
electrical safety precautions when exposed to live
electrical components could result in death or serious
injury.
If using existing refrigerant lines make certain that all
joints are brazed, not soldered.
Scroll compressor dome temperatures may be hot. Do
not touch the top of compressor; it may cause minor to
severe burning.
UNIT CONTAINS R-410A REFRIGERANT!
R-410A operating pressures exceed the limit of R-22.
Proper service equipment is required. Failure to use
proper service tools may result in equipment damage
or personal injury.
SERVICE
USE ONLY R-410A REFRIGERANT AND AP-
PROVED POE COMPRESSOR OIL.
Extreme caution should be exercised when opening
the Liquid Line Service Valve. Turn counterclockwise
until the valve stem just touches the rolled edge. No
torque is required. Failure to follow this warning will
result in abrupt release of system charge and may
result in personal injury and /or property damage.
2 18-AC51D1-8-EN
D
H
W
Section 2. Unit Location Considerations
2.1 Unit Dimensions and Weight
Table 2.1
Unit Dimensions and Weight
ModelsH x D x W (in)
4TTR4018L
4TTR4024/25L
4TTR4030/31L
4TTR4036/37L
4TTR4042/43L
4TTR4048L
4TTR4060L
* Weight values are estimated.
29 x 26 x 29133
29 x 26 x 29133
29 x 30 x 33156
33 x 30 x 33156
29 x 34 x 37184
29 x 34 x 37189
37 x 34 x 37211
When mounting the outdoor unit on a roof, be
sure the roof will support the unit’s weight.
Properly selected isolation is recommended to
alleviate sound or vibration transmission to the
building structure.
Please refer to application bulletin SSCAPG002-EN for detailed mounting information.
Weight* (lb)
2.2 Refrigerant Piping Limits
1. The maximum length of refrigerant lines
from outdoor to indoor unit should NOT
exceed sixty (60) feet.
2. The maximum vertical change should not
exceed sixty (60) feet.
3. Service valve connection diameters are
shown in Table 5.1.
Note: For line lengths greater than sixty (60)
feet, Refer to Refrigerant Piping Application
Guide, SS-APG006-EN or Refrigerant Piping
Software Program, 32-3312-03 (or latest revision).
Standard
Line Set
60’ Max
Line Length
60’
Max
Vertical
Change
18-AC51D1-8-EN 3
60’
Max
Vertical
Change
Avoid Install
2.3 Suggested Locations for Best Reliability
Ensure the top discharge area is unrestricted for
at least five (5) feet above the unit.
Three (3) feet clearance must be provided in
front of the control box (access panels) and any
other side requiring service.
Near Bedrooms
Min 5’ Unrestricted
Do not locate close to bedrooms as operational
sounds may be objectionable.
Position the outdoor unit a minimum of 12” from
any wall or surrounding shrubbery to ensure
adequate airflow.
Outdoor unit location must be far enough away
from any structure to prevent excess roof runoff
water from pouring directly on the unit.
Min. 12” to
Shrubbery
Min. 12” to
Shrubbery
Min 3’
Unrestricted
Access Panel
Min. 12”
to Wall
2.4 Coastal Considerations
If installed within one mile of salt water, including seacoasts and inland waterways, models without factory
supplied Seacoast Salt Shields require the addition of BAYSEAC001 (Seacoast Kit) at installation time. Please
refer to Application Guide SS-APB006-EN: Trane - Sea Coast Applications and Seascoast Corrosion Protection Bulletin UN-SVB11A-EN.
4 18-AC51D1-8-EN
Section 3. Unit Preparation
3.1 Prepare The Unit For Installation
STEP 1 - Check for damage and report prompt-
ly to the carrier any damage found to the unit.
STEP 2 - To remove the unit from the pallet,
remove tabs by cutting with a sharp tool.
Section 4. Setting the Unit
4.1 Pad Installation
When installing the unit on a support pad, such
as a concrete slab, consider the following:
• The pad should be at least 1” larger than the
unit on all sides.
• The pad must be separate from any structure.
• The pad must be level.
• The pad should be high enough above grade
to allow for drainage.
• The pad location must comply with National,
State, and Local codes.
For other applications refer to Application Guide
SSC-APG002-EN.
18-AC51D1-8-EN 5
Section 5. Refrigerant Line Considerations
5.1 Refrigerant Line and Service Valve Connection Sizes
Table 5.1
Line SizesService Valve Connection Sizes
Model
4TTR4018L3/43/83/43/8
4TTR4024/25L
4TTR4030/31L
4TTR4036/37L
4TTR4042/43L
4TTR4048L7/83/87/83/8
4TTR4060L7/83/87/83/8
Vapor
Line
3/43/83/43/8
3/43/83/43/8
3/43/83/43/8
7/83/87/83/8
5.2 Factory Charge
Trane outdoor condensing units are factory charged with the system charge required for the outdoor condensing
unit, fifteen (15) feet of tested connecting line, and the smallest indoor evaporative coil match. If connecting line
length exceeds fifteen (15) feet and/or a larger indoor evaporative coil is installed, then final refrigerant
charge adjustment is necessary.
Liquid
Line
Vapor Line
Connection
Liquid Line
Connection
5.3 Required Refrigerant Line Length
Determine required line length and lift. You will
need this later in STEP 2 of Section 14.
Total Line Length = __________ Ft.
Total Vertical Change (lift) = __________ Ft.
5.4 Refrigerant Line Insulation
Important: The Vapor Line must always be
insulated. DO NOT allow the Liquid Line and
Vapor Line to come in direct (metal to metal)
contact.
Liquid Line
Line Length
Vapor Line
Insulation
6 18-AC51D1-8-EN
5.5 Reuse Existing Refrigerant Lines
▲
CAUTION
!
If using existing refrigerant lines make certain that
all joints are brazed, not soldered.
For retrofit applications, where the existing
indoor evaporator coil and/or refrigerant lines
will be used, the following precautions should
be taken:
• Ensure that the indoor evaporator coil and
refrigerant lines are the correct size.
• Ensure that the refrigerant lines are free of
leaks, acid, and oil.
Important: For more information see publication numbers SS-APG006-EN and APPAPG011-EN.
Section 6. Refrigerant Line Routing
6.1 Precautions
Important: Take precautions to prevent noise
within the building structure due to vibration
transmission from the refrigerant lines.
For Example:
• When the refrigerant lines have to be fastened to floor joists or other framing in a structure, use isolation type
hangers.
• Isolation hangers should also be used when refrigerant lines are run in stud spaces or enclosed ceilings.
• Where the refrigerant lines run through a wall or sill, they should be insulated and isolated.
• Isolate the lines from all ductwork.
• Minimize the number of 90º turns.
8 Feet Maximum
Side View
8 Feet Maximum
Secure Vapor line from joists using isolators every 8 ft. Secure
Liquid Line directly to Vapor line using tape, wire, or other appropriate method every 8 ft.
Comply with National, State, and Local Codes when
isolating line sets from joists, rafters, walls, or other
structural elements.
Joist/Rafter
Isolator
Line Set
18-AC51D1-8-EN 7
Isolation From Joist/Rafter
8 Feet Maximum
Wall
Isolator
Wall
Side View
8 Feet Maximum
Line Set
Secure Vapor Line using isolators every 8 ft. Secure Liquid Line
directly to Vapor Line using tape, wire, or other appropriate
method every 8 ft.
Isolation In Wall Spaces
Sealant
Ductwork
Insulation
Vapor Line
Isolator
Line Set
Isolation Through Wall
Section 7. Refrigerant Line Brazing
7.1 Braze The Refrigerant Lines
STEP 1 - Remove caps or plugs. Use a debur-
ing tool to debur the pipe ends. Clean both
internal and external surfaces of the tubing
using an emery cloth.
DO NOT hang line sets from ductwork
8 18-AC51D1-8-EN
STEP 2 - Remove the pressure tap cap and
3-4” from valve
valve cores from both service valves.
STEP 3 - Purge the refrigerant lines and indoor
coil with dry nitrogen.
STEP 4 - Wrap a wet rag around the valve body
to avoid heat damage and continue the dry nitrogen purge.
Braze the refrigerant lines to the service valves.
For units shipped with a field-installed external
drier, check liquid line filter drier’s directional flow
arrow to confirm correct direction of refrigeration
flow (away from outdoor unit and toward evaporator coil) as illustrated. Braze the filter drier to
the Liquid Line.
Continue the dry nitrogen purge. Do not remove
the wet rag until all brazing is completed.
Important: Remove the wet rag before stopping
the dry nitrogen purge.
Note: Install drier in Liquid Line.
18-AC51D1-8-EN 9
STEP 5 - Replace the pressure tap valve cores
150 PSIG
after the service valves have cooled.
Section 8. Refrigerant Line Leak Check
8.1 Check For Leaks
STEP 1 - Pressurize the refrigerant lines and
evaporator coil to 150 PSIG using dry nitrogen.
STEP 2 - Check for leaks by using a soapy solution or bubbles at each brazed location.
Remove nitrogren pressure and repair any leaks
before continuing.
10 18-AC51D1-8-EN
Section 9. Evacuation
1/4 TURN ONLY
9.1 Evacuate the Refrigerant Lines and Indoor Coil
Important: Do not open the service valves until
the refrigerant lines and indoor coil leak check
and evacuation are complete.
STEP 1 - Evacuate until the micron gauge reads
no higher than 350 microns, then close off the
valve to the vacuum pump.
STEP 2 - Observe the micron gauge. Evacuation
is complete if the micron gauge does not rise
above 500 microns in one (1) minute.
Once evacuation is complete blank off the
vacuum pump and micron gauge, and close the
valves on the manifold gauge set.
0350
Microns
ON
OFF
1 MIN.
Section 10. Service Valves
10.1 Open the Gas Service Valve
Important: Leak check and evacuation must be
completed before opening the service valves.
NOTE: Do not vent refrigerant gases into the
atmosphere
STEP 1 - Remove valve stem cap.
STEP 2 - Using an adjustable wrench, turn valve
stem 1/4 turn counterclockwise to the fully open
position.
STEP 3 - Replace the valve stem cap to prevent
leaks. Tighten finger tight plus an additional 1/6
turn.
CAP
UNIT SIDE
OF VALVE
PRESSURE TAP PORT
COUNTERCLOCKWISE
FOR FULL OPEN
POSITION
VALVE STEM
GAS LINE CONNECTION
18-AC51D1-8-EN 11
10.1 Open the Liquid Service Valve
▲
WARNING
!
Extreme caution should be exercised when
opening the Liquid Line Service Valve. Turn
counterclockwise until the valve stem just
touches the rolled edge. No torque is required.
Failure to follow this warning will result in abrupt
release of system charge and may result in
personal injury and /or property damage.
Important: Leak check and evacuation must be
completed before opening the service valves.
STEP 1 - Remove service valve cap.
STEP 2 - Fully insert 3/16” hex wrench into the
stem and back out counterclockwise until valve
stem just touches the rolled edge (approximately
five (5) turns.)
STEP 3 - Replace the valve cap to prevent leaks.
Tighten finger tight plus an additional 1/6 turn.
Cap
Unit Side
of Service
Valve
Service Port
3/16” Hex Wrench
Rolled Edge to
Captivate Stem
Hex Headed
Valve System
Section 11. Electrical - Low Voltage
11.1 Low Voltage Maximum Wire Length
Table 11.1 defines the maximum total length of
low voltage wiring from the outdoor unit, to the
indoor unit, and to the thermostat.
Table 11.1
24 VOLTS
WIRE SIZEMAX. WIRE LENGTH
18 AWG150 Ft.
16 AWG225 Ft.
14 AWG300 Ft.
12 18-AC51D1-8-EN
11.2 Low Voltage Hook-up Diagrams
Air Conditioner
W2
Pink
White
R
G
B
W1
B
Y
R
G
B/C
Y
W
Blue
24 VAC HOT
FAN
24 VAC
Common
COOLING
HEAT
ThermostatAir Handler
Outdoor
Unit
In AC systems for multiple stages
of electric heat, jumper W1 and
W2 together if comfort control has
only one stage of heat.
TEM3, TEM4
Hook-up Diagram
Variable Speed Furnace
Hook-up Diagram
Comfort Control
R
Y1
G
W1
W2
B
18-AC51D1-8-EN 13
Red
Yellow
Green
White
Black
Blue
Neatly bundle all low voltage
wires behind the service
valve cover as shown.
Variable Speed
Furnace
R
BK
Y
Y
G
W1
W2
O
Yellow
LO
B
Blue
Yellow
Blue
Notes:
1. If single stage
heating thermostat
is used, jumper
W1-W2 on furnace
terminal strip.
Air Conditioner
Communicating Indoor Unit
with 24 V Control Hook-up
Diagram
Neatly bundle all low voltage
wires behind the service
valve cover as shown.
Comm. Variable Speed
Furnace or Air Handler
Comfort Control
R
Y1
G
W1
W2
B
Red
Yellow
Green
White
Black
Blue
Communicating Indoor Unit
in Comm. Mode
Hook-up Diagram
R
BK
D
Y1
Y2
G
W1
W2
W3
O
Notes:
1. See User Interface setup
menu for 24 VAC control
mode and cooling CFM
Yellow
B
Blue
Neatly bundle all low voltage
wires behind the service
valve cover as shown.
Yellow
Blue
Air Conditioner
options.
2. W3 terminal may not be
present on unit.
3. If single stage heating
thermostat is used, jumper
W1-W2 on furnace terminal strip.
Communicating
Comfort Control
(*CONT900)
D
R
B
Brown
Red
Blue
Comm. Variable Speed
Furnace or Air Handler
14 18-AC51D1-8-EN
D
R
BK
Y1
Y2
G
W1
W2
W3
O
Yellow
B
Blue
Yellow
Blue
Notes:
1. See User Interface
setup menu for cooling
CFM options.
2. W3 terminal may not
be present on unit.
Air Conditioner
Air Conditioner
1
1
12345
12345
HP
2(Comp ressor)
2(Stages)
AC (System)
}
OUTDOOR
Capacity (Tons)
OUTDOOR
}
Torque
CFM/Ton
Cool OffDelay
}
INDOOR
CFM
+12V
R13
R14
R4
1
U1
RNET1
S1
on
on
S2
RNET2
R
6
C22
C19
C15C
12
C10
D9
L1
TAM7 Air Handler
Hook-up Diagram
Comfort Control
W
G
Y1
O
R
B
Y2
Field wiring
White
Green
Yellow
Red
Blue
Air Handler
W3
W2
W1
G
YI
O
R
B
YO
Y2
DH/BK
(In)
(Out)
Neatly bundle all low voltage
wires behind the service
valve cover as shown.
B - Blue
Y1 - Yellow
Blue
Yellow
Control Board
Must configure to
“ON” for AC Units.
TAM4, GAM5 Air Handler
Hook-up Diagram
Comfort Control
White
W
Green
G
Yellow
Y
Orange
O
Red
18-AC51D1-8-EN 15
Blue
Field wiring
R
B
White
Green
Yellow
Red
Blue
Air Handler
W3
W2
W1
G
YI (In)
O **
R **
B
YO (Out)
B - Blue
Y - Yellow
Must configure to “OFF” for
single-stage compressors.
Neatly bundle all low voltage
wires behind the service
valve cover as shown.
Blue
Yellow
1. * For multiple stages of
electric heat, jumper W1,
W2, and W3 together if
comfort control has only
one stage of heat.
2. ** R to O jumper must
be in place as shown for
cooling only, non-heat
pump systems for proper
operation.
3. Yi and Yo connections
must be made as shown
for freeze protection and
internally mounted condensate overflow circuits
to work properly.
4. Internally mounted condensate switch is optional
and must be ordered
separately.
5. If 3rd party condensate
overflow switches are
installed, they should be
wired in series between
YO and Y to the outdoor
unit.
Section 12. Electrical - High Voltage
▲
WARNING
!
12.1 High Voltage Power Supply
LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing, and
troubleshooting of this product, it may be necessary to work with live electrical components.
Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
The high voltage power supply must agree with
the equipment nameplate.
Power wiring must comply with national, state,
and local codes.
Follow instructions on unit wiring diagram located
on the inside of the control box cover and in the
Service Facts document included with the unit.
12.2 High Voltage Disconnect Switch
Install a separate disconnect switch at the
outdoor unit.
For high voltage connections, flexible electrical conduit is recommended whenever vibration transmission may create a noise problem
within the structure.
12.3 High Voltage Ground
Ground the outdoor unit per national, state, and
local code requirements.
16 18-AC51D1-8-EN
Section 13. Start Up
OFF
DON
E
CANCEL
ON
OFF
E
13.1 System Start Up
STEP 1 - Ensure Sections 7 through 12 have
been completed.
STEP 2 - Set System Thermostat to OFF.
STEP 3 - Turn on disconnect(s) to apply power
to the indoor and outdoor units.
STEP 4 - Wait one (1) hour before starting the
unit if compressor crankcase heater accessory is used and the Outdoor Ambient is below
70ºF.
STEP 5 - Set system thermostat to ON.
60 MIN.
ON
DON
CANCEL
18-AC51D1-8-EN 17
Section 14. System Charge Adjustment
14.1 Temperature Measurements
STEP 1 - Check the outdoor temperatures.
Subcooling (in cooling mode) is the only recommended method of charging above 55º F ambient outdoor temperature.
For best results the indoor temperature should
be kept between 70º F to 80º F.
Note: It is important to return in the spring or
summer to accurately charge the system in the
cooling mode when outdoor ambient temperature is above 55º F.
120º F
55º F
Outdoor Temp
80º F
70º F
Indoor Temp
14.2 Subcooling Charging in Cooling (Above 55º F Outdoor Temp.)
STEP 1 - Use the refrigerant line total length
and lift measurements from Section 5.3.
Total Line Length = __________ Ft.
Vertical Change (Lift) = __________ Ft.
LIFT
18 18-AC51D1-8-EN
STEP 2 -
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
102025304060
Add 1° of Subcooling
Add 4° of
Subcooling
Use Design Subcool Value
60
50
40
30
25
20
15
10
0
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
102025304060
Add 2° of Subcooling
Add 4° of Subcooling
Add 6° of
Subcooling
Use Design Subcool Value
60
50
40
30
25
20
15
10
0
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
102025304060
Add 2° of Subcooling
Add 4° of
Subcooling
Use Design Subcool Value
60
50
40
30
25
20
15
10
0
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
102025304060
Add 2° of Subcooling
Add 4° of Subcooling
Add 5° of
Subcooling
Use Design Subcool Value
60
50
40
30
25
20
15
10
0
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
10202530406080
Add 2° of Subcooling
Add 4°
Add 6° of
Subcooling
Use Design Subcool Value
60
50
40
30
25
20
15
10
0
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
102025304060
Add 2° of Subcooling
Add 5°
Use Design Subcool Value
60
50
40
30
25
20
15
10
0
Determine the final subcooling value using total Line Length and Lift measured in STEP 1 and the charts below.
1 1/2 - 2 Ton Units
3 Ton Units
4 Ton Units
2 1/2 Ton Units
3 1/2 Ton Units
5 Ton Units
STEP 3 - Stabilize the system by operating for a
minimum of 20 minutes.
At startup, or whenever charge is removed or
added, the system must be operated for a minimum of 20 minutes to stabilize before accurate
measurements can be made.
18-AC51D1-8-EN 19
Design Subcooling Value = __________º F
(from nameplate or Service Facts)
Subcooling Correction = __________º F
Final Subcooling Value = __________º F
20 MIN.
STEP 4 - Measure the liquid line temperature
3
and pressure at the outdoor unit’s service valve.
Measured Liquid Line Temp = __________ º F
Liquid Gage Pressure = __________ PSI
Final Subcooling Value = __________ º F
STEP 5 - Use the final subcooling value, refrigerant temperature and pressure from STEP 4, to
determine the proper liquid gage pressure using
Table 14.2.
Example: Assume a 12º F Final Subcooling
value and liquid temp of 90º F.
1. Locate 12º F Final Subcooling in Table 14.2.
2. Locate the Liquid Temperarature (90º F) in
the left column.
3. The Liquid Gage Pressure should be approximately 327 PSI. (This is the shown as
the intersection of the Final Subcooling column
and the Liquid Temperature row.
Table 14.2
R-410A REFRIGERANT CHARGING CHART
LIQUID
TEMP
F)
(
°
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
FINAL SUBCOOLING (
891011121314
LIQUID GAGE PRESSURE (PSI)
179 182 185 188 191 195 198
195 198 201 204 208 211 215
211 215 218 222 225 229 232
229 232 236 240 243 247 251
247 251 255 259 263 267 271
267 271 275 279 283 287 291
287 291 296 300 304 309 313
309 313 318 322 327 331 336
331 336 341 346 351 355 360
355 360 365 370 376 381 386
381 386 391 396 402 407 413
407 413 418 424 429 435 441
435 441 446 452 458 464 470
464 470 476 482 488 495 501
495 501 507 514 520 527 533
From Dwg. D154557P01 Rev.
°
107 °F
F)
20 18-AC51D1-8-EN
STEP 6 - Adjust refrigerant level to attain
PRESSURE CURVES FOR 4TTX5049E1
proper gage pressure.
Add refrigerant if the Liquid Gage Pressure
is lower than the chart value.
1. Connect gages to refrigerant bottle
and unit as illustrated.
2. Purge all hoses.
3. Open bottle.
4. Stop adding refrigerant when liquid
line temperature and Liquid Gage
Pressure matches the charging chart
Final Subcooling value.
Recover refrigerant if the Liquid Gage Pressure is higher than the chart value.
STEP 7 - Stabilize the system.
1. Wait 20 minutes for the system condition to stabilize between adjustments.
Note: When the Liquid Line Temperature and
Gage Pressure approximately match the chart,
the system is properly charged.
2. Remove gages.
3. Replace service port caps to prevent
leaks. Tighten finger tight plus an additional 1/6 turn.
STEP 8 - Verify typical performance.
Refer to System Pressure Curves in the Service
Facts to verify typical performance.
20 MIN.
(Example only - see Service Facts)
4TXCD010CC3
520
INDOOR ENTERING
WET BULB CURVES
470
TOP TO BOTTOM
71, 67, 63 AND 59 DEG F.
420
370
320
270
220
LIQUID PRESSURE (PSIG)
170
4050 6070 8090 100 110 120
170
INDOOR ENTERING
165
WET BULB CURVES
TOP TO BOTTOM
160
71, 67, 63 AND 59 DEG F.
155
150
145
140
135
130
N PRESSURE (PSIG)
125
Cooling @ 1400 CFM
(4)
OUTDOOR TEMPERATURE (Degree F)
(5)
(2)
(3)
(1)
(2)
(3)
18-AC51D1-8-EN 21
STEP 9 - Record System Information for reference.
Record system pressures and temperatures
after charging is complete.
Outdoor model number = _________________
Measured Outdoor Ambient = __________ º F
Measured Indoor Ambient = __________ º F
Measured Suction Line Temp = __________ º F
Liquid Gage Pressure = __________ PSI
Suction Gage Pressure = __________ PSI
Measured Liquid Line Temp = __________ º F
Section 15. Checkout Procedures and Troubleshooting
15.1 Operational And Checkout Procedures
Final phases of this installation are the unit Operational and Checkout Procedures. To obtain proper performance, all units
must be operated and charge adjustments made.
Important: Perform a final unit inspection to be sure that factory tubing has not shifted during shipment. Adjust tubing if necessary so tubes do not rub against each other when the unit runs. Also be sure that wiring connections are tight and properly
secured.
CHECKOUT PROCEDURE
After installation has been completed, it is recommended that the entire system be checked against the following list:
C - Cooling H - Heating P - Primary Causes S - Secondary Causes * - 3 Phase Only
REF. CIR. RES TRIC TION S
RES. I.D. AIRFL OW
SUP ERHE AT
S
S
S
S
P
P
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
CHE CK VALVE LE AKIN G
*
SOV CO IL DE FECT IVE
SOV LE AKIN G
S
P
S
S
S
P
S
S
P
P
S
P
S
P
S
DEF ROST CONTR OL DEF.
DEF ROST RELAY DEF.
S
S
S
P
P
S
S
S
S
S
S
S
P
P
P
P
P
P
P
S
S
P
P
18-AC51D1-8-EN 23
6200 Troup Highway
Tyler, TX 75707
www.trane.com
24 18-AC51D1-8-EN
The manufacturer has a policy of continuous product and product data improvement
and it reserves the right to change design and specifications without notice.
Representative-only illustrations included in this document.