Product Data
Split System Cooling
4TTR4018L1000A
4TTR4024L1000A
4TTR4025L1000A
4TTR4030L1000A
4TTR4031L1000A
4TTR4036L1000A
4TTR4037L1000A
4TTR4042L1000A
4TTR4043L1000A
4TTR4048L1000A
4TTR4060L1000A
March 2016
NNoottee:: “Graphics in this document are for representation
only. Actual model may differ in appearance.”
22-1904-1G-EN
Product Specifications
Model No.
(a)
POWER CONNS. — V/PH/HZ
4TTR4018L1000A
(b)
208/230/1/60 208/230/1/60 208/230/1/60 208/230/1/60
4TTR4024L1000A/
4TTR4025L1000A
4TTR4030L1000A/
4TTR4031L1000A
4TTR4036L1000A/
4TTR4037L1000A
MIN. BRCH. CIR. AMPACITY 12 14 17 18
BR. CIR. PROT. RTG. — MAX.
(AMPS)
COMPRESSOR
20 25 25 30
CLIMATUFF®-
SCROLL
CLIMATUFF®-
SCROLL
CLIMATUFF®-
SCROLL
CLIMATAUFF®-
SCROLL
RL AMPS — LR AMPS 9 — 63 10.9 — 63 12.8— 68 14.1— 72
Outdoor Fan FL AMPS 0.60 0.60
Fan HP
Fan Dia (inches)
1/15 1/15 1/8 1/8
18.2 18.2 23.0 23.0
0.77/.64 0.77/.64
Coil SPINE FIN™ SPINE FIN™ SPINE FIN™ SPINE FIN™
Refrigerant R-410A 4 LBS., 8 OZ 4 LBS., 11 OZ 5 LBS., 4 OZ 6 LBS., 1 OZ
LINE SIZE — IN. O.D. GAS
LINE SIZE — IN. O.D. LIQ.
Charge Spec. Subcooling
Dimensions H x W X D Crated
(IN.)
Weight — Shipping (lbs.)
Weight — Net (lbs.)
(c)
(c)
3/4 3/4 3/4 3/4
3/8 3/8 3/8 3/8
10°F 10°F 10°F
10°F / ( 8°F on 037)
30.1 x 26.7 x 30 30.1 x 26.7 x 30 34 x 30.1 x 33 38 x 30.1 x 33
153 153 183 183
133 133 156 156
Optional Accessories:
Anti-short Cycle Timer
Evaporator Defrost Control
TAYASCT501A TAYASCT501A TAYASCT501A TAYASCT501A
AY28X079 AY28X079 AY28X079 AY28X079
Rubber Isolator Kit BAYISLT101 BAYISLT101 BAYISLT101 BAYISLT101
Extreme Condition Mount Kit BAYECMT023 BAYECMT023 BAYECMT023 BAYECMT023
Start Kit BAYKSKT263 — BAYKSKT263 BAYKSKT263
Crankcase Heater Kit BAYCCHT302 BAYCCHT302 BAYCCHT302 BAYCCHT302
Seacoast Kit BAYSEAC001 BAYSEAC001 BAYSEAC001 BAYSEAC001
Low Ambient Kit BAYLOAM103 BAYLOAM103 BAYLOAM103 BAYLOAM103
Refrigerant Lineset
(d)
TAYREFLN950 TAYREFLN950 TAYREFLN7* TAYREFLN7*
Service Valve Panel Cover AAYSVPANL0022AA AAYSVPANL0022AA AAYSVPANL0032AA AAYSVPANL3343AA
(a)
Certified in accordance with the Unitary Air-conditioner equipment certification program which is based on AHRI standard
210/240.
(b)
Calculated in accordance with N.E.C. Only use HACR circuit breakers or fuses.
(c)
Standard line lengths — 60’, Standard lift — 60’ Suction and Liquid line. For Greater lengths and lifts refer to refrigerant
piping software Pub#32–3312–0* (* denotes latest revision)..
(d)
* = 15, 20, 25, 30, 40 and 50 foot lineset available.
2
22-1904-1G-EN
PPrroodduucctt SSppeecciiffiiccaattiioonnss
Model No.
(a)
POWER CONNS. — V/PH/HZ
(b)
4TTR4042L1000A/
4TTR4043L1000A
4TTR4048L1000A 4TTR4060L1000A
280/230/1/60 280/230/1/60 280/230/1/60
MIN. BRCH. CIR. AMPACITY 22 24 31
BR. CIR. PROT. RTG. — MAX. (AMPS)
COMPRESSOR
CLIMATUFF®- SCROLL CLIMATUFF®- SCROLL CLIMATUFF®- SCROLL
35 40 50
RL AMPS — LR AMPS 16.7 — 109 18.5 — 124 23.7 — 152.5
Outdoor Fan FL AMPS 1.05 1.05 1.05
Fan HP
Fan Dia (inches)
1/5 1/5 1/5
27.5 27.5 27.5
Coil SPINE FIN™ SPINE FIN™ SPINE FIN™
Refrigerant R-410A 6 LBS., 7 OZ 6 LBS., 9 OZ 7 LBS., 10 OZ
LINE SIZE — IN. O.D. GAS
LINE SIZE — IN. O.D. LIQ.
Charge Spec. Subcooling
Dimensions H x W X D Crated (IN.)
Weight — Shipping (lbs.)
Weight — Net (lbs.)
(c)
(c)
7/8 7/8 7/8
3/8 3/8 3/8
12°F 10°F 10°F
34.4 x 35.1 x 38.7 34.4 x 35.1 x 38.7 42.4 x 35.1 x 38.7
216 212 246
184 189 211
Optional Accessories:
Anti-short Cycle Timer
Evaporator Defrost Control
TAYASCT501A TAYASCT501A TAYASCT501A
AY28X079 AY28X079 AY28X079
Rubber Isolator Kit BAYISLT101 BAYISLT101 BAYISLT101
Extreme Condition Mount Kit BAYECMT004 BAYECMT004 BAYECMT004
Start Kit BAYKSKT263 BAYKSKT263 BAYKSKT263
Crankcase Heater Kit BAYCCHT301 BAYCCHT301 BAYCCHT301
Seacoast Kit BAYSEAC001 BAYSEAC001 BAYSEAC001
Low Ambient Kit BAYLOAM103 BAYLOAM103 BAYLOAM103
Refrigerant Lineset
(d)
TAYREFLN7* TAYREFLN3* TAYREFLN3*
Service Valve Panel Cover AAYSVPANL0044AA
(a)
Certified in accordance with the Unitary Air-conditioner equipment certification program which is based on AHRI standard
210/240.
(b)
Calculated in accordance with N.E.C. Only use HACR circuit breakers or fuses.
(c)
Standard line lengths — 60’, Standard lift — 60’ Suction and Liquid line. For Greater lengths and lifts refer to refrigerant
piping software Pub#32–3312–0* (* denotes latest revision)..
(d)
* = 15, 20, 25, 30, 40 and 50 foot lineset available.
22-1904-1G-EN
3
PPrroodduucctt SSppeecciiffiiccaattiioonnss
MODEL
4TTR4018L1 71 74 71 65 68 67 63 56 50
4TTR4024L1
4TTR4025L1
4TTR4030L1
4TTR4031L1
4TTR4036L1
4TTR4037L1
4TTR4042L1
4TTR4043L1
4TTR4048L1 71 81 72 69 69 66 60 57 54
4TTR4060L1 71 81 72 69 69 66 60 57 54
Note: Rated in accordance with AHRI Standard 270–2008 *For Reference Only
A-Weighted
Sound Power
Full Octave Sound Power(dB)
Level [dB(A)]
63
125Hz250Hz500Hz1000Hz2000
Hz*
71 74 71 65 68 67 63 56 50
71 73 73 72 69 68 60 52 45
71 73 73 72 69 68 60 52 45
71 81 72 69 69 66 60 57 54
Hz
4000
Hz
8000
Hz
4
22-1904-1G-EN