Trane 4TEE3F48A1000A, 4TEE3F39A1000A, 4TEE3F48B1000A, 4TEE3F64A1000A Installer's Manual

Installer’s Guide
18-GE12D1-8
Convertible Variable Speed – Air Handlers 3.5 - 5 Ton
4TEE3F39A1000A, 4TEE3F48A1000A, 4TEE3F48B1000A, 4TEE3F64A1000A
WARNING:
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service informa-
tion pack upon completion of work.
NOTE: The 4TEE3F48B air handler should NOT be installed in the horizontal left or down flow configuration unless the outdoor unit has an AHRI rating with 18-GJ23D1 in the AHRI Directory. System ratings listed without 18-GJ23D1 are for horizontal right and upflow configurations only. The manufacturer recommends installing only approved, matched indoor and outdoor systems.
A. GENERAL INFORMATION
!
THIS INFORMATION IS FOR USE BY INDIVIDUALS HAVING ADEQUATE BACKGROUNDS OF ELECTRICAL AND MECHANICAL EXPERIENCE. ANY ATTEMPT TO REPAIR A CENTRAL AIR CONDITIONING PRODUCT MAY RESULT IN PERSONAL INJURY AND/OR PROP­ERTY DAMAGE. THE MANUFACTURER OR SELLER CANNOT BE RESPONSIBLE FOR THE INTERPRETA­TION OF THIS INFORMATION, NOR CAN IT ASSUME ANY LIABILITY IN CONNECTION WITH ITS USE.
HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING
CONTENTS
General Information .............................................. 1
Installation Limitations & Recommendations ...................... 1
Two Piece Cabinet Disassembly ........................ 3
Unit Installation ...................................................... 4
Vertical Upflow ....................................................................... 4
Vertical Downflow ................................................................... 4
Horizontal Left ........................................................................ 7
WARNING
Horizontal Right ..................................................................... 8
Refrigerant Piping ................................................. 8
Condensate Drain Piping ...................................... 9
Electrical - Wiring ................................................. 10
Airflow Adjustment ............................................... 10
Hook Up Diagrams ............................................... 12
Outline Drawings ................................................. 15
!
CAUTION
To prevent shortening its service life, the air handler should not be used during the finishing phases of con­struction. The low return air temperatures can lead to the formation of condensate. Condensate in the pres­ence of chlorides and fluorides from paint, varnish, stains, adhesives, cleaning compounds, and cement creates a corrosive condition which may cause rapid
deterioration of the cabinet and internal components.
These instructions do not cover all variations in sys­tems or provide for every possible contingency. Should further information be desired or particular problems arise which are not covered sufficiently by this manual, contact your local distributor or the manufacturer as listed on the air handler nameplate. These Air Handlers are shipped from the factory in the upflow or horizontal right configuration and are fully convertible to downflow or horizontal left. Refer to Sec­tion C beginning on page 3 for additional information.
INSPECTION
Check carefully for any shipping damage. This must be reported to and claims made against the transportation company immediately. Check to be sure all major com-
Checkout Procedures .......................................... 18
NOTE: Version française sur la page 17.
ponents are in the unit. Any missing parts should be re­ported to your supplier at once, and replaced with au­thorized parts only.
!
CAUTION
Cardboard packing material must be removed from in­side the blower assembly before starting the unit. Failure to do so may cause indoor blower motor failure.
INSTALLATION LIMITATIONS & RECOMMENDATIONS
The general location of the air handler is normally se­lected by the architect, contractor and/or home owner for the most effective application and satisfaction.
NOTE: Condensation may occur on the surface of the air handler when installed in an unconditioned loca­tion. When units are installed in unconditioned spaces, verify that all electrical and refrigerant line penetrations on the air handler are sealed completely.
Installer’s Guide
AIR HANDLER SUB-BASE
JOISTS
HEADER
HEADER
JOISTS
FLOOR OPENING - SIZE
MODEL NO. A B
TAYBASE100 23-3/4 14-13/16
TAYBASE101 21-3/4 14-13/16
TAYBASE102 26-3/4 14-13/16
These air handlers are suitable for installation in a closet, alcove or utility room with free, non-ducted, air return, using the area space as a return air plenum. With ducted supply air, if the minimum clearances to combustible materials and service access are observed, the above installations are suitable. This area may also be used for other purposes, includ­ing an electric hot water heater - but in no case shall
a fossil fuel device be installed and/or operated in the same closet, alcove or utility room.
In addition, these air handlers are suitable for installa­tion in an attic, garage or crawl space with ducted sup­ply and return air. This equipment has been evaluated in accordance with the Code of Federal Regulations, Chapter XX, Part 3280 or the equivalent. “SUITABLE FOR MOBILE HOME USE” For proper installation the following items must be con­sidered:
1. If adequate power is available and correct according to nameplate specifications.
2. Insulate all ducts, particularly if unit is located out­side of the conditioned space.
3. Pursuant to Florida Building Code 13-610.2.A.2.1, this unit meets the criteria for a factory sealed air handler.
4. To ensure maximum efficiency and system perfor­mance, the existing supply and return duct system static pressures must not exceed the total available static pressure of the air handler. Reference ACCA Manual D, Manual S and Manual RS along with the air handler Product Data and Service Facts for addi­tional information.
5. It is recommended that the outline drawing be stud­ied and dimensions properly noted and checked against selected installation site. By noting in ad­vance which knockouts are to be used, proper clear­ance allowances can be made for installation and possible future service.
JOIST
B
A
JOIST
Figure 1
REAR FLANGE
ONE INCH DUCT SPACERS
FRONT OF
UNIT
NAILS
HEADER
APPROX. 3/4" FLANGES ON FIELD FABRICATED DUCT OR PLENUM
1"
UNIT
MIN. SPACING TO ANY COMBUSTIBLE
1"
MATERIAL.
SUBBASE
FLOOR
NAILS
HEADER
6. When the air handler with supplementary heater is to be installed in the downflow position on combus­tible flooring an accessory sub-base (TAYBASE100 for 4TEE3F39-64) must be used. See Figure 1.
7. If supplementary heat is to be added, power supply must be sufficient to carry the load. In addition, minimum air flow settings, unit and duct clearances to combustible material must be maintained as stated on the air handler rating nameplate.
!
CAUTION
For air handlers not equipped with a factory installed electric heater, a field installed heater is available from American Standard Inc. Only heaters built by American Standard Inc. are approved for use in the air handler. These heaters have been designed and tested in accor­dance with UL standards to provide safe and reliable operation. A list of approved heaters is provided on the air handler rating nameplate. Heaters that are not fac­tory approved could cause damage and are not cov­ered under equipment warranty.
NOTE: If air handler is used WITHOUT a supplementary electric heater, a sheetmetal plate is required to cover
.
the open hole in the airflow system (See Figure 2)
In addition, ensure that the cabinet is sealed air tight where the field wires enter the unit.
IF AIRHANDLER IS USED SUPPLEMENTARY HEATER, A PLATE IS REQUIRED TO COVER THE OPEN HOLE IN THE AIR FLOW SYSTEM
1"
4"
3/8"
WITHOUT
17"
ACCESSORY BAY99X123
Figure 2
A FACTORY FURNISHED
1/4" HOLES (4)
6"
From Dwg. 21B140413
© 2010 American Standard Heating & Air Conditioning
S L L
8. If the unit is installed without a return air duct, ap­plicable local codes may limit this air handler to in­stallation only in a single story residence & within conditioned space.
9. If the outdoor unit is to be installed later, or by oth­ers, then installation of the air handler must be made to allow access for refrigerant lines, or attach refrigerant lines to air handler when installing.
10. Make sure there are provisions for installing con­densate drain lines.
11. If side, front or rear return is required, air handler must be elevated or placed on a plenum (TAYPLNM100). Connecting return duct directly to the side, front or rear of the cabinet is not ap­proved.
12. Route refrigerant & condensate drain lines away from air handler so they do not interfere with ac­cess panels and filters.
13. When external accessories are used, the additional height and width requirements must be considered in the overall space needed.
14. These units are not approved for outdoor installa­tion.
15. These units are approved for draw-through application only.
16. Flow-through Bypass Humidifiers Excessive bypass air may cause water blow-off, which will adversely affect system operation and air cleaner performance. To verify bypass airflow, fol­low the Bypass Humidifier Pre-Installation Check­out and Set-Up Procedures available through your local distributor. Ask for publication number 18­CH37D1-1.
Steam and Flow-through Fan Power Duct­mounted Humidifiers
Follow the humidifier installation instructions. These should only be installed on the supply air side of the system.
Installer’s Guide
CREWS 5-8 OCATED ON EFT SIDE
1
3
Figure 3 Closeup of Spear Locations
Figure 4
2 Piece Wrapper Spear
2
4
B. Two Piece Cabinet Disassembly
(OPTIONAL)
NOTE: For easier installation into tight areas, the 4 and 5 ton air handlers can be disassembled and reas-
sembled after moved to an attic or other space.
Steps for disassembly and reassembly (See Figures 3 and 4)
1. Disconnect wiring.
2. Remove center bracket.
3. Remove blower assembly.
4. Remove coil.
8. Set air handler in place.
9. Attach screws - insure gaskets are aligned along flange.
10. Use foil tape to seal - use minimum 3" foil tape.
11. Insert coil.
12. Reinstall blower assembly.
13. Reinstall center bracket.
14. Reconnect wiring.
NOTE: In Downflow, remove coil before blower by re­versing steps 3 and 4.
5. Cut foil tape - minimum 3" foil tape.
6. Remove top 8 screws. See Figure 3.
7. Lift upper section.
18-GE12D1-8 3
Installer’s Guide
C. UNIT INSTALLATION
UPFLOW
a. For maximum efficiency, the horizontal drip
tray should be removed. See Figures 5, 6 and 7. Tray removal requires that the coil be removed by sliding the coil out on the coil channel sup­ports. There is a coil support tab at the top of the coil connected to the case must be removed first. Remove 1 inch insulation strip covering the lip of the drip tray. The tray is detached by removing the two screws at the drain pan. Remove the two screws holding the two brackets at the top of the coil. Remove drip tray by gently breaking the seal between the drip tray and drain pan.
b. Remove the factory installed baffle assembly
from the apex of the coil by using a 5/16" nutdriver to remove the screw. Replace this baffle with the factory supplied narrow coil baffle using the screws removed previously. See Figure
8. Reinstall coil assembly.
!
CAUTION
When installing the narrow coil baffle, make sure to align the baffle up with the holes so NOT to puncture
the coil tubing.
Figure 5 Drip Pan Foam Removal
c. Position unit on Pedestal or other suitable foun-
dation. If Pedestal is not used, a frame strong enough to support the total weight must be pro­vided. Provide a minimum height of 14 inches for proper unrestricted airflow.
d. If a return air duct is connected to the air han-
dler, it must be the same dimensions as shown in the outline drawing on page 14.
e. Pedestal and unit should be isolated from the
foundation using a suitable isolating material.
f. Openings where field wiring enters the
cabinet must be completely sealed. Location of power entry is shown on the Outline Drawing. Use 2.5" clear stickers provided to seal all unused electrical knockouts. See Figure 13.
g. After ductwork connections are made, seal air-
tight and per Local codes.
DOWNFLOW
a. For maximum efficiency, the horizontal drip
tray should be removed. See the Downflow Kit Installer's Guide 18-GJ23D1-1 for complete in­structions.
b. If a return duct is connected to the air handler, it
must be the same dimensions as the return opening shown in the outline drawing on page
15.
Figure 6 Horitzontal Drip Pan Removal
Figure 7 Drip Pan Bracket Removal
4 18-GE12D1-8
Installer’s Guide
c. Openings where field wiring enters the
cabinet must be completely sealed. Loca­tion of power entry is shown in the outline drawing. Use 2.5" clear stickers provided to seal all unused electrical knockouts. See Figure 13.
d. After ductwork connections are made, seal air-
tight and per Local codes.
DOWNFLOW BAFFLE KIT
SCREWS TO REMOVE COIL
7/8" GASKET
For Maximum Efficiency on
Horizontal Left,
Upflow and Downflow
Remove and Discard
Figure 8
DISCARD DRIP TRAY
Replace with Narrow Baffle
7/8" GASKET
SECT. X-X
(TYP. BOTH SIDES)
WATER
BLOW-OFF
BAFFLES
ATTACH WITH
2 SCREWS
EACH SIDE
X
X
1/2" GASKET INSIDE SURFACE OF BAFFLE
WATER
DIVERTER
BAFFLES
(5-ton only)
FILL WITH SEALANT
SCREWS TO REMOVE COIL
Figure 9
18-GE12D1-8 5
Installer’s Guide
Figure 10
Figure 11
FOR DOWNFLOW OR HORIZONTAL LEFT APPLICATIONS:
WHEN INSERTING COIL, TILT COIL FORWARD TO ALLOW DRAINPAN TO CLEAR TABS ON COIL CHANNEL SUPPORTS.
DRAINPAN SHOWN IN PLACE
TAB - AS MOUNTED ON COIL CHANNEL SUPPORT
TO REMOVE BLOWER ASSEMBLY WHEN COIL IN PLACE, PRESS UP ON COIL USING THUMBS WHILE PULLING BLOWER FORWARD.
Figure 12
6 18-GE12D1-8
Electrical Knockout Sticker Sheet
Installer’s Guide
Rail
Figure 13
HORIZONTAL LEFT
a. For maximum efficiency and Customer ease of
filter maintenance, it is recommended that a properly sized remote filter and grille be in­stalled for horizontal applications. Airflow should not exceed the face velocity of the filter being used. The factory installed filter should then be removed from the unit.
b. To convert the unit to horizontal left, front ac-
cess, slide the coil out on the coil channel sup­ports and rotate the complete coil 180 degrees.
c. Remove the factory installed baffle assembly
from the apex of the coil by using a 5/16" nutdriver to remove the hex head screw. There is a coil support tab at the top of the coil con­nected to the case must be removed first. Re­place this baffle with the factory supplied narrow coil baffle using the screws removed previously. See Figure 9.
d. The coil is then inserted back into the cabinet on
the opposite side coil channel supports. The unit is now horizontal left with front access. Do not reattach coil support tab.
e. If the unit is suspended, it must be supported
from the bottom near both ends as well as the middle to prevent sagging. The service access must remain unobstructed. If the unit is sup­ported along the length of the front and back with rails, the air handler only needs to be sus­pended at both ends. See Figure 14.
Figure 14
If the unit is not suspended it must be supported as mentioned above and isolated carefully to pre­vent sound transmission. Vibration isolators (pur­chased locally) must be placed under the unit.
f. It is always recommended that an auxiliary drain
pan be installed under a horizontal air handler (See Condensate Piping) to prevent possible dam­age to ceilings.
g. Isolate the auxiliary drain pan from the unit or
from the structure.
h. Connect the auxiliary drain line to a separate
drain line (no trap is needed in this line) and ter­minate according to national and local codes.
i. If a return duct is connected to the air handler, it
must be the same dimensions as the return opening shown in the outline drawing on page
14.
j. Openings where field wiring enters the
cabinet must be completely sealed. Location of power entry is shown on the outline drawing. Use 2.5" clear stickers provided to seal all unused electrical knockouts. See Figure 13.
k. After ductwork connections are made, seal air-
tight and per Local codes.
18-GE12D1-8 7
Installer’s Guide
HORIZONTAL RIGHT
a. For maximum efficiency and Customer ease of
filter maintenance, it is recommended that a properly sized remote filter grille be installed for horizontal applications. Airflow should not ex­ceed the face velocity of the filter being used.
The factory installed filter should then be removed from the unit.
b. Unit is shipped from the factory in the upflow or
horizontal right configuration. Unit conversion is not required.
c. If the unit is suspended, it must be supported
from the bottom near both ends as well as the middle to prevent sagging. The service access must remain unobstructed. If the unit is sup­ported along the length of the front and back, the air handler only needs to be suspended at both ends. See Figure 14.
d. If the unit is not suspended it must be isolated
carefully to prevent sound transmission. Vibra­tion isolators (purchased locally) must be placed under the unit.
e. It is always recommended that an auxiliary drain
pan be installed under a horizontal air handler (See Condensate Drain Piping) to prevent pos­sible damage to ceilings.
f. Isolate the auxiliary drain pan from the unit or
from the structure.
g. If a return duct is connected to the air handler, it
must be the same dimensions as the return opening shown in the outline drawing on page
14.
h. If a return duct is connected to the air handler, it
must be the same dimensions as the return opening shown in the outline drawings.
i. Openings where field wiring enters the cabi-
net must be completely sealed. Location of power entry is shown on the outline drawing. Use 2.5" clear stickers provided to seal all unused electrical knockouts. See Figure 13.
j. After ductwork connections are made, seal air-
tight and per Local codes.
Figure 15
Flange Attachment
E. REFRIGERANT PIPING
IMPORTANT: Refrigerant piping must be routed to maintain service access to blower compartment and provide easy re­moval of filter access panel and filter.
NOTE: Penetration around the Refrigerant lines must be sealed and Electrical inlets need to be sealed at
both the low and the high voltage.
1. Refrigerant connections are made outside the cabi­net.
2. Installation of refrigerant lines is covered in the in­stallation instructions packaged with the outdoor unit. Evacuation, leak testing and brazing proce­dures are included in those instructions. Read those instructions before starting installation of refriger­ant lines.
NOTE: TXV Equipped is Non-Bleed, and may require a start kit on the outdoor unit.
Figure 16
BRAZE SHIELD
D. DUCT CONNECTIONS
The supply and return air ducts should be connected to the unit with flame retardant duct connectors. Convertible duct flanges are provided on the discharge opening to provide a “flush fit” for 3/4" or 1-1/2" duct board applications, see the Outline drawing on page 16 for sizes of the duct connections. After the duct is se­cured, seal around the supply duct to prevent air leak­age.
NOTE: If the convertible duct flanges are not used, they must be removed and discarded for proper airflow.
8 18-GE12D1-8
Installer’s Guide
F. BRAZING TO EVAPORATOR SECTION
NOTE: A brazing shield is provided in the information pack accompanying this unit. This shield fits over the refrigerant fittings while brazing. Wet the shield before brazing. See Figure 16.
IMPORTANT: Do NOT unseal refrigerant tubing until ready to cut and fit refrigerant lines.
1. Remove both sealing caps from indoor coil.
2. Field supplied tubing should be cut squared-off, en­suring the tube is still round and free of burrs at the connecting end. Clean the tubing to prevent contaminants from entering the system.
3. Run refrigerant tubing into the stub sockets of in­door unit coil. Refrigerant line openings must be
completely sealed.
4. Braze and evacuate according to indoor and outdoor installation instructions.
5. Seal around refrigerant lines.
PAINTED AREAS OF UNIT MUST BE SHIELDED DURING BRAZING
G. CONDENSATE DRAIN PIPING
NOTE: Make certain that the unit has been installed in a level position to ensure proper draining.
For proper drainage of condensate, the following steps should be followed:
1. The primary drain line must be trapped with a minimum of 2" water seal as shown in Figures 17 &
18. Do not use preformed 3/4" PVC running
traps.
The use of Field fabricated or manufactured traps as shown in Figures 18 & 19 is acceptable. The manufactured trap shown in Figure 18 allows for a float switch option to be added. Refer to the manufacturers data and instructions for details.
2. The trap must be located within 4 feet of the air handler drain outlet connection.
3. It is recommended that a clean-out tee or cross be installed in the primary drain line for future main­tenance (See Figure 18 & 19).
Manufactured traps
2" MINIMUM
The indoor blower is downstream of the evaporator coil which creates a negative pressure at the condensate drain connections during operation. The condensate drain connections in front of the indoor coil are 3/4" NPT. The lower connection is the primary drain. See Figure 17. Two secondary drain connections are provided for the different orientations (See Figure 17). The lower of the two should be connected as a backup to prevent conden­sate overflow by a blocked primary drain.
Figure 17
3/4" NPT Secondary drain connection
3/4" NPT Primary drain connection
2" MINIMUM
EZT-105
Figure 18
Field fabricated trap
CAP OR PLUG
2" MIN.
2" MIN.
Close as possible
Trap must be within 4' of air handler condensate drain connection.
4. Do not use reducing fittings in the condensate drain lines.
5. Slope the drain lines downward a minimum of 1/4" per foot.
6. Insulate the primary drain to prevent sweating where pipe temperature could meet or fall below dewpoint temperatures.
7. Provide means for drainage to prevent winter freeze-up of condensate line.
Figure 19
18-GE12D1-8 9
Installer’s Guide
8. Do not connect the drain line to a closed drain sys­tem.
9. Use Teflon nections! CPVC cement!
It is always recommended that an auxiliary drain pan be installed under a horizontally installed air handler.
Connect the auxiliary drain line to a separate drain line (no trap is needed in this line) and terminate according to local codes.
NOTE: DO NOT use a torch or flame near the plastic drain pan coupling.
NOTE: DO NOT tighten the drain pipe excessively. Sup­port the condensate piping and traps outside the unit to prevent strain on the drain coupling.
®
tape on the air handler drain line con-
Do Not Use pipe joint compound or PVC/
H. ELECTRICAL — POWER WIRING
1. These Air Handlers are shipped from the factory wired for 230 volts. The units may be wired for 208 volts. Follow instructions on unit wiring diagram lo­cated on blower housing and in the Service Facts document included with the unit.
2. The selection of wire and fuse sizes should be made according to the Minimum Branch Circuit Ampacity and the Maximum Overcurrent Device listed on the unit nameplate.
!
WARNING
TO PREVENT INJURY OR DEATH DUE TO ELECTRICAL SHOCK OR CONTACT WITH MOVING PARTS, LOCK UNIT DISCONNECT SWITCH IN OPEN POSITION BE-
FORE SERVICING UNIT.
3. Field wiring diagrams for electric heaters and unit accessories are shipped with the accessory.
4. Wiring must conform to National and Local codes.
If an electric heater is not installed, connections are made through the 7/8" knockout into the air handler junction box to the two power leads and ground wire connections which are located near the discharge of the blower.
NOTE: If air handler is used with or without a heater, the electrical entry hole as well as any other cabinet penetrations must be sealed air-tight.
I.CONTROL WIRING
1. Connect wiring between indoor unit, outdoor unit and Comfort Control. The use of color-coded low­voltage wires is recommended.
2. A low voltage terminal board is provided for control wiring, and is located on the left side of the cross brace in the center of the unit.
3. If the low voltage wiring diagram is not listed in this installer’s guide for the particular application, refer to the wiring diagram located on the control box cover of the outdoor unit or in the outdoor unit’s service facts.
IMPORTANT: When supplementary heaters are installed, inspect to insure that all packaging material has been removed.
J. AIRFLOW ADJUSTMENT
!
CAUTION
Disconnect power to the air handler before changing dip switch positions. Failure to follow this procedure may result in equip­ment damage.
Blower speed changes are made on the ECM Fan Con­trol mounted on the control box. The ECM Fan Control controls the variable speed motor. There is a bank of 8 dip switches (See Figure 20). The dip switches work in pairs to match the airflow for the outdoor unit size (tons), cooling airflow adjustment, Fan off-delay options, and heating airflow adjustment. The switches appear as shown in Figure 21. If the airflow needs to be increased or decreased, see the Airflow Label on the air handler or the Blower Per­formance Table in the Service Facts. Information on changing the speed of the blower motor for your specific outdoor model size is in the Blower Performance Table.
10 18-GE12D1-8
Installer’s Guide
Be sure to set the airflow for the correct tonnage. Refer to blower housing for correct setting.
Switches 1 - 4 Cooling Airflow Switches 5 - 6 Fan Off Delay Options Switches 7 - 8 Auxiliary Heat
CFM SELECTION LIGHT
ECM FAN CONTROL
DIP SWITCHES
Figure 20
From Dwg. 800796a
If the optional humidistat is used, remove R-BK jumper from the low voltage terminal board (not shown) and in­stall the humidistat between R and BK. (Jumper R to O for cooling-only/non-heat pump systems with a humidis­tat.)
INDOOR BLOWER TIMING
IMPORTANT: Leave dip switch 5 & 6 in the "as-shipped" position during system start-up and check out. Afterwards, ad­just as desired.
The FAN-OFF period is set on the ECM Fan Control board by dip switches #5 and #6. The blower off-delay settings are as follows:
COOLING OFF - DELAY OPTIONS
SWITCH SETTINGS
SELECTION
5 - OFF 6 - OFF NONE SAME
5 - ON 6 - OFF 1.5 MINUTES 100% *
5 - OFF 6 - ON 3 MINUTES 50%
5 - ON 6 - ON ENHANCED** 50 - 100%
** - This ENHANCED MODE selection provides a ramping up and ramping down of the blower speed to provide improved comfort, quietness, and potential energy savings. The graph shows the ramping process.
NOMINAL AIRFLOW
NOTE: Direct drive motors have bearings which are permanently lubricated and under normal use lubrica­tion is not recommended.
100% if necessary
80%
Dehumidify
50%
Fast Coil Cooling
FAN OPERATION (CFM)
OFF OFF
and Heating
Efficiency
50%
Figure 21
COOLING
HEATING
AIRFLOW
FAN OFF
DELAY
DIP SWITCHES (AS SHIPPED)
AUXILIARY
HEAT SPEEDS
1
minute
COMPRESSOR OPERATION ON
7.5
minutes
as required
3
minutes
OFF
K. CHECKOUT PROCEDURE
1. Check the Air Handler installation in accordance with the instructions on page 16.
2. “Operational Procedure” for the system installation can be found in the outdoor unit installer guide and will be compatible with this Air Handler.
18-GE12D1-8 11
Installer’s Guide
4TEE3F39, 48, 64 AIR HANDLERS WITH SINGLE STAGE COOLING, 2 STAGE HEAT
COMFORT CONTROL
2-STAGE HEAT/ 1-STAGE COOL
VARIABLE SPEED
AIR HANDLER
COOLING
O.D. SECTION
(SINGLE SPEED)
NOTES:
1. LOW VOLTAGE WIRING TO BE NO. 18 A.W.G. MINIMUM CONDUCTOR.
2. WHEN HEATERS ARE USED, DISCARD POWER LEADS WITH POLARIZED PLUG PM-A AND CONNECT 1-PF TO MATING PLUG IN THE HEATER CONTROL BOX AS SHOWN.
3. TERMINAL W2 WILL HAVE INTERNAL CONNECTIONS ONLY IF 2ND CONTACTOR IS USED BY THE HEATER FOR CONTROLLING POWER TO ELECTRIC HEAT ELEMENTS. IF 2ND (BH) CONTACTOR IS NOT USED, THEN FIELD CONNECTIONS TO W2 CAN BE OMITTED AS APPROPRIATE.
4. CONNECTIONS TO "R", "BK", "O" AND "Y" MUST BE MADE AS SHOWN FOR PROPER OPERATION OF BLOWER WITH HUMIDISTAT IN COOLING.
From Dwg. No. B801074
4TEE3F39, 48, 64 AIR HANDLERS WITH SINGLE STAGE HEAT PUMP
HEAT PUMP
O.D. SECTION
(SINGLE SPEED)
NOTES:
1. LOW VOLTAGE WIRING TO BE NO. 18 A.W.G. MINIMUM CONDUCTOR.
2. WHEN HEATERS ARE USED, DISCARD POWER LEADS WITH POLARIZED PLUG PM-A AND CONNECT 1-PF TO MATING PLUG IN THE HEATER CONTROL BOX AS SHOWN.
3. TERMINAL W2 WILL HAVE INTERNAL CONNECTIONS ONLY IF 2ND CONTACTOR IS USED BY THE HEATER FOR CONTROLLING POWER TO ELECTRIC HEAT ELEMENTS. IF 2ND (BH) CONTACTOR IS NOT USED, THEN FIELD CONNECTIONS TO W2 CAN BE OMITTED AS APPROPRIATE.
4. IF ODT IS NOT USED, THEN CONNECT APPROPRIATE JUMPER FROM W1 TO W2 TO W3 ON LVTB..
5. CONNECTIONS TO "R", "BK", "O" AND "Y" MUST BE MADE AS SHOWN FOR PROPER OPERATION OF BLOWER WITH HUMIDISTAT IN COOLING.
6. CONNEECT W2 TO W3 ONLY IF USING HEATER WITH 3 HEATER STAGES.
COMFORT CONTROL
VARIABLE SPEED
AIR HANDLER
From Dwg. No. B801077
12 18-GE12D1-8
Installer’s Guide
4TEE3F AIR HANDLERS WITH 2 STEP COOLING
STEP
Air Handler
Notes:
1. Be sure power supply agrees with equipment nameplate.
2. Power wiring and grounding of equipment must comply with local codes.
3. Low voltage wiring to be No. 18 AWG minimum conductor.
4. If outdoor thermostat (ODT) is not used, connect W2 to W3.
5. Be sure the jumper between “R” and “BK” is cut or removed (See Note B below).
6. With “O” and “Y/Y2” energized, indoor fan is at 80% airflow.
7. With “O”, “Y/Y2” and “BK” energized, indoor fan is at 100% airflow.
8. When heaters are used, discard power leads with polarized plug PM-A and connect 1-PF to mating plug in the heater control box as shown.
REQUIRED WIRING
• Refer to Field Hook-up Diagrams.
• 4TTX6/4TWX6/4A7A6/4A6H6 units require 80% airflow with “Y1”
(firststage), 100% airflow with “Y2” (second stage).
Note A – The installer must jumper at the LVTB “R” to “O”.
Note B – Cut/remove the factory installed “BK” jumper.
• Connect “Y1” from thermostat to “Y/Y2” at VS Air Handler to “Y1” at
Outdoor Unit.
• Connect “Y2” from thermostat to “BK” at VS Air Handler to “Y2” at
Outdoor Unit.
See Note B
4TEE3F AIR HANDLERS WITH 2 STEP HEAT PUMP
STEP
Notes:
1. ODT-B must be set lower than ODT-A.
2. If ODT-B is not used, connect A Jumper wire from W3 to W2. If ODT-A is not used, connect a jumper wire from W2 to W1.
3. If electric heat does not have 3rd contactor (CH), connect a jumper wire from W3 to W2. If electric heat does not have 2nd contactor (BH), connect a jumper wire from W2 to W1.
4. X2 must be connected to variable speed air handler terminal W3, as shown, for proper indoor air flow during the defrost cycle.
5. Connect only if used with applicable indoor thermostat.
6. When heaters are used, discard power leads with polarized plug PM-A and connect 1-PF to mating plug in the heater control box as shown.
REQUIRED WIRING
• Refer to Field Hook-up Diagrams.
• 4TTX6/4TWX6/4A7A6/4A6H6 units require 80% airflow with “Y1”
(firststage), 100% airflow with “Y2” (second stage).
Note A – The installer must jumper at the LVTB “R” to “O”.
Note B – Cut/remove the factory installed “BK” jumper.
• Connect “Y1” from thermostat to “Y/Y2” at VS Air Handler to “Y1” at
Outdoor Unit.
• Connect “Y2” from thermostat to “BK” at VS Air Handler to “Y2” at
LEGEND
FACTORY WIRING
FIELD WIRING
Outdoor Unit.
18-GE12D1-8 13
Installer’s Guide
4TEE3F48 AIR HANDLERS WITH 2 STAGE COOLING, 2 STAGE HEAT
COMFORT CONTROL
VARIABLE SPEED
AIR HANDLER
2 STAGE
AIR CONDITIONER
NOTES:
1. BE SURE POWER SUPPLY AGREES WITH EQUIPMENT NAMEPLATE.
2. POWER WIRING AND GROUNDING OF EQUIPMENT MUST COMPLY WITH LOCAL CODES.
3. LOW VOLTAGE WIRING TO BE NO. 18 AWG MINIMUM CONDUCTOR.
4. IF OUTDOOR THERMOSTAT (ODT) IS NOT USED, CONNECT W2 TO W3.
5. WHEN HEATERS ARE USED, DISCARD POWER LEADS WITH POLARIZED PLUG PM-A AND CONNECT 1-PF TO MATING PLUG IN THE HEATER CONTROL BOX AS SHOWN.
4TEE3F48 AIR HANDLERS WITH 2 STAGE HEAT PUMP
HEAT PUMP
O.D. SECTION
(2 STAGE)
NOTES:
1. LOW VOLTAGE WIRING TO BE NO. 18 A.W.G. MINIMUM CONDUCTOR.
2. WHEN HEATERS ARE USED, DISCARD POWER LEADS WITH POLARIZED PLUG PM-A AND CONNECT 1-PF TO MATING PLUG IN THE HEATER CONTROL BOX AS SHOWN.
3. TERMINAL W2 WILL HAVE INTERNAL CONNECTIONS ONLY IF 2ND CONTACTOR IS USED BY THE HEATER FOR CONTROLLING POWER TO ELECTRIC HEAT ELEMENTS. IF 2ND (BH) CONTACTOR IS NOT USED, THEN FIELD CONNECTIONS TO W2 CAN BE OMITTED AS APPROPRIATE.
4. IF ODT IS NOT USED, THEN CONNECT APPROPRIATE JUMPER FROM W1 TO W2 TO W3 ON LVTB..
5. CONNEECT W2 TO W3 ONLY IF USING HEATER WITH 3 HEATER STAGES.
COMFORT CONTROL
VARIABLE SPEED
AIR HANDLER
14 18-GE12D1-8
Installer’s Guide
OUTLINE DRAWING FOR 4TEE3F39, 48, 64
From Dwg. D802101 Rev. 9
18-GE12D1-8 15
Installer’s Guide
4TEE3F39, 48, 64 AIR HANDLERS DIMENSIONAL DATA
H
21.0"
4TEE3F39A, 48A, 48B & 60A Are two piece cabinets
Model No. H W
4TEE3F39A1000A
4TEE3F48A1000A 4TEE3F48B1000A
4TEE3F64A1000A
16 18-GE12D1-8
57.90 23.50
W
Installer’s Guide
18-GE12D1-8 17
CHECKOUT PROCEDURES
After installation has been completed, it is recommended that the Air Handler be checked against the following checklist.
1. Make sure power is “OFF” at power disconnect
switch ........................................................................ [ ]
2. Check all field wiring for tight connections. See that
grounding of unit is in accord with code ................. [ ]
3. Make sure unit suspension (if used) is secure and that there are no tools or loose debris in, around or on
top of the unit ........................................................... [ ]
4. Check all duct outlets; they must be open and unre-
stricted ...................................................................... [ ]
5. Check drain lines and be sure all joints are tight
6. Make sure secondary drain pan is installed ..... [ ]
7. Check power supply for correct requirements per
unit nameplate ......................................................... [ ]
8. Check filters for proper size. Inform owner of
proper procedure for removal and reinstallation .... [ ]
9. Energize the system and carefully observe its op-
eration; make any necessary adjustment ............... [ ]
10. Instruct owner, engineer (if possible) on proper operating procedure and leave Use and Care Manual
with owner ................................................................ [ ]
.................................................................................. [ ]
SUPPLEMENTARY HEATERS CHECKOUT PROCEDURES,
IF a heater is USED, see "limitations and recommendations"
to determine if the heater requires a SPECIAL CIRCUIT.
1. Be sure the disconnect switch is “OFF”, and safety label (if any) is attached ................................................ [ ]
2. Check on field wiring for tight connections and grounding according to codes ............................................... [ ]
3. Check circuit protection for proper size per nameplate specifications ........................................................... [ ]
4. Check control box panel — in place and secured .......................................................................................... [ ]
NOTE: OPERATION OF HEATERS MUST BE CHECKED DURING THE OPERATION CHECK OF THE TOTAL SYSTEM.
Trane 6200 Troup Highway Tyler, TX 75707 www.trane.com
For more information contact your local dealer (distributor)
Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change design and specifications without notice.
06/10
Loading...