Trane 4PXCAU24BS3HAB Installer's Manual

Page 1
WARNING
!
18-AD41D1-1B-EN
WARNING
!
Installer’s Guide
Cased Aluminum Coils
"Dedicated Upow / Downow"
Convertible to horizontal with separately purchased kit
Upow models:
4PXCAU24BS3HAB 4PXCAU32BS3HAB 4PXCBU24BS3HAB 4PXCBU30BS3HAB 4PXCCU30BS3HAB 4PXCBU36BS3HAB 4PXCCU36BS3HAB 4PXCBU42BS3HAB
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information pack
upon completion of work.
WARNING (Medium/high pressure)
System contains oil and refrigerant under high pressure. Recover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use non-approved refrigerants, refrigerant substitutes, or refrigerant additives.
Failure to follow proper procedures or the use of non­approved refrigerants, substitutes, or refrigerant additives
could result in death, serious injury, or equipment damage.
This product can expose you to chemicals including lead, which are known to the State of California to case cancer and birth defects or other reproductive harm. For more information go to www. P65Warnings.ca.gov
A. GENERAL
These coils are designed for use in combination with a heat pump or cooling outdoor section using R-410A REFRIGERANT.
The 4PXC equipment has been evaluated in accordance with the Code of Federal Regulations, Chapter XX, Part 3280 or the equivalent. “Suitable for Mobile Home use” The height of the Furnace, Coil and discharge duct work must be 7 ft. or less.
Inspect the coil for shipping damage. Notify the transportation company immediately if the coil is damaged.
B. APPLICATION INFORMATION
NOTE: 4PXC upow coils may be installed in Upow, Down­ow, Horizontal Right with kit, and Horizontal Left with kit. 4PXC downow coils may be installed in Downow and Horizontal Right with kit.
1. FURNACE AND COIL The coil MUST BE installed downstream (in the outlet air)
of the furnace.
4PXCCU42BS3HAB 4PXCBU48BS3HAB 4PXCCU48BS3HAB 4PXCDU48BS3HAB 4PXCCU60BS3HAB 4PXCDU60BS3HAB
Downow models:
4PXCBD30BS3HDB 4PXCBD36BS3HDB 4PXCCD36BS3HDB 4PXCBD42BS3HDB 4PXCCD42BS3HDB
Table of Contents
General .................................................................................1
Application Information ......................................................1
Recommendation ................................................................2
Furnace in Upow Position ................................................2
Furnace in Downow Position ...........................................2
Maximum Airow Setting, CFM ..........................................3
Installing / Brazing Refrigerant Lines ................................3
Leak Check...........................................................................4
Condensate Drain Piping ....................................................4
Cleaning the Coil .................................................................4
Outline Drawings .................................................................5
Troubleshooting Indoor TXV / Cooling Mode ...................7
NOTE: OPTIONAL DOWNFLOW GASKET INSTALLATION: For unusually humid applications that expect prolonged operation above 70% RH, it is recommended to use the BAYGSKT001A0 gasket kit to prevent water from forming on the bottom of the drain pan and dripping into the supply ductwork.
2. INDOOR UNIT AIRFLOW Indoor unit must provide the required airflow for the heat
pump or cooling combinations approved for these coils.
IMPORTANT: Review your installation requirements. Check the table on the outline drawings and note all dimensions for your coil before beginning the installation.
4PXCCD60BS3HDB 4PXCDD60BS3HDB
Figure 1
Page 2
Installer’s Guide
CAUTION
!
TH SIDES)
SELF TAPPING SCREWS (4)
CAUTION
!
Remove and Discard
Replace
C. RECOMMENDATION
If a coil is part of the total system installation, use the Installer’s Guide packaged with the furnaces, outdoor sections, and ther­mostat for physically installing those components.
IMPORTANT:
If installing the coil in the horizontal position, you MUST use the horizontal kit listed below for this coil model num-
ber and follow the instructions in the installation guide provided with the conversion kit.
NOTE:
4PXC upow coils may be installed in Upow, Downow, Horizontal Right with kit, and Horizontal Left with kit. 4PXC downow coils may be installed in Downow and Horizontal Right with kit.
Model Number Horizontal Kit No.
4PXCAU24BS3HAB 4PXCAU32BS3HAB 4PXCBU24BS3HAB 4PXCBU30BS3HAB 4PXCCU30BS3HAB 4PXCBD30BS3HDB
4PXCBU36BS3HAB 4PXCCU36BS3HAB 4PXCBD36BS3HDB
4PXCCD36BS3HDB 4PXCBU42BS3HAB
4PXCCU42BS3HAB 4PXCBU48BS3HAB 4PXCCU48BS3HAB 4PXCDU48BS3HAB 4PXCBD42BS3HDB 4PXCCD42BS3HDB
4PXCCU60BS3HAB 4PXCDU60BS3HAB 4PXCCD60BS3HDB 4PXCDD60BS3HDB
BAYCONV18B
BAYCONV23B
BAYCONV27B
BAYCONV30B
Figure 2
2. UPFLOW GAS FURNACE
a. Apply gasket material (duct seal field supplied) to ALL mating surfaces between the furnace and the coil case.
b. Set the coil case on top of the furnace. Connect the ductwork to the coil case using field supplied screws.
See Figure 3.
c. Secure the coil case to the furnace and seal for air leaks as required.
1-1/2” MAXIMUM FIELD SUPPLIED
CASED
COIL
FOR UPFLOW /
HORIZONTAL LEFT
INSTALLATIONS
SCREWS
UPFLO
FURNA
W CE
(BO
Figure 3
E. FURNACE IN DOWNFLOW POSITION
D. FURNACE IN UPFLOW POSITION APPLICATION USES UPFLOW COIL MODELS ONLY
Caution: This coil is pressurized with 8-12 psig of dry
air. Do not stand directly in front of the coil connections when removing sealing plugs. If no pressure is released,
Caution: This coil is pressurized with 8-12 psig of dry
air. Do not stand directly in front of the coil connections when removing sealing plugs. If no pressure is released, check for leaks.
1. UPFLOW COIL CONVERSION (Models: 4PXCBU36BS3HAB, 4PXCCU36BS3HAB, 4PXCBU42BS3HAB, 4PXCCU42BS3HAB, 4PXCBU48BS3HAB, 4PXCCU48BS3HAB, 4PXCDU48BS3HAB, 4PXCCU60BS3HAB, 4PXCDU60BS3HAB only)
a. For maximum efficiency, remove the factory installed
two-piece baffle assembly from the apex of the coil by removing the 5/16” hex head screws. See Figure 2.
b. Replace only the top baffle using the same screws
previously removed.
check for leaks.
1. DOWNFLOW GAS FURNACE When a coil is used with a downflow furnace, a subbase
is not required between the coil case and combustible flooring.
a. Place the coil case on the furnace supply air plenum.
b. Secure the coil case to the plenum.
c. Set the furnace on top of the coil case, making sure
that the back side of the discharge opening is snug up against the duct flange at the top rear of the coil case.
d. Secure the coil case to the furnace and seal for air
leaks as required.
DOWNFLOW GASKET INSTALLATION (OPTIONAL):
2. For unusually humid applications that expect prolonged
operation above 70% RH, it is recommended to use the BAYGSKT001A0 gasket kit to prevent water from forming
2 18-AD41D1-1B-EN
on the bottom of the drain pan and dripping into the supply ductwork.
Page 3
Installer’s Guide
CAUTION
!
a. Lay the coil on its back side.
b. Locate the 4" wide gasket material found in BAYGSKT001A0.
c. Attach the 4" gasket material to three sides of the bottom
of the drain pan as shown. Make sure to start by matching up the edge of the gasket material to the inner edge of the drain pan by the coil fins and working outwards.
d. The gasket material can be cut or r ipped easily so that it
can be tailored to fit. The gasket material must cover the three sides along the entire length of the coil as shown in Figure 4.
Start here
F. MAXIMUM AIRFLOW SETTING, CFM
NOTE: Water blow-off could occur in certain installation posi-
tions if the airow setting exceeds the maximum values
listed.
Maximum airflow setting, CFM
Coil
4PXC*U24BS3HAB 900 750 800 900
4PXC*U30BS3HAB 1125
4PXC*D30BS3HDB n/a n/a
4PXC*U32BS3HAB
4PXC*D36BS3HDB n/a n/a
4PXC*U42BS3HAB 1575
4PXC*D42BS3HDB n/a n/a
4PXC*U48BS3HAB 1800 1475 1600 1800
4PXC*U60BS3HAB 2250
4PXC*D60BS3HDB n/a n/a
* May be "A", "B", "C", or "D"
Upflow Downflow
925
1350
1200 1350
1100
1300
1850
Horizontal
Left
1000
1200
1400
2000
Horizontal
Right
1125
13504PXC*U36BS3HAB
1575
2250
Attach Downow
Bottom Gasket
Figure 4
Note: when installing coil onto an S-Series furnaces in horizontal right or downow conguration, bend the anges downward for a ush t.
Figure 5
NOTE: The TXV setting on this unit may run high superheat
(15-25°F) by design when measured at the outdoor unit.
G. INSTALLING / BRAZING REFRIGERANT LINES
Do NOT open refrigerant valve at the outdoor unit until the
refrigerant lines and coil have been brazed, evacuated, and
leak checked. This would cause contamination of the refrig­erant or possible discharge of refrigerant to the atmosphere.
1. The following steps are to be considered when installing the refrigerant lines:
a. Determine the most practical way to run the lines.
b. Consider types of bends to be made and space
limitations.
c. Route the tubing making all required bends and properly secure the tubing before making final connections.
NOTE: Refrigerant lines must be isolated from the structure and the holes must be sealed weather tight after installation.
IMPORTANT:
Do not unseal refrigerant tubing until ready to t refrigerant
lines.
There is only a holding charge of dry air in the indoor coil, therefore no loss of operating refrigerant charge occurs when the sealing plugs are removed.
18-AD41D1-1B-EN 3
Page 4
Installer’s Guide
Capillary tubes will come out the top of bulb when positioned correctly.
Figure 6
NOTE:
TXV bulb MUST be protected (wrapped with wet rag) or removed, while brazing the tubing. Overheating of the
sensing bulb will affect the functional characteristics and performance of the comfort coil.
1. Remove both rubber plugs from the indoor coil.
2. Field supplied tubing should be cut square, round and free of burrs at the connecting end. Clean the tubing to prevent contaminants from entering the system.
3. Run the refrigerant tubing into the stub tube sockets of the indoor unit coil.
PAINTED AREAS OF THE UNIT MUST BE SHIELDED DURING BRAZING.
4. Flow a small amount of nitrogen through the tubing while brazing.
5. Use good brazing technique to make leakproof joints.
6. Minimize the use of sharp 90 degree bends.
7. Insulate the suction line and its fittings.
8. Do NOT allow un-insulated lines to come into contact with each other.
When replacing the TXV bulb, reinstall the bulb in the proper orientation. Some models will use a spring steel clip to attach the TXV bulb, and some models will use a hose clamp. When supplied with a hose clamp, the clamp should
be "snug" but not "tight" - the specication is to torque the hose clamp to 20 +/- 5 in-lbs.
9. Wrap the TXV with insulation after the hose clamp has been installed.
H. LEAK CHECK
1. Using a manifold gauge, connect an external supply of dry nitrogen to the gauge port on the liquid line.
2. Pressurize the connecting lines and indoor coil to 150 PSIG maximum.
3. Leak check brazed line connections using soap bubbles. Repair leaks (if any) after relieving pressure.
4. Evacuate and charge the system per the instructions packaged with the outdoor unit.
I. CONDENSATE DRAIN PIPING
Condensate drain connections are located in the drain pan at the bottom of the coil/enclosure assembly. The female threaded fitting protrudes outside of the enclosure for external connection. A field fabricated trap is not required for proper drainage due to the positive pressure of the furnace; however, it is recommended to prevent efficiency loss of conditioned air.
1. The drain hole in the drain pan must be cleared of all insulation.
2. Insulate the primary drain line to prevent sweating where dew point temperatures may be met. (Optional depending on climate and application needs)
3. Connect the secondary drai trap is needed in this line).
J. CLEANING THE COIL
The two piece door allows removal of the outer casing doors without interference from refrigerant or condensate lines.
The foil covered insulation on 4PXC coils should be wiped down and residual dirt and dust should be vacuumed up to maintain good air quality. See Figure 7.
The manufacturer’s recommendation for coil cleaning is to initially use only water to wash away debris that may have collected on and in the coil fin surface. Removing an evaporator coil is the best way to effectively clean a coil that is heavily contaminated. This is accomplished by removing the coil from the cabinet, sealing the liquid and vapor line and using a strong water stream such as from a garden hose, being careful to prevent fin damage. Use chemical cleaners, only when necessary.
NOTE:
Refer to Service Guideline, UN-SVG001C-EN, Evaporator
Coil Cleaning and Condensate Drain Maintenance Guide­lines for important information on cleaning coils with chemical treatments.
n line to a separate drain line (no
Figure 7
4 18-AD41D1-1B-EN
Page 5
Installer’s Guide
MODEL
4PXCAU24BS3 4PXCAU32BS3 4PXCBU24BS3
4PXCBU30BS3
4PXCBD30BS3
4PXCBU36BS3
4PXCBD36BS3
4PXCCU36BS3
4PXCBU42BS3
4PXCBD42BS3
4PXCBU48BS3
4PXCCU42BS3
4PXCCD42BS3
4PXCCU48BS3
4PXCDU48BS3
4PXCCU60BS3
4PXCCD60BS3
4PXCDU60BS3
4PXCDD60BS3
SEE FIGURE FIGURE A FIGURE A FIGURE B FIGURE A FIGURE A FIGURE A FIGURE A FIGURE A FIGURE A FIGURE A
SHIPPING WEIGHT (LBS.)39434754566164687377
REFRIGERANT CONTROL TXV (NON-BLEED)
HEIGHT "A" (IN.) 17 - 5/8
22 - 1/2 17 - 5/8
22 - 1/2
22 - 1/2
26 - 7/8 26 - 7/8 26 - 7/8 30 - 3/4 30 - 3/4
OVERALL WIDTH "B" (IN.) 14 - 1/2
14 - 1/2 17 - 1/2
17 - 1/2
21
17 - 1/2 21 24 - 1/2 21 24 - 1/2
OPENING WIDTH "C" (IN.)
13 - 5/8
13 - 5/8 16 - 5/8
16 - 5/8
20 - 1/8
16 - 5/8 20 - 1/8 23 - 5/8 20 - 1/8 23 - 5/8
TOP OPENING "D" 12 - 3/4
12 - 3/4 15 - 3/4
15 - 3/4
19 - 1/4
15 - 3/4 19 - 1/4 22 - 3/4 19 - 1/4 22 - 3/4
GAS CONNECTION 3/4 7/8
LIQUID CONNECTION 3/8
MATCHED FURNACE WIDTH
(NO ADAPTER RQUIRED)
14 - 1/2 14 - 1/2 17 - 1/2 17 - 1/2 21 17 - 1/2 21 24 - 1/2 21 24 - 1/2
DRAIN PAN PLASTIC
4PXCCD36BS3
FIGURE A
42
17 - 5/8
17 - 1/2
16 - 5/8
15 - 3/4
3/4
17 - 1/2
4PXCCU30BS3
FIGURE B
49
17 - 1/2
21
20 - 1/8
19 - 1/4
21
From Dwg
D346711 RevB
Outline Drawing for Upflow models: 4PXCAU24BS3HAB, 4PXCAU32BS3HAB, 4PXCBU24BS3HAB, 4PXCBU30BS3HAB, 4PXCCU30BS3HAB, 4PXCBU36BS3HAB, 4PXCCU36BS3HAB, 4PXCBU42BS3HAB,
4PXCCU42BS3HAB, 4PXCBU48BS3HAB, 4PXCCU48BS3HAB, 4PXCDU48BS3HAB, 4PXCCU60BS3HAB, 4PXCDU60BS3HAB and Downflow models: 4PXCBD30BS3HDB, 4PXCBD36BS3HDB,
4PXCCD36BS3HDB, 4PXCBD42BS3HDB, 4PXCCD42BS3HDB, 4PXCCD60BS3HDB, 4PXCDD60BS3HDB
18-AD41D1-1B-EN 5
Page 6
Installer’s Guide
From Dwg. D346711 RevB
6 18-AD41D1-1B-EN
Page 7
Before starting, insure the
blower wheel, indoor and outdoor
coils are clean.
Installer’s Guide
Troubleshooting Indoor TXV / Cooling Mode
Is sub cooling at the
outdoor unit between
8 to 12F?
Verify line set is
sized properly for application
NO
YES
NO
Is superheat
< 5F?
NO
Is superheat
< 25F?
NO
Is the liquid line
temperature at indoor
coil within 8F of outdoor
liquid line temperature?
YES
Is indoor
temperature more
than 85F?
YES
The system is running at max
capacity and this may be
causing the High superheat.
Wait until indoor temperature
is less than 80F and check
superheat again.
YES
NO
Is air flow at least
350 CFM per ton?
Remove sensing bulb from the
suction line. Measure superheat
at indoor coil while holding the
bulb in bare hand for one minute.
Does superheat decrease?
Verify Inlet screen
assembly is clear
YES
NO
of inlet tube
of debris
YES
NO
Correct air
flow
problem
Measure superheat at indoor coil
YES
while placing the bulb in an ice and water bath for one minute.
Does superheat increase?
Verify Inlet screen
assembly is clear
TXV is OK
YES
NO
of inlet tube
of debris
Confirm that charge
Is sub cooling less
than 8F?
NO
Confirm that
charge is
correct.
YES
is correct and look
for dirty or restricted
outdoor coil.
Replace the
TXV
18-AD41D1-1B-EN 7
Page 8
About Trane and American Standard Heating and Air Conditioning
Trane and American Standard create comfortable, energy efficient indoor environments for residential applications. For more information, please visit www.trane.com or www.americanstandardair.com
The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.
18-AD41D1-1B-EN 27 Apr 2021 Supersedes 18-AD41D1-1A-EN (February 2021)
© 2021
Loading...