ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information pack
upon completion of work.
WARNING (Medium/high pressure)
Contains Refrigerant!
System contains oil and refrigerant under high pressure.
Recover refrigerant to relieve pressure before opening
the system. See unit nameplate for refrigerant type. Do not
use non-approved refrigerants, refrigerant substitutes, or
refrigerant additives.
Failure to follow proper procedures or the use of nonapproved refrigerants, substitutes, or refrigerant additives
could result in death, serious injury, or equipment damage.
This product can expose you to chemicals including
lead, which are known to the State of California to case
cancer and birth defects or other reproductive harm.
For more information go to www. P65Warnings.ca.gov
A. GENERAL
These coils are designed for use in combination with a heat pump
or cooling outdoor section using R-410A REFRIGERANT.
The 4PXC equipment has been evaluated in accordance with
the Code of Federal Regulations, Chapter XX, Part 3280 or the
equivalent. “Suitable for Mobile Home use” The height of the
Furnace, Coil and discharge duct work must be 7 ft. or less.
Inspect the coil for shipping damage. Notify the transportation
company immediately if the coil is damaged.
B. APPLICATION INFORMATION
NOTE: 4PXC upow coils may be installed in Upow, Downow, Horizontal Right with kit, and Horizontal Left with kit.
4PXC downow coils may be installed in Downow and
Horizontal Right with kit.
1. FURNACE AND COIL
The coil MUST BE installed downstream (in the outlet air)
NOTE:
OPTIONAL DOWNFLOW GASKET INSTALLATION: For
unusually humid applications that expect prolonged
operation above 70% RH, it is recommended to use the
BAYGSKT001A0 gasket kit to prevent water from forming
on the bottom of the drain pan and dripping into the
supply ductwork.
2. INDOOR UNIT AIRFLOW
Indoor unit must provide the required airflow for the heat
pump or cooling combinations approved for these coils.
IMPORTANT: Review your installation requirements. Check
the table on the outline drawings and note all dimensions
for your coil before beginning the installation.
4PXCCD60BS3HDB
4PXCDD60BS3HDB
Figure 1
Page 2
Installer’s Guide
CAUTION
!
TH SIDES)
SELF TAPPING SCREWS (4)
CAUTION
!
Remove
and
Discard
Replace
C. RECOMMENDATION
If a coil is part of the total system installation, use the Installer’s
Guide packaged with the furnaces, outdoor sections, and thermostat for physically installing those components.
IMPORTANT:
If installing the coil in the horizontal position, you MUST
use the horizontal kit listed below for this coil model num-
ber and follow the instructions in the installation guide
provided with the conversion kit.
NOTE:
4PXC upow coils may be installed in Upow, Downow,
Horizontal Right with kit, and Horizontal Left with kit.
4PXC downow coils may be installed in Downow and
Horizontal Right with kit.
a. For maximum efficiency, remove the factory installed
two-piece baffle assembly from the apex of the coil by
removing the 5/16” hex head screws. See Figure 2.
b. Replace only the top baffle using the same screws
previously removed.
check for leaks.
1. DOWNFLOW GAS FURNACE
When a coil is used with a downflow furnace, a subbase
is not required between the coil case and combustible
flooring.
a. Place the coil case on the furnace supply air plenum.
b. Secure the coil case to the plenum.
c. Set the furnace on top of the coil case, making sure
that the back side of the discharge opening is snug up
against the duct flange at the top rear of the coil case.
d. Secure the coil case to the furnace and seal for air
leaks as required.
DOWNFLOW GASKET INSTALLATION (OPTIONAL):
2.
For unusually humid applications that expect prolonged
operation above 70% RH, it is recommended to use the
BAYGSKT001A0 gasket kit to prevent water from forming
2 18-AD41D1-1B-EN
on the bottom of the drain pan and dripping into the supply
ductwork.
Page 3
Installer’s Guide
CAUTION
!
a. Lay the coil on its back side.
b. Locate the 4" wide gasket material found in
BAYGSKT001A0.
c. Attach the 4" gasket material to three sides of the bottom
of the drain pan as shown. Make sure to start by matching
up the edge of the gasket material to the inner edge of the
drain pan by the coil fins and working outwards.
d. The gasket material can be cut or r ipped easily so that it
can be tailored to fit. The gasket material must cover
the three sides along the entire length of the coil as shown
in Figure 4.
Start
here
F. MAXIMUM AIRFLOW SETTING, CFM
NOTE:
Water blow-off could occur in certain installation posi-
tions if the airow setting exceeds the maximum values
listed.
Maximum airflow setting, CFM
Coil
4PXC*U24BS3HAB900750800900
4PXC*U30BS3HAB1125
4PXC*D30BS3HDBn/an/a
4PXC*U32BS3HAB
4PXC*D36BS3HDBn/an/a
4PXC*U42BS3HAB1575
4PXC*D42BS3HDBn/an/a
4PXC*U48BS3HAB1800147516001800
4PXC*U60BS3HAB2250
4PXC*D60BS3HDBn/an/a
* May be "A", "B", "C", or "D"
Upflow Downflow
925
1350
12001350
1100
1300
1850
Horizontal
Left
1000
1200
1400
2000
Horizontal
Right
1125
13504PXC*U36BS3HAB
1575
2250
Attach Downow
Bottom Gasket
Figure 4
Note: when installing coil onto an S-Series furnaces
in horizontal right or downow conguration, bend
the anges downward for a ush t.
Figure 5
NOTE:
The TXV setting on this unit may run high superheat
(15-25°F) by design when measured at the outdoor unit.
G. INSTALLING / BRAZING REFRIGERANT LINES
Do NOT open refrigerant valve at the outdoor unit until the
refrigerant lines and coil have been brazed, evacuated, and
leak checked. This would cause contamination of the refrigerant or possible discharge of refrigerant to the atmosphere.
1. The following steps are to be considered when installing
the refrigerant lines:
a. Determine the most practical way to run the lines.
b. Consider types of bends to be made and space
limitations.
c. Route the tubing making all required bends and
properly secure the tubing before making final
connections.
NOTE: Refrigerant lines must be isolated from the structure and
the holes must be sealed weather tight after installation.
IMPORTANT:
Do not unseal refrigerant tubing until ready to t refrigerant
lines.
There is only a holding charge of dry air in the indoor coil, therefore
no loss of operating refrigerant charge occurs when the sealing
plugs are removed.
18-AD41D1-1B-EN 3
Page 4
Installer’s Guide
Capillary tubes will come
out the top of bulb when
positioned correctly.
Figure 6
NOTE:
TXV bulb MUST be protected (wrapped with wet rag) or
removed, while brazing the tubing. Overheating of the
sensing bulb will affect the functional characteristics and
performance of the comfort coil.
1. Remove both rubber plugs from the indoor coil.
2. Field supplied tubing should be cut square, round and free
of burrs at the connecting end. Clean the tubing to prevent
contaminants from entering the system.
3. Run the refrigerant tubing into the stub tube sockets of the
indoor unit coil.
PAINTED AREAS OF THE UNIT MUST BE SHIELDED DURING
BRAZING.
4. Flow a small amount of nitrogen through the tubing while
brazing.
5. Use good brazing technique to make leakproof joints.
6. Minimize the use of sharp 90 degree bends.
7. Insulate the suction line and its fittings.
8. Do NOT allow un-insulated lines to come into contact with
each other.
When replacing the TXV bulb, reinstall the bulb in the
proper orientation. Some models will use a spring steel clip
to attach the TXV bulb, and some models will use a hose
clamp. When supplied with a hose clamp, the clamp should
be "snug" but not "tight" - the specication is to torque the
hose clamp to 20 +/- 5 in-lbs.
9. Wrap the TXV with insulation after the hose clamp has
been installed.
H. LEAK CHECK
1. Using a manifold gauge, connect an external supply of dry
nitrogen to the gauge port on the liquid line.
2. Pressurize the connecting lines and indoor coil to 150 PSIG
maximum.
3. Leak check brazed line connections using soap bubbles.
Repair leaks (if any) after relieving pressure.
4. Evacuate and charge the system per the instructions packaged
with the outdoor unit.
I. CONDENSATE DRAIN PIPING
Condensate drain connections are located in the drain pan at the
bottom of the coil/enclosure assembly. The female threaded fitting
protrudes outside of the enclosure for external connection. A field
fabricated trap is not required for proper drainage due to the positive
pressure of the furnace; however, it is recommended to prevent
efficiency loss of conditioned air.
1. The drain hole in the drain pan must be cleared of all insulation.
2. Insulate the primary drain line to prevent sweating where
dew point temperatures may be met. (Optional depending on
climate and application needs)
3. Connect the secondary drai
trap is needed in this line).
J. CLEANING THE COIL
The two piece door allows removal of the outer casing doors
without interference from refrigerant or condensate lines.
The foil covered insulation on 4PXC coils should be wiped down
and residual dirt and dust should be vacuumed up to maintain
good air quality. See Figure 7.
The manufacturer’s recommendation for coil cleaning is to initially
use only water to wash away debris that may have collected on
and in the coil fin surface. Removing an evaporator coil is the best
way to effectively clean a coil that is heavily contaminated. This
is accomplished by removing the coil from the cabinet, sealing
the liquid and vapor line and using a strong water stream such
as from a garden hose, being careful to prevent fin damage. Use
chemical cleaners, only when necessary.
NOTE:
Refer to Service Guideline, UN-SVG001C-EN, Evaporator
Coil Cleaning and Condensate Drain Maintenance Guidelines for important information on cleaning coils with
chemical treatments.
n line to a separate drain line (no
Figure 7
4 18-AD41D1-1B-EN
Page 5
Installer’s Guide
MODEL
4PXCAU24BS3 4PXCAU32BS34PXCBU24BS3
4PXCBU30BS3
4PXCBD30BS3
4PXCBU36BS3
4PXCBD36BS3
4PXCCU36BS3
4PXCBU42BS3
4PXCBD42BS3
4PXCBU48BS3
4PXCCU42BS3
4PXCCD42BS3
4PXCCU48BS3
4PXCDU48BS3
4PXCCU60BS3
4PXCCD60BS3
4PXCDU60BS3
4PXCDD60BS3
SEE FIGUREFIGURE AFIGURE AFIGURE BFIGURE AFIGURE AFIGURE AFIGURE AFIGURE AFIGURE AFIGURE A
while placing the bulb in an ice
and water bath for one minute.
Does superheat increase?
Verify Inlet screen
assembly is clear
TXV is OK
YES
NO
of inlet tube
of debris
Confirm that charge
Is sub cooling less
than 8F?
NO
Confirm that
charge is
correct.
YES
is correct and look
for dirty or restricted
outdoor coil.
Replace the
TXV
18-AD41D1-1B-EN 7
Page 8
About Trane and American Standard Heating and Air Conditioning
Trane and American Standard create comfortable, energy efficient indoor environments for residential applications.
For more information, please visit www.trane.com or www.americanstandardair.com
The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are
committed to using environmentally conscious print practices.