Trane 4PXCAU24BS3HAA Installer's Manual

Page 1
WARNING
!
18-AD32D1-4E-EN
WARNING
!
Installer’s Guide
Cased Aluminum Coils "Dedicated Upflow / Downflow" Convertible to horizontal with separately purchased kit
Upflow models: 4PXCAU24BS3HAA 4PXCAU32BS3HAA 4PXCBU24BS3HAA 4PXCBU30BS3HAA 4PXCCU30BS3HAA 4PXCBU36BS3HAA 4PXCCU36BS3HAA 4PXCBU42BS3HAA
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information pack
upon completion of work.
WARNING (Medium/high pressure)
System contains oil and refrigerant under high pressure. Recover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use non-approved refrigerants, refrigerant substitutes, or refrigerant additives.
Failure to follow proper procedures or the use of non­approved refrigerants, substitutes, or refrigerant additives
could result in death, serious injury, or equipment damage.
This product can expose you to chemicals including lead, which are known to the State of California to case cancer and birth defects or other reproductive harm. For more information go to www. P65Warnings.ca.gov
A. GENERAL
These coils are designed for use in combination with a heat pump or cooling outdoor section using R-410A REFRIGERANT.
The 4PXC equipment has been evaluated in accordance with the Code of Federal Regulations, Chapter XX, Part 3280 or the equivalent. “Suitable for Mobile Home use” The height of the Furnace, Coil and discharge duct work must be 7 ft. or less.
Inspect the coil for shipping damage. Notify the transportation company immediately if the coil is damaged.
B. APPLICATION INFORMATION
NOTE: 4PXC upow coils may be installed in Upow, Downow, Horizontal Right with kit, and Horizontal Left with
kit.
4PXC downow coils may be installed in Downow and Horizontal Right with kit.
1. FURNACE AND COIL
The coil MUST BE installed downstream (in the outlet air) of the furnace.
4PXCCU42BS3HAA 4PXCBU48BS3HAA 4PXCCU48BS3HAA 4PXCDU48BS3HAA 4PXCCU60BS3HAA 4PXCDU60BS3HAA
Downflow models: 4PXCAD24BS3HDA 4PXCBD24BS3HDA 4PXCBD30BS3HDA 4PXCCD30BS3HDA 4PXCBD36BS3HDA 4PXCCD36BS3HDA 4PXCBD42BS3HDA 4PXCCD42BS3HDA
Table of Contents
General .................................................................................1
Application Information ......................................................1
Recommendation ................................................................2
Furnace in Upflow Position ................................................2
Furnace in Downflow Position ...........................................3
Maximum Airflow Setting, CFM ..........................................3
Installing / Brazing Refrigerant Lines ................................3
Leak Check ...........................................................................4
Condensate Drain Piping ....................................................4
Cleaning the Coil .................................................................4
Outline Drawings .................................................................5
Troubleshooting Indoor TXV / Cooling Mode ....................8
NOTE: OPTIONAL DOWNFLOW GASKET INSTALLATION: For unusually humid applications that expect prolonged operation above 70% RH, it is recommended to use the BAYGSKT001A0 gasket kit to prevent water from forming on the bottom of the drain pan and dripping into the sup­ply ductwork.
2. INDOOR UNIT AIRFLOW
Indoor unit must provide the required airflow for the heat pump or cooling combinations approved for these coils.
IMPORTANT: Review your installation requirements. Check the table on the outline drawings and note all dimensions for your coil before beginning the installation.
4PXCBD48BS3HDA 4PXCCD48BS3HDA 4PXCDD48BS3HDA 4PXCCD60BS3HDA 4PXCDD60BS3HDA
Figure 1
A341869P30
Page 2
Installer’s Guide
CAUTION
!
TH SIDES)
SELF TAPPING SCREWS (4)
CAUTION
!
Remove and Discard
Replace
C. RECOMMENDATION
If a coil is part of the total system installation, use the Installer’s Guide packaged with the furnaces, outdoor sections, and ther­mostat for physically installing those components.
IMPORTANT:
If installing the coil in the horizontal position, you MUST use the horizontal kit listed below for this coil model num-
ber and follow the instructions in the installation guide provided with the conversion kit.
NOTE:
4PXC upow coils may be installed in Upow, Downow, Horizontal Right with kit, and Horizontal Left with kit. 4PXC downow coils may be installed in Downow and Horizontal Right with kit.
Model Number Horizontal Kit No.
4PXCAU24BS3HAA
4PXCAU32BS3HAA 4PXCBU24BS3HAA 4PXCBU30BS3HAA 4PXCCU30BS3HAA 4PXCAD24BS3HDA 4PXCBD24BS3HDA 4PXCBD30BS3HDA 4PXCCD30BS3HDA
4PXCBU36BS3HAA 4PXCCU36BS3HAA 4PXCBD36BS3HDA 4PXCCD36BS3HDA
4PXCBU42BS3HAA 4PXCCU42BS3HAA 4PXCBU48BS3HAA 4PXCCU48BS3HAA 4PXCDU48BS3HAA 4PXCBD42BS3HDA 4PXCCD42BS3HDA 4PXCBD48BS3HDA 4PXCCD48BS3HDA 4PXCDD48BS3HDA
4PXCCU60BS3HAA 4PXCDU60BS3HAA 4PXCCD60BS3HDA 4PXCDD60BS3HDA
BAYCONV18A
BAYCONV23A
BAYCONV27A
BAYCONV30A
D. FURNACE IN UPFLOW POSITION APPLICATION USES UPFLOW COIL MODELS ONLY
Caution: This coil is pressurized with 8-12 psig of dry
air. Do not stand directly in front of the coil connections when removing sealing plugs. If no pressure is released, check for leaks.
1. UPFLOW COIL CONVERSION (Models: 4PXCBU36BS3HAA, 4PXCCU36BS3HAA, 4PXCBU42BS3HAA, 4PXCCU42BS3HAA, 4PXCBU48BS3HAA, 4PXCCU48BS3HAA, 4PXCDU48BS3HAA, 4PXCCU60BS3HAA, 4PXCDU60BS3HAA only)
a. For maximum efficiency, remove the factory installed
two-piece baffle assembly from the apex of the coil by removing the 5/16” hex head screws. See Figure 2.
b. Replace only the top baffle using the same screws
previously removed.
Figure 2
2. UPFLOW GAS FURNACE a. Apply gasket material (duct seal field supplied) to ALL
mating surfaces between the furnace and the coil case.
b. Set the coil case on top of the furnace. Connect the
ductwork to the coil case using field supplied screws.
c. Secure the coil case to the furnace and seal for air
leaks as required.
1-1/2” MAXIMUM FIELD SUPPLIED
CASED
COIL
FOR UPFLOW /
HORIZONTAL LEFT
INSTALLATIONS
SCREWS
UPFLO
FURNA
W CE
(BO
Figure 3
E. FURNACE IN DOWNFLOW POSITION
Caution: This coil is pressurized with 8-12 psig of dry
air. Do not stand directly in front of the coil connections when removing sealing plugs. If no pressure is released, check for leaks.
1. DOWNFLOW GAS FURNACE
When a coil is used with a downflow furnace, a subbase is not
required between the coil case and combustible flooring.
a. Place the coil case on the furnace supply air plenum.
b. Secure the coil case to the plenum.
c. Set the furnace on top of the coil case, making sure
that the back side of the discharge opening is snug up against the duct flange at the top rear of the coil case.
d. Secure the coil case to the furnace and seal for air
leaks as required.
2. DOWNFLOW GASKET INSTALLATION (OPTIONAL): For unusually humid applications that expect prolonged operation above 70% RH, it is recommended to use the BAYGSKT001A0 gasket kit to prevent water from forming on the bottom of the drain pan and dripping into the supply ductwork.
a. Lay the coil on its back side. b. Locate the 4" wide gasket material found in
18-AD32D1-4E-EN
Page 3
Installer’s Guide
CAUTION
!
BAYGSKT001A0.
c. Attach the 4" gasket material to three sides of the bottom
of the drain pan as shown. Make sure to start by matching up the edge of the gasket material to the inner edge of the drain pan by the coil fins and working outwards.
d. The gasket material can be cut or ripped easily so that
it can be tailored to fit. The gasket material must cover the three sides along the entire length of the coil as shown in Figure 4.
Start here
Attach Downflow Bottom Gasket
Figure 4
F. MAXIMUM AIRFLOW SETTING, CFM
NOTE: Water blow-off could occur in certain installation posi-
tions if the airow setting exceeds the maximum values
listed.
Maximum airflow setting, CFM
Coil
4PXC*U24BS3HAA 900
4PXC*D24BS3HDA n/a n/a
4PXC*U30BS3HAA 1125
4PXC*D30BS3HDA n/a n/a
4PXC*U32BS3HAA
4PXC*D36BS3HDA n/a n/a
4PXC*U42BS3HAA 1575
4PXC*D42BS3HDA n/a n/a
4PXC*U48BS3HAA 1800
4PXC*D48BS3HDA n/a n/a
4PXC*U60BS3HAA 2250
4PXC*D60BS3HDA n/a n/a
* May be "A", "B", "C", or "D"
NOTE: The TXV setting on this unit may run high superheat
(15-25°F) by design when measured at the outdoor unit.
G. INSTALLING / BRAZING REFRIGERANT LINES
Upflow Downflow
750
925
1350
1200 1350
1100
1300
1475
1850
Horizontal
Left
800
1000
1200
1400
1600
2000
Horizontal
Right
900
1125
13504PXC*U36BS3HAA
1575
1800
2250
Note: when installing coil onto an S-Series furnaces in horizontal right or downflow configuration, bend the flanges downward for a flush fit.
Figure 5
18-AD32D1-4E-EN 3
Do NOT open refrigerant valve at the outdoor unit until the
refrigerant lines and coil have been brazed, evacuated, and
leak checked. This would cause contamination of the refrig­erant or possible discharge of refrigerant to the atmosphere.
1. The following steps are to be considered when installing the refrigerant lines:
a. Determine the most practical way to run the lines.
b. Consider types of bends to be made and space limitations.
c. Route the tubing making all required bends and properly
secure the tubing before making final connections. NOTE: Refrigerant lines must be isolated from the structure and the holes must be sealed weather tight after installation.
IMPORTANT:
Do not unseal refrigerant tubing until ready to t refrigerant
lines.
There is only a holding charge of dry air in the indoor coil, therefore no loss of operating refrigerant charge occurs when the sealing plugs are removed.
Page 4
Installer’s Guide
Capillary tubes will come out the top of bulb when positioned correctly.
Figure 6
NOTE:
TXV bulb MUST be protected (wrapped with wet rag) or removed, while brazing the tubing. Overheating of the
sensing bulb will affect the functional characteristics and performance of the comfort coil.
1. Remove both rubber plugs from the indoor coil.
2. Field supplied tubing should be cut square, round and free of burrs at the connecting end. Clean the tubing to prevent contaminants from entering the system.
3. Run the refrigerant tubing into the stub tube sockets of the indoor unit coil.
PAINTED AREAS OF THE UNIT MUST BE SHIELDED DURING BRAZING.
4. Flow a small amount of nitrogen through the tubing while brazing.
5. Use good brazing technique to make leakproof joints.
6. Minimize the use of sharp 90 degree bends.
7. Insulate the suction line and its fittings.
8. Do NOT allow un-insulated lines to come into contact with each other.
When replacing the bulb and hose clamp, the clamp should be "snug" but not "tight" - spec is to torque the hose clamp
to 20+/-5in-lb.
9. Wrap the TXV with insulation after the hose clamp has been installed.
H. LEAK CHECK
1. Using a manifold gauge, connect an external supply of dry nitrogen to the gauge port on the liquid line.
2. Pressurize the connecting lines and indoor coil to 150 PSIG maximum.
3. Leak check brazed line connections using soap bubbles. Repair leaks (if any) after relieving pressure.
4. Evacuate and charge the system per the instructions packaged with the outdoor unit.
positive pressure of the furnace; however, it is recommended to prevent efficiency loss of conditioned air.
1. The drain hole in the drain pan must be cleared of all insulation.
2. Insulate the primary drain line to prevent sweating where dew point temperatures may be met. (Optional depending on climate and application needs)
3. Connect the secondary drai trap is needed in this line).
J. CLEANING THE COIL
The two piece door (3-piece on 24.5" wide models) allows removal of the outer casing doors without interference from refrigerant or condensate lines. Once the outer doors are removed the split inner coil panels can be easily removed. The inside and outside of the coil can be easily cleaned with a brush and vacuum with the panels removed. See Figure 7.
The foil covered insulation on 4PXC coils should be wiped down and residual dirt and dust should be vacuumed up to maintain good air quality. See Figure 8.
n line to a separate drain line (no
Figure 7
I. CONDENSATE DRAIN PIPING
Condensate drain connections are located in the drain pan at the bottom of the coil/enclosure assembly. The female threaded fit­ting protrudes outside of the enclosure for external connection. A field fabricated trap is not required for proper drainage due to the
4 18-AD32D1-4E-EN
Figure 8
Page 5
Installer’s Guide
From Dwg.
D345397 RevE
4PXCCU60BS3
4PXCCD60BS3
4PXCCU42BS3
4PXCCD42BS3
4PXCCU48BS3
4PXCCD48BS3
4PXCBU42BS3
4PXCBU48BS3
4PXCBD42BS3
4PXCBD48BS3
4PXCCU36BS3
4PXCCD36BS3
4PXCBU36BS3
4PXCBD36BS3
4PXCBU24BS3
4PXCBD24BS3
4PXCAU32BS3
4PXCCD36BS3HDA, 4PXCBD42BS3HDA, 4PXCCD42BS3HDA, 4PXCBD48BS3HDA, 4PXCCD48BS3HDA, 4PXCCD60BS3HDA
4PXCAU24BS3
4PXCAD24BS3
14-1/2 14-1/2 17-1/2 17-1/2 21 17-1/2 21 21
Outline Drawing for Upflow models: 4PXCAU24BS3HAA, 4PXCAU32BS3HAA, 4PXCBU24BS3HAA, 4PXCBU36BS3HAA, 4PXCCU36BS3HAA, 4PXCBU42BS3HAA, 4PXCCU42BS3HAA,
MODEL
4PXCBU48BS3HAA, 4PXCCU48BS3HAA, 4PXCCU60BS3HAA, and Downflow models: 4PXCAD18BS3HDA, 4PXCBD18BS3HDA, 4PXCAD24BS3HDA, 4PXCBD24BS3HDA, 4PXCBD36BS3HDA,
WEIGHT (LBS.) 39 43 42 54 56 61 64 73
REFRIGERANT CONTROL TXV (NON-BLEED)
HEIGHT "A" (IN.) 17-1/2 22-1/2 17-1/2 22-1/2 22-1/2 26-7/8 26-7/8 30-3/4
OVERALL WIDTH "B" (IN.) 14-1/2 14-1/2 17-1/2 17-1/2 21 17-1/2 21 21
OPENING WIDTH "C" (IN.) 13-5/8 13-5/8 16-5/8 16-5/8 20-1/8 16-5/8 20-1/8 20-1/8
TOP OPENING "D" 12-3/4 12-3/4 15-3/4 15-3/4 19-1/4 15-3/4 19-1/4 19-1/4
GAS CONNECTION 3/4 3/4 3/4 7/8 7/8 7/8 7/8 7/8
LIQUID CONNECTION 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8
MATCHED FURNACE WIDTH
(NO ADAPTER REQUIRED)
18-AD32D1-4E-EN 5
DRAIN PAN PLASTIC
Page 6
Installer’s Guide
From Dwg. D345398 RevC
Downflow models: 4PXCBD30BS3HDA, 4PXCCD30BS3HDA
Outline Drawing for Upflow models: 4PXCBU30BS3HAA, 4PXCCU30BS3HAA, and
4PXCCU30BS3
4PXCCD30BS3
4PXCBU30BS3
4PXCBD30BS3
MODEL
WEIGHT (LBS.) 47 49
REFRIGERANT CONTROL TXV (NON-BLEED)
HEIGHT (IN.) 17-1/2 17-1/2
OVERALL WIDTH (IN.) 17-1/2 21
OPENING WIDTH (IN.) 16-5/8 20-1/8
TOP OPENING 15-3/4 19-1/4
GAS CONNECTION 3/4 3/4
17-1/2 21
LIQUID CONNECTION 3/8 3/8
MATCHED FURNACE WIDTH
(NO ADAPTER REQUIRED)
DRAIN PAN PLASTIC
6 18-AD32D1-4E-EN
Page 7
Installer’s Guide
From Dwg. D345408 RevD
Downflow models: 4PXCDD48BS3HDA, 4PXCDD60BS3HDA
Outline Drawing for Upflow models: 4PXCDU48BS3HAA, 4PXCDU60BS3HAA, and
4PXCDU60BS3
4PXCDD60BS3
4PXCDU48BS3
4PXCDD48BS3
MODEL
WEIGHT (LBS.) 68 77
REFRIGERANT CONTROL TXV (NON-BLEED)
HEIGHT (IN.) 26-7/8 30-3/4
OVERALL WIDTH (IN.) 24-1/2 24-1/2
OPENING WIDTH (IN.) 23-5/8 23-5/8
TOP OPENING 22-3/4 22-3/4
GAS CONNECTION 7/8 7/8
24-1/2 24-1/2
LIQUID CONNECTION 3/8 3/8
MATCHED FURNACE WIDTH
(NO ADAPTER REQUIRED)
DRAIN PAN PLASTIC
18-AD32D1-4E-EN 7
Page 8
Before starting, insure the
blower wheel, indoor and outdoor
coils are clean.
Troubleshooting Indoor TXV / Cooling Mode
Is sub cooling at the
outdoor unit between
8 to 12F?
Verify line set is
sized properly for application
NO
YES
NO
Is superheat
< 5F?
NO
Is superheat
< 25F?
NO
Is the liquid line
temperature at indoor
coil within 8F of outdoor
liquid line temperature?
YES
Is indoor
temperature more
than 85F?
YES
The system is running at max
capacity and this may be
causing the High superheat.
Wait until indoor temperature
is less than 80F and check
superheat again.
YES
NO
Is air flow at least
350 CFM per ton?
Remove sensing bulb from the
suction line. Measure superheat
at indoor coil while holding the
bulb in bare hand for one minute.
Does superheat decrease?
Verify Inlet screen
assembly is clear
YES
NO
of inlet tube
of debris
YES
Correct air
NO
YES
flow
problem
Measure superheat at indoor coil
while placing the bulb in an ice and water bath for one minute.
Does superheat increase?
NO
Verify Inlet screen
of inlet tube
assembly is clear
of debris
TXV is OK
YES
Confirm that charge
Is sub cooling less
than 8F?
NO
Confirm that
charge is
correct.
YES
is correct and look
for dirty or restricted
outdoor coil.
Replace the
TXV
About Trane and American Standard Heating and Air Conditioning
Trane and American Standard create comfortable, energy efficient indoor environments for residential applications. For more information, please visit www.trane.com or www.americanstandardair.com
The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.
18-AD32D1-4E-EN 18 Jun 2020 Supersedes 18-AD32D1-4D-EN (December 2018)
© 2020
Loading...