Product Specifications4
A-weighted Sound Power Level [dB(A)]4
Accessory Description and Usage5
ARI Standard Capacity Rating Conditions5
Model Nomenclature6
Electrical Data7
Dimensions9
Mechanical Specification Options11
22-1750-053
General
Data
Product Specifications
Model No.
Electrical Data V/Ph/Hz
1
2
2TWX4018B12TWX4024B12TWX4030B12TWX4036B1
200/230/1/60200/230/1/60208/230/1/60208/230/1/60
Min Cir Ampacity8111821
Max Fuse Size (Amps)15153035
CompressorCLIMATUFF
®
CLIMATUFF
®
CLIMATUFF® - SCROLLCLIMATUFF® - SCROLL
RL Amps - LR Amps6.2 - 458.3 - 6213.5 - 7316.0 - 88
Outdoor Fan FL Amps0.600.901.301.30
Fan HP1/151/81/61/6
Fan Dia (inches)232327.627.6
CoilSpine Fin™Spine Fin™Spine Fin™Spine Fin™
Refrigerant R-227/12-LB/OZ8/00-LB/OZ7/10-LB/OZ8/15-LB/OZ
Line Size - (in.) O.D. Gas
Line Size - (in.) O.D. Liquid
3
3
5/83/43/47/8
1/45/165/163/8
Dimensions H x W x D (Crated)43.6 x 30.1 x 3347.6 x 30.1 x 3345.4 x 35.1 x 38.749.4 x 35.1 x 38.7
Weight - Shipping249263276295
Weight - Net215228232249
Anti-short Cycle TimerTAYASCT501ATAYASCT501ATAYASCT501ATAYASCT501A
Evaporator Defrost Control A/CAY28X084AY28X084AY28X084AY28X084
Rubber Isolator KitBAYISLT101BAYISLT101BAYISLT101BAYISLT101
Snow Leg - Base & Cap 4" HighBAYLEGS002BAYLEGS002BAYLEGS002BAYLEGS002
Snow Leg - 4" ExtensionBAYLEGS003BAYLEGS003BAYLEGS003BAYLEGS003
Hard Start Kit ScrollBAYKSKT260BAYKSKT260
Extreme Condition Mounting KitBAYECMT023BAYECMT023BAYECMT004BAYECMT004
Refrigerant Lineset
1
Certified in accordance with the Air-Source Unitary Heat Pump Equipment certification program which is based on ARI Standard 210/240.
2
Calculated in accordance with N.E.C. Only use HACR circuit breakers or fuses.
3
Standard line lengths - 60'. Standard lift - 60' Suction and Liquid line.
For Greater lengths and lifts refer to refrigerant piping software Pub# 32-3312-0
SOUND POWERA-WEIGHTED FULL OCTAVE SOUND POWER LEVEL dB - [dB(A)]
MODELLEVEL [dB(A)]631252505001000200040008000
2TWX4018B17147.855.060.264.365.061.856.857.5
2TWX4024B17448.354.158.863.569.766.159.056.6
2TWX4030B17347.259.560.666.567.162.355.551.2
2TWX4036B17447.857.764.066.469.361.755.048.8
2TWX4042B17450.258.864.265.771.063.456.053.1
2TWX4048B17450.258.864.265.771.063.456.053.1
2TWX4060B17450.655.262.069.369.365.664.753.7
Note: Tested in accordance with ARI Standard 270.95. (Not listed with ARI)
422-1750-05
General
Data
Product Specifications
Model No.
Electrical Data V/Ph/Hz
Min Cir Ampacity2 42 83 4
Max Fuse Size (Amps)4 04 55 0
CompressorCLIMATUFF® - SCROLLCLIMATUFF® - SCROLLCLIMATUFF® - SCROLL
RL Amps - LR Amps17.9 - 10421.2 - 13725.0 - 148
Outdoor Fan FL Amps1.301.302.80
Fan HP1 / 61 / 61 / 3
Fan Dia (inches)27.627.627.6
CoilSpine Fin™Spine Fin™Spine Fin™
Refrigerant R-229/10-LB/OZ10/05-LB/OZ11/12-LB/OZ
Line Size - (in.) O.D. Gas
Line Size - (in.) O.D. Liquid
Dimensions H x W x D (Crated)53.4 x 35.1 x 38.753.4 x 35.1 x 38.753.4 x 35.1 x 38.7
Weight - Shipping3 1 03 1 43 3 9
Weight - Net2 6 12 6 62 9 0
Start ComponentsN ON OY E S
Sound EnclosureY E SY E SY E S
Compressor Sump HeatY E SY E SY E S
Optional Accessories:
Anti-short Cycle TimerTAYASCT501ATAYASCT501ATAYASCT501A
Evaporator Defrost Control A/CAY28X084AY28X084AY28X084
Rubber Isolator KitBAYISLT101BAYISLT101BAYISLT101
Snow Leg - Base & Cap 4" HighBAYLEGS002BAYLEGS002BAYLEGS002
Snow Leg - 4" ExtensionBAYLEGS003BAYLEGS003BAYLEGS003
Hard Start Kit ScrollBAYKSKT260BAYKSKT260
Extreme Condition Mounting KitB A YECMT004BAYECMT004BAYECMT004
Refrigerant Lineset
1
5
2
4
3
3
2TWX4042B12TWX4048B12TWX4060B1
208/230/1/60208/230/1/60208/230/1/60
7/ 81-1/81-1/8
3/83/83/8
TAYREFLN3*TAYREFLN4*TAYREFLN4*
Accessory Description and Usage
Anti-Short Cycle Timer — Solid state timing device that
prevents compressor recycling until 5 minutes have elapsed
after satisfying call or power interruptions. Use in area with
questionable power delivery, commercial applications, long
lineset, etc.
Evaporator Defrost Control — SPST Temperature actuated switch that cycles the condenser off as indoor coil
reaches freeze-up conditions. Used for low ambient cooling
to 30°F with TXV.
Rubber Isolators — 5 large rubber donuts to isolate
condensing unit from transmitting energy into mounting
frame or pad. Use on any application where sound transmission needs to be minimized.
Hard Start kit — Start capacitor and relay to assist compressor
motor startup. Use in areas with marginal power supply, on
long linesets, low ambient conditions, etc.
Extreme Condition Mount Kit — Bracket kits to securely
mount condensing unit to a frame or pad without removing any
panels. Use in areas with high winds, or on commercial roof
tops, etc.
22-1750-055
ARI Standard Capacity Rating Conditions
ARI STANDARD 210/240 RATING CONDITIONS —
(A) Cooling 80°F DB, 67°F WB air entering indoor coil,
95°F DB air entering outdoor coil.
(B) High Temperature Heating 47°F DB, 43°F WB air entering
outdoor coil, 70°F DB air entering indoor coil.
(C) Low Temperature Heating 17°F DB, 15°F WB air entering
outdoor coil, 70°F DB air entering indoor coil.
(D) Rated indoor airflow for heating is the same as for cooling.
ARI STANDARD 270 RATING CONDITIONS — (Noise rating
numbers are determined with the unit in cooling operation.)
Standard Noise Rating number is at 95°F outdoor air.
SPLIT SYSTEM
Model
Nomenclature
Outdoor Units
Refrigerant Type
2 = R-22
4 = R-410A
TRANE
Product Type
W = Split Heat Pump
T = Split Cooling
Product Family
Z = Leadership – Two Stage
X = Leadership
R = Replacement/Retail
B = Basic
A = Light Commercial
The 2TWX4 shall be fully charged from
the factory for matched indoor section
and up to 15 feet of piping. This unit must
be designed to operate at outdoor
ambient temperatures as high as 115°F.
Cooling capacities shall be matched with
a wide selection of air handlers and
furnace coils that are ARI certified. The
unit is certified to UL 1995. Exterior must
be designed for outdoor application.
Casing
Unit casing is constructed of heavy
gauge, galvanized steel and painted with
a weather-resistant powder paint.
Corrosion and weatherproof CMBP-G30
DuraTuff™ base.
Refrigerant Controls
Refrigeration system controls include
condenser fan and compressor
contactor. High and low pressure controls
are inherent to the compressor. Another
standard feature is the liquid line dryer.
Compressor
The Climatuff
internal over temperature and pressure
protector, total dipped hermetic motor
and thermostatically controlled sump
heater. Other features include: roto lock
suction and discharge refrigeration
connections, centrifugal oil pump, and
low vibration and noise.
®
compressor features
Condenser Coil
The Spine Fin™ coil shall be continuously wrapped, corrosion resistant all
aluminum with minimum brazed joints.
This
coil is 3/8 inch O.D. seamless aluminum
glued to a continuous aluminum fin. Coils
are lab tested to withstand 2,000 pounds
of pressure per square inch. The outdoor
coil provides low airflow resistance and
efficient heat transfer. The coil is protected on all four sides by louvered
panels.
Low Ambient Cooling
As manufactured, this unit has a cooling
capability to 55°F. The addition of an
evaporator defrost control permits
operation to 40°F. The addition of an
evaporator defrost control with TXV
permits low ambient cooling to 30°F.
Accessories
Thermostats — Heating/Cooling
(manual and automatic changeover).
Sub-base to match thermostat and
locking thermostat cover.
Evaporator Defrost Control — See
Low Ambient Cooling.
Outdoor Thermostat — Supplemental
heat outdoor ambient lockout from
46 to –10°F.
22-1750-0511
Trane
www.trane.com
Literature Order Number
File Number
Supersedes
Stocking Location04/09
Trane has a policy of continuous product and product data improvement and it reserves the right to change
design and specifications without notice.