Trane 2TWR3, XR13 Installer's Manual

Page 1
18-BC59D1-1
Installer’s Guide
Heat Pumps
2TWR3
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information
pack upon completion of work.
These instructions do not cover all variations in systems nor provide for every possible contingency to be met in connection with installation. All phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES. Should further information be
desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to your installing dealer or local distributor.
1
5 FT. ABOVE UNIT — UNRESTRICTED
A. GENERAL
!
WARNING
This information is intended for use by individuals posses­sing adequate backgrounds of electrical and mechanical experience. Any attempt to repair a central air conditioning product may result in personal injury and or property damage. The manufacturer or seller cannot be responsible for the interpretation of this information, nor can it assume any liability in connection with its use.
NOTICE: Trane has always recommended installing Trane approved matched indoor and outdoor systems.
The benefits of installing approved matched systems are maximum efficiency, optimum performance and best overall system reliability.
Check for transportation damage after unit is uncrated. Report promptly, to the carrier, any damage found to the unit.
To determine the electrical power requirements of the unit, refer to the nameplate of the unit. The electrical power available must agree with that listed on the nameplate.
®
The Weathertron manufactured to withstand and operate in severe winter conditions. However, there are precautionary steps which should be taken at the time of installation which will help assure the efficient operation of the unit. It is recom-
mended that these precautions be taken for units being installed in areas where snow accumulation and prolonged below freezing temperatures occur.
1. Units should be elevated 3 to 12 inches above the pad or
rooftop, depending on local weather. This additional height will allow better drainage of snow and ice (melted during defrost cycle) prior to its refreezing. This should
prevent a build-up of ice around the unit which occurs when unit is not elevated. Insure that drain holes in
unit base pan are not obstructed preventing draining of defrost water.
Heat Pump has been designed and
2. If possible, avoid locations that are likely to accumulate snow drifts. If not possible, a snow drift barrier should be installed around the unit to prevent a build-up of snow on the sides of the unit and should be of sufficient distance from the unit to prevent restriction of airflow to and from the unit. Also allow for proper maintenance space. The barrier should be constructed of materials which will blend in with the building design.
3. Avoid locating the unit where condensation and freezing of defrost vapor may annoy the customer. For instance, installing the unit under a bedroom, kitchen, or picture window may be annoying to the customer since conden­sate and fog will occur during the defrost cycle.
4. Avoid locating the unit under the eaves or other over­head structures as sizeable icicles may form and the unit may be damaged by these falling icicles.
B. LOCATION AND PREPARATION
OF THE UNIT
1. When removing unit from the pallet, notice the tabs on the basepan. Remove tabs by cutting with a sharp tool as shown on page 2, Figure 2, and slide unit off of pallet.
2. The unit should be set on a level support pad at least as large as the unit base pan, such as a concrete slab. If this is not the application used please refer to application bulletin “Trane XR-APG**-EN” (* denotes latest revision number).
3. The support pad must NOT be in direct contact with any structure. Unit must be positioned a minimum of 12"
Page 2
Installer’s Guide
2
from any wall or surrounding shrubbery to insure adequate airflow. Clearance must be provided in front of control box (access panels) and any other side requiring service access to meet National Electrical Code. Also, the unit location must be far enough away from any structure to prevent excess roof run-off water from pouring directly on the unit. Do not locate unit(s) close to bedroom(s).
4. The top discharge area must be unrestricted for at least five (5) feet above the unit.
5. When the outdoor unit is mounted on a roof, be sure the roof will support the unit’s weight. Properly selected isolation is recommended to prevent transmission to the building structure.
6. The maximum length of refrigerant lines from outdoor to indoor unit should NOT exceed sixty (60) feet.
7. If outdoor unit is mounted above the air handler, maxi­mum lift should not exceed sixty (60) feet (suction line). If air handler is mounted above condensing unit, maxi­mum lift should not exceed sixty (60) feet (liquid line).
8. Locate and install indoor coil or air handler in accor­dance with instruction included with that unit.
BASEPAN TAB REMOVAL
NOTE: Large diameter tubing will be very difficult to rebend once it has been shaped.
3. Determine the best starting point for routing the refriger­ant tubing — INSIDE OR OUTSIDE THE STRUCTURE.
4. Provide a pull-thru hole of sufficient size to allow both liquid and gas lines.
5. Be sure the tubing is of sufficient length.
6. Uncoil the tubing — do not kink or dent.
7. Route the tubing making all required bends and properly secure the tubing before making connections.
8. To prevent a noise within the building structure due to vibration transmission from the refrigerant lines, the following precautions should be taken:
a. When the refrigerant lines have to be fastened to floor
joists or other framing in a structure, use isolation type hangers.
b. Isolation hangers should also be used when refrigerant
lines are run in stud spaces or enclosed ceilings.
c. Where the refrigerant lines run through a wall or sill,
they should be insulated and isolated.
d. Isolate the lines from all ductwork.
D. SERVICE VALVE OPERATION
BRASS LIQUID AND GAS LINE SERVICE VALVES
The Brass Liquid and Gas Line Service Valves are factory shipped in the seated position to hold factory charge. The pressure tap service port (when depressed) opens only to the field brazing side of the valve when the valve is in the seated position. The liquid line valve is not a back seating valve (see WARNING below).
C. INSTALLING REFRIGERANT LINES
!
CAUTION
If using existing refrigerant lines make certain that all joints are brazed, not soldered.
Condensing units have provisions for braze connections. Pressure taps are provided on the service valves of outdoor
unit for compressor suction and liquid pressures. The indoor end of the recommended refrigerant line sets
may be straight or with a 90 degree bend, depending upon situation requirements. This should be thoroughly checked out before ordering refrigerant line sets.
The gas line must always be insulated.
!
CAUTION
In scroll compressor applications, dome temperatures may be hot. Do not touch top of compressor, may cause minor to severe burning.
The units are factory charged with the system charge required when using fifteen (15) feet of rated connecting line. Unit nameplate charge is the same.
Final refrigerant charge adjustment is necessary. Use the Charging Information in the outdoor unit Service Facts and on page 6.
1. Determine the most practical way to run the lines.
2. Consider types of bends to be made and space limitations.
!
WARNING
Extreme caution should be exercised when opening the Liquid and Gas Line Service Valves. Turn valve stem counterclockwise only until the stem contacts the rolled edge. (See Figures 3 and 5) No torque is required.
BRASS GAS LINE BALL SERVICE VALVE
The Brass Gas Line Service Valve is shipped in the closed position to hold the factory refrigerant charge. The pressure tap service port (when depressed) opens only to the field brazing side when the valve is in the closed position.
The Gas Line Service Valve is full open with a 1/4 turn. See Figure 4.
3
LIQUID LINE SERVICE VALVE
© 2005 American Standard Inc. All Rights Reserved 18-BC59D1-1
Page 3
Installer’s Guide
4
GAS LINE BALL SERVICE VALVE
UNIT SIDE OF VALVE
COOLING
CAP
PRESSURE TAP PORT
GAS LINE CONNECTION
CAP
CORE
1/4 TURN ONLY COUNTERCLOCKWISE FOR FULL OPEN POSITION
VALVE STEM
BODY
HEATING
BRAZING REFRIGERANT LINES
1. Remove lower access cover to access service valves.
2. Before brazing, remove plugs from external copper stub tubes. Clean internal and external surfaces of stub tubes prior to brazing.
3. Cut and fit tubing, minimizing the use of sharp 90° bends.
4. Insulate the entire gas line and its fittings.
5. Do NOT allow uninsulated liquid line to come in direct contact with bare gas line.
6. Precautions should be taken to avoid heat damage
to the pressure tap valve core during brazing. It is recommended that the pressure tap port valve core be removed and a wet rag wrapped around the valve body.
NOTE: Use care to make sure that no moisture enters pressure tap port, while wet rag is being used.
NOTE: Precautions should be taken to avoid heat damage to basepan during brazing. It is recommended to keep the flame directly off of the basepan.
7. Use a Dry Nitrogen Purge and Brazing Alloy without flux when brazing the field line to the copper factory connection. Flow dry nitrogen into either valve pressure tap port, thru the tubing and out the other port while brazing.
8. Braze using accepted good brazing techniques.
LEAK CHECK
IMPORTANT:
Replace pressure tap port valve core before attaching hoses for evacuation.
5
GAS LINE SERVICE VALVE
other leak-checking methods to see that all field joints are leak-free! If not, release pressure; then repair!
SYSTEM EVACUATION
NOTE: Since the outdoor unit has a refrigerant charge, the gas and liquid line valves must remain closed.
1. Upon completion of leak check, evacuate the refrigerant lines and indoor coil before opening the gas and liquid line valves.
2. Attach appropriate hoses from manifold gauge to gas and liquid line pressure taps.
NOTE: Unnecessary switching of hoses can be avoided and com­plete evacuation of all lines leading to sealed system can be accomplished with manifold center hose and connecting branch hose to a cylinder of HCFC-22 and vacuum pump.
3. Attach center hose of manifold gauges to vacuum pump.
4. Evacuate until the micron gauge reads no higher than 350 microns.
5. Close off valve to vacuum pump and observe the micron gauge. If gauge pressure rises above 500 microns in one (1) minute, then evacuation is incomplete or system has a leak.
6. If vacuum gauge does not rise above 500 microns in one (1) minute, the evacuation should be complete.
7. With vacuum pump and micron gauge blanked off, open valve on HCFC-22 cylinder and charge refriger­ant lines and indoor coil with vapor to tank pressure of HCFC-22 supply.
NOTE: DO NOT VENT REFRIGERANT INTO THE ATMOSPHERE.
8. Close valve on HCFC-22 supply cylinder. Close valves on manifold gauge set and remove refrigerant charging hoses from liquid and gas pressure tap ports.
NOTE: A 3/16" Allen wrench is required to open liquid line service valve. A 1/4" Open End or Adjustable wrench is required to open gas line valve. A 3/4" Open End wrench is required to take off the valve stem cap.
After the brazing operation of refrigerant lines to both the outdoor and indoor unit is completed, the field brazed connections must be checked for leaks. Pressurize through the service valve ports, the indoor unit and field refrigerant lines with dry nitrogen to 350-400 psi. Use soap bubbles or
18-BC59D1-1 3
9. The liquid line shut-off valve can now be opened. Remove shut-off valve cap. Fully insert hex wrench into the stem and backout counterclockwise until valve stem just touches rolled edge (approximately five [5] turns) observing WARNING statement on page 3. See Figure 3.
Page 4
Installer’s Guide
FRC_DFT
TEST_COMMON
TST
10. Replace liquid service pressure tap port cap and valve
stem cap. These caps MUST BE REPLACED to prevent leaks. Replace valve stem and pressure tap cap finger tight, then tighten an additional 1/6 turn.
11. The gas valve can now be opened. For a ball type gas valve, open the gas valve by removing the shut-off valve cap and turning the valve stem 1/4 turn counterclock­wise, using 1/4" Open End or Adjustable wrench. See Figure 4. For brass gas line service valve opening, follow 9 and 10 above. See Figure 5.
12. The gas valve is now open for refrigerant flow. Replace valve stem cap to prevent leaks. Again, these caps MUST BE REPLACED to prevent leaks. Replace valve stem and pressure tap cap finger tight, then tighten an additional 1/6 turn. See Figure 3.
If refrigerant lines are longer than 15 feet and/or a different size than recommended, it will be necessary to adjust system refrigerant charge upon completion of installation. See unit Service Facts.
E. ELECTRICAL CONNECTIONS
!
WARNING
When installing or servicing this equipment, ALWAYS exercise basic safety precautions to avoid the possibility of electric shock.
1. Power wiring and grounding of equipment must comply with local codes.
2. Power supply must agree with equipment nameplate.
3. Install a separate disconnect switch at the outdoor unit.
4. Ground the outdoor unit per local code requirements.
5. Provide flexible electrical conduit whenever vibration transmission may create a noise problem within the structure.
6. The use of color coded low voltage wire is recommended to simplify connections between the outdoor unit, the thermostat and the indoor unit.
Table 1 — NEC Class II Control Wiring
the heat pump system. By measuring the change in delta-T, we can determine the need for defrost. The coil sensor also serves to sense outdoor coil temperature for termination of the defrost cycle.
FAULT IDENTIFICATION
A fault condition is indicated by the flashing light on the defrost control inside the heat pump control box.
In normal operation, the defrost control light will flash once each second. If the light is flashing more than once per second or not at all, refer to the service manual for that unit.
PIN IDENTIFICATION (See Figure 6.)
1. TEST_COMMON (Shorting any of the other pins to this pin causes the function of the other pin to be executed. Leaving this pin open results in the normal mode of operation.)
2. TST = Test (Shorting TEST_COMMON to this pin speeds up all defrost board timings.)
3. FRC_DFT = Forced Defrost (Short TEST_COMMON to this pin for two (2) seconds to initiate a forced defrost. Remove the short after defrost initiates.)
DEFROST CONTROL CHECKOUT
Normal operation requires:
a. LED on board flashing 1 time/second. b. 24V AC between R & B
c. 24V AC between Y & B with unit operating
d. Defrost initiation when FRC_DFT pin is shorted to
TEST_COMMON pin.
If a defrost control problem is suspected, refer to the service information in control box.
!
WARNING
Do NOT connect 24V AC to T1 (ODS-A) terminal. ODS-A thermistor WILL BE BLOWN.
6
PIN IDENTIFICATION
24 VOLTS
WIRE SIZE MAX. WIRE LENGTH
18 AWG 150 FT 16 AWG 225 FT. 14 AWG 300 FT.
7. Table 1 defines maximum total length of low voltage
wiring from outdoor unit, to indoor unit, and to thermostat.
8. Mount the indoor thermostat in accordance with instruc­tion included with the thermostat. Wire per appropriate hook-up diagram (included in these instructions).
F. DEFROST CONTROL
The demand defrost control measures heat pump outdoor ambient temperature with a sensor located outside the outdoor coil. A second sensor located on the outdoor coil is used to measure the coil temperature. The difference between the ambient and the colder coil temperature is the difference or delta-T measurement. This delta-T measurement is representative of the operating state and relative capacity of
4 18-BC59D1-1
G. COMPRESSOR START UP
After all electrical wiring is complete, SET THE THERMO­STAT SYSTEM SWITCH IN THE OFF POSITION SO COMPRESSOR WILL NOT RUN, and apply power by closing the system main disconnect switch. This will activate the compressor sump heat (where used). Do not change the Thermostat System Switch until power has been applied for one (1) hour. Following this procedure will prevent potential compressor overload trip at the initial start-up.
H. OPERATIONAL AND
CHECKOUT PROCEDURES
Final phases of this installation are the unit Operational and Checkout Procedures which are found in this instruction on
Page 5
Installer’s Guide
page 8. To obtain proper performance, all units must be operated and charge adjustments made in accordance with procedures found in the Service Facts.
I. ELECTRIC HEATERS
Electric heaters, if used, are to be installed in the air han­dling device according to the instructions accompanying the air handler and the heaters.
J. START CONTROL
Some models have quick start components which are factory installed. For models that do not have factory installed start components, provisions are made for a field installed start kit accessory. When adding an accessory, follow the instructions provided with the kit.
K. OUTDOOR THERMOSTAT
An outdoor thermostat TAYSTAT250B may be field installed. For data, see wiring diagram attached to unit and instruction sheet packaged with outdoor thermostat.
L. SEACOAST SALT SHIELD
Units installed within one mile of salt water including seacoasts and inland waterways, require the addition of BAYSEAC001 (Seacoast Kit) at the time of installation.
IMPORTANT:
See Limited Warranty information in Use and Care Manual.
M. TROUBLESHOOTING
TROUBLESHOOTING CHART — WHAT TO CHECK
WHAT TO CHECK MODE
HIGH VOLTAGE WIRING
COMPRESSOR IOL
SYSTEM FAULTS
REFRIGERANT CIRCUIT
Head Pressure Too High
Head Pressure Too Low
Suction Pressure Too High
Suction Pressure Too Low
Liquid Refrig. Floodback (TXV)
I.D. Coil Frosting
Compressor Runs Inadequate or No Cooling/Htg
ELECTRICAL
Compressor & O.D. Fan Won’t Start
Compressor Will Not Start But O.D. Fan Runs
O.D. Fan Won’t Start
Compressor Hums But Won’t Start
Compressor Cycles on IOL
I.D. Blower Won’t Start
DEFROST
Unit Won’t Initiate Defrost
Defrost Terminates on Time
Unit Icing Up
C - Cooling H - Heating P - Primary Causes S - Secondary Causes * - 3 Phase Only
POWER SUPPLY
C H C H C H C H C H C H C H
C H C H C H C H C H C H
C H C H C H
P P
P P
RUN CAPACITOR
P P P P P P
P P P P
CONTACTOR CONTACTS
START CAPACITOR
START RELAY
S
P
S
P P P P P
S
P
S
P
LOW VOLTAGE WIRING
S S
S S S S
CONTROL TRANSFORMER
STUCK COMPRESSOR
LOW VOLTAGE FUSE
INEFFICIENT COMP.
CONTACTOR COIL
THERMOSTAT
S
P
S
PPP
S
P
S
S
S
S
S S S
S
S
S
S
S
S
S
S
S
P
S
S
P
S
EXCESSIVE EVAP. LOAD
NONCONDENSABLES
REF. UNDERCHARGE
RES. O.D. AIRFLOW
REF. OVERCHARGE
P P
P
S
P
S
P
S S
P P
P
P
S
P
S
P
P P
P P
P
P
S
P
P
P
S
P S S
P
P
O.D. AIR RECIRCULATION
TXV STUCK OPEN
P
S
P
S
P
S
P
S
S
S
S
S
S S
S
S
S
S
S
S
S
REF. CIR. RESTRICTIONS
CHECK VALVE LEAKING
*
DEFROST RELAY DEF.
SOV COIL DEFECTIVE
RES. I.D. AIRFLOW
SOV LEAKING
SUPERHEAT
S S
P
S
S
S
S
S
S
S
S
P
S
P
S
S
P
S
S
S P P
S
S
P
S
S
S
P
S
S
S
S
P
S
S
DEFROST CONTROL DEF.
S
P P P
S
P P
S
S S
P
P
PP
P
P
TYPICAL FIELD HOOK-UP DIAGRAMS
Notes:
1. Be sure power supply agrees with equipment nameplate.
2. Power wiring and grounding of equipment must comply with local codes.
3. Low voltage wiring to be No. 18 AWG minimum conductor.
4. ODT-B must be set lower than ODT-A.
5. If outdoor thermostats (ODT) are not used, connect W1 to W2 and W3.
6. N/A to programmable thermostat.
18-BC59D1-1 5
LEGEND
FACTORY WIRING FIELD WIRING
Page 6
Installer’s Guide
SUBCOOLING CHARGING IN COOLING ABOVE 55°F OD AMBIENT
The Trane company has always recommended installing Trane approved
All 13 SEER Trane split systems are ARI rated with only TXV indoor systems.
The benefits of installing approved indoor and outdoor split systems are maximum efficiency, optimum performance and the best overall system reliability.
The following charging methods are therefore prescribed for systems with indoor TXVs.
1. Subcooling (in the cooling mode) is the method of charging above 55°F ambient temperatures.
2. For best results - the indoor temperature should be kept between 70°F to 80°F. Add system heat if needed.
3. At start-up, or whenever charge is removed or added, the system must be operated for a minimum 20 minutes to stabilize before accurate measurements can be made.
4. Measure Liquid Line Temperature and Refrigerant Pressure at service valves.
5. Determine total refrigerant line length, and height (lift) if indoor section is above the condenser.
6. Determine the Design Subcool Charging Temperature from the unit nameplate.
7. Locate this value in the appropriate column of the Subcooling Charging Table. Locate your liquid line temperature in the left column of the table, and the intersecting liquid line pressure under your nameplate subcool value column. Add refrigerant to raise the pres­sure to match the table, or remove refrigerant to lower the pressure. Again, wait 20 minutes for the system conditions to stabilize before adjusting charge again.
8. When system is correctly charged, you can refer to System Pressure Curves (in Service Facts) to verify typical performance.
matched indoor and outdoor systems.
only recommended
R-22 SUBCOOLING CHARGING TABLE
LIQUID
TEMP.
(°F)
45 89 93 96 100 50 98 102 105 109 55 107 111 115 119 60 117 121 126 130 65 128 132 137 141 70 139 144 148 153 75 151 156 161 166 80 163 168 174 179 85 176 182 187 193 90 190 196 202 208
95 205 211 217 223 100 220 226 233 239 105 236 243 249 256 110 253 260 267 274 115 271 278 285 293 120 289 297 305 313 125 309 317 325 333
DESIGN SUBCOOLING VALUES (°F)
8101214
LIQUID LINE PRESSURE (psi)
SUBCOOL CHARGING TABLE CORRECTIONS FOR LINE LENGTH AND RISE
60 50 40 30 25
Add 5 psig to Subcool Charging Table Pressure
20 15 10
REFRIGERANT
LINE LIFT (FEET)
Subtract 5 psig from S.C. Table Pressure
0
Use Design Subcool Value from Table
10 20 25 30 40 60 80
TOTAL REFRIGERANT LINE LENGTH (FEET)
SUBCOOLING CHARGING BELOW 55°F OD AMBIENT – IN HEATING ONLY
1. The Subcool Charging Method in cooling is not recom­mended below 55°F outdoor ambient.
2. The only recommended method of charging at outdoor ambients below 55°F, is to weigh in the charge heating mode.
3. Use Nameplate charge plus standard charge adders for line length.
6 18-BC59D1-1
in the
4. Check liquid line temperature and pressure (at the OD valves) to obtain a minimum of 10°F subcooling.
5. Add charge if a minimum of 10°F subcooling is not obtained with the nameplate charge plus line length correction.
6. It is important to return in the spring or summer to accurately charge the system in the cooling mode at outdoor ambients above 55°F.
Page 7
Installer’s Guide
2TWR3 OUTLINE DRAWING
NOTE: ALL DIMENSIONS ARE IN MM (INCHES).
MODELS BASE FIG. A B C D E F G H J K
2TWR3018A 2 2 832 (32-3/4) 724 (28-1/2) 651 (25-5/8) 5/8 1/4 137 (5-3/8) 65 (2-5/8) 210 (8-1/4) 57 (2-1/4) 457 (18) 2TWR3024A 2 1 832 (32-3/4) 724 (28-1/2) 651 (25-5/8) 5/8 5/16 143 (5-5/8) 65 (2-5/8) 210 (8-1/4) 57 (2-1/4) 457 (18) 2TWR3030A 3 2 933 (36-3/4) 829 (32-5/8) 756 (29-3/4) 3/4 5/16 143 (5-5/8) 92 (3-5/8) 210 (8-1/4) 79 (3-1/8) 508 (20) 2TWR3036A 4 1 943 (37-1/8) 946 (37-1/4) 870 (34-1/4) 7/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 508 (20) 2TWR3042A 4 1 1045 (41-1/8) 946 (37-1/4) 870 (34-1/4) 7/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 508 (20) 2TWR3048A 4 1 1045 (41-1/8) 946 (37-1/4) 870 (34-1/4) 1-1/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 508 (20) 2TWR3060A 4 1 1045 (41-1/8) 946 (37-1/4) 870 (34-1/4) 1-1/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 508 (20)
18-BC59D1-1 7
From Dwg. 21D152898 Rev. 10
Page 8
Installer’s Guide
MOUNTING HOLE LOCATION Note: All dimensions are in MM (Inches).
NOTE: For model base size, see table on page 7.
From Dwg. 21D152637 Rev. 1
CHECKOUT PROCEDURE
After installation has been completed, it is recommended that the entire system be checked against the following list:
1. Refrigerant Line, Leak checked .................................. [ ]
2. Suction Lines and Fittings properly insulated ........... [ ]
3. Have all Refrigerant Lines been secured and
isolated properly? ........................................................ [ ]
4. Have passages through masonry been sealed? If mortar is used, prevent mortar from coming
into direct contact with copper tubing ........................ [ ]
5. Verify tightness of all electrical connects ................... [ ]
6. Observe outdoor fan during on cycle for clearance
and smooth operation .................................................. [ ]
7. Indoor coil drain line drains freely. Pour water
into drain pan .............................................................. [ ]
8. Supply registers and return grilles open and
unobstructed................................................................ [ ]
9. Return air filter installed ............................................ [ ]
10. Thermostat thermometer is accurate. Check against a reliable thermometer. Adjust per
instructions with thermostat ...................................... [ ]
11. Is correct speed tap being used?
(Indoor blower motor) .................................................. [ ]
12. Operate complete system in each mode to
insure safe operation. .................................................. [ ]
Trane A business of American Standard Companies www.trane.com
Trane has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.
P.I. 10/05
Loading...