Trane 2TTB3030A, 2TTB3036A, 2TTB3042A, 2TTB3048A, 2TTB3060A Installer's Manual

...
18-BC56D1-5
Installer’s Guide
Replacement Condensing Units
2TTB3/2TWB3
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information
pack upon completion of work.
NOTICE: This outdoor unit is designed as a component replacement option for existing HCFC 22 systems. This system is shipped with a DRY NITROGEN charge and does not contain HCFC 22.
These instructions do not cover all variations in systems nor provide for every possible contingency to be met in connection with installation. All phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES. Should further
information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to your installing dealer or local distributor.
A. GENERAL
!
WARNING
This information is intended for use by individuals posses­sing adequate backgrounds of electrical and mechanical experience. Any attempt to repair a central air conditioning product may result in personal injury and or property damage. The manufacturer or seller cannot be responsible for the interpretation of this information, nor can it assume any liability in connection with its use.
NOTICE: The manufacturer has always recommended installing approved matched indoor and outdoor systems.
The benefits of installing approved matched systems are maximum efficiency, optimum performance and best overall system reliability.
Check for transportation damage after unit is uncrated. Report promptly, to the carrier, any damage found to the unit.
To determine the electrical power requirements of the unit, refer to the nameplate of the unit. The electrical power available must agree with that listed on the nameplate.
1
5 FT. ABOVE UNIT — UNRESTRICTED
B. LOCATION AND PREPARATION OF THE UNIT
(INFORMATION APPLICABLE TO HEAT PUMPS ONLY)
This Heat Pump has been designed and manufactured to withstand and operate in severe winter conditions. However, there are precautionary steps which should be taken at the time of installation which will help assure the efficient operation of the unit. It is recommended
that these precautions be taken for units being installed in areas where snow accumulation and prolonged below freezing temperatures occur.
1. Units should be elevated 3 to 12 inches above the pad or rooftop, depending on local weather. This additional height will allow better drainage of snow and ice (melted during defrost cycle) prior to its refreezing. This should prevent a
build-up of ice around the unit which occurs when unit is not elevated. Insure that drain holes in unit base pan
are not obstructed preventing draining of defrost water.
2. If possible, avoid locations that are likely to accumulate snow drifts. If not possible, a snow drift barrier should be installed around the unit to prevent a build-up of snow on the sides of the unit and should be of sufficient distance from the unit to prevent restriction of airflow to and from the unit. Also allow for proper maintenance space. The barrier should be constructed of materials which will blend in with the building design.
3. Avoid locating the unit where condensation and freezing of defrost vapor may annoy the customer. For instance, installing the unit under a bedroom, kitchen, or picture window may be annoying to the customer since conden­sate and fog will occur during the defrost cycle.
4. Avoid locating the unit under the eaves or other overhead structures as sizeable icicles may form and the unit may be damaged by these falling icicles.
Installer’s Guide
2
(INFORMATION APPLICABLE TO ALL UNITS)
1. When removing unit from the pallet, notice the tabs on
2. The unit should be set on a level support pad at least as
3. The support pad must NOT be in direct contact with any
4. The top discharge area must be unrestricted for at least
5. When the outdoor unit is mounted on a roof, be sure the
6. The maximum length of refrigerant lines from outdoor to
7. If outdoor unit is mounted above the air handler, maxi-
NOTE: Refer to “Refrigerant Piping Software” Pub. No. 32-3312-0* (the position of the * denotes the latest revision number). The outdoor unit must be properly matched to the indoor unit. Refer to Application Bulletin # SCC-APG009-EN.
If using existing refrigerant lines make certain that all joints are brazed, not soldered.
In scroll compressor applications, dome temperatures may be hot. Do not touch top of compressor, may cause minor to severe burning.
BASEPAN TAB REMOVAL
the basepan. Remove tabs by cutting with a sharp tool as shown in Figure 2.
large as the unit base pan, such as a concrete slab. If this is not the application used please refer to application bulletin SSC-APG001-EN.
structure. Unit must be positioned a minimum of 12" from any wall or surrounding shrubbery to insure adequate airflow. Clearance must be provided in front of control box (access panels) & any other side requiring service access to meet National Electrical Code. Also, the unit location must be far enough away from any structure to prevent excess roof run-off water from pouring directly on the unit. Do not locate unit(s) close to bedroom(s).
five (5) feet above the unit.
roof will support the unit’s weight. Properly selected isolation is recommended to prevent sound or vibration transmission to the building structure.
indoor unit should NOT exceed sixty (60) feet.
mum lift should not exceed sixty (60) feet (suction line). If air handler is mounted above condensing unit, maxi­mum lift should not exceed sixty (60) feet (liquid line).
!
CAUTION
!
CAUTION
NOTE: The refrigerant charge specified on the data plate is the system charge plus 15 feet of rated line set.
C. SERVICE VALVE OPERATION
BRASS LIQUID AND GAS LINE SERVICE VALVES
The Brass Liquid and Gas Line Service Valves are factory shipped in the seated position to hold factory nitrogen charge. The pressure tap service port (when depressed) opens only to the field brazing side of the valve when the valve is in the seated position. The liquid line valve is not a back seating valve (see WARNING below).
!
WARNING
Extreme caution should be exercised when opening the Liquid Line Service Valve. Turn valve stem counterclock­wise only until the stem contacts the rolled edge. (See Figure 3) No torque is required.
BRASS GAS LINE BALL SERVICE VALVE
The Brass Gas Line Ball Service Valve is shipped in the closed position to hold the factory nitrogen charge. The pressure tap service port (when depressed) opens only to the field brazing side when the valve is in the closed position. The Gas Line Ball Service Valve is full open with a 1/4 turn. See Figure 4.
BRAZING REFRIGERANT LINES
1. Before brazing, remove plugs from external copper stub tubes. Clean internal and external surfaces of stub tubes prior to brazing.
2. Cut and fit tubing, minimizing the use of sharp 90° bends.
3. Insulate the entire gas line and its fittings.
4. Do NOT allow uninsulated liquid line to come in direct contact with bare gas line.
5. Precautions should be taken to avoid heat damage to the pressure tap valve core during brazing. It is recommended that the pressure tap port valve core be removed and a wet rag wrapped around the valve body.
NOTE: Use care to make sure that no moisture enters pressure tap port, while wet rag is being used.
NOTE: Precautions should be taken to avoid heat damage to basepan during brazing. It is recommended to keep the flame directly off of the basepan.
6. Use a Dry Nitrogen Purge and Brazing Alloy without flux when brazing the field line to the copper factory connec­tion. Flow dry nitrogen into either valve pressure tap port, thru the tubing and out the other port while brazing.
7. Braze using accepted good brazing techniques.
LEAK CHECK
IMPORTANT:
Replace pressure tap port valve core before attaching hoses for evacuation.
Final refrigerant charge adjustment is necessary. Use the Subcooling Charging procedure in the outdoor unit Service Facts.
© 2012 Trane 18-BC56D1-5
After the brazing operation of refrigerant lines to both the outdoor and indoor unit is completed, the field brazed connections must be checked for leaks. Pressurize through the service valve ports, the indoor unit and field refrigerant
Installer’s Guide
3
LIQUID LINE SERVICE VALVE
lines with dry nitrogen to 150 psi. Use soap bubbles or other leak-checking methods to see that all field joints are leak­free! If not, release pressure; then repair!
SYSTEM EVACUATION
1. Upon completion of leak check, evacuate the refrigerant lines and indoor coil before opening the gas and liquid line valves.
2. Attach appropriate hoses from manifold gauge to gas and liquid line pressure taps.
NOTE: Unnecessary switching of hoses can be avoided and complete evacuation of all lines leading to sealed system can be accomplished with manifold center hose and connecting branch hose to a cylinder of HCFC-22 and vacuum pump.
3. The outdoor unit ships with a holding charge of dry nitrogen. The nitrogen should be removed and the entire system must be evacuated. Remove the refrigerant connection seal caps and open the service gas and liquid valves slowly to release the nitrogen from the unit.
NOTE: A 3/16" Allen wrench is required to open liquid line service valve. A 1/4" Open End or Adjustable wrench is required to open gas line valve. A 3/4" Open End wrench is required to take off the valve stem cap.
4. Attach center hose of manifold gauges to the vacuum pump once the nitrogen pressure has been relieved.
5. Evacuate until the micron gauge reads no higher than 350 microns.
6. Close off valve to vacuum pump and observe the micron gauge. If gauge pressure rises above 500 microns in one (1) minute, then evacuation is incomplete or system has a leak.
7. If vacuum gauge does not rise above 500 microns in one (1) minute, the evacuation should be complete.
8. With vacuum pump and micron gauge blanked off, weigh in HCFC 22 refrigerant based on the outdoor unit data plate and refrigerant line set length adjust­ments noted on page 1 of the Service Facts.
9. Close valve on HCFC-22 supply cylinder when the appropriate refrigerant charge has been achieved.
10. Replace gas and liquid service caps. These caps MUST BE REPLACED to prevent leaks. Replace caps by finger tightening, then tighten an additional 1/6 turn.
GAS LINE SERVICE VALVE
If refrigerant lines are longer than 15 feet and/or a different size than recommended, it will be necessary to adjust system refrigerant charge upon completion of installation. See page 6 or in the unit Service Facts.
D. ELECTRICAL CONNECTIONS
!
WARNING
When installing or servicing this equipment, ALWAYS exercise basic safety precautions to avoid the possibility of electric shock.
1. Power wiring and grounding of equipment must comply with local codes.
2. Power supply must agree with equipment nameplate.
3. Install a separate disconnect switch at the outdoor unit.
4. Ground the outdoor unit per local code requirements.
5. Provide flexible electrical conduit whenever vibration transmission may create a noise problem within the structure.
4
GAS LINE BALL SERVICE VALVE
UNIT SIDE OF VALVE
COOLING
CAP
PRESSURE TAP PORT
GAS LINE CONNECTION
CAP
CORE
1/4 TURN ONLY COUNTERCLOCKWISE FOR FULL OPEN POSITION
VALVE STEM
BODY
18-BC56D1-5 3
Loading...
+ 5 hidden pages