Trane 2TTB3030A, 2TTB3018A,2TTB3024A,2TTB3030A,2TTB3036A,2TTB3042A,2TTB3048A,2TTB3060A,2TWB3018A,2TWB3024A,2TWB3030A,2TWB3036A,2TWB3042A,2TWB3048A,2TWB3060A, 2TTB3036A, 2TTB3042A, 2TTB3048A Installer's Manual

...
Page 1
18-BC56D1-5
Installer’s Guide
Replacement Condensing Units
2TTB3/2TWB3
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information
pack upon completion of work.
NOTICE: This outdoor unit is designed as a component replacement option for existing HCFC 22 systems. This system is shipped with a DRY NITROGEN charge and does not contain HCFC 22.
These instructions do not cover all variations in systems nor provide for every possible contingency to be met in connection with installation. All phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES. Should further
information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to your installing dealer or local distributor.
A. GENERAL
!
WARNING
This information is intended for use by individuals posses­sing adequate backgrounds of electrical and mechanical experience. Any attempt to repair a central air conditioning product may result in personal injury and or property damage. The manufacturer or seller cannot be responsible for the interpretation of this information, nor can it assume any liability in connection with its use.
NOTICE: The manufacturer has always recommended installing approved matched indoor and outdoor systems.
The benefits of installing approved matched systems are maximum efficiency, optimum performance and best overall system reliability.
Check for transportation damage after unit is uncrated. Report promptly, to the carrier, any damage found to the unit.
To determine the electrical power requirements of the unit, refer to the nameplate of the unit. The electrical power available must agree with that listed on the nameplate.
1
5 FT. ABOVE UNIT — UNRESTRICTED
B. LOCATION AND PREPARATION OF THE UNIT
(INFORMATION APPLICABLE TO HEAT PUMPS ONLY)
This Heat Pump has been designed and manufactured to withstand and operate in severe winter conditions. However, there are precautionary steps which should be taken at the time of installation which will help assure the efficient operation of the unit. It is recommended
that these precautions be taken for units being installed in areas where snow accumulation and prolonged below freezing temperatures occur.
1. Units should be elevated 3 to 12 inches above the pad or rooftop, depending on local weather. This additional height will allow better drainage of snow and ice (melted during defrost cycle) prior to its refreezing. This should prevent a
build-up of ice around the unit which occurs when unit is not elevated. Insure that drain holes in unit base pan
are not obstructed preventing draining of defrost water.
2. If possible, avoid locations that are likely to accumulate snow drifts. If not possible, a snow drift barrier should be installed around the unit to prevent a build-up of snow on the sides of the unit and should be of sufficient distance from the unit to prevent restriction of airflow to and from the unit. Also allow for proper maintenance space. The barrier should be constructed of materials which will blend in with the building design.
3. Avoid locating the unit where condensation and freezing of defrost vapor may annoy the customer. For instance, installing the unit under a bedroom, kitchen, or picture window may be annoying to the customer since conden­sate and fog will occur during the defrost cycle.
4. Avoid locating the unit under the eaves or other overhead structures as sizeable icicles may form and the unit may be damaged by these falling icicles.
Page 2
Installer’s Guide
2
(INFORMATION APPLICABLE TO ALL UNITS)
1. When removing unit from the pallet, notice the tabs on
2. The unit should be set on a level support pad at least as
3. The support pad must NOT be in direct contact with any
4. The top discharge area must be unrestricted for at least
5. When the outdoor unit is mounted on a roof, be sure the
6. The maximum length of refrigerant lines from outdoor to
7. If outdoor unit is mounted above the air handler, maxi-
NOTE: Refer to “Refrigerant Piping Software” Pub. No. 32-3312-0* (the position of the * denotes the latest revision number). The outdoor unit must be properly matched to the indoor unit. Refer to Application Bulletin # SCC-APG009-EN.
If using existing refrigerant lines make certain that all joints are brazed, not soldered.
In scroll compressor applications, dome temperatures may be hot. Do not touch top of compressor, may cause minor to severe burning.
BASEPAN TAB REMOVAL
the basepan. Remove tabs by cutting with a sharp tool as shown in Figure 2.
large as the unit base pan, such as a concrete slab. If this is not the application used please refer to application bulletin SSC-APG001-EN.
structure. Unit must be positioned a minimum of 12" from any wall or surrounding shrubbery to insure adequate airflow. Clearance must be provided in front of control box (access panels) & any other side requiring service access to meet National Electrical Code. Also, the unit location must be far enough away from any structure to prevent excess roof run-off water from pouring directly on the unit. Do not locate unit(s) close to bedroom(s).
five (5) feet above the unit.
roof will support the unit’s weight. Properly selected isolation is recommended to prevent sound or vibration transmission to the building structure.
indoor unit should NOT exceed sixty (60) feet.
mum lift should not exceed sixty (60) feet (suction line). If air handler is mounted above condensing unit, maxi­mum lift should not exceed sixty (60) feet (liquid line).
!
CAUTION
!
CAUTION
NOTE: The refrigerant charge specified on the data plate is the system charge plus 15 feet of rated line set.
C. SERVICE VALVE OPERATION
BRASS LIQUID AND GAS LINE SERVICE VALVES
The Brass Liquid and Gas Line Service Valves are factory shipped in the seated position to hold factory nitrogen charge. The pressure tap service port (when depressed) opens only to the field brazing side of the valve when the valve is in the seated position. The liquid line valve is not a back seating valve (see WARNING below).
!
WARNING
Extreme caution should be exercised when opening the Liquid Line Service Valve. Turn valve stem counterclock­wise only until the stem contacts the rolled edge. (See Figure 3) No torque is required.
BRASS GAS LINE BALL SERVICE VALVE
The Brass Gas Line Ball Service Valve is shipped in the closed position to hold the factory nitrogen charge. The pressure tap service port (when depressed) opens only to the field brazing side when the valve is in the closed position. The Gas Line Ball Service Valve is full open with a 1/4 turn. See Figure 4.
BRAZING REFRIGERANT LINES
1. Before brazing, remove plugs from external copper stub tubes. Clean internal and external surfaces of stub tubes prior to brazing.
2. Cut and fit tubing, minimizing the use of sharp 90° bends.
3. Insulate the entire gas line and its fittings.
4. Do NOT allow uninsulated liquid line to come in direct contact with bare gas line.
5. Precautions should be taken to avoid heat damage to the pressure tap valve core during brazing. It is recommended that the pressure tap port valve core be removed and a wet rag wrapped around the valve body.
NOTE: Use care to make sure that no moisture enters pressure tap port, while wet rag is being used.
NOTE: Precautions should be taken to avoid heat damage to basepan during brazing. It is recommended to keep the flame directly off of the basepan.
6. Use a Dry Nitrogen Purge and Brazing Alloy without flux when brazing the field line to the copper factory connec­tion. Flow dry nitrogen into either valve pressure tap port, thru the tubing and out the other port while brazing.
7. Braze using accepted good brazing techniques.
LEAK CHECK
IMPORTANT:
Replace pressure tap port valve core before attaching hoses for evacuation.
Final refrigerant charge adjustment is necessary. Use the Subcooling Charging procedure in the outdoor unit Service Facts.
© 2012 Trane 18-BC56D1-5
After the brazing operation of refrigerant lines to both the outdoor and indoor unit is completed, the field brazed connections must be checked for leaks. Pressurize through the service valve ports, the indoor unit and field refrigerant
Page 3
Installer’s Guide
3
LIQUID LINE SERVICE VALVE
lines with dry nitrogen to 150 psi. Use soap bubbles or other leak-checking methods to see that all field joints are leak­free! If not, release pressure; then repair!
SYSTEM EVACUATION
1. Upon completion of leak check, evacuate the refrigerant lines and indoor coil before opening the gas and liquid line valves.
2. Attach appropriate hoses from manifold gauge to gas and liquid line pressure taps.
NOTE: Unnecessary switching of hoses can be avoided and complete evacuation of all lines leading to sealed system can be accomplished with manifold center hose and connecting branch hose to a cylinder of HCFC-22 and vacuum pump.
3. The outdoor unit ships with a holding charge of dry nitrogen. The nitrogen should be removed and the entire system must be evacuated. Remove the refrigerant connection seal caps and open the service gas and liquid valves slowly to release the nitrogen from the unit.
NOTE: A 3/16" Allen wrench is required to open liquid line service valve. A 1/4" Open End or Adjustable wrench is required to open gas line valve. A 3/4" Open End wrench is required to take off the valve stem cap.
4. Attach center hose of manifold gauges to the vacuum pump once the nitrogen pressure has been relieved.
5. Evacuate until the micron gauge reads no higher than 350 microns.
6. Close off valve to vacuum pump and observe the micron gauge. If gauge pressure rises above 500 microns in one (1) minute, then evacuation is incomplete or system has a leak.
7. If vacuum gauge does not rise above 500 microns in one (1) minute, the evacuation should be complete.
8. With vacuum pump and micron gauge blanked off, weigh in HCFC 22 refrigerant based on the outdoor unit data plate and refrigerant line set length adjust­ments noted on page 1 of the Service Facts.
9. Close valve on HCFC-22 supply cylinder when the appropriate refrigerant charge has been achieved.
10. Replace gas and liquid service caps. These caps MUST BE REPLACED to prevent leaks. Replace caps by finger tightening, then tighten an additional 1/6 turn.
GAS LINE SERVICE VALVE
If refrigerant lines are longer than 15 feet and/or a different size than recommended, it will be necessary to adjust system refrigerant charge upon completion of installation. See page 6 or in the unit Service Facts.
D. ELECTRICAL CONNECTIONS
!
WARNING
When installing or servicing this equipment, ALWAYS exercise basic safety precautions to avoid the possibility of electric shock.
1. Power wiring and grounding of equipment must comply with local codes.
2. Power supply must agree with equipment nameplate.
3. Install a separate disconnect switch at the outdoor unit.
4. Ground the outdoor unit per local code requirements.
5. Provide flexible electrical conduit whenever vibration transmission may create a noise problem within the structure.
4
GAS LINE BALL SERVICE VALVE
UNIT SIDE OF VALVE
COOLING
CAP
PRESSURE TAP PORT
GAS LINE CONNECTION
CAP
CORE
1/4 TURN ONLY COUNTERCLOCKWISE FOR FULL OPEN POSITION
VALVE STEM
BODY
18-BC56D1-5 3
Page 4
Installer’s Guide
6. The use of color coded low voltage wire is recommended to simplify connections between the outdoor unit, the thermostat and the indoor unit.
Table 1 — NEC Class II Control Wiring
24 VOLTS
WIRE SIZE MAX. WIRE LENGTH
18 AWG 150 FT
16 AWG 225 FT.
14 AWG 300 FT.
7. Table 1 defines maximum total length of low voltage wiring from outdoor unit, to indoor unit, and to thermostat.
8. Mount the indoor thermostat in accordance with instruc­tion included with the thermostat. Wire per appropriate hook-up diagram (included in these instructions).
E. DEFROST CONTROL
The demand defrost control measures heat pump outdoor ambient temperature with a sensor located outside the outdoor coil. A second sensor located on the outdoor coil is used to measure the coil temperature. The difference between the ambient and the colder coil temperature is the difference or delta-T measurement. This delta-T measurement is representative of the operating state and relative capacity of the heat pump system. By measuring the change in delta-T, we can determine the need for defrost. The coil sensor also serves to sense outdoor coil temperature for termination of the defrost cycle.
FAULT IDENTIFICATION
A fault condition is indicated by the flashing light on the defrost control inside the heat pump control box.
In normal operation, the defrost control light will flash once each second. If the light is flashing more than once per second or not at all, refer to the service manual for that unit.
PIN IDENTIFICATION (See Figure 6.)
1. TEST_COMMON (Shorting any of the other pins to this pin causes the function of the other pin to be executed. Leaving this pin open results in the normal mode of operation.)
2. TST = Test (Shorting TEST_COMMON to this pin speeds up all defrost board timings.)
(HEAT PUMPS ONLY)
3. FRC_DFT = Forced Defrost (Short TEST_COMMON to this pin for two (2) seconds to initiate a forced defrost. Remove the short after defrost initiates.)
DEFROST CONTROL CHECKOUT
Normal operation requires:
a. LED on board flashing 1 time/second.
b. 24V AC between R & B
c. 24V AC between Y & B with unit operating
d. Defrost initiation when FRC_DFT pin is shorted to
TEST_COMMON pin.
If a defrost control problem is suspected, refer to the service information in control box.
F. COMPRESSOR START UP
After all electrical wiring is complete, SET THE THERMO­STAT SYSTEM SWITCH IN THE OFF POSITION SO COMPRESSOR WILL NOT RUN, and apply power by closing the system main disconnect switch. This will activate the compressor sump heat (where used). Do not change the Thermostat System Switch until power has been applied for one (1) hour. Following this procedure will prevent potential compressor overload trip at the initial start-up.
!
WARNING
Do NOT connect 24 VAC to T1 (ODS-A) terminal. ODS-A thermistor WILL BE BLOWN.
G. OPERATIONAL AND CHECKOUT
PROCEDURES
Final phases of this installation are the unit Operational and Checkout Procedures which are found in this instruction. To obtain proper performance, all units must be operated and charge adjustments made in accordance with procedures found in the Service Facts.
H. ELECTRIC HEATERS
Electric heaters, if used, are to be installed in the air han­dling device according to the instructions accompanying the air handler and the heaters.
I. START CONTROL
Some models have quick start components which are factory installed. For models that do not have factory installed start
PIN IDENTIFICATION
6
components, provisions are made for a field installed start kit accessory. When adding an accessory, follow the instructions provided with the kit.
J. OUTDOOR THERMOSTAT
An outdoor thermostat TAYSTAT250B may be field installed. For data, see wiring diagram attached to unit and instruction sheet packaged with outdoor thermostat.
TEST_COMMON
FRC_DFT
4 18-BC56D1-5
TST
K. SEACOAST SALT SHIELD
If installed within one mile of salt water, including sea­coasts and inland waterways, models without factory sup­plied Seacoast Salt Shields require the addition of BAYSEAC001 (Seacoast Kit) at installation time.
IMPORTANT:
See Limited Warranty information in Use and Care Manual.
Page 5
L. TROUBLESHOOTING
TROUBLESHOOTING CHART — WHAT TO CHECK
SYSTEM FAULTS
REFRIGERANT CIRCUIT
Liquid Pressure Too High
Liquid Pressure Too Low
Suction Pressure Too High
Suction Pressure Too Low
Liquid Refrig. Floodback TXV System
I.D. Coil Frosting
Compressor Runs Inadequate or No Cooling
ELECTRICAL
Compressor & O.D. Fan Do Not Start
Compressor Will Not Start But O.D. Fan Runs
O.D. Fan Won’t Start
Compressor Hums But Won’t Start
Compressor Cycles on IOL
I.D. Blower Won’t Start
P - Primary Causes S - Secondary Causes
HIGH VOLTAGE WIRING
POWER SUPPLY
CONTACTOR CONTACTS
START CAPACITOR
RUN CAPACITOR
START RELAY
COMPR. IOL
P
P
P
S
P
P
P
P
P
P
SPP
P
P
P
S
REFRIGERANT UNDERCHARGE
REFRIGERANT OVERCHARGE
CONTROL TRANSFORMER
LOW VOLTAGE WIRING
P
PPS
S
INEFFICI
STUCK COMPRESSOR
LOW VOLTAGE FUSE
CONTACTOR COIL
ENT COMPRESSOR
SSPPPP
S
S
PSPSS S S S
P
Installer’s Guide
RESTRICTED O.D. AIRFLOW
EXCESSIVE EVAP. LOAD
S
S
S
O.D. AIR RECIRCULATION
NONCONDENSABLES
P
P
P
S
P
P
TXV STUCK OPEN
P
PS
P
PSS
REF. CIRCUIT RESTRICTIONS
RESTRICTED I.D. AIRFLOW
O.D. FAN SPEED
SUPERHEAT
S
S
S
S
P
S
S
S
SWITCH
S
S
S
P
S
P
S
P
S
S
Thermostat
24 VAC HOT
FAN
24 VAC Common
SOV
COOL/HEAT 1st STAGE
HEATING 2nd STAGE
TYPICAL FIELD HOOK-UP DIAGRAMS
HEAT PUMP SYSTEMS
Indoor
Unit
R
G
R
G
B B/C
O
Y
W
W
Outdoor
Unit
R
B
O
Y
X2
Black
Thermostat
24 VAC HOT
FAN
24 VAC Common
COOLING
HEAT
AC SYSTEMS
Indoor
Unit
R
G
R
G
B B/C
Y
W
W
Outdoor
Unit
B
Y
Notes:
1. Be sure power supply agrees with equipment nameplate.
2. Power wiring and grounding of equipment must comply with local codes.
3. Low voltage wiring to be No. 18 AWG minimum conductor.
18-BC56D1-5 5
Page 6
Installer’s Guide
Installer’s Guide
SUBCOOLING CHARGING IN COOLING ABOVE 55°F OD AMBIENT
The manufacturer has always recommended installing approved
All 13 SEER split systems are AHRI rated with only TXV indoor systems.
The benefits of installing approved indoor and outdoor split systems are maximum efficiency, optimum performance and the best overall system reliability.
The following charging methods are therefore prescribed for systems with indoor TXVs.
1. Subcooling (in the cooling mode) is the
2. For best results - the indoor temperature should be kept
3. At start-up, or whenever charge is removed or added, the
4. Measure Liquid Line Temperature and Refrigerant
5. Determine total refrigerant line length, and height (lift)
6. Determine the Design Subcool Charging Temperature
7. Locate this value in the appropriate column of the
8. When system is correctly charged, you can refer to
matched indoor and outdoor systems.
only recommended
method of charging above 55°F ambient temperatures.
between 70°F to 80°F. Add system heat if needed.
system must be operated for a minimum 20 minutes to stabilize before accurate measurements can be made.
Pressure at service valves.
if indoor section is above the condenser.
from the unit nameplate.
Subcooling Charging Table. Locate your liquid line temperature in the left column of the table, and the intersecting liquid line pressure under your nameplate subcool value column. Add refrigerant to raise the pres­sure to match the table, or remove refrigerant to lower the pressure. Again, wait 20 minutes for the system conditions to stabilize before adjusting charge again.
System Pressure Curves (in Service Facts) to verify typical performance.
R-22 SUBCOOLING CHARGING TABLE
LIQUID
TEMP.
(°F)
45 89 93 96 100
50 98 102 105 109
55 107 111 115 119
60 117 121 126 130
65 128 132 137 141
70 139 144 148 153
75 151 156 161 166
80 163 168 174 179
85 176 182 187 193
90 190 196 202 208
95 205 211 217 223
100 220 226 233 239
105 236 243 249 256
110 253 260 267 274
115 271 278 285 293
120 289 297 305 313
125 309 317 325 333
DESIGN SUBCOOLING VALUES (°F)
8101214
LIQUID LINE PRESSURE (psi)
SUBCOOL CHARGING TABLE CORRECTIONS FOR LINE LENGTH AND RISE
60 50 40 30 25
Add 5 psig to Subcool Charging Table Pressure
20 15
Use Design Subcool Value from Table
10
REFRIGERANT
LINE LIFT (FEET)
Subtract 5 psig from S.C. Table Pressure
0
10 20 25 30 40 60 80
TOTAL REFRIGERANT LINE LENGTH (FEET)
6 18-BC56D1-5
Page 7
Installer’s Guide
OUTLINE DRAWING
NOTE: ALL DIMENSIONS ARE IN MM (INCHES).
MODELS BASE FIG. A B C D E F G H J K
2TTB3018A 2 2 651 (25-5/8) 724 (28-1/2) 651 (25-5/8) 5/8 1/4 127 (5) 57 (2-1/4) 181 (7-1/8) 44 (1-3/4) 457 (18)
2TTB3024A 2 2 832 (32-3/4) 724 (28-1/2) 651 (25-5/8) 3/4 5/16 137 (5-3/8) 65 (2-5/8) 210 (8-1/4) 57 (2-1/4) 457 (18)
2TTB3030A 3 2 832 (32-3/4) 829 (32-5/8) 756 (29-3/4) 3/4 5/16 137 (5-3/8) 86 (3-3/8) 210 (8-1/4) 79 (3-1/8) 508 (20)
2TTB3036A 3 2 832 (32-3/4) 829 (32-5/8) 756 (29-3/4) 7/8 3/8 137 (5-3/8) 86 (3-3/8) 210 (8-1/4) 79 (3-1/8) 508 (20)
2TTB3042A 4 1 841 (33-1/8) 946 (37-1/4) 870 (34-1/4) 7/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 508 (20)
2TTB3048A 4 1 1045 (41-1/8) 946 (37-1/4) 870 (34-1/4) 1-1/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 508 (20)
2TTB3060A 4 1 1045 (41-1/8) 946 (37-1/4) 870 (34-1/4) 1-1/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 508 (20)
MODELS BASE FIG. A B C D E F G H J K
2TWB3018A 2 2 832 (32-3/4) 724 (28-1/2) 651 (25-5/8) 5/8 1/4 127 (5) 57 (2-1/4) 181 (7-1/8) 44 (1-3/4) 457 (18)
2TWB3024A 2 1 832 (32-3/4) 724 (28-1/2) 651 (25-5/8) 3/4 5/16 137 (5-3/8) 65 (2-5/8) 210 (8-1/4) 57 (2-1/4) 457 (18)
2TWB3030A 3 1 933 (36-3/4) 829 (32-5/8) 756 (29-3/4) 3/4 5/16 143 (5-5/8) 92 (3-5/8) 210 (8-1/4) 79 (3-1/8) 508 (20)
2TWB3036A 4 1 943 (37-1/8) 946 (37-1/4) 870 (34-1/4) 7/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 508 (20)
2TWB3042A 4 1 943 (37-1/8) 946 (37-1/4) 870 (34-1/4) 7/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 508 (20)
2TWB3048A 4 1 1045 (41-1/8) 946 (37-1/4) 870 (34-1/4) 1-1/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 508 (20)
2TWB3060A 4 1 1045 (41-1/8) 946 (37-1/4) 870 (34-1/4) 1-1/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 508 (20)
18-BC56D1-5 7
Page 8
Installer’s Guide
MOUNTING HOLE LOCATION Note: All dimensions are in MM (Inches).
NOTE: For model base size, see table on page 7.
CHECKOUT PROCEDURE
After installation has been completed, it is recommended that the entire system be checked against the following list:
1. Refrigerant Line, Leak checked .................................. [ ]
2. Suction Lines and Fittings properly insulated ........... [ ]
3. Have all Refrigerant Lines been secured and
isolated properly? ........................................................ [ ]
4. Have passages through masonry been sealed? If mortar is used, prevent mortar from coming
into direct contact with copper tubing ........................ [ ]
5. Verify tightness of all electrical connects ................... [ ]
6. Observe outdoor fan during on cycle for clearance
and smooth operation .................................................. [ ]
7. Indoor coil drain line drains freely. Pour water
into drain pan .............................................................. [ ]
6200 Troup Highway Tyler, TX 75707
The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.
8. Supply registers and return grilles open and
unobstructed ................................................................ [ ]
9. Return air filter installed ............................................ [ ]
10. Thermostat thermometer is accurate. Check against a reliable thermometer. Adjust per
instructions with thermostat ...................................... [ ]
11. Is correct speed tap being used?
(Indoor blower motor) .................................................. [ ]
12. Operate complete system in each mode to
insure safe operation. .................................................. [ ]
02/12
Loading...