TRACO TIS600-172, TIS600-148SIG, TIS600-148, TIS600-148RED, TIS600-128 Datasheet

...
http://www.tracopower.com Page 1
Industrial Power Supplies
TIS Series 75 - 600 Watt
Features
Switch mode power supplies for DIN-rail mounting
4 power ranges with 3, 6, 12 and 24 A output current (24 VDC models)
Selectable 115/ 230 VAC input Very low ripple and noise EMI complies with EN50081-2 and
EN50082-2 Conducted EMI to EN55011 class B For system operation available with
built-in functions:
RED: Redundancy module for N+1
systems with true current sharing.
SIG: Signal module with AC-Power-
fail, DC- OK Signal and external ON/OFF control
UDS: DC-UPS module for uninter-
ruptable battery backed-up power systems.
Worldwide Safety Approvals Easy snap-on mounting on DIN-rails
or chassis mounting 2 Year Product Warranty
The switching power supplies of the TIS series have been particular y de­signed for applications in industrial process control systems and machine tools. Excellent specifications and high immunity against electrical distur­bances guarantee reliable power for sensitive loads in rugged industrial environments. With help of optional function modules specific requirements for system applications can be met by a standard product. With the UDS module the power supplies can be extended to a perfect DC-UPS with auto­matic battery- backup. This function is ver y often required in applications where a time delayed shutdown of a system is necessary. To monitor and control the power supply a signal module can be installed. For parallel operation with active power sharing a redundancy option is available. This flexibility makes the TIS series power supplies a cost effective solution for many industrial applications.
Models
Ordercode Input Voltage Output Power Output Voltage Output Current
(includes terminal plugs) max. nom. max.
TIS 75-112
115 / 230 VAC
12 VDC 6.0 A
TIS 75-124
selectable
75 W 24 VDC 3.0 A
TIS 75-148 48 VDC 1.5 A
TIS 150-124 115 / 230 VAC
150 W
24 VDC 6.0 A
TIS 150-148 selectable 48 VDC 3.0 A TIS 300-124
115 / 230 VAC
24 VDC 12 A
TIS 300-148
selectable
300 W 48 VDC 6.0 A
TIS 300-172 72 VDC 4.2 A TIS 500-124 230 V AC 500 W 24 VDC 20 A TIS 600-124 24 VDC 24 A
TIS 600-128 115 / 230 VAC
600 W
28 VDC 22 A
TIS 600-148 selectable 48 VDC 12 A TIS 600-172 72 VDC 8.5 A
TIS 300-124 DCI 300 - 800 VDC 300 W 24 VDC 12 A
http://www.tracopower.com Page 2
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
Industrial Power Supplies
TIS Series 75-600 Watt
Input Specifications
Input voltage range – TIS 75, TIS 150, TIS 300, TIS 600 93 132 VAC / 187 264 VAC
– TIS 500 187 – 264 VAC – TIS 300 DCI 300 – 800 VDC
Input frequency 47 – 63 Hz Input current at full load (typ.) 115 VAC 230 VAC
– TIS 75 1.7 A 0.9 A – TIS 150 3.0 A 1.7 A – TIS 300 5.4 A 3.3 A
– TIS 500 5.5 A – TIS 600 10.5 A 6.4 A
Inrush current (< 2 ms) 115 VAC 230 VAC – TIS 75 < 16.5 A < 33 A
– TIS 150 < 35 A < 70 A – TIS 300 < 35 A < 70 A
– TIS 500 < 70 A – TIS 600 < 70 A < 80 A
Output Specifications
Output voltage adj. range – 12 VDC models 12 14 VDC
– 24 VDC models 24 – 28 VDC – 28 VDC models 28 – 32 VDC – 48 VDC models 48 – 52 VDC (48 – 55 VDC on request)) – 72 VDC models 60 – 76 VDC
Regulation – Input variation ± 0.2 % max.
– Load variation (10–90%) – TIS 75, TIS 150 ± 1.0 % max.
– TIS 300, TIS 500, TIS 600 ± 0.3 % max.
(± 1.5 % in parallel operation) Ripple and Noise (20MHz Bandwidth) < 50 mV pk-pk Electronic shor t circuit protection current limitation at 110 % typ.
(constant current, automatic restart) Overvoltage protection, triggerpoint at 140 % typ. Vout nom. Hold-up time 115 VAC 230 VAC
– TIS 75 ... TIS 300 min. 25 ms min. 30 ms
– TIS 500 min. 40 ms – TIS 600 min. 15 ms min. 25 ms
http://www.tracopower.com Page 3
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
General Specifications
Temperature ranges Operating (ambient temp.) 25 °C+70 °C max.
Derating above 50 °C 2% /°C Storage (non operating) 25 °C+ 85 °C
Humidity (non condensing) 95 % rel H max.
Temperature coefficient 0.02 % / °C Switching frequency 80 kHz typ. (Pulswidth modulation) Efficiency TIS 75 ... TIS 300 85 % typ.
TIS 500 90 % typ. TIS 600 88 % typ.
Isolation according to EN 60950, UL 1950, UL 508C Reliability, calculated MTBF (MIL-HDBK-217 E) – TIS 75 /150 450000 h @ +25°C/ 420000 h @ +25°C
TIS 300 /500 360000 h @ +25°C/ 340000 h @ +25°C TIS 600 300000 h @ +25°C
Safety standards IEC 60950, EN 60950 (SELV),
UL/cUL 1950, UL 508C
Safety approvals UL/cUL 1950 recognized, File E18138
UL/cUL 508C listed, File E210002 UL/cuL 1604 listed, File E213613
(Class I,Division
2, Groups A, B, C and D hazardous locations)
CB-Scheme
Electromagnetic compatibility (EMC), Emissions EN 50081-1 / EN 50081-2 – Conducted RI suppression on input EN 55011 class B, EN 55022 class B,
FCC part 15, level B
Radiated RI suppression EN 55011 class A, EN 55022 class A,
FCC part 15, level A
Electromagnetic compatibility (EMC), Immunity EN 50082-2
– Electrostatic discharge (ESD) IEC / EN 61000-4-2 4 kV / 8 kV – Radiated RF field immunity IEC / EN 61000-4-3 10 V / m – Electrical fast transient / burst immunity IEC / EN 61000-4-4 2 kV – Surge immunity IEC / EN 61000-4-5 2 kV / 4 kV
– Immunity to conducted RF disturbances IEC / EN 61000-4-6 10 V – Power frequency field immunity IEC / EN 61000-4-8 30 A / m
Safety class Degree of Protection 1 (IEC 536) Case protection IP 20 (IEC 529) Environment – Vibration IEC 60068-2-6,1 gn, 200 sweeps, each axis
– Shock IEC 60068-2-27, 15 gn, 11 ms, each axis Enclosure material Aluminium (chassis) / stainless steel (cover) Mounting (snap-on with selflocking spring) for 35 mm DIN-rails as per EN 50022 Connection Plugable screw terminals (plugs included)
(TIS 600: screw terminal blocks)
Industrial Power Supplies
TIS Series 75-600 Watt
http://www.tracopower.com Page 4
Specifications can be changed without notice
Optional Mounting Systems Dimensions mm (inches)Power Supplies with Redundancy Function
With this option a parallel operation of up to 5 units is possible. Decoupling diodes and current share lines allow to build true N +1 redundant systems with active current sharing for all units. This function also includes an alarm relay to signal a single unit failure. This option is available for TIS 150 W, TIS 300 W and TIS 600 W models. Please note: A combination with other options is not possible.
Models
Ordercode Input Voltage Output Power Output Voltage Output Current
(includes terminal plugs) max. nom. max.
TIS 150-124 RED 115 / 230 VAC
150 W
24 VDC 6.0 A
TIS 150-148 RED selectable 18 VDC 12 A TIS 300-124 RED 115 / 230 VAC
300 W
24 VDC 12 A
TIS 300-148 RED selectable 48 VDC 6.0 A TIS 600-124 RED 115 / 230 VAC
600 W
24 VDC 24 A
TIS 600-148 RED selectable 48 VDC 12 A
Industrial Power Supplies
TIS Series 75-600 Watt
Specifications
Raiting per relay contact 60 VDC /0.36 A max.
I-Sense
Regulator
L
Con1 Pin3
N
115/230VAC
Con1 Pin1
AC
Con1 Pin2
DC
Common
Unit OK
Unit OK
Con3 - Pin1
Bus Indicator
Con2 - Pin1/2
Con2 - Pin3/4
V-Sense
+Vout
Current Share­line
Unit OK
Con3 - Pin4
Con3 - Pin3 Con3 - Pin2
-Vout
24/48VDC
Loading...