This manual and labels on the inverter provide very important information that you should bear in
mind to use the inverter properly and safely, and also to avoid injury to yourself and other people and
damage to property.
Read the safety precautions in the instruction manual for your inverter before reading this manual
and strictly follow the safety instructions given.
E6581315
Notice
♦ Insert an electromagnetic contactor between the inverter and the power supply so that
the machine can be stopped without fail from an external controller in case of an emergency.
♦ Do not write the same parameter to the EEPROM more than 10,000 times. The life time
of EEPROM is approximately 10,000 times.(Some parameters are not limited, please
refer to the “9.Parameter data “)
When using the TOSHIBA inverter protocol and the data does not need to be records,
use P command (the data is written only to RAM).
♦ About the handling of the inverter, please follow the instruction manual of the inverter.
Reference
Inverter instruction
manual
Section 4.2
“Commands”
1
E6581315
Contents
1.General outlines of the communication function......................................................................................................... 3
3.1. About the handling of received frames............................................................................................................... 5
4.1. Data transmission format ................................................................................................................................... 7
4.1.1. Data transmission format used in ASCII mode......................................................................................... 7
4.1.2. Data transmission format used in binary mode ...................................................................................... 10
4.1.3. Transmission format of Block Communication ....................................................................................... 13
4.4. Broadcast communication function .................................................................................................................. 21
4.5. Examples of the use of communication commands......................................................................................... 23
4.6. Examples of Communication programs ........................................................................................................... 24
6.Inter-drive communication ........................................................................................................................................ 33
6.1. Proportional control of speed ........................................................................................................................... 37
6.2. Transmission format for inter-drive communication ......................................................................................... 39
8.Commands and monitoring from the computer ........................................................................................................ 45
8.1. Communication commands (commands from the computer) .......................................................................... 45
8.2. Monitoring from the computer .......................................................................................................................... 49
8.3. Utilizing panel (LEDs and keys) by communication ......................................................................................... 58
8.3.1. LED setting by communication ............................................................................................................... 58
8.3.2. Key utilization by communication ........................................................................................................... 61
Appendix 1 Table of data codes........................................................................................................................................ 67
Appendix 2 Response time ............................................................................................................................................... 68
Appendix 3 Compatibility with the communication function of the VF-A7 ......................................................................... 69
This manual explains the RS485 communication function provided for the TOSVERT VF-AS1 series
of industrial inverters.
(1) RS485 communication by the use of a two-wire RS485 communication port (standard function)
(2) RS485 communication by the use of a four-wire RS485 communication port (standard function)
(1) 2-wire RS485 communication
connecto
(2) 4wire RS485 communication
connecto
By using these communication functions in combination with the computer link function designed to
establish a link between a higher level computing machine or controller (hereinafter referred to as a
computer) and each inverter on the network, or with the inter-drive communication function that allows proportional control of inverters without using a computer, you can set up a network for data
communication between inverters.
There are two communication protocols available: Toshiba Inverter Protocol and MODBUS-RTU
Protocol (this command does not support all commands). To select a protocol, the communication
protocol selection parameter f807 or f829 is used. (Refer to Section 3. Communication protocol.)
E6581315
<Computer link>
By preparing the program (explained later), the following information can be exchanged between the
computer (host) and the inverter.
(1) Monitoring function (used to monitor the operating status of the inverter: Output frequency,
current, voltage, etc.)
(2) Command function (used to issue run, stop and other commands to the inverter)
(3) Parameter function (used to set parameters and read their settings)
<Inter-drive communication function>
Master inverter sends the data, that is selected by the parameter, to all the slave inverters on the
same network. This function allows a network construction in which a simple synchronous or
proportional operation is possible among plural inverters (without the host computer).
As for data communication codes, the TOSVERT VF-AS1 series of inverters support the binary
(HEX) code, in addition to the JIS (ASCII) code. A communication number is used to access the desired data item.
* The smallest unit of information that computers handle is called a “bit (binary digit),” which repre-
sents the two numbers in the binary system: 1 or 0. A group of 16 bits is referred to as a “word,”
which is the basic unit of information the VF-AS1 series of inverters use for data communication.
One word can handle data items of 0 to FFFFH in hexadecimal notation (or 0 to 65535 in decimal
notation).
BIT15BIT8BIT7BIT0
1 bit
1 word
3
2. Data transmission specifications
ItemsSpecifications
Transmission schemeHalf-duplex
Synchronization schemeStart-stop synchronization
Communication baud rate9600/19200*/38400 bps (selectable using a parameter)
*1
Communication protocolTOSHIBA Inverter Protocol * / MODBUS-RTU (selectable using a parameter)
Character transmission<ASCII mode> JIS X 0201 8-bit (ASCII)
<Binary mode, MODBUS-RTU> Binary codes fixed to 8 bits
Stop bit lengthReceived by inverter: 1 bit, Sent by inverter: 2 bits
*3
Error detecting schemeParity *2: Even */Odd/Non parity (selectable using a parameter) *1,
11-bit characters *1 (Stop bit=1, with parity)
format
Order of bit transmissionLow-order bits transmitted first
Frame lengthVariable (to a maximum of 17 bytes)
*1: Changes to setting do not take effect until the inverter is turned back on or reset.
*2: JIS-X-0201 (ANSI)-compliant 8-bit codes are used for all messages transmitted in ASCII mode
and vertical (even) parity bits specified by JIS-X-5001 are added to them. These even parity bits
can be changed to odd parity bits by changing the parameter setting (a change to the parameter
setting does not take effect until the inverter has been reset.)
*: Standard
default setting
E6581315
*1
*3: Here are the default character transmission format.
Characters received: 11 bits (1 start bit + 8 bits + 1 parity bit + 1 stop bit)
START
BIT BIT0BIT1BIT2BIT3BIT4BIT5BIT6BIT7
The inverter receives one stop bit.
(The computer can be set so as to send 1, 1.5 or 2 stop bits.)
Characters sent: 12 bits (1 start bit + 8 bits + 1 parity bit + 2 stop bits)
START
BITBIT0BIT1
BIT2BIT3BIT4BIT5BIT6BIT7
The inverter sends two stop bits.
(The computer can be set so as to receive 1, 1.5 or 2 stop bits.)
PARITY
BIT
PARITY
BIT
STOP
BIT
STOP
BIT
STOP
BIT
4
3. Communication protocol
This communication protocol supports the TOSHIBA Inverter Protocol and part of MODBUS-RTU
protocol.
Select the desired protocol from in the following communication protocol selection parameters
(, ).
“Parameter Name and , Communication Number. 0807 and 0829”
* A parameter change is reflected when the inverter is reset, such as in power off.
3.1. About the handling of received frames
To send and receive data frames, a frame synchronization system for locating the start and end
points of each frame is defined with time for which no data is sent (time interval equivalent to the
time required to send 3.5 bytes of data).
If no data is sent for the time required to send 3.5 bytes of data at the current transmission speed
(approx. 4 ms or more at 9,600 bps or approx. 2 ms or more at 19,200/38,400 bps) after receipt of a
frame, the entire frame is assumed to have reached and information in it is analyzed. For this reason, an interval corresponding to at least 3.5 bytes of data must be placed between frames.
When sending a significant data set using two or more frames, an interval corresponding to at least
1.5 bytes of data must be placed between frames. If an interval corresponding to 1.5 bytes or more
is not placed, the contents of a frame are analyzed separately from those of the other frames, and
therefore communication are not carried out normally.
When two or more inverters on the same line are controlled individually one after another, not only
data from the host computer to an inverter but also a response from an inverter to the host computer
are transmitted to the other inverters on the line too. Therefore, an interval corresponding to at least
3.5 bytes should be placed between the time when the host computer receives a response from an
inverter and the time when it sends a frame to the next inverter. Otherwise the return frame received
and the frame that is sent immediately after receipt of the return frame will be recognized as one
frame and communication will not be carried out normally.
E6581315
[Correct]
Frame A
[Wrong] If divided into two smaller frames, frame A cannot be received as a
single frame.
Frame A (1/2)
1.5 bytes or more
5
3.5 bytes or more
Frame A (2/2)
Note: Correct if the interval corresponds
to less than 1.5 bytes of data.
Note: An inverter cannot receive frame
B before it finishes analyzing the
contents of frame A.
Frame B
Frame B
4. TOSHIBA Inverter Protocol
Select “TOSHIBA” (, =) in the communication protocol selection parameters.
“TOSHIBA” (, =) is set for initial communication protocol selection of shipment
setting. (See “3. Communication protocol.”)
Exchange of data between the computer and the inverter
In communication between the computer and the VF-AS1 (hereinafter referred to as the inverter),
the inverter is always placed in wait states and acts as a slave that operates on a request from the
computer.
A discrimination between ASCII mode and binary mode is automatically made with the start code.
ASCII mode“(”Required
Binary mode“2FH(/) ”Not required
(1) If there is no transmission format or the inverter number that matches, an error occurs and no
response is returned.
E6581315
Start code“CR” (carriage return)
Note
(2) When an inverter number is added behind the “(” communication will take place only in case of
broadcast communication or if the number matches up with that assigned to the inverters.
(3) When a time-out period is specified with parameter f803 (communication time-out time), a
time-out occurs if communication do not terminate normally within the specified time. With
parameter f804 (communication time-out action), you can specify what the inverter should do
if a time-out occurs. For details, refer to Section 7.3.
(4) On executing the command received, the inverter returns data to the computer. For the response
time, see Appendix 2, “Response time.”
Communication is not possible for about two seconds after the power is supplied to the inverter until
the initial setting is completed. If the control power is shut down due to an instantaneous voltage
drop, communication is temporarily interrupted.
6
4.1. Data transmission format
Note: The term “trip status” used in this manual includes retry waiting status and trip retention status.
4.1.1. Data transmission format used in ASCII mode
A communication number is used to specify a data item, all data is written in hexadecimal, and JISX-0201 (ASCII (ANSI))-compliant transmission characters are used.
Computer → Inverter
Omissible in one-to-one communication For the W and P commands only Omissible
E6581315
(3.5bytes
Blank)
Omissible
"("
(28H)
Checksum area
1. “(“ (1 byte): Start code in ASCII mode
2. INV-NO (2 bytes) : Inverter number (Omissible in one-to-one communication) ... 00 (30H, 30H) to 99 (39H,
3. CMD (1 byte): Command (For details, see the table below.)
4. Communication No.(4 bytes)
5. Data (0 to 4 bytes): Write data (valid for the W and P commands only)
6. “&” (1 byte): Checksum discrimination code (omissible. When omitting this code, you also need to omit
INV-NO
2 bytes
CMD
1 byte
39h), *(2AH)
The command is executed only when the inverter number matches up with that specified
using a parameter.
(When * is specified in broadcast communication, the inverter number is assumed to match
if all numbers except * match. When * is specified instead of each digit (two-digit number),
all inverters connected are assumed to match.)
If the inverter number does not match or if the inverter number is of one digit, the data will
be judged invalid and no data will be returned.
: Communication number (See 11, “Parameter data.”)
the checksum.)
Communication No.
4 bytes
DATA
0 to 4 bytes
"&"
(26H)
SUM
2 bytes
")"
(29H)
CR
(0DH)
(3.5bytes
Blank)
7. Sum (2 bytes): Checksum (omissible)
Add the ASCII-coded value of the last two digits (4 bits/digit) of the sum of a series of bits
(ASCII codes) from the start code to the checksum discrimination code.
Ex.: (R0000&??) CR
28H+52H+30H+30H+30H+30H+26H=160H
The last two digits represent the checksum. = 60
When omitting the checksum, you also need to omit the checksum discrimination
code.
8. “)” (1 byte): Stop code (omissible)
9. CR (1 byte): Carriage return code
Details of commands and data
CMD (1 byte)Write data (0 to 4 bytes) Hexadecimal number
R (52H): RAM read command
W (57H): RAM/EEPROM write command
P (50H) RAM write command
No data
Write data (0 to FFFF)
Write data (0 to FFFF)
7
Inverter → computer
At time of broadcast communication, returning of data is not executed, except for the inverters to be
returned, when the inverter number is not matched, and the inverter number has only one character.
This is because there will be a risk of that the returned data may be deformed.
Data returned when data is processed normally (ASCII mode)
Omissible in one-to-one communication Omissible
E6581315
(3.5bytes
Blank)
Omissible
"("
(28H)
Checksum area
1. “(“ (1 byte): Start code in ASCII mode
2. INV-NO (2 bytes) : Inverter number (omitted if it is not found in the data received) ... 00 (30H, 30H) to 99 (39H,
3. CMD (1 byte): Command ... The command is also used for a check when an inverter is tripped.
4. Communication No.(4 bytes) :
INV-NO
2 bytes
CMD
1 byte
39H)
If the inverter number matches up with that specified using a parameter, data will be returned to the computer. In broadcast communication, only the destination inverter (with a number matching up with the smallest effective number) returns data to the computer.
In broadcast communication, no data is returned from any inverters except the inverter
bearing a number that matches up with the smallest effective number.
Ex.: (*2R0000) CR -> (02R00000000) CR)
Under normal conditions... The uppercase letter R, W or P is returned, depending on the
command received: R, W or P command.
When an inverter is tripped... The lowercase letter r, w or p is returned, depending on the
command received: R, W or P command.
(The command received is returned with 20H added to it.)
The communication number received is returned.
Communication No.
4 bytes
Data is returned from the inverter with the number 2 only, but no data is returned from
inverters with the number 12, 22 ....
DATA
0 to 4 bytes
"&"
(26H)
SUM
2 bytes
")"
(29H)
CR
(0DH)
(3.5bytes
Blank)
5. Data (0 to 4 bytes): Data ... The data read in is returned for the R command, while the data received is returned
for the W and P commands. If the data received is composed of less than 4 digits, it will be
converted into 4-digit data and returned.
Ex.: (W123412) CR → (W12340012) CR)
6. “&” (1 byte): Checksum discrimination code (omitted if it is not found in the data received)
7. Sum (2 bytes): Checksum ... Omitted if no checksum discrimination code is found in the data received.
ASCII-coded value of the last two digits (4 bits/digit) of the sum of a series of bits (ASCII
codes) from the start code to the checksum discrimination code.
8. “)” (1 byte): Stop code (omitted if it is not found in the data received)
9. CR (1 byte): Carriage return code
8
• Data returned when data is not processed normally (ASCII mode)
In case an error occurs, communication error command (4EH(N) or 6EH(n)) and the error type number is returned to the computer in addition to the checksum. At time of broadcast communication of
the binary mode, returning of data is not executed except for the inverter to be returned (inverter
number 00H) and when the inverter number is not matched. This is because there will be a risk that
the returned data may be deformed.
Omissible Omissible
E6581315
(3.5bytes
Blank)
“(“
(28H)
INV-NO
2 bytes
“N” or “n”
(4EH) (6EH)
DATA
4 bytes
"&"
(26H)
SUM
2 bytes
Checksum area
Omissible
“(“ (1 byte): Start code in ASCII mode
“N” or “n” (1 byte):Communication error command ... This is also used for the checking of inverter trip.
“N” for the normal communication and “n” during the inverter trip.
INV-NO (2 bytes): Inverter number (omitted if it is not found in the data received) ... 00 (30H, 30H) to 99 (39H,
39H)
If the inverter number matches up with that specified using a parameter, data will be returned to the computer. In broadcast communication, only the destination inverter (with a number matching up with the smallest effective number) returns data to the computer.
Data (4 bytes): Error code (0000~0004)
0000 ... Impossible to execute (Although communication is established normally, the
command cannot be executed because it is to write data into a parameter whose
setting cannot be changed during operation (e.g., maximum frequency) or the
EEPROM is faulty.)
0001 ... Data error (The data is outside the specified range or it is composed of too many
digits.)
0002 ... Communication number error (There is no communication number that matches.)
0003 ... Command error (There is no command that matches.)
0004 ... Checksum error (The checksum result differs.)
")"
(29H)CR(0DH)
(3.5bytes
Blank)
“)” (1 byte): Stop code ... This code is omitted if it is not found in the data received.
Examples:
(N0000&5C)CR... Impossible to execute (e.g., a change of maximum frequency data during opera-
tion)
(N0001&5D)
(N0002&5E)
(N0003&5F)
... Data error (Data is outside the specified range.)
CR
... No communication number (There is no communication number that matches.)
CR
... There is no command that matches. (Commands other than the R, W and P
CR
commands)
(Ex.: L, S, G, a, b, m, r, t, w ...)
(N0004&60)
... Checksum error (The checksum result differs.)
CR
No data returned ... Format error or invalid inverter number
9
4.1.2. Data transmission format used in binary mode
A communication number is used to specify a data item, data is written in hexadecimal form, and
data in transmission characters are represented by binary codes (HEX codes).
Computer → Inverter (binary mode)
Omissible in one-to-one communication No data for the 52H (R) command
E6581315
(3.5bytes
Blank)
1. 2FH (“/”) (1 byte) : Start code in binary mode
2. INV-NO (2 bytes) : Inverter number (Omissible in one-to-one communication) ... 00H to 3FH ,FFH
3. CMD (1 byte): Command (For details, see the table below.)
4. Communication No.(2 bytes)
5. Data (2 bytes): 0000H to FFFFH
“/”
INV-NO
(2FH)
Checksum area Not omissible
1 byte
CMD
1 byte
In case the inverter number is other than FFH (broadcast communication), command is ex-
ecuted only when the inverter number coincides with the one designated with the panel. If
the inverter number is not matched, it will be judged invalid and the data is not returned.
52H (R) command: The size of the data following CMD is fixed to 3 bytes. (Communication
number: 2 bytes, checksum: 1 byte)
57H (W), 50H (P) and 47H (G) commands: The size of the data following CMD is fixed to 5
bytes.
(Communication number: 2 bytes, data: 2 byte, checksum: 1 byte)
Any command other than the above is rejected and no error code is returned.
: Communication number (See 11, “Parameter data.”)
57H (W) and 50H (P) commands: Write data (An area check is performed.)
47H (G) command: Dummy data (e.g., 0000) is needed.
52H (R) command: Any data is judged invalid. (No data should be added.)
Communication No.
2 bytes
DATA
2 bytes
SUM
1 byte
(3.5bytes
Blank)
6. Sum (2 bytes): Checksum (not omissible) 00H to FFH
Value of the last two digits (1 byte) of the sum of a series of bits (codes) from the start code
of the data returned to the data (or to the communication number for the 52H (R) command)
Ex.: 2F 52 00 ?? ... 2FH+52H+00H+00H=81H
The last two digits (??) represent the checksum= 81
No data
Write data (0000H to FFFFH)
Write data (0000H to FFFFH)
Dummy data (0000H to FFFFH)
10
Inverter → computer (binary mode)
At time of broadcast communication of the binary mode, returning of data is not executed except for
the inverter to be returned (inverter number 00H) and when the inverter number is not matched. This
is because there will be a risk that the returned data may be deformed.
• Data returned when data is processed normally (Binary mode)
Omissible
E6581315
(3.5bytes
Blank)
1. 2FH (“/“) (1 byte) : Start code in binary mode
2. INV-NO (2 bytes) : Inverter number... 00H to 3FH (The inverter number is omitted if it is not found in the data
3. CMD (1 byte): Command...The command is also used for a check when the inverter is tripped.
4. Communication No. (4 bytes)
5. Data (2 bytes): Data ... 0000H to FFFFH
6. Sum (1 bytes): Checksum (not omissible) 00H to FFH
“/”
INV-NO
(2FH)
Checksum area Not omissible
1 byte
CMD
1 byte
received.)
If the inverter number matches up with that specified from the operation panel, data will be
returned from the inverter. If the inverter number does not match, the data will be invalid
and no data will be returned.
Under normal conditions...52H (R), 47H (G), 57H (W) or 50H (P) is returned, depending on
the command received.
When the inverter is tripped...The lowercase letter 72H (r), 67H (g), 77H (w) or 70H (p) is
returned with 20H added to it, depending on the command received.
: The communication number received is returned.
The data read is returned for the 52H (R) and 47H (G) commands, while the data written is
returned for the 57H (W) and 50H (P) commands.
Value of the last two digits (1 byte) of the sum of a series of bits (codes) from the start code
to the data.
Communication No.
2 bytes
DATA
2 bytes
SUM
1 byte
(3.5bytes
Blank)
11
2) Error Processing (Binary mode)
In case an error occurs, communication error command (4EH(N) or 6EH(n)) and the error type number is returned to the computer in addition to the checksum. At time of broadcast communication of
the binary mode, returning of data is not executed except for the inverter to be returned (inverter
number 00H) and when the inverter number is not matched. This is because there will be a risk that
the returned data may be deformed.
Omissible
(3.5bytes
Blank)
Norn (1 byte): Communication error command ... This command is also used for a check when the in-
Data (2 bytes): Error code (0000~0004)
“/”
INV-NO
(2FH)
Checksum area Not omissible
1 byte
verter is tripped.
“4EH (N)” is returned under normal conditions, while “6EH (n)” is returned when the in-
verter is tripped.
0000 ... Impossible to execute (Although communication is established normally, the com-
mand cannot be executed because it is to write data into a parameter whose setting cannot be changed during operation (e.g., maximum frequency) or the
EEPROM is faulty.)
0001 ... Data error (The data is outside the specified range or it is composed of too many
digits.)
0002 ... Communication number error (There is no communication number that matches.)
0004 ... Checksum error (The checksum result differs.)
Norn
(4EH)(6EH)
DATA
2 bytes
SUM
1 byte
(3.5bytes
Blank)
E6581315
Examples:
No code returned ...Command error, format error (failure to receive the specified number of
bytes within 0.5 seconds, or an parity, overrun or framing error) or the
inverter number does not match or an inverter in broadcast communication in the binary mode except for the inverter for data returning (the
inverter numbered 00H).
2FH, 4EH, 00H, 00H, 7DH ... Impossible to execute (e.g., a change of maximum frequency data
during operation)
2FH, 4EH, 00H, 01H, 7EH ... Data setting error (The data specified falls outside the specified
range.)
2FH, 4EH, 00H, 02H, 7FH ... No communication number (There is no communication number that
matches.)
2FH, 4EH, 00H, 04H, 81H ... Checksum error (The checksum result differs.)
12
4.1.3. Transmission format of Block Communication
What is block communication?
Data can be written in and read from several data groups set in one communication by setting the
type of data desired for communication in the block communication parameters (, , to ) in advance. Block communication can save the communication time.
Data is transmitted hexadecimal using the binary (HEX) code transmission characters. “Computer
→ inverter” is for writing only, while “Inverter → computer” for reply is for reading only.
Computer → Inverter (Block Communication)
E6581315
Number of writing data groups x 2 bytes
Number of
read
data
groups
Write
data1
High
Write
data1
Low
Write
data2
High
Write
data2
Low
(3.5bytes
Blank)
Start
Code
“/”
Omissible
INV-NOCMD
“X”
Num-
ber of
write
data
groups
Checksum Area
1. 2FH(“/”) (1 byte) : Start code of binary mode
2. INV-NO (1 byte) : Inverter number. (Can be omitted in 1:1 communication): 00H to 3FH, FFH
Executed only when the inverter number matches the inverter number. Set on the panel, except in FFH (broadcast communication).
Communication data will be invalidated and data will not be returned either if the inverter
number. Does not match.
3. CMD (1 byte): ‘X’ (Block communication command)
4. Number of write data groups (1 byte)
: Specify the number of data groups to be written (00H to 02H).
If specified outside of the range, data will be treated as a format error and data will not be returned.
5. Number of read data groups (1 byte)
: Specify the number of data groups to be read (00H to 05H).
If specified outside of the range, data will be returned as “Number of read data groups = 0”
when returned by the inverter.
SUM
(3.5bytes
Blank)
6. Write data1 (2 bytes)
: Needed when the number of write data groups is larger than 1.
Data to be written to the specified parameter selected by
Dummy data is needed if the number of write data groups is larger than 1 even though(none)
is selected for
7. Write data2 (2 bytes)
: Needed when the number of write data groups is 2.
Data to be written to the specified parameter selected by
Dummy data is needed if the number of write data groups is 2 even though(none) is selected
for
8. SUM (1 byte): Checksum (Cannot be omitted) 00H to FFH
Lower two digits (1 byte) of total sum from start code (SUM value not included)
13
E6581315
Block Write 1, 2
Select data, which is desired to be written in block communication, in block write Data 1 and 2 Parameters (, ). This parameter becomes effective when the system is reset, such as
when power is turned off. When the setting is completed, turn off and then on the power.
No.Block Write DataFor data details, see:
0Deselect −
1Command information 1 (FA00)
2Command information 2 (FA20)
3Frequency Command (FA01)
4Terminal board output data (FA50)
5Communication analog output (FA51)
* When “Deselect” is specified in the parameters, no data will be written even though write data is
specified.
Block Read 1 to 5
Select read data, which is desired to be read in block communication, in block read data 1 and 5 Parameters (to). This parameter becomes effective when the system is reset,
such as when power is turned off. When the setting is completed, turn off and then on the power.
“8.1 Command by communication”
No.Block Read DataFor data details, see:
0Deselect −
1Status information (FD01)
2Output frequency (FD00)
3Output current (FD03)
4Output voltage (FD05)
5Alarm Information (FC91)
6PID feedback value (FD22)
7Input terminal board monitor (FD06)
8Output terminal board monitor (FD07)
monitor (FE37) will become hold data during a trip. Otherwise, real-time data appears.
* “0000” will be returned as dummy data,if “0 (Deselect)” is selected for the parameter and “read” is
specified.
“8.2 Monitoring from communication”
14
Inverter → Computer
At time of broadcast communication of the binary mode, returning of data is not executed except for
the inverter to be returned (inverter number 00H) and when the inverter number is not matched. This
is because there will be a risk that the returned data may be deformed.
1) Normal processing
E6581315
(3.5
bytes
Blank)
Omissible
Start
Code
“/”
INV
No.
CMD
“Y”
Number
of Read
Data
Groups
Write
Status
Read
data1
high
Number of read data groups x 2 bytes
Read
Read
Read
Read
data3
data2
data2
data1
high
low
high
low
Checksum area
1. 2FH “/” (1 byte):Start code in binary mode
2. INV-NO (1Byte):Inverter number・・・00H to 3FH
If the inverter number matches up with that specified from the operation panel, data will
be returned from the inverter. If the inverter number does not match, the data will be
judged invalid and no data will be returned.
Communication data will be invalidated and data will not be returned either if the inverter number does not match.(Inverter number is considered matched if it is omitted
during reception)
3. CMD(1Byte):‘Y’ (Block communication command [monitoring])
Lowercase letter ‘y’ during an inverter trip, including standing by for retrying and during
a trip.
4. Number of read data groups (1 byte)
: Return the number of data groups to be read (00H to 05H).
5. Write status (1 byte) : Return 00H to 03H.
* Failing to write in the specified parameter in the number of write data groups, set “1”
in the corresponding bit for the parameter failed to write. (See below.)
Read
data3
low
Read
data4
high
Read
data4
low
Read
data5
high
Read
data5
low
SUM(3.5
bytes
Blank)
Bit Position76543210
Data Type−
6. Read data1 - 5 (2 bytes)
: Return according to the number of read data groups. “0000H” is returned as dummy
data if “0” is selected as a parameter.
Read data1: Data selected by . Read data2: Data selected by .
Read data3: Data selected by . Read data4: Data selected by .
Read data5: Data selected by .
7.SUM(1Byte): Checksum (Cannot be omitted) 00H to FFH
Lower two digits (1 byte) of total sum from start code of return data to read data.
Example
(When set as follows: = (Command information 1), = (frequency command),
= (status information), = (output frequency), = (output current), = (output
voltage) and = (alarm information)
2) Error Processing (Binary mode)
In case an error occurs, communication error command (4EH(N) or 6EH(n)) and the error type number is returned to the computer in addition to the checksum.
Omissible
(3.5bytes
Blank)
“N” or “n” (1 byte) : Communication error command. Also for check during an inverter trip (includes standing
DATA (2 bytes): Error code (0004)
“/”
INV-NO
(2FH)
Checksum area Not omissible
0004 : Checksum error (The checksum does not match)
No return : Command error, format error (specified number of bytes is not received in 1sec,
1 byte
by for retrying and trip holding). “4EH (N)” when normal, “6EH (n)” during an inverter trip.
or parity error, overrun error or framing error), inverter number mismatch, and
inverter number other than 00H in broadcast communication.
R command Reads the data with the specified communication number.
W command Writes the data with the specified communication number. (RAM and EEPROM).
P command Writes the data with the specified communication number. (RAM).
G command
X command Block communication (Computer -> Inverter)
Y command Block communication (Inverter -> Computer)
E6581315
Reads the data with the specified communication number. (For binary mode only.
Dummy data is required for this command.)
W (57H) (RAM
This command is used to write new data into the parameter specified using it communication number. It writes data into the RAM and EEPROM. For parameters whose settings cannot be stored in
the EEPROM (e.g., parameter with the communication number FA00), the W (57H) command writes
data into the RAM only. It cannot be used to write data into read-only parameters (e.g., parameter
with the communication number FD?? or FE??).
Each time an attempt to write data is made, the inverter checks if the data falls within the specified
range. If this check reveals that the data falls outside the specified range, the inverter will reject it
and return an error code.
- Ex.: Setting the deceleration time (communication number: 0010) to 10 sec.
<ASCII mode>
<Binary mode>
♦ Do not write the same parameter to the EEPROM more than 10,000 times. The life time of EEPROM is
approximately 10,000 times.(Some parameters are not limited, please refer to the “9.Parameter data “)
The lifetime of EEPROM is approximately 10,000 times. When using the TOSHIBA inverter protocol and
the data does not need to be records, use P command (the data is written only to RAM).
*1: The RAM is used to temporarily store inverter operation data. Data stored in the RAM is cleared
*2: The EEPROM is used to store inverter operation parameter settings, and so on. Data stored in
when the inverter is turned off, and data stored in the EEPROM is copied to the RAM when the
inverter is turned back on.
the EEPROM is retained even after the power is turned off, and it is copied to the RAM when the
inverter is turned on or reset.
17
E6581315
P (50H) (RAM
*1
write)
This command is used to rewrite data into the parameter specified using a communication number.
It writes data into the RAM only. It cannot be used to write data into any read-only parameters. Each
time an attempt to write data is made the inverter checks whether the data falls within the specified
range. If this check reveals that the data falls outside the range, the inverter will reject it and return
an error code.
- Ex.: Entering the emergency stop command (communication number: FA00) from the computer
<ASCII mode>
This command is used to read the parameter data specified using a communication number. Although this command is used for the previous model to control the operation of two or more inverters
in binary mode through a two-wire RS485 network, the “R” command can also be used without
problems for the VF-AS1 series.
To use the “G” command, however, dummy data (2 bytes) is needed.
This command is available only in binary mode.
- Ex.: Monitoring the electric current (communication number: FE03)
Computer → InverterInverter
2F 47 FE 03 00 00 772F 47 FE 03 07 7B F9
* In this example, the data 00H sent from the computer to the inverter is dummy data.
→ Computer
S (53 H)/ s (73 H) Inter-drive communication command(RAM
This command is for using frequency command values in % (1 = 0.01%), instead of in Hz, and is for
synchronous-proportional operation in inter-drive communication. This command can also be
used in ordinary computer link communication.
When writing in the frequency command (FA01, FA05) is enabled and a parameter other than it is
specified, a communication number error will result. Data is written in the RAM only and at this
time the data check such as an upper limit and lower limit checking is not carried out.
Data is not returned from the inverters while this command is used. This command can be used
only in the binary mode.
For the details of the format, see “6.2 Transmission format for inter-drive communication.”
Use (%) as the unit for frequency command values specified by the command S, instead of (Hz),
and the receiving side converts units for frequency values to “Hz” in accordance with the point conversion parameter. The conversion formula is shown below.
*1
Write)
Frequency command value (Hz) =
Point 2 frequency (F813) − Point 1 frequency (F812)
Point 2 (F814) − Point 1 (F811)
− Point 1 (F811) + Point 1 frequency (F812)
18
x (Frequency command value (%)
E6581315
When Command “s” (lowercase letter) is received, the slave side judges that the master side is
tripped and operates in accordance with the inter-drive communication parameter (,).
For detail, see "7. Communication parameters ".
- Examples: 50% frequency command (2-wire RS485 communication)
(If maximum frequency = Frequency for operation at 80Hz = 40Hz: 50% = 5000d = 1388H)
Data selected in the block communication write parameters (,) is written in the
RAM. When returning data, data selected in block communication read parameters ( to
) is read and is returned.
For detail, see "4.1.3. Transmission format of Block Communication ".
- Examples: 60Hz operation command from communication and monitoring (Monitoring when al-
The command is impossible to execute, though communication was
established normally.
0000
1 Writing data into a parameter whose setting cannot be changed
during operation (e.g., maximum frequency)
*1
2 Writing data into a parameter while “” is in progress
Data errorInvalid data is specified.0001
Communication
There is no communication number that matches.0002
number error
Command errorThe command specified does not exist.0003 (ASCII mode)
No code returned (Binary
mode)
Checksum errorThe Checksum does not match.0004
Format errorThe data transmission format does not match.
No code returned
1 One-digit inverter number (ASCII mode)
2 The CR code is found in the designated position. (ASCII mode)
Ex.:Communication number of 4 digit or less. In the case of (R11)
CR, 11) CR is recognized as a communication number and
the CR code is not recognized, with the result that a format
error occurs.
3 A code other then the stop code (“)”) is entered in the stop code
position.
Receiving errorA parity, overrun or framing error has occurred.
*2
No code returned
*1: For parameters whose settings cannot changed during operation, see ”Table of parameters.”
*2: Parity error: The parity does not match.
Overrun error : A new data item is entered while the data is being read.
Framing error : The stop bit is placed in the wrong position.
* For the errors with “no code returned” in the above table, no error code is returned to avoid a data
crash.
If no response is received, the computer side recognizes that a communication error has occurred.
Retry after a lapse of some time.
* If the inverter number does not match, no processing will be carried out and no data will be re-
turned, though it is not regarded as an error.
20
4.4. Broadcast communication function
Broadcast communication function can transmit the command (write the data) to multiple inverters
by one communication. Only the write (W, P) command is valid and the read (R, G) command is invalid. The inverters subject to the broadcast communication are the same to the independent communication; 0 to 99 (00H - 63H) in the ASCII mode, and 0 to 63 (00H - 3FH) in the binary mode. To
avoid data deforming, the inverters to return data will be limited.
“Overall” broadcast communication (ASCII mode / Binary mode)
- ASCII Mode
If you enter two asterisks (**) in the inverter number position of the data transmission format, the
computer will send the data simultaneously to all inverters (with an inverter number between 0 and
99 (00 to 63H)) on the network.
- Binary Mode
To put "FF" to the specified place of the inverter number in the communication format validates the
broadcast communication and the command is transmitted to all the applicable inverters in the net-
work (inverter numbers from 0 to 63 (00 to 3FH)).
<Inverter that returns data to the computer>
Data is returned from the inverter bearing the inverter number 00 only.
If you do not want inverters to return data, do not assign the number 00 to any inverter on the network.
E6581315
“Group” broadcast communication (ASCII mode only)
If you put “*?” In the inverter number position of the data transmission format, data will be sent
simultaneously to all inverters bearing a number whose digit in the one’s place in decimal notation
is”?”
If you put ”?*” In the inverter number position of the data transmission format, the data will be sent
simultaneously to all inverters bearing a number whose digit in the ten’s place in decimal notation
is”?”.
(“?”: Any number between 0 and 9.)
<Inverter that returns data to the computer>
Data is returned only from the inverter bearing the smallest number in the same group of inverters
(i.e., inverter whose number in the position of ”*” is 0).
If you do not want inverters to return data to the computer, do not assign a number having a 0 in the
position of “*” to any inverter on the network.)
Examples of broadcast communication
Ex: Set the frequency setting for communication to 60Hz.
1 Host computer → Multiple inverters: broadcast communication (ASCII Mode)
Example of transmission of data from host computer to inverter: (**PFA011770)
Example of data returned from inverter to host computer: (00PFA011770)
Data is returned from the inverter numbered 00 only, while commands are issued to all inverters
connected to the network.
2 Host computer → A specific group of inverters: group communication (ASCII Mode)
Example of transmission of data from host computer to inverters: (*9PFA011770)
Example of data returned from inverter to host computer: (09PFA011770)
Data is returned only the inverter numbered 09 only, while commands are issued to a maximum
of 10 inverters bearing the number 09, 19, 29, 39, ... or 99.
CR
CR
CR
CR
21
Loading...
+ 51 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.