Toshiba RS4002Z-0 Instruction Manual

E6580938
RS485 Converter Unit Instruction Manual
RS4002Z-0
© TOSHIBA SCHNEIDER INVERTER CORPORATION
2001
All Rights Reserved.
1. Make sure that this instruction manual is delivered to the end user of the RS485 converter unit.
2. Read this manual before installing or operating the RS485 Converter unit. And keep it in a safe place for reference.
E6580938
1
Safety precautions
On the inverter and in its instruction manual, important information is contained for preventing injuries to users and damages to assets and for proper use of the device. Read the instruction manual attached to the inverter along with this instruction manual for completely understanding the safety precautions and adhere to the contents of these manuals.
■■■■
Handling in general
Danger
Never
Disassemble
Never disassemble, modify or repair the product.
Disassembling the product could cause electric shocks, fire or injuries.
For repairs, call your agency.
Prohibited
Do not remove connectors when the power is on.
It could lead to electric shocks.
Do not put or insert foreign objects such as waste cable, bars, or wires into the product.
It could lead to electric shocks or fire.
Do not splash water over the product.
It could lead to electric shocks or fire.
Mandatory
Wiring should be conducted after turning the inverter power off.
Turn off the power immediately in case any abnormalities such as smokes, smells or
abnormal noise are found.
Neglect of these conditions could lead to fire.
For repairs, call your agency.
■■■■
Transportation and installation
Danger
Prohibited
Do not install or operate the inverter if it is damaged or any part is missing from it.
Operating the inverter in a defective condition could lead to electric shocks or fire.
For repairs, call your agency. Do not put any inflammable material near the product.
It could catch fire if the product sparks because of a breakdown and the like. Do not install the product where it could be splashed with water and the like.
It could lead to electric shocks or fire.
Mandatory
The product must be used under environmental conditions prescribed in this instruction
manual.
Using the product under conditions not specified by the instruction manual could lead to
breakdown.
Cautions
Prohibited
Do not install the product in any place subject to vibrations or it could fall.
Otherwise it can cause injury to people.
E6580938
2
Wiring
Danger
Mandatory
Turn off input power before wiring.
Wait at least ten minutes and check to make sure that the charge lamp (on the inverter
main unit) is no longer lit.
Tighten the screws on the terminal board to specified torque.
If the screws are not tightened to the specified torque, it could lead to fire.
■■■■
About operation
Danger
Prohibited
Do not wipe the body with a wet cloth.
It could lead to electric shocks. Do not pull on the cable
It could cause damage or error.
■■■■
About disposal of the product
Warning
Mandatory
▼
Dispose of the
product
as an industrial waste. Unless it is disposed of as an industrial waste, it will become risks for human injury.
Notes on use

NOTES
Avoid installation locations that may be subjected to rapid changes in ambient temperature
or/and humidity.
Route the transmission cable separate from the inverter input/output power wiring.
When disconnecting connection cable, make sure to hold its connector with care not to give
unreasonable stress to the cable and the unit.
Separate the SHIELD terminal ground of the RS485 converter unit from those of
the inverter and the motor. It could cause malfunction due to noise.
Since connectors of optional cables have locking pawls for disconnection prevention at the  
inverter and the Option Unit, disconnect such a connector while pressing the pawl by finger for unlocking. Mount the Option Unit securely on the panel, otherwise it could fall and cause
malfunction or breakdown Connect an electromagnetic contactor or the like between the inverter and the power
source to secure external control of emergency stop of operation.
E6580938
−3−
Introduction
Thank you for purchasing the “RS485 Converter Option Unit(RS4002Z)” for TOSVERT series inverter.
Using this RS485 Option Unit, a communication between the inverter, which has the common serial
option (communication) connector, and a host computer is available.
Please read the entire manual carefully before attempting to control your inverter via RS485 serial
connection. Besides this instruction manual, the “Serial Communications Function Manual” is needed
to develop software which communicates with the inverter. In such a case, consult with our branch
office or sales office about it.
In addition, it has this manual kept to the operator using "RS485 Converter Unit", and please use it for
future maintenance and inspection
■■■■
Explanation of part number of RS485 Option Unit
RS4002Z −0
■■■■
Check of accessories
The RS485 Converter Unit is shipped together with the following items in the package. Contact your
sales agency if any of these is missing.
(1) RS485 Converter Unit …… 1 unit (RS4002Z)
(2) Instruction manual of RS485 Option Unit……1 copy
(E6580938)
(3) Connector terminal (remover side)……1 pcs
(TMSTBP 2.5/6-ST-5.08 : Phoenix Contact)
Note
The RS485 Option Unit (Part Number : RS4002Z) is not provided with connection cable between the inverter and Option Unit. This should be purchased separately.
Part number of connection cable between the Inverter and Option Unit
Cable length
CAB0011 1m (1.2m) CAB0013 3m (3.6m) CAB0015 5m (4.8m)
M
A
N
U
A
L
Revision number Cable length (Cable length between inverter and Option Unit)
Z: Without cable Model number of RS485 Option Unit
Symbol of RS485
E6580938
−4−
Table of Contents
1. OVERVIEW
・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・
5
2. COMMUNICATION SPECIFICATIONS
・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・
5
3. NAMES AND FUNCTIONS OF MAIN PARTS
・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・
6
4. CONNECTION WITH EQUIPMENT
・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・
7
4.1. Installation of RS485 converter unit
・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・
8
4.2. Wiring of inverter cables
・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・
8
4.3. Wiring of RS485 communication cable
・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・
9
4.3.1. Connection of RS485 communication cable
・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・
10
5. DIMENSIONS
・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・
11
6. COMMUNICATION PARAMETERS
・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・
12
7. SPECIFICATIONS
・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・
12
8. WARRANTY
・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・
12
E6580938
−5−
1. Overview
By using RS485 Converter Unit, a network can be constructed that allows communication between a host computer or PLC etc. and multiple inverter units.
A maximum of 32 Option Units can be connected on the same network. And 8 inverters can be connected to one RS485 Converter Unit. A maximum of 256 inverters
can be connected on the same
network.
Only when communicating between inverters, and the number is limited when communicating with
individual inverters depending on the function of each inverter.)
Host computer
RS4002Z
INV
Connection with up to 8 inverters
(*) A maxim um number of inverters connectable is 32 × 8 = 256. This number applies only to
communications between inverters. Up to 248 units can be connected in broadcast comm unication. In the case of indiv idual com m unications, the number is limited by the function of each inverter. Check the transmission format specification of the inverter to be used.
Example of VF-A7 series inverter
Communication between inverters: 32 × 8 = 256 units m ax
Broadcast communication: 31 × 8 = 248 units m ax
(31 units because of 1 unit needed for PC.)
Individual communication (ASCII mode): 100 units max
Individual communication (binary mode): 64 units max
RS485
<System configuration>
INV INV INV INV INV INV INV
RS4002Z
INV INV INV INV INV INV INV INV
2.
Communication specifications
Item Specifications Interface Conforming to EIA RS485 standard Configuration 4-wire/2-wire, bus type (A terminating resistor is
required at both ends of the system) Transmission method Semi-duplex Communication Distance 1,000m maximum Number of option units connectable 32 units maximum (31 units when PC is connected) Number of inverters connectable per option unit 8 units maximum Number of inverters on the Same Network 256 units maximum
(※)
Communication Line Isolation Not isolated Communication Speed 1200/2400/4800/9600/19200 baud selectable
(parameter and switch selection) Bit length 11 or12 bits (switch selectable)
E6580938
−6−
3.
Names and functions of main parts
The outline view of the RS485 converter unit and the names of each part
<How to remove the setting switch cover>
Insert a flat-head screwdriver into a slit marked with ∆ on the right-hand side of the unit to remove the cover.
mark on the right-hand side
of the unit
Connectors CN 1 to 8 to connect with inverters
View with the cover removed
Terminal board cover
Terminal board for RS485 communication cable (connector side)
To be connected to the inverter
’s connector for
common serial option
RS4002Z
Setting switches for communication speed and
bit
length
ON
1   4
ON
SW2
SW
1
1   4
Setting switches for terminating resistors and wiring method (4-wire/2-wire)
Speed SW1‑1 SW1‑2 SW1‑3
19200bps OFF OFF ON
9600bps ON ON OFF 4800bps OFF ON OFF 2400bps ON OFF OFF 1200bps OFF OFF OFF
Set the same communication speed as set for
p
arameter (F800) in the inverter unit.
Bitlength SW1‑4
12bit OFF 11bit ON
Set the transmission bit length set on the inverter side Set to 12 bits if the system has parity bit.
Start(1)+Data(8)+Parity(1)+Stop(2)=12bit
Terminating resistor 110Ω‑1/2W
SW2‑3 SW2‑4
Not
connected
OFF OFF
Connected
ON ON
SW2-3 (ON): Reception side (between RXA and RXB) terminating resistor is connected SW2-4 (ON): Transmission side (between TXA and TXB) terminating resistor is connected
Wiringmethod SW2‑1 SW2‑2
4‑wire OFF OFF 2‑wire ON ON
When communication is made in binary mode, inverters with 2-wire system (G command function is provided) can only communicate in 2-wire system SW2-1 (ON): RXA-TXA shorted SW2-2
(ON)
: RXB-TXB shorted
Terminal board for RS485 communication cable (plug side)
RXARXBTXATXBSGSHIELD
Terminating resistors should be connected at both ends of the system
.
E6580938
−7−
4. Connection with equipment
Connect the RS485 converter unit with inverters as follows:
(1) Turn off input power of the inverter and wait at least ten minutes and check to make sure that the
charge lamp is no longer lit.
(2) Set the communication speed, bit length and wiring method (4-wire or 2-wire) using the switches
of the RS485 converter unit. Furthermore, when communicating in the binary mode, the inverters
conforming to 2-wire system (G command function is provided) can only be communicated in 2-
wire system. When using the binary method but without the 2-wire system function, use 4-wire
system.
Use the same communication speed, bit length and wiring method for RS485 converter units that are connected in the same network. (Refer to page 6.)
(3)
Connect terminating resistor in both ends of units. The RS485 Option Unit has internal
terminating resistor. Set SW2-3 and SW2-4 to ON to connect these terminating resistors.
(Refer to page 6.) (4) Install the RS485 Option Unit on a metal panel. (Refer to page 8.) (5) Connect the RS485 communication cable to the removable terminal block. (Refer to page 9 and
page 10.).
Be sure not to short any wires.
(6) Connect the shield of the twisted pair cable to the SHIELD terminal on each RS485 Option Unit,
and make the ground connection. Do not connect the shield of the twisted pair cable to a power
ground or any other noise-producing ground connection
(7) Insert the removable terminal block back into the RS485 Option Unit.
(8) Connect the communication connectors (CN1 to 8) of the RS485 Option
Unit to the inverter’s common serial option (communication) connector of the with the optional
cable.
(9) Turn on the power of the inverter (10) Set the communication parameters of the inverter. (Refer to page 12.)
(11) Turn off the power of the inverter and then turn it on again if the parameters have been changed.
* Transmission/Reception is automatically changed in the RS485 converter unit.
This unit can be used only in semi-duplex transmission.
* Observe the following when data is transmitted from PC to the inverter.
To prevent a possible error due to the difference of communication speed between the equipment,
provide a time interval for one bit data length or more from the time data is received before starting
data to the inverter.
Time for one bit data = 1 ÷ communication speed (Example) in the case of 19200bps: 1 ÷ 19200 = 52µs
E6580938
8
4.1. Installation of RS485 converter unit
Install the unit on the panel of a cabinet etc. and secure the unit with two M4 screws.
Install the cables (connection cables between inverters and converter unit, and RS485 communication
cable). Separate the cables at least 20 cm from the main circuit cables. Do not bundle them together.
Attach the cables to the wall inside the cabinet etc.
*1 Unit interconnection screw hole: not used for this option.
4.2. Wiring of inverter cables
Observe the following when wiring is carried out:
Connect the inverter’s common serial option connector and this unit’s inverter connection connector
with optional connection cable.
Connection cable: CAB0011 (1m), CAB0013 (3m), CAB0015 (5m)
Separate the connection cables at least 20 cm from the main circuit cables. Do not bundle them
together.
Wiring them close to each other may lead to malfunction due to noise.
To inverter’s common serial option connectors
M4
RS485 communication cable
M4
Connection cables between inverters and converter unit
M4
M4
*1
*1
*1
*1
Connection cables between inverters and converter unit
E6580938
9
4.3. Wiring of RS485 communication cable
Observe the following when wiring is carried out:
Use shielded twist cables of 0.2 to 2.5 mm
2
for communication cables. Select wire size depending on
the transmission distance referring to the table below.
Use the same type of wires inside the system.
Recommended transmission cable
Item Specification
Transmission cable
Shielded twist cable
Connection method
Twist RXA and RXB wires and twist TXA and TXB. Twist RXA (or TXA) and RXB (or TXB) wires for 2-wire system. Note: Connect a terminating resistor at both ends of wires.
Cable type Cable length
Recommended maker
CPEV-CU
1.2 mmφ (single wire)
1000 m or less
KMPEV-SB
0.75 mm
2
(twisted wire)
700 m or less
KMPEV-SB
0.5 mm
2
(twisted wire)
500 m or less
Cable length
GECLS-9004 AWG24 (0.2 mm
2
) (single wire)
300 m or less
SHOWA W IRE &
CABLE Co. Ltd.,
Remove the sheath of wire about 10 mm from the end of wire. Use a flat-head screwdriver with the blade thickness of 0.6 mm and width of 3.5 mm. Screw tightening torque for the terminal board screws should be 0.5 to 0.6 N·m Separate the communication cables at least 20 cm from the main circuit cables. Do not bundle
them together.
Wiring them close to each other may lead to malfunction due to noise.
E6580938
10
4.3.1.
Connection of RS485 communication cable
Signal name Name
RXA Receiving data (+) RXB Receiving data (−) TXA Transmitting data (+) TXB Transmitting data (−)
SG Signal ground
SHIELD Shield
Upper and lower wire inlets are connected inside.
Removable terminal block
Maker : Phoenix Contact Type: TMSTBP 2.5/6-ST-5.08
Claw side
RXA
RXB
TXA
TXB
SG
SHIELD
Refer to the following together with items described above as to cable connection to terminal block.
Do not connect the ground of shield to power ground such as that of the inverter.
Se
p
arate the communication cables at least 200mm from the main circuit cables.
Recommended terminating resistor 120Ω-1/2W
SW2-1、SW2-2=OFF SW2-3、SW2-4=ON (Terminating resistor setting)
Grade 3 ground (Ground resistance 100Ω)
Host computer
RS485 converter unit
TXA TXB RXA RXB
SG FG
RXA RXB TXA TXB
SG
SHIELD
RXA RXB TXA TXB
SG
SHIELD
RXA RXB TXA TXB
SG
SHIELD
Shielded twist cable
Connection exam
p
le for 2-wire system
Grade 3 ground (Ground resistance 100Ω)
Host computer
− SG FG
RXA RXB TXA TXB
SG
SHIELD
RXA RXB TXA TXB
SG
SHIELD
RXA RXB TXA TXB
SG
SHIELD
Shielded twist cable
Connection exam
p
le for 4-wire system
+: Transmitting and receiving data (Positive)
: Transmitting and receiving data
(Negative)
SW2-1〜SW2-4=OFF
SW2-1、SW2-2=ON SW2-3、SW2-4=OFF
SW2-1、SW2-2=ON Either SW2-3 or SW2-4 should be set to ON. In this example, SW2-3 = OFF, SW2-4 = ON (Terminating resistor setting)
SW2-1、SW2-2=ON SW2-3、SW2-4=OFF
* Terminal numbers of host computer differ with models.
Read the instruction manual of host computer before wiring.
SW2‑4=ON
SW2‑3=ON
SW2‑4=ON
RS485 converter unit
RS485 converter unit
RS485 converter unit
RS485 converter unit
RS485 converter unit
Recommended terminating resistor 120Ω-1/2W
SW2-1〜SW2-4=OFF
E6580938
−11−
5.
Dimensions
Outline drawing of RS485 Converter Unit (RS4002Z)      (Unit: mm)
Dimension of the unit body
160
100
R2.5
180
168
25
16.5
8.5
R2.5
30
Panel installation dimension
E6580938
12E
6.
Communication parameters
Be careful the parameter setting range, initial value, etc. may change with the inverter models.
Function Parameter Note
Communication speed
f800
Communication speed must be the same in the same network (Inverters, Host computer, RS485 units).
Parity
f801
Parity setting must be the same in the same network (Inverters, Host computer).
Furthermore, set bit length using the setting switch referring to parity bit specification.
(Refer to page 6.)
Inverter number
f802
Do not assign the same inverter number in the same network (Inverters, Host computer). Need to set the inverter number in the transmission format.
7.
Specifications
Item Specifications
Part number RS4002Z-0
Service environment
Indoors. Altitude of less than 1000m. (3280ft) Must not be exposed to direct sunlight, subjected to corrosive and/or explosive gases, vapor, dust, chips, cutting oil, grinding agent, etc.
Ambient temperature From -10°C to +50°C (14°F to 104°F) Storage temperature From -25°C to +65°C (-13°F to 149°F)
Relative humidity 20 to 90% (no condensation allowed) Vibration
5.9 m/s
2
(0.6G) or less (10 to 55 Hz) (Conforming to JIS C0040)
8.
Warranty
Any part of the RS485 Option Unit that proves defective will be repaired free of charge under the
following conditions:
1. If and when a trouble occurs on the option unit properly installed and handled within one year of
delivery, and if the trouble is clearly attributable to defects inherent in our design and manufacture,
the product will be repaired free of charge.
2. The warranty covers only the delivered option unit.
3. Even in the term of the warranty, repair service will be charged for the following cases.
1) Fault or damage resulting from misuse, unauthorized modification or repair.
2) Fault or damage resulting from falling down of the product or traffic accident during transportation.
3) Fault or damage originating from fire, salt water/salty breezes, some kind of gas, earthquake,
storm or flood, lightning, abnormal supply voltage, other natural disasters.
4) Fault or damage caused by improper use of this option unit as it is used for a purpose out of its
original function.
4. If there is another special warranty contracted for this option unit, the special warranty has
priority over this warranty.