For upper pipe hole of indoor unit
(0.2” - thickness × 5.1” × 6.3” (6 - thickness × 130 × 160 mm))
–2–
EN
2-EN
Under Ceiling Type
Installation Manual
2PRECAUTIONS FOR SAFETY
Installing, starting up, and servicing air--conditioning equipment can be hazardous due to system pressures,
electrical components, and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should install, start--up, and service this equipment.
Untrained personnel can perform basic maintenance functions such as cleaning heat exchanger. All other
operations should be performed by trained service personnel.
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached
to the equipment.
Follow all safety codes.Wear safety glasses and work gloves. Keep quenching cloth and fire extinguisher nearby
when brazing. Use care in handling, rigging, and setting bulky equipment.
Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the
unit. Consult local building codes and National Electrical Code (NEC) for special requirements. Recognize safety
information. This is the safety--alert symbol . When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.Understand these signal words: DANGER, WARNING, and
CAUTION. These words are used with the safety--alert symbol.
DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING
signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which
may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which
will result in enhanced installation, reliability, or operation.
WARNING
• Ask an authorized dealer or qualified installation professional to install (including moving)/maintain the air
conditioner.
Inappropriate installation may result in water leakage, electric shock or fire.
• Be sure to connect ground wire. (grounding work)
Incomplete grounding cause an electric shock.
Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone wires.
• Turn off the circuit breaker before attempting any electrical work.
Make sure all circuit breaker is off. Failure to do so may cause electric shock.
• Install the refrigerant pipe securely during the installation work before operating the air conditioner.
If the air conditioner is operated with the valve open and without the refrigerant pipe, the compressor sucks air and
the refrigeration cycle is overpressurized, which may cause a burst or injury.
• When moving the air conditioner for the installation into another place, be very careful not to enter any
gaseous matter other than the specified refrigerant into the refrigeration cycle.
If air or any other gas is mixed in the refrigerant, the gas pressure in the refrigeration cycle becomes abnormally high
and it resultingly causes pipe burst and injuries on persons.
• Perform installation work properly according to the Installation Manual.
Inappropriate installation may result in water leakage, electric shock or fire.
• When the air conditioner is installed in a small room, provide appropriate measures to ensure that the
concentration of refrigerant leakage occur in the room does not exceed the critical level.
• Install the air conditioner securely in a location where the base can sustain the weight adequately.
• Perform the specified installation work to guard against an earthquake.
If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.
• If refrigerant gas has leaked during the installation work, ventilate the room immediately.
If the leaked refrigerant gas comes in contact with fire, noxious gas may generate.
• After the installation work, confirm that refrigerant gas does not leak.
If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas might
generate.
• Electrical work must be performed by a qualified electrician in accordance with the Installation Manual. Make
sure the air conditioner uses an exclusive power supply.
An insufficient power supply capacity or inappropriate installation may cause fire.
• Use the specified wires for wiring connect the terminals securely fix.
To prevent external forces applied to the terminals from affecting the terminals.
3-EN
–3–
Under Ceiling Type
• Conform to the regulations of the local electric company when wiring the power supply.
Inappropriate grounding may cause electric shock.
• For the refrigerant recovery work (collection of refrigerant from the pipe to the compressor), stop the
compressor before disconnecting the refrigerant pipe.
If the refrigerant pipe is disconnected while the compressor is working with the valve open, the compressor sucks air
and the refrigeration cycle is overpressurized, which may cause a burst or injury.
Installation Manual
CAUTION
• THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY
OZONE LAYER.
• The characteristics of R410A refrigerant are ; easy to absorb water, oxidizing membrane or oil, and its pressure is
approx. 1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil has also
been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerating oil does
not enter the refrigerating cycle.
• To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port of
the main unit and installation tools are changed from those for the conventional refrigerant.
• Accordingly the exclusive tools are required for the new refrigerant (R410A).
• For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust does not
enter.
• Tighten the flare nut with a torque wrench in the specified manner.
Excessive tightening of the flare nut may cause a crack in the flare nut after a long period, which may result in
refrigerant leakage.
• Wear heavy gloves during the installation work to avoid injury.
• The installation fuse must be used for the power supply line of this conditioner.
–4–
EN
4-EN
Under Ceiling Type
Installation Manual
3SELECTION OF INSTALLATION PLACE
WARNING
• Install the air conditioner at enough strong place
to withstand the weight of the unit.
If the strength is not enough, the unit may fall down
resulting in injury.
• Install the air conditioner at a height 8’ (2.4 m) or
more from the floor.
If you insert your hands or others directly into the unit
while the air conditioner operates, it is dangerous
because you may contact with revolving fan or active
electricity.
CAUTION
• Do not install the air conditioner in a location
subject to a risk of exposure to a combustible gas.
If a combustible gas leaks and stays around the unit,
a fire may occur.
Upon approval of the customer, install the air
conditioner in a place that satisfies the
following conditions.
• Place where the unit can be installed horizontally.
• Place where a sufficient servicing space can be
ensured for safety maintenance and check.
• Place where drained water will not cause any
problem.
Avoid installing in the following places.
• Place exposed to air with high salt content (seaside
area), or place exposed to large quantities of sulfide
gas (hot spring).
(Should the unit be used in these places, special
protective measures are needed.)
• Place exposed to oil, vapor, oil smoke or corrosive
gas.
• Place where organic solvent is used nearby.
• Place close to a machine generating high frequency.
• Place where the discharged air blows directly into
the window of the neighbor house. (Outdoor unit)
• Place where noise of the outdoor unit is easily
transmitted.
(When install the outdoor unit on the boundary with
the neighbor, pay due attention to the level of noise.)
• Place with poor ventilation. (Before air ducting work,
check whether value of fan speed, static pressure
and duct resistance are correct.)
Installation space
Secure the specified space in the figure for
installation and servicing.
Unit: in (mm)
9.8” (250)
or more
19.7” (500) or more
9.8” (250)
or more
Height of ceiling
Set the installable height of the ceiling within 13’1” (4
m), otherwise the air distribution will become poor.
If height of ceiling exceeds 11’6” (3.5 m), hot air
becomes difficult to reach the floor surface, and then
the change of setup of high ceiling is necessary.
For the change method of high ceiling, refer to the
application control, “In case of installation to high
ceiling” and “In case of incorporating filter sold
separately” in this Manual.
List of installable ceiling height
Setup data
0000
0001High ceiling 1
According to the conditions of installation, setup time of
turning-on of filter sign (notification of filter cleaning) of
the remote control can be changed.
When it is difficult to warm up the room due to
installation place or structure of the room, the detection
temperature of heating can be raised.
For change the setup time, refer to the application
control, “Change of filter sign turning-on time” and
“How to increase the heating effect” in this Manual.
Standard
(Factory default)
11’6” (3.5 m) or less
more than 11’6” (3.5 m)
up to 13’1” (4.0 m)
5-EN
–5–
Under Ceiling Type
Installation Manual
Wireless remote control
Decide the position which remote control is operated
and the installation place.
And then refer to the Installation Manual of the wireless
remote controller kit sold separately.
(The signal of the wireless type remote control can be
received within approx. 23’ (7 m). This distance is a
criterion and varies a little according to capacity of the
battery, etc.)
• To prevent malfunction, select a place where is not
affected by a fluorescent lamp or direct sunlight.
• Two or more (up to 6 units) wireless-type indoor units
can be set in a room.
A
p
p
r
o
x
.
2
3
’
(
7
m
)
2Removing wire guard
Remove the screws (2 pcs.) which are fixing the
wire guard.
Remove the clamp fixing screws and remove the
wire guard.
Clamps
Screw
CAUTION
Attach back the wire guard once indoor unit is installed.
Remove the 2 screws fixing the wire guard and hung the
wire guard with the clamps during a service.
Before installation
1Removal of suction grille
Slide the suction grille fixing knobs (2 positions)
toward the arrow direction, and then open the
suction grille.
Under the condition of suction grille opened, push
the hook section of hinges (2 positions) at the rear
side, and then pull out the suction grille.
Suction grille
Hinge
Suction grille
fixing knob
Wire guard
S
l
i
d
e
Pull out suction grille
while pushing hook.
–6–
EN
6-EN
Under Ceiling Type
3Removal of side panel
After removing the side panel fixing screws (1
each at right and left), slide the side panel forward
and then remove it.
Protector
Side panel
Level louver
Slide forward.
4Removal of protective vinyl
Peel out the protective vinyl on the level louver.
Installation Manual
5Removal of protector
Remove the protector (1 pcs.) of the fan.
(RAV-SP240CT only)
External view
REQUIREMENT
Strictly comply with the following rules to prevent
damage of the indoor units and human injury.
• Do not put a heavy article on the indoor unit. (Even
units are packaged)
• Carry in the indoor unit as it is packaged if possible.
If carrying in the indoor unit unpacked by necessity,
be sure to use buffering cloth, etc. to not damage
the unit.
• Do not apply force to the other parts (refrigerant
pipe, drain pan, foamed parts, or resin parts, etc.).
• Carry the package by two or more persons, and do
not bundle it with plastic band at positions other
than specified.
7-EN
–7–
Under Ceiling Type
Upper pipe draw-out port (knockout)
Hole for remote control wires (knockout)
3.3” (84)
6.7” (170)
(Hole for power supply cable. knockout)
12.6” (320)
Left drain size
Conduit hole
2.8”
(70)
Refrigerant pipe
(Liquid side ØC)
Refrigerant pipe (Gas side ØD)
B (Hanging position)
3.0” (75)
5.3” (135)
2.1”
(53)
1.5” (39)
2.0” (52)
8.5” (216)
5.7” (146)
13.7” (347)
12.2” (311)
10.3” (262)
3.5”
(90)
4.3” (110)
3.0” (76)
4.1” (105)
5.1” (130)
Drain pipe
connecting
port
3.8” (97)
8.3” (210)
2.0” (50)
26.8” (680)
7.9” (200) (Liquid pipe)
Hole for remote control wires
Conduit hole
(knockout)
3.6” (92)
1.3” (32)
Installation Manual
Unit: in (mm)
6.6” (167)
Pipe draw-out port
(knockout)
Drain port VP20
(Inner dia. Ø1.0” (26), hose
attached)
4.5” (114)
5.6” (141)
8.5” (216) (Gas pipe)
3.3” (84)
Hanging bolt
Within
2.0” (50)
Ceiling surface
Unit
Pipe hole on wall
(Ø3.9” (100) hole)
A
Outside air take-in port (Duct sold separately)
Knockout hole Ø3.6” (92))
5.7” (145)
Hole for power supply cable
Left drain pipe
draw-out port
(knockout)
Wireless sensor
mounting section
Unit: in (mm)
Model nameABCD
180CT
240CT
300CT, 360CT
to 420CT
35.8”
(910)
46.5”
(1180)
62.8”
(1595)
33.7”
(855)
44.3”
(1125)
60.6”
(1540)
Ø1/4”
(6.4)
Ø3/8”
(9.5)
Ø1/2”
(12.7)
Ø5/8”
(15.9)
Considering pipe/wire connecting work inside the ceiling after the indoor unit has been hanged, select an
installation place and determine piping direction.
• If the ceiling has already been set before hanging the main unit, prepare refrigerant pipe, drain pipe, indoor
connecting wire, remote control cord, etc. up to the place where pipe and wire can be connected.
• Check the size of the indoor unit, and match the indoor unit size using the attached installation pattern.
6.7” (171)
–8–
EN
8-EN
Under Ceiling Type
Installation Manual
Using attached installation pattern
Ceiling surface
Wall face
Installation pattern
Using the pattern, positioning of the hanging bolt and
pipe hole can be performed.
* As an error to some degree may generate on the
pattern size due to temperature and humidity, be
sure to confirm the size.
Installation of hanging bolts
Use 3/8” (M10) hanging bolts (4 pcs, to be local
procure).
Matching to the existing structure, set pitch according
to size in the unit external view as shown below.
New concrete slab
Install the bolts with insert brackets or anchor bolts.
Rubber
(Blade type
bracket)
Use existing angles or install new support angles.
(Slide type
bracket)
Steel flame structure
Hanging bolt
Anchor bolt
(Pipe hanging
anchor bolt)
Pipe knockout hole
• Piping from rear side
* Cut off the groove section with a plastic cutter, etc.
Rear cover
100
Opened when
Grooves
Opened when only drain pipe is
taken out from the rear side
• Piping from right side
* Cut off the groove section with a metal saw or
plastic cutter, etc.
• Piping from left side
Taking pipe from left side is applied only to the
drain pipe.
The refrigerant pipe cannot be taken out from the
left side.
* Cut off the groove section with a metal saw or
plastic cutter, etc.
refrigerant pipe is
taken out from the
rear side
Groove
Side panel (Right side)
Hanging bolt Support angle
Existing concrete slab
Use a hole-in anchors, hole-in plugs, or a hole-in bolts.
Draw-out direction of pipe/
wire
• Decide installation place of the unit and draw-out
direction of pipe and wire.
Groove
Side panel (Left side)
• Piping from upper side
Taking pipe from upper side is applied only to
the refrigerant pipe.
When taking out the drain pipe from the upper
side, use a drain up kit sold separately.
Open the upper pipe draw-out port (Knockout hole)
shown in the external view.
(Knockout hole of thin plate)
After piping, cut off the attached thermal insulator of
the top plate to pipe shape, and then seal the
knockout hole.
9-EN
–9–
Under Ceiling Type
Installation Manual
Installation of indoor unit
• Preparation before holding down main unit
* Confirm the presence of the ceiling material
beforehand because the fixing method of hanging
metal when the ceiling material is set differs from
that when the ceiling material is not set.
▼ There is ceiling material
Hanging bolt
(Procured locally)
Ceiling surface
Indoor
unit
Nut
(Procured locally)
Indoor
unit
Washer (Accessory)
Double nut
(Procured locally)
Hanging metal
Hanging bolt
(Procured locally)
Ceiling surface
Washer (Accessory)
(2) Hang the unit to the hanging bolt as shown the
figure below.
(3) As shown in the figure below, fix the ceiling material
securely with the double nuts.
2.0” (50 mm)
REQUIREMENT
• The ceiling surface may not be horizontal. Be
sure to confirm that width and depth directions
are level.
Double nut
(Procured locally)
Hanging metal
* Tighten the hanging metal with upper/lower nuts
as shown in the figure.
▼ There is no ceiling material
Hanging bolt
(Procured locally)
Washer
Indoor
unit
(Procured locally)
Washer (Accessory)
Double nut
(Procured locally)
• Holding down of main unit
(1) Attach washer and nuts to the hanging bolt.
Ceiling surface
0.8” - 1.2”
(20 - 30 mm)
Installation of remote control
(Sold separately)
For installation of the wired remote control, follow the
Installation Manual attached with the remote control.
• Pull out the remote control cord together with the
refrigerant pipe or drain pipe.
Be sure to pass the remote control cord through
upper side of the refrigerant pipe and drain pipe.
• Do not leave the remote control at a place exposed
to the direct sunlight and near a stove.
• Operate the remote control, confirm that the indoor
unit receives a signal surely, and then install it.
(Wireless type)
• Keep 3’3” (1 m) or more from the devices such as
television, stereo, etc.
(Disturbance of image or noise may generate.)
(Wireless type)
Washer
(Accessory)
Double nut
(Procured locally)
Hanging bolt
–10–
EN
10-EN
Loading...
+ 23 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.