Toshiba RAV-SP1104AT8Z-TR, RAV-SP1104AT8-TR, RAV-SP1404AT8-E, RAV-SP1404AT8-TR, RAV-SP1104AT8ZG-TR User Manual

...
SERVICE MANUAL
SPLIT TYPE
FILE NO. A10-002
OUTDOOR UNIT
<SUPER DIGITAL INVERTER>
RAV-SP1104AT8-E RAV-SP1104AT8-TR RAV-SP1104AT8Z-E RAV-SP1104AT8Z-TR RAV-SP1104AT8ZG-E RAV-SP1104AT8ZG-TR
RAV-SP1404AT8-E RAV-SP1404AT8-TR RAV-SP1404AT8Z-E RAV-SP1404AT8Z-TR RAV-SP1404AT8ZG-E RAV-SP1404AT8ZG-TR
RAV-SP1604AT8-E RAV-SP1604AT8-TR RAV-SP1604AT8Z-E RAV-SP1604AT8Z-TR RAV-SP1604AT8ZG-E RAV-SP1604AT8ZG-TR
RAV-SP1104AT7 RAV-SP1404AT7 RAV-SP1604AT7 RAV-SP1104AT7Z RAV-SP1404AT7Z RAV-SP1604AT7Z RAV-SP1104AT7ZG RAV-SP1404AT7ZG RAV-SP1604AT7ZG
R410A
PRINTED IN JAPAN, Apr., 2010 ToMo
CONTENTS
ORIGINAL INSTRUCTION ..................................................................................................... 3
WARNING INDICATIONS ON THE AIR CONDITIONER UNIT .............................................. 5
PRECAUTION FOR SAFETY ................................................................................................. 6
NEW REFRIGERANT (R410A) ............................................................................................ 11
1. SPECIFICATIONS ........................................................................................................ 13
1-1. Indoor Unit .................................................................................................................................. 13
1-2. Outdoor Unit ............................................................................................................................... 29
1-3. Operation Characteristic Curve ............................................................................................... 30
2. CONSTRUCTION VIEWS (EXTERNAL VIEWS) .......................................................... 32
2-1. Outdoor Unit ............................................................................................................................... 32
3. OUTDOOR UNIT REFRIGERATING CYCLE DIAGRAM ............................................. 35
4. WIRING DIAGRAM ...................................................................................................... 36
4-1. Outdoor Unit ............................................................................................................................... 36
5. SPECIFICATIONS OF ELECTRICAL PARTS .............................................................. 37
5-1. Outdoor Unit ............................................................................................................................... 37
6. REFRIGERANT R410A ................................................................................................ 38
6-1. Safety During Installation/Servicing ........................................................................................38
6-2. Refrigerant Piping Installation ............................................................................................... 38
6-3. Tools ............................................................................................................................................ 42
6-4. Recharging of Refrigerant ........................................................................................................ 42
6-5. Brazing of Pipes ......................................................................................................................... 43
6-6. Instructions for Re-use Piping of R22 or R407C .................................................................... 45
7. CIRCUIT CONFIGURATION AND CONTROL SPECIFICATIONS .............................. 48
7-1. Outdoor Unit Control ................................................................................................................. 48
7-2. Outline of Main Controls ........................................................................................................... 52
8. TROUBLESHOOTING .................................................................................................. 57
8-1. Summary of Troubleshooting ................................................................................................... 57
8-2. Troubleshooting ......................................................................................................................... 59
9. SETUP AT LOCAL SITE AND OTHERS...................................................................... 82
9-1. Calling of Error History ............................................................................................................. 82
9-2. Group Control Operation .......................................................................................................... 82
9-3. Outdoor Unit ............................................................................................................................... 84
10. ADDRESS SETUP ....................................................................................................... 91
10-1. Address Setup Procedure ......................................................................................................... 91
10-2. Address Setup & Group Control ..............................................................................................92
10-3. Remote Controller Wiring.......................................................................................................... 95
10-4. Address Setup (Manual setting from remote controller) ....................................................... 96
10-5. Confirmation of Indoor Unit No. Position ................................................................................ 97
11. REPLACEMENT OF THE SERVICE P.C. BOARD (4316V392) MCC-1599 ................. 99
12. HOW TO EXCHANGE COMPRESSOR...................................................................... 100
12-1. Exchanging Procedure of Compressor (Outline) ................................................................. 100
12-2. Exchange of Compressor ....................................................................................................... 100
13. INSTALLATION MANUAL .......................................................................................... 101
14. DETACHMENTS ......................................................................................................... 118
14-1. Outdoor Unit ............................................................................................................................. 118
15. EXPLODED VIEWS AND PARTS LIST ...................................................................... 130
15-1. Outdoor Unit ............................................................................................................................. 130
– 2 –
Original instruction
Please read carefully through these instructions that contain important information which complies with the “Machinery” Directive (Directive 2006/42/EC), and ensure that you understand them.
Some of the details provided in these instructions differ from the service manual, and the instructions provided here take precedence.
Generic Denomination: Air Conditioner
Definition of Qualified Installer or Qualified Service Person
The air conditioner must be installed, maintained, repaired and removed by a qualified installer or qualified service person.
When any of these jobs is to be done, ask a qualified installer or qualified service person to do them for you.
A qualified installer or qualified service person is an agent who has the qualifications and knowledge described in the table below.
Agent
Qualified installer (1)
Qualified service person (1)
Qualifications and knowledge which the agent must have
• The qualified installer is a person who installs, maintains, relocates and removes the air conditioners made by Toshiba Carrier Corporation.
He or she has been trained to install, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to these operations.
• The qualified installer who is allowed to do the electrical work involved in installation, relocation and removal has the qualifications pertaining to this electrical work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified installer who is allowed to do the refrigerant handling and piping work involved in installation, relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified installer who is allowed to work at heights has been trained in matters relating to working at heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified service person is a person who installs, repairs, maintains, relocates and removes the air conditioners made by Toshiba Carrier Corporation. He or she has been trained to install, repair, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to these operations.
• The qualified service person who is allowed to do the electrical work involved in installation, repair, relocation and removal has the qualifications pertaining to this electrical work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified service person who is allowed to do the refrigerant handling and piping work involved in installation, repair, relocation and removal has the qualifications pertaining to this refrigerant handling
she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified service person who is allowed to work at heights has been trained in matters relating to working at heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
and piping work as stipulated by the local laws and regulations, and he or
– 3 –
Definition of Protective Gear
When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and ‘safety’ work clothing.
In addition to such normal protective gear, wear the protective gear described below when undertaking the special work detailed in the table below.
Failure to wear the proper protective gear is dangerous because you will be more susceptible to injury, burns, electric shocks and other injuries.
Work undertaken
All types of work
Electrical-related work
Work done at heights (50 cm or more)
Transportation of heavy objects
Repair of outdoor unit
Protective gloves “Safety” working clothing
Gloves to provide protection for electricians and from heat Insulating shoes Clothing to provide protection from electric shock
Helmets for use in industry
Shoes with additional protective toe cap
Gloves to provide protection for electricians and from heat
Protective gear worn
The important contents concerned to the safety are described on the product itself and on this Service Manual.
Please read this Service Manual after understanding the described items thoroughly in the following contents (Indications/Illustrated marks), and keep them.
[Explanation of indications]
Indication
Explanation
DANGER
WARNING
CAUTION
Indicates contents assumed that an imminent danger causing a death or serious injury of the repair engineers and the third parties when an incorrect work has been executed.
Indicates possibilities assumed that a danger causing a death or serious injury of the repair engineers, the third parties, and the users due to troubles of the product after work when an incorrect work has been executed.
Indicates contents assumed that an injury or property damage (∗) may be caused on the repair engineers, the third parties, and the users due to troubles of the product after work when an incorrect work has been executed.
Property damage : Enlarged damage concerned to property, furniture, and domestic animal/pet
[Explanation of illustrated marks]
Mark Explanation
Indicates prohibited items (Forbidden items to do)
The sentences near an illustrated mark describe the concrete prohibited contents.
Indicates mandatory items (Compulsory items to do)
The sentences near an illustrated mark describe the concrete mandatory contents.
Indicates cautions (Including danger/warning)
The sentences or illustration near or in an illustrated mark describe the concrete cautious contents.
– 4 –
Warning Indications on the Air Conditioner Unit
[Confirmation of warning label on the main unit]
Confirm that labels are indicated on the specified positions
If removing the label during parts replace, stick it as the original.
Warning indication
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect all remote electric power supplies before servicing.
WARNING
Moving parts. Do not operate unit with grille removed. Stop the unit before the servicing.
Description
WARNING
ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies
before servicing.
WARNING
Moving parts. Do not operate unit with grille removed. Stop the unit before the servicing.
CAUTION
High temperature parts. You might get burned when removing
this panel.
CAUTION
Do not touch the aluminum fins of the unit. Doing so may result in injury.
CAUTION
BURST HAZARD
Open the service valves before the operation, otherwise there might be the burst.
CAUTION
High temperature parts. You might get burned when removing this panel.
CAUTION
Do not touch the aluminum fins of the unit. Doing so may result in injury.
CAUTION
BURST HAZARD Open the service valves before the operation,
otherwise there might be the burst.
– 5 –
Precaution for Safety
WARNING
Before starting to repair the air conditioner, read carefully through the Service Manual, and repair the air conditioner by following its instructions.
Only qualified service person (1) is allowed to repair the air conditioner. Repair of the air conditioner by unqualified person may give rise to a fire, electric shocks, injury,
water leaks and/or other problems.
Only a qualified installer (1) or qualified service person (1) is allowed to carry out the electrical work of the air conditioner.
Under no circumstances must this work be done by an unqualified individual since failure to carry out the work properly may result in electric shocks and/or electrical leaks.
Wear protective gloves and safety work clothing during installation, servicing and removal.
When connecting the electrical wires, repairing the electrical parts or undertaking other electrical jobs, wear gloves to provide protection for electricians and from heat, insulating shoes and clothing to provide protection from electric shocks.
Failure to wear this protective gear may result in electric shocks.
Use wiring that meets the specifications in the Installation Manual and the stipulations in the local regulations and laws.
Use of wiring which does not meet the specifications may give rise to electric shocks, electrical leakage, smoking and/or a fire.
General
Only a qualified installer (1) or qualified service person (1) is allowed to undertake work at heights using a stand of 50 cm or more or to remove the intake grille of the indoor unit to undertake work.
When working at heights, use a ladder which complies with the ISO 14122 standard, and follow the procedure in the ladder’s instructions.
Also wear a helmet for use in industry as protective gear to undertake the work.
When working at heights, put a sign in place so that no-one will approach the work location, before proceeding with the work.
Parts and other objects may fall from above, possibly injuring a person below.
Do not touch the aluminum fin of the outdoor unit. You may injure yourself if you do so. If the fin must be touched for some reason, first put on
protective gloves and safety work clothing, and then proceed.
Do not climb onto or place objects on top of the outdoor unit. You may fall or the objects may fall off of the outdoor unit and result in injury.
When transporting the air conditioner, wear shoes with additional protective toe caps.
When transporting the air conditioner, do not take hold of the bands around the packing carton. You may injure yourself if the bands should break.
This air conditioner has passed the pressure test as specified in IEC 60335-2-40 Annex EE.
DENGER
Before carrying out the installation, maintenance, repair or removal work, be sure to set the circuit breaker to the OFF position. Otherwise, electric shocks may result.
Before opening the intake grille of the indoor unit or service panel of the outdoor unit, set the circuit breaker to the OFF position.
Failure to set the circuit breaker to the OFF position may result in electric shocks through contact with the interior parts.
Turn off
breaker.
Only a qualified installer (1) or qualified service person (1) is allowed to remove the intake grille of the indoor unit or service panel of the outdoor unit and do the work required.
Before starting to repair the outdoor unit fan or fan guard, be absolutely sure to set the circuit breaker to the OFF position, and place a “Work in progress” sign on the circuit breaker.
When cleaning the filter or other parts of the indoor unit, set the circuit breaker to OFF without fail, and place a “Work in progress” sign near the circuit breaker before proceeding with the work.
– 6 –
Execute
discharge
between
terminals.
Prohibition
Stay on
protection
WARNING
Check earth
wires.
Even if the circuit breaker has been set to the OFF position before the service panel is removed and the electrical parts are repaired, you will still risk receiving an electric shock.
For this reason, short-circuit the high-voltage capacitor terminals to discharge the voltage before proceeding with the repair work.
For details on the short-circuiting procedure, refer to the Service Manual. You may receive an electric shock if the voltage stored in the capacitors has not been sufficiently
discharged.
Place a “Work in progress” sign near the circuit breaker while the installation, maintenance, repair or removal work is being carried out.
There is a danger of electric shocks if the circuit breaker is set to ON by mistake.
If, in the course of carrying out repairs, it becomes absolutely necessary to check out the electrical parts with the electrical parts box cover of one or more of the indoor units and the service panel of the outdoor unit removed in order to find out exactly where the trouble lies, wear insulated heat-resistant gloves, insulated boots and insulated work overalls, and take care to avoid touching any live parts.
You may receive an electric shock if you fail to heed this warning. Only qualified service person (1) is allowed to do this kind of work.
Before troubleshooting or repair work, check the earth wire is connected to the earth terminals of the main unit, otherwise an electric shock is caused when a leak occurs.If the earth wire is not correctly connected, contact an electric engineer for rework.
After completing the repair or relocation work, check that the ground wires are connected properly.
Be sure to connect earth wire. (Grounding work) Incomplete grounding causes an electric shock. Do not connect ground wires to gas pipes, water pipes, and lightning rods or ground wires for
telephone wires.
Do not modify the products.Do not also disassemble or modify the parts. It may cause a fire, electric shock or injury.
Prohibition of
modification.
Use specified
parts.
Do not bring a child close to the equipment.
Insulating measures
No fire
When any of the electrical parts are to be replaced, ensure that the replacement parts satisfy the specifications given in the Service Manual (or use the parts contained on the parts list in the Service Manual).
Use of any parts which do not satisfy the required specifications may give rise to electric shocks, smoking and/or a fire.
If, in the course of carrying out repairs, it becomes absolutely necessary to check out the electrical parts with the electrical parts box cover of one or more of the indoor units and the service panel of the outdoor unit removed in order to find out exactly where the trouble lies, place "Keep out" signs around the work site before proceeding.
Third-party individuals may enter the work site and receive electric shocks if this warning is not heeded.
Connect the cut-off lead wires with crimp contact, etc, put the closed end side upward and then apply a water-cut method, otherwise a leak or production of fire is caused at the users’ side.
When performing repairs using a gas burner, replace the refrigerant with nitrogen gas because the oil that coats the pipes may otherwise burn.
When repairing the refrigerating cycle, take the following measures.
1) Be attentive to fire around the cycle. When using a gas stove, etc, be sure to put out fire before work; otherwise the oil mixed with
refrigerant gas may catch fire.
2) Do not use a welder in the closed room. When using it without ventilation, carbon monoxide poisoning may be caused.
3) Do not bring inflammables close to the refrigerant cycle, otherwise fire of the welder may catch the inflammables.
– 7 –
Refrigerant
Assembly/
Cabling
Insulator
check
Ventilation
Compulsion
The refrigerant used by this air conditioner is the R410A. Check the used refrigerant name and use tools and materials of the parts which match with it. For the products which use R410A refrigerant, the refrigerant name is indicated at a position on
the outdoor unit where is easy to see. To prevent miss-charging, the route of the service port is changed from one of the former R22.
For an air conditioner which uses R410A, never use other refrigerant than R410A. For an air conditioner which uses other refrigerant (R22, etc.), never use R410A. If different types of refrigerant are mixed, abnormal high pressure generates in the refrigerating
cycle and an injury due to breakage may be caused. Do not charge refrigerant additionally.
If charging refrigerant additionally when refrigerant gas leaks, the refrigerant composition in the refrigerating cycle changes resulted in change of air conditioner characteristics or refrigerant over the specified standard amount is charged and an abnormal high pressure is applied to the inside of the refrigerating cycle resulted in cause of breakage or injury.
Therefore if the refrigerant gas leaks, recover the refrigerant in the air conditioner, execute vacuuming, and then newly recharge the specified amount of liquid refrigerant.
In this time, never charge the refrigerant over the specified amount. When recharging the refrigerant in the refrigerating cycle, do not mix the refrigerant or air other
than R410A into the specified refrigerant. If air or others is mixed with the refrigerant, abnormal high pressure generates in the refrigerating
cycle resulted in cause of injury due to breakage. After installation work, check the refrigerant gas does not leak.
If the refrigerant gas leaks in the room, poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.
Never recover the refrigerant into the outdoor unit. When the equipment is moved or repaired, be sure to recover the refrigerant with recovering device. The refrigerant cannot be recovered in the outdoor unit; otherwise a serious accident such as
breakage or injury is caused.
After repair work, surely assemble the disassembled parts, and connect and lead the removed wires as before.
Perform the work so that the cabinet or panel does not catch the inner wires. If incorrect assembly or incorrect wire connection was done, a disaster such as a leak or fire is
caused at user’s side.
After the work has finished, be sure to use an insulation tester set (500V Megger) to check the resistance is 2MΩ or more between the charge section and the non-charge metal section (Earth position).
If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s side.
When the refrigerant gas leaks during work, execute ventilation.
If the refrigerant gas touches to a fire, poisonous gas generates. A case of leakage of the refrigerant and the closed room full with gas is dangerous because a
shortage of oxygen occurs. Be sure to execute ventilation.
When the refrigerant gas leaks, find up the leaked position and repair it surely. If the leaked position cannot be found up and the repair work is interrupted, pump-down and
tighten the service valve, otherwise the refrigerant gas may leak into the room. The poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove
though the refrigerant gas itself is innocuous. When installing equipment which includes a large amount of charged refrigerant such as a multi
air conditioner in a sub-room, it is necessary that the density does not the limit even if the refrigerant leaks.
If the refrigerant leaks and exceeds the limit density, an accident of shortage of oxygen is caused.
Tighten the flare nut with a torque wrench in the specified manner. Excessive tighten of the flare nut may cause a crack in the flare nut after a long period, which may
result in refrigerant leakage.
Nitrogen gas must be used for the airtight test.
The charge hose must be connected in such a way that it is not slack.
For the installation/moving/reinstallation work, follow to the Installation Manual. If an incorrect installation is done, a trouble of the refrigerating cycle, water leak, electric shock or
fire is caused.
– 8 –
Check after
repair
Do not
operate the
unit with the
valve closed.
Check after
reinstallation
Cooling check
Installation
Once the repair work has been completed, check for refrigerant leaks, and check the insulation resistance and water drainage.
Then perform a trial run to check that the air conditioner is running properly.
After repair work has finished, check there is no trouble. If check is not executed, a fire, electric shock or injury may be caused. For a check, turn off the power breaker.
After repair work (installation of front panel and cabinet) has finished, execute a test run to check there is no generation of smoke or abnormal sound.
If check is not executed, a fire or an electric shock is caused. Before test run, install the front panel and cabinet.
Check the following matters before a test run after repairing piping.
• Connect the pipes surely and there is no leak of refrigerant.
• The valve is opened.
Running the compressor under condition that the valve closes causes an abnormal high pressure resulted in damage of the parts of the compressor and etc. and moreover if there is leak of refrigerant at connecting section of pipes, the air is suctioned and causes further abnormal high pressure resulted in burst or injury.
Only a qualified installer (1) or qualified service person (1) is allowed to relocate the air conditioner. It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire, electric shocks, injury, water leakage, noise and/or vibration may result.
Check the following items after reinstallation.
1) The earth wire is correctly connected.
2) The power cord is not caught in the product.
3) There is no inclination or unsteadiness and the installation is stable.
If check is not executed, a fire, an electric shock or an injury is caused.
When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe.
Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air, etc. to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly resulting in reputing, injury, etc.
When the service panel of the outdoor unit is to be opened in order for the compressor or the area around this part to be repaired immediately after the air conditioner has been shut down, set the circuit breaker to the OFF position, and then wait at least 10 minutes before opening the service panel.
If you fail to heed this warning, you will run the risk of burning yourself because the compressor pipes and other parts will be very hot to the touch. In addition, before proceeding with the repair work, wear the kind of insulated heat-resistant gloves designed to protect electricians.
When the service panel of the outdoor unit is to be opened in order for the fan motor, reactor, inverter or the areas around these parts to be repaired immediately after the air conditioner has been shut down, set the circuit breaker to the OFF position, and then wait at least 10 minutes before opening the service panel.
If you fail to heed this warning, you will run the risk of burning yourself because the fan motor, reactor, inverter heat sink and other parts will be very hot to the touch.
In addition, before proceeding with the repair work, wear the kind of insulated heat-resistant gloves designed to protect electricians.
Only a qualified installer (1) or qualified service person (1) is allowed to install the air conditioner. If the air conditioner is installed by an unqualified individual, a fire, electric shocks, injury, water leakage, noise and/or vibration may result.
Before starting to install the air conditioner, read carefully through the Installation Manual, and follow its instructions to install the air conditioner.
Do not install the air conditioner in a location that may be subject to a risk of expire to a combustible gas.
If a combustible gas leaks and becomes concentrated around the unit, a fire may occur.
Install the indoor unit at least 2.5 m above the floor level since otherwise the users may injure themselves or receive electric shocks if they poke their fingers or other objects into the indoor unit while the air conditioner is running.
Install a circuit breaker that meets the specifications in the installation manual and the stipulations in the local regulations and laws.
Install the circuit breaker where it can be easily accessed by the qualified service person (∗1).
Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner, otherwise it may cause imperfect combustion.
– 9 –
Explanations given to user
• If you have discovered that the fan grille is damaged, do not approach the outdoor unit but set the circuit breaker to the OFF position, and contact a qualified service person to have the repairs done.
Do not set the circuit breaker to the ON position until the repairs are completed.
Relocation
• Only a qualified installer (1) or qualified service person (1) is allowed to relocate the air conditioner. It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire, electric shocks, injury, water leakage, noise and/or vibration may result.
• When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe. Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air, etc. to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly resulting in reputing, injury, etc.
(1) Refer to the “Definition of Qualified Installer or Qualified Service Person.”
Declaration of Conformity
Manufacturer: Toshiba Carrier Corporation
336 Tadehara, Fuji-shi, Shizuoka-ken 416-8521 JAPAN Authorized Nick Ball Representative/TCF holder: Toshiba EMEA Engineering Director
Toshiba Carrier UK Ltd.
Porsham Close, Belliver Industrial Estate,
PLYMOUTH, Devon, PL6 7DB.
United Kingdom Hereby declares that the machinery described below: Generic Denomination: Air Conditioner Model/type: RAV-SP1104AT8-E RAV-SP1404AT8-E RAV-SP1604AT8-E
RAV-SP1104AT8Z-E RAV-SP1404AT8Z-E RAV-SP1604AT8Z-E
RAV-SP1104AT8ZG-E RAV-SP1404AT8ZG-E RAV-SP1604AT8ZG-E
RAV-SP1104AT8-TR RAV-SP1404AT8-TR RAV-SP1604AT8-TR
RAV-SP1104AT8Z-TR RAV-SP1404AT8Z-TR RAV-SP1604AT8Z-TR
RAV-SP1104AT8ZG-TR RAV-SP1404AT8ZG-TR RAV-SP1604AT8ZG-TR Commercial name: Super Digital Inverter Series Air Conditioner Complies with the provisions of the “Machinery” Directive (Directive 2006/42/EC) and the regulations transposing
into national law. Complies with the provisions of the following harmonized standard:
EN 378-2: 2008 Note: This declaration becomes invalid if technical or operational modifications are introduced without the
manufacturer’s consent.
Disposal
How to dispose of air conditioners with a rating of 12 kW and below in accordance with the 2002/96/EC Directive WEEE (Waste Electrical and Electronic Equipment) is provided in the Installation Manual supplied with your product. For disposal of the product above 12 kW in rating you should use a registered company in accordance with any national or EU legislation.
<Model names with a rating of 12 kW and below (outdoor units)>
DI series
RAV-SM563AT-E RAV-SM803AT-E RAV-SM1103AT-E
SDI series
RAV-SP404AT-E RAV-SP404ATZ-E RAV-SP404ATZG-E RAV-SP454AT-E RAV-SP454ATZ-E RAV-SP454ATZG-E RAV-SP564AT-E RAV-SP564ATZ-E RAV-SP564ATZG-E RAV-SP804AT-E RAV-SP804ATZ-E RAV-SP804ATZG-E RAV-SP1104AT-E RAV-SP1104ATZ-E RAV-SP1104ATZG-E RAV-SP1104AT8-E RAV-SP1104AT8Z-E RAV-SP1104AT8ZG-E RAV-SP1104AT8-TR RAV-SP1104AT8Z-TR RAV-SP1104AT8ZG-TR
– 10 –
New Refrigerant (R410A)
This air conditioner adopts a new HFC type refrigerant (R410A) which does not deplete the ozone layer.
1. Safety Caution Concerned to New Refrigerant
The pressure of R410A is high 1.6 times of that of the former refrigerant (R22).
Accompanied with change of refrigerant, the refrigerating oil has been also changed.
Therefore, be sure that water, dust, the former refrigerant or the former refrigerating oil is not mixed into the refrigerating cycle of the air conditioner with new refrigerant during installation work or service work.
If an incorrect work or incorrect service is performed, there is a possibility to cause a serious accident.
Use the tools and materials exclusive to R410A to purpose a safe work.
2. Cautions on Installation/Service
1) Do not mix the other refrigerant or refrigerating oil.
For the tools exclusive to R410A, shapes of all the joints including the service port differ from those of the former refrigerant in order to prevent mixture of them.
2) As the use pressure of the new refrigerant is high, use material thickness of the pipe and tools which are specified for R410A.
3) In the installation time, use clean pipe materials and work with great attention so that water and others do not mix in because pipes are affected by impurities such as water, oxide scales, oil, etc.
Use the clean pipes.
Be sure to brazing with flowing nitrogen gas. (Never use gas other than nitrogen gas.)
4) For the earth protection, use a vacuum pump for air purge.
5) R410A refrigerant is azeotropic mixture type refrigerant.
Therefore use liquid type to charge the refrigerant. (If using gas for charging, composition of the refrigerant changes and then characteristics of the air conditioner change.)
3. Pipe Materials
For the refrigerant pipes, copper pipe and joints are mainly used.
It is necessary to select the most appropriate pipes to conform to the standard.
Use clean material in which impurities adhere inside of pipe or joint to a minimum.
1) Copper pipe
<Piping>
The pipe thickness, flare finishing size, flare nut and others differ according to a refrigerant type.
When using a long copper pipe for R410A, it is recommended to select “Copper or copper-base pipe without seam” and one with bonded oil amount 40mg/10m or less.
Also do not use crushed, deformed, discolored (especially inside) pipes. (Impurities cause clogging of expansion valves and capillary tubes.)
<Flare nut>
Use the flare nuts which are attached to the air conditioner unit.
2) Joint
The flare joint and socket joint are used for joints of the copper pipe.
The joints are rarely used for installation of the air conditioner.
However clear impurities when using them.
– 11 –
4. Tools
1. Required Tools for R410A
Mixing of different types of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.
1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))
2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)
3) Tools commonly used for R410A and for conventional refrigerant (R22)
The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
No.
Q
R
S
T
U
V
W
X
Y
Used tool
Flare tool
Copper pipe gauge for adjusting projection margin
Torque wrench
Gauge manifold
Charge hose
Vacuum pump adapter
Electronic balance for refrigerant charging
Refrigerant cylinder
Leakage detector
Usage
Pipe flaring
Flaring by conventional flare tool
Tightening of flare nut
Evacuating, refrigerant charge, run check, etc.
Vacuum evacuating
Refrigerant charge
Refrigerant charge
Gas leakage check
air conditioner installation
Existence of
new equipment
for R410A
Ye s (Note)
Ye s (Note)
Ye s N o
Ye s N o
Ye s N o
Ye s Ye s
Ye s N o
Ye s N o
R410A
Whether conventional
equipment can be used
Conventional air
conditioner installation
Whether
conventional equipment
can be used
Ye s
(Note)
No
No
Ye s
Ye s
No
Ye s
(Note) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary as the general tools.
1) Vacuum pump. Use vacuum pump by attaching vacuum pump adapter. 7) Screwdriver (+, –)
2) Torque wrench 8) Spanner or Monkey wrench
3) Pipe cutter 9) Hole core drill
4) Reamer 10) Hexagon wrench (Opposite side 4mm)
5) Pipe bender 11) Tape measure
6) Level vial 12) Metal saw
Also prepare the following equipments for other installation method and run check.
1) Clamp meter 3) Insulation resistance tester (Megger)
2) Thermometer 4) Electroscope
– 12 –
1. SPECIFICATIONS
1-1. Indoor Unit
1-1-1. 4-Way Air Discharge Cassette Type
<Single type>
Model
Cooling capacity (kW)
Heating capacity (kW)
Power supply
Cooling Power factor (%) 81 87 90 81 87 90
Electrical characteristics
Heating Power factor (%) 81 87 90 81 87 90
Appearance
Outer dimension
Total weight
Heat exchanger Finned tube
Fan unit Standard air flow H/M/L (m³/min)
Sound pressure level H/M/L (dB•A) 43/38/33 44/38/34 45/40/36 43/38/33 44/38/34 45/40/36
Sound power level H/M/L (dB•A) 58/53/48 59/53/49 60/55/51 58/53/48 59/53/49 60/55/51
Connecting pipe Drain port VP25
Outer dimension
Connecting pipe
Fan unit Standard air flow high (m³/min) 101 103 103 101 103 103
Sound pressure level Cooling/Heating (dB•A) 49/50 51/52 51/53 49/50 51/52 51/53
Sound power level Cooling/Heating (dB•A) 66/67 68/69 68/70 66/67 68/69 68/70
Indoor unit RAV-SM 1104UT-E 1404UT-E 1604UT-E 1104UT-E 1404UT-E 1604UT-E
Outdoor unit RAV-SP
Running current (A) 4.45 - 4.07 6.03 - 5.52 7.55 - 6.91 4.45 6.03 7.55
Power consumption (kW) 2.37 3.46 4.49 2.37 3.46 4.49
EER 4.22 3.61 3.12 4.22 3.61 3.12
Energy efficiency class A A B ———
Running current (A) 4.52 - 4.14 5.97 - 5.47 7.26 - 6.65 4.52 5.97 7.26
Power consumption (kW) 2.42 3.42 4.30 2.42 3.42 4.30
COP 4.63 4.09 3.72 4.63 4.09 3.72
Energy efficiency class A A A ———
Maximum current (A) 14.7 14.7 14.7 14.7 14.7 14.7
Main unit Zinc hot dipping steel plate
Ceiling panel (Sold separately)
Main unit Width (mm) 840 840 840 840 840 840
Ceiling panel (Sold separately)
Main unit (kg) 24 24 24 24 24 24
Ceiling panel (Sold separately) (kg) 4.2 4.2 4.2 4.2 4.2 4.2
Fan Turbo fan
Motor (W) 68 72 72 68 72 72
Standard length (m) 7.5 7.5 7.5 7.5 7.5 7.5
Min. length (m) 3 33333
Max. total length (m) 75 75 75 75 75 75
Over 30m 40g/m (31m to 75m)
Hight difference
Gas side (mm) 15.9 15.9 15.9 15.9 15.9 15.9
Liquid side (mm) 9.5 9.5 9.5 9.5 9.5 9.5
Fan Propeller fan
Motor (W) 100 + 100 100 + 100 100 + 100 100 + 100 100 + 100 100 + 100
Model RBC-U31PG(W,WS)-E , RBC-U31PGS(W,WS)-E
Panel color
Height (mm) 319 319 319 319 319 319
Depth (mm) 840 840 840 840 840 840
Height (mm) 30 30 30 30 30 30
Width (mm) 950 950 950 950 950 950
Depth (mm) 950 950 950 950 950 950
Outdoor lower (m) 30 30 30 30 30 30
Outdoor high (m) 30 30 30 30 30 30
1104AT8-E 1404AT8-E 1604AT8-E 1104AT7 1404AT7 1604AT7 1104AT8-TR 1404AT8-TR 1604AT8-TR
10.0 12.5 14.0 10.0 12.5 14.0
(2.6-12.0) (2.6-14.0) (2.6-16.0) (2.6-12.0) (2.6-14.0) (2.6-16.0)
11.2 14.0 16.0 11.2 14.0 16.0
(2.4-15.6) (2.4-18.0) (2.4-19.0) (2.4-15.6) (2.4-18.0) (2.4-19.0)
3 phase 4wired (3N-4pole) 3 phase 4wired (3N-4pole)
380V - 415V 50Hz 380V 60Hz
Indoor unit
W:Moon-white(2.5GY 9.0/0.5),
WS:Stripe-white(2.5GY 9.0/0.5,(Gray:8B 3/0.3))
33.5/24.0/19.5 35.0/24.0/20.5 35.5/25.0/21.0 33.5/24.0/19.5 35.0/24.0/20.5 35.5/25.0/21.0
Outdoor unit
– 13 –
: IEC standard
<Twin type>
Indoor unit 1 RAV-SM 564UT-E 804UT-E 804UT-E 564UT-E 804UT-E 804UT-E
Model
Cooling capacity (kW)
Heating capacity (kW)
Power supply
Cooling Power factor (%) 81 87 90 81 87 90
Electrical characteristics
Heating Power factor (%) 81 87 90 81 87 90
Appearance
Outer dimension
Total weight
Heat exchanger Finned tube
Fan unit Standard air flow H/M/L (m³/min)
Sound pressure level H/M/L (dB•A) 32/29/28 35/31/28 35/31/28 32/29/28 35/31/28 35/31/28
Sound power level H/M/L (dB•A) 47/44/43 50/46/43 50/46/43 47/44/43 50/46/43 50/46/43
Connecting pipe Drain port VP25
Outer dimension
Connecting pipe
Fan unit Standard air flow high (m³/min) 101 103 103 101 103 103
Sound pressure level Cooling/Heating (dB•A) 49/50 51/52 51/53 49/50 51/52 51/53
Sound power level Cooling/Heating (dB•A) 66/67 68/69 68/70 66/67 68/69 68/70
Indoor unit 2 RAV-SM 564UT-E 804UT-E 804UT-E 564UT-E 804UT-E 804UT-E
Outdoor unit RAV-SP
Running current (A) 4.45 - 4.07 6.03 - 5.52 7.55 - 6.91 4.45 6.03 7.55
Power consumption (kW) 2.37 3.46 4.49 2.37 3.46 4.49
EER 4.22 3.61 3.12 4.22 3.61 3.12
Energy efficiency class A A B ———
Running current (A) 4.52 - 4.14 5.97 - 5.47 7.26 - 6.65 4.52 5.97 7.26
Power consumption (kW) 2.42 3.42 4.30 2.42 3.42 4.30
COP 4.63 4.09 3.72 4.63 4.09 3.72
Energy efficiency class A A A ———
Maximum current (A) 14.5 14.5 14.5 14.5 14.5 14.5
Main unit Zinc hot dipping steel plate
Ceiling panel (Sold separately)
Main unit Width (mm) 840 840 840 840 840 840
Ceiling panel (Sold separately)
Main unit (kg) 20 20 20 20 20 20
Ceiling panel (Sold separately) (kg) 4.2 4.2 4.2 4.2 4.2 4.2
Fan Turbo fan
Motor (W) 14 20 20 14 20 20
Standard length (m) 7.5 7.5 7.5 7.5 7.5 7.5
Min. length (m) 3 33333
Max. total length (m) 50 50 50 50 50 50
Over 30m 40g/m (31m to 50m)
Hight difference
Gas side
Liquid side
Fan Propeller fan
Motor (W) 100 + 100 100 + 100 100 + 100 100 + 100 100 + 100 100 + 100
Model RBC-U31PG(W,WS)-E , RBC-U31PGS(W,WS)-E
Panel color
Height (mm) 256 256 256 256 256 256
Depth (mm) 840 840 840 840 840 840
Height (mm) 30 30 30 30 30 30
Width (mm) 950 950 950 950 950 950
Depth (mm) 950 950 950 950 950 950
Outdoor lower (m) 30 30 30 30 30 30
Outdoor high (m) 30 30 30 30 30 30
Main (mm) 15.9 15.9 15.9 15.9 15.9 15.9
Sub (mm) 12.7 15.9 15.9 12.7 15.9 15.9
Main (mm) 9.5 9.5 9.5 9.5 9.5 9.5
Sub (mm) 6.4 9.5 9.5 6.4 9.5 9.5
1104AT8-E 1404AT8-E 1604AT8-E 1104AT7 1404AT7 1604AT7 1104AT8-TR 1404AT8-TR 1604AT8-TR
10.0 12.5 14.0 10.0 12.5 14.0
(2.6-12.0) (2.6-14.0) (2.6-16.0) (2.6-12.0) (2.6-14.0) (2.6-16.0)
11.2 14.0 16.0 11.2 14.0 16.0
(2.4-15.6) (2.4-18.0) (2.4-19.0) (2.4-15.6) (2.4-18.0) (2.4-19.0)
3 phase 4wired (3N-4pole) 3 phase 4wired (3N-4pole)
380V - 415V 50Hz 380V 60Hz
Indoor unit
W:Moon-white(2.5GY 9.0/0.5),
WS:Stripe-white(2.5GY 9.0/0.5,(Gray:8B 3/0.3))
17.5/14.5/13.0 20.5/16.0/13.5 20.5/16.0/13.5 17.5/14.5/13.0 20.5/16.0/13.5 20.5/16.0/13.5
Outdoor unit
– 14 –
: IEC standard
<Triple type>
Indoor unit 1 RAV-SM 564UT-E 564UT-E
Model
Cooling capacity (kW) 14.0 (2.6-16.0) 14.0 (2.6-16.0)
Heating capacity (kW) 16.0 (2.4-19.0) 16.0 (2.4-19.0)
Power supply
Cooling Power factor (%) 90 90
Electrical characteristics
Heating Power factor (%) 90 90
Appearance
Outer dimension
Total weight
Heat exchanger Finned tube
Fan unit Standard air flow H/M/L (m³/min) 17.5/14.5/13.0 17.5/14.5/13.0
Sound pressure level H/M/L (dB•A) 32/29/28 32/29/28
Sound power level H/M/L (dB•A) 47/44/43 47/44/43
Connecting pipe Drain port VP25
Outer dimension
Connecting pipe
Fan unit Standard air flow high (m³/min) 103 103
Sound pressure level Cooling/Heating (dB•A) 51/53 51/53
Sound power level Cooling/Heating (dB•A) 68/70 68/70
Indoor unit 2 RAV-SM 564UT-E 564UT-E
Indoor unit 3 RAV-SM 564UT-E 564UT-E
Outdoor unit RAV-SP
Running current (A) 7.55 - 6.91 7.55
Power consumption (kW) 4.49 4.49
EER 3.12 3.12
Energy efficiency class B—
Running current (A) 7.26 - 6.65 7.26
Power consumption (kW) 4.30 4.30
COP 3.72 3.72
Energy efficiency class A—
Maximum current (A) 14.8 14.8
Indoor unit
Main unit Zinc hot dipping steel plate
Ceiling panel (Sold separately)
Main unit Width (mm) 840 840
Ceiling panel (Sold separately)
Main unit (kg) 20 20
Ceiling panel (Sold separately) (kg) 4.2 4.2
Fan Turbo fan
Motor (W) 14 14
Standard length (m) 7.5 7.5
Min. length (m) 3 3
Max. total length (m) 50 50
Over 30m 40g/m (31m to 50m)
Hight difference
Gas side
Liquid side
Fan Propeller fan
Motor (W) 100 + 100 100 + 100
Model RBC-U31PG(W,WS)-E , RBC-U31PGS(W,WS)-E
Panel color
Height (mm) 256 256
Depth (mm) 840 840
Height (mm) 30 30
Width (mm) 950 950
Depth (mm) 950 950
Outdoor unit
Outdoor lower (m) 30 30
Outdoor high (m) 30 30
Main (mm) 15.9 15.9
Sub (mm) 12.7 12.7
Main (mm) 9.5 9.5
Sub (mm) 6.4 6.4
1604AT8-E 1604AT7
1604AT8-TR
3 phase 4wired (3N-4pole) 3 phase 4wired (3N-4pole)
380V – 415V, 50Hz 380V, 60Hz
W:Moon-white(2.5GY 9.0/0.5),
WS:Stripe-white(2.5GY 9.0/0.5,(Gray:8B 3/0.3))
– 15 –
: IEC standard
1-1-2. Concealed Duct Type
<Single type>
Model
Cooling capacity (kW)
Heating capacity (kW)
Power supply
Cooling Power factor (%) 81 87 81 87
Electrical characteristics
Heating Power factor (%) 81 87 81 87
Appearance Main unit Zinc hot dipping steel plate
Outer dimension Main unit Width (mm) 1350 1350 1350 1350
Total weight Main unit (kg) 54 54 54 54
Heat exchanger Finned tube
Fan unit Standard
Sound pressure level H/M/L (dB•A) 42 / 39 / 36 44 / 41 / 38 42 / 39 / 36 44 / 41 / 38
Sound power level H/M/L (dB•A) 57 / 54 / 51 59 / 56 / 53 57 / 54 / 51 59 / 56 / 53
Connecting pipe Drain port VP25
Outer dimension
Connecting pipe
Fan unit Standard air flow high (m³/min) 101 103 101 103
Sound pressure level Cooling/Heating (dB•A) 49/50 51/52 49/50 51/52
Sound power level Cooling/Heating (dB•A) 66/67 68/69 66/67 68/69
Indoor unit RAV-SM 1102BT-E 1402BT-E 1102BT-E 1402BT-E
Outdoor unit RAV-SP
Running current (A) 5.51 - 5.05 6.73 - 6.16 5.51 6.73
Power consumption (kW) 2.94 3.86 2.94 3.86
EER 3.40 3.24 3.40 3.24
Energy efficiency class AA——
Running current (A) 5.18 - 4.74 6.20 - 5.68 5.18 6.20
Power consumption (kW) 2.77 3.55 2.77 3.55
COP 4.04 3.94 4.04 3.94
Energy efficiency class AA——
Maximum current (A) 15.6 16.0 15.6 16.0
Indoor unit
Height (mm) 320 320 320 320
Depth (mm) 800 800 800 800
Fan Centrifugal fan
Standard air flow H/M/L (m³/min) 27.0/23.0/18.9 33.0/28.0/23.1 27.0/23.0/18.9 33.0/28.0/23.1
Motor (W) 120 120 120 120
External static pressure
Standard length (m) 7.5 7.5 7.5 7.5
Min. length (m) 3 3 3 3
Max. total length (m) 75 75 75 75
Over 30m 40g/m (31m to 75m)
Hight difference
Gas side (mm) 15.9 15.9 15.9 15.9
Liquid side (mm) 9.5 9.5 9.5 9.5
Fan Propeller fan
Motor (W) 100 + 100 100 + 100 100 + 100 100 + 100
(at shipment)
Set up for tap exchange
Outdoor lower (m) 30 30 30 30
Outdoor high (m) 30 30 30 30
(Pa) 40
(Pa) 20/40/70/100 20/40/65/90 20/40/70/100 20/40/65/90
Outdoor unit
1104AT8-E 1404AT8-E 1104AT7 1404AT7
1104AT8-TR 1404AT8-TR
10.0 12.5 10.0 12.5
(2.6-12.0) (2.6-14.0) (2.6-12.0) (2.6-14.0)
11.2 14.0 11.2 14.0
(2.4-14.0) (2.4-18.0) (2.4-14.0) (2.4-18.0)
3 phase 4wired (3N-4pole) 3 phase 4wired (3N-4pole)
380V - 415V 50Hz 380V 60Hz
– 16 –
: IEC standard
<Twin type>
Indoor unit 1 RAV-SM 562BT-E 802BT-E 802BT-E 562BT-E 802BT-E 802BT-E
Model
Cooling capacity (kW)
Heating capacity (kW)
Power supply
Cooling Power factor (%) 81 87 90 81 87 90
Electrical characteristics
Heating Power factor (%) 81 87 90 81 87 90
Appearance Main unit Zinc hot dipping steel plate
Outer dimension Main unit Width (mm) 700 1000 1000 700 1000 1000
Total weight Main unit (kg) 30 39 39 30 39 39
Heat exchanger Finned tube
Fan unit Standard
Sound pressure level H/M/L (dB•A) 40/37/33 40/37/34 40/37/34 40/37/33 40/37/34 40/37/34
Sound power level H/M/L (dB•A) 55/52/48 55/52/49 55/52/49 55/52/48 55/52/49 55/52/49
Connecting pipe Drain port VP25
Outer dimension
Connecting pipe
Fan unit Standard air flow high (m³/min) 101 103 103 101 103 103
Sound pressure level Cooling/Heating (dB•A) 49/50 51/52 51/53 49/50 51/52 51/53
Sound power level Cooling/Heating (dB•A) 66/67 68/69 68/70 66/67 68/69 68/70
Indoor unit 2 RAV-SM 562BT-E 802BT-E 802BT-E 562BT-E 802BT-E 802BT-E
Outdoor unit RAV-SP
Running current (A) 5.51 - 5.05 6.73 - 6.16 8.61 - 7.88 5.51 6.73 8.61
Power consumption (kW) 2.94 3.86 5.12 2.94 3.86 5.12
EER 3.40 3.24 2.73 3.40 3.24 2.73
Energy efficiency class A A D ———
Running current (A) 5.18 - 4.74 6.20 - 5.68 7.77 - 7.11 5.18 6.20 7.77
Power consumption (kW) 2.77 3.55 4.60 2.77 3.55 4.60
COP 4.04 3.94 3.48 4.04 3.94 3.48
Energy efficiency class A A B ———
Maximum current (A) 16.4 16.4 16.4 16.4 16.4 16.4
Height (mm) 320 320 320 320 320 320
Depth (mm) 800 800 800 800 800 800
Fan Centrifugal fan
Standard air flow H/M/L (m³/min)
Motor (W) 120 120 120 120 120 120
External static pressure
Standard length (m) 7.5 7.5 7.5 7.5 7.5 7.5
Min. length (m) 3 33333
Max. total length (m) 50 50 50 50 50 50
Over 30m 40g/m (31m to 50m)
Hight difference
Gas side
Liquid side
Fan Propeller fan
Motor (W) 100 + 100 100 + 100 100 + 100 100 + 100 100 + 100 100 + 100
(at shipment)
Set up for tap exchange
Outdoor lower (m) 30 30 30 30 30 30
Outdoor high (m) 30 30 30 30 30 30
Main (mm) 15.9 15.9 15.9 15.9 15.9 15.9
Sub (mm) 12.7 15.9 15.9 12.7 15.9 15.9
Main (mm) 9.5 9.5 9.5 9.5 9.5 9.5
Sub (mm) 6.4 9.5 9.5 6.4 9.5 9.5
1104AT8-E 1404AT8-E 1604AT8-E 1104AT7 1404AT7 1604AT7 1104AT8-TR 1404AT8-TR 1604AT8-TR
10.0 12.5 14.0 10.0 12.5 14.0
(2.6-12.0) (2.6-14.0) (2.6-16.0) (2.6-12.0) (2.6-14.0) (2.6-16.0)
11.2 14.0 16.0 11.2 14.0 16.0
(2.4-14.0) (2.4-18.0) (2.4-19.0) (2.4-14.0) (2.4-18.0) (2.4-19.0)
3 phase 4wired (3N-4pole) 3 phase 4wired (3N-4pole)
380V - 415V 50Hz 380V 60Hz
Indoor unit
13.0/11.9/9.8 19.0/16.2/13.3 19.0/16.2/13.3 13.0/11.9/9.8 19.0/16.2/13.3 19.0/16.2/13.3
(Pa) 40
(Pa) 20/40/70/100
Outdoor unit
– 17 –
: IEC standard
<Triple type>
Indoor unit 1 RAV-SM 562BT-E 562BT-E
Model
Cooling capacity (kW) 14.0 (2.6-16.0) 14.0 (2.6-16.0)
Heating capacity (kW) 16.0 (2.4-19.0) 16.0 (2.4-19.0)
Power supply
Cooling Power factor (%) 90 90
Electrical characteristics
Heating Power factor (%) 90 90
Appearance Main unit Zinc hot dipping steel plate
Outer dimension Main unit Width (mm) 700 700
Total weight Main unit (kg) 30 30
Heat exchanger Finned tube
Fan unit Motor (W) 120 120
Sound pressure level H/M/L (dB•A) 40 / 37 / 33 40 / 37 / 33
Sound power level H/M/L (dB•A) 55 / 52 / 48 55 / 52 / 48
Connecting pipe Drain port VP25
Outer dimension
Connecting pipe
Fan unit Standard air flow high (m³/min) 103 103
Sound pressure level Cooling/Heating (dB•A) 51/53 51/53
Sound power level Cooling/Heating (dB•A) 68/70 68/70
Indoor unit 2 RAV-SM 562BT-E 562BT-E
Indoor unit 3 RAV-SM 562BT-E 562BT-E
Outdoor unit RAV-SP
Running current (A) 8.61 - 7.88 8.61
Power consumption (kW) 5.12 5.12
EER 2.73 2.73
Energy efficiency class D—
Running current (A) 7.77 – 7.11 7.77
Power consumption (kW) 4.60 4.60
COP 3.48 3.48
Energy efficiency class B—
Maximum current (A) 16.4 16.4
Indoor unit
Height (mm) 320 320
Depth (mm) 800 800
Fan Centrifugal fan
Standard air flow H/M/L (m³/min) 13.0 / 11.9 / 9.8 13.0 / 11.9 / 9.8
Standard External static pressure
Standard length (m) 7.5 7.5
Min. length (m) 3 3
Max. total length (m) 50 50
Over 30m 40g/m (31m to 50m)
Hight difference
Gas side
Liquid side
Fan Propeller fan
Motor (W) 100 + 100 100 + 100
(at shipment)
Set up for
tap exchange
Outdoor lower (m) 30 30
Outdoor high (m) 30 30
Main (mm) 15.9 15.9
Sub (mm) 12.7 12.7
Main (mm) 9.5 9.5
Sub (mm) 6.4 6.4
(Pa) 40
(Pa) 20/40/70/100
Outdoor unit
1604AT8-E 1604AT7
1604AT8-TR
3 phase 4wired (3N-4pole) 3 phase 4wired (3N-4pole)
380V - 415V 50Hz 380V 60Hz
– 18 –
: IEC standard
1-1-3. Under Ceiling Type
<Single type>
Model
Cooling capacity (kW)
Heating capacity (kW)
Power supply
Cooling Power factor (%) 81 87 81 87
Electrical characteristics
Heating Power factor (%) 81 87 81 87
Appearance Main unit Shine white
Outer dimension Main unit Width (mm) 1595 1595 1595 1595
Total weight Main unit (kg) 33 33 33 33
Heat exchanger Finned tube
Fan unit Standard air flow H/M/L (m³/min) 27.5/24.0/21.2 30.0/26.0/23.1 27.5/24.0/21.2 30.0/26.0/23.1
Sound pressure level H/M/L (dB•A) 41 / 38 / 35 43 / 40 / 37 41 / 38 / 35 43 / 40 / 37
Sound power level H/M/L (dB•A) 56 / 53 / 50 58 / 55 / 52 56 / 53 / 50 58 / 55 / 52
Connecting pipe Drain port VP20
Outer dimension
Connecting pipe
Fan unit Standard air flow high (m³/min) 101 103 101 103
Sound pressure level Cooling/Heating (dB•A) 49/50 51/52 49/50 51/52
Sound power level Cooling/Heating (dB•A) 66/67 68/69 66/67 68/69
Indoor unit RAV-SM 1102CT-E 1402CT-E 1102CT-E 1402CT-E
Outdoor unit RAV-SP
Running current (A) 5.23 - 4.79 6.67 - 6.11 5.23 6.67
Power consumption (kW) 2.79 3.83 2.79 3.83
EER (W/W) 3.58 3.26 3.58 3.26
Energy efficiency class AA——
Running current (A) 4.99 - 4.57 6.46 - 5.92 4.99 6.46
Power consumption (kW) 2.67 3.70 2.67 3.70
COP (W/W) 4.19 3.78 4.19 3.78
Energy efficiency class AA——
Maximum current (A) 15.2 15.2 15.2 15.2
Indoor unit
Height (mm) 210 210 210 210
Depth (mm) 680 680 680 680
Fan Centrifugal fan
Motor (W) 120 120 120 120
Outdoor unit
Standard length (m) 7.5 7.5 7.5 7.5
Min. length (m) 3 3 3 3
Max. total length (m) 75 75 75 75
Over 30m 40g/m (31m to 75m)
Hight difference
Gas side (mm) 15.9 15.9 15.9 15.9
Liquid side (mm) 9.5 9.5 9.5 9.5
Fan Propeller fan
Motor (W) 100 + 100 100 + 100 100 + 100 100 + 100
Outdoor lower (m) 30 30 30 30
Outdoor high (m) 30 30 30 30
1104AT8-E 1404AT8-E 1104AT7 1404AT7
1104AT8-TR 1404AT8-TR
10.0 12.5 10.0 12.5
(2.6-12.0) (2.6-14.0) (2.6-12.0) (2.6-14.0)
11.2 14.0 11.2 14.0
(2.4-14.0) (2.4-18.0) (2.4-14.0) (2.4-18.0)
3 phase 4wired (3N-4pole) 3 phase 4wired (3N-4pole)
380V - 415V 50Hz 380V 60Hz
– 19 –
: IEC standard
<Twin type>
Indoor unit 1 RAV-SM 562CT-E 802CT-E 802CT-E 562CT-E 802CT-E 802CT-E
Model
Cooling capacity (kW)
Heating capacity (kW)
Power supply
Cooling Power factor (%) 81 87 90 81 87 90
Electrical characteristics
Heating Power factor (%) 81 87 90 81 87 90
Appearance Main unit Shine white
Outer dimension Main unit Width (mm) 910 1180 1180 910 1180 1180
Total weight Main unit (kg) 21 25 25 21 25 25
Heat exchanger Finned tube
Fan unit Standard air flow H/M/L (m³/min)
Sound pressure level H/M/L (dB•A) 36/33/30 38/36/33 38/36/33 36/33/30 38/36/33 38/36/33
Sound power level H/M/L (dB•A) 51/48/45 53/51/48 53/51/48 51/48/45 53/51/48 53/51/48
Connecting pipe Drain port VP20
Outer dimension
Connecting pipe
Fan unit Standard air flow high (m³/min) 101 103 103 101 103 103
Sound pressure level Cooling/Heating (dB•A) 49/50 51/52 51/53 49/50 51/52 51/53
Sound power level Cooling/Heating (dB•A) 66/67 68/69 68/70 66/67 68/69 68/70
Indoor unit 2 RAV-SM 562CT-E 802CT-E 802CT-E 562CT-E 802CT-E 802CT-E
Outdoor unit RAV-SP
Running current (A) 5.23 - 4.79 6.67 - 6.11 8.39 - 7.68 5.23 6.67 8.39
Power consumption (kW) 2.79 3.83 4.99 2.79 3.83 4.99
EER 3.58 3.26 2.81 3.58 3.26 2.81
Energy efficiency class A A C ———
Running current (A) 4.99 - 4.57 6.46 - 5.92 7.77 -7.11 4.99 6.46 7.77
Power consumption (kW) 2.67 3.70 4.60 2.67 3.70 4.60
COP 4.19 3.78 3.48 4.19 3.78 3.48
Energy efficiency class A A B ———
Maximum current (A) 14.8 15.6 15.6 14.8 15.6 15.6
Height (mm) 210 210 210 210 210 210
Depth (mm) 680 680 680 680 680 680
Fan Centrifugal fan
Motor (W) 60 60 60 60 60 60
Standard length (m) 7.5 7.5 7.5 7.5 7.5 7.5
Min. length (m) 3 33333
Max. total length (m) 50 50 50 50 50 50
Over 30m 40g/m (31m to 50m)
Hight difference
Gas side
Liquid side
Fan Propeller fan
Motor (W) 100 + 100 100 + 100 100 + 100 100 + 100 100 + 100 100 + 100
Outdoor lower (m) 30 30 30 30 30 30
Outdoor high (m) 30 30 30 30 30 30
Main (mm) 15.9 15.9 15.9 15.9 15.9 15.9
Sub (mm) 12.7 15.9 15.9 12.7 15.9 15.9
Main (mm) 9.5 9.5 9.5 9.5 9.5 9.5
Sub (mm) 6.4 9.5 9.5 6.4 9.5 9.5
1104AT8-E 1404AT8-E 1604AT8-E 1104AT7 1404AT7 1604AT7 1104AT8-TR 1404AT8-TR 1604AT8-TR
10.0 12.5 14.0 10.0 12.5 14.0
(2.6-12.0) (2.6-14.0) (2.6-16.0) (2.6-12.0) (2.6-14.0) (2.6-16.0)
11.2 14.0 16.0 11.2 14.0 16.0
(2.4-14.0) (2.4-18.0) (2.4-19.0) (2.4-14.0) (2.4-18.0) (2.4-19.0)
3 phase 4wired (3N-4pole) 3 phase 4wired (3N-4pole)
380V - 415V 50Hz 380V 60Hz
Indoor unit
13.0/11.2/10.0 18.5/16.7/14.6 18.5/16.7/14.6 13.0/11.2/10.0 18.5/16.7/14.6 18.5/16.7/14.6
Outdoor unit
– 20 –
: IEC standard
<Triple type>
Indoor unit 1 RAV-SM 562CT-E 562CT-E
Model
Cooling capacity (kW) 14.0 (2.6-16.0) 14.0 (2.6-16.0)
Heating capacity (kW) 16.0 (2.4-19.0) 16.0 (2.4-19.0)
Power supply
Cooling Power factor (%) 90 90
Electrical characteristics
Heating Power factor (%) 90 90
Appearance Main unit Shine white
Outer dimension Main unit Width (mm) 910 910
Total weight Main unit (kg) 21 21
Heat exchanger Finned tube
Fan unit Standard air flow H/M/L (m³/min) 13.0 / 11.2 / 10.0 13.0 / 11.2 / 10.0
Sound pressure level H/M/L (dB•A) 36 / 33 / 30 36 / 33 / 30
Sound power level H/M/L (dB•A) 51 / 48 / 45 51 / 48 / 45
Connecting pipe Drain port VP20
Outer dimension
Connecting pipe
Fan unit Standard air flow high (m³/min) 103 103
Sound pressure level Cooling/Heating (dB•A) 51/53 51/53
Sound power level Cooling/Heating (dB•A) 68/70 68/70
Indoor unit 2 RAV-SM 562CT-E 562CT-E
Indoor unit 3 RAV-SM 562CT-E 562CT-E
Outdoor unit RAV-SP
Running current (A) 8.39 - 7.68 8.39
Power consumption (kW) 4.99 4.99
EER 2.81 2.81
Energy efficiency class C—
Running current (A) 7.77 -7.11 7.77
Power consumption (kW) 4.60 4.60
COP 3.48 3.48
Energy efficiency class B—
Maximum current (A) 15.3 15.3
Indoor unit
Height (mm) 210 210
Depth (mm) 680 680
Fan Centrifugal fan
Motor (W) 60 60
Outdoor unit
Standard length (m) 7.5 7.5
Min. length (m) 3 3
Max. total length (m) 50 50
Over 30m 40g/m (31m to 50m)
Hight difference
Gas side
Liquid side
Fan Propeller fan
Motor (W) 100 + 100 100 + 100
Outdoor lower (m) 30 30
Outdoor high (m) 30 30
Main (mm) 15.9 15.9
Sub (mm) 12.7 12.7
Main (mm) 9.5 9.5
Sub (mm) 6.4 6.4
1604AT8-E 1604AT7
1604AT8-TR
3 phase 4wired (3N-4pole) 3 phase 4wired (3N-4pole)
380V - 415V 50Hz 380V 60Hz
– 21 –
: IEC standard
1-1-4. High Wall Type
<Twin type>
Indoor unit 1 RAV-SM 562KRT-E 802KRT-E 802KRT-E 562KRT-E 802KRT-E 802KRT-E
Model
Cooling capacity (kW)
Heating capacity (kW)
Power supply
Cooling Power factor (%) 81 87 90 81 87 90
Electrical characteristics
Heating Power factor (%) 81 87 90 81 87 90
Appearance Main unit Pure white
Outer dimension Main unit Width (mm) 998 998 998 998 998 998
Total weight Main unit (kg) 12 12 12 12 12 12
Heat exchanger Finned tube
Fan unit Standard air flow H/M/L (m³/min)
Sound pressure level H/M/L (dB•A) 39/36/33 45/41/36 45/41/36 39/36/33 45/41/36 45/41/36
Sound power level H/M/L (dB•A) 54/51/48 60/56/51 60/56/51 54/51/48 60/56/51 60/56/51
Connecting pipe Drain port VP16
Outer dimension
Connecting pipe
Fan unit Standard air flow high (m³/min) 101 103 103 101 103 103
Sound pressure level Cooling/Heating (dB•A) 49/50 51/52 51/53 49/50 51/52 51/53
Sound power level Cooling/Heating (dB•A) 66/67 68/69 68/70 66/67 68/69 68/70
Indoor unit 2 RAV-SM 562KRT-E 802KRT-E 802KRT-E 562KRT-E 802KRT-E 802KRT-E
Outdoor unit RAV-SP
Running current (A) 5.48 - 5.02 6.97 - 6.38 8.57 - 7.85 5.48 6.97 8.57
Power consumption (kW) 2.92 4.00 5.10 2.92 4.00 5.10
EER 3.42 3.08 2.75 3.42 3.08 2.75
Energy efficiency class A B D ———
Running current (A) 5.33 - 4.88 6.78 - 6.20 8.24 - 7.54 5.33 6.78 8.24
Power consumption (kW) 2.85 3.88 4.88 2.85 3.88 4.88
COP 3.93 3.61 3.28 3.93 3.61 3.28
Energy efficiency class A A C ———
Maximum current (A) 14.5 14.8 14.8 14.5 14.8 14.8
Height (mm) 298 298 298 298 298 298
Depth (mm) 221 221 221 221 221 221
Fan Cross flow fan
Motor (W) 30 30 30 30 30 30
Standard length (m) 7.5 7.5 7.5 7.5 7.5 7.5
Min. length (m) 3 33333
Max. total length (m) 50 50 50 50 50 50
Over 30m 40g/m (31m to 50m)
Hight difference
Gas side
Liquid side
Fan Propeller fan
Motor (W) 100 + 100 100 + 100 100 + 100 100 + 100 100 + 100 100 + 100
Outdoor lower (m) 30 30 30 30 30 30
Outdoor high (m) 30 30 30 30 30 30
Main (mm) 15.9 15.9 15.9 15.9 15.9 15.9
Sub (mm) 12.7 15.9 15.9 12.7 15.9 15.9
Main (mm) 9.5 9.5 9.5 9.5 9.5 9.5
Sub (mm) 6.4 9.5 9.5 6.4 9.5 9.5
1104AT8-E 1404AT8-E 1604AT8-E 1104AT7 1404AT7 1604AT7 1104AT8-TR 1404AT8-TR 1604AT8-TR
10.0 12.3 14.0 10.0 12.3 14.0
(2.6-12.0) (2.6-13.5) (2.6-16.0) (2.6-12.0) (2.6-13.5) (2.6-16.0)
11.2 14.0 16.0 11.2 14.0 16.0
(2.4-14.0) (2.4-18.0) (2.4-19.0) (2.4-14.0) (2.4-18.0) (2.4-19.0)
3 phase 4wired (3N-4pole) 3 phase 4wired (3N-4pole)
380V - 415V 50Hz 380V 60Hz
Indoor unit
14.0/12.5/10.7 18.5/14.6/12.2 18.5/14.6/12.2 14.0/12.5/10.7 18.5/14.6/12.2 18.5/14.6/12.2
Outdoor unit
– 22 –
: IEC standard
<Triple type>
Indoor unit 1 RAV-SM 562KRT-E 562KRT-E
Model
Cooling capacity (kW) 14.0 (2.6-16.0) 14.0 (2.6-16.0)
Heating capacity (kW) 16.0 (2.4-19.0) 16.0 (2.4-19.0)
Power supply
Cooling Power factor (%) 90 90
Electrical characteristics
Heating Power factor (%) 90 90
Appearance Main unit Pure white
Outer dimension Main unit Width (mm) 998 998
Total weight Main unit (kg) 12 12
Heat exchanger Finned tube
Fan unit Standard air flow H/M/L (m³/min) 14.0 / 12.5 / 10.7 14.0 / 12.5 / 10.7
Sound pressure level H/M/L (dB•A) 39 / 36 / 33 39 / 36 / 33
Sound power level H/M/L (dB•A) 54 / 51 / 48 54 / 51 / 48
Connecting pipe Drain port VP16
Outer dimension
Connecting pipe
Fan unit Standard air flow high (m³/min) 103 103
Sound pressure level Cooling/Heating (dB•A) 51/53 51/53
Sound power level Cooling/Heating (dB•A) 68/70 68/70
Indoor unit 2 RAV-SM 562KRT-E 562KRT-E
Indoor unit 3 RAV-SM 562KRT-E 562KRT-E
Outdoor unit RAV-SP
Running current (A) 8.57 - 7.85 8.57
Power consumption (kW) 5.10 5.10
EER 2.75 2.75
Energy efficiency class D—
Running current (A) 8.24 - 7.54 8.24
Power consumption (kW) 4.88 4.88
COP 3.28 3.28
Energy efficiency class C—
Maximum current (A) 14.9 14.9
Indoor unit
Height (mm) 298 298
Depth (mm) 221 221
Fan Cross flow fan
Motor (W) 30 30
Outdoor unit
Standard length (m) 7.5 7.5
Min. length (m) 3 3
Max. total length (m) 50 50
Over 30m 40g/m (31m to 50m)
Hight difference
Gas side
Liquid side
Fan Propeller fan
Motor (W) 100 + 100 100 + 100
Outdoor lower (m) 30 30
Outdoor high (m) 30 30
Main (mm) 15.9 15.9
Sub (mm) 12.7 12.7
Main (mm) 9.5 9.5
Sub (mm) 6.4 6.4
1604AT8-E 1604AT7
1604AT8-TR
3 phase 4wired (3N-4pole) 3 phase 4wired (3N-4pole)
380V - 415V 50Hz 380V 60Hz
– 23 –
: IEC standard
1-1-5. Compact 4-Way Cassette (600 × 600) Type
<Twin type>
Indoor unit 1 RAV-SM 562MUT-E 562MUT-E
Model
Cooling capacity (kW) 10.0 (2.6-12.0) 10.0 (2.6-12.0)
Heating capacity (kW) 11.2 (2.4-14.0) 11.2 (2.4-14.0)
Power supply
Cooling Power factor (%) 81 81
Electrical characteristics
Heating Power factor (%) 81 81
Appearance
Outer dimension
Total weight
Heat exchanger Finned tube
Fan unit Standard air flow H/M/L (m³/min) 13.3 / 11.2 / 9.1 13.3 / 11.2 / 9.1
Sound pressure level H/M/L (dB•A) 43 / 39 / 34 43 / 39 / 34
Sound power level H/M/L (dB•A) 58 / 54 / 49 58 / 54 / 49
Connecting pipe Drain port VP16
Outer dimension
Connecting pipe
Fan unit Standard air flow high (m³/min) 101 101
Sound pressure level Cooling/Heating (dB•A) 49/50 49/50
Sound power level Cooling/Heating (dB•A) 66/67 66/67
Indoor unit 2 RAV-SM 562MUT-E 562MUT-E
Outdoor unit RAV-SP
Running current (A) 5.23 - 4.79 5.23
Power consumption (kW) 2.79 2.79
EER 3.58 3.58
Energy efficiency class A—
Running current (A) 4.99 - 4.57 4.99
Power consumption (kW) 2.67 2.67
COP 4.19 4.19
Energy efficiency class A—
Maximum current (A) 14.9 14.9
Indoor unit
Main unit Zinc hot dipping steel plate
Ceiling panel (Sold separately)
Main unit Width (mm) 575 575
Ceiling panel (Sold separately)
Main unit (kg) 16 16
Ceiling panel (Sold separately) (kg) 3 3
Fan Turbo fan
Motor (W) 60 60
Standard length (m) 7.5 7.5
Min. length (m) 3 3
Max. total length (m) 50 50
Over 30m 40g/m (31m to 50m)
Hight difference
Gas side
Liquid side
Fan Propeller fan
Motor (W) 100 + 100 100 + 100
Model RBC-UM11PG(W)-E
Panel color Moon-white ( Muncel 2.5GY 9.0/0.5 )
Height (mm) 268 268
Depth (mm) 575 575
Height (mm) 27 27
Width (mm) 700 700
Depth (mm) 700 700
Outdoor unit
Outdoor lower (m) 30 30
Outdoor high (m) 30 30
Main (mm) 15.9 15.9
Sub (mm) 12.7 12.7
Main (mm) 9.5 9.5
Sub (mm) 6.4 6.4
1104AT8-E 1104AT7
1104AT8-TR
3 phase 4wired (3N-4pole) 3 phase 4wired (3N-4pole)
380V - 415V 50Hz 380V 60Hz
– 24 –
: IEC standard
<Triple type>
Indoor unit 1 RAV-SM 562MUT-E 562MUT-E
Model
Cooling capacity (kW) 14.0 (2.6-16.0) 14.0 (2.6-16.0)
Heating capacity (kW) 16.0 (2.4-19.0) 16.0 (2.4-19.0)
Power supply
Cooling Power factor (%) 90 90
Electrical characteristics
Heating Power factor (%) 90 90
Appearance
Outer dimension
Total weight
Heat exchanger Finned tube
Fan unit Standard air flow H/M/L (m³/min) 13.3 / 11.2 / 9.1 13.3 / 11.2 / 9.1
Sound pressure level H/M/L (dB•A) 43 / 39 / 34 43 / 39 / 34
Sound power level H/M/L (dB•A) 58 / 54 / 49 58 / 54 / 49
Connecting pipe Drain port VP25
Outer dimension
Connecting pipe
Fan unit Standard air flow high (m³/min) 103 103
Sound pressure level Cooling/Heating (dB•A) 51/53 51/53
Sound power level Cooling/Heating (dB•A) 68/70 68/70
Indoor unit 2 RAV-SM 562MUT-E 562MUT-E
Indoor unit 3 RAV-SM 562MUT-E 562MUT-E
Outdoor unit RAV-SP
Running current (A) 8.39 - 7.68 8.39
Power consumption (kW) 4.99 4.99
EER 2.81 2.81
Energy efficiency class C—
Running current (A) 7.77 - 7.11 7.77
Power consumption (kW) 4.60 4.60
COP 3.48 3.48
Energy efficiency class B—
Maximum current (A) 15.4 15.4
Indoor unit
Main unit Zinc hot dipping steel plate
Ceiling panel (Sold separately)
Main unit Width (mm) 575 575
Ceiling panel (Sold separately)
Main unit (kg) 16 16
Ceiling panel (Sold separately) (kg) 3 3
Fan Turbo fan
Motor (W) 60 60
Standard length (m) 7.5 7.5
Min. length (m) 3 3
Max. total length (m) 50 50
Over 30m 40g/m (31m to 50m)
Hight difference
Gas side
Liquid side
Fan Propeller fan
Motor (W) 100 + 100 100 + 100
Model RBC-UM11PG(W)-E
Panel color Moon-white ( Muncel 2.5GY 9.0/0.5 )
Height (mm) 268 268
Depth (mm) 575 575
Height (mm) 27 27
Width (mm) 700 700
Depth (mm) 700 700
Outdoor unit
Outdoor lower (m) 30 30
Outdoor high (m) 30 30
Main (mm) 15.9 15.9
Sub (mm) 12.7 12.7
Main (mm) 9.5 9.5
Sub (mm) 6.4 6.4
1604AT8-E 1604AT7
1604AT8-TR
3 phase 4wired (3N-4pole) 3 phase 4wired (3N-4pole)
380V - 415V 50Hz 380V 60Hz
– 25 –
: IEC standard
1-1-6. Slim Duct Type
<Twin type>
Indoor unit 1 RAV-SM 564SDT-E 564SDT-E
Model
Cooling capacity (kW) 10.0 (2.6-12.0) 10.0 (2.6-12.0)
Heating capacity (kW) 11.2 (2.4-14.0) 11.2 (2.4-14.0)
Power supply
Cooling Power factor (%) 81 81
Electrical characteristics
Heating Power factor (%) 81 81
Appearance Main unit Zinc hot dipping steel plate
Outer dimension Main unit Width (mm) 845 845
Total weight Main unit (kg) 22 22
Heat exchanger Finned tube
Fan unit Standard air flow H/M/L (m³/min) 13.0 / 11.3 / 9.7 13.0 / 11.3 / 9.7
Sound pressure level
Sound power level
Connecting pipe Drain port VP25
Outer dimension
Connecting pipe
Fan unit Standard air flow high (m³/min) 101 101
Sound pressure level Cooling/Heating (dB•A) 49/50 49/50
Sound power level Cooling/Heating (dB•A) 66/67 66/67
Indoor unit 2 RAV-SM 564SDT-E 564SDT-E
Outdoor unit RAV-SP
Running current (A) 5.23 - 4.79 5.23
Power consumption (kW) 2.79 2.79
EER 3.58 3.58
Energy efficiency class A—
Running current (A) 4.99 - 4.57 4.99
Power consumption (kW) 2.67 2.67
COP 4.19 4.19
Energy efficiency class A—
Maximum current (A) 15.1 15.1
Indoor unit
Height (mm) 210 210
Depth (mm) 645 645
Fan Centrifugal fan
Motor (W) 60 60
Under air inlet H/M/L (dB•A) 45 / 40 / 36 45 / 40 / 36
Back air inlet H/M/L (dB•A) 33 / 31 / 28 33 / 31 / 28
Under air inlet H/M/L (dB•A) 60 / 55 / 51 60 / 55 / 51
Back air inlet H/M/L (dB•A) 48 / 46 / 43 48 / 46 / 43
Outdoor unit
Standard length (m) 7.5 7.5
Min. length (m) 3 3
Max. total length (m) 50 50
Over 30m 40g/m (31m to 50m)
Hight difference
Gas side
Liquid side
Fan Propeller fan
Motor (W) 100 + 100 100 + 100
Outdoor lower (m) 30 30
Outdoor high (m) 30 30
Main (mm) 15.9 15.9
Sub (mm) 12.7 12.7
Main (mm) 9.5 9.5
Sub (mm) 6.4 6.4
1104AT8-E 1104AT7
1104AT8-TR
3 phase 4wired (3N-4pole) 3 phase 4wired (3N-4pole)
380V - 415V 50Hz 380V 60Hz
– 26 –
: IEC standard
<Triple type>
Indoor unit 1 RAV-SM 564SDT-E 564SDT-E
Model
Cooling capacity (kW) 14.0 (2.6-16.0) 14.0 (2.6-16.0)
Heating capacity (kW) 16.0 (2.4-19.0) 16.0 (2.4-19.0)
Power supply
Cooling Power factor (%) 90 90
Electrical characteristics
Heating Power factor (%) 90 90
Appearance Main unit Zinc hot dipping steel plate
Outer dimension Main unit Width (mm) 845 845
Total weight Main unit (kg) 22 22
Heat exchanger Finned tube
Fan unit Standard air flow H/M/L (m³/min) 13.0 / 11.3 / 9.7 13.0 / 11.3 / 9.7
Sound pressure level
Sound power level
Connecting pipe Drain port VP25
Outer dimension
Connecting pipe
Fan unit Standard air flow high (m³/min) 103 103
Sound pressure level Cooling/Heating (dB•A) 51/53 51/53
Sound power level Cooling/Heating (dB•A) 68/70 68/70
Indoor unit 2 RAV-SM 564SDT-E 564SDT-E
Indoor unit 3 RAV-SM 564SDT-E 564SDT-E
Outdoor unit RAV-SP
Running current (A) 8.39 - 7.68 8.39
Power consumption (kW) 4.99 4.99
EER 2.81 2.81
Energy efficiency class C—
Running current (A) 7.77 - 7.11 7.77
Power consumption (kW) 4.60 4.60
COP 3.48 3.48
Energy efficiency class B—
Maximum current (A) 15.8 15.8
Indoor unit
Height (mm) 210 210
Depth (mm) 645 645
Fan Centrifugal fan
Motor (W) 60 60
Under air inlet H/M/L (dB•A) 45 / 40 / 36 45 / 40 / 36
Back air inlet H/M/L (dB•A) 33 / 31 / 28 33 / 31 / 28
Under air inlet H/M/L (dB•A) 60 / 55 / 51 60 / 55 / 51
Back air inlet H/M/L (dB•A) 48 / 46 / 43 48 / 46 / 43
Outdoor unit
Standard length (m) 7.5 7.5
Min. length (m) 3 3
Max. total length (m) 50 50
Over 30m 40g/m (31m to 50m)
Hight difference
Gas side
Liquid side
Fan Propeller fan
Motor (W) 100 + 100 100 + 100
Outdoor lower (m) 30 30
Outdoor high (m) 30 30
Main (mm) 15.9 15.9
Sub (mm) 12.7 12.7
Main (mm) 9.5 9.5
Sub (mm) 6.4 6.4
1604AT8-E 1604AT7
1604AT8-TR
3 phase 4wired (3N-4pole) 3 phase 4wired (3N-4pole)
380V - 415V 50Hz 380V 60Hz
– 27 –
: IEC standard
1-1-7. High Static Duct Type
<Single type>
Model
Cooling capacity (kW) 13.0 (3.3-14.1) 14.3 (3.3-16.0)
Heating capacity (kW) 14.0 (4.2-18.0) 16.0 (4.2-19.0)
Power supply 3 phase 4wired (3N-4pole) 415V 50Hz
Cooling Power factor (%) 87 90
Electrical characteristics
Heating Power factor (%) 87 90
Appearance Main unit Zinc hot dipping steel plate
Outer dimension Main unit Width (mm) 1050
Total weight Main unit (kg) 57
Heat exchanger Finned tube
Fan unit
Sound pressure level H (dB•A) 49 50
Sound power level H (dB•A) 64 65
Connecting pipe Drain port VP25
Outer dimension
Connecting pipe
Fan unit Standard air flow high (m³/min) 103 103
Sound pressure level Cooling/Heating (dB•A) 51/52 51/53
Sound power level Cooling/Heating (dB•A) 68/69 68/70
Indoor unit RAV-SM 1403DT-A 1603DT-A
Outdoor unit RAV-SP 1404AT8-E 1604AT8-E
Running current (A) 6.89 7.71
Power consumption (kW) 4.32 5.01
EER 3.01 2.85
Energy efficiency class ( B ) ( C )
Running current (A) 5.48 6.85
Power consumption (kW) 3.43 4.43
COP 4.08 3.61
Energy efficiency class ( A ) ( A )
Maximum current (A) 16.3 16.3
Indoor unit
Height (mm) 380
Depth (mm) 600
Fan Centrifugal fan
Standard air flow
Motor (W) 600
External static pressure
Standard length (m) 7.5 7.5
Min. length (m) 3 3
Max. total length (m) 75 75
Over 30m 40g/m (31m to 75m)
Hight difference
Gas side (mm) 15.9 15.9
Liquid side (mm) 9.5 9.5
Fan Propeller fan
Motor (W) 100 + 100 100 + 100
at 100pa/HH tap
Standard
(at HH tap)
Range
at HH tap
Outdoor lower (m) 30 30
Outdoor high (m) 30 30
(m³/min)
(Pa) 100
(Pa) 50 – 250
Outdoor unit
55.0 58.0
– 28 –
: IEC standard
1-2. Outdoor Unit
Model Outdoor unit
Power supply
Type
Compressor Motor (kW)
Pole
Refirigerant charged (kg)
Refirigerant control
Standard length (m)
Minmum length (m)
Max. total length (m)
Pipe
Outer dimension
Additional refrigerant chrge under long piping connection
Height difference
Height (mm)
Width (mm)
Depth (mm)
Outdoor lower (m)
Outdoor higher (m)
RAV-SP RAV-SP
1104AT8-E 1404AT8-E 1604AT8-E 1104AT7 1404AT7 1604AT7
1104AT8-TR 1404AT8-TR 1604AT8-TR
3 phase 4wired (3N-4pole) 3 phase 4wired (3N-4pole)
380V – 415V 50Hz 380V 60Hz
(Power exclusive to outdoor required.) (Power exclusive to outdoor required.)
Hermetic compressor
3.75 3.75 3.75 3.75 3.75 3.75
444444
3.1 3.1 3.1 3.1 3.1 3.1
Pulse motor valve
7.5 7.5 7.5 7.5 7.5 7.5
333333
75 75 75 75 75 75
40g/m (31m to 75m)
30 30 30 30 30 30
30 30 30 30 30 30
1340 1340 1340 1340 1340 1340
900 900 900 900 900 900
320 320 320 320 320 320
Appearance
Total weight (kg)
Heat exchanger
Connecting pipe
Fan
Fan unit Standard air flow (m³/min)
Motor (W)
Sound pressure level
Sound power level
Outside air temperature, cooling (°C)
Outside air temperature, Heating (°C)
Gas side (mm)
Liquid side (mm)
Cooling/Heating
(dB•A)
Cooling/Heating
(dB•A)
Silky shade (Muncel 1Y8.5-0.5)
95 95 95 95 95 95
Finned tube
15.9 15.9 15.9 15.9 15.9 15.9
9.5 9.5 9.5 9.5 9.5 9.5
Propeller fan
101 103 103 101 103 103
100 + 100 100 + 100 100 + 100 100 + 100 100 + 100 100 + 100
49/50 51/52 51/53 49/50 51/52 51/53
66/67 68/69 68/70 66/67 68/69 68/70
46 to –15°C
15 to –20°C
– 29 –
1-3. Operation Characteristic Curve
SP140
SP110
SP160
SP160
SP140
SP110
• Operation characteristic curve, 50Hz <Super Digital Inverter>
RAV-SP1104AT8 (Z) (ZG)-E, -TR RAV-SP1404AT8 (Z) (ZG)-E, -TR RAV-SP1604AT8 (Z) (ZG)-E, -TR
<Cooling> <Heating>
10
9
8
7
SP160
SP160
6
SP140
SP110
SP110
SP140
5
Current (A)
4
3
2
1
0
0 1020304050607080
• Conditions Indoor : DB27˚C/WB19˚C Outdoor : DB35˚C Air flow : High Pipe length : 7.5m 400V, 50Hz (3 phase)
15
14
13
12
11
10
9
8
7
Current (A)
6
5
4
3
2
1
0
0 102030405060708090
Compressor speed (rps)
• Operation characteristic curve, 60Hz <Super Digital Inverter>
RAV-SP1104AT7 (Z) (ZG) RAV-SP1404AT7 (Z) (ZG) RAV-SP1604AT7 (Z) (ZG)
<Cooling> <Heating>
10
SP160
SP160
SP110
SP110
9
8
7
6
5
Current (A)
4
3
2
1
0
0 10203040506070
• Conditions Indoor : DB27˚C/WB19˚C Outdoor : DB35˚C Air flow : High Pipe length : 7.5m 380V, 60Hz (3 phase)
SP140
SP140
80
15
14
13
12
11
10
9
8
7
Current (A)
6
5
4
3
2
1
0
0 102030405060708090
Compressor speed (rps)
• Conditions Indoor : DB20˚C Outdoor : DB7˚C/WB6˚C Air flow : High Pipe length : 7.5m 400V, 50Hz (3 phase)
Compressor speed (rps)
• Conditions Indoor : DB20˚C Outdoor : DB7˚C/WB6˚C Air flow : High Pipe length : 7.5m 380V, 60Hz (3 phase)
Compressor speed (rps)
100 110
100 110
– 30 –