Toshiba RAV-SM2804AT8ZG-E, RAV-SM2804AT7ZG, RAV-SM2804AT8-E, RAV-SM2804AT7Z, RAV-SM2244AT8Z-E User Manual

...
SERVICE MANUAL
AIR-CONDITIONER
SPLIT TYPE
FILE NO. A09-004
OUTDOOR UNIT
<DIGITAL INVERTER>
RAV-SM2244AT8-E RAV-SM2804AT8-E RAV-SM2244AT8Z-E RAV-SM2804AT8Z-E RAV-SM2244AT8ZG-E RAV-SM2804AT8ZG-E
RAV-SM2244AT7 RAV-SM2804AT7 RAV-SM2244AT7Z RAV-SM2804AT7Z RAV-SM2244AT7ZG RAV-SM2804AT7ZG
R410A
PRINTED IN JAPAN, Jun, 2009 ToMo
Adoption of New Refrigerant
This Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the conventional refrigerant R22 in order to prevent destruction of the ozone layer.
WARNING
Cleaning of the air filter and other parts of the air filter involves dangerous work in high places, so be sure to have a service person do it. Do not attempt it yourself.
The cleaning diagram for the air filter is there for the service person, and not for the customer.
CONTENTS
SAFETY CAUTION ............................................................................................ 4
1. SPECIFICATIONS .................................................................................... 11
1-1. Indoor Unit......................................................................................................... 11
1-2. Outdoor Unit...................................................................................................... 24
1-3. Operation Characteristic Curve....................................................................... 25
2. CONSTRUCTION VIEWS (EXTERNAL VIEWS)....................................... 27
2-1. Outdoor Unit...................................................................................................... 27
3. OUTDOOR UNIT REFRIGERANTING CYCLE DIAGRAM ...................... 31
4. WIRING DIAGRAM................................................................................... 33
4-1. Outdoor Unit...................................................................................................... 33
5. SPECIFICATIONS OF ELECTRICAL PARTS .......................................... 34
5-1.Outdoor Unit ......................................................................................................... 34
6. REFRIGERANT R410A ............................................................................ 35
6-1. Safety During Installation/Servicing ............................................................... 35
6-2. Refrigerant Piping Installation....................................................................... 35
6-3. Tools .................................................................................................................. 39
6-4. Recharging of Refrigerant................................................................................ 39
6-5. Brazing of Pipes................................................................................................ 40
6-6. Instructions for Re-use Piping of R22 or R407C ............................................ 42
– 2 –
7. CIRCUIT CONFIGURATION AND CONTROL SPECIFICATIONS ........... 45
7-1. Outdoor Unit Control........................................................................................ 45
7-2. Outline of Main Controls .................................................................................. 49
8. TROUBLESHOOTING .............................................................................. 55
8-1. Summary of Troubleshooting........................................................................... 55
8-2. Troubleshooting................................................................................................ 57
9. SETUP AT LOCAL SITE AND OTHERS .................................................. 80
9-1. Calling of Error History .................................................................................... 80
9-2. Group Control Operation ................................................................................. 80
9-3. Outdoor Unit...................................................................................................... 82
10. ADDRESS SETUP.................................................................................... 89
10-1. Address Setup Procedure................................................................................ 89
10-2. Address Setup & Group Control...................................................................... 90
10-3. Remote Controller Wiring................................................................................. 93
10-4. Address Setup (Manual setting from remote controller)............................... 94
10-5. Confirmation of Indoor Unit No. Position ....................................................... 95
11. INSTALLATION MANUAL ........................................................................ 97
12. REPLACEMENT OF
THE SERVICE P.C. BOARD (4316V392) MCC-1599 ............................. 110
13. HOW TO EXCHANGE COMPRESSOR .................................................. 111
13-1. Exchanging Procedure of Compressor (Outline)......................................... 111
13-2. Exchange of Compressor .............................................................................. 111
14. DETACHMENTS ..................................................................................... 112
14-1. Outdoor Unit.................................................................................................... 112
15. EXPLODED VIEWS AND PARTS LIST .................................................. 124
15-1. Outdoor Unit.................................................................................................... 124
15-2. Inverter Assembly........................................................................................... 126
15-3. Outdoor Unit.................................................................................................... 128
15-4. Inverter Assembly........................................................................................... 130
3
SAFETY CAUTION
The important contents concerned to the saf ety are described on the product itself and on this Service Manual. Please read this Service Manual after understanding the described items thoroughly in the following contents
(Indications/Illustrated marks), and keep them.
[Explanation of indications]
Indication
DANGER
WARNING
CAUTION
Property damage : Enlarged damage concerned to property, furniture, and domestic animal/pet
Indicates contents assumed that an imminent danger causing a death or serious injury of the repair engineers and the third parties when an incorrect work has been executed.
Indicates possibilities assumed that a danger causing a death or serious injury of the repair engineers, the third parties, and the users due to troubles of the product after work when an incorrect work has been executed.
Indicates contents assumed that an injury or proper ty damage (∗) may be caused on the repair engineers, the third parties, and the users due to troubles of the product after work when an incorrect work has been executed.
Explanation
[Explanation of illustrated marks]
Mark Explanation
Indicates prohibited items (Forbidden items to do) The sentences near an illustrated mark describe the concrete prohibited contents.
Indicates mandatory items (Compulsory items to do) The sentences near an illustrated mark describe the concrete mandatory contents.
Indicates cautions (Including danger/warning) The sentences or illustration near or in an illustrated mark describe the concrete cautious contents.
[Confirmation of warning label on the main unit]
Confirm that labels are indicated on the specified positions (Refer to the Parts disassembly diagram (Outdoor unit).)
If removing the label during parts replace, stick it as the original.
DANGER
Turn “OFF” the breaker before removing the front panel and cabinet, otherwise an electric shock is caused by high voltage resulted in a death or injury.
During operation, a high voltage with 400V or higher of circuit () at secondary circuit of the high-voltage transformer is applied.
If touching a high voltage with the naked hands or body, an electric shock is caused even if using an
Turn off breaker.
Execute discharge
between terminals.
Prohibition
electric insulator.
• Attach a plate indicating “WORKING” or others on the breaker so that you don’t accidentally turn on the breaker during work.
: For details, refer to the electric wiring diagram.
When removing the front panel or cabinet, execute short-circuit and discharge between high-voltage capacitor terminals.
If discharge is not executed, an electric shock is caused by high voltage resulted in a death or injury. After turning off the breaker, high voltage also keeps to apply to the high-voltage capacitor.
Do not turn on the breaker under condition that the front panel and cabinet are removed.
An electric shock is caused by high voltage resulted in a death or injury.
– 4 –
Check earth wires.
Prohibition of modification.
Use specified parts.
Do not bring a child
close to the equipment.
Insulating measures
No fire
WARNING
Before troubleshooting or repair work, check the earth wire is connected to the earth terminals of the main unit, otherwise an electric shock is caused when a leak occurs.
If the earth wire is not correctly connected, contact an electric engineer for rework.
Do not modify the products.
Do not also disassemble or modify the parts. It may cause a fire, electric shock or injury.
For spare parts, use those specified (
If unspecified parts are used, a fire or electric shock may be caused.
: For details, refer to the parts list.
Before troubleshooting or repair work, do not bring a third party (a child, etc.) except the repair engineers close to the equipment.
It causes an injury with tools or disassembled parts. Please inform the users so that the third party (a child, etc.) does not approach the equipment.
Connect the cut-off lead wires with crimp contact, etc, put the closed end side upward and then apply a water-cut method, otherwise a leak or production of fire is caused at the users’ side.
When repairing the refrigerating cycle, take the following measures.
1) Be attentive to fire around the cycle. When using a gas stove, etc, be sure to put out fire before work; otherwise the oil mixed with refrigerant gas may catch fire.
2) Do not use a welder in the closed room. When using it without ventilation, carbon monoxide poisoning may be caused.
3) Do not bring inflammables close to the refrigerant cycle, otherwise fire of the welder may catch the inflammables.
∗∗
∗).
∗∗
Refrigerant
Check the used refrigerant name and use tools and materials of the parts which match with it.
For the products which use R410A refrigerant, the refrigerant name is indicated at a position on the outdoor unit where is easy to see. To prevent miss-charging, the route of the service por t is changed from one of the former R22.
For an air conditioner which uses R410A, never use other refrigerant than R410A. For an air conditioner which uses other refrigerant (R22, etc.), never use R410A.
If different types of refrigerant are mixed, abnormal high pressure generates in the refrigerating cycle and an injury due to breakage may be caused.
Do not charge refrigerant additionally.
If charging refrigerant additionally when refrigerant gas leaks, the refrigerant composition in the refrigerating cycle changes resulted in change of air conditioner characteristics or refrigerant over the specified standard amount is charged and an abnormal high pressure is applied to the inside of the refrigerating cycle resulted in cause of breakage or injury. Therefore if the refrigerant gas leaks, recover the refrigerant in the air conditioner, execute vacuuming, and then newly recharge the specified amount of liquid refrigerant. In this time, never charge the refrigerant over the specified amount.
When recharging the refrigerant in the refrigerating cycle, do not mix the refrigerant or air other than R410A into the specified refrigerant.
If air or others is mixed with the refrigerant, abnormal high pressure generates in the refrigerating cycle resulted in cause of injury due to breakage.
After installation work, check the refrigerant gas does not leak.
If the refrigerant gas leaks in the room, poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.
Never recover the refrigerant into the outdoor unit.
When the equipment is moved or repaired, be sure to recover the refrigerant with recovering device. The refrigerant cannot be recovered in the outdoor unit; otherwise a serious accident such as breakage or injury is caused.
Assembly/Cabling
After repair work, surely assemble the disassembled parts, and connect and lead the removed wires as before. Perform the work so that the cabinet or panel does not catch the inner wires.
If incorrect assembly or incorrect wire connection was done, a disaster such as a leak or fire is caused at user’s side.
– 5 –
Insulator check
Ventilation
Be attentive to
electric shock
Compulsion
WARNING
After the work has finished, be sure to use an insulation tester set (500V Megger) to check the resistance is 2MΩ or more between the charge section and the non-charge metal section (Earth position).
If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s side.
When the refrigerant gas leaks during work, execute ventilation.
If the refrigerant gas touches to a fire, poisonous gas generates. A case of leakage of the refrigerant and the closed room full with gas is dangerous because a shortage of oxygen occurs. Be sure to execute ventilation.
When checking the circuit inevitably under condition of the power-ON, use rubber gloves and others not to touch to the charging section.
If touching to the charging section, an electric shock may be caused.
When the refrigerant gas leaks, find up the leaked position and repair it surely.
If the leaked position cannot be found up and the repair work is interrupted, pump-down and tighten the service valve, otherwise the refrigerant gas may leak into the room. The poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.
When installing equipment which includes a large amount of charged refrigerant such as a multi air conditioner in a sub-room, it is necessary that the density does not the limit even if the refrigerant leaks.
If the refrigerant leaks and exceeds the limit density, an accident of shortage of oxygen is caused.
For the installation/moving/reinstallation work, follow to the Installation Manual.
If an incorrect installation is done, a trouble of the refrigerating cycle, water leak, electric shock or fire is caused.
Check after repair
Check after reinstallation
Put on gloves
Cooling check
After repair work has finished, check there is no trouble.
If check is not executed, a fire, electric shock or injury may be caused. For a check, turn off the power breaker.
After repair work (installation of front panel and cabinet) has finished, execute a test run to check there is no generation of smoke or abnormal sound.
If check is not executed, a fire or an electric shock is caused. Before test run, install the front panel and cabinet.
Check the following items after reinstallation.
1) The earth wire is correctly connected.
2) The power cord is not caught in the product.
3) There is no inclination or unsteadiness and the installation is stable. If check is not executed, a fire, an electric shock or an injury is caused.
CAUTION
Be sure to put on the gloves () and a long sleeved shirt: otherwise an injury may be caused with the parts, etc.
() Heavy gloves such as work gloves
When the power was turned on, start to work after the equipment has been sufficiently cooled.
As temperature of the compressor pipes and others became high due to cooling/heating operation, a burn may be caused.
– 6 –
New Refrigerant (R410A)
This air conditioner adopts a new HFC type refrigerant (R410A) which does not deplete the ozone layer.
1. Safety Caution Concerned to New Refrigerant
The pressure of R410A is high 1.6 times of that of the former refrigerant (R22). Accompanied with change of refrigerant, the refrigerating oil has been also changed. Therefore, be sure that water, dust, the former refr igerant or the former refrigerating oil is not mixed into the
refrigerating cycle of the air conditioner with new refrigerant during installation work or service work. If an incorrect work or incorrect service is performed, there is a possibility to cause a serious accident. Use the tools and materials exclusive to R410A to purpose a safe work.
2. Cautions on Installation/Service
1) Do not mix the other refrigerant or refrigerating oil. For the tools exclusive to R410A, shapes of all the joints including the service port differ from those of
the former refrigerant in order to prevent mixture of them.
2) As the use pressure of the new refrigerant is high, use material thickness of the pipe and tools which are specified for R410A.
3) In the installation time, use clean pipe materials and work with great attention so that water and others do not mix in because pipes are affected by impurities such as water, oxide scales, oil, etc.
Use the clean pipes. Be sure to brazing with flowing nitrogen gas. (Never use gas other than nitrogen gas.)
4) For the earth protection, use a vacuum pump for air purge.
5) R410A refr igerant is azeotropic mixture type refrigerant. Therefore use liquid type to charge the refrigerant. (If using gas for charging, composition of the
refrigerant changes and then characteristics of the air conditioner change.)
3. Pipe Materials
For the refrigerant pipes, copper pipe and joints are mainly used. It is necessary to select the most appropriate pipes to conform to the standard. Use clean material in which impurities adhere inside of pipe or joint to a minimum.
1) Copper pipe
<Piping>
The pipe thickness, flare finishing size, flare nut and others differ according to a refrigerant type. When using a long copper pipe for R410A, it is recommended to select “Copper or copper-base pipe without
seam” and one with bonded oil amount 40mg/10m or less. Also do not use crushed, deformed, discolored (especially inside) pipes.
(Impurities cause clogging of expansion valves and capillary tubes.)
<Flare nut>
Use the flare nuts which are attached to the air conditioner unit.
2) Joint
The flare joint and socket joint are used for joints of the copper pipe. The joints are rarely used for installation of the air conditioner. How ever clear impurities when using them.
– 7 –
4. Tools
1. Required T ools for R410A Mixing of different types of oil may cause a trouble such as generation of sludge, clogging of capillary,
etc. Accordingly, the tools to be used are classified into the following three types.
1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))
2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)
3) Tools commonly used for R410A and for conventional refrigerant (R22) The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
No.
Flare tool
Q
Copper pipe gauge for
R
adjusting projection margin Torque wrench
S
Gauge manifold
T
Charge hose
U
V acuum pump adapter
V
Electronic balance for
W
refrigerant charging Refrigerant cylinder
X
Leakage detector
Y
Used tool
Usage
Pipe flaring Flaring by conventional
flare tool Tightening of flare nut
Evacuating, refrigerant charge, run check, etc.
Vacuum evacuating
Refrigerant charge
Refrigerant charge Gas leakage check
air conditioner installation
R410A
Existence of Whether conven-
new equipment tional equipment
for R410A can be used
Yes (Note)
Yes (Note)
Yes No
Yes No
Yes No
Yes Yes
Yes No Yes No
Conventional air
conditioner installation
Whether conventional
equipment can be used
Yes
(Note)
No
No
Yes
Yes
No
Yes
(Note) When flaring is carr ied out for R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which ser ve also for R22 are necessary as the general tools.
1) Vacuum pump. Use vacuum pump by attaching vacuum pump adapter.
2) Torque wrench 8) Spanner or Monkey wrench
3) Pipe cutter 9) Hole core drill
4) Reamer 10) Hexagon wrench (Opposite side 4mm)
5) Pipe bender 11) Tape measure
6) Level vial 12) Metal saw
7) Screwdriver (+, –)
Also prepare the following equipments for other installation method and run check.
1) Clamp meter 3) Insulation resistance tester (Megger)
2) Thermometer 4) Electroscope
– 8 –
n Combination Pattern (Indoor Unit / Outdoor Unit)
<RAV-SM2244AT series> Simultaneous twin
4-way air discharge
cassette type
RAV-SM1104UT-E RAV-SM1104UT-E
Concealed
duct type
RAV-SM1102BT-E RAV-SM1102BT-E
Simultaneous triple
4-way air discharge
cassette type
RAV-SM804UT-E RAV-SM804UT-E RAV-SM804UT-E
Concealed
duct type
RAV-SM802BT-E RAV-SM802BT-E RAV-SM802BT-E
Simultaneous double twin
4-way air discharge
cassette type
RAV-SM564UT-E RAV-SM564UT-E RAV-SM564UT-E RAV-SM564UT-E
Compact 4-way
cassette (600×600) type
RAV-SM562MUT-E RAV-SM562MUT-E RAV-SM562MUT-E RAV-SM562MUT-E
Ceiling type
RAV-SM1102CT-E RAV-SM1102CT-E
Ceiling type
RAV-SM802CT-E RAV-SM802CT-E RAV-SM802CT-E
Slim duct type
RAV-SM564SDT-E RAV-SM564SDT-E RAV-SM564SDT-E RAV-SM564SDT-E
High wall type
(2 series)
RAV-SM802KRT-E RAV-SM802KRT-E RAV-SM802KRT-E
Concealed
duct type
RAV-SM562BT-E RAV-SM562BT-E RAV-SM562BT-E RAV-SM562BT-E
Ceiling type
RAV-SM562CT-E RAV-SM562CT-E RAV-SM562CT-E RAV-SM562CT-E
High wall type
(2 series)
RAV-SM562KRT-E RAV-SM562KRT-E RAV-SM562KRT-E RAV-SM562KRT-E
<RAV-SM2804AT series> Simultaneous twin
4-way air discharge
cassette type
RAV-SM1404UT-E RAV-SM1404UT-E
Concealed
duct type
RAV-SM1402BT-E RAV-SM1402BT-E
Simultaneous triple
4-way air discharge
cassette type
RAV-SM804UT-E RAV-SM804UT-E RAV-SM804UT-E
Concealed
duct type
RAV-SM802BT-E RAV-SM802BT-E RAV-SM802BT-E
Simultaneous double twin
4-way air discharge
cassette type
RAV-SM804UT-E RAV-SM804UT-E RAV-SM804UT-E RAV-SM804UT-E
Concealed
duct type
RAV-SM802BT-E RAV-SM802BT-E RAV-SM802BT-E RAV-SM802BT-E
Ceiling type
RAV-SM1402CT-E RAV-SM1402CT-E
Ceiling type
RAV-SM802CT-E RAV-SM802CT-E RAV-SM802CT-E
Ceiling type
RAV-SM802CT-E RAV-SM802CT-E RAV-SM802CT-E RAV-SM802CT-E
High wall type
(2 series)
RAV-SM802KRT-E RAV-SM802KRT-E RAV-SM802KRT-E
High wall type
(2 series)
RAV-SM802KRT-E RAV-SM802KRT-E RAV-SM802KRT-E RAV-SM802KRT-E
– 9 –
RAV-SM2244AT series
Branch kit
Slimultaneous twin
Simultaneous triple
Simultaneous double twin
Slimultaneous twin
Simultaneous triple
Simultaneous double twin
SM110 — SM110
SM80 SM80 SM80
SM56 SM56 SM56 SM56
RAV-SM2804AT series
SM140 — SM140
SM80 SM80 SM80
SM80 SM80 SM80 SM80
RBC-TWP101E
RBC-TRP100E
RBC-DTWP101E
Branch kit
RBC-TWP101E
RBC-TRP100E
RBC-DTWP101E
– 10 –
1. SPECIFICATIONS
1-1. Indoor Unit
1-1-1. 4-Way Cassette Type
<Twin type>
Indoor unit 1 RAV-SM 1104UT-E 1404UT-E 1104UT-E 1404UT-E
Model Indoor unit 2 RAV-SM 1104UT-E 1404UT-E 1104UT-E 1404UT-E
Outdoor unit RAV-SM 2244AT8-E 2804AT8-E 2244AT7 2804AT7
Cooling capacity (kW) 20.0 23.0 20.0 23.0 Heating capacity (kW) 22.4 27.0 22.4 27.0 Power supply 3 phase 380 – 415V 50Hz 3 phase 380V 60Hz
Indoor unit
Running current (A) 10.09 – 9.24 13.24 – 12.12 10.09 13.24 Power consumption (kW) 6.24 8.19 6.24 8.19
Cooling Power factor (%) 94 94 94 94
EER 3.21 2.81 3.21 2.81
Energy efficiency class AC—— Electrical characteristics
Running current (A) 9.41 – 8.61 12.09 – 11.07 9.41 12.09
Power consumption (kW) 5.82 7.48 5.82 7.48
Heating Power factor (%) 94 94 94 94
COP 3.85 3.61 3.85 3.61
Energy efficiency class AA——
Maximum current (A) 18 22 18 22
Fan Turbo fan Turbo fan Turbo fan Turbo fan Fan unit Standard air flow H/M/L (m³/min.) 33.5/24.0/19.5 35.0/24.0/20.5 33.5/24.0/19.5 35.0/24.0/20.5
Motor (W) 68 72 68 72 Sound pressure level H/M/L (dB•A) 43 / 38 / 33 44 / 38 / 34 43 / 38 / 33 44 / 38 / 34 Sound power level H/M/L (dB•A) 58 / 53 / 48 59 / 53 / 49 58 / 53 / 48 59 / 53 / 49
Outdoor unit
Max. total length (m) 70 70 70 70
Outer dimension
Fan unit Standard air flow high (m³/min.) 133 133 133 133
Min. length (m) 7.5 7.5 7.5 7.5
Outdoor lower (m) 30 30 30 30
Height difference
Outdoor high (m) 30 30 30 30
Fan Propeller fan Propeller fan Propeller fan Propeller fan
Motor (W) 100 + 100 100 + 100 100 + 100 100 + 100
Outdoor unit – Pipe branch
Connecting pipe
Pipe branch – Indoor unit
Sound pressure level Cooling / Heating (dB•A) 56 / 57 57 / 58 56 / 57 57 / 58 Sound power level Cooling / Heating (dB•A) 72 / 74 74 / 75 72 / 74 74 / 75
Gas side (mm) 28.6 28.6 28.6 28.6 Liquid side (mm) 12.7 12.7 12.7 12.7 Gas side (mm) 15.9 15.9 15.9 15.9 Liquid side (mm) 9.5 9.5 9.5 9.5
: IEC standard
– 11 –
1-1-2. Duct Type
<Twin type>
Indoor unit 1 RAV-SM 1102BT-E 1402BT-E 1102BT-E 14002BT-E
Model Indoor unit 2 RAV-SM 1102BT-E 1402BT-E 1102BT-E 1402BT-E
Outdoor unit RAV-SM 2244AT8-E 2804AT8-E 2244AT7 2804AT7
Cooling capacity (kW) 20.0 23.0 20.0 23.0 Heating capacity (kW) 22.4 27.0 22.4 27.0 Power supply 3 phase 380 – 415V 50Hz 3 phase 380V 60Hz
Indoor unit
Running current (A) 11.51 – 10.54 15.44 – 14.13 11.51 15.44
Power consumption (kW) 7.12 9.55 7.12 9.55
Cooling Power factor (%) 94 94 94 94
EER 2.81 2.41 2.81 2.41
Energy efficiency class CE—— Electrical characteristics
Heating Power factor (%) 94 94 94 94
Running current (A) 10.34 – 9.47 12.80 – 11.72 10.34 12.80
Power consumption (kW) 6.40 7.92 6.40 7.92
COP 3.50 3.41 3.50 3.41
Energy efficiency class BB——
Maximum current (A) 18 22 18 22
Fan Centrifugal Centrifugal Centrifugal Centrifugal Fan unit Standard air flow H/M/L (m³/min.) 27.0/23.0/18.9 33.0/28.0/23.1 27.0/23.0/18.9 33.0/28.0/23.1
Motor (W) 120 120 120 120 Sound pressure level H/M/L (dB•A) 42 / 39 / 36 44 / 41 / 38 42 / 39 / 36 44 / 41 / 38 Sound power level H/M/L (dB•A) 57 / 54 / 51 59 / 56 / 53 57 / 54 / 51 59 / 56 / 53
Outdoor unit
Max. total length (m) 70 70 70 70
Outer dimension
Fan unit Standard air flow high (m³/min.) 133 133 133 133
Connecting pipe
Min. length (m) 7.5 7.5 7.5 7.5
Outdoor lower (m) 30 30 30 30
Height difference
Outdoor high (m) 30 30 30 30
Fan Propeller fan Propeller fan Propeller fan Propeller fan
Motor (W) 100 + 100 100 + 100 100 + 100 100 + 100
Gas side (mm) 28.6 28.6 28.6 28.6
Outdoor unit – Pipe branch
Liquid side (mm) 12.7 12.7 12.7 12.7 Gas side (mm) 15.9 15.9 15.9 15.9
Pipe branch – Indoor unit
Liquid side (mm) 9.5 9.5 9.5 9.5 Sound pressure level Cooling / Heating (dB•A) 56 / 57 57 / 58 56 / 57 57 / 58 Sound power level Cooling / Heating (dB•A) 72 / 74 74 / 75 72 / 74 74 / 75
: IEC standard
– 12 –
1-1-3. Ceiling Type
<Twin type>
Indoor unit 1 RAV-SM 1102CT-E 1402CT-E 1102CT-E 1402CT-E
Model Indoor unit 2 RAV-SM 1102CT-E 1402CT-E 1102CT-E 1402CT-E
Outdoor unit RAV-SM 2244AT8-E 2804AT8-E 2244AT7 2804AT7
Cooling capacity (kW) 20.0 23.0 20.0 23.0 Heating capacity (kW) 22.4 27.0 22.4 27.0 Power supply 3 phase 380 – 415V 50Hz 3 phase 380V 60Hz
Indoor unit
Running current (A) 11.51 – 10.54 15.44 – 14.13 11.51 15.44 Power consumption (kW) 7.12 9.55 7.12 9.55
Cooling Power factor (%) 94 94 94 94
EER 2.81 2.41 2.81 2.41
Energy efficiency class CE—— Electrical characteristics
Heating Power factor (%) 94 94 94 94
Running current (A) 10.34 – 9.47 12.80 – 11.72 10.34 12.80
Power consumption (kW) 6.40 7.92 6.40 7.92
COP 3.50 3.41 3.50 3.41
Energy efficiency class BB——
Maximum current (A) 18 22 18 22
Fan Centrifugal Centrifugal Centrifugal Centrifugal Fan unit Standard air flow H/M/L (m³/min.) 27.5/24.0/21.2 30.0/26.0/23.1 27.5/24.0/21.2 30.0/26.0/23.1
Motor (W) 120 120 120 120 Sound pressure level H/M/L (dB•A) 41 / 38 / 35 43 / 40 / 37 41 / 38 / 35 43 / 40 / 37 Sound power level H/M/L (dB•A) 56 / 53 / 50 58 / 55 / 52 56 / 53 / 50 58 / 55 / 52
Outdoor unit
Max. total length (m) 70 70 70 70
Outer dimension
Fan unit Standard air flow high (m³/min.) 133 133 133 133
Connecting pipe
Min. length (m) 7.5 7.5 7.5 7.5
Outdoor lower (m) 30 30 30 30
Height difference
Outdoor high (m) 30 30 30 30
Fan Propeller fan Propeller fan Propeller fan Propeller fan
Motor (W) 100 + 100 100 + 100 100 + 100 100 + 100
Gas side (mm) 28.6 28.6 28.6 28.6
Outdoor unit – Pipe branch
Liquid side (mm) 12.7 12.7 12.7 12.7 Gas side (mm) 15.9 15.9 15.9 15.9
Pipe branch – Indoor unit
Liquid side (mm) 9.5 9.5 9.5 9.5 Sound pressure level Cooling / Heating (dB•A) 56 / 57 57 / 58 56 / 57 57 / 58 Sound power level Cooling / Heating (dB•A) 72 / 74 74 / 75 72 / 74 74 / 75
: IEC standard
– 13 –
1-1-4. 4-Way Cassette Type
<Triple type>
Indoor unit 1 RAV-SM 804UT-E 804UT-E 804UT-E 804UT-E
Model
Cooling capacity (kW) 20.0 23.0 20.0 23.0 Heating capacity (kW) 22.4 27.0 22.4 27.0 Power supply 3 phase 380 – 415V 50Hz 3 phase 380V 60Hz
Electrical characteristics
Indoor unit 2 RAV-SM 804UT-E 804UT-E 804UT-E 804UT-E Indoor unit 3 RAV-SM 804UT-E 804UT-E 804UT-E 804UT-E Outdoor unit RAV-SM 2244AT8-E 2804AT8-E 2244AT7 2804AT7
Indoor unit
Running current (A) 11.51 – 10.54 15.44 – 14.13 11.51 15.44 Power consumption (kW) 7.12 9.55 7.12 9.55
Cooling Power factor (%) 94 94 94 94
EER 2.81 2.41 2.81 2.41 Energy efficiency class CE—— Running current (A) 10.34 – 9.47 12.80 – 11.72 10.34 12.80 Power consumption (kW) 6.40 7.92 6.40 7.92
Heating Power factor (%) 94 94 94 94
COP 3.50 3.41 3.50 3.41 Energy efficiency class BB—— Maximum current (A) 18 22 18 22 Fan Turbo fan Turbo fan Turbo fan Turbo fan
Fan unit Standard air flow H/M/L (m³/min.) 20.5/16.0/13.5 20.5/16.0/13.5 20.5/16.0/13.5 20.5/16.0/13.5
Motor (W) 20 20 20 20 Sound pressure level H/M/L (dB•A) 35 / 31 / 28 35 / 31 / 28 35 / 31 / 28 35 / 31 / 28 Sound power level H/M/L (dB•A) 50 / 46 / 43 50 / 46 / 43 50 / 46 / 43 50 / 46 / 43
Outdoor unit
Max. total length (m) 70 70 70 70
Outer dimension
Fan unit Standard air flow high (m³/min.) 133 133 133 133
Connecting pipe
Min. length (m) 7.5 7.5 7.5 7.5
Outdoor lower (m) 30 30 30 30
Height difference
Outdoor high (m) 30 30 30 30
Fan Propeller fan Propeller fan Propeller fan Propeller fan
Motor (W) 100 + 100 100 + 100 100 + 100 100 + 100
Gas side (mm) 28.6 28.6 28.6 28.6
Outdoor unit – Pipe branch
Liquid side (mm) 12.7 12.7 12.7 12.7 Gas side (mm) 15.9 15.9 15.9 15.9
Pipe branch – Indoor unit
Liquid side (mm) 9.5 9.5 9.5 9.5 Sound pressure level Cooling / Heating (dB•A) 56 / 57 57 / 58 56 / 57 57 / 58 Sound power level Cooling / Heating (dB•A) 72 / 74 74 / 75 72 / 74 74 / 75
: IEC standard
– 14 –
1-1-5. Duct Type
<Triple type>
Indoor unit 1 RAV-SM 802BT-E 802BT-E 802BT-E 802BT-E
Model
Cooling capacity (kW) 20.0 23.0 20.0 23.0 Heating capacity (kW) 22.4 27.0 22.4 27.0 Power supply 3 phase 380 – 415V 50Hz 3 phase 380V 60Hz
Electrical characteristics
Indoor unit 2 RAV-SM 802BT-E 802BT-E 802BT-E 802BT-E Indoor unit 3 RAV-SM 802BT-E 802BT-E 802BT-E 802BT-E Outdoor unit RAV-SM 2244AT8-E 2804AT8-E 2244AT7 2804AT7
Indoor unit
Running current (A) 11.51 – 10.54 15.44 – 14.13 11.51 15.44 Power consumption (kW) 7.12 9.55 7.12 9.55
Cooling Power factor (%) 94 94 94 94
EER 2.81 2.41 2.81 2.41 Energy efficiency class CE—— Running current (A) 10.34 – 9.47 12.80 – 11.72 10.34 12.80 Power consumption (kW) 6.40 7.92 6.40 7.92
Heating Power factor (%) 94 94 94 94
COP 3.50 3.41 3.50 3.41 Energy efficiency class BB—— Maximum current (A) 18 22 18 22 Fan Centrifugal Centrifugal Centrifugal Centrifugal
Fan unit Standard air flow H/M/L (m³/min.) 19.0/16.2/13.3 19.0/16.2/13.3 19.0/16.2/13.3 19.0/16.2/13.3
Motor (W) 120 120 120 120 Sound pressure level H/M/L (dB•A) 40 / 37 / 34 40 / 37 / 34 40 / 37 / 34 40 / 37 / 34 Sound power level H/M/L (dB•A) 55 / 52 / 49 55 / 52 / 49 55 / 52 / 49 55 / 52 / 49
Outdoor unit
Max. total length (m) 70 70 70 70
Outer dimension
Fan unit Standard air flow high (m³/min.) 133 133 133 133
Connecting pipe
Min. length (m) 7.5 7.5 7.5 7.5
Outdoor lower (m) 30 30 30 30
Height difference
Outdoor high (m) 30 30 30 30
Fan Propeller fan Propeller fan Propeller fan Propeller fan
Motor (W) 100 + 100 100 + 100 100 + 100 100 + 100
Gas side (mm) 28.6 28.6 28.6 28.6
Outdoor unit – Pipe branch
Liquid side (mm) 12.7 12.7 12.7 12.7 Gas side (mm) 15.9 15.9 15.9 15.9
Pipe branch – Indoor unit
Liquid side (mm) 9.5 9.5 9.5 9.5 Sound pressure level Cooling / Heating (dB•A) 56 / 57 57 / 58 56 / 57 57 / 58 Sound power level Cooling / Heating (dB•A) 72 / 74 74 / 75 72 / 74 74 / 75
: IEC standard
– 15 –
1-1-6. Ceiling Type
<Triple type>
Indoor unit 1 RAV-SM 802CT-E 802CT-E 802CT-E 802CT-E
Model
Cooling capacity (kW) 20.0 23.0 20.0 23.0 Heating capacity (kW) 22.4 27.0 22.4 27.0 Power supply 3 phase 380 – 415V 50Hz 3 phase 380V 60Hz
Electrical characteristics
Indoor unit 2 RAV-SM 802CT-E 802CT-E 802CT-E 802CT-E Indoor unit 3 RAV-SM 802CT-E 802CT-E 802CT-E 802CT-E Outdoor unit RAV-SM 2244AT8-E 2804AT8-E 2244AT7 2804AT7
Indoor unit
Running current (A) 11.51 – 10.54 15.44 – 14.13 11.51 15.44 Power consumption (kW) 7.12 9.55 7.12 9.55
Cooling Power factor (%) 94 94 94 94
EER 2.81 2.41 2.81 2.41 Energy efficiency class CE—— Running current (A) 10.34 – 9.47 12.80 – 11.72 10.34 12.80 Power consumption (kW) 6.40 7.92 6.40 7.92
Heating Power factor (%) 94 94 94 94
COP 3.50 3.41 3.50 3.41 Energy efficiency class BB—— Maximum current (A) 18 22 18 22 Fan Centrifugal Centrifugal Centrifugal Centrifugal
Fan unit Standard air flow H/M/L (m³/min.) 18.5/16.7/14.6 18.5/16.7/14.6 18.5/16.7/14.6 18.5/16.7/14.6
Motor (W) 60 60 60 60 Sound pressure level H/M/L (dB•A) 38 / 36 / 33 38 / 36 / 33 38 / 36 / 33 38 / 36 / 33 Sound power level H/M/L (dB•A) 53 / 51 / 48 53 / 51 / 48 53 / 51 / 48 53 / 51 / 48
Outdoor unit
Max. total length (m) 70 70 70 70
Outer dimension
Fan unit Standard air flow high (m³/min.) 133 133 133 133
Connecting pipe
Min. length (m) 7.5 7.5 7.5 7.5
Outdoor lower (m) 30 30 30 30
Height difference
Outdoor high (m) 30 30 30 30
Fan Propeller fan Propeller fan Propeller fan Propeller fan
Motor (W) 100 + 100 100 + 100 100 + 100 100 + 100
Gas side (mm) 28.6 28.6 28.6 28.6
Outdoor unit – Pipe branch
Liquid side (mm) 12.7 12.7 12.7 12.7 Gas side (mm) 15.9 15.9 15.9 15.9
Pipe branch – Indoor unit
Liquid side (mm) 9.5 9.5 9.5 9.5 Sound pressure level Cooling / Heating (dB•A) 56 / 57 57 / 58 56 / 57 57 / 58 Sound power level Cooling / Heating (dB•A) 72 / 74 74 / 75 72 / 74 74 / 75
: IEC standard
– 16 –
1-1-7. High Wall T ype
<Triple type>
Indoor unit 1 RAV-SM 802KRT-E 802KRT-E 802KRT-E 802KRT-E
Model
Cooling capacity (kW) 20.0 23.0 20.0 23.0 Heating capacity (kW) 22.4 27.0 22.4 27.0 Power supply 3 phase 380 – 415V 50Hz 3 phase 380V 60Hz
Electrical characteristics
Indoor unit 2 RAV-SM 802KRT-E 802KRT-E 802KRT-E 802KRT-E Indoor unit 3 RAV-SM 802KRT-E 802KRT-E 802KRT-E 802KRT-E Outdoor unit RAV-SM 2244AT8-E 2804AT8-E 2244AT7 2804AT7
Indoor unit
Running current (A) 11.51 – 10.54 15.44 – 14.13 11.51 15.44 Power consumption (kW) 7.12 9.55 7.12 9.55
Cooling Power factor (%) 94 94 94 94
EER 2.81 2.41 2.81 2.41 Energy efficiency class CE—— Running current (A) 10.34 – 9.47 12.80 – 11.72 10.34 12.80 Power consumption (kW) 6.40 7.92 6.40 7.92
Heating Power factor (%) 94 94 94 94
COP 3.50 3.41 3.50 3.41 Energy efficiency class BB—— Maximum current (A) 18 22 18 22 Fan Cross flow fan Cross flow fan Cross flow fan Cross flow fan
Fan unit Standard air flow H/M/L (m³/min.) 18.5/14.6/12.2 18.5/14.6/12.2 18.5/14.6/12.2 18.5/14.6/12.2
Motor (W) 30 30 30 30 Sound pressure level H/M/L (dB•A) 45 / 41 / 36 45 / 41 / 36 45 / 41 / 36 45 / 41 / 36 Sound power level H/M/L (dB•A) 60 / 56 / 51 60 / 56 / 51 60 / 56 / 51 60 / 56 / 51
Outdoor unit
Max. total length (m) 70 70 70 70
Outer dimension
Fan unit Standard air flow high (m³/min.) 133 133 133 133
Connecting pipe
Min. length (m) 7.5 7.5 7.5 7.5
Outdoor lower (m) 30 30 30 30
Height difference
Outdoor high (m) 30 30 30 30
Fan Propeller fan Propeller fan Propeller fan Propeller fan
Motor (W) 100 + 100 100 + 100 100 + 100 100 + 100
Gas side (mm) 28.6 28.6 28.6 28.6
Outdoor unit – Pipe branch
Liquid side (mm) 12.7 12.7 12.7 12.7 Gas side (mm) 15.9 15.9 15.9 15.9
Pipe branch – Indoor unit
Liquid side (mm) 9.5 9.5 9.5 9.5 Sound pressure level Cooling / Heating (dB•A) 56 / 57 57 / 58 56 / 57 57 / 58 Sound power level Cooling / Heating (dB•A) 72 / 74 74 / 75 72 / 74 74 / 75
: IEC standard
– 17 –
1-1-8. 4-Way Cassette Type
<Double twin type>
Indoor unit 1 RAV-SM 564UT-E 804UT-E 564UT-E 804UT-E Indoor unit 2 RAV-SM 564UT-E 804UT-E 564UT-E 804UT-E
Model Indoor unit 3 RAV-SM 564UT-E 804UT-E 564UT-E 804UT-E
Indoor unit 4 RAV-SM 564UT-E 804UT-E 564UT-E 804UT-E Outdoor unit RAV-SM 2244AT8-E 2804AT8-E 2244AT7 2804AT7
Cooling capacity (kW) 20.0 23.0 20.0 23.0 Heating capacity (kW) 22.4 27.0 22.4 27.0 Power supply 3 phase 380 – 415V 50Hz 3 phase 380V 60Hz
Indoor unit
Running current (A) 11.51 – 10.54 15.44 – 14.13 11.51 15.44 Power consumption (kW) 7.12 9.55 7.12 9.55
Cooling Power factor (%) 94 94 94 94
EER 2.81 2.41 2.81 2.41
Energy efficiency class CE—— Electrical characteristics
Running current (A) 10.34 – 9.47 12.80 – 11.72 10.34 12.80
Power consumption (kW) 6.40 7.92 6.40 7.92
Heating Power factor (%) 94 94 94 94
COP 3.50 3.41 3.50 3.41
Energy efficiency class BB——
Maximum current (A) 18 22 18 22
Fan Turbo fan Turbo fan Turbo fan Turbo fan Fan unit Standard air flow H/M/L (m³/min.) 17.5/14.5/13.0 20.5/16.0/13.5 17.5/14.5/13.0 20.5/16.0/13.5
Motor (W) 14 20 14 20 Sound pressure level H/M/L (dB•A) 32 / 29 / 28 35 / 31 / 28 32 / 29 / 28 35 / 31 / 28 Sound power level H/M/L (dB•A) 47 / 44 / 43 50 / 46 / 43 47 / 44 / 43 50 / 46 / 43
Outdoor unit
Max. total length (m) 70 70 70 70
Outer dimension
Fan unit Standard air flow high (m³/min.) 133 133 133 133
Min. length (m) 7.5 7.5 7.5 7.5
Outdoor lower (m) 30 30 30 30
Height difference
Outdoor high (m) 30 30 30 30
Fan Propeller fan Propeller fan Propeller fan Propeller fan
Motor (W) 100 + 100 100 + 100 100 + 100 100 + 100
Outdoor unit – Pipe branch
Connecting pipe
Pipe branch – Indoor unit
Sound pressure level Cooling / Heating (dB•A) 56 / 57 57 / 58 56 / 57 57 / 58 Sound power level Cooling / Heating (dB•A) 72 / 74 74 / 75 72 / 74 74 / 75
Gas side (mm) 28.6 28.6 28.6 28.6 Liquid side (mm) 12.7 12.7 12.7 12.7 Gas side (mm) 15.9 15.9 15.9 15.9 Liquid side (mm) 9.5 9.5 9.5 9.5
: IEC standard
– 18 –
1-1-9. Compact 4-Way Cassette (600 × 600) Type
<Double twin type>
Indoor unit 1 RAV-SM562MUT-E RAV-SM562MUT-E Indoor unit 2 RAV-SM562MUT-E RAV-SM562MUT-E
Model Indoor unit 3 RAV-SM562MUT-E RAV-SM562MUT-E
Indoor unit 4 RAV-SM562MUT-E RAV-SM562MUT-E Outdoor unit RAV-SM2244AT8-E RAV-SM2244AT7
Cooling capacity (kW) 20.0 20.0 Heating capacity (kW) 22.4 22.4 Power supply 3 phase 380 – 415V 50Hz 3 phase 380V 60Hz
Indoor unit
Running current (A) 11.51 – 10.54 11.51
Power consumption (kW) 7.12 7.12
Cooling Power factor (%) 94 94
EER 2.81 2.81
Energy efficiency class C Electrical
characteristics
Heating Power factor (%) 94 94
Fan unit Standard air flow H/M/L (m³/min.) 13.3 / 11.2 / 9.1 13.3 / 11.2 / 9.1
Sound pressure level H/M/L (dB•A) 43 / 39 / 34 43 / 39 / 34 Sound power level H/M/L (dB•A) 58 / 54 / 49 58 / 54 / 49
Max. total length (m) 70 70
Outer dimension
Fan unit Standard air flow high (m³/min.) 133 133
Connecting pipe
Sound pressure level Cooling / Heating (dB•A) 56 / 57 56 / 57 Sound power level Cooling / Heating (dB•A) 72 / 74 72 / 74
Min. length (m) 7.5 7.5
Height difference
Fan Propeller fan Propeller fan
Motor (W) 100 + 100 100 + 100 Outdoor unit –
First pipe branch
First pipe branch – Second pipe branch
Second pipe branch – Indoor unit
Running current (A) 10.34 – 9.47 10.34
Power consumption (kW) 6.40 6.40
COP 3.50 3.50
Energy efficiency class B
Maximum current (A) 18 18
Fan Turbo fan Turbo fan
Motor (W) 60 60
Outdoor unit
Outdoor lower (m) 30 30 Outdoor high (m) 30 30
Gas side (mm) 28.6 28.6 Liquid side (mm) 12.7 12.7 Gas side (mm) 15.9 15.9 Liquid side (mm) 9.5 9.5 Gas side (mm) 12.7 12.7 Liquid side (mm) 6.4 6.4
– 19 –
: IEC standard
1-1-10. Slim Duct Type
<Double twin type>
Indoor unit 1 RAV-SM564SDT-E RAV-SM564SDT-E Indoor unit 2 RAV-SM564SDT-E RAV-SM564SDT-E
Model Indoor unit 3 RAV-SM564SDT-E RAV-SM564SDT-E
Indoor unit 4 RAV-SM564SDT-E RAV-SM564SDT-E Outdoor unit RAV-SM2244AT8-E RAV-SM2244AT7
Cooling capacity (kW) 20.0 20.0 Heating capacity (kW) 22.4 22.4 Power supply 3 phase 380 – 415V 50Hz 3 phase 380V 60Hz
Indoor unit
Running current (A) 11.51 – 10.54 11.51
Power consumption (kW) 7.12 7.12
Cooling Power factor (%) 94 94
EER 2.81 2.81
Electrical characteristics
Heating Power factor (%) 94 94
Fan Centrifugal fan Centrifugal fan Standard air flow H/M/L (m³/min.) 13.0 / 11.3 / 9.7 13.0 / 11.3 / 9.7
Fan unit Motor (W) 60 60
Extermal static pressure
Sound pressure level
Sound power level
Max. total length (m) 70 70
Outer dimension
Fan unit Standard air flow high (m³/min.) 133 133
Connecting pipe
Sound pressure level Cooling / Heating (dB•A) 56 / 57 56 / 57 Sound power level Cooling / Heating (dB•A) 72 / 74 72 / 74
Min. length (m) 7.5 7.5
Height difference
Fan Propeller fan Propeller fan
Motor (W) 100 + 100 100 + 100 Outdoor unit –
First pipe branch
First pipe branch – Second pipe branch
Second pipe branch – Indoor unit
Energy efficiency class C
Running current (A) 10.34 – 9.47 10.34
Power consumption (kW) 6.40 6.40
COP 3.50 3.50
Energy efficiency class B
Maximum current (A) 18 18
Standard (at shipment) (Pa) 10 10
Set up for tap exchange (Pa) 10 / 20 / 35 / 50 10 / 20 / 35 / 50 Under air inlet H/M/L (dB•A) 45 / 40 / 36 45 / 40 / 36 Back air inlet H/M/L (dB•A) 33 / 31 / 28 33 / 31 / 28 Under air inlet H/M/L (dB•A) 60 / 55 / 51 60 / 55 / 51 Back air inlet H/M/L (dB•A) 48 / 46 / 43 48 / 46 / 43
Outdoor unit
Outdoor lower (m) 30 30
Outdoor high (m) 30 30
Gas side (mm) 28.6 28.6
Liquid side (mm) 12.7 12.7 Gas side (mm) 15.9 15.9 Liquid side (mm) 9.5 9.5 Gas side (mm) 12.7 12.7 Liquid side (mm) 6.4 6.4
– 20 –
: IEC standard
1-1-11. Duct Type
<Double twin type>
Indoor unit 1 RAV-SM 562BT-E 802BT-E 562BT-E 802BT-E Indoor unit 2 RAV-SM 562BT-E 802BT-E 562BT-E 802BT-E
Model Indoor unit 3 RAV-SM 562BT-E 802BT-E 562BT-E 802BT-E
Indoor unit 4 RAV-SM 562BT-E 802BT-E 562BT-E 802BT-E Outdoor unit RAV-SM 2244AT8-E 2804AT8-E 2244AT7 2804AT7
Cooling capacity (kW) 20.0 23.0 20.0 23.0 Heating capacity (kW) 22.4 27.0 22.4 27.0 Power supply 3 phase 380 – 415V 50Hz 3 phase 380V 60Hz
Indoor unit
Running current (A) 11.51 – 10.54 15.44 – 14.13 11.51 15.44 Power consumption (kW) 7.12 9.55 7.12 9.55
Cooling Power factor (%) 94 94 94 94
EER 2.81 2.41 2.81 2.41 Energy efficiency class CE——
Electrical characteristics
Heating Power factor (%) 94 94 94 94
Fan Centrifugal Centrifugal Centrifugal Centrifugal
Fan unit Standard air flow H/M/L (m³/min.) 13.0/11.9/9.8 19.0/16.2/13.3 13.0/11.9/9.8 19.0/16.2/13.3
Motor (W) 120 120 120 120 Sound pressure level H/M/L (dB•A) 40 / 37 / 33 40 / 37 / 34 40 / 37 / 33 40 / 37 / 34 Sound power level H/M/L (dB•A) 55 / 52 / 48 55 / 52 / 49 55 / 52 / 48 55 / 52 / 49
Max. total length (m) 70 70 70 70
Outer dimension
Fan unit Standard air flow high (m³/min.) 133 133 133 133
Connecting pipe
Sound pressure level Cooling / Heating (dB•A) 56 / 57 57 / 58 56 / 57 57 / 58 Sound power level Cooling / Heating (dB•A) 72 / 74 74 / 75 72 / 74 74 / 75
Min. length (m) 7.5 7.5 7.5 7.5
Height difference
Fan Propeller fan Propeller fan Propeller fan Propeller fan
Motor (W) 100 + 100 100 + 100 100 + 100 100 + 100
Outdoor unit –
First pipe branch
First pipe branch –
Second pipe branch
Second pipe branch –
Indoor unit
Running current (A) 10.34 – 9.47 12.80 – 11.72 10.34 12.80 Power consumption (kW) 6.40 7.92 6.40 7.92
COP 3.50 3.41 3.50 3.41 Energy efficiency class BB—— Maximum current (A) 18 22 18 22
Outdoor unit
Outdoor lower (m) 30 30 30 30 Outdoor high (m) 30 30 30 30
Gas side (mm) 28.6 28.6 28.6 28.6 Liquid side (mm) 12.7 12.7 12.7 12.7 Gas side (mm) 15.9 15.9 15.9 15.9 Liquid side (mm) 9.5 9.5 9.5 9.5 Gas side (mm) 12.7 15.9 12.7 15.9 Liquid side (mm) 6.4 9.5 6.4 9.5
– 21 –
: IEC standard
1-1-12. Ceiling Type
<Double twin type>
Indoor unit 1 RAV-SM 562CT-E 802CT-E 562CT-E 802CT-E
Indoor unit 2 RAV-SM 562CT-E 802CT-E 562CT-E 802CT-E Model Indoor unit 3 RAV-SM 562CT-E 802CT-E 562CT-E 802CT-E
Indoor unit 4 RAV-SM 562CT-E 802CT-E 562CT-E 802CT-E
Outdoor unit RAV-SM 2244AT8-E 2804AT8-E 2244AT7 2804AT7
Cooling capacity (kW) 20.0 23.0 20.0 23.0 Heating capacity (kW) 22.4 27.0 22.4 27.0 Power supply 3 phase 380 – 415V 50Hz 3 phase 380V 60Hz
Indoor unit
Running current (A) 11.51 – 10.54 15.44 – 14.13 11.51 15.44 Power consumption (kW) 7.12 9.55 7.12 9.55
Cooling Power factor (%) 94 94 94 94
EER 2.81 2.41 2.81 2.41 Energy efficiency class CE——
Electrical characteristics
Heating Power factor (%) 94 94 94 94
Fan Centrifugal Centrifugal Centrifugal Centrifugal Fan unit Standard air flow H/M/L (m³/min.) 13.0/11.2/10.0 18.5/16.7/14.6 13.0/11.2/10.0 18.5/16.7/14.6
Motor (W) 60 60 60 60 Sound pressure level H/M/L (dB•A) 36 / 33 / 30 38 / 36 / 33 36 / 33 / 30 38 / 36 / 33 Sound power level H/M/L (dB•A) 51 / 48 / 45 53 / 51 / 48 51 / 48 / 45 53 / 51 / 48
Max. total length (m) 70 70 70 70
Outer dimension
Fan unit Standard air flow high (m³/min.) 133 133 133 133
Connecting pipe
Sound pressure level Cooling / Heating (dB•A) 56 / 57 57 / 58 56 / 57 57 / 58 Sound power level Cooling / Heating (dB•A) 72 / 74 74 / 75 72 / 74 74 / 75
Min. length (m) 7.5 7.5 7.5 7.5
Height difference
Fan Propeller fan Propeller fan Propeller fan Propeller fan
Motor (W) 100 + 100 100 + 100 100 + 100 100 + 100
Outdoor unit –
First pipe branch
First pipe branch –
Second pipe branch
Second pipe branch –
Indoor unit
Running current (A) 10.34 – 9.47 12.80 – 11.72 10.34 12.80 Power consumption (kW) 6.40 7.92 6.40 7.92
COP 3.50 3.41 3.50 3.41 Energy efficiency class BB—— Maximum current (A) 18 22 18 22
Outdoor unit
Outdoor lower (m) 30 30 30 30 Outdoor high (m) 30 30 30 30
Gas side (mm) 28.6 28.6 28.6 28.6 Liquid side (mm) 12.7 12.7 12.7 12.7 Gas side (mm) 15.9 15.9 15.9 15.9 Liquid side (mm) 9.5 9.5 9.5 9.5 Gas side (mm) 12.7 15.9 12.7 15.9 Liquid side (mm) 6.4 9.5 6.4 9.5
– 22 –
: IEC standard
1-1-12. High Wall T ype
<Double twin type>
Indoor unit 1 RAV-SM 562KRT-E 802KRT-E 562KRT-E 802KRT-E
Indoor unit 2 RAV-SM 562KRT-E 802KRT-E 562KRT-E 802KRT-E Model Indoor unit 3 RAV-SM 562KRT-E 802KRT-E 562KRT-E 802KRT-E
Indoor unit 4 RAV-SM 562KRT-E 802KRT-E 562KRT-E 802KRT-E
Outdoor unit RAV-SM 2244AT8-E 2804AT8-E 2244AT7 2804AT7
Cooling capacity (kW) 20.0 23.0 20.0 23.0 Heating capacity (kW) 22.4 27.0 22.4 27.0 Power supply 3 phase 380 – 415V 50Hz 3 phase 380V 60Hz
Indoor unit
Running current (A) 11.51 – 10.54 15.44 – 14.13 11.51 15.44 Power consumption (kW) 7.12 9.55 7.12 9.55
Cooling Power factor (%) 94 94 94 94
EER 2.81 2.41 2.81 2.41 Energy efficiency class CE——
Electrical characteristics
Heating Power factor (%) 94 94 94 94
Fan Cross flow fan Cross flow fan Cross flow fan Cross flow fan Fan unit Standard air flow H/M/L (m³/min.) 14.0/12.5/10.7 18.5/14.6/12.2 14.0/12.5/10.7 18.5/14.6/12.2
Motor (W) 30 30 30 30 Sound pressure level H/M/L (dB•A) 39 / 36 / 33 45 / 41 / 36 39 / 36 / 33 45 / 41 / 36 Sound power level H/M/L (dB•A) 54 / 51 / 48 60 / 56 / 51 54 / 51 / 48 60 / 56 / 51
Max. total length (m) 70 70 70 70
Outer dimension
Fan unit Standard air flow high (m³/min.) 133 133 133 133
Connecting pipe
Sound pressure level Cooling / Heating (dB•A) 56 / 57 57 / 58 56 / 57 57 / 58 Sound power level Cooling / Heating (dB•A) 72 / 74 74 / 75 72 / 74 74 / 75
Min. length (m) 7.5 7.5 7.5 7.5
Height difference
Fan Propeller fan Propeller fan Propeller fan Propeller fan
Motor (W) 100 + 100 100 + 100 100 + 100 100 + 100
Outdoor unit –
First pipe branch
First pipe branch –
Second pipe branch
Second pipe branch –
Indoor unit
Running current (A) 10.34 – 9.47 12.80 – 11.72 10.34 12.80 Power consumption (kW) 6.40 7.92 6.40 7.92
COP 3.50 3.41 3.50 3.41 Energy efficiency class BB—— Maximum current (A) 18 22 18 22
Outdoor unit
Outdoor lower (m) 30 30 30 30 Outdoor high (m) 30 30 30 30
Gas side (mm) 28.6 28.6 28.6 28.6 Liquid side (mm) 12.7 12.7 12.7 12.7 Gas side (mm) 15.9 15.9 15.9 15.9 Liquid side (mm) 9.5 9.5 9.5 9.5 Gas side (mm) 12.7 12.7 12.7 12.7 Liquid side (mm) 6.4 9.5 6.4 9.5
– 23 –
: IEC standard
1-2. Outdoor Unit
Model Outdoor unit RAV-SM
Power supply
Type
Compressor Motor (kW)
Pole Refrigerant charged (kg) Refrigerant control
Max. total length (m)
Min. length (m) Pipe
Outdoor lower (m)
Height difference
Outdoor higher (m)
Height (mm) Outer dimension Width (mm)
2244AT8-E 2804AT8-E 2244AT7 2804AT7
1 phase 380 – 415V 50Hz 1 phase 380V 60Hz
(Power exclusive to outdoor is required.)
Hermetic compressor Hermetic compressor
3.75 3.75 3.75 3.75 4444
5.9 5.9 5.9 5.9
Pulse motor valve Pulse motor valve
70 70 70 70
7.5 7.5 7.5 7.5 30 30 30 30 30 30 30 30
1540 1540 1540 1540
900 900 900 900
Depth (mm)
Appearance
Total weight (kg) Heat exchanger
Fan
Fan unit Standard air flow (m³/min.)
Motor (W)
Connecting pipe (Outdoor unit side)
Sound pressure level Cooling/Heating (dB•A) Sound power level Cooling/Heating (dB•A) Outside air temperature, Cooling (°C) Outside air temperature, Heating (°C)
Gas side (mm) Liquid side (mm)
320 320 320 320
Silky shade Silky shade
(Muncel 1Y8.5/0.5) (Muncel 1Y8.5/0.5)
134 134 134 134
Finned tube Finned tube
Propeller fan Propeller fan
133 133 133 133
100 + 100 100 + 100 100 + 100 100 + 100
19.1 19.1 19.1 19.1
12.7 12.7 12.7 12.7 56 / 57 57 / 58 56 / 57 57 / 58 72 / 74 74 / 75 72 / 74 74 / 75
46 to –15°C 46 to –15°C 15 to –20°C 15 to –20°C
– 24 –
1-3. Operation Characteristic Curve
SM224
SM280
SM224
SM280
SM224
SM280
SM224
SM280
• Operation characteristic curve <Digital Inverter>
RAV-SM2244AT8 (Z) (ZG) -E, RAV-SM2804AT8 (Z) (ZG) -E
<Cooling> <Heating>
18
16
14
12
10
8
Current (A)
6
4
2
0
0 20 40 60 80 100
SM280
SM280
SM224
SM224
• Conditions Indoor : DB27˚C/WB19˚C Outdoor : DB35˚C Air flow : High Pipe length : 7.5m 400V, 50Hz (3 phase)
Compressor speed (rps)
18
16
SM280
SM280
14
12
10
8
Current (A)
6
SM224
SM224
4
2
0
0 20406080100
• Conditions Indoor : DB20˚C Outdoor : DB7˚C/WB6˚C Air flow : High Pipe length : 7.5m 400V, 50Hz (3 phase)
Compressor speed (rps)
RAV-SM2244AT7 (Z) (ZG), RAV-SM2804AT7 (Z) (ZG)
<Cooling> <Heating>
18
16
SM280
14
12
10
8
Current (A)
6
4
2
0
0 20 40 60 80 100
SM280
SM224
SM224
• Conditions Indoor : DB27˚C/WB19˚C Outdoor : DB35˚C Air flow : High Pipe length : 7.5m 380V, 60Hz (3 phase)
18
16
14
12
10
8
Current (A)
6
4
2
0
0 20406080100
Compressor speed (rps)
SM280
SM280
SM224
SM224
• Conditions Indoor : DB20˚C Outdoor : DB7˚C/WB6˚C Air flow : High Pipe length : 7.5m 380V, 60Hz (3 phase)
Compressor speed (rps)
– 25 –
• Capacity variation ratio according to temperature
RAV-SM2244AT8 (Z) (ZG) -E, RAV-SM2804AT8 (Z) (ZG) -E RAV-SM2244AT7 (Z) (ZG), RAV-SM2804AT7 (Z) (ZG)
<Cooling> <Heating>
105
100
95
90
85
80
75
70
Capacity ratio (%)
65
60
55
50
32 33 34 35 36 37 38 394041 42 43 44 45 46
Conditions Indoor : DB27˚C/WB19˚C Indoor air flow : High Pipe length : 7.5m
Outdoor temp. (˚C)
120 110 100
90 80 70 60 50
Capacity ratio (%)
40 30 20 10
0
-14-16-18-20 -12 -10 -8 -6 -4 -2 0 2 4 6 8 10
Conditions Indoor : DB20˚C Indoor air flow : High Pipe length : 7.5m
Outdoor temp. (˚C)
– 26 –
2. CONSTRUCTION VIEWS (EXTERNAL VIEWS)
2-1. Outdoor Unit
– 27 –
RBC-DTWP101E (Simultaneous Double Twin) <Branch pipe> <Joint pipe>
Inner
diameter
Ø D
Inner diameter
Ø C
A
Model
B
Gas side
Inner
diameter
Ø D
Outer diameter
Ø25.4
2422
Inner diameter
Ø28.6
1 pc.
ABCD
74 37 25.4 15.9 42 23 15.9 15.9
54
Q’ty
1 2
RBC-DTWP101E
Liquid side
43 23 15.9 12.7 35 18 12.7 9.5 34 14 9.5 9.5 36 14 9.5 6.4
2 1 2 2
– 28 –
RBC-TRP100E (Simultaneous Triple)
<Gas side>
Header assembly
300
Inner diameter Ø25.4Inner diameter Ø12.7
<Liquid side>
Branch pipe assembly
35
80 80100
1 pc.
Inner diameter Ø15.9
100
80 80100
Inner diameter Ø9.52
1 pc.
Insulator
Gas side socket Liquid side socket
Outer diameter
Ø15.9
Ø12.7
12
10
28
Ø15.9
(External
diameter)
3 pcs. 3 pcs. 1 pc.
46
Ø25.4
(External
diameter)
1 pc. 1 pc.
Ø25.4
2422
Inner
diameter
Ø28.6
54
Ø6.4
6
24
Ø9.5
(External
diameter)
100
Ø9.5
9
26
Ø12.7
(External
diameter)
– 29 –
RBC-TWP101E (Simultaneous Twin) <Branch pipe> <Joint pipe>
Inner
diameter
Ø D
Inner diameter
Ø C
A
RBC-TWP101E
Model
B
Inner
diameter
Ø D
Gas side Liquid side
Outer diameter
Ø25.4
2422
54
Inner diameter
Ø28.6
1 pc.
ABCDQ’ty
74 37 25.4 15.9 1 35 18 12.7 9.5 1
– 30 –