Please read this Installation Manual carefully before installing the Air Conditioner.
• This Manual describes the installation method of the outdoor unit.
• For installation of the indoor unit, follow the Installation Manual attached to the indoor unit.
ADOPTION OF NEW REFRIGERANT
This Air Conditioner is a new type that has adopted a new refrigerant HFC (R410A) instead of the conventional refrigerant R22 in
order to prevent destruction of the ozone layer.
This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to Ssc (*1) at the
interface point between the user’s supply and the public system. It is the responsibility of the installer or user of the equipment to
ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a
short-circuit power Ssc greater than or equal to Ssc (*1).
Installation manual1(Hand this directly to the customer.)
Drain nipple1
Waterproof rubber cap1
Protective bush1For protecting wires (pipe cover)
Guard material for passage part1For protecting passage part (pipe cover)
Clamp filter1
Ø19.1 mm pipe1For the pipe inside the outdoor unit
Joint (Ø19.1 – Ø25.4 mm)1For connecting the pipe
Joint (Ø25.4 – Ø28.6 mm)1For connecting the pipe
Elbow1For connecting the pipe
For conforming to EMC standards
(Used for power wire)
INFORMATION
•The main pipe on the gas side of this outdoor unit has a diameter of Ø28.6 mm, but a Ø19.1 mm flare connection is used
where the valve is connected. Be sure to use the Ø19.1 mm pipe and joint provided as accessories for the pipe connection.
•Before installing the unit, check that the unit has the correct model name to prevent the wrong unit from being installed in the
wrong place.
•Before proceeding to weld the refrigerant pipe, be sure to pass nitrogen through the pipe.
•Before installing the indoor units, read the instructions in the installation manual provided with the indoor units.
•Before installing a branch pipe, read the instructions in the installation manual provided with the branch pipe kit.
•In the case of a simultaneous double twin system, use indoor unit with the same capacity for all four indoor units.
Branch pipe kitCombination indoor unit
RAV-SM2244RBC-DTWP101ESM56 × 4 units
RAV-SM2804RBC-DTWP101ESM80 × 4 units
•P.C. board settings are required for some of the indoor units if they are to be used in a twin, triple or double twin system.
Refer to the instructions in the installation manual of the branch pipe kit, and ensure that the settings are selected correctly.
•Combination with the indoor units
Combination with the indoor units is possible only when units with the same type are combined. Combinations of units with
different types cannot be used.
2EN
Digital Inverter
2SAFETY PRECAUTIONS
•Ensure that all Local, National and International regulations are satisfied.
•Read these “SAFETY PRECAUTIONS” carefully before installation.
•The precautions described below include important items regarding safety.
Observe them without fail.
•After the installation work, perform a trial operation to check for any problem.
Follow the Owner’s Manual to explain to the customer how to use and maintain the unit.
•Ask the customer to keep the Installation Manual together with the Owner’s Manual.
WARNING
•Ask an authorized dealer or qualified installation professional to install/maintain the air conditioner.
Perform installation work properly according to the Installation Manual.
Inappropriate installation may result in water leakage, electric shock or fire.
•Be sure to connect earth wire (grounding work).
Incomplete grounding cause an electric shock.
Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone wires.
•Turn off the main power supply switch or breaker before attempting any electrical work and maintenance.
Make sure all power switches are off. Failure to do so may cause electric shock.
Use an exclusive power circuit for the air conditioner. Use the rated voltage.
•Connect the connecting wire correctly.
If the connecting wire is incorrect, electric parts may be damaged.
•When moving the air conditioner for installation to another place, be very careful not to allow the specified
refrigerant (R410A) to become mixed with any other gaseous body into the refrigeration cycle.
If air or any other gas mixes with the refrigerant, the gas pressure in the refrigeration cycle will become abnormally high and
it may result in the pipe bursting or personal injuries.
•Do not modify this unit by removing any of the safety guards or by by-passing any of the safety interlock switches.
•Do not touch the intake or aluminum fins of the outdoor unit.
Doing so may result in injury.
•Tighten the flare nut with a torque wrench in the specified manner.
Excessive tightening of the flare nut may cause a crack in the flare nut after a long period, which may result in refrigerant
leakage.
•Install the air conditioner securely in a location where the base can sustain the weight of the unit adequately.
•Perform the specified installation work to guard against an earthquake.
If the air conditioner is not installed appropriately, accidents may occur due to the unit falling.
•If refrigerant gas has leaked during the installation work, ventilate the room immediately.
If the leaked refrigerant gas comes in contact with fire, noxious gas may be generated.
•After the installation work, confirm that refrigerant gas does not leak.
If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas may be generated.
•Electrical work must be performed by a qualified electrician in accordance with the Installation Manual. Make sure
the air conditioner uses an exclusive power supply.
An insufficient power supply capacity or inappropriate installation may cause fire.
•Use only the specified wiring during the unit installation. Ensure that all terminals are securely fixed, so preventing
any external forces having a negative effect on the terminals.
•When the air conditioner cannot cool or heat a room well, contact the dealer from whom you purchased the air
conditioner as refrigerant leakage is considered as the cause.
In the case of repair that requires refill of refrigerant, ask service personnel about details of the repair.
The refrigerant used in the air conditioner is harmless.
Generally, the refrigerant does not leak. However, if the refrigerant leaks in a room and a heater or stove burner in the room
catches fire, it may generate toxic gas.
When you ask service personnel for repairing refrigerant leakage, confirm that the leakage portion has been completely
repaired.
•Conform to the regulations of the local electric company when wiring the power supply.
Inappropriate grounding may cause electric shock.
•Do not install the air conditioner in a location that may be subjected to a risk of exposure to a combustible gas.
If a combustible gas leaks and becomes concentrated around the unit, a fire may occur.
EN3
Digital Inverter
•Install the refrigerant pipe securely during the installation work before operating the air conditioner.
If the compressor is operated with the valve open and without the refrigerant pipe, the compressor sucks air and the
refrigeration cycle is overpressurized, which may cause a burst or injury.
•When carrying out the pump-down work, shut down the compressor before disconnecting the refrigerant pipe.
Disconnecting the refrigerant pipe with the service valve left open and with the compressor still operating will cause air, etc.
to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly resulting in
rupturing, injury, etc.
CAUTION
•Do not climb onto or place objects on top of the outdoor unit.
You may fall or the objects may fall off of the outdoor unit and result in injury.
•Wear heavy gloves during the installation work to avoid injury.
To Disconnect the Appliance from the Main Power Supply
•This appliance must be connected to the main power supply by means of a switch with a contact separation of at least 3 mm.
•A 25 A installation fuse (all fuse types can be used) must be used for the power supply line of this conditioner.
3INSTALLATION OF NEW REFRIGERANT AIR
CONDITIONER
CAUTION
New Refrigerant Air Conditioner Installation
•THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY OZONE
LAYER.
R410A refrigerant is apt to be affected by impurities such as water, oxidizing membrane, and oils because the working pressure
of R410A refrigerant is approx. 1.6 times as that of refrigerant R22. Accompanied with the adoption of the new refrigerant, the
refrigerant oil has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or
refrigerant oil does not enter the new type refrigerant R410A air conditioner cycle.
To prevent mixing of refrigerant or refrigerant oil, the sizes of connecting sections of charging port on main unit and installation
tools are different from those of the conventional refrigerant units. Accordingly, special tools are required for the new refrigerant
(R410A) units. For connecting pipes, use new and clean piping materials with high pressure fittings made for R410A only, so
that water and/or dust does not enter.
4EN
Digital Inverter
Required Tools/Equipment and Precautions for Use
Prepare the tools and equipment listed in the following table before starting the installation work.
Newly prepared tools and equipment must be used exclusively.
Legend
: Prepared newly (Use for R410A only. Do not use for refrigerant R22 or R407C etc.)
Vacuuming/charging refrigerant
and operation check
Vacuum drying
Welding pipes
Prepared newly for R410A only
Prepared newly for R410A only
Unusable (Use the refrigerant charging measure
instead.)
Prepared newly
R22 (Conventional tools)
Usable if dimensions are adjusted.
R22 (Conventional tools)
For R410A only
Exclusive for Ø12.7 mm and Ø19.1 mm
R22 (Conventional tools)
R22 (Conventional tools)
R22 (Conventional tools)
Refrigerant Piping
New refrigerant (R410A)
When using the conventional piping
•When using the conventional piping with no indication of applicable refrigerant types, be sure to use it with a wall thickness
of 0.8 mm for Ø6.4 mm, Ø9.5 mm, and Ø12.7 mm, with a wall thickness of 1.0 mm for Ø15.9 mm, with a wall thickness of
1.2 mm for Ø19.1 mm, and with a wall thickness of 1.0 mm for Ø28.6 mm (half hard). Do not use the conventional piping with
a wall thickness less than these thicknesses due to insufficient pressure capacity.
When using general copper pipes
•Use general copper pipes with a wall thickness of 0.8 mm for Ø6.4 mm, Ø9.5 mm, and Ø12.7 mm, with a wall thickness of
1.0 mm for Ø15.9 mm, with a wall thickness of 1.2 mm for Ø19.1 mm, and with a wall thickness of 1.0 mm for Ø28.6 mm
(half hard).
Do not use any copper pipes with a wall thickness less than these thicknesses.
Flare nuts and flare machining
•The flare nuts and flare machining are different from those for the conventional refrigerant.
Use the flare nuts supplied with the air conditioner or those for R410A.
Be sure to prepare to the following items before installation.
Length of refrigerant pipe
Length of refrigerant pipe
connected to indoor/
outdoor unit
7.5 to 30 m
*31 to 70 m
*If the total length of the refrigerant pipe exceeds 30 m,
add refrigerant in the amount given in the “Adding
additional refrigerant”.
*Do not connect a refrigerant pipe that is shorter than
7.5 m.
This may cause a malfunction of the compressor or other
devices.
Addition of refrigerant is
unnecessary at the local site.
<Addition of refrigerant>
Add 40 g of refrigerant for
every 1 m of piping that
exceeds 30 m.
Airtight test
1. Before starting an airtight test, further tighten the spindle
valves on the gas and liquid sides.
2. Pressurize the pipe with nitrogen gas charged from the
service port to the design pressure (4.15 MPa) to
conduct an airtight test.
3. After the airtight test is completed, evacuate the nitrogen
gas.
Item
Earthing
WARNING
Make sure that proper earthing is provided.
Improper earthing may cause an electric shock. For details
on how to check earthing, contact the dealer who installed
the air conditioner or a professional installation company.
•Proper earthing can prevent charging of electricity on the
outdoor unit surface due to the presence of a high
frequency in the frequency converter (inverter) of the
outdoor unit, as well as prevent electric shock. If the
outdoor unit is not properly earthed, you may be exposed
to an electric shock.
•Be sure to connect the earth wire (grounding work).
Incomplete grounding can cause an electric shock.
Do not connect ground wires to gas pipes, water pipes,
lightning rods or ground wires for telephone wires.
Test Run
Turn on the leakage breaker at least 12 hours before starting
a test run to protect the compressor during startup.
CAUTION
Incorrect installation work may result in a malfunction or
complaints from customers.
Air purge
•To purge air, use a vacuum pump.
•Do not use refrigerant charged in the outdoor unit to
purge air. (The air purge refrigerant is not contained in
the outdoor unit.)
Electrical wiring
•Be sure to fix the power wires and indoor/outdoor
connecting wires with clamps so that they do not come
into contact with the cabinet, etc.
6EN
Digital Inverter
Installation Location
WARNING
Install the outdoor unit properly in a location that is
durable enough to support the weight of the outdoor
unit.
Insufficient durability may cause the outdoor unit to fall,
which may result in injury.
This outdoor unit has a weight of about 135 kg. Pay special
attention when installing the unit onto a wall surface.
CAUTION
Do not install the outdoor unit in a location that is
subject to combustible gas leaks.
Accumulation of combustible gas around the outdoor unit
may cause a fire.
Install the outdoor unit in a location that meets the
following conditions after the customer’s consent is
obtained.
•A well-ventilated location free from obstacles near the air
inlets and air outlet
•A location that is not exposed to rain or direct sunlight
•A location that does not increase the operating noise or
vibration of the outdoor unit
•A location that does not produce any drainage problems
from discharged water
Do not install the outdoor unit in the following locations.
•A location with a saline atmosphere (coastal area) or one
that is full of sulfide gas (hot-spring area) (Special
maintenance is required.)
•A location subject to oil, vapor, oily smoke, or corrosive
gases
•A location in which organic solvent is used
•A location where high-frequency equipment (including
inverter equipment, private power generator, medical
equipment, and communication equipment) is used
(Installation in such a location may cause malfunction of
the air conditioner, abnormal control or problems due to
noise from such equipment.)
•A location in which the discharged air of the outdoor unit
blows against the window of a neighboring house
•A location where the operating noise of the outdoor unit is
transmitted
•When the outdoor unit is installed in an elevated position,
be sure to secure its feet.
•A location in which drain water poses any problems.
CAUTION
1. Install the outdoor unit in a location where the discharge
air is not blocked.
2. When an outdoor unit is installed in a location that is
always exposed to strong winds like a coast or on the
high stories of a building, secure normal fan operation by
using a duct or wind shield.
3. When installing the outdoor unit in a location that is
constantly exposed to strong winds such as on the upper
stairs or rooftop of a building, apply the windproofing
measures referred to in the following examples.
1) Install the unit so that its discharge port faces the
wall of the building.
Keep a distance 500 mm or more between the unit
and wall surface.
500 mm
2) Consider the wind direction during the operational
season of the air conditioner, and install the unit so
that the discharge port is set at a right angle relative
to the wind direction.
Strong wind
Strong wind
• When using an air conditioner under low outside
temperature conditions (Outside temp:-5 °C or lower)
in COOL mode, prepare a duct or wind shield so that it
is not affected by the wind.
<Example>
Wind shield
EN7
Wind shield
Digital Inverter
Necessary Space for Installation
(Unit: mm)
Obstacle at rear side
Upper side is free
1. Single unit installation
more
150 or
2. Obstacles on both right and left sides
The height of the
more
200 or
150 or
more
3. Serial installation of two or more units
obstacle should be
lower than the height of
the outdoor unit.
250 or
more
Obstacle in front
Above unit is free
1. Single unit installation
500 or
2. Serial installation of two or more units
Obstacle also at the above unit
1,000 or
more
800 or
more
more
more
1,000 or
150 or
more
The height of the obstacle should be lower than the height
of the outdoor unit.
250 or
more
250 or
more
Obstacle also above unit
150 or
more
more
500 or
250 or
more
200 or more
Obstacles in both front and rear of unit
Open above and to the right and left of the unit.
The height of an obstacle in both the front and rear of the
unit, should be lower than the height of the outdoor unit.
Standard installation
1. Single unit installation
more
150 or
more
1,000 or
2. Serial installation of two or more units
more
200 or
250 or
more
200 or
more
1,000 or
more
8EN
Loading...
+ 18 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.