Toshiba RAS-M24N3KV2-E Service Manual

SERVICE MANUAL
AIR-CONDITIONER
SPLIT TYPE
Indoor Unit
FILE NO. SVM-12087
<High Wall, Heat Pump Type>
RAS-M24N3KV2-E
R410A
FILE NO. SVM-12087
CONTENTS
1. SAFETY PRECAUTIONS .......................................................................... 2
2. SPECIFICATIONS...................................................................................... 4
3. REFRIGERANT R410A ............................................................................. 5
4. CONSTRUCTION VIEWS ........................................................................ 13
5. WIRING DIAGRAM .................................................................................. 14
6. SPECIFICATIONS OF ELECTRICAL PARTS ........................................ 15
7. REFRIGERANT CYCLE DIAGRAM ........................................................ 16
8. CONTROL BLOCK DIAGRAM ................................................................ 17
9. OPERATION DESCRIPTION ................................................................... 18
10. INSTALLATION PROCEDURE ................................................................ 38
11. HOW TO DIAGNOSE THE TROUBLE ...................................................... 50
12. HOW TO REPLACE THE MAIN PARTS ................................................... 67
13. EXPLODED VIEWS AND PARTS LIST ................................................... 74
1
13-1. Indoor Unit
FILE NO. SVM-12087
13. EXPLODED VIEWS AND PARTS LIST
Location Part Location Part
No. No. No. No.
201 43T21407 MOTOR FAN 222 43T39020 BAND, MOTOR, LEFT
202 43T22312 BEARING ASSY, MOLD 223 43T39023 BAND,MOTOR, RIGHT DOWN
203 43T70313 HOSE, DRAIN 224 43T39022 BAND, MOTOR, RIGHT UP
204 43T20016 FAN, ASSY, CROSS FLOW 225 43T09040 LOUVER, HORIZONTAL
205 43T49010 PIPE, SHIELD 226 43T03384 BODY ASSY, BACK
206 43T83305 HOLDER, REMOTE CONTROL 228 43T09471 GRILLE OF AIR INLET ASSY
207 43T82008 PLATE, INSTALLATION 229 43T80331 FILTER-AIR
209 43T19333 HOLDER, SENSOR 230 43T00594 FRONT PANEL ASSY
210 43T49043 HOLDER, PIPE 232 43T62031 COVER, TERMINAL
212 43T39021 BASE, BEARING 235 43T44031 EVAPORATOR ASSY
218 43T79313 CAP, DRAIN 238 43T66317 WIRELESS REMOTE CONTROLLER
Description Description
74
FILE NO. SVM-12087
1. SAFETY PRECAUTIONS
For general public use
Power supply cord of parts of appliance for outdoor use shall be at least polychloroprene sheathed flexible cord (design H07RN-F) or cord designation 60245 IEC66. (Shall be installed in accordance with national wiring regulations.)
• Read this “SAFETY PRECAUTIONS” carefully before servicing.
• The precautions described below include the important items regarding safety. Observe them without fail.
• After the servicing work, perform a trial operation to check for any problem.
• Turn off the main power supply switch (or breaker) before the unit maintenance.
CAUTION
New Refrigerant Air Conditioner Installation
• THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY OZONE LAYER.
R410A refrigerant is apt to be affected by impurities such as water, oxidizing membrane, and oils because the working pressure of R410A refrigerant is approx. 1.6 times of refrigerant R22. Accompanied with the adoption of the new refrigerant, the refrigeration machine oil has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigeration machine oil does not enter into the new type refrigerant R410A air conditioner circuit.
To prevent mixing of refrigerant or refrigerating machine oil, the sizes of connecting sections of charging port on main unit and installation tools are different from those used for the conventional refrigerant units.
Accordingly, special tools are required for the new refrigerant (R410A) units. For connecting pipes, use new and clean piping materials with high pressure fittings made for R410A only, so that water and/or dust does not enter. Moreover, do not use the existing piping because there are some problems with pressure fittings and possible impurities in existing piping.
CAUTION
TO DISCONNECT THE APPLIANCE FROM THE MAIN POWER SUPPLY
This appliance must be connected to the main power supply by a circuit breaker or a switch with a contact separation of at least 3 mm.
DANGER
• ASK AN AUTHORIZED DEALER OR QUALIFIED INSTALLATION PROFESSIONAL TO INSTALL/ MAINTAIN THE AIR CONDITIONER.
INAPPROPRIATE SERVICING MAY RESULT IN WATER LEAKAGE, ELECTRIC SHOCK OR FIRE.
• TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
DANGER: HIGH VOLTAGE
The high voltage circuit is incorporated. Be careful to do the check service, as the electric shock may be caused in case of touching parts
on the P.C. board by hand.
• CORRECTLY CONNECT THE CONNECTING CABLE. IF THE CONNECTING CABLE IS INCOR­RECTLY CONNECTED, ELECTRIC PARTS MAY BE DAMAGED.
• CHECK THAT THE EARTH WIRE IS NOT BROKEN OR DISCONNECTED BEFORE SERVICE AND INSTALLATION. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
2
FILE NO. SVM-12087
• DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS. FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
• TO PREVENT THE INDOOR UNIT FROM OVERHEATING AND CAUSING A FIRE HAZARD, PLACE THE UNIT WELL AWAY (MORE THAN 2 M) FROM HEAT SOURCES SUCH AS RADIATORS, HEAT REGISTERS, FURNACE, STOVES, ETC.
• WHEN MOVING THE AIR CONDITIONER FOR INSTALLATION IN ANOTHER PLACE, BE VERY CARE­FUL NOT TO ALLOW THE SPECIFIED REFRIGERANT (R410A) TO BECOME MIXED WITH ANY OTHER GASEOUS BODY INTO THE REFRIGERATION CIRCUIT. IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT, THE GAS PRESSURE IN THE REFRIGERATION CIRCUIT WILL BECOME ABNORMALLY HIGH AND IT MAY RESULT IN THE PIPE BURSTING AND POSSIBLE PERSONNEL INJURIES.
• IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE SERVICE WORK AND THE INSTALLATION WORK, IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE REFRIGERANT GAS IS HEATED, SUCH AS BY FIRE, GENERATION OF POISONOUS GAS MAY RESULT.
WARNING
• Never modify this unit by removing any of the safety guards or bypass any of the safety interlock switches.
• Do not install in a place which cannot bear the weight of the unit. Personal injury and property damage can result if the unit falls.
• After the installation work, confirm that refrigerant gas does not leak.
If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas may generate.
• The electrical work must be performed by a qualified electrician in accordance with the Installa­tion Manual. Make sure the air conditioner uses an exclusive circuit.
An insufficient circuit capacity or inappropriate installation may cause fire.
• When wiring, use the specified cables and connect the terminals securely to prevent external forces applied to the cable from affecting the terminals.
• Be sure to provide grounding.
Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone cables.
• Conform to the regulations of the local electric company when wiring the power supply.
Inappropriate grounding may cause electric shock.
CAUTION
• Exposure of unit to water or other moisture before installation may result in an electrical short. Do not store in a wet basement or expose to rain or water.
• Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify the noise level of the unit or where noise or discharged air might disturb neighbors.
• To avoid personal injury, be careful when handling parts with sharp edges.
• Perform the specified installation work to guard against an earthquake.
If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.
For Reference:
If a heating operation would be continuously performed for a long time under the condition that the outdoor temperature is 0°C or lower, drainage of defrosted water may be difficult due to freezing of the bottom plate, resulting in a trouble of the cabinet or fan.
It is recommended to procure an antifreeze heater locally for a safe installation of the air conditioner. For details, contact the dealer.
3
2. SPECIFICATIONS
FILE NO. SVM-12087
Unit model Outdoor Cooling capacity (kW) Cooling capacity range (kW) Heating capacity (kW) Heating capacity range (kW) Power supply Electric Indoor Operation mode Cooling Heating characteristic Running current (A) 0.38-0.35 0.38-0.35
Power consumption (W) 50 50 Power factor (%) 60 60
Outdoor Operation mode Cooling Heating
Running current (A) Power consumption (W) Power factor (%)
Starting current (A) COP (Cooling/Heating) Operating Indoor High (Cooling/Heating) (dB-A) noise Medium (Cooling/Heating) (dB-A)
Low (Cooling/Heating) (dB-A)
Outdoor (Cooling/Heating) (dB-A)
Indoor unit Dimension High (mm)
Medium (mm)
Depth (mm)
Net weight (kg) Fan motor output (W) Air flow rate (Cooling/Heating)
Outdoor unit Dimension High (mm)
Medium (mm)
Depth (mm)
Net weight (kg) Compressor Motor output (W)
Type
Model
Fan motor output (W)
Air flow rate (Cooling/Heating) Piping Type connection Indoor unit Liquid side (mm)
Gas side (mm)
Outdoor unit Liquid side (mm)
Gas side (mm) Maximum length (m) Maximum chargeless length (m) Maximum height difference (m)
Refrigerant Name of refrigerant
Weight (kg)
Wiring Power supply connection Interconnection Usable temperature range Indoor (Cooling/Heating)
Outdoor (Cooling/Heating)
Accessory Indoor unit Installation plate
Wireless remote controller
Batteries
Remote controller holder
Toshiba New IAQ filter
Mounting screw
Remote controller holder
Pan head wood screw
Installation manual
Owner's manual Outdoor unit Drain nipple
Water-proof rubber cap
(m3/min)
(m3/min)
(°C) (°C)
RAS-M24N3KV2-E
*
*
*
*
1Ph/50Hz/220-240V, 1Ph/60Hz/220V
*
*
*
* *
49/49 43/43 37/37
*
320
1050
228
13 30
18.9/19.2 * * * * *
*
* * *
Flare connection
6.3512.7
* *
* * *
R410A
*
3Wires:includes earth(Outdoor)
4Wires:includes earth
21-32/ 0-28
* 1 1 2 1 4
6(4x25L)
2(3.1Lx16L)
1 1 * *
*1 Refer to Service manual of the multi outdoor unit to be combined. The specifications may be subject to change without notice for purpose of improvement.
4
3. REFRIGERANT R410A
FILE NO. SVM-12087
This air conditioner adopts the new refrigerant HFC (R410A) which does not damage the ozone layer.
The working pressure of the new refrigerant R410A is 1.6 times higher than conventional refrigerant (R22). The refrigerating oil is also changed in accordance with change of refrigerant, so be careful that water, dust, and existing refrigerant or refrigerating oil are not entered in the refrigerant cycle of the air conditioner using the new refrigerant during installation work or servicing time.
The next section describes the precautions for air conditioner using the new refrigerant. Conforming to contents of the next section together with the general cautions included in this manual, perform the correct and safe work.
3-1. Safety During Installation/Servicing
As R410A’s pressure is about 1.6 times higher than that of R22, improper installation/servicing may cause a serious trouble. By using tools and materials exclusive for R410A, it is necessary to carry out installation/servicing safely while taking the following precautions into consideration.
1. Never use refrigerant other than R410A in an air conditioner which is designed to operate with R410A.
If other refrigerant than R410A is mixed, pressure in the refrigeration cycle becomes abnormally high, and it may cause personal injury, etc. by a rupture.
2. Confirm the used refrigerant name, and use tools and materials exclusive for the refrigerant R410A.
The refrigerant name R410A is indicated on the visible place of the outdoor unit of the air condi­tioner using R410A as refrigerant. To prevent mischarging, the diameter of the service port differs from that of R22.
3. If a refrigeration gas leakage occurs during installation/servicing, be sure to ventilate fully.
If the refrigerant gas comes into contact with fire, a poisonous gas may occur.
4. When installing or removing an air conditioner, do not allow air or moisture to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture or personal injury may be caused.
5. After completion of installation work, check to make sure that there is no refrigeration gas leakage.
If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
6. When an air conditioning system charged with a large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, even when refrigerant leaks, its concentration does not exceed the marginal level.
If the refrigerant gas leakage occurs and its concentration exceeds the marginal level, an oxygen starvation accident may result.
7. Be sure to carry out installation or removal according to the installation manual.
Improper installation may cause refrigeration trouble, water leakage, electric shock, fire, etc.
8. Unauthorized modifications to the air conditioner may be dangerous.
If a breakdown occurs please call a qualified air conditioner technician or electrician.
Improper repair may result in water leakage, electric shock and fire, etc.
3-2. Refrigerant Piping Installation
3-2-1. Piping Materials and Joints Used
For the refrigerant piping installation, copper pipes and joints are mainly used.
Copper pipes and joints suitable for the refrigerant must be chosen and installed.
Furthermore, it is necessary to use clean copper pipes and joints whose interior surfaces are less affected by contaminants.
1. Copper Pipes
It is necessary to use seamless copper pipes which are made of either copper or copper alloy and it is desirable that the amount of residual oil is less than 40 mg/10 m.
Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the interior surface).
Otherwise, the expansion valve or capillary tube may become blocked with contaminants.
As an air conditioner using R410A incurs pres­sure higher than when using R22, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in Table 3-2-1.
Never use copper pipes thinner than 0.8 mm even when it is available on the market.
5
Table 3-2-1 Thicknesses of annealed copper pipes
Thickness (mm)
FILE NO. SVM-12087
Nominal diameter
1/4
3/8
1/2
5/8
Outer diameter (mm)
6.35
9.52
12.70
15.88
R410A R22
0.80 0.80
0.80 0.80
0.80 0.80
1.00 1.00
2. Joints
For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants. a) Flare Joints
Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds 20 mm. In such a case, socket joints can be used.
Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables 3-2-3 to 3-2-6 below.
b) Socket Joints
Socket joints are such that they are brazed for connections, and used mainly for thick pipings whose diameter is larger than 20 mm.
Thicknesses of socket joints are as shown in Table 3-2-2.
Table 3-2-2 Minimum thicknesses of socket joints
Nominal diameter
1/4
3/8
1/2
5/8
Reference outer diameter of
copper pipe jointed (mm)
6.35
9.52
12.70
15.88
Minimum joint thickness
(mm)
0.50
0.60
0.70
0.80
3-2-2. Processing of Piping Materials
When performing the refrigerant piping installation, care should be taken to ensure that water or dust does not enter the pipe interior, that no other oil than lubricating oils used in the installed air-water heat pump is used, and that refrigerant does not leak. When using lubricating oils in the piping processing, use such lubricating oils whose water content has been removed. When stored, be sure to seal the container with an airtight cap or any other cover.
1. Flare processing procedures and precautions
a) Cutting the Pipe
By means of a pipe cutter, slowly cut the pipe so that it is not deformed.
b) Removing Burrs and Chips
If the flared section has chips or burrs, refrigerant leakage may occur. Carefully remove all burrs and clean the cut surface before installation.
c) Insertion of Flare Nut
6
A
ØD
d) Flare Processing
Make certain that a clamp bar and copper pipe have been cleaned.
By means of the clamp bar, perform the flare processing correctly.
Use either a flare tool for R410A or conven­tional flare tool.
Flare processing dimensions differ according to the type of flare tool.
When using a conventional flare tool, be sure to secure “dimension A” by using a gauge for size adjustment.
Table 3-2-3 Dimensions related to flare processing for R410A
FILE NO. SVM-12087
Fig. 3-2-1 Flare processing dimensions
Nominal
diameter
1/4 6.35 0.8
3/8 9.52 0.8
1/2 12.70 0.8
5/8 15.88 1.0
Nominal
diameter
1/4 6.35 0.8
3/8 9.52 0.8
Outer
diameter
(mm)
Table 3-2-4 Dimensions related to flare processing for R22
Outer
diameter
(mm)
Thickness
(mm)
Thickness
(mm)
Flare tool for R410A
clutch type
0 to 0.5
0 to 0.5
0 to 0.5
0 to 0.5
Flare tool for R22
clutch type
0 to 0.5
0 to 0.5
A (mm)
Conventional flare tool
Clutch type Wing nut type
1.0 to 1.5 1.5 to 2.0
1.0 to 1.5 1.5 to 2.0
1.0 to 1.5 2.0 to 2.5
1.0 to 1.5 2.0 to 2.5
A (mm)
Conventional flare tool
Clutch type Wing nut type
0.5 to 1.0 1.0 to 1.5
0.5 to 1.0 1.0 to 1.5
1/2 12.70 0.8
5/8 15.88 1.0
Table 3-2-5 Flare and flare nut dimensions for R410A
Nominal Outer diameter Thickness
diameter (mm) (mm)
1/4 6.35 0.8
3/8 9.52 0.8
1/2 12.70 0.8
5/8 15.88 1.0
7
0 to 0.5
0 to 0.5
Dimension (mm)
ABCD
9.1 9.2 6.5 13
13.2 13.5 9.7 20
16.0 16.6 12.9 23
19.0 19.7 16.0 25
0.5 to 1.0 1.5 to 2.0
0.5 to 1.0 1.5 to 2.0
Flare nut width
(mm)
17
22
26
29
Table 3-2-6 Flare and flare nut dimensions for R22
FILE NO. SVM-12087
Nominal Outer diameter Thickness
diameter (mm) (mm)
1/4 6.35 0.8
3/8 9.52 0.8
1/2 12.70 0.8
5/8 15.88 1.0
3/4 19.05 1.0
45˚ to 46˚
B A
Dimension (mm)
ABCD
9.0 9.2 6.5 13
13.0 13.5 9.7 20
16.0 16.2 12.9 20
19.0 19.7 16.0 23
23.3 24.0 19.2 34
D
C
43˚ to 45˚
Flare nut width
(mm)
17
22
24
27
36
Fig. 3-2-2 Relations between flare nut and flare seal surface
2. Flare Connecting Procedures and Precautions
a) Make sure that the flare and union portions do not have any scar or dust, etc. b) Correctly align the processed flare surface with the union axis. c) Tighten the flare with designated torque by means of a torque wrench.
The tightening torque for R410A is the same as that for conventional R22. Incidentally, when the torque is weak, the gas leakage may occur.
When it is strong, the flare nut may crack and may be made non-removable. When choosing the tightening torque, comply with values designated by manufacturers. Table 3-2-7 shows reference values.
NOTE :
When applying oil to the flare surface, be sure to use oil designated by the manufacturer. If any other oil is used, the lubricating oils may deteriorate and cause the compressor to burn out.
Table 3-2-7 Tightening torque of flare for R410A [Reference values]
Nominal
diameter
Outer
diameter
(mm)
Tightening torque
N•m (kgf•cm)
1/4 6.35 14 to 18 (140 to 180)
torque wrenches available on the market
Tightening torque of
N•m (kgf•cm)
16 (160), 18 (180)
3/8 9.52 33 to 42 (330 to 420)
1/2 12.70 50 to 62 (500 to 620)
5/8 15.88 63 to 77 (630 to 770)
8
42 (420)
55 (550)
65 (650)
FILE NO. SVM-12087
3-3. Tools
3-3-1. Required Tools
The service port diameter of packed valve of the outdoor unit in the air-water heat pump using R410A is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.
1. Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))
2. Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)
3. Tools commonly used for R410A and for conventional refrigerant (R22) The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
No.
1
2
3
4
5
6
7
8
9
10
Used tool
Flare tool
Copper pipe gauge for adjusting projection margin
Torque wrench (For Ø12.7)
Gauge manifold
Charge hose
Vacuum pump adapter
Electronic balance for refrigerant charging
Refrigerant cylinder
Leakage detector
Charging cylinder
Usage
Pipe flaring
Flaring by conventional flare tool
Connection of flare nut
Evacuating, refrigerant charge, run check, etc.
Vacuum evacuating
Refrigerant charge
Refrigerant charge
Gas leakage check
Refrigerant charge
air-water heat pump installation
R410A
Existence of Whether conventional new equipment equipment can be for R410A used
Ye s (Note 1)
Ye s (Note 1)
Ye s No
Ye s No
Ye s No
Ye s No
Ye s No
Ye s No
(Note 2) No
Conventional air-water heat pump installation
Whether new equipment can be used with conventional refrigerant
Ye s
(Note 1)
No
No
Ye s
Ye s
No
Ye s
No
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
(Note 2) Charging cylinder for R410A is being currently developed.
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also for R22 are neces­sary as the general tools.
1. Vacuum pump Use vacuum pump by attaching vacuum pump adapter.
2. Torque wrench (For Ø6.35, Ø9.52)
3. Pipe cutter
4. Reamer
5. Pipe bender
6. Level vial
7. Screwdriver (+, –)
8. Spanner or Monkey wrench
9. Hole core drill (Ø65)
10. Hexagon wrench (Opposite side 4mm)
11. Tape measure
12. Metal saw
Also prepare the following equipments for other installation method and run check.
1. Clamp meter
2. Thermometer
3. Insulation resistance tester
4. Electroscope
9
FILE NO. SVM-12087
3-4. Recharging of Refrigerant
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps.
Recover the refrigerant, and check no refrigerant remains in the equipment.
Connect the charge hose to packed valve service port at the outdoor unit’s gas side.
Connect the charge hose to the vacuum pump adapter.
Open fully both packed valves at liquid and gas sides.
When the compound gauge’s pointer has indicated –0.1 Mpa (–76 cmHg), place the handle Low in the fully closed position, and turn off the vacuum pump’s power switch.
Keep the status as it is for 1 to 2 minutes, and ensure that the compound gauge’s pointer does not return.
Set the refrigerant cylinder to the electronic balance, connect the connecting hose to the cylinder and the connecting port of the electronic balance, and charge liquid refrigerant.
Place the handle of the gauge manifold Low in the fully opened position, and turn on the vacuum pump’s power switch. Then, evacuating the refrigerant in the cycle.
(For refrigerant charging, see the figure below.)
1. Never charge refrigerant exceeding the specified amount.
2. If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.
3. Do not carry out additional charging. When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the
refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high pressure, and may cause a rupture or personal injury.
(Indoor unit)
Opened
(Outdoor unit)
Refrigerant cylinder
(with siphon)
Check valve
Opened Open/close valve for charging
Electronic balance for refrigerant charging
Fig. 3-4-1 Configuration of refrigerant charging
Opened
Closed
Service port
– 10
FILE NO. SVM-12087
1. Be sure to make setting so that liquid can be charged.
2. When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant. Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the cylinder upside down if cylinder is not equipped with siphon.
[ Cylinder with siphon ] [ Cylinder without siphon ]
Gauge manifold
OUTDOOR unit
Refrigerant
cylinder
Gauge manifold
OUTDOOR unit
cylinder
Refrigerant
Electronic
balance
R410A refrigerant is HFC mixed refrigerant. Therefore, if it is charged with gas, the composi­tion of the charged refrigerant changes and the characteristics of the equipment varies.
3-5. Brazing of Pipes
3-5-1. Materials for Brazing
1. Silver brazing filler
Silver brazing filler is an alloy mainly composed of silver and copper. It is used to join iron, copper or copper alloy, and is relatively expensive though it excels in solderability.
2. Phosphor bronze brazing filler
Phosphor bronze brazing filler is generally used to join copper or copper alloy.
Electronic
balance
Siphon
Fig. 3-4-2
1. Phosphor bronze brazing filler tends to react with sulfur and produce a fragile compound water solution, which may cause a gas leakage. Therefore, use any other type of brazing filler at a hot spring resort, etc., and coat the surface with a paint.
2. When performing brazing again at time of servicing, use the same type of brazing filler.
3-5-2. Flux
3. Low temperature brazing filler
Low temperature brazing filler is generally called solder, and is an alloy of tin and lead. Since it is weak in adhesive strength, do not use it for refrigerant pipes.
1. Reason why flux is necessary
• By removing the oxide film and any foreign matter on the metal surface, it assists the flow of brazing filler.
• In the brazing process, it prevents the metal surface from being oxidized.
• By reducing the brazing filler’s surface tension, the brazing filler adheres better to the treated metal.
– 11
Nitrogen gas
cylinder
Pipe
Flow meter
M
Stop valve
From Nitrogen cylinder
Nitrogen gas
Rubber plug
2. Characteristics required for flux
• Activated temperature of flux coincides with the brazing temperature.
• Due to a wide effective temperature range, flux is hard to carbonize.
• It is easy to remove slag after brazing.
• The corrosive action to the treated metal and brazing filler is minimum.
• It excels in coating performance and is harm­less to the human body.
As the flux works in a complicated manner as described above, it is necessary to select an adequate type of flux according to the type and shape of treated metal, type of brazing filler and brazing method, etc.
3. Types of flux
• Noncorrosive flux
Generally, it is a compound of borax and boric acid.
It is effective in case where the brazing tem­perature is higher than 800°C.
• Activated flux
Most of fluxes generally used for silver brazing are this type.
It features an increased oxide film removing capability due to the addition of compounds such as potassium fluoride, potassium chloride and sodium fluoride to the borax-boric acid compound.
4. Piping materials for brazing and used brazing filler/flux
FILE NO. SVM-12087
3-5-3. Brazing
As brazing work requires sophisticated techniques, experiences based upon a theoretical knowledge, it must be performed by a person qualified.
In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to proceed with brazing while letting dry Nitrogen gas (N2) flow.
Never use gas other than Nitrogen gas.
1. Brazing method to prevent oxidation
1) Attach a reducing valve and a flow-meter to the Nitrogen gas cylinder.
2) Use a copper pipe to direct the piping mate­rial, and attach a flow-meter to the cylinder.
3) Apply a seal onto the clearance between the piping material and inserted copper pipe for Nitrogen in order to prevent backflow of the Nitrogen gas.
4) When the Nitrogen gas is flowing, be sure to keep the piping end open.
5) Adjust the flow rate of Nitrogen gas so that it is lower than 0.05 m (0.2kgf/cm2) by means of the reducing valve.
6) After performing the steps above, keep the Nitrogen gas flowing until the pipe cools down to a certain extent (temperature at which pipes are touchable with hands).
7) Remove the flux completely after brazing.
3
/Hr or 0.02 MPa
Piping material
Copper - Copper
1. Do not enter flux into the refrigeration cycle.
2. When chlorine contained in the flux remains
3. When adding water to the flux, use water
4. Remove the flux after brazing.
Copper - Iron
Iron - Iron
Used brazing filler
Phosphor copper
Silver
Silver
Used flux
Do not use
Paste flux
Vapor flux
within the pipe, the lubricating oil deterio­rates. Therefore, use a flux which does not contain chlorine.
which does not contain chlorine (e.g. distilled water or ion-exchange water).
Fig. 3-5-1
Prevention of oxidation during brazing
– 12
FILE NO. SVM-12087
Indoor Unit
Grille Inlet
Front Panel
73.5 7 50
Knock out system Knock out system
Heat exchanger
320
4. CONSTRUCTION VIEWS
Air Inlet
1050
Air filter
Air outlet
243
50
73.5 7
Drain hose (0.5m)
Connecting pipe (0.39m)
(Flare
50
72 78
132
525
Hanger Hanger
Connecting pipe (0.49m)
12.70)
85
Hanger
786
235
215 215
235
78 72
150 200 222 200 278
(Flare
23
50
Wireless remote controller
Remote controller holder
6.35)
For stud bold ( For stud bold (
57
63
6) 8~
172
18
149
17.5
10)
320
40
47
65
215.5
Hanger
262.5
Center line
262.5
Installation plate outline
13
Hanger
153.5
Outline of indoor unit
65
109
40
Indoor Unit
Outdoor Terminal Block
5. WIRING DIAGRAM
Indoor Terminal Block
1
1
BLK
2
2
WHI
3
3
RED
FILE NO. SVM-12087
GRN&YEL
Heat exchanger
SHEET METAL
CN01
3
(WHI)
3
Fuse F01
T3.15A 250VAC
1 1 2
2
Heat Exchanger Sensor
(TCJ)
Heat Exchanger Sensor
(TC)
Thermo Sensor
(TA)
CN63 (YEL)
2112
CN62 (BLU)
11 22
CN61 (WHI)
BLU
1
BLU
2
2
BLU
3
3
BLU
4
4
BLU
5
5
BLU
6
6
BLU
7
7
BLU
8
8
BLU
9
9
BLU
10 10
WP-027
WHI
11111
CN10
(WHI)
Varistor
CN21
(WHI)
Wireless Unit Assembly
21
CN11
(BLK)
1 1
Line Filter
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
BLK
CN51
CN02
6 6
CN31
(WHI)
2 2
4 4
CN32 (WHI)
DC5V DC12V DC15V
Main P.C Board
MCC-5045
1 32 5
CN81 (WHI)
11
33 44 55
DC Motor
Fan Motor
WHI
1 1
11
YEL
22
YEL
3 3
33
YEL
44
YEL
5 5
55
Louver Motor
CN22
(WHI)
1 2 3 4
Color indication
YEL:YELLOW BLK:BLACK RED:RED BLU:BLUE
Power Supply Circuit
WHI:WHITE GRN&YEL: GREEN & YELLOW
6
4
14
IIndoor Unit
FILE NO. SVM-12087
6. SPECIFICATIONS OF ELECTRICAL PARTS
No.
1
Fan motor (for indoor)
2
Room temp. sensor (TA-sensor)
3
Heat exchanger temp. sensor (TC-sensor)
4
Heat exchange temp. sensor (TCJ-sensor)
5 Louver motor
Parts name
Type
MF-340-30-3
( — )
( — )
( — )
MSBPC20F04
Specifications
DC340V, 30W
10k at 25°C
10k at 25°C
10k at 25°C
Output (Rated) 1W, 16 poles, DE12V
15
7. REFRIGERANT CYCLE DIAGRAM
FILE NO. SVM-12087
P
Pressure measurement Gauge attaching port
Vacuum pump connecting port
Deoxidized copper pipe Outer dia. : 12.7mm
Thickness : 0.8mm
INDOOR UNIT
Indoor heat
exchanger
Cross flow fan
Deoxidized copper pipe Outer dia. : 6.35mm
Thickness : 0.8mm
Sectional shape of heat insulator
T1 Temp. measurement
TCJ
TC
TA
difference: * m
Allowable height
Per 1 unit
Max. : * m Min. : * m Chargeless : * m Charge : * m
Total
Max. : * m
Allowable pipe length
OUTDOOR UNIT *
NOTE :
* Refer to SERVICE MANUAL of connected outdoor unit.
The specification is different to each outdoor unit.
NOTE:
Gas leak check position
16
Indoor Unit
FILE NO. SVM-12087
8. CONTROL BLOCK DIAGRAM
Heat Exchanger Sensor (Tcj)
Heat Exchanger Sensor (Tc)
Room Temperature Sensor (Ta)
Infrared Rays Signal Receiver
and Indication
Initializing Circuit
Clock Frequency
Oscillator Circuit
Power Supply Circuit
Converter (D.C circuit)
Noise Filter
M.C.U.
Functions
• Cold draft preventing Function
• 3-minute Delay at Restart for Compressor
• Fan Motor Starting Control
• Processing (Temperature Processing)
• Timer
• Serial Signal Communication
• Clean Function
Serial Signal Transmitter/Receiver
Indoor Unit Control Unit
Louver
Motor
Louver Motor Drive Control
Indoor Fan
Motor Control
Indoor
Fan Motor
From Outdoor Unit
220-240V ~50Hz
220V ~60Hz
REMOTE CONTROLLER
Serial Signal Communication
(Operation Command and Information)
Remote Controller
Infrared Rays, 36.7kHz
Operation (START/STOP)
Operation Mode Selection
AUTO, COOL, DRY, HEAT
Thermo. Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver AUTO Swing
Louver Direction Setting
ECO
Hi-POWER
COMFORT SLEEP
QUIET
QUIET
SLEEP (1, 3, 5, 9 OFF TIMER)
17
9. OPERATION DESCRIPTION
FILE NO. SVM-12087
9-1. Outline of Air Conditioner Control
This air conditioner is a capacity-variable type air conditioner, which uses DC motor for the indoor fan motor and the outdoor fan motor. And the capacity­proportional control compressor which can change the motor speed in the range from 11 to 120 rps is mounted. The DC motor drive circuit is mounted to the indoor unit. The compressor and the inverter to control fan motor are mounted to the outdoor unit.
The entire air conditioner is mainly controlled by the indoor unit controller.
The indoor unit controller drives the indoor fan motor based upon command sent from the remote controller, and transfers the operation command to the outdoor unit controller. The outdoor unit controller receives operation com­mand from the indoor unit side, and controls the outdoor fan and the pulse motor valve. (PMV) Besides, detecting revolution position of the compres­sor motor, the outdoor unit controller controls speed of the compressor motor by controlling output voltage of the inverter and switching timing of the supply power (current transfer timing) so that motors drive according to the operation command. And then, the outdoor unit controller transfers reversely the operating status information of the outdoor unit to control the indoor unit controller.
As the compressor adopts four-pole brushless DC motor, the frequency of the supply power from inverter to compressor is two-times cycles of the actual number of revolution.
1. Role of indoor unit controller
The indoor unit controller judges the operation commands from the remote controller and assumes the following functions.
• Judgment of suction air temperature of the indoor heat exchanger by using the indoor temp. sensor. (TA sensor)
• Judgment of the indoor heat exchanger tempera­ture by using heat exchanger sensor (TC sensor) (Prevent-freezing control, etc.)
• Louver motor control
• Indoor fan motor operation control
• LED (Light Emitting Diode) display control
• Transferring of operation command signal (Serial signal) to the outdoor unit
• Reception of information of operation status (Serial signal including outside temp. data) to the outdoor unit and judgment/display of error
• Air purifier operation control
2. Role of outdoor unit controller
Receiving the operation command signal (Serial signal) from the indoor unit controller, the outdoor unit performs its role.
• Compressor operation control
• Operation control of outdoor fan motor
• PMV control
• 4-way valve control
Operations followed to judgment
of serial signal from indoor side.
• Detection of inverter input current and current release operation
• Over-current detection and prevention operation to IGBT module (Compressor stop function)
• Compressor and outdoor fan stop function when serial signal is off (when the serial signal does not reach the board assembly of outdoor control by trouble of the signal system)
• Transferring of operation information (Serial signal) from outdoor unit controller to indoor unit controller
• Detection of outdoor temperature and operation revolution control
• Defrost control in heating operation (Temp. measurement by outdoor heat exchanger and control for 4-way valve and outdoor fan)
3. Contents of operation command signal (Serial signal) from indoor unit controller to outdoor unit controller
The following three types of signals are sent from the indoor unit controller.
• Operation mode set on the remote controller
• Compressor revolution command signal defined
by indoor temperature and set temperature (Correction along with variation of room tempera­ture and correction of indoor heat exchanger temperature are added.)
• Temperature of indoor heat exchanger
• For these signals ([Operation mode] and [Com-
pressor revolution] indoor heat exchanger tem­perature), the outdoor unit controller monitors the input current to the inverter, and performs the followed operation within the range that current does not exceed the allowable value.
4. Contents of operation command signal (Serial signal) from outdoor unit controller to indoor unit controller
The following signals are sent from the outdoor unit controller.
• The current operation mode
• The current compressor revolution
• Outdoor temperature
• Existence of protective circuit operation
For transferring of these signals, the indoor unit controller monitors the contents of signals, and judges existence of trouble occurrence.
Contents of judgment are described below.
• Whether distinction of the current operation status meets to the operation command signal
• Whether protective circuit operates When no signal is received from the outdoor
unit controller, it is assumed as a trouble.
18
FILE NO. SVM-12087
9-2. Operation Description
9-2. 1. Basic operation ........................................................................................................... 20
1. Operation control ................................................................................................... 20
2. Cooling/Heating operation ..................................................................................... 21
3. AUTO operation...................................................................................................... 21
4. DRY operation ........................................................................................................ 21
2. Indoor fan motor control.............................................................................................. 22
3. Capacity control .......................................................................................................... 24
4. Current release control ............................................................................................... 24
5. Release protective control by temperature of indoor heat exchanger ........................ 25
6. Louver control ............................................................................................................. 26
1) Louver position....................................................................................................... 26
2) Air direction adjustment ......................................................................................... 26
3) Swing ..................................................................................................................... 26
7. Defrost control (Only in heating operation)................................................................. 27
8. ECO operation ............................................................................................................ 27
9. Temporary operation................................................................................................... 27
10. Pulse motor valve (PMV) control ................................................................................ 28
11. Self-Cleaning function ................................................................................................ 28
12. Remote Controller-A or B selection ............................................................................ 29
13. QUIET mode ............................................................................................................... 30
14. COMFORT SLEEP ..................................................................................................... 30
15. Short Timer ................................................................................................................. 30
16. One Touch Comfort ..................................................................................................... 31
17. Hi POWER Mode ........................................................................................................ 31
9-3. Auto Restart Function
9-3-1. How to Set the Auto Restart Function .................................................................... 32
9-3-2. How to Cancel the Auto Restart Function.............................................................. 33
9-3-3. Power Failure during Timer Operation.................................................................... 33
9-4. Remote Controller
9-4-1. Remote Controller and Its Functions ..................................................................... 34
9-4-2. Operation of Remote Controller .............................................................................. 34
9-4-3. Names and Functions of Indications on Remote Controller ................................ 37
19
FILE NO. SVM-12087
Item
1. Basic operation
Operation flow and applicable data, etc.
1. Operation control
Receiving the user’s operation condition setup, the operation statuses of indoor/outdoor units are controlled.
1) The operation conditions are selected by the remote controller as shown in the below.
2) A signal is sent by ON button of the remote controller.
3) The signal is received by a sensor of the indoor unit and processed by the indoor controllers as shown in the below.
4) The indoor controller controls the indoor fan motor and louver motor.
5) The indoor controller sends the operation command to the outdoor controller, and sends/ receives the control status with a serial signal.
6) The outdoor controller controls the operation as shown in the left, and also controls the com­pressor, outdoor fan motor, 4-way valve and pulse motor valve.
Selection of
operation conditions
ON/OFF
Remote controller
Control contents of remote controller
• ON/OFF (Air conditioner / Air purifier)
• Operation select (COOL /HEAT / AUTO / DRY)
• Temperature setup
• Air direction
• Swing
• Air volume select (AUTO / LOW / LOW+ / MED / MED+ / HIGH)
• ECO • COMFORT SLEEP
• ON timer setup • QUIET
• OFF timer setup • PRESET
• Hi-POWER • ONE-TOUCH
Description
Signal receiving
Indoor unit control
Operation command
Serial signal send/receive
Serial signal send/receive
Outdoor unit control
Indoor unit
Indoor unit control
• Command signal generating function of indoor unit operation
• Calculation function (temperature calculation)
• Activation compensation function of indoor fan
• Cold draft preventive function
• Timer function
• Indoor heat exchanger release control
Outdoor unit
Outdoor unit control
• Frequency control of inverter output
• Waveform composite function
• Calculation function (Temperature calculation)
• AD conversion function
• Quick heating function
• Delay function of compressor reactivation
• Current release function
• GTr over-current preventive function
• Defrost operation function
Inverter
• Indoor fan motor
• Louver motor
~
• Compressor
• Outdoor fan motor
• 4-way valve
• Pulse Motor valve (PMV)
– 20
FILE NO. SVM-12087
Item
1. Basic operation
Operation flow and applicable data, etc.
2. Cooling/Heating operation
The operations are performed in the following parts by controls according to cooling/heating conditions.
1) Receiving the operation ON signal of the remote controller, the cooling or heating operation signal starts being transferred form the indoor controller to the outdoor unit.
2) At the indoor unit side, the indoor fan is operated according to the contents of “2. Indoor fan motor control” and the louver according to the contents of “8. Louver control”, respectively.
3) The outdoor unit controls the outdoor fan motor, compressor, pulse motor valve and 4-way valve according to the operation signal sent from the indoor unit.
Operation ON
Indoor unit control
Sending of operation command signal
Outdoor unit control
3. AUTO operation
Selection of operation mode As shown in the following figure, the operation starts by selecting automatically the status of room temperature (Ta) when starting AUTO operation.
*1. When reselecting the operation mode, the fan speed
is controlled by the previous operation mode.
Ta
Cooling operation
Ts + 1
Monitoring (Fan)
Ts – 1
Heating operation
Setup of remote controller
Indoor fan motor control / Louver control / Operation Hz Control (Requierment)
Compressor revolution control / Outdoor fan motor control / Operation Hz control (Include limit control) 4-way valve control In cooling operation: ON
Pulse Motor valve control
[ ]
In heating operation: OFF
1) Detects the room temperature (Ta) when the operation started.
2) Selects an operation mode from Ta in the left figure.
3) Fan operation continues until an operation mode is selected.
4) When AUTO operation has started within 2 hours after heating operation stopped and if the room temperature is 20°C or more, the fan operation is performed with ”Super Ultra LOW” mode for 3 minutes. Then, select an operation mode.
5) If the status of compressor-OFF continues for 15 minutes the room temperature after selecting an operation mode (COOL/HEAT), reselect an operation mode.
Description
4. DRY operation
DRY operation is performed according to the difference between room temperature and the setup temperature as shown below.
In DRY operation, fan speed is controlled in order to prevent lowering of the room temperature and to avoid air flow from blowing directly to persons.
[C]
Ta
+
1.0
+
0.5
L (W5)
(W5+W3) / 2
SL (W3)
Tsc
Fan speed
21
1) Detects the room temperature (Ta) when the DRY operation started.
2) Starts operation under conditions in the left figure according to the temperature difference between the room tempera­ture and the setup temperature (Tsc). Setup temperature (Tsc)
= Set temperature on remote controller
(Ts) + (0.0 to 1.0)
3) When the room temperature is lower 1°C or less than the setup temperature, turn off the compressor.
FILE NO. SVM-12087
Item
2. Indoor fan motor control
COOL ON
Fan speed setup
AUTO
Ta
[°C]
+2.5
a
+2.0
b
+1.5
c
+1.0
Operation flow and applicable data, etc.
<In cooling operation>
(This operation controls the fan speed at indoor unit side.) The indoor fan (cross flow fan) is operated by the phase-
control induction motor. The fan rotates in 5 stages in MANUAL mode, and in 5 stages in AUTO mode, respectively. (Table 1)
MANUAL
Indication
L
L+
M
M+
H
(Fig. 1)
Fan speed
W6
(L + M) / 2
W9
(M + H) / 2
WC
(Fig. 2)
Air volume AUTO
M+(WB)
*3
*4
*5
*3 : Fan speed = (M + –L) x 3/4 + L
*4 : Fan speed = (M + –L) x 2/4 + L
*5 : Fan speed = (M + –L) x 1/4 + L
Description
∗∗
Symbols
∗∗
UH: Ultra High H : High M+: Medium+ M : Medium L+ : Low+ L: Low L- : Low– UL : Ultra Low SUL : Super Ultra Low
* The fan speed broadly varies due
to position of the louver, etc. The described value indicates one under condition of inclining downward blowing.
1) When setting the fan speed to L, L+, M, M+ or H on the remote controller, the operation is performed with the constant speed shown in Fig. 1.
2) When setting the fan speed to AUTO on the remote controller, revolution of the fan motor is controlled to the fan speed level shown in Fig. 2 and Table 1 according to the setup tempera­ture, room temperature, and heat exchanger temperature.
+0.5
Ts c
d
L(W6)
e
(Table 1) Indoor fan air flow rate
Fan
speed
COOL HEAT DRY
level
WF WE WD WC WB WA W9 W8 W7 W6 W5 W4 W3 W2 W1
H
M+ M
ML+
L+ L– L+
L– UL L– UL UL
SUL SUL
UH
H
M+
L
SUL
(Linear approximation from M+ and L)
Fan speed Air flow rate
(rpm) (m
1250 1156 1250 1156 1250 1156 1230 1134 1130 1034 1070 957
1030 913
900 768 860 669 850 713 810 669 750 603 650 492 500 325 500 325
3
/h)
22
Loading...