1:1 Bi Flow Console
RAS-B10-B18UFV-E
Engineering
Databook
TCTC 09-006

1:1 Bi Flow Console: RAS-B10-B18UFV-E
Contents
Specifications
3
Dimensions of Indoor and outdoor units
4
Wiring Diagram
7
Sensible Capacity Table
9
Part Load Performance
11
Air Speed Distribution
14
Sound Characteristics (NC Curve)
17
- 2 -

Specifications
1:1 Bi Flow Console: RAS-B10-B18UFV-E
Technical specifications Heat Pump
Outdoor unit RAS-10SAV2-E RAS-13SAV2-E RAS-18SAV2-E
Indoor unit RAS-B10UFV-E RAS-B13UFV-E RAS-B18UFV-E
Cooling capacity kW 2,5 3,5 5,0
Cooling range (min. - max.) kW 1,1-3,1 1,1-4,1 1,0-5,7
Power input (min - rated - max.) kW C 0,23-0,60-0,82 0,23-0,97-1,35 0,20-1,66-1,95
EER 4,20 3,61 3,01
Energy efficiency class C A A B
Annual energy consumption kWh 298 485 830
Heating capacity kW 3,2 4,2 5,8
Heating range (min. - max.) kW 1,0-4,8 1,0-5,4 1,1-6,3
Power input (min - rated - max.) kW H 0,18-0,75-1,40 0,18-1,13-1,70 0,20-1,81-2,20
COP 4,27 3,73 3,21
Energy efficiency class H A A C
Indoor unit RAS-B10UFV-E RAS-B13UFV-E RAS-B18UFV-E
Air Flow (h) m3/h - l/s C 467-130 509-140 602-170
Sound pressure level (h/l) dB(A) C 39/26 40/27 46/34
Sound power level (h/l) dB(A) C 54/41 55/42 61/49
Air Flow (h) m3/h - l/s H 509-140 550-150 644-180
Sound pressure level (h/l) dB(A) H 39/26 40/27 46/34
Sound power level (h/l) dB(A) H 54/41 55/42 61/49
Dimensions (H x W x D) mm 600x700x220 600x700x220 600x700x220
Weight kg 16 16 16
Outdoor unit RAS-10SAV2-E RAS-13SAV2-E RAS-18SAV2-E
Air Flow (h) m3/h - l/s C 1800-500 2250-625 1914-532
Sound pressure level (h) dB(A) C 46 48 49
Sound power level (h) dB(A) C 59 61 64
Operating range °C C -10/46 -10/46 -10/46
Air Flow (h) m3/h - l/s H 1800-500 2250-625 1914-532
Sound pressure level (h) dB(A) H 47 50 50
Sound power level (h) dB(A) H 60 63 65
Operating range °C H -15/24 -15/24 -15/24
Dimensions (HxWxD) mm 550x780x290 550x780x290 550x780x290
Weight kg 33 33 39
Compressor type DC Rotary DC Rotary DC Twin Rotary
Flare connections (gas - liquid) 3/8" - 1/4" 3/8" - 1/4" 1/2" - 1/4"
Minimum pipe length m 2 2 2
Maximum pipe length m 20 20 20
Maximum height difference m 10 10 10
Chargeless pipe lenght m 15 15 15
Power supply V-ph-Hz
Filter Toshiba New IAQ Filter x 2
220/240-1-50 &
220-230/1/60
C = cooling mode
H = heating mode
220/240-1-50 &
220-230/1/60
220/240-1-50 &
220-230/1/60
- 3 -

1:1 Bi Flow Console: RAS-B10-B18UFV-E
Dimensions of Indoor and outdoor units
Indoor Unit:
- 4 -

Outdoor Unit:
1:1 Bi Flow Console: RAS-B10-B18UFV-E
- 5 -

1:1 Bi Flow Console: RAS-B10-B18UFV-E
Outdoor Unit:
RAS-18SAV2-E
- 6 -