3,473,470,15 x 1 = 0,150,5
5,695,690,15 x 1 = 0,150,5
7,017,010,15 x 1 = 0,150,5
6,386,380,15 x 2 = 0,300,5
7,817,810,15 x 2 = 0,300,5
7,967,960,15 x 2 = 0,300,5
7,967,960,15 x 2 = 0,300,5
8,058,050,15 x 2 = 0,300,5
8,158,150,15 x 2 = 0,300,5
8,058,050,15 x 3 = 0,450,5
9,349,340,15 x 3 = 0,450,5
9,349,340,15 x 3 = 0,450,5
9,349,340,15 x 3 = 0,450,5
3,293,290,15 x 1 = 0,150,5
5,425,420,15 x 1 = 0,150,5
6,676,670,15 x 1 = 0,150,5
6,066,060,15 x 2 = 0,300,5
7,447,440,15 x 2 = 0,300,5
7,587,580,15 x 2 = 0,300,5
7,587,580,15 x 2 = 0,300,5
7,707,700,15 x 2 = 0,300,5
7,767,760,15 x 2 = 0,300,5
7,657,650,15 x 3 = 0,450,5
8,898,890,15 x 3 = 0,450,5
8,898,890,15 x 3 = 0,450,5
8,898,890,15 x 3 = 0,450,5
3,123,120,15 x 1 = 0,150,5
5,165,160,15 x 1 = 0,150,5
6,376,370,15 x 1 = 0,150,5
5,785,780,15 x 2 = 0,300,5
7,097,090,15 x 2 = 0,300,5
7,237,230,15 x 2 = 0,300,5
7,237,230,15 x 2 = 0,300,5
7,317,310,15 x 2 = 0,300,5
7,407,400,15 x 2 = 0,300,5
7,307,300,15 x 3 = 0,450,5
8,488,480,15 x 3 = 0,450,5
8,488,480,15 x 3 = 0,450,5
8,488,480,15 x 3 = 0,450,5
NOTE :
Model of Indoor unit 10 : RAS-M10UKCV-E, 13 : RAS-M13UKCV-E, 16 : RAS-M16UKCV-E
MCA: Minimum Circuit Amps.
ICF: Maximum Instantaneous Current Flow
(Equivalent to MCA in case of inv erter air conditioner)
MOCP : Maximum Overcurrent Protection (Fuse only)
MSC: Maximum Starting Current
Indoor temp.°C2719
FLA: Full Load Amps.
RLA: Rated Load Amps. RLA under conditions on the right.
Outdoor temp.°C35—
– 6 –
DBWB
2. REFRIGERANT R410A
This air conditioner adopts the new refrigerant HFC
(R410A) which does not damage the ozone layer.
The working pressure of the new refrigerant R410A
is 1,6 times higher than conventional refrigerant
(R22). The refrigerating oil is also changed in
accordance with change of refrigerant, so be careful
that water, dust, and e xisting refrigerant or refrigerating oil are not entered in the refrigerant cycle of the
air conditioner using the new refrigerant during
installation work or servicing time.
The next section describes the precautions for air
conditioner using the new refrigerant. Conf orming to
contents of the next section together with the
general cautions included in this manual, perform
the correct and safe work.
2-1. Safety During Installation/Servicing
As R410A’s pressure is about 1,6 times higher than
that of R22, improper installation/servicing may
cause a serious trouble. By using tools and materials exclusive for R410A, it is necessary to carry out
installation/servicing safely while taking the following
precautions into consideration.
(1) Never use refrigerant other than R410A in an air
conditioner which is designed to operate with
R410A.
If other refrigerant than R410A is mixed, pressure in the refrigeration cycle becomes abnormally high, and it may cause personal injury, etc.
by a rupture.
(2) Confirm the used refrigerant name, and use
tools and materials exclusive f or the refrigerant
R410A.
The refrigerant name R410A is indicated on the
visible place of the outdoor unit of the air conditioner using R410A as refrigerant. To prevent
mischarging, the diameter of the service port
differs from that of R22.
(3) If a refrigeration gas leakage occurs during
installation/servicing, be sure to ventilate fully .
If the refrigerant gas comes into contact with fire,
a poisonous gas may occur.
(4) When installing or removing an air conditioner,
do not allow air or moisture to remain in the
refrigeration cycle. Otherwise, pressure in the
refrigeration cycle may become abnormally high
so that a rupture or personal injury may be
caused.
(5) After completion of installation work, check to
make sure that there is no refrigeration gas
leakage.
If the refrigerant gas leaks into the room, coming
into contact with fire in the fan-driven heater ,
space heater, etc., a poisonous gas may occur.
(6) When an air conditioning system charged with a
large volume of refrigerant is installed in a small
room, it is necessary to exercise care so that,
even when refrigerant leaks , its concentration
does not exceed the marginal lev el.
If the refrigerant gas leakage occurs and its
concentration exceeds the marginal lev el, an
oxygen starvation accident may result.
(7) Be sure to carry out installation or removal
according to the installation manual.
Improper installation may cause refrigeration
trouble, water leakage , electric shock, fire , etc.
(8) Unauthorized modifications to the air conditioner
may be dangerous. If a breakdown occurs
please call a qualified air conditioner technician
or electrician.
Improper repair’s ma y result in w ater leakage,
electric shock and fire, etc.
2-2. Refrigerant Piping Installation
2-2-1. Piping Materials and Joints Used
For the refrigerant piping installation, copper pipes
and joints are mainly used. Copper pipes and joints
suitable for the refrigerant must be chosen and
installed. Furthermore, it is necessary to use clean
copper pipes and joints whose interior surfaces are
less affected by contaminants.
(1) Copper Pipes
It is necessary to use seamless copper pipes
which are made of either copper or copper alloy
and it is desirable that the amount of residual oil
is less than 40 mg/10 m. Do not use copper
pipes having a collapsed, deformed or discolored portion (especially on the interior surface).
Otherwise, the expansion valve or capillary tube
may become block ed with contaminants.
As an air conditioner using R410A incurs
pressure higher than when using R22, it is
necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A
are as shown in Table 2-2-1. Never use copper
pipes thinner than 0,8 mm even when it is
available on the mark et.
For copper pipes, flare joints or soc k et joints are
used. Prior to use, be sure to remo ve all contaminants.
a) Flare Joints
Flare joints used to connect the copper pipes
cannot be used for pipings whose outer
diameter exceeds 20 mm. In such a case,
socket joints can be used.
Sizes of flare pipe ends, flare joint ends and
flare nuts are as shown in Tables 2-2-3 ~ 2-2-6
below .
T a ble 2-2-2 Minim um thic knesses of socket joints
Socket joints are such that they are br azed
for connections, and used mainly f or thic k
pipings whose diameter is larger than 20 mm.
Thicknesses of socket joints are as shown in
T ab le 2-2-2.
5/815,880,80
2-2-2. Processing of Piping Materials
When performing the refrigerant piping installation,
care should be taken to ensure that water or dust
does not enter the pipe interior, that no other oil
other than lubricating oils used in the installed air
conditioner is used, and that refrigerant does not
leak. When using lubricating oils in the piping
processing, use such lubricating oils whose water
content has been removed. When stored, be sure to
seal the container with an airtight cap or any other
cover .
(1) Flare Processing Procedures and Precautions
a) Cutting the Pipe
By means of a pipe cutter, slowly cut the pipe
so that it is not deformed.
b) Removing Burrs and Chips
If the flared section has chips or burrs,
refrigerant leakage may occur . Carefully
remove all burrs and clean the cut surface
before installation.
– 8 –
c) Insertion of Flare Nut
d) Flare Processing
Make certain that a clamp bar and copper
pipe have been cleaned.
By means of the clamp bar, perf orm the flare
processing correctly .
Use either a flare tool for R410A or conv entional flare tool.
T a ble 2-2-3 Dimensions related to flare pr ocessing f or R410A
Nominal
diameter
Outer
diameter
(mm)
Thickness
(mm)
Flare processing dimensions differ according
to the type of flare tool. When using a conventional flare tool, be sure to secure “dimension A” by using a gauge for size adjustment.
Fig. 2-2-1 Flare processing dimensions
Flare tool for
R410A clutch type
ØD
A
A (mm)
Conventional flare tool
Clutch typeWing nut type
1/4 6,350,8
3/8 9,520,8
1/212,700,8
5/815,881,0
Table 2-2-4 Dimensions related to flare processing for R22
Nominal
diameter
Outer
diameter
(mm)
1/4 6,350,8
3/8 9,520,8
1/212,700,8
5/815,881,0
T a ble 2-2-5 Flare and flare nut dimensions f or R410A
Thickness
(mm)
0 to 0,51,0 to 1,51,5 to 2,0
0 to 0,51,0 to 1,51,5 to 2,0
0 to 0,51,0 to 1,52,0 to 2,5
0 to 0,51,0 to 1,52,0 to 2,5
A (mm)
Flare tool for
R22 clutch type
Conventional flare tool
Clutch typeWing nut type
0 to 0,50,5 to 1,01,0 to 1,5
0 to 0,50,5 to 1,01,0 to 1,5
0 to 0,50,5 to 1,01,5 to 2,0
0 to 0,50,5 to 1,01,5 to 2,0
Fig. 2-2-2 Relations between flare nut and flare seal surface
(2) Flare Connecting Procedures and Precautions
a) Make sure that the flare and union portions
do not have any scar or dust, etc.
b) Correctly align the processed flare surface
with the union axis.
c) Tighten the flare with designated torque by
means of a torque wrench. The tightening
torque for R410A is the same as that for
conventional R22. Incidentally, when the
torque is weak, the gas leakage may occur .
Table 2-2-7 Tightening torque of flare for R410A [Reference values]
NominalOuter diameterTightening torque
diameter(mm)N•m (kgf•cm)
1/46,3514 to 18 (140 to 180)16 (160), 18 (180)
When it is strong, the flare nut may cra c k and
may be made non-remov abl e. When choosing the tightening torque, comply with values
designated by manufacturers. Table 2-2-7
shows reference values.
Note:
When applying oil to the flare surface, be sure to use
oil designated by the manufacturer. If any other oil is
used, the lubricating oils may deteriorate and cause
the compressor to burn out.
Tightening torque of torque
wrenches available on the market
N•m (kgf•cm)
3/89,5233 to 42 (330 to 420)42 (420)
1/212,7050 to 62 (500 to 620)55 (550)
5/815,8863 to 77 (630 to 770)65 (650)
– 10 –
2-3. Tools
2-3-1. Required T ools
The service port diameter of pac ked valv e of the outdoor unit in the air conditioner using R410A is changed to prev ent
mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side
dimension of flare nut (For Ø12,7 copper pipe) of the refrigerant piping are lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge,
clogging of capillary, etc. Accordingly, the tools to be used are classified into the f ollowing three types .
(1) T ools e xclusive for R410A (Those which cannot be used for con v entional refrigerant (R22))
(2) T ools e xclusive for R410A, but can be also used for con ventional refrigerant (R22)
(3) T ools commonly used f or R410A and f or conventional refrigerant (R22)
The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the
following steps.
Recover the refrigerant, and check no refrigerant
remains in the equipment.
Connect the charge hose to packed valve service
port at the outdoor unit’s gas side.
When the compound gauge’s pointer has indicated
–0,1 Mpa (–76 cmHg), place the handle Low in the
fully closed position, and turn off the vacuum pump’s
power switch.
Connect the charge hose of the vacuum pump
adapter.
Open fully both packed valves at liquid and gas
sides.
Place the handle of the gauge manifold Low in the
fully opened position, and turn on the vacuum pump’s
power switch. Then, evacuating the refrigerant in the
cycle.
Never charge refrigerant e xceeding the specified amount.
If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.
Do not carry out additional charging.
Keep the status as it is for 1 to 2 minutes, and ensure
that the compound gauge’s pointer does not return.
Set the refrigerant cylinder to the electronic balance,
connect the connecting hose to the cylinder and the
connecting port of the electronic balance, and charge
liquid refrigerant.
(For refrigerant charging, see the figure below.)
When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the
refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high pressure, and may cause a rupture or personal injury .
(INDOOR unit)
Refrigerant cylinder
(With siphon pipe)
Check valve
Open/Close valve
for charging
Electronic balance for refrigerant charging
Fig. 2-4-1 Configuration of refrigerant charging
(Liquid side)
(Gas side)
– 12 –
(OUTDOOR unit)
Opened
Closed
Service port
Be sure to make setting so that liquid can be charged.
When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant.
Accordingly , when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the
cylinder upside down if cylinder is not equipped with siphon.
[ Cylinder with siphon ][ Cylinder without siphon ]
Gauge manifold
OUTDOOR unit
Refrigerant
cylinder
Gauge manifold
OUTDOOR unit
cylinder
Refrigerant
Electronic
balance
R410A refrigerant is HFC mixed refrigerant.
Therefore, if it is charged with gas, the composition of the charged refrigerant changes and
the characteristics of the equipment varies.
2-5. Brazing of Pipes
2-5-1. Materials for Brazing
(1) Silver brazing filler
Silver brazing filler is an alloy mainly composed
of silver and copper . It is used to join iron,
copper or copper alloy, and is relatively expensive though it excels in solderability.
(2) Phosphor bronze brazing filler
Phosphor bronze brazing filler is generally used
to join copper or copper alloy.
(3) Low temperature brazing filler
Low temperature brazing filler is generally called
solder, and is an alloy of tin and lead. Since it is
weak in adhesive strength, do not use it for
refrigerant pipes.
Fig. 2-4-2
Electronic
balance
Siphon
Phosphor bronze brazing filler tends to react
with sulfur and produce a fragile compound
water solution, which may cause a gas leakage. Therefore, use any other type of brazing
filler at a hot spring resort, etc., and coat the
surface with a paint.
When performing brazing again at time of
servicing, use the same type of brazing filler.
2-5-2. Flux
(1) Reason why flux is necessary
• By removing the oxide film and any f oreign
matter on the metal surface, it assists the flow
of brazing filler.
• In the brazing process, it prevents the metal
surface from being oxidiz ed.
• By reducing the brazing filler’s surface tension,
the brazing filler adheres better to the treated
metal.
– 13 –
Nitrogen gas
cylinder
Pipe
Flow meter
M
Stop valve
From Nitrogen cylinder
Nitrogen
gas
Rubber plug
(2) Characteristics required for flux
• Activated temperature of flux coincides with
the brazing temperature.
• Due to a wide effective temper ature range ,
flux is hard to carbonize.
• It is easy to remove slag after brazing.
• The corrosive action to the treated metal and
brazing filler is minimum.
• It excels in coating performance and is
harmless to the human body .
As the flux works in a complicated manner as
described above, it is necessary to select an
adequate type of flux according to the type and
shape of treated metal, type of brazing filler and
brazing method, etc.
(3) Types of flux
• Noncorrosive flux
Generally, it is a compound of borax and boric
acid.
It is effective in case where the br azing
temperature is higher than 800°C.
• Activated flux
Most of fluxes generally used for silver brazing
are this type.
It features an increased oxide film remo ving
capability due to the addition of compounds
such as potassium fluoride, potassium chloride and sodium fluoride to the borax-boric
acid compound.
(4) Piping materials for brazing and used braz-
ing filler/flux
2-5-3. Brazing
As brazing work requires sophisticated techniques,
experiences based upon a theoretical knowledge, it
must be performed by a person qualified.
In order to prev ent the o xide film from occurring in
the pipe interior during brazing, it is effective to
proceed with brazing while letting dry Nitrogen gas
(N2) flow .
Never use gas other than Nitrogen gas.
(1) Brazing method to prevent oxidation
Attach a reducing valve and a flow-meter to
the Nitrogen gas cylinder.
Use a copper pipe to direct the piping
material, and attach a flow-meter to the
cylinder.
Apply a seal onto the clearance between the
piping material and inserted copper pipe for
Nitrogen in order to prevent bac kflo w of the
Nitrogen gas.
When the Nitrogen gas is flowing, be sure to
keep the piping end open.
Adjust the flow rate of Nitrogen gas so that it
is lower than 0,05 m3/Hr or 0,02 MPa (0,2kgf/
cm2) by means of the reducing valve .
After performing the steps above , keep the
Nitrogen gas flowing until the pipe cools
down to a certain extent (temperature at
which pipes are touchable with hands).
Remove the flux completely after brazing.
Copper - Copper
Piping
material
Copper - Iron
Iron - Iron
Do not enter flux into the refrigeration cycle.
When chlorine contained in the flux remains
within the pipe, the lubricating oil deteriorates. Therefore , use a flux which does not
contain chlorine.
When adding water to the flux, use water
which does not contain chlorine (e.g. distilled
water or ion-exchange w ater).
For installation of the outdoor unit,
open (60cm or more) two directions at
least of A , B , C , and D directions.
Z
Mounting dimensions of anchor bolt
50 or more
200 or more
B
D
Outlet
600
Outside line
of product
Intake
4 × ø11 × 17 long hole
(For ø8-ø10 anchor bolt)
view
A
250 or more
(Minimum distance
from wall)
Detailed A leg part
50
36
11
310
296
R5,5
310
296
11
36
50
Detailed B leg part
600
2-ø6 hole
2-ø6 hole
Outside line
of product
600
R15
Outside line
of product
R15
R5,5
– 16 –
4-1. Indoor Unit
RAS-M10UKCV-E
RAS-M13UKCV-E
RAS-M16UKCV-E
4. WIRING DIAGRAM
Table 4-1-1 Simple check points for diagnosing faults
Check items
OPERATION
1
INDICATOR
TERMINAL
2
BLOCK
FUSE
3
6.3A
DC 5V
4
DC 12V
5
DC 35V
6
(DC310 ~ 340V)
Refer to the service data for the detailed failure diagnosis.
Check to see if the OPERATION indicator goes on and off when the main switch
or breaker is turned on. (Check the primary and secondary voltage of transformer.)
Check for power supply voltage between
(Check the primary and secondary voltage of transformer.)
Check for fluctuate voltage between
Check to see if the fuse blows out.
(Check the R04 of the varistor.)
Check the voltage at the No.4 pin on CN13 connector of the infrared receiver.
(Check the transformer and the power supply circuit of the rated voltage.)
Check for voltage at the while lead of louver motor.
(Check the transformer and the power supply circuit of the rated voltage.)
Check the voltage at the No.1 pin on CN10 connector.
(Check the DB01, R05 and C03.)
3,15A, AC250V
15A,AC250V
25A,AC250V
500µF, DC400V X 4 pieces
26,5V x 3, 16V x 1, 15V x 1
– 19 –
6. REFRIGERANT CYCLE DIAGRAM
6-1. Refrigerant Cycle Diagram
To
C room
To
B room
INDOOR UNIT A
Indoor heat
exchanger
T1
Temp. measurement
To
C room
To
B room
Connecting pipe
Thickness : 0,8 mm
Ø9,52 :
RAS-M10UKCV-E
RAS-M13UKCV-E
Ø12,7 :
RAS-M16UKCV-E
Pressure
P
measurement
Gauge attaching port
Vacuum pump
connecting port
Cross flow fan
Connecting pipe
Thickness : 0,8 mm
Ø6,35
Sectional shape
of heat insulator
(Ø9,52) (Ø9,52) (Ø12,7)(Ø6,35) (Ø6,35) (Ø6,35)
TGc
TGb
TGa
Allowable height
Strainer
Pulse modulating
valve at liquid side
(SEV15RC2)
Per 1 unit
Max. : 20m
Min. : 2m
Total
Max. : 40m
difference : 10m
Allowable pipe length
Accumulating tank
Ø51 x 300
(460cc)
Temp. measurement
Outdoor heat
T
2
OUTDOOR UNIT
TD
Compressor
DA130A1F-21F
exchanger
Propeller fan
Refrigerant amount : 1,5kg (R410A)
NOTE :
Gas leak check position
Refrigerant flow
NOTE :
The maximum pipe length of this air conditioner is 40 m. The additional charging of refrigerant is unnecessary
because this air conditioner is designed with charge-less specification.
0,921 142
0,85 947
0,73 850
0,9610,5 to 11,549
0,9211 to 1251
0,9211 to 1251
0,9211 to 1251
0,9211 to 1251
0,9211 to 1251
1,0412,5 to 13,551
0,9812 to 1352
0,9812 to 1352
0,9812 to 1352
This air conditioner is a capacity-variable type air
conditioner, which uses DC motor f or the indoor fan
motors and the outdoor fan motor . And the capacityproportional control compressor which can change
the motor speed in the range from 13 to 120 rps is
mounted. The DC motor drive circuit is mounted to
the indoor unit. The compressor and the inverter to
control fan motor are mounted to the outdoor unit.
The entire air conditioner is mainly controlled by the
indoor unit controller.
The indoor unit controller drives the indoor fan motor
based upon command sent from the remote control,
and transfers the operation command to the outdoor
unit controller.
The outdoor unit controller receives operation
command from the indoor unit side, and controls the
outdoor fan and the pulse modulating valv e.
Besides, detecting revolution position of the compressor motor, the outdoor unit controller controls
speed of the compressor motor by controlling output
voltage of the inv erter and switching timing of the
supply power (current transfer timing) so that motors
drive according to the operation command. And
then, the outdoor unit controller transfers re v ersely
the operating status information of the outdoor unit
to control the indoor unit controller.
As the compressor adopts four-pole brushless
DC motor, the frequenc y of the supply po wer
from inverter to compressor is two-times
cycles of the actual number of rev olution.
(1) Role of indoor unit controller
The indoor unit controller judges the operation
commands from the remote control and assumes the following functions.
• Judgment of suction air temperature of the
indoor heat exchanger by using the indoor
temp. sensor .
• Temperature setting of the indoor heat exchanger by using heat exchanger sensor
(Prevent-freezing control)
• Louver motor control
• Indoor fan motor operation control
• LED display control
• Transferring of operation command signal
(Serial signal) to the outdoor unit
• Reception of information of operation status
(Serial signal including outside temp. data) to
the outdoor unit and judgment/display of error
(2) Role of outdoor unit controller
Receiving the operation command signal (Serial
signal) from the indoor controller, the outdoor
unit performs its role.
• Compressor operation
Operations followed
control
• Operation control of
outdoor fan motor
• P.M.V. control
• Detection of inverter input current and current
release operation
• Over-current detection and prev ention opera-
tion to transistor module (Compressor stop
function)
• Compressor and outdoor fan stop function
when serial signal is off (when the serial signal
does not reach the board assembly of outdoor
control by trouble of the signal system)
• Transferring of operation information (Serial
signal) from outdoor unit to indoor unit
• Detection of outdoor temperature and opera-
tion revolution control
(3) Contents of operation command signal (Serial
signal) from indoor unit controller to outdoor unit
controller
The following three types of signals are sent
from the indoor unit controller.
• Operation mode set on the remote control
• Compressor revolution command signal defined
by indoor temperature and set temperature
(Correction along with variation of room
temperature and correction of indoor heat
exchanger temperature are added.)
• For these two types of signals ( [Operation
mode] and [Compressor revolution] ), the
outdoor unit controller monitors the input
current to the inverter, and perf orms the
followed operation within the range that
current does not exceed the allowab le value.
• T emper ature of indoor heat exchanger b y indoor
signal) from outdoor unit controller to indoor unit
controller
The following signals are sent from the outdoor
unit controller.
• The current operation mode
• The current compressor revolution
• Outdoor temperature
• Existence of protective circuit operation
For transf erring of these signals, the indoor
unit controller monitors the contents of signals,
and judges existence of trouble occurrence .
Contents of judgment are described below.
• Whether distinction of the current operation
status meets to the operation command
signal
• Whether protective circuit operates
When no signal is received from the
outdoor unit controller, it is assumed as a
trouble.
8-1-2. Current Release Control
The outdoor main circuit control section (Inverter
assembly) detects the input current to the outdoor
unit. If the current v alue with compressor motor
speed instructed from indoor side exceeds the
specified value, the outdoor main circuit control
section controls compressor motor speed by reducing motor speed so that value becomes closest to
the command within the limited value.
8-1-3. Power Factor Improvement Control
Po w er f actor impro v ement control is perf ormed
mainly aiming to reduce the current on much power
consumption of cooling operation. Controlling starts
from the time when input power has reached at a
certain point. To be concrete, IGBT of the power
factor improv ement circuit is used, and the po wer
factor is improv ed by keeping IGBT on for an arbitrary period to widen electro-angle of the input
current.
8-1-1. Capacity Control
The cooling capacity is varied by changing compressor motor speed. The inverter changes compressor
motor speed by changing AC 220–230–240V power
to DC once, and controls capacity by changing
supply power status to the compressor with transistor module (includes 6 transistors). The outline of the
control is as follows: The revolution position and
revolution speed of the motor are detected by
detecting winding electromotive force of the compressor motor under operation, and the revolution
speed is changed so that the motor drives based
upon revolution speed of the operation command b y
changing timing (current transfer timing) to exchange inverter output voltage and supply power
winding.
Detection of the revolution position f or controlling is
performed 12 times per 1 revolution of compressor.
The range of supply power frequency to the compressor differs according to the operation status
(COOL, DRY).
T able 8-1-1 Compressor re volution range
8-1-4. Prevent-Freezing Control
The indoor heat exchanger sensor detects refrigerant vapor temperature in COOL/DR Y operation. If
the temperature is below the specified value, compressor motor speed is reduced so that operation is
performed in temperature below the specified value
to prevent-freezing of indoor heat e xchanger.
8-1-5. P. M. V. (Pulse Modulating Valve)
Using P.M.V., refrigerant flow of refrigeration cycle is
varied for the optimum temperature . Controlling
each unit separately by three P.M.V. corresponds to
difference of pipe length, fan speed, and unit temperature.
If an error occurs on cycle temperature when power
source of the air conditioner has been turned on,
and if start/stop times of the outdoor unit are 30
times, move the valve once until it hits on the
stopper for positioning of the valve. In this case,
ticktack sound may be heard.
No. ofCombination ofCompressor
operating unitindoor unitsrevolution (rps)
RAS-M16UKCV-E16 to 77
1 unitRAS-M13YKCV-E16 to 72
RAS-M10YKCV-E16 to 45
2 units
3 units
: In case that any multiple indoor units are combined.
*
¡
¡
*
*
19 to 84
23 to 92
– 25 –
8-1-6. Louver Control
8-1-7.Indoor Fan Control (DC Fan Motor)
(1) Vertical air flow louvers
Positions of vertical air flow louv ers are automatically controlled according to the operation
status (COOL, AUTO, DR Y, FAN ONLY). Besides, positions of vertical air flow louvers can be
arbitrarily set by pressing the [SET] button. The
louver position which has been set by the [SET]
button is stored in microcomputer , and the louv er
is automatically set at the stored position in the
next operation.
(2) Swing
If the [AUTO] button is pressed during running
operation, vertical air flow louvers start swinging.
When the [AUTO] button is pressed again,
swinging stops.
FanOperation
Remote
modemodeControl
Motor speed
( rpm )
HHIGH119056012105901350670
M108051011305301250610
Cooling
and Fan
only
+
MED110051011305301250610
+
MMED100046010504901150550
LOW9604409904601070500
+
L9504309504301050490
+
LLOW910400910400980450
L850370850370920410
-
L9504309504301050490
+
L910400910400980450
DRY
L850370850370920410
-
UL720300750310920410
SUL660260700280800340
T able 8-1-3
RAS-M10UKCV-E
ir flow rateMotor speed
( m
/h )
The indoor fan is operated by motor speed non-step
variable DC drive system motor. For flow rate, motor
speed is controlled manually in three steps (LOW,
MED , HIGH), and with the unit of 10 rpm from upper
limit to lower limit in AUTO mode as described in
Table 8-1-3. It is not selected by rela y, so selecting
sound does not generate.
RAS-M13UKCV-ERAS-M16UKCV-E
ir flow rateMotor speedAir flow rate
( rpm )
( m
/h )
( rpm )
( m
/h )
NOTE : UL : Ultra Low, SUL : Super Ultra Low
8-1-8. Outdoor Fan Control (DC Fan Motor)
Although the outdoor fan motor drives the outdoor f an b y non-step v ariab le system of the re v olution speed, the
revolution speed is restricted to three steps on the con v enience of controlling.
If a strong wind is lashing outside of the room, the operation may be continued as the outdoor f an stops in order
to protect the outdoor fan motor.
If a fan lock occurred due to entering of f oreign matter, the air conditioner stops and an alarm is displayed.
T able 8-1-4
Compressor revolution (rps)
TO ≥ 38°C500 (r pm)800 (rpm)800 (rpm)
Outdoor temp. sensor
TO
ECONO. operation38°C > TO ≥ 15°C500 (rpm)500 (rpm)700 (rpm)
TO is abnormal700 (rpm)700 (rpm)800 (rpm)
38°C > TO ≥ 15°C500 (rpm)700 (rpm)800 (rpm)
15°C > TO390 (rpm)390 (rpm)390 (rpm)
TO ≥ 38°C500 (r pm)700 (rpm)800 (rpm)
15°C > TO390 (rpm)390 (rpm)390 (rpm)
~
17,4
38,939
~
~
– 26 –
Loading...
+ 60 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.