3,473,470,15 x 1 = 0,150,5
5,695,690,15 x 1 = 0,150,5
7,017,010,15 x 1 = 0,150,5
6,386,380,15 x 2 = 0,300,5
7,817,810,15 x 2 = 0,300,5
7,967,960,15 x 2 = 0,300,5
7,967,960,15 x 2 = 0,300,5
8,058,050,15 x 2 = 0,300,5
8,158,150,15 x 2 = 0,300,5
8,058,050,15 x 3 = 0,450,5
9,349,340,15 x 3 = 0,450,5
9,349,340,15 x 3 = 0,450,5
9,349,340,15 x 3 = 0,450,5
3,293,290,15 x 1 = 0,150,5
5,425,420,15 x 1 = 0,150,5
6,676,670,15 x 1 = 0,150,5
6,066,060,15 x 2 = 0,300,5
7,447,440,15 x 2 = 0,300,5
7,587,580,15 x 2 = 0,300,5
7,587,580,15 x 2 = 0,300,5
7,707,700,15 x 2 = 0,300,5
7,767,760,15 x 2 = 0,300,5
7,657,650,15 x 3 = 0,450,5
8,898,890,15 x 3 = 0,450,5
8,898,890,15 x 3 = 0,450,5
8,898,890,15 x 3 = 0,450,5
3,123,120,15 x 1 = 0,150,5
5,165,160,15 x 1 = 0,150,5
6,376,370,15 x 1 = 0,150,5
5,785,780,15 x 2 = 0,300,5
7,097,090,15 x 2 = 0,300,5
7,237,230,15 x 2 = 0,300,5
7,237,230,15 x 2 = 0,300,5
7,317,310,15 x 2 = 0,300,5
7,407,400,15 x 2 = 0,300,5
7,307,300,15 x 3 = 0,450,5
8,488,480,15 x 3 = 0,450,5
8,488,480,15 x 3 = 0,450,5
8,488,480,15 x 3 = 0,450,5
NOTE :
Model of Indoor unit 10 : RAS-M10UKCV-E, 13 : RAS-M13UKCV-E, 16 : RAS-M16UKCV-E
MCA: Minimum Circuit Amps.
ICF: Maximum Instantaneous Current Flow
(Equivalent to MCA in case of inv erter air conditioner)
MOCP : Maximum Overcurrent Protection (Fuse only)
MSC: Maximum Starting Current
Indoor temp.°C2719
FLA: Full Load Amps.
RLA: Rated Load Amps. RLA under conditions on the right.
Outdoor temp.°C35—
– 6 –
DBWB
Page 7
2. REFRIGERANT R410A
This air conditioner adopts the new refrigerant HFC
(R410A) which does not damage the ozone layer.
The working pressure of the new refrigerant R410A
is 1,6 times higher than conventional refrigerant
(R22). The refrigerating oil is also changed in
accordance with change of refrigerant, so be careful
that water, dust, and e xisting refrigerant or refrigerating oil are not entered in the refrigerant cycle of the
air conditioner using the new refrigerant during
installation work or servicing time.
The next section describes the precautions for air
conditioner using the new refrigerant. Conf orming to
contents of the next section together with the
general cautions included in this manual, perform
the correct and safe work.
2-1. Safety During Installation/Servicing
As R410A’s pressure is about 1,6 times higher than
that of R22, improper installation/servicing may
cause a serious trouble. By using tools and materials exclusive for R410A, it is necessary to carry out
installation/servicing safely while taking the following
precautions into consideration.
(1) Never use refrigerant other than R410A in an air
conditioner which is designed to operate with
R410A.
If other refrigerant than R410A is mixed, pressure in the refrigeration cycle becomes abnormally high, and it may cause personal injury, etc.
by a rupture.
(2) Confirm the used refrigerant name, and use
tools and materials exclusive f or the refrigerant
R410A.
The refrigerant name R410A is indicated on the
visible place of the outdoor unit of the air conditioner using R410A as refrigerant. To prevent
mischarging, the diameter of the service port
differs from that of R22.
(3) If a refrigeration gas leakage occurs during
installation/servicing, be sure to ventilate fully .
If the refrigerant gas comes into contact with fire,
a poisonous gas may occur.
(4) When installing or removing an air conditioner,
do not allow air or moisture to remain in the
refrigeration cycle. Otherwise, pressure in the
refrigeration cycle may become abnormally high
so that a rupture or personal injury may be
caused.
(5) After completion of installation work, check to
make sure that there is no refrigeration gas
leakage.
If the refrigerant gas leaks into the room, coming
into contact with fire in the fan-driven heater ,
space heater, etc., a poisonous gas may occur.
(6) When an air conditioning system charged with a
large volume of refrigerant is installed in a small
room, it is necessary to exercise care so that,
even when refrigerant leaks , its concentration
does not exceed the marginal lev el.
If the refrigerant gas leakage occurs and its
concentration exceeds the marginal lev el, an
oxygen starvation accident may result.
(7) Be sure to carry out installation or removal
according to the installation manual.
Improper installation may cause refrigeration
trouble, water leakage , electric shock, fire , etc.
(8) Unauthorized modifications to the air conditioner
may be dangerous. If a breakdown occurs
please call a qualified air conditioner technician
or electrician.
Improper repair’s ma y result in w ater leakage,
electric shock and fire, etc.
2-2. Refrigerant Piping Installation
2-2-1. Piping Materials and Joints Used
For the refrigerant piping installation, copper pipes
and joints are mainly used. Copper pipes and joints
suitable for the refrigerant must be chosen and
installed. Furthermore, it is necessary to use clean
copper pipes and joints whose interior surfaces are
less affected by contaminants.
(1) Copper Pipes
It is necessary to use seamless copper pipes
which are made of either copper or copper alloy
and it is desirable that the amount of residual oil
is less than 40 mg/10 m. Do not use copper
pipes having a collapsed, deformed or discolored portion (especially on the interior surface).
Otherwise, the expansion valve or capillary tube
may become block ed with contaminants.
As an air conditioner using R410A incurs
pressure higher than when using R22, it is
necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A
are as shown in Table 2-2-1. Never use copper
pipes thinner than 0,8 mm even when it is
available on the mark et.
For copper pipes, flare joints or soc k et joints are
used. Prior to use, be sure to remo ve all contaminants.
a) Flare Joints
Flare joints used to connect the copper pipes
cannot be used for pipings whose outer
diameter exceeds 20 mm. In such a case,
socket joints can be used.
Sizes of flare pipe ends, flare joint ends and
flare nuts are as shown in Tables 2-2-3 ~ 2-2-6
below .
T a ble 2-2-2 Minim um thic knesses of socket joints
Socket joints are such that they are br azed
for connections, and used mainly f or thic k
pipings whose diameter is larger than 20 mm.
Thicknesses of socket joints are as shown in
T ab le 2-2-2.
5/815,880,80
2-2-2. Processing of Piping Materials
When performing the refrigerant piping installation,
care should be taken to ensure that water or dust
does not enter the pipe interior, that no other oil
other than lubricating oils used in the installed air
conditioner is used, and that refrigerant does not
leak. When using lubricating oils in the piping
processing, use such lubricating oils whose water
content has been removed. When stored, be sure to
seal the container with an airtight cap or any other
cover .
(1) Flare Processing Procedures and Precautions
a) Cutting the Pipe
By means of a pipe cutter, slowly cut the pipe
so that it is not deformed.
b) Removing Burrs and Chips
If the flared section has chips or burrs,
refrigerant leakage may occur . Carefully
remove all burrs and clean the cut surface
before installation.
– 8 –
Page 9
c) Insertion of Flare Nut
d) Flare Processing
Make certain that a clamp bar and copper
pipe have been cleaned.
By means of the clamp bar, perf orm the flare
processing correctly .
Use either a flare tool for R410A or conv entional flare tool.
T a ble 2-2-3 Dimensions related to flare pr ocessing f or R410A
Nominal
diameter
Outer
diameter
(mm)
Thickness
(mm)
Flare processing dimensions differ according
to the type of flare tool. When using a conventional flare tool, be sure to secure “dimension A” by using a gauge for size adjustment.
Fig. 2-2-1 Flare processing dimensions
Flare tool for
R410A clutch type
ØD
A
A (mm)
Conventional flare tool
Clutch typeWing nut type
1/4 6,350,8
3/8 9,520,8
1/212,700,8
5/815,881,0
Table 2-2-4 Dimensions related to flare processing for R22
Nominal
diameter
Outer
diameter
(mm)
1/4 6,350,8
3/8 9,520,8
1/212,700,8
5/815,881,0
T a ble 2-2-5 Flare and flare nut dimensions f or R410A
Thickness
(mm)
0 to 0,51,0 to 1,51,5 to 2,0
0 to 0,51,0 to 1,51,5 to 2,0
0 to 0,51,0 to 1,52,0 to 2,5
0 to 0,51,0 to 1,52,0 to 2,5
A (mm)
Flare tool for
R22 clutch type
Conventional flare tool
Clutch typeWing nut type
0 to 0,50,5 to 1,01,0 to 1,5
0 to 0,50,5 to 1,01,0 to 1,5
0 to 0,50,5 to 1,01,5 to 2,0
0 to 0,50,5 to 1,01,5 to 2,0
Fig. 2-2-2 Relations between flare nut and flare seal surface
(2) Flare Connecting Procedures and Precautions
a) Make sure that the flare and union portions
do not have any scar or dust, etc.
b) Correctly align the processed flare surface
with the union axis.
c) Tighten the flare with designated torque by
means of a torque wrench. The tightening
torque for R410A is the same as that for
conventional R22. Incidentally, when the
torque is weak, the gas leakage may occur .
Table 2-2-7 Tightening torque of flare for R410A [Reference values]
NominalOuter diameterTightening torque
diameter(mm)N•m (kgf•cm)
1/46,3514 to 18 (140 to 180)16 (160), 18 (180)
When it is strong, the flare nut may cra c k and
may be made non-remov abl e. When choosing the tightening torque, comply with values
designated by manufacturers. Table 2-2-7
shows reference values.
Note:
When applying oil to the flare surface, be sure to use
oil designated by the manufacturer. If any other oil is
used, the lubricating oils may deteriorate and cause
the compressor to burn out.
Tightening torque of torque
wrenches available on the market
N•m (kgf•cm)
3/89,5233 to 42 (330 to 420)42 (420)
1/212,7050 to 62 (500 to 620)55 (550)
5/815,8863 to 77 (630 to 770)65 (650)
– 10 –
Page 11
2-3. Tools
2-3-1. Required T ools
The service port diameter of pac ked valv e of the outdoor unit in the air conditioner using R410A is changed to prev ent
mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side
dimension of flare nut (For Ø12,7 copper pipe) of the refrigerant piping are lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge,
clogging of capillary, etc. Accordingly, the tools to be used are classified into the f ollowing three types .
(1) T ools e xclusive for R410A (Those which cannot be used for con v entional refrigerant (R22))
(2) T ools e xclusive for R410A, but can be also used for con ventional refrigerant (R22)
(3) T ools commonly used f or R410A and f or conventional refrigerant (R22)
The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the
following steps.
Recover the refrigerant, and check no refrigerant
remains in the equipment.
Connect the charge hose to packed valve service
port at the outdoor unit’s gas side.
When the compound gauge’s pointer has indicated
–0,1 Mpa (–76 cmHg), place the handle Low in the
fully closed position, and turn off the vacuum pump’s
power switch.
Connect the charge hose of the vacuum pump
adapter.
Open fully both packed valves at liquid and gas
sides.
Place the handle of the gauge manifold Low in the
fully opened position, and turn on the vacuum pump’s
power switch. Then, evacuating the refrigerant in the
cycle.
Never charge refrigerant e xceeding the specified amount.
If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.
Do not carry out additional charging.
Keep the status as it is for 1 to 2 minutes, and ensure
that the compound gauge’s pointer does not return.
Set the refrigerant cylinder to the electronic balance,
connect the connecting hose to the cylinder and the
connecting port of the electronic balance, and charge
liquid refrigerant.
(For refrigerant charging, see the figure below.)
When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the
refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high pressure, and may cause a rupture or personal injury .
(INDOOR unit)
Refrigerant cylinder
(With siphon pipe)
Check valve
Open/Close valve
for charging
Electronic balance for refrigerant charging
Fig. 2-4-1 Configuration of refrigerant charging
(Liquid side)
(Gas side)
– 12 –
(OUTDOOR unit)
Opened
Closed
Service port
Page 13
Be sure to make setting so that liquid can be charged.
When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant.
Accordingly , when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the
cylinder upside down if cylinder is not equipped with siphon.
[ Cylinder with siphon ][ Cylinder without siphon ]
Gauge manifold
OUTDOOR unit
Refrigerant
cylinder
Gauge manifold
OUTDOOR unit
cylinder
Refrigerant
Electronic
balance
R410A refrigerant is HFC mixed refrigerant.
Therefore, if it is charged with gas, the composition of the charged refrigerant changes and
the characteristics of the equipment varies.
2-5. Brazing of Pipes
2-5-1. Materials for Brazing
(1) Silver brazing filler
Silver brazing filler is an alloy mainly composed
of silver and copper . It is used to join iron,
copper or copper alloy, and is relatively expensive though it excels in solderability.
(2) Phosphor bronze brazing filler
Phosphor bronze brazing filler is generally used
to join copper or copper alloy.
(3) Low temperature brazing filler
Low temperature brazing filler is generally called
solder, and is an alloy of tin and lead. Since it is
weak in adhesive strength, do not use it for
refrigerant pipes.
Fig. 2-4-2
Electronic
balance
Siphon
Phosphor bronze brazing filler tends to react
with sulfur and produce a fragile compound
water solution, which may cause a gas leakage. Therefore, use any other type of brazing
filler at a hot spring resort, etc., and coat the
surface with a paint.
When performing brazing again at time of
servicing, use the same type of brazing filler.
2-5-2. Flux
(1) Reason why flux is necessary
• By removing the oxide film and any f oreign
matter on the metal surface, it assists the flow
of brazing filler.
• In the brazing process, it prevents the metal
surface from being oxidiz ed.
• By reducing the brazing filler’s surface tension,
the brazing filler adheres better to the treated
metal.
– 13 –
Page 14
Nitrogen gas
cylinder
Pipe
Flow meter
M
Stop valve
From Nitrogen cylinder
Nitrogen
gas
Rubber plug
(2) Characteristics required for flux
• Activated temperature of flux coincides with
the brazing temperature.
• Due to a wide effective temper ature range ,
flux is hard to carbonize.
• It is easy to remove slag after brazing.
• The corrosive action to the treated metal and
brazing filler is minimum.
• It excels in coating performance and is
harmless to the human body .
As the flux works in a complicated manner as
described above, it is necessary to select an
adequate type of flux according to the type and
shape of treated metal, type of brazing filler and
brazing method, etc.
(3) Types of flux
• Noncorrosive flux
Generally, it is a compound of borax and boric
acid.
It is effective in case where the br azing
temperature is higher than 800°C.
• Activated flux
Most of fluxes generally used for silver brazing
are this type.
It features an increased oxide film remo ving
capability due to the addition of compounds
such as potassium fluoride, potassium chloride and sodium fluoride to the borax-boric
acid compound.
(4) Piping materials for brazing and used braz-
ing filler/flux
2-5-3. Brazing
As brazing work requires sophisticated techniques,
experiences based upon a theoretical knowledge, it
must be performed by a person qualified.
In order to prev ent the o xide film from occurring in
the pipe interior during brazing, it is effective to
proceed with brazing while letting dry Nitrogen gas
(N2) flow .
Never use gas other than Nitrogen gas.
(1) Brazing method to prevent oxidation
Attach a reducing valve and a flow-meter to
the Nitrogen gas cylinder.
Use a copper pipe to direct the piping
material, and attach a flow-meter to the
cylinder.
Apply a seal onto the clearance between the
piping material and inserted copper pipe for
Nitrogen in order to prevent bac kflo w of the
Nitrogen gas.
When the Nitrogen gas is flowing, be sure to
keep the piping end open.
Adjust the flow rate of Nitrogen gas so that it
is lower than 0,05 m3/Hr or 0,02 MPa (0,2kgf/
cm2) by means of the reducing valve .
After performing the steps above , keep the
Nitrogen gas flowing until the pipe cools
down to a certain extent (temperature at
which pipes are touchable with hands).
Remove the flux completely after brazing.
Copper - Copper
Piping
material
Copper - Iron
Iron - Iron
Do not enter flux into the refrigeration cycle.
When chlorine contained in the flux remains
within the pipe, the lubricating oil deteriorates. Therefore , use a flux which does not
contain chlorine.
When adding water to the flux, use water
which does not contain chlorine (e.g. distilled
water or ion-exchange w ater).
For installation of the outdoor unit,
open (60cm or more) two directions at
least of A , B , C , and D directions.
Z
Mounting dimensions of anchor bolt
50 or more
200 or more
B
D
Outlet
600
Outside line
of product
Intake
4 × ø11 × 17 long hole
(For ø8-ø10 anchor bolt)
view
A
250 or more
(Minimum distance
from wall)
Detailed A leg part
50
36
11
310
296
R5,5
310
296
11
36
50
Detailed B leg part
600
2-ø6 hole
2-ø6 hole
Outside line
of product
600
R15
Outside line
of product
R15
R5,5
– 16 –
Page 17
4-1. Indoor Unit
RAS-M10UKCV-E
RAS-M13UKCV-E
RAS-M16UKCV-E
4. WIRING DIAGRAM
Table 4-1-1 Simple check points for diagnosing faults
Check items
OPERATION
1
INDICATOR
TERMINAL
2
BLOCK
FUSE
3
6.3A
DC 5V
4
DC 12V
5
DC 35V
6
(DC310 ~ 340V)
Refer to the service data for the detailed failure diagnosis.
Check to see if the OPERATION indicator goes on and off when the main switch
or breaker is turned on. (Check the primary and secondary voltage of transformer.)
Check for power supply voltage between
(Check the primary and secondary voltage of transformer.)
Check for fluctuate voltage between
Check to see if the fuse blows out.
(Check the R04 of the varistor.)
Check the voltage at the No.4 pin on CN13 connector of the infrared receiver.
(Check the transformer and the power supply circuit of the rated voltage.)
Check for voltage at the while lead of louver motor.
(Check the transformer and the power supply circuit of the rated voltage.)
Check the voltage at the No.1 pin on CN10 connector.
(Check the DB01, R05 and C03.)
3,15A, AC250V
15A,AC250V
25A,AC250V
500µF, DC400V X 4 pieces
26,5V x 3, 16V x 1, 15V x 1
– 19 –
Page 20
6. REFRIGERANT CYCLE DIAGRAM
6-1. Refrigerant Cycle Diagram
To
C room
To
B room
INDOOR UNIT A
Indoor heat
exchanger
T1
Temp. measurement
To
C room
To
B room
Connecting pipe
Thickness : 0,8 mm
Ø9,52 :
RAS-M10UKCV-E
RAS-M13UKCV-E
Ø12,7 :
RAS-M16UKCV-E
Pressure
P
measurement
Gauge attaching port
Vacuum pump
connecting port
Cross flow fan
Connecting pipe
Thickness : 0,8 mm
Ø6,35
Sectional shape
of heat insulator
(Ø9,52) (Ø9,52) (Ø12,7)(Ø6,35) (Ø6,35) (Ø6,35)
TGc
TGb
TGa
Allowable height
Strainer
Pulse modulating
valve at liquid side
(SEV15RC2)
Per 1 unit
Max. : 20m
Min. : 2m
Total
Max. : 40m
difference : 10m
Allowable pipe length
Accumulating tank
Ø51 x 300
(460cc)
Temp. measurement
Outdoor heat
T
2
OUTDOOR UNIT
TD
Compressor
DA130A1F-21F
exchanger
Propeller fan
Refrigerant amount : 1,5kg (R410A)
NOTE :
Gas leak check position
Refrigerant flow
NOTE :
The maximum pipe length of this air conditioner is 40 m. The additional charging of refrigerant is unnecessary
because this air conditioner is designed with charge-less specification.
0,921 142
0,85 947
0,73 850
0,9610,5 to 11,549
0,9211 to 1251
0,9211 to 1251
0,9211 to 1251
0,9211 to 1251
0,9211 to 1251
1,0412,5 to 13,551
0,9812 to 1352
0,9812 to 1352
0,9812 to 1352
This air conditioner is a capacity-variable type air
conditioner, which uses DC motor f or the indoor fan
motors and the outdoor fan motor . And the capacityproportional control compressor which can change
the motor speed in the range from 13 to 120 rps is
mounted. The DC motor drive circuit is mounted to
the indoor unit. The compressor and the inverter to
control fan motor are mounted to the outdoor unit.
The entire air conditioner is mainly controlled by the
indoor unit controller.
The indoor unit controller drives the indoor fan motor
based upon command sent from the remote control,
and transfers the operation command to the outdoor
unit controller.
The outdoor unit controller receives operation
command from the indoor unit side, and controls the
outdoor fan and the pulse modulating valv e.
Besides, detecting revolution position of the compressor motor, the outdoor unit controller controls
speed of the compressor motor by controlling output
voltage of the inv erter and switching timing of the
supply power (current transfer timing) so that motors
drive according to the operation command. And
then, the outdoor unit controller transfers re v ersely
the operating status information of the outdoor unit
to control the indoor unit controller.
As the compressor adopts four-pole brushless
DC motor, the frequenc y of the supply po wer
from inverter to compressor is two-times
cycles of the actual number of rev olution.
(1) Role of indoor unit controller
The indoor unit controller judges the operation
commands from the remote control and assumes the following functions.
• Judgment of suction air temperature of the
indoor heat exchanger by using the indoor
temp. sensor .
• Temperature setting of the indoor heat exchanger by using heat exchanger sensor
(Prevent-freezing control)
• Louver motor control
• Indoor fan motor operation control
• LED display control
• Transferring of operation command signal
(Serial signal) to the outdoor unit
• Reception of information of operation status
(Serial signal including outside temp. data) to
the outdoor unit and judgment/display of error
(2) Role of outdoor unit controller
Receiving the operation command signal (Serial
signal) from the indoor controller, the outdoor
unit performs its role.
• Compressor operation
Operations followed
control
• Operation control of
outdoor fan motor
• P.M.V. control
• Detection of inverter input current and current
release operation
• Over-current detection and prev ention opera-
tion to transistor module (Compressor stop
function)
• Compressor and outdoor fan stop function
when serial signal is off (when the serial signal
does not reach the board assembly of outdoor
control by trouble of the signal system)
• Transferring of operation information (Serial
signal) from outdoor unit to indoor unit
• Detection of outdoor temperature and opera-
tion revolution control
(3) Contents of operation command signal (Serial
signal) from indoor unit controller to outdoor unit
controller
The following three types of signals are sent
from the indoor unit controller.
• Operation mode set on the remote control
• Compressor revolution command signal defined
by indoor temperature and set temperature
(Correction along with variation of room
temperature and correction of indoor heat
exchanger temperature are added.)
• For these two types of signals ( [Operation
mode] and [Compressor revolution] ), the
outdoor unit controller monitors the input
current to the inverter, and perf orms the
followed operation within the range that
current does not exceed the allowab le value.
• T emper ature of indoor heat exchanger b y indoor
signal) from outdoor unit controller to indoor unit
controller
The following signals are sent from the outdoor
unit controller.
• The current operation mode
• The current compressor revolution
• Outdoor temperature
• Existence of protective circuit operation
For transf erring of these signals, the indoor
unit controller monitors the contents of signals,
and judges existence of trouble occurrence .
Contents of judgment are described below.
• Whether distinction of the current operation
status meets to the operation command
signal
• Whether protective circuit operates
When no signal is received from the
outdoor unit controller, it is assumed as a
trouble.
8-1-2. Current Release Control
The outdoor main circuit control section (Inverter
assembly) detects the input current to the outdoor
unit. If the current v alue with compressor motor
speed instructed from indoor side exceeds the
specified value, the outdoor main circuit control
section controls compressor motor speed by reducing motor speed so that value becomes closest to
the command within the limited value.
8-1-3. Power Factor Improvement Control
Po w er f actor impro v ement control is perf ormed
mainly aiming to reduce the current on much power
consumption of cooling operation. Controlling starts
from the time when input power has reached at a
certain point. To be concrete, IGBT of the power
factor improv ement circuit is used, and the po wer
factor is improv ed by keeping IGBT on for an arbitrary period to widen electro-angle of the input
current.
8-1-1. Capacity Control
The cooling capacity is varied by changing compressor motor speed. The inverter changes compressor
motor speed by changing AC 220–230–240V power
to DC once, and controls capacity by changing
supply power status to the compressor with transistor module (includes 6 transistors). The outline of the
control is as follows: The revolution position and
revolution speed of the motor are detected by
detecting winding electromotive force of the compressor motor under operation, and the revolution
speed is changed so that the motor drives based
upon revolution speed of the operation command b y
changing timing (current transfer timing) to exchange inverter output voltage and supply power
winding.
Detection of the revolution position f or controlling is
performed 12 times per 1 revolution of compressor.
The range of supply power frequency to the compressor differs according to the operation status
(COOL, DRY).
T able 8-1-1 Compressor re volution range
8-1-4. Prevent-Freezing Control
The indoor heat exchanger sensor detects refrigerant vapor temperature in COOL/DR Y operation. If
the temperature is below the specified value, compressor motor speed is reduced so that operation is
performed in temperature below the specified value
to prevent-freezing of indoor heat e xchanger.
8-1-5. P. M. V. (Pulse Modulating Valve)
Using P.M.V., refrigerant flow of refrigeration cycle is
varied for the optimum temperature . Controlling
each unit separately by three P.M.V. corresponds to
difference of pipe length, fan speed, and unit temperature.
If an error occurs on cycle temperature when power
source of the air conditioner has been turned on,
and if start/stop times of the outdoor unit are 30
times, move the valve once until it hits on the
stopper for positioning of the valve. In this case,
ticktack sound may be heard.
No. ofCombination ofCompressor
operating unitindoor unitsrevolution (rps)
RAS-M16UKCV-E16 to 77
1 unitRAS-M13YKCV-E16 to 72
RAS-M10YKCV-E16 to 45
2 units
3 units
: In case that any multiple indoor units are combined.
*
¡
¡
*
*
19 to 84
23 to 92
– 25 –
Page 26
8-1-6. Louver Control
8-1-7.Indoor Fan Control (DC Fan Motor)
(1) Vertical air flow louvers
Positions of vertical air flow louv ers are automatically controlled according to the operation
status (COOL, AUTO, DR Y, FAN ONLY). Besides, positions of vertical air flow louvers can be
arbitrarily set by pressing the [SET] button. The
louver position which has been set by the [SET]
button is stored in microcomputer , and the louv er
is automatically set at the stored position in the
next operation.
(2) Swing
If the [AUTO] button is pressed during running
operation, vertical air flow louvers start swinging.
When the [AUTO] button is pressed again,
swinging stops.
FanOperation
Remote
modemodeControl
Motor speed
( rpm )
HHIGH119056012105901350670
M108051011305301250610
Cooling
and Fan
only
+
MED110051011305301250610
+
MMED100046010504901150550
LOW9604409904601070500
+
L9504309504301050490
+
LLOW910400910400980450
L850370850370920410
-
L9504309504301050490
+
L910400910400980450
DRY
L850370850370920410
-
UL720300750310920410
SUL660260700280800340
T able 8-1-3
RAS-M10UKCV-E
ir flow rateMotor speed
( m
/h )
The indoor fan is operated by motor speed non-step
variable DC drive system motor. For flow rate, motor
speed is controlled manually in three steps (LOW,
MED , HIGH), and with the unit of 10 rpm from upper
limit to lower limit in AUTO mode as described in
Table 8-1-3. It is not selected by rela y, so selecting
sound does not generate.
RAS-M13UKCV-ERAS-M16UKCV-E
ir flow rateMotor speedAir flow rate
( rpm )
( m
/h )
( rpm )
( m
/h )
NOTE : UL : Ultra Low, SUL : Super Ultra Low
8-1-8. Outdoor Fan Control (DC Fan Motor)
Although the outdoor fan motor drives the outdoor f an b y non-step v ariab le system of the re v olution speed, the
revolution speed is restricted to three steps on the con v enience of controlling.
If a strong wind is lashing outside of the room, the operation may be continued as the outdoor f an stops in order
to protect the outdoor fan motor.
If a fan lock occurred due to entering of f oreign matter, the air conditioner stops and an alarm is displayed.
T able 8-1-4
Compressor revolution (rps)
TO ≥ 38°C500 (r pm)800 (rpm)800 (rpm)
Outdoor temp. sensor
TO
ECONO. operation38°C > TO ≥ 15°C500 (rpm)500 (rpm)700 (rpm)
TO is abnormal700 (rpm)700 (rpm)800 (rpm)
38°C > TO ≥ 15°C500 (rpm)700 (rpm)800 (rpm)
15°C > TO390 (rpm)390 (rpm)390 (rpm)
TO ≥ 38°C500 (r pm)700 (rpm)800 (rpm)
15°C > TO390 (rpm)390 (rpm)390 (rpm)
~
17,4
38,939
~
~
– 26 –
Page 27
8-2. Description of Operation Circuit
• Turning [ON] the breaker flashes the oper ation
lamp.
This is the display of power-ON (or notification of
power failure).
• When pushing [START/STOP] button of the
remote control, receive sound is issued from the
main unit, and the next operations are performed
together with opening the vertical air flow louvers.
8-2-1. Fan Only Operation
(The Remote Control MODE Button is
Set to the FAN ONLY Operation)
• Once the setting is made, the operation mode is
memorized in the microcomputer so that the
same operation can be effected thereafter simply
by pushing [START/STOP] button.
• When the FAN button is set to the AUTO position,
the indoor fan motor operates as shown in Fig. 82-1. When the F AN SPEED b utton is set to
LOW, MED, or HIGH, the motor operates with a
constant air flow .
• ECONO. mode cannot be set.
8-2-2. Cooling Operation
(The Remote Control MODE Button is
Set to the COOL Position)
• Once the setting is made, the operation mode is
memorized in the microcomputer so that the
same operation can be effected thereafter simply
by pushing [START/STOP] b utton.
• A cooling operation signal is transmitted to
outdoor unit.
• The indoor fan motor operates as shown in Fig.82-2 when F AN button is set to AUT O.
• The motor operates with a constant air flow when
the FAN button is set to LOW, MED , or HIGH.
• The outdoor unit controls the outdoor fan relay
R01, R02 and R03, and the compressor motor
speed according to the operation command
signal sent from the indoor unit.
˚C
(Room temp.) – (Set temp.)
Set
temp.
+3
+2,5
+2
+1,5
+1
+0,5
0
(Set temp.) 25˚C
M+
*1
*1
*1
L–
NOTE :
*1 :Calculated from difference in motor speed of M+
and L–, and controlled.
Fig. 8-2-1 Auto setting of air flow
˚C
+3
M+
*1
*1
*1
L–
In normal
operation
Set
temp.
+2,5
+2
+1,5
+1
(Room temp.) – (Set temp.)
+0,5
0
–0,5
NOTE :
*1 :Calculated from difference in motor speed of M+
and L–, and controlled.
Fig. 8-2-2 Setting of air flow [FAN AUTO]
– 27 –
Page 28
(1) Cooling capacity control
• The cooling capacity and room temperature
are controlled by changing the compressor
motor speed according to both the difference
between the temperature detected by the
room temperature sensor and the temperature
set by TEMP button and also any change in
room temperature.
• When compressor has been activated or
reactivated, it operates with Max. 33 rps for 2
minute, with Max. 57 rps from 2 to 4 minutes,
with Max. 91 rps from 4 to 7 minutes, and with
Max. 92 rps after 7 minutes passed.
• When room temperature is lower than set
temperature, indoor fan motor is oper ated at
fan speed L– as shown in Fig. 8-2-2 while the
outdoor unit stops.
(2) Prevent-freezing control
If temperature of indoor heat exchanger detected by the indoor heat exchanger sensor is
5°C or lower, compressor motor speed is
gradually lowered to prev ent freezing of the
indoor heat exchanger . If temper ature is 7°C or
higher, return the operation to the abov e item (1).
(3) Current release control
The input current of compressor and outdoor fan
motor (Precisely inverter main circuit control
section) which occupy most of air conditioner
input is detected by the outdoor current sensor ,
and compressor motor speed is gradually
lowered so that current value does not e xceed
I1A if current value exceeds I1A. When the
current value lowers to I2A, return the operation
to the above item (1).
Comp. motor
I1
speed down
(4) Outdoor temperature release control
The outdoor temperature release is controlled by
changing the current release points I1 and I2 in
the above item according to temperature detected by the outdoor temperature sensor .
For e xample, if the outdoor temper ature is ov er
40°C, the value of current release point becomes 7,7A.
(5) Limit for maximum compressor motor speed
by indoor fan speed
When outdoor temperature sensor detected
32°C or lower , and indoor heat exchanger
sensor detected 17°C or lower , the maximum
compressor motor speed is limited by the indoor
fan speed.
For e xample, when 1 unit only oper ates , the
compressor motor speed is limited as described
in the table below.
T able 8-2-2
Air flowM10UKCV-EM13UKCV-EM16UKCV-E
rate(rps)(rps)(rps)
HIGH457277
M+425966
MED.344054
L–, L313143
UL, SUL313131
(6) Louver control
The vertical air flow louvers are automatically set
to horizontal or cool memory position.
When temperature of indoor heat exchanger
becomes 5°C or lower by the prevent-freezing
control and the compressor is turned off, the
vertical air flow louvers close once and then
return to the position of previous time.
Comp. motor
I2
Current value (A)
Normal control
speed keep
Fig. 8-2-3
T able 8-2-1
Current valueCurrent limit
I19.5
I29,0
(7) Discharge temperature control
The discharge temperature of refrigerant gas
from the compressor is detected by the discharge temperature sensor, and controls operating compressor motor speed.
1) Control 1 (A zone) : Normal operation zone
When TD detect value is 101°C or lower, the
operation is performed with operating motor
speed instructed by the serial signal.
2) Control 2 (B zone) : Slow-up z one of motor
speed
When TD detect v alue is 101°C or higher,
operating motor speed is slowly up.
– 28 –
Page 29
3) Control 3 (C zone) : Keep zone
When TD detect v alue is 108°C or higher,
operating motor speed is not changed if
raising operation speed.
4) Control 4 (D zone) : Slo w do wn zone of motor
speed
When TD detect v alue is 111°C or higher,
operating motor speed is slowly down.
TD
(˚C)
120
115
111
Zone
F
E
D
Operation stop zone
Normal down zone of motor speed
Slow down of motor speed
5) Control 5 (E zone) : Normal down of motor
speed
When TD detect v alue is 115°C or higher,
operating motor speed is down.
6) Control 6 (F zone) : Oper ation stop zone
If TD detect v alue exceeds 120°C during
operation, stop the operation immediately.
Then, restart the operation when TD detect
value becomes 108°C or lower.
Release of motor speed
108
101
C
B
A
Fig. 8-2-4 Compressor motor speed contr ol
(8) ECONO. operation control
When the ECONO. button of the remote control
is pushed, quiet and mild operation is performed
by restraining air flow and operating motor
speed.
1) Indoor air flow is controlled between SUL
and L– (Low air (–)).
Compressor motor speed
3,5
3
Keep zone : Motor speed is not changed.
Slow-up zone of motor speed
Normal operation zone
2)Setting M10UKCV-E at 16 rps, M13UKCV-E
at 20 rps and M16UKCV-E at 26 rps as the
maximum operating compressor motor
speed, the minimum capacity operation range
is widened every 1 hour and 2 hours hav e
passed after ECONO. operation had started.
3) Maximum operating compressor motor speed
lowers up to 37 rps when the ECONO.
instruction is sent from even a room.
1 unit
Air volume
M13UKCV-EM16UKCV-EM10UKCV-E
20 rps16 rpsL–
16 to 20 rps
26 rps
16 to 26 rps
2 units3 units
37 rps
19 to 37 rps
23 to 37 rps16 rps(L– + SUL)/2
37 rps
2,5
2
1,5
1
(Room temp.) – (Set temp.)
0,5
Time2H1H
16 rps16 rps19 rps23 rps16 rpsSUL
Fig. 8-2-5
– 29 –
Page 30
32
22
Outdoor
temp.
(˚C)
Powerful Cool mode
Cool mode
Fan Only mode
8-2-3. DRY Operation
(The Remote Control MODE Button is
Set to the DRY Position)
• Once the setting is made, the operation mode is
memorized in the microcomputer so that the
same operation can be effected thereafter simply
by pushing [START/STOP] b utton.
• Dry operation signal is transmitted to outdoor
unit.
• The Cooling operation giving priority to dehumidifying, which restrains the indoor fan speed and
compressor motor speed, is performed.
• The indoor fan motor operates as shown in Fig.
8-2-6. (Fan speed is AUTO only.)
• The outdoor unit controls the outdoor fan relay
R01, R02 and R03, and the compressor motor
speed according to the operation command
signal sent from the indoor unit.
• When the air conditioner operates in Dry
mode, the maximum compressor motor speed
is restricted.
While multiple indoor units operate, compressor motor speed is calculated in the outdoor
unit to operate.
• When room temperature is lower than set
temperature, indoor fan motor is oper ated at
fan speed SUL as shown in Fig. 8-2-6 while
the outdoor unit stops.
• ECONO. mode cannot be set.
• Other controls than the above-mentioned
controls are common to those of Cooling
operation.
8-2-4. Auto Operation
+2,5
(Room temp.) – (Set temp.)
Set
temp.
+2,0
+1,5
+1,0
+0,5
0
–0,5
L–
*1
SUL
NOTE :
*1 : Middle motor speed between L– and SUL
Fig. 8-2-6 Setting of air flow
(1) Dehumidifying-preferential Cooling capacity
control
• The cooling capacity and room temperature
are controlled by changing the compressor
motor speed according to both the difference
between the temperature detected by the
room temperature sensor and the temperature
set by TEMP button and also any change in
room temperature.
• The compressor operates with maximum 28
rps for 1 minute when started and restarted.
• The operation mode is selected according to the
outdoor temperature when Auto operation has
started, as shown in Fig. 8-2-7. The Fan only
mode will continue until the operation mode is
selected. The air flow display on the remote
control becomes AUT O.
Fig. 8-2-7
• If the compressor is turned off by room temperature or outdoor temperature for 15 minutes
consecutively after operation mode has been
selected, the operation mode is selected again.
• In Powerful Cool mode, the louver directs downward, and air flow increases. When room temperature comes close to the set temperature, the
louver returns to Cooling operation position.
• The other controls than the above-mentioned
controls follow that of each operation.
– 30 –
Page 31
8-3. Temporary Operation
8-3-1. Temporary Auto Operation
• Temporary A uto operation, existence of Auto
Restart, and Temporary Cooling operation can be
set by the TEMPORARY button of the indoor
controller.
0
3S
TEMPORARY button
Fig. 8-3-1
T able 8-3-1
TEMPORARY buttonControl
→→
OFF
→ ONTemporary Auto operation start
→→
After pushing button
for 3 seconds
Auto Restart control select
• When the TEMPORARY button is pushed, the
Auto operation with set temperature fixed at 24°C
starts. Controlling is same as that of Auto operation by the remote control.
• When the TEMPORARY button is pushed again,
the operation stops.
• During Temporary Auto operation, operation by
the remote control is accepted.
• Using the Auto Restart function, the Temporary
Auto operation starts when power failure is reset.
8-3-2. Temporary Cooling Operation
• When the TEMPORARY operation button keeps
pushed for 10 seconds, Cooling operation of
which compressor motor speed and the indoor
fan speed are fix ed starts.
Compressor motor speed : 28 rps
Indoor fan speed : Lo w
• When the TEMPORARY operation button is
pushed again, the operation stops.
• Auto Restart function is unavailable.
After pushing buttonTemporary Cooling
for 10 secondsoperation start
– 31 –
Page 32
8-4. Auto Restart Function
8-4-1. How to Set the Auto Restart
This unit is equipped with an Automatic restarting
facility which allows the unit to restart and resume
the set operating conditions in the event of a po wer
supply shutdown without the use of the hand control.
The operation will resume without warning three
minutes after the power is restored.
The Auto Restart function is set not to work on
shipment from the factory, and so it is necessary to
set it to function as required.
• When the system is stand-by (not operating)
Operation
Push the TEMPORARY button
continuously more than three
seconds.
Stand-by
↓
The system starts to operate.The green light goes on.
↓ about three seconds after
The unit beeps three times.The orange light goes on.
↓
0
3S
The system is operating.
If the system is not required to run at this time, push the TEMPORARY
TEMPORARY button
button once more or use the remote control and the unit will stop.
To set the Auto Restart function, proceed as follows:
Access the TEMPORARY button located in the lower
right hand corner beneath the hinged front panel of
the indoor unit (please refer to Fig. 8-3-1). The
power supply to the unit must be on - the function
will not be set if the power is off.
To enable the Auto Restart function, push the
TEMPORARY b utton continuously f or three
seconds.
The unit will acknowledge the setting and beep three
times. The system will now restart automatically .
The above A uto Restart settings can be carried out:
Motion
• When the system is operating
Operation
Push the TEMPORARY button
continuously more than three
seconds.
OperatingThe green light goes on.
↓
The system stops to operate.The green light goes off.
↓ about three seconds after
The unit beeps three times.
0
3S
The system stops.
↓
If the system is not required to stop at this time, use the remote control
TEMPORARY button
and to restart.
During subsequent operation, the orange light goes on.
• The Auto Restart function will not accept an
instruction if timer operation with the remote
control is selected.
Motion
• During louver swing (A UTO) operation, after
restart by the Auto Restart function the louver
swing stops.
– 32 –
Page 33
8-4-2. How to Cancel the Auto Restart
To cancel the Auto Restart function, proceed as
follows:
Repeat the setting procedure: the unit will
acknowledge the instruction and beep three times.
• When the system is stand-by (not operating)
The system will now be required to manually restart
with the remote control after the main supply is
turned off.
Cancellation is carried out:
Operation
Push the TEMPORARY button
continuously more than three
seconds.
0
3S
TEMPORARY button
• When the system is operating
Operation
Push the TEMPORARY button
continuously more than three
seconds.
0
3S
TEMPORARY button
Motion
Stand-by
↓
The system starts to oper ate .The orange light goes on.
↓ about three seconds after
The unit beeps three times.The green light goes on.
↓
The system is operating.
If the system is not required to run at this time, push the TEMPORARY
button once more or use the remote control and the unit will stop.
Motion
OperatingThe orange light goes on.
↓
The system stops to operate.The orange light goes off.
↓ about three seconds after
The unit beeps three times.
↓
The system stops.
If the system is not required to stop at this time, use the remote control
and to restart.
During subsequent operation, the green light goes on.
8-4-3. In Case of Power Failure during the
Timer Operation
(1) If ON-TIMER operation is reserved with setting
of Auto Restart operation, it is cancelled with
power failure . (The OPERATION lamp on the
main unit goes on and off to inform of power
failure.) In that case, try to reserve ON-TIMER
operation once again.
(2) If OFF-TIMER operation is reserved without
setting of Auto Restart operation, the reservation
is cancelled with power failure.
(The OPERATION lamp on the main unit goes
on and off to inform of power failure .) In that
case, try to reserve OFF-TIMER operation.
When Auto Restart operation is set, OFF-TIMER
reservation is also cancelled with power failure.
– 33 –
Page 34
8-5. Remote control
8-5-1. Remote control and its functions
RAS-M10UKCV, RAS-M13UKCV, RAS-M16UKCV
11
1 Infrared signal emitter
11
Transmits a signal to the indoor unit.
22
2 START/STOP button
22
Press the button to start operation.
(A receiving beep is heard.)
Press the button again to stop operation.
(A receiving beep is heard.)
If no receiving sound is heard from the indoor unit,
press the button twice.
33
3 Mode select button (MODE)
33
Press this button to select a mode.
Each time you press the button, a mode is
selected in a sequence that goes from A : Auto
changeover control, : Cool,
: Heat,
: Fan only, and back to A.
(A receiving beep is heard.)
44
4 Temperature button (
44
The set temperature is increased up to 30°C.
,.......
9.......
The set temperature is dropped down to 17°C.
(A receiving beep is heard.)
55
5 Fan speed button (FAN)
55
Press this button to select fan speed. When you
select AUTO, the fan speed is automatically
adjusted according to the room temperature.
You can also manually select the desired fan
speed from among five settings.
+
(LOW
MED
, LOW
+
, HIGH
, MED
(A receiving beep is heard.)
66
6 Auto louver button (SWING)
66
Press this button to swing the louver.
(A receiving beep is heard.)
Press the FIX button to stop the louver swinging.
(A receiving beep is heard.)
77
7 Set louver button (FIX)
77
Press this button to adjust the air flow direction.
(A receiving beep is heard.)
88
8 Off timer button (OFF)
88
Press this button to set the OFF timer.
99
9 On timer button (ON)
99
Press this button to set the ON timer.
!!
! Reserve button (SET)
!!
Press this button to reserve time settings.
(A receiving beep is heard.)
""
" Cancel button (CLR)
""
Press this button to cancel ON timer and OFF
timer. (A receiving beep is heard.)
##
# High power button (Hi POWER)
##
Press this button to start the high power
operation.
: Dry,
)
,
)
$$
$Memory button (MEMO)
$$
Press this button to stand by memorizing the
settings.
Press the button again for more than 4 seconds
to memorize the setting indicated on the remote
control and
%%
%Automatic operation button (AUTO)
%%
mark is indicated.
Press this button to operate the air conditioner
automatically.
(A receiving beep is heard.)
&&
&ECO timer button (ECO)
&&
Press this button to start the ECO timer (OFF
timer) operation.
You can select the OFF timer time from among
four settings (1,3,5 or 9 hours).
((
(FILTER button
((
Press this button to turn off the filter cleaning
lamp on the indoor unit.
Press this button after cleaning the air filter.
))
)PRESET button
))
Press this button to operate the air conditioner
according to settings memorized by the MEMO
button.
~~
~TIMER button
~~
Use this button to change the clock, ON timer,
and OFF timer times.
To forward the time, press the “TIMER
To set back the time, press the “TIMER
1
AUTOA
AB
4
4
2
2
5
5
6
6
9
9
8
8
16
16
START/STOP
FANMODE
SWING
7
7
FIX
ON
OFFSETCLR
FILTER
ECO
TIMER
PRESET
AUTO
Hi-POWER
MEMO
CLOCK CHECKRESET
” button.
” button.
13
17
3
3
14
14
15
15
12
12
13
17
11
11
10
10
18
18
– 34 –
Page 35
8-5-2. Names and functions of indications on remote control
Display
All indications, except for clock time indication, are indicated by pressing the START/STOP button.
11
1 Transmission mark
11
This transmission mark (,) indicates when the remote control transmits signals to the indoor unit.
22
2 Mode display
22
Indicates the current operation mode.
(AUTO : Automatic control, A : Auto changeover control, : Cool,
: Dry, : Heat,
33
3 Temperature display
33
: Fan only)
Indicates the temperature setting (17°C to 30°C).
When you set the operating mode to
: Fan only, no temperature
setting is indicated.
44
4 Louver operation display
44
1
3
2
AUTOA
8
AB
Indicates the louver positioning and operation.
Five selectable positions
55
5 FAN speed display
55
,,,,
Automatic Swing
Indicates the selected fan speed. AUTO or one of five fan speed levels
+
(LOW
, LOW
, MED
, MED
can be indicated.
Indicates AUTO when the operating mode is either AUTO or
66
6 TIMER and clock time display
66
The time set for timer operation or clock time is indicated.
The present time is always indicated except for TIMER operation.
77
7 Hi POWER display
77
+
, HIGH
: Dry.
9
)
7
• In the illustration, all indications
are indicated for explanation.
During operation, only the
relevant indications will be
indicated on the remote control.
5
Indicates when the Hi POWER operation starts.
Press the Hi POWER button to start and press it again to stop
the operation.
88
(MEMORY) display
8
88
A
AB
Flashes for 4 seconds when the MEMO button is pressed during
operation.
mark is indicated when keeping the button depressed for more
than 4 seconds while the mark is flashing.
Press another button to turn off the mark.
99
9 ECO TIMER display
99
Indicates when the ECO TIMER is in operation.
Each time you press the ECO button, the display changes in the sequence of 1,3,5 or 9h.
4
6
– 35 –
Page 36
9. INSTALLATION PROCEDURE
9-1. Safety Cautions
For general public use
Power supply cord of parts of appliance for Outdoor use shall be more than polychloroprene sheathed flexible cord (design H07RN-F), or cord
designation 245IEC66. (1.5 mm
2
or more)
CAUTION
• THIS AIR CONDTIONER ADOPTS THE NEW HFC REFRIGERANT (R-410A) WHICH DOES NOT DESTROY OZONE LAYER.
R-410A refrigerant is apt to be affected by impurity such as water , oxidizing membrane, and oils because pressure of R-410A refrigerant
is approx. 1,6 times of refrigerant R-22. Accompanied with adoption of the new refrigerant, refrigerating machine oil has been also changed.
Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerating machine oil does not enter into the refrigerating
cycle or new-refrigerant air coditioner.
To prevent mixin of refrigerant or refrigerating machine oil, the sizes of connecting sections of charging port of the main unit or installation tools are
different from those for the coventional refrigerant. Accordingly, the exclusive tools are required for the new refrigerant (R-410A) as shown below.
For conecting pipes, use new and clean piping materials with high pressure-tight force, which were made fro R-410A only, so that water or dust
does not enter. Moreover, do not use the existing piping because there are problems about pressure-tight forec and inner impurity in the existing
piping.
CAUTION
This appliance must be connected to the main power supply by means of a circuit breaker or a switch with a contact separation of at least 3 mm.
The installation fuse (25A D type
(RAS-13UKV-E only)
New Refrigerant Air Conditioner Installation
TO DISCONNECT THE APPLIANCE FROM THE MAIN POWER SUPPLY.
) must be used for the power supply line of this air conditioner.
DANGER
• FOR USE BY QUALIFIED PERSONS ONLY.
• TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE ALL POWER SWITCHES ARE OFF.
FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
• CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED BY WRONG WAY, ELECTRIC PARTS
MAY BE DAMAGED.
• CHECK THE EARTH WIRE IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION.
• DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS.
FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
• TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD, PLACE THE UNIT WELL AWAY (MORE THAN 2 M)
FROM HEAT SOURCES SUCH AS RADIATORS, HEAT REGISTORS, FURNACE, STOVES, ETC.
• WHEN MOVING THE AIR-CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN, BE VERY CAREFUL NOT TO GET THE
SPECIFIED REFRIGERANT WITH ANY OTHER GASEOUS BODY INTO THE REFRIGERATION CYCLE. IF AIR OR ANY O THER GAS IS
MIXED IN THE REFRIGERANT, THE GAS PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNORMALLY HIGH AND IT
RESULTINGLY CAUSES BURST OF THE PIPE AND INJURIES ON PERSONS.
• IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE INSTALLATION WORK, IMMEDIATELY LET
FRESH AIR INTO THE ROOM. IF THE REFRIGERANT GAS IS HEATED BY FIRE OR SOMETHING ELSE, IT CAUSES GENERATION OF
POISONOUS GAS.
WARNING
• Never modify this unit by removing any of the safety guards or by by-passing any of the safety interlock switches.
• Do not install in a place which cannot bear the weight of the unit.
Personal injury and property damage can result if the unit falls.
• Before doing the electrical work, attach an approved plug to the power supply cord.
And, make sure the equipment to be earthed.
• Appliance shall be installed in accordance with national wiring regulations.
If you detect any damage, do not install the unit. Contact your Toshiba dealer immediately.
CAUTION
• Exposure of unit to water or other moisture before installation will result in an electrical short.
Do not store in a wet basement or expose to rain or water.
• After unpacking the unit, examine it carefully for possible damage.
• Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify the noise level of the unit or where
noise and discharged air might disturb neighbors.
• To avoid personal injury, be careful when handling parts with sharp edges.
• Please read this installation manual carefully before installing the unit. It contains further important instructions for proper installation.
– 36 –
Page 37
9-1-1. Installation/Servicing Tools
Changes in the product and components
In the case of an air condition using R-410A, in order to prevent any other refrigerant from being charged accidentally, the service port diameter
of the outdoor unit control valve (3 way valve) has been changed. (1/2 UNF 20 threads per inch)
• In order to increase the pressure resisting strength of the refrigerant piping, flare processing diameter and size of opposite side of flare nuts
has been changed. (for copper pipes with nominal dimensions 1/2 and 5/8)
New tools for R-410A
New tools for R-410AApplicable to R-22 modelChanges
As pressure is high, it is impossible to measure by means of conventional gauge .
Gauge manifold
Charge hose
Electronic balance for
refrigerant charging
Torque wrench
(nominal diam. 1/2, 5/8)
Flare tool
(clutch type)
Gauge for projection adjustment
Vacuum pump adapter
Gas leakage detector
In order to prevent any other refrigerant from being charged, each port diameter
has been changed.
In order to increase pressure resisting strength, hose materials and port size
have been changed (to 1/2 UNF 20 threads per inch).
When purchasing a charge hose, be sure to confirm the port size.
As pressure is high and gasification speed is fast, it is difficult to read the
indicated value by means of charging cylinder, as air bubbles occur.
The size of opposite sides of flare nuts have been increased. Incidentally,
a common wrench is used for nominal diameters 1/4 and 3/8.
By increasing the clamp bar's receiving hole, strength of spring in the tool has
been improved.
Used when flare is made by using conventional flare tool.
Connected to conventional vacuum pump. It is necessary to use an adapter to
prevent vacuum pump oil from flowing back to the charge hose.
The charge hose connecting part has two ports-one for conventional refrigerant
(7/16 UNF 20 threads per inch) and one for R410A. If the vacuum pump oil
(mineral) mixes with R-410A a sludge may occur and damage the equipment.
Exclusive for HFC refrigerant.
• Incidentally, the “refrigerant cylinder” comes with the refrigerant designation (R-410A) and protector coating in the U.S's ARI specified rose color
(ARI color code: PMS 507).
• Also, the “charge port and packing for refrigerant cylinder” require 1/2 UNF 20 threads per inch corresponding to the charge hose's port size.
– 37 –
Page 38
9-2. Indoor unit
RAS-M10UKCV-E
RAS-M13UKCV-E
RAS-M16
UKCV-E
5
Zeolite filter
Before installing the wireless
remote control
• With the remote control cover
open, load the batteries supplied
correctly, observing their
polarity.
2 Wireless remote control
Cover
170 mm
or more
Air filter
(Attach to the front panel)
6
Purifying filter
2
Wireless remote
control
Hook
8
Flat head wood screw
4
Remote control holder
Hook
65 mm or more
1
Installation
plate
Shield pipe
170 mm
or more
For the rear left and left piping
Wall
Insert the cushion between
the indoor unit and wall,
and tilt the indoor unit for better
operation.
Do not allow the drain hose to
get slack.
Cut the piping hole
sloped slightly
Make sure to run the drain hose
sloped downward.
The auxiliary piping can be
connected the left, rear left,
rear right, right, bottom right or
bottom left.
3 Batteries
Insulate the refrigerant
pipes separately with insulation,
not together.
6 mm thick heat resisting
polyethylene foam
9-2-1. Accessory and Installation Parts
Part
No.
Part name (Q'ty)
1
Installation plate x 1
2
Wireless remote control x 1
3
Battery x 2
Others
Name
Owner's manual
Installation manual
This model is not equipped with an extension drain hose.
Option :
For the extension drain hose, use an optionally available
RB-821SW or commercially available one.
Part
No.
Part name (Q'ty)
4
Remote control holder x 1
5
Zeolite filter x 1
6
Purifying filter x 1
Right
Part
No.
Rear right
Rear left
Bottom right
Part name (Q'ty)
7
Mounting screw ∅4 x 25 s x 6
8
Flat head wood screw ∅3.1 x 16 s x 2
9
B Label x 1
B
Left
Bottom left
– 38 –
Page 39
9-2-2. Installation Place
∅65 mm
100 mm
• A place which provides the spaces around the indoor unit as shown in
the above diagram.
• A place where there is no obstacle near the air inlet and outlet.
• A place which allows easy installation of the piping to the outdoor unit.
•
A place which allows the front panel to be opened.
• The indoor unit shall be installed as top of the indoor unit comes to at
least 2m height.
Also it must be avoided to put anything on the top of the indoor unit.
CAUTION
• Direct sunlight to the indoor unit wireless receiver should be
avoided.
• The microprocessor in the indoor unit should not be too close to
r-f noise sources.
(For details, see the owner's manual.)
Remote controller
• A place where there are no obstacles such as a curtain that may block
the signal from the indoor unit.
• Do not install the remote control in a place exposed to direct sunlight
or close to a heating source, such as a stove.
• Keep the remote control at least 1 m apart from the nearest TV set or
stereo equipment. (This is necessary to prevent image disturbances or
noise interference.)
• The location of the remote control should be determined as shown
below.
Remote
control
(Top view)
Indoor unit
Reception range
* : Axial distance
Fig. 9-2-1
5 m
45°
5 m
45°
Remote control
* 7 m
(Side view)
7 m
Indoor unit
75°
Reception
range
9-2-3. Cutting a Hole and Mounting Installation Plate
Cutting a Hole
When install the refrigerant pipes from the rear.
Mounting the Installation Plate
For installation of the indoor unit, use the paper pattern on the back.
Anchor bolt holes
62
82.5
1
Installation
plate
170
85
Pipe hole
Indoor unit
Hook
Hook
Thread
Weight
Hook
7
Mounting screw
Pipe hole
Fig. 9-2-3
When the installation plate is directly mounted on the wall
1.Securely fit the installation plate onto the wall by screwing it in the
upper and lower parts to hook up the indoor unit.
2.To mount the installation plate on a concrete wall with anchor bolts,
utilize the anchor bolt holes as illustrated in the above figure.
3. Install the installation plate horizontally in the wall.
CAUTION
When installing the installation plate with a mounting screw, do not
use the anchor bolt hole. Otherwise the unit may fall down and result
in personal injury and property damage.
Anchor bolt
5 mm dia. hole
Clip anchor
(local parts)
7 Mounting
screw
∅4 x 25 s
Fig. 9-2-4
Projection
15 mm or less
2 m or more from floor
Pipe
hole
The center of the pipe
hole is above the arrow.
Fig. 9-2-2
1.After determining the pipe hole position on the mounting plate (A)
drill the pipe hole (∅65 mm) at a slight downward slant to the outdoor
side.
NOTE
• When drilling a wall that contains a metal lath, wire lath or metal plate,
be sure to use a pipe hole brim ring sold separately.
CAUTION
Failure to firmly install the unit may result in personal injury and
property damage if the unit falls.
• In case of block, brick, concrete or similar type walls, make 5 mm dia.
holes in the wall.
• Insert clip anchors for appropriate 7 mounting screws.
NOTE
• Install the installation plate using 4 to 6 pieces of mounting screw
securing four corners with screws.
9-2-4. Electrical Work
1.The supply voltage must be the same as the rated voltage of the air
conditioner.
2.Prepare the power source for exclusive use with the air conditioner.
NOTE
• Wire type : More than H07RN-F or 245IEC66 (1.0 mm2 or more)
– 39 –
Page 40
CAUTION
• This appliance can be connected to the mains in either of the
following two ways.
(1) Connection to fixed wiring :
A switch or circuit breake which disconnects all poles and
has a contact separation of at least 3 mm must be incorporate in the fixed wiring. An approved circuit breaker or
switches must used.
(2) Connection with power supply plug :
Attach power supply plug with power cord and plug it into
wall outlet. An approved power supply cord and plug must
be used.
NOTE
• Perform wiring works so as to allow a generous wiring capacity.
9-2-5. Wiring Connection
How to connect the connecting cable
Wiring of the connecting cable can be carried out without
removing the front panel.
1.Remove the air inlet grille.
Open the air inlet grille upward and pull it toward you.
2.Remove the terminal cover and cord clamp.
3.Insert the connecting cable (according to the local cords) into the pipe
hole on the wall.
4.Take out the connecting cable through the cable slot on the rear panel
so that it protrudes about 15 cm from the front.
5.Insert the connecting cable fully into the terminal block and secure it
tightly with screws.
6.Tightening torque :1.2 N·m (0.12 kgf·m)
7.Secure the connecting cable with the cord clamp.
8.Fix the terminal cover, rear plate bushing and air inlet grille on the
indoor unit.
9-2-6 Piping and Drain Hose Installation
Piping and Drain Hose Forming
* Since dewing results in a machine trouble, make sure to insulate both
the connecting pipes. (Use polyethylene foam as insulating material.)
Rear right
Rear left
Bottom left
Changing
Left
Bottom right
Right
Die-cutting
Front panel slit
drain hose
Piping preparation
1. Die-cutting Front panel slit
Cut out the slit on the left or right side of the front panel for the left or
right connection and the slit on the bottom left or right side of the front
panel for the bottom left or right connection with a pair of nippers.
2. Changing drain hose
For left connection, left-bottom connection and rear-left connection’s
piping, it is necessary to change the drain hose and drain cap.
How to remove the Drain Cap
Clip drain cap by needle-nose plier, and pull out.
CAUTION
• Be sure to refer to the wiring system diagram labeled inside the
front panel.
• Check local electrical cords and also any specific wiring instruc-
tions or limitations.
Cord clampTeminal block
15
cm
Screw
Screw
Earth wire
Connecting cable
80 mm
10mm
10mm
3
2
1
10mm
50 mm
Earth line
Terminal cover
Screw
NOTE
• Wire type : More than H07RN-F or 245IEC66 (1.0 mm2 or more)
Connecting cable
about
Fig. 9-2-6
How to install the Drain Hose
Firmly insert drain hose connecting part until hitting on a heat insulator.
Heat insulator
Drain hose
Fig. 9-2-7
How to fix the Drains Cap
1)Insert hexagonal wrench (4 mm) in a center head.
4 mm
Fig. 9-2-8
2)Firmly insert drains cap.
No gap
Do not apply lubricating oil (refrigerant
machine oil) when inserting the drain cap.
Application causes deterioration and
drain leakage of the plug.
Insert a hexagon wrench (4 mm)
Fig. 9-2-9
Fig. 9-2-5
CAUTION
Firmly insert the drain hose and drain cap; otherwise, water may leak.
– 40 –
Page 41
In case of right or left piping
• After scribing slits of the front panel
with a knife or a making-off pin, cut
them with a pair of nippers or an
equivalent tool.
Slit
Fig. 9-2-10
In case of bottom right or bottom left piping
• After scribing slits of the front panel
with a knife or a making-off pin, cut
them with a pair of nippers or an
equivalent tool.
Slit
Fig. 9-2-11
Left-hand connection with piping
Bend the connecting pipe so that it is laid within 43 mm above the wall
surface. If the connecting pipe is laid exceeding 43 mm above the wall
surface, the indoor unit may unstably be set on the wall. When bending
the connecting pipe, make sure to use a spring bender so as not to
crush the pipe.
Bend the connection pipe within a radius of 30 mm (Ø6.35) 40 mm
(Ø9.52).
To connect the pipe after installation of the unit (figure)
(To the forefront of flare)
270 mm
170 mm
R30 or less (Ø6.35) R40 or less (Ø9.52) (Use polisin
(polyethylene core or the like for bending pipe.)
43 mm
Liquid side
Gas side
Outward form of indoor unit
9-2-6 Indoor Unit Fixing
1.Pass the pipe through the hole in the wall, and hook the indoor unit on
the installation plate at the upper hooks.
2.Swing the indoor unit to right and left to confirm that it is firmly hooked
up on the installation plate.
3.While pressing the indoor unit onto the wall, hook it at the lower part
on the installation plate. Pull the indoor unit toward you to confirm that
it is firmly hooked up on the installation plate.
1
2
Hook
Hook here
1
Installation plate
Press
(unhook)
Fig. 9-2-14
• For detaching the indoor unit from the installation plate pull the indoor
unit toward you while pushing its bottom up at the specified parts.
Push
Push
Fig. 9-2-15
9-2-7 Drainage
1.Run the drain hose sloped downwards.
NOTE
• Hole should be made at a slight downward slant on the outdoor side.
Do not rise the drain hose.
Do not form the drain hose into the
waved shape.
°
0
Use the handle of screwdriver, etc.
8
Fig. 9-2-12
NOTE
If the pipe is bent incorrectly, the indoor unit may unstably be set on the
wall.
After passing the connecting pipe through the pipe hole, connect the
connecting pipe to the auxiliary pipes and wrap the facing tape around
them.
CAUTION
• Bind the auxiliary pipes (two) and connecting cable with facing tape
tightly. In case of leftward piping and rear-leftward piping, bind the
auxiliary pipes (two) only with facing tape.
Indoor unit
Auxiliary pipes
Installation plate
Fig. 9-2-13
• Carefully arrange pipes so that any pipe does not stick out of the
rear plate of the indoor unit.
• Carefully connect the auxiliary pipes and connecting pipes to each
other and cut off the insulating tape wound on the connecting pipe
to avoid double-taping at the joint, moreover, seal the joint with the
vinyl tape, etc.
• Since dewing results in a machine trouble, make sure to insulate
both the connecting pipes. (Use polyethylene foam as insulating
material.)
• When bending a pipe, carefully do it not to crush it.
Connecting cable
50 mm
or more
Do not put the
drain hose end
into water.
Do not put the
drain hose end
in the drainage
ditch.
Fig. 9-2-16
2.Put water in the drain pan and make sure that the water is drained out
of doors.
3.When connecting extension drain hose, insulate the connecting part
of extension drain hose with shield pipe.
Shield pipe
Inside the roomDrain hose
Extension drain hose
Fig. 9-2-17
CAUTION
Arrange the drain pipe for proper drainage from the unit.
Improper drainage can result in dew-dropping.
This air conditioner has the structure
designed to drain water collected from
dew, which forms on the back of the
indoor unit, to the drain pan.
Therefore, do not store the power cord
and other parts at a height above the
drain guide.
Space for pipes
Fig. 9-2-18
Wall
Drain
guide
– 41 –
Page 42
9-2-8. Setting of Remote Controller Selector
Switch
When two indoor units are installed in the
separated rooms, there is no need to change
the select switches.
Remote Controller Selector Switch
• When two indoor units are installed in the
same room or adjacent two rooms, if operating
a unit, two units may receive the remote
controller signal simultaneously and operate. In
this case, the operation can be preserved by
setting either one indoor unit and remote
controller to B setting
(Both are set to A setting in factory shipment).
• The remote control signal is not received
when the settings of indoor unit and remote
controller are different.
• There is no relation between A setting/B
setting and A room/B room when connecting
the piping and cables.
(1) Stop the operation of the air conditioner and turn
turn off its main power supply.
(2) Pull the air inlet grille toward you to open it and
remove the air inlet grille.
(3) First open the horizontal louver and then remove
the front panel from the back body by pulling it
toward you.
Position of Remote Control Selector Switch
1. Setting of remote controller switch at the
indoor unit side
How to remove the front cabinet
Fig. 9-2-20
How to mount the front panel
Push the front panel back in and make sure all hook
are locked.
Adhesion of B label (When setting to [B])
Be sure to affix the B label on the front panel same
as the below figure.
Fig. 9-2-19
Fig. 9-2-21
– 42 –
Page 43
2. Setting of remote controller selector at the
remote controller side
[B] of the remote controller is displayed with
liquid crystal only when it is set to [B].
There is no display of [A].
• Enter the batter.
• Push the [CHK] button by something with thin
edge. ([00] is displayed.)
INFORMATION
• If [MODE] button is pushed while pushing [CHK]
button, the small [B] is displayed at the right of the
setting temperature indication section.
To reset [A] setting, push the [MODE] button
*
again while pusing the [CHK] button.
3. Confirm the indoor unit can operate with
the changed setting of the remote controller.
9-2-9. Check and Test Operation
¨1. Check the unit is firmly hooked up on the
installation plate.
¨2. Check the connecting pipes tightened
securely.
Confirm that there is no gas leakage.
¨3. Confirm that all connecting cables are
secured and correct.
¨4. Check the pipes insulation.
¨5. Check the drainage.
¨6. Connection of the grounding wire.
¨7. To switch the TEST RUN (COOL) mode, turn
the switch on.
To switch the TEST RUN (COOL) mode,
press TEMPORARY button for 10 sec.
(The beeper will make a short beep.)
MODE button
The above remote controller is one for cooling
*
only model.
B
PRESET
START/STOP
AUTO
MODE
FAN
SWING
FIX
ON OFF SET CLR
FILTER
ECO
TIMER
Hi-POWER
MEMO
CLOCK CHECKRESET
Fig. 9-2-22
[CHK] button
B
TEMPORARY button
TEMPORARY button
Fig. 9-2-23
¨8. Operate the unit at cooling operation mode
for fifteen minutes or more .
Measure the temperature of the intake and
discharge air. Ensure the difference between
the intake temperature and the discharge one
is more, than 8°C.
NOTE: Three-minutes protection feature
A protection feature prevents the air
conditioner from being activated for about 3
minutes when it is restarted immediately
after operation or when the power switch is
turned on.
¨9. Check the remote controller operation.
When finished the check and test operation,
make sure to return to REMOTE CONTROLLER.
(Push the temporary switch with once again.)
¨ 10. Explain to the customer on the correct usage
of air conditioner simplelayman’s terms.
– 43 –
Page 44
9-3. Outdoor Unit
CAUTION
9-3-1. Accessory and Installation Parts
1
Owner's manual x 1
2
Outdoor unit installation manual x 1
S
P
E
C
IF
IC
A
TIO
N
S
3
Specifications x 1
9-3-2. Refrigerant Piping
• Piping kit used for the conventional refrigerant
cannot be used.
• Use copper pipe with 0.8 mm or more thick-
ness.
• Flare nut and flare works are also different from
those of the conventional refrigerant. Take out the
flare nut attached to the main unit of the air conditioner, and use it.
9-3-3. Installation Place
• A place which provides the spaces around the
outdoor unit.
• A place where the operation noise and discharged
air do not disturb your neighbors.
• A place which is not exposed to a strong wind.
• A place which does not block a passage.
• When the outdoor unit is to be installed in an
elevated position, be sure to secure its feet.
• There must be sufficient spaces for carrying the
unit into and out of the site.
• A place where the drain water does not raise any
problem.
1. Install the outdoor unit without anything
blocking the air discharging.
2. When the outdoor unit is installed in a place
exposed always to a strong wind like a coast
or on a high story of a building, secure the
normal fan operation using a duct or a wind
shield.
3. Specially in windy area, install the unit to
prevent the admission of wind.
Strong
wind
Fig. 9-3-1
4. Installation in the following places may result
in trouble. Do not install the unit in such
places.
• A place full of machine oil.
• A place full of sulfide gas.
• A place where high-frequency waves are
likely to be generated as from audio
equipment, welders, and medical equipment.
9-3-4. Optional Installation Parts
(Local Supply)
Parts name
Refrigerant piping
A
Liquid side: Ø6.35 mm
Gas side: Ø9.52 mm or Ø12.7 mm
B
Pipe insulating material
(polyethylene foam, 6 mm thick)
1. Take away dust and moisture .
(Inside of the connecting pipes)
2. Tight connection (between pipes and unit)
3. Evacuate the air in the connecting pipes using
VACUUM PUMP.
4. Check gas leak. (connected points)
Flaring
1. Cut the pipe with a pipe cutter.
• Flaring siz e : A (Unit : mm)
+0
A
Outer dia. of copper pipe
6.35
9.52
12.7
In the case of flaring for R410A with the conven-
*
tional flare tool, pull out it approx.
R410AR22
0.5 mm more than that for R22 to
- 0.4
9.1 9.0
13.213.0
16.616.2
A
adjust to the specified flare size.
The copper pipe gauge is useful
for adjusting projection margin size.
Fig. 9-3-4
9-3-7. Installation
NOTE : For installation, at least 3 dimensions should
be kept free from obstacles (walls).
90˚
Obliquity RoughnessWarp
Fig. 9-3-2
2. Insert a flare nut into the pipe, and flare the pipe.
As the flaring sizes of R410A differ from those of
refrigerant R22, the flare tools newly manufactured for R410A are recommended.
However, the con ventional tools can be used by
adjusting projection margin of the copper pipe.
B
Fig. 9-3-3
• Projection margin in flaring : B (Unit : mm)
Rigid (Clutch type)
Outer dia. of
copper pipe
6.35
9.52
12.7
R410A tool used
R410AR22
0 to 0.5 (Same as left)
0 to 0.5 (Same as left)
0 to 0.5 (Same as left)
Conventional tool used
R410AR22
1.0 to 1.50.5 to 1.0
1.0 to 1.50.5 to 1.0
1.0 to 1.50.5 to 1.0
100mm or
more from w
all
200mm or more
As shown in the figure, hang power cord
and connecting cable downward, and
take out it along piping connection port.
50mm or more
600mm or more
from wall
250mm or
more from w
Fig. 9-3-5
Fixing bolt arrangement of outdoor unit
600
Suction side
115
310
76
Fig. 9-3-6
all
Imperial (Wing nut type)
Outer dia. of copper pipe
6.35
9.52
12.7
R410AR22
1.5 to 2.01.0 to 1.5
1.5 to 2.01.0 to 1.5
2.0 to 2.51.5 to 2.0
– 45 –
Diffuser
Drain hole
• Secure the outdoor unit with the fixing bolts
and nuts if the unit is likely to be e xposed to a
strong wind.
• Use Ø8 mm or Ø10 mm anchor bolts and nuts.
Page 46
1. Piping connections to the outdoor unit should be
arranged in the sequence A, B, C
starting from
the bottom.
(For each piping connection, the gas pipe is on
the bottom and the liquid pipe is on the top.)
2. When multiple indoor units are to be connected to
the outdoor unit, make the ends of the pipes and
wires from each indoor unit to ensure that they
will be connected to the outdoor unit correctly.
(Problems caused by indoor units being connected to the outdoor unit incorrectly are very
common in multiple-unit installations.)
3. The length and height difference of the connecting pipes between the indoor and outdoor units
must be within the ranges indicated below.
• T otal piping length :
4 units (A + B + C
Non. Additional refrigerant
) Multi,
:40 m or less
• Minimum piping length :
A or B or C
= 2 m or more
• Maximum indoor piping length :
A or B or C
• Maximum piping height difference :
A or B or C
• Maximum piping/height
difference between 2
= 20 m or less
= 10 m or less
rooms
A
Outdoor
unit
C
= 10 m or less
10 m or less
Fig. 9-3-7
B
4. If the outdoor units is to be mounted on a wall,
make sure that the platform supporting it is
sufficiently strong. The platform should be
designed and manufactured to maintain its
strength over a long period of time, and sufficient
consideration should be given to ensuring that the
outdoor unit will not fall.
5. When the outdoor unit is to be mounted high on a
wall, take particular care to ensure that parts do
not fall installer is protected.
6. When doing installation work on level ground, it is
usual to wiring and piping connections to the
indoor units. And/then make to the outdoor unit.
However if outdoor work is difficult it is possible
instead to make changes to the procedure.
For example by making adjustments to the wiring
and piping length on the inside (rather than the
outside).
How to remove the side panel
1. Remove a screws
value.
of the
2. Pull the
downward.
value cover
Valve
cover
Fig. 9-3-8
Tightening connection
Align the centers of the connecting pipes and tighten
the flare nut as far as possible with your fingers.
Then tighten the nut with a spanner and torque
wrench as shown in the figure.
CAUTION
• Do not apply excess torque. Otherwise, the
nut may crack depending on the conditions.
(Unit : N·m)
Outer dia. of copper pipe
Ø6.35 mm
Ø9.52 mm
Ø12.7 mm
• Tightening torque of flare pipe connections
Pressure of R410A becomes higher than that of R22.
(Approx. 1.6 times) Therefore, using a torque
wrench, tighten firmly the flare
pipe connecting sections
which connect the indoor
and outdoor units up to the
specified tightening torque.
Incorrect connections may
cause not only a gas
leakage, but also a trouble
of the refrigeration cycle.
14 to 18 (1.4 to 1.8 kgf•m)
33 to 42 (3.3 to 4.2 kgf•m)
50 to 62 (5.0 to 6.2 kgf•m)
Flare at
indoor
unit side
Flare at
outdoor
unit side
Flare nut
Internally
threaded side
Use a torque wrench to tighten.
C UNIT
B UNIT
A UNIT
Indoor unit
– 46 –
Page 47
9-3-8. Evacuating
After the piping has been connected to all indoor
unit(s), you can perform the air purge together at
once.
AIR PURGE
Evacuate the air in the connecting pipes and in
the indoor unit using vacuum pump.
Do not use the refrigerant in the outdoor unit.
For details, see the manual of vacuum pump.
Use a vacuum pump
Be sure to use a vacuum pump with counter-flow
prevention function so that inside oil of the pump
does not flow backward into pipes of the air conditioner when the pump stops.
(If inside oil of the vacuum pump enters into the air
conditioner which adopts R410A, a trouble of the
refrigeration cycle may be caused.)
1. Connect the charge hose from the manifold valve
to the service port of the gas side packed valve.
2. Connect the charge hose to the port of vacuum
pump.
3. Open fully the low pressure side handle of the
gauge manifold valve.
4. Operate the vacuum pump to start for evacuating.
Perform evacuating for about 15 minutes if the
piping length is total 20 meters. (15 minutes for
total 20 meters) (assuming a pump capacity of 27
liters per minute.)
Then confirm that the compound pressure gauge
reading is –101 kPa ( –76 cmHg).
5. Close the low pressure side valve handle of
gauge manifold.
6. Open fully the valve stem of the packed valves
(both sides of Gas and Liquid).
7. Remove the charging hose from the service port.
8. Securely tighten the caps on the packed valves.
Packed valve handling precautions
• Open the valve stem all the way out ; do not try to
open it beyond the stopper.
• Securely tighten the valve stem cap in torque is as
follows :
Gas side (Ø12.7 mm)
Gas side (Ø9.52 mm)
Liquid side (Ø6.35 mm)
Service port
50 to 62 N•m (5.0 to 6.2 kgf•m)
33 to 42 N•m (3.3 to 4.2 kgf•m)
14 to 18 N•m (1.4 to 1.8 kgf•m)
14 to 18 N•m (1.4 to 1.8 kgf•m)
Hexagonal wrench is required.
Fig. 9-3-13
9-3-9. Electrical W ork
For the air conditioner that has no pow er cord,
connect a power cord to it as mentioned below.
Power supply
Maximum running current
Installation fuse rating
Power cord
220 – 240 V
Single phase 50/60 Hz
11 A
15 A
2,0 mm2 (AWG-14) or more
Compound pressure gauge Pressure gauge
-101kPa (-76cmHg)
Handle Lo
Charge hose
(For R410A only)
Connecting
pipe
Service port
(Valve core (Setting pin))
B
A
Packed valve at liquid side
Packed valve at gas side
Manifold valve
Handle Hi
(Keep full closed)
Charge hose
(For R410A only)
Vacuum pump adapter
for counter-flow prevention
(For R410A only)
Vacuum
pump
Fig. 9-3-12
How to wire
1. Connect the connecting cable to the terminal as
identified with their respective matched numbers
on the terminal block of indoor and outdoor unit.
(1.0 mm2 AWG 18 or more)
2. When connecting the connecting cable to the
outdoor unit terminal, prevent water coming in the
outdoor unit.
3. Insulate the unused cords (conductors) stripped
the sheath of connecting cable with PVC tape.
Process them so that they do not touch any
electrical or metal parts.
4. For inter-unit wiring, do not use a cut wire jointed
to another on the way.
Use wires long enough to cover the entire length.
– 47 –
Page 48
Three room (A + B + C) Multi
Terminal block
(Connecting cable)
Screw
Connecting cable
(A unit)
Power cordConnecting cable
Connecting cable
(C unit)
Fig. 9-3-14
CAUTION
(B unit)
9-3-10. Check and Test Operation
For R410A, use the leak detector exclusively
manufactured for HFC refriger ant (R410A,
R134a, etc.).
The conventional leak detector for HCFC refriger-
*
ant (R22, etc.) cannot be used because its sensitivity for HFC refrigerant lowers to approx. 1/40.
• Pressure of R410A becomes approx. 1.6 times of
that of R22. If installation work is incompletely
finished, a gas leakage may occur in the cases
such as pressure
rise during operation. Therefore, be sure to test
the piping connections for leaking.
• Wrong wiring connection may cause some
electrical parts burn out.
• Be sure to use the cord clamps specified
positions with attached to the product.
• Do not damage or scratch the conductive core
and inner insulator of power and inter-connecting cables when peeling them.
• Be sure to comply with local cords on running
the wire from outdoor unit to indoor unit (size of
wire and wiring method etc.)
• Use the power cord and Inter-connecting cab le
with specified thickness, specified type, and
protective devices specified.
Stripping length power cord and connecting cable
10
40
Connecting
cable
30
10
LN
10
40
Earth lineEarth line
Power cord
30
123
10
Fig. 9-3-15
Flare nut connections
(Indoor unit)
• Flare nut connections(Outdoor unit)
• Valve stem cap connection
• Service port cap connection
Fig. 9-3-16
• Check the flare nut connections, valve stem cap
connections and service port cap connections for
gas leak with a leak detector or soap water.
CAUTION
• Use a circuit breaker of a type that is not
tripped by shock waves.
• If incorrect/incomplete wiring is carried out, it
will cause an electrical fire or smoke.
• Prepare the power supply f or exclusive use
with the air conditioner.
• This product can be connected to the mains.
Connection to fixed wiring :
A switch or circuit breaker which disconnects
all poles and has a contact separation of at
least 3 mm must be incorporate in the fixed
wiring.
An approved short circuit breaker or switches
must be used.
(A breaker having a sensitivity of approxi-
*
mately 0.1 second or less and a capacity of
approximately 30 mA is usually used.)
– 48 –
Page 49
9-3-11. Useful Functions
Self-Diagnosis by LED Indication
• For this outdoor unit, the self-diagnonsis is possible
by using five LEDs (Red).
• Refer to the table in page 68 for more details.
* LEDs (Red) (D11 to D15) locate on the sub-control
borad underneath of the inverter.
1. If a trouble occurs, LED (Red) goes on according to
the contents of trouble as shown in the table in
page 68.
2. When two or more troubles occur, LEDs go on
cyclically (alternately).
3. Usually, LEDs (Red) go off.
Wiring port
9-3-12. Miswiring (Mispiping) Check
Make sure that the wiring and piping for each room
have the same alphabetical codes (A, B, C).
Connect and secure the power cord.
Use the power cord/cables with thickness, type and
protective devices specified in this man ual.
Insulate the unused cords (conductors) with PVC
tape.
1. Turn on the power breaker.
2. Open side panel of the outdoor unit.
3. Start the check.
• Run the indoor unit in A room, and confirm cool
air blow out.
• Conform the indoor unit in B,C rooms do not run,
also check flowing sound of refrigerant is not heard.)
• Stop operation of the indoor unit in A room, and
execute the same checks on the indoor unit in
B and C rooms.
D11 D12 D13 D14 D15
LED (Red)
Fig. 9-3-14
For Singapore only y
IMPORTANT INSTRUCTIONS
To All Installers :
1) Please be reminded that all air conditioner
installed at HDB flat are subjected to amp .
restriction of either 8,5A or 11,0A.
2) It is the installer's responsibility to have the
current release control set correctly for the
type of HDB flat in which the IES unit is
installed.
3) Figure below shows how the connector can
be arranged for the appropriate setting.
Wiring port
Connector No.
Full operation
11A
(Delivery)
8,5A
CONNECTOR
(CN600)
CN600
Short
Open
– 49 –
Page 50
10. HOW TO DIAGNOSE THE TROUBLE
The pulse modulating circuits are mounted to both indoor and outdoor units. Theref ore, diagnose troubles
according to the trouble diagnosis procedure as described below. (Refer to the check points in servicing written
on the wiring diagrams attached to the indoor/outdoor units.)
Table 11-1
No.
1
2
3
4
5
6
7
8
9
First Confirmation
Primary Judgment
Judgment by Flashing LED of Indoor Unit
Self-Diagnosis by Remote Controller (Check Code)
Judgment of Trouble by Every Symptom
Trouble Diagnosis by Outdoor LED
How to Diagnose Trouble in Outdoor Unit
How to Check Simply the Main Parts
How to Simply Judge Whether Outdoor Fan Motor is Good or Bad
Troubleshooting Procedure
NOTE :
A large-capacity electrolytic capacitor is used in the
outdoor unit controller (inverter). Therefore, if the
power supply is turned off, charge (charging voltage
DC280V) remains and discharging takes a lot of
time. After turning off the power source, if touching
the charging section before discharging, an electrical
shock may be caused. Discharge the electrolytic
capacitor completely by using soldering iron, etc.
Page
51
51
52
53
56
62
63
64
70
< Discharging method >
(1) Remove the inverter cover (plating) b y opening
four mounting claws.
(2) As shown below, connect the discharge
resistance (approx. 100Ω/40W) or plug of the
soldering iron to voltage between + – terminals of
the C13 (“CAUTION HIGH VOLT AGE 320V” is
indicated.) electrolytic capacitor (760µF/400V) on
P.C. board, and then perform discharging.
Discharging position
(Discharging period
10 seconds or more)
Fig. 11-1
Plug of
soldering iron
Inverter cover
P. C. board
(Soldered surface)
– 50 –
Page 51
10-1. First Confirmation
10-1-1. Confirmation of Power Supply
Confirm that the power breaker operates (ON) normally.
10-1-2. Confirmation of Power Voltage
Confirm that power voltage is AC 220–240V ± 10%.
If power voltage is not in this range, the unit may not
operate normally.
Table 10-1-1
10-1-3. Operation Which is not a Trouble
(Program Operation)
For controlling the air conditioner, the program
operations are built in the microcomputer as described in the following table. If a claim is made for
running operation, check whether or not it meets to
the contents in the following tab le. When it does, we
inform you that it is not trouble of equipment, but it is
indispensable for controlling and maintaining of air
conditioner.
No.
1
2
3
4
5
Operation of air conditioner
When power breaker is turned “ON”, the
operation lamp (Green) of the indoor unit
flashes.
Compressor may not operate even if the
room temperature is within range of
compressor-ON.
In DRY and ECONO. mode, FAN (air flow)
display does not change even though FAN
(air flow select) button is operated.
Increasing of compressor motor speed
stops approx. 30 seconds after operation
started, and then compressor motor speed
increases again approx. 30 seconds after.
The set value of the remote control should
be below the room temperature.
Description
The OPERATION lamp of the indoor unit flashes when
power source is turned on. If “START/STOP” button is
operated once, flashing stops. (Flashes also in power
failure)
The compressor does not operate while compressor
restart delay timer (3-minutes timer) operates.
The same phenomenon is found after power source has
been turned on because 3-minutes timer operates.
The air flow indication is fixed to [AUTO].
For smooth operation of the compressor, the compressor
motor speed is restricted to Max. 33 rps for 2 minutes and
Max. 57 rps for 2 minutes to 4 minutes, respectively after
the operation has started.
If the set value is above the room temperature, Cooling
operation is not performed. And check whether battery of
the remote control is consumed or not.
10-2. Primary Judgment
To diagnose the troubles, use the following methods.
(1) Judgment by flashing LED of indoor unit
(2) Self-diagnosis by service check remote controller
(3) Judgment of trouble by every symptom
Firstly use the method (1) for diagnosis. Then, use the method (2) or (3) to diagnose the details of troubles.
For any troub le occurred at the outdoor unit side, detailed diagnosis is possible by 5-serial LED on the inverter
P.C. board.
– 51 –
Page 52
10-3. Judgment by Flashing LED of Indoor Unit
While the indoor unit monitors the operation status of the air conditioner, if the protective circuit operates, the
contents of self-diagnosis are displayed with block on the indoor unit indication section.
Table 10-3-1
LampsSelf-diagnosis
AOPERATION lamp is blinking. (1Hz)
BOPERATION lamp is blinking. (5Hz)
COPERATION lamp is blinking. (5Hz)
DOPERATION lamp is blinking. (5Hz)
EOPERATION lamp is blinking. (5Hz)
FOPERATION and TIMER lamps are blinking.
(5Hz)
GOPERATION, TIMER and FAN ONLY lamps
are blinking.
HOPERATION, TIMER and FAN ONLY lamps
are blinking.
Power failure (when the power supply is turning on)
Thermo sensor (TA) short or break
Heat exchanger sensor (TC) short or break
Indoor fan motor lock or failure
Indoor P.C. board failure
Wrong wiring of connecting cable
• Gas shortage or other refrigerant cycle trouble
• Heat exchanger sensor open, break or short
• Overload relay or thermostat trouble of compressor
Cycle failure
NOTES:
(1) The contents of items B and C and a part of item E are displayed when air conditioner operates.
(2)
When item B and C, and item B and a part of item E occur concurrently, priority is given to the block of item B.
(3) The check codes can be confirmed on the remote controller for servicing.
(4)When connecting the changing kit, first-push priority control is executed. The secondary operation lamp
continues flashing. For details, refer to the section 10. Changing Kit.
– 52 –
Page 53
10-4. Self-Diagnosis by Remote Control
(Check Code)
(1) If the lamps are indicated as shown B to H in Table
11-3-1, exchanger the self-diagnosis by the
remote control.
(2) When the remote control is set to the service
mode, the indoor controller diagnoses the operation condition and indicate the information of the
self-diagnosis on the display of the remote control
with the check codes. If a fault is detected, all
lamps on the indoor unit will blink at 5Hz and it will
beep for 10 seconds (Pi, Pi, Pi....). The timer lamp
usually blinks (5Hz) during the self-diagnosis.
10-4-1. How to use remote control in service mode
SETCLR
CLOCK CHECKRESET
AUTOA
AB
(1) Press [CHECK] button with a tip of pencil to set
the remote control to the service mode.
• “00” is indicated on the display of the remote
control.
• The timer lamp on the indoor unit blinks
continuously. (5 times per 1 sec.)
START/STOP
FANMODE
SWING
ON
ECO
TIMER
FIX
OFFSETCLR
FILTER
PRESET
AUTO
Hi-POWER
MEMO
CLOCK CHECKRESET
(2) Press [TIMER 8] button.
If there is no fault with a code, the indoor unit will
beep once (Pi) and the display of the remote
control will change as follows:
; 00 ; 01 ; 02 ··· 1d ; 1E ; 22
• Check the unit with all 35 check codes (00 to
22). as shown in Table 10-4-1.
• Press [TIMER 9] button to change the check
code backwards.
If there is a fault, the indoor unit will beep for 10
seconds (Pi, Pi, Pi...).
Note the check code on the display of the remote
control.
• 2-digits alphanumeric will be indicated on the
display.
• All lamps on the indoor unit will blink. (5 times
per 1 sec.)
(3) Press [CLR] button. After service finish for clear
service code in memory.
• “7F” is indicated on the display of the remote
control.
• Alphanumeric characters are used for the check
code.
is 5.is 6.
is A.is B.
is C.is D.
(4) Press [START/STOP] button to release the service
mode.
• The display of the remote control returns to as it
was before service mode was engaged.
– 53 –
Page 54
10-4-2. Operation Control by Rated Frequency in Service Mode
In the service mode, pushing “ON” or “OFF” operates the air conditioner by rated frequency of COOL mode for
30 minutes.
10-4-3. Caution at Servicing
(1) After servicing, push the START/STOP button to return to the normal mode.
(2) After servicing by the check code, turn off breaker of the power supply, and turn on breaker of the power
supply again so that memory in the microcomputer returns the initial status. However , the check codes are
not deleted even if the power supply is turned off because they are stored in the fixed memory.
Table 10-4-1
Block distinction
Check
code
Block
Indoor P.C.
board etc.
Not
displayed
Connecting
cable and
serial signal
Check
code
Operation of diagnosis function
Cause of operation
Short-circuit or disconnection of the room temperature sensor (TA sensor).
Coming-off,
disconnection,
short-circuit, or migration
of heat exchanger sensor
(TC sensor)
Lock of indoor fan or
trouble on the indoor fan
circuit
Trouble on other indoor
P.C. boards
Return serial signal is not
sent to indoor side from
operation started.
(1) Defective wiring of
connecting cable
(2) Operation of
compressor thermo.
Gas shortage
Gas leak
Air
conditioner
status
Operation
continues.
Operation
continues.
All off
Operation
continues.
Operation
continues.
Condition
Displayed when
error is detected.
Displayed when
error is detected.
Displayed when
error is detected.
Displayed when
error is detected.
Flashes when
trouble is detected
on Return serial
signal, and normal
status when signal
is reset.
Judgment and action
1. Check the room temp. sensor.
2. When the room temp. sensor is
normal, check P.C. board.
1. Check heat exchanger sensor.
2. When heat exchanger sensor is
normal, check P.C. board.
1. Check P.C. board.
2. When P.C. board is normal, check
the motor.
Replace P.C. board.
1. When the outdoor unit never
operate:
(1) Check connecting cable, and
correct if defective wiring.
(2) Check 25A ( or 30A) fuse (F01)
of outdoor main P.C. board.
(3) Check 3.15A fuse (F04) of
outdoor main P.C. board.
2. To display [Other] block during
operation, check compressor
thermo. operation and supply gas
(check gas leak also).
3. Unit operates normally during
check.
If Return serial signal does not
stop between indoor terminal
board 2 and 3, replace inverter P.C.
board.
If signal stops between indoor
terminal board 2 and 3, replace
indoor P.C. board.
Operation command
signal is not sent to
outdoor side.
Operation
continues.
– 54 –
Flashes when
trouble is detected
on Operation
command signal,
and normal status
when signal is
reset.
If Operation command signal does not
stop between indoor terminal board 2
and 3, replace inverter P.C. board.
If signal stops between indoor
terminal board 2 and 3, replace indoor
P.C. board.
Compressor does not
rotate. (Current protective
circuit does not operate
when a specified time
passed after compressor
had been activated.)
Discharge temp. exceeded 120°C.
Break down of
compressor
Operation
continues.
All off
All off
All off
All off
All off
——
Displayed when
error is detected.
Displayed when
error is detected.
Displayed when
error is detected.
Displayed when
error is detected.
Displayed when
error is detected.
1. Check outdoor temp. sensor (TO).
2. Check P.C. board.
Check 5-serial LED.
When 20 seconds passed after start-up,
position-detect circuit error occurred. :
Replace compressor.
Check 5-serial LED.
1. Miswiring of connecting wire of A/B/
C/D rooms in indoor/outdoor units
2. Check gas leakage.
3. Check disconnection of sensor.
4. Electronic control valve error
1. Trouble on compressor
2. Trouble on wiring of compressor
(Missed phase)
1. Check dischage temp. sensor (TD).
2. Degassing
3. Trouble on P.M.V.
1. Check power voltage.
(220–240 V ±10%)
2. Overload operation of refr igeration
cycle
Check installation condition
(Short-circuit of outdoor diffuser).
– 55 –
Page 56
10-5. Judgement of Trouble by Every Symptom
10-5-1. Indoor unit (Including remote controller)
(1) Power is not turned on (Does not operate entirely)
supply once, and 5
second later, turn it
NO
Is fuse (F01)
of indoor control
board blown?
NO
Turn off power
on again.
Is OPERATION
lamp blinking?
YES
Is it possible to
turn on power
supply by
pressing
[START/STOP]
button on
remote control?
YES
YES
(R04, C01,
DB01, C03, R01
IC01 and T01)
are defective.
Parts
NO
Does
transmission
mark on
remote control
flash normally,
and is its signal
transmitted
properly?
YES
NO
Does
fan motor
connector
between 1
and 2
short-circuit?
Operation
Check item
Conceivable principle
cause
Measure
Item by symptoms
Remote control is
defective.
Refer to (5)
“Troubleshooting for
Remote Control.”
Unit operates
normally.
YES
Is voltage
(DC 12V or 5V)
NO
indicated on
rear of indoor
control board
normal?
Is DC
310 – 340V
suppalied to
primary side of
transfer s witch?
YES
Are DC 15V,
DC 12V and
DC 7V
supplied to
secondary
side of
transfer
switch?
YESYES
NO
NONO
Refer to
<Primary check>
or this problem
is one step short
of power P.C.
board block.
Turn off breaker
once and turn it
on again after
removing motor.
YES
Are DC 15V,
DC 12V or
DC 7V
supplied to
secondary
side of
transfer
switch?
NO
Microcomputer
is defective.
Transfer switch,
IC (IC01) for
power supply or
fan motor is
defective.
Replace main
P.C. board.
Replace motor.
• Be sure to disconnect the motor connector CN10 after shut off the power supply, or it will be a cause of
damage of the motor.
– 56 –
Page 57
(2) Power is not turned on though Indoor P.C. board is replaced
<Confirmation procedure>
Turn on power supply.
Does operation lamp flash?
YESYES
NONO
Is wired correctly to white and black
lead wires of terminal board?
Correct wiring.
To item of
“Power is not turned on”.
– 57 –
Page 58
(3) Only indoor fan motor does not operate.
<Preliminary check>
1 Is it possible to detect the power supply voltage (200 – 240V) between 1 and 2 on the terminal block?2 Does the indoor fan motor operate in cooling operation?
(In heating operation, the indoor fan motor does not operate for
Operation
approximately 5 minutes after it is turned on, to prevent a cold air
from blowing in.)
Turn off power
supply once, and
turn it on again.
Check item
Conceivable principle
cause
Measure
Item by symptoms
Does
compressor
continue to
operate?
NO
Start to operate
indoor unit in
cooling operation
at airflow
level “LOW”.
Does indoor
fan operate?
YES
Change airflow
level to “High”.
Is it possible to
change airflow
level to “High”?
YES
YES
NO
NO
Is it possible to detect
DC 1V or more between
and 3dof motor
5
e
connector (CN10).
Is it possible to detect DC
310 – 340V between
and 3d of motor
1
e
connector (CN10).
(Motor connection condition)
Is it possible to detect DC 15V
between 4
motor connector (CN10).
Start to operate the
indoor unit. At this time, is it
possible to detect DC 1V or
more between 5e and 3d
of motor connector (CN10)?
Is it possible to rotate cross-
flow fan by hand properly?
YES
YES
and 3d of
e
YES
NO
NO
NO
NO
NO
Turn off indoor unit
and remove connector
from motor. Then press
START/STOP b utton
on remote control to
stop blinking lamp on
indoor unit.
Is it possible to detect
DC 15V between 4
and 3d of motor
connector (CN10).
Turn off indoor unit
and remove connector
from motor.
Then start to operate
indoor unit with
remote control.
e
NO
Replace indoor
fan motor.
Replace main
P.C. board.
Fan motor
operates normally.
Turn off indoor unit and rotate
cross-flow fan by hand when the
unit is on standby. At this time,
is it possible to detect DC 1V or
more between 5e and 3
of motor connector (CN10).
YES
d
NO
– 58 –
Start to operate the indoor
unit in except heating
operation. At this time, is it
possible to detect DC 1V
or more between 5e and
3d of motor connector
(CN10)? (Check this
condition within 15 seconds
after starting unit.)
YES
NO
Replace bearing.
Page 59
(4) Indoor fan motor starts rotating by turning on power supply alone
<Cause>
The IC is built in the indoor fan motor. Therefore the P.C. board is also mounted to the inside of the motor.
If the P.C. board is soldered imperfectly or the IC is defective, the fan motor may automatically rotate by turning
on power supply.
<Confirmation procedure>
(1) Rem
ove the front panel.(Remove 4 screws.)
(2) Remove cover of the fan motor lead wires.
(3) Check DC voltage with CN10 connector while the fan rotating.
NOTE :
• Do not disconnect the connector while the fan rotates.
• Use a thin tester rod.
P.C. board
Indoor fan starts rotating when power supply breaker is turned “ON”.
CN10
(Check output voltage (DC) of the fan motor on P.C. board.)
Measure the voltage of the motor connector
CN10 pin 2 (GND : Black) and pin 3 (V line : Yellow)
under condition that the indoor fan rotates.
Above DC 0.4V
P.C. board is defective.
Below DC 0.4V
Motor is defective.
Yellow
Black
DC
6 (Blue)
5 (Yellow)
4 (Blue)
3 (Yellow)
2 —
1 (Red)
– 59 –
Page 60
(5) How to examine whether remote controller is good or bad
• Does setting (A/B) of the remote controller selection match with that indoor unit?
Operation
Check Items
Considerable main cause
Measures
Item by symptom
Is there direct
sunlight on the
receptor of the
air conditioner?
YES
fluorescent light
NO
Is there any
thyristor
near by?
YES
NO
Press the START/STOP button.
Does the transmission
indicator of remote
controller light?
YES
Is operation
NO
possible when the
transmitter is moved
nearer to the infrared
signal receiver of the
air conditioner?
YES
Battery life
There is no beep from
the indoor unit.
The operation lamp of
the air conditioner main
unit does not light.
NO
Short-circuit ACL switch with
a coin or others at rear side
of remote controller.
Push the START/
STOP button
Avoid direct
sunlight.
NO
Keep the air
conditioner away
from thyristor
fluorescent light.
Is Temporary Cool
operation possible when
keeping the temporary
switch of the air conditioner
main unit pushed for
10 seconds or more?
YES
Can any signal tone
be heard in a transistor
radio when transmitting
within 5cm distance
from the radio?
YES
Replace
P.C. board.
NO
Replace the
battery.
indicator light?
NO
receiving sound
and operation?
Normal
Does the
transmission
YES
Is there any
YES
NO
Remote controller
is failure.
– 60 –
Page 61
10-5-2.Wiring Failure (Interconnecting and Serial Signal Wire)
(1) Outdoor unit does not operate
1) Is the voltage between
and of the indoor terminal block varied?
Confirm that transmission from indoor to outdoor is correctly performed based upon the following diagram.
NOTE:
• Measurement should be performed 2 minutes and 30 seconds after starting of the operation.
• Be sure to prepare a diode for judgment.
Terminal block at indoor side
Red
White
3
2
Terminal block
1
S5277G
Tester
S5277G or equivalent (G or J type)
(Diode with rated voltage of 400V
or more is acceptable.)
Fig. 11-5-1
Normal time: Voltage swings between DC15 and 60V.
Abnormal time : Voltage does not vary.
(2) Outdoor unit stops in a little while after operation started
<Check procedure> Select phenomena described belo w .
(1) The outdoor unit stops 10 to 20 minutes after operation started, and 10 minutes or more are required to
restart the unit.
Gas circulation amount is down.
Measure gas pressure.
Thermo. operation of compressor
Gas shortage
Gas leak
Pipe clogging
(2) If the unit stops once, it does not operate until the power will be turned on again.
To item of Compressor does not operate.
(3) The outdoor unit stops 10 minutes to 1 hour after operation started, and an alarm is displa y ed.
(Discharge temp. error check code 03, 1E)
Gas leak
P.M.V. is defectiv e.
Miswiring of connecting wires of indoor/outdoor units
Clogging of pipe and coming-off of TG, TC sensors
– 61 –
Page 62
10-6.Trouble Diagnosis by Outdoor LED
For the outdoor unit, the self-diagnosis is possible by
five LEDs (Red).
• LEDs (Red) (D11 to D15) are provided on the
sub-control board under surface of the inv erter ,
and as shown below , the y are chec k ed from the
wiring port when removing the wiring cover.
1 . If a trouble occurs, LED (Red) goes on accord-
ing to the trouble as described in the table below.
2 . When two or more troubles occur, LEDs go on
cyclically.
3 . Usually, LEDs (Red) go off.
Wiring port
D11 D12 D13 D14 D15
Fig. 11-6-1
LED (Red)
¤
LED display
D11D12D13D14D15
lllll
llll
¤
l
¤¤
ll
l
¤¤¤
lll
¤
2
*
*
*
*
*1
¤¤¤¤
2
¤
2
¤¤
1
l
¤¤¤l¤
lll
¤
lll
ll
¤
¤¤
ll
ll
¤
l
lll
¤¤
ll
¤
ll
l
l
l
¤
¤
¤
Indoor
check
code
None
07
14
16
17
19
1A
1B
1C
––
––
––
––
––
: LED ON, l : LED OFF P.M.V. : Pulse modulating valve
Description
During normal operation
Compressor thermo. operation, instantaneous power failure,
gas leak
IGBT short circuit, compressor motor rear shor t
Position-detect circuit error
Current-detect circuit error
Discharge temp. sensor (TD) error
Outdoor fan error
Outside temp. sensor (TO) error
Compressor system error
A room gas side temp. sensor (TGa) error
B room gas side temp. sensor (TGb) error
C room gas side temp. sensor (TGc) error
Gas leakage, P.M.V. sensor error
Indoor heat exchanger sensor (TC) disconnection, P.M.V.
sensor error
lll
¤¤
ll
¤
l
¤
¤¤
1 Back-up operation is performed without block display of the indoor unit.
*
2 Operated normally when the air conditioners in other rooms are driven.
*
l
l
l
¤¤
¤¤
l
¤
l
¤
l
¤
—
1C
1D
1E
1F
Indoor/outdoor miswiring, gas leakage, TC sensor
disconnection, P.M.V. sensor error
Communication error between MCU
Compressor lock
Discharge temp. error, gas leakage
Compressor break down
– 62 –
Page 63
10-7.How to Diagnose Trouble in Outdoor Unit
10-7-1.Summarized Inner Diagnosis of Inverter Assembly
Diagnosis/Process flowchartItem
Preparation
Remove
connector of
compressor.
Check 25A fuse
(Part No.F01).
OK
Check
15A fuse
(Part No.F03).
OK
NG
Replace fuse.
capacitor, diode
NG
Replace control
board assembly.
Check
electrolytic
block, etc.
Check
Check
Contents
Turn “OFF” the power breaker,
and remove 3P connector
which connects inverter and
compressor.
• Check whether 25A fuse on
the control board assembly
is blown or not. (F01)
Check whether 15A fuse on
the control board assembly
is blown or not. (F03)
• 15A fuse (F03) on the
control board is provided for
power factor improvement
control circuit. The operation
continues even if fuse is
blown.
Summary
If fuse was blown, be sure to
check the electrolytic
capacitor and diode block.
(DB01)
• Connect discharge
resistance (approx.
100Ω40W) or soldering
iron (plug) between +, –
terminals of the electrolytic capacitor (500µF) of
C15 (with printed CAUTION HIGH VOLTAGE) on
P.C. board.
Discharging position
(Discharging period
10 seconds or more)
Plug of
soldering
iron
Check
terminal voltage
of electrolytic
capacitor.
OK
Does outdoor
fan rotate?
YES
Does LED on control
board flash or go on?
Remove connector
CN300 of outdoor fan
NG
tester, check resistance
value between every
phases at motor side.
Replace
outdoor
fan motor.
NG
Check
electrolytic
capacitor, diode
block, etc.
NO
NO
motor, and using a
OK
YES
CBA
Operation
Measurement
Check
Stop
Check
Measurement
Tur n on power breaker, and
operate the air conditioner in
COOL mode by short-circuit of
the timer.
Measure terminal voltage of
the electrolytic capacity.
500µF:400WV x 4
After operation, turn off the
power breaker after 2 minutes
20 seconds passed, and
discharge the electrolytic
capacity by soldering iron.
Check voltage between motor
phases.
• Is not winding between
, -
, or - opened
-
or short-circuited?
• Is not frame grounded with
, or ?
,
If 15A fuse is blown,
discharge both edges of
the electrolytic capacitor
with soldering iron.
OK if 500µF
→→
→ DC280V
→→
Remove CN300 while
pushing the part indicated
by an arrow.
→→
→ Resistance between
→→
phases should be approx.
55 to 77Ω.
→→
→ Should be 10MΩ or more.
→→
– 63 –
Page 64
Diagnosis/Process flowchartItem
Contents
Summary
fan motor
NG
Replace
outdoor
fan
motor.
Check
compressor
winding
resistance.
OK
Replace
control board.
CBA
Check
winding of
compressor.
OK
Check
position
detect
signal.
OK
Replace control
board assembly.
NG
Replace
compressor.
NG
Replace
compressor.
Check
Operation
Check
Check winding resistance
between phases of compressor, and resistance between
outdoor frames by using a
tester.
• Is not grounded.
• Is not shor t-circuited
between windings.
• Winding is not opened.
Remove connector CN300 of
the outdoor fan motor, turn
on the power breaker, and
perform the operation.
(Stops though activation is
prompted.)
Check operation within 2
minutes 20 seconds after
activation stopped.
<Output check of fan motor
position detect signal>
While connecting connector
5P (CN301) for position
detection, using a tester,
measure voltage between
- . Between - : 5V
→→
→ OK if 10MΩ or more
→→
→→
→ OK if 0,51Ω → 0,57Ω
→→
(Check by a digital tester.)
a)One or two of three
voltages should be 5V,
and others should be 0V.
(When all are 0V or 5V, it
is not accepted.)
b)When rotating the fan
slowly with hands, the
voltage between pins
should move from 0V to
5V.
(Check it with an analog
tester.)
10-8.How to Check Simply the Main
Parts
10-8-1.How to Check the P.C. Board
(Indoor Unit)
(1) Operating precautions
1) When removing the front panel or the P.C.
board, be sure to shut off the power supply
breaker .
2) When removing the P.C. board, hold the edge
of the P.C. board and do not apply force to
the parts.
3) When connecting or disconnecting the
connectors on the P.C. board, hold the whole
housing. Do not pull at the lead wire .
(2) Inspection procedures
1) When a P.C. board is judged to be defective,
check for disconnection, b urning, or discoloration of the copper foil pattern or this P.C.
board.
2) The P.C. board consists of the following 2
parts
a. Main P .C. boar d part:
DC power supply circuit (5V, 12V, 35V),
Indoor fan motor control circuit, CPU and
peripheral circuits, buzzer, and Driving circuit
of top/bottom louvers
b. Indication unit of infrared ray receiving
Infrared ray receiving circuit, LED:
To check defect of the P.C. board, follow the
procedure described below.
– 64 –
Page 65
(3) Check procedures
Table 10-8-1
No.
1
Shut off the power supply and
remove the P.C. board assembly
from the electronic parts base.
Remove the connecting cable from
the terminal block.
2
Remove the connector for the
motor, and turn the power on.
If the OPERATION lamp flashes
(0,5 sec. :ON, 0,5 sec. :OFF) when
the power turning on, the checking
points described as 1-5 of right
column are not necessary to
perform.
3
Make the operation status by
pushing once the START/STOP
button, except the status of [FAN
ONLY], [ON TIMER].
Procedure
Check point (Symptom)
1.Is the fuse blown?
Voltage check
1.Between TP1 and TP2
(220–230–240V AC)
2.Between TP2 and pin 1 of CN04
(220–230–240V AC)
3.Between TP2 and pin 3 of CN04
(220–230–240V AC)
4.Between + and – of C02
(310 ~ 340V DC)
5.Between 35V and GND
6.Between 12V and GND
7.Between 5 V and GND
Voltage check
1. Voltage of relay coil. (DC 12V)
Between pin 10 of IC31 and GND
Between pin 11 of IC31 and GND
2. Between No. 1 and 2 of connecting
cable terminal block.
(220–230–240V AC)
Causes
1.* Application of shock voltage.
* Overload by short-circuit of the
parts.
1.* AC power cord is defective.
* Poor contact of the terminal plate.
* Miss wiring of the power relay.
2.Fuse is defective.
3.Operation of the thermal fuse.
4.* Capacitor (C01, C15) is defective.
* Line filter (L01) is defective.
* Resistor (R01) is defective.
* Diode (DB01) is defective.
5.IC01, IC02, T01 are defective.
6.IC01, IC02, T01, F03 are defective.
7.IC01, IC02, T01, F02, Q29, IC03
are defective.
1.Breaking wire of the relay coil,
defective relay driver. (IC31)
2.Poor contact of relay.
4
Start the operation with the system
which the time of the restart delay
timer is shortened.
5
Make the operation status by pressing
once the START/STOP button.
1.The time of the restar t delay timer
is shortened.
2.Cool operation
3.Air volume [AUTO]
4. Make the setting temperature lower
enough than room temperature.
5.Continuous operation.
Tur n the power on after connecting
6
the motor connector.
Start the operation with the following
condition.
1.Operation [Cooling]
2.Airflow [High fan]
3.Continuous operation
1.All indicators light for 3 sec.
2. Indicators do not indicate normally
after approximate 3 sec.
1.Compressor does not operate.
2. OPERATION lamp flashes.
1.The voltage of DC 35V is not
measured between the red and
black of the motor terminals.
2. Motor does not rotate.
(The key operation is accepted.)
3. The motor rotates, but it vibrates too
much.
Defective indicator, or poor
housing assembly. (CN13)
1.The temperature of the indoor heat
exchanger is abnormally low.
2.Poor contact of the heat exchanger
sensor. (The connector is
disconnected.) (CN01)
3.Heat exchanger sensor, main P.C.
board are defective.
4.Main P.C. board is defective.
1.Indoor fan motor is defective.
(Protecting operation on the P.C.
board.)
2. Poor contact of the motor
connector.
3.P.C. board is defective.
– 65 –
Page 66
10-8-2. P.C. Board Layout
<T op View>
<Bottom View>
– 66 –
Page 67
<Sensor characteristic table>
100
90
80
70
60
50
40
30
Resistance value (k )
20
10
0
0102030 4050
Temperature (˚C)
TD
TA, TC, TO, TGa, TGb, TGc, TGd
TD : Discharge temp. sensor
TA : Room temp. sensor
TC : Heat exchanger temp. sensor
TO : Outdoor temp. sensor
TGa : Gas side temp. sensor
TGb : Gas side temp. sensor
TGc : Gas side temp. sensor
TGd : Gas side temp. sensor
– 67 –
Page 68
10-8-3.Indoor Unit (Other Parts)
No.Part name
1Room temp. (TA) sensor
Heat exchanger (TC) sensor
2Remote control
3Louver motor
MP24GA
4Indoor fan motor
11-8-4. Outdoor Unit
Checking procedure
Disconnect the connector and measure the resistance value with tester .
(Normal temp.)
Temperature
Sensor
TA, TC (kΩ)20,712,610,07,94,5
10°C20°C25°C30°C40°C
To item of How to judge whether remote control is good or bad of the
Judgment of trouble b y symptom.
Measure the resistance value of each winding coil by using the tester .
(Under normal temp. 25°C)
1
White
Yellow
Yellow
Yellow
Yellow
2
3
4
5
Position Resistance value
1 to 4
1 to 6
2 to 3
130 ± 10 Ω
2 to 5
Since judgment of DC motor is difficult on the single motor, ref er to 115-1. (3).
No.Part name
1Compressor
(Model : D A130A1F-21F)
2Outdoor fan motor
(Model : ICF-140-40-8)
3Compressor thermo.
Bimetal type
(Model : PW - 2AL)
4Outdoor temperature sensor
(TO), pipe temperature sensor
(TGa, TGb, TGc), discharge
temperature sensor (TD)
Checking procedure
Measure the resistance value of each winding by using the tester.
Red
WhiteBlack
PositionResistance value
Red - White0,51 to 0,57 Ω
White - Black0,51 to 0,57 Ω
Black - Red0,51 to 0,57 Ω
Under 20°C
Measure the resistance value of winding by using the tester.
Red
WhiteBlack
1 Yellow
4 Pink
5 Gray
PositionResistance value
Yellow - Pink5 to 20 k Ω
For details, ref er to Section 11-9.
Check conduction by using the tester.
Disconnect the connector, and measure resistance v alue with the
tester. (Normal temperature)
Temperature
Sensor
TD (kΩ)10564412718
TO, TGa, TGb, TGc (kΩ)20,712,610,07,94,5
10°C20°C30°C40°C50°C
– 68 –
Page 69
10-8-5.Checking Method for Each Part
No.Part name
1Electrolytic capacitor
(For raising pressure,
smoothing)
2Converter module
Checking procedure
1. Turn OFF the power supply break er.
2. Discharge all four capacitors completely.
3 . Check that safety valv e at the bottom of capacitor is not broken.
4 . Check that vessel is not swollen or exploded.
5 . Check that electrolytic liquid does not blow off.
6. Check that the normal charging characteristics are shown in
continuity test by the tester .
C12 C13
Heat sink IGBT side
C14
C15
MCC-758
Soldered
surface
Case that product is good
Pointer swings once, and
returns slowly. When
performing test once again
under another polarity, the
pointer should return.
C12, C13, C14, C15 → 500µF/400V
1 . Turn OFF the power supply breaker.
2 . Discharge all four capacitors completely.
3 . Check that the normal rectification characteristics are shown in
continuity test by the tester .
Mark
3IGBT module
+~–~
Diode check
Tester rod
–
+
~
1
–
~
2
~
+
E
1
~
2
~
1
~
2
A
EG
21
Resistance value
in good product
50kW or more
(0 in trouble)
+~1–~
IGBT check
Tester rod
+–
~
E
2
G
E
2
1.Turn OFF the po w er supply switch.
2. Discharge all four electrolytic capacitors completely.
3. Execute continuity test with a tester.
+
BU
U
BX
BV
V
BY
BW
W
BZ
–
BZ BY BXBW
WVU
–
A
Resistance value
in good product
50kW or more
(0
EG
in trouble)
BVBU
+
Tester rod
Case that product is good
– 69 –
+
–
1M
+
or more
UVWUVW
WVUWVU
100k to 300k
–
–
+
200k to 300k
Page 70
10-9. How to Simply Judge Whether Outdoor Fan Motor is Good or Bad
1. Symptom
• Outdoor fan motor does not rotate.
• Outdoor fan motor stops within several tens seconds though it started rotating.
• Outdoor fan motor rotates or does not rotate according to the position where the fan stopped., etc.
Remote control check code “02 : Outdoor block, 1A : Outdoor fan drive system error”
2. Cause
The following causes are considered when the outdoor f an motor does not normally rotate.
1) Mechanical lock of the outdoor fan motor
2) Winding error of the outdoor fan motor
3) Position-detect circuit error inside of the outdoor fan motor
or
4) Motor drive circuit error of the outdoor P.C. board
3. How to simply judge whether outdoor fan motor is good or bad
Turn OFF the breaker.
Disconnect two connectors (CN300 and CN301)
of the outdoor fan motor from the inverter.
Does the fan rotate without trouble
when rotating it with hands?
YES
If the resistance value between
1 (Red lead)– 2 (White lead)
2 (White lead) – 3 (Black lead)
3 (Black lead) – 1 (Red lead)
1 (Yellow lead) – 4 (Pink lead)
(CN301 : Motor position detection)
of the connector
(CN300 : Motor winding)
is 50 to 80
If the resistance value between
of the connector
is 5k to 20k , it is normal.
Fan motor is normal.
(Outdoor P.C. board error)
, it is normal.
YES
YES
NO
NO
NO
CN300
Fan motor error
NOTE :
Howe ver, GND circuit error inside of the motor may be accepted in some cases when the abo ve check is
performed.
When the fan motor does not become normal even if P.C. board is replaced, replace the outdoor fan motor.
– 70 –
Page 71
11. HOW TO REPLACE THE MAIN PARTS
6 2-Screws
2 4-Screws
2
22
11-1. Indoor Unit
No.Part nameProceduresRemarks
1Front panel
2Electrical part
How to remove the front panel
1) Stop operation of the air conditioner and
turn off its main power supply.
2) Pull the air inlet grille toward you to open it
and remove the air inlet grille.
Then remove the 4 screws fixing the front
panel.
3) First open the horizontal louver, and then
remove the front panel from the back body
by pulling it toward you.
How to mount the front panel
Push the front panel back in and make
sure all hooks are locked.
How to remove the electrical part.
1) Remove the front panel with procedure 1.
2) Remove the screw holding the electrical
part cover.
3) Remove the drain guide .
4) Disconnect the 2 connectors (3P) for the
fan motor and the connector (5P) for the
louver motor from the P.C. board assembly.
5) Pull out the TC sensor from the sensor
holder.
6) Remove the screw for the ground
connection, remove the 2 screws for the
electrical part box and remove the screw
from the LED unit. Then remove the LED
unit and the electrical part box from the
main unit.
How to mount the electrical part.
1) To put back the electrical part box, lock it
to the upper hook of the back body.
2) Tighten the 2 screws on the electrical part
box.
3) Connect the 3 connectors and arrange the
wiring same as original condition and then
tighten the screw from the LED unit to the
back body.
4) Attach the TC sensor to the holder.
5) Tighten the screw for the ground connection.
6) Assemble the drain guide (the TC sensor
wire should be covered by the drain guide).
7)
Tighten the screw on the electrical part cover.
3 Drain guide
6 Screws
3
2 Screws
5 TC Sensor
3-Connectors
4
3Horizontal
louver
1) Remove the front panel and the electrical
part following procedure 2.
2) Remove the center shaft of the horizontal
louver from the back body.
3) Remove the left shaft from the back body.
4) Remove the horizontal louver from the
back body.
– 71 –
3 Left shaft
2 Center shaft
Page 72
No.Part nameProceduresRemarks
3 2-Screws
4Heat exchanger
5Cross flow fan
1) Remove the front panel, electrical part
and the horizontal louver following
procedure 3.
2) Remove the pipe holder at the rear side of
main unit.
3) Remove the 2 screws on the heat
exchanger at the base bearing.
4) Remove the 2 screws on the heat
exchanger at the 2 fixed plates (upper and
lower) from the back body, and then pull
out the upper side of the heat exchanger
slowly.
1) Remove the front panel, electrical part,
horizontal louver and the heat exchanger
following procedure 4.
2) Remove the 2 screws on the band motor
(L) and remove the 2 screws on the band
motor (R) and then remove the cross flow
fan.
3) Loosen the set screw of the cross flow fan
then separate the fan and the fan motor.
2 Pipe holder
4 2-Screws
2 2-Screws (R)
2 2-Screws (L)
4 mm
6Base bearing
Notice
To assemble cross flow fan and fan motor to
the unit, please turn the fan motor unit the
center of its terminal meets the lowest point
of band motor (R) (point A).
Fix the cross flow fan with the set screw at
the position where the gap between the back
body and the right surface of the cross flow
fan is 4 mm.
1) Remove the front panel, electrical part,
horizontal louver, heat exchanger and the
cross flow fan following procedure 5.
2) Remove the 2 screws fixing the base
bearing.
3) Remove the bearing from the base
bearing. If the housing protrudes from the
base bearing, put the housing in position
and attach the bearing to the base
bearing.
3 Set screws
Middle of the fan motor terminal
2 2-Screws
– 72 –
Page 73
11-2.Microcomputer
No.
Part name
Common
procedure
Procedure
1) Turn the power supply off to stop the operation of airconditioner.
2) Remove the front panel.
• Remove the two fixing screws. (φ4 x 14l)
3) Remove the electrical part base.
Remarks
Replace the thermal fuse, terminal
block, microcomputer ass’y and the
P.C. board ass’y.
– 73 –
Page 74
11-3. Outdoor Unit
No.Part name
Common
procedure
Procedure
1. Detachment
1) Stop operation of the air conditioner, and remov e
the power plug of the indoor unit from plug
socket.
2) Remove the valve cover. (ST1TØ4 x 10
• After removing screw, remove the valve cover
pulling it downward.
3) Remove wiring cover (ST1TØ4 x 10
and then remove connecting cable .
4) Remove the upper cabinet.
(ST1TØ4 x 10
• After removing screws, remove the upper
cabinet pulling it upward.
2. Attachment
1) Attach the upper cabinet.
(ST1TØ4 x 10
• Hook the rear side of the upper cabinet to claw
of the rear cabinet, and then put it on the front
cabinet.
2) Perf orm cabling of connecting cable , and attach
the wiring cover . (ST1TØ4 x 10
3) Attach the valve cover. (ST1TØ4 x 10
• Insert the upper part to the upper cabinet, set
hook claw of the valv e cover to square holes
(at three positions) of the main unit, and attach
it pushing upward.
ll
l 2 pcs.)
ll
ll
l 2 pcs.)
ll
ll
l 2 pcs.)
ll
ll
l 1 pc.)
ll
ll
l 2 pcs.),
ll
ll
l 1 pcs.)
ll
Remarks
Upper cabinet
Wiring
cover
Valve
cover
Upper cabinet
Front cabinet
1. Detachment
1) Perf orm work of item 1 of .
2) Remove screw (ST1TØ4 x 10
cabinet and inverter cover and screws (ST1TØ4
ll
x 10
l 3 pcs.) of the front cabinet and lower part
ll
of the front cabinet and motor base (ST1TØ4 x
ll
10
l 2 pcs.).
ll
• The left side of the front is made to insert to
the rear cabinet, so remove it pulling upward.
2. Attachment
1) Insert claw at the left side of the front into the
rear cabinet.
2) Hook the lower part at the right side of the front
to concave part of the bottom plate. Insert claw
of the rear cabinet into square hole of the front
cabinet.
3) Attach the removed screws to the original
positions.
ll
l 1 pc.) of the front
ll
Square
hole
Concave part
Claw
– 74 –
Page 75
No.Part name
Procedure
Remarks
Inverter
assembly
1. Detachment
1) Perf orm work of items 1. of and .
2) Remove screw (ST1TØ4 x 10
ll
l 1 pc.) of the
ll
upper part of the front cabinet.
• If removing the inverter cover in this condition,
P.C. board can be checked.
• If there is no space in the upper part of the
upper cabinet, perform work of .
Be careful to check the inverter because
high-voltage circuit is incorporated in it.
3) Perf orm discharging by connecting + , – polarity
by discharging resistance (approx. 100Ω40W) or
plug of soldering iron to + , – terminals of the
C15 (printed “CAUTION HIGH VOLTAGE” is
attached.) electrolytic capacitor (500µF) on P.C .
board.
Be careful to discharge the capacitor
because the electrolytic capacitor cannot
naturally discharge and voltage remains
according to trouble type in some cases.
Inverter cover
Discharging position
(Discharging period
10 seconds or more)
Adjust length of every lead wires
other than complete and case
thermo., and bundle them.
P. C. board
(Soldered surface)
Plug of
soldering
iron
NOTE :
This capacitor is one with mass capacity .
Therefore, it is dangerous that a lar ge
spark generates if short-circuiting between + , – polarity with screwdriver, etc.
for discharging.
4) Remove screw (ST1TØ4 x 10
ll
l 1 pc.) fixing the
ll
main body and the inverter box.
5) Remove various lead wires from the holder at
upper part of the inverter box and wiring holder
at right side of the terminal block.
6) Remove the lead wire from the bundled part at
left side of the terminal block.
7) Pull the inverter box upward.
8) Disconnect connectors of various lead wires.
Holder
TO sensor
P.M.V. coil
(A, B, and C rooms)
TGa, TGb, TGc
sensor
The connector is one with lock,
so remove it while pushing the
part indicated by an arrow.
– 75 –
Page 76
No. P art name
,
Procedure
Remarks
Control
board
assembly
1) Disconnect lead wires and connectors connected
from the control board assembly to other parts.
1. Lead wires
• Connection with terminal block : 10 wires
(Black, Orange, Pink, Red, Two white wires,
Four white wires (reactors))
• Connection with compressor :
Remove the connector (3P).
• Connection with reactor :
Remove the relay connectors from
P07, 08 (2P, White) and P11, P12 (2P, Yellow).
2. Connectors
• Main control board assembly side
CN300 : Outdoor f an (3P, White)
CN301 : Outdoor fan position detection (5P, White)
• Sub-control board assembly side
CN02 : TD sensor (3P, White)
CN05 : TGa sensor (3P, Yellow)
CN06 : TGb sensor (3P, Brown)
CN07 : TGc sensor (3P, Green)
CN08 : Case thermo. (2P, White)
CN12 : C room pulse modulating v alv e (6P, Green)
CN13 : B room pulse modulating v alve (6P, Red)
CN14 : A room pulse modulating v alv e (6P, Black)
2) Disconnect cable connecting the main control board
assembly side and sub-control board assembly.
• Main control board assembly side
CN704 : Connecting cab le (4P, White)
• Sub.-control board assembly side
CN15 : Connecting cab le (4P, White)
Main board
CN15
CN301
CN300
CN04
CN02CN
CN
CN14
CN 12
CN08
CN05
06
13
Sub-board
CN06 CN07
CN300 and 301 at the main
control board assembly side and
CN08 and 15 at the sub- control
board assembly side are connectors with locks. Therefore ,
remove the connector while
pushing the part indicated by an
arrow.
Rear
cabinet
3) Remove the control board assembly from P.C. board
base.
1. Main control board assembly side
• Remove two claws of P.C. board base, and
remove upward the heat sink with hands .
• Remove three screws fixing the heat sink and
main control board assembly side, and replace
the board with a new one.
2. Sub- control board assembly side
• Remove P.C. board base from the in verter box.
• Remove two claws of P.C. board base, and
replace the board with a new one.
3. Be sure to use the radiating sheet between heat
sink and IGBT and also screws with tube.
1) Perform work of item 1 of , and .
2) Remove fixed scre ws fixing to the bottom plate .
(ST1TØ4 x 10
ll
l 2 pcs.)
ll
3) Remove fixed scre ws fixing to the heat
exchanger. (ST1TØ4 x 10
ll
l 2 pcs.)
ll
4) Remove fixed scre w fixing to the valve mounting
plate. (ST1TØ4 x 10
ll
l 1 pc.)
ll
P. C. board base
P. C. board
When mounting a new board,
check that the board is correctly
set in the groove of base holder
of P.C. board base.
– 76 –
Page 77
No.Part name
,
RemarksProcedure
Fan motor
Compressor
1) Perf orm work of item 1 of and .
2) Remove the flange nut fixing the fan motor and
the propeller fan.
• Flange nut is loosened by turning clockwise.
(To tighten the flange nut, turn counterclockwise.)
3) Remove the propeller fan.
4) Disconnect the connector for fan motor from the
inverter.
5) Remove the fixing screws (3 pcs.) holding by
hands so that the fan motor does not fall.
1) Perform work of item 1 of and , , , .
2) Evacuate refrigerant gas.
3) Remove the partition board.
(ST1TØ4 x 10
ll
l 3 pcs.)
ll
4) Remove the sound-insulation material.
5) Remove terminal cover of the compressor , and
disconnect lead wire of the compressor thermo.
and the compressor from the terminal.
6) Remove pipe connected to the compressor with
a burner.
7) Remove the fixing screw of the bottom plate and
heat exchanger . (ST1TØ4 x 10
ll
l 1 pc.)
ll
8) Remove the fixing screw of the bottom plate and
valve clamping plate. (ST1TØ4 x 10
ll
l 2 pcs.)
ll
9) Pull upward the refrigeration cycle.
10) Remove nut fixing the compressor to the
bottom plate.
Propeller fan
Flange nut
Partition
board
Fan motor
Valve
clamping
plate
Compressor
thermo.
Compressor
Reactor
1) Perform work of item 1 of , and .
Reactor
2) Remove lead wires clung in holder on the
partition board.
3) Remove screws fixing the reactor .
(ST1TØ4 x 10
ll
l 2 pcs.)
ll
– 77 –
Page 78
No.Part name
RemarksProcedure
Pulse
modulating
valve coil
1. Detachment
1) Perform work of item 1 of , and , , .
2) Turn the coil clockwise or counterclockwise by
90 degrees, and remove coil from the pulse
modulating valve.
2. Attachment
1) Set take-out part of the lead wire of coil to the
coil inserting position of the pulse modulating
valve, and attach the coil.
2) Turn the coil clockwise or counterclockwise by
90 degrees, set surely the concave part at lower
part of the coil to the positioning hole of the
pulse modulating valve , and then fix the coil.
The pulse modulating valve has A, B and
C room side.
After mounting it, check that coil at B
room side (Red marking is marked on the
pulse modulating valve.) is connected to
CN13.
Check that coil at C room side (Green
marking is marked on the pulse modulating valve.) is connected to CN12 of the
control board assembly respectivel y.
Take-out part
of lead wire
Notch
Coil inserting
position
Coil inserting
position
Coil fix
position
Positioning
hole
Fan guard
1. Detachment
1) Perf orm work of item 1 of , and .
2) Remove the front cabinet, and put it down so
that fan guard side directs downward.
Perform w ork on a corrugated cardboar d,
cloth, etc. to prevent flaw to the product.
3) Remove the hooking claws by pushing minus
screwdriver according to the arrow mark in the
right figure, and remove the fan guard.
2. Attachment
1) Insert claw of the fan guard in the hole of the
front cabinet. Push the hooking cla ws (10
positions) by hands and fix the claws.
All the attaching works have completed.
Check that all the hooking claws are fixe d
to the specified positions.
Minus screwdriver
Hooking claw
– 78 –
Page 79
No.Part name
RemarksProcedure
11Replacement
of temperature
sensor for
servicing only
Common service
parts of sensor
TO , TGa, TGb,
TGc (without TD)
1) Cut the sensor 100 mm longer than old one.
2) Cut the protective tube after pulling out it
(200 mm).
3) Move the protective tube to w ard the thermal
sensor side and tear the tip of lead wire in
two then strip the covering part.
4) Pass the stripped part through the thermal
constringent tube.
5) Cut the old sensor 100 mm length on the
connector side, and recycle that connector.
6) Tear the lead wire in two on the connector
side and strip the covering part.
7) Twist the leads on the connector and sensor
sides, and solder them.
8) Move the thermal constringent tubes toward
the soldered parts and heat them with the
dryer and constring them.
9) Wind the attached color tape round the both
terminals of the protective tube when colored
protective tube is used.
10)Fix the sensor again.
NOTES :
1) Store the joint part of the sensor and the
connector in the electric parts box.
2) Never joint them near the thermal sensor
part. Otherwise it would cause insulation
inferiority because of dew drops.
3) When replacing the sensor using the colored
protective tube, wind the color tape matching
the color of that tube.
Thermal
sensor part
200
Thermal
constringent tube
Cutting here
100
15
70
Winding the color tape
Connector
Soldered part
Dryer
Cutting here
100
Cutting here
15
70
These are parts
for servicing
sensors.
Please check
that the accessories shown in the
right table are
packed.
Parts nameQ'tyRemarks
1Sensor1Length : 3m
2Sensor Spring (A)1For spare
3Sensor Spring (B)1For spare
4Thermal constringent tube3Including one spare
5Color tape19 colors
6Terminal3
– 79 –
Page 80
MCC-758
CN600
– 80 –
Page 81
MCC-775
– 81 –
Page 82
12-1. Indoor Unit (1)
403
12. EXPLODED VIEWS AND PARTS LIST
406
405
402
404
Location
No.
401 43T69319 Temperature Sensor
40243T60002 Terminal Block, 3P,
403 43T69320Temperature Sensor
404 43T69003Cord Clamp
Part No.Description
TC, 10kΩ, 25°C
AC 300V, 20A
TC, 10kΩ, 25°C
401
Location
No.
406 43T69333 P.C. Board Ass’y,
406 43T69334 P.C. Board Ass’y,
406 43T69335 P.C. Board Ass’y,
Part No.Description
MCC-867(RAS-M10UKCV-E)
MCC-867(RAS-M13UKCV-E)
MCC-867(RAS-M16UKCV-E)
405 43T69079 P.C. Board Ass’y,
WRS-LED
– 82 –
Page 83
217
216
217
Indoor Unit
202
234
204
206
212
210
201
211
215
205
204
218
219
228
220
229
226
227
214
208
203
221
Electric Parts
Assembly
209
233
225
207
222
223
224
Location
No.
Part No.Description
201 43T00352 Panel Ass’y, Front
202 43T09316Inlet Grille Assy
203 43T03302Back body Assy
204 43T80301 Air Filter
205 43T09309Horizontal Louver
206 43T08350LED Panel Assy
207 13T70002 Drain Hose
208 43T79301
Cap Drain
209 43T21321 Motor Louver
Refrigeration Cycle Assy
211 43T47006 Pipe Delivery
212 43T47305
Pipe Suction
(RAS-M10UKCV-E,M13UKCV-E)
212 43T47016
Pipe Suction
(RAS-M16UKCV-E)
214 43T11301Pipe Shield
215 43T19302 Holder Sensor
216 43T49302Plate of EVA Seal
217 43T49006Holder Plate EVA Seal
218 43T79302Guide Drain
219 43T22002
Bearing
220 43T39301 Base Bearing
221 43T20302 Fan Cross Flow
222 43T39302Band Motor - L
223 43T21327Motor Fan
224 43T39303Band Motor -R
225 43T82301Plate Installation
Location
No.
Part No. Description
226 43T69310 Remote Controller
227 43T83003 Holder Remote Controller
228 43T85362 Owner's Manual
229 43T62302 Terminal Cover
231 43T60317Cord Motor Louver
232 43T60316Cord Motor Fan
233 43T07303 Holder Pipe
234 43T01303Mark
– 89 –
Page 84
12-2. Outdoor Unit
27
18
17
1
2
8
10
12,15
19
11,14
13,16
28
23
20
22
9
21
24,
25
7
6
2
5
1
4
3
22
4
23
29
30
5
LocationPart
No.No.
0143005452Cabinet, Back, Assembly
0243005369Cabinet, Upper, Assembly
0343005364Cabinet, Front, Assembly
044301V030 Guard, Fan
0543042461Base, Assembly
064301V029 Cover, Valve, Packed
0743062230Cover, Wiring, Assembly
084301V021 Hanger
0943041771Compressor, DA130A1F-21F
1043043650Condenser, Assembly
1143046332Valve, Packed, 6,35 DIA
1243046349Valve, Packed, 9,52 DIA
1343046356Valve, Packed, 12,7 DIA
1443147196Bonnet, 1/4 IN
1543047401Bonnet, 3/8 IN
1643147195Bonnet, 1/2 IN
No. 18 Coil, P.M.V. : F or standardization of the servicing parts, one type only is provided.
Therefore, color of the connector ma y be diff erent in replacement work.