Toshiba RAS-18UKHP-ES4, RAS-18UKP-ES4, RAS-24UKHP-ES4, RAS-24UKP-ES4 SERVICE MANUAL

Page 1
SERVICE MANUAL
AIR CONDITIONER
RAS-24UKHP-ES4 / RAS-24UAH-ES4
RAS-18UKHP-ES4 / RAS-18UAH-ES4
RAS-24UKP-ES4 / RAS-24UA-ES4
RAS-18UKP-ES4 / RAS-18UA-ES4
FILE NO. SVM-05011
SPLIT WALL TYPE
18 Class
24 Class18 Class
(Cooling only model)
May 2005
Page 2
CONTENTS
1. SPECIFICATIONS
2. CONSTRUCTION VIEWS
2-1 Indoor Unit 2-2 Outdoor Unit (RAS-24UAH-ES4, RAS-24UA-ES4) 2-3 Outdoor Unit (RAS-18UAH-ES4) 2-4 Outdoor Unit (RAS-18UA-ES4)
3. WIRING DIAGRAM
3-1 RAS-24UKHP-ES4 / RAS-24UAH-ES4 3-2 RAS-18UKHP-ES4 / RAS-18UAH-ES4 3-3 RAS-24UKP-ES4 / RAS-24UA-ES4 3-4 RAS-18UKP-ES4 / RAS-18UA-ES4
4. SPECIFICATION OF ELECTRICAL PARTS
4-1 Indoor Unit (RAS-24UKHP-ES4, RAS-18UKHP-ES4) 4-2 Outdoor Unit (RAS-24UAH-ES4) 4-3 Outdoor Unit (RAS-18UAH-ES4) 4-4 Indoor Unit (RAS-24UKP-ES4, RAS-18UKP-ES4) 4-5 Outdoor Unit (RAS-24UA-ES4) 4-6 Outdoor Unit (RAS-18UA-ES4)
FILE NO. SVM-05011
5. REFRIGERATION CYCLE DIAGRAM
5-1 RAS-24UKHP-ES4 / RAS-24UAH-ES4 5-2 RAS-18UKHP-ES4 / RAS-18UAH-ES4 5-3 RAS-24UKP-ES4 / RAS-24UA-ES4 5-4 RAS-18UKP-ES4 / RAS-18UA-ES4
6. CONTROL BLOCK DIAGRAM
6-1 RAS-24UKHP-ES4, RAS-18UKHP-ES4 6-2 RAS-24UKP-ES4, RAS-18UKP-ES4
7. OPERATION DESCRIPTION
7-1 Outline of Air Conditioner Control 7-2 Description of Operation Circuit 7-3 Hi POWER Mode 7-4 High-Temperature Limit Control 7-5 Low-Temperature Limit Control 7-6 Defrost Operation 7-7 Auto Restart Function 7-8 Filter Check Lamp
7-9 Self-Cleaning function
7-10 QUIET Mode 7-11 COMFORT SLEEP mode
- 1 -
Page 3
8. INSTALLATION PROCEDURE
8-1 Safety Cautions 8-2 Installation Diagram of Indoor and Outdoor Units 8-3 Installation 8-4 Indoor Unit 8-5 Outdoor Unit 8-6 How to Set Remote Control Selector Switch 8-7 Others
9. TROUBLESHOOTING CHART
9-1 Troubleshooting Procedure 9-2 Basic Check Items 9-3 Primary Judgement 9-4 Self-Diagnosis by Remote Control (Check Code) 9-5 How to Diagnose Faulty Part 9-6 Troubleshooting for Indoor Unit 9-7 Troubleshooting for Wiring (Interconnect cable and Serial Signal Wire) 9-8 Troubleshooting for P.C. Board 9-9 Troubleshooting for Remote Control
FILE NO. SVM-05011
10. PARTS REPLACEMENT
10-1 Indoor Unit 10-2 Outdoor Unit (RAS-24UAH-ES4, RAS-24UA-ES4) 10-3 Outdoor Unit (RAS-18UAH-ES4) 10-4 Outdoor Unit (RAS-18UA-ES4)
11. EXPLODED VIEWS AND PARTS LIST
11-1 Indoor Unit (E - Parts Assy) 11-2 Indoor Unit 11-3 Outdoor Unit (RAS-24UAH-ES4) 11-4 Outdoor Unit (RAS-18UAH-ES4) 11-5 Outdoor Unit (RAS-24UA-ES4) 11-6 Outdoor Unit (RAS-18UA-ES4)
This air conditioner is charged with HFC (R410A) that doesn't deplete the Ozone layer.
This air conditioner requires special installation for the refrigerant R410A.
- 2 -
Page 4

1. SPECIFICATIONS

FILE NO. SVM-05011
MODEL
ITEM
Capacity
Phase 1
Power source V 220 - 240
Power consumption W 2650 2760 2750 2870 2560 2690 1850 1900 1678 1748 1860 1960 Power factor % 96 91 95 90 94 89 98 97 94 92 97 96
Running current A 0.3/ 0.3/
Indoor/Outdoor 12.2 12.3 8.4 8.0 7.9 7.7
Starting current A Moisture removal lit/h 2.5 2.7 2.0 2.0
Noise
Refrigerant
Refrigerant control Capillary tube
Interconnection Connection type Flare connection pipe Maximum length
INDOOR UNIT RAS-24UKHP-ES4 RAS-24UKP-ES4 RAS-18UKHP-ES4 RAS-18UKP-ES4
Dimensions Width mm 998
Net weight kg 13 Evaporator type Finned tube Indoor fan type Cross flow fan
Air volume Medium fan m3/h 750 800 750 667 708 667
Fan motor output W 30 Air filter Honeycomb woven filter with PP frame OUTDOOR UNIT RAS-24UAH-ES4 RAS-24UA-ES4 RAS-18UAH-ES4 RAS-18UA-ES4
Dimensions Width mm 880 830 780
Net weight kg 59 63 44 39 Condenser type Finned tube Outdoor fan type Propeller fan Airflow volume m3/h 3380 3560 3380 3560 3380 3560 1830 2010 1830 2010 2120 2200 Fan motor output W 65 42
Compressor
Safety device IOL, Td Sensor IOL IOL, Td Sensor IOL Louver type Automatic louver Usable outdoor temperature range °C 15 ~ 43 -10 ~ 24 15 ~ 43 15 ~ 43 -10 ~ 24 15 ~ 43
Note *1 Chargeless pipe
*2 Maximum pipe
Indoor (H/M/L) dB Outdoor (220-240V) dB 56-57 57-58 56-57 52-53 53-54 51-52 Name of refrigerant R410A Rated amount
Gas side size mm ∅12.7 Connection type Flare connection Liquid side size mm ∅6.35
(One way) 25* Maximum height
difference
Height mm 298
Depth mm 208
High fan m3/h 900 900 900 750 800 750
Low fan m3/h 625 667 625 543 584 543
Height mm 690 538
Depth mm 310
Model Output W 2200 1500
45/43/41/39/37
RAS-24UKHP-ES4 RAS-24UKP-ES4 RAS-18UKHP-ES4 RAS-18UKP-ES4
RAS-24UAH-ES4 RAS-24UA-ES4 RAS-18UAH-ES4 RAS-18UA-ES4
Cooling Heating Cooling Cooling Heating Cooling
220V 240V 220V 240V 220V 240V 220V 240V 220V 240V 220V 240V
kW 6.80 6.85 7.30 7.50 6.80 6.85 5.00 5.05 5.45 5.55 5.30 5.35
Hz
220V 240V 220V 240V 220V 240V 220V 240V 220V 240V 220V 240V
0.3/
0.3/
12.85
56
kg
m
m 8
1.50
5JS315DAG01
0.3/12.1 0.3/12.35
13.00
2
10
65
1.6 1.02 1.16
50
0.2/ 0.2/ 0.2/ 0.2/
35
1
15*
300
0.2/8.5 0.2/8.3
42/41/39/37/35
2
20*
5KS225DAA
32
550
270
- 3 -
Page 5
Note : 1
· Capacity is based on the following temperature conditions.
FILE NO. SVM-05011
Condition
Temperature
Indoor unit inlet air temperature
Outdoor unit inlet air temperature
Note : 2
· Charge refrigerant according to the table below.
Refrigerant
*1
No need to charge extra refrigerant
*2 Need to charge
extra refrigerant
RAS-24UKHP-ES4 / RAS-24UAH-ES4
RAS-24UKP-ES4 / RAS-24UA-ES4 RAS-18UKP-ES4 / RAS-18UA-ES4
Over 15m up to 25m (20g/m) Over 15m up to 20m (20g/m)
(DB) 27°C 20°C
(WB) 19°C 15°C
(DB) 35°C 7°C
(WB) 24°C 6°C
15m or less
B8615-1
Cooling Heating
RAS-18UKHP-ES4 / RAS-18UAH-ES4
15m or less
- 4 -
Page 6
2-1. Indoor Unit
Back body
Front panel
Grille inlet
298

2. CONSTRUCTION VIEWS

998
FILE NO. SVM-05011
208
75 7
51
Knock out system
Outline of indoor unit
Connection pipe (0.39m) (Flare
55 or more
Minimum distance
to ceiling
298
12.7)
763.5
20
48
998
450
Drain hose (0.54m)
Connection pipe (0.49m) Wireless remote control (Flare
20
10
75
6.35)
56
(For stud bolt
29
50
Knock out system
57
6)
41
48
55 5555
75
8
50
160
18
65
100
Installation Plate outline
100
65
40
5
Page 7
2-2. Outdoor Unit (RAS-24UAH-ES4, RAS-24UA-ES4)
10
8
12X18
600
600 or
more
-
for
4
600 or
more
anchor bolt
Electric
Parts cover
Liquid side
6.35)
(Flare
Gas side
2.7)
1
(Flare
FILE NO. SVM-05011
Service Port
1212
more
52
Air inlet
340
68
Installation dimension
100 or
25 Drain outlet
120
Air outlet
100 or
more
140
600
310
23
Handle
340 (pitch)
88
74
880
364
A
600
Detail Drawing
A
50
63.8 340
27
12x18 hole
340
690
Handle
6
Page 8
2-3. Outdoor Unit (RAS-18UAH-ES4)
10
-
8
11x14
anchor bolt
for
4x
600 or more
600
600 or
Air inlet
more
Liquid side
Electric
Parts cover
6.35)
(Flare
12.7)
Gas side
(Flare
FILE NO. SVM-05011
Installation dimension
120
Air inlet
325
100 or more
Air
outlet
100 or more
6 holes
-
8
10 anchor bolt)
8
11x14 holes
(for fixing outdoor unit)
or
6-
25 Drain outlet
Service Port
54
344
9
1
60
50
90
600
830
A
R10
600
50
Detail Drawing
A
35
52
325
23
6 hole
11x14 hole
Fan guard
Handle
420
90
538
300
7
Page 9
2-4. Outdoor Unit (RAS-18UA-ES4)
A
FILE NO. SVM-05011
A Detail Drawing (Back Leg)
600
52
310
36
302
270
6 Hole
R15
R5.5
32.5
310
302
30 Drain outlet
436
530
265
FAN GUARD
115 125
2-∅11x14 Hole (For ∅8-∅10 anchor bolt)
600 90 780 62
102
11x14 Hole
B
B Detail Drawing (Front Leg)
310
302
6 Hole
36
52
310 330
R15
COVER PV
Z
Electrical part cover
Installation dimension
100 or more
325
100 or more
Z View
Air outlet
600
Air inlet
600 or more
120
75
600 or more
4x∅11 Long holes (For∅ 8-∅ 10 anchor bolt)
Liquid side (Flare ∅6.35)
Gas side (Flare ∅12.7)
5
4
Service port
8
Page 10
3-1.
RAS-24UKHP-ES4 / RAS-24UAH-ES4
COLOR IDENTIFICATION
BRW : BROWN RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY ORN : ORANGE GRN : GREEN GRN&YEL : GREEN & YELLOW
P04BLK
CN30 CN31

3. WIRING DIAGRAM

Louver motor
BLU
YEL
ORN
PNK
6
5 223311
4
6
5
4
Varistor
DSA
F01
250V6.3A
MAIN P.C. BOARD (WP-003)
FILE NO. SVM-05011
Infrared rays receive
and Indication parts
BLU
RED
BRW
CN07
BLU
1 2 3 4 65 10
98 1071 2 3
4 65 4 6
5
BLU
BLU
BLU
BLU
5 64
321
CN25
10
9871 2 3
BLU
BLU
BLU
WHI
98
7
CN13
10
8 9
7
+12 VDC
+5 VDC
WP-003
OUTDOOR TERMINAL BLOCK
C
SR
COMPRESSOR TERMINAL
POWER SUPPLY 220-240 V~ 50 Hz
L
BLK
RED
BLK
RED
WHI PNK
COMPRESSOR
INDOOR TERMINAL BLOCK
i
N
FERRITE CORE
RED
MAGNETIC
CONTACTOR
R
S
(1/L1)
(3/L2)
(2/T1)
(4/T2)
U
V
CAPACITOR
S
C
R
BLK
1
1
GRN&YEL
T
(5/L3) (6/T3)
W
A1
52C
A2
CN23
2
2
RED
RE
3
3
WHI
i
CHASSIS
CAPACITOR
D
FAN MOTOR
Serial Signal
circuit
INDOOR UNIT
OUTDOOR UNIT
TRANSFORMER
GRN&YEL
COIL FOR 4 WAY VALVE
BLK
BLK BLK
RED RED
BLK BLK WHI RED GRY
BLU
YEL
BLU
BLU
YEL
GRY
BRW
1 3
1 3
1 3 5 7 9
1 313
11 33
1
2
4
3
1
2
66554
3
145 C
TEMP FUSE
MAIN P.C. BOARD (MCC-890)
1 2
CN06
3
1
CN05
3
1 3 5
CN01
7 9
SG01
F01
250VAC T6. 3A
TNR R74
CN11
CR11
CN02
CR12
CR13
BLK
1 1
CN03
RY07
RY05
3
TNR R73
RY06
CN07
CN08
DISCHARGE PIPE SENSOR (TD)
BLU
1
1 2 3
3
BLU
BLK
1
1
2 3
3
BLK
HEA
T
EXCHANGER SENSOR (TE)
9
Page 11
3-2. RAS-18UKHP-ES4 / RAS-18UAH-ES4
COLOR IDENTIFICATION
BRW : BROWN RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY ORN : ORANGE GRN : GREEN GRN&YEL : GREEN & YELLOW
CN30 CN31
P04BLK
DSA
Varistor
F01
250V6.3A
MAIN P.C. BOARD (WP-003)
Louver motor
BLU
PNK
6
5 223311 5
6
FILE NO. SVM-05011
Infrared rays receive
and Indication parts
BLU
CN07
BLU
1 2 3 4 65 10
RED
YEL
ORN
BRW
4 4
98 1071 2 3
4 65 4 6
5
BLU
BLU
BLU
BLU
5 64
321
CN25
10
9871 2 3
WHI
BLU
BLU
BLU
98
7
CN13
10
8 9
7
+12 VDC
+5 VDC
WP-003
OUTDOOR TERMINAL BLOCK
C
SR
COMPRESSOR TERMINAL
POWER SUPPLY 220-240 V~ 50 Hz
L
BLK
RED
BLK
RED
WHI PNK
COMPRESSOR
CN23
INDOOR TERMINAL BLOCK
i
N
FERRITE CORE
RED
MAGNETIC
CONTACTOR
R
S
1
1
GRN&YEL
T
A1
2
3
2
3
i
CHASSIS
INDOOR UNIT
OUTDOOR UNIT
GRN&YEL
52C
BLK
A2
W
RED
WHI
D
RE
FAN MOTOR
U
V
CAPACITOR CAPACITOR
S
C
R
Serial Signal
circuit
TRANSFORMER
YEL
BLK BLK
RED RED
BLK BLK WHI RED GRY
BLU
YEL
BLU
BLU COIL FOR 4 WAY VALVE
BLK
GRY
BRW
1 3
1 3
1 3 5 7 9
1 313
11 33
1
2
4
3
1
2
66554
3
145 C
TEMP FUSE
MAIN P.C. BOARD (MCC-890)
1 2
CN06
3
1
CN05
3
1 3 5
CN01
7 9
SG01
F01
250VAC T6. 3A
TNR R74
CN11
CR11
CN02
CR12
CR13
CN03
1 1
BLK
RY07
RY05
3
TNR R73
RY06
CN07
CN08
DISCHARGE PIPE SENSOR (TD)
BLU
1
1 2 3
3
BLU
BLK
1
1
2 3
3
BLK
HEA
T
EXCHANGER SENSOR (TE)
10
Page 12
3-3. RAS-24UKP-ES4 / RAS-24UA-ES4
COLOR IDENTIFICATION
BRW : BROWN RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY ORN : ORANGE GRN : GREEN
GRN&YEL : GREEN & YELLOW
P04
BLK
CN30 CN31
CN27
DSA
Varistor
6.3A
F01
250V
Varistor
Louver motor
BLU
PNK
6
5 223311
6
5
FILE NO. SVM-05011
Infrared rays receive
and Indication parts
1 2 3 4 6 10
BLU
BLU
BLU
YEL
RED
BRW
ORN
4
CN07
4
BLU
1 2 3 4 65 10
321
Power supply circuit
Control Fan motor circuit
7
5 98
7
BLU
BLU
7
5 64
7
105 64321
8 9
CN25
BLU
BLU
BLU
WHI
98
CN13
10
8 9
OUTDOOR TERMINAL BLOCK
INDOOR TERMINAL BLOCK
POWER SUPPLY 220 240 V ~ 50 Hz
L
N
BLK
RED
BLK
RED
RED
1
1
BLK BLK
SPARK KILLER
A2 A1
52C
1/L1 2/T1
3/L2 4/T2
6/T35/L3
GRN&YEL
2
2
GRN&YEL
RED
CAPACITOR
3
3
GRY
CHASSIS
RED
WHI PNK
COMPRESSOR
MAIN P.C. BOARD (WP-003)
INDOOR UNIT
OUTDOOR UNIT
CAPACITOR
S
C
R
WHI RED
FAN MOTOR
BLK
COMPRESSOR TERMINAL
2
1
21
1
GRY
BRW
YEL
1
2
4
3
1
2
66554
3
145 C
TEMP FUSE
BLK2BLK
Thermo. sensor
(TA)
CN03
Heat exchanger sensor
(TC)
CN01
2
1
BLK
BLK
BLK
C
SR
MAGNETIC CONTACTOR
11
Page 13
RAS-18UKP-ES4 / RAS-18UA-ES4
3-4.
P04
BLK
CN30 CN31
CN27
GRN&YEL
COLOR IDENTIFICATION
BRW : BROWN RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY ORN : ORANGE GRN : GREEN GRN&YEL : GREEN & YELLOW
Varistor
DSA
6.3A
MAIN P.C. BOARD (WP-003)
F01
250V
Varistor
Louver motor
BLU
YEL
PNK
6
5 223311
4
6
5
4
FILE NO. SVM-05011
Infrared rays receive
and Indication parts
1 2 3 4 6 10
BLU
BLU
BLU
RED
BRW
ORN
CN07
BLU
1 2 3 4 65 10
321
Power supply
circuit
Control Fan motor circuit
GRY
BRW
YEL
5 98
BLU
BLU
5 64
105 64321
8 9
7 7
BLU
7 7
8 9
CN25
BLU
BLU
WHI
98
CN13
10
2
1
21
1
BLK2BLK
CN03
CN01
2
1
BLK
BLK
OUTDOOR TERMINAL BLOCK
POWER SUPPLY 220 240 V ~ 50 Hz
L
BLK
MAGNETIC
CONTACTOR
BLK
RED
INDOOR
TERMINAL
BLOCK
N
RED
R
U
1
1
GRN&YEL
S
V
2
2
RED
SPARK KILLER
T
W
BLK
1
2
4
3
1
2
3
145 C
TEMP FUSE
3
3
BLK
CHASSIS
(or A)
A1
(or B)
A2
INDOOR UNIT
OUTDOOR UNIT
GRN&YEL
GRY
Thermo. sensor
66554
(TA)
Heat exchanger sensor
(TC)
CAPACITOR
RED
S
WHI PNK
R
COMPRESSOR
COMPRESSOR TERMINAL
CAPACITOR
RED
C
BLK
WHI
RED
BLK
FAN MOTOR
C
R
S
12
Page 14
FILE NO. SVM-05011

4. SPECIFICATION OF ELECTRICAL PARTS

4-1. Indoor Unit (RAS-24UKHP-ES4, RAS-18UKHP-ES4)
No. Parts name Type Specifications
1 Fan motor (for indoor) AFS-220-31A AC 200 240V, 31W 2 Thermo sensor (TA-sensor) ——— 10 k at 25°C 3 Micro Power Module (M01) µRM1260V DC 390 V, Secondary DC 12 V 4 Microcontroller TMP87CM40AN 5 Heat exchanger sensor
(TC-sensor) 6 Line filter (L01) LC*SS11V-06270 27mH, 600mA 7 Diode (DB01) D3SBA60 4 A, 600 V 8 Capacitor (C63) KMH400VSSN47M22S 4.7µF, 400 V 9 Fuse (F01) BET6.3A T6.3 A, 250 V
10 Varistor (R21, R22) 15G561K 560 V
11 Resistor (R319) RF-2TK5R6 5.6 , 2 W 12 Louver motor MP35EA12 Output (Rated) 2 W, 10 poles, 1 phase,
——— 10 k at 25°C
DC 12 V
4-2. Outdoor Unit (RAS-24UAH-ES4)
No. Parts name Type Specifications
Output (Rated) 2200W, 2poles, 1 phase, 220 − 240V, 50Hz
1 Compressor 5JS315DAG01 Winding resistance (Ω) Red-Black White-Black
(at 20°C) 0.830 2.257 Output (Rated) 65W, 6poles, 1 phase, 220 – 240V, 50Hz
2 Fan motor (for outdoor) KFG6-71SB5P-T1 Winding resistance () Red-Black White-Black
(at 20°C) 64.4 127.4
Running capacitor
3
(for fan motor)
Running capacitor
4
(for compressor)
Solenoid coil
5
(for 4-way valve) 6 Thermo sensor TE / TD 10k at 25°C / 50k at 25°C 7 Magnetic contactor A35 220 ~ 240V, 50Hz 8 Transformer TT-05 220 ~ 240V 9 Microcontroller TMP47C840N
10 Varistor (R73, R74) 15G471K 470V 11 Fuse (F01) TSCR T6.3A, 250V
451355L AC 450V, 3.5µF
BUM44X4505B AC 440V, 45µF
VHV (STF) AC 220 ~ 240V
– 13 –
Page 15
FILE NO. SVM-05011
4-3. Outdoor Unit (RAS-18UAH-ES4)
No. Parts name Type Specifications
Output (Rated) 1500W, 2poles, 1 phase, 220 − 240V, 50Hz
1 Compressor 5KS225DAA Winding resistance (Ω) Red-Black White-Black
(at 20°C) 1.632 2.457 Output (Rated) 65W, 6poles, 1 phase, 220 – 240V, 50Hz
2 Fan motor (for outdoor) WLF-240-42A-2 Winding resistance (Ω) Red-Black White-Black
(at 20°C) 188 289
Running capacitor
3
(for fan motor)
Running capacitor
4
(for compressor)
Solenoid coil
5
(for 4-way valve) 6 Thermo sensor TE / TD 10k at 25°C / 50k at 25°C 7 Magnetic contactor CLK-26J 220 − 240V, 50Hz 8 Transformer TT-05 220 − 240V 9 Microcomputer TMP47C840N
10 Varistor (R73, R74) 15G471K 470V 11 Fuse (F01) TSCR T6.3A, 250V
451155L AC 450V, 1.5 µF
BUM44X4505B AC 440V, 45µF
VHV (STF) AC 220 − 240V
4-4. Indoor Unit (RAS-24UKP-ES4, RAS-18UKP-ES4)
No. Parts name Type Specifications
1 Fan motor (for indoor) AFS-220-31A AC 200 240V, 31W 2 Thermo sensor (TA-sensor) ——— 10 k at 25°C 3 Micro Power Module (M01) µRM1260V DC 390 V, Secondary DC 12 V 4 Microcontroller TMP87CM40AN 5 Heat exchanger sensor
(TC-sensor) 6 Line filter (L01) LC*SS11V-06270 27mH, 600mA 7 Diode (DB01) D3SBA60 4 A, 600 V 8 Capacitor (C63) KMH400VSSN47M22S 4.7µF, 400 V 9 Fuse (F01) BET6.3A T6.3 A, 250 V
10 Varistor (R21, R22) 15G561K 560 V
11 Resistor (R319) RF-2TK5R6 5.6, 2 W 12 Louver motor MP35EA12 Output (Rated) 2 W, 10 poles, 1 phase,
13 Relay : (RY04) G5NB-1A Coil DC 12V, 16.7mA, Contact AC 250V, 1A
——— 10 k at 25°C
DC 12 V
14
Page 16
FILE NO. SVM-05011
4-5. Outdoor Unit (RAS-24UA-ES4)
No. Parts name Type Specifications
Output (Rated) 2200W, 2poles, 1 phase, 220 − 240V, 50Hz
1 Compressor 5JS315DAG01 Winding resistance ( ) Red-Black White-Black
(at 20°C) 0.830 2.257 Output (Rated) 65W, 6poles, 1 phase, 220 − 240V, 50Hz
2 Fan motor (for outdoor) KFG6-71SB5P-T Winding resistance (Ω) Red-Black White-Black
(at 20° C) 64.4 127.4
Running capacitor
3
(for fan motor) Running capacitor
4
(for compressor)
5
Magnetic contactor
451355L AC 450V, 3.5µ F
BUM44X4505B
A35
AC 440V, 45µ F
220 240V, 50Hz
4-6. Outdoor Unit (RAS-18UA-ES4)
No. Parts name Type Specifications
Output (Rated) 1500W, 2poles, 1 phase, 220 − 240V, 50Hz
1 Compressor 5KS225DAA Winding resistance (Ω) Red-Black White-Black
(at 20°C ) 1. 632 2.457
Output (Rated) 42W, 6poles, 1 phase, 220 240V, 50Hz
2 Fan motor (for outdoor) WLF-240-42A-1 Winding resistance (Ω) Red-Black White-Black
(at 20°C) 188 289
Running capacitor
3
(for fan motor) Running capacitor
4
(for compressor)
5
Magnetic contactor
451155L AC 450V, 1.5µF
BUM44X4505B AC 440V, 45µF
CLK-26J
220 240V, 50Hz
15
Page 17

5. REFRIGERATION CYCLE DIAGRAM

5-1. RAS-24UKHP-ES4 / RAS-24UAH-ES4
FILE NO. SVM-05011
0.39m (Connecting pipe)
12.7
O.D.:12.7mm
Cooling
Heating
Tank
Indoor unit
Cooling
Heating
P
Packed valve
(
12.7)
Gas container connection (Reinstall etc.)
Heating
4-way valve
Cooling
Compressor
5JS315DAG01
Heat exchanger
Cross flow fan
T1
Packed valve
(
6.35)
Capillary tube
2.0x800
s
0.
49m
(Connecting pipe)
6.35
O.D.:6.35mm
Condenser
Refrigerant R410A 1.5 kg
)means check points of Gas Leak.
Cooling Heating
Propeller fan
Outdoor unit
Mark(
Ambient temp.
50Hz
Standard
pressure
(MPaG)
P
Surface temp. of heat
exchanger interchanging
pipe
T1
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
Indoor Outdoor
Standard 3.1 50.9 High 20/– 7/6
Heating Overload*1 3.8 ~ 4.0 57.0 ~ 59.0 Low 27/– 24/18
Low temperature 2.6 35.0 High 20/– –10/–10 Standard 0.8 7.2 High 27/19 35/24
Cooling Overload 1.3 12.0 High 32/23 43/26
Low temperature 0.6 1.0 Low 21/15 21/15
Note :
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
*1 During heating overload operation, a value for the high temperature limit control operation is included.
– 16
Page 18
5-2. RAS-18UKHP-ES4 / RAS-18UAH-ES4
FILE NO. SVM-05011
0.39m (Connecting pipe)
12.7
O.D.:12.7mm
Cooling
Heating
Indoor unit
Cooling
Heating
P
Packed valve
(
Heating
4-way valve
Cooling
Compressor
12.7)
5KS225DAA
Accumulator
Evaporator
Cross flow fan
T1
Packed valve
6.35)
(
Capillary tube
2.0x1200
s
0.49m (Connecting pipe)
6.35
O.D.:6.35mm
Condenser
Cooling Heating
Propeller fan Outdoor unit
Mark(
Refrigerant R410A 1.
)means check points of Gas Leak.
02 kg
Ambient temp.
50Hz
Standard
pressure
(MPaG)
P
Surface temp. of heat
exchanger interchanging
pipe
T1
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
Indoor Outdoor
Standard 2.6 44.7 High 20/– 7/6
Heating Overload*1 3.0 ~ 3.6 49.0 ~ 56.0 Low 27/– 24/18
Low temperature 2.0 32.0 High 20/––10/–10 Standard 0.9 9.5 High 27/19 35/24
Cooling Overload 1.1 12.6 High 32/23 43/26
Low temperature 0.7 2.4 Low 21/15 21/15
Note :
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
*1 During heating overload operation, a value for the high temperature limit control operation is included.
17
Page 19
5-3. RAS-24UKP-ES4 / RAS-24UA-ES4
FILE NO. SVM-05011
0.39m (Connecting pipe)
12.7
O.D.:12.7mm
Cooling
Compressor
Indoor unit
Cooling
P
Packed valve
(
12.7)
Gas container connection (Reinstall etc.)
Accumulator
5JS315DAG01
Heat exchanger
Cross flow fan
T1
Packed valve
6.35)
(
Capillary tube
2.0x700
s
0.49m (Connecting pipe)
6.35
O.D.:6.35mm
Condenser
Refrigerant R410A 1.6kg
)means check points of Gas Leak.
Cooling
Propeller fan Outdoor unit
Mark(
Ambient temp.
50Hz
Standard
pressure
(MPaG)
P
Surface temp. of heat
exchanger interchanging
pipe
T1
(° C)
Fan speed
(indoor)
conditions DB/WB
(° C)
Indoor Outdoor
Standard 0.6 6.0 High 27/19 35/24
Cooling Overload 1.10 10.0 High 32/23 43/26
Low temperature 0.5 2.0 Low 21/15 21/15
Note :
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
18
Page 20
5-4. RAS-18UKP-ES4 / RAS-18UA-ES4
FILE NO. SVM-05011
0.39m (Connecting pipe)
12.7
O.D.:12.7mm
Cooling
Compressor
Indoor unit
Cooling
P
Packed valve
(
12.7)
5KS225DAA
Evaporator
Cross flow fan
T1
Packed valve
6.35)
(
Capillary tube
1.7x600
s
0.49m (Connecting pipe)
6.35
O.D.:6.35mm
Condenser
Cooling
Propeller fan Outdoor unit
Mark(
Refrigerant R410A 1.
)means check points of Gas Leak.
16 kg
Ambient temp.
50Hz
Standard
pressure
(MPaG)
P
Surface temp. of heat
exchanger interchanging
pipe
T1
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
Indoor Outdoor
Standard 1.1 10.0 High 27/19 35/24
Cooling Overload 1.2 13.0 High 32/23 43/26
Low temperature 0.6 2.0 Low 21/15 21/15
Note :
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
19
Page 21

6. CONTROL BLOCK DIAGRAM

6-1. RAS-24UKHP-ES4, RAS-18UKHP-ES4
Indoor Unit Control Panel
Heat Exchanger Sensor
Functions
Louver Control
FILE NO. SVM-05011
M.C.U.
Operation
Display
Temperature Sensor
Infrared Rays Signal Receiver
Infrared
Rays
Remote
Control
From Outdoor Unit
220 ~ 240 V AC 50 Hz
Initiallizing Circuit
Clock Frequency
Oscillator Circuit
Power Supply
Circuit
Noise Filter
3-minute Delay at Restart for Compressor
Motor Revolution Control
Processing
(Temperature Processing)
Timer
Serial Signal Communication
Louver ON/OFF Signal
Louver Driver
Serial Signal Transmitter/Receiver
Serial Signal Communication
Timer
Display
Filter Sign
Display
PRE DEF.
Sign Display
Hi Power
Sign Display
Indoor
Fan Motor
Louver Motor
REMOTE CONTROL
Infrared Rays
Remote Control
Operation ( )Operation ( )
Operation Mode Selection
AUTO, COOL, DRY, HEAT, FAN ONLY
Temperature Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
Louver Direction Setting
ECO
Hi power
TIMER 1.3.5.9H
COMFORT SLEEP
QUIET
20
Page 22
6-2. RAS-24UKP-ES4, RAS-18UKP-ES4
Indoor Unit Control Panel
Heat Exchanger Sensor
Functions  Louver Control
FILE NO. SVM-05011
M.C.U.
Operation
Display
Temperature Sensor
Infrared Rays Signal Receiver
Infrared
Rays
Remote
Control
From Outdoor Unit
220 ~ 240V AC 50Hz
Initiallizing Circuit
Clock Frequency
Oscillator Circuit
Power Supply
Circuit
Noise Filter
 3-minute Delay at Restart for Compressor
 Motor Revolution Control
 Processing
(Temperature Processing)
 Timer
Outdoor unit
ON/OFF Signal
Relay Driver
Relay RY04
Outdoor Unit
Louver ON/OFF Signal
Louver Driver
Timer
Display
Filter Sign
Display
Fan Only
Sign Display
Hi Power
Sign Display
Indoor
Fan Motor
Louver Motor
REMOTE CONTROL
Infrared Rays
Remote Control
Operation ( )Operation ( )
Operation Mode Selection
AUTO, COOL, DRY, HEAT, FAN ONLY
Temperature Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
Louver Direction Setting
ECO
Hi power
TIMER 1.3.5.9H
COMFORT SLEEP
QUIET
21
Page 23

7. OPERATION DESCRIPTION

FILE NO. SVM-05011
7-1. Outline of Air Conditioner Control
This is a fixed capacity type air conditioner, which uses a AC motor for an indoor fan. The AC motor drive circuit is mounted in the indoor unit. And electrical parts which operate the compressor and the outdoor fan motor, are mounted in the outdoor unit. The air conditioner is mainly controlled by the indoor unit controller. The controller operates the indoor fan motor based upon commands transmitted by the remote control and transfers the operation commands to the outdoor unit controller. The outdoor unit controller receives operation commands from the indoor unit, and operates the outdoor fan motor and the compressor.
(1) Role of indoor unit controller
The indoor unit controller receives the operation commands from the remote control and executes them.
· Temperature measurement at the air inlet of the indoor heat exchanger by the indoor temperature sensor
· Temperature setting of the indoor heat exchanger by the heat exchanger sensor
· Louver motor control
· Indoor fan motor operation control
· LED display control
· T ransferring of operation commands to the
outdoor unit
· Receiving of information of the operation status and judging of the information or indication of error
Table 7-1-1
OPERATION MODE
RAS-24UKHP Series
RAS-18UKH Series
Model
RAS-24UKP Series
RAS-18UKP Series
Cooling
Heat
Fan Only
Dry
rpm
Air Flow volume(m /h)
rpm
Air Flow volume(m /h)
rpm
Air Flow volume(m /h)
rpm
Air Flow volume(m /h)
3
3
3
3
1300
790
(2) Role of outdoor unit controller
The outdoor unit controller receives the operation commands from the indoor controller and executes them.
· Compressor operation
control
· Operation control of
outdoor fan motorf
Turning off the compressor and outdoor fan
·
when the outdoor unit receives the shutdown command
· Defrost control in heating operation
(Temperature measurement by the outdoor heat exchanger and control for the four-way valve and the outdoor fan motor) *Heat pump Model only
7-1-1. Louver contr
ol
(1) Vertical air flow louver
Position of veritcal air flow louver is automatically controlled according to the operation mode. Besides, position of vertical air flow louver can be arbitrarily set by pressing [FIX] button. The louver position which is set by [FIX] button is stored in the microcomputer, and the louver is automatically set at the stored position for the next operation.
(2) Swing
If [SWING] button is pressed when the indoor unit is in operation, the vertical air flow louver starts swinging. When [FIX] button is pressed, it stops swinging.
7-1-2. Indoor fan control (AC Fan motor)
(1) The indoor fan is operated by the stepless speed
change AC motor
(2) For air flow level, speed of the indoor fan motor is
controlled in five steps (LOW, LOW and HIGH). If AUTO mode is selected, the fan motor speed is automatically controlled by the difference between the preset temperature and
the room temperature.
FAN TAP
UH H
900
M+
H M+ M
M+ M
1250 1200
830
11501200
750
1300
900
1150
750
1100
1250
830
1100
708
708
M L+
MUH H
1150 1050 1000 900 800 700
790
750
1050
667
1150
750
1050
667
667
950
584
.
1050
667
950
584
Operations according to the commands from the indoor unit
L L- UL SUL/SL-
L L-
L L-
625
900
543
1000
625
900
543
UL
543
800
461
900
543
800
461
461
700
380
800
461
700
380
L-LL+
L+
L+
+
, MED, MED
UL SUL
380
600
300
700
380
600
300
+
SUL/SL-
600
300
500
220
Note : Under some function of setting. The fan motor is controlled automatically.
Then LOW+ = LOW + MED and MED
2
+
= MED + HIGH
2
22
Page 24
FILE NO. SVM-05011
7-2. Description of Operation Circuit
(1) When turning on the breaker, the operation lamp
blinks. This means that the power is on (or the power supply is cut off.)
(2) When pressing [ ] button on the
remote control, receiving beep sounds from the indoor unit, and the next operation is performed together with opening the vertical air flow louver.
(3) Once the operation mode is set, it is memorized in
the microcomputer so that the previous operation can be effected thereafter simply by pressing [ ] button.
7-2-1. Fan only operation
([MODE] button on the remote control is set to the fan only operation.)
(1) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-1. When [FAN] button is set to LOW, LOW HIGH, the motor operates with a constant air flow.
+
, MED, MED+ or
7-2-2. Cooling operation
([MODE] button on the remote control is set to the cooling operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display lamp are controlled as shown in Fig. 7-2-2.
ON
4-way valve
Compressor
Outdoor fan
(Heat pump model)
Preset temp.
0.5
ON
OFF OFF OFF ON
0
Fig. 7-2-2
display lamp
OPERATION
+3
+2.5
(Preset temp.)
-
+2
+1.5
+1
+0.5
(Room temp.)
Preset temp.
0
(Preset temp.: 24°C)
NOTE : *1: The values marked with *1 are calculated and
controlled by the difference in motor speed between M+ and L-.
(2)
The Hi Power, ECO and COMFORT SLEEP operation cannot be set.
Fig. 7-2-1 Setting of air flow [FAN:AUTO]
M+
*1
*1
*1
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-3. When [FAN] button is set to LOW, LOW
+
, MED, MED+ or
HIGH, the motor operates with a constant air flow.
(Preset temp.)
-
(Room temp.)
Preset temp.
+3
+2.5
+2
+1.5
+1
+0.5
0
-0.5
M+
*1
*1
*1
NOTE : *1: The values marked with *1 are calculated and
controlled by the difference in motor speed between M+ and L-.
Fig. 7-2-3 Setting of air flow [FAN:AUTO]
- 23 -
Page 25
FILE NO. SVM-05011
7-2-3. Dry operation
([MODE] button on the remote control is set to the dry operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display lamp are controlled as shown in Fig. 7-2-4.
ON:6min.
OFF:4min.
ON:5min.
OFF:5min.
OFF
4-way valve
Outdoor fan
Preset temp.
+3
+2
+1
ON:6min.
OFF:4min.
OFF
ON:5min.
OFF:5min.
OFF
0
Compressor
Fig. 7-2-4
ON
display lamp
OPERATION
7-2-4. Heating operation *Heat pump model only
([MODE] button on the remote control is set to the heating operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display lamp are controlled as shown in Fig. 7-2-6.
Preset temp.
OFF
ON
ON
Compressor
ON
OFF
ON
4-way valve
Outdoor fan
OPERATION
Fig. 7-2-6
display lamp
(2) The microprocessor turns the compressor on and
off at the regular intervals (4 to 6 minutes). While the compressor is turning off, the indoor fan motor operates in the SUPER LOW position. The pattern of operation depending on the relation between room temperature and preset temperatures is shown in Fig. 7-2-5.
Room temp.
Preset temp.+1
Preset temp.
Compressor
Outdoor fan
Indoor fan
ON ON ON ON
OFF OFF OFF
L. *S.L. S.L.L. L. S.L. L.
*Super Low
Fig. 7-2-5
(3) [FAN] button on the remote control is set to AUTO
only.
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-7. When [FAN] button is set to LOW, LOW
+
, MED, MED+ or
HIGH, the motor operates with a constant air flow.
Preset temp.
0
-0.5
-1
-1.5
-2
-5.0
-5.5
[FAN AUTO]
L
*1 *2
+
M
H
*1, *2 : The values marked with *1 and *2 are
calculated and controlled by the difference in motor speed between M+ and L.
Fig. 7-2-7 Setting of air flo w [FAN:AUTO]
(4) The ECO and Hi Power operations can not be set.
- 24 -
Page 26
FILE NO. SVM-05011
(3) The indoor heat exchanger restricts revolving
speed of the fan motor to prevent a cold draft. The upper limit of the revolving speed is shown in Fig. 7-2-8 and Table 7-2-1.
Manual (One of
AUTO
*4
SUL*
SUL*1 Stop
5 speed)
L-H (Up to setting
3
speed)
*2
A+4 A+4
464534
33
33 21 32 20
A-8 A-8
*6 *5
NOTES :
*1: The fan stops for 2 minutes after thermostat-OFF. *2: A is 24°C when the preset temperature is 24°C or
more and A is the preset temperature when it is
under 24°C. *3: SUL means Super Ultra Low. *4: Calculated from difference in motor speed
between SUL and HIGH.
7-2-5. Automatic operation
([MODE] button on the remote control is set to the automatic operation.)
(1) One of 3 operations (Cooling, Fan only or Heating)
is selected according to difference between the preset temperature and the room temperature at which the automatic operation has started, as shown in Fig. 7-2-9. The Fan only operation continues until the room temperature reaches a level at which another mode is selected.
(2) Temporary Auto
When the TEMPORARY button on the indoor unit is pushed, the preset temperature is fixed at 24°C and the indoor unit is controlled as shown in Fig. 7-2-9.
C
Cooling operation
The louver moves to the position same as Hi POWER operation.
+4
Cooling operation
0
Fan only operation
Fig. 7-2-8 Cold draft preventing control
*5 and *6:
Table 7-2-1
Fan *5 *6 speed Starting period Stabilized period
AUTO Up until 12 minutes
passed after starting the unit
From 12 to 25 minutes
passed after starting the unit and room temperature is 3°C lower than preset temperature
Manual Room temperature (L - H) < Preset temperature
From 12 to 25 minutes passed after starting the unit and room temperature is between preset temperature and 3°C lower than preset temperature
25 minutes or more passed after starting the unit
Room temperature
Preset temperature
-4°C
-3.5°C
Heating operation
(Room temp.) - (Preset temp.)
RAS-24UKHP-ES4 RAS-18UKHP-ES4
RAS-24UKP-ES4 RAS-18UKP-ES4
Fig. 7-2-9
- 25 -
Page 27
FILE NO. SVM-05011
60
55 52
Compressor
Outdoor fan
OFF
OFF
ON
ON
OFF
ON
Heat exchanger temp.
7-3. Hi POWER Mode
([Hi POWER] button on the remote control is pressed.)
When [Hi POWER] button is pressed while the indoor unit is in Auto, Cooling or Heating operation, Hi POWER mark is indicated on the display of the remote control and the unit operates as follows.
(1) Automatic operation
· The indoor unit operates in according to the
current operation.
(2) Cooling operation
· The preset temperature drops 3°C.
(The value of the preset temperature on the remote control does not change.)
·
 If the room temperature is higher than the
setting temperature by 3.5 °C or more, the
horizontal louver moves to the Hi POWER position automatically. Then when the room
temperature is °C less than the setting temperature the horizontal louver returns automatically.
·
 FAN speed : [AUTO]
If the temperature is higher than the
setting temperature by 3.5°C or mor, the air conditioner operates at maxim airflow
level. If the temperature is higher than the
setting temperature by less than 3.5°C, the air conditioner operates at normal airflow level.
·
 FAN speed : One of 5 levels
If the temperature is higher than the
setting temperature by 3.5°C or more, the air conditioner operates at higher consecutive airflow level. If the room temperature is higher
than the setting temperature by less than 3.5°C, the air conditioner operates at normal airflow level.
7-4. High-Temperature Limit Control
*Heat pump model only
The microcontroller detects the indoor heat exchanger temperature to prevent pressure of a refrigerating cycle from increasing excessively. The compressor and outdoor fan motor are controlled as shown in Fig. 7-4-1.
Fig. 7-4-1
7-5. Low-Temperature Limit Control
The microcontroller detects the indoor heat exchanger temperature to prevent the indoor heat exchanger from freezing.
· The compressor and outdoor fan motor are controlled as shown in Fig. 7-5-1.
Heat exchanger temperature
6
2
Compressor Outdoor fan
ON
Less than continues
for 5 minutes
OFF
Fig. 7-5-1
7-6. Defrost Operation *Heat pump model only
(3) Heating operation (UKH Series only)
·
 The preset temperature increases 2°C,
(The value of the preset temperature on the remote control does not change.)
 The indoor unit operates in normal heating
·
mode except the preset temperature is higher (+2°C).
(4) The Hi POWER mode can not be set in Dry or
Fan only operation.
When the indoor unit is in heating operation, if the refrigerant evaporation temperature detected by the outdoor heat exchanger sensor is under the specified temperature, the outdoor unit starts the defrosting operation. At this time, the 4-way valve relay and the outdoor fan motor are turned off. The indoor fan motor is also turned off by the cold draft preventing control of the indoor microcomputer. Then, [PRE. DEF.] lamp on the indoor unit comes on. The defrosting operation stops and the 4-way valve relay, outdoor fan motor and the indoor fan motor are turned on automatically when the refrigerant evaporation increases to the specified temperature, or when the defrosting time is over 12 minutes.
- 26 -
Page 28
FILE NO. SVM-05011
7-6-1. Defrost starting condition
A-Zone : If -10°C > Teo ≥ − 18°C, defrost will
start when. Teo - Te 2.5°C at teat 20 sec or
~ 30 min after operation.
B-Zone : If Te ≤ −18°C, defrost start instantaneously
(Suddenly) 00 ~ 25 min ofter operation
C-Zone : If -2ºC Teo ≥ −10°C defrost will start when
Teo - Te ≤ −3°C at least 20 sec or ~ 60 min after operation.
7-6-2. Defrost finish condition.
1) If Te 3°C at least 60 sec -->4 way value on.
2) If Te 8°C --> 4 way value on.
Timing
Operation time (4 Loops = Tt)
Td1
Td2
Td3 Td4
Finish time recordStart time record
Defrost time rate : (Td/Tt) x 100 Heating time rate : (Tt - Td) x Tt
Fig. 7-6-2
-
27
-
Page 29
FILE NO. SVM-05011
7-7. Auto Restart Function
The indoor unit is equipped with an automatic restarting function which allows the unit to restart operating with the set operating conditions in the event of power supply being accidentally shut down. The operation will resume without warning three minutes after power is restored. This function is not set to work when shipped from the factory. Therefore it is necessary to set it to work.
7-7-1. How to set auto restart function
To set the auto restart function, proceed as follows: The power supply to the unit must be on; the function will not set if the power is off. Push the [TEMPORARY] button located in the center of the front panel continuously for three seconds. The unit receives the signal and beeps three times. The unit then restarts operating automatically in the event of power supply being accidentally shut down.
When the unit is on standby (Not operating)
Operation Motions
Push [TEMPORARY] button for more The unit is on standby. than three seconds.
The unit starts to operate. The green lamp is on.
After approx. three seconds,
0
3S
The unit beeps three times The lamp changes from and continues to operate. green to orange.
TEMPORARY button
If the unit is not required to operate at this time, push [TEMPORARY] button once more or use the remote control to turn it off.
When the unit is in operation
Operation Motions
Push [TEMPORARY] button for more The unit is in operation. The green lamp is on. than three seconds.
The unit stops operating. The green lamp is turned off.
After approx. three seconds,
0
3S
TEMPORARY button
While this function is being set, if the unit is in operation, the orange lamp is on.
This function can not be set if the timer operation
The unit beeps three times. If the unit is required to operate at this time, push [TEMPORARY]
button once more or use the remote control to turn it on.
While the filter check lamp is on, the [TEMPORARY] button has the function of filter reset button.
has been selected.
When the unit is turned on by this function, the louver will not swing even though it was swinging automatically before shutting down.
28
Page 30
7-7-2. How to cancel auto restart function
To cancel auto restart function, proceed as follows: Repeat the setting prodedure: the unit receives the signal and beeps three times. The unit will be required to be turned on with the remote control after the main power supply is turned off.
When the unit is on standby (Not operating)
Operation Motions
Push [TEMPORARY] button for more The unit is on standby. than three seconds.
FILE NO. SVM-05011
The unit starts to operate. The orange lamp is on.
After approx. three seconds,
0
3S
The unit beeps three times The lamp changes from and continues to operate. orange to green.
TEMPORARY button
If the unit is not required to operate at this time, push [TEMPORARY] button once more or use the remote control to turn it off.
When the unit is in operation
Operation Motions
Push [TEMPORARY] button for more The unit is in operation. The orange lamp is on. than three seconds.
The unit stops operating. The orange lamp is turned off.
After approx. three seconds,
0
3S
TEMPORARY button
While this function is being set, if the unit is in
The unit beeps three times. If the unit is required to operate at this time, push [TEMPORARY]
button once more or use the remote control to turn it on.
7-8. Filter Check Lamp
operation, the orange lamp is on.
When the elapsed time reaches 1000 hours, the filter
7-7-3. Power failure during timer operation
check lamp indicates. After cleaning the filters, turn off the filter check lamp.
When the unit is in Timer operation, if it is turned off because of power failure, the timer operation is
7-8-1. How to turn off filter check lamp
cancelled. Therefore, set the timer operation again.
Press [FILTER] button on the remote control. OR push [TEMPORARY] button on the indoor unit.
Note:
If [TEMPORARY] button is pushed while the filter check lamp is not indicating, the indoor unit will start the Automatic Operation.
29
Page 31
y
y
g
g
play
g
(
(
y
p
g
)
g
y
g Op
g
g
p
g
g
y
g
(
(
y
g
g
)
g
y
g
g
g
p
FILE NO. SVM-05011
7-9. Self-Cleaning function.
Self-Cleaning function is designed to reduce humidity that causes mold to form inside the air conditioning unit. This advanced, efficient s fan activates and dries the moisture in the coil for 20 minutes, then turns off automaticall
stem reduces moisture in the coil. When you turn off your air conditioner, the internal
.
Operation display
FCU fan
FCU louver OPEN CLOSE CLOSE
Timer display
Compressor
CDU fan
rpm is depend on preseting. rpm is SUL speed.
depend on preseting of timer function. depend on preseting of timer function.
depend on preseting per room temperature.
depend on preseting per room temperature.
Cool mode or dry mode Self-Cleaning mode
operation more than 10 mins. operate 20 mins.
ON OFF OFF
ON ON
ON or OFF
ON or OFF
ON or OFF
Turn off by remote controller
or timer-off function.
ON
OFF OFF
OFF OFF
Automatically turn-off.
ON or OFF
The Self-Cleaning function is set as default at ex-factory.
Self-Cleaning operation can stop manually by press [ ] botton of the remote control two more time.
7-9-1. How to cancel Self-Cleanin
To cancel the Self-Cleanin
Press [TEMPORARY] button one time or use remote control to
function, proceed as follows:
function
turn on air conditioner. The OPERATION dis oran
e color (When AUTO-RESTART is ON) or green color
When AUTO-RESTART is OFF).
Hold down the [TEMPORARY] button for more than 20 seconds.
The air conditioner will stop suddenl
when the [TEMPORARY] is
ressed but keep holding it continue. Then will beep 3 times in
the first 3 seconds but it is not related to Self-Cleanin
After holdin
times without an
The Self-Cleanin
about 20 seconds, the air conditioner will beep 5
blinking of display.
eration had been concelled.
OFF
Operation time
will show in
function
Remarks
Per settin
of Self-Cleaning function above, AUTO-RESTART
function had been cancelled. To set AUTO-RESTART a
lease follow item 7-7-1.
7-9-2. How to set Self-Cleanin
To set the Self-Cleanin
Press [TEMPORARY] button one time or use remote control to
function, proceed as follows.
turn on air conditioner. The OPERATION displa
e color (When AUTO-RESTART is ON) or green color
oran
function.
will show in
When AUTO-RESTART is OFF).
Hold down the [TEMPORARY] button for more than 20 seconds.
The air conditioner will stop suddenl
pressed but keep holdin
it continue. Then will beep 3 times is
the first 3 seconds but it is not related to Self-Cleanin
After holdin
about 20 seconds, the air conditioner will beep
5 times and OPERATION displa
The Self-Cleanin
function had been set.
when the [TEMPORARY] is
function
blinks 5 times.
Remarks
Per settin
of Self-Cleaning function above, AUTO-RESTART
function had been cancelled. To set AUTO-RESTART a
lease follow item 7-7-1.
- 29-(1) -
ain,
ain,
Page 32
FILE NO. SVM-05011
7-10. QUIET Mode
Quiet mode is the system which, control the revolving speed of indoor fan to work constantly
at lower than speed L. In addition, noise level of indoor unit is less than usual.
When the [QUIET] button is pressed, the fan of the indoor unit will be restricted the revolving speed at
speed L
again (cancel Quiet mode).
Remarks :
1. Quiet mode is unable to work in dry mode.
2. Quiet mode is appropriate to work with less
-
until the [QUIET] button is pressed once
cooling load and less heating load condition. Because of the fan speed L- may cause not
enough the cooling capacity or heating capacity.
7-11. COMFORT SLEEP mode
The principles of comfort sleep mode are:
Quietness for more comfortable.
Save energy by changing room temperature
automatically.
The air condition can shut down by itself
automatically.
7-11-1. Cooling mode
The fan speed of indoor unit operates automatically,
it relates with the compressor's operation.
Compressor’s Operation Fan Speed
-
ON L
OFF SL
The preset temperature will increase 1°C after the
Comfort sleep mode has operated for 1 hour and the temperature will increase another 1°C after the comfort sleep mode has operated for 2 hour. (The value of the preset temperature on the remote control
does not change.)
Press the [COMFORT SLEEP] button to choose the
operating hours. Repeat pressing to select the hours. (1hr, 3hr, 5hr or 9hr)
If the [COMFORT SLEEP] button is pressed again
means cancel comfort sleep mode.
7-11-2. Heating mode
The fan speed of indoor unit operates automatically,
it relates with the compressor's operation.
Compressor’s Operation Fan Speed
ON L
OFF SL
-
Remarks:
1. Comfort sleep mode will not operate in dry mode
and fan only mode.
2. Comfort sleep mode is appropriate to work with less
cooling load and less heating load condition.
Because of the fan speed L- may cause not enough the cooling capacity or heating capacity.
The preset temperature will drop down 1°C after the
comfort sleep mode has operated for 1 hour and the temperature will decrease another 1°C after the comfort sleep mode has operated for 2 hour. (The
value of the preset temperature on the remote control. dose not change.)
Press the [COMFORT SLEEP] button to choose the
operating hours. Repeat pressing to select the hours. (1hr, 3hr, 5hr or 9 hr)
If the [COMFORT SLEEP] button is pressed again
means cancel comfort sleep mode.
-
30
-
Page 33

8. INSTALLATION PROCEDURE

8-1. Safety Cautions
For general public use
Power supply cord of Outdoor unit shall be more than 4 mm sheathed flexible cord) or 3.5 mm2 (AWG-12).
FILE NO. SVM-05011
2
(H07RN-F or 245 IEC66 : polychloroprene
CAUTION
THIS AIR CONDITIONER USES THE NEW HFC REFRGERANT (R410A), WHICH DOES NOT DESTROY THE OZONE LAYER.
R410A refrigerant is apt to be affected by impurity such as water, oxidizing membranes, and oils because the pressure of R410A refrigerant is approx. 1.6 times of refrigerant R22. As well as the adoption of this new refrigerant, refrigerating machine oil has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerating machine oil does not enter into the refrigerating cycle of a new-refrigerant air conditioner. To avoid mixing refrigerant and refrigerating machine oil, the sizes of charging port connecting sections on the main unit are different from those for the conventional refrigerant, and different size tools are also required. Accordingly, special tools are required for the new refrigerant (R410A) as shown below. For connecting pipes, use new and clean piping materials with high-pressure withstand capabilities, designed for R410A only, and ensure that water or dust does not enter. Moreover, do not use any existing piping as its pressure withstand may be insufficient, and may contain impurities.
CAUTION
This appliance must be connected to the main power supply by means of a circuit breaker or a switch with a contact separation of at least 3 mm. If this is not possible, a power supply plug with earth must be used. This plug must be easily accessible after installation. The pl appliance completely from the mains.
New Refrigerant Air conditioner Installation
To Disconnect the Appliance from the Main Power Supply.
ug must be disconnected from the power supply socket in order to disconnect the
31
Page 34
FILE NO. SVM-05011
DANGER
FOR USE BY QUALIFIED PERSONS ONLY.
TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE
ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED WRONGLY, ELECTRIC PARTS MAY BE DAMAGED.
CHECK THE EARTH WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION.
DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS.
FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD, PLACE THE UNIT WELL AWAY (MORE THAN 2 M) FROM HEAT SOURCES SUCH AS RADIATORS, HEATORS, FURNACE, STOVES, ETC.
WHEN MOVING THE AIR-CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN, BE VERY CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT (R410A) WITH ANY OTHER GASEOUS BODY INTO THE REFRIGERATION CYCLE. IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT, THE GAS PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNORMALLY HIGH AND IT RESULTINGLY CAUSES BURST OF THE PIPE AND INJURIES ON PERSONS.
IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE INSTALLATION WORK, IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE REFRIGERANT GAS IS HEATED BY FIRE OR SOMETHING ELSE, IT CAUSES GENERATION OF POISONOUS GAS.
WARNING
Never modify this unit by removing any of the safety guards or bypassing any of the safety interlock switches.
Do not install in a place which cannot bear the weight of the unit. Personal injury and property damage can result if the unit falls.
Before doing the electrical work, attach an approved plug to the power supply cord. Also, make sure the equipment is properly earthed.
Appliance shall be installed in accordance with national wiring regulations. If you detect any damage, do not install the unit. Contact your TOSHIBA dealer immediately.
CAUTION
Exposure of unit to water or other moisture before installation could result in electric shock. Do not store it in a wet basement or expose to rain or water.
After unpacking the unit, examine it carefully for possible damage.
Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify
the noise level of the unit or where noise and discharged air might disturb neighbors.
To avoid personal injury, be careful when handling parts with sharp edges.
Please read this installation manual carefully before installing the unit. It contains further important instruc-
tions for proper installation.
REQUIREMENT OF REPORT TO THE LOCAL POWER SUPPLIER
Please make absolutely sure that the installation of this appliance is reported to the local power supplier before installation. If you experience any problems, or if the installation is not accepted by the supplier, the service agency will take adequate countermeasures.
Remark per EMC Directive 89/336/EEC
To prevent flicker impressions during the start of the compressor (technical process) following installation conditions do apply.
1. The power connection for the air conditioner has to be done at the main power distribution. This distribution has to be of an impedance. Normally the required impedance is reached at a 32A fusing point. Air conditioner fuse has to be 16A max.!
2. No other equipment should be connected to this power line.
3. For detailed installation acceptance, please contact your power supplier whether its restriction does apply for products like washing machines, air conditioners or electrical ovens.
4. For power details of the air conditioner, refer to the rating plate of the product.
– 32
Page 35
FILE NO. SVM-05011
8-2. Installation Diagram of Indoor and Outdoor Units
Hook
65 mm or more
(Atta
c
h to th
e f
r
on
t panel) (A
6 Bio enzyme & Gingko filter
5 Sasa Zeolite plus filter
170 mm
or more
ttac
h to
the air filter)
1 Installation
plate
170 mm
or more
Shield
pipe
For the rear left and left piping
Wall
Insert the cushion between the indoor unit and wall, and lift the indoor unit for better operation.
Do not allow the drain hose to get slack.
Cut the piping hole sloped slightly
Make sure to run the drain hose sloped downward.
Before installing the wireless remote control
With the remote control cover open, load the batteries supplied correctly, observing their polarity.
2 Wireless remote control
Cover
3 Batteries
m
0
0
1
m
r
o
1
0
0
m
m
o
r m
o
re
m
r
o
m
m
0
60
r
o
600 mm or more
e
m
r
o
e
2 Wireless remote control
Extension drain hose (Not available, provided by installer)
Electric parts cover
6
0
0
m
o
m
r m
o
re
6
o
8 Pan head wood screw
4 Remote control holder
Vinyl tape Apply after carrying out a drainage test.
1
0
0
m
m
o
r m
o
re
re
o
m
r
o
r m
0
0
m
o
m
m
0
m
0
6
re
ore
100 mm
or m
600 mm or more
Saddle
Extension drain hose (Not available, provided by installer)
Electric parts cover
6
0
0
m
o
m
r m
o
re
The auxiliary piping can be connected the left, rear left, rear, right or bottom.
Right
Rear
Bottom
Rear left
Left
Insulate the refrigerant
pipes separately with insulation, not together.
6 mm thick heat resisting polyethylene foam
18 Class Heat pump 24 Class
Loop the connecting cable (about 100 mm in diameter and 300 - 350 mm long).
18 Class Cooling
Loop the connecting cable (about 100 mm in diameter and 300 - 350 mm long).
33
Page 36
8-3. Installation
8-3-1. Optional installation parts
FILE NO. SVM-05011
Part
Code
Parts name
Refrigerant piping Liquid side : ∅6.35 mm
A
Gas side : ∅12.7 mm Pipe insulating material
B
(polyethylene foam, 6 mm thick)
C
Putty, PVC tapes
<Fixing bolt arrangement of outdoor unit> RAS-24UA-ES4,RAS-24UAH-ES4
600 mm
Air inlet
120 mm
64 mm
340 mm
Q'ty
One
each
1
One
each
Air outlet
Drain outlet
Fig. 8-3-1
RAS-18UAH-ES4 RAS-18UA-ES4
600 mm
Air inlet
125 mm115 mm
Air inlet
102 mm
90 mm
Drain outlet
325 mm
52 mm
Air outlet
Air outlet
120 mm
310 mm
32.5 mm
7 mm
73 mm
Air outlet
30
600 mm
Fig. 8-3-2 Fig. 8-3-3
Secure the outdoor unit with fixing bolts and nuts if the unit is likely to be exposed to a strong wind.
Use ∅8 mm or ∅10 mm anchor bolts and nuts.
If it is necessary to drain the defrost water, attach drain nipple Š to the bottom plate of the outdoor unit
before installing it.
– 34
Page 37
8-3-2. Accessory and installation parts
FILE NO. SVM-05011
Part
No.
Part name (Q'ty)
1
Installation plate x 1
2
Wireless remote control x 1
3
Battery x 2
Others
Owner’s manual
Installation manual
Name
Part
No.
Part name (Q'ty)
4
Remote control holder x 1
5
Sasa Zeolite plus filter x 2
6
Bio enzyme & Gingko filter x 2
Part
No.
Part name (Q'ty)
7
Mounting screw 4 x 25 x 8
l
8
Pan head wood screw 3.1 x 16 x 2
l
9
Drain nipple* x 1
The part marked with asterisk (*) is packaged with the outdoor unit.
(For Heat pump model only)
35
Page 38
FILE NO. SVM-05011
8-3-3. Installation/Servicing tools
<Changes in the product and components>
In the case of an air conditioner using R410A, in order to prevent any other refrigerant from being charged accidentally, the service port diameter of the outdoor unit control valve (3 way valve) has been changed. (1/2 UNF 20 threads per inch)
In order to increase the pressure withstand strength of the refrigerant piping, flare processing diameter and size of opposite side of flare nuts have been changed. (for copper pipes with nominal dimensions 1/2 and 5/8)
New tools for R410A
New tools for R410A Applicable to R22 model Changes
Gauge manifold As pressure is high, it is impossible to measure by
means of conventional gauge. In order to prevent any other refrigerant from being charged, each port diameter has been changed.
Charge hose In order to increase pressure withstand strength,
hose materials and port size have been changed (to 1/2 UNF 20 threads per inch). When purchasing a charge hose, be sure to confirm the port size.
Electronic balance As pressure is high and gasification speed is fast, for refrigerant charging it is difficult to read the indicated value by means
of a charging cylinder, as air bubbles occur.
Torque wrench The size of opposing side of flare nuts have been (nominal dia. 1/2, 5/8) increased.
Incidentally, a common wrench is used for nominal diameters 1/4 and 3/8.
Flare tool By increasing the clamp bar’s receiving hole, (clutch type) strength of spring in the tool has been improved.
Gauge for projection Used when flare is made by using conventional flare adjustment tool.
Vacuum pump adapter Connected to conventional vacuum pump. It is
Gas leakage detector Exclusive for HFC refrigerant.
necessary to use an adapter to prevent vacuum pump oil from flowing back to the charge hose. The charge hose connecting part has two ports­one for conventional refrigerant (7/16 UNF 20 threads per inch) and one for R410A. If the vacuum pump oil (mineral) mixes with R410A, a sludge may occur and damage the equipment.
Incidentally, the “refrigerant cylinder” comes with the refrigerant designation (R410A) and protector coating in the U. S’s ARI specified rose color (ARI color code: PMS 507).
Also, the “charge port and packing for refrigerant cylinder” require 1/2 UNF 20 threads per inch corresponding to the charge hose’s port size.
– 36
Page 39
FILE NO. SVM-05011
8-4. Indoor Unit
8-4-1. Installation place
A place which provides the spaces around the indoor unit as shown in the above diagram.
A place where there is no obstacle near the air inlet and outlet.
A place that allows easy installation of the piping to the outdoor unit.
A place which allows the front panel to be opened.
CAUTION
Direct sunlight to the indoor unit’s wireless
receiver should be avoided.
The microprocessor in the indoor unit should not
be too close to RF noise sources. (For details, see the owner’s manual.)
<Remote control>
A place where there are no obstacles such as a curtain that may block the signal from the indoor unit.
Do not install the remote control in a place exposed to direct sunlight or close to a heating source, such as a stove.
Keep the remote control at least 1 m apart from the nearest TV set or stereo equipment. (This is necessary to prevent image disturbances or noise interference.)
The location of the remote control should be determined as shown below.
Remote
control
(Top view)
Indoor unit
Reception range
* : Axial distance
5 m
5 m
45
°
45
°
Remote control
ndoor unit
I
(Side view)
7 m
°
5
7
Reception range
8-4-2. Cutting a hole and mounting installation
plate
<Cutting a hole>
When installing the refrigerant pipes from the rear.
Pipe hole
65 mm
The center of the pipe hole is above the arrow.
100 mm
Fig. 8-4-2
1. After determining the pipe hole position on the mounting plate (A), drill the pipe hole (65 mm) at a slight downward slant to the outdoor side.
NOTE
When drilling a wall that contains a metal lath, wire lath or metal plate, be sure to use a pipe hole brim ring sold separately.
<Mounting the installation plate>
For installation of the indoor unit, use the paper pattern on the back.
55
Hook
* 7 m
170
120
65
Fig. 8-4-1
37
Pipe hole
Indoor unit
Hook
Thread
Weight
Fig. 8-4-3
Hook
Pipe hole
7 Mounting screw
Installation plate
1
Page 40
FILE NO. SVM-05011
<When the installation plate is directly mounted on the wall>
1. Securely fit the installation plate onto the wall by screwing it in the upper and lower parts to hook up the indoor unit.
2. To mount the installation plate on a concrete wall with anchor bolts, utilize the anchor bolt holes as illustrated in the above figure.
3. Install the installation plate horizontally in the wall.
CAUTION
When installing the installation plate with a mounting screw, do not use the anchor bolt hole. Otherwise the unit may fall down and result in personal injury and property damage.
Installation plate <Keep horizontal direction>
Anchor bolt
Projection
5 mm dia. hole
15 mm or less
8-4-3. Electrical work
1. The supply voltage must be the same as the rated voltage of the air conditioner.
2. Prepare the power source for exclusive use with the air conditioner.
NOTE
2
Wire type : More than 1.5 mm
(H07RN-F or
245 IEC66) or 1.3 mm2 (AWG-16)
CAUTION
This appliance can be connected to the mains in the following way. Connection to fixed wiring: A switch or circuit breaker which disconnects all poles and has a contact separation of at least 3 mm must be incorporate in the fixed wiring. An approved circuit breaker or switches must used.
NOTE
Perform wiring works so as to allow a generous wiring capacity.
7 Mounting
screw
ss
4 x 25
s
ss
Clip anchor (local parts)
Fig. 8-4-4
CAUTION
Failure to firmly install the unit may result in personal injury and property damage if the unit falls.
In case of block, brick, concrete or similar type walls, make 5 mm dia. holes in the wall.
Insert clip anchors for appropriate mounting screws
7 .
NOTE
Secure four corners and lower parts of the installation plate with 6 to 7 mounting screws to install it.
– 38
Page 41
FILE NO. SVM-05011
8-4-4. Wiring connection
Air Inlet grille
2
1
Cord clamp
Screw
Terminal cover
Screw
Terminal block
Front panel
Earth line
CAUTION
Be sure to refer to the wiring system diagram labeled inside the front panel.
Check local electrical cords and also any specific wiring instructions or limitations.
Connecting cable
about 15 cm
Fig. 8-4-6
<Stripping length of connecting cable>
10
10
40
50
Connecting cable
Fig. 8-4-5
<How to connect the connecting cable>
Wiring of the connecting cable can be carried out without removing of the front panel.
1. Remove the air inlet grille. Open the air inlet grille upward and pull it toward you.
2. Remove the terminal cover and cord clamp.
3. Insert the connecting cable (according to local cords) into pipe hole on the wall.
4. Take out the connecting cable through the cable slot on the rear panel so that it protrudes about 15 cm from the front.
5. Insert the connecting cable fully into the terminal block and secure it tightly with screws.
6. Tightening torque : 1.2 N·m (0.12 kgf·m).
7. Secure the connecting cable with the cord clamp.
8. Fix the terminal cover, rear plate bushing and air inlet grille on the indoor unit.
Earth line
Fig. 8-4-7
NOTE
Use stranded wire only.
Wire type : More than 1.5 mm 2 (H07RN-F or 245 IEC66) or 1.3 mm2 (AWG-16)
Fig. 8-4-8
NOTE
Connect the earth line to the metallic part (i mark) located at the side of 3P terminal.
<How to install the air inlet grille on the indoor unit>
When attaching the air inlet grille, the contrary of
the removed operation is performed.
Fig. 8-4-9
39
Page 42
FILE NO. SVM-05011
8-4-5. Piping and Drain Hose Installation <In case of rightward piping>
After scribing slits of the body-right by a knife or a making-off pin, cut them by a pair of nippers or the like.
Slit (Body-right)
Fig. 8-4-10
<In case of downward piping>
After scribing slits of the body-right by a knife or a making-off pin, cut them by a pair of nippers or the like.
To connect the pipe after installation of the unit (figure)
(To the forefront of flare)
400 mm
300 mm
R 30 mm (Use polisin (polyethylene) core or the like for bending pipe.)
43 mm
80
Liquid side
Gas side
Outward form of indoor unit
Use the handle of screwdriver, etc.
Fig. 8-4-12
NOTE
If the pipe is bent incorrectly, the indoor unit may unstably be set on the wall. After passing the connecting pipe through the pipe hole, connect the connecting pipe to the auxiliary pipes and wrap the facing tape around them.
Slit (Body-right)
Fig. 8-4-11
<Left-hand connection with piping>
Bend the connecting pipe so that it is laid within 43 mm above the wall surface. If the connecting pipe is laid exceeding 43 mm above the wall surface, the indoor unit may unstably be set on the wall. When bending the connecting pipe, make sure to use a spring bender so as not to crush the pipe.
Bend the connection pipe within a radius of 30 mm.
CAUTION
Bind the auxiliary pipes (two) and connecting cable with facing tape tightly. In case of leftward piping and rear-leftward piping, bind the auxiliary pipes (two) only with facing tape.
Indoor unit
Auxiliary pipes
Installation plate
Carefully arrange pipes so that any pipe does not stick out of the rear plate of the indoor unit.
Carefully connect the auxiliary pipes and connecting pipes to each other and cut off the insulating tape wound on the connecting pipe to avoid double-taping at the joint, moreover, seal the joint with the vinyl tape, etc.
Since dewing results in a machine trouble, make sure to insulate both the connecting pipes. (Use polyethylene foam as insulating material.)
When bending a pipe, carefully do it not to crush
it.
Connecting cable
Drain hose
40
Page 43
FILE NO. SVM-05011
8-4-6. Indoor unit fixing
1. Pass the pipe through the hole in the wall, and hook the indoor unit on the installation plate at the upper hooks.
2. Swing the indoor unit to right and left to confirm that it is firmly hooked up on the installation plate.
3. While pressing the indoor unit onto the wall, hook it at the lower part on the installation plate. Pull the indoor unit toward you to confirm that it is firmly hooked up on the installation plate.
1
2
Hook
Hook here
1 Installation
plate
Press
(unhook)
Fig. 8-4-13
For detaching the indoor unit from the installation
plate, pull the indoor unit toward you while pushing
its bottom up at the specified parts.
8-4-7. Drainage
1. Run the drain hose sloped downwards.
NOTE
Hole should be made at a slight downward slant on the outdoor side.
Do not form the Do not rise the drain hose.
50 mm or more
Do not put the drain hose end into water.
drain hose into
a wavy shape.
Do not put the drain hose end in the drainage ditch.
Fig. 8-4-15
2. Put water in the drain pan and make sure that the water is drained out of doors.
3. When connecting extension drain hose, insulate the connecting part of extension drain hose with shield pipe.
Fig. 8-4-14
Shield pipe
Drain hose
PushPush
Inside the room
Fig. 8-4-16
Extension drain hose
CAUTION
Arrange the drain pipe for proper drainage from the unit. Improper drainage can result in dew-dropping.
This air conditioner has the structure designed to drain water collected from dew, which forms on the back of the indoor unit, to the drain pan. Therefore, do not store the power cord and other parts at a height above the drain guide.
Wall
Drain guide
Space for pipes
41
Fig. 8-4-17
Page 44
FILE NO. SVM-05011
8-5. Outdoor Unit
8-5-1. Installation place
A place which provides the spaces around the
outdoor unit as shown in the left diagram.
A place which can bear the weight of the outdoor unit and does not allow an increase in noise level and vibration.
A place where the operation noise and discharged air do not disturb your neighbors.
A place which is not exposed to a strong wind.
A place free of a leakage of combustible gases.
A place which does not block a passage.
When the outdoor unit is to be installed in an
elevated position, be sure to secure its feet.
An allowable length of the connecting pipe is up 15 m. (Refer to the table of TO CHARGE REFRIGERANT for detail.)
An allowable height level is up to 8 m.
A place where the drain water does not raise any
problem.
CAUTION
1. Install the outdoor unit without anything blocking the air discharging.
2. When the outdoor unit is installed in a place exposed always exposed to strong wind like a coast or on a high storey of a building, secure the normal fan operation using a duct or a wind shield.
3. In particularly windy areas, install the unit such as to avoid admission of wind.
4. Installation in the following places may result in trouble. Do not install the unit in such places.
A place full of machine oil.
A saline-place such as the coast.
A place full of sulfide gas.
A place where high-frequency waves are likely
to be generated as from audio equipment, welders, and medical equipment.
8-5-2. Refrigerant piping connection
1. Cut the pipe with a pipe cutter.
90°
Obliquity
Roughness Warp
Fig. 8-5-2
2. Insert a flare nut into the pipe, and flare the pipe.
Projection margin in flaring : A (Unit : mm)
A
Die
Pipe
Fig. 8-5-3
Rigid (Clutch type)
Outer dia. R410A Conventional
of copper pipe tool used tool used
6.35 0 to 0.5 1.0 to 1.5
9.52 0 to 0.5 1.0 to 1.5
12.70 0 to 0.5 1.0 to 1.5
Imperial (wing nut type, conventional tool)
Outer dia.
of copper pipe
R410A
6.35 1.5 to 2.0
9.52 1.5 to 2.0
12.70 2.0 to 2.5
<Tightening connection>
Align the centers of the connecting pipes and tighten the flare nut as far as possible with your fingers. Then tighten the nut with a spanner and torque wrench as shown in the figure.
Strong
wind
Fig. 8-5-1
CAUTION
Do not apply excess torque.
Otherwise, the nut may crack depending on the
conditions.
– 42
Page 45
FILE NO. SVM-05011
(Unit : N·m)
Outer dia.
of copper pipe
Tightening torque
6.35 mm 16 to 18 (1.6 to 1.8 kgf·m)9.52 mm 30 to 42 (3.0 to 4.2 kgf·m)
12.70 mm 50 to 62 (5.0 to 6.2 kgf·m)
Tightening torque of flare pipe connections
The operating pressure of R410A is higher than that of R22. (Approx. 1.6 times). It is therefore necessary to firmly tighten the flare pipe connecting sections (which connect the indoor and outdoor units) up to the specified tightening torque. Incorrect connections may cause not only a gas leakage, but also damage to the refrigerant cycle.
Flare at indoor unit side
Flare at outdoor unit side
Fig. 8-5-4
Flare nutHalf union
Externally threaded side
Use a wrench to secure.
Use a torque wrench to tighten.
Internally threaded side
Fig. 8-5-5
8-5-3. Evacuating
After the piping has been connected to the indoor unit, you can perform the air purge together at once.
AIR PURGE
Evacuate the air in the connecting pipes and in the indoor unit using a vacuum pump. Do not use the refrigerant in the outdoor unit. For details, see the manual of the vacuum pump.
<Using a vacuum pump>
Be sure to use a vacuum pump with counter-flow prevention function so that inside oil of the pump does not flow backward into pipes of the air conditioner when the pump stops. (If oil inside of the vacuum pump enters into the air conditioner, which use R410A, refrigeration cycle trouble may result.)
1. Connect the charge hose from the manifold valve to the service port of the gas side packed valve.
2. Connect the charge hose to the port of the vacuum pump.
3. Open fully the low pressure side handle of the gauge manifold valve.
4. Operate the vacuum pump to start evacuating. Perform evacuating for about 15 minutes if the piping length is 20 meters. (15 minutes for 20 meters) (assuming a pump capacity of 27 liters per minute. Then confirm that the compound pressure gauge reading is –101 kPa (–76 cmHg).
5. Close the low pressure side valve handle of gauge manifold.
6. Open fully the valve stem of the packed valves (both side of Gas and Liquid).
7. Remove the charging hose from the service port.
8. Securely tighten the caps on the packed valves.
CAUTION
KEEP IMPORTANT 4 POINTS FOR PIPING WORK
(1) Take away dust and moisture (Inside of the
connecting pipes.) (2) Tight connection (between pipes and unit) (3) Evacuate the air in the connecting pipes using
VACUUM PUMP. (4) Check gas leak (connected points)
– 43
Compound pressure gauge
-101kPa (-76cmHg)
Handle Lo
Charge hose
(For R410A only)
Connecting pipe
Packed valve at liquid side
Fig. 8-5-6
Pressure gauge
Manifold valve
Handle Hi (Keep full closed)
Charge hose (For R410A only)
Vacuum pump adapter for counter-flow prevention (For R410A only)
Vacuum
pump
Packed valve at gas side
Service port (Valve core (Setting pin))
Page 46
FILE NO. SVM-05011
70
60
L
N
10
70
10
10
80
10
123
TO CHARGE REFRIGERANT
Refrigerant
No need to charge refrigerant
Need to charge Over 15 m up to Over 15 m up to refrigerant 25 m (20g/m) 20 m (20g/m)
24 Class
15 m or less 15 m or less
18 Class
<Packed valve handling precautions>
Open the valve stem all the way out; but do not try to open it beyond the stopper.
Securely tighten the valve stem cap with torque in the following table:
Gas side 50 to 62 N·m (∅12.70 mm) (5.0 to 6.2 kgf·m)
Gas side 30 to 42 N·m (∅9.52 mm) (3.0 to 4.2 kgf·m)
Liquid side 16 to 18 N·m (∅6.35 mm) (1.6 to 1.8 kgf·m)
Service port
9 to 10 N·m (0.9 to 1.0 kgf·m)
Hexagonal wrench is required.
8-5-4. Wiring connection
1. Remove the valve cover from the outdoor unit.
2. Connect the connecting cable to the terminal as identified with their respective matched numbers on the terminal block of indoor and outdoor unit.
3. When connecting the connecting cable to the outdoor unit terminal, make a loop as shown in the
installation diagram of indoor and outdoor unit, to
prevent water coming in the outdoor unit.
4. Insulate the unused cords (conductors) from any water coming in the outdoor unit. Proceed them so that they do not touch any electrical or metal parts.
<Stripping length of connecting cable>
Terminal block
LN 1 32
Terminal screw
Cord clamp
Power supply cord
Earth line
Screw
Cord clamp
Connecting cable
4 mm
Fig. 8-5-7
Power supply cord
Earth line
Connecting cable
Fig. 8-5-8
Model
Power source 50 Hz, 220 240 V Single phase Maximum running current 18A 16A Plug socket & fuse rating
Power cord
24 Class
20A 20A
2
(H07R N-F or 245 IE C 66)
4 mm or 3.5 mm2 (AWG -12)
18 Class
CAUTION
Wrong wiring connection may cause some electrical parts burn out.
Be sure to comply with local codes on running the wire from indoor unit to outdoor unit (size of wire and wiring method etc).
Every wire must be connected firmly.
NOTE: Connecting cable
Wire type: More than 1.5 mm 245 IEC66) or 1.3 mm
– 44
2
(H07RN-F or
2 (AWG-16)
Page 47
FILE NO. SVM-05011
8-6. How to Set Remote Control Selector
Switch
When two indoor units as installed in seperated rooms, there is no need to change the selector switch.
<Remote control selector switch>
When two indoor units are installed in the same room or the adjacent two rooms, they may be controlled simultaneously with a single remote control. To prevent this, set either unit and its remote control to B setting. (Both units are set to A setting before shipment.)
The remote control signal is not recived when the indoor unit setting is different from the remote control one.
1. Set the remote control selectors witch with the indoor unit.
1) Turn the circuit breaker of the main power switch off before setting the selector switch.
2) Remove the Air inlet grille and Front panel. (Refer to Chapter 10-1, procedure 1 )
3) Open the Electrical part cover (Refer to chapter 10-1, procedure 2 ), then cut the jumper (J90) with only the nippers.
2. Set the remote control selector switch with the remote control
[B] is indicated on the liquid crystal display when setting remote control selector switch to B. [A] is not indicated on the display even if the selector switch is set to A.
1) Load the remote control with the batteries.
2) Press the [CHECK] button using something with sharp point. (The preset temperature on the remote control changes to [00].)
3) Press the [MODE] button while pressing the [CHECK] button, [B] is indicted at the right of the present temperature display.
To reset the switch to the [A] setting, press the [MODE] button again while pressing the [CHECK] button.
CAUTION
Do not use any other sharp tools (such as cutters, pliers, or the like). Such tools
may cause breakage or damage.
See Fig. 8-6-1
Fig. 8-6-1
[MODE] button
[CHK] button
Fig. 8-6-2
3. Confirm that the indoor unit can operate with the new setting.
45
Page 48
FILE NO. SVM-05011
8-7. Others
8-7-1. Gas leak test
Electric parts cover
D
Flare nut connections (Outdoor unit)
B
Valve stem cap connection
Fig. 8-7-1
Check the flare nut connections, valve stem cap connections and service port cap connections for gas leak with a leak detector or soap water.
8-7-2. Test operation
C
Flare nut connections (Indoor unit)
Valve stem cap
connection
A
Service cap connection
8-7-3. Auto restart setting
This product is designed so that, after a power failure, it can restart automatically in the same operating mode as before the power failure.
Information
The product was shipped with Auto Restart function in the off position. Turn it on as required.
<How to set the auto restart>
Press and hold the TEMPORARY button for about 3 seconds. After 3 seconds, the electronic beeper makes three short beeps to tell you the Auto Restart has been selected.
To cancel the Auto Restart, follow the steps described in the section Auto Restart Function of the Owner’s Manual.
To switch the TEST RUN (COOL) mode, press TEMPORARY button for 10 sec. (The beeper will make a shaort beep.)
TEMPORARY button
Fig. 8-7-2
46
Page 49

9. TROUBLESHOOTING CHART

FILE NO. SVM-05011
9-1. Tr oub leshooting Pr ocedure :
9-2-2. Incorrect cable connection between Indoor
and outdoor units
Follow the details of 9-2. Basic Check Items. If there is no trouble corresponding to 9-2, check whether or not there are faulty parts following
9-4. Self-Diagnosis by Remote Control.
9-2. Basic Check Items
The indoor unit is connected to the outdoor unit with 4 cables. Check that the indoor and outdoor units have been properly connected with terminals assigned the same numbers. If the connectors are not properly connected, the outdoor unit will not operate normally, or OPERATION lamp and TIMER lamp will blink (5 Hz).
9-2-1. Power supply voltage
The line voltage must be AC 220 – 240 V. If it is not within this range, the air conditioner may not operate normally.
9-2-3. Program control
The microcontroller operates as shown in Table 9-2-1 to control the air conditioner. If there are any opera­tional problems, check whether or not the problems correspond to Table 9-2-1. If they correspond to the Table, they are not problems with the air conditioner, but they are indispensable operations to control and maintain the air conditioner properly.
Table 9-2-1
No. Operation of air conditioner Descriptions
1 When the main power supply is turned
on, the OPERATION lamp on the indoor unit blinks.
2 The indoor fan motor speed does not
change in the Dry operation.
3 The compressor is not turned off even
though the room temperature is in the range that the compressor is turned off.
4 The compressor is not turned on and
off even though the thermo control is operated in the Dry operation.
*5 The PRE-DEF. lamp is indicated when
the Heating operation starts.
The OPERATION lamp blinks to indicate that power is turned on. If the [ ] button is pressed, the lamp stops blinking.
The indoor fan motor speed is automatically controlled in the Dry operation.
The compressor has a function that it is not turned off for 3 minutes after it is turned on even though the room temperature is in the range that the compressor is turned off.
In the Dry operation, the compressor is turned on and off automatically at the regular intervals, independent of the thermo control.
The PRE-DEF. lamp is indicated during the Defrosting operation or if the indoor heat exchanger temperature is low when the Heating operation starts. At this time, the indoor fan motor stops to prevent cold air from blowing in the room.
*6 The outdoor fan motor stops in the
Heating operation.
7 The compressor is not turned on even
though the room temperature is in the range that the compressor is turned on.
8 The operation mode changes in the
Automatic operation.
9 The Fan only operation continues in the
Automatic operation.
10 The ECO operation or Hi-POWER
operation does not work.
11 When [Hi POWER] button is pressed,
the display on the remote control does not change at all.
Note *5 and *6 are for Heat pump model :
When the indoor heat exchanger temperature is high, the outdoor fan motor is stopped by the high-temperature limit control operation.
The compressor is not turned on in the restart delay timer (3-minutes timer) operation. It is also not turned on after the power supply is turned on because of this timer operation.
In Automatic operation, the room temperature is detected all time for control fan speed and the operation mode is changed every 15 minutes according to difference between the room temperature and the preset temperature.
When the room temperature is in the range (Preset temperature ± 1°C), the Fan only operation is selected.
These operations do not work when the unit is in the Dry operation or Fan only operation.
The display on the remote control does not change when [Hi POWER] button is pressed. However the microcontroller gives commands to change the preset temperature and air flow level.
47
Page 50
FILE NO. SVM-05011
9-3. Primary Judgement
9-3-1. Role of indoor unit controller
The indoor unit controller receives the operation commands from the remote control and executes them.  Temperature measurement at the air outlet of the
·
indoor heat exchanger by the indoor temperature sensor
 Temperature setting of the indoor heat exchanger by
·
the heat exchanger sensor
 Louver motor control
·
 Indoor fan motor operation control
·
 LED display control
·
 Transferring of operation commands to the outdoor
·
unit
Table 9-3-1
Lamps Self-diagnosis
A OPERATION lamp is blinking. (1Hz) B OPERATION lamp is blinking. (5Hz) C OPERATION lamp is blinking. (5Hz) D OPERATION lamp is blinking. (5Hz) E OPERATION lamp is blinking. (5Hz) F OPERATION and TIMER lamps are blinking.
(5Hz)
9-3-2. Failure diagnosis
The indoor unit diagnoses the operation condition and indicates the information of the self-diagnosis with the lamps on the display panel of the indoor unit.
Power failure (when the power supply is turning on) Thermo sensor (TA) short or break Heat exchanger sensor (TC) short or break Indoor fan motor lock or failure Indoor P.C. board failure Wrong wiring of connecting cable
G OPERATION, TIMER and PRE-DEF.
(or FAN ONLY for cooling only model) lamps are blinking.
Table 9-3-2 Diagnosis by detective operation
Symptom Check Primary judgement
The remote control does not work.
The outdoor fan does not rotate.
Turn off the power supply once, then turn it on. Try to operate the remote control.
The compressor operates.
The compressor does not operate.
Cycle failure  Gas shortage or other refrigerant cycle trouble
·
 Heat exchanger sensor open, break or short
·
·
 Overload relay or thermostat trouble of compressor
The remote control still does not work.
The remote control works.
The indoor unit (and/or remote control) is/are defective.
OK.
The outdoor unit (Outdoor fan motor) is defective.
An internal part of the compressor or P.C. board is defective.
- 48 -
Page 51
9-4. Self-Diagnosis by Remote Control
(Check Code)
(1) If the lamps are indicated as shown B to G in Table
9-3-1, exchanger the self-diagnosis by the remote control.
(2) When the remote control is set to the service
mode, the indoor controller diagnoses the operation condition and indicate the information of the self-diagnosis on the display of the remote control with the check codes. If a fault is detected, all lamps on the indoor unit will blink at 5Hz and it
will beep for 10 seconds (Pi, Pi, Pi....). The timer
lamp usually blinks (5Hz) during the self-diagnosis.
9-4-1. How to use remote control in service mode
FILE NO. SVM-05011
(1) Press [CHK] button with a tip of pencil to set the
remote control to the service mode.
“00” is indicated on the display of the remote control.
The timer lamp on the indoor unit blinks continuously. (5 times per 1 sec.)
(2) Press [TIMER 8] button.
If there is no fault with a code, the indoor unit will beep once (Pi) and the display of the remote control will change as follows:
00
01
Check the unit with all 35 check codes (00 to 22). as shown in Table 9-4-1.
Press [TIMER 9] button to change the check code backwards.
If there is a fault, the indoor unit will beep for 10 seconds (Pi, Pi, Pi...). Note the check code on the display of the remote control.
2-digits alphanumeric will be indicated on the display.
All lamps on the indoor unit will blink. (5 times per 1 sec.)
(3) Press [CLR] button. After service finish for clear
service code in memory.
“7F” is indicated on the display of the remote control.
1d
02
1E
22
Alphanumeric characters are used for the check code.
is 5. is 6. is A. is B. is C. is D.
* This illustration in only for Heat pump model.
For Cooling only model, there is not the ( ) symbol.
(4) Press [ ] button to release the service
mode.
The display of the remote control returns to as it was before service mode was engaged.
49
Page 52
Table 9-4-1
Block level Diagnosis function
Check
code code status
Block
Indoor P.C. board
Cable connection
Outdoor P.C. board
Other parts (including compressor)
Check
Symptom
The indoor thermo sensor (TA) is defective. Disconnection or short-circuit
The indoor heat exchanger sensor (TC) is defective. Disconnection or short-circuit
The indoor fan motor or its circuit is defective.
The part other than the above parts on the indoor P.C. board is defective. EEPROM access error
IOL operation
The serial signals can not be transmitted and received between indoor and outdoor units.
The crossover wire is connected wrongly.
The serial signal transmitting circuit on the outdoor P.C. board is defective.
The serial signal receiving circuit on the indoor P.C. board is defective.
The operation command signals are not transmitted from the indoor unit to the outdoor unit.
The outdoor thermo sensor (TE) is defective. Disconnection or short-circuit
The outdoor heat exchanger (TD) sensor is defective. Disconnection or short-circuit
The reply serial signal has been transmitted when starting the unit, but stops being transmitted shortly after.
1. Compressor thermo operation
Gas shortage
Gas leak
2. Instantaneous power failure
The discharge temperature is over 120°C.
The IOL operation is defective.
Unit
Operation continues.
Operation continues.
All off
Operation continues.
All off
Operation continues.
Operation continues.
All off
All off
Operation continues.
All off
All off
Condition
The lamp on the indoor unit blinks when error is defected.
The lamp on the indoor unit blinks when error is defected.
The lamp on the indoor unit blinks when error is defected.
The lamp on the indoor unit blinks when error is defected.
The lamp on the indoor unit blinks when error is
.
defected The lamp on the
indoor unit blinks when error is defected.
The lamp on the indoor unit blinks when error is defected. And it returns to the normal condition when recovering from errors.
The lamp on the indoor unit blinks when error is defected.
The lamp on the indoor unit blinks when error is defected.
The lamp on the indoor unit blinks when error is defected. And it returns to the normal condition when recovering from errors.
The lamp on the indoor unit blinks when error is defected.
The lamp on the indoor unit blinks when error is detected.
FILE NO. SVM-05011
Judgement and action
1. Check the indoor thermo sensor (TA).
2. Check the indoor P.C. board.
1. Check the indoor heat exchanger sensor (TC).
2. Check the indoor P.C. board.
1. Check the connector circuit of the indoor fan motor (CN10).
2. Check the indoor fan motor.
3. Check the indoor P.C. board.
1. Check the indoor P.C. board. (EEPROM and peripheral circuits)
Overload operation of refrigerating cycle
1. In the case of the outdoor unit not operating at all;
Check the crossover cable and
connect it properly.
Check the outdoor P.C. board.
2. In the case of the outdoor unit operating normally;
Check whether or not both of serial
LED (Green) and serial LED (Orange) is blinking. If the serial LED (Green) is not blinking, check the outdoor P.C. board. If the serial LED (Orange) is not blinking, check the indoor P.C. board.
If the operation command signals continue to be transmitted between 2 and 3 of the indoor terminal block, replace the outdoor P.C. board.
1. Check the outdoor thermo sensor (TE).
2. Check the outdoor P.C. board.
1. Check the outdoor heat exchanger sensor (TD).
2. Check the outdoor P.C. board.
1. Repeatedly turn the indoor unit on and off with the interval of approx. 10 to 40 minutes. (The check code is not indicated during operation.) And supply gas. (Check gas leak.)
2. The indoor unit operates normally during the check. If the reply serial signal continues to be transmitted between 2 and 3 of the indoor terminal block, replace the outdoor P.C. board. If the signal stops between them, replace the indoor P.C. board.
1. Check the heat exchanger sensor (TD).
2. Gas purging
When turning on the unit, the normal phase (RST) is detected but T-R waveform has not been detected for 120 seconds or more.
50
Page 53
9-5. How To Diagnose Faulty Parts
[04 Serial signal error] (Heat pump model)
FILE NO. SVM-05011
Operation
Check item
Conceivable principle cause
Measure
Does outdoor
unit operate?
YES
NO
Are 1, 2 and 3 crossover
wires connected properly?
YES
Is connector
connected properly?
YES
Does LED (Orange) on
outdoor P.C. board blink?
YES
Does LED (Green) on
outdoor P.C. board blink?
YES
NO
NO
NO
NO
Outdoor P.C. board
is defective.
Indoor P.C. board
is defective.
Item by symptoms
Connect crossover
wires properly.
Connect connector
properly.
Replace
P.C. board.
Replace
P.C. board.
[08 Four-way valve error] (Heat pump model)
Does four-way valve
operate properly?
YES
Is TC sensor
resistance value
(10kat 25°C) normal?
NO
NO
YES
Does coil terminal have 220 − 240 V
in heating operation?
YES
Are circuit
wires normal?
YES
Is outdoor P.C. board
normal?
YES
YES
NO
NO
Four-way valve
is defective.
Outdoor P.C. board
is defective.
(CN11 220 240V)
Indoor P.C. board
is defective.
Replace
Four-way valve
Circuit check/modification
Replace
P.C. board.
Replace
P.C. board.
Replace TC sensor.
51
Page 54
[09 Other cycle error] (1) (Heat pump model)
FILE NO. SVM-05011
NO
Replace TC
sensor.
YES
Connect TC
sensor properly.
Does compressor operate?
YES
Is compressor
turned off shortly?
NO
Is TC sensor
resistance value
(10kΩ at 25°C) normal?
YES
Is TC sensor
disconnected from
the sensing element?
NO
NO
YES
Does inner
overload relay
(in compressor)
operate?
NO
Is circuit wiring
normal?
YES
Is outdoor P.C. board normal?
YES
YES
NO
NO
Check charged amount of refrigerant.
Check defective overload.
Check compressor.
Failure
Wiring check/modification
Outdoor P.C. board
is defective.
Indoor P.C. board
is defective.
Replace
compressor.
Replace
P.C. board.
Replace
P.C. board.
[09 Other cycle error] (2)
NO
Connect
connector
properly.
NO
Replace
condenser.
NO
Replace
fan motor.
Is connector
connected properly?
Is condenser normal?
Is indoor fan
motor normal?
YES
YES
YES
NO
Does indoor fan operate?
Are filters clogged?
Is TC sensor
resistance value
(10kΩ at 25°C) normal?
Is charged amount
of refrigerant normal?
Is outside air
low load?
YES
NO
YES
YES
NO
YES
NO
NO
YES
Anti-freezing operation
Anti-freezing operation
Clean filters.
Replace
TC sensor.
Charge
refrigerant.
Indoor P.C. board
is defective.
52
Replacd
P.C. board.
Page 55
[0C Indoor TA sensor error]
FILE NO. SVM-05011
Is CN04 (TA sensor connector)
connected properly?
YES
Is TA sensor resistance value
(10 kΩ at 25
°C)
YES
normal?
[0d Indoor TC sensor error]
Is CN05 (TC sensor connector)
connected properly?
YES
NO
NO
NO
Indoor P.C. board is defective.
Connect CN04 properly.
Replace TA sensor.
Replace P.C. board.
Connect CN05 properly.
Is TC sensor resistance value
(10 k
at 25°C) normal?
YES
NO
Indoor P.C. board is defective.
[18 outdoor TE sensor error] (Heat pump model)
Is TE sensor connector
connected properly?
YES
Is TE sensor resistance value
(10 k
at 25°C) normal?
YES
NO
NO
Replace TC sensor.
Replace P.C. board.
Connect connector
properly.
Replace TE sensor.
Indoor P.C. board is defective.
53
Replace P.C. board.
Page 56
[19 outdoor TD sensor error] (Heat pump model)
FILE NO. SVM-05011
Is TD sensor
connected properly?
YES
Is TD sensor resistance value
(50 k
at 25°C) normal?
YES
NO
NO
Outdoor P.C. board is defective.
[1E Discharge temp. error] (Heat pump model)
Connect connector
properly.
Replace TD sensor.
Replace P.C. board.
Is protective
controller such as discharge
thermostat normal?
YES
Is charged amount
of refrigerant normal?
YES
Is overload relay normal?
NO
Is TD sensor resistance value
(50 k at 25°C) normal?
YES
NO NO
NO
YES
NO
Are wires connected
to connector properly?
Outdoor P.C. board is defective.
Connect wires to
connector properly.
Check and modify charged
amount of refrigerant.
Unit operates normally.
Replace TD sensor.
Replace P.C. board.
54
Page 57
FILE NO. SVM-05011
Operation
Measure
Item by symptoms
Check item
Conceivable principle
cause
9-6.
Troubleshooting for Indoor unit
9-6-1. Power can not be turned on. (The unit does not operate at all.)
<Primar check>
(1) Is the supply voltage normal? (2) Is the connection to the AC output OK? (3) Is the fuse (F01) blown?
Turn off power supply once, and 5 second later, turn it
on again.
NO
Is OPERATION
lamp blinking?
YES
Does
Is it possible to
turn on power
supply by
pressing
[START/STOP]
button on remote
control?
YES
NO
transmission
mark on
remote
control flash
normally, and
is its signal transmitted
properly?
YES
NO
Remote control is
defective.
Refer to 9-9
ÒTroubleshooting for
Remote Control.Ó
Is DC 310 -
340V across
C63?
Are DC 12V,
across C66?
YES
YES
NO
NO
Is fuse (F01)
control board
Is voltage (DC
NO
indicated on
rear of indoor
control board
Turn off breaker
once and turn it
on again after
removing motor.
of indoor
blown?
NO
12V or 5V)
normal?
YES
YES
Parts (R21, R22, SG01,
C01, DB01,
C02,
M01 and IC04)
are defective.
Are DC 12V,
across C66?
YES
55
NO
Does the fan
motor
connector
between 1
and 2 short-
circuit?
NO
Microcomputer is
defective.
M01 is
def
ec
tive.
Unit operates
normally.
YES
Replace main P.C.
board.
Replace motor.
Page 58
FILE NO. SVM-05011
9-6-2. Only the indoor fan does not operate
<Primary chec k>
(1) Is it possible to detect the power supply voltage (200 − 240V) between 1 and 2 on the terminal block? (2) Does the indoor fan motor operate in cooling operation?
(In heating operation, the indoor fan motor does not operate for approximately 5 minutes after it is turned on, to prevent a cold air from blowing in.)
Shut off the
power supply once.
Turn the power supply.
Does the fan stop in
no operating status?
YES
Start the operation
with low fan setting
in cool operation.
Does the fan rotate?
YES
Change the setting of
cooling to high fan.
Does the fan speed
become higher?
YES
NO
NO
NO
Control P.C. board is defective.
Does AC 120V
or higher voltage apply
to between red and black
lead of fan motor?
YES
Shut off the power supply.
Does the cross flow fan rotate normally?
YES
Turn on the power supply.
Operation
stops
NO
NO
Replace the P.C. board.
Does connecting
terminal, connecting
cable or power supply
cord completely?
Does not found the short
wire about connecting
cable and power cord?
YES
Repair the bearing of
the fan.
Motor control circuit failure
(IC30, IC03, D38, R25, R26, Q17)
or 12V power circuit failure.
Replace the P.C. board.
of incompleted connecting.
NO
Thermal fuse operated
due to prevent
temperature rising cause
Normal
Is the rotation signal (DC+5V-0V)
output between 2 (gray lead wire)
and 3 (brown lead wire) of the motor
connector (CN11) when rotating
the cross flow fan by hand in no
operating status?
(1 pulse/one turn)
YES
Replace the control
P.C. board.
56
NO
Replace the fan motor
Replace connecting
the cable (or power cord),
thermal fuse and
terminal block.
Page 59
FILE NO. SVM-05011
9-6-3. Compressor does not operate. <Primary check>
(1) Is the preset temperature higher than the room temperature in cooling operation? (2) Is the crossover cable connected properly?
<Inspection procedure>
Turn on power supply.
Does OPERATION
lamp blink?
YES
Does miniature relay RY04
switch on and off due to
temperature changes?
YES
Is it possible to detect AC
220 – 240V between 2
and 3 on terminal block?
YES
Are all of compressor cords normal?
YES
Is compressor motor winding
normal?
(Check winding resistor.)
YES
Is capacitor for compressor normal?
NO
NO
NO
Is resistance value of thermo
sensor (TA) and heat ex-
changer sensor (TC) normal?
YES
Microcomputer is defective.
Miniature relay RY04 is
defective.
NO
NO
NO
Compressor is defective.
NO
Capacitor is defective.
Refer to 9-6-1 “Power
can not be turned on”.
Thermo sensor or
heat exchanger
sensor is defective.
Replace thermo sensor
or heat exchanger
sensor.
Replace P.C. board.
Rewire or replace
defective cords.
Replace compressor.
Replace capacitor.
YES
Is overload relay normal?
YES
Does compressor start?
YES
Does compressor stop after a while?
YES
Is gas quantity normal?
(Check gas pressure.)
YES
Compressor is defective.
YES
Replace P.C. board.
NO
NO
NO
Overload relay is
defective.
Compressor is defective.
Gas shortage (Gas leak)
– 57 –
Replace overload relay.
Replace compressor.
Supply gas.
Page 60
<Inspection procedure>
- Cooling model -
Turn on power supply.
FILE NO. SVM-05011
Does OPERATION
lamp blink?
YES
Is it possible to start
unit by remote control?
YES
Is it possible to detect AC 200V
between 2 and 3 on terminal block?
YES
Is crossover cable normal?
YES
Are all of compressor cords normal?
YES
Is compressor motor winding normal?
(Check winding resistor.)
YES
Is capacitor for compressor normal?
YES
NO
NO
NO
NO
NO
NO
NO
Compressor is defective.
Capacitor is defective.
Refer to item Power
can not be turned on .
Refer to 9-9 Troubleshooting
for Remote Control .
Replace P.C. Board
Connect crossover
cable properly.
Rewire or replace
defective cords.
Replace compressor.
Replace compressor.
Is overload relay normal?
YES
Does compressor start?
YES
Does compressor stop after a while?
YES
Is gas quantity normal?
(Check gas pressure.)
YES
Compressor is defective.
YES
Replace P.C. borad
NO
NO
NO
Overload relay is defective.
Compressor is defective.
Gas shortage (Gas leak)
Replace overload relay.
Replace compressor.
Supply gas.
58
Page 61
<Inspection procedure)
- Heating model -
AC 70-100V
FILE NO. SVM-05011
Replace transformer
outdoor
P.C. board.
59
Page 62
YES
FILE NO. SVM-05011
Are all of compressor cords normal?
YES
Is compressor motor winding normal?
(Check winding resistor.)
YES
Is capacitor for compressor normal?
YES
Is overload relay normal?
YES
Does compressor start?
YES
Does compressor stop after a while?
YES
Is gas quantity normal?
(Check gas pressure.)
YES
NO
NO
NO
NO
NO
NO
Compressor is defective.
Capacitor is defective.
Overload relay is defective.
Compressor is defective.
Gas shortage (Gas leak)
Rewire or replace
defective cords.
Replace compressor.
Replace capacitor.
Replace overload relay.
Replace compressor.
Supply gas.
Compressor is defective.
YES
Replace compressor.
– 60 –
Page 63
FILE NO. SVM-05011
9-7. Troubleshooting for Wiring (Interconnect cable and Serial Signal Wire)
9-7-1. Outdoor unit does not operate. <Inspection procedure>
(1) Is the voltage between and of the indoor terminal block varied?
1
(2) Are signals from the indoor unit to the outdoor unit transmitted correctly based upon the following diagram?
NOTE:
 Measure the voltage for 2 minutes and 30 seconds after starting the unit. 
Heatpump model
Terminal block on indoor side
Red
2
3
White
2
1
Terminal block
Tester
Normal condition : Voltage varied between AC70 ~ 100V Abnormal condition : Voltage does not vary.
Cooling model
Terminal block on indoor side
Red
White
3
2
1
Terminal block
Tester
Fig. 9-7-1
Normal condition : After start operated about 2 minutes and 30 seconds. Voltage between 2 and 3 of the
of the indoor's Terminal block should be equal AC 220 ~ 240V (For Asia model), AC 220V (For Thai model).
Abnormal condition : Don't found voltage AC 220 ~ 240V (For Asia model), AC 220V (For Thai model) from
terminal block (0V)
9-7-2. Outdoor unit stops a while after starting the unit.
<Confirmation procedure> Select one of 3 cases below and follow the procedure.
(1) The outdoor unit stops between 10 and 20 minutes passed after starting and it takes 10 minutes or more to
restart the unit.
Gas has a low circulation.
Measure gas pressure.
Compressor is turned off and on automatically by thermo sensor
(Heat pump Model) or thermostat (Cooling only Model).
Gas shortage Gas leak
Pipe clogging
(2) The outdoor unit stops once, it would not operate until the power is turned on again.
Refer to 9-6-4 "Compressor does not operate"
(3) The outdoor unit stops between 10 minutes to 1 hour after starting and a check code is indicated on the
remote control. (Check code 03-1E : Refer to Table 9-4-1.)
61
Page 64
FILE NO. SVM-05011
9-8. Troubleshooting for P.C. board
9-8-1. How to check indoor P.C. board <Cautions for handling P.C. board>
(1) When removing the front panel and the P.C. board,
be sure to turn off the power supply.
(2) When removing the P.C. board, hold the edge of
the P.C. board and do not apply force to the parts.
(3) When connecting or disconnecting the connectors
on the P.C. board, hold the housing. Do not pull at lead wires.
<Inspection procedure>
(1) If the P.C. board is detective, check for disconnec-
tion, burn or discoloration of the copper foil pattern of the P.C. board.
(2) The P.C. board consists of the following 2 parts:
a. Main P.C. board parts.
Power relay, indoor fan motor drive circuit and control circuit, C.P.U. and peripheral circuits, buzzer drive circuit and buzzer.
b. Infrared rays parts:
Infrared rays receiving circuit
Check the defects of the P.C. board with Table 9-8-1.
Table 9-8-1 Inspection pr ocedure
No. Procedure Check points Causes
1 Turn off the power supply and
remove the P.C. board assembly from electric parts base. Remove the connecting cables from the terminal block.
2 Remove the connector of the motor
and turn on the power supply. If OPERATION lamp blinks (once per second), it is not neccessary to check steps (1 to 3) in the right next column.
Check whenther or not the fuse (F01) is blown.
Check power supply voltage;
1. Between CN30 and CN31 (220 240 V AC) : Except
2. Between + and of C63 (DC310 340 V)
3. Between 12 V and GND
4. Between 5 V and GND
Impluse voltage was applied or the indoor fan motor short-circuited.
1. The terminal block or the crossover cable is connected wrongly.
2. The capacitor (C01 and C02 ) line filter (L01), resistor (R319), or the diode (DB01) is defective.
3. C65, C66 and M01 are defective.
4. IC04, C05, C06 and C07 are
defective.
3 Press [ ] button once
to start the unit. (Do not set the mode to Fan Only or On-Timer operation).
4 Shorten the line of the restart delay
timer and start unit.
Check power supply voltage; <Heat pump model>
1. Between CN31 and CN23 (DC15 60 V)
<Cooling only model>
1. Between connector of Q24 and GND (for relay coil (DC12 V))
2. Between 1 and 2 of terminal block for connecting cable
Check whether or not all lamps (OPERATION, TIMER, PRE.-DEF. (or FAN ONLY), FILTER. and Hi Power) are indicated for 3 seconds and they return to normal 3 seconds later.
<Heat pump model> IC32 and IC33 are defectice.
<Cooling only model>
1. The wire of the relay coil (RY04) comes down or the relay drive (Q24) is defective.
2. CN27 or RY04 is connected wrongly.
The lamps are defective or the housing assembly (CN13) is defective.
62
Page 65
FILE NO. SVM-05011
No. Procedure Check points Causes
5 Press [ ] button once
to start the unit.
Shorten the time of the restart delay timer.
Set the operation mode to COOL.
Set the fan speed level to AUTO.
Set the preset temperature much
lower than the room temperature. (The unit (compressor) operates continuously in the above condition.)
1. Check whether or not the compressor operates.
2. Check whether or not the OPERATION lamp blinks.
1. The temperature of the indoor heat exchanger is extremely low.
2. The connection of the heat exchanger sensor is loose. (The connector is disconnected.) (CN01)
3. The heat exchanger sensor and the P.C. board are defective. (Refer to Table 9-8-2.)
4. The main P.C. board is defective.
6 If the above condition (No. 6) still
continues, start the unit in the following condition.
Set the operation mode to HEAT.
Set the preset temperature much
higher than room temperature.
7 Connect the motor connector to the
motor and turn on the power supply. Start the unit in the following condition.
Set the operation mode to FAN.
Set the fan speed level to HIGH.
(The unit (compressor) operates continuously in the above codition.)
1. Check whether or not the compressor operates.
2. Check whether or not the OPERATION lamp blinks.
1. Check it is impossible to detect the voltage (DC 12 V) between and1
3 of the motor terminals.
2. The motor does not operate. (But it is possible to receive the signal from the remote control.)
3. The motor rotates but vibrates strongly.
1. The temperature of the indoor heat exchanger is extremely high.
2. The connector of the heat exchanger sensor short-circuited. (CN01)
3. The heat exchanger sensor and the P.C. board are defective. (Refer to Table 9-8-2.)
4. The main P.C. board is defective.
1. The indoor fan motor is defective. (Protected operation of P.C. board)
2. The connection of the motor connector is loose.
3. The P.C. board is defective.
Table 9-8-2 Approximate resistance value of thermo sensor
Temperature 0°C10°C20°C25°C30°C
Resistance value 33.8 20.35 12.59 10.0 7.99
(kΩ)
9-8-2. How to Shorten Time of Restart Delay Timer
1 Press [CLR] button while pressing [CHK] button
with a tip of a pencil.
2 Then press [ ] button to transmit the
signal to the indoor unit.
9-8-3. How to use self cleaning function
The self cleaning function is set from a factory. To cancel this function, should keep press the temporary switch for 20 secounds till can hear the long combination sound and repeat the
same procedure when need to set.
63
2
1
Page 66
9-9. Troubleshooting for Remote Control
FILE NO. SVM-05011
Is receiver on
indoor unit exposed
to direct sunlight?
YES
NO
Is there any
thyristor fluorescent
light nearby?
YES
YES
NO NO
Press START/STOP
button.
Is transmission
mark indicated?
Does indoor unit
operate when
moving remote control
near receiver or
indoor unit?
YES
Batteries are
exhausted.
The unit does not beep at all. OPERATION lamp on indoor unit is not indicated.
NO
Press RESET button
on remote control
with tip of pencil.
Press START/STOP
button.
Avoid direct
sunlight.
Keep indoor unit
away from
thyristor
fluorescent light.
Does indoor unit
NO
start to operate by
automatic restart
function?
YES
Does radio sound
is affected by
remote control when
a signal is transmitted
at distance of 5 cm
from radio?
P.C. board is
defective.
Replace
P.C. board.
YES
NO
NO
Replace
batteries.
Note : After replacing batteries,
press the RESET button with a tip of a pencil.
64
Is transmission mark
indicated?
YES
Does indoor unit
beep and operate?
YES
Normal
operation
NO
Remote control
is defective.
Replace
remote control.
Page 67
FILE NO. SVM-05011
(2)
(2)
(2)
4-screws
(6) TC sensor

10. PART REPLACEMENT

10-1. Indoor Unit
No. Part name Procedures Remarks
1 Front panel
How to remove the front panel
1) Stop the operation of the air conditioner and turn off its main power supply.
2) Pull the inlet grille toward you to open it and remove 4 screws fixing the front panel.
3) Remove upper 3 hooks of the front panel from the back body.
4) Open the horizontal grille right below by hand.
5) Pull the lower side of the front panel toward you until it touches the horizontal grille to remove it.
2 Electrical part
assembly
How to mount the front panel
1) Mount the front panel with the inverse procedure of “How to remove the front panel”.
2) Push 3 places (right, left and center) of the air outlet.
3) Check the gap between the front panel and the back body. If you operate the air conditioner in cooling or dry operation without pushing the 3 places, the surface of the front panel may be covered with frost and have dewdrops.
1) Remove the front panel with the procedure 1.
2) Remove the screw fixing the electrical part box.
3) Remove the drain guide.
4) Remove the connector (
and the connector (6P) for the louver motor from the microcomputer assembly.
5) Remove the screw for the earth, and pull the electrical part base toward you to remove it from the main unit.
6) Pull out the TC sensor from the sensor holder.
3P x 2) for the fan motor
(3) Drain guide
(3)
(4)
(5) screws
(3P X 2) 6P
(2) screws
When assembling the electrical parts assembly, make the connecting cable U-shaped and put it in the drain pan.
65
Page 68
FILE NO. SVM-05011
Bearing base
Bearing
Motor fixture
(4) BODY (R)
(3) 2 screws
(5)
No. Part name Procedures Remarks
3 Horizontal grille
4 Heat exchanger
1) Remove center 2 shafts of the horizontal grille from the back body.
2) Remove left shaft of the horizontal grille from the back body.
3) Remove the horizontal grille from the back body.
1) Remove the front panel, electrical parts assembly and the horizontal grille with procedure 2 and 3.
2) Remove the screw on the rear side of the main unit to remove the pipe holder.
3) Remove 2 screws fixing the heat exchanger and the bearing base.
4) Remove 2 screws fixing the heat exchanger fixtures (upper and lower) and the back body then pull out the upper side of the heat exchanger slowly.
(1) Center shafts
(2) Left shafts
(3) 2 screws
(2) Screw
Bearing base
(3)
Pipe holder
(4) 2 screws
5 Cross flow fan
6 Bearing base
1) Remove the front panel, electrical parts assembly, horizontal grille and the heat exchanger with procedure 4.
2) Loosen the set screw of the cross flow fan.
3) Remove 2 screws fixing the bearing base and the
back body.
4) Pull the cross flow fan toward you.
1) Remove the front panel, electrical parts assembly, horizontal grille, heat exchanger and the cross flow fan with procedure 5.
2) Remove the bearing from the bearing base. If the housing protrudes from the base bearing, put the housing in position and assemble the bearing to the bearing base.
(3) Screws
(2) Set screw
When assembling the cross flow fan, fix it with the set screw at the position where the gap between the back body and the right surface of the cross flow fan is 4 mm.
7 Fan motor
1) Remove the front panel, electrical parts assembly, horizontal grille, and the heat exchanger with procedure 4.
2) Loosen the set screw of the cross flow fan.
3) Remove 2 screws of the motor fixture.
4) Remove the lower side of the body (R) and move it right to remove it.
5) Remove the motor from the motor fixture.
66
Page 69
FILE NO. SVM-05011
10-2. Outdoor Unit (RAS-24UAH-ES4, RAS-24UA-ES4)
No. Part name Procedures Remarks
1 Common
procedure
1) Stop the operation of the air conditioner and turn off its main power supply or remove the power supply cord.
2) Remove the electrical parts cover. (4 screws 4 x 10L)
3) Remove 2 cord clamps (4 screws 4 x 22L) and disconnect the power supply cord and connecting cable after removing 6 screwson on the terminal block and 1 ground screw on the electrical parts base.
4) Remove the top cabinet. (7 screws 4 x 10L)
5) Remove the front cabinet. (2 screws 4 x 10L)
6) Remove the side cabinet (4 screws 4 x 10L & 2 screws 4 x 14L)
Top cabinet
Front cabinet Side cabinet
4 screws 4 x 22L
Electrical parts cover
2 Running
capacitor for compressor
3 Running
capacitor for fan motor
4 Magnetic
contactor
5 Transformer
(Heat pump model)
6 P.C. Board
(Heat pump model)
7 Spark killer
(Cooling only model)
1) Perform the common procedure 1
2) Remove the capacitor band. (1 screw 4 x 10L)
3) Disconnect the lead wires from the capacitor terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (1 screw 4 x 10L)
3) Disconnect the lead wires from the capacitor terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (2 screws 4 x 10L)
3) Disconnect the lead wires from the terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (2 screws 4 x 10L)
3) Disconnect the housing from the P.C. Board.
1) Perform the common procedure 1
2) Disconnect the lead wires from the P.C. Board.
3) Remove P.C.Board after unhooking 4 clams.
1) Perform the common procedure 1
2) Remove the fixing screw. (1 screw 4 x 10L)
3) Disconnect the lead wires from the terminal.
Magnetic contactor
P.C. Board
Transformer
Spark killer
Running capacitor for compressor
Running capacitor for fan motor
RAS-24UAH-ES4
Running capacitor for compressor
67
Magnetic contactor
RAS-24UA-ES4
Running capacitor for fan motor
Page 70
FILE NO. SVM-05011
10-3. Outdoor Unit (RAS-18UAH-ES4)
No. Part name Procedures Remarks
1 Common
procedure
1) Stop the operation of the air conditioner and turn off its main power supply or remove the power supply cord.
2) Remove the electrical parts cover. (4 screws 4 x 10L)
3) Remove 2 cord clamps (4 screws 4 x 22L) and disconnect the power supply cord and connecting cable after removing 6 screws on the terminal block and 1 ground screw on the electrical parts base.
4) Remove the front cabinet. (8 scerws 4 x 10L) (Pull the front lower portion toward you, and pull out it upward to remove it.)
5) Remove the side cabinet. (8 screws ∅4 x 10L)
Remove 8 screws 4 x 10L
4 screws 4 x 22L 4 screws 4 x 10L
2 Running
capacitor for compressor
3 Running
capacitor for fan motor
4 Magnetic
contactor
5 Transformer
6 P.C. Board
1) Perform the common procedure 1
2) Remove the capacitor band. (1 screw 4 x 10L)
3) Disconnect the lead wires from the capacitor terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (1 screw 4 x 10L)
3) Disconnect the lead wires from the capacitor terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (2 screws 4 x 10L)
3) Disconnect the lead wires from the relay terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (2 screws 4 x 10L)
3) Disconnect the housing from the P.C. Board.
1) Perform the common procedure 1
2) Disconnect the lead wires from the P.C. Board.
3) Remove P.C. Board after unhooking 4 clams.
Running capacitor for compressor
P.C. Board
Transformer
Running capacitor for fan motor
Magnetic contactor
68
Page 71
FILE NO. SVM-05011
10-4. Outdoor Unit (RAS-18UA-ES4)
No. Part name Procedures Remarks
1 Common
procedure
1) Stop the operation of the air conditioner and turn off its main power supply or remove the power supply cord.
2) Remove the packed valved cover and the electrical
Parts cover
(3 screws 4 x 10L)
3) Remove 2 cord clamps (4 screws 4 x 22L) and disconnect the power supply cord and connecting cable after removing 6 screws on the terminal block and 1 ground screw on the electrical parts base.
4) Remove the upper cabinet. (4 scerws ∅ 4 x 10L) (Pulling out upward)
5) Remove the front cabinet. (3 screws∅ 4 x 10L) (Pull the front right protion toward you, and remove
it pulling out upward.)
3 - screws 4 x 10L
Packed valve cover
Upper cabinet
Electric parts cover
2 Cord clamps
4 - screws 4 x 22L
Running
2
capacitor for compressor
Running
3
capacitor
or fan motor
f
Magnetic contactor
4
5
Spark killer
1) Perform the common procedure 1
2) Remove the capacitor band. (1 screw ∅4 x 10L)
3) Disconnect the lead wires from the capacitor terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (1 screw ∅4 x 10L)
3) Disconnect the lead wires from the capacitor terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (2 screws 4 x 10L)
3) Disconnect the lead wires from the terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (1 screw ∅ 4 x 10L)
3) Disconnect the lead wires from the terminal.
Front
cabinet
Running capacitor for compressor
Magnetic contactor
Spark killer
Running capacitor for fan motor
69
Page 72
11. EXPLODED VIEWS AND PARTS LIST
11-1. Indoor Unit (E-Parts Assy)
FILE NO. SVM-05011
Location Part
No. No.
402 43T60002 Terminal Block, 3P
3P AC300V, 20A
403 43T50004 Sensor, Heat Exchanger
10k 25°C 404 43T69005 Sensor, Thermostat 10k25°C 405 43T69066 P.C. Board ASSY, WRS-LED
MCC-819 406 43T69438 P.C. Board ASSY
(RAS-24UKHP-ES4)
Description
Location Part
No. No.
406 43T69439 P.C. Board ASSY
406 43T69440 P.C. Board ASSY
406 43T69441 P.C. Board ASSY
407 43T62003 Clamp, Cord
70
Description
(RAS-24UKP-ES4)
(RAS-18UKHP-ES4)
(RAS-18UKP-ES4)
Page 73
11-2. Indoor Unit
FILE NO. SVM-05011
Location Part
No. No.
201 43T00409 Front Panel, ASSY 202 43T09346 Grille ASSY (For Heat pump model) 202 43T09347 Grille ASSY (For cooling only model) 203 43T80306 Air Filter (L) 204 43T80312 Air Filter (R) 207 43T03010 Body, Right 208 43T03011 Body, Left 209 43T03012 Hide, Claw 210
43T09345
211 43T70301 Hose ASSY, Drain 212 43T21302 Motor, Stepping 213
43T44360 Refrigeration Cycle Assembly
214
43T47311 Pipe, Delivery
215
43T47312 Pipe, suction 216 43T49021 217 43T19003 Holder, Sensor 218 43T49009 Spring 219 43T49036 Plate, EVA-Seal 220 43T49039 Holder, Plate, EVA-Seal
Louver-H
, Shield
Pipe
Description
Location Part
No. No.
221 43T49038 Plate, EVA-Seal 222 43T49037 Holder , Plate EVA-Seal 223 43T79007 Guide Drain 224 43T39306 Fix Motor 226 43T21346 Motor, Fan 227 43T20309 Fan, Cross Flo 228 43T22002 M-Bearing ASSY 229 43T39015 Base, Bearing 230 43T03013 Back Body ASSY 231 43T07022 Holder, Pipe 232 43T82007 Plate, Installation 233 43T85468 Owner's Manual 233 43T85469 Owner's Manual 233 43T85470 Owner's Manual 233 43T85471 Owner's Manual
234 43T69421 Remote Control, Wireless WH-H01EE
(For Heat pump model)
234 43T69422 Remote Control, Wireless WC-H01EE
(For Cooling model)
235 43T83003 Holder, Remote Control 236 43T62029 Cover, Terminal
Description
71
Page 74
11-3. Outdoor Unit (RAS-24UAH-ES4)
FILE NO. SVM-05011
Location Part
No. No.
01 43T00024 Panel, Air Outlet 02 43T00025 Panel, Front 03 43T00026 Panel, Side 04 43T42307 Base Assembly 05 43T19320 Guard, Fin 06 43T19319 Guard, Fan 07 43T91001 Plate, Roof 08 43T42005 Plate, Valve, Packed 09 43T15001 Handle 10 43T43307 Condenser Assembly 11 43T46318 Valve, Packed, 12.7Dia. 12 43T46317 Valve, Packed, 6.35Dia. 13 43T47018 Bonnet, 12.7Dia. 14 43T47020 Bonnet, 6.35Dia. 15 43T47013 Capillary Tube, 2.0Dia. 16 43T60324 Terminal Block, 6P 17 43T60325 Filter, Clamp 18 43T41350 Compressor, 5JS315DAG01 19 43T62014 Protector, Cord 20 43T62015 Protector, Cord
Description
Location Part
No. No.
23 43T49309 Cushion, Rubber 24 43T21315 Motor, Fan, AC 220 240V 50Hz 25 43T20301 Fan, Propeller, 491 26 43T96001 Bushing 27 43T96004 Bushing, Cord 28 43T62013 Cover, E-Parts 29 43T52305 Switch, Magnet, A35
30 43T55322 MF Capacitor (45µF 440V) 31 43T55321 MF Capacitor (3.5µF 450V) 32 43T96003 Clip, Cable 33 43T46319 Valve, 4way 34 43T46330 Coil, V-4way AC 220 240V 35 43T69059 Sensor 36 43T69060 Sensor, TD 37 43T79305 Nipple, Drain 38 43T58301 Transformer, TT-05 39 43T69336 PC Board Assembly 40 43T47317 Nut, Flange
Description
72 −
Page 75
11-4. Outdoor Unit (RAS-18UAH-ES4)
FILE NO. SVM-05011
Location Part
No. No.
01 43005144 Cabinet, Front 02 43T00005 Cabinet, Back 03 43T00004 Cabinet, Side 04 43T42312 Base 05 43T00011 Plate, Packed, Valve 06 43T19314 Guard, Fan 07 43T19005 Handle 08 43T62301 Cover, E-Parts 09 43020302 Fan, Propeller 10 43T21358 Motor, Fan, WLF-240-42A-2 11 43T47001 Nut, Flange 12 43T63004 Clamp, Lead Wire 13 43T96001 Bushing 14 43T43309 Condenser Assembly 15 43T46317 Valve, Packed, 6.35Dia. 16 43T47020 Bonnet, 6.35Dia. 17 43T46318 Valve, Packed 12.7Dia. 18 43T47018 Bonnet, 12.7Dia.
Description
Location Part
No. No.
73
Description
19 43T47013 Capillary Tube, 1.0Dia. 23
43T49008 Cushion, Rubber
24
43T55332 MF Capacitor (50µ F 440V)
25
43T55324
26
43T60324 Terminal Block, 6P
27
43T41349 Compressor, 5KS225DAA
28
43T52302 Magnetic Contactor (CLK-26J)
29
43T46319 Valve, 4way STF-0213G
30
43T46330 Coil, V-4way AC 220 240V 50Hz
31
43T69059 Sensor, TE
32
43T69060 Sensor, TD
33
43T79305 Nipple, Drain
34
43T58301 Transformer, TT-05
35 43T69336 PC Board 38 43T60325 Filter, Clamp
MF Capacitor (2µ F 450V)
Page 76
11-5. Outdoor Unit (RAS-24UA-ES4)
FILE NO. SVM-05011
Location Part
No. No.
01 43T00024 Panel, Air Outlet 02 43T00025 Panel, Front 03 43T00026 Panel, Side 04 43T42307 Base Assembly 05 43T19320 Guard, Fin 06 43T19319 Guard, Fan 07 43T91001 Plate, Roof 08 43T42005 Plate, Valve, Packed 09 43T15001 Handle 10 43T43347 Condenser Assembly 11 43T46318 Valve, Packed 12.7Dia. 12 43T46317 Valve, Packed 6.35Dia. 13 43T47333 Bonnet, 12.7Dia. 14 43T47331 Bonnet, 6.35Dia. 15 43T47013 Capillary Tube, 2.0Dia. 16 43T60324 Terminal Block, 6P
Description
Location Part
No. No.
18 Compressor, 5JS315DAG01 19 43T62014 Protector, Cord 20 43T62015 Protector, Cord
23 24 43T21314 Motor, Fan, AC 220 240V 50Hz
25 43T20301 26 43T96001 Bushing
27 43T96004 Bushing, Cord 28 43T62013 Cover, E-Parts 29 43T52305 Switch, Magnet, A35
30 43T55322 MF Capacitor (45µ F 440V) 31 43T55321 MF Capacitor (3.5µ F 450V) 32 43T96003 Clip, Cable 40 43T47317 Nut, Flange 43
74
Description
43T41350
43T49309 Rubber Cushion
an, Propeller, PP491
F
43T33002 Spark-Killer
Page 77
11-6. Outdoor Unit (RAS-18UA-ES4)
FILE NO. SVM-05011
Location Part
No. No.
01 43T00368 Cabinet, Front 02 43T03308 Cabinet, Side 04 43T09318 Grard, Fan 05 43T62311 Cover, E-Parts 06 43T20307 Fan, Propeller 07 43T21345 Fan, Motor 08 43T47001 Nut, Flange 09 43020302 Fan, Propeller 10 43T46308 Valve, Packed 6.35 Dia. 11
43T46318
12 43T47331 Bonnet, 6.35 Dia. 13 43T47333 Bonnet, 12.70 Dia. 14 Fixing, Plate, Valve
43T63303
Valve, Packed 12.7 Dia.
Description
Location Part
No. No.
16
75
Description
15 43T47014 Capillary Tube,1.7Dia.
43T41349 Compressor, 5KS225DAA 43T47324 Bolt Compressor (M6)
17
43T49008 Cushion, Rubber
18 19 43T52310 Packed Valve Cover Assembly
43T00395 Upper Cabinet Assembly
20 21 43T55322 MF Capacitor (45µF 440V) 22 43T55325 Capacitor, Plastic Film 23 43T60352 Terminal Block, 6P 27
43T52302 Magnetic Contactor (CLK-26J) 43T33002 Spark Killer
28
Page 78
FILE NO. SVM-03009(1)
TOSHIBA CARRIER (THAILAND) CO.,LTD.
144/9 MOO 5, BANGKADI INDUSTRIAL PARK, TIVANON ROAD, TAMBOL BANGKADI,
AMPHUR MUANG, PATHUMTHANI 12000,THAILAND.
75
Loading...