7-1Outline of Air Conditioner Control
7-2Description of Operation Circuit
7-3Hi POWER Mode
7-4High-Temperature Limit Control
7-5Low-Temperature Limit Control
7-6Defrosting Operation
7-7 Auto Restart Function
7-8Filter Check Lamp
7-9 Self-Cleaning function
7-10QUIET Mode
7-11COMFORT SLEEP mode
TION DESCRIPTION
– 1 –
8.INSTALLATION PROCEDURE
8-1Safety Cautions
8-2Installation Diagram of Indoor and Outdoor Units
8-3Installation
8-4Indoor Unit
8-5Outdoor Unit
8-6How to Set Remote Control Selector Switch
8-7Others
9.TROUBLESHOOTING CHART
9-1Troubleshooting Procedure
9-2Basic Check Items
9-3Primary Judgement
9-4Self-Diagnosis by Remote Control (Check Code)
9-5How to Diagnose Faulty Part
9-6Troubleshooting for Indoor Unit
9-7Troubleshooting for Wiring (Interconnect cable and Serial Signal
9-8Troubleshooting for P.C. Board
9-9Troubleshooting for Remote Control
FILE NO. SVM-06004
Wire)
10. PARTS REPLACEMENT
10-1 Indoor Unit
10-2 Outdoor Unit (RAS-24NA-E, RAS-24N2AX)
10-3 Outdoor Unit (RAS-18NAH-E, RAS-18NA-E, RAS-18N2AX)
11. EXPLODED VIEWS AND PARTS LIST
11-1 Indoor Unit (E - Parts Assy)
11-2 Indoor Unit
11-3 Outdoor Unit
11-4 Outdoor Unit (RAS-24NA-E, RAS-24N2AX)
11-5 Outdoor Unit (RAS-18NA-E, RAS-18N2AX)
(RAS-18NAH-E)
− 2 −
1. SPECIFICATIONS
FILE NO. SVM-06004
MODEL
ITEM Cooling Cooling
CapacitykW
Power source V 220 – 240
Power consumption W 2350 2440 2350 2440
Power factor % 99 90 99 90
Running current A
Indoor/Outdoor
Starting current A
Moisture removal lit/h
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
GRN : GREEN
GRN&YEL : GREEN & YELLOW
P04
DSA
F01
6.3A
CN30
CN31
Varistor
250V
MAIN P.C. BOARD
(WP-003)
Varistor
Louver
motor
BLU
PNK
6
5223311
6
5
YEL
RED
BRW
ORN
4
CN07
4
GRY
BRW
YEL
FILE NO. SVM-06004
Infrared rays receive
and Indication parts
1 2 3 4 610
BLU
BLU
BLU
BLU
1 2 3 4 6510
321
Power supply
circuit
Control
Fan motor
circuit
7
598
7
BLU
BLU
7
5 64
7
105 64321
8 9
CN25
BLU
BLU
BLU
WHI
98
CN13
10
8 9
2
1
21
1
BLK2BLK
CN03
CN01
2
1
BLK
BLK
OUTDOOR
TERMINAL
BLOCK
POWER SUPPLY
220-240V ~ 50Hz
L
BLK
MAGNETIC
CONTACTOR
BLK
RED
INDOOR
TERMINAL
BLOCK
N
RED
R
U
i
1
1
GRN&YEL
S
V
2
2
RED
T
W
3
3
BLK
BLK
CHASSIS
SPARK KILLER
(or A)
A1
(or B)
A2
INDOOR
UNIT
OUTDOOR
UNIT
GRN&YEL
i
GRY
1
2
4
3
1
2
3
145 C
TEMP FUSE
Thermo.
sensor
66554
(TA)
Heat exchanger
sensor
(TC)
CAPACITOR
RED
S
WHI
PNK
R
COMPRESSOR
C
S
COMPRESSOR TERMINAL
CAPACITOR
RED
C
BLK
WHI
RED
BLK
FAN MOTOR
R
– 11 –
FILE NO. SVM-06004
4. SPECIFICATION OF ELECTRICAL PARTS
4-1. Indoor Unit (RAS-18NKHP-E)
No.Parts nameTypeSpecifications
1 Fan motor (for indoor) AFS-220-31AAC 200 − 240V, 31W
2Thermo sensor (TA-sensor)———10 kΩ at 25°C
3 Micro Power Module (M01) µRM1260V DC 390 V, Secondary DC 12 V, 5 V
4MicrocontrollerTMP87CM40AN
5Heat exchanger sensor
(TC-sensor)
6 Line filter (L01) LC*SS11V-06270 27mH, 600mA
7Diode (DB01)D3SBA604 A, 600 V
8 Capacitor (C63) KMH400VSSN47M22S4.7µF, 400 V
9 Fuse (F01) BET6.3A T6.3 A, 250 V
10 Varistor (R21, R22) 15G561K 560 V
11 Resistor (R319) RF-2TK5R6 5.6Ω , 2 W
12 Louver motor MP35EA12 Output (Rated) 2 W, 10 poles, 1 phase,
2 Fan motor (for outdoor) FG-240-42A-1 Winding resistance (Ω) Red-Black White-Black
(at 20°C)128 126
Running capacitor
3
(for fan motor)
Running capacitor
4
(for compressor)
Solenoid coil
5
(for 4-way valve)
6Thermo sensorTE / TD10 kΩ at 25°C / 50 kΩ at 25°C
7 Magnetic contactor
8TransformerTT-05220 – 240 V
9MicrocontrollerTMP47C840N
10Varistor (R73, R74, R86)15G471K470 V
11Fuse (F01)MT3T6.3 A, 250 V
451305L AC 450 V, 3.0µF
RS44B506U0218S AC 440 V, 50µF
VHV (STF)AC 220 – 240 V
CLK-26J
220 − 240 V, 50 Hz
– 12 –
FILE NO. SVM-06004
4-3. Indoor Unit (RAS-24NKP-E, RAS-24NKPX,
RAS-18NKP-E, RAS-18NKPX)
No.Parts nameTypeSpecifications
1 Fan motor (for indoor) AFS-220-31AAC 200 − 240V, 31W
2Thermo sensor (TA-sensor)———10 kΩ at 25°C
3 Micro Power Module (M01) µRM1260V DC 390 V, Secondary DC 12 V, 5 V
4MicrocontrollerTMP87CM40AN
5Heat exchanger sensor
(TC-sensor)
6 Line filter (L01) LC*SS11V-06270 27mH, 600mA
7Diode (DB01)D3SBA604 A, 600 V
8 Capacitor (C63) KMH400VSSN47M22S4.7µF, 400 V
9 Fuse (F01) BET6.3A T6.3 A, 250 V
10 Varistor (R21, R22) 15G561K 560 V
11 Resistor (R319) RF-2TK5R6 5.6Ω, 2 W
12 Louver motor MP35EA12 Output (Rated) 2 W, 10 poles, 1 phase,
13Relay : (RY04) G5NB-1A Coil DC 12V, 16.7mA, Contact AC 250V, 1A
Cooling High temperature 0.6 15.0 High 32/23 43/26
Low temperature 0.32 1.8 Low 21/15 21/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
*1 : During heating overload, the high temperature limit control operation is included.
– 14 –
5-2. RAS-24NKP-E / RAS-24NA-E
RAS-24NKPX / RAS-24N2AX
FILE NO. SVM-06004
Indoor unit
Cooling
0.39 m
(Connecting pipe)
∅
1 5.88
O.D.:15.88 mm O.D.:6.35 mm
Cooling
Compressor
P
Packed valve
(∅15.88)
Gas container connection (Reinstall etc.)
PH400X3CS-4KT1
Evaporator
Cross flow fan
T
0.49 m
(Connecting pipe)
∅
6 .35
Packed valve
(∅6.35)
Capillary tube
700 s
∅2.4x
Condenser
Refrigerant
R22 1.68 kg
Cooling
Propeller fan
Outdoor unit
Mark ( ) means check points of Gas Leak
Ambient temp.
50 Hz
Standard
pressure
(MPaG)
P
Surface temp. of heat
exchanger interchanging
pipe
T
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
IndoorOutdoor
Standard 0.43 8.5 High 27/19 35/24
Cooling High temperature 0.56 12.5 High 32/23 43/26
Low temperature 0.32 2.0 Low 21/15 21/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
– 15 –
5-3. RAS-18NKP-E / RAS-18NA-E
FILE NO. SVM-06004
Indoor unit
Evaporator
(Connecting pipe)
0.39 m
∅12.7
Cross flow fan
O.D.:12.7 mmO.D.:6.35 mm
Compressor
P
Packed valve
(∅12.7)
PH340X3C-4KT1
Condenser
Propeller fan
Outdoor unit
T
Packed valve
(∅6.35)
Capillary tube
∅2.0x600 s
Refrigerant
0 kg
R22 1.
Mark ( ) means check points of Gas Leak
0.49 m
(Connecting pipe)
∅6.35
Ambient temp.
50 Hz
Standard
pressure
(MPaG)
P
Surface temp. of heat
exchanger interchanging
pipe
T
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
IndoorOutdoor
Standard 0.41 11.0 High 27/19 35/24
Cooling High temperature 0.56 15.0 High 32/23 43/26
Low temperature 0.32 2.0 Low 21/15 21/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
– 16 –
5-4. RAS-B18NKPX / RAS-18N2AX
FILE NO. SVM-06004
(Connecting pipe)
0.39 m
∅12.7
O.D.:12.7 mm
Compressor
P
Packed valve
(∅12.7)
PH340X3C-4KT1
Indoor unit
Evaporator
Cross flow fan
Condenser
Propeller fan
T
0.49 m
(Connecting pipe)
∅6.35
O.D.:6.35 mm
Packed valve
(∅6.35)
Capillary tube
∅2.0x600 s
Dryer
Refrigerant
R22 1.0 kg
Outdoor unit
Mark ( ) means check points of Gas Leak
Ambient temp.
Surface temp. of heat
exchanger interchanging
pipe
T
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
IndoorOutdoor
50 Hz
Standard
pressure
(MPaG)
P
Standard 0.41 11.0 High 27/19 35/24
Cooling High temperature 0.56 15.0 High 32/23 43/26
Low temperature 0.32 2.0 Low 21/15 21/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
This is a fixed capacity type air conditioner, which uses
a AC motor for an indoor fan. The AC motor drive
circuit is mounted in the indoor unit. And electrical
parts which operate the compressor and the outdoor
fan motor, are mounted in the outdoor unit.
The air conditioner is mainly controlled by the indoor
unit controller. The controller operates the indoor fan
motor based upon commands transmitted by the
remote control and transfers the operation commands
to the outdoor unit controller.
The outdoor unit controller receives operation
commands from the indoor unit, and operates the
outdoor fan motor and the compressor.
(1) Role of indoor unit controller
The indoor unit controller receives the operation
commands from the remote control and executes
them.
• Temperature measurement at the air inlet of the
indoor heat exchanger by the indoor
temperature sensor
• Temperature setting of the indoor heat
exchanger by the heat exchanger sensor
• Louver motor control
• Indoor fan motor operation control
• LED display control
• Transferring of operation commands to the
outdoor unit
• Receiving of information of the operation status
and judging of the information or indication of
error
(2) Role of outdoor unit controller
The outdoor unit controller receives the operation
commands from the indoor controller and
executes them.
• Compressor operation
control
• Operation control of
outdoor fan motor
OPERATION
MODE
RAS-18NKHP Series
RAS-24NKP Series
Model
RAS-18NKP Series
Operations according
to the commands
from the indoor unit
Table 7-1-1
Cooling UH H M+
Heat
Fan only
Dry
rpm
Air flow volume (m3/h)
rpm
Air flo w volume (m3/h)
rpm
Air flow volume (m3/h)
UHH
1300
900
−
−
−
−
• Turning off the compressor and outdoor fan
when the outdoor unit receives the shutdown
command
• Defrost control in heating operation
(Temperature measurement by the outdoor heat
exchanger and control for the four-way valve
and the outdoor fan motor) *Heat pump Model
only
7-1-1. Louver control
(1) Vertical air flow louver
Position of veritcal air flow louver is automatically
controlled according to the operation mode.
Besides, position of vertical air flow louver can be
arbitrarily set by pressing [FIX] button.
The louver position which is set by [FIX] button is
stored in the microcomputer, and the louver is
automatically set at the stored position for the next
operation.
(2) Swing
If [SWING] button is pressed when the indoor unit
is in operation, the vertical air flow louver starts
swinging. When [FIX] button is pressed, it stops
swinging.
7-1-2. Indoor fan control (AC Fan motor)
(1) The indoor fan is operated by the stepless speed
change AC motor.
(2) For air flow level, speed of the indoor fan motor is
controlled in five steps (LOW, LOW
+
, MED, MED
and HIGH). If AUTO mode is selected, the fan
motor speed is automatically controlled by the
difference between the preset temperature and
the room temperature.
LOW
=
LOW+MED
+
2
MED+=
MED+HIGH
2
FAN TAP
M
M
1050
650
1150
750
1050
667
L
950
570
−
1050
−
667
−
950
−
M
H
M+M
M+
1100
700
1250
830
1100
708
−
−
−
−
1300
873
−
750584
L
L+
LL+
L
L
L+
900
530
1000
625
900
543
L
L- SUL/SL-
ULL+
L-
L- UL SUL
800
700
600
380 220
461
900
543
800
461
800
461
700
380
300
700380
600
300
SUL/SL-
+
500
−
−
−
−
− 20 −
FILE NO. SVM-06004
7-2. Description of Operation Circuit
(1) When turning on the breaker, the operation lamp
blinks. This means that the power is on (or the
power supply is cut off.)
(2) When pressing [ ] button on the
remote control, receiving beep sounds from the
indoor unit, and the next operation is performed
together with opening the vertical air flow louver.
(3) Once the operation mode is set, it is memorized in
the microcomputer so that the previous operation
can be effected thereafter simply by pressing
[ ] button.
7-2-1. Fan only operation
([MODE] button on the remote control is set
to the fan only operation.)
(1) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-1. When
[FAN] button is set to LOW, LOW+, MED, MED+ or
HIGH, the motor operates with a constant air flow.
°C
7-2-2. Cooling operation
([MODE] button on the remote control is set
to the cooling operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display lamp are controlled as shown in
Fig. 7-2-2.
°C
ON ON
OFF OFF OFF ON
4-way valve
Compressor
Outdoor fan
(Room temp.) (Preset temp.)
Preset
temp.
0.5
0
Fig. 7-2-2
display lamp
OPERATION
+3
+2.5
+2
+1.5
+1
+0.5
(Room temp.) − (Preset temp.)
Preset
temp.
0
(Preset temp.: 24°C)
NOTE :
*1: The values marked with *1 are calculated and
controlled by the difference in motor speed
between M+ and L–.
(2) The Hi POWER, ECO and COMFORT SLEEP
operation cannot be set.
Fig. 7-2-1 Setting of air flow [FAN:AUTO]
M+
*1
*1
*1
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-3. When
[FAN] button is set to LOW, LOW+, MED, MED+ or
HIGH, the motor operates with a constant air flow.
°C
(Room temp.) − (Preset temp.)
Preset
temp.
+3
+2.5
+2
+1.5
+1
+0.5
0
-0.5
M+
*1
*1
*1
NOTE :
*1: The values marked with *1 are calculated and
controlled by the difference in motor speed
between M+ and L–.
Fig. 7-2-3 Setting of air flow [FAN:AUTO]
– 21 –
FILE NO. SVM-06004
7-2-3. Dry operation
([MODE] button on the remote control is set
to the dry operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display lamp are controlled as shown in
Fig. 7-2-4.
°C
ON:6min.
OFF:4min.
ON
ON:5min.
OFF:5min.
OFF
4-way valve
Outdoor fan
(Room temp.) (Preset temp.)
Preset
temp.
+3
+2
+1
ON:6min.
OFF:4min.
OFF
ON:5min.
OFF:5min.
OFF
0
Compressor
Fig. 7-2-4
7-2-4. Heating operation *Heat pump model only
(1) The compressor, 4-way valve, outdoor fan and
Preset
temp.
display lamp
OPERATION
([MODE] button on the remote control is set
to the heating operation.)
operation display lamp are controlled as shown in
Fig. 7-2-6.
°C
0
ON
OFF
0.5
ON
(Room temp.) (Preset temp.)
OFF
ON
4-way valve
Compressor
Outdoor fan
ON
display lamp
OPERATION
Fig. 7-2-6
(2) The microprocessor turns the compressor on and
off at the regular intervals (4 to 6 minutes). While
the compressor is turning off, the indoor fan motor
operates in the SUPER LOW position.
The pattern of operation depending on the relation
between room temperature and preset
temperatures is shown in Fig. 7-2-5.
R oom temp.
Preset temp.+1
Preset temp.
Compressor
Outdoor fan
Indoor fan
ONONONON
OFFOFFOFF
L. *S.L.S.L.L.L.S.L.L.
*Super Low
Fig. 7-2-5
(3) [FAN] button on the remote control is set to AUTO
only.
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-7. When
[FAN] button is set to LOW, LOW+, MED, MED+ or
HIGH, the motor operates with a constant air flow.
Preset
temp.
°C
0
-0.5
-1
-1.5
-2
-5.0
-5.5
[FAN AUTO]
(Room temp.) − (Preset temp.)
L
*1
*2
+
M
H
*1, *2 : The values marked with *1 and *2 are
calculated and controlled by the difference in
motor speed between M+ and L.
Fig. 7-2-7 Setting of air flow [FAN:AUTO]
(4) The ECO and Hi Power operations can not be set.
– 22 –
FILE NO. SVM-06004
(3) The indoor heat exchanger restricts revolving
speed of the fan motor to prevent a cold draft. The
upper limit of the revolving speed is shown in
Fig. 7-2-8 and Table 7-2-1.
Manual
(One of
AUTO
*4
SUL*
SUL*1
Stop
5 speed)
L-H
(Up to
setting
3
speed)
*2
A+4 A+4
464534
33
3321
3220
A-8 A-8
*6*5
NOTES :
*1: The fan stops for 2 minutes after thermostat-OFF.
*2: A is 24°C when the preset temperature is 24°C or
more and A is the preset temperature when it is
under 24°C.
*3: SUL means Super Ultra Low.
*4: Calculated from difference in motor speed
between SUL and HIGH.
7-2-5. Automatic operation
([MODE] button on the remote control is set
to the automatic operation.)
(1) One of 3 operations (Cooling, Fan only or Heating)
is selected according to difference between the
preset temperature and the room temperature at
which the automatic operation has started, as
shown in Fig. 7-2-9. The Fan only operation
continues until the room temperature reaches a
level at which another mode is selected.
(2) Temporary Auto
When the TEMPORARY button on the indoor unit
is pushed, the preset temperature is fixed at 24°C
and the indoor unit is controlled as shown in
Fig. 7-2-9.
°C
Cooling operation
The louver moves to the position same
as Hi POWER operation.
+4
Cooling operation
0
Fan only operation
-1
Fig. 7-2-8 Cold draft preventing control
*5 and *6:
Table 7-2-1
Fan*5*6
speedStarting periodStabilized period
AUTO• Up until 12 minutes
passed after starting
the unit
• From 12 to 25 minutes
passed after starting
the unit and room
temperature is 3°C
lower than preset
temperature
Manual• Room temperature
(L – H)< Preset temperature
• From 12 to 25 minutes
passed after starting
the unit and room
temperature is
between preset
temperature and 3°C
lower than preset
temperature
• 25 minutes or more
passed after starting
the unit
• Room temperature
Preset temperature
–4°C
–3.5°C
Heating operation
RAS-18NKHP-ERAS-24NKP-E, RAS-24NKPX
(Room temp.) − (Preset temp.)
RAS-18NKP-E, RAS-18NKPX
Fig. 7-2-9
– 23 –
FILE NO. SVM-06004
62
55
54
Compressor
Outdoor fan
OFF
OFF
ON
ON
OFF
ON
Heat exchanger
temp.
(°C)
7-3. Hi PO
([Hi PO
contr
When [Hi PO
unit is in A.)uto
PO
WER mar
control and the unit oper
(1)anA
·
WER Mode
WER] b
utton on the remote
ol is pressed.)
WER] b
, Cooling or Heating oper
k is indicated on the displa
utomatic operation
The indoor unit oper·ates in according to the
utton is pressed while the indoor
ation, Hi
y of the remote
ates as f
ollo
current operation.
(2) Cooling operation
• The setting temperature drops 3°C.
(The value of the setting temperature on the
remote control does not change.)
• If the room temperature is higher than the
setting temperature by 3.5°C or more, the
horizontal louver moves to the Hi POWER
position automatically. Then when the room
temperature is 1°C less than the setting
temperature the horizontal louver returns
automatically.
• FAN speed : [AUTO]
If the room temperature is higher than the
setting temperature by 3.5°C or more, the air
conditioner operates at maximum airflow level.
If the room temperature is higher than the
setting temperature by less than 3.5°C, the air
conditioner operates at normal airflow level.
• FAN speed : One of 5 levels
If the room temperature is higher than the
setting temperature by 3.5°C or more, the air
conditioner operates at higher consecutive
airflow level. If the room temperature is higher
than the setting temperature by less than 3.5°C,
the air conditioner operates at normal airflow
level.
(3)
Heating operation
The preset temper
·
(The v
alue of the preset temper
ature increases 2
ature on the
remote control does not change
The indoor unit oper
mode e
(+2
(4)
The Hi POwsWER mode can not be set in Dr.y or F
xcept the preset temper
°C).
ates in nor
mal heating
ature is higher
only operation.
°C,
7-4.High-Temperature Limit Control
*Heat pump model only
The microcontroller detects the indoor heat exchanger
temperature to prevent pressure of a refrigerating cycle
from increasing excessively.
The compressor and outdoor fan motor are controlled
as shown in Fig. 7-4-1.
Fig. 7-4-1
7-5.Low-Temperature Limit Control
The microcontroller detects the indoor heat exchanger
temperature to prevent the indoor heat exchanger from
freezing.
The compressor and outdoor fan motor are controlled
as shown in Fig. 7-5-1.
Heat exchanger
temperature
(°C)
6
2
Compressor Outdoor fan
ON
Less than continues
for 5 minutes
OFF
Fig. 7-5-1
7-6.Defrost Operation *Heat pump model only
When the indoor unit is in heating operation, if the
refrigerant evaporation temperature detected by the
outdoor heat exchanger sensor is under the specified
temperature, the outdoor unit starts the defrosting
operation. At this time, the 4-way valve relay and the
outdoor fan motor are turned off. The indoor fan motor
is also turned off by the cold draft preventing control of
the indoor microcomputer. Then, [PRE. DEF.] lamp on
the indoor unit comes on.
The defrosting operation stops and the 4-way valve
relay, outdoor fan motor and the indoor fan motor are
turned on automatically when the refrigerant
evaporation increases to the specified temperature, or
when the defrosting time is over 12 minutes.
– 24 –
FILE NO. SVM-06004
7-6-1. Defrost starting condition
A-Zone : If -10°C > Teo ≥ − 18°C, defrost will
start when.
Teo - Te ≥ 2.5°C at teat 20 sec or
~ 30 min after operation.
B-Zone : If Te ≤ −18°C, defrost start instantaneously
(Suddenly) 00 ~ 25 min ofter operation
C-Zone : If -2ºC ≥ Teo ≥ −10°C defrost will start when
Teo - Te ≤ −3°C at least 20 sec or ~ 60 min
after operation.
7-6-2. Defrost finish condition.
1) If Te ≥ 3°C at least 60 sec -->4 way value on.
2) If Te ≥ 8°C --> 4 way value on.
Timing
Operation time (4 Loops = Tt)
Td1
Td2
Td3 Td4
Finish time recordStart time record
Defrost time rate : (Td/Tt) x 100
Heating time rate : (Tt - Td) x Tt
Fig. 7-6-2
-
25
-
FILE NO. SVM-06004
7-7.Auto Restart Function
The indoor unit is equipped with an automatic
restarting function which allows the unit to restart
operating with the set operating conditions in the event
of power supply being accidentally shut down. The
operation will resume without warning three minutes
after power is restored.
This function is not set to work when shipped from the
factory. Therefore it is necessary to set it to work.
7-7-1. How to set auto restart function
To set the auto restart function, proceed as follows:
The power supply to the unit must be on; the function
will not set if the power is off.
Push the [TEMPORARY] button located in the center
of the front panel continuously for three seconds.
The unit receives the signal and beeps three times.
The unit then restarts operating automatically in the
event of power supply being accidentally shut down.
When the unit is on standby (Not operating)
OperationMotions
Push [TEMPORARY] button for moreThe unit is on standby.
than three seconds.
The unit starts to operate.The green lamp is on.
0
The unit beeps three timesThe lamp changes from
3S
→
→
and continues to operate.green to orange.
TEMPORARY button
If the unit is not required to operate at this time, push [TEMPORARY]
button once more or use the remote control to turn it off.
After approx. three seconds,
When the unit is in operation
OperationMotions
Push [TEMPORARY] button for moreThe unit is in operation.The green lamp is on.
than three seconds.
The unit stops operating.The green lamp is turned off.
→
→
After approx. three seconds,
0
TEMPORARY button
The unit beeps three times.
3S
If the unit is required to operate at this time, push [TEMPORARY]
button once more or use the remote control to turn it on.
•While this function is being set, if the unit is in
operation, the orange lamp is on.
•This function can not be set if the timer operation
•While the filter check lamp is on, the
[TEMPORARY] button has the function of filter
reset button.
has been selected.
•When the unit is turned on by this function, the
louver will not swing even though it was swinging
automatically before shutting down.
– 26 –
7-7-2. How to cancel auto restart function
To cancel auto restart function, proceed as follows:
Repeat the setting prodedure: the unit receives the
signal and beeps three times.
The unit will be required to be turned on with the
remote control after the main power supply is turned
off.
When the unit is on standby (Not operating)
OperationMotions
Push [TEMPORARY] button for moreThe unit is on standby.
than three seconds.
→
FILE NO. SVM-06004
The unit starts to operate.The orange lamp is on.
→
After approx. three seconds,
0
TEMPORARY button
The unit beeps three timesThe lamp changes from
3S
and continues to operate.orange to green.
If the unit is not required to operate at this time, push [TEMPORARY]
button once more or use the remote control to turn it off.
When the unit is in operation
OperationMotions
Push [TEMPORARY] button for moreThe unit is in operation.The orange lamp is on.
than three seconds.
The unit stops operating.The orange lamp is turned off.
→
→
After approx. three seconds,
0
TEMPORARY button
The unit beeps three times.
3S
If the unit is required to operate at this time, push [TEMPORARY]
button once more or use the remote control to turn it on.
TEMPORARY button
•While this function is being set, if the unit is in
7-8. Filter Check Lamp
operation, the orange lamp is on.
When the elapsed time reaches 1000 hours, the filter
7-7-3. Power failure during timer operation
check lamp indicates. After cleaning the filters, turn off
the filter check lamp.
When the unit is in Timer operation, if it is turned off
because of power failure, the timer operation is
7-8-1. How to turn off filter check lamp
cancelled. Therefore, set the timer operation again.
Press [FILTER] button on the remote control.
Or push [TEMPORARY] button on the indoor unit.
Note:
If [TEMPORARY] button is pushed while the filter
check lamp is not indicating, the indoor unit will start
the Automatic Operation.
– 27 –
FILE NO. SVM-06004
7-9. Self-Cleaning function
Self-Cleaning function is designed to reduce humidity that causes mold to form inside the air conditioning unit.
This advanced, efficient system reduces moisture in the coil. When air conditioner is turned off, the internal fan
activates and dries the moisture in the coil for 20 minutes, then it turns off automatically.
Operation displayONOFFOFF
FCU fan
FCU louverOPENCLOSECLOSE
Timer display
Compressor
CDU fanON or OFF
rpm is depend on presetting. rpm is SL speed.
depend on presetting of timer function.depend on presetting of timer function.
depend on presetting per room temperature.
depend on presetting per room temperature.
Cool mode or dry mode
operation more than 10 mins.
ONON
ON or OFF
ON or OFF
8
Self-Cleaning mode
Turn off by remote controller or
timer-off function.
ON
OFFOFF
OFFOFF
8
operate 20 mins.
Automatically turn-off.
• The Self-Cleaning function is set as default at ex-factory.
• Self-Cleaning operation can stop manually by press [
7-
9-1. How to cancel Self-Cleaning function
To cancel the Self-Cleaning function, proceed as
follows:
• Press [
TEMPORARY] button one time or use remote
control to turn on air conditioner. The OPERATION
display will show in orange color (When AUTORESTART is ON) or green color (When AUTORESTART is OFF).
• Hold down the [
TEMPORARY] button for more than
20 seconds. (The air conditioner will stop suddenly
when the [
TEMPORARY] button is pressed but keep
holding it continue. Then will beep 3 times in the first
3 seconds but it is not related to Self-Cleaning
function)
• After holding about 20 seconds, the air conditioner
will beep 5 times without any blinking of display.
• The Self-Cleaning Operation had been cancelled.
] button of the remote control two more time.
9-2. How to set Self-Cleaning function.
7-
To set the Self-Cleaning function, proceed as follows.
• Press [
TEMPORARY] button one time or use remote
control to turn on air conditioner. The OPERATION
display will show in orange color (When AUTORESET is ON) or green color (When AUTORESTART is OFF).
• Hold down the [
TEMPORARY] button for more than
20 seconds. (The air conditioner will stop suddenly
when the [
holding it
TEMPORARY] button is pressed but keep
continue. Then will beep 3 times is the first
3 seconds but it is not related to Self-Cleaning
function)
• After holding about 20 seconds, the air conditioner
will beep 5 times and OPERATION display blinks
5 times.
• The Self-Cleaning function had been set.
OFF
ON or OFF
-
Operation time
Remarks
• Per setting of Self-Cleaning function above, AUTORESTART function had been cancelled. To set
AUTO-RESTART again, please follow item 7-
8-1.
TEMPORARY button
Remarks
• Per setting of Self-Cleaning function above, AUTORESTART function had been cancelled. To set
AUTO-RESTART again, please follow item 7-
– 28 –
8-1.
FILE NO. SVM-06004
7-10. QUIET Mode
Quiet mode is the system which, control the
revolving speed of indoor fan to work constantly
at lower than speed L. In addition, noise level of
indoor unit is less than usual.
When the [QUIET] button is pressed, the fan of the
indoor unit will be restricted the revolving speed at
speed L
again (cancel Quiet mode).
Remarks :
1. Quiet mode is unable to work in dry mode.
2. Quiet mode is appropriate to work with less
-
until the [QUIET] button is pressed once
cooling load and less heating load condition.
Because of the fan speed L- may cause not
enough the cooling capacity or heating capacity.
7-11. COMFORT SLEEP mode
The principles of comfort sleep mode are:
• Quietness for more comfortable.
• Save energy by changing room temperature
automatically.
• The air condition can shut down by itself
automatically.
7-11-1. Cooling mode
• The fan speed of indoor unit operates automatically,
it relates with the compressor's operation.
Compressor’s Operation Fan Speed
ONL
OFF SL
• The preset temperature will increase 1°C after the
Comfort sleep mode has operated for 1 hour and
the temperature will increase another 1°C after the
comfort sleep mode has operated for 2 hour. (The
value of the preset temperature on the remote control
does not change.)
• Press the [COMFORT SLEEP] button to choose the
operating hours. Repeat pressing to select the hours.
(1hr, 3hr, 5hr or 9hr)
• If the [COMFORT SLEEP] button is pressed again
means cancel comfort sleep mode.
7-11-2. Heating mode
• The fan speed of indoor unit operates automatically,
it relates with the compressor's operation.
Compressor’s Operation Fan Speed
ON L
OFF SL
-
-
Remarks:
1. Comfort sleep mode will not operate in dry mode
and fan only mode.
2. Comfort sleep mode is appropriate to work with less
cooling load and less heating load condition.
Because of the fan speed L- may cause not enough
the cooling capacity or heating capacity.
• The preset temperature will drop down 1°C after the
comfort sleep mode has operated for 1 hour and the
temperature will decrease another 1°C after the
comfort sleep mode has operated for 2 hour. (The
value of the preset temperature on the remote control.
dose not change.)
• Press the [COMFORT SLEEP] button to choose the
operating hours. Repeat pressing to select the hours.
(1hr, 3hr, 5hr or 9 hr)
• If the [COMFORT SLEEP] button is pressed again
means cancel comfort sleep mode.
-
29
-
FILE NO. SVM-06004
8. INSTALLATION PROCEDURE
8-1.Safety Cautions
For general public use
Power supply cord of Outdoor unit shall be more than 4 mm2 (H07RN-F or 245 IEC66 : polychloroprene
sheathed flexible cord) or 3.5 mm2 (AWG-12).
CAUTION
This appliance must be connected to the main power supply by means of a circuit breaker or a switch with a
contact separation of at least 3 mm.
If this is not possible, a power supply plug with earth must be used. This plug must be easily accessible after
installation. The plug must be disconnected from the power supply socket in order to disconnect the
appliance completely from the mains.
To Disconnect the Appliance from the Main Power Supply.
DANGER
• FOR USE BY QUALIFIED PERSONS ONLY.
• TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE
ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
• CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED
WRONGLY, ELECTRIC PARTS MAY BE DAMAGED.
• CHECK THE EARTH WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION.
• DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS.
FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
• TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD, PLACE THE UNIT
WELL AWAY (MORE THAN 2 M) FROM HEAT SOURCES SUCH AS RADIATORS, HEATORS,
FURNACE, STOVES, ETC.
• WHEN MOVING THE AIR-CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN, BE VERY
CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT (R410A) WITH ANY OTHER GASEOUS
BODY INTO THE REFRIGERATION CYCLE. IF AIR OR ANY OTHER GAS IS MIXED IN THE
REFRIGERANT, THE GAS PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNORMALLY
HIGH AND IT RESULTINGLY CAUSES BURST OF THE PIPE AND INJURIES ON PERSONS.
• IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE
INSTALLATION WORK, IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE REFRIGERANT GAS
IS HEATED BY FIRE OR SOMETHING ELSE, IT CAUSES GENERATION OF POISONOUS GAS.
WARNING
• Never modify this unit by removing any of the safety guards or bypassing any of the safety interlock
switches.
• Do not install in a place which cannot bear the weight of the unit.
Personal injury and property damage can result if the unit falls.
• Before doing the electrical work, attach an approved plug to the power supply cord.
Also, make sure the equipment is properly earthed.
• Appliance shall be installed in accordance with national wiring regulations.
If you detect any damage, do not install the unit. Contact your TOSHIBA dealer immediately.
CAUTION
• Exposure of unit to water or other moisture before installation could result in electric shock.
Do not store it in a wet basement or expose to rain or water.
• After unpacking the unit, examine it carefully for possible damage.
• Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify
the noise level of the unit or where noise and discharged air might disturb neighbors.
• To avoid personal injury, be careful when handling parts with sharp edges.
• Please read this installation manual carefully before installing the unit. It contains further important instruc-
tions for proper installation.
– 30 –
FILE NO. SVM-06004
REQUIREMENT OF REPORT TO THE LOCAL POWER SUPPLIER
Please make absolutely sure that the installation of this appliance is reported to the local power supplier
before installation. If you experience any problems, or if the installation is not accepted by the supplier, the
service agency will take adequate countermeasures.
Remark per EMC Directive 89/336/EEC (For Europe model only)
To prevent flicker impressions during the start of the compressor (technical process) following installation
conditions do apply.
1. The power connection for the air conditioner has to be done at the main power distribution. This distribution
has to be of an impedance.
Normally the required impedance is reached at a 32A fusing point. Air conditioner fuse has to be 16A max.!
2. No other equipment should be connected to this power line.
3. For detailed installation acceptance, please contact your power supplier whether its restriction does apply
for products like washing machines, air conditioners or electrical ovens.
4. For power details of the air conditioner, refer to the rating plate of the product.
– 31 –
8-2. Installation Diagram of Indoor and Outdoor Units
FILE NO. SVM-06004
(A
tta
c
h
to
7
Bio enzyme & Gingko filter
6
Sasa zeolite vitamin c filter
5
Filter frame
Before installing the
wireless remote control
• With the remote control cover
open, load the batteries supplied
correctly, observing their polarity.
2
Wireless remote control
Cover
170 mm or more
Hook
100 mm or more
Hook
1 Installation
plate
170 mm or mo
r
e
For the rear left and left piping
Wal l
Insert the cushion between
the indoor unit and wall, and
tilt the indoor unit for better
operation.
Do not allow the drain hose to
get slack.
Cut the piping
hole sloped
slightly .
Shield
th
e
fr
o
n
t p
a
n
e
l.) (A
tta
c
h
to
th
e
a
ir
filte
r
.)
pipe
Make sure to run the drain
hose sloped downward.
The auxiliary piping can be
connected to the left, rear left,
9
Pan head wood screw
4
Remote control holder
rear, right or bottom.
Right
Rear
Rear left
Bottom
Insulate the refrigerant pipes
Left
separately with insulation, not
together.
2
Wireles sremote control
6 mm thick heat resisting
polyethylene foam
3
Batteries
1
0
0
m
m
Extension drain hose
(Not available,
e
provided by installer)
mor
or
m
m
100
1
0
0
o
r
m
o
r
e
m
or
m
m
0
0
6
600 mm or more
ore
600
m
m
or
m
o
r
e
18 Class24 Class
32 −
−
Vinyl tape
Apply after carrying
out a drainage test.
Saddle
Extension
e
r
o
or m
m
m
0
10
600 mm or more
m
m
o
r
m
o
r
e
ore
or m
m
m
0
0
6
drain hose
(Not available,
provided by
installer)
6
0
0
m
m
o
r
m
o
r
e
8-3.Installation
8-3-1. Optional installation parts
FILE NO. SVM-06004
Part
Code
Refrigerant piping
Liquid side : ∅6.35 mm
A
Gas side : ∅12.70 mm (18 series
: ∅15.88 mm (24 series
Pipe insulating material
B
(polyethylene foam, 6 mm thick)
Putty, PVC tapes
C
<Fixing bolt arrangement of outdoor unit>
124 mm109 mm
321 mm
28 mm
86 mm
Air outlet
25
Æ
600 mm
Air inlet
Parts name
)
)
116 mm
90 mm
Drain outlet
Q'ty
One
each
1
One
each
Fig. 8-3-1.
• Secure the outdoor unit with fixing bolts and nuts if the unit is likely to be exposed to a strong wind.
• Use
∅ 8 mm or
∅ 10 mm anchor bolts and nuts.
• If it is necessary to drain the defrost water, attach drain nipple 10 to the bottom plate of the outdoor unit
before installing it.
– 33 –
8-3-2. Accessory and installation parts
FILE NO. SVM-06004
Part
No.
Part name (Q'ty)
1
Installation plate x 1
2
Wireless remote control x 1
3
Battery x 2
Others
Owner’s manual
Installation manual
Name
Part
No.
Part name (Q'ty)
4
Remote control holder x 1
5
Filter frame x 2
6
Sasa zeolite vitamin c filter x 2
Part
No.
Part name (Q'ty)
7
Bio enzyme & Gingko filter x 2
8
Mounting screw ∅4 x 25 s x 8
9
Pan head wood screw
∅3.1 x 16 s x 2
!
Drain nipple* x 1
The part marked with asterisk (*) is packaged with the
outdoor unit.
(For Heat pump model only)
– 34 –
FILE NO. SVM-06004
8-4.Indoor Unit
8-4-1. Installation place
• A place which provides the spaces around the
indoor unit as shown in the above diagram.
• A place where there is no obstacle near the air inlet
and outlet.
• A place that allows easy installation of the piping to
the outdoor unit.
• A place which allows the front panel to be opened.
CAUTION
• Direct sunlight to the indoor unit’s wireless
receiver should be avoided.
• The microprocessor in the indoor unit should not
be too close to RF noise sources.
(For details, see the owner’s manual.)
<Remote control>
• A place where there are no obstacles such as a
curtain that may block the signal from the indoor
unit.
• Do not install the remote control in a place exposed
to direct sunlight or close to a heating source, such
as a stove.
• Keep the remote control at least 1 m apart from the
nearest TV set or stereo equipment. (This is
necessary to prevent image disturbances or noise
interference.)
• The location of the remote control should be
determined as shown below.
Remote
control
(Top view)
Indoor unit
Reception
range
* : Axial distance
45
°
5 m
°
Remote control
m
5
45
Indoor unit
(Side view)
7 m
°
5
7
Reception
range
8-4-2. Cutting a hole and mounting installation
plate
<Cutting a hole>
When installing the refrigerant pipes from the rear.
Pipe
hole
6
5
m
m
The center of the pipe
hole is above the arrow.
100 mm
Fig. 8-4-2
1. After determining the pipe hole position on the
mounting plate (A), drill the pipe hole (∅65 mm) at
a slight downward slant to the outdoor side.
NOTE
• When drilling a wall that contains a metal lath, wire
lath or metal plate, be sure to use a pipe hole brim
ring sold separately.
<Mounting the installation plate>
For installation of the indoor unit, use the paper pattern
on the back.
Hook
* 7 m
170
120
55
65
Fig. 8-4-1
– 35 –
Pipe hole
Indoor unit
Hook
Thread
Weight
Fig. 8-4-3
Hook
Pipe hole
Installation
plate
8 Mounting screw
1
FILE NO. SVM-06004
<When the installation plate is directly mounted on
the wall>
1. Securely fit the installation plate onto the wall by
screwing it in the upper and lower parts to hook up
the indoor unit.
2. To mount the installation plate on a concrete wall
with anchor bolts, utilize the anchor bolt holes as
illustrated in the above figure.
3. Install the installation plate horizontally in the wall.
CAUTION
When installing the installation plate with a
mounting screw , do not use the anchor bolt hole.
Otherwise the unit may fall down and result in
personal injury and property damage.
Installation plate
<Keep horizontal direction>
Anchor
bolt
Projection
5 mm dia. hole
15 mm or less
8-4-3. Electrical work
1. The supply voltage must be the same as the rated
voltage of the air conditioner.
2. Prepare the power source for exclusive use with the
air conditioner.
NOTE
2
• Wire type : More than 1.5 mm
(H07RN-F or
245 IEC66) or 1.3 mm2 (AWG-16)
CAUTION
• This appliance can be connected to the mains in
the following way.
Connection to fixed wiring:
A switch or circuit breaker which disconnects all
poles and has a contact separation of at least
3 mm must be incorporate in the fixed wiring. An
approved circuit breaker or switches must used.
NOTE
• Perform wiring works so as to allow a generous
wiring capacity.
88
8 Mounting
88
screw
ss
∅4 x 25
s
ss
Clip anchor
(local parts)
Fig. 8-4-4
CAUTION
Failure to firmly install the unit may result in
personal injury and property damage if the unit falls.
• In case of block, brick, concrete or similar type
walls, make 5 mm dia. holes in the wall.
• Insert clip anchors for appropriate mounting screws
8.
NOTE
• Secure four corners and lower parts of the
installation plate with 6 to 8 mounting screws to
install it.
– 36 –
8-4-4. Wiring connection
Air Inlet grille
Front panel
FILE NO. SVM-06004
CAUTION
• Be sure to refer to the wiring system diagram
labeled inside the front panel.
• Check local electrical cords and also any specific
wiring instructions or limitations.
1
Cord clamp
Screw
Terminal block
Connecting cable
Earth
line
Terminal
cover
Screw
2
Fig. 8-4-5
<How to connect the connecting cable>
Wiring of the connecting cab le can be carried out
without remo ving of the fr ont panel.
Connecting cable
a
b
o
u
t 1
5
c
m
Fig. 8-4-6
<Stripping length of connecting cable>
10
10
40
50
Earth line
Fig. 8-4-7
NOTE
Use stranded wire only.
• Wire type : More than 1.5 mm2 (H07RN-F or
245 IEC66) or 1.3 mm2 (AWG-16)
1. Remove the air inlet grille.
Open the air inlet grille upward and pull it toward
you.
2. Remove the terminal cover and cord clamp.
3. Insert the connecting cable (according to local
cords) into pipe hole on the wall.
4. Take out the connecting cable through the cable
slot on the rear panel so that it protrudes about
15 cm from the front.
5. Insert the connecting cable fully into the terminal
block and secure it tightly with screws.
6. Tightening torque : 1.2 N·m (0.12 kgfám).
7. Secure the connecting cable with the cord clamp.
8. Fix the terminal cover, rear plate bushing and air
inlet grille on the indoor unit.
Fig. 8-4-8
NOTE
Connect the earth line to the metallic part (i mark)
located at the side of 3P terminal.
<How to install the air inlet grille on the indoor unit>
• When attaching the air inlet grille, the contrary of
the removed operation is performed.
– 37−
Fig. 8-4-9
FILE NO. SVM-06004
8-4-5. Piping and Drain Hose Installation
<In case of rightward piping>
• After scribing slits of the body-right by a knife or a
making-off pin, cut them by a pair of nippers or the
like.
Slit (Body-right)
Fig. 8-4-10
<In case of downward piping>
• After scribing slits of the body-right by a knife or a
making-off pin, cut them by a pair of nippers or the
like.
To connect the pipe after installation of the unit (figure)
(To the forefront of flare)
400 mm
300 mm
R 30 mm (Use polisin (polyethylene)
core or the like for bending pipe.)
43 mm
80
Liquid side
Gas side
Outward form of indoor unit
Use the handle of screwdriver, etc.
Fig. 8-4-12
NOTE
If the pipe is bent incorrectly, the indoor unit may
unstably be set on the wall.
After passing the connecting pipe through the pipe
hole, connect the connecting pipe to the auxiliary pipes
and wrap the facing tape around them.
Slit (Body-right)
Fig. 8-4-11
<Left-hand connection with piping>
Bend the connecting pipe so that it is laid within 43 mm
above the wall surface. If the connecting pipe is laid
exceeding 43 mm above the wall surface, the indoor
unit may unstably be set on the wall. When bending the
connecting pipe, make sure to use a spring bender so
as not to crush the pipe.
Bend the connection pipe within a radius of 30 mm.
CAUTION
• Bind the auxiliary pipes (two) and connecting
cable with facing tape tightly. In case of leftward
piping and rear-leftward piping, bind the auxiliary
pipes (two) only with facing tape.
Indoor unit
Auxiliary pipes
Installation plate
• Carefully arrange pipes so that any pipe does not
stick out of the rear plate of the indoor unit.
• Carefully connect the auxiliary pipes and
connecting pipes to each other and cut off the
insulating tape wound on the connecting pipe to
avoid double-taping at the joint, moreover, seal
the joint with the vinyl tape, etc.
• Since dewing results in a machine trouble , make
sure to insulate both the connecting pipes. (Use
polyethylene foam as insulating material.)
• When bending a pipe, carefully do it not to crush
it.
Connecting cable
Drain hose
– 38 –
FILE NO. SVM-06004
8-4-6. Indoor unit fixing
1. Pass the pipe through the hole in the wall, and hook
the indoor unit on the installation plate at the upper
hooks.
2. Swing the indoor unit to right and left to confirm that
it is firmly hooked up on the installation plate.
3. While pressing the indoor unit onto the wall, hook it
at the lower part on the installation plate. Pull the
indoor unit toward you to confirm that it is firmly
hooked up on the installation plate.
1
2
Hook
Hook here
1 Installation
plate
Fig. 8-4-13
• For detaching the indoor unit from the installation
plate, pull the indoor unit toward you while pushing
its bottom up at the specified parts.
8-4-7. Drainage
1. Run the drain hose sloped downwards.
NOTE
• Hole should be made at a slight downward slant on
the outdoor side.
Do not form the
Do not rise the
drain hose.
50 mm
or more
Do not put
the drain
hose end
into water.
drain hose into
a wavy shape.
Do not put
the drain
hose end in
the drainage
ditch.
Fig. 8-4-15
2. Put water in the drain pan and make sure that the
water is drained out of doors.
3. When connecting extension drain hose, insulate the
connecting part of extension drain hose with shield
pipe.
PushPush
Push
(unhook)
Fig. 8-4-14
Shield pipe
Drain hose
Inside the room
Extension drain hose
Fig. 8-4-16
CAUTION
Arrange the drain pipe for proper drainage from the
unit.
Improper drainage can result in dew-dropping.
This air conditioner has the structure designed to drain
water collected from dew, which forms on the back of
the indoor unit, to the drain pan.
Therefore, do not store the power cord and other parts
at a height above the drain guide.
Wall
Drain guide
Space for pipes
– 39 –
Fig. 8-4-17
FILE NO. SVM-06004
8-5.Outdoor Unit
8-5-1. Installation place
• A place which provides the spaces around the
outdoor unit as shown in the left diagram.
• A place which can bear the weight of the outdoor
unit and does not allow an increase in noise level
and vibration.
• A place where the operation noise and discharged
air do not disturb your neighbors.
• A place which is not exposed to a strong wind.
• A place free of a leakage of combustible gases.
• A place which does not block a passage.
• When the outdoor unit is to be installed in an
elevated position, be sure to secure its feet.
• An allowable length of the connecting pipe is up
15 m. (Refer to the table of TO CHARGEREFRIGERANT for detail.)
• An allowable height level is up to 8 m. (RAS-18 class)
or 10 m. (RAS-24 class)
• A place where the drain water does not raise any
problem.
CAUTION
1. Install the outdoor unit without anything blocking
the air discharging.
2. When the outdoor unit is installed in a place
exposed always to a strong wind like a coast or
on a high story of a building, secure
the normal fan operation using a duct or a wind
shield.
3. Specially in windy area, install the unit to prevent
the admission of wind.
4. Installation in the following places may result in
trouble.
Do not install the unit in such places.
• A place full of machine oil.
• A saline-place such as the coast.
• A place full of sulfide gas.
• A place where high-frequency waves are likely
to be generated as from audio equipment,
welders, and medical equipment.
8-5-2. Refrigerant piping connection
1. Cut the pipe with a pipe cutter.
90°
Obliquity
Roughness
Fig. 8-5-2
2. Insert a flare nut into the pipe, and flare the pipe.
• Projection margin in flaring : A (Unit : mm)
A
Die
Pipe
Fig. 8-5-3
Outer dia.
of copper pipe
RigidImperial
A
6.351.0 to 1.51.5 to 2.0
12.701.0 to 1.52.0 to 2.5
15.881.0 to 1.52.0 to 2.5
<Tightening connection>
Align the centers of the connecting pipes and tighten
the flare nut as far as possible with your fingers. Then
tighten the nut with a spanner and torque wrench as
shown in the figure.
CAUTION
• Do not apply excess torque.
• Otherwise, the nut may crack depending on the
conditions.
Warp
Strong
wind
Fig. 8-5-1
– 40 –
FILE NO. SVM-06004
(Unit : N·m)
Outer dia.
of copper pipe
Tightening torque
∅6.35 mm16 to 18 (1.6 to 1.8 kgf·m)
∅12.70 mm50 to 62 (5.0 to 6.2 kgf·m)
∅15.88 mm65 to 80 (6.5 to 8.0 kgf·m)
• Tightening torque of flare pipe connections
Flare at indoor unit side
Flare at outdoor unit side
Fig. 8-5-4
Flare nutHalf union
Externally
threaded side
Use a wrench to secure.
Use a torque wrench to tighten.
Internally
threaded side
Fig. 8-5-5
CAUTION
•
KEEP IMPORTANT 4 POINTS FOR PIPING WORK
(1) Take away dust and moisture (Inside of the
connecting pipes.)
(2) Tight connection (between pipes and unit)
(3) Evacuate the air in the connecting pipes using
VACUUM PUMP.
(4) Check gas leak (connected points)
8-5-3. Evacuating
After the piping has been connected to the indoor unit,
you can perform the air purge together at once.
AIR PURGE
Evacuate the air in the connecting pipes and in the
indoor unit using a vacuum pump. Do not use the
refrigerant in the outdoor unit. For details, see the
manual of the vacuum pump.
<Using a vacuum pump>
Be sure to use a vacuum pump with counter-flow
prevention function so that inside oil of the pump does
not flow backward into pipes of the air conditioner
when the pump stops.
1. Connect the charge hose from the manifold valve to
the service port of the gas side packed valve.
2. Connect the charge hose to the port of vacuum
pump.
3. Open fully the low pressure side handle of the
gauge manifold valve.
4. Operate the vacuum pump to start for evacuating.
Perform evacuating for about 15 minutes if the
piping length is 20 meters. (15 minutes for
20 meters) (assuming a pump capacity of 27 liters
per minute.) Then confirm that the compound
pressure gauge reading is –101 kPa (–76 cmHg).
5. Close the low pressure side valve handle of gauge
manifold.
6. Open fully the valve stem of the packed valves
(both side of Gas and Liquid).
7. Remove the charging hose from the service port.
8. Securely tighten the caps on the packed valves.
Compound pressure gauge
-101 kPa (-76 cmHg)
Handle Lo
Pressure gauge
Manifold valve
Handle Hi
(Keep full closed)
– 41 –
Charge hose
Connecting pipe
Packed valve at liquid side
Packed valve at gas side
Service port
(Valve core (Setting pin))
Fig. 8-5-6
Charge hose
Vacuum pump
adapter for
counter-flow
prevention
Vacuum
pump
FILE NO. SVM-06004
70
60
L
N
10
70
10
10
80
10
123
TO CHARGE REFRIGERANT
Refrigerant
No need to charge
extra refrigerant
Need to chargeOver 15 m up toOver 15 m up to
extra refrigerant25 m (20 g/m)20 m (20 g/m)
24 class 18 class
15 m or less15 m or less
<Packed valve handling precautions>
• Open the valve stem all the way out; but do not try
to open it beyond the stopper.
• Securely tighten the valve stem cap with torque in
the following table:
Gas sideTightening torqueA
Gas side 65 to 80 N·m 4 mm
(∅15.88 mm)(6.5 to 8.0 kgf·m)
Gas side60 to 62 N·m4 mm
(∅12.70 mm)(6.0 to 6.2 kgf·m)
Liquid side16 to 18 N·mSame as
(∅6.35 mm)(1.6 to 1.8 kgf·m)Gas side
Service port
9 to 10 N·m
(0.9 to 1.0 kgf·m)
• Hexagonel wrench : A (Unit : mm)
Hexagonal wrench
is required.
A
<Stripping length of connecting cable>
Terminal block
LN132
Terminal
screw
Cord clamp
Power supply cord
Earth line
Power supply cord
Earth line
Screw
Cord clamp
Connecting cable
Connecting cable
Fig. 8-5-8
Model
Power source
Maximum
running current
Plug socket &
fuse rating
Power cord4 mm2 (H07RN-F or 245 IEC66) or 3.5 mm2 (AWG-12)
24 class 18 class
50 Hz, 220 - 240 V Single phase
50 Hz, 220 V Single phase
(For RAS-24NKPX / RAS-24N2AX and
RAS-B18NKPX / RAS-18N2AX model)
18A16A
20A20A
Fig. 8-5-7
8-5-4. Wiring connection
1. Remove the valve cover from the outdoor unit.
2. Connect the connecting cable to the terminal as
identified with their respective matched numbers on
the terminal block of indoor and outdoor unit.
3. When connecting the connecting cable to the
outdoor unit terminal, make a loop as shown in the
installation diagram of indoor and outdoor unit, to
prevent water coming in the outdoor unit.
4. Insulate the unused cords (conductors) from any
water coming in the outdoor unit. Proceed them so
that they do not touch any electrical or metal parts.
CAUTION
• Wrong wiring connection may cause some
electrical parts burn out.
• Be sure to comply with local codes on running
the wire from indoor unit to outdoor unit (size of
wire and wiring method etc).
• Every wire must be connected firmly.
NOTE: Connecting cable
• Wire type: More than 1.5 mm2 (H07RN-F or
245 IEC66) or 1.3 mm2 (AWG-16)
– 42 –
FILE NO. SVM-06004
8-6. How to Set Remote Control Selector
Switch
When two indoor units as installed in seperated rooms,
there is no need to change the selector switch.
<Remote control selector switch>
• When two indoor units are installed in the same
room or the adjacent two rooms, they may be
controlled simultaneously with a single remote
control. To prevent this, set either unit and its
remote control to B setting. (Both units are set to A
setting before shipment.)
• The remote control signal is not received when the
indoor unit setting is different from the remote
control one.
1. Set the remote control selectors witch with the
indoor unit.
1) Turn the circuit breaker of the main power switch off
before setting the selector switch.
2) Remove the Air inlet grille and Front panel. (Refer to
Chapter 10-1, procedure 1 )
3) Open the Electrical part cover (Refer to chapter
10-1, procedure 2 ), then cut the jumper (J90)
with only the nippers.
2. Set the remote control selector switch with the
remote control
[B] is indicated on the liquid crystal display when
setting remote control selector switch to B. [A] is
not indicated on the display even if the selector
switch is set to A.
1) Load the remote control with the batteries.
2) Press the [CHK] button using something with
sharp point. (The preset temperature on the remote
control changes to [00].)
3) Press the [MODE] button while pressing the
[CHK] button, [B] is indicted at the right of the
present temperature display.
• To reset the switch to the [A] setting, press the
[MODE] button again while pressing the [CHK]
button.
CAUTION
Do not use any other sharp tools (such
as cutters, pliers, or the like). Such tools
may cause breakage or damage.
See Fig. 8-6-1
Fig. 8-6-1
[MODE] button
[CHK] button
Fig. 8-6-2
3. Confirm that the indoor unit can operate with
the new setting.
− 43 −
FILE NO. SVM-06004
8-7.Others
8-7-1. Gas leak test
Electric parts cover
D
Flare nut connections
(Outdoor unit)
B
Valve stem cap connection
Fig. 8-7-1
• Check the flare nut connections, valve stem cap
connections and service port cap connections for
gas leak with a leak detector or soap water.
8-7-2. Test operation
C
Flare nut connections
(Indoor unit)
Valve stem cap
connection
A
Service cap connection
8-7-3. Auto restart setting
This product is designed so that, after a power failure,
it can restart automatically in the same operating mode
as before the power failure.
Information
The product was shipped with Auto Restart function
in the off position. Turn it on as required.
<How to set the auto restart>
• Press and hold the TEMPORARY button for about
3 seconds. After 3 seconds, the electronic beeper
makes three short beeps to tell you the Auto
Restart has been selected.
• To cancel the Auto Restart, follow the steps
described in the section Auto Restart Function of
the Owner’s Manual.
To switch the TEST RUN (COOL) mode, press
TEMPORARY b utton for 10 sec.
(The beeper will make a short beep.)
TEMPORARY button
Fig. 8-7-2
– 44 –
9. TROUBLESHOOTING CHART
FILE NO. SVM-06004
9-1. Troubleshooting Pr ocedure :
9-2-2. Incorrect cable connection between Indoor
and outdoor units
Follow the details of 9-2. Basic Check Items.
If there is no trouble corresponding to 9-2, check
whether or not there are faulty parts following
9-4. Self-Diagnosis by Remote Control.
9-2. Basic Check Items
The indoor unit is connected to the outdoor unit with
4 cables. Check that the indoor and outdoor units have
been properly connected with terminals assigned the
same numbers. If the connectors are not properly
connected, the outdoor unit will not operate normally,
or OPERATION lamp and TIMER lamp will blink (5 Hz).
9-2-1. Power supply voltage
The line voltage must be AC 220 – 240 V. If it is not
within this range, the air conditioner may not operate
normally.
9-2-3. Program control
The microcontroller operates as shown in Table 9-2-1
to control the air conditioner. If there are any operational problems, check whether or not the problems
correspond to Table 9-2-1. If they correspond to the
Table, they are not problems with the air conditioner,
but they are indispensable operations to control and
maintain the air conditioner properly.
Table 9-2-1
No.Operation of air conditionerDescriptions
1When the main power supply is turned
on, the OPERATION lamp on the
indoor unit blinks.
2The indoor fan motor speed does not
change in the Dry operation.
3The compressor is not turned off even
though the room temperature is in the
range that the compressor is turned off.
4The compressor is not turned on and
off even though the thermo control is
operated in the Dry operation.
*5The PRE-DEF. lamp is indicated when
the Heating operation starts.
The OPERATION lamp blinks to indicate that power is turned on. If the
[ ] button is pressed, the lamp stops blinking.
The indoor fan motor speed is automatically controlled in the Dry
operation.
The compressor has a function that it is not turned off for 3 minutes
after it is turned on even though the room temperature is in the range
that the compressor is turned off.
In the Dry operation, the compressor is turned on and off automatically
at the regular intervals, independent of the thermo control.
The PRE-DEF. lamp is indicated during the Defrosting operation or if
the indoor heat exchanger temperature is low when the Heating
operation starts. At this time, the indoor fan motor stops to prevent
cold air from blowing in the room.
*6The outdoor fan motor stops in the
Heating operation.
7The compressor is not turned on even
though the room temperature is in the
range that the compressor is turned on.
8The operation mode changes in the
Automatic operation.
9The Fan only operation continues in the
Automatic operation.
10The ECO operation or Hi-POWER
operation does not work.
11When [Hi POWER] button is pressed,
the display on the remote control does
not change at all.
Note *5 and *6 are for Heat pump model :
When the indoor heat exchanger temperature is high, the outdoor fan
motor is stopped by the high-temperature limit control operation.
The compressor is not turned on in the restart delay timer (3-minutes
timer) operation. It is also not turned on after the power supply is
turned on because of this timer operation.
In Automatic operation, the room temperature is detected all time
for control fan speed and the operation mode is changed every
15 minutes according to difference between the room temperature
and the preset temperature.
When the room temperature is in the range
(Preset temperature ± 1°C), the Fan only operation is selected.
These operations do not work when the unit is in the Dry
operation or Fan only operation.
The display on the remote control does not change when
[Hi POWER] button is pressed. However the microcontroller gives
commands to change the preset temperature and air flow level.
– 45 –
FILE NO. SVM-06004
9-3. Primary Judgement
9-3-1. Role of indoor unit controller
The indoor unit controller receives the operation
commands from the remote control and executes
them.
• Temperature measurement at the air outlet of the
indoor heat exchanger by the indoor temperature
sensor
• Temperature setting of the indoor heat exchanger by
the heat exchanger sensor
• Louver motor control
• Indoor fan motor operation control
• LED display control
• Transferring of operation commands to the outdoor
unit
Table 9-3-1
LampsSelf-diagnosis
AOPERATION lamp is blinking. (1 Hz)
BOPERATION lamp is blinking. (5 Hz)
COPERATION lamp is blinking. (5 Hz)
DOPERATION lamp is blinking. (5 Hz)
EOPERATION lamp is blinking. (5 Hz)
FOPERATION and TIMER lamps are blinking.
(5 Hz)
9-3-2. Failure diagnosis
The indoor unit diagnoses the operation condition and
indicates the information of the self-diagnosis with the
lamps on the display panel of the indoor unit.
Power failure (when the power supply is turning on)
Thermo sensor (TA) short or break
Heat exchanger sensor (TC) short or break
Indoor fan motor lock or failure
Indoor P.C. board failure
Wrong wiring of connecting cable
GOPERATION, TIMER and PRE-DEF.
(or FAN ONLY for cooling only model) lamps
are blinking.
Table 9-3-2 Diagnosis by detective operation
SymptomCheckPrimary judgement
The remote control
does not work.
The outdoor fan
does not rotate.
Turn off the power supply once,
then turn it on. Try to operate
the remote control.
The compressor operates.
The compressor does not operate.
Cycle failure
• Gas shortage or other refrigerant cycle trouble
• Heat exchanger sensor open, break or short
• Overload relay or thermostat trouble of compressor
The remote control
still does not work.
The remote control
works.
The indoor unit (and/or remote
control) is/are defective .
OK.
The outdoor unit (Outdoor fan
motor) is defective .
An internal part of the
compressor or P.C. board is
defective.
– 46 –
9-4. Self-Diagnosis by Remote Control
(Check Code)
(1) If the lamps are indicated as shown B to G in Table
9-3-1, exchanger the self-diagnosis by the remote
control.
(2) When the remote control is set to the service
mode, the indoor controller diagnoses the
operation condition and indicate the information of
the self-diagnosis on the display of the remote
control with the check codes. If a fault is detected,
all lamps on the indoor unit will blink at 5 Hz and it
will beep for 10 seconds (Pi, Pi, Pi....). The timer
lamp usually blinks (5 Hz) during the self-diagnosis.
9-4-1. How to use remote control in service mode
FILE NO. SVM-06004
(1) Press [CHK] button with a tip of pencil to set the
remote control to the service mode.
• “00” is indicated on the display of the remote
control.
• The timer lamp on the indoor unit blinks
continuously. (5 times per 1 sec.)
(2) Press [TIMER 8] button.
If there is no fault with a code, the indoor unit will
beep once (Pi) and the display of the remote
control will change as follows:
00
01
• Check the unit with all 35 check codes (00 to 22).
as shown in Table 9-4-1.
• Press [TIMER 9] button to change the check
code backwards.
If there is a fault, the indoor unit will beep f or 10
seconds (Pi, Pi, Pi...).
Note the check code on the display of the remote
control.
• 2-digits alphanumeric will be indicated on the
display.
• All lamps on the indoor unit will blink. (5 times
per 1 sec.)
(3) Press [CLR] button. After service finish for clear
service code in memory.
• “7F” is indicated on the display of the remote
control.
1d
1E0222
• Alphanumeric characters are used for the check code.
is 5.is 6.
is A.is B.
is C.is D.
* This illustration is only for Heat pump model.
For Cooling only model, there is not the ( ) symbol.
– 47 –
(4) Press [ ] button to release the service
mode.
• The display of the remote control returns to as it
was before service mode was engaged.
Table 9-4-1
Block levelDiagnosis function
Check
codecodestatus
Block
Indoor
P.C. board
Cable
connection
Outdoor
P.C. board
Other parts
(including
compressor)
Check
Symptom
The indoor thermo sensor (TA) is
defective.
Disconnection or short-circuit
The indoor heat exchanger
sensor (TC) is defective.
Disconnection or short-circuit
The indoor fan motor or its circuit
is defective.
The part other than the above
parts on the indoor P.C. board is
defective.
EEPROM access error
IOL operation
The serial signals can not be
transmitted and received between
indoor and outdoor units.
The crossover wire is
•
connected wrongly.
The serial signal transmitting
•
circuit on the outdoor P.C. board
is defective.
The serial signal receiving
•
circuit on the indoor P.C. board
is defective.
The operation command signals
are not transmitted from the
indoor unit to the outdoor unit.
The outdoor thermo sensor (TE)
is defective.
Disconnection or short-circuit
The outdoor heat exchanger (TD)
sensor is defective.
Disconnection or short-circuit
The reply serial signal has been
transmitted when starting the
unit, but stops being transmitted
shortly after.
1. Compressor thermo operation
•
Gas shortage
• Gas leak
2. Instantaneous power failure
The discharge temperature is
over 120°C.
The IOL operation is defective.
Unit
Operation
continues.
Operation
continues.
All off
Operation
continues.
All off
Operation
continues.
Operation
continues.
All off
All off
Operation
continues.
All off
All off
Condition
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
defected. And it
returns to the
normal condition
when recovering
from errors.
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
defected. And it
returns to the
normal condition
when recovering
from errors.
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
detected.
FILE NO. SVM-06004
Judgement and action
1. Check the indoor thermo sensor (TA).
2. Check the indoor P.C. board.
1. Check the indoor heat exchanger
sensor (TC).
2. Check the indoor P.C. board.
1. Check the connector circuit of the
indoor fan motor (CN10).
2. Check the indoor fan motor.
3. Check the indoor P.C. board.
1. Check the indoor P.C. board.
(EEPROM and peripheral circuits)
Overload operation of refrigerating cycle
1. In the case of the outdoor unit not
operating at all;
•
Check the crossover cable and
connect it properly.
•
Check the outdoor P.C. board.
2. In the case of the outdoor unit operating
normally;
•
Check whether or not both of serial
LED (Green) and serial LED (Orange)
is blinking.
If the serial LED (Green) is not
blinking, check the outdoor P.C. board.
If the serial LED (Orange) is not
blinking, check the indoor P.C. board.
If the operation command signals continue
to be transmitted between 2 and 3 of the
indoor terminal block, replace the outdoor
P.C. board.
1. Check the outdoor thermo sensor (TE).
2. Check the outdoor P.C. board.
1. Check the outdoor heat exchanger
sensor (TD).
2. Check the outdoor P.C. board.
1. Repeatedly turn the indoor unit on and
off with the interval of approx. 10 to 40
minutes. (The check code is not
indicated during operation.) And supply
gas. (Check gas leak.)
2. The indoor unit operates normally
during the check.
If the reply serial signal continues to be
transmitted between 2 and 3 of the
indoor terminal block, replace the
outdoor P.C. board.
If the signal stops between them,
replace the indoor P.C. board.
1. Check the heat exchanger sensor (TD).
2. Gas purging
When turning on the unit, the normal
phase (RST) is detected but T-R waveform
has not been detected for 120 seconds or
more.
−48−
9-5. How To Diagnose Faulty Parts
[04 Serial signal error] (Heat pump model)
FILE NO. SVM-06004
Operation
Check item
Conceivable principle cause
Measure
Does outdoor
unit operate?
YES
NO
Are 1, 2 and 3 crossover
wires connected properly?
YES
Is connector
connected properly?
YES
Does LED (Orange) on
outdoor P.C. board blink?
YES
Does LED (Green) on
outdoor P.C. board blink?
YES
NO
NO
NO
NO
Outdoor P.C. board
is defective.
Indoor P.C. board
is defective.
Item by symptoms
Connect crossover
wires properly.
Connect connector
properly.
Replace
P.C. board.
Replace
P.C. board.
[08 Four-way valve error] (Heat pump model)
Does four-way valve
operate properly?
YES
Is TC sensor
resistance value
(10 kΩ at 25°C) normal?
NO
NO
YES
Does coil terminal
have 220 − 240 V
in heating operation?
YES
Are circuit
wires normal?
YES
Is outdoor P.C. board
normal?
YES
YES
NO
NO
Four-way valve
is defective.
Outdoor P.C. board
is defective.
(CN11 220 − 240 V)
Indoor P.C. board
is defective.
Replace
Four-way valve
Circuit check/modification
Replace
P.C. board.
Replace
P.C. board.
Replace TC sensor.
– 49 –
[09 Other cycle error] (1) (Heat pump model)
FILE NO. SVM-06004
NO
Replace TC
sensor.
YES
Connect TC
sensor properly.
Does compressor operate?
YES
Is compressor
turned off shortly?
NO
Is TC sensor
resistance value
(10 kΩ at 25°C) normal?
YES
Is TC sensor
disconnected from
the sensing element?
NO
NO
YES
Does inner
overload relay
(in compressor)
operate?
NO
Is circuit wiring
normal?
YES
Is outdoor P.C.
board normal?
YES
YES
NO
NO
Check charged amount of refrigerant.
Check defective overload.
Check compressor.
Failure
compressor.
Wiring check/modification
Outdoor P.C. board
is defective.
Indoor P.C. board
is defective.
Replace
Replace
P.C. board.
Replace
P.C. board.
[09 Other cycle error] (2)
NO
Connect
connector
properly.
NO
Replace
condenser.
NO
Replace
fan motor.
Is connector
connected properly?
Is condenser normal?
Is indoor fan
motor normal?
YES
YES
YES
NO
Does indoor
fan operate?
Are filters clogged?
Is TC sensor
resistance value
(10 kΩ at 25°C) normal?
Is charged amount
of refrigerant normal?
Is outside air
low load?
YES
NO
YES
YES
NO
YES
NO
NO
YES
Clean filters.
Replace
TC sensor.
Anti-freezing operation
Charge
refrigerant.
Anti-freezing operation
Indoor P.C. board
is defective.
– 50 –
Replacd
P.C. board.
[0C Indoor TA sensor error]
FILE NO. SVM-06004
Is CN03 (TA sensor connector)
connected properly?
YES
Is TA sensor resistance value
(10 kΩ at 25°C) normal?
YES
[0d Indoor TC sensor error]
Is CN01 (TC sensor connector)
connected properly?
YES
NO
NO
NO
Indoor P.C. board is defective.
Connect CN03 properly.
Replace T A sensor.
Replace P.C. board.
Connect CN01 properly.
Is TC sensor resistance value
(10 kΩ at 25°C) normal?
YES
NO
Indoor P.C. board is defective.
[18 outdoor TE sensor error] (Heat pump model)
Is TE sensor connector
connected properly?
YES
Is TE sensor resistance value
(10 kΩ at 25°C) normal?
YES
NO
NO
Replace TC sensor.
Replace P.C. board.
Connect connector
properly.
Replace TE sensor.
Indoor P.C. board is defective.
– 51 –
Replace P.C. board.
[19 outdoor TD sensor error] (Heat pump model)
FILE NO. SVM-06004
Is TD sensor
connected properly?
YES
Is TD sensor resistance value
(50 kΩ at 25°C) normal?
YES
NO
NO
Outdoor P.C. board is defective.
[1E Discharge temp. error] (Heat pump model)
Connect connector
properly.
Replace TD sensor.
Replace P.C. board.
Is protective
controller such as discharge
thermostat normal?
YES
Is charged amount
of refrigerant normal?
YES
Is overload relay normal?
NO
Is TD sensor resistance value
(50 kΩ at 25°C) normal?
YES
NONO
NO
YES
NO
Are wires connected
to connector properly?
Outdoor P.C. board is defective.
Connect wires to
connector properly.
Check and modify charged
amount of refrigerant.
Unit operates normally.
Replace TD sensor.
Replace P.C. board.
– 52 –
9-6. Troubleshooting for Indoor unit
Operation
Measure
Item by symptoms
Check item
Conceivable principle
cause
9-6-1. Power can not be turned on. (The unit does not operate at all.)
<Primar check>
(1) Is the supply voltage normal?
(2) Is the connection to the AC output OK?
(3) Is the fuse (F01) blown?
Turn off power
supply once, and 5
second later, turn it
on again.
NO
Is OPERATION
lamp blinking?
YES
Does
Is it possible to
turn on power
supply by
pressing
[START/STOP]
button on remote
control?
YES
NO
transmission
mark on
remote
control flash
normally, and
is its signal
transmitted
properly?
YES
NO
FILE NO. SVM-06004
Remote control is
defective.
Refer to 9-9
" Troubleshooting for
Remote Control."
Is DC 310 -
340V across
C63?
Are DC 12V,
across C66?
YES
YES
NO
NO
Is fuse (F01)
control board
Is voltage (DC
12V or 5V)
NO
indicated on
rear of indoor
control board
Turn off breaker
once and turn it
on again after
removing motor.
of indoor
blown?
NO
normal?
YES
YES
Parts (R21,
R22, SG01,
C01, DB01,
C02,
M01 and IC04)
are defective.
Are DC 12V,
across C66?
YES
– 53−
NO
Does the fan
motor
connector
between 1
and 2 short-
circuit?
NO
Microcomputer is
defective.
M01 is
def
ec
tive.
Unit operates
normally.
YES
Replace main P.C.
board.
Replace motor.
FILE NO. SVM-06004
9-6-2. Only the indoor fan does not operate
<Primary chec k>
(1) Is it possible to detect the power supply voltage (200 − 240V) between 1 and 2 on the terminal block?
(2) Does the indoor fan motor operate in cooling operation?
(In heating operation, the indoor fan motor does not operate for approximately 5 minutes after it is turned on,
to prevent a cold air from blowing in.)
Shut off the
power supply once.
Turn the power supply.
Does the fan stop in
no operating status?
YES
Start the operation
with low fan setting
in cool operation.
Does the fan rotate?
YES
Change the setting of
cooling to high fan.
Does the fan speed
become higher?
YES
NO
NO
NO
Control P.C. board is defective.
Does AC 120V
or higher voltage apply
to between red and black
lead of fan motor?
YES
Shut off the power supply.
Does the cross flow
fan rotate normally?
YES
Turn on the power supply.
Operation
stops
NO
NO
Replace the P.C. board.
Does connecting
terminal, connecting
cable or power supply
cord completely?
Does not found the short
wire about connecting
cable and power cord?
YES
Repair the
bearing of
the fan.
Motor control circuit failure
(IC30, IC03, D38, R25, R26, Q17)
or 12V power circuit failure.
Replace the P.C. board.
of incompleted connecting.
NO
Thermal fuse operated
due to prevent
temperature rising cause
Normal
Is the rotation signal (DC+5V-0V)
output between 2 (gray lead wire)
and 3 (brown lead wire) of the motor
connector (CN11) when rotating
the cross flow fan by hand in no
operating status?
(1 pulse/one turn)
YES
Replace the control
P.C. board.
−54−
NO
Replace the fan motor
Replace connecting
the cable (or power cord),
thermal fuse and
terminal block.
9-6-3. Compressor does not operate.
<Primary check>
(1) Is the preset temperature higher than the room temperature in cooling operation?
(2) Is the crossover cable connected properly?
<Inspection procedure>
Turn on power supply.
FILE NO. SVM-06004
Does OPERATION
lamp blink?
YES
Does miniature relay RY04
switch on and off due to
temperature changes?
YES
Is it possible to detect AC
220 – 240V between 2
and 3 on terminal block?
YES
Are all of compressor cords normal?
YES
Is compressor motor winding
normal?
(Check winding resistor.)
YES
Is capacitor for compressor normal?
NO
NO
NO
Is resistance value of thermo
sensor (TA) and heat ex-
changer sensor (TC) normal?
Microcomputer is defective.
Miniature relay RY04 is
defective.
NO
NO
NO
Compressor is defective.
NO
YES
Capacitor is defective.
Refer to 9-6-1 “Power
can not be turned on”.
Thermo sensor or
heat exchanger
sensor is defective.
Replace thermo sensor
or heat exchanger
sensor.
Replace P.C. board.
Rewire or replace
defective cords.
Replace compressor.
Replace capacitor.
YES
Is overload relay normal?
YES
Does compressor start?
YES
Does compressor stop after a while?
YES
Is gas quantity normal?
(Check gas pressure.)
YES
Compressor is defective.
YES
Replace P.C. board.
NO
NO
NO
Overload relay is
defective.
Compressor is defective.
Gas shortage (Gas leak)
– 55 –
Replace overload relay.
Replace compressor.
Supply gas.
<Inspection procedure>
- Cooling model -
Turn on power supply.
FILE NO. SVM-06004
Does OPERATION
lamp blink?
YES
Is it possible to start
unit by remote control?
YES
Is it possible to detect AC 200V
between 2 and 3 on terminal block?
YES
Is crossover cable normal?
YES
Are all of compressor cords normal?
YES
Is compressor motor winding normal?
(Check winding resistor.)
YES
Is capacitor for compressor normal?
YES
NO
NO
NO
NO
NO
NO
NO
Compressor is defective.
Capacitor is defective.
Refer to item Power
can not be turned on .
Refer to 9-9 Troubleshooting
for Remote Control .
Replace P.C. Board
Connect crossover
cable properly.
Rewire or replace
defective cords.
Replace compressor.
Replace compressor.
Is overload relay normal?
YES
Does compressor start?
YES
Does compressor stop after a while?
YES
Is gas quantity normal?
(Check gas pressure.)
YES
Compressor is defective.
YES
Replace P.C. borad
NO
NO
NO
Overload relay is defective.
Compressor is defective.
Gas shortage (Gas leak)
Replace overload relay.
Replace compressor.
Supply gas.
− 56−
<Inspection procedure)
- Heating model -
AC 70-100V
FILE NO. SVM-06004
Replace transformer
outdoor
P.C. board.
− 57−
YES
FILE NO. SVM-06004
Are all of compressor cords normal?
YES
Is compressor motor winding normal?
(Check winding resistor.)
YES
Is capacitor for compressor normal?
YES
Is overload relay normal?
YES
Does compressor start?
YES
Does compressor stop after a while?
YES
Is gas quantity normal?
(Check gas pressure.)
YES
NO
NO
NO
NO
NO
NO
Compressor is defective.
Capacitor is defective.
Overload relay is defective.
Compressor is defective.
Gas shortage (Gas leak)
Rewire or replace
defective cords.
Replace compressor.
Replace capacitor.
Replace overload relay.
Replace compressor.
Supply gas.
Compressor is defective.
YES
Replace compressor.
– 58 –
FILE NO. SVM-06004
9-7. Troubleshooting for Wiring (Interconnect cable and Serial Signal Wire)
9-7-1. Outdoor unit does not operate.
<Inspection procedure>
(1) Is the voltage between and of the indoor terminal block varied?
1
(2) Are signals from the indoor unit to the outdoor unit transmitted correctly based upon the following diagram?
NOTE:
Measure the voltage for 2 minutes and 30 seconds after starting the unit.
Heatpump model
Terminal block on indoor side
Red
2
3
White
2
1
Terminal block
Tester
Normal condition : Voltage varied between AC70 ~ 100V
Abnormal condition : Voltage does not vary.
Cooling model
Terminal block on indoor side
Red
White
3
2
1
Terminal block
Tester
Fig. 9-7-1
Normal condition : After start operated about 2 minutes and 30 seconds. Voltage between 2 and 3 of the
of the indoor's Terminal block should be equal AC 220 ~ 240V
Abnormal condition : Don't found voltage AC 220 ~ 240V from terminal block (0V)
9-7-2. Outdoor unit stops a while after starting the unit.
<Confirmation procedure> Select one of 3 cases below and follow the procedure.
(1) The outdoor unit stops between 10 and 20 minutes passed after starting and it takes 10 minutes or more to
restart the unit.
Gas has a low circulation.
Measure gas pressure.
Compressor is turned off and on automatically by thermo sensor
(Heat pump Model) or thermostat (Cooling only Model).
Gas shortage
Gas leak
Pipe clogging
(2) The outdoor unit stops once, it would not operate until the power is turned on again.
Refer to 9-6-4 "Compressor does not operate"
(3) The outdoor unit stops between 10 minutes to 1 hour after starting and a check code is indicated on the
remote control. (Check code 03-1E : Refer to Table 9-4-1.)
−59−
FILE NO. SVM-06004
9-8. Troubleshooting for P.C. board
9-8-1. How to check indoor P.C. board
<Cautions for handling P.C. board>
(1) When removing the front panel and the P.C. board,
be sure to turn off the power supply.
(2) When removing the P.C. board, hold the edge of
the P.C. board and do not apply force to the parts.
(3) When connecting or disconnecting the connectors
on the P.C. board, hold the housing. Do not pull at
lead wires.
<Inspection procedure>
(1) If the P.C. board is detective, check for disconnec-
tion, burn or discoloration of the copper foil pattern
of the P.C. board.
(2) The P.C. board consists of the following 2 parts:
a. Main P.C. board parts.
Power relay, indoor fan motor drive circuit and
control circuit, C.P.U. and peripheral circuits, buzzer
drive circuit and buzzer.
b. Infrared rays parts:
Infrared rays receiving circuit
Check the defects of the P.C. board with Table 9-8-1.
Table 9-8-1 Inspection pr ocedure
No. Procedure Check points Causes
1Turn off the power supply and
remove the P.C. board assembly
from electric parts base. Remove
the connecting cables from the
terminal block.
2Remove the connector of the motor
and turn on the power supply. If
OPERATION lamp blinks (once per
second), it is not neccessary to
check steps (1 to 3) in the right
next column.
Check whenther or not the fuse (F01)
is blown.
Check power supply voltage;
1. Between CN30 and CN31
(220 − 240 V AC) : Except
2. Between + and − of C63
(DC310 − 340 V)
3. Between 12 V and GND
4. Between 5 V and GND
Impluse voltage was applied or the
indoor fan motor short-circuited.
1. The terminal block or the
crossover cable is connected
wrongly.
2. The capacitor (C01 and C02 )
line filter (L01), resistor (R319), or
the diode (DB01) is defective.
3. C65, C66 and M01 are defective.
4. IC04, C05, C06 and C07 are
defective.
3 Press [ ] button once
to start the unit. (Do not set the
mode to Fan Only or On-Timer
operation).
4Shorten the line of the restart delay
timer and start unit.
Check power supply voltage;
<Heat pump model>
1. Between CN31 and CN23
(DC15 − 60 V)
<Cooling only model>
1. Between connector of Q24 and
GND (for relay coil (DC12 V))
2. Between 1 and 2 of terminal
block for connecting cable
Check whether or not all lamps
(OPERATION, TIMER, PRE.-DEF.
(or FAN ONLY), FILTER. and Hi Power)
are indicated for 3 seconds and they
return to normal 3 seconds later.
<Heat pump model>
IC32 and IC33 are defectice.
<Cooling only model>
1. The wire of the relay coil (RY04)
comes down or the relay drive
(Q24) is defective.
2. CN27 or RY04 is connected
wrongly.
The lamps are defective or the
housing assembly (CN13) is
defective.
– 60−
FILE NO. SVM-06004
No.ProcedureCheck pointsCauses
5 Press [ ] button once
to start the unit.
• Shorten the time of the restart
delay timer.
• Set the operation mode to COOL.
• Set the fan speed level to AUTO.
• Set the preset temperature much
lower than the room temperature.
(The unit (compressor) operates
continuously in the above
condition.)
1. Check whether or not the
compressor operates.
2. Check whether or not the
OPERATION lamp blinks.
1. The temperature of the indoor
heat exchanger is extremely low.
2. The connection of the heat
exchanger sensor is loose.
(The connector is disconnected.)
(CN01)
3. The heat exchanger sensor and
the P.C. board are defective.
(Refer to Table 9-8-2.)
4. The main P.C. board is defective.
6If the above condition (No. 6) still
continues, start the unit in the
following condition.
• Set the operation mode to HEAT.
• Set the preset temperature much
higher than room temperature.
7Connect the motor connector to the
motor and turn on the power supply.
Start the unit in the following
condition.
• Set the operation mode to FAN.
• Set the fan speed level to HIGH.
(The unit (compressor) operates
continuously in the above codition.)
1. Check whether or not the
compressor operates.
2. Check whether or not the
OPERATION lamp blinks.
1. Check it is impossible to detect the
voltage (DC 12 V) between and1
3 of the motor terminals.
2. The motor does not operate.
(But it is possible to receive the
signal from the remote control.)
3. The motor rotates but vibrates
strongly.
1. The temperature of the indoor
heat exchanger is extremely high.
2. The connector of the heat
exchanger sensor short-circuited.
(CN01)
3. The heat exchanger sensor and
the P.C. board are defective. (Refer
to Table 9-8-2.)
4. The main P.C. board is defective.
1. The indoor fan motor is defective.
(Protected operation of P.C. board)
2. The connection of the motor
connector is loose.
3. The P.C. board is defective.
Table 9-8-2 Approximate resistance value of thermo sensor
Temperature0°C10°C20°C25°C30°C
Resistance value33.820.3512.5910.07.99
(kΩ)
9-8-2. How to Shorten Time of Restart Delay Timer
1 Press [CLR] button while pressing [CHK] button
with a tip of a pencil.
2 Then press [ ] button to transmit the
signal to the indoor unit.
9-8-3. How to use self cleaning function
The self cleaning function is set from a factory.
To cancel this function, should keep press the
temporary switch for 20 secounds till can hear
the long combination sound and repeat the
same procedure when need to set.
2
1
– 61 –
9-9. Troubleshooting for Remote Control
FILE NO. SVM-06004
Is receiver on
indoor unit exposed
to direct sunlight?
YES
NO
Is there any
thyristor fluorescent
light nearby?
YES
YES
NONO
Press [ ]
button.
Is transmission
mark indicated?
Does indoor unit
operate when
moving remote control
near receiver or
indoor unit?
YES
Batteries are
exhausted.
The unit does not beep at all.
OPERATION lamp on
indoor unit is not indicated.
NO
Press RESET button
on remote control
with tip of pencil.
Press [ ]
button.
Avoid direct
sunlight.
Keep indoor unit
away from
thyristor
fluorescent light.
Does indoor unit
NO
start to operate by
automatic restart
function?
YES
Does radio sound
is affected by
remote control when
a signal is transmitted
at distance of 5 cm
from radio?
P.C. board is
defective.
Replace
P.C. board.
YES
NO
NO
Replace
batteries.
Note : After replacing batteries,
press the RESET button
with a tip of a pencil.
– 62 –
Is transmission mark
indicated?
YES
Does indoor unit
beep and operate?
YES
Normal
operation
NO
Remote control
is defective.
Replace
remote control.
FILE NO. SVM-06004
(6) TC sensor
(4)
(3)
4-screws
(2)
(2)
(2)
10. PART REPLACEMENT
10-1. Indoor Unit
No.Part nameProceduresRemarks
1Front panel
How to remove the front panel
1) Stop the operation of the air conditioner and turn off
its main power supply.
2) Pull the inlet grille toward you to open it and remove
the inlet grille.
3) Take off the right side of air filter.
4) Pull out the plasma air purifier and remove 4 screws
fixing the front panel before open the horizontal
louver and then remove the front panel from back
body by pulling it toward you.
5)
Open the horizontal grille right below by hand.
6)
Pull the lower side of the front panel toward you
until it touches the horizontal grille to remove it.
How to mount the front panel
1) Mount the front panel with the inverse procedure of
"How to remove the front panel".
2) Push 3 places (right, left and center) of the air
outlet.
3) Check the gap between the front panel and the
back body.
If you operate the air conditioner in cooling or dry
operation without pushing the 3 places, the surface
of the front panel may be covered with frost and
have dewdrops.
2Electrical part
assembly
1) Remove the front panel with the procedure 1.
2) Remove the screw fixing the electrical part box.
3) Remove the drain guide.
4) Remove the connector (5P) for the fan motor and
the connector (6P) for the louver motor from the
microcomputer assembly.
5) Remove the screw for the earth, and pull the
electrical part base toward you to remove it from
the main unit.
6) Pull out the TC sensor from the sensor holder.
(3) Drain guide
(3) Drain guide
When assembling the electrical parts
assembly, make the connecting cable
U-shaped and put it in the drain pan.
(5) screws
(2) screws
5P
6P
– 63–
FILE NO. SVM-06004
Bearing base
Bearing
Motor fixture
(4) BODY (R)
(3) 2 screws
(4)
No.Part nameProceduresRemarks
3Horizontal grille
1) Remove center 2 shafts of the horizontal louver from
the back body.
2) Remove left shaft of the horizontal
louver from the
back body.
3) Remove the horizontal grille from the back body.
(1) Center shafts
(2) Left shafts
4Heat exchanger
5Cross flow fan
1) Remove the front panel, electrical parts assembly
and the horizontal grille with procedure 2 and 3.
2) Remove the screw on the rear side of the main unit
to remove the pipe holder.
3) Remove 2 screws fixing the heat exchanger and
the bearing base.
4) Remove 2 screws fixing the heat exchanger fixtures
(upper and lower) and the back body then pull out
the upper side of the heat exchanger slowly.
1) Remove the front panel, electrical parts assembly,
horizontal grille and the heat exchanger with
procedure 4 .
2) Loosen the set screw of the cross flow fan.
(Hexagonal wrench is required.)
3) Remove 2 screws fixing the bearing base and the
back body.
4) Pull the cross flow fan toward you.
Pipe holder
(3) 2 screws
(2) Screw
Bearing base
(4) 2 screws
(3) Screws
(2) Set screw
6Bearing base
7Fan motor
When assembling the cross flow fan, fix it
with the set screw at the position where the
gap between the back body and the right
surface of the cross flow fan is 6 mm.
1) Remove the front panel, electrical parts assembly,
horizontal grille, heat exchanger and the cross flow
fan with procedure 5.
2) Remove the bearing from the bearing base.
If the housing protrudes from the base bearing, put
the housing in position and assemble the bearing to
the bearing base.
1) Remove the front panel, electrical parts assembly,
horizontal grille, and the heat exchanger with
procedure 4.
2) Loosen the set screw of the cross flow fan.
3) Remove 2 screws of the motor fixture.
4) Remove the lower side of the body (R) and move it
right to remove it.
5) Remove the motor from the motor fixture.
– 64 –
FILE NO. SVM-06004
10-2. Outdoor Unit (RAS-24NA-E, RAS-24N2AX)
No. Part name Procedures Remarks
Top cabinet
1Common
procedure
1) Stop the operation of the air conditioner and turn off
its main power supply or remove the power supply
cord.
2) Remove the packed valve cover and the
electrical parts cover (2 screws ∅4 x 10L)
3) Remove 2 cord clamps (4 screws ∅4 x 16L) and
disconnect the power supply cord and connecting
cable after removing 6 screwson on the terminal
block and 1 ground screw on the electrical parts
base.
4) Remove the top cabinet. (7 screws ∅ 4 x 10L)
(Pulling out upward)
5) Remove the top cabinet. (2 screws ∅ 4 x 10L)
(Pull the front right portion toward you, and
remove it pulling out upward)
Front cabinet
3 screws
∅4 x 10L
Packed valve cover
2 Cord clamps
Side cabinet
4 screws ∅4 x 16L
7 screws ∅4 x 10L
Front
cabinet
– 65 –
FILE NO. SVM-06004
No.
2Running
3Running
4Magnetic
5 Spark killer
Part name
capacitor
for compressor
capacitor
for fan motor
contactor
(Cooling only model)
Procedures
1) Perform the common procedure 1
2) Remove the capacitor band. (1 screw ∅4 x 10L)
3) Disconnect the lead wires from the capacitor
terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (1 screw ∅4 x 10L)
3) Disconnect the lead wires from the capacitor
terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (2 screws ∅4 x 16L)
3) Disconnect the lead wires from the terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (1 screws ∅4 x 10L)
3) Disconnect the lead wires from the terminal.
Remarks
Running capacitor
for compressor
Running capacitor
for fan motor
Cooling only model
Spark killer
Magnetic contactor
– 66 –
FILE NO. SVM-06004
10-3 Outdoor Unit (RAS-18NAH-E, RAS-18NA-E, RAS-18N2AX)
No. Part name Procedures Remarks
1Common
procedure
1) Stop the operation of the air conditioner and turn off
its main power supply or remove the power supply
cord.
2) Remove the packed valved cover and the electrical
Parts cover
(2 screws ∅ 4 x 10L)
3) Remove 2 cord clamps (4 screws ∅ 4 x 16L) and
disconnect the power supply cord and connecting
cable after removing 6 screws on the terminal block
and 1 ground screw on the electrical parts base.
4) Remove the upper cabinet. (4 scerws ∅ 4 x 10L)
(Pulling out upward)
5) Remove the front cabinet. (3 screws∅ 4 x 10L)
(Pull the front right protion toward you, and remove
it pulling out upward.)
Packed valve cover
3 screws ∅4 x 10L
Upper
cabinet
2 Cord clamps
4 screws ∅4 x 16L
Running
2
capacitor
for compressor
Running
3
capacitor
for fan motor
4
Magnetic contactor
Transformer
5
(Heat pump model)
P.C. Board
6
(Heat pump model)
7
Spark killer
(Cooling only model)
1) Perform the common procedure 1
2) Remove the capacitor band. (1 screw ∅4 x 10L)
3) Disconnect the lead wires from the capacitor
terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (1 screw ∅4 x 10L)
3) Disconnect the lead wires from the capacitor
terminal.
form the common procedure 1
1) Per
2) Remove the fixing screw. (2 screws ∅ 4 x 10L)
3) Disconnect the lead wires from the terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (2 screws ∅ 4 x 10L)
3) Disconnect the housing from the P.C. Board.
1) Perform the common procedure 1
2) Disconnect the lead wires from the P.C. Board.
3) Remove P.C.Board after unhooking 4 clams.
1) Perform the common procedure 1
2) Remove the fixing screw. (1 screw ∅ 4 x 10L)
3) Disconnect the lead wires from the terminal.
Running capacitor
for fan motor
Running
capacitor
for compressor
Running capacitor
Running capacitor
for compressor
Front
cabinet
Heat pump model
for fan motor
Cooling only model
P.C. Board
Transformer
Magnetic contactor
Spark killer
Magnetic contactor
− 67 −
11. EXPLODED VIEWS AND PARTS LIST
)
)
11-1. Indoor Unit (E-Parts Assy)
FILE NO. SVM-06004
LocationPartLocationPart
No.No.No.No.
40243T60002 TERMINAL BLOCK; 3P41143T69451 PC BOARD (RAS-24NKP-E,
40343T50004 SENSOR; HEAT EXCHANGER
40443T50314 SENSOR;THERMOSTAT41143T69508 PC BOARD (RAS-18NKP-E,
40543T69487 PC BOARD ASSY ; WRS-LED
40743T62003 CORD CLAMP41143T69507 PC BOARD (RAS-18NKHP-E)
DescriptionDescription
RAS-24NKPX
RAS-B18NKPX
41343T63310 SENSOR HOLDER
– 68 –
11-2. Indoor Unit
213
221
222
203
217
238
219
220
201
229
227
214
228
215
216
218
208
230
FILE NO. SVM-06004
232
209
211
231
226
224
212
207
237
204
202
LocationPartLocationPart
No.No.No.No.
236
DescriptionDescription
223
20143T00409 FRONT PANEL ASSY
20243T09388 GRILLE ASSY
20343T80306 AIR FILTER (L)
20443T80312 AIR FILTER (R)
20743T03010 BODY; RIGHT
20843T03011 BODY; LEFT
20943T03012 HIDE; CLAW
21043T09345 LOUVER-H
21143T70309 HOSE ASSY; DRAIN
21243T21373 MOTOR; STEPPING
21343T44310 REFRIGERATION CYCLE
22343T79007 GUIDE DRAIN
22443T39306 FIX FOR MOTOR
22643T21370 MOTOR FAN (For Part 43T21359)
22743T20309 FAN; CROSS FLOW
22843T22309 ASM-M-BEARING
22943T39015 BASE; BEARING
23043T03344 BACK BODY ASSY
143T42324 BASE PLATE ASSEMBLY2343T39318 MOTOR BASE
243T41371 COMPRESSOR;2443T19330 PACKED VALVE COVER
PH340X3C-4KT1(Made in China)2543T00452 UPPER CABINET
343T49011 BASE; SPRING; A2643T96304 BUSHING
443T49012 BASE;SPRING; B2743T62325 ELECTRIC PART COVER(NEW)
543T49019 SPRING; BUFFER2843T61304 ELECTRIC PART BASE
643T97307 COMPRESSOR BOLT (M6)2943T52302 MAGNETIC CONTACTOR;
743T43371 CONDENSER ASSEMBLYAC220-240V 50Hz
843T00448 FIXING PLATE VALVE3043T55340 MF CAPACITOR (50uF 440V)
943T46308 VALVE;PACKED 6.35 DIA3143T55341 CAPACITOR;PLASTIC-FILM
1043T46019 VALVE,PACKED 12.7 DIA3243T60352 TERMINAL BLOCK; 6P
1143T47331 BONNET, 6.35 DIA3443T61305 MAGNETIC RELAY BASE
1243T47333 BONNET, 12.70 DIA3543T19331 FIN GUARD
1343T47013 CAPILLARY TUBE; 2.0 DIA3943T46337 4 WAY VALVE
1443T00449 FRONT CABINET4043T46339 COIL;V-4WAY;
1543T00458 LEFT CABINETAC220-240V 50Hz(NEW)
1643T00451 RIGHT CABINET ASSEMBLY (NEW)4143T69059 SENSOR; TE
1743T21378 FAN MOTOR;AC220-240V 50Hz4243T69060 SENSOR; TD
1843T20319 PROPELLER FAN4343T79305 DRAIN NIPPLE
1943T47001 NUT FLANGE4443T58301 TRANSFORMER; TT-05
2043T19329 FAN GUARD4543T69336 PC Board
2143T04301 PARTITION4643T60325 FILTER;CLAMP
2243T39317 MOTOR BASE
CONNECTION PLATE(NEW)
DescriptionDescription
– 70 –
11-4. Outdoor Unit (RAS-24NA-E, RAS-24N2AX)
FILE NO. SVM-06004
LocationPartLocationPart
No.No.No.No.
143T42324 BASE PLATE ASSEMBLY2043T19329 FAN GUARD
243T41370 COMPRESSOR(Made in China)2143T04302 PARTITION
343T49011 BASE; SPRING; A2243T39317 MOTOR BASE
443T49012 BASE;SPRING; BCONNECTION PLATE(NEW)
543T49019 SPRING; BUFFER2343T39318 MOTOR BASE
643T97307 COMPRESSOR BOLT (M6)2443T19330 PACKED VALVE COVER
743T43370 CONDENSER ASSEMBLY2543T00455 UPPER CABINET
843T00448 FIXING PLATE VALVE2643T96304 BUSHING
943T46308 VALVE;PACKED 6.35 DIA2743T62325 ELECTRIC PART COVER(NEW)
1043T46338 VALVE,PACKED 15.88 DIA2843T61306 ELECTRIC PARTS BASE
1143T47331 BONNET, 6.35 DIA2943T52305 MAGNETIC CONTACTOR
1243T47334 BONNET; 15.88 DIA.3043T55340 MF CAPACITOR (50uF 440V)
1343T47013 CAPILLARY TUBE; 2.0 DIA3143T55341 CAPACITOR;PLASTIC-FILM
1443T00449 FRONT CABINET3243T60352 TERMINAL BLOCK; 6P
1543T00453 LEFT CABINET3343T33002 SPARK-KILLER
1643T00454 RIGHT CABINET3543T19331 FIN GUARD
1743T21377 FAN MOTOR;AC220-240V 50Hz3643T00456 UPPER FRONT CABINET; A
1843T20319 PROPELLER FAN3743T00457 UPPER FRONT CABINET; B
1943T47001 NUT FLANGE3843T71301 HANDLE
DescriptionDescription
– 71 –
11-5. Outdoor Unit (RAS -18NA-E, RAS-18N2AX)
FILE NO. SVM-06004
LocationPartLocationPart
No.No.No.No.
143T42324 BASE PLATE ASSEMBLY1943T47001 NUT FLANGE
243T41371 COMPRESSOR;2043T19329 FAN GUARD
PH340X3C-4KT1(Made in China)2143T04301 PARTITION
343T49011 BASE; SPRING; A2243T39317 MOTOR BASE
443T49012 BASE;SPRING; BCONNECTION PLATE(NEW)
543T49019 SPRING; BUFFER2343T39318 MOTOR BASE
643T97307 COMPRESSOR BOLT (M6)2443T19330 PACKED VALVE COVER
743T43369 CONDENSER ASSEMBLY2543T00452 UPPER CABINET
843T00448 FIXING PLATE VALVE2643T96304 BUSHING
943T46308 VALVE;PACKED 6.35 DIA2743T62325 ELECTRIC PART COVER(NEW)
1043T46019 VALVE,PACKED 12.7 DIA2843T61304 ELECTRIC PART BASE
1143T47331 BONNET, 6.35 DIA2943T52302 MAGNETIC CONTACTOR;
1243T47333 BONNET, 12.70 DIAAC220-240V 50Hz
1343T47013 CAPILLARY TUBE; 2.0 DIA3043T55340 MF CAPACITOR (50uF 440V)
1443T00449 FRONT CABINET3143T55324 CAPACITOR; PLASTIC-FILM
1543T00450 LEFT CABINET3243T60352 TERMINAL BLOCK; 6P
1643T00451 RIGHT CABINET ASSEMBLY(NEW)3343T33002 SPARK-KILLER
1743T21345 FAN-MOTOR(Made in China)3443T61305 MAGNETIC RELAY BASE
1843T20319 PROPELLER FAN3543T19331 FIN GUARD
DescriptionDescription
– 72 –
FILE NO. SVM-03010(1)
TOSHIBA CARRIER (THAILAND) CO.,LTD.
144/9 MOO 5, BANGKADI INDUSTRIAL PARK, TIVANON ROAD, TAMBOL BANGKADI,
AMPHUR MUANG, PATHUMTHANI 12000, THAILAND.
– 87 –
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.