1-1Specifications
1-2Operation Characteristic Curve
1-3 Capacity Variation Ratio According to Temperature
2.REFRIGERANT R410A
2-1Safety During Installation/Servicing
2-2Refrigerant Piping Installation
2-3Tools
2-4.Recharging of Refrigerant
2-5. Brazing of Pipes
3.CONSTRUCTION VIEWS
3-1Indoor Unit
3-2Outdoor Unit
4.WIRING DIAGRAM
4-1Indoor Unit
4-2Outdoor Unit (RAS-13UAV-E3)
4-3Outdoor Unit (RAS-16UAV-E)
FILE NO. SVM-04013
5.SPECIFICATION OF ELECTRICAL PARTS
5-1Indoor Unit
5-2 Outdoor Unit (RAS-13UAV-E3)
Outdoor Unit (RAS-16UAV-E)
6.REFRIGERANT CYCLE DIAGRAM
6-1Refrigerant Cycle Diagram
6-2Operation Data
7.CONTROL BLOCK DIAGRAM
7-1Indoor Unit
7-2Outdoor Unit (Inverter Assembly)
8.OPERATION DESCRIPTION
8-1Outlined of Air Conditioner Control
8-2Description of Operation Circuit
8-3Temporary Operation
8-4Auto Restart Function
8-5Filter Check Lamp
8-6Remote Control and its Functions
8-7Hi POWER Mode ([Hi POWER] button on the remote control is pushed.)
9.INSTALLATION PROCEDURE
9-1Safety Cautions
9-2INDOOR UNIT
9-3OUTDOOR UNIT
−1 −
10. HOW TO DIAGNOSE THE TROUBLE
10-1 First Confirmation
10-2 Primary Judgment
10-3 Judgment by Flashing LED of Indoor Unit
10-4 Self-Diagnosis by Remote Control (Check Code)
10-5 Judgment of Trouble by Every Symptom
10-6 Check Code 1C (Miswiring in indoor/outdoor units) and 1E
10-7 How to Diagnose Trouble in Outdoor Unit
10-8 How to Check Simply the Main Parts
10-9 How to Simply Judge Whether Outdoor Fan Motor is Good or Bad
11. HOW TO REPLACE THE MAIN PARTS
11-1 Indoor Unit
11-2 Microcomputer
11-3 Outdoor Unit
12. EXPLODED VIEWS AND PARTS LIST
12-1 Indoor Unit (E-Parts Assy)
12-2 Indoor Unit
12-3 Outdoor Unit (RAS-13UAV-E3)
12-4 Outdoor Unit (RAS-16UAV-E)
12-5 Outdoor Unit (E-Parts Assy)
TypeTwin rotary type with DC-inverter variable speed control
Model DA130A1F-24F
Gas side ∅12.7
Gas side ∅12.7
Interconnection4 Wires: includes earth
Outdoor (Cooling / Heating)(°C)10 – 43 / –10 – 24
Wireless remote control1
Remote controller holder1
Flat head wood screw2 (∅3.1 x 16L)
Purifying filter1
Zeolite filter1
Batteries2
Mounting screw6 (∅4 x 25L)
Installation manual1
Owner’s manual1
0.2
30
65
Heating
• The specification may be subject to change without notice for purpose of improvement.
– 4 –
1-2.Operation Characteristic Curve
<Cooling><Heating>
FILE NO. SVM-04013
7
6
5
4
3
Current (A)
2
• Conditions
Indoor : DB 27°C/WB 19°C
Outdoor : DB 35°C
1
Air flow : High
Pipe length : 5m
230V
0
020406080100
Compressor speed (rps)
7
6
5
4
3
Current (A)
2
• Conditions
Indoor : DB 20°C
Outdoor : DB 7°C/WB 6°C
1
Air flow : High
Pipe length : 5m
230V
0
020406080100
Compressor speed (rps)
1-3.Capacity Variation Ratio According to Temperature
<Cooling><Heating>
105
100
95
90
85
80
75
70
Capacity ratio (%)
65
60
55
50
3234
Current Limited Start
• Conditions
Indoor : DB27°C/WB19°C
Indoor air flow : High
Pipe length 5m
36384042333537394143
Outdoor temp. (°C)
120
110
100
90
80
70
60
50
Capacity ratio (%)
40
30
20
10
0
−10−9−8−7−6−5−4−3−2−1012345678910
• Conditions
Indoor : DB 20°C
Indoor air flow : High
Pipe length : 5m
Outdoor temp. (°C)
Capacity ratio : 100% = Nominal Capacity
*
– 5 –
2. REFRIGERANT R410A
FILE NO. SVM-04013
This air conditioner adopts the new refrigerant HFC
(R410A) which does not damage the ozone layer.
The working pressure of the new refrigerant R410A is
1.6 times higher than conventional refrigerant (R22).
The refrigerating oil is also changed in accordance
with change of refrigerant, so be careful that water,
dust, and existing refrigerant or refrigerating oil are not
entered in the refrigerant cycle of the air conditioner
using the new refrigerant during installation work or
servicing time.
The next section describes the precautions for air
conditioner using the new refrigerant. Conforming to
contents of the next section together with the general
cautions included in this manual, perform the correct
and safe work.
2-1.Safety During Installation/Servicing
As R410A’s pressure is about 1.6 times higher than
that of R22, improper installation/servicing may cause
a serious trouble. By using tools and materials exclusive for R410A, it is necessary to carry out installation/
servicing safely while taking the following precautions
into consideration.
(1) Never use refrigerant other than R410A in an air
conditioner which is designed to operate with
R410A.
If other refrigerant than R410A is mixed, pressure
in the refrigeration cycle becomes abnormally
high, and it may cause personal injury, etc. by a
rupture.
(2) Confirm the used refrigerant name, and use tools
and materials exclusive for the refrigerant R410A.
The refrigerant name R410A is indicated on the
visible place of the outdoor unit of the air conditioner using R410A as refrigerant. To prevent
mischarging, the diameter of the service port
differs from that of R22
(3) If a refrigeration gas leakage occurs during instal-
lation/servicing, be sure to ventilate fully.
If the refrigerant gas comes into contact with fire,
a poisonous gas may occur.
(4) When installing or removing an air conditioner,
do not allow air or moisture to remain in the
refrigeration cycle. Otherwise, pressure in the
refrigeration cycle may become abnormally high
so that a rupture of personal injury may be
caused.
(5) After completion of installation work, check to
make sure that there is no refrigeration gas
leakage.
If the refrigerant gas leaks into the room, coming
into contact with fire in the fan-driven heater,
space heater, etc., a poisonous gas may occur.
(6) When an air conditioning system charged with a
large volume of refrigerant is installed in a small
room, it is necessary to exercise care so that,
even when refrigerant leaks, its concentration
does not exceed the marginal level.
If the refrigerant gas leakage occurs and its
concentration exceeds the marginal level, an
oxygen starvation accident may result.
(7) Be sure to carry out installation or removal
according to the installation manual.
Improper installation may cause refrigeration
trouble, water leakage, electric shock, fire, etc.
(8) Unauthorized modifications to the air conditioner
may be dangerous. If a breakdown occurs please
call a qualified air conditioner technician or
electrician.
Improper repair’s may result in water leakage,
electric shock and fire, etc.
2-2.Refrigerant Piping Installation
2-2-1. Piping materials and joints used
For the refrigerant piping installation, copper pipes and
joints are mainly used. Copper pipes and joints suitable for the refrigerant must be chosen and installed.
Furthermore, it is necessary to use clean copper pipes
and joints whose interior surfaces are less affected by
contaminants.
(1) Copper Pipes
It is necessary to use seamless copper pipes
which are made of either copper or copper alloy
and it is desirable that the amount of residual oil is
less than 40 mg/10 m. Do not use copper pipes
having a collapsed, deformed or discolored
portion (especially on the interior surface).
Otherwise, the expansion valve or capillary tube
may become blocked with contaminants.
As an air conditioner using R410A incurs pressure
higher than when using R22, it is necessary to
choose adequate materials.
Thicknesses of copper pipes used with R410A are
as shown in Table 2-2-1. Never use copper pipes
thinner than 0.8 mm even when it is available on
the market.
For copper pipes, flare joints or socket joints are
used. Prior to use, be sure to remove all
contaminants.
a) Flare Joints
Flare joints used to connect the copper pipes
cannot be used for pipings whose outer
diameter exceeds 20 mm. In such a case,
socket joints can be used.
Sizes of flare pipe ends, flare joint ends and
flare nuts are as shown in Tables 2-2-3 to 2-2-6
below.
Socket joints are such that they are brazed for
connections, and used mainly for thick pipings
whose diameter is larger than 20 mm.
Thicknesses of socket joints are as shown in
Table 2-2-2.
copper pipe jointed (mm)(mm)
2-2-2. Processing of piping materials
When performing the refrigerant piping installation,
care should be taken to ensure that water or dust does
not enter the pipe interior, that no other oil other than
lubricating oils used in the installed air conditioner is
used, and that refrigerant does not leak. When using
lubricating oils in the piping processing, use such
lubricating oils whose water content has been removed.
When stored, be sure to seal the container with an
airtight cap or any other cover.
(1) Flare Processing Procedures and Precautions
a) Cutting the Pipe
By means of a pipe cutter, slowly cut the pipe
so that it is not deformed.
b) Removing Burrs and Chips
If the flared section has chips or burrs,
refrigerant leakage may occur. Carefully
remove all burrs and clean the cut surface
before installation.
c) Insertion of Flare Nut
– 7 –
d) Flare Processing
Make certain that a clamp bar and copper pipe
have been cleaned.
By means of the clamp bar, perform the flare
processing correctly.
Use either a flare tool for R410A or
conventional flare tool.
Flare processing dimensions differ according to
the type of flare tool. When using a
conventional flare tool, be sure to secure
“dimension A” by using a gauge for size
adjustment.
∅D
A
Fig. 2-2-1 Flare processing dimensions
FILE NO. SVM-04013
Table 2-2-3 Dimensions related to flare processing for R410A
Nominal
diameter
1/46.350.80 to 0.51.0 to 1.51.5 to 2.0
3/89.520.80 to 0.51.0 to 1.51.5 to 2.0
1/212.700.80 to 0.51.0 to 1.52.0 to 2.5
5/815.881.00 to 0.51.0 to 1.52.0 to 2.5
Nominal
diameter
1/46.350.80 to 0.50.5 to 1.01.0 to 1.5
3/89.520.80 to 0.50.5 to 1.01.0 to 1.5
1/212.700.80 to 0.50.5 to 1.01.0 to 2.0
Outer
diameter
(mm)
Table 2-2-4 Dimensions related to flare processing for R22
Outer
diameter
(mm)
Thickness
(mm)
Thickness
(mm)
Flare tool for R410A
clutch type
Flare tool for R410A
clutch type
A (mm)
Conventional flare tool
Clutch typeWing nut type
A (mm)
Conventional flare tool
Clutch typeWing nut type
5/815.881.00 to 0.50.5 to 1.01.0 to 2.0
Table 2-2-5 Flare and flare nut dimensions for R410A
Fig. 2-2-2 Relations between flare nut and flare seal surface
(2) Flare Connecting Procedures and Precautions
a) Make sure that the flare and union portions do
not have any scar or dust, etc.
b) Correctly align the processed flare surface with
the union axis.
c) Tighten the flare with designated torque by
means of a torque wrench. The tightening
torque for R410A is the same as that for
conventional R22. Incidentally, when the torque
is weak, the gas leakage may occur.
Table 2-2-7 Tightening torque of flare for R410A [Reference values]
NominalOuter diameterTightening torque
diameter (mm) N·m (kgf·m)
1/46.3514 to 18 (140 to 180)16 (160), 18 (180)
3/89.5233 to 42 (330 to 420)42 (420)
1/212.7050 to 62 (500 to 620)55 (550)
5/815.8863 to 77 (630 to 770)65 (650)
When it is strong, the flare nut may crack and
may be made non-removable. When choosing
the tightening torque, comply with values
designated by manuf acturers. Table 2-2-7
shows reference values.
Note:
When applying oil to the flare surface, be sure to use
oil designated by the manufacturer. If any other oil is
used, the lubricating oils may deteriorate and cause
the compressor to burn out.
Tightening torque of torque
wrenches available on the market
N·m (kgf·m)
– 9 –
FILE NO. SVM-04013
2-3. T ools
2-3-1. Required tools
The service port diameter of packed valve of the outdoor unit in the air conditioner using R410A is changed to
prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and
opposite side dimension of flare nut (For ∅12.70 copper pipe) of the refrigerant piping are lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge,
clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.
(1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))
(2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)
(3) Tools commonly used for R410A and for conventional refrigerant (R22)
The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
R410A air conditionerConventional air
installationconditioner installation
No.Used toolUsageExistence ofWhetherWhether new equipment
new equipmentconventionalcan be used with
for R410Aequipment canconventional refrigerant
be used
1Flare toolPipe flaringYes*(Note 1)
2Copper pipe gaugeFlaring by
for adjusting projection conventional flareYes*(Note 1)*(Note 1)
margintool
Evacuating,
refrigerant charge,Yes
run check, etc.
Refrigerant chargeYes
Yes
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
(Note 2) Charging cylinder for R410A is being currently developed.
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary as
the general tools.
(1) Vacuum pump(4) Reamer(9) Hole core drill (∅65)
Use vacuum pump by(5) Pipe bender(10) Hexagon wrench
attaching vacuum pump adapter. (6) Level vial(Opposite side 5 mm)
(2) Torque wrench (For ∅6.35)(7) Screwdriver (+, –)(11) Tape measure
(3) Pipe cutter(8) Spanner of Monkey wrench(12) Metal saw
Also prepare the following equipments for other installation method and run check.
(1) Clamp meter(3) Insulation resistance tester
(2) Thermometer(4) Electroscope
– 10 –
FILE NO. SVM-04013
2-4. Recharging of Refrigerant
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the
following steps.
Recover the refrigerant, and check no refrigerant
remains in the equipment.
When the compound gauge’s pointer has indicated -0.1 Mpa (-76 cmHg), place the handle Low
Connect the charge hose to packed valve service
port at the outdoor unit’s gas side.
in the fully closed position, and turn off the
vacuum pump’s power switch.
Connect the charge hose to the vacuum pump
adapter.
Open fully both packed valves at liquid and gas
sides.
Keep the status as it is for 1 to 2 minutes, and
ensure that the compound gauge’s pointer does
not return.
Set the refrigerant cylinder to the electronic
balance, connect the connecting hose to the
cylinder and the connecting port of the electronic
balance, and charge liquid refrigerant.
Place the handle of the gauge manifold Low in
(For refrigerant charging, see the figure below.)
the fully opened position, and turn on the vacuum
pump’s power switch. Then, evacuating the
refrigerant in the cycle.
1 Never charge refrigerant exceeding the specified amount.
2 If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.
3 Do not carry out additional charging.
When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the
refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the
specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high
pressure, and may cause a rupture or personal injury.
(INDOOR unit)
Refrigerant cylinder
(With siphon pipe)
Check valve
Open/Close valve
for charging
Electronic balance for refrigerant charging
Fig. 2-4-1 Configuration of refrigerant charging
(Liquid side)
(Gas side)
– 11 –
(OUTDOOR unit)
Opened
Closed
Service port
FILE NO. SVM-04013
1 Be sure to make setting so that liquid can be charged.
2 When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant.
Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the
cylinder upside down if cylinder is not equipped with siphon.
[Cylinder with siphon][Cylinder without siphon]
Gauge manifold
OUTDOOR unit
Refrigerant
cylinder
Electronic
balance
R410A refrigerant is HFC mixed refrigerant.
Therefore, if it is charged with gas, the composition
of the charged refrigerant changes and the
characteristics of the equipment varies.
Gauge manifold
OUTDOOR unit
Refrigerant
cylinder
Electronic
balance
Siphon
Fig. 2-4-2
2-5. Brazing of Pipes
2-5-1. Materials for brazing
(1) Silver brazing filler
Silver brazing filler is an alloy mainly composed of
silver and copper. It is used to join iron, copper or
copper alloy, and is relatively expensive though it
excels in solderability.
(2) Phosphor bronze brazing filler
Phosphor bronze brazing filler is generally used to
join copper or copper alloy.
(3) Low temperature brazing filler
Low temperature brazing filler is generally called
solder, and is an alloy of tin and lead. Since it is
weak in adhesive strength, do not use it for
refrigerant pipes.
1 Phosphor bronze brazing filler tends to react
with sulfur and produce a fragile compound
water solution, which may cause a gas leakage .
Therefore, use any other type of brazing filler at
a hot spring resort, etc., and coat the surface
with a paint.
2 When performing brazing again at time of
servicing, use the same type of brazing filler.
2-5-2. Flux
(1) Reason why flux is necessary
• By removing the oxide film and any foreign
matter on the metal surface, it assists the flow
of brazing filler.
• In the brazing process, it prevents the metal
surface from being oxidized.
• By reducing the brazing filler’s surface tension,
the brazing filler adheres better to the treated
metal.
– 12 –
FILE NO. SVM-04013
(2) Characteristics required for flux
• Activated temperature of flux coincides with the
brazing temperature.
• Due to a wide effective temperature range, flux
is hard to carbonize.
• It is easy to remove slag after brazing.
• The corrosive action to the treated metal and
brazing filler is minimum.
• It excels in coating performance and is
harmless to the human body.
As the flux works in a complicated manner as
described above, it is necessary to select an
adequate type of flux according to the type and
shape of treated metal, type of brazing filler and
brazing method, etc.
(3) Types of flux
• Noncorrosive flux
Generally, it is a compound of borax and boric
acid.
It is effective in case where the brazing
temperature is higher than 800°C.
• Activated flux
Most of fluxes generally used for silver brazing
are this type.
It features an increased oxide film removing
capability due to the addition of compounds
such as potassium fluoride, potassium chloride
and sodium fluoride to the borax-boric acid
compound.
2-5-3. Brazing
As brazing work requires sophisticated techniques,
experiences based upon a theoretical knowledge, it
must be performed by a person qualified.
In order to prevent the oxide film from occurring in the
pipe interior during brazing, it is effective to proceed
with brazing while letting dry Nitrogen gas (N2) flow.
Never use gas other than Nitrogen gas.
(1) Brazing method to prevent oxidation
1 Attach a reducing valve and a flow-meter to the
Nitrogen gas cylinder.
2 Use a copper pipe to direct the piping material,
and attach a flow-meter to the cylinder.
3 Apply a seal into the clearance between the
piping material and inserted copper pipe for
Nitrogen in order to prevent backflow of the
Nitrogen gas.
4 When the Nitrogen gas is flowing, be sure to
keep the piping end open.
5 Adjust the flow rate of Nitrogen gas so that it is
lower than 0.05 m3/Hr or 0.02 Mpa (0.2 kgf/
cm2) by means of the reducing valve.
6 After performing the steps above, keep the
Nitrogen gas flowing until the pipe cools down
to a certain extent (temperature at which pipes
are touchable with hands).
7 Remove the flux completely after brazing.
(4) Piping materials for brazing and used brazing
filler/flux
PipingUsed brazingUsed
material filler flux
Copper - Copper Phosphor copperDo not use
Copper - IronSilverPaste flux
Iron - IronSilverVapor flux
1 Do not enter flux into the refrigeration cycle.
2 When chlorine contained in the flux remains
within the pipe, the lubricating oil deteriorates.
Therefore, use a flux which does not contain
chlorine.
3 When adding water to the flux, use water which
does not contain chlorine (e.g. distilled water or
ion-exchange water).
4 Remove the flux after brazing.
M
Flow meter
Stop valve
Nitrogen gas
cylinder
From Nitrogen cylinder
Pipe
Rubber plug
Nitrogen
gas
Fig. 2-5-1 Prevention of oxidation during brazing
– 13 –
3-1. Indoor Unit
FILE NO. SVM-04013
3. CONSTRUCTION VIEWS
Front panel
Back body
660
Knock out system
Air inlet
Air filter
790
Heat exchanger
275
Air outlet
12080
590
Hanger
64
53
48
208
48
Knock out system
660
Drain hose (0.54m)
Hanger
45
Minimum
distance
to ceiling
275
1
7
0
o
r m
o
re
320
620
235235
215215
re
Minimum
distance
to ceiling
o
r m
o
5
6
Hanger
– 14 –
Connecting pipe (0.43m)
(Flare ∅6.35)
Connecting pipe (0.33m)
Flare ∅9.52
Hanger
Hanger
150150160160
Installation plate outline
Center line
For stud bolt
(∅8~∅10)
For stud bolt (∅6)
26
4519040
Minimum
distance
to ceiling
1
7
0
o
r m
o
re
32
9090
160
5718
Wireless remote control
3-2.Outdoor Unit
FILE NO. SVM-04013
A
A Detail drawing (Back Leg)
∅6 Hole
310
600
52
36
302
270
R15
R5.5
32.5
310
302
∅30 Drain outlet
∅436
530
265
FAN GUARD
115125
2-∅11 x 14 Hole
(For ∅8-∅10 anchor bolt)
600
780
90
102
∅6 Hole
∅11 x 14 Hole
B
62
B Detail drawing (Front Leg)
310
302
36
52
R15
310
330
COVER PV
Z
Electrical
part cover
600 or more
320
100 or more
Z View
Installation dimension
600
Air inlet
Air outlet
600 or more
4 x ∅11 x 14 Long holes (For ∅8 −∅10 anchorbolt)
600 or more
120
75
Liquid side
(Flare ∅6.35)
Gas side
(Flare ∅9.52)
54
Service port
– 15 –
4-1.Indoor Unit
FILE NO. SVM-04013
4. WIRING DIAGRAM
Table 4-1-1 Simple Check for Failure Diagnosis
Check Item
OPERATION
1
INDICATOR
TERMINAL BLOCK
2
FUSE 3.15A
3
DC5V
4
5
DC12V
DC325V
6
(DC310 to 340V)
Refer to the service data for the detailed failure diagnosis.
Check to see if the OPERATION indicator goes on and off when the main
switch or breaker is turned on.
(Check the primary and secondary voltage of the transformer.)
Check the power supply v oltage between 1 and 2. (Refer to the name plate.)
(Check the primary and secondary voltage of the transformer.)
Check the fluctuating voltage between 2 and 3. (DC15 to 60 V)
Check to see if the fuse blows out.
(Check the R04 of the varistor.)
Check the voltage at the No. 4 pin on CN13 connector of the infrared receiver.
(Check the transformer and the power supply circuit of the rated voltage.)
Check the voltage at the white lead of the louver motor.
(Check the transformer and the power supply circuit of the rated voltage.)
Check the voltage at the No. 1 pin on CN10 connector.
(Check the DB01, R05 and C03.)
Diagnosis Result
– 16 –
4-2.Outdoor Unit (RAS-13UAV-E3)
FILE NO. SVM-04013
PULSE
MODULATING
VALVE
121
REACTOR
ORN
CONVERTER
MODULE
DB01
BRW
IGBTMODULE
Q200
BLUP18
TE
2
P10
BUEUBVEVBWEWBXBYBZ
G
EA
112
2
CN600
P07P08
P09
P19P20
P17
TD
11223
CT
POEWRRELAY
ELECTRONICSTARTER
P.C. BOARD
(MCC-813)
P21P22P23
3
TO
RED
WHI
BLK
TS
112
2
C12C13C14
1
1
2
2
3
3
COMPRESSOR
11223311223
CN701
RELAY
CM
COILfor4-WAYVALVE
3
BLKP06CN703CN603CN602CN601
VARISTOR
Q300
WHI
112
SURGEABSORBER
F04FUSET3.15A
PMV
YEL
ORN
BLU
RED
GRY
3
44556
2
3
F01
FUSE
T25A
6
P01
BLKORN
P03
WHI
P02
P11
P12
P13
P14
CN300
CN301
IGBT:InsulatedGateBipolarTransistor
121
1
1
2
2
3
3
1
1
2
2
3
3
4
4
5
5
N
L321
2
REACTOR
PUR
FANMOTER
REDWHIBLK
YEL
PNKGRY
POWERSUPPLY220-240V~50/60Hz
TOINDOORUNIT
FM
– 17 –
4-3.Outdoor Unit (RAS-16UAV-E)
FILE NO. SVM-04013
PULSE
MODULATING
VALVE
TE
THERMOSTATFORCOMPRESSOR
121
2
121
2
REACTOR
ORN
P10
G
EA
CONVERTER
MODULE
DB01
BRW
BUEUBVEVBWEWBX
IGBTMODULE
BYBZ
Q200
BLUP18
112
2
CN600CN500
P07P08
P09
P19P20
P17
TD
11223
CT
POEWRRELAY
ELECTRONICSTARTER
P.C. BOARD
(MCC-813)
P21P22P23
3
TO
RED
WHI
BLK
TS
112
2
C12C13C14
1
1
2
2
3
3
COMPRESSOR
11223311223
CN701
RELAY
CM
COILfor4-WAYVALVE
3
BLKP06CN703CN603CN602CN601
VARISTOR
Q300
WHI
112
SURGEABSORBER
F04FUSET3.15A
PMV
YEL
ORN
BLU
RED
GRY
3
44556
2
3
F01
FUSE
T25A
6
P01
BLKORN
P03
WHI
P02
P11
P12
P13
P14
CN300
CN301
IGBT:InsulatedGateBipolarTransistor
121
1
1
2
2
3
3
1
1
2
2
3
3
4
4
5
5
N
L321
2
REACTOR
PUR
FANMOTER
REDWHIBLK
YEL
PNKGRY
POWERSUPPLY220-240V~50/60Hz
TOINDOORUNIT
FM
– 18 –
FILE NO. SVM-04013
5. SPECIFICATION OF ELECTRICAL PARTS
5-1. Indoor Unit
No.Parts nameTypeSpecifications
1Fan motor (for indoor)ICF-340-30-2DC 340 V, 30 W
2Thermo. sensor (TA-sensor)———10 kΩ at 25°C
3DC-DC transformer (T01)SWT-70DC 390 V, Secondary DC 15 V, 12 V, 7 V
4MicrocomputerµPD780024AGK
5Heat exchanger sensor
(TC-sensor)
6Line filter (L01SS11V-0627027mH, AC 0.6A
7Diode (DB01)D3SBA604A, 600 V
8Capacitor (C03)KMH450VNSN120M25C120µF, 450 V
9Fuse (F01)FCU250V, 3.15AT3.15A, 250 V
10Power supply IC (IC01)STR-L472
11Varistor (R21, R109)15G561K560 V
12Resistor (R01)RF-5TK4R74.7Ω, 5 W
13Louver motorMP24GA
———10 kΩ at 25°C
Output (Rated) 1 W,16 poles, 1 phase,
DC 12 V
5-2. Outdoor Unit (RAS-13UAV-E3)
No.Parts nameModel nameRating
1SC coilL01ADR2516-0R6TB20A, 150µH
(Noise filter)L03ADR2520-R15TB15A, 0.6mH
Primary side DC280V, Secondary
2 DC-DC transformer SWT-78 side 7.5 V x 1, 13 V x 1, 26.5V x 3,
16 V x 1, 15 V x 1
3ReactorCH-57-Z-TL=10mH, 16A x 2
4Outside fan motorICF-140-43-1DC140 V, 43 W
5Suction temp. sensor
(TS sensor)
Discharge temp. sensor
6
(TD sensor)
Outside air temp. sensor
7
(TO sensor)
Heat exchanger temp.
8
sensor (TE sensor)
9 Terminal block (6P)
10Fuse
11Electrolytic capacitorLLQ2G501KHUATF, 400LISN500K35F500µF, DC 400 V x 3 pieces
12 Transistor module 6MBI25GS-060-01 or 6MBI25GS-060-01A 25A, 600 V
13 Compressor DA91A1F-45F 3-phases 4-poles 750 W
For protection of switching power source3.15A, AC 250 V
For protection of inverter input overcurrent25A, AC 250 V
(Inverter attached)10 kΩ (25°C)
(Inverter attached)62 kΩ (20°C)
(Inverter attached)10 kΩ (25°C)
(Inverter attached)10 kΩ (25°C)
JXO-6B
30A, 600 VAC
15
Convertor module
MP 7003
– 19 –
Diode: 25A, 600 V,
IG BT: 40 A, 600V
FILE NO. SVM-04013
5-3. Outdoor Unit (RAS-16UAV-E)
No.Parts nameModel nameRating
1SC coilL01ADR2516-0R6TB20A, 150µH
(Noise filter)L03ADR2520-R15TB15A, 0.6mH
Primary side DC280V, Secondary
2 DC-DC transformer SWT-78 side 7.5 V x 1, 13 V x 1, 26.5V x 3,
16 V x 1, 15 V x 1
3ReactorCH-57-Z-TL=10mH, 16A x 2
4Outside fan motorICF-140-43-1DC140 V, 43 W
5Suction temp. sensor
(TS sensor)
Discharge temp. sensor
6
(TD sensor)
Outside air temp. sensor
7
(TO sensor)
Heat exchanger temp.
8
sensor (TE sensor)
9 Terminal block (6P)
10Fuse
11Electrolytic capacitorLLQ2G501KHUATF, 400LISN500K35F500µF, DC 400 V x 3 pieces
12 Transistor module 6MBI25GS-060-01 or 6MBI25GS-060-01A 25A, 600 V
13 Compressor DA130A1F-24F 3-phases 4-poles 1100 W
For protection of switching power source3.15A, AC 250 V
For protection of inverter input overcurrent25A, AC 250 V
(Inverter attached)10 kΩ (25°C)
(Inverter attached)62 kΩ (20°C)
(Inverter attached)10 kΩ (25°C)
(Inverter attached)10 kΩ (25°C)
JXO-6B
30A, 600 VAC
15
Convertor module
MP 7003
Diode: 25A, 600 V,
IG BT: 40 A, 600V
– 20 –
6. REFRIGERANT CYCLE DIAGRAM
6-1. Refrigerant Cycle Diagram
RAS-13UKV-E3 / RAS-13UAV-E3
P
Pressure measurement
Gauge attaching port
Vacuum pump connecting port
Deoxidized copper pipe
Outer dia. : 9.52 mm
Thickness : 0.8 mm
INDOOR UNIT
Indoor heat
exchanger
Cross flow fan
Deoxidized copper pipe
Outer dia. : 6.35 mm
Thickness : 0.8 mm
Sectional shape
of heat insulator
T1
Temp. measurement
FILE NO. SVM-04013
Max. : 15 m
Allowable height
difference : 10m
Allowable pipe length
4-way valve
(CHV-0213)
TS
Temp. measurement
T2
Muffler
Muffler
TD
Compressor
DA91A1F-45F
TO
Outdoor heat
exchanger
Propeller fan
OUTDOOR UNIT
Split capillary
∅1.5 x 200
∅1.5 x 200
TE
s
s
NOTE :
Strainer
Pulse modulating
valve at liquid side
(SEV16RC3)
Refrigerant amount : 0.8 kg
Gas leak check position
Refrigerant flow (Cooling)
Refrigerant flow (Heating)
Note :
•The maximum length of the pipe for this air conditioner is 15 m. The additional charging of refrigerant is
unnecessary because this air conditioner is designed with charge-less specification.
– 21 –
RAS-16UKV-E / RAS-16UAV-E
P
Pressure measurement
Gauge attaching port
Vacuum pump connecting port
Deoxidized copper pipe
Outer dia. : 12.7 mm
Thickness : 0.8 mm
INDOOR UNIT
Indoor heat
exchanger
Cross flow fan
Deoxidized copper pipe
Outer dia. : 6.35 mm
Thickness : 0.8 mm
Sectional shape
of heat insulator
T1
Temp. measurement
FILE NO. SVM-04013
Max. : 15 m
Allowable height
difference : 10m
Allowable pipe length
4-way valve
(CHV-0213)
TS
Temp. measurement
T2
Muffler
Muffler
TD
Compressor
DA130A1F-24F
TO
Outdoor heat
exchanger
Propeller fan
OUTDOOR UNIT
Split capillary
∅1.5 x 200
∅1.5 x 200
TE
s
s
NOTE :
Strainer
Pulse modulating
valve at liquid side
(SEV16RC3)
Refrigerant amount : 0.95 kg
Gas leak check position
Refrigerant flow (Cooling)
Refrigerant flow (Heating)
Note :
•The maximum length of the pipe for this air conditioner is 15 m. The additional charging of refrigerant is
unnecessary because this air conditioner is designed with charge-less specification.
– 22 –
6-2. Operation Data
RAS-13UKV-E3 / RAS-13UAV-E3
<Cooling>
FILE NO. SVM-04013
Temperature
condition ( °C)
IndoorOutdoor
27/19 35/− 13UKV-E3 0.8 to 1.0 9 to 11 49 to 45 High High 77
<Heating>
Temperature
condition ( °C)
IndoorOutdoor
20/− 7/6 13UKV-E3 2.5 to 2.7 42 to 44 0 to 3 High High 80
Model
name
Model
name
Standard
pressure
P (MPa)
Standard
pressure
P (MPa)
Heat exchanger
pipe temp.
T1 (°C)T2 (°C)
Heat exchanger
pipe temp.
T1 (°C)T2 (°C)
Indoor
fan
mode
Indoor
fan
mode
Outdoor
fan
mode
Outdoor
fan
mode
RAS-16UKV-E / RAS-16UAV-E
<Cooling>
Temperature
condition (° C)
IndoorOutdoor
27/19 35/− 0.9 to 1.27 to 1050 to 45 High High 77
Model
name
16UKV-E
Standard
pressure
P (MPa)
Heat exchanger
pipe temp.
T1 (°C)T2 ( °C)
Indoor
fan
mode
Outdoor
fan
mode
Compressor
revolution
(rps)
Compressor
revolution
(rps)
Compressor
revolution
(rps)
<Heating>
Temperature
condition ( °C)
IndoorOutdoor
20/− 7/6 2.7 to 2.9 42 to 46 0 to 3 High High 82
Note :
(1) Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
(2) Connecting piping condition : 5m
Model
name
16UKV-E
Standard
pressure
P (MPa)
Heat exchanger
pipe temp.
T1 (°C)T2 (
°C)
Indoor
fan
mode
Outdoor
fan
mode
Compressor
revolution
(rps)
− 23 −
7-1.Indoor Unit
Heat Exchanger Sensor
7. CONTROL BLOCK DIAGRAM
Indoor Unit Control Panel
M.C.U
Functions
• Louver Control
FILE NO. SVM-04013
Operation
Display
Temperature Sensor
Infrared Rays Signal Receiver
Initiallizing Circuit
Infrared
Rays
36.7KHz
Clock Frequency
Oscillator Circuit
Power Supply
Remote
Control
Noise Filter
From Outdoor Unit
Circuit
•
3-minute Delay at Restart for Compressor
•
Motor Revolution Control
•
Processing
(Temperature Processing)
•
Timer
•
Serial Signal Communication
Louver ON/OFF Signal
Louver Driver
Serial Signal Transmitter/Receiver
Serial Signal Communication
Timer
Display
Filter
Sign Display
PRE DEF.
Sign Display
Indoor
Fan Motor
Louver
Motor
Louver Motor
REMOTE CONTROL
Infrared Rays
Remote Control
Operation (START/STOP)
Operation Mode Selection
AUTO, COOL, DRY, HEAT, FAN ONLY
Temperature Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
Louver Direction Setting
ECO
Hi power
Filter Reset
– 24 –
7-2.Outdoor Unit (Inverter Assembly)
220 − 240 V
50/60 Hz
MICRO-COMPUTER BLOCK DIAGRAM
Over current
sensor
Driver circuit
of P.M.V.
Over current
sensor
Heat exchanger
temp.sensor
Suction temp.
sensor
Outdoor air
temp. sensor
Discharge
temp. sensor
Inddor unit
send/receive
circuit
Relay
circuit
Noise
Filter
Converter
(AC → DC)
Clock
frequency
16MHz
High Power
factor Correction
circuit
Input current
sensor
Rotor position
detect circuit
Rotor position
detect circuit
• PWM synthesis function
• Input current release control
• IGBT over-current detect control
• Outdoor fan control
• High power factor correction control
• Inverter output frequency control
• A/D converter function
• P.M.V. control
• Discharge temp. control
• 4-way valve control
• Signal communication to indoor unit
P.M.V : Pulse Modulating Valve
M.C.U : Micro Control Unit
M.C.U
For INDOOR UNIT
4-way
valve
P.M.V.
Inverter
(DC → AC)
Over current
detect circuit
Gate drive
circuit
Gate drive
circuit
Over current
sensor
Inverter
(DC → AC)
Outdoor
Fan motor
Compressor
MCC813 (P.C.B)
OUTDOOR UNIT
FILE NO. SVM-04013
– 25 –
8. OPERATION DESCRIPTION
FILE NO. SVM-04013
8-1.Outlined of Air Conditioner Control
This air conditioner is a capacity-variable type air
conditioner, which uses DC motor for the indoor fan
motor and the outdoor fan motor. And the capacity
proportional control compressor which can change the
motor speed in the range from 13 to 110 rps is
mounted. The DC motor drive circuit is mounted to the
indoor unit. The compressor and the inverter to control
fan motor are mounted to the outdoor unit.
The entire air conditioner is mainly controlled by the
indoor unit controller.
The indoor unit controller drives the indoor fan motor
based upon command sent from the remote control,
and transfers the operation command to the outdoor
unit controller.
The outdoor unit controller receives operation
command from the indoor unit side, and controls the
outdoor fan and the pulse modulating valve. (P.M.V)
Besides, detecting revolution position of the
compressor motor, the outdoor unit controller controls
speed of the compressor motor by controlling output
voltage of the inverter and switching timing of the
supply power (current transfer timing) so that motors
drive according to the operation command. And then,
the outdoor unit controller transfers reversely the
operating status information of the outdoor unit to
control the indoor unit controller.
As the compressor adopts four-pole brushless
DC motor, the frequency of the supply power
from inverter to compressor is two-times
cycles of the actual number of revolution.
(1) Role of indoor unit controller
The indoor unit controller judges the operation
commands from the remote controller and
assumes the following functions.
• Judgment of suction air temperature of the
indoor heat exchanger by using the indoor
temp. sensor (TA sensor)
• Temperature setting of the indoor heat
exchanger by using heat exchanger sensor
(TC sensor) (Prevent-freezing control)
• Louver motor control
• Indoor fan motor operation control
• LED (Light Emitting Diode) display control
• Transferring of operation command signal
(Serial signal) to the outdoor unit
• Reception of information of operation status
(Serial signal including outside temp. data) to
the outdoor unit and judgment/display of error
(2) Role of outdoor unit controller
Receiving the operation command signal (Serial
signal) from the indoor controller, the outdoor unit
performs its role.
• Compressor operation
control
• Operation control of
outdoor fan motor
• P.M.V. control
• Detection of inverter input current and current
release operation
• Over-current detection and prevention
operation to IGBT module (Compressor stop
function)
• Compressor and outdoor fan stop function
when serial signal is off (when the serial signal
does not reach the board assembly of outdoor
control by trouble of the signal system).
• Transferring of operation information (Serial
signal) from outdoor unit to indoor unit
• Detection of outdoor temperature and
operation revolution control
• Defrost control in heating operation (Temp.
measurement by outdoor heat exchanger and
control for 4-way valve and outdoor fan)
Operations followed
to judgment of serial
signal from indoor
side.
– 26 –
FILE NO. SVM-04013
(3) Contents of operation command signal (Serial
signal) from indoor unit controller to outdoor unit
controller
The following three types of signals are sent from
the indoor unit controller.
•Operation mode set on the remote control
• Compressor revolution command signal
defined by indoor temperature and set temperature (Correction along with variation of
room
temperature and correction of indoor heat
exchanger temperature are added.)
• For these two types of signals ([Operation
mode] and [Compressor revolution]), the
outdoor unit controller monitors the input
current to the inverter, and performs the
followed operation within the range that current
does not exceed the allowable value.
• Temperature of indoor heat exchanger by
indoor heat exchanger sensor
(Minimum revolution control)
(4) Contents of operation command signal (Serial
signal) from outdoor unit controller to indoor unit
controller
The following signals are sent from the outdoor
unit controller.
• The current operation mode
• The current compressor revolution
• Outdoor temperature
• Existence of protective circuit operation
For transferring of these signals, the indoor unit
controller monitors the contents of signals, and
judges existence of trouble occurrence.
Contents of judgment are described below.
• Whether distinction of the current operation
status meets to the operation command signal
• Whether protective circuit operates
When no signal is received from the outdoor
unit controller, it is assumed as a trouble.
8-1-1. Capacity control
The cooling and heating capacity is varied by changing
compressor motor speed. The inverter changes
compressor motor speed by changing
AC 220-240 V power to DC once, and controls capacity by changing supply power status to the compressor
with transistor module (includes 6 transistors). The
outline of the control is as follows:
The revolution position and revolution speed of the
motor are detected by detecting winding electromotive
force of the compressor motor under operation, and
the revolution speed is changed so that the motor
drives based upon revolution speed of the operation
command by changing timing (current transfer timing)
to exchange inverter output voltage and supply power
winding.
Detection of the revolution position for controlling is
performed 12 times per 1 revolution of compressor.
The range of supply power frequency to the
compressor differs according to the operation status
(COOL, HEAT, DRY).
Table 8-1-1 Compressor revolution range
OperationModel
modename
COOL
HEAT
COOL
HEAT
8-1-2. Current release control
The outdoor main circuit control section (Inverter
assembly) detects the input current to the outdoor unit.
If the current value with compressor motor speed
instructed from indoor side exceeds the specified
value, the outdoor main circuit control section controls
compressor motor speed by reducing motor speed so
that value becomes closest to the command within the
limited value.
13UKV-E3
16UKV-E
Compressor
revolution (rps)
13 to 88
16 to 110
13 to 91
13 to 106
8-1-3. Power factor improvement control
Power factor improvement control is performed mainly
aiming to reduce the current on much power consumption of cooling/heating operation. Controlling starts
from the time when input power has reached at a
certain point. To be concrete, IGBT of the power factor
improvement circuit is used, and the power factor is
improved by keeping IGBT on for an arbitrary period to
widen electro-angle of the input current.
– 27 −